1. Maximum Application alarm help form and recipe pages limited by hard disk capacity no of pages Maximum 1024 alarm pages Curves 16 real time curves 16 trending curves Adjustment General screens with 4 front corrector panels supervision and adjustment screens OLE server Interface with third party software Visual Basic Excel etc Software extension PL7 Pro Dyn PLC diagnostic functions dynamic display of programs etc Supervision Web Client Monitor via Intranet Ethernet TCP IP Connections PLC RS 232 C RS 422 485 isolated serial link downloadable communication protocols see page 27 Configuration PC Non isolated RS 232 C serial link Printer Parallel link External keypad PS 2 compatible link Bus or network Slot for type II or III PCMCIA communication card communication protocols see Schneider Software Pack page 27 ISA bus cards Depending on the model two 2 3 format slots network TSX Premium coprocessor connection etc Real time clock Incorporated and backed up Alarm relay 1 volt free N O contact max 0 5 A 24 V Connection Power supply and Plug in terminal 5 screw terminals 5 08 mm pitch alarm relay Max clamping capacity 1 5 mm PLC High density female 26 way SUB D connector and T CCX CB 10 cable with female 25 way SUB D connector PLC side Configuration PC Male 9 way SUB D connector Printer Female 25 way SUB D connector External k
2. 1 The operator dialogue application memory can be supported by a PCMCIA type II card 10 Mb maximum or by the internal hard disk 2 1 Gb Telemecanique 19 Operator dialogue terminals Magelis terminals with graphic screen Characteristics References page 21 Dimensions page 31 Type of terminal XBT F011 XBT F032 XBT F023 F024 XBT F034 Environment Conforming to standards IEC 1131 2 IEC 801 2 level 3 IEC 801 3 and IEC 801 4 level 3 IEC 68 2 6 IEC 68 2 27 UL 508 CSA Product certifications CE UL CSA Temperature Operation 0 4 45 C Storage 20 60 C Relative humidity 0 85 no condensation Degree of protection Front panel IP 65 conforming to IEC 529 Nema 4 Rear panel IP 20 conforming to IEC 529 Shock resistance Conforming to IEC 68 2 27 semi sinusoidal pulse 11 ms 15 gn in the 3 axes Mechanical characteristics Mounting and fixing Flush mounted fixed with spring clips Supplied pressure mounted on a 1 to 6 mm thick panel 10 spring clips Ta spring clips 12 spring clips 10 spring clips Material Front section Polyphenyl oxide 10 glass fibre PPO GFN1 SE 1 Keypad Anti UV treated toughened polyester Autoflex EB AG Enclosure Polyphenyl oxide 10 glass fibre PPO GFN1 SE 1 Keys Soft keys 8 with LED 10 with LED Static keys 10 with LED and 12 with LED and re usable labels re
3. Magelis display units with 2 line alohanumeric screen References Characteristics page 8 Dimensions mounting page 30 Display units with 2 lines of 20 characters fluorescent Downloadable Number of keys Supply Language Reference Weight exchange Funct Service Num voltage version protocol V kg No printer port no log ai ko ie See 24 Multilingual XBT H002010 0 600 page 28 XBT H020010 4 1 24 Multilingual XBT H022010 0 600 5 24 Multilingual XBT H012010 0 600 With printer port with log XBT H0106010 See 5 24 Multilingual XBT H012110 0 600 page 28 Display unit with 2 lines of 20 characters LCD No printer port no log XBT H000010 Uni Telway 5 24 and 5 Multilingual XBT H811050 0 600 See via terminal page 28 socket on the TSX Nano Micro Premium PLC Display units with 2 lines of 20 characters back lit LCD No printer port no log See 24 Multilingual XBT H001010 0 600 page 28 4 1 24 Multilingual XBT H021010 0 600 5 24 Multilingual XBT H011010 0 600 Separate parts Description Use Reference Weight kg Development software Under Windows 3 1 or 95 See page 27 for downloading the application and protocols Connecting cables Connection to PLCs S
4. Magelis terminals with 2 or 4 line alohanumeric screen Characteristics Type of terminal XBT E014010 XBT E016010 fluorescent XBT E013010 XBT E015010 back lit LCD Environment Conforming to standards IEC 1131 2 IEC 68 2 6 IEC 68 2 27 EN 61131 2 UL 508 CSA C22 2 no 14 Product certifications ce UL CSA Temperature Operation 0 50 C Storage 40 70 C 20 60 C Degree of protection IP 65 conforming to IEC 529 Nema 4 Mechanical characteristics Mounting and fixing Flush mounted fixed with 4 or 6 screws supplied pressure mounted on a 1 to 6 mm thick panel Material Enclosure Polyphenyl oxyde 10 glass fibre PPO GFN1 SE1 Keypad Anti UV treated toughened polyester Autoflex EB AG Keys Function 24 Service 10 Alphanumeric 12 Electrical characteristics Display unit Fluorescent green matrix characters 5 x 7 pixels Back lit LCD 5 x 7 pixels XBT E014010 XBT E016010 XBT E013010 XBT E015e10 2 lines of 40 characters 4 lines of 40 characters 2 lines of 40 characters 4 lines of 40 characters height 5 mm height 5 mm height 5 mm height 5 mm Power supply Voltage 24 V not isolated Voltage limits 1E R30 N Ripple 5 maximum Consumption 20 W 10 W Operating characteristics Signalling 33 LEDs 1 buzzer Memory 384 Kb Flash EPROM 800 application pages approximately 2 lines per page 256 avai
5. Multiple see pages 6 and 28 Real time clock Access to the PLC real time clock Printer port asynchronous serial link RS 232 C XBT HM017110 Connection Power supply Plug in terminal block 3 screw terminals 5 08 mm pitch Max clamping capacity 1 5 mm Serial port Female 25 way SUB D connector Printer port Male 9 way SUB D connector 14 J Telemecanique Operator dialogue terminals Characteristics page 14 Dimensions mounting page 30 Magelis display units with 8 line matrix screen References Display units with 8 line matrix screen of 40 characters back lit LCD Downloadable Number of keys Supply Language Reference Weight exchange Funct Service Num voltage version protocol V kg No printer port no log See 24 Multilingual XBT HM007010 0 600 page 28 XBT HM007010 4 1 24 Multilingual XBT HM027010 0 600 5 24 Multilingual XBT HM017010 0 600 XBT HM027010 With printer port with log See 5 _ 24 Multilingual XBT HM017110 0 600 page 28 XBT HM017 e10 Separate parts Description Use Reference Weight kg Development software Under Windows 95 or NT 4 e See page 27 for downloading the application and protocols Connectin
6. Real time and trending curves Alarm log and management of alarm groups Management of help pages form pages recipe pages Pages can be called by the user or by the PLC Three levels of password Printing of form pages date stamped log and alarms Communication protocol application support in the PCMCIA type II application memory card The role of the function keys is defined using the XBT L100 ee software Modifications cannot be made during operation Each function key can be associated with an internal bit of the PLC application Static function keys Static function keys are defined for the whole application They can be used for e Access to a page Pulse a PLC memory bit Latch a PLC memory bit Static keys can be marked with re usable labels Soft function keys Soft function keys are associated with a page Their role can differ from one page to another They can perform the following functions e Access to a page Pulse a PLC memory bit e Latch a PLC memory bit e Access to the modification of a value Each soft key can be assigned a label or icon displaying its function Service keys Service keys are the arrow keys and the control keys and are used for modifying the parameters of the control system The control keys are used to perform the following actions ENTER Confirm a selection or entry acknowledge an alarm MOD Change to the mode for entering pages passwords fields or gr
7. Separate parts Description Use Reference Weight kg Development Under Windows 95 or NT 4 e See page 27 software for downloading the application and protocols PCMCIA type Il Application memory See page 28 memory cards PCMCIA type Ill Bus and industrial See page 28 z communication cards networks connection Connecting cables Serial link See page 29 Uni Telway bus configuration terminal printer connection Sheets of labels Labels for function keys See page 28 Replacement parts Description Use Memory Reference Weight XBT MEM02 2E kg PCMCIA type II XBT F 2 Mb XBT MEM02 0 100 memory card terminals Telemecanique 21 Operator dialogue terminals Magelis graphic stations Characteristics References page 23 Dimensions page 31 Type of graphic station TXBT F023 TXBT F024 TXBT F034 Environment Conforming to standards IEC 1131 2 IEC 801 2 level 3 IEC 801 3 and IEC 801 4 level 3 IEC 68 2 6 IEC 68 2 27 UL 508 CSA Product certifications CE UL CSA Temperature Operation 0 4 45 C Storage 20 60 C Relative humidity 0 85 without condensation Degree of protection Front panel IP 65 conforming to IEC 529 Nema 4 Rear panel IP 20 conforming to IEC 529 Shock resistance Conforming to IEC 68 2 27 semi sinusoidal pulse 11 ms 15 gn in the 3 axes Mechanical characteristics Mounting and fixing Flush mounted fixed with spring clips Supplied
8. bound T XBT F0Oeee10F French T XBT DMOOF 0 500 for TXBT graphic stations 2 T XBT F0eeei0E English T XBT DMOOE 0 500 1 The T CCX CB 10 cable length 0 2 m fitted with 2 x 25 and 26 way SUB D connectors is included as standard Add the suffix E for an English version of Windows 95 and English documentation to be supplied with the product and the letter F for a French version of Windows 95 and French documentation to be supplied with the product 2 For documentation in German Spanish and Italian consult our Regional Sales Office Telemecanique 23
9. depending on the model static function keys with indicator lights and re usable labels 6 Twelve service keys with indicator lights 7 Twelve alphanumeric keys 0 9 associated with 3 alphabetical access keys A Z 6 7 Front panel of XBT FO3 touch sensitive screen terminals XBT F03 touch sensitive screen terminals comprise on the front panel 1 Atouch sensitive colour screen 5 7 or 10 4 depending on the model 2 Acommunication monitoring indicator light 1 3 A tactile feedback activity indicator light Back panel of XBT F graphic screen terminals XBT F graphic screen terminals comprise on the back panel 4 1 A plug in screw terminal for 24 V power supply and alarm relay connection 2 A female 25 way SUB D connector for connection to PLCs 3 A male 9 way SUB D connector for printer connection and for transferring applications from an FTX terminal or i PC compatibles 4 Two slots for PCMCIA card one type II for application memory one type Ill for connection to the communication architecture bus or network 3 2 18 J Telemecanique Operator dialogue terminals Characteristics page 22 References page 23 Dimensions page 31 Magelis graphic stations Description Front panel of TXBT F02 graphic keypad stations TXBT F02 graphic keypad stations comprise on the front panel Modicon Magelis 1 Amonochrome or colour screen 9 5 or 10 4 depending on the model 2 2x5 soft function ke
10. pressure mounted on a 1 to 6 mm thick panel 12 spring clips 10 spring clips Material Front section Polyphenyl oxide 10 glass fibre PPO GFN1 SE 1 Keypad Anti UV treated toughened polyester Autoflex EB AG Rear enclosure Zinc coated steel Keys Soft keys 10 with LED Static keys 12 with LED and re usable labels Service keys 14 Alphanumeric 12 3 for alphabetical access keys Pointing device Yes tactile keypad No Electrical characteristics LCD screen Type 9 5 monochrome back lit 10 4 TFT 256 colours back lit 10 4 TFT 256 colours back lit with 16 levels of grey with resistive analogue feedback Resolution 640 x 480 pixels Power supply Voltage 24 V not isolated Limits 18 30 V maximum ripple 5 maximum microbreaks 1 ms Protection Against polarity inversion and overloads ISA bus extension Maximum available at12V 1 2A at5V 2A Consumption 80 W Operating characteristics Signalling 1 communication monitoring LED and 1 keypad activity or tactile feedback activity LED and 11 LEDs associated with service and alphanumeric keys Processor 80486 DX4 100 MHz Internal hard disk 1 6 Gb Operating system Windows 95 installed on the hard disk Dynamic RAM memory 16 Mb as standard and up to 32 Mb with extension Application memory On hard disk or PCMCIA type II card 2 4 8 or 10 Mb Dialogue application
11. screen Characteristics Type of display unit XBT HM0e7e10 back lit LCD Environment Conforming to standards IEC 1131 2 IEC 68 2 6 IEC 68 227 EN 61131 2 UL 508 CSA C222 no 14 Product certifications ce UL CSA Temperature Operation 0 45 C Storage 20 60 C Degree of protection IP 65 conforming to IEC 529 Nema 4 Mechanical characteristics Mounting and fixing Flush mounted fixed with spring clips supplied pressure mounted on a 1 to 6 mm thick panel Material Enclosure Polyphenyl oxide 10 glass fibre PPO GFN1 SE1 Keypad Anti UV treated toughened polyester Autoflex EB AG XBT HM007010 XBT HM027010 XBT HM017e10 Keys No keys 4 function keys 5 service keys 1 service key Electrical characteristics Display unit Back lit LCD 240 x 64 pixels 8 lines of 40 characters height 5 3 mm single size 4 lines of 20 characters height 10 6 mm double height double width Power supply Voltage 24V not isolated Voltage limits 18 230V Ripple 5 maximum Consumption 15 W Operating characteristics Signalling XBT HM007010 XBT HM027010 XBT HM017e10 1 LED 6 LEDs 4 LEDs Memory 384 Kb Flash EPROM 600 application pages approximately 8 lines per page 256 available alarm pages 2 lines per page Transmission asynchronous serial link RS 232 C RS 485 RS 422 Downloadable protocol
12. usable labels Service keys 12 12 Alphanumeric keys 12 3 12 3 for alphabetical access for alphabetical access Electrical characteristics LCD screen Type 5 7 monochrome back lit 5 7 STN 256 colours back lit XBT F023 9 5 10 4 TFT with 16 levels of grey with resistive matrix monochrome back lit with 256 colours with resistive tactile feedback 16 levels of grey analogue tactile feedback XBT F024 10 4 TFT 256 colours Resolution 320 x 240 pixels 640 x 480 pixels Power supply Voltage 24 V not isolated Limits 18 30 V maximum ripple 5 maximum microbreaks 1 ms Protection Against polarity inversion and overloads Consumption 35 W Operating characteristics Signalling Operating system 1 communication monitoring LED and 1 keypad activity or tactile feedback activity LED and 11 LEDs associated with service and alphanumeric keys Magelis Dynamic RAM memory 2 5 Mb Application memory On 2 Mb PCMCIA II card supplied 4 8 or 10 Mb Dialogue application Maximum 50 to 450 application alarm help form and recipe 30 to 300 application alarm help form and recipe no of pages pages depending on the memory card used pages depending on the memory card used Curves 16 real time curves 16 real time curves Connections PLC RS 232 C RS 422 485 insulated serial link downloadable communication protocols See page 27 and configuration PC page 2
13. 8 Printer RS 232 C serial link Bus or network Slot for PCMCIA type Ill communication card depending on the model communication protocols see page 28 Real time clock Access to the PLC real time clock Alarm relay 1 volt free N O contact max 0 5 A 24 V Connection Power supply and Plug in terminal 5 screw terminals 5 08 mm pitch alarm relay Max clamping capacity 1 5 mm PLC Female 25 way SUB D connector Printer Male 9 way SUB D connector configuration PC 20 J Telemecanique Operator dialogue terminals Characteristics page 20 Dimensions page 31 Magelis terminals with graphic screen References Terminals with keypad Downloadable Type and size Supply Type III slot Reference Weight exchange of screen voltage for PCMCIA protocol communication card kg See Monochrome 24 No XBT F011110 1 800 page 2 Our and page 28 Yes XBT F011310 1 800 Monochrome 24 No XBT F023110 2 00 9 5 Yes XBT F023310 2 00 XBT F024e10 Colour 24 No XBT F024110 2 00 10 4 Yes XBT F024310 2 700 Terminals with touch sensitive screens See Colour 24 No XBT F032110 1 600 page 27 5 7 and page 28 Yes XBT F032310 1 600 XBT F034010 Colour 24 No XBT F034110 2 400 10 4 Yes XBT F034310 2 400
14. Operator dialogue terminals References page 9 Dimensions mounting page 30 Magelis display units with 2 line alohanumeric screen Characteristics Type of display unit XBT H002e10 fluorescent XBT H811050 LCD XBT H001010 back lit LCD Environment Conforming to standards IEC 1131 2 IEC 68 2 6 IEC 68 2 27 EN 61131 2 UL 508 CSA C22 2 no 14 Product certifications c UL CSA Temperature Operation 0 50 C Storage AAC 2o OC Degree of protection IP 65 conforming to IEC 529 Nema 4 Mechanical characteristics Mounting and fixing Flush mounted fixed with 4 or 6 screws supplied pressure mounted on a 1 to 6 mm thick panel Material Enclosure Polyphenyl oxide 10 glass fibre PPO GFN1 SE1 Keypad Anti UV treated toughened polyester Autoflex EB AG XBT H 002010 022010 012010 811050 001010 021010 011010 Keys No 4 function 5 service 5 service keys No 4 function 5 service key keys keys key keys keys 1 service 1 service key key Electrical characteristics Display unit Fluorescent green matrix characters 5 x 7 pixels 2 lines of 20 characters height 5 mm LCD 5 x 7 pixels 2 lines of 20 characters height 9 mm Back lit LCD 5 x 7 pixels 2 lines of 20 characters height 9 mm Power supply Voltage 24V not isolated 24V not isolated during configuration 5V via TSX Nano Micro Premium PLC terminal p
15. aphic objects ESC Cancel an entry suspend or stop a current action Display previous pages in succession Quit the alarm display SHIFT Access the second of the dual key functions MENU Access a menu containing the operating functions which do not have direct access keys HOME Return to the entry point of the current menu Example return to the first page of the application SYST Access confidential mode which contains the implementation functions protected by a password ALARM View the alarms PRINT Print The arrow keys can be used to Change page within a menu Change fields on a page Select an object on a page Move around on a page Select the value of a digit Select a value from a list of choices When used with the SHIFT key increment or decrement the value of a variable field SYST MENU ESC PRINT MOD ALARM ENTER Telemecanique 17 Operator dialogue terminals Magelis terminals with graphic screen Characteristics page 20 Description References page 21 Dimensions page 31 Front panel of XBT FO1 F02 keypad terminals XBT F01 F02 keypad terminals comprise on the front panel 1 A monochrome or colour screen 5 7 or 9 5 or 10 4 depending on the model 2 2x4or2x5 depending on the model soft function keys with indicator lights 3 A communication monitoring indicator light 4 A keypad activity indicator light 5 2x5 or 2 x 6
16. ee page 29 configuration terminals etc Documentation Description Format Included in Reference Weight the product 1 kg Magelis A5 bound XBT L1003 e XBT X0000e 0 200 user s manual and XBT L1004e 1 Add the following suffixes EN English FR French DE German ES Spanish IT Italian Telemecanique 9 Operator dialogue terminals References page 11 Dimensions mounting page 30 Magelis display units with 2 line alohanumeric screen Characteristics Type of terminal XBT P002e10 fluorescent XBT P0e1010 back lit LCD Environment Conforming to standards IEC 1131 2 IEC 68 2 6 IEC 68 2 27 EN 61131 2 UL 508 CSA C22 2 no 14 Product certifications ce UL CSA Temperature Operation 0 50 C Storage 40 70 C 20 60 C Degree of protection IP 65 conforming to IEC 529 Nema 4 Mechanical characteristics Mounting and fixing Flush mounted fixed with 4 or 6 screws supplied pressure mounted on a 1 to 6 mm thick panel Material Enclosure Polyphenyl oxyde 10 glass fibre PPO GFN1 SE1 Keypad Anti UV treated toughened polyester Autoflex EB AG XBT P012010 XBT P022010 XBT P011010 XBT P021010 Keys 8 function keys 12 function keys 8 function keys 12 function keys 10 service keys 12 numeric keys 9 service keys 10 service keys 12 numeric keys 9 service keys Electrical characteristics Display u
17. er port and log See 24 10 12 24 Multilingual XBT E014110 1 000 page 28 Terminals with 4 line display of 40 characters fluorescent No printer port no log See 24 10 12 24 Multilingual XBT E016010 1 000 page 28 With printer port and log XBT E016010 m See 24 10 12 24 Multilingual XBT E016110 1 000 page 28 Terminals with 2 line display of 40 characters back lit LCD No printer port no log 2e See 24 10 12 24 Multilingual XBT E013010 1 000 me page 28 J f With printer port and log See 24 10 12 24 Multilingual XBT E013110 1 000 XBT E013010 page 28 Terminals with 4 line display of 40 characters back lit LCD No printer port no log See 24 10 12 24 Multilingual XBT E015010 1 000 page 28 With printer port and log See 24 10 12 24 Multilingual XBT E015110 1 000 aii io page 28 XBT E015010 Separate parts Description Use Reference Weight kg Development software Under Windows 3 1 or 95 See page 27 for downloading the application and protocols Connecting cables Connection to PLCs See page 29 configuration terminals etc Documentation Description Format Included in Reference Weight the product 1 kg Magelis A5 bound XBT L1003 e XBT X0000e 0 200 user s manual and XBT L1004e 1 Add the following suffixes EN English FR French DE German ES Spanish IT Italian Telemecanique 13 Operator dialogue terminals References page 15 Dimensions mounting page 30 Magelis display units with 8 line matrix
18. eypad 8 way mini DIN connector 22 J Telemecanique Operator dialogue terminals Characteristics page 22 Dimensions page 31 Magelis graphic stations References T XBT F0240e100 T XBT F0340100e Graphic stations with keypads Downloadable Type and size Supply Number Reference Weight exchange of screen voltage of ISA 1 protocol v bus slots kg See Monochrome 24 T XBT F0233106 5 100 page 27 9 5 2 2 3 format T XBT F0234106 5 500 Colour 24 T XBT F0243106 5 100 10 4 2 2 3 format T XBT F0244106 5 500 Graphic stations with touch sensitive screens See Colour 24 T XBT F0343106 4 800 page 27 10 4 2 2 3 format T XBT F03441060 5 200 Separate parts Description Use Reference Weight kg Development Under Windows 95 or NT 4 e See page 27 software for downloading the application and protocols PCMCIA type Il Application memory See page 28 memory cards PCMCIA type IlI Bus and industrial See page 28 D communication cards networks connection Connecting cables Serial link See page 29 Uni Telway bus configuration terminal printer etc connection Sheets of labels Labels for function keys See page 28 Documentation Description Format Included in Language Reference Weight the product kg User s manual A5
19. fluorescent Downloadable Number of keys Supply Language Reference Weight exchange Funct Service Num voltage version protocol Ve kg No printer port no log See 8 9 24 Multilingual XBT P012010 0 800 page 28 XBT P010010 12 10 12 24 Multilingual XBT P022010 0 800 EA With printer port and log a2 o oo See 12 10 12 24 Multilingual XBT P022110 0 800 ai Fo SOS iO e page 28 XBT P020010 Terminals with 2 line display of 20 characters back lit LCD No printer port no log See 8 9 24 Multilingual XBT P011010 0 800 page 28 12 10 12 24 Multilingual XBT P021010 0 800 With printer port and log See 12 10 12 24 Multilingual XBT P021110 0 800 page 28 Separate parts Description Use Reference Weight kg Development software Under Windows 3 1 or 95 See page 27 for downloading the application and protocols Connecting cables Connection to PLCs See page 29 configuration terminals etc Documentation Description Format Included in Reference Weight the product 1 kg Magelis A5 bound XBT L10030 XBT X0000e 0 200 user s manual and XBT L1004e 1 Add the following suffixes EN English FR French DE German ES Spanish IT Italian J Telemecanique 11 Operator dialogue terminals References page 13 Dimensions mounting page 30
20. g cables Connection to PLCs See page 29 configuration terminals etc Documentation Description Format Included in Reference Weight the product 1 kg Magelis A5 bound XBT L1003 e XBT X0000e 0 200 user s manual and XBT L1004e 1 Add the following suffixes EN English FR French DE German ES Spanish IT Italian J Telemecanique 15 Operator dialogue terminals Magelis terminals with graphic screen Characteristics pages 20 and 22 General References pages 21 and 23 Dimensions fi E Be E SEER mee TETTE TELL EEE XBT F01 F03 XBT FO2Z FO3 TXBTFOZFOS XBT L1000 Typef10 dop 2 Fichier Edition Affichage Page Configuration Transfert Simulation Fen tre olsiel le a sill a elajal el 3 Temp 1 Saisie Phase Saisie Module Saisie Pression J debua 784Ko 251 130 XBT GTOC NUM TXBT F O ped 4 gt Oo k Graphic screen operator dialogue terminals are available with 5 or 10 screens in monochrome or colour with a keypad or a touch sensitive screen XBT F graphic screen terminals are specially designed for operator dialogue graphic functions TXBT F graphic stations operate under Windows 95 enabling them to access other control system functions All Magelis graphic screen terminals have the same user interface static and soft function keys service keys alphanumeric keys Mageli
21. lable alarm pages 2 lines per page 400 application pages approximately 4 lines per page 128 available alarm pages 4 lines per page Log function Possibility of storing alarm pages Transmission asynchronous serial link RS 232 C RS 485 RS 422 Downloadable protocol Multiple see pages 6 and 28 Real time clock Incorporated Printer port asynchronous serial link RS 232 C XBT E014110 XBT E016110 RS 232 C XBT E013110 XBT E015110 Alarm relay 1 N O contact min 1 mA 5 V max 0 5 A 24 V Connection Power supply and Plug in terminal block alarm relay 5 screw terminals 5 08 mm pitch Max clamping capacity 1 5 mm Serial port Female 25 way SUB D connector Printer port Male 9 way SUB D connector 12 J Telemecanique Operator dialogue terminals Characteristics page 12 Dimensions mounting page 30 Magelis terminals with 2 or 4 line alphanumeric screen References Terminals with 2 line display of 40 characters fluorescent Downloadable Number of keys Supply Language Reference Weight exchange Funct Service Alphanum voltage version protocol V kg No printer port no log i Fio See 24 10 12 24 Multilingual XBT E014010 1 000 ia padoe XBT E014610 With print
22. nit Fluorescent green matrix characters 5 x 7 pixels 2 lines of 20 characters height 5mm Back lit LCD 5 x 7 pixels 2 lines of 20 characters height 9 mm Power supply Voltage 24 V not isolated Voltage limits 18 230 V Ripple 5 maximum Consumption 10 W Operating characteristics Signalling XBT P012010 XBT P022010 XBT P011010 XBT P021010 17 LEDs 21 LEDs 17 LEDs 21 LEDS Memory 256 Kb Flash EPROM 400 application pages approximately 2 lines per page 256 available alarm pages 2 lines per page Log function Possibility of storing alarm pages XBT P022110 Possibility of storing alarm pages XBT P021110 Transmission asynchronous serial link RS 232 C RS 485 RS 422 Downloadable protocol Multiple see pages 6 and 28 Real time clock Access to the PLC real time clock Printer port asynchronous serial link RS 232 C XBT P022110 RS 232 C XBT P021110 Connection Power supply Plug in terminal block 3 screw terminals 5 08 mm pitch Max clamping capacity 1 5 mm Serial port Female 25 way SUB D connector Printer port Male 9 way SUB D connector 10 J Telemecanique Operator dialogue terminals Characteristics page 10 Dimensions mounting page 30 Magelis display units with 2 line alohanumeric screen References Terminals with 2 line display of 20 characters
23. ort during operation 24V not Isolated Voltage limits 18 230V Ripple 5 maximum Consumption 10 W 1 5 W 10 W Operating characteristics XBT H 002010 022010 012010 811050 001010 021010 011010 Signalling PEED 6 LEDs 4 LEDs PEED 6 LEDs 4 LEDs Memory 128 Kb Flash EPROM 256 Kb 128 Kb Flash EPROM 128 Kb Flash EPROM 256 Kb XBT H012110 100 application pages approximate 200 application pages approximately 2 lines per page 2 lines per page 256 available alarm pages 2 lines per page 128 available alarm pages 2 lines per page XBT H011010 200 application pages approximatel 2 lines per page 256 available alarm pages 2 lines per page Log function Possibility of storing alarm pages XBT H012110 Transmission asynchronous serial link RS 232 C RS 485 RS 422 RS 232 C RS 485 RS 232 C RS 485 RS 422 Downloadable protocol Multiple see pages 6 and 28 Uni Telway see pages 6 and 28 Multiple see pages 6 and 28 Real time clock Access to the PLC real time clock Printer port asynchronous serial link RS 232 C XBT H012110 Connection Power supply Plug in terminal block 3 screw terminals 5 08 mm pitch Max clamping capacity 1 5 mm Serial port Female 25 way SUB D connector Printer port Male 9 way SUB D connector 8 J Telemecanique Operator dialogue terminals
24. s graphic screen terminals can be configured using the same XBT L100e software in a Windows environment XBT L100e software provides graphic screen terminals with a library of animated graphic objects such as bargraphs volume indicator meters selectors potentiometers and trending curves The variable for animating an object can be selected directly from a list of symbols given by the PL7 or Concept software The application program for the graphic terminals is stored on a PCMCIA memory card XBT F and TXBT F graphic screen terminals communicate with PLCs via an integrated point to point or multidrop serial link or via a fieldbus with a PCMCIA type III card The communication protocols are those used by Schneider Group PLCs as well as those of the other main market suppliers 16 J Telemecanique Operator dialogue terminals Characteristics page 20 References page 21 Dimensions page 31 Magelis terminals with graphic screen Functions Functions XBT F and TXBT F graphic screen operator dialogue terminals have the following functions e Display of animated synoptic screens control modification of numeric and alphanumeric variables e Display of a service line status and alarm bar with the current time e Dynamic visualisation of operating data setpoints measurements recipes maintenance messages and process errors Control via soft or static function keys Scaling of analogue variables
25. ys with indicator lights 3 A communication monitoring indicator light 4 A keypad activity indicator light 5 Twelve static function keys with indicator lights and re usable labels 6 Fourteen service keys with indicator lights 7 Twelve alphanumeric keys 0 9 associated with 3 alphabetical access keys A Z 8 A touch sensitive pointing device 6 7 8 aR TET TXBT F03 graphic screen terminals with touch sensitive n a e screens comprise on the front panel 1 A touch sensitive colour screen 10 4 2 A communication monitoring indicator light 3 A tactile feedback activity indicator light Front panel of TXBT F graphic stations TXBT F graphic stations comprise on the front panel 1 A plug in screw terminal for 24 V power supply and alarm relay connection vol 2 Afemale 26 way SUB D high density connector for PLC connection with a T CCX CB 10 cable length 0 2 m supplied fitted with 1 male 26 way SUB D high density connector and 1 female 25 way SUB D connector 3 A female 25 way SUB D connector for parallel printer connection or external CD drive A 4 Two slots for PCMCIA card one type II 1 one type III 5 Amale 9 way SUB D 9 connector for connecting an FTX configuration terminal or a PC compatible 6 An 8 way mini DIN socket for connecting a PS 2 compatible external keyboard 7 Two standard IBM PC slots ISA bus 2 3 format depending on the model 3 5 2 6