Home

1758-IN001 - Rockwell Automation

image

Contents

1. 10 co E Hs H1 H2 H2 pro P11 P12 Ri AOV AOV AOO AOV AO aov 15 Jaio lan AI2 AI AI Ais v DOO DO1 DO2 DO3 Voos Voo I 44376 ry 3 Item Description Discrete Inputs and wake up connectors Status indicators Ethernet connector RS 232 COM 2 connector RS 232 COM 1 connector RS 485 COM 1 connector Discrete Output connectors Power Input and Analog Input connectors oO N N oy A wy N HART Pulse Input and Analog Output connectors Pulse Input Filter switches Publication 1758 IN001C EN P June 2011 6 DataSite Natural Gas Flow Meter and Remote Terminal Unit Mounting the Controller Most applications require installation in an industrial enclosure to reduce the effects of electrical interference and environmental exposure Locate your controller as far as possible from power lines load lines and other sources of electrical noise such as hard contact switches relays and AC motor drives For more information on proper grounding guidelines see the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 You can mount the controller either horizontally or vertically on DIN rails but horizontal mounting is recommended fo
2. 7 RTS CTS B 8 CTS 5 L gt 9 44388 RS232 DTE to RS232 DCE with Handshaking RS232 DTE DCE DCD T DCD RXD Z 2 RXD TXD B 3 TXD DTR G 4 DTR GND 5 5 GND 6 6 RTS 7 7_ RTS CTS 8 8 CTS an g Publication 1758 IN001C EN P June 2011 14 DataSite Natural Gas Flow Meter and Remote Terminal Unit Wiring for RS485 Serial Communications RS 485 network p _ 1200 m 4000 feet Master Station First station in network requires terminations D D Slave Station De 4 maximum length Slave Station D Last station in network D requires terminations 44390 Wire the Controller for HART Communication The controller comes with three HART protocol communications ports including one that is multi point and can connect to thirteen HART protocol meters The other two are point to point ports and can also collect 4 20 mA signals HARTO multi point port wiring to passive meters HO HO Two Wire Two Wire Two Wire Slave 1 Slave 2 Slave 13 DC Power Supply Publication 1758 IN001C EN P June 2011 44391 DataSite Natural Gas Flow Meter and Remote Terminal Unit 15
3. The DataSite controller uses a lithium battery that allows the real time clock RTC to maintain the correct time setting through periods when line power has been removed from the unit Current drain on the battery during these periods is approximately 1 microamp and the battery should provide approximately 10 years of operation for the RTC without power applied The DS Settings Utility provides a display of the battery voltage If the battery voltage should drop below 2 0 V contact Rockwell Automation Technical Support see the back page for contact information to arrange for repait exchange of the DataSite unit Register Group Address Offline New Group Delete Group Rename Group Add Register Edit Register Delete Register Exit Controller Current Error Clear Error Read Battery Voltage V Error Record Read Continue System Status ISaGRAF PC Time Jan 05 2009 14 11 19 Mon Adjust Time Init State Controller Time Set Time WARNING The lithium battery is not user replaceable Publication 1758 IN001C EN P June 2011 DataSite Natural Gas Flow Meter and Remote Terminal Unit 17 Decommission and Recycle the Battery The lithium battery is not user replaceable Follow the instructions in this section to remove the battery from the DataSite unit for recycling when decommissioning the DataSite unit Dispose of used battery promptly Keep away from children Do not di
4. HART1 or HART2 point to point wiring to passive meters H1 H1 H2 H2 Two Wire Two Wire Slave 1 Slave 2 DC Power DC Power Supply Supply 44393 Wire the Controller for Sleep Wake Up mode To reduce power consumption in unattended or solar powered applications the controller can be configured to enable Sleep mode and disable Sleep mode when inputs are detected 27 28 29 WAKEUP 3 l 12 24V DC 44396 Ground the Module In solid state control systems grounding and wire routing help limit the effects of noise due to electromagnetic interference EMI Run the ground connection from the ground terminal of the controller to the ground bus prior to connecting any devices Use AWG 14 wire ATTENTION All devices connected to the RS 232 485 communication port must be referenced to controller ground or be floating not referenced to a potential other than ground Failure to follow this procedure may result in property damage or personal injury Publication 1758 IN001C EN P June 2011 16 DataSite Natural Gas Flow Meter and Remote Terminal Unit You must also provide an acceptable grounding path for each device in your application For mote information on proper grounding guidelines refer to the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Battery Status Check
5. Wire the Controller for Digital Output 11 12 13 14 15 16 D01 D02 003 DOV DOV 24V FET 5 olls OUTPUT E 3 8 E 12 24V 44384 WARNING Refer to Power Source Requirements for details on wiring Publication 1758 IN001C EN P June 2011 12 DataSite Natural Gas Flow Meter and Remote Terminal Unit Wire the Controller for Pulse Input 35 36 37 38 39 40 PIO PI2 PI 12 24V 44385 WARNING Refer to Power Source Requirements for details on wiring A Wiring for RS232 Serial Communications GND TxD RxD CTS RTS 13807 65232 DTE to 5232 DTE without Handshaking RS232 DTE DTE DCD i 1 DCD RXD 2 2 TXD 3 3 TXD DIR 4 4 GND 5 5 GND 6 6 RIS 7 7 RTS CTS 8 8 CTS 9 9 44387 Publication 1758 IN001C EN P June 2011 DataSite Natural Gas Flow Meter and Remote Terminal Unit 13 RS232 DTE to RS232 DTE with Handshaking RS232 DTE DTE DCD 1 1H DCD RXD 2 2 RXD TXD ps 3 TXD DIR 4 9 114 DTR GND 5 5 GND 6 6 RTS 7
6. 0 Hz Shock IEC 60068 2 27 18 shocks semi sinusoidal 15g 11 ms Electrical EMC EN 61000 6 4 2007 EN 61000 6 2 2005 ESD immunity IEC 61000 4 2 4 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 8096 AM from 80 1000 MHz 10V m with 200 Hz 5096 Pulse 10096 AM at 900 MHz 10V m with 200 Hz 5096 Pulse 10096 AM at 1890 MHz 3V m with 1 kHz sine wave 80 AM from 1000 2700 MHz Publication 1758 IN001C EN P June 2011 DataSite Natural Gas Flow Meter and Remote Terminal Unit 25 Environmental Specifications Attribute EFT B immunity Value IEC 61000 4 4 2 kV at 5 kHz on power ports 2 kV at 5 kHz on signal ports 1 kV at 5 kHz on communications ports Surge transient immunity IEC 61000 4 5 1 kV line line DM and 2 kV line earth CM on power ports 1 kV line line DM and 2 kV line earth CM on signal ports 1 kV line earth CM on shielded ports 1 kV line earth CM on communications ports Conducted RF immunity Certifications Certification when product is marked IEC 61000 4 6 rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Value C UL US UL Listed Industrial Control Equipment UL Listed Industrial Control Equipment for use in Canada UL Listed for Class I Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E10314 CE Marked for all application directives C Tick A
7. Installation Instructions DataSite Natural Gas Flow Meter and Remote Terminal Unit Catalog Numbers 1758 FLO301 1758 FLO302 1758 RTU201 1758 RTU202 Topic Page Important User Information 2 Environment and Enclosure 3 Hazardous Location Considerations 3 Overview 4 Controller Description 5 Mounting the Controller 6 DIN Rail Mounting 7 Power Source Requirements 9 Wiring for Power Supply Input 9 Wire the Controller for HART Communication 14 Ground the Module 15 Status Indicators 20 Specifications 21 Additional Resources 26 Rockwell ALLEN BRADLEY ROCKWELL SOFTWARE Automation 2 DataSite Natural Gas Flow Meter and Remote Terminal Unit Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls Publication SGI 1 1 available from your local Rockwell Automation sales office or online at http literature rockwellautomation com describes some important differences between solid state equipment and hard wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable In no event will Rockwell Automation Inc be responsibl
8. alog Outputs Attribute D A resolution ratio Power supply Continuous input must not exceed 160 of the rated range Description 16 bit 2 ccessive approximation Output signal range 4 20mA Maximum load 1000 Qwith 24V DC loop power Impedance 400 with 12V DC loop power Output type Single ended regulation on positive side with common negative return Isolation voltage OV AC or 100V DC Absolute accuracy 0 2 25 C with 250 Qload 0 596 full temperature range 0 1000 Qload H HE Response time 00 ms typical 10 90 Noise and ripple max 0 04 Transient protection 600 W HART Attribute Description Modulation Frequency Shift Keying FSK Logic 1 1200 Hz Logic 0 2200 Hz Data rate 1200 bps Transmit level 500 mVp p 250 Q Receive sensitivity 120 mVp p on 80 mVp p off Publication 1758 IN001C EN P June 2011 24 DataSite Natural Gas Flow Meter and Remote Terminal Unit HART Attribute Description Output impedance 300 Q transformer isolated Input impedance 4000 Q transformer isolated Load resistor 250 Q 1 W max Environmental Specifications Attribute Value Temperature operating 40 70 C 40 158 F Temperature non operating 50 80 C 58 176 F Relative humidity 5 95 non condensing Vibration IEC 60068 2 6 Constant amplitude 0 15mm 10 57 Hz Constant acceleration 2g 57 15
9. ashing red Transmitting data through serial port 2 RX2 Flashing green Receiving data through serial port 2 LINK Flashing yellow Transmitting or receiving data through Ethernet port Yellow Controller is connected to Ethernet network 10 100M Red Speed for ethernet connection 10 100 Mbps PH Green Ethernet mode half duplex or full duplex Publication 1758 IN001C EN P June 2011 DataSite Natural Gas Flow Meter and Remote Terminal Unit 21 Specifications General Attribute Dimensions Description 213 x 133 x 56 mm 8 375 x 5 25 x 2 20 in Number of 1 0 8 digital inputs 4 digital outputs 8 analog inputs 2 analog outputs 3 pulse inputs Power supply voltage 12V DC 1596 10 Heat dissipation nominal lt 1 2W Power consumption 80 120 mA Input circuit type Current Sinking Output circuit type Current Sourcing FET Terminal screw torque 0 8 Nm 7 in Ib North American temp code T4 Wire size Pulse Input 0 34 2 5 mm 22 12 AWG solid or stranded copper wire rated at 90 C 194 F or greater 1 2 mm 3 64 in insulation max Attribute Description Voltage range 12 24V DC Off state voltage 8V DC Operating frequency 10 kHz with filters off 30 kHz with filters on On state current min 5mA On state current nom 6 mA On state current max 13 2 mA Off state leakage current 25mA Nominal impedance 2kQ Publicat
10. be installed in an enclosure All cables connected to the product must remain in the enclosure or be protected by conduit or other means e All wiring must comply with N E C article 501 10 b Use only the following communication cables in Class I Division 2 hazardous locations Communication Cables 1747 CP3 RS 232 Serial Communications Cable Environment Classification Class I Division 2 Hazardous Environment Publication 1758 IN001C EN P June 2011 4 DataSite Natural Gas Flow Meter and Remote Terminal Unit Environnements dangereux Cet quipement est pour une utilisation en environnements dangereux de Classe I Division 2 Groupes A B C D La mise en garde suivante s applique a utilisation en envitonnements dangereux WARNING DANGER D EXPLOSION e a substitution de composants peut rendre cet quipement impropre une utilisation en environnement de Classe I Division 2 e Ne pas remplacer de composants ou d connecter l quipement sans s tre assur que l alimentation est coup e Ne pas connecter ou d connecter des composants sans s tre assur que alimentation est coup e e Ce produit doit tre install dans une armoire Tous les c bles connect s appareil doivent rester dans l armoire ou tre prot g s par une goulotte ou tout autre moyen e l ensemble du c blage doit tre conforme la r glementation en vigueur dans les pays l appareil est insta
11. e or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations Identifies information about practices or circumstances that can cause an explosion in a hazardous environment which may lead to personal injury or death property damage or economic loss IMPORTANT Identifies information that is critical for successful application and understanding of the product ATTENTION Identifies information about practices orcircumstances that can lead to personal injury or death property damage or economic loss Attentions help you identify a hazard avoid a hazard and recognize the consequences SHOCK HAZARD Labels may be on or inside the equipment for example drive or motor to alert people that danger
12. erminal Unit 19 4 Remove the battery CR2325 LITHIUM BATTERY amp 44740 5 Replace the board onto the standoffs looooocooooooo000Q aa o il CELE BASSE En 3 RU A E 0000000099 200002 SSS o edo e Gao Tm 6 Replace the cover and fasten the screws securely Publication 1758 IN001C EN P June 2011 20 DataSite Natural Gas Flow Meter and Remote Terminal Unit Status Indicators PWR STAT DOO 002 DIO 012 DIM 06 PIO PI2 TXO TX TX2 10 100M RUN ERR DO1 DH 013 DIS 07 LINK RX1 RX2 FH Indicator State Description control settings RUN Green Normal operation This indicator is not affected by LED power control settings STAT Flashing red ISaGRAF application running ERR Yellow Error detected DIO DI7 Green Corresponding digital input is on DOO DO3 Green Corresponding digital output is on PIO PI2 Green Corresponding pulse input voltage is more than 8V TX0 Flashing red Transmitting data through HART port Flashing green Receiving data through HART port TX1 Flashing red Transmitting data through serial port 1 RX1 Flashing green Receiving data through serial port 1 TX2 Fl
13. ion 1758 IN001C EN P June 2011 22 DataSite Natural Gas Flow Meter and Remote Terminal Unit Digital Input Attribute Description On state voltage range 8 24V DC Off state voltage range 0 4V DC Operating frequency 100 Hz On state current min 3mA On state current nom 5mA On state current max 11mA Off state leakage current 2mA Nominal impedance 2 4 kQ Digital Output Attribute Description Power supply 12 24V DC Continuous current per point 200 mA Operating frequency 100 Hz On state current min 1mA On state current max 200 mA Off state leakage current 1 mA Analog Inputs Attribute Description A D resolution 16 bit Conversion type Successive approximation Type Single ended unipolar Isolation voltage 500V AC from logic power supply Transient variety protection 600 W Voltage Input Range 0 10V DC or 4 20 mA versions Upload time 10 ms Response time 10 ms 10 90 Type of Data Integer Input Coding Hexadecimal Publication 1758 IN001C EN P June 2011 DataSite Natural Gas Flow Meter and Remote Terminal Unit 23 Analog Inputs Attribute Voltage input impedance Description 100 for 10V DC inputs 170 Qfor 20 mA inputs Input Resolution 16 bit Non linearity 0 1 of full scale Overall accuracy 0 1 of full scale at 25 C 0 3 of full scale over temperature range Voltage Input Overvoltage Protection An
14. ll Utilisez uniquement les c bles de communication suivants dans les environnements dangereux de Classe I Division 2 Classification des environnements Cables de communication Environnement dangereux de Classe Division 2 1747 CP3 RS 232 Serial Communications Cable Overview DataSite controllers ate suitable for use in an industrial environment when installed in accordance with these instructions Specifically this equipment is intended for use in clean dry environments Pollution degree 20 and with circuits not exceeding Over Voltage Category IEC 60664 1 Install your DataSite unit using these installation instructions Pollution Degree 2 is an environment where normally only non conductive pollution occurs except that occasionally a temporary conductivity caused by condensation shall be expected Over Voltage Category Il is the load level section of the electrical distribution system At this level transient voltages are controlled and do not exceed the impulse voltage capability of the product s insulation 8 Pollution Degree 2 and Over Voltage Category Il are International Electrotechnical Commission IEC designations Publication 1758 IN001C EN P June 2011 DataSite Natural Gas Flow Meter and Remote Terminal Unit 5 Controller Description 1 2 3 DIO Dit DI2 DI3 Dia DIS DIG DI 7 WAKEUP
15. oducts to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures United States Contact your distributor You must provide a Customer Support case number call the phone number above to obtain one to your distributor in order to complete the return process Outside United States Please contact your local Rockwell Automation representative for the return procedure Allen Bradley Rockwell Automation DataSite and TechConnect are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation Vorstlaan Boulevard du Souverain 36 1170 Brussels Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1758 IN001C EN P June 2011 PN 117506 Supercedes Publication 1758 1 001 November 2010 Copyright 2011 Rockwell Automation Inc All rights reserved Printed in China
16. ous voltage may be present BURN HAZARD Labels may be on or inside the equipment for example drive or motor to alert people that surfaces may reach dangerous temperatures Publication 1758 IN001C EN P June 2011 DataSite Natural Gas Flow Meter and Remote Terminal Unit 3 Environment and Enclosure Do not remove the protective debris strip until after the module and all other equipment ATTENTION s in the panel near the module are mounted and wiring is complete Once wiring is complete remove protective debris strip Failure to remove strip before operating can cause overheating ATTENTION Electrostatic discharge can damage semiconductor devices inside the module Do not touch the connector pins or other sensitive areas ATTENTION To comply with UL restrictions the product and any connected devices must be powered from a source compliant with the following A Class 2 or Limited Voltage Current Hazardous Location Considerations This equipment is suitable for use in Class I Division 2 Groups A B C D locations only The following WARNING statement applies to use in hazardous locations EXPLOSION HAZARD e Substitution of components may impair suitability for Class Division 2 e Do not replace components or disconnect equipment unless power has been switched off e Do not connect or disconnect components unless power has been switched off e This product must
17. r thermal considerations ATTENTION Be careful of metal chips when drilling mounting holes for your controller or other equipment within the enclosure or panel Drilled fragments that fall into the controller could cause damage Dimensions 1758 FLO301 1758 FLO302 1758 RTU201 1758 RTU202 5 6 cm 2 20 in 00000000000000 FRA 0000000000000 Allen Bradley 13 0 DataSite jp grin 2020000000 Bale 5275 CT 21 3 cm 8 395 in 44374 Publication 1758 IN001C EN P June 2011 DataSite Natural Gas Flow Meter and Remote Terminal Unit 7 Controller Spacing When mounting the controller allow 25 mm 1 in of space on all sides for adequate ventilation as shown below Top 0000000000000 20000000000 donnees E Allen Bradley DataSite m ooe 0000000020022 22000222000 pocoo abeg 295 Bottom 44375 DIN Rail Mounting A small Phillips screwdriver is required for the installation or removal of the controller The controller can be mounted to EN50022 35 x 7 5 DIN rails Follow these steps to install your controller on the DIN rail 1 Mount your DIN rail Make sure that the placement of the cont
18. roller on the DIN rail meets the recommended spacing requirements 2 Loosen the two clamp screws until the clamp can slide out IMPORTANT Do not remove the screws from the clamp otherwise they will fall into the chassis 3 Place the controller onto the DIN rail using the rail hooks on the back of the controller Publication 1758 IN001C EN P June 2011 8 DataSite Natural Gas Flow Meter and Remote Terminal Unit 4 Slide the clamp out while pushing the controller fully onto the DIN rail 1 When the controller is propetly aligned on the DIN rail 2 slide the clamp in so that it makes direct contact with the lower edge of the DIN rail 3 2 3 DIN rail 5 44538 44539 44540 5 Tighten the clamp screws Follow these steps to remove your controller from the DIN rail 1 Loosen the two clamp screws until the clamp can slide out taking care not to dislodge the clamp screws from the clamp 2 Remove the controller Publication 1758 IN001C EN P June 2011 DataSite Natural Gas Flow Meter and Remote Terminal Unit 9 Power Source Requirements ATTENTION The DataSite modules 1758 FL0301 1758 0302 1758 RTU201 1758 RTU202 must be powered by a National Electrical Code NEC or Canadian Electrical Code CEC Class 2 power source when used in locations covered by Underwriters Laboratories In locations governed by International Electrotechnical Commis
19. sassemble and do not dispose of in fire gt f IMPORTANT Refer to the SLC 500 Lithium Battery Installation Instructions publication 1747 IN515 for more information on handling usage storage and disposal of lithium batteries When you connect or disconnect the battery an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that the area is nonhazardous before proceeding For Safety information on the handling of lithium batteries including handling and disposal of leaking batteries see Guidelines for Handling Lithium Batteries publication AG 5 4 1 Remove the cover by first removing the screws on either side of the controller 44737 Publication 1758 IN001C EN P June 2011 18 DataSite Natural Gas Flow Meter and Remote Terminal Unit 2 Pry the board off from the standoffs 22222000 QN pmr a ge all mL 1 Ha 78 looooooooooooQO0O0O2 REED eR 8 92 U EHE CEST F J2zoaeeroda eooeoe oo Ur o Beetle pto 44738 3 Use a flat blade screwdriver to pry the battery out from under the clamp a 44739 Publication 1758 IN001C EN P June 2011 DataSite Natural Gas Flow Meter and Remote T
20. sion IEC or EN standards a Safety Extra Low Voltage SELV power source must be used Wiring for Power Supply Input 1 2 3 rh Vt OV EN 44380 Ground 12V DC WARNING Refer Power Source Requirements for details wiring Publication 1758 IN001C EN P June 2011 10 DataSite Natural Gas Flow Meter and Remote Terminal Unit Wire the Controller for Analog Input The analog input circuits are equipped with overvoltage and overcurrent protection 4 5 6 7 8 9 10 AIO AIT AI2 Al3 AI4 AI5 V Two wire Three sensor wire sensor T TEE _ 44381 24VDC Power Supply WARNING Refer to Power Source Requirements for details on wiring Wire the Controller for Analog Output Analog Output wiring 40 41 42 43 44 45 AOV AOV A00 AOV A01 AOV qvo qvo P 12 24V 44382 WARNING Refer to Power Source Requirements for details on wiring Publication 1758 IN001C EN P June 2011 DataSite Natural Gas Flow Meter and Remote Terminal Unit 11 Wire the Controller for Digital Input DICOM DIO DI1 DI2 DI3 DI4 DI5 DI6 DI7 o a o p g NH o 12 24V DC 44383 WARNING Refer to Power Source Requirements for details on wiring
21. ur local Rockwell Automation distributor or sales representative Publica tion 1758 IN001C EN P June 2011 DataSite Natural Gas Flow Meter and Remote Terminal Unit 27 Notes Publication 1758 IN001C EN P June 2011 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products At http support rockwellautomation com you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect support programs For more information contact yout local distributor or Rockwell Automation representative or visit http support rockwellautomation com Installation Assistance If you experience a problem within the first 24 hours of installation please review the information that s contained in this manual You can also contact a special Customer Support number for initial help in getting your product up and running United States 1 440 646 3434 Monday Friday 8 a m 5 p m EST Outside United States Please contact your local Rockwell Automation representative for any technical support issues New Product Satisfaction Return Rockwell Automation tests all of its pr
22. ustralian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions See the Product Certification link at http www ab com for Declaration of Conformity Certificates and other certification details Publication 1758 IN001C EN P June 2011 26 DataSite Natural Gas Flow Meter and Remote Terminal Unit Additional Resources These documents contain additional information concerning related Rockwell Automation produc ts Resource DataSi Terminal Unit Hardware User Manual 1758 UM001 Electronic Flow Meter and Remote Description Information on how to install and wire a DataSite controller Customized Function Blocks for DataSite Electronic Description of the customized function blocks used for Flow Meter and Remote Terminal Unit User programming DataSite controllers using ISaGRAF Manual 1758 RM001 software DataSite Electronic Flow Meter and Remote Information on how to install and use the software Terminal Unit Software User Manual 1758 U M002 tools DS Settings DS FloConfig and DS DNP3 to configure and monitor DataSite controllers Industri al Automation Wiring and Grounding Guidelines publication 1770 4 1 You can view or download publications at http Provides general guidelines for ins Automation industrial system alling a Rockwell literature rockwellautomation com To order paper copies of technical documentation contact yo