1. hager Tebis application software e mete Dimmer KNX STXA210AN STXA213N Electrical Mechanical characteristics see product user manual 565 Product reference Product designation TXA210AN Dimmer 1 x 600W TXA210N Dimmer 1 x 300W Dimmer 3 x 300W TXA210AN Input modules KNX EIB TXA210N Load connected TXA213N 1 Description of the Dimming functions of STXA210AN STXA213N 2 COMMON SEUNG 3 rA 5 FUNCION LISSCMOUON RR ET 5 2 Dimming functions configuration and setting e EET m 23 2M duisi 23 STXA210AN STXA213N 1 6T 8082 02a hager 1 Description of the Dimming functions of STXA210AN STXA213N applications The STXA210AN and STXA213N application software is used to individually configure each output for the Dimming applications The main functions are the following m ON OFF The ON OFF function is used to switch a lighting circuit ON or OFF e ON switching ON at the lighting level defined by parameters Switching ON can be gradual or instantaneous e OFF switching OFF Switching off c
2. Tripping delay AND logic Switching and tripping delay STXA210AN STXA213N hager Parameters ON OFF Switching delay Tripping delay Switching and tripping delay Timer Operation Parameter The output is the result of the AND logic between the value of the ON OFF object and the value of the Automatic control object owitching delay The output is the result of the AND logic between the 0 5 s 24 value of the ON OFF object delayed when switching and the value of the Automatic control object Default value 3 min Tripping delay The output is the result of the AND logic between the 0 5 s 24 h value of the ON OFF logic delayed when switching and the value of the Automatic control object l Default value 3 min Switching delay 0 5 s 24 h The output is the result of the logical AND between the value of the ON OFF object delayed when switching Default value 3 min and when tripping and the value of the Automatic Tripping delay control object 0 5 s 24 h Default value 3 min Time switch delay 0 s 24 h The output is the result of the AND logic between the value of the ON OFF delayed object and the value of the Automatic control object Timer operation ON OFF Default value 3 min Default value ON 20 6T 8082 02a hager Automatis n Control type Operation Parameter The output is the result of the OR logic betwe
3. e Manual mode authorised Manual mode can be activated at any time e Manual mode inhibited The switch is permanently inhibited It is impossible to switch to manual mode e Time limited manual mode Manual mode can be activated for a configurable duration Default value Manual mode authorised 15 min 30 min 60 min Default value 15 min 6T 8082 02a hager Designation Description Values If the value is Active the values associated with Not active Active the scenes during the last download are restored during the receipt of thei object Default value Not active Scenes restore object See also Scene function only reference TXA213N f the position of the switch is not consistant with the status of the product the indicators associated with the outputs light up in sequence This parameter is only visible if the Activation of manual mode parameter has the value Time limited manual mode m Adjustment of the minimum and maximum dimming values The relative dimming range is adjustable on the product or by ETS configuration A Local adjustment A 4 position switch on the front of the product is used to select the following modes TXA210N 210AN TXA213N The Min and Max positions are used to adjust the minimum and maximum lighting levels for the outputs This adjustment is performed by storing the current value of the output by a long press on the push button corresponding to the output on the
4. no action 101 Dimming speed to scene 4 0s Brightness value for scene 5 101 Ca Value 0 100 no action 101 x Dimming speed to scene 5 Os x Brightness value for scene 6 101 Value 0 100 no action 101 c2 Screen 4 Designation Description Values This parameter authorizes or forbids scene Used Not used Scene storing storing Default value Used This parameter activates or deactivates inversion of the status of the output indicating memorisation Scene memorisation Used Not used acknowledge Default value Used From 0 to 100 in intervals of 1 101 Do Lighting value of the scene This parameter defines the status of the output nothing X associated to scene X Default value 101 Do nothing 05 15 25 35 45 5 105 15 20 5 30 45 s 1 min 2 min min 4 min 5 min 10 min 15 min 20 min 30 min 45 min 1 h 1 h 30 min 2h 2h 30min 3h 3h 30min 4h This parameter defines the dimming speed to achieve the lighting level applied for scene Default value 0s This parameter allows 2 of the 32 possible scenes to be activated with the help of the Scene 1 bit object Not active Active Scene activation 1 bit Default value Not active When the parameter Scene activation 1 bit has the value Active the parameters Scene activation A and Scene activation B must be set These parameters define the scenes to be activated for the two values of the
5. The dimming speed is configurable same values as for the ON OFF function Parameters Switch ON speed Duration Cut OFF speed Duration Parameter Setting screen See Screen Designation Description Values 05 15 25 35 45 5 5 65 9 5 15 5 30 5 60 Switch ON speed As for This parameter defines the dimming speed to s 2 min 5 min 10 min 20 min 30 min the ON OFF function achieve the lighting level when switching on Default value 5 05 15 25 35 45 5 5 65 95 15 5 30 5 60 s 2 min 5 min 10 min 20 min 30 min Cut OFF speed As for the This parameter defines the dimming speed for ON OFF function switching off the light Default value 0 5 STXA210AN STXA213N 9 6T 8082 02a m Timer function hager The Timer function is used to switch a lighting circuit ON or OFF for an adjustable time The function is started by the Timer object The dimming speed is configurable same values as for the ON OFF function Cut off pre warning in ON operation An adjustable cut OFF pre warning indicates the end of the delay time by dividing the lighting level by two The Cut OFF pre warning parameter value defines the time before the end of the delay time when the pre warning will be applied Parameters Timer Not active Duration Cut OFF pre warning No pre warning Duration Timer operation ON OFF Switch ON speed Duration Cut OFF speed Duration Parame
6. Setting range 0 s 24 h 05 055 15 25 35 55 105 15 5 20 5 30 5 40 s 45 s 50 s 1 min 1 min 15 s 1 min 30 s 2 min 2 min 30 s min 4 min 5 min 6 min 7 min 8 min 9 min 10 min 11 min 12 min 13 min 14 min 15 min 20 min 30 min 40 min 50 min 1 h 1 h 30 min 2h 2h30min 3h 3h 4h 5h 6h 12 h 24 h E Special status The settings covered in this section make it possible to define the behaviour of the outputs in certain specific cases Parameter Lighting level when 230 V is restored Value 0 100 Status before cut off 101 Parameter Lighting level on Bus cut off Value 0 100 Maintain 101 Parameter Status after download OFF Maintain Parameter Setting screen See Screen STXA210AN STXA213N 21 6T 8082 02a Designation Lighting level on Bus cut off Lighting level when 230 V is restored Status after download m Metering function hager Description Values From 0 to 100 in intervals of 1 101 Maintain This parameter defines the lighting level applied when the bus is restored Default value 101 Maintain From 1 to 100 in intervals of 1 101 Status before This parameter defines the lighting level cut off applied when the 230 V is restored Default value 101 Status before cut off This parameter defines the status of the orb Mantan output applied after a download Default value Mainta
7. These outputs can be set to an adjustable predefined status Pressing a push button activates a scene The dimming speeds to achieve these levels of lighting are configurable m Metering The Metering function is used to measure the total duration at ON or at OFF for an output A set point triggering an alarm may be programmed m Adjustment of the minimum and maximum limits of the dimming range This function is used to set the minimum and maximum dimming limits for each output These limits can be adjusted by ETS configuration or locally on the front face of the product E Selection of the number of outputs used The product allows 1 2 or 3 lighting circuits to be controlled The maximum available power per output depends on the number of outputs used The total power is limited to 900W e 1 output used 900W e 2 outputs used one 600W output and one 300W output e 3 outputs used 300W per output m Manu Mode Manu Mode is used to isolate the product from the bus In this mode it is possible to force the level of lighting of the lighting circuits locally These parameters can also be adjusted in ETS A local adjustment on the product overrides the last values downloaded only reference TXA213N STXA210AN STXA213N 2 6T 8082 02a hager m Expert mode Expert mode is used to force dimming mode manually It is possible to carry out this adjustment locally on the front face of the product or via an ETS parameter 2 Dimming
8. has following value Active STXA210AN STXA213N 22 6T 8082 02a hager 3 Main characteristics TXA210N Max number of links o 4 Physical addressing To perform physical addressing or check the presence of the bus press the lighted push button located above the label holder on the right of the product Programming LED ON Bus present and the product is in programming mode The product remains in programming mode until the physical address has been transmitted by ETS Press again to exit programming mode Physical addressing can be performed in Auto or Manu mode STXA210AN STXA213N 23 6T 8082 02a hager STXA210AN STXA213N 24 6T 8082 02a
9. imposed by the input This function is started by the Priority object The lighting level for the Priority ON is configurable The dimming speed is configurable same values as for the ON OFF function Priority is the function with the highest priority Only a cancellation command for the priority can end the priority and authorise the bus commands to be to be followed again Parameters Lighting level on Priority ON Value 1 dou 00 Maintain Restore 101 Status after priority Maintain Inversion ON OFF Status before priority Theoretical status at the end of the priority Switch ON speed Duration Cut OFF speed Duration Parameter Setting screen See Screen Description of the Priority object Output behaviour 00 Priority end Output behaviour 01 Priority end 10 Priority OFF 11 Priority ON STXA210AN STXA213N 12 6T 8082 02a hager Parameter Setting screen Participant 1 1 3 Dimmer 3x 300W General l l Brightness at priority 10095 O1 Settings Value 0 100 Maintain value 101 I Timer and Automatic controls _ Status after priority Maintain Scene Special status modd Status after jamming Maintain Metering Q2 Settings Jamming type Permanently Timer and Automatic controls Scene BUS CUT OFF RETURN 230 V ma seit DOWNLOADING Metering ee d Brightness at bus failure Maint
10. 5 min 20 min 30 min 40 min 50 min 1 h 1 h 30 min 2 h 2 h 30 min 3h 3h 30 min 4 h 5 h 6h 12 h 24 h Remark Timer commands repeated n times during the first ten seconds after the beginning of the time delay multiply the duration of the time delay by n times the value of the Timer parameter Timer commands repeated n times within 10 seconds after the beginning of the delay time restart the timer only once m Time limited toggle switch function The Time limited toggle switch function is used to create a toggle switch with a configurable cut off time delay This function is started by the Time limited toggle switch object eee Parameters Time limited toggle switch Not active Duration Parameter Setting screen See Screen Designation Description Value This parameter defines the duration of the eee male ee ea Time limited toggle switch switch OFF delay time Default value 1 h Setting range 0 5 s 24 h 0 5 5 15 25 35 5 105 15 20 5 30 5 40 s 45 s 505 1 min 1 min 15 s 1 min 30 s 2 min 2 min 30 s min 4 min 5 min 6 min 7 min 8 min 9 min 10 min 11 min 12 min 13 min 14 min 15 min 20 min 30 min 40 min 50 min 1 h 1 h 30 min 2h 2h30 min 3h 3h 30 min 4 h 5 h 6h 12h 24 h STXA210AN STXA213N 11 6T 8082 02a hager W Priority function The Priority function allows the outputs to be forced and maintained at a definite ON or OFF status
11. Dimming 4 bit C R W U 10 Output 2 Brightness value 1 Byte C R W U 8 1 Output 2 Timer 1 bit U n 12 Output2 Priority 2 bit C R W U gl Output2 Scene 1 Byte C R U 14 Output 2 Status indication ON OFF 1 bit C R T U 15 Output2 Brightness value 1 Byte C R T U 16 Output3 ON OFF 1 bit C R W U 17 Output3 Dimming 4 bit C R U 18 Output 3 Brightness value 1 Byte C R W U 8 19 Output3 1 bit C R W U 20 Output3 Priority 2 bit C R W U n 21 Output3 Scene 1 Byte C R W U 22 Output 3 Status indication ON OFF 1 bit C R T U 23 Output 3 Brightness value 1 Byte G IR T U 0 26 Outputi Faulty load 1 bit C R T U 27 Output 1 Jamming 1 bit COR W U zz 29 Output 1 Toggle switch 1 bit C R W U zl 31 Output 1 Load memorisation 1 bit C R W U 35 Output2 Faulty load 1 bit C R T U 36 Output 2 Jamming 1 bit C R W U n 38 Output 2 Toggle switch 1 bit C R W U 40 Output 2 Load memorisation 1 bit C R U Output3 Faulty load 1 bit C R T U 45 Output 3 Jamming 1 bit C R U B 47 Output 3 switch 1 bit C R W U 49 Output 3 Load memorisation 1 bit C R U BQ 54 All lighting out Maintenance 2 Byte C R T U 2 3 Function Description Dimmers KNX TXA210N TXA210AN and TXA213N have a load memorisation function in order to control dimmable fluocompact lamps and LED lamps more effectively These products also have a priority function for the dimming mode which allows the desired dim
12. E REVAN Minimum dimming value the lighting level during dimming Default value 1 From 51 to 100 in intervals of 1 This parameter defines the maximum value of the lighting level during dimming Maximum dimming value Default value 100 These parameters are only visible if the Relative dimming limits parameter during downloading has the value Values settings in ETS STXA210AN STXA213N 7 6T 8082 02a hager m Dimming function The dimming can be relative or absolute A Relative dimming The relative dimming allows increasing or decreasing the lighting level of the lighting circuit as long as a push button is pressed down The relative dimming function is started by the Dimming object The speed of dimming is configurable Parameter Relative dimming speed Duration Parameter Setting screen See Screen Designation Description Values 2 15 25 35 45 5 5 65 9 5 15 5 30 5 60 5 Relative dimming speed This parameter defines the dimming speed to go from level 0 to level 100 Default value 4 s STXA210AN STXA213N 8 6T 8082 02a hager B Absolute dimming The parameters set in the ON OFF function are also applied to the Absolute dimming function No specific adjustment needs to be performed The Absolute dimming function allows applying a brightness level to the lighting circuit when switching it ON or OFF The absolute dimming function is started by the Brightness value object
13. N or at OFF if the Time switch delay value of the Automatic control object is O ON OFF Timer toggle switch Default value 3 min change over Default value ON The output is delayed when switching if the owitching delay value of the Automatic control object is 1 0 5 s 24 h The commands are not taken into consideration if the value of the Automatic control object is 0 Default value min Switching delay The output is delayed when tripping of the value Tripping delay of the Automatic control object is 1 0 5 s 24 h The commands are not taken into consideration if the value of the Automatic control object is 0 Default value min Tripping delay Authorization Switching delay l MM 0 5 s 24 h The output is delayed when switching and when tripping if the value of the Automatic control object is 1 The commands are not taken into consideration if the value of the Automatic control object is O Default value 3 min Switching and tripping delay Tripping delay 0 5 s 24 h Default value 3 min Time switch delay 0 5 24 h The output is delayed if the value of the Automatic control object is 1 Default value 3 min The commands are not taken into consideration Timer operation if the value of the Automatic control object is 0 ON OFF Default value ON STXA210AN STXA213N 19 6T 8082 02a Automatis m type Control type ON OFF Switching delay
14. Scene 1 bit object Scene A activation 0 No active scene Scene 1 to Scene 32 Scene B activation 1 Default value No active scene This parameter is only visible if the Scenes memorisation parameter is activated These parameters are only visible if the Activation scene 1 bit parameter has the value Active B Learning and storing in the room This procedure modifies and stores a scene by local action on the push buttons located in the room e Activate the scene by pressing briefly on the room push button that triggers the scene e Setthe outputs to the desired status using the push buttons that control them individually e Store the output statuses by pressing the room push button that triggers the scene for longer than 5 s Storage is indicated by the inversion of the status of the outputs concerned for 3s STXA210AN STXA213N 16 6T 8082 02a hager C Learning and storing on the product This procedure allows modifying and storing a scene by means of local action on the push buttons located on the front side of the products This procedure also allows an output to be removed from a scene Not involved Activate the scene by pressing briefly on the room push button that triggers the scene Store the output statuses by pressing the room push button that triggers the scene for longer than 5 s The storage is indicated by the status inversion of the involved outputs for 3 sec As soon as the indicators associated with
15. Values Used Not used This parameter defines if the load Load memorisation Ma memorisation function can be used or not Default value Not used This parameter is only available when the Dimming mode after download parameter is defined as the value configured in ETS m ON OFF Status indication and Brightness value indication functions The ON OFF function enables switching the output to ON or to OFF using the ON OFF object e ON switching ON at the lighting level defined by parameters Switching ON can be gradual or instantaneous e OFF switching OFF Switching off can be progressive or instantaneous The speed of dimming is configurable The speed at which the lighting switches on and off are configured for the ON OFF function the values of these parameters are re used by the Absolute dimming Timer and Priority functions The output status and the lighting level are indicated on the bus by the Status indication object and Brightness value indication object Parameters Switch ON speed Duration Cut OFF speed Duration Lighting level on switching on Value 0 100 Last value 101 Minimum dimming value Value 1 50 Maximum dimming value Value 51 100 These parameters are only visible if the Relative dimming limits parameter during downloading has the value Values settings in ETS m Operating principle STXA210AN STXA213N 6 6T 8082 02a hag
16. ain Q3 Settings z Value 0 100 Maintain value 101 ee Timer and Automatic controls ne BADBEAA Sorte Brightness at mains return Maintain Value 09 1009 Last value 101 ee Special status Metering Status after download Maintain Information Screen 3 Designation Description Values Lighting level on Priority ON Status after priority Switch ON speed As for the ON OFF function Cut OFF speed As for the ON OFF function STXA210AN STXA213N From 1 to 100 in intervals of 1 101 101 e If the output is off Re establishment of the level defined by the Lighting level when lighting is switched on parameter e lf the output is on Maintains the level before the priority This parameter defines the lighting level for the priority Default value 100 Maintain Inversion Status before priority e Maintain Maintains the output at the status active during Priority e Inversion Inversion of the output s status with regards to the status active during Priority ON to OFF and OFF to ON ON Switch the output to ON OFF Switch the output to OFF Status before priority Switch the output to the status in place before the Priority control e Theoretical status at the end of the priority Switch the output to the status which would be in place if no priority control had taken place This parameter defines the level of lighting applied at the end of the priority Default value M
17. aintain 05 15 25 35 45 5 5 6s 95 15 30 s 605 2 min 5 min 10 min 20 min 30 min This parameter defines the dimming speed to achieve the lighting level when switching on Default value 0 s 05 15 25 35 45 55 65 95 15 30 s 605 2 min 5 min 10 This parameter defines the min 20 min 30 min dimming speed for switching off the light Default value 0 s 13 6T 8082 02a hager m Jamming function The Jamming function allows the outputs to be locked in their current status This function is started by the Jamming object The Jamming function is the function with the second highest priority after Priority A Jamming end command ends the jamming and allows again taking the commands from the bus into consideration A Priority command ends the Jamming Parameters Status after jamming Maintain Inversion OFF Theoretical status at the end of jamming Jamming type Permanently Time limited Jamming duration Duration Parameter Setting screen See Screen Designation Description Value Maintain Inversion ON OFF Theoretical status at the end of jamming e Maintain Maintains the output at the status active during Jamming e Inversion Inversion of the output status with regards to the status active during Jamming This parameter defines the output status to ON to OFF and OFF to ON be applied at the end of the Jamming ON Switch the output to ON e OFF Switch the o
18. an be progressive or instantaneous The control can come from push buttons m Relative or absolute dimming Brightness value The relative dimming allows increasing or decreasing the lighting level as long as a push button is pressed down The speed of dimming is configurable The absolute dimming allows defining in 96 the lighting level to reach by means of the Lighting level object m Timer The Timer function is used to switch a lighting circuit ON or OFF for an adjustable time Depending on the operation mode selected the output may be delayed for ON or OFF switching An adjustable cut OFF pre warning indicates the end of the delay time by dividing the lighting level by two The timer can be interrupted before the end of the time delay m Time limited toggle switch The Time delayed switch function combines a toggle function and a cut OFF delay Pressing briefly a push button inverts the output If the output is at ON it switches automatically to OFF after a programmable time delay to prevent it being forgotten Application Lighting for attics cellars store rooms etc m Priority The Priority function allows overriding an output to an adjustable lighting level This command has the highest priority No other command is taken into account if a priority is active Only a priority end command re enables the other commands Application maintaining lighting ON for safety reasons m Scene The Scene function groups a set of outputs
19. d Default value Switching and tripping delay hager Operation Parameter The output is controlled directly The Automatic control object is ignored owitching delay The output is delayed when switching 0 5 s 24 h The Automatic control object is ignored Default value 3 min Tripping delay The output is delayed when tripping 0 5 5 24 h The Automatic control object is ignored Default value 3 min owitching delay l 0 5 5 24 h The output is delayed when switching and when tripping E Default value 3 min The Automatic control object is ignored The switching and tripping delay times may be different Tripping delay 0 5 s 24 h Default value 3 min Time switch delay 0 5 s 24 The output is delayed at ON or at OFF Default value 3 min The Automatic control object is ignored Timer operation ON OFF Default value ON Alternating time switch delay Duration O s to 24 hrs Alternating timer operation ON OFF Parameter Setting screen See Screen STXA210AN STXA213N 18 6T 8082 02a hager Parameters Timer toggle switch change over Switching delay Tripping delay Switching and tripping delay Timer Automatism type Control type Operation Parameter Time switch delay l l s 24 h The output is controlled directly by the ON OFF object if the value of the Automatic control object is 1 The output is delayed at O
20. d the push button which initiates the scene Each output can be integrated in 32 different scenes The status of each output may be defined by parameterising by learning in the room using the push buttons of the installation or on the product A Configuration and storing by parameterisation Parameters 32 Scenes Lighting value of the scene X Value 0 100 Do nothing 101 Dimming speed to scene X Duration Tete Tete Description of the Scene object 1 byte Operating principle Scene 1 Scene 2 Scene 1 STXA210AN STXA213N 15 6T 8082 02a Parameter Setting screen Participant 1 1 3 Dimmer 3x 300W General Scene activation 1 bit hager Not active O1 Settings Timer and Automatic controls Scene memorisation Used Scene by long key press Special status Scene memorisation acknowledge Not used x Metering 02 Settings Brightness value for scene 1 101 fixer end Ad ELS Value 0 100 no action 101 Scene Dimming speed to scene 1 o S Special status Metering Brightness value for scene 2 101 Y C i 03 Settings Value 0 100 no action 101 Timer and Automatic controls Dimming speed to scene 2 0s Scene Special status Brightness value for scene 3 101 Ca Value 0 100 no action 101 C Metering Information Dimming speed to scene 3 lo 5 X Brightness value for scene 4 101 Value 0 100
21. en the ON OFF value of the ON OFF object and the value of the Automatic control object owitching delay The output is the result of the OR logic between the 0 5 s 24 h Switching delay value of the ON OFF object delayed when switching and the value of the Automatic control object Default value 3 min Tripping delay The output is the result of the OR logic between the 0 5 s 24h Tripping delay value of the ON OFF object delayed when trippign and the value of the Automatic control object Default value 3 min owitching delay 0 5 s 24 h logicOR The output is the result of the OR logic between the Default value 3 min ON OFF object delayed when switching and tripping and the value of the Automatic control object Switching and tripping delay Tripping delay 0 5 s 24 h Default value 3 min Time switch delay 0 s 24 h The output is the result of the OR logic between the Default value 3 min value of the ON OFF delayed object and the value of the Automatic control object Timer operation ON OFF Default value ON Setting range 0 5 s 24 h 0 5 s 1s 2 s 35 5 105 15 5 20 5 30 5 40 5 45 s 50 s 1 min 1 min 15 s 1 min 30 s 2 min 2 min 30 s min 4 min 5 min 6 min 7 min 8 min 9 min 10 min 11 min 12 min 13 min 14 min 15 min 20 min 30 min 40 min 50 min 1 h 1h 30 min 2 h 2 h 30 min 3h 3h min 4 h 5h 6h 12 h 24 h
22. er Switch ON speed Relative dimming speed Cut OFF speed Lighting level on switching on Min lighting level Parameter Setting screen Participant 1 1 3 Dimmer 300W General TIMER O1 Settings Timer and Automatic controls Timer min Scene Cut OFF pre warning No pre warning Special status C Metering Timer operation ON M Q2 Settings Timer and Automatic controls Timer interruption Interrupti ble by long press Scene seine Time limited toggle switch 1 h Metering Soo AUTOMATIC CONTROLS Timer and Automatic controls ee ae Control type ON OFF Special status Autamatism type Not used E Metering Information Screen 2 Designation Description Values 05 15 25 35 45 5 5 65 9 15 5 30 5 60 Switch ON speed This parameter defines the dimming speed to s 2 min 5 min 10 min 20 min 30 min achieve the lighting level when switching on Default value Os 05 15 25 35 45 5 5 65 95 15 5 30 5 60 Cut OFF speed This parameter defines the dimming speed for s 2 min 5 min 10 min 20 min 30 min switching off the light Default value 0 s From 0 to 100 in intervals of 1 101 Last Lighting level on switching This parameter defines the lighting level when value on switching on Default value 101 Last value This parameter defines the minimum value for FIOI Eat SO
23. front of the product B Parameters ETS In case of ETS downloading it is possible to e Not modify the limits set locally e Replace the limits set locally by the configured values e Replace the dimming mode selected locally by the configured values Designation Description Values This parameter is used to authorise or prohibit the Forbidden Authorized taking into account of the Min and Max positions of the switch Default value Authorized Local min max dimmer settings autorisation Values adjusted on the product This parameter authorises or prohibits the taking into Values settings in ETS account of the limit values for the dimming range configured with the ETS Default value Values adjusted on the product Relative dimming min max values after download Values adjusted on the product Dimming mode after This parameter is used to define which setting is taken download into account after downloading Default value Values adjusted on the product STXA210AN STXA213N 4 6T 8082 02a hager 2 2 Objects List go Output1 ON OFF 1 bit U 5 1 Output1 Dimming 4 bit C R U 2 Output 1 Brightness value 1 Byte C R W U 3 Output1 1 bit C R W U DES Outputi Priority 2 bit C R W U 5 Outputi Scene 1 Byte C R W U 5 Output 1 Status indication OFF 1 bit C R T U 57 Output 1 Brightness value 1 Byte C R rien Output2 ON OFF 1 bit C R W U Output2
24. functions configuration and setting 2 1 Common settings Selection of the number of outputs This parameter is used to select the number of outputs used Parameter Setting screen Participant 1 1 3 Dimmer 3x 300W General Tm I C Number of outputs 01 Settings tp 3 Timer and Automatic controls Local min max dimmer Used Scene settings autorisation i Special status ae Relative dimming min max values Values adjusted on the product Metering after download Q2 Settings Dimming mode after download Timer and Automatic controls Scene Special status OTHER PARAMETERS Metering Activation of manual mode Q3 Settings Timer and Automatic controls Scene Special status Metering Information Screen 1 Designation Description Values Number of outputs used Activation of manual Duration of manual mode activation STXA210AN STXA213N This parameter is used to select the number of outputs used This parameter enables or disables the 2 position switch located on the front side of the product This switch is used to select Manu or Auto mode In Manu mode the outputs can be controlled using the push buttons on the front of the product In Auto mode the orders from the bus control the outputs This parameters defines the duration of activation of the manual mode 1 2 3 Default value 3 Manual mode authorised Manual mode inhibited Time limited manual mode
25. in The Metering function is used to measure the total duration of an output at ON or at OFF The duration is transmitted by the Metering object A set point triggering an alarm may be programmed The alarm is transmitted by the Counter set point reached object The current measurement can be consulted at any time using the Meter object Parameter Setting screen Parameters Metering function Not active Active Output status for hours counter OFF ON Hours counter mode Increment Countdown Set point for sending alert hour Duration Periodic sending of counter value Duration Designation Description Values This parameter allows activating the Counter function Not active Active Metering function The value of the counter can be read through the Output status for This parameter allows choosing the status of which OFF ON hours counter the cumulated time is measured Default value ON Hours counter mode This parameter is used to define the Hours counter _ Increment Countdown mode Default value Increment Set point for sending This parameter defines an alarm set point for which alert hour the Counter set point reached object will be sent From 0 to 50000 hours with 1 hour steps Remark The Counter set point reached object may be reset either by a new download or by means of a display tool Default value 1000 This parameter is only visible if the Counter function parameter
26. ming modes to be selected The Memorisation object is used to launch the memorisation procedure Memorisation of the load can also be launched thanks to a specific sequence of presses on a KNX push button e With a KNX push button configured for dimming give 5 short presses 5 ON 5 OFF or 5 ON OFF followed by a long press until the load switches off e Give a brief press on the push button to launch memorisation two presses to return to factory dimming mode This operation lasts approximately 30 s and varies the level of lighting After this memorisation the load lights at the maximum level and flashes once to indicate that memorisation is terminated Depending on the load connected the minimum lighting level can be modified This memorisation can be authorised or not authorised thanks to the memorisation authorisation parameter Dimming mode can be configured to a fixed value using the Selection of the dimmig mode parameter Designation Description Values Fluocompact Capacitive load Induction load This parameter is used to define the LED load Load memorisation Factory mode dimming mode applied Dimming mode selection Default value Factory mode This parameter is used to define if it is Used Not used possible to modify the dimming mode using the expert button on the front of the product Default value Used Authorisation of the expert button STXA210AN STXA213N 5 6T 8082 02a hager Designation Description
27. ter Setting screen See Screen Values Designation Description Timer This parameter defines the length of the delay AOAC RANJE Ded Mes Default value 3 min The parameter value defines the time before the No pre warning 15 s 30 s 1 min Cut OFF pre warning end of the delay time when the pre warning will be applied Default value No pre warning This parameter defines whether the delay time ONOFF Timer operation triggers an ON or an OFF status Default value ON 05 15 25 35 45 55 6 5 95 15 5 30 5 60 Switch ON speed As for This parameter defines the dimming speed to s 2 min 5 min 10 min 20 min 30 min the ON OFF function achieve the lighting level when switching on Default value 0 s 05 15 25 35 45 5 5 65 9 15 5 60 Cut OFF speed As for the This parameter defines the dimming speed for s 2 min 5 min 10 min 20 30 min ON OFF function switching off the light Default value 0 5 This parameter allows or not the interruption of Interruptible timer Non interruptible timer Timer interruption the timer when the associated push button is pressed for a long time Default value Interruptible timer STXA210AN STXA213N 10 6T 8082 02a hager Setting range 1 s 24 h 1 5 25 35 55 10 5 15 20 s 30 s 40 s 45 5 50 s 1 min 1 min 15 s 1 min 30 s 2 min 2 min 30 s min 4 min 5 min 6 min 7 min 8 min 9 min 10 min 11 min 12 min 13 min 14 min 1
28. the outputs blink slowly press briefly and repeatedly the push buttons linked with the outputs to set the outputs to the desired status The indicators associated with the outputs show the status chosen e Off if the value selected for the scene is 0 e Permanent red if the value selected for the scene is greater than or equal to 1 e Red and quickly blinking if the value selected for the scene is Not involved Store the status selected for this scene pressing for a time longer than 3 sec the push button associated with the output The storage is indicated by the return of the slow blinking of the indicators associated with the outputs Repeat the previous step for each of the outputs of the scene E Timer and Automatic controls functions The Timer and Automatic controls function allow the outputs to be controlled by The time delay functions Timer toggle switch change over Timer Switching delay Tripping delay Switching and tripping delay The automatic controls functions Authorization AND or OR logical combinations Parameters The status of the output depends on the combination of the parameters Type of automatic control and Control type Parameters ON OFF Switching delay Tripping delay Switching and tripping delay Timer Parameter Setting screen See Screen STXA210AN STXA213N 17 6T 8082 02a Automatism type Control type ON OFF Default value Switching delay Tripping delay Not use
29. utput to OFF e Theoretical status at the end of jamming Switch the output to the status which would be in place if no jamming control had taken place Status after jamming Default value Maintain Permanently Time limited e Time limited Jamming is active for a This parameter defines whether Jamming parameterisable limited duration Jamming type is permanent or time limited Default value Permanently Not active Range 0 s 24 h This parameter defines the Jamming duration Jamming duration Default value 1 h Setting range 0 s 24 h 5 15 25 35 5 10 5 15 20 s 30 5 40 s 45 5 505 1 min 1 min 15 s 1 min 30 s 2 min 2 min 30 s min 4 min 5 min 6 min 7 min 8 min 9 min 10 min 11 min 12 min 13 min 14 min 15 min 20 min 30 min 40 min 50 min 1 h 1 h 30 min 2h 2h 30 min 3h 3h 30 4h 5h 6h 12h 24 h This parameter is only visible if the Jamming type parameter has following value Time limited STXA210AN STXA213N 14 6T 8082 02a hager m Scene function A scene is used to control a group of outputs Each of the outputs in the group will be set to a status pre defined for the scene A scene has been initiated by the object Scene For each scene it is possible to configure the lighting level and the dimming speed to achieve this level The group of outputs is created in advance by establishing the link between the outputs that are to be part of the scene an