Home
Newport 400 MPC 3000 (Rotoflow) User Manual
Contents
1. Bg Eu dura dL pisse p pedes Jue ash paper go Installation Basics Thruhull Not Supplied Read the directions e Avoid tight hose bends and excessive runs e Use heavy gauge wire Install feed pump as low as possible e Use a dedicated thruhull with scoop type strainer Thru hulls It is mandatory that a dedicated 3 4 to 1 forward facing scoop type intake thru hull and seacock be installed Install the intake for the system close to the middle and as far below the water line as possible Thru hulls in the bow area are susceptible to air intake in rough condi tions Sharing a thru hull with another system is not acceptable and will void the warranty Sharing a thru hull can introduce unforeseen problems such as intermittent flow restriction air bubbles and contaminates For racing boats and high speed power boats above 15 knots a retractable snorkel type thru hull fitting is preferred to be able to pick up water away from the hull Do not install the intake close to or downstream of a head discharge Install as far below the waterline and as close to center line as possible to avoid contamination and air induction The brine discharge through hull should be mounted above the waterline in or just above the bo
2. y 30 Normal Start Up Using the Auto Run Button Press Auto Run button once and the system will prime and run for 1 hour The dis play reads AUTO RUN MODE then STARTING with 30 second priming countdown timer After the prime the display reads AUTO RUN MODE with a countdown timer An hour of run time is added up to 12 hours with each successive momentary press of the Auto Run button hour can be added at any time The dis play shows the default readout unless there is an alarm condition Successive presses of the Alarm Display button will scroll through the displays starting with GPH PRODUCT Upon auto shut down by the timer or by the optional tank full float switches the system will automatically fresh water flush and re flush every 5 days Pressing the Stop button stops the sequence at any time with no flushes Normal Operation For optimum performance Auto run the system as long as possible at one time Never let the system sit with salt water in it Never allow continuous air leaks in the intake Normal Shut Down If the system was started using the Auto Run button the system will shut off on its own when the selected run time is over and will auto flush every 5 days Pressing the Stop button at any time will shut off the system with no auto flush function The optional tank float switches will shut off the system from any mode If the sys tem was started by t
3. 26 Membrane Pressure Vessel Relocation eee 45 Z Brane Install qen 3e D iino iin 56 Operation New Systems Start Up and Testing Unos aa sea eR De 27 Dry Testi cave aS SA aem tec sa tears os tps 30 Normal Start Up Using Auto Run sina e d p Ae ps 31 Automatic Fresh Water Flush Cycle i eet tta ree exch 32 Emergency Operatioh couches pedo un M Sassy QU a uS aca Mh Ted iat dors queen URN 33 Maintenance oderit Ne pin etti Ten eee 38 Service amp Maintenance Long Termi Storage Pro edures 34 WIRE ID ce daz TEM 37 Membrane Cleanitig iere t ak pana a isparar pa 39 Salinity Probe Cali br ati s perse atus erede da enda us die 41 a BI Ant aa 44 Newport Troubleshooting Procedures Service Bulletins 47 Parts breakdown for all Newport 2 59 Getting Started Unpack the system and inspect it to make sure that it has not been damaged in shipment Refer to the shipping list for your system to make sure you have received all of the compo nents listed Do not discard any packaging until you have found and identified all of the parts The small installation pa
4. High Pressure blocked brine discharge Check brine discharge fouled membrane Clean membrane Voltage Too High battery voltage too high or Charge batteries Voltage Too Low low Check charging voltage loose wires or poor connec Check power connections tions Re starting no signal from stroke sensor See remedy above for system at startup System Air locked stalled Check Fuse followed by fuse number blown fuse at circuit board Replace fuse mini automotive type ATM Look for cause Service Prefilter clogged filters loose or defective pressure sensor wires Install new filters Check sensor wiring Sea Strainer clogged strainer dirty 50 Micron prefilter Seacock closed Clean strainer screen change 50 Mic Check through hull and intake hoses Salinity High high product water salinity chlorine damage to mem branes defective salinity probe or cable cable disconnected Check for low feed pressure Check for leaks at high pressure hoses Remove and clean probe con tacts check calibration Check cable connections Clean membrane 48 Operation and Repair Bulletins The following documents are sections of our complete service bulletin set These are available on our website Spectratermakers com MB 2 MEMBRANE CARE Membrane life is affected by a large number of factors and is somewhat unpredictable A big commercial pl
5. coal filter you will toast a 450 00 membrane on the first flush The other factor is the flow rate that the filter can handle Because the chlorine is deactivated by a chemical reaction with the charcoal it must remain in contact with the charcoal for sufficient period of time for the reaction to be complete The filter we use can handle 1 5 gallons 6 litres per minute flow and are good for 3000 gallons 12 000 litres at 1 5 GPM or six months whichever comes first Regardless of the flow the charcoal loses its effectiveness after six months 7 26 04 55 SPECTRA WATERMAGHINES Z BRANE OPERATION MANUAL The Z brane is a revolutionary product which incorporates the Z Guard High Voltage Capacitive technology into the membrane pressure vessel Always active the Z Brane creates an environment that is unfriendly to bio film and bacteria The Z technoalgy also assits in the prevention of scale formation on the membrane surfaces The Z Brane allows the system to be shut down or decommissioned for extended periods of time without chemicals or preservatives The Z Brane will not prevent freezing so that in cold climates Propylene Glycol is still required The Z Brane system is integral with the watermaker unit and only requires continuous 12Vor 24V DC power to be operative The installation of the Z Brane only consists of wiring the power supply to a continuous source The Z brane power supply can tolerate voltages between 10V a
6. Alkaline cleaners are used for bio fouling Cleaning chemicals espe cially the alkaline are not good for the membrane Every time you clean the membrane it shortens its life Clean only when necessary and avoid cleaning as a diagnostic tool Chlorine will destroy a membrane in minutes It attacks the material that the membrane is made from Always use product water or water filtered slowly through a charcoal filter for flushing and chemical treatments Oil simply plugs up the matrix of the membrane and clogs it up We have brought back oil fouled membranes with Joy soap See MB 5 Cleaning with Detergent For storage we recommend using propylene glycol potable water system antifreeze if avail able It can safely be left in the system for one year and will keep things from freezing in cold conditions It is hard to find in warm climates and takes up a lot of room on a small boat so our 5 1 is best for tropical cruising 49 Given good care a membrane will eventually just start to slowly fade away The feed pres sure may rise and or the ppm go up Hardly ever will they just fail overnight 8 13 04 MB 5 MEMBRANE CLEANING WITH DETERGENT If the membrane has been fouled with oil it may be possible to save it by cleaning it with dish soap such as Joy Don t use anything that may contain bleach You will need quite a lot of chlorine free fresh water If using shore water run it through a charcoal filter at a rate of not more than 1 5 g
7. SO HPP PLP Valve port seals SO HPP VP Pilot valve port seals Piston rod Center block cvlinder O rings SO HPP ECCB Pilot spool O rings 4 Mount inside block SO HPP PV HP CB PVS Pilot spool HP CB PPS Pilot valve pin SO HPP PS Pin seal O rings HP CB PVPS Pin seals HP CB PVCR Clip rings Pilot orifice UR Center block Rod lip seals Mount inside block SO HPP PR7 PR10 PR15 Feed in Check valve port O rings SO HPP CVP Check valve assembly Piston to rod O rings 2 Inside pistons Glass rod models only Center Block i Check valve SO HPP CVS I O ring Check valve seat HP CB CVS 7 Check valve poppet HP CB CV Check valve spring Check valve washer Check valve retainer HP CB CVR 70 S S compression 2 co De lt lt pi We CYL lt iston with seal cu m Y id Sy NS J Composite cylinder and base HP CYL CCA Cylinder Assembly
8. run separate wires from the switch to each tank switch The second wires can both be run to the Float Switch 1 terminal 2 If you are using two switches in each tank you will need a double pole double throw switch 26 New System Start Up and Testing Avoid running the system if the vessel is in contaminated water such as in a harbor or ca nal The system should be fully run tested before leaving port It is preferable to sacrifice a filter by running the system in turbid water rather than waiting to get offshore to discover a problem or deficiency in the installation If the location or weather prevents proper testing refer to the section Dry Testing Warning Damage may occur if the purge sequence is bypassed and the membrane is pressurized with storage chemical in it 1 First Check That Thru hull valve is open Power is on If you have an AC system both the AC power and the DC control voltage to the unit needs to be on Manual Auto Run Switch in Auto Position Manual Auto Flush Switch in Auto Position Domestic fresh water system must be on 2 Open pressure relief valve 1 2 turn 3 Power up the system e Alarm will sound Push the Alarm Display button to silence alarm 27 4 Press Auto Run Button gt y s o The system will go into a start mode and the feed pump will start shortly after The system should prime within 60 90 seconds Check the strainer and the brin
9. secure from vibration and chafe Have at least one shallow bend in a tube assembly after it is installed Refer to figure 1 If a fitting has been dissembled reassemble as illustrated The notch on the ferrule must engage the inside of the nut properly for the nut to seat down fully Once the tube is inserted the ferrule and nut will naturally align Refer to figure 2 Insert tube fully into the fitting it should go in 0 9 Tighten the nut finger tight while moving the tube around to prevent binding One thread should be showing under the nut Secure the tube so it won t back out when tightening Refer to figure 3 Use 13 16 wrench to hold a straight body fitting or a 3 4 wrench for a 90 body and a 7 8 wrench for the nut Hold the body recheck the tube insertion then tighten the nut 1 1 4 turns Use the index mark on the nut as a guide The threads should be completely covered by the nut Make Sure these fittings are tight on initial assembly or they will fail The correct Torque is specification is 85 foot pounds Index mark Straight thread Straight or 90 deg 3 8 pipe thread LIS p OJ Lj LU SZ Nut Ferrule Body Nut finger tight with thread showing Cut tube square UN Figure 2 Black high pressure tubing z z Tighten l 2 3 turns 10 flats of the nut with a7 8 wrench after finger tight Use index mark as guide y No threads showing Figure 3
10. 1 2 NPT X 5 8 HOSE BARB NYL ST 1 2 X 1 4 BUSHING REDUCER PL TEE 1 2FN 1 2 TEE FEMALE NYLON PL PSG LP2 5 SPECTRA PRESSURE GAUGE PL NP 1 2N 1 2 CLOSE NIPPLE NYLON PL ACC TK ACCUMULATOR TANK 67 End block B HP TB VEB B Valve block HP TB VB PEDE E cylinder Brine out HPCYLCCA Pressure relief valve HP TB BV Center block HP CB CB7 10 15 20 Feed in ka steel tube 7 Cylinder ring Clark Pump HP CYL EC End block A End block B Reset button Not on all unitsHP TB RSB3 Alternate brine out SR Composite cvlinder and base High pressure in Test port Center block High pressure out Stainless steel tube Cylinder ring Clark Pump End cap 68 5 16 3 1 4 SS AH Bolts HD CPS 5 16X3 Relief Valve O Ring SO HPP RV Annular Ring O Rings Mount inside Valve Block SO HPP AR Valve Block HD CPS 5 16275 5 16 2 3 4 SS bolts Reset button and O ring E End block B SO HPP sP Ps20 Piston O ring aa HP TB VSP VSP20 Spool piston HP TB SR Spacer ring Valve block l SO HPP VB Valve bore O ring Valve bore Spacer ring Oils Spool piston End block A SO HPP VP Valve spool Pilot port O rings SO HPP PLP Reversing Valve LY End Blocks 69
11. 2 and SC 3 are never mixed together Do not use them for stor age pickling solution Cleaning Procedure Step 1 Flush the system twice Use the Auto Flush button on the MPC 3000 display once the first flush has been completed press Stop to cancel the 5 day interval timer then press Auto Flush again Step 2 Remove the quick disconnect fitting from the brine discharge outlet of the Clark pump and replace with a quick disconnect from your service kit fitted to a hose and lead the hose to a 5 gallon bucket Step 3 Press Auto Flush again 700 1000 systems use service switch to fill the bucket with fresh unchlorinated water 1 gallon 4L for 400 systems 2 gallons 8L for 1000 systems Press Stop when the bucket has reached the desired level Step 4 Connect a hose using the garden hose barb fitting from your service kit to the ser vice port of the fresh water flush module Lead the hose into the bucket Turn the service valve on the fresh water flush module 180 so the intake is now coming from the bucket Step 5 Mix the cleaning chemical compound into the water in the bucket Step 6 Make sure the pressure relief valve on the Clark pump is Open unpressurized Step 7 Use the Feed Pump Manual switch 700 1000 systems use service switch on the MPC control box to turn on the feed pump Circulate the storage chemical in the sys tem for approximately 25 minutes Turn off the switch when finished Cle
12. 24V EL MTR SPCDC12 3 4 HP SPEED CONTROLLER 12V 1 2 MPT X 3 4 HOSE BARB ELBOW PL CLP 10SS 10 CLAMP HSE 3 4 1 316 EL MTR 1 3D12 NEWPORT SUB NP MNFC 400 MOTOR 12V EL MTR 1 3D24 NEWPORT NEWPORT INTAKE MANIFOLD 400 MOTOR 24V PL NLT 1 2HP 1 2 HIGH EL SWT VC VACUUM SWITCH PRESSURE TUBE DAYCO PL HS 3 4SH PL PMP VBC V BAND CLAMP 3 4 REINFORCE SUCTION HOSE PL MTE 1 2X1 2P 1 2 MALE NPTX1 2 TUBE FITTING ELL PL HBE 1 2X3 4 PL PMP 140175 1 2 MPT X 3 4 HOSE BARB ROTARY VANE PUMP 140 175 ELBON AUST 60 700 1000 Models EL MTR 3 4AC220 3 4 HP 240 VAC 3 PHASE 56C MOTOR EL MTR 3 4D24 3 4 HP MOTOR 24V SUB NP MNFC NEWPORT INTAKE MANIFOLD PL HBE 1 2X3 4 1 2 MPT X 3 4 HOSE BARB PL PMP PCA ELBOW MOTOR COUPLING AND ADAPTOR EL SWT VC VACUUM SWITCH PL PMP VBC V BAND CLAMP FOR PL HS 3 4SH ROTARY VANE PUMP 3 4 REINFORCE SUCTION HOSE PL MTE 1 2X1 2S 1 2 X 1 2 TUBE FITT ELL PL NLT 1 2HP 1 2 HIGH SS PRESSURE TUBE DAYCO 1 2 MPT X 3 4 HOSE BARB PL PMP 240250 ELBOW ROTARY VANE PUMP 240 250 PL CLP 10SS AUST 10 CLAMP HSE 3 4 1 316 EL MTR SPCDC 3 4HP SPEED CONTROLLER 24V EL MTR SPCDC12 3 4 HP SPEED CONTROLLER 12V EL TM 30A4 TERMINAL BLOCK 30A 4 CIRCUITS SUB NP 12VRLBA 12V RELAY MODULE SUB NP 24VRLBA 24V RELAY MODULE EL MPC PCB CONTROL MODULE PCB FM NPC ACB NEWPORT AC BOX 61 FT PV UTC PL NLT 1 4LP PL
13. Systems may use the switches on the control box Step 4 Connect a hose using the garden hose barb fitting from your service kit to the ser vice port of the fresh water flush module Lead the hose into the bucket Turn the service valve on the fresh water flush module 180 so the intake is now coming from the bucket Step 5 Mix the storage chemical compound into the water in the bucket Step 6 Make sure the pressure relief valve on the Clark pump is Open unpressurized Step 7 Use the Feed Pump Manual switch 700 100 systems use the service switch on the MPC control box to turn on the feed pump Circulate the storage chemical in the system for ap proximately 10 minutes Turn off the switch when finished Remove the quick disconnect from the Clark pump brine discharge and replace the origi nal hose that leads to the thru hull You may at this point if you choose to pump the bucket dry by using the feed pump switch Stop when the bucket is empty Turn the service valve 180 back to its original position and remove the service hose Turn off the power to the system and the MPC control 35 9t Step 1 Flush the system by pressing Auto Flush on the LCD display Press Start Stop when the flush is done to cancel the 5 day timer Then press Auto Flush to flush the system a second time Press Start Stop again when finished E Step 3 Press Auto Flush to fill bucket with desired level
14. flow 15 sensed then the MPC will fault with the code SYSTEM STALLED Product water to tank Check valve Reject Product e Product water from membranes Salinty Probe Diversion Valve Salinity Probe Rotoflow Assembly This assembly located at the Clark pump Membrane module on Newport models The salin ity probe should be removed and cleaned once a year if incorrect readings occur The probe wire is connected by a plug under the rubber boot at the sensor Both the diversion valve wires two conductor and the rotorflow sensor three conductor are to be spliced with the supplied butt connectors to their respective harness Heat the con nectors to shrink Note There is no polarity or color code on the diversion valve wires The Rotoflow wires connect red to red Black to black and the brown to white 24 Connection of Optional Accessories Use of any external devices not approved by the factory may cause permanent damage to the controller and is not covered by the Spectra warranty Accessory outputs are lim ited to 2 amps maximum load Do not connect motors pumps etc to accessory outputs Optional Z Guard System Detailed instructions are included with the Z Guard kit Con nect to the Aux1 and GND terminals of the MPC board Ultraviolet Sterilizer Detailed instructions are included with the sterilizer kit The UV sterilizer lamp module and ballast unit should mount vertically with the pro
15. get past the prefilters If membrane performance is reduced and they have not been pickled recently cleaning with both chemicals is recommended The acid cleaner should be used first If the membrane fails to respond to both cleanings this is an indication of another problem with the system or that it is time to replace the membrane Contact Spectra Watermakers before removing a membrane Membrane Cleaning For normal cleaning the SC 3 Acid Cleaning Compound is used first then the SC 2 Alkaline Cleaning Compound If known bio fouling is present the SC 2 may be used first Using hot wa ter if possible up to 120 45C is recommended as it greatly enhances the ability of the cleaners to do their jobs If the history of the system is unknown or has been left unpickled for an extended length of time and biological growth is present it is recommended that the system is cleaned with SC 2 using an alternate source of unchlorinated fresh water before the system is run under pressure A simple test can be performed to see if biological growth has occurred Before running the sys tem remove the prefilters and examine their condition If the housings are full of smelly discol ored water the system was not properly stored Install clean prefilters if they were bad Next check the membrane Detach the brine discharge hose and lead to a bucket Open the pressure relief valve one turn and manually run the system for 30 seconds Examine the brine wa
16. of fresh water Press Start Stop when done Step 72 Use feed pump manual switch to activate pump run for 10 minutes l krezzzzzzzzntj Step 2 Remove brine discharge and replace with service hose leading to bucket Step 4 Connecta service hose to service port of FWF module lead hose to bucket and turn service valve 180 Step 5 vix sC 1 into bucke Step 8 You re done Winterizing Warning Only use potable water antifreeze Propylene Glycol Do not use automotive antifreeze Ethylene Glycol Storage and Winterizing Step 1 Flush the system twice Use the Auto Flush button on the LCD display once the first flush has been completed press Stop to cancel the 5 day interval timer then press Auto Flush again Step 2 Remove the quick disconnect fitting from the brine discharge outlet of the Clark pump and replace with a quick disconnect from your service kit fitted to a hose and lead the hose to a 5 gallon bucket Step 3 Press Auto Flush again 700 1000 systems use the flush switch on the control box to fill the bucket with fresh un chlorinated water 1 gallon 4 liters for 400 sys tems 2 gallons 8liters for 1000 systems Press Stop when the bucket has reached the desired level Step 4 Conne
17. remained closed for two minutes the watermaker will shut down and flush itself The water maker will start back up when the water level drops below the tank empty switch and it remains open for 2 minutes This configuration allows for com pletely automatic operation If the watermaker does not need to start up within five days it will automatically do a fresh water flush AutoFill mode can be ended by pushing the stop button or the Autoflush button If the watermaker is in Autorun mode it can be put into Autofill mode without stopping it by holding down the Autorun button If the owner prefers to install the automatic shutoff feature without the automatic start up option only the tank full switch is used A jumper must be placed between the tank empty terminals Float switch 2 in place of the tank empty switch because the watermaker will only shut down if both sets of terminals are closed To use this mode the watermaker must be started up with the Stop start button or the Autorun button After the unit starts up then press and hold the Autorun button until the display reads Auto Fill Mode The water maker will fill the tank and automatically enter Autoflush mode It is possible to use the autofill feature with 2 tanks A double throw electrical switch must be installed in a convenient location If only the single tank full switch is installed in each tank connect the wire From the Float Switch 1 terminal 1 to the common on the switch and
18. that are connected to the Newport Control System Systems will have Power inlet harness with terminal block Fresh water flush harness and Clark pump module harness consisting of the Rotorflow harness salinity cable and the di version valve control lead And a 75 26 M harness with connectors for the MPC 3000 con trol display Fresh water flush harness Power inlet harness ter minal block M n 75 26M harness with connectors for the MPC 3000 control display Diversion valve control feed Salinity probe cable Rotoflow harness Clark pump module harness 17 400 700 1000 AC Versions 700 1000 24V DC versions 400 700 1000 systems AC 120V 220V 240V will have an integral electrical enclosure that mates to the Newport pump module This enclosure houses the Variable Frequency motor Drive and the MPC 3000 control board The VFD serves several functions First it allows the machine to run with almost any AC frequency Regardless of the input conditions the drive will hold a constant motor speed The motor controller outputs three phase AC to the motor allowing it to run quieter and more efficiently The control will soft start the motor preventing generator sag or dimming lights This will allow the watermaker to be run on a very small generator if desired The motor control also slows the motor for the flush and maintenance procedures Pump Module Assembly With
19. 1 Dissemble fitting components Step 2 Install the Nut first then use the bevelled side of the Spacer to push the Grab Ring onto the tube no more than 1 2 Slip the O ring over the tube to hold the Spacer in place If the Grab Ring is pushed too far trim back the tube so about 1 4 of tube extends past the O ring Step 3 Gently fit the tube into the body and loosely thread on the nut Be careful not to cross thread the nut 1 2 tube should not bottom out in the fitting to allow full compression of the O ring Step 4 Hand tighten the nut DO NOT OVER TIGHTEN DO NOT USE A WRENCH The tube should not come out if pulled by hand If it does tighten the grab ring tabs 1 4 3 8 1 2 Parker Tube Fitting Assembly 15 Wiring 400 12V 24V systems Identify cables that are connected to the Newport Control System 400 Systems will have Power inlet harness with a terminal block Fresh water flush harness and Clark pump module harness consisting of the Rotoflow harness salinity cable and the diversion valve control lead And a 50 15M harness with connectors for the MPC 3000 control display Fresh water flush harness Power inlet harness with terminal block b 50 15M harness with connectors for the MPC 3000 control display gt Diversion valve control feed Connector for Rotoflow sensor Clark pump module harness 16 Wiring 700 1000 24V DC Systems Identify cables
20. 30A4 TERMINAL BLOCK 30A 4 CIRCUITS EL RL 40A12 12V CUBE RELAY EL RL 40A24 24V CUBE RELAY FM NPC TC EL SWT TGSDPDT COVER CHASSIS TOGGLE SWITCH DP DT FM NPC FC FM NPC ACB FM NPC ACC FRONT COVER N P CHASSIS NEWPORT AC NEWPORT AC BOX COVER For more information on the AC Tech drives please go to the technical section of our web site and download the Installation and Operation manual for SCL and SCM series drives 59 400 DC Models EL SWT TK1 S P S T ON OFF SWITCH FM MPC MPCB EL SWT TSBHC MPC BOX TOGGLE SWITCH B SPECTRA A EL SSR 150 SEAL PRESSURE TRANSDUCER 150 PSI EL SSR PSH PRESSURE SENSOR PL MFF 1 4X1 4 CABLE 1 4 MPT X 1 4 FPT ELBOW NYLON PL HBE 3 4X5 8 3 4 MALE NPTX5 8 HOSE BARB ELL NYL PL CLP 8SS 8 HOSE CLAMP PL MTE 3 4X1 2P 3 4 MPT X 1 2 TUBE FITTING ELBOW FT FHB 10HD PL NP 3 4N FT FTH 10H HIGH PRESS HOUSING B BRACKET DUPLEX 3 4 CLOSE NIPPLE NYLON HIGH PRESSURE FILTER HOUSING PL SLN 1 4D12VB 1 4 DIVERSION VALVE 12V W O VB PL MTE 3 8X3 8P PL SLN 1 4D24VB 1 4 DIVERSION VALVE 24V W O VB 3 8 MPT X 3 8 TUBE FITT PL CKV 1 4M F ELBOW f 1 4 PLASTIC CK VALVE M F PL MTS 1 4X3 8P SUB NP DVM 1 4 MPT X 3 8 TUBE DIVERSION VALVE FITT ST MANIFOLD PL FTS 3 8X3 8P EL MPC SP 3 8 FPT X 3 8 TUBE FITT ST SALINITY PROBE EL SSR IFM INLINE FLOW METER PL HBE 1 2X3 4 SENSOR EL MTR SPCDC 3 4HP SPEED CONTROLLER
21. AYCO PL NLT 1 2HP id 64 3 8 MPT X 3 8 TUBE FITT ST PL MTS 3 8X3 8P 3 8 NPT X 1 4 TUBE FITT ELL PL MTE 3 8X1 4 1 4 MPT X 3 8 TUBE FITTING ELBOW 1 4 3 8 1 8 FEMALE NPTX1 A TUBE FITTING gt ELL PL FTE 1 8X1 4P 1 8 NPT NIPPLE NYLON PL NP 1 8N 1 4 HEX PLUG NYLON PL HP 1 4N 3 8 MALE NPTX1 2 TUBE SS FITT ST PL MTS 3 8X1 2S MEMBRANE END PLUG FT PV EP 1 4 DIVERSION VALVE 12V W O VB PL SLN 1 4D12VB 1 4 DIVERSION VALVE 24V W O VB PL SLN 1 4D24VB 1 4 PLASTIC CK VALVE M F PL CKV 1 4M F 1 4 MALE NPTX1 4 TUBE FITTING ST 1 4 HEX PLUG NYLON PL MTS 1 4X1 4P PL HP 1 4N DIVERSION VALVE MANIFOLD SUB NP DVM SALINITY PROBE EL MPC SP 65 3 8 LOW PRESS TUBE PL NLT 3 8LP 1 4 X 3 8 TUBE FITTING ELBOW a PL MTE 1 4X3 8P 3 4NPTX1 2 HOSE BARB NYL ELL PL HBE 3 4X1 2 3 4 MPT X 3 4 HOSE BARB ELBOW PL HBE 3 4X3 4 LOW PRESSURE FILTER HOUSING FT FTH 10L GARDEN HOSE CAP PL GHF GC 3 4 MPT X 3 4 HOSE BARB ELBOW PL HBE 3 4X3 4 3 4 3 WAY VALVE PL VLV 3W3 4 FRESH WATER FLUSH MODULE BRACKET FM NPC IM 50 MICRON FILTER ELEMENT CHARCOAL FILTER FT FTC 50 FT FTC CC 3 4 NPT X 3 4 HOSE BARB ST PL HBS 3 4X3 4 STROKE SENSOR amp 1 5 CABLE EL MPC SC15 3 8 NPT QUICK DISCNT COUP 5 8 QUICK DISCNT FITT HOSE BODY BARB PL QDC BD3 8 PL QDC HB5 8 66 PL HBS 1 2X5 8 PL BSH 1 2X1 4N
22. Electrical enclosure Manual Control Switch Variable Frequency Drive VFD AC Versions DC versions have PWM Speed control MPC 3000 Controller 18 Fresh water flush harness Power inlet harness with terminal block Note AC Systems will have two terminal blocks The AC input will be thr wires with green as ground safety Ground The two wire terminal block will be the DC control power feed MP C 3000 control display cable d Diversion valve A gt control feed i Salinity probe cable a Rotoflow cable The Control module on larger units may be demounted for relocation within 4 1 2M of the pump module A long screwdriver will be required to access the fasteners 19 Wiring continued Mount the main power terminals or junction box on a bulkhead adjacent to the feed pump module Make sure that this is a dry location well above bilge level and not subject to water spray Route the control cable through the boat to the MPC display location Be careful not to dam age the connector Plug this into the back of the control Route the Clark pump harness to the high pressure pump location and install stroke sensor see photo Plug in the salinity sensor cable and install the plastic boot over the connection Locate the diversion valve wires and splice the remaining two conductor cables with the supplied butt splices These are heat shrink connectors so you can seal
23. MTE 3 8X3 8P U TUBE CONNECTOR 1 4 PRODUCT TUBE 3 8 MPT X 3 8 TUBE FITT ELBOW PL MTS 3 8NPTX1 2S 3 8 NPTX1 2 TUBE SS FITT ST PLATE BRACKET FT PV ER MEMBRANE RING FM PVB PBI PLATE BRACKET INTERMEDIATE FT PV ZEP FM PVB PBE Z BRANE END CAP A PLATE BRACKET END EL ZTG 1 2RD 8 X 1 2 O D Z ROD FT PV ER PL FTE 1 4X1 4P MEMBRANE RING 1 4 1 4 FITTING ELL FT PV ZEPB Z BRANE END CAP B PL NLT 1 2HP 1 2 HIGH PRESSURE TUBE DAYCO EL TM 1 4PPCP 1 4 CABLE CAP STUD INSULATOR BLK FT PV UTC PL NP 1 8N U TUBE CONNECTOR 1 8 NPT NIPPLE NYLON 62 PL MTE 3 8X3 8P 3 8 MPT X 3 8 TUBE FITT ELBOW PL SLN 1 4D12VB 1 4 DIVERSION VALVE 12V W O VB PL SLN 1 4D24VB 1 4 DIVERSION VALVE 24V W O VB PL CKV 1 4M F 1 4 PLASTIC CK VALVE M F PL MTS 1 4X3 8P 1 4 MPT X 3 8 TUBE FITT ST SUB NP DVM DIVERSION VALVE MANI FOLD PL MTS 1 4X1 4P PL MTE 1 4X1 4P 1 4 NPTX1 4 TUBE FITT ST 1 4 NPTX1 4 TUBE FITTING ELL PL MTE 3 8X3 8P 3 8 MPT X 3 8 TUBE FITT ELBOW PL NLT 3 8LP 3 8 LOW PRESS TUBE 63 E MPC CONTROL PANEL VFD EL MPC RMCDF HI REJECTION MEMBRANE 40 FT MB 40 3 4 16 ST X 1 2 TUBE FITT ELL SS f PL MTE 3 4SX1 2 i iy PLATE BRACKET END FM PVB PBE RUBBER MOUNT HD RBP RM 3 8 MALE NPTX5 8 HOSE BARB ELL NYL PL HBE 3 8X5 8 PLATE BRACKET FM PVB PB 1 2 HIGH PRESSURE TUBE 3 8 LOW PRESS TUBE D
24. SPECTRA WATERMACHINES NEWPORT SERIES INSTALLATION MANUAL Spectra Watermakers Inc 20 Mariposa Road San Rafael CA 94901 Phone 415 526 2780 Fax 415 526 2787 E mail spectra spectrawatermakers com www spectrawatermakers com 12 10 04 Rotoflow Thank you for your purchase of a Spectra Newport system Properly installed it will provide years of trouble free service Please pay attention to the installation instructions and the sys tem layout Like any piece of mechanical equipment the system will require inspection and service from time to time Do not place the components in inaccessible areas that will pre vent proper maintenance If you are having a dealer install the system for you review the location of the components to make sure that the installation will meet your approval upon completion Newport Installation Quick Start Important Details for Installer 1 system must have a dedicated sea water inlet to guarantee a solid flow of water to the system The inlet should be as low in the boat as possible and with a scoop type for ward facing thru hull fitting installed 2 Follow the wire gauge charts in the instructions Using larger wire than specified is ac ceptable 3 MPC control must have DC power continuously to achieve the full benefits of the fresh water flush system The domestic fresh water pressure must be on and the fresh water tank level maintained Calculate 3 gallons 12L per flush for 400
25. a soft brush and water in a bucket Occasionally lightly lube the O rings with silicone grease Oil Water Separator Optional To install oil water Removal capability remove the supplied 20 micron filter element in the duplex filter set and replace with the 20 micron oil water separator cartridge Replace this when the MPC alerts you with a Service Prefilter alarm The Charcoal Fresh Water Flush Filter e Replace the charcoal filter element at least every 6 months 38 The Membranes The membranes need to be cleaned only when they have lost up to 15 of their capacity due to fouling or the product quality degrades The leading cause of fouling is from biologi cal growth that occurs when the system is left unused without flushing or pickling Fouling from mineral scaling can happen during operation under certain sea water conditions and from rust Monitor the product salinity and feed pressure bar graphs for higher than normal readings for the conditions Other conditions can cause high pressure such as cold feed wa ter or clogged filters Low product flow is usually due to low voltage damaged feed pump or Clark pump Look for all other causes before cleaning the membrane Membrane life can be shortened by excessive cleaning e There are two types of cleaners acid and alkaline The acid cleaner SC 3 will remove min eral scaling The alkaline cleaner SC 2 is used to remove biological by products oil and dirt particles that
26. ably need to have the filters changed due to odor before they are dirty enough to restrict water flow Prefilters can be cleaned We recommend that you have three sets in service one in the unit one set soaking overnight in a bucket of clean fresh or salt water and one set drying for the next use After shutting down the unit remove the used prefilters and install the dry set Leave the housings full of air until the next use On non automated systems open the pressure relief when starting if there is a lot of air in the system until the air is cleared out through the brine overboard The filters will get just as clean when soaked in sea water but dry much faster if soaked in fresh Given gentle han dling prefilters can be reused many times Bad smelling product water is usually caused by bad smelling feed water but can also be caused by a fouled membrane if the membrane has been left unpickled If the unit makes smelly but not salty water after a long idle period and the prefilters are new the smell can be eliminated by running the unit unpressurized for an hour or so to flush the membrane Odors in the product water can also be eliminated by adding a charcoal filter in the product water line Spectra offers a product water filter kit p n KIT FLT CC More on this subject is available on our website at www spectrawatermakers com 8 17 04 52 4 FRESH WATER FLUSH The purpose of the fresh water flush is to replace the sea water in t
27. allons 6 liters per minute Fill a bucket with fresh water and mix in a couple squirts of the detergent Run the system depressurized with the watermaker drawing water from the bucket and discharging over board When about half the water is gone from the bucket stop the unit and let the mem brane soak for a few minutes Restart and pump the remaining solution overboard Repeat until the discharge appears clean After most of the oil is cleaned out you can put the brine discharge into the bucket and run the system with the soapy water circulating as you would for the other cleaning chemicals Rinse the system with a bucket of fresh water or the fresh water flush cycle then flush for twenty minutes using sea water Pressurize and test 5 12 04 50 MPC 5 PURGE MODE BYPASS Whenever the control power 12 or 24 volt DC has been shut off the system will prompt you through the purge mode when it is turned back on This is because the only time the MPC 3000 should be turned off is after the system has been pickled Purge Mode prompts the operator to open the pressure relief and then runs seawater through the system for 20 minutes to clear away the chemicals Normally during periods of disuse the MPC 3000 will remain powered up so that it can do the five day flush cycles and no storage solution will be present If the control power has been interrupted but the system is not filled with storage solution Purge Mode can be bypassed by tapping the tw
28. an Up Remove the quick disconnect from the Clark pump brine discharge and replace the origi nal hose that leads to the thru hull You may at this point if you choose to pump the bucket dry by using the feed pump switch Stop when the bucket is empty Turn the service valve 180 back to its original position and remove the service hose 40 Salinity Probe Calibration Salinity is a measurement of TDS total dissolved solids in liquid these solids will conduct elec tricity to varying degrees A special probe is used with two electrical contacts in it to determine the resistance to the flow of electricity in the liquid In the Spectra Watermakers systems the salinity probe is located just before the diversion valve at the output of the RO membrane This way we can look at the salinity level of the product water before deciding to either reject the water or accept it and divert it into the holding tank The salinity level in parts per million can be seen either through the salinity meter in the soft ware or a jumper can be added to the MPC board in the calibrate position where it can then be seen on the LCD display rather than a bar graph After adding the jumper it may be necessary to cycle through the different LCD displays until the display reads salinity Procedure 1 Locate the Calibrate jumper location on the MPC 3000 Board Jump the terminals 2 Start the system and after the salinity stabilizes test the p
29. and the feed pump Module and as low as possible in the vessel It should be mounted with the filter housings vertical and accessible for changing filters Allow 2 below the filter housing for removal Do not install over electrical equipment Remove filter bowls for access to the screw holes in the mounting plate The unit contains a 50 Micron prefilter charcoal filter for the flush water flush solenoid and three way intake service valve Optional Z Brane The optional Z Brane Water treatment system is permanently in stalled in the membrane pressure vessels and continuously helps prevent biogrowth and fouling of the membrane system Feed Pump Main Module Mount the feed pump main module on a horizontal or vertical sur face that can be up to 4 1 2M above the waterline It is prefer able to mount as low as possible Locate in an area that allows easy access to filters and a location that will not be a problem when water spills during filter change Keep future maintenance in mind when choosing a location The MPC control box can be removed from the main feed pump module and relocated if necessary Remove front cover to access mounting holes in the enclo sure cated You may Parker tubing Filters may be relo need additional 1 2 The MPC Control Box The accumulator assembly 400 only is plumbed between the feed pump module and the Clark pump pressure vessel unit Plumb as shown with the analog
30. ant running 24 7 will get 10 to 12 years out of a set of membranes But they do all kinds of fancy chemical injections and never shut the thing off Most cruisers are lucky to get five or six years out of one You hear of the eight or ten year old membrane now and then The biggest killers of membranes are lack of use chlorine damage and improper storage Don t let membranes sit around with sea water or stale fresh water in them Biological growth will occur in the membrane Here at the factory we frequently get back membranes for inspection that reek of hydrogen sulfide rotten eggs This odor is produce by anaerobic bacteria that live in an unused membrane feeding on whatever animal or vegetable matter is trapped in it from the plankton that gets through the system Membranes badly fouled in this way can seldom be saved These bacteria are always present but are inhibited by the oxygen in sea water while the unit is in frequent use by scheduled fresh water flushes or by pickling Keeping the prefilters clean is also important in preventing bio fouling If your prefilters are allowed to become a breeding ground for bacteria get smelly the contamina tion will spread throughout the system When we cut open a failed membrane we also find mildew another form of bio fouling probably due to long term storage with no biocide or stale biocide After many hours of water making mineral deposits will form and must be dissolved away with an acid cleaner
31. assembly This needs to be active when the boat is unattended for the fresh water flush system to function properly The domestic fresh water pump must be able to deliver 2 5 gallons per minute at 25 PSI Connect the wiring harness and heat shrink butt splices N 13 Product Water tubing 400 700 1000 Systems Product water tubing is 1 4 6 3mm parker tubing on the 400 3 8 9 5mm on the 7700 1000 models See the Parker tube fitting assembly diagram next page Product water is pre plumbed from the membrane into the electric diversion valve The diversion valve will dump product water into the overboard brine stream until good quality is measured by the MPC 3000 control Product water is then diverted into the fresh water tank You will need to route the product water from the valve into the top of the tank Install a tee in the water fill or tap a pipe thread into an inspection port in the top of the tank Do not feed the water into a manifold or bottom of the tank Make sure there is no re striction in this plumbing Product water to tank Diversion Valve Solenoid Salinity probe and rotoflow assembly Brine Discharge Route the Brine discharge from the quick disconnect fitting to location above the waterline using the supplied 5 8 15 9MM hose 14 Parker Tube Fitting Assembly Procedure Spacer Single grab ring for 1 4 amp 3 8 tube O ring Use 2 grab rings for 1 2 tube Nut Tubing Step
32. be com patible with the modern engineering plastics and composites in the Spectra pumps Do not use any substitute except propylene Glycol SC 1 Storage Compound has to be mixed at a ratio of 1 Spectra container to 3 gallons 12L of fresh water to have the proper solution An average of 2 gallons 8L of water is in a 400 system or 4 gallons 16L in a 1000 sys tem This water has to be figured in to the mixture A 400 system uses one SC 1 container A 700 1000 system uses two containers Do not be concerned if the powder does not go completely into solution Caution Avoid contact with skin eyes or lungs with the storage chemical va Aare d am s inp as TERES id SW eter La ka irre ri As sansa for ainsi prosit 34 Storage Procedure Clean Up Step 1 Flush the system twice Use the Auto Flush button on the LCD display once the first flush has been completed press Stop to cancel the 5 day interval timer then press Auto Flush again Step 2 Remove the quick disconnect fitting from the brine discharge outlet of the Clark pump and replace with a quick disconnect from your service kit fitted to a hose and lead the hose to a 5 gallon bucket Step 3 Press Auto Flush again to fill the bucket with fresh unchlorinated water 1 gallon for 400 systems 2 gallons for 700 1000 systems Press Stop when the bucket has reached the desired level 700 1000
33. ct a hose using the garden hose barb fitting from your service kit to the service port of the fresh water flush module Lead the hose into the bucket Turn the service valve on the fresh water flush module 180 so the intake 15 now coming from the bucket Step 5 Mix the propylene glycol into the water in the bucket Follow the instructions on container Step 6 Make sure the pressure relief valve on the Clark pump is open unpressurized Step 7 Use the Feed Pump Manual switch on the MPC control box 700 100 sys tems use the service switch to turn on the feed pump Circulate the storage chemical in the system for approximately 10 minutes Turn off the switch when finished Step 8 Disconnect the product water tubing and use compressed air to blow any resid ual water out of the lines to prevent freeze damage Step 9 Turn off the power to the entire system Clean Up Remove the quick disconnect from the Clark pump brine discharge and replace the original hose that leads to the thru hull You may at this point if you choose to pump the bucket dry by using the feed pump switch Stop when the bucket is empty Turn the service valve 180 back to its original position and remove the service hose 37 Maintenance General Periodically inspect the entire system for leakage and chafe on the tubing and hoses Repair any leaks you find as soon as practical Some crystal formation around the Clark pump blocks is normal Wi
34. d Insert tube 0 9 until it stops IMPORTANT Hold fitting body with 13 16 wrench when tightening Spectra Watermakers Newport Troubleshooting Procedures SYMPTOMS PROBABLE CAUSE REMEDY Feed pump runs constantly will not turn off Manual override switches in on position Turn off manual switch on control box Feed pump runs with loud noise Intake blocked Air in system Check thru hull valve Check sea strainer for leaks Check FWF module for leaks Re prime system restart No lights or display system does not operate Remote display not connected No power to control box Check display cable connec tions at back of display and at control box Check and reset main DC supply breaker Check for voltage 12 or 24vDC at control box power input studs Try manual bypass switches if pumps run then control or display is defective Pumps run intermittently cycling on off System operating in flush mode DC models System will time out or manually stop with the Start Stop button Display activates but pump will not run loose or broken pump wire connection bad pump relay blown F3 or F5 fuse on MPC tanks are full Check wiring at terminal block inside MPC Test power relay replace Replace fuse mini automo tive type ATM Check tanks system cannot be started if tanks are full System runs no product water
35. delivered to water tanks GHP bar graph shows OK Good LED activated diversion valve inoperative wiring fault disconnected or broken product tubing diversion valve plunger Check wiring at diversion valve and inside control box Check product tubing Disassemble and clean diverion valve plunger or re place valve contact factory System runs no product water delivered to water tanks GPH bar graph shows OK reject LED activated high salinity of product water causing system to reject water salinity probe out of cali bration or defective bad cable chlorine damage to mem branes pressure relief valve open Check for low feed pressure close pressure relief valve Check for leaks at high pres sure hoses Test product water with hand held tester if over 500 for 1 hour contact factory Close Valve 47 Spectra Watermakers Newport Troubleshooting Procedures SYMPTOMS Error Messages PROBABLE CAUSE REMEDY System stalled system stalled may alarm when using the control panel to run system for servicing with the pressure relief valve open use manual override switch instead pressure relief valve open intake thru hull closed airlocked system no signal from stroke sensor Close pressure relief valve Check thru hull Verify stroke sensor fully in serted in pump Check stroke sensor wiring at control box Replace stroke sensor
36. duct water inlet at the bottom outlet at the top The ballast wires plug into the end of the bulb in the lamp module The ballast RED wire connects to STER terminal on the MPC board and the bal last BLACK wire connects to the GND terminal If the wires must be extended use mini mum 16AWG wire External Buzzer s In addition to the external buzzer s installed at each remote control display panel a buzzer unit may be installed at the control box The buzzer RED wire con nects to the BUZZ terminal on the MPC board and the buzzer BLACK wire connects to GND 25 Tank Switch Installation and Operation There are two sets of terminals on the MPC 3000 PCB that can be used in four dif ferent configurations to automatically start and stop the watermaker or to automatically stop the watermaker when the tank s are full without the auto start feature These terminals are on the green ten pin connector and are labeled Float Switch 1 and Float Switch 2 Float Switch 1 is the tank full switch and Float Switch 2 is the tank empty switch If the unit is wired for both Autostart and Autostop it can be put into AutoFill Mode by pushing and holding the Auto Run switch on the MPC 3000 display In this mode the water maker will start whenever the water level drops below the tank empty switch so that it is open not conducting electricity When the tank fills up and both the tank full switch and the tank empty switch have
37. e discharge for water flow There should be no bubbles anywhere in the intake hoses and the feed pump should sound smooth after priming If the feed pump continues to sound rough find the reason before con tinuing Inspect the system for leaks Note If you must stop the purge sequence for any reason the control will default back to the beginning of the purging mode to protect your system If you wish you can bypass the purge sequence and initiate a normal start Pressing both Auto and Stop simultaneously anytime during the purge sequence will bypass the purge sequence and enable a normal start 5 After the purge sequence The control will alarm with the message Close pressure relief valve Close the valve and proceed by pressing Auto Run 6 The system is now running under pressure and making water The display will read purging product water This mode dumps the product water overboard for ten minutes in case there is any residual chemicals in the membrane Carefully inspect for leaks over the entire system Shut down the system and repair any leaks you find 7 The system is now in the operational mode You may start and run you system as you de sire You will not have to go through the purging mode unless you de power the system If you do you can bypass the purging mode by pushing Stop and Auto run buttons at the same time It is best to use the auto run button which defaults to the automatic f
38. ess tube nut firmly 43 Suggested Spares Short term cruising weekends etc We suggest a basic cruise kit Kit consists of 3 ea 50 micron 20micron and 5 micron filters and two SC 1 storage chemicals Cruising 2 to 6 months at a time Two basic cruise kits One each replacement charcoal filter One replacement feed pump head Longer than 6 months Additional filters offshore cruising kit consisting of Clark pump seals O rings tools and membrane cleaning chemicals One replacement strainer screen O ring for strainer screen O rings for filter housing Spectra Watermakers parts list Part Number SC 1 STORAGE CHEMICAL P N FT CHE SC1 SC 2 CLEANER FT CHE SC2 SC 3 CLEANER FT CHE SC3 BASIC CRUISE KIT C NEWPORT KIT BCK C 5 MIC FILTER FT FTC 5 20 MIC FILTER FT FTC 20 50 MIC FILTER FT FTC 50 CHARCOAL FILTER FT FTC CC 6 STRAINER SCREEN FT STN 6S OIL WATER FILTER FT FTC OW FEED PUMP HEAD Contact Factory with Model and Voltage 6 STRAINER O RING SO STN 6SS FILTER HOUSING O RING SO FHS 10H OFF SHORE KIT KIT OFFSH 20 MEMBRANE FT MB 20 40 MEMBRANE FT MB 40 44 Membrane Pressure Vessel Relocation Use ONLY Dayco Imperial Nylo Seal 88 NSR 1 2 tubing for high pressure connections Pay attention to the direction and flow path of the tubing before disassembly Make sure that you reinstall the tubing in the same manner Rotate the 90 degree high pressure tube fittings on the Clark pump for ideal tube runs The h
39. he Auto Run button the system will flush and then re flush every 5 days If the system was started by the Start Stop button it will do a 1 time flush The display will read 5 FULL Once one of the tank float switches opens the alarm and TANK S FULL display will cease on its own Note that if TANK S FULL is displayed the system cannot be restarted 31 Automatic Fresh Water Flush Cycle Warning Proper understanding of the Spectra flush system and the vessel s fresh water system configuration is mandatory for extended automatic flush cycles The flush cycle must not be allowed to drain all the fresh water from the vessel or damage to the vessel s systems may occur Make sure there is enough water in the fresh water supply system to supply the water maker for more than the expected time of operation in the re flush every 5 days mode The 400 requires 4 gallons 16 liters and the 700 1000 units require 6 gallons 24 liters every 5 days Make sure that the pressure water supply is on and will stay on during the flush mode If this is not possible contact your certified dealer Make sure that the pressure relief valve is closed It should be closed if the system was just used to make water The auto flush may not operate if the valve is open The power for the system must remain on during the auto flush mode Turning off the power will disable the auto flush function and damage may occur Pressing the Auto Store bu
40. he watermaker with fresh water whenever the system is not operating The Auto Flush Mode changes the fresh water every five days if the system has been idle that long The watermaker will last longer and operate better if it is always kept filled with fresh water between uses Most spectra watermakers are equipped with a fresh water flush module This module in cludes a 50 micron filter to filter out abrasive particles in the feed water that might damage the feed pump a charcoal filter to remove any chlorine in the fresh water that might damage the membrane an electrically operated valve and a check or way valve The electri cally operated solenoid valve opens during the fresh water flush allowing the boats pressur ized water system to supply water to the system The check valve prevents the fresh water from going out backwards through the sea strainer and sea cock The charcoal filter has a maximum flow rate of 1 5 gallons per minute 6lpm so the feed pump is operated at a re duced speed on some models or is cycled on and off on other models to avoid exceeding this flow rate If the ship s water system is unable to provide flush water at the required flow rate sea water will be drawn in to make up the difference This will cause the flush water to be brackish and ineffective in preserving the watermaker At initial startup the fresh water flush system should be tested by taking a sample of the brine discharge water just as the flu
41. igh pressure fittings are typically pre installed at the factory These fitting seal with an O ring and require no Teflon tape or pipe dope Loosen the backing nut rotate the fitting and reseat the backing nut Follow the high pressure tube connection instructions on the next page Connect the tubes to one of the components secure the tube runs and then trim and connect to the other component A 90 degree bend in a tube is better than a 90 degree fitting A tube when mounted should have at least one gentle bend to allow for expansion Do not connect a tube straight between hard mounted fittings When connecting the tubes to their components be sure to hold the fitting body with a wrench during the final tightening Of special note are the stainless steel tube fittings on the membrane housing seal on an O ring and should be seated all the way in Hold the fit ting with a wrench while installing the tube The fittings on the Clark pump have an O ring seal and can be re oriented by backing out the O ring Stop nut Rotate the fitting to align with the tube and tighten the nut just past hand tight Do Not over tighten 45 Spectra High Pressure Tube Fitting Assembly Use ONLY Dayco Imperial Nylo Seal 88 NSR 1 2 tubing for high pressure connections Carefully fit and measure the tubing before cutting with a sharp razor knife or hose cutter and remove any burrs Minimum tubing bend radius is 6 Route tubing away from excessive heat sources and
42. incredibly dirty domestic water in your boat About six months after installation the charcoal filter element will lose its effectiveness at removing any membrane damaging chlo rine which may be present in domestic water Charcoal filter elements must be replaced every six months if there is ANY chance that chorine could be introduced into the flush wa ter Charcoal filter elements cannot be cleaned To ensure that filter elements fit properly and remove chlorine effectively they should be purchased at factory authorized dealers Our element part number is FT FTC XX The last two digits indicate the micron rating e g FT FTC 05 is for a 5 micron element Charcoal elements are FT FTC CC 06 03 04 54 PF 2 CHARCOAL FILTERS The function of the charcoal filter element p n FT FTC CC is to remove any chlorine in the fresh water flush water supply It also removes any particulate matter The charcoal filter we use removes 99 7 of the chlorine Beware when buying other charcoal filters If they don t specify the percentage of chlorine removed don t use them The cheap ones in most cases will only remove 60 or 7096 Also there are aftermarket filters which are very close to but not exactly the same dimensions that will not seal properly in the housing The membrane can only handle small amounts of chlorine for short periods without damage The chlorine will damage the bonding agent in the membrane in a very short time So if you skimp on the char
43. ine outlet You will have to bypass the diversion valve with the parker tubing Remove check valve Connect Product Di fitting S and reconnect the Brine tube Po valve to the check valve as shown Activate manual switch 33 Long Term Storage Procedures Watermakers are best run continuously When not in use biological growth in the membrane is the leading cause of membrane fouling A warm environment will cause more growth than a cold environment The auto fresh water flush system will greatly reduce biological growth but may not stop it completely in certain conditions The 5 day re flush feature allows the system to be shut down without any service procedures for extended periods of time but it doesn t re place performing a storage procedure for long periods of non use If an optional Zeta Guard water treatment system is installed in the system the 5 day re flush will maintain the system as long as unchlorinated pressurized fresh water is provided System Storage or Pickling If the system is to be left unused for more than 2 weeks perform the following storage pro cedure The procedure introduces a chemical compound into the system that prevents bio logical growth This procedure requires de chlorinated water which can be made with the Spectra s charcoal filter Charcoal filters last a maximum of 6 months once wetted Spectra SC 1 a special storage compound used by the US Navy It is formulated to
44. itute a different type of cable Contact the factory if you need longer or additional cables Each remote control display panel can accommodate an external alarm buzzer to provide audible alerts in the event of a fault or at the end of certain timed cycles Use only the buzzer units supplied by Spectra Watermakers as current on the LCD buzzer terminal is limited to 20 mA any excessive load may damage the controller or remote display panel Connect the buzzer RED wire to the terminal marked POSITIVE connect the buzzer BLACK wire to the terminal marked NEGATIVE on the back of the remote display panel A buzzer may also be installed at the control box current limit is 150mA MPC 3000 REMOTE PANEL BACK SIDE This buzzer output terminal is 20mA MAX current limit DO NOT CONNECT POWER TO THESE TERMINALS L CONAECT TO BOARD 23 Pressure Sensors The pressure sensors mount on the filter housings to monitor system pressure and A differential pressure across the filters art If the wire leads for the sensors must be extended you must use a minimum 18AWG 3 conductor twisted and shielded marine grade wire Make both sensor wires close to the same length Make a waterproof soldered splice connection to the new wire and seal the splice in waterproof heat shrink tubing Rotoflow Sensor The Rotoflow sensor measures the fresh product flow and sends a pulsed signal to the MPC 3000 control If no
45. k pump The outlet of the filter assembly on the main module to the Clark pump assembly is under pressure Use the supplied braided clear vinyl hose rated to 150 PSI 11 bar HOSE From the inlet thru hull to the flush module and from the flush module to the pump module inlet A i use the supplied clear 3 4 19mm spiral suc tion rated hose C 11 700 1000 System Piping Specification From the Clark pump brine discharge quick connec tor to the overboard thru hull use the supplied 5 8 15 9mm clear braided vinyl hose Note 700 1000 systems use Spectra high pressure tubing with stainless fittings See page 45 for assembly instructions mrar s u m u x m 2 3 T T F 0 lt am s TE HILI LLL TII ee ee ee d d A From the inlet thru hull to the flush module and from the flush module to pump module inlet use the supplied clear 3 4 19mm spiral suc tion rated hose 12 Note When plumbing the Newport Pump Module route the feed water so that the front cover may be opened without removing the hose or tubing Fresh Water Flush Run a feed line from the domestic cold pressure water system to the 1 2 hose barb on the fresh water flush
46. nd 28V DC Note There is no reason to open the transformer enclosure Do not ser vice this unit without disconnecting the power source There may be high voltage present It is recommended that the Z Brane be connected to a discreet continuous power source The power must be on during the time that the system is operation and during the time the Z Brane is used for membrane storage If the power is obtained from the MPC then the MPC must be powered up at all times during storage This may not be desirable Fuse the power at the source with a 5 amp fuse or circuit breaker Red is Positive Black is Ground Z Brane Power Harness 57 Operation During normal operation the Red LED should be on Power needs to be supplied to the Z Brane unit at all times that you wish to have the biofouling and scale protection We recom mend that your watermaker be flushed after each use not only to protect the membrane but to prevent corrosion in the feed water system To achieve full effectiveness thoroughly fresh water flush the watermaker several times before leaving the vessel The Z Brane may be de powered if the system is stored with chemicals or winterized with Glycol Power on LED High Voltage connector DO NOT DISCONNECT OR SPLICE ANY OF THE HIGH VOLTAGE WIRING Contact the factory if modifications are required 58 EL MTR SPCAC110 3 4 SPEED CONTROLLER AC 110 EL MTR SPCAC220 3 4 SPEED CONTROLLER AC 220 EL TM
47. o left hand buttons at the same time until the display reads PURGE MODE BYPASSED The buttons must be pushed at exactly the same time You can t hold one down and then push the other From Purge Mode By passed you can run the system in any mode 4 20 04 1 WINTERIZING OR PICKLING W ANTIFREEZE WARNING Use only propylene glycol based drinking water system antifreeze Do not use ethylene glycol based automotive antifreeze which is toxic Propylene glycol can be used instead of Spectra SC 1 storage chemical for storage in any climate up to one year following this procedure Replace the prefilters with clean ones Flush the system with fresh water until the brine discharge water is below 1000 ppm or until the brine discharge does not taste salty 3 Setup the system for pickling according to the directions for your model 4 Place enough antifreeze in a bucket to fill your system This will be about two gallons for a 150 or 200 model three gallons for a 380 or 400 and larger systems will take more 5 Run the system DEPRESSURIZED with the feed pump drawing from the bucket and the brine discharging overboard until the colored antifreeze solution begins to appear at the brine discharge then switch the brine discharge into the bucket and recycle the remaining solution until the glycol and water are completely mixed about ten minutes On some models you will have to shut down the unit to switch the brine discharge into the bucket 6 The prod
48. ort 400 24V Meters AWG SQ MM 10 3 12 4 15 4 5 10 6 20 6 1 8 10 25 7 6 8 10 30 9 4 8 10 35 10 6 6 16 40 12 6 16 45 14 6 16 50 15 4 25 Newport 7000 1000 Meters AWG SQ MM 10 3 10 6 15 4 5 10 6 20 6 1 8 10 25 7 6 6 16 30 9 4 6 16 35 10 6 4 25 40 12 4 25 45 14 4 25 50 15 4 25 21 110 Volt AC System Motor Wiring Wire Length AWG wire size To 25 feet 12 awg 7 5M 25 feet to 50 feet 10 awg 7 5M to 15M 50 feet to 75 feet 8 awg 15M to 23M 220 Volt AC System Motor Wiring Wire Length AWG wire size To 25 feet 14 awg 7 5 25 feet to 50 feet 12 awg 7 5M to 15M 50 feet to 75 feet 10 awg 15M to 23 Wire length for a pair of wires is measured from source circuit breaker to control box Square MM wire size 3 sq mm 5 sq mm 8 sq mm Square MM wire size 2 sq 3 sq mm 5 sq mm 22 MPC Remote Control Display Panels There are currently two types of display options available Liquid Crystal Diode LCD display which is dark lettering on a backlit background or Vacuum Florescent Display VFD which are bright characters on a dark background The VFD demands more power from the MPC controller The displays must be mounted in a protected location out of direct sunlight and away from spray or dripping water Commands to the system can be entered at any panel The display panels connect with the supplied 50 foot modular type cable to the MPC board sockets marked DISPLAYS Do not subst
49. ot stripe to minimize water lift Double clamp all hose connections below the waterline Pipe Fitting Instruction Plastic to plastic fittings should have 3 to 4 wraps of Teflon tape and will thread almost all the way in Avoid getting dirt or debris into the piping or hoses during assembly A small bit of de bris can stop the system Avoid getting tape over the end of fittings that might get into the system To insure this does not happen leave the very first thread uncoated Avoid restrictions or long runs on the entire inlet side of the plumbing from the thru hull to the main feed pump module Prevent tight bends and excessive elbows Any restrictions will hamper system performance Secure the piping away from moving objects such as engine belts and hatches Prevent chafe on the tubing as required Test and inspect all piping and hose clamps after several hours of operation Wiring Pay attention to wire size or system performance will be impaired Perform wiring to UL ABYC CE or applicable standards Component Placement l Refer to the Plumbing Diagrams Strainer Mount the strainer in an accessible area close to the intake through hull that can handle water spillage during service Extra care during assemblv must be taken to avoid air leaks from the strainer Use the supplied Block and wire tie for mounting Fresh Water Flush Module The fresh water flush module should be located between the intake strainer
50. pe down any salt encrusted areas with a damp cloth The Seawater Strainer and 50 Micron Filter e The sea water strainer s stainless steel element should be inspected removed and cleaned as needed A clogged strainer or 50 Micron filter will cause the MPC control to alarm Check Sea Strainer Be careful to ensure that the thru hull is closed before disassembly and the seal and element are in place before reassembly Put the screen up to a light for inspection When the system is put into storage remove rinse and reassemble dry to impede corrosion Check frequently during operation The 50 micron filter needs to be properly maintained to protect the feed pump Only use Spectra approved filters These may be cleaned several times before discarding The Prefilters e Service the prefilters as soon as possible after the first prefilter alarm sounds When the second alarm sounds the system will shut down to prevent damage If cleaning and re using filter elements clean when the first segment appears on the filter condition bar graph on the LCD display e service the filters shut off the thru hull open the housings discard the old filters Clean out the housing bowls reassemble the housings with new 20 and 5 micron filter elements The 5 micron filter goes downstream from the 20 micron Leave dry until next startup e Use only Spectra approved filters or you may void your warranty The filters may be cleaned several times with
51. pressure gauge in one port The pressure is preset at the factory so no adjust ment is necessary Clark Pump Membrane Module The Clark pump membrane module comes complete with a mounting system Be sure to use the supplied washers on the rubber feet Use it as a template for drilling the mount holes Mount in any position but leave access to the pressure relief valve on the Clark pump Install in an area that maintains a temperature below 120F 50C A cool location is preferable Keep this unit within the 15 4 5M reach of the wires from main feed pump module This unit may be placed as high in the boat as you desire Make sure that the area around and under the pump does not have any water sensitive equipment Water will be spilled during any repairs or if a leak occurs Membrane Pressure Vessel Mounting The Clark pump and membrane assembly has been pre assembled at the factory If it is nec essary to disassemble this module and mount the pressure vessel remotely use guidelines in back of the manual Use only approved tubing for assembly Remote Control Panel The remote control panel can be mounted anywhere that s dry and convenient Cut a 4 9 16 116 mm wide by 2 7 8 68mm high opening for the panel Locate in an area that is easily visible and easy to manipulate the buttons Use only Spectra approved remote cable The cable is not standard LAN cable or phone cord Plumbing 400 Systems From the inlet thru hull
52. resh water rinse If you shut down the system from the stop button then use the auto store but ton to effect a fresh water flush cycle 8 Check that the system is operating within its normal parameters Compare with the chart on the next page Product Flow 400 Will produce 15 16 5 GPH 60 65 LPH 700 will produce 29 30 GPH 115 120 LPH 1000 will produce 33 40 GPH 155 160 LPH NOTE To toggle between GPH and Liters push and hold Alarm Disp Salinity Salinity reads in parts per million Sys tem rejects water higher than 750 PPM Anything below 500 is excellent Feedwater Pressure 400 Pressure range 100 125 PSI 7 9 BAR 700 Pressure range 150 180 PSI 10 13 BAR 1000 Pressure range 180 215 PSI 13 16 BAR Pressure will be higher in cold water and lower in warm water Filter Condition Clean filters on first alarm as soon as convenient On second alarm filters will need to be replaced 29 Dry Testing With Artificial Ocean If it is not possible to test run the system with the boat in the water testing may be accomplished with an artificial ocean Purchase enough aquarium salts to make 5 gallons 20 liters of salt water Make sure that the domestic water system is powered up and that there is water in the tank Confirm that the Charcoal filter 15 installed in the Fresh water flush module and that the domestic water line had been installed and all valves are open 1 Open Pressure Relief Valve Po
53. roduct water with a calibrated hand held tester 3 Locate the MPC calibration trimmer potentiometer on the board below the salinity probe jack Adjust until the display PPM matches the PPM reading from the hand held salinity monitor Turning the trim pot clockwise will lower the salinity reading and counter clockwise will raise it 4 Shut the system down and disconnect the jumper on the MPC board If a hand held meter is not available you can remove the probe and dip it into a known calibrated solution This can be obtained from Spectra MPC 3099 CALIBRATION ADJUSTMENT CALIBRATION JE MER 41 Vane Pump Replacement Remove the front cover of the pump control module Leave filters attached Loosen nut on the black plastic tube Loosen the V band clam until pump head can be removed 42 Loosen the hose clamp on the inlet hose Drop the pump down and remove the coupling tang Remove the inlet hose by rotating the pump counterclockwise To Reinstall open the band clamp all the way Make sure the coupling tang is in place Tang ends may be different width Mate the pump flange to the motor flange Hold the pump firmly against the flange while lining up the clamp Squeeze the clamp over both flanges and hold the pump in place while you tighten the clamp screw The Plastic tube nut 400 systems should be just past hand tight Do not over tighten On 700 1000 systems use two wrenches to tighten the stainl
54. rts are listed on the cellophane bags pick list We will not be held responsible for shortages and or freight damage that are not reported within thirty days of the ship date Next study the system layout diagram component photos and descriptions before beginning your installation This will assist you in understanding the function of each component Layout the system Before starting the installation identify the location where each module and component will be placed Insure that there is proper clearance around the components for removal of filters and system service Also check to make sure you have adequate tubing and hose before starting so additional parts may be ordered Check to see that the MPC cable is long enough to reach from the display location to the main module Newport 400 DC shipping list Newport Feed Pump Module High Pressure Clark Pump and Reverse Osmosis Membrane Module Newport Fresh Water Flush Module Newport Installation Kit 400 e Newport Service Kit 5 8 Hose 25 3 4 Suction Hose 25 Newport 400 AC shipping list Newport Feed Pump Module High Pressure Clark Pump and Reverse Osmosis Membrane Module Newport Fresh Water Flush Module Newport Installation Kit 400 Newport Service Kit 5 8 Hose 25 3 4 Suction Hose 25 50 Micron Filter Kit Newport 700 DC shipping list Newport Feed Pump Module High Pressure Clark Pump and Reverse Osmosis Membrane Mod
55. sh cycle is ending This water should not taste salty and should read less than 1000 ppm on a digital tds meter The flush cycle can also be tested by closing the sea cock during the flush cycle If the MPC 3000 display gives a CK SEA STRAINER alarm this means that the fresh water supply is insufficient Because the pre filters trap the plankton in the feed water they can be subject to going an aerobic or starting to smell like rotten eggs as the trapped plankton decay For this reason it is advisable to always put in clean elements if the unit is going to be left on Auto Flush Mode In daily or regular use the fresh water flush after each shutdown will help prevent this problem but in excessively warm or fertile waters the pre filters will need regular atten tion 7 26 04 53 PREFILTERS VANE PUMP SYSTEMS Five different filters are used on these Spectra Watermakers to make sure that no damaging foreign materials enter the system There are four filters in the system to clean the feed wa ter of abrasive materials while the system is in operation and a fifth filter that prevents the entrance of chlorine during fresh water flushing During normal operation the feed water is filtered in two stages First it enters a fine mesh metal sea strainer then passes through a fifty micron pleated cellulose filter These protect the vane pump from damage due to abrasion from silt and hard shelled plankton found in the feed water After pas
56. sing through the pump the feed water enters the filter housings contain ing 20 and 5 micron elements These filters remove very fine particles which could damage the Clark pump and which would shorten membrane life Cleaning schedules will vary widely depending on how and where the system is used If large amounts of feed water are run through the system in a relatively short period in bio logically fertile near shore waters the prefilters will plug up the pressure drop across the filters will rise product production and quality will drop and the system will sense plugged filters and give a service prefilters or check strainer alarm if so equipped Plugged filters can be cleaned several times by soaking in a bucket towing behind the boat at moderate speeds or hosing them off When operated only an hour or two a day in inland or near shore waters the trapped plank ton will begin to decay in the filters long before the elements plug up and the bacteria in volved in the decay will cause a rotten egg smell in the product water This decay will set in overnight in tropical waters or after a week or two in high latitudes If handled gently and changed regularly before they get too smelly filters in this service can last through doz ens of cleanings In crystal clear blue water conditions the filters may need to be cleaned much less frequently The charcoal filter used in the fresh water flush system will not plug up unless you have some
57. systems and 5 gallons 20L for 700 and 1000 systems 4 MPC 3000 control must be de powered DC power off after the system is put in storage pickled where a storage chemical or antifreeze is run through the system 5 If you are separating the Clark pump membrane assembly please review the high pres sure tube assembly instructions Improper assembly will cause failure 6 Run test then sea trial the complete system before assuming the system is opera tional If the boat is in fresh or dirty water see Dry testing the system 7 Spectra dealers are responsible for educating the vessel owners on the operation and maintenance of the system We request that you walk through the installation with our customer 8 Please have the owner fill out the warranty card The warranty is void if it is not regis tered Table of Contents Installation Page Number Getting SIarteduy m tate a leg ha Qa nahh f 4 Newport 5 EVA PN D ta 6 Tnstallati reBasiCs et sts oi eee A ee EE 7 Component Placements Tenar n n dade A D Sut e E a 8 PIUmDIng 2 10 Parker Tube Fitting Assembly Procedure a 15 Wille Qan edi oeste b aaa 16 MPC Tank Switch Wiring and operation
58. ter if it s discolored and smells bad perform an SC 2 cleaning with an alternate source of unchlori nated water before running the system pressurized If the brine is fairly clean the system can be purged run normally and checked for performance Clean the membranes only if performance is reduced Heating the water is preferable One way to do this is to find a camp stove and use a large stainless steel pot to heat the solution in The cleaning solution throughout the system will heat as it circulates in and out of the pot An alternative 15 to heat the one or two gallons of initial water to 120 on the main stove before mixing in the cleaner and circulating it into the system Periodi cally stop and reheat the solution Perform the cleaning procedures while the ship is in acceptable sea water for purging and testing 39 Note Procedures are the same for the SC 2 and SC 3 cleaners Warning The pressure relief valve on the Clark pump must be open for this procedure or membrane damage may result Maximum pressure 50 psi A Spectra Cleaning Compound SC 2 or SC 3 must be mixed with fresh water at a ratio of 1 con tainer of compound to 3 gallons 12L of unchlorinated water to have the proper solution An aver age of two gallons 8L of water is already present inside a 400 system or 4 gallons 16L in a 1000 system This water has to be figured into the mixture A 400 system will use 1 container of com pound a 1000 system will use 2 SC
59. them after splicing Route the single two conductor harnesses to the fresh water flush module and splice the wires to the solenoid wires Heat the splice for sealing Check the wire size chart to select the proper size power feed to the main power harness DC power feeds should be uninterruptible so as not to lose the microprocessors memory during storage cycle Avoid house breaker panels that could be easily tripped DC Systems 400 Systems e 2V Use a 35Amp breaker and size the wiring for 26Amperes e 24V use 15 Amp breaker and size the circuit for 13Amperes Provide circuit protection at the source Inadequate wiring will cause a loss of system performance DC power should be uninterruptible 700 1000 Systems e Install a 30A mp breaker at source and size the wiring for 25Amperes Provide circuit protection at the source Inadequate wiring will cause a loss of system per formance DC power should be uninterruptible Note If the specified circuit breaker sizes are unavailable use the next higher rating but do not exceed the specification by more then 10 wiring to be done to applicable ABYC Marine UL or CE standards 20 Wire length for a pair of wires is measured from Newport 400 12V DC System Wiring source circuit breaker or fuse to control terminal block Wire Length FT Meters AWG SQ MM 10 3 10 6 15 4 5 8 10 20 6 1 6 16 25 7 6 4 25 30 9 4 4 25 35 10 6 4 25 40 12 2 35 45 14 2 35 50 15 2 35 Newp
60. to flush module and from flush module to pump module inlet use supplied clear 3 4 19mm spiral suction rated hose The outlet of the filter assembly on the main module to the Clark pump assembly is under pressure Use the supplied braided clear vinyl hose rated to 150 PSI 11 bar Install the supplied accumulator and gauge between the filter and the Clark pump per photos From Clark pump brine discharge connector use sup plied 5 8 15 9mm clear braided vinyl hose Route all hoses and tubes to prevent kinks and restrictions Se cure piping away from moving objects such as engine belts and hatches Prevent chafe on tubing as required Test and inspect all piping and hose clamps after several hours of operation 700 1000 Systems From the inlet thru hull to the flush module and from flush module to the pump module inlet use the supplied clear 3 4 19mm spiral suction rated hose The outlet of the filter as sembly on the main module to the Clark pump assembly is under a pressure of 200 PSI 14 5 bar Use the supplied 1 2 12 7mm tubing Follow the HP tube assembly instruc tions p 47 From the Clark pump brine discharge quick disconnect fitting use the sup plied 5 8 15 9mm clear braided vinyl hose 10 400 Systems Piping Specification From the Clark pump brine discharge connector use the supplied 5 8 15 9mm braided vinyl hose Install the supplied accumulator and gauge between the filter assembly and Clar
61. tton will engage a flush and then the 5 day flush cycle The flush pump starts and the flush water solenoid opens for 5 7 minutes and then shuts down the display reads FRESH WATER FLUSH with a countdown timer and then will read FLUSH TIMER INTERVAL and the countdown timer will reflect the num ber of hours until the next flush Pressing and holding the Auto Store button for 3 seconds will engage a 1 time flush The system flushes as described above but will not re flush every 5 days Display will read FRESH WATER FLUSH with a countdown timer then the default display when fin ished Pressing the Stop button will cancel the auto flush mode Emergency Operation In the event of an MPC control failure the system may be operated manually using the manual feed switch on the MPC control box e For manual start up switch on the feed pump using the feed pump switch Shut the unit down if the Clark pump does not cycle Shut down if air 15 continuously present in the intake line or if the feed pump is excessively noisy The automatic safety controls are disabled in manual mode Always discard the product water for the first few minutes of operation The initial prod uct water from the system may not be potable Taste the product water before sending to a tank In manual operation the salinity control is inoperative Product water is available either directly from the membrane product water out or at the diversion valve br
62. uct water side of the system will not contain antifreeze and should be protected from freezing by blowing or draining it dry if necessary 7 Turn off power to the system leaving the pressure relief valve open 2 turn N 5 25 04 51 OP 2 BAD SMELLING PRODUCT WATER The reverse osmosis membrane is permeable by many gases including hydrogen sulfide the gas that causes rotten eggs to smell the way they do If there are bad odors in the feed water they will go through the membrane and the product water will be affected Usually the source of the odor is from the decay of planktonic creatures trapped in the sea strainer and prefilters These tiny oxygen loving creatures soon suffocate and die inside the prefilter housings when the unit is shut down Once all the available oxygen is consumed anaerobic bacteria begin to grow causing the odor If a unit being used frequently begins to make smelly water it will be the prefilters that are the source of the problem This occurs in a week or two in cold climates but in less than one night in very warm waters like the Sea of Cortes or Red Sea These bacteria can spread throughout the watermaker and begin to grow on the membrane causing poor water quality and high feed pressures Filling the system with fresh water after every use greatly slows this process allowing the automated spectra units to operate with less frequent prefilter changes but units operated for only an hour or so a day will prob
63. ule Newport Fresh Water Flush Module Newport Installation Kit k Newport Service Kit 1 2 High Pressure Tube 10 3 8 Low Pressure Tube 15 5 8 Hose 25 3 4 Suction Hose 25 Newport 700 AC shipping list Newport Feed Pump Module High Pressure Clark Pump and Reverse Osmosis Membrane Module Newport Fresh Water Flush Module Newport Installation Kit k Newport Service Kit 1 2 High Pressure Tube 10 3 8 Low Pressure Tube 15 5 8 Hose 25 3 4 Suction Hose 25 Newport 1000 DC shipping list Newport Feed Pump Module High Pressure Clark Pump and Reverse Osmosis Membrane Module Newport Fresh Water Flush Module Newport Installation Kit k Newport Service Kit 1 2 High Pressure Tube 10 3 8 Low Pressure Tube 15 5 8 Hose 25 3 4 Suction Hose 25 Newport 1000 AC shipping list Newport Feed Pump Module High Pressure Clark Pump and Reverse Osmosis Membrane Module Newport Fresh Water Flush Module Newport Installation Kit k Newport Service Kit 1 2 High Pressure Tube 10 3 8 Low Pressure Tube 15 5 8 Hose 25 3 4 Suction Hose 25 ju i afj Ceres ewe oppssod P jap aeg rq A ad doors e Sep e Im z UI P TEE s s k eee xem EIDEM oes x ii E IEEE Ses I aur Ere nacer eee em aes zem pls
64. wer up the control system 3 Press both Auto Run and Stop to bypass the purge sequence If the motor starts stop imme diately and press the Auto run and stop button again until you get a message PURGE MODE BYPASSED 4 Press the Auto Store button and allow the fresh water flush system to cycle through its timed op eration Cycle the auto store system 5 more times to purge all of the storage chemicals out of the system 5 Hook up your service hoses per the service diagram and photos Route them into a 5 gallon 20 Liter bucket Disconnect the product tube from the diversion valve and using another short piece of tube route the product water feed into the test bucket Turn the valve on the fresh water flush module from Run to Service 7 Press auto flush one or two more times to get enough water into the bucket to properly mix your salt water Mix the salt until it goes into solution If you are using a hydrometer mix the water to be 34 000 PPM Close the pressure relief valve and start the system using the Auto Run But ton 8 Run and test the system for as long as possible During the run test carefully inspect for leaks Check all of the system parameters to make sure the system is operating correctly Do not allow the water in the bucket to get above 120F 50C 9 Store the system per the Storage instructions D Outlet Service Port 2 j
Download Pdf Manuals
Related Search
Related Contents
Guida dell`utente - Sena Technologies, Inc. User Guide CompAfpToIpds Informations- und Datenblatt der Umwelteigenschaften gemäß den Echo PPT-230 User's Manual SAMSUNG - Intelware Le téléphone mobile grandes touches Mode d`emploi RayBio C-Series Human Stem Cell Array C1 TRACe-V304-TR Datasheet 取扱説明書 (3.69 MB/PDF) Copyright © All rights reserved.
Failed to retrieve file