image

Contents

1. 1 position switch A single position retractive switch controls both channels together together 1 position switch Two single position retractive switches controlling the channels separately x separate 11 Technical data Dimensions Weight Supply Voltage Frequency Circuit protection Maximum Load Power consumption Dimming output Terminal Capacity Temperature Humidity Material casing Type IP rating Compliance EBDHS DD LT30 88mm See diagrams opposite 0 2kg complete unit 230VAC 10 50Hz 10A Channel 1 switching 10A of lighting and or ventilation including incandescent fluorescent compact fluorescent low voltage by switching the primary of transformer Channel 2 dimming Maximum number of DSI or DALI ballasts is 10 unless the relay is disabled then it is 20 On 800mW Off 299mW DBB Basic insulation only Although low voltage this is not an SELV output and should be treated as if mains potential Use mains rated wiring 2 5mm 30 C to 35 C 5 to 95 non condensing Flame retardant ABS and PC ABS Class 2 40 without gasket 65 with gasket EMC 2004 108 EC C LVD 2006 95 EC Part numbers 76mm 50mm 60mm UK and international patents applied for Part number Complete detector EBDHS DD LT30 Description Accessories DBB Surface mounting box UHS5 Programming IR handset UNLCDHS Universal LCD IR handset IMPORTANT NOTICE This
2. Configured to absence detection Press and release up switch to turn on Maintains illuminance dimming channel only Press and release down switch to turn off Press and hold up switch to dim up press and hold down switch to dim down Turns off after occupancy Channel 1 does not operate with switch Channel mode Set to Switch and dim separate Switch mode Set to 2 position switch separate PLEASE NOTE THAT THE DIMMING SIGNAL IS USED TO SWITCH THE DIMMING LUMINAIRE ON OFF AND THEREFORE THE 240V FEED TO THE LUMINAIRE FITTING O E DIMMING Py MUSI COME FROM THE wy Barrast HZS LUMINAIRE NON DIMMING DIMMING LUMINAIRE DSI or DALI NEUTRAL LIVE O gt lt D EXTERNAL CIRCUIT PROTECTION 10A CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING Optional for presence mandatory for absence detection PLEASE NOTE THAT THE CENTRE BIASED RETRACTIVE SWITCH WILL PROVIDE CONTROL FOR THE DIMMING LUMAIRE S ONLY THE NON DIMMING LUMINAIRE S WILL BE CONTROLLED ONLY BY THE SENSOR sia tate Ke LETS LE ULEA Col Single channel switching Functions Switches channel 1 only with occupancy optional override switch No dimming output Configured to presence detection Turns on automatically with occupancy Press and release down switch to turn off Press and release up switch to turn back on Turns off after occupancy Configured to absence detection Press and release up switch to turn on Press and release down swi
3. Choosing a Suitable Location The EBDHS DD LT30 is designed to be ceiling mounted and must satisfy the following criteria Avoid positioning the unit where direct sunlight may enter the sensor element Do not site the sensor within 1m of any lighting forced air heating or ventilation Do not fix the sensor to an unstable or vibrating surface Sensor functionality Detection Mode The Detection Mode for both output Channels 1 and 2 can be set to behave in Presence or Absence mode e Presence When movement is detected the load will automatically turn on When the area is no longer occupied the load will automatically switch off after an adjustable time period e Absence The load is manually switched on When the area is no longer occupied the load will automatically switch off after the adjustable time period has elapsed In either case sensitivity to movement of the PIR sensor can be adjusted using the Sensitivity parameter HINT To assist in setting the Sensitivity turn on the Walk Test LED which will flash red when movement is detected Switch Level On Off Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level parameters Brighter Lux Off Level Ambient Light Level Lux On Level Darker Occupancy detected Maintained IIluminance The detector measures the overall light level in the detection area and calculates the correct output for the luminaires to ac
4. range Direct Dim EBDHS DD LT30 Product Guide lectronIcs intelligent energy control Ceiling PIR HS presence detector DALI DSI low temperature Overview N The EBDHS DD LT30 PIR passive infrared presence detector provides automatic control of lighting loads with optional manual control The EBDHS DD LT30 is a high sensitivity PIR detector suitable for high bay applications such as warehouses and factories and where high detection sensitivity is needed Output Channel 1 comprises a mains voltage relay capable of simple on off switching while Output Channel 2 provides dimmable control of either DALI or DSI type ballasts Functioning as a presence detector the unit can turn lights on when a room is occupied and off when the room is empty Optional settings allow lights to be turned off in response to ambient daylight or to implement a maintained illuminance daylight harvesting system The flexibility of having two channels and two switch inputs allows the following example scenarios e Dim an outside row of luminaires whilst internal fittings are switched e Provide absence detection for two separate channels e Maintained illuminance system with manual up down controls All functionality is fully programmable using an IR handset Front features Mounting Bezel ie ET Sensor Lens which covers PIR Sensor IR Receiver Light Level Sensor Status LEDs Back features Ret
5. Sets a minimum light level below which the PIR sensor is enabled allowing lights Switch level on For a higher resolution to be turned on by movement a scale of 101 199 is Note the Lux Level Off value must always be greater than the Lux Level On value available Lux off level 1to9 Sets a maximum light level above which the PIR sensor is disabled preventing Switch level off For a higher resolution lights from being turned on by movement a scale of 101 199 is available Light Level pe to 998 999 Sets a target light level to be maintained by the lighting system V J maintained illuminance ee fasana Load Type DALI DSI Sets the ballast control protocol to DSI z DALI Sets the ballast control protocol to DALI v y DALI On DALI On provides a permanent voltage to DALI ballasts when DALI has not been x v implemented correctly in the ballast Maximum number of ballasts is 5 unless the relay is disabled then it is 10 Memorise Yes or No i this is set to Yes the last manual lux level set will be memorised and used as MEJ new switch on level oan value sa 0 to 99 Dimming output level when switched on 0 99 ape Off value 0 to 99 Dimming output level when switched off 0 99 If a non zero off value is set then the output will toggle between this value and completely off depending on the switch level on and off values For example if it is light outside the fittings will be off if there is no occupancy If it is dark outside the
6. device should be installed by a qualified electrician in accordance with the latest edition of the IEE Wiring Regulations and any applicable Building Regulations 9001 14001 Quality Environmental Management Management E energy services and technology association FM 45789 EMS 534520 Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice 12 HS PIR presence detector DD DALI DSI low temperature EN r ectronics C P Electronics Ltd Brent Crescent London NW107XR United Kingdom Tel 44 0 333 900 0671 Fax 44 0 333 900 0674 www cpelectronics co uk enquiry cpelectronics co uk Ref WD732 Issue 2
7. or to raise lights Turn lights off or to lower lights When set to On this causes a red LED to flash on the sensor when it detects movement Use this feature to check for adequate sensitivity levels Once the detector is turned on this value sets how long the lights will stay on once movement has ceased Lux level setting to prevent the luminaires being switched on if the ambient light level is sufficient adjustable between 1 and 9 The luminaires will always be switched on at level 9 Sets a target light level to be maintained by the lighting system 9 999 disabled Lux level setting to switch the luminaires off during occupancy if the ambient light level goes above the setting adjustable between 1 and 9 Level 9 will always keep the lights on This setting can be used for window row switching Note the Lux Off Level value must always be greater than the Lux On Level value Sets the ballast control protocol to be used by the output channel Sensitivity level for detecting movement 1 low sensitivity 9 high sensitivity Returns the unit to the default settings Determines how long the output will be at 100 so that lamps burn in The burn in time is not affected by power supply interruptions Presence mode allows the output to turn on when movement is detected and off when movement ceases Absence mode allows the output to turn off when movement ceases but must be manually turned on
8. 9 max Sensitivity level for detecting movement when the detector is already on UHS5 VY S sets Sensitivity On and Off to the same value Sensitivity Off 1 min to 9 max Sensitivity level for detecting movement when the detector is off UHS5 sets Vt Sensitivity On and Off to the same value Lux time 0 disabled If the detector measures the lux level and decides that the output needs switching 4 99 minutes on or off as a consequence the lux time must elapse first If at any time during the timed delay the lux change reverses then the process is cancelled Lux Time enables absence detection to be implemented with a lux off level set When the button is pressed the lights will go on regardless of ambient light level However if there is sufficient ambient light they will turn off again after the Lux Time Note that whenever the an external switch is pressed whether in absence or presence mode if the lights were out because of the lux level they will be immediately turned on again for at least the Lux Time Power Up State On or Off Select No for a 30 second delay on start up If Yes is selected there will be no delay on start up and the detector will always power up detecting Disable Detector N YorN Disables detection leaving the relay output permanently off with the dimming output operational This mode is used when the unit is for maintained illuminance only On Delay 0 minutes 0 99 minutes The On Delay to allows the first channe
9. aining Spring Dimmable Control Output Connector Channel 2 Power Input amp Switched Output Connector Channel 1 Switch Input Retaining Spring Connector PIR Sensor Detects movement within the unit s detection range allowing load control in response to changes in occupancy IR Receiver Receives control and programming commands from an IR infrared handset Light Level Sensor Measures the overall light level in the detection area Status LEDs The LED flashes Red to indicate the following viy Walk Test LED active JQ when movement is detected 7 I y lo Valid setting received Q Power Input amp Switched Output Connector Channel 1 Used to connect mains power to the unit and to connect a switched load Dimmable Control Output Connector Channel 2 Used to connect DSI DALI controllable ballasts and transformers for dimmable loads Switch Input Connector Two input terminals can be used to manually override the dimming levels and override the lights on or off Detection diagrams Range Maximum mounting height 20m Detection pattern Walk across TEN Zi Walk towards A Es OS o0 Alignment marks The sensor head has 4 alignment marks These correspond to the 4 outer passive Gaze infrared sensors No ES under the lens i Use these marks EY to align with aisles 1 SAA and corridors to b Tee ensure the best detection characteristics See example ov
10. erleaf Applications Masking The EBDHS DD LT30 includes two clip on masking shields to allow for precise masking of the detection shape The masks can be easily shaped to produce detection patterns suitable for applications such as aisles and corners and for narrowing the detection diameter Important note Ensure all infra red IR programming is completed before affixing the masking shields to the detector The masking shields may impair the light sensor and IR sensors by covering them Ensure correct operation before completing commissioning Lateral tear pattern for a making a slot style detection shape Vai i WW Wo Reems N A SN Nes Radial tear pattern for narrowing the detection diameter N NNS i RQ amp A Pt VCS Aisles Slot Masking shield number coverage Slot number 1234 4321 Example Mounting height 6m Align trimmed shields with sensor head Trimmed to slots 2 alignment marks and aisle Aisle detection width 16m x 32 5 1m walk across 12m x 32 3 8m walk towards Narrow detection Masking shields trimmed for a narrow beam of detection AARE ae Diameter Masking shield AP giana MEN number coverage BCAA Y ENEADO Diameter number 12345 54321 Example Mounting height 15m Trimmed to diameter 3 Detection diameter 40m x 45 18m walk across 30m x 45 13 5m walk towards Installation
11. first Use this button to select the settings in red and blue signified by the Shift 1 and Shift 2 LEDs Advanced programming Detector Parameters Walk Test LED or Off When set to On this causes a red LED to flash on the sensor when it detects movement Use this feature to check for adequate sensitivity levels Time Out S minutes 0 99 minutes Once the detector is turned on this value sets how long the lights will stay on once Time adjustment movement has ceased Select 0 for 10 second delay use for commissioning TIEN Manual Time Out 10 minutes 0 99 minutes When a manual operation occurs either via the switch input or the infrared it x Ea invokes the timeout period Example 1 a detector in presence mode has a detector timeout of 15 minutes and a manual timeout of 3 minutes When the user leaves the room they press the off button The sensor will revert to automatic after 3 minutes and then walking back in the room will turn the lights on Example 2 using the settings above the user turns the lights off say for a presentation but stays in the room Every time a movement is detected the manual timeout period is re triggered but when it doesn t pick up for the short timeout period the sensor will timeout and revert to automatic This means the lights may turn on inadvertently during the presentation if the occupants are still for the manual timeout period so adjust the timing carefully Sensitivity On 1 min to
12. hat are either be used to switch a separate channel of standard fitted with dimming ballasts transformers non dimming luminaires or to isolate the mains supply to dimming ballasts saving on the standby current of the ballasts The ballasts transformers can be connected in parallel to Channel 2 via the DIM and DIM terminals Refer to the specification on page 12 for ballast quantities Multiple luminaires may be connected in parallel to Channel 1 via the N and L Out terminals as long as the maximum total load is not exceeded Channel 2 dimmable output of the EBDHS DD LT30 can The wiring examples below show common methods of connecting the output channels for a single detector unit Single channel dimming Functions Switches the luminaire with occupancy and maintains illuminance Dims and switches using optional centre biased retractive switch MK K4900 or similar Configured to presence detection Turns on automatically with occupancy Maintains illuminance Press and release down switch to turn off Press and release up switch to turn back on Press and hold up switch to dim up press and hold down switch to dim down Turns off after occupancy Configured to absence detection Press and release up switch to turn on Maintains illuminance Press and release down switch to turn off Press and hold up switch to dim up press and hold down switch to dim down Turns off after occupancy Channel mode Set to Switch and dim t
13. hieve a preset lux level maintained illuminance Readback function UNLCDHS handset only The UNLCDHS has the ability to read back the settings stored in a device To read back individual parameters Navigate to the parameter and press the R Read button whilst pointing at the device The handset will click when the parameter has been read back the device will flash its LED and the value will be shown against the parameter in the menu To read back all of the parameters in a menu Press and hold the R Read button for more than 1 second The handset will click every time a parameter is received The device will show multiple flashes of its LED All of the values will be shown against the parameters in the menu The individual parameters may be edited and then saved as a Macro Notes e If a parameter s has been missed because of a communication error the missing value s is replaced by dashes When reading back the Channel 1 relay where fitted will temporarily be switched off and will return to it s normal state 2 seconds after the read back has been completed Installation Assembly The EBDHS DD LT30 may be supplied in two S parts Follow the 4 ales instructions to J J a Push in sensor Wea assemble head connector to mating socket on power supply unit Locate sensor head onto power supply Remove connector cover The EBDHS DD LT30 is designed to be moun
14. l to switch on after the second channel A typical application for this would be where a detector is controlling lighting and air conditioning in an area When the occupant is detected the lighting will be turned on immediately whereas the air conditioning may be turned on after 15 minutes If the area is vacated and the detector times out before the delay then the air conditioning would never go on The delay can be set only for channel 1 using the on delay parameter Inhibit 4 seconds 1 to 999 seconds When the detector turns off a delay is instigated to prevent retriggering In certain circumstances this delay may not be enough This parameter allows the delay to be changed Requires two or more PIR detectors to detect to trigger the lights on Factory default a ee Restores factory default settings Channel Modes Switch only ee ee Ce Usually used for absence detection in this mode the dimming channel is not used Switch and dim Default The detector will switch and dim the lighting together x Z together Switch and dim Provides 2 channel operation Channel 1 is switched via the relay output and x separate Channel 2 is dimmed switched via the dimming output User Modes SS ree Le C OR I cerns Ul peer eee EA eee E ee T A EA EEA Scene Select the individual scene between 0 and 6 1 min output 2 10 3 25 4 50 5 75 6 100 Override On If the lights are off sending the IR command will
15. ncy Configured to absence detection Press and release switch to turn on Maintains illuminance dimming channel only Press and release switch to turn off Press and hold switch to dim up and down reverses direction with each press Turns off after occupancy Channel made Set to Switch and dim separate Switch mode Set to 1 position switch separate ww PLEASE NOTE THAT THE DIMMING SIGNAL IS USED TO SWITCH THE DIMMING LUMINAIRE ON OFF AND THEREFORE THE 240V FEED TO THE LUMINAIRE FITTING O Tanc K S N PERMANENT LIVE SUPPLY LS fearrast HRS LUMINAIRE NON DIMMING DIMMING LUMINAIRE DSI or DALI NEUTRAL SWITCH 1 MOMENTARY LIVE oL PUSH TO MAKE SWITCH EXTERNAL CIRCUIT PROTECTION 10A 240V SWITCHING o 240V SWITCHING Optional for presence mandatory for absence detection SWITCH 2 MOMENTARY 5 K PUSH TO MAKE SWITCH Optional for presence mandatory for absence detection Two channel single switch Functions Switches both channels with occupancy Maintains illuminance dims and switches the dimming channel using optional centre biased retractive switch Configured to presence detection Turns on automatically with occupancy Maintains illuminance dimming channel only Press and release down switch to turn off Press and release up switch to turn back on Press and hold up switch to dim up press and hold down switch to dim down Turns off after occupancy Channel 1 does not operate with switch
16. ogether Switch mode Set to 2 position switch together Jeata OS DIMMING LUMINAIRE DSI or DALI NEUTRAL LIVE o a EXTERNAL CIRCUIT PROTECTION 10A CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING Optional for presence mandatory for absence detection When there is a requirement to have an Off state that requires a permanent dimmed level then use the DSI DALI pair to both switch and dim and a live feed direct to the ballast Set the Off value in the Advanced Programming section to a value greater than zero to achieve a permanent dimmed level for the Off state See the diagram below for wiring details ED DIMMING LUMINAIRE DSI or DALI NEUTRAL LIVE EXTERNAL CIRCUIT PROTECTION 10A CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING Optional for presence mandatory for absence detection Two channel individual switches Functions Switches both channels with occupancy Maintains illuminance dims and switches the dimming channel using optional single position retractive switch switch 2 Switches the switching channel using the optional single position retractive switch switch 1 Configured to presence detection Turns on automatically with occupancy Maintains illuminance dimming channel only Press and release switch to toggle output Press and hold switch to dim up and down reverses direction with each press Turns off after occupa
17. ramming Parameter Name Default Value On Raise Off Lower The functionality of the EBDHS DD LT30 is controlled by a number of parameters which can be changed or programmed by any of the following devices e UHS5 Infrared Handset See below for programmable functions e UNLCDHS Infrared Handset with LCD See user guide for full programming details For most basic programming operations the UHS5 handset can be used and the following procedures are based on using this device Point the handset at the Sensor and send the required programming commands to the unit as shown below Valid commands will be indicated by a red LED flash See page 1 for details of other LED responses Note other functions on the UHS5 which are not shown below are not applicable to this product t Number of Shift key presses SHIFT ont Coat SHIFT1 SHIFT2 SHIFT1 SHIFT2 SHIFT1 SHIFT 2 SH 3 Os h ret lt LY IFT1 SHIFT 2 all Time Out Time adjustment Lux on level Switch level on Light Level Lux off level Switch level off Load Type Sensitivity Presence Absence 20 mins 6 600 DALI Presence 5 15 amp 30 minutes minutes 2 5 amp 7 4 6 amp 9 4 689 1 5 amp 9 3 68 amp 8 PoP 10 seconds 2 200 5 500 7 700 2 DALI 7 DSI 4 400 6 600 9 999 2 DALI on UHS5 Handset Graphics Description Turn lights on
18. tch to turn off Turns off after occupancy Channel mode Set to Switch only Switch mode Set to 2 position switch together Note a single position switch can be used instead to toggle the output set to 1 position switch separate oF US LUMINAIRE NON DIMMING NEUTRAL LIVE O gt lt D EXTERNAL CIRCUIT PROTECTION 10A CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING Optional for presence mandatory for absence detection Power up test procedure When power is applied to the unit the load will turn on immediately Set the timeout to 10 seconds vacate the room or remain very still and wait for the load to switch off Check that the load switches on when movement is detected The unit is now ready for programming Fault finding What if the load does not turn ON e Check that the live supply to the circuit is good e Check that the load is functioning by bypassing the sensor e g link terminals L and L Out on Channel e If the detection range is smaller than expected check the diagrams on page 2 Rotating the sensor slightly may improve the detection range HINT The Walk Test LED function can be used to check that the unit is detecting movement in the required area What if the load does not turn OFF e Ensure that the area is left unoccupied for longer than the Time Out Period e Ensure that the sensor is not adjacent to circulating air heaters or lamps Basic prog
19. ted using either e Flush fixing or e Surface fixing using the optional Surface Mounting Box part no DBB Both methods are illustrated below Use the supplied gasket to ensure IP rating not compatible with Surface Mounting Box part no DBB Flush Fixing Hole 64mm Warning be careful bending springs when mounting unit Pull out spring tab and rotate spring arm as shown Wire stripping details Important 4 gt Ensure that the cables are formed as shown te before affixing the cable clamp The clamp MUST clamp the outer sheath s only 6mm Bend cores as shown 35 mm Overview It is a requirement of many fluorescent lamp manufacturers to have the lamps on at maximum output for a period of time to guarantee lamp life refer to the manufacturer s datasheet for details As this EBDHS DD LT30 is able to dim the lamps using DALI DSI the product provides a facility to disable this for a given period of time Operation By setting the Burn in parameter you can select a time during which the lamps are not allowed to deviate from maximum output The unit counts the time and even remembers how long has elapsed in the event of a power failure To cancel the burn in function simply select a time of 0 Note that when the lamps are changed the burn in time should be set again 5 Wiring diagrams Channel 1 switched output of the EBDHS DD LT30 can be used to control the light output of luminaires t
20. turn them on immediately and revert to automatic operation using the manual timeout period Override Off If the lights are on sending the IR command will turn them off immediately After the manual timeout period described above the sensor will revert to automatic a ee Cancels the on or off override returning the detector to normal operation raga Advanced programming Channel 1 Switching Channel Detection Mode Presence Presence or Presence mode allows the output to turn on when movement is detected and off Absence when movement ceases Absence mode allows the output to turn off when movement ceases but must be manually turned on first Lux on level 1to9 Sets a minimum light level below which the PIR sensor is enabled allowing lights Switch level on For a higher resolution to be turned on by movement a scale of 101 199 is Note the Lux Level Off value must always be greater than the Lux Level On value available Lux off level 1to9 Sets a maximum light level above which the PIR sensor is disabled preventing Switch level off For a higher resolution lights from being turned on by movement a scale of 101 199 is available Channel 2 Dimming Channel Detection Mode Presence Presence or Presence mode allows the output to turn on when movement is detected and off Absence when movement ceases Absence mode allows the output to turn off when movement ceases but must be manually turned on first Lux on level 1 to 9
21. y will adopt the preset off value This feature is only enabled if Min value is set to 99 in Pos Mosse nous or Determines how long the output will be at 100 so that lamps burn in The burn Po to Mosse nous hours in time is not affected by power supply interruptions a value 0 to 99 After occupancy ceases this dimming output level is loaded for the fade time adjustable between 0 and 99 Fade mins 0 to 99 This is the time period adjustable between 0 and 99 minutes that the luminaire will be held at the fade value before turning off A value of 0 a the fade function Speed On Measured in 0 1 Determines the dimming response speed after the setup time has finished k sec intervals Speed Set 5 Measured in 0 1 Determines the dimming response speed during the set up time Measured in 0 1 J sec intervals sec intervals If set to O will disable dimming for Set seconds below used if x fittings are required to warm up before dimming Set Seconds 120 1 to 999 seconds Determines how long the dimming response set up period lasts on power up or on setting change This enables the desired lux level to be achieved rapidly when the x v4 lights come on or during setup Switch Modes 2 position switch Default A single centre biased retractive switch will be used to control both channels x y together together 2 position switch A single centre biased retractive switch will be used to control only the dimming separate channel