1. energy net MEASUREMENT CONNECTION CABLES 2 5 mm 90 SIRIO Ei Contatore DIN OMEGA da 35 Energy meter 4 Modules DIN 68 x 58 90 mm ATTENZIONE La Elcontrol Energy Net S p a declina ogni responsabilita per eventuali danni a persone cose originati da un uso da errato impiego dei propri prodotti Soggetto a modifiche senza preavviso WARNING Elcontrol Energy Net Spa declines all liability for any damage to people property caused by unsuitable or incorrect use of its products Elcontrol Energy Net reserves the right to change product specifications without prior notice ATTENTION Elcontrol Energy Net S p a d cline toute responsabilit pour ventuels dommages a personnes et mat riels caus es par une utilisation impropre ou par un emploi des produits incorrect Elcontrol Energy Net se r serve le droit de modifier sans pr avis les caract ristiques techniques des mat riels ACHTUNG Elcontrol Energy Net Spa lehnt jede Verantwortung f r eventuelle Sch den an Personen oder Sachen infolge von Gebrauch der Elcontrol Produkte ab Anderungen vorbehalten ATENCION Elcontrol Energy Net S p a declina toda responsabilidad por eventuales danos a personas cosas producidos por el uso inadecuado equivocado de sus productos Puede ser modificado sin preaviso ELCO SC a Maki
2. Condensation non condensing Digital outputs 1 electronic relays 120 100 1 electromechanical relay 1A 250Vac
3. d for digital output 2 Press the SEL key to select the digit to be edited Press the SET key to modify the selected digit Press PAG Pag 22 Setup of the alarm hysteresis for digital output 2 This value is expressed as percentage of the alarm threshold Possible values are between 00 and 99 Press the SEL key to select the digit to be edited Press the SET key to modify the selected digit Press PAG Pag 23 Setup of the alarm delay for digital output 2 The delay time is expressed in seconds Possible values are between 000 and 999 Press the SEL key to select the digit to be edited Press the SET key to modify the selected digit Press PAG exits the setup menu 7 TECHNICAL CHARACTERISTICS Measures 70 x 58 x 90 mm Power supply 230 or 115 Vac 10 35 400 Hz Consumption VA Display LCD 128 segments Voltmeter inputs 250 Vac phase neutral 450 Vac phase phase Voltmeter input impedance 2 Number of scales 1 scale for voltage 2 scales for current Current inputs external C T s required 1 VA Current inputs overload 7 A permanent 15 for 1 second Measurements T R M S true R M S up to the 25 harmonic Accuracy 1 for V 1 2 for power Class 2 IEC 1036 Connection Single phase three phase STAR 4 wires three phase DELTA 3 wires two phase neutral Weight 0 3 kg Protection level Instrument IP20 front panel IP60 Temperature range 10 60 C Relative humidity range 20 80
4. enance and repair operations requiring the opening of the instrument must be carried out only by suitably qualified and authorised personnel The instrument was shipped from the manufacturing plant in perfect technical safety conditions 1 2 SYMBOLS Please read carefully the instructions with this symbol before installing and using the instrument 1 3 PRELIMINARY INSPECTIONS Before installation check that the instrument is in good conditions and was not damaged during transport Check that the network voltage and the rated voltage coincide This instrument does not require an earth connection 1 4 PRECAUTIONS IN THE EVENTS OF MALFUNCTIONS When safe operation is no longer possible put the instrument out of service and ensure that it cannot be operated accidentally Safe operation cannot be guaranteed in the following circumstances When the instrument appears clearly damaged When the instrument no longer works After long storage in unsuitable conditions After being damaged in transit 2 POWER SUPPLY The power supply connections terminals are located on the rear side and are clearly indicated with the label POWER SUPPLY Use cables having a maximum section of 2 5 mm Earth connection is not required 2 1 CONNECTING VOLTAGE MEASUREMENT CABLES These cables having a maximum section of 2 5 2 to be connected the terminals labelled VOLTAGE INPUT 2 2 CONNECTING CURRENT MEASUREMENT CABLE Connect the sec
5. ng senge of your Unit 5 Southmill Trading Centre Bishop s Stortford Herts CM23 3DY User Manual 01279 503173 01279 654441 sales elcomponent co uk 116V 220 CURRENTINPUT RELAY POWER AY 1A 250V see AN A VOLTAGE INPUT MAX 450V u N VLI WL2 1PH CURRENT INPUT POWER 250 SUPPLY A VOLTAGE INPUT 4500 w WLI 2 VL3 2 CURRENT INPUT RELAY 1A 250V 4 MAX TA A VOLTAGE INPUT 450V oy VL ZIT 3 PH N CURRENT INPUT ny A VOLTAGE INPUT 450V u N VL2 Vu L3 12 Li 3 PH 1150 gaya RELAY 1A 250V Rs485 POWER SUPPLY A 115V 230 English SIRIO is a three phase energy analyzer with a 4 modules din rail case The high technological content and its flexibility make this instrument unique for it s quality and performance 1 STANDARDS and REGULATIONS CE Conformity declaration The SIRIO family of products conforms to Directive 89 336 EEC EMC Directive 73 23 EEC 93 68 EEC LVD In compliance with standards IEC 1010 1 400VCat III and protection level 2 according to IEC 664 664A Safety EN500081 1 EN50082 2 ed EN55022 EMC 1 1 USER SAFETY In order to preserve these safety conditions and ensure safe operation the user must observe all instructions and marks specified in this user manual All maint
6. ondary windings of the external CT s to the 2 5 mm terminals labelle CURRENT INPUT as shown Use CT s with secondary Use cables having a se appropriate to the length of the connection and the rated power of the CT s used Follow the connection diagram at the end of the manual NOTE 1 For safety reasons never leave the CT secondary open NOTE 2 To guarantee correct measurements ensure that the voltage measurement and the current measurement cables are connected in the same order of phases 3 MEASUREMENTS PAGES At startup SIRIO displays the last selected page before shutdown The PAG key is used to browse trough the measurements pages as described in the following Page 1 Voltage Current Page 2 W P F Page 3 kWh Pressing the SEL key while in page 2 the average AVG values and the peak MD values of power will be displayed 4 PROTECTION CODE FOR THE SETUP PAGES The access to the setup pages thus also to the counters reset function and to all setups necessary for a correct operation of the instrument can be restricted trough an access code To enable the access code it is necessary to keep simultaneously pressed both PAG and SEL keys for 30 seconds The code setup page P 000000 will be displayed at the end of this operation To set up a personal password select the digits to be edited by pressing the SEL key and modify them by pressing the SET key The instrument will prompt the user for the access code
7. r to be edited Press the SET key to modify the selected parameter The first digits from left are the Baud rate transmission speed Possible values are 9 6 19 2 2 4 4 8 kbaud The central digit is the parity check and can have the following values N None O Odd E Even The digits to the right represent the type of Modbus communication protocol Possible values are IEE Modbus IEEE standard INTEL format ASC Modbus ASCII with emulation of Vip Energy data format BCD Modbus BCD MODICON protocol Press PAG Pag 6 Address setup page On this page the RS 485 network address of the SIRIO instrument can be set Press the SEL key to select the digit to be edited Press the SET key to modify the selected digit Press PAG Pag 7 Digital outputs selection page Press the SET key to select one of the following 3 options e 0 10 SEC Pulse type output with 100 ms pulse width Press PAG to continue to point 8 e 0 02 SEC Pulse type output with 20 ms pulse width Press PAG to continue to point 8 e OUT RLY relays type output Press PAG to continue to point 12 Pag 8 Power measurement to be associated to output 1 page Press the SET key to choose between kWh and kVAh The selected power measure will be associated to output 1 Press PAG Pag 9 Power measurement to be associated to output 2 page Press the SET key to choose between kWh and kVAh The selected power measure will be associated to ou
8. t the digit to be edited Press the SET key to modify the selected digit Press PAG Pag 16 Set up of the alarm hysteresis for digital output 1 This value is expressed as percentage of the alarm threshold Possible values are between 00 and 99 Press the SEL key to select the digit to be edited Press the SET key to modify the selected digit Press PAG Pag 17 Set up of the alarm delay for digital output 1 The delay time is expressed in seconds Possible values are between 000 and 999 Press the SEL key to select the digit to be edited Press the SET key to modify the selected digit Press PAG Pag 18 Selection page of the measurement to be associated to relays output 2 Press the SET key to select the measurement to be associated to relays output 2 out of the following V voltage A current W power PF power factor RLY relays remote control via 5485 Press PAG Pag 19 Selection page of the operating mode for relays output 2 Press the SET key to choose one of the following 2 operation modes LEVEL the relays closes and remains closed until the alarm condition terminates PULSE the relays generates a pulse with fixed 100ms width upon start of the alarm conditic Press Pag 20 Setup of the upper alarm threshold for digital output 2 Press the SEL key to select the digit to be edited Press the SET key to modify the selected digit Press PAG Pag 21 Setup of the lower alarm threshol
9. tput 2 Press PAG Pag 10 Pulse value to be associated to output 1 page On this page the value associated to each pulse from output 1 can be selected Press the SEL key to select the digit to be edited K for editing the exponent Press the SET key to modify the selected digit Press PAG Pag 11 Pulse value to be associated to output 2 page On this page the value associated to each pulse from output 2 can be selected Press the SEL key to select the digit to be edited K for editing the exponent Press the SET key to modify the selected digit Pag 12 Selection page of the measurement to be associated to relays output 1 Press the SET key to select the measurement to be associated to relays output 1 out of the following V voltage A current W power PF power factor RLY relays remote control via Rs485 Press PAG Pag 13 Selection page of the operating mode for relays output 1 Press the SET key to choose one of the following 2 operation modes LEVEL the relays closes and remains closed until the alarm condition terminates PULSE the relays generates a pulse with fixed 100ms width upon start of the alarm conditic Press PAG Pag 14 Set up of the upper alarm threshold for digital output 1 Press the SEL key to select the digit to be edited Press the SET key to modify the selected digit Press PAG Pag 15 Set up of the lower alarm threshold for digital output 1 Press the SEL key to selec
10. whenever the access to the setup pages s requested IMPORTANT The password must not be lost Only the manufacturer trough a direct intervention on the instrument can unlock the instrument s protection code 5 PROGRAMMING THE INSTRUMENT The instrument can be fully programmed by means of the SETUP menu Press at the same time the PAG and the SEL keys to enter the SETUP If the setup protection code has been enabled the instrument will request the access password 6 SETUP PAGES Pag 1 C T page On this page it is possible to set up the current ratio of the amperometric transformers used Press the SEL key to select the digit to be edited Press the SET key to modify the selected digit Press PAG Pag 2 Connection page On this page the connection type of the instrument can be selected By pressing the SET key the connection type cycles trough STAR three phase with neutral 4 wires 2PH two phase 1 PH single phase DELTA three phase 3 wires Press PAG Pag 3 Average and peak power values reset page RESMEd Selecting Y by pressing the SET key will reset the peak and average values of the power measure Press PAG Pag 4 Counter reset page RESCNT Selecting Y by pressing the SET key will reset the kWh counter Press PAG exits setup menu for SIRIO continues to point 5 for SIRIO with 485 ALM option Pag 5 RS 485 communication parameters setup page Press the SEL key to select the paramete
Download Pdf Manuals
Related Search
Related Contents
Mode d`emploi DCR-DVD108/DVD308/ DVD608/DVD708 InstruccIones de InstalacIón para Puertas Plegables de - Jeld-Wen 1 ABOUT AP IMAGES FROM ACCUWEATHERTM Otterbox APL4-T4GXX-20-E4OTR mobile phone case StarTech.com Cat 6 RJ45 Modular Plug for Solid Wire - 50 Pack BroadR-Reach SPY - User Manual Savvy User Guide 2.7 Esprit Centrales : Manual de Instalación y Consulta Copyright © All rights reserved.