Installation Manual
Contents
1. gt Press the timer button once to set the ventilation unit to high mode for 10 minutes Press the timer button twice to set the ventilation unit to high mode for 20 minutes Press the timer button three times to set the ventilation unit to high mode for 30 minutes If the operation switch is used by choosing mode 1 2 or 3 while the timer is in operation the timer is switched off and the ventilation unit operates in the chosen mode The radio frequency operation does not require additional cabling 4 Maintenance A CAUTION The range of the RF operation switch transmitter is 100 metres in a free field The distance at which the RF operation switch can function properly depends on the obstacles interfering with the RF signal i e the walls and floors between the RF operation switch and the receiver 41 Cleaning grilles without filters Grilles without filters can be taken out of the duct opening twist to the left Before you clean the grille in warm water with detergent remove the foam plastic ring After cleaning the grille can be replaced in the duct opening with a twist to the left Always make sure you replace a grille in the same room The filters For the user maintenance is limited to cleaning the filters In order to safeguard the proper functioning of the unit the filters will have to be cleaned or replaced regularly The table below indicates the average terms for maintenance or replacement of the
2. Air drawn into the property by the fan is routed through an integral high efficiency synthetic heat exchanger where warmth from the extracted air is transferred to the incoming fresh air before it is supplied to the habitable rooms In employing this type of system there is no need to install background ventilators in the dwelling an ideal solution to noisy sites 12 BEUEUS El RIETI Warranty The HRU ECO 4 warranty is valid for 2 years after installation date The warranty does not apply to disassembly and assembly costs faults which are in the opinion of Itho B V and or Itho Ventilation Limited caused by incorrect treatment negligence or an accident faults that have been caused by repairs or intended repairs by third parties without authorisation from Itho Ventilation Limited If the appliance does not function correctly or develops a fault contact Itho Ventilation Limited immediately Ensure that only genuine spares are used for any repairs Liability The HRU ECO 4 was designed for balanced ventilation systems for both high rise and low rise buildings Any other application that has not been discussed with an Itho Ventilation Itho Ventilation is not liable for any damages caused by improper use normal wear and tear not following the instructions in this manual concerning safety operation and or maintenance the use of parts which have not been supplied by an Itho Ventilation 13 EEG Gener
3. thus remains safely above freezing Should the outside air temperature become even lower the intake fan will turn more slowly the fan is revved down until it reaches a minimum If the temperature drops even further the discharge fan will be revved up and the intake fan will keep turning at the minimum rate If the outside temperature drops to an extreme low the intake fan will be turned off but the discharge fan will remain in operation The frost valve will also be closed After some time the intake fan will turn at minimum speed and the frost valve will be reopened to check whether the risk of freezing has passed If the outside temperature rises the above measures are taken in reverse order until the risk of freezing has passed The resident always determines the air volume that is discharged The frost valve can be easily removed from the top of the HRU ECO 4 without tools Push the frost valve open into the unit using four fingers against each other with fingernail side up Make sure your thumb presses the black foam outside the unit between the valve housing and the adjacent nozzle Carefully pull the valve housing upwards while sliding it in the horizontal direction of the nozzle The motor and other bypass parts can now be inspected The servomotor can be replaced if required by uncoupling the connector and unscrewing the two Phillips screws Important Make sure nothing is ever placed on top of the frost va
4. 4 is to discharge 50 W thermal power per degree of temperature difference at 150 m3 h medium mode If the inside temperature is 25 C and the outside temperature is 15 C 500 W will be discharged in the medium mode Frost protection The heat recovery unit HRU ECO 4 is delivered as standard with frost protection The frost protection consists amongst other things of a unique frost valve integrated at the top of the unit This protection prevents the unit from freezing internally during the winter The operation of the frost protection is fully automatic Frost protection operation The air discharged from the house is used to heat up the fresh air coming from outside The air in the heat exchanger therefore cools down During a period of frost the frost protection ensures that the heat exchanger in the unit cannot freeze If the temperature of the discharge air in the heat exchanger nears freezing the device will open the frost valve at the top of the unit regularly and take in warm air from the area in which the unit is located This warm air is mixed with the cold air coming from outside At the same time the intake fan will turn faster the fan is revved up to ensure the volume of fresh outside air remains the same The pre heating of the fresh cold outside air ensures that the warm air discharged from the home does not have to warm the cold outside air too much The temperature of the discharge air in the heat exchanger
5. against the wall at the top in such a way that the mounting strip fits into the unit Lower the unit until the lower part of the unit is supported by the mounting set supports 3 5 Duct connections The HRU ECO 4 is delivered as standard with the motor module at the left Diagram 1 shows the duct connections for the standard version Diagram 2 shows the duct connections for the turned ver sion All exhaust and supply air connections have an internal dia meter of 150 mm and external 180 mm The connections can be used to attach Vortice modular rigid ducting and insulated flexible aluminium ducts and accessories Each connection is provided with an illustration that shows the direction and source of the air Diagram 1 Standard version Exhaust to atmosphere 4 A d i sd Frost protection valve Fresh air intake Y from atmosphere eg Extract from dwelling Supply to dwelling High Rise Building Filterholders Place holder for user manual Electrical connections Extract from dwelling Supply to dwelling Low Rise Building E d Condensation discharge Diagram 2 Turned version Frost protection valve Supply to dwelling Extract from dwelling High Rise Building Fresh air intake from atmosphere gt BL Exhaustto atmosphere Place holder for user manual Filterholders amp Supply to dwelling Low Rise Building Extract from dwelling 3 Condensation d
6. filters This may differ per situation The unit comes with standard G3 filters Up to half a year after the delivery ofthe house the filters will have to be cleaned once a month After this the filters will have to be replaced Filter Clean Replace G3 Every 3 months Once a year G4 Every 9 months Once every 1 5 years F7 Every 7 months Once a year Replace the filters in this order Take the power cable out of the socket gt Pull the filter holders out of the unit Remove the old filter C from the filter holder Clean the old filter or take the new one from the packaging filters can be cleaned with a vacuum cleaner gt Place the new filter in the filter holder Put the power cable back in the socket Insect filter Once a year the mosquito filter must be cleaned The occupant can do this him herself First remove the power cable Remove the yellow cap at the top of the unit Now insert the nozzle of the vacuum cleaner into the hole and turn on the vacuum cleaner This way the vacuum cleaner removes any mosquitoes and suchlike present Replace the yellow cap and switch the unit on again 4 2 Maz COUETTE In The long term efficiency of the heat exchanger may decrease due to the insulation effect of contamination that got past the filters How often the heat exchanger should be cleaned depends on the maintenance of the filters Replace the heat exchanger once every six years if the filters are maintain
7. the picture Turn the front door 90 degrees clockwise until it is vertical Make sure that the round foam disk is in place in the hole against the heat exchanger between the front door and the exchanger Place the bayonet catch in the new back in the same way Make sure that the foam disk between the heat exchanger and the bayonet catch is in place The unit has been turned and is ready for assembly The front is now the rear and vice versa The electrical connections are now located at the right of the unit 3 4 BOUT LOTO Ae SE LoT The HRU ECO 4 is delivered as standard with a mounting set The mounting materials are to be procured elsewhere The location of the drill holes is indicated in the drawing The edge of the mounting set corresponds with the centre lines of the ducts The notch at the bottom of the mounting set indicates the location of the condensation discharge left for the standard unit and right for the turned unit d 30 600 848 Standard b 480 5x 5mm lt gt version E p A A E 1 30 es m ig 1 A x 8 3 7 1 30 _ mere A E Yv y I I le 5xo5mm Turned 480 version Determine the exact location for the unit keeping the mounting requirements in mind Attach the mounting set to the wall using appropriate mounting material Place the unit on the lower supports and push the unit
8. use a REE The unit has two energy saving direct current motors The fans have a permanent magnet motor and therefore the required energy supply is minimal The blades are robust and bent backwards The shape of the blades ensures the fan is less susceptible to long term contamination The maintenance frequency for the cleaning of the blades is normally once every six years but this depends on the maintenance of the filters Follow these instructions to assemble and disassemble the fans Remove the two screws which secure the printed circuit board module to the motor module Remove the insulation plate Turn the printed circuit board module and pull the connector from the frost protection sensors and the connector from the bypass These are the connectors to the cables that are led through the black foam synthetic housing The hard synthetic plate including the fans power supply and control can now be separated from the black foam synthetic housing The fans can now be removed Remove the cable seal from the hole Disconnect the connector from the printed circuit board Loosen the four M4 nuts Remove the fan including the vibration dampers from the motor plate and pull the cable with the connector through the hole in the motor plate The fan is now ready for cleaning or replacement Follow the instructions in reversed order to mount the fans Pull the cable with the connector through the corresponding opening
9. 2 58 0 57 7 58 7 250 Hz dB 23 3 32 1 46 3 52 7 53 0 56 4 56 8 58 9 59 2 250 Hz dB 22 6 33 0 46 9 53 7 53 6 58 4 58 1 61 4 60 6 250 Hz dB 29 5 40 8 56 7 64 4 64 7 68 0 58 8 70 3 71 3 500 Hz dB 21 4 29 6 44 8 52 2 53 8 55 7 56 7 58 1 59 3 500 Hz dB 15 2 25 4 40 0 47 6 49 4 50 8 52 1 53 6 54 9 500 Hz dB 29 7 40 2 54 9 65 6 65 5 69 6 70 6 72 9 74 1 1000 Hz dB 13 2 24 2 40 9 47 8 48 9 51 5 52 5 54 7 55 6 1000 Hz dB 10 3 22 3 37 0 43 2 44 1 46 9 47 8 49 9 50 6 1000 Hz dB 227 35 3 51 3 58 6 59 7 62 4 63 3 65 9 67 0 2000 Hz dB 11 5 18 1 39 4 47 3 48 7 50 8 51 8 53 7 54 5 2000 Hz dB 7 1 12 1 30 6 37 7 38 9 40 9 42 0 43 8 44 5 2000 Hz dB 217 28 1 48 9 57 5 59 1 61 1 62 2 64 2 65 0 4000 Hz dB 4 7 5 6 25 1 35 7 38 6 41 3 43 4 45 6 47 2 4000 Hz dB 4 3 4 7 15 1 25 3 27 0 30 7 32 5 35 1 36 3 4000 Hz dB 7 2 13 4 36 2 47 0 48 9 52 7 54 6 57 2 58 7 8000 Hz dB 9 4 9 3 15 4 24 1 29 5 29 4 38 4 33 7 37 0 8000 Hz dB 9 0 8 8 12 5 14 3 14 9 16 8 17 4 19 8 20 6 8000 Hz dB 12 0 12 7 22 9 33 6 35 5 39 1 40 5 43 6 45 0 Installation regulations 3 1 Installation requirements The HRU ECO 4 should be installed following the general and local safety and installation regulations and the instructions in this manual The
10. 50 275 300 325 350 375 400 Capacity qv m3 h Capacity lt _ lt 1 capacity min 2 capacity low 3 capacity middle 4 capacity high 225 m3h 5 capacity highz75 mah amp capacity max 325 magih Inputpawer emma power min a power low 8 power middle 10 power high 225 mam 11 power high 275 mam 12 power max 325 mash 27 Sound Level Lw A 25 m3 h 20 Pa 75 m3 h 20 Pa EN 150 m3 h 80Pa 2 225 m3 h 100 Pa S 225m3 h 150 Pa amp 275 m h 100Pa 275 m3 h 150 Pa 325 m3 h 100 Pa 325 m3 h 150 Pa Sound Level Lw A 25 m3 h 20 Pa 75 m3 h 20 Pa 150 m3 h 80Pa 225m3 h 100 Pa E 225 m3 h 150 Pa w 275 m3 h 100 Pa 275 m3 h 150 Pa 325 m3 h 100 Pa 325 m3 h 150 Pa Sound Level Lw A 25 m3 h 20 Pa 75 m3 h 20 Pa 150 m3 h 80Pa 225 m3 h 100 Pa 225 m3 h 150 Pa 275 m3 h 100 Pa 275 m3 h 150 Pa 325 m3 h 100 Pa 325 m3 h 150 Pa total dB A lt 23 5 30 5 46 5 53 8 55 0 57 5 58 5 60 5 61 5 total dB A 20 5 28 5 42 5 49 5 50 5 53 5 54 0 56 5 57 0 total dB A 30 0 40 5 56 5 65 3 66 0 69 5 70 5 73 0 74 0 63 Hz dB 47 2 45 2 46 6 50 0 53 6 58 2 61 8 58 6 54 7 63 Hz dB 46 2 46 7 45 9 47 0 46 8 46 8 46 8 47 2 48 6 63 Hz dB 33 6 47 3 50 0 50 7 51 4 52 1 53 0 53 2 54 1 125 Hz dB 30 4 34 2 44 9 48 1 48 7 49 6 50 4 50 4 51 8 125 Hz dB 19 7 28 8 37 3 41 8 43 2 43 6 46 1 44 7 46 5 125 Hz dB 29 4 40 8 51 9 56 0 56 7 57
11. A TY INS Check the unit upon delivery to discover any faults prior to assembly This ensures the unit can be easily exchanged without requiring additional work Check whether the name plate data and the sticker on the box are correct before removing the packaging Take the unit carefully out of the box The unit can best be placed on the nozzles at the bottom or top Check the unit for visible damage The condensation coupling and the user manual should be included in the box 33 BU as The HRU ECO 4 is delivered as standard with the motor module at the left The unit can be easily turned without using tools before it is mounted if this is preferable with regards to the position of the duct system If the unit does not require turning please continue with the instructions in Section 3 4 If the unit does require turning follow the instructions below Remove the filters holders 1 Turn the front door 1 with bayonet catch 9o degrees anticlockwise and remove it Turn the bayonet catch at the rear 90 degrees anticlockwise as well and remove it Move the front plate 2 with your right hand without turning it to the other side and correctly place the plate by pressing the edge under the black edge of the housing This is easiest when the unit is flat on the floor Make sure the floor surface is level to ensure the aluminium casing is not damaged gt Place the front door at the new front of the unit Refer to
12. HRU ECO 4 Installer manual 1 1 1 2 1 3 2 1 2 2 2 3 2 4 25 2 6 2 7 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 Table of Contents General information Introduction Warranty and liability Safety Technical information General description Description of parts Dimensional sketch Bypass and frost protection Specifications Capacity graph Sound data Installation regulations Installation terms and conditions Check upon delivery Turning the unit Mounting the unit Duct connections Connecting the condensation discharge Capacity settings Control using RF Switch Pp OAD BWW uy Oo wW CO OO 00 CO 10 4 1 4 2 4 3 4 4 4 5 5 1 5 2 5 3 5 4 Maintenance Filters Heat exchanger service Motor module Fans Control printed circuit board Troubleshooting Operation troubleshooting Table of possible faults Table of causes Table of solutions Notes 1 General information 1 1 Introduction This installer manual was compiled for the installation and maintenance of the Itho Ventilation Limited supplied Itho heat recovery unit HRU ECO 4 which includes the following types HRU ECO 4 House HRU ECO 4 Apartment The objectives of this installer manual are to ensure optimum safety during installation and use ensure thorough maintenance provide reference material in the event of a failure Although this manual was created with great care no rights can be derived from it T
13. HRU ECO 4 should be located on a suitable internal wall The HRU ECO 4 requires 230 V 50 Hz mains voltage The tolerance for the mains voltage is 5 A two pole isolating switch with a minimum contact gap of 3mm must be fitted The feeder cable is 1 5 m long and the connection is located at the left side of the unit If the unit is assembled backwards this connection is at the right side of the unit The ducts should be of the correct dimensions The ducts to and from the exterior should be thermally insulated and damp proof The HRU ECO 4 should be mounted on a wall with a wall mass of at least 200 kg m2 The supplied silencer D 180 mm L 50 cm should be added to the supply duct to the home to achieve the optimum comfort level in the home lt The HRU ECO 4 has a condensation discharge that should be connected to the house sewerage Refer to Section 3 6 The HRU ECO 4 has to be mounted vertically and level due to the catch tray The HRU ECO 4 should be accessible for service and maintenance work Make sure there is 500 mm open space at the front of the unit This means that a distance of a metre from the wall should be available at the location where the unit is to be placed That space is required to be able to slide the service module the heat exchanger and the filters out of the unit The bottom of the unit and the electrical connections at the side should also be accessible for service work 3 2 RAN
14. al Safety The HRU ECO 4 heat recovery unit has been designed for integration into a ventilation installation WARNING Do not use this appliance for functions other than those described in the booklet gt After removing the appliance from its packaging ensure that it is complete and undamaged If in doubt contact Itho Ventilation Limited Do not leave the packaging within reach of children or the infirm Certain fundamental rules must be observed when using any electrical appliance including a never touch appliances with wet or damp hands b never touch appliances while barefoot c do not allow children to use the appliance without supervision d supervise infirm persons when using the appliance Store the appliance out of the reach of children and infirm persons if you decide to disconnect it from the power supply and no longer use it lt Do not operate the appliance in the presence of inflammable substances or vapours alcohols insecticides petrol etc CAUTION The following general instructions are important Follow the safety instructions to prevent fan damage and personal injuries Maintenance instructions must be followed to prevent damage and or excessive wear and tear The specifications in this manual may not be modified The fans may not be modified The motor module is only suitable for a 230 V 50 Hz a c system Do not expose the appliance to the weather rain sun etc Do not p
15. e of malfunction The motor module consists of a hard synthetic plate The fans and the control are mounted on this plate This hard synthetic plate is jammed in the black synthetic foam housing Follow these instructions for replacing the motor module Isolate the product from the electrical supply Remove the communication cables from the unit connectors Remove the filters and the heat exchanger as described in Section 4 2 Disconnect the electric cable from the bypass frost valve motor This has to take place near the supply fan Slide the motor module from the unit while holding the housing to ensure the unit stays mounted on the wall Follow the instructions in reverse order to mount the motor module lt Slide the motor module into the ventilation unit Push the casing a little outwards to make it easier to slide the motor module into the unit The motor module will encounter some resistance when it is at approximately 3 cm from the fully inserted position Press the motor module a little outwards from the inside of the unit Slide the motor module until the edge of the housing is level with the module Reconnect the bypass cable and the connector Position the heat exchanger Fasten the two nuts on the bottom of the unit Place the filters Place the sealing disk Mount the front door Connect the communication cables Place the feeder cable in the wall socket The unit is now ready for
16. eat exchanger may cause condensation The heat exchanger has a catch tray for the condensation which must be connected to the waste water system Heat exchanger This counterflow heat exchanger consists of triangular channels Each channel is therefore surrounded by three channels which flow in the opposite direction This special construction contributes to an average temperature efficiency of over 90 The efficiency depends on air volume 23 MINOR m N 2189 o xD 125 480 730 TOP VIEW DETAIL CROSS SECTION SUSPENSION SCALE 1 1 FRONT VIEW hi C LEFT HAND SIDE VIEW 233 233 306 424 BOTTOM VIEW 2 4 EEEE ECORI Bypass The heat recovery unit HRU ECO 4 is delivered as standard with a fully integrated bypass valve This valve is fully automatic The bypass ensures that the air from outside is fed around the heat exchanger It seals the path to the heat exchanger completely The return air flow still passes through the heat exchanger The fresh outside air is therefore not heated but blown directly into the home This is an advantage on hot summer nights In these circumstances the outside air is often cooler than the air within the home In bypass mode the returning air is filtered but the intake air is not The purpose of the bypass is to ventilate the house w
17. ed safe to touch This means that under normal operation no one can come near any turning parts without a deliberate action such as disassembly of the casing with appropriate tools taking out the heat exchanger after disassembling the casing removing the motor module after disassembling the casing Safety measures The HRU ECO 4 has been designed and constructed such that it is impossible to come into contact with moving parts or parts under voltage when the system is used ina normal way and without deliberate action The HRU ECO 4 meets the legal requirements for electrical devices The following safety measures should be taken into account Before starting maintenance activities always electrically discharge the device by isolating the product from the power supply Use appropriate and suitable tools Only use the device for an application for which it was designed as indicated in Section 1 2 Warranty and liability 2 Technical information 23 ROGERS The purpose of the HRU ECO 4 is optimum ventilation of homes with minimal energy loss Air is extracted from the kitchen bathrooms ensuites utility rooms and the toilet and if required from a storage room Air is supplied to the bedrooms and living room The volumes of air are specified in the Building Regulations Part Fi Means of Ventilation ADF The total volume of air extracted and supplied is equal The air flows are completely separated and filt
18. ed regularly The heat exchanger can be cleaned as follows Remove the filters from the unit as described in Section 4 1 Unscrew the two nuts at the bottom of the unit but make sure the nuts remain on the bolt Remove the heat exchanger from the unit by pulling the clamping strip This action causes friction because the unit has to be as leak proof as possible Hold the bottom of the unit to ensure it stays against the wall Use the clamping strip to carry the heat exchanger Do not use the green surfaces to carry it Caution The heat exchanger may leak N condensation This is normal and is not a problem Rinse the heat exchanger using a soap solution Slide the heat exchanger back into the unit without tilting it The green surface should be parallel to the edge of the housing Slide the filters into the unit until the filter no longer protrudes from the su exchanger lt Fasten the two nuts on the bottom of the unit If the sealing disk is not atta it should be placed against tl Put the front door back by pus the hole Turn the front 9o degrees clock is vertically in the unit Place the feeder cable in the wall socket The HRU ECO 4 is ready for use Replacement Heat Exchangers are available from Itho Ventilation Limited 43 WAIT mrs All moving parts except the bypass and the frost protection are located in the motor module The motor module can be replaced or repaired outside the unit in cas
19. er fan functions 1 2 3 2 Only the intake fan functions 4 3 Only the discharge fan functions 5 4 4 The unit is leaking water 6 7 5 The duct is leaking water 8 9 6 The unit is making a noise 10 11 7 The valves are making a noise 12 13 8 The air quality in the home is bad 13 9 The unit does not respond to the 3 position mode switch 14 53 No Possible problem Number of cause 1 No power supply to the wall socket 1 2 The supply cable is not fitted correctly to the unit connector 2 3 The fuse on the printed circuit board is faulty 3 4 The fan s connector on the printed circuit board is not fitted correctly as 5 _ The frost protection is active 6 6 The condensation discharge has not been connected 7 7 The condensation discharge is clogged 8 8 The ducts have not been insulated thermally or are not damp proof 9 9 Arooflead through has been applied which is not rain tight thermally insulated or damp proof 10 10 Theunit has been mounted on a wall with a mass less than 200 kg m 11 11 The unused nozzle has not been capped 12 12 An sound insulation hose has NOT been mounted 13 13 The valves have not been synchronised correctly 14 14 The 3 position mode switch is faulty 15 used to find the possible cause in the table of causes Each cause is also followed by a number This is the number of the possible solution Follow the instructions specified in the table 5 4 BE Crome TE No Possible solution or exp
20. ered The energy of the discharge air is transferred to the fresh air supply at a high efficiency of approximately 90 Condensation can be caused by the discharged air This is discharged through the sewer drain The HRU ECO 4 can be operated from for example the kitchen using a RF switch Correct application of the ventilation system creates an optimum healthy and comfortable home climate with minimum energy use 2 2 WES Eo The most important parts of the HRU ECO q are the following Casing The patented casing consists of an aluminium casing construction that clasps the synthetic inner parts around the heat exchanger This creates an optimum leak proof construction The front and back of the heat exchanger are sealed by a soft synthetic disk with a bayonet catch The front of this disk is integrated into the front door The colour of the casing construction is RAL 9002 the colour of the front panel is RAL 5014 and the colour of the front door is RAL 9002 The total unit weighs approximately 25 Kg Compartmentalisation section The internal construction for the distribution of the separate air flows is the compartmentalisation section This compartmentalisation section consists of four high quality polypropylene parts and is completely recyclable The result of the shape and material of the separate compartments is maximum thermal isolation and minimum internal air leakage The cooling of the discharged air flow in the h
21. hese products are in continuous development Itho B V and or Itho Ventilation Ltd reserve the right to modify this manual without prior notice Compliance with Building Regulations The 2006 Edition of the U K Building Regulations Approved Document F Means of Ventilation applicable in England and Wales details 4 clearly defined systems of ventilation to dwellings System 4 Continuous mechanical extract with heat recovery MVHR is complied with by the new HRU ECO 4 ultra high efficiency whole house heat recovery ventilation system System 4 Continuous Mechanical Supply amp Extract with Heat Recovery requires a minimum high rate in each wet room to be achieved Kitchens 13 l s and both utilities and bathrooms 8 l s sanitary only 6 l s The minimum low rate is calculated by taking the number of bedrooms in the dwelling and applying the l s value from Table 1 1b In addition the rate should be no less than o 3 l s per m of internal floor area all storeys plus for each additional occupant over and above the anticipated two for the first bedroom and one for each of the others a further 4 s must be added to the extract rate Also there is an addition of an allowance to be calculated for air infiltration The system provides quiet uninterrupted extract ventilation from the dwelling removing warm stale air via all of the wet rooms creating a permanent air path through the property from the dry habitable rooms
22. in the motor plate Put the ventilator in position by pushing the studs of the four vibration dampers through the motor plate Add a blocker ring to every vibration damper This prevents loosening through vibration Fasten the four Mz nuts gt Add the cable seal Connect the connector to the printed circuit board Attention The upper fan should be connected to the lower connector The lower fan should be connected to the upper connector The frost protection does not function if this is the other way around Reconnect the frost protection sensors connector and the bypass connector Refer to Section 4 5 for instructions on connecting the printed circuit board 4 5 Control printed circuit board The control does not require maintenance An overview of the functions of the critical parts is provided to help solve the problem in the event of malfunction 1 Feeder cable connector 2 Glass fuse T2A 250 V 20 x 5 mm 3 VKK jumper 4 Connector I2C 5 Potentiometer low speed 6 Potentiometer high speed 7 Connector PC communication RJ 45 8 Connector R 9 Connector control printed circuit board mn 5 Troubleshooting z The following table contains a list of possible problems Each problem is followed by a number This is the number of the possible cause of the problem This number can be 5 2 Table of possible problems No Possible problem Number of cause 1 Neith
23. ischarge gt Suction of fresh outside air This nozzle is used for the intake of outside air This duct should be thermally insulated and damp proof to prevent condensation on the outside of the duct Discharge to outside This nozzle is used for the discharge of air This duct should be thermally insulated and damp proof to prevent condensation on the inside and outside of the duct If venting to the roof we recommend using a lead through for the roof that does not allow condensation or rain to enter If this is not the case the parts of the duct system between the discharge nozzle and the lead through in the roof should be water tight The unit discharges any condensed water through the condensation discharge Supply to home in low rise building Heated air is supplied to the home through this nozzle The connection is at the bottom for a low rise building unit The supply nozzle for a high rise building unit is not used The silencer duct should be added to the supply duct to the home to achieve the optimum comfort level in the home Supply to home in high rise building The connection is at the top for a high rise building unit The supply nozzle for a low rise building is not used Return from home for low rise and high rise buildings These nozzles are used for the air sucked from the home The ducts do not require thermal insulation These two nozzles are connected internally The selection of one of the two noz
24. ithout transferring heat This is only desirable when the following conditions are met The inside temperature is higher than desired The inside temperature is higher than the outside temperature The outside temperature is higher than approximately 19 C for a sufficient time how long the bypass stays on depends on the exact outside temperature DEFROST VALVE ACCESS TO CLEAN BYPASS FILTER FRESH AIR INTAKE FROM ATMOSPHERE EXHAUST TO ATMOSPHERE AIR FILTERS SUPPLY TO DWELLING HIGH BUILDING EXTRACT FROM DWELLING ELECTRICAL CONNECTIONS SUPPLY TO DWELLING GENERAL VIEW 30 210 210 30 l 1 oo hit N i e Si i 3v Et c NO AS i 300 an RIGHT HAND SIDE VIEW BACK SIDE VIEW CONDENSATE DISCHARGE The outside temperature and the inside temperature are measured in the HRU ECO 4 The development of the temperatures allows the fan to recognise a summer day The bypass will be closed automatically as soon as one of these conditions is no longer met The power with which the bypass valve disharges heat this depends on the temperature of the air inside and the temperature of the air outside It also depends on the air volume discharged by the HRU ECO 4 The rule of thumb for the HRU ECO
25. lace objects on top of the appliance Regularly inspect the appliance for visible defects If any faults are found contact an Itho Ventilation immediately The appliance must only be installed by a professionally qualified person Ensure that the electrical system to which the appliance is connected complies with applicable standards Use a multi polar switch with a minimum contact gap of 3mm to install the appliance Switch of should be off the appliance at the main switch a ifthe appliance does not function take out full stop correctly b before cleaning the outside of the appliance c ifthe appliance is not to be used for any length of time Be careful to avoid damaging the electric circuit Do not use the appliance to control activation of water heaters room heaters etc nor should it discharge into the flues of any such appliances Ensure that the appliance discharges into a single duct dedicated to this product which is routed to the outside The air to be extracted from the dwelling must be clean i e free of grease soot chemical and corrosive agents explosive or flammable mixtures Keep the appliance intake and outlet grilles free to ensure optimum airflow at all times To ensure that the installation complies with the applicable CE Directives the electric connections of the heat recovery unit HRU ECO 4 should be installed according to the applicable standards The device has to be assembl
26. lanation 1 Check whether the wall socket has supply voltage and repair if required Check the operation of the unit 2 Check whether the plug has been fitted correctly to the unit connector Check the operation of the unit 3 Remove the motor module refer to Section 4 3 Check the other parts to find the cause of the trigge ring of the fuse Correct any defects and replace the fuse T2A 250 V 20 x 5 mm Check the operation of the unit 4 Remove the motor module refer to Section 4 3 Check whether the fan connector had been fitted correctly to the printed circuit board Check the operation of the unit 5 Remove the motor module refer to Section 4 3 Check whether the connector of the intake fan has not been exchanged with the connector of the dis charge fan chapter 5 4 Check the operation of the unit 6 Switch the control of the intake fan off in case of very low outside temperature to avoid frost problems When the outside temperature rises again the intake fan will automatically be switched on This is not a fault 7 Moisture may enter the heat exchanger due to diffe rences in air temperature This is normal Connect the condensation discharge 8 Remove the obstacle in the condensation discharge 9 Insulate the ducts thermally and make sure they are damp proof 10 Usea rain tight thermally insulated and damp proof roof lead through 11 Ensure the unit is mounted on a wall with a mass of at least 200 kg m 12 Clo
27. lation capacity for the low mode and the high mode The medium mode is set to the arithmetic average of the low mode and the high mode As standard the high mode is set to 225m3 h The ventilation volume may only be increased using the trimmer if and when the required air volume is not attained when the valves are set and the valves are already completely open This ensures that as little energy as possible is used 3 8 Control using RF Switch The HRU ECO 4 can be operated using the RF Switches These are used to switch between low medium and high mode The low mode is used at night the medium mode during the day when there are people at home and the high mode when cooking showering or bathing The RF Switches are often placed in the wet rooms kitchen bathroom etc The RF operation switch can be used to operate the ventilation from multiple locations refer to Section 3 10 Up to 20 wireless RF operation switches can be used to operate the HRU ECO 4 The RF operation switch transmitter can be used to set the ventilation unit to one of the three ventilation modes capacities low medium and high The switch also has a timer The ventilation unit is switched to high mode for a predetermined time when the timer button is pressed The timer automatically switches the ventilation unit to low mode after the time has elapsed The time setting depends on the number of times the timer button is pressed consecutively
28. lve This would hinder the proper operation of the frost protection 5 Specifications Capacity Pressure Power Current Voltage Cos phi Thermal efficiency m3 h Pa W A V E Mode Minimum mode 50 10 8 0 05 230 0 07 98 Mode 1 Low mode 75 20 12 0 1 230 0 55 98 Mode 2 Medium mode 150 40 29 0 24 230 0 53 96 2 Mode 2 Medium mode 150 80 38 0 31 230 0 53 96 2 Mode 3 High mode 225 100 74 0 59 230 0 59 94 Mode 3 High mode 225 150 88 0 69 230 0 56 94 Mode 3 High mode 275 100 106 0 83 230 0 56 93 Mode 3 High mode 275 150 126 0 99 230 0 56 93 Mode 3 Maximum mode 325 100 156 1 22 230 0 56 92 Mode 3 Maximum mode 325 150 176 1 36 230 0 56 92 Values to be entered in the EPC calculation according to NEN 5128 The thermal efficiency of the HRU ECO 4 has been Weight 24kg 1kg determined by TNO at 96 2 reference number TNO MEP Dimensions 848 mm H 2002KTW 534 730 mm W 479 mm D Other technical data Duct diameter 150 mm inner and Temperature efficiency with 180 mm outer equal mass flows 96 2 measured Condensation discharge diameter 40 mm outer according to NEN 5138 Degree of protection IP31 Supply voltage 230 V 5 Filter classification EUS Frequency 50 Hz Capacity graph Capacity qv dm s 10 20 30 40 50 60 70 g0 80 100 110 N N e 200 Static pressure Pst Pa Power input W E D KIC SEN ESEESEBESSESE oper C 9E QS pL Lo Nx IS Nx 25 50 75 1 00 125 150 175 200 225 2
29. se off the unused nozzle using a cap 13 Mount the sound insulation duct 14 Synchronise the valves using the air balance calculation 15 Replace the 3 position mode switch Itho Ventilation Ltd 10 Faraday Court First Avenue Centrum 100 Burton on Trent DE14 2WX T 44 0 870 460 6741 F 44 0 870 460 6742 E info itho co uk www itho co uk
30. zles for the return air connection is therefore open to the installer for both the low rise and high rise buildings It is also possible to use both nozzles which has a positive influence on the resistance of the duct system The red nozzle stop is used to close off the unused nozzle 3 6 Connecting the condensation discharge The condensation discharge piping is located at the bottom of the HRU ECO 4 Connect this properly to prevent damage to the unit by condensation The exterior diameter of the glued joint of the supplied condensation discharge coupling is 40 mm All other materials are to be procured elsewhere This condensation discharge can be mounted to a hose column using a glued joint A hose with an inner diameter of at least 20 mm should be mounted Make sure that the hose is placed sufficiently deep into the air trap at least 30 mm below water level Cut the end of the hose diagonally The condensation discharge can also be connected using PVC house sewerage material A provision to be able to refill the air trap should be added in that case Pour water into the air trap and check the condensation discharge for leakage Make sure that the air trap is not completely glued together to allow for the cleaning of the air trap 3 7 REIZE SHE The standard version of the plastic connection cover ofthe HRU ECO 4 has two potentiometers for the low mode and the high mode respectively These are used to determine the venti