        1756-IN512C-EN-P, ControlLogix Installation Instructions
         Contents
1.         e    NY 20854 M    3  Slide the locking tab down to lock the RTB  onto the module              Publication 1756 IN512C EN P   October 2000    10 ControlLogix DC  10 30V  Isolated Output Module       Check the Indicators    The indicators show individual I O status  yellow  for each point and  a bi colored LED for module  OK   red green            G gt  DC OUTPUT             3       ST 012345670                   ST 891011213415 K                   40457 M    During power up  an indicator test is done and the following occurs     e The  OK  indicator turns red for 1 second and then turns to  flashing green if it has passed the self test     e The I O status indicators turn ON for a maximum of 2 seconds  and then turn OFF                       LED This Means  Take this action   indicator    display   OK Steady The outputs are actively None  green light   being controlled by a system  processor   OK Flashing The module has passed Configure the module   green light   internal diagnostics but is  not actively controlled   OK Flashing red   Previously established Check controller and chassis  light communication has communication   timed out   OK Steady red   An unrecoverable error has   Replace the module   light occurred on the module   1 0 State Yellow The output is active  None                This completes installation of the module  Use the information below  to remove the module     Publication 1756 IN512C EN P   October 2000    ControlLogix DC  10 30V  Isolated Outp
2.      Removal and Insertion Under Power  RIUP        This module is designed so you can remove and insert it    under backplane power and field side power  When you  remove or insert a module while field side power is  applied  you may cause an electrical arc  An electrical  arc can cause personal injury or property damage  because it may    e send an erroneous signal to your system   s field  devices  causing unintended machine motion or loss  of process control    e cause an explosion in a hazardous environment   Repeated electrical arcing causes excessive wear to  contacts on both the module and its mating connector   Worn contacts may create electrical resistance     When you insert or remove the module while backplane  power is on  or you connect or disconnect the RTB with  field side power applied  an electrical arc can occur  This  could cause an explosion in hazardous location  installations  Be sure that power is removed or the area is  non hazardous before proceeding        Publication 1756 IN512C EN P   October 2000    4 ControlLogix DC  10 30V  Isolated Output Module       Understand Compliance to European Union Directive    If this product bears the CE marking  it is approved for installation  within the European Union and EEA regions  It has been designed  and tested to meet the following directives     EMC Directive    This product is tested to meet Council Directive 89 336 EEC  Electromagnetic Compatibility  EMC  and the following standards  in  whole or in par
3.    b  DC            DC 15    iq 34  3 Not used     4 Not used z  Not used O  D36 35  a   J DCI   AK   Daisy chain to other RTBs  30242 M  NOTES4  All terminals with the same name are connected together on the module  For       example  DC     can be connected to either terminal marked DC 15    2  When you use the second DC 15     terminal to daisy chain to other RTBs  always  connect the daisy chain to the terminal directly connected to the supply wire  as  shown in the example above    3  Outputs can be wired ina sink or source configuration as shown above    4  If separate power sources are used  do not exceed the specified isolation voltages     After completing field side wiring  secure the wires in the strain relief  area with a cable tie     Publication 1756 IN512C EN P   October 2000    8 ControlLogix DC  10 30V  Isolated Output Module       Assemble the Removable Terminal Block and the Housing  1  Align the grooves at the bottom of the housing with the side edges of the RTB          Groove  Side edge of the RTB    Strain relief area    Side edge of the RTB    2  Slide the RTB into the housing until it snaps into place  20858 M    Install the Removable Terminal Block onto the Module   The RTB is designed to support Removal and Insertion    WARNING   Under Power  RIUP   However  when you remove or  insert an RTB with field side power applied  unintended    machine motion or loss of process control can  occur  Exercise extreme caution when using this feature        It is
4.  If this product contains batteries  they must only be  changed in an area known to be nonhazardous        Publication 1756 IN512C EN P   October 2000    ControlLogix DC  10 30V  Isolated Output Module 15       Informations sur l utilisation de cet   quipement en environnements  dangereux      Les produits marqu  s    CL I  DIV 2  GP A  B  C  D    ne conviennent  qu   a une utilisation en environnements de Classe I Division 2  Groupes A  B  C  D dangereux et non dangereux  Chaque produit est  livr   avec des marquages sur sa plaque d   identification qui indiquent  le code de temp  rature pour les environnements dangereux  Lorsque  plusieurs produits sont combin  s dans un syst  me  le code de  temp  rature le plus d  favorable  code de temp  rature le plus faible   peut   tre utilis   pour d  terminer le code de temp  rature global du  systeme  Les combinaisons d     quipements dans le systeme sont  sujettes 4 inspection par les autorit  s locales qualifi  es au moment de  l installation     RISQUE D   EXPLOSION    e Couper le courant ou s   assurer que l   environnement       est class   non dangereux avant de d  brancher  l   quipement    e Couper le courant ou s   assurer que l   environnement  est class   non dangereux avant de d  brancher les  connecteurs  Fixer tous les connecteurs externes  reli  s    cet   quipement    l   aide de vis  loquets  coulissants  connecteurs filet  s ou autres moyens  fournis avec ce produit       La substitution de composants peut rendre 
5.  Software configurable       RTB Screw Torque  Cage clamp     4 4 inch pounds  0 4Nm  max        RTB Keying    User defined mechanical keying       RTB and Housing    36 Position RTB  1756 TBCH or TBS6H         Screwdriver Blade Width for RTB    1 8 inch  3 2mm  max        Environmental Conditions  Operating Temperature  Storage Temperature  Relative Humidity    0 to 60  C  32 to 140  F    40 to 85  C   40 to 185  F   5 to 95  noncondensing          Conductors Wire Size 22 14 gauge  2mm2  stranded   3 64 inch  1 2mm  insulation max   Category 123  Agency Certification     when product or packaging is  marked        Listed Industrial Control Equipment    Certified Process Control Equipment    Certified Class    Division 2  Group A  B  C  D   lt  gt  Approved Class I  Division 2  Group A  B  C  D  C     Marked for all applicable directives       Marked for all applicable acts  N223          level installation manual     Maximum wire size will require extended housing   1756 TBE   Use this conductor category information for planning conductor routing as described in the system    Refer to publication 1770 4 1    Industrial Automation Wiring and Grounding Guidelines           Additional Notes    The ControlLogix system must be mounted within a suitable enclosure to  prevent personal injury resulting from accessibility to live parts  The interior of  this enclosure must be accessible only by the use of a tool     This industrial control equipment is intended to operate in a Pollut
6.  recommended that field side power be removed  before installing the RTB onto the module        When you remove or insert a module while field side  power is applied  you may cause an electrical arc  An  electrical arc can cause personal injury or property  damage because it may    e send an erroneous signal to your system   s field  devices  causing unintended machine motion or loss  of process control    e cause an explosion in a hazardous environment   Repeated electrical arcing causes excessive wear to  contacts on both the module and its mating connector   Worn contacts may create electrical resistance    When you insert or remove the module while backplane  power is on  or you connect or disconnect the RTB with  field side power applied  an electrical arc can occur  This  could cause an explosion in hazardous location  installations  Be sure that power is removed or the area is  non hazardous before proceeding        Publication 1756 IN512C EN P   October 2000    ControlLogix DC  10 30V  Isolated Output Module 9       Before installing the RTB  make certain   e field side wiring of the RTB has been completed   e the RTB housing is snapped into place on the RTB   e the RTB housing door is closed   e the locking tab at the top of the module is unlocked     1  Align the side and top  bottom RTB guides with the  side  top and bottom module guides                       20853 M       2  Press quickly and evenly to seat the RTB on the  module until the latches snap into place 
7. Installation Instructions    ControlLogix  DC  10 30V  Isolated Output Module     Catalog Number 1756 0B16        To  See page   Obtain a User Manual          Identify the Module Components       Prevent Electrostatic Discharge       See Removal and Insertion Under Power  RIUP        Understand Compliance to European Union Directive       Note the Power Requirements   Install the Module   Key the Removable Terminal Block Interface Module  Wire the Module   Assemble the Removable Terminal Block and the Housing                   Install the Removable Terminal Block onto the Module  Check the Indicators  Remove the Removable Terminal Block from the Module             Remove the Module  See 1756 0B161 Specifications  Hazardous Location information            a             EIN  Nl 2 al               ao  A  ww  nN            Obtain a User Manual    This product also has a user manual  pub  no  1756 6 5 8   To view it   visit www ab com manuals or www theautomationbookstore com  You can also purchase a printed manual by        e contacting your local distributor or Rockwell Automation  representative    e visiting www theautomationbookstore com and placing  an order    Publication 1756 IN512C EN P   October 2000    2 ControlLogix DC  10 30V  Isolated Output Module       e calling 800 963 9548  USA Canada  or 001 320 725 1574   outside USA Canada     Identify the Module Components   You received the following components with your order   e 1756 OB16I module  e Removable Terminal Bloc
8. cet    quipement inadapt      une utilisation en  environnement de Classe 1  Division 2    e S assurer que l   environnement est class   non  dangereux avant de changer les piles        Publication 1756 IN512C EN P   October 2000    Reach us now at www rockwellautomation com    Wherever you need us  Rockwell Automation brings together leading  brands in industrial automation including Allen Bradley controls    Reliance Electric power transmission products  Dodge mechanical power  transmission components  and Rockwell Software  Rockwell Automation s  unique  flexible approach to helping customers achieve a competitive  advantage is supported by thousands of authorized partners  distributors       and system integrators around the world    Aten Bradiey   EME Doce  Americas Headquarters  1201 South Second Street  Milwaukee  WI 53204  USA  Tel   1  414 382 2000  Fax  1  414 382 4244 ma Rockwell  European Headquarters SA NV  avenue Hermann Debroux  46 1160 Brussels  Belgium  Tel   32  2 663 06 00  Fax  32  2 663 06 40 ockwe   Asia Pacific Headquarters  27 F Citicorp Centre  18 Whitfield Road  Causeway Bay  Hong Kong  Tel   852  2887 4788  Fax  852  2508 1846 Automation  Publication 1756 IN512C EN P   October 2000 PN 957424 14    Supersedes Publication 1756 5 12   September 1999    2000 Rockwell International Corporation  Printed in USA    
9. ch  9 5mm  maximum length of  wire  wire     2  Insert the screwdriver into the inner hole 2  Insert the wire into the open terminal   of the RTB  3      Turn the screw clockwise to close the  terminal on the wire                                      3  Insert the wire into the open  terminal and remove the      screwdriver  20860 M    SE    Publication 1756 IN512C EN P   October 2000                     icy             jen        ment  pen    20859 M    I          ControlLogix DC  10 30V  Isolated Output Module 7       Wire the Module    You can only connect wiring to your module through an RTB or IFM   The example below shows how to wire the module                                                                                                                                                                                      1756 0B161    Isolated sourcing  Isolated wiring Ne output wiring  DC 0       DC 0    2 1 4 OUT 0      DC 0   DC 1    Io OUT 1  a   3 p A  DC 2        DC 2   is s    ourz     o DC 2     DC 3    AY  8     OUT 3  q J i       DC 4    G10 9 OUT 4  Sinking output wiring DC 5    12 1114 OUT 5  DC 6     ons    Def 4 13 OUT 6 Oo DC6     DC 7    16 15    OUT 7  Jumper bar DC 8    Dhs 176 OUT 8   Cut to length  DC 9    D 196 OUT 9  DC 10    92 21 D OUT 10       DC 1   A T       Non isolated  r Be 2D   a 1   Non isolated  wiring DC 12    26 zo OUT 12        e sourcing  DC 13       Eh 27 OUT 13   e output  DC 14    D 2 OUT 14 j  e ing  DC 15    q 32 310 OUT 15 ___
10. ion Degree  2 environment  in overvoltage category II applications  as defined in IEC  publication 664A  at altitudes up to 2000 meters without derating     Publication 1756 IN512C EN P   October 2000    14 ControlLogix DC  10 30V  Isolated Output Module       Hazardous Location information    The following information applies when operating this equipment in  hazardous locations     Products marked    CL I  DIV 2  GP A  B  C  D    are suitable for use in  Class I Division 2 Groups A  B  C  D  Hazardous Locations and  nonhazardous locations only  Each product is supplied with markings  on the rating nameplate indicating the hazardous location  temperature code  When combining products within a system  the  most adverse temperature code  lowest    T    number  may be used to  help determine the overall temperature code of the system   Combinations of equipment in your system are subject to  investigation by the local Authority Having Jurisdiction at the time  of installation     warning   EXPLOSION HAZARD    e Do not disconnect equipment unless power has       been removed or the area is known to be  nonhazardous    e Do not disconnect connections to this equipment  unless power has been removed or the area is  known to be nonhazardous  Secure any external  connections that mate to this equipment by using  screws  sliding latches  threaded connectors  or  other means provided with this product    e Substitution of components may impair suitability  for Class I  Division 2    e
11. k  RTB  door label    If you did not receive these components  contact your Rockwell  Automation sales office     This module mounts in a ControlLogix    chassis and uses a  separately ordered RTB or a Bulletin 1492 Interface Module  IFM  to  connect all field side wiring     This module uses one of the following RTBs    e 1756 TBCH 36 position Cage clamp RTB   e 1756 TBSG6H 36 position Spring clamp RTB  Use an extended depth cover  1756 TBE  for applications with heavy  gauge wiring or requiring additional routing space  When using an    IFM  consult the documentation that came with it to connect  all wiring     IMPORTANT Before you install your module  you should  have already     e installed and grounded a 1756 chassis and  power supply        e ordered and received an RTB or IFM and its  components for your application        Publication 1756 IN512C EN P   October 2000    ControlLogix DC  10 30V  Isolated Output Module 3       Prevent Electrostatic Discharge       Electrostatic discharge can damage integrated circuits or  ATTENTION    semiconductors if you touch backplane connector pins   Follow these guidelines when you handle the module   e Touch a grounded object to discharge  static potential   e Wear an approved wrist strap grounding device      Do not touch the backplane connector or connector  pins      Do not touch circuit components inside the module   e If available  use a static safe work station   e When not in use  keep the module in its static shield  box   
12. lLogix Chassis       Backplane Current    350mA   5 1V de  amp  2 5mA   24V de   1 8W Total backplane power              Max  Power Dissipation  Module    3 gw   60  C  Thermal Dissipation 12 28 BTU hr  Output Voltage Range 10 30V de       Output Current Rating  Per Point  Per Module    2A max    30  C  amp  1A max    60  C  Linear derating   8A max    30  C  amp  4A max    60  C  Linear derating        Surge Current Point    4A for 10ms each  repeatable every 2s       Minimum Load Current    1mA per point             Max  On State Voltage Drop 1 2V de   2A  Max  Off State Leakage Current 0 5mA per point  Output Delay Time   OFF to ON 1ms max    ON to OFF 2ms max        Scheduled Outputs    Synchronization within 16 7s max   reference to the  Coordinated System Time       Configurable Fault States  Point    Hold Last State  ON or OFF  OFF is the default        Configurable States in Program  Mode Point    Hold Last State  ON or OFF  OFF is the default        Fusing       Not protected   Fused IFM is recommended to protect  outputs  See publication 1492 2 12        Publication 1756 IN512C EN P   October 2000    Con    rolLogix DC  10 30V  Isolated Output Module 13          Reverse Polarity Protection    None  If module is wired incorrectly  outputs may be  damaged         Isolation Voltage  Channel to channel    User to system    100  tested at 2546V dc for 1s   250V ac max  continuous voltage between channels   100  tested at 2546V dc for 1s       Module Keying  Backplane    
13. t  documented in a technical construction file     e EN 50081 2 EMC   Generic Emission Standard  Part 2    Industrial Environment   e EN 50082 2 EMC   Generic Immunity Standard  Part 2    Industrial Environment    This product is intended for use in an industrial environment     Low Voltage Directive    This product is tested to meet Council Directive 73 23 EEC Low  Voltage  by applying the safety requirements of EN 61131 2  Programmable Controllers  Part 2   Equipment Requirements and  Tests     For specific information required by EN 61131 2  see the appropriate  sections in this publication  as well as the following Allen Bradley  publications     e Industrial Automation Wiring and Grounding Guidelines   publication 1770 4 1    e Automation Systems Catalog  publication B111    This equipment is classified as open equipment and must be installed   mounted  in an enclosure during operation as a means of providing  safety protection     Publication 1756 IN512C EN P   October 2000    ControlLogix DC  10 30V  Isolated Output Module 5       Note the Power Requirements  This module receives power from the 1756 chasis power supply and  requires 2 sources of power from the backplane       350mA at 5 1V de   e 2 5mA at 24V de    Add this current power value  1 8W  to the requirements of all other  modules in the chassis to prevent overloading the power supply     Install the Module    You can install or remove the module while chassis power is applied     The module is designed to s
14. upport Removal and  Insertion Under Power  RIUP   However  when  you remove or insert an RTB with field side power  applied  unintended machine motion or loss of    process control can occur  Exercise extreme  caution when using this feature           1  Align circuit board with top and 2  Slide module into chassis until  bottom chassis guides  module locking tabs    click           Locking tab    Printed    Circuit    Board    AN    20861 M       Publication 1756 IN512C EN P   October 2000    6 ControlLogix DC  10 30V  Isolated Output Module       Key the Removable Terminal Block Interface Module  Wedge shaped keying tabs and U shaped keying bands came with  your RTB to prevent connecting the wrong wires to your module   Key positions on the module that correspond to unkeyed positions    on the RTB  For example  if you key the first position on the module   leave the first position on the RTB unkeyed     Key the Module Key the RTB IFM  1  Insert the U shaped band as shown  1  Insert the wedge shaped tab with rounded edge first   2  Push the band until it snaps in place  2  Push the tab until it stops                          Wedge shaped tab    Z       U shaped  bands  20850 M 20851 M  Reposition the tabs to rekey future module applications   Wire the Removable Terminal Block  Wire the RTB with a 1 8 inch  3 2mm  maximum flat bladed  screwdriver before installing it onto the module   Spring Clamp RTB Cage Clamp RTB  1  Strip 7 16 inch  11mm  maximum length of 1  Strip 3 8 in
15. ut Module 11       Remove the Removable Terminal Block from the Module       Shock hazard exists  If the RTB is removed from  the module while the field side power is applied   the module will be electrically live  Do not touch  the RTB   s terminals  Failure to observe this caution  may cause personal injury     The RTB is designed to support Removal and  Insertion Under Power  RIUP   However  when  you remove or insert an RTB with field side power  applied  unintended machine motion or loss of  process control can occur  Exercise extreme  caution when using this feature  It is  recommended that field side power be removed  before removing the module     When you insert or remove the module while  backplane power is on  or you connect or  disconnect the RTB with field side power applied   an electrical arc can occur  This could cause an  explosion in hazardous location installations  Be  sure that power is removed or the area is  non hazardous before proceeding        Before removing the module  you must remove the RTB     1  Unlock the locking tab at the 2  Open the RTB door and pull the    top of the module  RTB off the module                 20855 M    Publication 1756 IN512C EN P   October 2000    12 ControlLogix DC  10 30V  Isolated Output Module       Remove the Module    1  Push in top and bottom locking tabs     2  Pull module out of the chassis        1756 0B16l Specifications       Number of Outputs    16  individually isolated        Module Location    1756 Contro
    