Home
        Installation & Operating Instructions
         Contents
1.    e Slide the top secondary air control to open  Open the primary air control    e Lay a reasonable quantity of firelighters or rolled up newspapers on the grate  if necessary also use  dry kindling wood  Place a small quantity of solid fuel on top    e Light the newspaper or firelighters using a long taper and close the door    e When the fire is burning fiercely  add further fuel    e When the stove body is hot  close the top secondary air control    e The burning rate can now be adjusted by the primary air control     Re fuelling  See figure 4A  amp  4B    e Open the primary air control    e Open the glass door and add fuel   To load fuel  the door should be opened slowly  avoiding a  sudden  rush of intake air  so that smoke does not escape into the room       e Leave the primary air control open for a few minutes to allow the initial volatiles in the fuel to  burn    e Adjust the primary air control to the desired position    Fuel overloading  Never overload the firebox  The maximum amount of fuel specified in this   manual should not be exceeded  overloading can cause damage and smoke     Figure 4 A shows the air controls and riddling control when using the standard Multi Fuel stove in  smoke controlled zones  This configuration is suitable for wood and Ancit fuel in smoke controlled  zones  Important  If burning wood in smoke control zones the tertiary air control must be set to  the fully open position therfore leaving the tertiary air intake fully open and unrestric
2.   Evacuate all  people from the room until all odours have cleared  If for any reason the odours do not clear   extinguish the fire  amp  seek professional assistance     Enameled products   Condensation may form on the surface of the stove the first few times it is used  This must be wiped    off to prevent permanent stains forming when the surface heats up  taking adequate precautions and  protection from the hot stove surface     Air Control  See figure 4    Always use the key provided to operate the air controls  The amount of heat emitted by the stove is regulated using three air controls for smokeless fuel    burning and wood burning  however the tertiary air control must be set to the fully open position    therfore leaving the tertiary air intake fully open and unrestricted when burning wood     The primary air supply  where air passes up through the riddling grate  is controlled using the lever  air control situated below the glass on the front door  turn clockwise to close and anti clockwise to  open    The secondary air  air wash system   which is supplied to the combustion over the glass  is  controlled using the upper air control lever  move to the left to close and to the right to open    A third air inlet  normally named tertiary air  provides a constant  pre heated air supply to the  combustion just above the fire  this 1s controlled using the push  pull air control below the ash lip  between the legs of the stove  This air supply normally does not require to 
3.  263  C  Wood     264  C  Ancit     Technical data with optional Stoveasy grate     Material  Cast iron   Finish  High temp resistant paint  Fuel  Wood  Approved wood logs   Log length  30cm maximum    Stove outlet collar positions  Top and rear    Stove collar dimension  Internal diameter 125mm   113cm2 cross section    Approx  weight  106kgs    Dimensions  distances etc  Figure 2    Technical data according to EN 13240 A2 2004     Technical data according to EN 13240 A2 2004     Nominal heat output  4 8kw  Wood     Flue gas mass flow  4 7 g sec  Wood   Recommended chimney draught  12 Pa  Efficiency  78 4   Wood   CO emission  13  O     0 31   Wood   Flue gas temperature  248  C  Wood     Operational mode  Intermittent    2 0 Installation    2 1 Unpacking the stove    After removing the outer packaging  unbolt the combustion chamber from the wooden pallet and  place it gently on its back  The cardboard packaging can be placed underneath to prevent marring   Remove the leg pack from the stove and bolt each leg securely to the underside of the base on the  combustion chamber  using the bolts provided  found inside the stove   Note  There are lower bolts  supplied for fitment into holes in the base of each leg  these are adjustable to allow level adjustment  of stove to uneven surfaces    We recommend that two people perform the assembly and installation procedure     2 2 Installing this stove    The stove and chimney installations MUST comply with all current National and Loca
4.  DO    Flue Cover   a Gasket 2    Plate        A   464185   5 BE ER 23   Legs      A AA    IE ES  EL IS E BE  KOM IR  ns AAC IA      m CI    EN    cI                   5    A   FlatGasket   NT      Countersunk Inner Hexagon  BE SEE      55                EE HE    UU  p    g       Y                    cD   z        3  El   UN  cD    gt   O     ON  K    ON   gt   am  Z  aa  NY  O  ON  ya         O  N       E  ON      S  D    Y  a  lao        O  a    No      No  x  00  ON  n  x  Y  00  Ye     O  o v    N  E  E     A     gt   Z  Y       D   E  N  N   D        aD       O     UN   gt   Z  Dd    E  z 3  N O     gt        O  N e  Nn       3 z  O z  O          2 O     Z    00  00                y  N          N   lt             N  S  OD      gt  mua  O     2     ae      E  O  ON  E     S     5   aa     on      Yo  Ne           Z    T          z        3 7 Parts list for Knightsbridge SE and Highgrove SE with optional Stoveasy grate        i a   iron    ee n eS    Stainless Steel Hexagon  INE Bolts M6 20 4 RH Side Panel ETE 4      Gasket   D6 18 64 10  10 25       gt  Steel Countersunk  METIO Bolts MID 2 Air oo  Cover JUN zs    a Head Bolts        3    Sin Brick 4         Quantity   Number Quantity    ls     es     ls     er pi     EI         MEA IC oy   BEER a       steel  stainless steel blanking knob   knob E eS    Countersunk Inner Hexagon   Fs AFART     Primary Air Cover   Air Cover   2208338544      i    10     Grate Frame   Frame   542   42   1             gt       o es        HE
5.  external atmosphere    This also applies during firing  when the need is greatest     The weather is clear and there is a good wind     The chimney is of the proper height  i e  minimum 4 meters over the stove and the termination  adequately clear of the roof line   e The room that the stove is installed is adequately ventilated     2 9 1 Handle    This stove is supplied with one bakelite handle for operating the fire door with an optional stainless    steel handle for customer preference     Handle assembly    This stove is supplied with a bakelite handle when manufactured  If your preference is to use the  optional stainless steel handle  then please refer to the handle assembly picture for instructions on  how to change  The stove and handle will become very hot therefore it is recommended that an  approved five fingered heat proof glove of the correct size for each users hand 1s used to operate    this stove     Bakelite Handle     Step 1  Position Bakelite handle  screw and  washer fixings  into correct position with  steel elbow  Tighten screw securely        Stainless Steel Handle     The optional stainless steel handle is designed  to be of plug in and plug out type  this will  enable the handle to be removed when not  operating the door to avoid excessive heat  transfer into the handle when the stove is hot  due to the heat transfer    For aesthetic purposes there is a handle grub  screw supplied enabling the handle to be  fixed into position when the stove is cold 
6.  final disposal  If the ashes are disposed of by burial in soil or otherwise locally dispersed they  should be retained in the closed container until all cinders have completely cooled     Figure 5       Ash pan key  This key to be used also for operating    all air controls    3 3 1 Maintenance    The stove should be regularly serviced by an approved and competent engineer but some simple  procedures are given below which the user can also adopt     3 3 2 Cleaning glass    This product is equipped with an air wash for the glass  Air is sucked in through the air vent above  the stove and down along the inside of the glass    However  some soot will always stick to the glass  but the quantity will depend on the local draught  conditions and adjustment of the air wash vent  Most of the soot layer will normally be burned off  when the air wash vent is opened all the way and a fire is burning briskly in the stove    Good advice  For normal cleaning  when the stove is extinguished and cold  moisten a paper towel  with warm water and add some cooled ash from the burn chamber  Rub it over the glass and then  clean the glass with clean water  amp  then dry  If it is necessary to clean the glass more thoroughly we  recommend using a glass cleaner  follow manufacturer   s instructions      3 3 3 External surface cleaning    The cast surface of the stove is painted with heat resistant paint  It is best maintained by simply  vacuuming it with a soft brush attachment or wiping it down wit
7.  outside  Other factors that can influence the level of draft  include the length of the flue  insulation of the chimney  adverse weather conditions or tall buildings  or trees nearby the flue terminal     Poor draft occurs when    e The atmospheric temperature difference is too low  e g  a poorly insulated chimney  If the  chimney is excessively cool  it may help to    prime    the flue before the fire is lit  Just place a  screwed up sheet of newspaper in the flue way of the stove and ignite     The outside temperature is too high  e g  during the summer months     There 1s no air movement  wind  outside     The chimney is not tall enough  with the result that the terminal sits in the lee of the roof surface  or in the vicinity of tall trees or neighboring buildings  These conditions are also associated with  downdraft where the flue gases are pushed back down the chimney     Flue draft is diluted by residual air entering the chimney  e g  due to inadequate fluepipe joints  or leaks at the cleaning door or flue collar     Unsealed  unused fireplaces are connected to the chimney   e The flue is blocked  e g  by soot  due to inadequate cleaning  loose debris or even a birds nest     The room to which the stove is installed is too tightly sealed   See section on Fresh air supply      A good draft is achieved when   e The temperature difference between the flue way or chimney and outside atmosphere is high      Higher temperature in flue way or chimney and cooler temperature to
8. 002 must be used and such persons must be supervised at all times    It is also recommended that all other people should use a fireguard in accordance with BS  8423 2002 at all times when the stove is alight or hot    e Use the long key provided for operating and adjusting all air controls  including   the riddling control  amp  removal  amp  replacement of ash pan when necessary           e It is recommended that when operating this stove an approved heat resistant five fingered glove is  used of the correct size for the user    e Where the chimney is believed to have previously served an open fire installation it is possible  that the higher flue gas temperatures from a closed appliance may loosen deposits that were  previously firmly adhered  with the consequent risk of flue blockage  It is therefore recommended  that the chimney be swept a second time within a month of regular use after installation    e Chimneys and connectors should be cleaned at least twice a year  by an approved Chimney Sweep   At least once before heating season and at least once after    e If the stove is to be left unused for a prolonged period of time then it should be given a thorough  clean to remove ash and unburned fuel residues  To enable a good flow of air through the  appliance to reduce condensation and subsequent damage  leave the air controls fully open    e It is important that the flue connection  any appliance baffles or throat plates and the chimney are  swept prior to lighting up af
9. M NE I   fo                ERE Primary Air Shutter 2627404 ERIE EEN HEER Air Wash Plate pes TO      BlankingPlate   Plate en Air   Back Air Damper   0     E   E Inner    is ER  Bolts M6 8 Air Control  Countersunk Inner Hexagon  Bolts M6 20 air funnel  Banking Plate  Spring 51 Locking Bar  Flue Cover  M Gasket 2 T Plate      HingeA   A   464185   5    a ee RE CH ER    46   Ash pan Lifter L 0 36    po    Nn    23   Legs       77   mwregmosrope   os   1                       4mm  D6 22    M8 25    Hexagon Bolts    5    Flat Gasket    5    A Countersunk Inner Hexagon  Bolts    Inner Hexagon Spanner                        a    NW N     o      ER AA ONR  a EE A  u TE A Si wee    PI  CAR                 Q       q      ON   gt   N  qe   oO   gt   O       NY       ae   S  O  B   or  O  Ea          3  aa  NY  OD   gt   O     ON     E  ON     am  Y  aa  UN  cD   ON  yo    gt  mua     O  N            ON      E  D    Z       lao        O  a    No  O  No  x  00  ON  on  x  Y  00  Ye  E  O    v    N  E  E     A    CO  00           _   lt   A     O  LV a    lt      O   gt       DM     EE    A  2 2  O  N E  E ES  a U  A o    zE   oO  5 5      EL  Ba    bp  2     S x  Sh  su  Z     o 5     0     8   Og          WMAN    FIREPLACES LTD    Address  Units 6    7  Rawreth Barns  Dollyman s Farm  Doublegate Lane  Rawreth     Wickford  Essex  SS11 SUD   Tel  01268 763586  Fax  01268 762366       
10. WMAN    FIREPLACES LTD    Knightsbridge SE  amp  Highgrove SE    Multi fuel burning stoves with optional wood burning stoveasy grate           Installation  amp  user instructions     To be left with customer         KN IGHTBRIDGE SE    CE       HIGHGROVE SE    Reference  NSS   6 Issue 1 Date  8th January 2014     Pre installation checks  amp  general safety notes     The Clean Air Act 1993 and Smoke Control Areas    HETAS Ltd approval    Installation introduction including technical data     1 0 Technical data    2 0 Installation introduction    2 1 Unpacking the stove   22 Installing the stove   2 2 1 Assembling the tertiary air control   2 2 2 Assembling the baffle  log grate  air funnel and banking bar  2 3 Stove placement   clearance requirements   2 4 The chimney   Li   Pipe connections   2 6 Connecting to a masonry chimney   Zit Connecting to a steel chimney   2 8 Ventilation   Fresh air supply    2 9 Draft conditions   2 9 1 Assembling the handle   2 9 2 Commissioning and handover   3 0 User Manual   3 1 Choice of fuel   3 2 Use   3 2 1 Use with wood   3 2 2 Use with solid fuel   3 3 Ash Removal   3 3 1 Maintenance   3 3 2 Cleaning glass   3 3 3 External surface cleaning   3 3 4 Gaskets   3 4 Operational problems     troubleshooting   3 5 Replacement parts   3 6 Parts list for Knightsbridge SE  amp  Highgrove SE multi fuel  IT Parts list for Knightsbridge SE  amp  Highgrove SE with optional Stoveasy grate    Pre installation checks Y general safety notes    Installati
11. and  not being used        2 9 2 Commissioning and handover    e Ensure all parts are fitted in accordance with these instructions    e On completion of the installation allow a suitable period of time for any fire cement and  mortar to dry out  before lighting the stove  Once the stove is under fire check all seals for  soundness and check that the flue is functioning correctly and that all products of  combustion are vented safely to atmosphere via the chimney terminal    e On the completion of the installation and commissioning ensure that the operating  instructions for the stove are left with the customer  Ensure to advise the customer on the  correct use of the appliance and warn them to use only the recommended fuel for the stove    e Advise the user what to do should smoke or fumes be emitted from the stove     3 0 User Manual    WARNING     e This stove is a high heat producing appliance and may cause severe  burns  amp  injury if touched to any part    e Do not touch the surface of this stove when hot  This stove may still be hot even after the fire is  extinguished    e This stove gets very hot when burning and also remains very hot for some time even when the fire  is extinguished  therefore adequate protection must be provided  particularly in situations where  there is a safety risk to children  aged and the infirm  When using this stove in situations where  children  aged and   or infirm persons are present a fireguard manufactured in accordance with BS  8423 2
12. ases are released   when the wood is ignited and heated up  For this reason  it is important that the gases are ignited   quickly after stoking  If the wood just lies smoldering  especially after re stoking  a lot of smoke is   created  which  in the worst case  may cause an explosive ignition of the gasses  resulting in damage   to the stove    In order to ignite the gases that are released from the wood  and to keep clear  lasting flames during   the combustion process  it is important to let in the required quantity of oxygen  air supply  at all   times  The setting of the air supply  the method of ignition and the lighting intervals depend on the   draught in the chimney  the wind and weather  the amount of heat required  amp  fuel  etc  This means   that 1t may take some time before you get to know the correct functioning of the stove under any   given circumstances    Note   To load fuel  the door should be opened slowly  avoiding a sudden   rush of intake air  so that smoke does not escape into the room      Operation with door left open    Operation with the door open can cause excessive smoke  The appliance must not be operated with  the appliance door left open except as directed in the instructions    Operation with the air controls or appliance dampers open can cause excess smoke  The appliance  must not be operated with air controls  appliance dampers or door left open except as directed in the  instructions     3 2 2 Use with solid fuel  See figure 4    Lighting
13. be caustic  amp  should not be allowed to come into contact with skin  Refer  to manufacturers instructions    This stove contains no asbestos  If there is any situation or possibility of disturbing any    asbestos during installation seek professional advice    Both an installation manual with technical data and a manual on general use and  maintenance are enclosed with this product  The installation can only be used after it has  been inspected by a qualified inspector  A name plate of heat resistant material is affixed  to this product  This contains information about identification and documentation for the  product     The Clean Air Act 1993 and Smoke Control Areas    Under the Clean Air Act local authorities may declare the whole or part of the district of the  authority to be a smoke control area  It is an offence to emit smoke from a chimney of a  building  from a furnace or from any fixed boiler if located in a designated smoke control area   It is also an offence to acquire an  unauthorised fuel  for use within a smoke control area unless  it is used in an  exempt  appliance   exempted  from the controls which generally apply in the  smoke control area      The Secretary of State for Environment  Food and Rural Affairs has powers under the Act to  authorise smokeless fuels or exempt appliances for use in smoke control areas in England  In  Scotland and Wales this power rests with Ministers in the devolved administrations for those  countries  Separate legislation  t
14. be regulated  Normally it  will be necessary to keep this air supply open  The tertiary air control must be set to the fully open  position therfore leaving the tertiary air intake fully open and unrestricted when burning wood        The exact positioning of the air controls to achieve optimum burn for the Knightsbridge SE and  Highgrove SE will depend on many factors such as weather conditions  chimney size and local  topography  However  to give some guidance  if you adjust your settings so that two medium sized  logs  total weight 1 5kg  or half this weight of smokeless fuel burn for about an hour before needing  to refuel  then the appliance is operating at about 4 9Kw  This is the maximum amount of fuel that  should be used     3 2 1 Use with wood  See figure 4    Important  The Tertiary air control must be set to the fully open position therfore leaving the    tertiary air intake fully open and unrestricted when burning wood     Lighting  amp  re fuelling    Very Important     1  To achieve clean burning and maximize the performance and efficiency of the appliance it is  important to raise the temperature of the stove and chimney as quickly as possible  Thus when  lighting the appliance  the technique is to start with a small amount of kindling with all air  controls fully open and maybe the door slightly ajar  Then after a few   5  minutes  some larger  pieces of wood should be added  Only when these have been well alight and the flames dying  down  should the normal s
15. bout an hour before  needing to refuel  then the appliance is burning at about 5kw     Please note that HETAS LTD Appliance approval only covers the use of wood logs and approved  smokeless fuels on this appliance  HETAS LTD Approval does not cover the use of other fuels  either alone or mixed with the recommended fuels above  nor does it cover instructions for the use  of other fuels     Not recommended as fuel    Green or damp wood reduces stove efficiency and soils the glass  the internal walls and the flue   soot  tar  etc      Used timber  Burning treated wood  railway sleepers  telegraph poles  off cuts of plywood or chip  board  pallets  etc   quickly clogs the flue ways  soot  tar   etc  pollutes the environment  pollution  and smell   etc  and cause the fire to burn too quickly and overheat       Green wood    and    recovered wood    can eventually cause a chimney fire     Prohibited fuel    Plastic bags and any form of bituminous coal or petroleum based coke  Do not use the appliance as  an incinerator or use any liquid fuels  This is very dangerous  may damage the product and  pollute the atmosphere     3 2 Use    Odours when using the stove for the first time    Painted products   The stove may emit an irritating gas when used for the first time  and it may smell a little  The gas    is not toxic  but the room should be thoroughly ventilated  Let the fire burn with a high draught  until all traces of the gas have disappeared and no smoke or smells can be detected
16. ded as suitable for use in smoke control areas  when burning wood  Authorised smokeless fuels can also be used  In the Clean Air Act Legislation  a fuel that  can be used in a smoke control area is referred as an    authorised fuel and the list of these can be found online    here  http   smokecontrol defra gov uk fuels php    The appliance is only exempt when used in accordance with these instructions     HETAS LTD approval    The Knightsbridge SE and Highgrove SE appliances have been approved by HETAS Ltd as  intermittent operating appliances for burning wood logs and approved smokeless fuels     Installation introduction with technical data    1 0 Technical data      Knightsbridge SE  amp  Highgrove SE      Material  Cast iron  Finish  High temp resistant paint  Fuel  Wood  Approved wood logs     Approved smokeless fuels  Log length  30cm maximum  Stove outlet collar positions  Top and rear  Stove collar dimension  Internal diameter 125mm   113cm2 cross section  Approx  weight  106kgs  Dimensions  distances etc  Figure 2  Technical data according to EN 13240 A2 2004   Technical data according to EN 13240 A2 2004     Nominal heat output  4 9kw  Wood     Nominal heat output     Flue gas mass flow     Recommended chimney draught     Efficiency     Efficiency     CO emission  13  O        Flue gas temperature     Operational mode  Intermittent    5 0kw  Ancit    3 8 g sec  Wood    3 8 g sec  Ancit    12 Pa   80 3   Wood    77 7   smokeless fuel   0 30   Wood    0 26   Ancit   
17. egs     The product can be placed directly onto a wooden floor providing that it is covered by a metal plate  or other suitable  non inflammable material  The minimum thickness is 12mm Any flooring made  of combustible material  such as linoleum  carpets  etc  must be removed from under the floor plate   Requirements for protecting combustible flooring in front  rear  amp  sides of the stove_must be in    accordance with national laws and regulations  amp  any rules in force  including BS 8303 and BS  EN 15287 1 2007     See figure 2     Wooden floor protection using optional 75mm high legs     The stove with 75mm high legs can only be used with a constructional hearth and superimposed  hearth and must be in accordance with national laws and regulations  amp  any rules in force     including BS 8303 and BS EN 15287 1 2007     Figure 2    Product Min  distance to combustible wall Min  distance from product to brick wall  Min  distance to combustible wall protected by firewall        Lyell   gt     R a A                                             N    h  A   7   3 A   UD       Min  measure floorplate  X Y Acc  to national  standards and regulations       Combustible wall    Firewall       Dimensions refer to untreated products  After painting or  enamelling dimensions may have small divergences     Contact your local building authority regarding restrictions and installation requirements     Walls protection    Note  The side load door must not be used in corner installations 
18. evacuation plan      A plan to deal with a chimney fire as follows    a  Notify the fire department    b  Prepare all occupants for immediate evacuation    C  If safely possible  close all air openings into the stove     3 1 Choice of fuel    Recommended fuel  Wood   Use hard wood logs    Although you can fire this product with almost all kinds of wood  you should not fire with wet  wood  or unseasoned wood  Wood should to be stored under a roof for at least   year  and preferably  2 years  with free access to wind ventilation  Wood should be chopped as soon as possible after  felling if it is to dry quickly  The wood can be used once the moisture content is less than 20    During the EN test  all stoves are tested with wood with a moisture content of  16   4      Hardwood has a higher calorific value as the same volume  oak  ash  maple  birch  elm  beech  etc    Pieces of wood with a diameter greater than 10 cm should always be chopped  The pieces of wood  should be short enough to be able to lie flat over the layer of embers  with air at both ends  The  maximum length of wood to be no more than 30 cm  The maximum fuel load to be two medium  sized logs  total weight 1 5kg  this should burn for about an hour before needing to refuel  then the  appliance is operating at about 4 8 to 4 9Kw     Recommended fuel  Smokeless Coal  Smokeless fuels  including Coalite Nuts  Phurnacite  Ancit and Extracite     The maximum fuel load to be a total weight of 0 75kg  This should burn for a
19. flues or 125mm for  flues with bends or offsets  Refer to current Building regulations  any rules in force including BS  8303 and BS EN 15287 1 2007     2 7 Connecting to a steel chimney    Refer to building regulations  amp  any other rules in force  including BS 8303 and BS EN  15287 1 2007     If your installation involves taking the chimney straight up and through the ceiling  you must  comply with National  Local Building Regulations or flue manufacturer   s instructions concerning  clearances to combustible materials such as walls  floor joists and ceilings  The joint between the  stove flue collar and the stove pipe must also be sealed using the glass fibre rope provided  It 1s  important that the insulated flue system is properly supported both at ceiling level and at roof level   The Stove must not bear the weight of the chimney system  See chimney manufacturer   s    instructions   Excessive weight on the stove will inhibit expansion and could lead to damage of the  stove top  Damage caused to the stove in this way would not be covered by the manufacturers  guarantee  The chimney or flue way that the stove pipe is connected must be of at least 125mm  internal diameter or  11  rectangular or square flues having the same cross sectional and a minimum  dimension of 100m for straight flues or 125mm for flues with bends or offsets  Refer to current  Building regulations  any rules in force including BS 8303 and BS EN 15287 1 2007     Refer to building regulations  amp  a
20. h a dry  dust free cloth  but only  when the stove is not in use  amp  cold     If the stove is used too vigorously  the painted surface may assume a grey tinge over time  but the    stove can easily be freshened up with heat resistant spray paint but only when the stove 1s not in use    and cold  refer to manufacturers instructions  which 1s available from your local retailer     3 3 4 Gaskets    The gaskets in the door will wear out over time  and should be replaced as required in order to    prevent runaway combustion  Seek advice from a qualified stove engineer     3 4 Operational problems     troubleshooting    Seek advice from a qualified chimney    stove specialist     Wood green  too    e Fire difficult to  damp or poor    lity   Start ED      Logs are too big   e Fire goes out i p    Air starvation     Insufficient  draught     e Fire burns too    Excessive draw     quickly     Poor quality wood     Too much draught        Use the  recommended fuel   To light the fire  use  small  very dry  twigs  To maintain  the fire  use split  logs    Open lower spin  wheel and top air  control lever    Check that the flue is  not obstructed   Sweep it if necessary    Ensure that the lower  spin wheel is closed  Partially close the  top air control lever   Install a draught  stabilizer  Consult  your Dealer    Do not continuously  burn small wood   sticks  bundles   carpentry off cuts   plywood  pallets    etc     Flue duct 1s cold  Burn kindling wood  e Smokes when  to increase 
21. he Clean Air  Northern Ireland  Order 1981  applies in Northern  Ireland  Therefore it is a requirement that fuels burnt or obtained for use in smoke control areas  have been  authorised  in Regulations and that appliances used to burn solid fuel in those areas   other than  authorized  fuels  have been exempted by an Order made and signed by the  Secretary of State or Minister in the devolved administrations     Further information on the requirements of the Clean Air Act can be found here   http   smokecontrol defra gov uk     Your local authority is responsible for implementing the Clean Air Act 1993 including  designation and supervision of smoke control areas and you can contact them for details of  Clean Air Act requirements       To ensure smokeless operation when burning wood with either the multi fuel or optional  Stoveasy grate models the tertiary air control must be set to the fully open position therfore  leaving the tertiary air intake fully open and unrestricted  The appliance is only exempt when  used in accordance with these instructions   Please see instructions within this manual      The Knightsbridge SE  amp  Highgrove SE are suitable for burning either wood or authorised smokeless fuel  In the  Clean Air Act Legislation  a fuel that can be used in a smoke control area is referred as an    authorised fuel and    the list of these can be found online here  http   smokecontrol defra gov uk fuels php    The Knightsbridge SE and Highgrove SE have been recommen
22. heat   In houses equipped  Room with mechanical  decompression ventilation  open a  window until the fire    is well established     lighting up     Ventilation Consult a chimney  insufficient specialist   Check that the flue is  not obstructed   Sweep if necessary     e Smokes while    burning     Down draught  Install an anti down  draught cowl   Consult your Dealer    Room In houses equipped   decompression with Mechanical  Ventilation  an  outside air intake  must be installed for  the chimney     e Incorrect Fuels  e Use fuel  Low heat output   Recommended     3 5 Replacement parts    O Only use replacement parts recommended by the manufacturer     Modifications to this appliance must not be made        3 6 Parts list for Knightsbridge SE and Highgrove SE multi fuel            a a iron      D e Pal Rod ht ee E    EN KR    A CT         ee E   LH Side Panel   MUERTO Panel mm 45      Steel Hexagon  Head Bolts M6 20 4 RH Side Panel 5 4      Gasket   D6 18   64     DoorA     DoorA     10 25     10 25      RN   28   Stainless Steel Countersunk   Steel Countersunk   M630   E WEN   13   Air Wash Cover ESES    Se A  men Rod   O O    EN Inner Hexagon  ETT ESTA E Bar l  EF      Primary Air Cover e  Air Cover   220 33 54 4     Grate Frame Frame   Bay   42    i hn Primary Air Shutter 262 40 4 E IR Air Wash Plate EENEN  Blanking Plate AA Se Air   Back Air Damper   0 26           NC E Inner Hexagon  Countersunk Inner Hexagon  El AAA  Banking Plate  Spring 51 Locking Bar  7   o         
23. hings    We recommend that the stove be installed 115 cm from furniture  Serious consideration should also  be given to positioning of any furniture that could be adversely affected by heat  The clearances to  combustible materials in front of the stove must be a minimum of 700mm and to the sides of the  stove a minimum of 600mm  When lit  a wood burning stove gets hot and therefore adequate  protection must be provided  particularly in situations where there is a safety risk to children or the  infirm  When using this stove in situations where children  aged and   or infirm persons are present  a fireguard manufactured in accordance with BS 8423 2002 must be used and such persons must be    supervised at all times   It is also recommended that all other people should use a fireguard in accordance with BS  8423 2002 at all times when the stove is alight or hot     2 4 The chimney     Refer to current building regulations  amp  any other rule in force  including British standard BS  EN 15287 1 2007 and BS 8303    This product must never be connected to any shared chimney    An efficient modern stove places heavy demands on the chimney  and you should have the chimney  regularly swept and inspected by your approved chimney sweep    The installer must ensure that the chimney is examined for soundness and suitability before the  appliance is installed  Remedial action should be taken if required  seeking expert advice if  necessary  Where the chimney is believed to have previousl
24. if this product is a side load door  version     Distance to wall made of combustible material    See figure 2 refer to building regulations  amp  any other rules in force  including BS 8303 and BS  EN 15287 1 2007     Distance to walls covered by a firewall    See figure 2  amp  refer to building regulations  amp  any other rules in force  including BS 8303 and BS  EN 15287 1 2007     Firewall requirement     Refer to building regulations  amp  any other rules in force  including BS 8303 and BS EN  15287 1 2007     The firewall must be at least 100 mm thick and be made of brick  concrete stone or light concrete   Other materials and structures with satisfactory documentation may also be used    Note  When installing this stove into a non combustible chimney or non combustible wall   providing all surrounding non combustible walls have a minimum thickness of 200mm the  clearance between the rear  amp  sides of stove can be reduced to 50mm  refer to building regulations  amp   any rules in force  However it 1s recommended that the measurement between the sides  amp  rear of  stove to be as large as possible above this dimension  as the efficiency of this stove 1s dependent on  the clearances as shown in figure 2     Ceiling protection     Refer to building regulations  amp  any other rules in force  including BS 8303 and BS EN  15287 1 2007     There must be a minimum distance of 1200 mm to any combustible ceiling above the fireplace     Clearances to furniture and soft furnis
25. ized logs be added  After 2     3 minutes  when these logs are well  alight  the primary air control  and door  should be closed  but it is advisable that this first fuel  load be operated with the secondary air control fully open so that the room heats up quickly and  the stove reaches its optimum operating temperature    Refuelling on a low fuel bed    If there is insufficient burning material in the fire bed to light a new fuel charge  excessive  smoke emission can occur  Refuelling must be carried out onto a sufficient quantity of glowing  embers and ash that the new fuel charge will ignite in a reasonable period  If there are too few  embers in the fire bed  add suitable kindling to prevent excessive smoke    2  When re fuelling the appliance  open the primary and secondary air controls for 2 3 minutes  or  until the logs are well alight  before closing the primary air and adjusting the secondary air to  the desired setting     3  Always refuel onto a good bed of glowing embers    4  Never leave the primary air spin wheel open  other than when lighting and re fuelling the  appliance    5  Fuel overloading  Never overload the firebox  The maximum amount of fuel specified in this  manual should not be exceeded  overloading can cause excess smoke    6  Never leave the appliance unattended for long periods and always ensure that the newly charged  logs are burning well before leaving the room    Wood is a material that contains a great deal of gas  approximately 75     The g
26. l Building  Regulations and any rules in force including current issues of British Standard BS 8303 code of  practice for installation of domestic heating and cooking appliances burning solid mineral fuel and  British Standards BS EN 15287 1 2007 design  installation and commissioning of chimneys  your  approved dealer or your local building control officer can advise regarding this  Ultimately  it is you  and your installer who is responsible to ensure that the installation complies with all relevant  regulations and any rules in force     2 2 1 Assembling the Tertiary air control   See figure 1      The Tertiary air control is a standard part for the Highgrove SE and Knightsbridge SE stoves multi  fuel versions    After assembling the control  check for easy operation and check for complete seal when the plate 1s  closed     Important   If the stove is to be used for wood with standard grate or with optional Stoveasy grate the tertiary    air control must be set to the fully open position therfore leaving the tertiary air intake fully open  and unrestricted  The appliance is only exempt when used in accordance with these instructions        Figure 1    Tertiary air regulation      2 2 2 Assembling the baffle  grate   amp  banking bar     After the stove is located  check the baffle 1s in correct position  See figure 1 1  This shows how to  locate the baffle  Before lighting the stove for the first time  confirm the baffle is in correct location   Position grate   amp  banki
27. n adequate air supply into the room containing the stove    It is very important that flue ways are regularly swept  amp  checked by an approved person   It is recommended that sweeping and checking should be done at least twice each year   The installer must ensure that the chimney is examined for soundness and suitability  before the appliance is installed  Remedial action should be taken if required  seeking  expert advice if necessary  Where the chimney is believed to have previously served an  open fire installation it is possible that the higher flue gas temperatures from a closed  appliance may loosen deposits that were previously firmly adhered  with the consequent  risk of flue blockage  It is therefore recommended that the chimney be swept a second  time within a month of regular use after installation    All dampers or restrictors must be removed from the flue    This stove must be maintained to ensure safe operation    efficiency    Never use aerosol sprays or any other combustible products in the vicinity of the stove  when it is in operation or whenever the stove is hot  The stove will remain hot for some  time even after the fire is extinguished    The stove is hot while in operation and retains it heat for a long time after use  When using  this stove in situations where children  aged    or infirm persons are present a fireguard  manufactured in accordance with BS 8423   2002 must be used  amp  such persons must be  supervised at all times    Fire cement can 
28. n circumstances a purpose provided air vent may be required such as insufficient  natural ventilation or date of building construction etc    Purpose provided air vents must be of the correct size and be non closable and unrestricted  refer to  building regulation  amp  any other rules in force    Do not use any extractor fans or any other similar devices in the room into which the stove is  installed    Air inlet vents should be positioned in the room at locations to avoid them becoming blocked  If the  air supply is inadequate the chimney draft may be too weak  with the possible result that the stove    will not burn properly leading to a potentially dangerous situation  Smoke spillage may also occur  during the refueling process  When determining the ventilation requirements account will need to be  made for any other combustion devices in the room     2 9 Draft conditions    If smoke spillage occurs when the fire door is opened  it 1s probably due to poor chimney draft  This  type of stove requires at least 12 pa of chimney draft to achieve satisfactory combustion and smoke  spillage prevention  However  in cases where the stove door is opened too vigorously you could  expect that slight smoke spillage may occur    If you have any doubts  you may want to have your installer measure the draft in the chimney     Draft conditions   The chimney   s draft 1s the resulting effect within the flue caused by the difference in temperature  within the flue and the cooler temperature
29. ng bar correctly  See figures 1 1 and 1 2   If the stove is to be used for wood the tertiary air control must be set to the fully open position  therfore leaving the tertiary air intake fully open and unrestricted        Side view showing baffle  grate  amp  banking bar  position of multi fuel version        Side view showing baffle  banking bar position  with optional Stoveasy grate  To install the  optional Stoveasy grate remove the multi fuel  grate with riddling grate and control  Fit the  Stoveasy grate into correct position  same  position as standard multi fuel grate  and locate  air funnel into grate rebate ensuring it is  positioned as picture  Fit the riddling control  blank into hole that the riddling control was fitted  and tighten the nut to rear of blank securely        Front view showing air funnel  air funnel grate and riddling control blank fitted into correct  position           Riddling control blank when using optional Stoveasy grate        Part 1  Locking nut  Part 2  Threaded fixing bolt  Part 3  Riddling blank          2 3 Stove placement   clearance requirements    This stove must only be installed onto floors with an adequate load bearing capacity  If an existing  construction does not meet this requirement  suitable measures  e g  load distributing plate  must be  taken  Must be in accordance with national laws and regulations  amp  any rules in force     including BS  303 and BS EN 15287 1 2007     Wooden floor protection using standard 150mm high l
30. nt immediately     2 5 Pipe connections    The stove is supplied with a 125mm diameter outlet collar to which an approved suitable gauged  metal rigid stove flue pipe of compatible and correct size is installed  not supplied   this rigid stove  flue pipe must be connected correctly to the chimney or flue way    The chimney or flue way that the stove pipe is connected must be of at least 125mm internal  diameter or  11  rectangular or square flues having the same cross sectional and a minimum  dimension of 100m for straight flues or 125mm for flues with bends or offsets  Refer to current  Building regulations  any rules in force including BS 8303 and BS EN 15287 1 2007        Figure 3    a 5 Y   3 AA NEN y  4   Fa Yw   gt              Flue outlet collar Blanking plate    2 6 Connecting to a masonry chimney    Refer to building regulations  amp  any other rules in force  including BS 8303 and BS EN  15287 1 2007     A wall sleeve should be bricked securely into the wall of the chimney at the appropriate height and  the stove pipe inserted centrally  The pipe must not extend into the actual chimney opening  but  rather must reach only to the inside of the chimney aperture  The gap between the stove pipe and  sleeve must be sealed using suitable sealing packing rope  The chimney or flue way that the stove  pipe is connected must be of at least 125mm internal diameter or  11  rectangular or square flues  having the same cross sectional and a minimum dimension of 100m for straight 
31. ny other rules in force   CAUTION     In the event that a chimney fire occurs resulting from faulty operation or prolonged use of  damp wood fuel  evacuate all people from the house  if safely possible close the air vents  completely and contact your local fire department immediately     Cleaning procedure     Discuss this with chimney sweep or qualified installer prior to or during the stove installation    Chimney draft     If the chimney draft is naturally poor it is better to install the flue from the top of the stove so as to  minimize any internal resistance of the flue gases    Avoid having any more than 2 bends in the flue system and limit the length of the offset between  bends  Refer to building regulations and any other rules in force     2 8 Ventilation  Fresh air supply      Refer to building regulations  amp  any other rules in force  including BS 8303 and BS EN  15287 1 2007     Knightsbridge SE  amp  Highgrove SE  nominal heat output 4 9   5 0 kw   Knightsbridge SE  amp  Highgrove SE  with optional Stoveasy grate     nominal heat output 4 8 kw      A multi fuel burning stove requires air for combustion and therefore you may need to install  additional ventilation to the room  An adequate air supply for ventilation  amp  combustion is required  to the room into which the stove is installed  As this stove is CE tested to 5 0kw nominal heat output    Refer to Building Regulations Document J  a purpose provided air vent is not normally required   However in certai
32. on of this stove must be completed in accordance with current local codes and  regulations in each country  All local regulations  amp  any rules in force  including those  which refer to national and European standards  must be observed when installing this  product    Reference must be made to current issues of British Standard BS 8303  code of practice  for installation of domestic heating and cooking appliances burning solid mineral fuel and  BS EN 15287 1 2007 design  installation and commissioning of chimneys    Note  Please note that it is a legal requirement under England  amp  Wales Building  Regulations that the installation of this stove is undertaken under Local Authority  Building Control or is installed by a competent person registered with a Government  Approved Competent Persons Scheme  Hetas Ltd operate such a scheme and a listing of  their registered Competent Persons can be found on their website at www hetas co uk  An approved Carbon Monoxide alarm must be installed into the room into which the  stove is installed    This stove must not be installed into a flue that shares any other appliance    Extractions fans or units must not be installed into the room of stove installation    The installer has a responsibility to ensure that all requirements of Health    Safety At  Work Act are observed  amp  implemented    Due to the weight of this stove adequate facilities must be available for loading  un loading   amp  installation    Always ensure that there is a
33. ted        CAMA              Riddling control    Important   The Tertiary air control must be set  in the fully open position when  burning wood           Tertiary air control    Figure 4B shows the air controls used when burning wood using the optional Stoveasy grate  Note   The tertiary air control must be set to the fully open position therfore leaving the tertiary air intake    fully open and unrestricted   The Riddling control is removed and replaced with a stainless steel riddling control blank   B Es E   Figure 4        Important     The Tertiary air control must be set  in the fully open position when      burning wood   Tertiary air control    Very Important     The stove door should never be opened when the stove is being fired vigorously     e We would strongly recommend that you do not leave your stove alight at night  It harms the  environment  and constitutes very poor use of the wood  as the gases in the wood do not ignite  at the low temperature  but settle as soot  unburned gases  in the chimney and stove  Extreme  conditions  such as poor draught in the chimney  large quantities of wood or wet wood  may   in the worst case scenario  cause an explosive ignition      When firing in the summer period  when there is minimal need for heat  the combustion will  be poor  The stove provides too much heat  so the combustion should be reduced  But always  remember to make sure that there are lasting flames until the wood becomes charcoal  If you  want a weaker fire  s
34. ter prolonged shutdown periods    e An approved Carbon Monoxide detector must be installed into the room of stove installation  If  the alarm sounds unexpectedly  follow the instructions given under    Warning note    above        e WARNING NOTE    Properly installed  operated and maintained this stove will not emit fumes into the dwelling    Occasional fumes from de ashing and re fuelling may occur  However  persistent fume emission   is potentially dangerous and must not be tolerated  If fume emission does persist  then the   following immediate action should be taken      a  Open doors and windows to ventilate the room and then leave the premises     b  Let the fire go out     c  Check the flue for chimney blockage and clean if required     d  Do not attempt to relight the fire until the cause of the fume emission has been identified and  corrected  If necessary seek expert advice    The most common cause of fume emission is flue way or chimney blockage  For your safety these   must be kept clean at all times    e Never use aerosol sprays or any other combustible products in the vicinity of the stove  when it is in operation or whenever the stove is hot  The stove will remain hot for some time  even after the fire 1s extinguished    e Fire Safety  Serious consideration should be given for the following       The installation of smoke detectors    m A conveniently located approved fire extinguisher to contend with small fires resulting from  burning embers      A practical 
35. toke up using less wood     O After a prolonged shut down period the stove and chimney system should be checked to  ensure that there is no blockage  For example  a bird may have nested at the top of the  chimney    e If you fire the stove using wet wood  a lot of the fuel   s thermal energy will be spent forcing  the water out of the wood  without releasing any heat to the stove  This incomplete  combustion results in a layer of soot being left in the stove  pipe and chimney     3 3 Ash removal    Figure 5  How to remove ash pan     Always use the key provided to operate and to lift ash pan     It is essential to keep the grate free from a heavy build up of ashes  This product is equipped with an  air intake funnel which is removable  When the stove is not alight and cool  open both the glass and  lower ash pan doors  remove air funnel and sweep ashes into the ash pan with a suitable brush or  alternatively use a specialist ash vacuum for this task    Always empty the ash pan at least once a day or whenever it is full of ashes  Use the key provided  to remove and replace ash pan into position  Never allow the ash pan to overfill allowing ash to be  in contact with the underside of the grate  If this condition is allowed  the grate will wear out  pre maturely     Disposal of ash    Ashes should be placed in a metal container with a tight fitting lid  The closed container of ashes  should be on a non combustible floor or ground well away from all combustible materials pending 
36. y served an open fire installation it is  possible that the higher flue gas temperatures from a closed appliance may loosen deposits that  were previously firmly adhered  with the consequent risk of flue blockage  It is therefore  recommended that the chimney be swept a second time within a month of regular use after  installation    The cross sectional area of the chimney  at its narrowest point  must comply with National and  Local Building Regulations  Generally  the area needed for a wood burning stove installation should  measure at least 150 mm internal diameter    An over sized chimney is generally hard to keep warm and results in poor draft  In cases where  there is an oversized masonry chimney  it is recommended that the chimney be lined using an  appropriate chimney lining system with the correct internal diameter    With respect to the chimney termination  all chimneys should terminate in accordance with national  and Local Building Regulations    Note that National and Local Regulations also apply with regard to the placement of chimneys and  flues in connection with thatched roofs    The chimney or flue system must be equipped with access doors for inspection and cleaning  The  size of the cleaning door in the chimney must at least equal to that of the cross sectional area of the  chimney  In the event that a chimney fire occurs resulting from faulty operation or prolonged use of  damp wood fuel  close the air vents completely and contact your local fire departme
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Prince Castle 965-B User's Manual    Installation & Service Manual  3MTM 水性インクジェット用短期白色メディア IJ4332E    Copyright © All rights reserved. 
   Failed to retrieve file