Home

M101-P/M102-P Parameter Description

image

Contents

1. 46 Trip pln f 46 Reset LOVED M 46 Trip Reset e 46 AUTORESTART FUNCTION ONLY FOR M102 P 47 Function Enable Disable 1 ees casera nna rasan tapas rnn ita on anat sets ara a anna ran 49 Max Autoreclose Time 49 18 3 18 4 19 19 1 19 2 19 3 19 4 20 20 1 20 2 21 22 ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Maximum Power Down Time llueeeeeeeeeeeeeee eene e enne nnne nnns nnn n nnnm anna sanas ntn n ass nanna 49 Staggered Start Time teu cu cca cios sn ota esa cpu pacc 50 START LIMITATION 50 Function Enable Disable cauere cce n oer E Issa Drap re 51 WMS TV A eem 51 Number of Starissa ee a cece sce wade Sees desc 51 Trip Reset
2. 34 Huc 34 UNBALANCE lt lt 34 Function Enable Disable eese e eerie esee esee seen enne nnnm nine annm a ttn natnra sema sane a ann 35 Alarm Level 35 Trip LOVE 35 pg 36 Trip Reset Mode fee 36 UNDERLOAD PROTECTION 2 36 Function Enable Disable 37 Alarm LO Vel eE 37 Idle 37 WHIP DON AY e 38 Trip Reset 38 ABB 14 14 1 14 2 14 3 14 4 14 5 15 15 1 15 2 15 3 15 4 15 5 16 16 1 16 2 16 3 16 4 16 5 16 6 17 17 1 17 2 17 3 17 4 17 5 17 6 18 18 1 18 2 4 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description NOLOAD PROTECTION eene SE erg pa ae 38 Function 0 c cciccisiscsccccisassssccscecsessstn
3. Nani 27 2 27 ABB 9 7 9 8 9 9 9 10 9 11 9 12 10 10 1 10 2 10 3 10 4 11 12 12 1 12 2 12 3 12 4 12 5 13 13 1 13 2 13 3 13 4 13 5 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description MOL Trip 27 TOL Reset Level 28 Trip Reset sicssiccscccsescsecesssceiscccsanecsaciacecsseasisndscasesacacsainiatsdvecssasiaseatesaiestiesanteastedeonseacstaanes 28 TOL Bypass 28 Cooling Goes MUG scsi rannani r A aranais aaaea 28 LYulgdrundcu c 29 STALL PROTECTION 2 1i turtur unen Aasi Ei 30 Function Enable Disable erecti 31 Trip COV e 31 Trip Delay 31 Trip Reset Mode ee M 32 PHASE FAILURE PROTECTION 32 Function Enable Disable 33 Alarm 33 ee N 33 Delay e
4. For example The thermal capacity level of the motor reduces from 100 at 40 C to 85 at 50 C Therefore the motor can be loaded maximum to 9290 of its rated load at 50 C Manual reduction may be needed if other reduction multiplier than presented in the table above are required Output power reduction is done by setting the value 40 C to parameter motor ambient temperature and calculating the temperature reduction directly to nominal current When multiplier is calculated this way it must be applied to trip class time as well IS TFLC For example Motor data sheet specifies that in 60 C motor be loaded maximum of 75 of the nominal Thus motor ambient temperature is set to 40 C and when setting the nominal current the rated motor current is derated nominal current 0 75 When nominal current is derated trip class parameter is defined with the same factor It should also be considered that other parameter s i e protection function trip and alarm levels referring to nominal current are effected relatively 10 Stall Protection Stall protection is used to protect the driven mechanical system from jams and excessive overloads Under such conditions the motors have to be switched off in good time and reported to avoid undue mechanical and thermal stress on the motor and the installation This protection function is active only after the motor has successfully started or after parameterised motor star
5. 5 11111 16 jleyreachiet cec 16 Function Enable Disable eo ern aki Fo Rosas rau 17 Group Start eene crank dadas 17 iCCIPmlse 17 pd e 17 Group Stait Delay icenen irienna einean anneni snaa aaa rae aoaaa ra aaea SAn NEE Barnie 18 Stop Delay osean 18 DIGITAL INPUTS ieee 18 m 18 enprmbegigcm o o 19 ie upr 20 jen m 20 PROGRAMMABLE 0 5 chazecetendcedee 20 21 Eirienpg 21 THERMAL OVERLOAD PROTECTION TOL eere nennen 22 Function Enable CAR gana aac acea ku Rana done 23 INIM 23 Whip Class TO e 24 class 26 NAAM m
6. 52 Liz e M 52 Running time alarm level eese eeee sees eee essen eese snnm n nnns eine aane at tn astra snas snas 52 Start number alarm level 52 DIAGNOSIS 53 USER DEFINED 53 M101 P M102 P Parameter Description Notes This file is for M102 P V2 0 only 1 Introduction 1 1 Objective The objective of this document is to provide parameter description of M101 P M102 P Each chapter consists of brief explanation of the function the involved parameters and the parameter description along with the range The default values of all the parameters are listed in appendix Factory settings for M101 P M102 P Some examples and further explanations are provided for user s reference in parameterisation 1 2 Related documentation 1TNC911115D0202 M101 P M102 P User s Guide 1TNC911104M0202 Mcusetup User s manual 1TNC911507M0202 PROFIBUS Protocol Implementation for M101 P M102 P 2 Document Overview The parameterisation of M101 P M102 P can be done either from service laptop or workstation with Mcusetup P software installed The motor related parameters and the prot
7. Default setting NOP Related parameter Motor information Starter type Communication Communication failure delay Description M101 P M102 P offers a failsafe function where the user has the possibility to decide motor status after failure either in M101 P M102 P internal communication or PCS communication to M101 P M102 P If the M101 P M102 P detects a failure in communication a stored command is executed after a pre parameterized Communication failure delay 3 12 Communication Failure Delay Function PROFIBUS communication Range 1 1 25s 2555 Default setting 255s Related parameter D Description This parameter is to set the allowed time period in which no activity occurs on the communications ports After the delay M101 P M102 P will turn into Failsafe mode automatically If the serial communications link is used to control a process with several motors working together it may be desirable to shut down the motor if communication control is lost When no activity occurs on the communication port for 1 to 25 seconds it will trip if this feature is enabled If the value is set to be 255s the function of communication failure will no response even existing communication failure 3 13 Feedback Function Motor information Range enabled disabled Default setting enabled Related parameter Motor control Starter type Description The contactor feedback supervision functions provided by M101 P M102 P can be implemented via
8. 6 1 Function Enable Disable Function Motor Grouping Range Enabled Disabled Default setting Disabled Related parameter Motor grouping Parameters Description Motor grouping function can be disabled with the help of this parameter When disabled motor group function does not have any functionality in the M101 P M102 P and all other parameters of the function group number group identifier group start direction group start stop delay are greyed out in the Mcusetup P software 6 2 Group Start Direction Function Motor Grouping Range CW CCW Default setting CW Related parameters Motor grouping Parameters Motor information Starter type Description This parameter defines the direction of rotation of the motor when started by a group command The rotating direction of the motor depends on the starter type parameter value 6 3 Group Number Function Motor Grouping Range 1 1 9 Default setting 24 Related parameters Motor grouping Group Identifier Description The motors belonging to a specific group should be assigned the same number as the other group members 6 4 Group ID Function Motor Grouping Range 16 characters Default setting GROUP1 Related parameters Motor grouping Group number Description Group name is the name of the group to which the motors M101 P M102 P belong This name is used for visualisation purpose This parameter can be used optionally and has no fu
9. PTC Temperature Alarm alarm clear 16 1 Function Enable Disable Function PTC protection Range Enabled Disabled Alarm only Default setting Disabled Related parameter PTC protection Parameters Description The PTC protection function can be disabled with the help of this parameter When disabled the protection function does not have any functionality in the M102 P Alarm only is an option of function disable enable When alarm only is active an alarm occurs only if the measured value is more than the set alarm level 16 2 Alarm Level Function PTC protection Range 100 1 10 000 Ohms Default setting 1 600 Ohms Related parameter PTC protection Function enable disable Alarm mask table Description This parameter defines the alarm level for the PTC protection function The limit causes a message PTC temperature alarm to be issued when the measured temperature is higher than the alarm level The temperature is measured via the PTC thermistors Usually three PTC thermistors in series are built into the overhang of the stator winding at the coolant air exhaust end of the motor The thermistors are selected to have a rated operating temperature TNF to correspond with the insulation class type and construction of the motor If the resistance corresponding to the high temperature at one or more of the thermistors exceeds this value an PTC temperature alarm will be generated The PTC temperature alarm clears automatically on
10. Function Undervoltage Trip reset mode Undervoltage Trip delay Undervoltage Reset level Undervoltage Max power down time Description Max autoreclose time is the time during which the motor immediately restarts on restoration of voltage above the reset voltage level 18 3 Maximum Power Down Time Function Autorestart Range 0 1 1200 sec Default setting 5s Related parameter Autorestart Function Undervoltage Trip reset mode Undervoltage Trip delay Undervoltage Reset voltage level Autorestart Max autoreclose time Autorestart Staggered start time Description The Max powerdown time starts after the trip delay time has elapsed It is the maximum waiting time of E ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description the M102 P for the power resumption The motor would restart after staggered start delay on voltage restoration above the reset voltage level between end of max autoreclose time and max power down time The M102 P issues an undervoltage trip message if the voltage recover above the reset voltage level after the max powerdown time The trip can be reset based on the parameterisation of the trip reset mode Notes 18 4 Staggered Start Time Function Autorestart Range 0 1 1200 sec Default setting 5s Related parameter Autorestart Function Undervoltage Trip reset mode Undervoltage Trip delay Undervoltage Reset voltage level Autorestart Max autoreclose
11. M101 P M102 P Parameter Description N More optimised setting of the thermal protection is needed in case of one start for warm motor is otes required In this case the Trip class t6 parameter is derived from the warm condition time current diagram according to actual duration of motor start and motor startup current The derived Trip class t6 value is verified from the cold condition time current diagram to ensure that thermal protection trip time is less than maximum allowed start time for a cold motor i e the protection is well defined There is a need to arrange a separate protection for unsuccessful start i e stalled rotor if the thermal protection characteristic allows longer start before trip than is allowed for the motor Then stall protection is utilised for a cold motor start supervision By defining the operation of Startup time and stall protection Trip delay the trip must be set before motor maximum start time is exceeded in case of unsuccessful start 9 4 Trip class te Function TOL protection Range 1 1 250 sec Default setting 5s Related parameter TOL protection Thermal model EEx e TOL protection la In ratio Motor information Motor ambient temperature Description The safe locked rotor time te of a particular induction motor is the time necessary for the winding temperature to rise from its final operational value to a fixed maximum value determined by the corresponding temperature class of th
12. OR Reset level 9 1 Function Enable Disable Function TOL Protection Range Enabled Disabled Default setting Enabled Related parameter TOL protection Parameters Motor information Motor startup time Motor information Motor startup time N2 Description TOL protection function can be disabled with the help of this parameter When disabled all other parameters of the TOL function trip reset mode thermal model TOL bypass trip level trip delay T6 Te cool coe la In and temperature do not have any functionality in the motor control unit This function is disabled automatically during the motor startup period 9 2 Thermal Mode Function TOL Protection Range Standard EEx e Default setting Standard Related parameter TOL protection Parameters PTC protection Trip Level Reset Level Motor information Motor Ambient Temperature Description The thermal model can be selected as either standard or EEx e The standard model makes use of trip class startup ratio and motor startup time TOL calculation Parameter trip class definition defines the trip time for 6x motor nominal current In and it must be less than defined cold state maximum value for the motor The protection of explosion proof three phase induction motors with type of protection increased safety EEx e is done with two special parameters the stall nominal current ratio la In ratio and te time The tripping time o
13. 0 5T and end user must increase current circle to 5T 3 15 Earth fault primary Function Motor information Range 1Aor 5A Default setting 1A Related parameters Earth Fault Protection Function Earth fault protection Alarm level Earth fault protection Trip level Description The parameter defines the maximum primary current of the RCT 3 16 VT Primary L N only for M102 P Function Motor information Range 110 1 250V Default setting 220V Related parameters Motor information System supply voltage Undervoltage Protection and Autorestart Description This is used to define the input of internal voltage transformer serving for voltage related protection The value of VT Primary is computed automatically according to the value of power supply voltage 3 47 Motor Nominal Current N1 Function Motor information Range 0 4 1 0 Default setting 4A Related parameters Motor Information Motor Power Rating Motor information External CT parameters Description This is the rated current In of the motor at rated load at rated voltage and frequency The value is given on the motor rating plate The rated current can be set within this range In the case of starter with external current transformers the range is dependent on the nominal primary current of the current transformer The range varies from 0 4 to 1 0 of CT nominal primary current Example In the case of an external current transformer of 100A the range var
14. 4 Trip Delay Function Phase Failure Protection Range 0 1 60s Default setting 108 Related parameters Phase Failure Protection Function Enable Disable Phase Failure Protection Trip Level Description After trip level condition is reached the M101 P M102 P will delay the trip for the time defined by pre parameterised trip delay A message Phase failure trip is generated With this delay a short phase current loss can be filtered The M101 P M102 P can be reset according to the trip reset mode parameter 11 5 Trip Reset Mode Function Phase Failure Protection Range Remote Local Remote amp Local Default setting Remote amp Local Related parameter Phase Failure Protection Function Enable Disable Description Phase failure trip can be reset in multiple ways depending on the control philosophy It is possible to reset the trip as desired by suitable parameterisation Remote Reset The Phase failure trip reset is only possible via the fieldbus Local Reset Phase failure trip reset is only possible via Digital Input which is assigned for Reset or via operator panel MD 12 Unbalance Protection Unbalance protection function protects the motor against a small degree of unbalance in the motor phases The function monitors the ratio between liww li wax The calculation of the motor thermal capacity takes into account the unbalance for early tripping to prevent motor damage due to negative sequence currents For more inform
15. I O terminals Moreover in NR DOL and NR DOL RCU the contactor feedback via predefined input can be disabled by setting the parameter here and the feedback supervision functionality in M101 M102 is based on the current detected by the device 3 14 Internal CT Primary Function Motor information Range 0 5 1 0 5T 0 5 1 0 2T 0 5 1 0 2T 1 0 2 5 2 5 5 0 5 0 12 5 12 5 30 0 30 0 63 0 Default setting 2 5 5 0A Related parameters Motor information Nominal Current N1 Motor control Nominal Current N2 Motor information External CT Installed Motor information External CT1 Primary Motor information External CT2 Primary Description M101 P M102 P with internal CT can handle the motor with rated current up to 63A The parameter is used to describe the primary of internal CT To ensure the accuracy of measurement pls follow the rule that motor rating shall be a value among 0 4 1 CT primary For example as a 1 5kW 3 5A motor this parameter is recommended to be set as 2 5 5 0 While using an external current transformer for motor nominal current gt 63 A the setting of the 2 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description parameter must in line with the external CT secondary 5A and 1A are available in this case Notes If motor s nominal current is lower 0 08A it should increase the current circle T to measure the current For example as a 0 1A motor this parameter is recommended to be set as 0 5 1
16. Local DCS fieldbus Operator panel MD No Definition Note The blue shaded fields can be set to either Enabled or Disabled via parameterisation but for Profibus DPVO it is only change the control authority via parameterisation kit 5 1 Motor Control Mode Function Control Authority Range Enabled Disabled Default setting MD Operator panel Related parameter Digital Inputs Loc R Description When the LOC R input is defined via parameterisation the Control Authority function here is automatically deactivated except MD and HMI When cancelling the definition of LOC R input user can select the control mode as RCU MD Local and Fieldbus RCU Start Reserved This mode showing the control access belonging to control box nearby the motor is automatically activated for selection when DOL RCU and REV DOL RCU modes are selected in motor starter type MD Operator panel M101 M102 accepts the command from operator panel to control the motor Local via hardwire This control mode is via hardwire from M101 M102 terminal inputs to start stop motor It is a common requirement always from DCS system Fieldbus via bus communication This item is to define the motor control mode as bus communication Via communication port in M101 M102 up control system as PCS can easily control motor remotely HMI Reserved It is as an additional option for control via an operator control amp monitoring stat
17. earth faults are mainly caused due to ageing of the insulation deterioration of insulation due to sustained or cyclic overloading moisture or conductive dust Most insulation faults result in leakage to the frame of the motor The monitoring of the earth faults is done with a residual current transformer The residual current transformer method is normally employed for either isolated systems or for systems earthed with high impedance The sensitive protection against earth faults is possible The low current threshold helps to protect the stator winding from earth faults at the neutral end The earth fault protection is supressed during starting to avoid nuisance tripping due to harmonics caused by saturation of the current transformers Parameters involved in the earth fault protection are as below Function Enable Disable Alarm Level Trip Level Trip Delay Trip Reset Mode 40 ABB ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Figure 11 Earth fault protection Notes 1 Motor startup time 5 Trip delay cleared 2 Normal operation 6 Trip delay active Earth fault protection active 7 Contactor trip and trip message 3 Alarm message 8 Reset according to reset mode 4 Trip delay active 15 1 Function Enable Disable Function Earth fault protection Range Enabled Disabled Alarm only Default setting Disabled Related parameter Earth Fault Protection Parameters Motor information Motor startup
18. elements with a very high positive temperature coefficient PTC temperature detectors are used extensively in the protection of motors against excessive temperature rise They are embedded directly between the phase windings on the overhang of the stator winding normally during manufacture In contrast to the trip class t6 and TOL protection that responds to the load current the PTC protection responds to the change in thermistor resistance due to temperature rise in the windings The PTC protection is also sensitive to fall in temperature in order to make it possible to reset the trip The thermistors are selected to have a rated operating temperature TNF to correspond with the insulation class type and construction of the motor It s resistance increases sharply in the range of its rated operating temperature TNF For a temperature change of 10 C the resistance changes ten times The M102 P senses this abrupt change in the resistance to execute a trip command A trip will follow when trip level is detected by the measurement and reset is allowed when resistance is under reset level Parameters involved in PTC protection are as below Function Enable Disable Alarm Level Trip Level Trip Delay Reset Level Trip Reset Mode ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Figure 12 protection Notes PTC trip Trip reset H Trip delay a lt gt Trip Level Alarm Level Reset Level
19. for 102 11 Failsafe MOG 11 Communication Failure Delay eeeeeeeeeeeee nennen nennen nnne nnns nna nnns nnne 12 que 12 Dura 12 Earth falt priMay dE E E 13 VT Primary L N only for M102 P nnn 13 Motor Nominal Curtent N1 2 2 nca te Da runc votes aca 13 Motor Nominal Curtent 13 External CT WS cA 14 Su dnrdenBdur M 14 External 2 14 4 4 1 4 2 4 3 5 1 6 1 6 2 6 3 6 4 6 5 6 6 7 1 7 2 7 3 7 4 8 1 8 2 9 1 9 2 9 3 9 4 9 5 9 6 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description COMMS PROFIBUS DP COMMUNICATION eene enne nnn nter nnn nnn nnn 15 piu rre 15 Operating Mode 15 BIOGK DP 15 CONTROL AUTHORITY 2 212 arcas teca c uocare socracr seeescustasesceueseescesccesecsracseteecesseseerss 15 Motor Control Mode
20. reaches 1 25 times the nominal current This parameter defines the length of time for the startup phase of the motor during which the Overload alarm message and stall protection functions are deliberately suppressed In the case of M101 P M102 P in addition to the above the underload the unbalance and the earth fault protection functions are suppressed 3 7 Startup Time N2 Function Motor information Range 1 1 250s Default setting 5s Related parameter Motor information Motor startup time N1 Motor information Starter type NR 2N REV 2N Description This parameter is defined as the same as the definition of the previous parameter Motor Startup Time except that it is dedicated for speed N2 3 8 Changeover Time only for M102 P Function Motor information 10 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Range 1 1 250s Default setting 5s Related parameter Motor information Starter type NR SD Autotransformer Underload protection Enabled disabled No load protection Enabled disabled Description This parameter is applied to both NR SD starter and Autotransformer starter In the case of autotransformer starter the parameter defines the time that motor is running with reduced voltage that is the motor changes to line voltage connection when the defined time elapsed For SD starter the start to delta transition is executed after the defined time 3 9 Ramp Up Time o
21. relay Ground fault The relay is energized when no ground fault trip occurs When ground fault trip occurs the relay will de energized Resetting M101 P M102 P will energize the relay Overload The relay is energized when no overload trip occurs When overload trip occurs the relay will de energized Resetting M101 P M102 P will energize the relay Watchdog output M101 P M102 P has an internal hardware watchdog supervising the behavior of the microprocessor software Programmable output can be used as signaling output relay for indicating the status of the unit s internal watchdog In case of fault the watchdog activates and the relay is energized Communication failure The relay is energized when no communication failure occurs When the failure occurs the relay will be de energized RCU Mode for M101 P This definition is assigned to the programmable out when NR DOL RCU or REV DOL RCU is selected as motor starter mode The relay output serves the same function of de energized the contactor coil as CCC output in M102 Local remote output only for M102 P The relay is energized when the control authority is Remote only The relay will be de energized when the control authority is Local and Remote or Local only 8 2 Start Stop delay Function Programmable Output Range 0 125s Related parameter Programmable Output Function Energize on motor start delay Programmable Output Function De energize on motor stop delay Description R
22. time Autorestart Max power down time Description This parameter defines the time from the voltage rise above the reset voltage level to the time when the start command is executed It is applicable to the motors if the voltage restores above the reset voltage level between the delay This parameter can be used to start the motors sequentially after resumption of power to prevent voltage dip caused by simultaneous starting of several motors 19 Start Limitation Protection Start limitation helps to protect the motor and also the process against excess number of starts in a given interval When the number of starts is reached and the motor is switched off a new start is prevented The time interval starts from the first start After the elapse of the time interval the counter is reset to the pre set value The permissible motor starts per hour can be obtained from the manufacturers motor and apparatus data sheet However the minimum waiting time between two starts shall be complied The parameterisation of the protection function can be the number of starts per time interval or the time between two consecutive starts In the first case the user must wait after the trip for the reset to take place before making a start The time to reset after start limitation trip is provided to the fieldbus Independent of this function the motor is protected by TOL function and a start is possible only if the thermal capacity is below the startup inhibit leve
23. time Motor Information Number of phases 3 phase applications Description Earth fault protection function can be disabled with the help of this parameter When disabled the protection function does not have any functionality in the M101 P M102 P Alarm only is an option of function disable enable When alarm only is active an alarm occurs only if the measured value is more than the set alarm level Protection function is disable during motor start specified by motor startup time parameter and also when single phase application is implemented 15 2 Alarm Level Function Earth fault protection Range 100 100 3000mA Earth fault primary or 500 100 15000mA Earth fault primary 5A Default setting 500mA Related parameter Earth fault Function Description When the earth fault current exceeds the pre set level an alarm Earth fault alarm is generated The earth fault alarm is automatically reset when the current falls below the alarm level This function can be bypassed during the startup of a motor by parameterisation of a trip delay 15 3 Trip Level Function Earth Fault Protection Range 100 100 3000mA Earth fault primary or 500 100 15000mA Earth fault primary 5A Default setting 800mA Related parameter Earth Fault Protection Function al ABB ITNC911106M0202 Edition July 2005 Notes 42 M101 P M102 P Parameter Description Earth Fault Protection Trip delay Description When the earth fault current re
24. 2 Test Switch Emergency Stop PLC control Trip Reset Torque Switch F CA F CB F CC Loc R Main switch status MCCB trip input Default setting Digital Inputs Default function DIO LIMIT1 LIMIT2 DI2 START1 DI3 START2 014 015 016 DI7 F Cb DI8 F Cc DI9 NOP 0110 0111 0112 Main switch status 18 ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Related parameter Control Authorit Notes ij d Description Each digital input can be assigned to a specific function according to difference purpose NOP Not special operation for the digital input only for the check of digital input status Start1 The input is used to control motor to start via hardwire Motor can be running CW N1 Start1 Start2 The input is used to control motor to start via hardwire Motor can be running CCW N2 via Start2 Stop The input is used to control motor to stop via hardwire Limit That is limit position switch1 input Limit2 That is limit position switch2 input Process interlock1 The digital input is used to check the process interlock1 after motor is startup For more details please refer to M101 P M102 P User Guide Process interlock2 The digital input is used to check the process interlock2 after motor is startup Test switch input The input is used to indicate whether the main switch is in the test position While in
25. M101 P M102 P Parameter Description M101 P M102 P Parameter Description Table of Contents 1 1 1 1 2 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 3 10 3 11 3 12 3 13 3 14 3 15 3 16 3 17 3 18 3 19 3 20 3 21 ITNC911106M0202 Edition July 2005 INTRODUCTION e 6 le e 6 Related documentation 6 DOCUMENT Gucezbececeesdeccdederereceie 6 6 Starter e 7 ibid e 9 System Supply Voltage only for M102 P 9 kcudMdijj 9 Motor Power Rating 10 Time de cece tereti cei tuuc ncn 10 Startup Tim 2 10 Changeover Time only for 102 10 Ramp Up Time only for 102 11 Ramp Down Time only
26. T Installed Enabled Motor information Internal CT Primary 2 5 5A Motor information External CT1 Primary 100A Motor information External CT2 Primary Not active 4 COMMS PROFIBUS DP Communication The communication function provided by M101 P M102 P is basing on PROFIBUS DP The fieldbus interface is RS485 Parametering remote control data acquisition and transmission etc are implemented via the communication function More information of M101 P M102 P communication please refer to M101 P M102 P User Guide and Profibus Protocol Implementation for M101 P M102 P The parameters involved with the protection function are Device Address Operating Mode Block DP 4 1 Device Address Function COMMS Range 0 126 Default setting 11 Related parameter Do Description Each M101 P M102 P on the same serial communication network must have a unique address in the range of 0 to 126 Computer software driving the serial network must be configured to recognize each Separate address 4 2 Operating Mode Function COMMS Range DPVO Default setting DPVO Related parameter De Description M101 M102 supports only profibus DPVO operating mode so far 4 3 Block DP Function COMMS Range Enabled Disabled Related parameter Description The block DP function determines whether M101 M102 will update the parameters when receiving the initialization command from upward system If it is disabled the parameters in M101 M102
27. a voltage is supervised continuously It is possible to automatically restart the motor after momentary power loss Two alternative models of auto restart function are provided in M102 P Standard and enhanced In standard mode the reaction of the auto restart function depends on the length of the voltage dip The following cases show the different reactions of M102 P in different voltage dip situations Case 1 Voltage dip autoreclose time Figure 14 Voltage dip lt autoreclose time If voltage is restored within the autoreclose time the motor will be restarted immediately Case 2 autoreclose time voltage dip Max power down time Figure 15 autoreclose time voltage dip lt Max power down time E ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description If the supply is restored after the autoreclose time but before the Max power down time the motor will be Notes restarted after the Staggered start time Case 3 Voltage dip Max power down time Figure 16 Voltage dip Max power down time If the supply remain below the restore level after max power down time no automatic restart is triggered even voltage restores later If the voltage dip is taken more serious the enhanced autorestart function can be applied In the enhanced mode the reaction of the auto restart function not only depends on the length of the voltage dip but also the number of voltage dips within a certain time The following c
28. according to reset mode 3 Trip delay cleared 4 Trip delay active 14 14 Function Enable Disable Function Noload Protection Range Enabled Disabled Alarm only Default setting Disabled Related parameter No load Parameters Description No Load protection function can be disabled with the help of this parameter When disabled protection function does not have any functionality in the M101 P M102 P Alarm only is an option of function disable enable When alarm only is active an alarm occurs only if the measured value is more than the set alarm level This function is disabled automatically in the case of single phase motor and during the motor startup period 14 2 Alarm Level Function Noload Protection Range 5 1 50 Default setting 2096 Related parameter Noload protection Function Description If the highest phase current ILmax of the measured three phase currents is detected below the alarm level then a warning message Noload Alarm is created to inform the operator of the no load condition Noload Alarm clears automatically on restoration of normal condition 14 3 Trip Level Function Noload Protection Range 5 1 50 Default setting 1590 Related parameters Noload protection Function Noload protection Trip delay Description If the highest phase current of the measured three phase currents falls below the trip level for m ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Descr
29. ally this reduction of output power is done automatically by M101 P M102 P but it is also possible to do it manually which is instructed later in this chapter To calculate the thermal image of the motor being protected the M101 P M102 P needs to know the temperature of the environment in which the motor is running Especially in industries where the motors are located near the heat source the maximum thermal capacity level of the motor is reduced based on 29 ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description the increased surrounding temperature Notes SEP Motors designed for EEx e applications are always rated and certified for a certain maximum ambient temperature most commonly 40 C If EEx e motor is designed for other temperature manufacturer will supply the motor rated data Because of the nature of EEx e motor the output power ratings are not reduced automatically according to ambient temperature by M101 P M102 P Instead of using ambient temperature parameter M101 P M102 P uses fixed value 40 C thus multiplier is one 1 when TOL EEx e model is selected The M101 P M102 P reduces the maximum permitted current by the multiplier as indicated in the table below TOL standard model Ambient temp C 40 45 50 155 160 65 70 75 80 Ambient temp Permitted current In x 1 00 0 96 0 92 0 87 0 82 0 74 0 65 0 58 0 50 Permitted output 96 of rated output
30. any functionality in the M101 P M102 P Alarm only is an option of function disable enable When alarm only is active an alarm occurs only if the measured value is more than the set alarm level This function is disabled automatically in the case of single phase motor and during the motor startup period 11 2 Alarm Level Function Phase Failure Protection Range 10 1 9090 Default setting 8096 Related parameters Phase failure protection Function enable disable Description To avoid motor failure by phase failure the M101 P M102 P calculates the ratio between the lowest phase current to the highest phase current from the measured currents of all three phases If the condition set by this parameter is true There will be a Phase Failure Alarm warning message The Phase Failure Alarm clears automatically on restoration of normal condition 11 3 Trip Level Function Phase Failure Protection Range 5 1 90 Default setting 7090 Related parameters Phase Failure Protection Function Enable Disable ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Phase Failure Protection Trip delay Notes Description When the ratio Corresponds to the value set on trip level the M101 P M102 P will trip after the elapse of trip delay time with a message Phase Failure Trip If normal conditions are restored before the trip the M101 P M102 P will go back to normal operation 11
31. arameters Do Description The user can set a period after which a preventive maintenance is desired When the Running timer exceeds the preset running time alarm level a message Maintenance hours run is generated for the corresponding M101 P M102 P This helps to lubricate and maintain the bearings of the motor within the correct service interval When the parameter is set to 65535 the running time alarm is disabled 20 2 Start number alarm level Function Maintenance Range 0 1 65 535 Default setting 65535 Disabled Related parameters De Description This parameter reflects the control cycles of contactors User can set this parameter in lines with the electrical life of a contactor When start counter has run through the set value of cycles in preset start a ABB ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description number alarm level the corresponding M101 P M102 P generates a message Maintenance contactors Notes This help in carrying out preventive maintenance of power contacts When the parameter is set to 65535 the start number alarm is disabled 21 DIAGNOSIS INFORMATION M101 P M102 P as a slave station gives diagnosis information to master stations on the basis of the following three groups of information Group 1 Alarm information for selection TOL Overload Phase Failure Phase Unbalance Under Load No Load Earth Fault PTC Under Voltage Auto Reclose Contactor Feedback Welded Contactor D
32. as well For example la In ratio for EEx e motor is 7 and parameter te time value is 7 seconds By using the following cold condition time current diagram t6 curve can be found When t6 curve is defined other trip times vs motor current are available Motor ambient temperature is not observed because it does not have affect in TOL EEx e module usage thus la In can directly be used see parameter Ambient temperature The readout is t6 curve which is either existing in the diagram or is an estimation below the defined point In this case Trip class t6 9 seconds is estimated from the example picture below and is drawn to the diagram Trip time for current 3xIn is estimated approx 40 seconds 26 ABB ITNC911106M0202 Edition July 2005 Notes 27 M101 P M102 P Parameter Description Figure4 Trip class definition for TOL EEx e model from cold condition with time current diagram Diagram presented in 40 C Motor ambient temperature Selected t6 curve is exact or estimation below TM AANA DARE Y LL r i 40 a EE TEES ERES ERE 30 iM URNA UE ER ER c s E NEA Uh US UA E 7v E INN 20 er 10 e Le cl lt me ks pe 1 SSS SSS lt lt eS 2 L 1 J P l Cu
33. ases show the different reactions of M102 P in different voltage dip situations Case1 Voltage dip autoreclose time Identical to Standard mode Case1 Case2 autoreclose time lt voltage dip Max power down time Identical to Standard mode Case2 Csae3 Voltage dip Max power down time Identical to Standard mode Case3 Case4 2xdip 200ms within 1s Figure 17 gt 2xdip 200ms within 1s 48 ABB ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description If the interval between two voltage dips which length less than 200ms is less than 1 second Automatic Notes delay restart is triggered after second voltage restore Parameters involved in Autorestart function are as below Function Enable Disable Function mode Max Autoreclose Time Max Powerdown Time Staggered Start Time 18 4 Function Enable Disable Function Autorestart Range Enabled Disabled Default setting Disabled Related parameter Autorestart Parameters Undervoltage Parameters Description The Autorestart function can be disabled with the help of this parameter When disabled the autorestart does not have any functionality in the M102 P Because the function of autorestart is associated with the undervoltage protection If the function is to be enable the undervoltage protection will be enable automatically 18 2 Max Autoreclose Time Function Autorestart Range 100 100 1000 ms Default setting 200ms Related parameter Autorestart
34. ated parameter Stall protection Function enable disable Programmable inputs Function Description Stall trip can be reset in multiple ways depending on the control philosophy It is possible to reset the trip as desired by parameterisation Remote Reset Trip reset is only possible via the fieldbus Local Reset Trip reset is only possible via Digital Input which is assigned for Reset or via operator panel MD 11 Phase Failure Protection Phase failure in motor phase currents is common phenomenon in industrial environment It generally occurs because of pitted contacts in the contactor or SCPD imbalance in the mains supply loose connections blown fuse and faults within the motor It is an extreme situation where a complete loss of phase occurs This can be caused by a utility supply problem or by a blown fuse in one phase Unbalanced phase currents are a major cause of motor thermal damage due to the nature of the current The negative sequence current induced in the rotor is of double the power supply frequency and produces a counter torque to the desired motor output For small unbalances the overall output torque will remain same as motor develops a large positive sequence torque to overcome the negative sequence torque This opposing torque and the high negative sequence current lead to an increased temperature rise in the rotor and stator Reasons for the phase failure are neither temporary nor self covering Although TOL protect
35. ation refer to Phase Failure Protection Parameters involved in unbalance protection are as below Function Enable Disable Alarm Level Trip Level Trip Delay Trip Reset Mode it ABB ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Figure 8 Unbalance protection Notes lum Alarm level Trip level Trip delay 1 2 3 4 5 6 1 alarm 5 trip 2 start trip delay 6 trip reset 3 clear trip delay 4 start trip delay 12 4 Function Enable Disable Function Unbalance protection Range Enabled Disabled Alarm only Default setting Disabled Related parameter Unbalance protection Parameters Motor Information Number of phases 3 phase applications Motor information Motor startup time Motor information Motor startup time N2 Description The unbalance protection function can be disabled with the help of this parameter When disabled the protection function does not have any functionality in the M101 P M102 P Alarm only is an option of function disable enable When alarm only is active an alarm occurs only if the measured value is more than the set alarm level This function is disabled automatically in the case of single phase motor and during the motor startup period 12 2 Alarm Level Function Unbalance protection Range 50 1 90 96 Default setting 9096 Related parameter Unbalance Function Enable Disable Alarm only Description To avoid a motor failure by phase un
36. balance the M101 P M102 P calculates a ratio between the lowest phase current to the highest phase current from the measured currents of all the three phases If the condition set by this parameter is true there will be an Unbalance Alarm warning message The Unbalance alarm clears automatically after normal status is attained 12 3 Trip Level Function Unbalance protection Range 50 1 90 Default setting 8596 Related parameter Unbalance Function Enable Disable Alarm only Unbalance Trip delay ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Description Notes p When the ratio ILwin ILmax corresponds to the value set for this parameter M101 P M102 P will start a countdown set by trip delay parameter after which a trip occurs with a message Unbalance Trip If normal conditions are restored before the trip the M101 P M102 P will go back to normal operation 12 4 Trip Delay Function Unbalance protection Range 0 1 60 sec Default setting 108 Related parameter Unbalance Function Enable Disable Alarm only Unbalance Trip level Description After the trip level level is reached the M101 P M102 P will delay the trip for the time set by this parameter After the set trip delay the M101 P M102 P will trip the motor and give a message Unbalance trip With this delay short phase unbalances can be filtered The M101 P M102 P can later be reset accordin
37. ble for M102 P byte4 byte9 Note 1 Only the Profibus master station can decide which of the cyclical data type Type1 Type2 and Type3 will be mapped to the M101 P M102 P 2 Mcusetup_P software can be used to set the certain function for each configurable type or bit More details pls refer to Profibus DP implementation for M101 M102 T ABB ITNC911106M0202 Edition July 2005
38. cieacssceansacssataconsssacsenassnisicciseassencisansscccesate 39 Alarm Level res 39 TIP E an EE 39 Jg 40 Trip Reset Mode 40 EARTH FAULT stevseseecscasuertetsuerseestoress 40 Function Enable Disable 41 Alarm Level 41 e 41 Trip Delay icin tics cativdees ictietectacsices san scnactacssctsitasdacwesaaseatcdibusceocsvadieuatsonstsactedaabstoadshadtaieasasiaetaciacn 42 BID t4 Dee 42 PROTECTION ONLY FOR 102 42 Function Enable Disable esee c eere 43 Alarm Level 43 43 TIP Delay A E 44 Reset Level m E E E 44 Trip Reset Mode ce 44 UNDERVOLTAGE PROTECTION ONLY FOR M102 P eene 44 Function Enable Disable 45 Alarm LoVe 45 L VGl e
39. ction Motor information Range 1 1 2000A Default setting 100A Related parameters Motor information Nominal Current Motro control Nominal Current N2 Motor information External CT Installed Motor information Internal CT Primary Motor information External CT2 Primary Description This parameter can only be set when External CT Installed is enabled While using an external current transformer for motor nominal current gt 63 A the nominal primary current of the external current transformer is defined by this parameter 3 21 External CT2 Primary Function Motor information Range 1 1 2000A Default setting 100A Related parameters Motor information Starter type NR 2N Motor information Nominal Current Motro control Nominal Current N2 Motor information External CT Installed Motor information Internal CT Primary Motor information External CT1 Primary Description This parameter can only be set when External CT Installed is enabled While two speed Motor information is used another external CT2 must be used the nominal primary current of the external current transformer is defined by this parameter An example of current related setting in M101 P M102 P NR DOL Motor rating 45kW 86A External CT H ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description 100 5 Notes Motor Information Nominal Current 86A Motor Information Nominal Current N2 Not active Motor information External C
40. ction are as below Function Enable Disable Alarm Level Trip Level Trip Delay Trip Reset Mode 36 ABB ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Figure 9 Underload protection Notes EE cO TTE ee SUN 1 Trip level en EU eae ee UMS 1 1 ES 1 Trip delay d d 1 1 1 i o t 1 2 3 4 5 6 1 Alarm message 5 Contactor trip and trip message 2 Trip delay active 6 Reset according to reset mode 3 Trip delay cleared 4 Trip delay active 13 1 Function Enable Disable Function Underload Protection Range Enabled Disabled Alarm only Default setting Disabled Related parameter Motor information Ramp up time Motor information Ramp down time Motor information Startup Time Autotrafo Description Underload protection function can be disabled with the help of this parameter When disabled protection function does not have any functionality in the M101 P M102 P Alarm only is an option of function disable enable When alarm only is active an alarm occurs only if the measured value is more than the set alarm level In the Startup time of Softstarter Autotransformer underload protection is suppressed 13 2 Alarm Level Function Underload Protection Range 20 1 9090 Default setting 3096 Related parameters Underload protection Function Description If the highest phase current ILmax of the measured three phase currents is detecte
41. d below the alarm level then a warning message Underload Alarm is created to inform the operator of the underload condition Underload Alarm clears automatically on restoration of normal condition 13 3 Trip Level Function Underload Protection Range 5 1 90 Default setting 2096 Related parameters Underload protection Function Underload protection Trip delay Description id ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description When current reaches the trip level the M101 P M102 P trips the motor after elapse of trip delay time A message Underload Trip is generated after the trip If normal conditions are restored before the trip the M101 P M102 P will go back to normal operation Notes 13 4 Trip Delay Function Underload Protection Range 0 1 1800s Default setting 108 Related parameters Underload protection Function Underload protection Trip level Description The trip is delayed by the time set by this parameter If underload condition is not back to normal before the elapse of trip delay time a trip is generated with a message With this delay short underload situations can be filtered 13 5 Trip Reset Mode Function Underload Protection Range Remote Local Remote amp Local Default setting Remote amp Local Related parameter Underload protection Function Description Underload trip can be reset in multiple ways depending on the control philosophy It
42. dy of the motor During power failure the thermal capacity level of the motor is stored in the memory and the cooling down calculation starts from this level after resumption of power TOL Protection conforms to IEC 947 4 1 i e with a motor current 1 05xTFLC running for 2 hrs will not cause TOL trip and subsequent rise in current to 1 2xTFLC will cause trip within 2 hrs The time to trip calculation begin when the current is above 1 14xIn The time to reset is calculated after TOL trip and is equal to zero when the thermal image reaches the reset level In case of unbalance situation the fictitious negative sequence current in remaining phases is taken into TOL calculation to trip early Parameters involved in TOL protection are as below Function Disabled Enabled Thermal Model Trip Class t6 Standard model Trip Class te Time EEx e model la In Ratio EEx e model TOL Alarm Level Trip Reset Mode TOL Bypass Command Standard model Cool Coe Ambient temperature ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Figure 1 Illustration of motor thermal simulation behavior Notes Coolingof hotspots in the windings depending on background heat level 0 Bu 100 a mctu Cooling ofmotor irondepending on thecooldown time factor 4 l 4 w d 1 1 TOL alarm message 2 TOL trip and alarm Trip level 3 TOL trip reset 0A Alarm level
43. e 45 1 65Hz Default setting 50Hz Related parameter Do 9 ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Notes Description The user can assign a value within to describe the value of system supply frequency This message is for reference only and does not affect operation of the M101 P M102 P 3 5 Motor Power Rating Function Motor information Range 0 01 0 01 1000kW Default setting 1 5kW Related parameter Motor Information Motor Nominal Current N1 Motor Information Motor Nominal Current N2 Description This is the reference data at rated voltage and frequency The value is given on the motor rating plate and does not affect operation of the M101 P M102 P 3 6 Startup Time N1 Function Motor information Range 11 1 250s Default setting 5s Related parameter Motor information Starter type all Motor information Changeover time TOL protection TOL alarm Stall protection Function enable disable Phase failure protection Function enable disable Unbalance protection Function enable disable Earth fault protection Function enable disable Underload protection Function enable disable Noload protection Function enable disable Description Motor startup time parameter is used to define the maximum startup time for the motor It is the time that is required for the motor to complete its starting sequence The starting sequence is said to be complete when the startup current
44. e is more than the set alarm level This function is disabled automatically in the case of single phase motor and during the motor startup period 17 2 Alarm Level Function Undervoltage protection Range 50 1 100 Default setting 8096 45 1TNC911106M0202 Edition July 2005 Notes 46 M101 P M102 P Parameter Description Related parameter Undervoltage Function Description This parameter defines the voltage level for an undervoltage alarm The undervoltage protection is based on the lowest of the measured phase voltages An alarm Undervoltage alarm is generated when the lowest of the measured voltages is below the parameterised alarm level 17 3 Trip Level Function Undervoltage protection Range 50 1 100 Default setting 6596 Related parameter Undervoltage Protection Function Undervoltage Protection Trip delay Autorestart parameters Description This parameter defines the trip level for the undervoltage protection function When the lowest of the measured phase voltages goes below the trip level the M102 P will start counting a trip delay or into autorestart procession 17 4 Trip Delay Function Undervoltage Protection Range 0 2 0 1 5 sec Default setting 18 Related parameter Autorestart Max power down time Description This parameter defines the time from the undervoltage trip level to the execution of the trip command When the lowest of the measured phase voltages g
45. e motor during locked rotor It is of particular significance when the overload protection is specified for motors destined for use in hazardous locations The te time is for EEx e motors to withstand la In current The parameter value for trip class te time is as rated for EEx e motor in the data book which represents the maximum value Parametrised value for trip class te time can be equal or less than motor rated te time For a faster trip value less than rated is selected With la In ratio this parameter makes it possible for M101 P M102 P unit to calculate the trip time of the motor according to the load M101 P M102 P calculates the trip time for EEx e motor automatically but the trip time for a certain current for further investigation can be defined as presented in this chapter Trip time can be defined with the help of following cold condition time current diagram Diagram is according to TOL standard model cold condition Initial information as parametrised is required la In ratio for EEx e motor te time for EEx e motor When la In ratio is placed on the current IS TFLC axis and te time is placed on the time t axis the co ordinate on which the lines drawn through these points cross each other is located on the t6 curve According to defined t6 curve trip time vs motor current are available from cold condition time current diagram The same t6 curve can be used for defining the trip time from a hot condition time current diagram
46. e resetting 16 6 Trip Reset Mode Function PTC protection Range Auto Remote Local Remote amp Local Default setting Remote amp Local Related parameter PTC protection Function enable disable Description A PTC trip can be reset in multiple ways depending on the control philosophy It is possible to reset the trip as desired by parameterisation Auto Reset The PTC temperature trip resets automatically after the sensor loop resistance goes below the threshold set for the trip reset level Remote Reset Trip reset is only possible via the fieldbus after the PTC loop resistance reaches the trip reset level Local Reset Trip reset is only possible via Digital Input that is assigned for Reset or via operator panel MD 17 Undervoltage Protection only for M102 P The undervoltage protection function protects the motor against overload during voltage dips During a mains undervoltage the electrical energy required to drive the rotor remains same for some period owing to its inertia According to the energy conservation law Mechanical energy Electrical energy VL IL coso Equation 1 Where VL is the motor line voltage IL is the motor line current and Cosphi is the power factor E ABB ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description From equation 1 the motor draws more current during voltage dips to deliver the same mechanical Notes energy The motors switched off during voltage dip o
47. ection function are to be set based on the motor manufacturer s data sheet The parameterisation in the M101 P M102 P is mainly classified into following functions COMMS Communication Motor Information Control Authority Motor Grouping Digital Inputs Programmable Outputs TOL Protection Stall Protection Phase Failure Protection Unbalance Protection Underload Protection Noload Protection Earth fault Protection PTC Protection Undervoltage Protection amp Autorestart only for M102 P Start Limitation Protection Maintenance Diagnosis Information User Defined Data These functions are further subdivided into parameters which need to be set individually The above functions and its related parameters are covered in each of the subsequent chapters While changing any parameter the related parameters that are affected should be noticed by the user and shall be changed if necessary 3 Motor Information Motor information consists of parameters which reflects the configuration of motor feeder For example the ratings for external current transformers and contactor feedback supervision are included Parameters involved with the Motor Information are as below 6 ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Notes 3 1 Starter Type Function Range Default setting Related parameters Description Starter Type Motor Type System Supply Voltage System Frequency Motor Power Rating Star
48. efer to Chapter 8 1 1TNC911106M0202 Edition July 2005 Notes 22 M101 P M102 P Parameter Description 9 Thermal Overload Protection TOL M101 P M102 P protects the motor by calculating the thermal image of the motor both during running and stop This image is used to allow optimal performance of the motor with calculated time to restart and time to trip The thermal image is calculated based on the highest of the three measured phase currents and depends on the parameterised data such as trip class t6 motor ambient temperature Tams cool down time factor Mig Motor ambient temperature is taken into account for thermal image calculation by means of a device internal parameter TFLC Where TFLC is the highest of the measured three phase currents related to motor ambient temperature When the thermal capacity level reaches 1000 the thermal overload trip will occur The TOL trip can be reset after the thermal image goes below the motor reset level The motor can be restarted only after TOL trip is reset When the motor is being stopped the thermal image calculation continues by using the background heat level and cooling down time factor until thermal capacity level decreases to zero The thermal capacity decreases at a constant rate till it reaches the background heat level after which it depends on the parameters trip class and cool down time factor Thus simulating cooling down of the stator winding and the iron bo
49. emoving the M101 P M102 P from the starter will not prevent RCU operation depending however on the connection external relay and or switch is used for start and stop The stop pulse issued by the M101 P M102 P will override the RCU switch start position ACTUATOR only for M102 P Reversing starters for applications like valves dampers actuators etc Actuator starters are reversing direct on line starters where the limit switch inputs are used to stop the motor from running further after reaching the respective end positions When one of the limit switch inputs is active the motor can be started in another direction only In case of an actuator starter with torque sensor the torque switch associated with the sensor is used to stop the motor The limit switch will inhibit the starting to the respective direction and indicate the respective stop position One of the digital inputs can be used as input for the torque sensor If the torque sensor activates before the limit switch the motor is tripped with a message DI trip NR S D only for M102 P Reduced voltage starting in star and running of the motor in delta after meeting the transition conditions Star delta starters are used mainly to restrict the starting current of a motor due to supply limitations The motor is started with the winding connected in star and transferred to delta after the Changeover time The starting at a lower voltage also reduces shocks on the motor couplin
50. ent temperature is derived when Is and TFLC are known Is 7 5xIn _ TFLC 1 00x In The calculated start current ratio 7 5 and motor maximum start time 30 second are placed on the cold condition time current characteristic diagram Start current ratio is located on the horizontal axis while the maximum permitted time for cold motor start is set on the vertical axis The cross point of these ABB 1TNC911106M0202 Edition July 2005 Notes 25 ITNC911106M0202 M101 P M102 P Parameter Description constraints shows the maximum setting for Trip class t6 The received setting is the absolute maximum value without further considerations and a lower value can be selected A longer start is not protected by thermal protection and additional protection against stalled rotor is necessary In case of thermal protection trip at start with the setting of maximum Trip class t6 value it is recommended to check the motor size for extreme start requirement Now the setting of 40 second is limited by the range of parameter Value for Trip class t6 is derived from the cold condition time current diagram see the picture This setting allows start time up to approx 26 second for cold motor before a thermal protection trip occurs The start time for a warm motor with this parameter setting can be read from the hot condition time current diagram accordingly The check routine is shown in the latter picture The warm condition start must be wi
51. eset required or an alarm whenever the Process Interlock switch is unhealthy 8 Programmable Outputs 20 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description There are two separate programmable outputs in M102 P and there only one programmable outputs in Notes M101 P These outputs can be assigned the different function The parameters under programmable outputs are as below Function Start Stop delay 8 1 Function Function Programmable Outputs Range Energize on start delay De energize on stop delay Fieldbus control DI9 status DI10 status DI11 status Trips Ground fault trip Overload Watchdog output Communication failure RCU Mode only for M101 P Local remote output only for M102 P Default setting Fieldbus control Related parameter Programmable outputs Start Stop delay Description Energize on motor start delay The output relay is energized with a delay when motor is started De energize on motor stop delay The output relay is de energized with a delay when motor is stopped Fieldbus control The relay can be energized or de energized the fieldbus DI9 Status The relay will energize while DI9 switch is closed DI10 Status The relay will energize while 0110 is closed 0111 Status The relay will energize while 0111 switch is closed Trips The relay is energized when there is no trip When a trip occurs the relay will be de energized Resetting M101 P M102 P will energize the
52. f the TOL protection from the cold state motor must be less than the te time rated for the motor For EEx e thermal model a set of parameters have fixed values or are not available in order to simplify parametering instructions and parametering process while providing a secured protection functionality 23 ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description This should be carefully considered by the user since the given parameter value do not have effect to Notes functionality in this case These are following parameters are not available when EEx e mode is selected Motor information Motor ambient temperature Fixed 40 C TOL Protection TOL bypass command Disabled 9 3 Trip Class T6 Function TOL Protection Range 3 1 408 Default setting 68 Related parameter TOL Protection Thermal Model standard Motor Information Nominal Current In Motor information Motor Ambient Temperature Description Parameter trip class t6 is the basic setting of the thermal protection function For user it provides the possibility to set the thermal model characteristic according to motor startup requirements and characteristic With trip class parameter user defines the time that protection allows current of 6x In from cold condition for protected motor Motor start up is the most common occurrence of the short overload situations Normally two starts from cold condition and one start from a hot condition are perm
53. g belts and the gear mechanisms The starting current and the torque is reduced to 1 3 of the DOL value However it must be determined whether the reduced motor torque is sufficient to accelerate the load over the whole speed range The changeover is based on time the star to delta transition takes place after the parameterised Changeover time The star to delta switchover is done with a transition time of maximum to ensure quenching of the arc in star operation before it changes over to delta to prevent short circuit During the contactor transitions the M102 P waits until the previous sequence is successfully completed In case of any contactor failure the feedback supervision trip will open all the contactors NR 2N only for M102 P Non reversible two speed motor Two speed drives are used for applications requiring dual motor outputs In case of two speed drives there are separate commands for the two speeds When started by command speed1 the contactor CCA is closed and when started by command speed2 the contactor CCB is closed The contactor CCC is used for stopping the motor Two speed starter can be implemented either as Dahlander or separate winding starter Current measurement for two speed starter uses external current transformer Autotransformer only for M102 P Non reversible motor starter based on reduced voltage via auto transformer 8 ABB ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Descr
54. g to the trip reset mode parameter 12 5 Trip Reset Mode Function Unbalance protection Range Remote Local Remote amp Local Default setting Remote amp Local Related parameter Unbalance protection Function Enable Disable Alarm only Description A phase unbalance trip can be reset in multiple ways Depending on the control philosophy it is possible to reset the trip as desired by suitable parameterisation Remote Reset Unbalance trip reset is possible via the fieldbus Local Reset Unbalance trip reset is only possible via Digital Input which is assigned for Reset or via operator panel MD 13 Underload Protection Underload protection function monitors the process against loss or decrease in motor load This protection function is current based protection It is especially useful for indication of loss of suction for pumps broken belt for conveyors loss of airflow for fans broken tools for machines etc Such states do not harm the motor but early diagnosis helps to minimise the extent of damage to the mechanical installation and subsequent loss of production The motors on underload draw mainly the magnetising current and a small load current to overcome frictional losses Therefore the other reason to isolate the motors on underload is to reduce the reactive load on the power system network Underload protection function is based on the highest measured phase current Parameters involved in underload prote
55. ies from 40 to 100A The nominal motor current can be set within this range 3 18 Motor Nominal Current N2 Function Motor information Range 0 4 1 0 Default setting 0A Related parameters Motor Information Motor Power Rating Motor information External CT parameters Description This is the rated current In of the motor at rated load at rated voltage and frequency The value is given on the motor rating plate The rated current can be set within this range 13 ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description In the case of starter with external current transformers the range is dependent on the nominal primary Notes current of the current transformer The range varies from 0 4 to 1 0 of CT nominal primary current 3 49 External CT Used Function Motor information Range Disabled Enabled Default setting Disabled Related parameters Motor information Nominal Current Motor information Nominal Current N2 Motor information External CT1 Primary Motor information External CT2 Primary Description An internal CT is integrated inside M101 P M102 P when motor current is not up to 63A However External CTs are required when over than 63A This parameter is to active external CTs input in the latter case Example In the case of an external current transformer of 100A the range varies from 40 to 100 A The nominal motor current can be set within this range 3 20 External CT1 Primary Fun
56. ion Human Machine Interface 6 Motor Grouping Attention The function of Motor Grouping is not available for Profibus DPVO In the case of conventional switchgear the operator can start or stop a process by sequentially starting or stopping of the motors The required delay between the motors is introduced either manually or with the help of a timer and serial interlocks This would increase the operators time cabling and the initial cost of the starter With help of intelligent system the operator could start or stop the process with a single group command The start and stop delay can be set for individual motors The serial communication with logical connections between devices reduces the cabling process interlocks and the hardware In case of abnormality in any motor of the group a group tripping would follow In this context a motor group means a collection of motors which are operated by an individual group start or stop command The successful start of the motor group is indicated 16 ABB 1TNC911106M0202 Edition July 2005 Notes 17 M101 P M102 P Parameter Description Note Individual start stop command from fieldbus can also be given to the devices located in the group as well as via the switches connected to the device I O in the local mode The parameters under motor grouping function are as below Function Enable Disable Group Start Direction Group Number Group Identifier Group Start Delay Group Stop Delay
57. ion performs an accelerated trip during phase failure and unbalance over 20 there are no good reasons to wait for the trip to occur through TOL protection By the use of phase failure protection a motor can be tripped without waiting for thermal calculation Indeed phase failure protection should be parameterised to trip in shorter time than TOL does Parameters involved in Phase failure protection are as below Function Enabled Disable Alarm Level Trip Level Trip Delay Trip Reset Mode 32 ABB ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Figure 7 Phase failure protection Notes luu D ro Mie c THpdevel hea 1 1 1 1 Trip delay 1 1 1 1 1 1 1 1 1 2 3 4 5 6 1 Alarm message 5 Contactor trip and trip message 2 Trip delay active 6 Reset according to reset mode 3 Trip delay cleared 4 Trip delay active 11 1 Function Enable Disable Function Phase Failure Protection Range Enabled Disabled Alarm only Related parameter Phase Failure Protection Parameters Motor information Startup Time Motor information Startup Time N2 Motor information Ramp Time Motor information Motor type Description Phase failure protection function can be disabled with the help of this parameter When disabled protection function does not have
58. iption Auto transformer is used in order to reduce motor start current during start condition While reduced voltage limit the starting current also usable torque is limited significantly This must be considered carefully when designing starter based auto transformer Notes NR Softstarter only for M102 P Non reversible Softstarter control Softstarter applications are for controlling motor accessory softstarter device M101 P M102 P gives start and stop commands to the softstarter unit The softstarter is set for adjusting motor voltage with it s own parameters More information about softstarter can be found from softstarter s manual When Start command is given the internal relay CCA remains closed until the stop command is given Rev Softstarter only for M102 P Reversible softstarter control Functionality of this starter type is according to NR softstarter starter with support for reversing use of motor When Start CW command is given the internal relay CCA is closed first to control contactor followed by the closing of CCC to start the softstarter amp CCC remain closed until a stop command The direction of the motor can be changed only after a stop Similarly when CCW start command is given the internal relay CCB is closed first to control contactor then the CCC is closed to start the softstarter CCB amp CCC remain closed until a stop command Feeder The feeder application is regarded as specific starter
59. iption longer than the time period set by the trip delay the M101 P M102 P trips the motor with a Noload Trip Notes message 14 4 Trip Delay Function Noload Protection Range 0 1 1800s Default setting 5s Related parameters Noload protection Function Noload protection Trip level Description When the current reach the no load trip level the M101 P M102 P trips the motor after elapse of trip delay time A message Noload Trip is generated after the trip If normal conditions are restored before the trip the M101 P M102 P will go back to normal operation With this delay a short noload situations can be filtered 14 5 Trip Reset Mode Function Noload Protection Range Remote Local Remote amp Local Default setting Remote amp Local Related parameter No load protection Function Description The noload trip can be reset in multiple ways depending on the control philosophy It is possible to reset the trip as desired by suitable parameterisation Remote Reset Noload trip reset is possible via the fieldbus Local Reset Noload trip reset is only possible via Digital Input which is assigned for Reset or via operator panel MD 15 Earth Fault Protection The earth fault protection function protects the motor and the network against ground current flow During earth fault the motors can reach a dangerous potential above the ground level thus posing safety hazard to personnel The
60. is possible to reset the trip as desired by suitable parameterisation Remote Reset The Underload Trip reset is possible via the fieldbus Local Reset The Underload Trip reset is only possible via Digital Input which is assigned for Reset or via operator panel MD 14 Noload Protection The noload protection function protects the process against sudden loss of load Though this condition does not harm the motor but requires a switch off to safe guard the process The no load current is of the order of 0 2 to 0 6 In depending on the size and speed of the motor The no load current of slow speed motors is high and that of large motors is low The noload protection function is based on the highest phase current measured by the current measurement unit The noload protection function detects missing current with respect to the contactor and the main switch ON feedback and executes actions as parameterised Parameters involved in noload protection are as below Function Enabled Disable Alarm Level Trip Level Trip Delay Trip Reset Mode 38 ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Figure 10 Noload protection Notes In cnr MEMEDE A NS BURN HERI CEDENS ME usd Trip delay gt 2 uw 3 E t 1 2 3 4 5 6 1 Alarm message 5 Contactor trip and trip message 2 Trip delay active 6 Reset
61. itted The Trip class t6 value can be set according to one cold start which allows easy setting of protection The Trip class t6 time for protection is defined based on the motor maximum start time which is informed by the manufacturer Initial information required for Trip class t6 definition Motor startup current ratio rated motor data Is In see parameterStartup ratio Maximum start time permitted for cold motor Maximum start time permitted for warm motor Motor ambient temperature see parameter Motor ambient temperature Example 1 A thermal protection is set for a motor M2BA315SMC 110 kW Motor startup current ratio Is In 7 5 Maximum start time for cold motor 30s Maximum start time for warm motor 15s Motor ambient temperature 40 With the initial information the protection characteristic can be defined by the following procedure First the motor start current is calculated according to the ambient temperature Practically with 40 of ambient temperature the following calculation for start current can be passed For more information of ambient temperature coefficient see table of maximum permitted current in chapter Ambient Temperature Temperature coefficient is derived with the following routine Since the motor ambient temperature in the example is 40 C the TFLC is 1 00 x In Motor startup current ratio is 7 5 thus motor rated start current Is is WA Is mn X In The effect of ambi
62. l If motor data specifies the number of starts during a certain time span the advantage of this protection function can be taken of supervising the number of starts On some other cases process may put requirements for the motor start number thus this protection can be employed Functionality is presented in the following example The next picture presents the start limitation protection with 3 starts allowed 1 Normal situation after stop command motor can be started normally Start 2 Every start activates an internal timer for the time defined by time interval parameter The number of active timers are reviewed after every stop command and compared to value of number of starts parameter Stop command can thus exist during active or elapsed timer 2 Two timers are still active thus stop command generates alarm message Start limitation alarm and one more start is allowed Start 3 3 The 3rd start has been executed A contactor trip and trip message Start Limitation Trip alarm will follow when motor is stopped while there are two active timers here starting from Start 1 When start limitation trip is active the time to reset is provided to the fieldbus 4 Trip can be reset when the first timer from Start 1 is finished Motor start is possible when all pending trips are reset Supervision continues with a new timer from Start 4 50 ABB ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Descrip
63. mains above the trip level for a pre set trip delay time the M101 P M102 P will generate a trip command with a message Earth fault trip If normal conditions are restored before the trip delay time elapses the M101 P M102 P will go back to normal operation 15 4 Trip Delay Function Earth Fault Protection Range 0 2 0 1 60 sec Default setting 108 Related parameter Earth fault Function Earth fault Trip level Description When the earth fault current rises above the trip level the M101 P M102 P will execute a trip command after elapse of the time specified in the trip delay parameter The trip is followed with a message Earth Fault Trip The count down is reset if the earth fault current goes below the trip level before the pre set trip delay The trip is reset depending on the parameterisation of the trip reset mode 15 5 Trip Reset Mode Function Earth fault protection Range Remote Local Remote amp Local Default setting Remote amp Local Related parameter Earth Fault Protection Function Description An earth fault trip can be reset in multiple ways depending on the control philosophy It is possible to reset the trip as desired by parameterisation Remote Reset The trip reset is only via the fieldbus Local Reset The trip reset is only possible via Digital Input which is assigned for Reset or via operator panel MD 16 PTC Protection only for M102 P PTC thermistors are semiconductor
64. n TOL Protection Range 10 1 60 Default setting 50 Related parameter D Description Following a TOL trip the thermal capacity of the motor is descreasing Until the motor thermal level reaches thermal capacity level set by this parameter TOL trip cannot be reset Nor can restart the motor before resetting 9 9 Trip Reset Mode Function TOL Protection Range Auto Remote Local Remote amp Local Default setting Remote amp Local Related parameter Programmable inputs Function Description TOL trip can be reset in multiple ways depending on the control philosophy It is possible to reset the fault as desired by parameterisation Auto Reset Trip resets automatically after the calculated thermal capacity attains the reset level time to reset reaches 0 Remote Reset Trip reset is only possible after the calculated thermal capacity attains the reset level via the fieldbus Local Reset Trip reset is only possible after the calculated thermal capacity attains the reset level via Digital Input which is assigned for Reset or via operator panel 9 10 TOL Bypass Enable Disable Function TOL protection Range Enabled Disabled Default setting Disabled Related parameter TOL protection Thermal model standard Description The operation of the TOL protection function can be prevented by a special TOL bypass command given via the fieldbus when the thermal level rises over the TOL alarm level With the TOL by
65. nctional impact on the 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description motor control unit The motors belonging to a specific motor group are identified by the same name 6 5 Group Start Delay Function Motor Grouping Range 0 1 300s Default setting 0s Related parameters Motor grouping Group start direction Motor grouping Motor startup time Motor grouping Group number Description This is the delay for the start of the motor after receipt of the group start command 6 6 Group Stop Delay Function Motor Grouping Range 0 1 300s Default setting 08 Related parameters Do Description This is the delay for the stop of the motor after receipt of the group stop command 7 Digital Inputs The M101 P M102 P has 13 programmable digital inputs for motor control and supervision Each input can be configured with various functions according to the predefined list These functions Limit1 Limit2 PLC contact F CA F CB F CC Loc R Main switch status MCCB trip input only can be assigned for one time at the same parameterization file For each input specific characteristic such as Contactor Type Delay etc can be defined to different purposes The parameters under digital inputs are as below Function Contactor Type Operation Delay Operation 7 1 Function Function Digital input Range NOP Start1 Start2 Stop Limit1 Limit2 Process interlock1 Process interlock
66. nly for M102 P Function Motor information Range 1 1 250 sec Default setting 10s Related parameter Motor information Starter type NR Softstarter REV Softstarter Phase Failure Protection Unbalance Protection Underload Protection Noload Protection Description Softstarter is a separate unit to start motor in a smooth way by limiting inrush current The ramp up time is the parameter of softstarter set to start up the motor Upon this delay the listed protection functions are deactivated Phase current loss Unbalance Underload No load M102 P control the motor by giving start stop commands to the softstarter The motor protection is done by the softstarter during startup Note The accuracy of the current measurement is affected by the harmonics caused by the soft starters 3 10 Ramp Down Time only for M102 P Function Motor information Range 1 1 250 sec Default setting 10s Related parameter Motor information Starter type NR DOL REV DOL Phase Failure Protection Unbalance Protection Underload Protection Noload Protection Description Softstarter unit has a parameter which is used to select the stop ramp time of the motor M102 P is adapted to this stop time by setting the Ramp down time 2 selected stop ramp time of the motor 3 11 Failsafe Mode Function Motor control us ABB ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Range Start1 CW Start2 CCW Tri Notes TO
67. oes below the trip level for a time specified in the trip delay the M102 P will open the contactor 17 5 Reset Level Function Undervoltage Protection Range 50 1 100 Default setting 9096 Related parameter Undervoltage Trip delay Autorestart Max autoreclose time Autorestart Max power down time Autorestart Staggered start time Description The reset voltage level is a voltage limit for restarting the motor after an undervoltage trip The motor will start immediately or after a delay depending on the time during which the reset voltage level is reached refer figure 17 6 Trip Reset Mode Function Undervoltage protection Range Auto Remote Local Remote amp Local Default setting Remote amp Local Related parameter Undervoltage Function Description An undervoltage trip can be reset in multiple ways depending on the control philosophy It is possible to ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description reset the trip as desired by parameterisation Notes Auto Reset Undervoltage trip resets automatically after the voltage goes above the reset voltage level Remote Reset Trip reset is only possible via the fieldbus after the voltage goes above the reset voltage level Local Reset Trip reset is only possible via Digital Input that is assigned for Reset or via operator panel MD 18 Autorestart Function only for M102 P The phase A U
68. p command will close 1TNC911106M0202 Edition July 2005 ABB M101 P M102 P Parameter Description relay CCC for 1 sec The wiring of the self auxiliary contact across the start command latches the Notes contactor Removing the M101 P M102 P from the starter will not prevent RCU operation depending however on the connection external relay and or switch is used for start and stop The stop pulse issued by the M101 P M102 P will override the RCU switch start position REV DOL Reversing Direct On Line REV Reversing means that the motor can run in both directions clockwise CW counter clockwise REV DOL is reversing direct on line starters The motor can be run both directions clockwise and counter clockwise and can be stopped When Start CW command is given the internal relay CCA remains closed until the stop command is given The direction of the motor can be changed only after a stop Similarly wnen CCW start command is given the internal relay CCB remains closed until a stop command The relay CCC has no function REV DOL RCU Reversing Direct On Line remote control of the contactor bypassing the M101 P M102 P The Start CW command closes the internal relay CCA 1sec respectively The Start CCW command closes the internal relay CCB 1sec respectively only after a stop The stop command will close relay CCC for 1 sec The wiring of the self auxiliary contact across the start command latches the contactor R
69. pass feature the thermal level can be raised up to 200 after which a trip will be executed The possibility for execution of this command is enabled by this parameter If there is no trip the TOL bypass command sent before is automatically deactivated when the thermal capacity decreases below the TOL alarm level An emergency restart is possible with the thermal capacity being above the startup inhibit level by issuing a start command immediately after TOL bypass command TOL bypass command cannot be enabled when the EEx e parameter is active Note TOL Bypass function can t be available for Profibus DPVO 9 11 Cooling Coe Mt6 Function TOL Protection 28 ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Range 1 1 10 Notes 0 Related parameter Do Description For an accurate thermal image of the motor M101 P M102 P needs to know the characteristics of the motor to be controlled Different motors in different environments need different time periods to warm up and to cool down The cooling down period for a stopped motor is usually about four times longer than the warm up period and it certainly differs within the motor e g in certain hot spots of the windings from the iron core But this value can be different depending on dirt or other material covering the motor motor body size weight installation place etc The normal value for the parameter is between 4 8 descriping the slower cooling for a s
70. r power failure can be restarted on power resumption sequentially to prevent simultaneous switch on of the motors and thus prevent another mains failure on the network The tripping of motors due to undervoltage of short duration can be bypassed The feature also would help to restart the process on power resumption by sequentially starting the motors staggered start The Undervoltage protection also prevents startup of the motor if the voltage is not high enough and indicates phaseloss before switching ON the motor Parameters involved in undervoltage protection are as below Function Enable Disable Alarm Level Trip Level Trip Delay Reset Voltage Level Trip Reset Mode Figure 13 Undervoltage protection Ulmin Resore level 1 Alarm Alarm level 2 Alarm clear Trip level 3 Trip 17 4 Function Enable Disable Function Undervoltage Protection Range Enabled Disabled Alarm only Default setting Disabled Related parameter Undervoltage Parameters Autorestart Function Description The undervoltage protection function can be disabled with the help of this parameter When disabled the protection function does not have any functionality in the M102 P Because the function of autorestart is associated with the undervoltage protection If the undervoltage protection is disabled the function of autorestart can not be enabled Alarm only is an option of function disable enable When alarm only is active an alarm occurs only if the measured valu
71. re with operation delay is set to 0 a motor start is prohibited if the unhealthy contact is detected iii When one of Digital Inputs is defined as Emergency stop or Torque switch the input is regarded as unhealthy if high low input is detected as different from the setting contact type i e If contact type set NO a high input will be regarded as unhealthy input 7 8 Operation delay Function Digital input Range 0 3600s Default setting 0s Related parameter Digital input Function process interlock1 process interlock2 Description For process interlock1 this parameter sets the amount of time that the Process interlock switch can remain open on the occurrence of a motor start If the switch remains unhealthy for longer than this time trip stop will occur If this parameter is set to 0 that the process interlock switch must be healthy in order for M101 P M102 P to allow the motor to start For process interlock2 this parameter sets the amount of time that the process interlock switch can be unhealthy during normal running If the switch remains unhealthy for longer than this time a trip stop will occur 7 4 Operation Function Digital input Range Stop trip only alarm only trip and alarm Default setting Stop Related parameter Function process interlock1 process interlock2 Description this parameter determines whether process interlock feature is a trip reset required in order to restart the motor or a stop no r
72. reaching the normal condition i e resistance restores below alarm level 16 3 Trip Level Function PTC protection Range 100 1 10 000 Ohms Default setting 3 600 Related parameter PTC protection Function i ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Description Notes When PTC resistance remains above the trip level for a pre set trip delay time the M102 P will generate a trip command with a message PTC trip If normal conditions are restored before the trip delay time elapses the M102 P will go back to normal operation 16 4 Trip Delay Function PTC Protection Range 1 1 1800 sec Default setting 18 Related parameter PTC Protection Function PTC Protection Trip level Description When the PTC resistance rises above the trip level the M102 P will execute a trip command after elapse of the time specified in the trip delay parameter The trip is followed with a message PTC Trip The count down is reset if PTC resistance goes below the trip level before the pre set trip delay The trip is reset depending on the parameterisation of the trip reset mode 16 5 Reset Level Function PTC Protection Range 100 1 10 000 Ohms Default setting 1 600 Ohms Related parameter PTC protection Function Description Following a PTC trip the resistance of PTC is decreasing Until the resistance reaches the level set by this parameter PTC trip cannot be reset Nor can restart the motor befor
73. rive Failed to Start Drive Failed to Stop Start Limitation Ready to Trip Reset Running Time Start Number DIO 011 DI2 DI3 014 015 DI6 017 018 DI9 DI10 DI11 DI12 Group 2 Trip information for selection TOL Stalled Failure Phase Failure Phase Unbalance Under Load No Load Earth Fault PTC Under Voltage Contactor Feedback Start Limitation Feeder DIO DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10 DI11 DI12 Group 3 Other information for selection Signal input from terminal X1 DIO 011 012 DI3 014 DI5 016 DI7 DI8 DI9 DI10 DI11 0112 Trigger resource Field MD2 Field Bus DIO DI2 013 015 DI6 017 DI8 019 DI10 DI11 DI12 Other Information Block DP Discrepancy in parameter settings Hardware Fault Parameter Status Current of Last TOL trip By tipping the ticket in front of each message user can defined what message needed to send out 22 USER DEFINED DATA The M101 P M102 P contains a User Definable Data area in the memory map Three data structures are available for user to define in different applications Up to 12 bytes data can be sent out to Profibus master station with three options of 4 bytes 8 bytes 12bytes The functions for selection are as below 4 Bytes In and 2 Bytes Out No bytes are mappable But in the Configurable Area Byte1 bit4 7 can be defined for Dls DIO DI12 by user Type2 8 Bytes In and 2 Bytes Out 3 bytes in are mappable by master station Da
74. rrent at lain 7 9 5 la In Function TOL protection Range 1 2 0 1 8 Default setting 215 Related parameter TOL protection Thermal model EEx e TOL protection Trip class te time Description 05 ds 255 155 05 75 5s Is TFLC It is the ratio of stall current to the nominal current for EEx e application The motor shall withstand this current for the duration trip class te time This information is rated for EEx e motor and available in motor data sheet 9 6 TOL Alarm Level Function TOL Protection Range 60 1 10096 Default setting 9096 Related parameter De Description When the motor thermal level reaches thermal capacity level set by this parameter the M101 P M102 P sends a warning TOL Alarm The TOL alarm is automatically reset when the thermal capacity reaches the parameterised TOL alarm level again An O L alarm and the time to trip is reported when the motor current exceeds 1 14 x In The time to reset becomes zero when the reset level is reached 9 7 TOL Trip Level Function Range 1TNC911106M0202 Edition July 2005 TOL Protection 60 1 100 M101 P M102 P Parameter Description Default settin 100 Notes s Related parameter Do Description When the motor thermal level reaches thermal capacity level set by this parameter M101 P M102 P issues a trip command to stop motor with a message TOL Trip 9 8 TOL Reset Level Functio
75. t has decreased under 1 25 x In after current inrush time specified by motor startup time parameter has elapsed 10 2 Trip Level Function Stall Protection Range 120 10 80096 Default setting 400 Related parameters Stall protection Function enable disable Stall protection Trip delay Description When the highest of the measured phase currents remains above the set value for a trip delay time the M101 P M102 P will perform a trip with a message Stall trip If normal conditions are restored before the trip delay elapses the M101 P M102 P will go back to normal operation The trip level referenced to In shall be set based on the motor technical data sheet supplied by the manufacturer and the requirements restrictions of the application 10 3 Trip Delay Function Stall Protection Range 0 0 0 1 25 05 Default setting 0 58 Related parameters Stall Protection Function Enable Disable al ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Stall protection Trip level Notes Description When the condition for a stall trip is present the M101 P M102 P will start a count down for the time specified in trip delay parameter The trip is followed with a message Stall Trip The trip delay shall be based on the requirements restrictions of the application 10 4 Trip Reset Mode Function Stall Protection Range Remote Local Remote amp Local Default setting Remote amp Local Rel
76. t setting Remote amp Local Related parameter Start limitation Function enable disable Description This parameter defines the trip reset modes for the start limitation protection trip Remote The Start limitation trip can be reset via the fieldbus Local The Start limitation trip is only possible via Digital Input that is assigned for Reset or via operator panel MD 20 Maintenance Preventive maintenance is the best way to have long service life for any equipment Maintenance function can be configured suitably as a reminder for preventive maintenance This would reap high benefits to the user in terms of reduced process down time and loss due to stoppage of production Maintenance function indicates the operation of the motor in terms of hours run and the usage of starter in the form of operating cycles Number of hours run helps to assess the bearing life and it s lubrication or replacement whereas the number of operating cycles help in deciding replacement of worn out power contacts or the contactor itself Maintenance alarm can be activated after lapse of the set counter The counters can be set after maintenance according to two different principles depending of course on normal routine of the user Parameters under Maintenance function are as below Running time alarm level Start number alarm level 20 1 Running time alarm level Function Maintenance Range 0 1 65 535 h Default setting 65535 Disabled Related p
77. ta assignable for byte4 amp 5 two bytes value only includes la In Ib In Ic In Ua Ub Uc Power Factor Ground Current Power Thermistor value Data assignable for byte6 Thermal Capacity And 12 bits can be defined to Dis DIO DI1 012 DI3 DI4 DI5 016 017 DI8 019 D110 D111 DI12 by user 4 bits come from Configurable Area Byte1 bit4 7 8 bits come from User definable area byte 7 bit0 7 Note Ua Ub Uc Power Factor Power and Thermistor value are available for M102 P byte4 amp 5 Type3 12 Bytes In and 2 Bytes Out 7 bytes in are mappable by master station Data assignable for byte4 amp 5 two bytes value only includes la In Ib In Ic In Ua Ub Uc ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Power Factor Ground Current Power Thermistor value Notes Data assignable for byte6 amp 7 two bytes value only includes la In Ib In Ic In Ua Ub Uc Power Factor Ground Current Power Thermistor value Data assignable for byte8 amp 9 two bytes value only includes la In Ib In Ic In Ua Ub Uc Power Factor Ground Current Power Thermistor value Data assignable for byte10 Thermal Capacity And 12 bits can be defined to DIS DIO DI2 DI3 DI4 DI5 DI6 DI7 DI8 019 DI10 DI11 DI12 by user 4 bits come from Configurable Area Byte1 bit4 7 8 bits come from User definable area byte 11 bit0 7 Note Ua Ub Uc Power Factor Power and Thermistor value are availa
78. test position M101 P M102 P monitors the I O statuses and phase currents voltages Contactor operations by M101 P M102 P are allowed but all protection functions based on the current and voltage measurement are disabled and the test of control circuit is allowed Emergency Stop If the input is defined as emergency stop M102 will activate a stop command the motor after a high input is detected PLC Contact M101 P M102 P accepts the commands from PLC to control motor when programmable DI is configured as PLC Control When the PLC contact closes the motor runs When the contact opens the motor stops This input is only suitable for no reversing starter Trip Reset the input is used to reset after a trip Torque switch The input is used to check the status of torque switch used for Actuator Starter When the input is different from normal state M101 P M102 P will release all contactor control relays to stop the motor F CA That is contactor control A feedback F CB That is contactor control B feedback F CC That is contactor control C feedback Loc R That is Local Remote control switch input Main switch status That is auxiliary contact from main switch It s used to indicate the status of main Switch MCCB Trip Input That is feedback contact when the circuit breaker tripped Only use for the starter type Feeder 7 2 Contactor type Function Digital input Range NO NC Default setting NO Related parameter Digital input Func
79. thin motor ratings In this case the start time for a warm motor is approximated from the latter picture and must be shorter than 12 second as read from the picture In practice start lasting longer than 12 second will lead to trip from the thermal protection Figure 2 Trip class t6 definition from cold condition time current diagram Diagram presented in 40 C Motor ambient temperature t s f Hy EM 4 J _f ___ __ f __ __ __ _ 200 lt b ENS SSS Ie 9 i T j nt es Ny JY Mi 11111 E Figure 3 Start time vs Trip class t6 definition from hot condition time current diagram Edition July 2005 Diagram presented in 40 C Motor ambient temperature fi l f M AA UL LL TI Il 7 F 1 4 1 F AM PAP LOU LI i wi LB VADE LLL TI MIU ABER LIE LL Wf OBL UU Wi 7s 5s Is TFLC
80. tion Notes Figure 18 gt Start limitation alarm Time interval Stat 4 Start 3 The parameters involved with the protection function are Function Enable Disable Time interval Number of starts Trip reset mode 19 1 Function Enable Disable Function Start limitation protection Range Enabled Disabled Default setting Disabled Related parameter Start limitation Parameters Description The start limitation protection function can be disabled with the help of this parameter When disabled the protection function does not have any functionality in the M101 P M102 P 19 2 Time Interval Function Start limitation protection Range 1 1 600 min Default setting 1min Related parameter Start limitation Number of starts Description During this time interval the number of starts is limited by setting the parameter number of starts 19 3 Number of Starts Function Start limitation protection Range 1 1 10 Default setting 22 Related parameter Start limitation Time interval 51 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Description Notes This parameter defines the number of allowed starts during a predefined time window set by the parameter time interval If this value is set to one the parameterised time interval will define the time between two consecutive starts 19 4 Trip Reset Mode Function Start limitation protection Range Remote Local Remote amp Local Defaul
81. tion Description This parameter is used to define the normal state of the input Normally open or normally closed Digital Inputs have many functions for selection and different functions have different characters The below table shows the details 13 ABB ITNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description i Trigger Digital Input isis Notes Mode Contactor type Function Description Start1 Start2 If the input status is deferent as the setting the Edge BERE function will be active triggering Stop Trip Reset NO PLC contact Please see7 1 Process Interlock1 If the input status is the same as the setting the function will be active NO NC Emergency Stop If the input status is deferent as the setting the Torque switch function will be active Level triggering Process Interlock2 NO Test switch If the input status is open M102 is in the test position whereas in the normal position NO NC NOP Only detect the input status Note i When motor starter type is Actuator of Digital Inputs may be defined as Torque switch input if needed The wiring details pls refer to user guide ii When one of Digital Inputs is defined as Process interlock1 the input is regarded as unhealthy if the high low is detected as the same type as the preset contact type i e If contact type is set as NO type a low input will be regarded as unhealthy input Therefo
82. topped motor curve 1 and 2 than cooling of a running motor curve 3 In practise this has been discovered as the normal rule for motors covering various applications However if motor manufacturer gives recommendation for another value it may be set to the protection For example External cooling system is installed for improving the cooling down of a stopped motor Furthermore according to statement from motor manufacturer cooling time constants for a running and stopped motor are equal Thus the parameter can be set below recommended value 4 curve 1 Figure 5 Cooling Coe Mt6 parameter influence on stopped motor cooling principle picture 100 96 90 80 70 60 7 50 96 Mt6 8 40 3 2 4 THERMAL CAPACITY 30 90 7 20 4 10 9 Mtg 1 0 96 T T Motor current 10 0 0 10 0 20 0 30 0 40 0 50 0 TIME min 9 12 Ambient Temperature Function Motor information Range 0 5 80 C Default setting 40 C Related parameter TOL protection Thermal model Motor information Nominal current TOL protection Trip class TOL protection Trip class te time TOL protection TOL and O L Alarm Description Motors of basic design are intended for operation in a maximum ambient temperature of 40 C If a motor is to be operated in higher ambient temperature it should normally be derated and should not be loaded to the same thermal capacity Norm
83. tup Time N1 Startup Time N2 Changeover time only for M102 P Ramp Up Time only for M102 P Ramp Down Time only for M102 P Failsafe Mode Communication Failure delay Feedback Internal CT Primary Earth Fault Primary Motor Nominal Current Motor Nominal Current N2 VT Primary L N only for M102 P External CT Used External CT1 Primary External CT2 Primary Motor information M101 P NR DOL NR DOL RCU REV DOL REV DOL RCU Feeder M102 P NR DOL NR DOL RCU REV DOL REV DOL RCU Actuator NR S D NR 2N Autotransformer NR Softstarter REV Softstarter Feeder NR DOL Motor information N2 parameters NR 2N Motor information S D parameters NR S D Motor information Autotransformer parameters Motor information Ramp Up Down Time M101 P M102 P supports different kinds of motor connections This parameter need to be set according to type of control desired for the motor More detail of M101 P M102 P starter types is described in M101 P M102 P User Guide NR DOL Non Reversing Direct On Line NR Non Reversing means that the motor only runs in one direction When a Start command is given the internal relay CCA remains closed until a stop command is given The internal relay CCB amp CCC has no function here NR DOL RCU Non Reversing Direct On Line remote control of the contactor bypassing the M101 P M102 P The Start CW command closes the internal relay CCA 1sec respectively The sto
84. tup time has elapsed and will cause relay activation in case of a motor stall while it is running The parameter can be set to a higher value for application experiencing overload as part of normal operation Note Large low voltage motors and those having short admissible stalling time less than the startup time are not protected by this function Mixers crushers saw cutters etc Stall protection function consists of following parameters Function Enable Disable Trip Level Trip Delay Trip Reset Mode 30 ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description Figure 6 Stall protection function Notes l max Startup c rrent 5 a Trip Level i EM MM MMC CDL E ___Trip Delay E Startup Function activated E t 10 1 Function Enable Disable Function Stall Protection Range Enabled Disabled Default setting Disabled Related parameter Stall protection Parameters Motor information Motor startup time Motor information Motor startup time N2 Description Stall protection function can be disabled with the help of this parameter When disabled all other parameters of the stall function trip level trip delay and trip reset mode do not have any functionality in the motor control unit Stall protection activates after motor startup and either of below two conditions is fulfilled motor have succesful start i e curren
85. type in M102 For feeder mode the dedicated motor protections are either auto inhabited or prohibited via parameter setting The trip sign of circuit breaker is detected by M102 via specified inputs before an alarm can be given out the measurement and control s functions are activated for this application Note The internal relays CCA and CCB are electrically interlocked for all starter type 3 2 Motor type Function Motor information Range 1 Single Phase 32 Three Phases Default setting 32 Three Phases Related parameter Motor Information Starter Type Phase Failure Protection Function Unbalance Protection Function Description M101 P M102 P can handle a single or three phase AC motor Based on the number of phases of the motor single or three can be selected For single phase motors the motor current lead or the CT secondary lead for 63 A is passed through L1 phase window of the M101 P M102 P internal current transformer Attention Single Phase application is practicable with NR DOL starter type Neither the phase failure protection nor the unbalance protection is available for the application 3 3 System Supply Voltage only for M102 P Function Motor Information Range 220 1 690V Default setting 380V Related parameter Motor information VT Primary L N Description The parameter defines the rated voltage of main supply for motor 3 4 System Frequency Function Motor information Rang
86. will be overwritten by the data transmitted from master station during startup of the DP master If enabled the updating command from master DP during startup is ignored and the parameters are allowed to be set via parameter software only 5 Control Authority 15 ABB 1TNC911106M0202 Edition July 2005 M101 P M102 P Parameter Description There are different control modes from where the motor can be started stopped M101 P M102 P Notes provides 4 modes for motor control MD Operator panel HMl reserved Local via terminal and Fieldbus via bus communication With the Control Authority functionality it can be decided which one of the modes is applied to access the motor M101 P M102 P will accept the command via the authorized mode while refusing to pass on command from unauthorized mode to the motor In addition to authorize the control mode via the parameter M101 P M102 P has the functionality of authorizing control access via hardwire input when a digital input is defined to Loc R The default control mode as follows Loc R input Control Authority Local Fieldbus Operator panel MD O open input Disabled Enabled 1 close input Enabled Disabled When none of digital inputs is defined as Loc R input the function of Local Remote is disabled control commands only authorized by the control mode parameter The default control mode as follows Local Remote input Control Authority

Download Pdf Manuals

image

Related Search

Related Contents

  300 Series XPR  流 速 / 水 温 セ ン サ S  ワイドダイナミックレンジカメラ(電源分離型)  Manual do Utilizador do Nokia C2-02  

Copyright © All rights reserved.
Failed to retrieve file