Data Sheet DB EN IB IL 24 DO 4
Contents
1. A 5557A004 Figure 3 Typical actuator connection A 3 wire termination B 2 wire termination 5557_en_05 PHOENIX CONTACT 8 IB IL 24 DO 4 Notes on Using the Terminal in Potentially Explosive Areas Approval in acc with EG RL 94 9 ATEX II 3G EEx nAC IIC T4 U This Inline terminal conforms to standard EN 50021 and can be installed in a Zone 2 potentially explosive area These Inline terminals are Category 3 items of equipment UL Approval These Inline terminals for the indicated hardware version or later are suitable for use in Class I Division 2 Groups A B C D Ey Before using an Inline terminal in a Zone 2 potentially explosive area check that the terminal has been approved for installation in this area For a list of terminals that are approved for the potentially explosive areas of Zone 2 please refer to the AH EN IL EX ZONE 2 application note Check the labeling on the Inline terminal and the packaging see Figure 4 vomncem Potential routing 4 A maximum IBx IL xx OX it Order No Module ID xx Ye HWIFW XXI ORI ee MO S Sreser REN GLN ON 2 Gn ABCD TS 5561B001 Figure 4 Example labeling of terminals for use in potentially explosive areas Before startup ensure that the following points and instructions are observed 1 When working on the Inline terminal always switch off the supply voltage
2. Ohmic 489 12 W Lamp 12W Inductive 12 VA 1 2 H 50 Q Signal delay upon power up of Ohmic nominal load 100 us typical Lamp nominal load 100 ms typical with switching frequencies up to 8 Hz above this frequency the lamp load responds like an ohmic load Inductive nominal load 100 ms 1 2 H 50 Q typical Signal delay upon power down of Ohmic nominal load 1 ms typical Lamp nominal load 1 ms typical Inductive nominal load 50 ms 1 2 H 50 Q typical Switching frequency with Ohmic nominal load 300 Hz maximum This switching frequency is limited by the selected data rate the number of bus devices the bus structure the software and the control or computer system used Lamp nominal load 300 Hz maximum This switching frequency is limited by the selected data rate the number of bus devices the bus structure the software and the control or computer system used Inductive nominal load 0 5 Hz 1 2 H 50 Q maximum 5557_en_05 PHOENIX CONTACT 3 IB IL 24 DO 4 Digital Outputs Continued Overload response Response time with ohmic overload 129 Restart frequency with ohmic overload Restart frequency with lamp overload Response with inductive overload Response time in the event of a short circuit Reverse voltage protection against short pulses Resistance to permanently applied reverse voltages Resistance to permanently applied surge voltage Validity of output data after connecting the 24 V vo
3. 2 The Inline terminal must only be installed started up and maintained by qualified specialist personnel 3 Install the Inline terminals in a control cabinet or metal housing The minimum requirement for both items is IP54 protection according to EN 60529 4 The Inline terminal must not be subjected to any mechanical or thermal strain which exceeds the limits specified in the product documentation 5 The Inline terminal must not be repaired by the user Repairs may only be carried out by the manufacturer The Inline terminal is to be replaced by an approved terminal of the same type 6 During operation only Category 3G equipment must be connected to Inline terminals in Zone 2 7 Observe all applicable standards e g EN 60079 and national safety and accident prevention regulations for installing and operating equipment Restrictions When using terminals in potentially explosive areas observe the technical data and limit values specified in the corresponding documentation user manual data sheet package slip AN Restrictions regarding the Inline system The maximum permissible current flowing through potential jumpers Up and Us total current is limited to 4 Awhen using the Inline terminals in potentially explosive areas 5557_en_05 PHOENIX CONTACT 9 IB IL 24 DO 4 Programming Data Configuration Data Local Bus INTERBUS ID code BDhex 189dec Length code 41 hex
4. IB IL 24 DO 4 Inline Terminal With 4 Digital Outputs AUTOMATIONWORX Data Sheet 5557_en_05 PHOENIX CONTACT 01 2007 Description The terminal is designed for use within an Inline station It is used to output digital signals Features Connections for 4 digital actuators Connection of actuators in 2 and 3 wire technology Nominal current per output 0 5 A Total current of the terminal 2 A Short circuit and overload protected outputs Diagnostic and status indicators E manual for your bus system IR Make sure you always use the latest documentation This data sheet is only valid in association with the IB IL SYS PRO UM E user manual or the Inline system It can be downloaded at www download phoenixcontact com A conversion table is available on the Internet at www download phoenixcontact com general 7000_en_00 pdf Ey This data sheet is valid for all products listed on the following page DO GD OO GD GD OGD OO OD Likoniic GDC INSPIRING INNOVATIONS IB IL 24 DO 4 Ordering Data Products Description Inline terminal with four digital outputs without accessories Transmission speed 500 kbps Inline terminal with four digital outputs including accessories connectors and labeling field Transmission speed 500 kbps Inline terminal with four digital outputs without accessories Transmission speed 2 Mbps Inline terminal with four digital outputs including a
5. Process data channel 4 bits Input address area 0 bits Output address area 4 bits Parameter channel PCP 0 bits Register length bus 4 bits Other Bus Systems ICJ For the programming data configuration data of other bus systems please refer to the corre sponding electronic device data sheet e g GSD EDS PHOENIX CONTACT 01 2007 Process Data Assignment of the Terminal Points to the OUT Process Data Byte bit view Assignment Status indicator Byte bit 0 3 0 2 0 1 0 0 Terminal point 2 4 1 4 2 1 1 1 signal Terminal point GND 2 5 1 5 2 2 1 2 Terminal point FE 2 6 1 6 2 3 1 3 LED 4 3 2 1 The assignment of the Byte Bit view shown here to your INTERBUS control system or your computer system please refer to the data sheet DB GB IBS SYS ADDRESS Part No 9000990 5557_en_05 PHOENIX CONTACT GmbH amp Co KG 32823 Blomberg Germany Phone 49 0 5235 3 00 Fax 49 0 5235 3 4 12 00 www phoenixcontact com 10
6. ccessories connectors and labeling field Transmission speed 2 Mbps Type Order No IB IL 24 DO 4 2726256 IB IL 24 DO 4 PAC 2861276 IB IL 24 DO 4 2MBD 2855211 IB IL 24 DO 4 2MBD PAC 2861988 Pcs Pkt 1 IEY One of the listed connectors is needed for the complete fitting of the IB IL 24 DO 4 and the IB IL 24 DO 4 2MBD terminals Accessories Description Connector without colored identification for digital 4 or 16 channel Inline terminals Connector colored identification for digital 4 or 16 channel Inline terminals Documentation Description User manual Automation Terminals of the Inline Product Range User manual Configuring and Installing the INTERBUS Inline Product Range Application note Inline Terminals for Use in Zone 2 Potentially Explosive Areas Technical Data General Data Housing dimensions width x height x depth Weight Operating mode Connection method for actuators Permissible temperature operation Permissible temperature storage transport Permissible humidity operation storage transport Permissible air pressure operation storage transport Degree of protection Class of protection Connection data of connector Connection method Conductor cross section Interface Local bus Type Order No IB IL SCN 12 2726340 IB IL SCN 12 OCP 2727624 Type Order No IL SYS INST UM E 2698973 IB IL SYS PRO UM E 2743048 AH EN IL EX ZONE 2 7217 12 2 mm x 120 mm x 71 5 mm 44
7. g without connector 66 g with connector Process data mode with 4 bits 2 and 3 wire technology 25 C to 55 C 25 C to 85 C 10 to 95 according to DIN EN 61131 2 70 kPa to 106 kPa up to 3 000 m above sea level IP20 according to IEC 60529 Class 3 according to VDE 0106 IEC 60536 Spring cage terminals 0 2 mm to 1 5 mm solid or stranded AWG 24 16 Through data routing Pcs Pkt 1 Pcs Pkt 1 5557_en_05 PHOENIX CONTACT 2 IB IL 24 DO 4 Transmission Speed IB IL 24 DO 4 500 kbps IB IL 24 DO 4 PAC 500 kbps IB IL 24 DO 4 2MBD 2 Mbps IB IL 24 DO 4 2MBD PAC 2 Mbps Power Consumption 500 kbps 2 Mbps Communications power 7 5V DC 7 5VDC Current consumption at UL 44 mA maximum 65 mA maximum Power consumption at UL 0 33 W maximum 0 49 W maximum Segment supply voltage Us 24 V DC nominal value 24 V DC nominal value Nominal current consumption at Us 2 A 4 x 0 5 A maximum 2 A 4 x 0 5 A maximum Supply of the Module Electronics and I O Through Bus Coupler Power Terminal Connection method Through potential routing Digital Outputs Number 4 Nominal output voltage UouT 24 V DC Differential voltage for Inom lt 1V Nominal current Inom per channel 0 5A Tolerance of the nominal current 10 Total current 2A Protection Short circuit overload IE All four channels are thermally coupled i e an error in one channel can affect the other channels Nominal load
8. iate connector Local Diagnostic and Status Indicators Des Color Meaning D Green Diagnostics 1 2 3 4 Yellow Status indicators of the outputs Function Identification Pink 2 Mbps white stripe in the vicinity of DLED Terminal Assignment Terminal Assignment Point 1 1 Signal output OUT 1 2 1 Signal output OUT 2 1 2 2 2 Ground contact GND for 2 and 3 wire termination 1 3 2 3 FE connection for 3 wire termination 1 4 Signal output OUT 3 2 4 Signal output OUT 4 1 5 2 5 Ground contact GND for 2 and 3 wire termination 1 6 2 6 FE connection for 3 wire termination 5557_en_05 PHOENIX CONTACT 6 IB IL 24 DO 4 Internal Circuit Diagram Key Local bus ee Protocol chip bus logic including voltage conditioning U LED Fq Optocoupler lt Transistor a Digital Output Electrically isolated area 4 Other symbols used are explained in the 24 V Us IB IL SYS PRO UM E user manual or in the Inline system manual for your bus system 24 V Uy rom 55570003 Figure 2 Internal wiring of the terminal points 5557_en_05 PHOENIX CONTACT 7 IB IL 24 DO 4 Connection Example When connecting the actuators observe the assignment of the terminal points to the process data see page 10
9. ital output terminal described here using the bus coupler or a power terminal from separate power supply units Interconnection of the power supply units in the 24 V area is not permitted See also user manual Common Potentials The 24 V main voltage 24 V segment voltage and GND have the same potential FE is a separate potential area Separate Potentials in the System Consisting of Bus Coupler Power Terminal and I O Terminal Test Distance Test Voltage 5 V supply incoming remote bus 7 5 V supply bus logic 500 V AC 50 Hz 1 min 5 V supply outgoing remote bus 7 5 V supply bus logic 500 V AC 50 Hz 1 min 7 5 V supply bus logic 24 V supply I O 500 V AC 50 Hz 1 min 24 V supply I O functional earth ground 500 V AC 50 Hz 1 min Error Messages to the Higher Level Control or Computer System Short circuit overload of an output Yes An error message is generated when an output is short circuited and switched on In addition the diagnostic LED D flashes on the ter minal at 2 Hz medium under these conditions Falling below or exceeding the operating voltage No Approvals For the latest approvals please visit www download phoenixcontact com 5557_en_05 PHOENIX CONTACT 5 IB IL 24 DO 4 Local Diagnostic Status Indicators and Terminal Point Assignment Figure 1 5557B002 The terminal with the appropr
10. ltage supply power up Response upon power down Limitation of the voltage induced on circuit interruption One time unsolicited energy Protective circuit type Overcurrent shutdown Output current when switched off Output voltage when switched off Output current with ground connection interrupted Switching power with ground connection interrupted Inrush current with lamp load Auto restart 3 s approximately 250 Hz approximately 250 Hz approximately Output may be damaged 850 ms approximately Protected against reverse voltages Up to2 ADC No 5 ms typical The output follows the supply voltage without delay 15 V lt Ugemag lt 46 V Udemag demagnetization voltage 400 mJ maximum Integrated 45 V Zener diode in the output chip 0 7 A minimum 300 pA maximum 2 V maximum 25 mA maximum 100 mW at 1 KQ load resistance typical 1 5 A for 20 ms maximum Output Characteristic Curve When Switched On Typical 500 kbps and 2 Mbps Output Current A 0 0 1 0 2 0 3 0 4 0 5 Power Dissipation 500 kbps Differential Output Voltage V 0 0 04 0 08 0 12 0 16 0 20 2 Mbps Formula to Calculate the Power Dissipation of the Electronics n Pror 0 19W 0 10 W I x 0 4 Q Where Pe Total power dissipation of the module i index n Number of set outputs n 1 to 4 le Load current of output i Power dissipation of the housing Pyoy 0 6 W maximum within the permissible operating tempe
11. rature n Pror 0 4W gt 0 1W I x 0 4 Q 5557_en_05 PHOENIX CONTACT 4 IB IL 24 DO 4 Limitation of Simultaneity Derating Ambient Maximum load current at Temperature TA 100 Simultaneity 75 Simultaneity 50 Simultaneity lt 35 C 0 5A 0 5A 0 5A lt 45 C 0 375 A 0 5A 0 5A lt 55 C 0 25A 0 33 A 0 5A With 100 simultaneity a load current of 0 5 A for each channel is permissible up to 35 C ambient temperature range a load current of 0 375 A between 35 C and 45 C and a load current of 0 25 A up to 55 C If a maximum of two channels are operated in the permissible ambient temperature range 50 simultaneity a load current of 0 5 A can be tapped If all 4 channels are used the permissible working point must be defined according to the above formula An example can be found in the IB IL SYS PRO UM E user manual Safety Equipment Overload short circuit in segment circuit Electronic with 4 channel driver Surge voltage Protective circuits of the power terminal Protection up to 33 V DC Polarity reversal of the supply voltage Protective circuits of the power terminal It is necessary to protect the voltage supply The power supply unit should be able to supply 4 times 400 the nominal current of the fuse Reverse voltage Protection up to 2 A DC Electrical Isolation To provide electrical isolation between the logic level and the I O area it is necessary to supply the station bus coupler and the dig