1. Sa m NETWORK 1275 Danner Dr _Tel 330 562 7070 Im EH H EWE E H TECHNOLOGIES Aurora OH 44202 Fax 330 562 1999 E Ww EE INCORPORATED www networktechinc com ENVIROMUX Series Installation Instruction For ENVIROMUX IMD P INFRARED MOTION SENSOR ENVIROMUX IMD CM P CEILING MOUNT MOTION SENSOR ENVIROMUX IMD TAA INFRARED MOTION SENSOR TAA COMPLIANT ENVIROMUX GBS P GLASS BREAK DETECTION SENSOR ENVIROMUX CMD P CARBON MONOXIDE DETECTOR The ENVIROMUX Sensors listed above are intended for connection to an NTI ENVIROMUX MINI MINI LXO SEMS 16 U 16D 5D 2D for use in detecting changes in the environment inside a server room When properly connected the sensors will provide signals to the ENVIROMUxX that with proper configuration will result in alert messages being sent to the administrator of the ENVIROMUX Each sensor has screw terminals for easy user connections The sensors used with the ENVIROMUX 16D 5D 2D and ENVIROMUX SEMS 16 U can be powered by the ENVIROMUX and don t require an external power supply Sensors models without the P are used for these models i e ENVIROMUX IMD Sensors used with the ENVIROMUX MINI MINI LXO require an external power supply To include a 12VDC AC adapter order models with P i e ENVIROMUX IMD P Access Screw Terminals See the images below for instruction to open the case for each model to access the screws terminals ENVIROMUX IMD P ENVIROMUX IMD TAA B E
2. ALARM Wire to contact terminals pe eg contacts aoe BS P ENVIROMUX CMD P wat an are Cik Fl i J 1 Th ay ia arn ae 1 i Pennine unr PLOZ Aq yun asejday Wire to contact terminals Wire to contact terminals Contacts Wire to contact terminals 5 Be sure to tighten terminals to secure each conductor to the terminal block 6 Mount the sensor as needed according to the type of sensor being connected Installation ENVIROMUX 16D 5D 2D SEMS 16 U Using RJ45 Sensor Socket If an RJ45 socket is available a contact sensor can be connected to it using a CAT5 cable Connect the CAT5 cable as indicated in the image below Connect the white orange and orange ALARM wires to the contact terminals of the sensor Schematic for wiring Contact Sensor to RJ45 Socket Se gepggy ALARM 12VDC TAMPER wht blue Phe brown Baebes abel gt For 5VDC contact for 12VDC sensors substitute contact sensors 12345678 pin 4 5VDC for pin 7 12VDC View looking into RJ45 Socket If the sensor does not have a tamper feature or you do not wish to use it simply omit the connection to pin 5 APPLICATION NOTE The wire gauge specified for connection is 16 26 awg The maximum 24AWG cable length that can be used on an ENVIROMUX CMD Carbon Monoxide Detector is 500 feet To increase the maximum distance to up to 1000 feet order 22 awg 4 conductor c
3. Motion Detector RJ45 Connector 7 Description Undefined 7 Group Group 0 Disable alerts for this sensor Normal Status Normal Status Closed M Enable Tamper Alert Tamper Normal Status Open gt Sampling Sampling Period i Sec gt Add to Data Log File Add Reading to Log File Every jeo Min gt Alert Timing Alert Delay fo Sec Notify again after 30 Min M Notify when return to normal Alert Notifications l Enable E mail Alerts Enable SNMP Traps Enable SMS Alerts Enable Syslog Alerts Enable Siren Alerts Enable Alarm Beacon Outputs Associate Output a On alert close the output contact On return to normal open the output contact Block output command on tamper alert Apply status Remove Example of sensor configuration in ENVIROMUX SEMS 16 using RJ45 Digital Input Configuration Type Digital Input Description Digital Input 1 Group Group 0 C Disable alerts for this sensor Normal Status Normal Status Upen Sampling Samplin T Bahera 20 Sec l Add te Data Log File Add reading to log file every 60 Min Alert Timing Sex Notify again after 30 Min Notify when return to normal Alert Delay 30 Alert Notifications l Enable E mail Alerts Enable SNMP Traps l Enable SMS Alerts T Enable Alarm Enable Syslog Alerts F Enable Siren Alerts Bescon Associate output Mone 7 On alert
4. A OUTPUT RELAYS m DIGITALIN OUTPUT m 1 TACH ALARM iiach UTEN CEE SESE TE Savy TRENIT HENO TETETETE P T FC NENO NENO 412V Switch w 12VDC powered device 500mA max Switch w 12VDC powered device 500mA max 3 Connect two more 18 22 awg wires not supplied between the 12V and ground terminals and the 12 and NEG terminals on the sensor Note If the AUX PWR terminals on the ENVIROMUX 2D 5D are already powering another sensor then an external power supply may be required to power the new sensor with power connections made as explained on pages 2 3 If the combined power consumption of the two sensors exceeds 500mA then an external power supply will be required 4 Be sure to tighten terminals to secure each conductor to the terminal block 5 Mount the sensor as needed according to the type of sensor being connected Operation 1 If the sensor includes an AC adapter connect the AC adapter to a 120VAC power source If the sensor is powered by an ENVIROMUxX the sensor will be powered any time the ENVIROMUX is ON Each sensor has an LED that will illuminate to indicate the sensor is functioning Refer to the instructions that accompany each sensor for proper LED indications 2 Configure the ENVIROMUxX to report signals from the connected dry contact sensor as alert detection occurs Refer to ENVIROMUX manual for details on configuration see also examples on next page
5. open the output contact On return to normal open the output contact Apply Status Remove Example of sensor configuration in ENVIROMUX SEMS 16 using DIGITAL IN terminals Dry Contact Sensor Configuration NOTE Alert hysteresis must be set to 1 second for ENVIROMUX IMD P and ENVIROMUX IMD CM P models Name Server Room Motion De I hresholds Alert liming ic fi seconds Nak wees Alert hysteresis Joti Notify again after fi minnes Sane 2 Max notifications per alert fo 0 Is unlimited norrral F Automatically acknowledge alert when condition clears Alert Methods F E mail F SNMP Notify addresses Notify address F Syslog Notify address 1921683116 separate by commas max 112 characters F SMS Cell Phone Number GSM Modem Status Message to send with alerts optional Server Room Morion Pereernor Alerr max 260 characters only first 240 wil be shown on SMS messages F Disable alerts for this sensor Apply Cancel lest Alerts Simulate Aled Dien Example of sensor configuration in ENVIROMUX MINI Warranty Information The warranty period on this product parts and labor is two 2 years from the date of purchase Please contact Network Technologies Inc at 800 742 8324 800 RGB TECH or 330 562 7070 or visit our website at http www networktechinc com for information regarding repairs and or returns A return authorization number is required for all repair
6. NVIROMUX IMD CM P Gems aT Insert screwdriver Af p to slot and twist to open case Loosen screw approx 10 turns to open case Remove screw to open case j ENVIROMUX CMD P ENVIROMUX GBS P AFCUAT 7 zeca j Z lia ine w ee n l Insert screwdriver to slot pry gently up and Push tab to open case release tab to open case 1 Installation with External Power Supply ENVIROMUX MINI ENVIROMUX MINI LXO 1 Connect two 16 26 awg wires not supplied from any set of dry contacts see below on the ENVIROMUX MINI set 1 2 3 or 4 or ENVIROMUX MINI LXO set 1 5 2 Connect the other end of those two wires to the switch terminals C and N O ALARM on some models on the sensor Apply one wire to each terminal it doesn t matter which wire goes on which terminal VIEW OF CONTACTS ON ENVIROMUX MINI VIEW OF CONTACTS ON ENVIROMUX MINI LXO OUTPUT RELAY CONTACTS arr DIGITAL oar 1 s Pele ERIE DIR NO C NC CONNECT THE SENSOR C AND N O TERMINALS TO ANY SET OF CONTACTS ON THE ENVIROMUX MINI 1 4 OR ENVIROMUX MINI LXO 1 5 3 Connect the AC adapter wire labeled PLUS 12 to the 12 marked in the images below for each sensor 4 Connect the AC adapter wire labeled NEG to the terminal labeled negative as shown in the images below for each sensor 12 VDC ADAPTER ENVIROMUX IMD CMP gt PIR 2712 REVO J07
7. When an alert condition is detected the switch terminals on the sensor will close to generate an alert message from the ENVIROMUX For maintenance and testing instruction see the instructions that are included from the sensor manufacturer for each sensor Digital Input Configuration H Digital Input Settings Description Test Switch 1 Descriptive name for the digital input Normal Status Open i Select the normal status for the digital input Refresh Rate 4 Sec The refresh rate at which the digital input view is updated Group Settings Schedule Settings Disable Alerts E Disable alert notifications for this digital input Alert Delay 5 Sec Duration the digital input must be out of normal status before alert is generated Notify Again Time 6 Hr Time after which alert notifications will be sent again Notify on return to normal Send a notification when this digital input returns to normal status Auto acknowledge Automatically acknowledge alert when digital input returns to normal status Enable Syslog Alerts Send alerts for this digital input via syslog Enable SNMP Traps Send alerts for this digital input via SNMP traps Enable E mail Alerts E Send alerts for this digital input wia e mail E mail Subject Test Switch 1 Subject of e mails sent for alerts Select IP Camera None Available x Select IP camera for image capture on alert Attach IP camera capture E to e mail Attach captured ima
8. ge from selected IP camera to alert e mail Save image to USB Save captured image from selected IP camera to USB Flash Enable SMS Alerts Send alerts for this digital input via SMS Enable Siren Beacon al alarm Turn on the siren beacon alarm when digital input goes to alert Associated Output Relay None Name of the output relay that can be controlled by this digital input Output Relay status on Inactive alert Status of the output relay when going to alert Output Relay status on Inactive return from alert Status of the output relay when returning from alert Data Logging Simulate Alert Clear Alert Example of sensor configuration in ENVIROMUX 2D or ENVIROMUX MINI LXO using DIGITAL IN terminals Motion Detector 16 Configuration Type Motion Detector Sensor Settings Description Normal Status Enable Tamper Alert Tamper Normal Status Refresh Rate Motion Detector 16 Descriptive name for the sensor Closed Select the normal status for the sensor Enable tamper alert notifications for this sensor Closed Select the tamper contact normal status 1 Sec The refresh rate at which the sensor view is updated Group Settings Schedule Settings Critical Alert Settings Data Logging Alert Simulation Simulate Alert Clear Alert Example of sensor configuration in ENVIROMUX 16D 5D 2D using RJ45 Motion Detector Sensor Configuration Type
9. ommunications cable NTI COMM4 BULK22 STRND and the compatible RJ45 plug NTI 5E PLG AWG22 Using DIGITAL IN Terminals The ENVIROMUX 16D and ENVIROMUX SEMS 16 U have 8 sets of terminals for connecting contact sensors The ENVIROMUX 5D 2D have 5 sets Terminals on ENVIROMUX 16D Terminals on ENVIROMUX 5D Terminals on ENVIROMUX 2D DIGITA IN DIGITAL IN r DIGITALIN s OUTPUT race 1 TACH RELAY TASH Tav siavi 12V i Sav 4 12V av ev TEPES I och a SESE PEST C NCNO T TAAA OGU US GS CoJo o SU VG UU uu aa aa aa laa aa Wa aa 1 Connect two 16 26 awg wires not supplied to the and and on the ENVIROMUX 5D 2D of any set of Digital In terminals see next page on the ENVIROMUX 2 Connect the other end of those two wires to the switch terminals C and N O ALARM on some models on the sensor Apply one wire to each terminal it doesn t matter which wire goes on which terminal Terminal Blocks on ENVIROMUX 16D DIGITAL IN 1 2 3 4 Connect devices rated 50mA or less to Digital In 1 7 lM ME Connect devices rated 650mA or less to Digital In 8 Se er era TI Switch w 12VDC powered a Switch Only A pE s device Symbol 50mA Max in Digital In 1 7 Door Contact ln P n P P a P a P a a oO l rir rir T Panic 650mA Max in Sensor Button Digital In 8 Terminal Blocks on ENVIROMUX 5D Terminal Blocks on ENVIROMUX 2D gm DIGITALIN
10. s returns COPYRIGHT Copyright 2007 2013 by Network Technologies Inc All rights reserved No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means electronic mechanical photocopying recording or otherwise without the prior written consent of Network Technologies Inc 1275 Danner Drive Aurora Ohio 44202 CHANGES The material in this guide is for information only and is subject to change without notice Network Technologies Inc reserves the right to make changes in the product design without reservation and without notification to its users Man056 Rev 1 13 14