1. 4 and ENT keys v 52 ZONE ADC or press hot key 2 ENTER CODE _ Enter the device adddress valid value from 1 to 127 or select ADDRESS _ valid address value by gt 4 key and press ENT ENTER LOOP 17_ 43 BOLID FIRE AND ALARM CONSOLE Type alarm loop number or select value by keys gt 4 key and press ENT If the command was successfully comleted ADC or measured 002 017 51 value is displayed in format device address loop number value In this example the measured by ADC value of loop Ne 17 of device with address 2 is equal to 51 Each 0 5 seconds console automatically refreshes given loop ADC value By means of buttons gt other loop ADC values of given device can be viewed The following tables contain couples of loop resistance and corresponding ADC value ADC value can vary from 0 to 255 Value 0 corresponds to loop open circuit value 255 corresponds to to short circuit a Correspondence between loop resistance and Signal 20P device ADC value alarm loop resistance 0 2 0 kOhm 4 7 kOhm 6 0 kOhm Open ADC value 255 89 46 38 0 Normal range for fire loop type 1 2 3 and for alarm loop with tamper checking type 5 is from 2 0 kOhm to 6 0 kOhm Normal range for alarm loop type 4 is from 2 0 kOhm to 11 0 kOhm 6 Correspondence between loop resistance and S2000 4 ADC devi
2. Zone config err Fire trouble faults Device restart Tamper alarm Disconnected RS 485 or 2 wire device Entry alarm Intrusion alarm Silent alarm personal attack Fire prealarm Fire maximum alarm level Message Arm failed is not alarm message but it required personal attention Message Arm failed is not accompanied with sound signal To view event buffer messages transmit panel in the time indication mode and press button MEM By gt scrolling events in chronological order and scrolling events in back order 1023 last messages can be scrolled at LCD Console makes double sound indicator if buffer finished Double sound signal at scrolling events in direct chronological order means that shown on LCD event was last in the buffer at scrolling events in back order first To view message time and date press and hold button 0 For immediate transition from message displaying mode in time displaying mode use button CLR 2 2 2 Partition arming and disarming Partitions and partition groups are controlled identically partition group is a partition type so below we will consider partition control only Control functions are authority level password protected or Touch Memory key or Proximity card protected If password is correct and its owner has control privilegies console saves USER S CODE
3. and Ne35 ASPT A1 programs will not be turned on in the last case will be turned on if control time restrictions are not given There are other distinctions between programs Starting of relay outputs supplied with Ne34 and No35 programs is blocked up if there are blocking conditions in any associated partition On the contrary output supplied with Ne11 or Ne33 programs will be turned on if there is at least one partition met the launching condition specifically there are fire alarms and there are no broken auxiliary alarm loop and failed outputs without regard to another concerning partition states 5 Executive programs Ne11 ASPT and No34 ASPT A allow to turn output on when either two smoke or heat detectors in partition have been activated or a manual fire detector IPR has been started if the type Manual launch for IPR controlling zone was configured 6 Output FAULT is used to control the operative status of fire partitions Output opening follows with short circuit open circuit or fault of fire detector y short or open circuit of output relay Y connection loss between the console and RS 485 lined control receiving device or relay unit or between 2 wire connected addressable detector or relay unit and S2000 KDL controller vY short circuit or trouble of 2 wire addressable line v primary or backup power supply troubles y Disarmed or Arming has failed status of partition
4. NEW ADDR _ SECURITY SYSTEMS FIRE AND ALARM CONSOLE and connecting device with new address followed by state information In case of operation faulting the console makes sound signal Error and displays diagnostic message COMMAND ERROR DEVICE OFF LINE COMMAND ERROR UNKNOWN COMMAND COMMAND ERROR ADDR UNKNOWN 2 wire device is not connected to S2000 KDL COMMAND ERROR ADDR OCCUPIED programming address has occupied by already existing 2 wire device or COMMAND ERROR operation fault 2 wire device addresses programming 2 wire device address programming should be made if it addresses are unknown To programming 2 wire devices address refer to their maintenance guides Enter the S2000 KDL device into address programming mode Enter in programming menu press button PRG ENTER CODE Type engineer password 3 ADRESSES Select ADDRESSES menu item by P 4 and ENT keys or press hot key 3 2 WIRE DEVICES Select 2 WIRE DEVICES menu item by gt 4 and ENT keys or press hot key 2 PROGR ADDRESS Select PROGR ADDRESS menu item by P 4 and ENT keys Enter S2000 KDL address valid value from 1 to 127 or RS485 ADDR sel select valid address value by P 4 keys and press ENT Enter programming 2 wire device address valid value from 1 to 127 or select va
5. RELAY 8 SYSTEM INFO 9 AUXILIARY
6. in menu File or press button Open configuration file In window Open file select file type select file and press button OK There are two available types of configuration files text with TXT extension or encrypted with GPC extension To read encrypted configuration file it is necessary to enter engineer password To write configuration in the file select command Save or Save as in File menu or press button Save configuration file Configuration can be saved in text or encrypted file Edited configuration can be saved in a file loaded from a file written to the console nonvolatile memory or read from the console memory To write or read the configuration S2000M console has to be connected to personal computer The console can be connected both via RS 232 or RS 485 interfaces In the first case console is connected to computer as shown on the Figure 5 and the second case is shown on the Figure 8 Set console programming mode press PRG key ENTER CODE enter engineer password default value lt 123456 gt and press ENT key 5 SETTINGS select menu item SETTINGS by keys and Y and ENT or press key 5 REMOTE PROGRAM select menu item REMOTE PROGRAM by keys and Y and ENT or press key 6 the LCD will display PROGRAMMING MODE indicating the console status PROGRAMMING MODE Console i
7. in selected level of top window Authority levels The partition will be added in the authority level partition list Selected partition in the inspector s window control privilegies of the partition can be set enabling or denying arm or disarm Adding and editing of passwords are made on the Passwords tab of program pprog exe At password setting user number password type code value and the password access level have to be set Also user text identificator can be given Also user text identificator name can be set All these parameter are set in the inspector window controls For new password press button Add password and in the inspector window in line Number set identificator number in line Code set identificator value in line User set user text description in line Authority levels set password authority level To edit parameter select line by double mouse click and input new value User number is number from 1 to 2047 which with text description identify user in the system Password with number one 1 is main password always set up password It has type main password PIN code from 1 to 8 digits and used for programming only User passwords can have numbers from 2 up to 2047 It is recommended to type text description also User name any text string with length up to 16 symbols Console support two user identification ways PIN code digit password at console or S20
8. As this output is normalle closed the relay unit power down or open relay output circuit are considered to be fault signals 7 Fire LAMP output differs from LAMP by turning on only when all assigned partitions are armed 8 Program Ne17 Turn on for a given time before arming can be used for 4 wired detectors auto reset when arming To do this the detectors are powered through normally closed contact of S2000 SP1 device relay output This output is given by the executive program Ne17 and control time sufficient to reset detectors For 4 wired detectors alarm loops the arming delay is to be given Arming delay must be more then the sum of resetting time and maximum restore time of detectors after power reset As a result when arming command is given the relay will turn on for given time with 4 wired power circuits being broken and thus reset activated detectors 9 Programs Ne 38 45 can be used in gas powder or aerosol fire extinguishing systems based on S2000M ASPT devices These programs allow turning on or off device outputs both for given time or as long as on off condition is in effect Controlling without time restrictions is realized by givening the maximum control time value being egual to 8191 875 seconds Program Ne 38 Turn on during launching delay can be used for activating audible alarms and light boxes GET OUT and KEEP OUT when launching delay Program Ne 39 also can be used in gas extinguis
9. Message category is intended to classify messages with the aim of printing or transmitting to the S2000 K keyboards or S2000 IT phone communicators Renaiming script having been created should be associated with corresponding zones 2 1 7 8 Controlling S2000 BI devices settings S2000M panel with programmed partitions can be connected to S2000 BI indication units Prior configuration of indication blocks with the help of S2000M console or program uprog exe has to be set Minimal setup is programming partition number for each indicator At connecting indication units to S2000M console LED S2000 BI indicators will show states of partitions 31 BOLID BOOD FIRE AND ALARM CONSOLE 2 1 7 9 Using the console for creating of systems controlling gas powder or aerosol fire extinguishing installations based on S2000 ASPT devices The console is suitable in gas powder or aerosol fire extinguishing systems based on S2000 ASPT devices especially in case of using several extinguishing areas at once The console can be used in such systems as follows 1 To indicate system status by means of S2000 PT devices each displaying the current status of 10 areas of extinguishing For each area several status are displayed among them fires faults of fire loops output circuits primary and standby power supply launch blocking fire extinguishing launching mode manual or auto various statuses of laun
10. Outputs are controlled by given control programs according to the states of the connected partitions Relay output can be connected with any number of partitions up to 255 and partition can be connected with arbitrary number of the outputs up to 255 Console support 35 different relay control programs Control program determines state of output at different states of connected with it partitions Relay control program description is shown in the table 3 Description of partition states are shown in the appendix C Partitions partition links with outputs and control programs are setup at customizing see item 2 1 7 4 Table 7 Relay executive programs Program description 1 On If Intrusion alarm or Fire alarm ON else OFF output 2 Off If Intrusion alarm or Fire alarm OFF else ON output 3 On for a time If Intrusion alarm or Fire alarm ON for a time else OFF output 4 Off for a time If Intrusion alarm or Fire alarm OFF for a time else ON output 5 Blinking Normal state If Intrusion alarm or Fire alarm blink 0 5 s ON 0 5 s OFF OFF else OFF output 6 Blinking Normal state If Intrusion alarm or Fire alarm blink 0 5 s ON 0 5 s ON OFF else ON output 7 Blinking for a time If Intrusion alarm or Fire alarm blink 0 5 s ON 0 5 s Normal state OFF OFF during given t
11. S2000 PI XT3 ISOLATED RS 485 To consoles S2000 PI S2000M RS 485 XT3 XT1 3 XT1 2 To devices ISOLATED S2000M S2000M alarm panel S2000 PI interface converter repeater S2000 PI BP power supply 1 connection cable S2000 PI and PC Figure 7 Connection of several S2000M to the PC with ARM Orion with galvanic isolation of interface RS 485 diagram 24 S2000M MAINTENANCE GUIDE 2 1 7 Console configuring 2 1 7 1 General information If it is required to use S2000 SP1 S2000 BI S2000 K S2000 KS S2000 IT devices in the system then console must have control rules of the devices These rules are setup when console is configuring Creating the console configuration can be done only with the help of personal computer and program pprog exe version 2 04 and above The program is free It is available on the site www bolid ru Console configuration steps are 1 Run program pprog exe Read configuration from console or file or create new one 2 Correct it if necessary and save in file 3 Write ready configuration in file To create new configuration by means of pprog exe select command Create in menu File or press button Create new configuration Select console version and press OK The default configuration will be created and it can be edited if necessary To read present configuration select command Open
12. _ Group disarming EN Type password Select ARM menu item by 4 and ENT keys or press hot key 1 Select ARM LOOP menu item by 4 and ENT keys or press hot key 1 Enter device address valid values from 1 to 127 or select valid address value by gt 4 buttons and press ENT Type loop number or select valid value by gt 4 buttons and press ENT Type password Select ARM menu item by 4 and ENT keys or press hot key 1 Select ARM GROUP menu item by gt 4 and ENT keys or press hot key 2 Enter device address valid value from 1 to 127 or select valid address value by 4 keys and press ENT Type password Select ARM menu item by and ENT keys or press hot key 1 Select ARM ALL menu item by 4 and ENT keys or press hot key 3 Enter device address valid value from 1 to 127 or select valid address value by 4 keys and press ENT Type password Select DISARM menu item by 4 and ENT keys or press hot key 2 Select DISARM LOOP menu item by 4 and ENT keys or press hot key 1 Enter device address valid value from 1 to 127 or select va
13. amp 6 AUX FUNCTIONS Select AUX FUNCTIONS menu item by and ENT keys or press hot key 6 62 SET DATE Select SET DATE menu item by gt and ENT keys or press hot key 6 Current time is displayed on LCD in JUIMM IT format day DAE Ray month and year Enter new date After date changing console forms two messages DATE CHANGED and DATE Message DATE CHANGED informs when user has changed date Message DATE displays user date value 2 2 3 8 Printing event buffer This function allows to print whole event buffer last 1023 events ENTER CODE Type password Select AUX FUNCTIONS menu item by P and ENT keys or press hot key 6 Select PRINT LOG menu item by gt 4 and ENT keys or press hot key 3 6 AUX FUNCTIONS 63 PRINT LOG 2 2 3 9 S2000 IT phone communicator message buffer cleaning If S2000 IT phone communicator message transition speed is higher then phone line message transition one message buffer of S2000 IT can be overflowed in short time Normally emptying of buffer can take a long time Console can send command to empty message buffer without event transition through phone line ENTER CODE Type password 6 AUX FUNCTIONS Select AUX FUNCTIONS menu item by gt 4 and ENT keys or press hot key 6 c gt ch dq gt c gt 264 CLR COMM
14. signal Confirmation Unsuccessful operation Long sound signal signal Error Intrusion alarm or Silent alarm messages are received Sound signal Alarm interrupted sound signal with signal duration approximately equal to the pause duration Fire prealarm message is received Sound signal Attention periodic sequence of alternate short and long signals Fire alarm message is received Sound signal Fire alarm interrupted sound signal with long signals and short pauses Tamper alarm device restar messages are received disconnection the device is occurred Sound signal Break interrupted high frequency sound signal Loop trbl open loop trbl short fire trouble 2wire line open 2wire line short 2wire line short power failed battery failed AC power failed messages are received Sound signal Fault interrupted sound signal with short beeps and long pauses 2 5 s between signals S2000M MAINTENANCE GUIDE Note Alarm indication at LED indicator and sound annunciator is made only if option ALARM SOUND is on Default option setting is on 1 2 22 Console allow user to control by relay outputs of signal start S2000 SP1 blocks and also by Signal 20P S2000 4 Signal 20 series 02 device outputs Total number of controlled outputs is up to 255
15. where 100 is partition number 80 is user number Printer 120 12 18 26 59 ARMED PART 10 S1 100 Corridor 1 floor Administrator partition 100 Corridor 1 floor armed 20 December at 18 hours 26 minutes 59 seconds at reader at device with address 10 by user Administrator Receiving device message console displays it on LCD and save in event buffer After 20 seconds console returns to the time displaying mode After printer switching on the all received messages will be read from event buffer and printed Indicators ALARM FIRE FAULT and TROUBLE display current console partition states according to the tables 2 5 When parameter ALARM SOUND is on mode with alarm indication displaying alarm messages differ from shown above When console receives one or few alarm messages alarm sound signal is given according to table 6 LCD shows the alarm message If console gets few equal alarm messages it displays the last one Single console key pressure cancels alarm sound signal At the same time printer outputs message ALARM CANCEL To cancel displayed on 36 S2000M MAINTENANCE GUIDE LCD alarm message press keyboard button CLR If all alarm messages are canceled console will return in time displaying mode The events below are shown in alarm level increasing order Arm failed troubles Loop trbl short Loop trbl open Power failed Battery failed
16. Console version update 3 STORAGE 4 TRANSPORTATION 5 CERTIFICATION INFORMATION 6 INFORMATION ABOUT MANUFACTURER 7 WARRANTY Appendix A S2000M console dimensions Appendix B Zone status list Appendix C The list of messages being displayed MAINTENANCE GUIDE 43 43 44 45 45 45 46 46 47 47 48 49 51 51 51 52 53 53 54 54 54 54 54 55 56 57 61 BOLID FIRE AND ALARM CONSOLE This maintenance guide is intended to help you to study the operation and maintenance principles of Fire and Alarm Console S2000M version 2 04 elsewhere the console Console version is shown on the label on the processor which can be seen when console back cover is open 1 Description of the product and its operability 1 1 Purpose 1 1 1 S2000M fire and alarm console is designed to work as part of fire alarm system It checks device states and gathers information logs system events indicates alarms controls arm controls disarm controls by automatics Console joins connected to it devices in one system providing interaction between each other It is necessary for using Signal 20P S2000 KDL S2000 SP1 S2000 BI S2000 K S2000 IT devices 1 1 2 Console can be connected to receive checking devices Signal 20 Signal 20 version 02 Signal 20P S2000 4 2 wired line S2000 KDL controllers keyboards S2000 K and S2000 KC relay s S2000 SP1 module
17. K and S2000 KS devices matching resistance jumper is absent So it is recommended for the first and the last device in the line to set jumper for Signal 20 Signal 20P S2000 4 S2000 SP1 or resistor 620 Ohm between contacts A and B for S2000 S2000 K and S2000 KS At all other devices jumpers should be removed S2000M console can be set at any place in the RS 485 line If it is first or last device in the line then between contacts A and B matching resistor 620 Ohm need to be set Branches in the line are not undesirable because they increase reflection signal in the line But they can be if length of branch is short enough Matching resistor is not setup at separate branches Resistance of each interface line A or B from console to the most remote device has to be no more 200 Ohm In the presence of strong external electromagnetic field it is recommended to use winding pair Devices and console 0 V circuits have to be connected It is no need to connect 0 V circuits if console and devices connected to the one power supply To extend connection line length RS 485 interface repeaters with automatic area transmission switching can be used Figure 3 For example S2000 PI interface converter repeater with galvanic isolator allow to extend line length up to 2000 m implement galvanic isolation between line segments and automatically off sh
18. MSG Select CLR COMM MSG menu item by 3 and ENT keys or press hot key 4 Enter S2000 IT phone communicator number valid value from 1 to 127 or select valid address value by 4 key and press ENT 2 2 3 10 Alarm message indication reset ADDRESS In alarm message indication mode console requires that user views all alarm messages Indication of each alarm message resets by CLR key see item 2 2 1 Console does not transmit in time indication mode while all alarm messages are not viewed If number of alarm messages is too big it is possible during mounting defect of devices or RS 485 line then each message reset by CLR key too tiresome This function can reset indication of all alarm messages in console buffer 45 BOL ID SECURITY SYSTEMS FIRE AND ALARM CONSOLE ENTER CODE Type password Select SERVICE menu item by gt 4 and ENT keys or v 6 SERVICE press hot key 6 Select CANCEL ALARM menu item by 4 and ENT a 65 CANCEL ALARM keys or press hot key 5 During execution of this operation the console cancels all alarm messages Of course all alarm messages leave in console event buffer and can be viewed or printed 2 2 4 Device and console programming functions Programming functions are designed for configuring console and intrusion and fire alarm panelss This function is protected by pass
19. ON for a given time else OFF output 13 Fire output If Fire alarm or Fire prealarm then ON close outputs else OFF open output Output FAULT If there are zones in the states Disconnected alarm loop Relay disconnected Fire trouble Loop open circuit Configuration error Open relay output Relay output short circuit Battery 14 failed AC power failed Power failed 2 wire line short circuit or 2 wire line trouble or Disarmed Disarmed and ready Disarmed and not ready or Arming has failed then OFF open output else ON close output Fire LAMP If Fire alarm Fire prealarm Intrusion alarm Entry alarm or Arming has failed then blink 0 5 s ON 0 5 s OFF 15 if Disconnected alarm loop or Fire alarm then blink 0 25 s ON 1 75 s OFF if state of all relay associated zones is Zone armed then ON else OFF output Alarm output 2 If all zones are armed or disarmed then ON 16 else OFF output Turn on for a given time If at least one zone is in Arming delay state then ON for 17 before arming a given time else OFF output Turn off for a given If at least one zone is in Arming delay state then OFF 18 time before arming for a given time else ON output 19 Turn on for a given time If at least one zone is armed th
20. Potok 3N device configuration For example zone Ne 32 responsible for manual launching is used only for systems without pressure To display the statuses of the pump station and each pump LED four indicators of S2000 BI 01 are assigned By means of program uprog exe designate the partition number for each indicator group of S2000 BI 01 in so manner that the appointment of the partition being corresponded with the caption on the facial label 2 1 7 11 Using the console with the phone communicator S2000 IT In order to adjust the devices S2000 IT for message transmission from alarm system the console should be configured to transfer event messages to these devices Refer to the 2 1 7 5 section of this manual for descripton of configuring of event reporting The messages contain the information about loop arming and disarming by specific users provided that the passwords or 33 BOLID FIRE AND ALARM CONSOLE codes with corresponding authority levels are assigned in console configuration Passwords being programmed into the console have some numbers transmitting by the console in arm and disarm messages as user s identificators 2 1 8 Console mounting Console can be mounted in any convenient place on the wall or on the other constructions protected from atmospheric condensation mechanical damages and access of outliers 2 1 9 Prevention of the accidents at device installation Console construction satisfies requirements
21. alarms fires faults use transmission To all devices to transmit messages large number of devices 30 S2000M MAINTENANCE GUIDE 2 For displaying console transmitted events by S2000 K keyboards their configuration parameters Event indication and Alarm indication have to be customized 3 S2000 K keyboards may not support come of the console messages Such messages will not be displayed 4 Transmission speed through phone lines by S2000 IT informators is low That is why to avoid informatory buffer overflow it is recommended to transmit to informatory just the most important and rare messages alarms fires To do this needed event categories has to be permited for transmission and others have to be forbidden At informatory buffer overflow it should be cleared see item 2 2 3 9 2 1 7 6 Entry zone settings Console support up to 32 input zones Each of them is determined by device address alarm loop number in device and alarm delay Any alarm ALs connected to the device console can be used as input ALs Delay can has value from 0 to 254 seconds Input zones are setted on tab Entry zones pprog exe program In the top window Input zones contains alarm loop list set up as input zone In botton window Devices loops there is a list of system devices and its alarm loops To create input zone drag alarm loop from Devices loops window in the window Entry zone and
22. carried out from the computer The console is active but disconnected from the system When the PC has stopping poll the devices for given time the console has automatically connected to the devices with the help of S2000M SP1 relay unit The monitoring and controlling are carried out from the computer The console is directly connected to the computer via RS 232 interface with the the devices being connected to the console through RS 485 interface The console doesn t control devices doesn t show their states and is unresponsive to key pressions When the PC has stopping poll the devices for given time the console has automatically switches to the active mode The console is directly connected to the computer via RS 232 interface with the the devices being connected to the console through RS 485 interface The console monitors all the devices and gets their states with the computer polling the concole or consoles and getting the device operative information Both the console and the computer can control the relay outputs and indication units If the computer fails the console will retain to execute the controlling functions Configuration method In accordance with the S2000M SP1 relay unit maintenance guide In accordance with the 2 2 4 8 section ot this maintenance guide set RS 232 operating mode to the S2000 PC value and give the switching delay In accordance with the 2 2 4 8 section ot this
23. fires and prohibit another ones for example arm disarm alarm loop Message categories are in appendix T Partition list allows send only the messages from loop of this list Message transition is set on tab Event translation program pprog exe Top window Event transition contain list of devices for message transition from console Each device has to have transition permitted partition list Bottom window can display either system device list Devices or partition list Partitions Device list is used for adding devices in message device list in window Event transition At adding device tree node To all devices console messages will be receive all system devices Its unload RS 485 line at transmission the same messages to the large number of devices but exclude individual message send For each device added in window Message transition in inspector next message categories are pointed which will be transmitted to it Also for each device list of permitted message sources partitions should be set For that in bottom window select partition list and drag selected devices Also event transmission to printer can be required This setting is selection of event category that has to be printed Default value is all events are printed Attention 1 Message transition heavily load RS 485 interface that decrease system operation speed To unload interface need to transmit just rare events such as
24. in digit view INTRUSION ALARM 100 002 007 where 100 is the partition number 002 is the device address and 007 is the number of alarm loop When button 2 is pressed the partition and zone descriptions are displayed Corridor 1 floor 35 SECURITY SYSTEMS FIRE AND ALARM CONSOLE Door 1 if partition and zone have text descriptions Corridor 1 floor and Door 1 correspondently PART 100 ZONE 002 007 if partition and loop have not text descriptions Printer Date Time Event Device Part Description User 120 12 17 41 11 INTRUSION ALARM 2 7 100 Corridor 1 floor Loop disarming Display DISARMED Door 1 disarm alarm loop Door 1 If key 1 is pressed DISARMED 100 002 007 where 100 partition number 002 device address 007 alarm loop If key 2 is pressed Corridor 1 floor Door 1 where Corridor 1 floor is partitiojn name a Door 1 is alarm loop name Events ARMED PART DISARMED PART PART ARMING PART DISARMING include partition number and partition user At printing address device and partition control reader number are printed also Address in device message equal 0 if partitions controlled at S2000M console Display ARMED PART Corridor 1 Floor partition Corridor 1 floor armed At pressure key 3 user name who arm partition can be seen At pressure key 1 ARMED PART 100 U 80
25. in the inspector window Alarm delays set in seconds transition delay alarm loop from intrusion alarm mode in the alarm mode 2 1 7 7 Setting user messages Console allows create user messages which will be displayed and transmitted instead standard messages Standard messages rename rules are determined in scripts Rename script for each standard message gives new name sound signal alarm level and category Script allows rename up to 4 standard messages Console allows create up to 32 rename scripts Script can be set for any alarm loop or few ALs from console database If loop rename script is set then standard messages of the loop will be replaced to user defined messages if such replace is in script Message renaming is actual for auxiliary alarm loops which are usually checking state of an equipment This possibility permits display for example instead of standard messages AUX ZONE ALARM and AUX ZONE RESTORE other messages for example VALVE OPEN and VALVE CLOSE Message renaming is defined on the tab Message renaming of pprog exe program Create renaming script select base messages to be renamed select sound signals set alarm levels and select categories of renamed messages Alarm level determines the priority order for displaying message by the console LCD if few alarm messages are received Higher alarm level value corresponds to the higher displaying priority of alarm messages
26. loops and 511 partitions It is possible to reserve the PC by several S2000M consoles One can connect only single console to the PC RS 232 interface therefore it is necessary to convert RS 232 interface to the RS 485 interface by means of S2000 PI which several consoles are connected to The consoles are connected to the RS 485 interface line by their RS 232 outputs via S2000 PI convertors The devices are connected to the RS 485 outputs of consoles Figure 7 displayes the way of connecting several S2000M consoles to the computer In addition to the capability of several consoles the S2000 PI convertors provides the galvanic isolation between the PC and the console When ARM Orion reserving by several consoles the system device number should not exceed 127 and all system devices should have unique addresses If the computer failes each console will control own connected devices i e the system will disintegrate to several unrelated subsystems For regardful reserving the consol configuration should correspond to ARM Orion or ARM Orion Pro one given by Database Administrator program The structure and the names of the zones and partitions should be the same in both configurations The user names given for the same password are to be identical It is recommended to to write the console configuration from the computer by means of Database Administrator program 23 BOLID FIRE AND ALARM CONSOLE
27. maintenance guide set RS 232 operating mode to the S2000 amp PC value and give the own console address Note that the techniques 1 and 2 are obsolete but technique 3 is recommended Figure 5 Figure 6 and Figure 7 demonstrates the connection diagrams Figure 5 shows the simplest way to connect the console to the computer The defect of this way is the galvanic coupling between the PC and system devices through the RS 232 interface This galvanic coupling result to the devices or RS 485 interface and the PC interfere to each other To isolate the PC from intrusion and fire alarm panelss the RS 485 interface repeaters with galvanic isolation e g S2000 PI can be used The connecting diagram providing galvanic isolation RS 485 line by S2000 PI device is shown on the Figure 6 Note that to provide isolation the console and interface repeater should be powered by separate source without 0 V circuit of this source coupling with the 0 V devices circuit 22 S2000M MAINTENANCE GUIDE S2000M S2000 PI RS 232 computer GENEP RS 485 z To devices S2000M S2000M alarm panel S2000 PI interface converter repeater S2000 PI BP power supply Figure 6 S2000M PC with AUP Orion with galvanic isolation of interface RS 485 connection diagram The S2000M database storage is far less then ARM Orion database It prevents the creation of backuping if system has more than 2048 alarm
28. of the console effect only console controlled output operating algorithm and does not effect on outputs controlled by intrusion and fire alarm panelss 1 3 Delivery set 1 3 1 List of delivery set components of the console S20000M is shown in table 8 Table 8 Delivery set of console S2000M Quantity Check and control fire alarm S2000M console 1 Check and control fire alarm S2000M console Maintenance guide Screw with 1 3x20 016 Dowel 8x35 Printer cable Personal computer communication cable 1 4 Description the product and capabilities 1 4 1 Console has the plastic case The printed circuit board is mounted inside the case Wires are to be screwed connected to the terminal board There is the LCD display at the top of case Under indicator from the right the LED indicators READY ALARM FIRE TROUBLE and FAULT are located Indicator READY has green lighting with the others ones have red lighting Below indicators there is a keyboard with 20 keys Keyboard has supplied with the cover for dust and casual pressure protection The layout overall and mounting dimensions are presented in appendix A 14 S2000M MAINTENANCE GUIDE 2 Maintenance 2 1 Preparation the product 2 1 1 General information Console uses RS 485 interface to connect fire alarm system devices RS 232 interface to connect printer with consequence interface or personal computer and contacts to connect rese
29. off The default value is on CODES REQUIRED parameter determines if control functions are password protected If the parameter has value off then arming disarming and other control functions are available without password The default value is on These parameter settings are described in the item 2 2 4 4 It is necessary to setup the current date and time Time and date are required for event logging and for correct working of time zones in access control devices S2000 4 and S2000 2 If clock is not accurate it can be corrected Description of time and date input and also clock correction is shown in item 2 2 3 7 and in item 2 2 4 1 2 2 Using console Working with console functions is executed with the help of console menu To select function use keys Y and ENT to cancel key CLR is used Numbers can be entered either by typing from keypad or by choosing valid values from the list with the help of and 7 keys For example entering the device address one can choose the address from the console polling device list If operation succeeded console send Confirmation sound signal otherwise it send sound signal Error with diagnostic LCD message The following messages are possible COMMAND ERROR DEVICE OFF LINE command was given for disconnected device COMMAND ERROR UNKNOWN COMMAND console do not support this command etc 34 S2000M M
30. one zone is armed then OFF else ON output Turn on when auxiliary If at least one zone is in the state Auxiliary alarm then 31 alarm ON else OFF output Turn off when auxiliary If at least one zone is in the state Auxiliary alarm then 32 alarm OFF else ON output ASPT I ON for a given time if at least one zone in partition have Fire alarm status and there are no zones having states 33 Auxiliary alarm Relay disconnected Open relay output Relay output short circuit When the failure removed the relay output will be ON ASPT A ON for a given time if at least two zones in partition have Fire alarm status and there are no zones having states 34 Auxiliary alarm Relay disconnected Open relay output Relay output short circuit When the failure removed the relay output will not be on ASPT A 1 ON for a given time if at least one zone in partition have Fire alarm status and there are no zones having states 35 Auxiliary alarm Relay disconnected Open relay output Relay output short circuit When the failure removed the relay output will not be on Turn on with ON for a given time when the temperature has exceeded temperature increasing temperature high threshold in High temperature status else OFF output Turn on with ON for a given time when the temperature has being below temperature decreasing temperature low threshold in Low temper
31. or Proximity card Key card have to be saved in console memory see item 2 1 7 3 has the partition control and have not be saved in S2000 4 key memory At first key touch S2000 4 reader outer LED blinks shortly after that displays state of controlled partition flashes if partition armed off if disarmed blinks if wrecked in alarm or in fire state Each next key touch partition armed if it was disarmed and disarmed if it was in state arm fault alarm or fire Partition can be controlled at other Orion system devices which have port for Touch Memory or Wiegand reader S2000 2 Signal 20P SMD version 2 01 and above S2000 KDL version 1 15 and above 2 2 3 Device control functions This control functions are destined for manual remote control by loops and alarm panel outputs arming disarming alarm reset and so on They are available by user which has control rights W O PART CONTROL ARM and DISARM ARM w o DISARM or MAX AUTHORITY In order to get access to control functions press ENT and input password If password is correct console forms message USER S CODE ENTR and grants acces to control functions Console has parameter CODE REQUIRED allowing acces to these functouns without password entering If this parameter has value Off device control functions are accessible without password entering To exit from control mode use bu
32. suitable for using the console coupled with any ARM Orion software version providing the unlimited computer controlling of the system The disadvantages of this mode are as follows 1 The console and ARM Orion are in operation without reference to each other Messages receiving by the console cannot be obtained by the computer when having restored On the other hand messages receiving by ARM Orion are not registered by the console 20 S2000M MAINTENANCE GUIDE 2 There is some switching delay required when the control is taken over for false switching protection device detection period and for initiation The more system is greater the more switching delay is needed The switching criterium is the absence of computer polling during given time There are two ways of switching the control from PC to the console 1 by means of self acting mechanically RS 485 lines switching with the help of S2000M SP1 relay units and 2 using the special console operating mode that is interface converter mode with automatic transit to redundant mode The first way supposes the console to be physically disconnected and is described by the S2000M SP1 maintenance guide One shoulde use the S2000M SP1 device version 1 20 or above The second way supposes the console to be directly connected to the computer via RS 232 interface with the the devices being connected to the console through RS 485 interface Being operative ARM
33. that is controlled as one unit This gives next advantages Arm disarm require fewer users actions take less time and probability of operators mistake is decreased also If need to arm the large number of ALs especially if there are ALs of different devices joining the alarm loop give very significant event User can arm disarm just partitions authorized to him Partition arm disarm can be controlled not only at console but also at connected S2000 K and S2000 4 devices New opportunity to organize the system outputs relay s is added S2000 BP units can be used for partitions state indication There are the restrictions Number of alarm loop that can be included in partitions is limited Console has to be configured with help of personal computer 1 1 6 Console allows group partitions in the groups Partitions group can be controlled Arm disarm and also display their states on indication S2000 BI blocks and LED S2000 KS keyboards 1 1 7 Console allows one to control by partition arm disarm and to view their states Access to the functions is password protected PIN code Touch Memory key or Proximity card Partitions that authorized to user and partition control rights arm disarm permission are determined by level of its password Console indicates arm disarm operation result Partition control possible both at console PIN code and at connected to console S2000 K key
34. the console or exit from programming mode If it is happened writing operation has to be repeated PC PI S2000M RS 485 A RS 485 B RS 485 To devices PC computer PI interface converter RS 232 RS 485 for example PI PI GR S2000 PI S2000M S2000M alarm console Figure 8 S2000M connection for configuration by personal computer through RS 485 interface Configuration creating steps 1 Add required devices into console data base and create the partition 2 Define the authority levels for partition controlling assign reguired PIN codes and registered corresponding Touch Memory keys or Proximity cards 3 Set the relay output controlling 4 Set the event reporting to S2000 K keyboards and S2000 IT informators 5 Set the entry zones 6 Create user messages if it s needed These steps are described in sections 2 1 7 3 2 1 7 7 2 1 7 2 Adding devices into console database and partition creation Device loops can be included in partitions and their outputs can be automatically controlled by S2000M console if these devices are presented in console database To add the device specify it address and type 26 S2000M MAINTENANCE GUIDE Select Devices tab of program pprog exe It can be done by two ways manually and from list of polling devices To obtain the devices list press Start searching Program detects connected devices Devices are a
35. to the section Technical support on NVP BOLID site www bolid ru for additional information To enter RS 485 interface operative mode Press PRG key ENTER CODE Type engineer password Select SETTINGS menu item by 4 and ENT keys or press hot key 5 Select RS485 SETTINGS menu item by gt 4 keys and press ENT or press hot key 4 One should set several parameters that are listed below RING TOPOLOGY set parameter to the ON value displayed Default value is OFF SWITCH ADDR type the address of RS 485 line switcher unit S2000 SP1 Unit periodically connect console to first or second end of RS 485 line Default address value is 126 RATE NO FLT set the period for line ends switching if RS 485 interface line faults are not detected Valid range is from 1 to 255 minutes Default value is 240 RATE FLT set the period for line ends switching if RS 485 interface line faults are detected Valid range is from 1 to 255 seconds Default value is 2 5 SETTINGS RS485 SETTINGS 2 2 4 10 Console entering into programming mode In programming mode console database is configured at personal computer with pprog exe program Press button PRG ENTER CODE Type engineer password Select SETTINGS menu item by gt 4 and ENT keys or press hot key 5 Se
36. with discreteness 1 s For example if console clock is known to be 5 seconds slow per day it should enter the correction value being equal to 5 Enter in programming menu press button PRG ENTER CODE Type enginner password Select CLOCK SETUP menu item by 4 and ENT keys or press hot key 1 Select CALIBRATION VAL menu item by 4 and ENT keys or press hot key 2 1 CLOCK SETUP CALIBRATION VAL EN S2000M MAINTENANCE GUIDE LCD displays current correction value 0 for our example By means of gt lt and keys select new correction value and press ENT SEC DAY 0 Date setting Enter the programming menu press button PRG ENTER CODE Type engineer password Select DATE menu item by gt 4 and ENT keys or press hot key 2 LCD displays current date in DD MM YY format day month and year Input new date 2 2 4 2 RS 485 device address changing 2 DATE DATE DD MM YY Enter in programming menu press button PRG ENTER CODE Type engineer password 3 ADDRESSES Select ADDRESSES menu item by gt 4 and ENT keys or press hot key 3 RS485 DEVICES Select RS485 DEVICES menu item by 4 and ENT keys or press hot key 1 Enter current device address valid value from 1 to 127 or ADDRESS select valid address valu
37. 00 K or S2000 KS keyboards and Touch Memory key or Proximity cards at S2000 4 and S2000 2 Respectively there are differ two type of identificators PIN code password of S2000 K S2000 KS keyboards and S2000M console and Touch Memory key or Proximity cards password of S2000 4 and S2000 4 devices Identificator type determined by program automatically Entered at S2000 K keyboard password has to contain 4 digits If password entered at S2000 console then it can contain from 1 to 8 digits Maximum length of user password for S2000 console determine by value of the CODE LENGTH parameter 28 S2000M MAINTENANCE GUIDE Console finished password enter if number typed symbols equal to value of the parameter Parameter CODE LENGTH can be in range from 1 to 8 symbols see item 2 2 4 4 Identity code is input from the computer keypad or S2000 K S2000 KS S2000 4 S2000 2 Signal 20P SMD or S2000 KDL devices provided that they are polled by means of program pprog exe Reading identifiers from the polled device is faster and more useful then manual input Device must be polled by program pprog exe to input identificator code If device is not polled search this device on the tab Devices in window Search To set code on tab Password press button Read code and touch Touch Memory key Proximity card to the reade
38. 000 ARM Orion or ARM Orion Pro software Depending on connected to console equipment or software RS 232 interface mode need to be set by corresponded way 51 BOLID FIRE AND ALARM CONSOLE Console supports the following operative modes through RS 232 interface 1 PRINTER is the mode for printering event messages 2 S2000 amp PC mode for operating with ARM S2000 and ARM ORION Pro programs 3 S2000 PC RS 232 RS 485 interface converter mode with auto switching in active mode device operation mode when personal computer fails It is designed to reserve ARM Orion operations by the S2000M console The default parameter value is PRINTER To change parameter value make the following steps Enter in programming menu press button PRG ENTER CODE _ Type engineer password Select SETTINGS menu item by 4 and ENT keys or press hot key 5 Select RS232 SETTINGS menu item by 4 keys and press ENT or press hot key 5 5 SETTINGS RS232 SETTINGS Indicator will displays the current operative mode To change RS232 MODE mode press ENT key PRINTER Select new mode value by keys and confirm selection RS232 MODE gt by pressing ENT key S2000 amp PC For working in S2000 amp PC mode set console address see 2 2 4 7 Fither set the p
39. 2000 KDL devices must be also configured item 2 1 4 To customize the control by relay units S2000 SP1 indicator units S2000 BI keyboards S2000 K and S2000 KS informators S2000 IT console have to be configured Also at configuration user passwords and their rights partition and user text descriptions have to be set See details in the item If in the system S2000 4 S2000 2 or S2000 KDL devices are used which contain Touch Memory keys and Proximity cards for local control by loops or by access it is recommended to program these keys in console and to set test description for them Otherwise device event do not contain user identificator 2 1 2 Connection console and devices to RS 485 interface instructions To connect devices and console to the RS 485 interface their contacts A and B need to be connected to the A and B interface lines It is supposed that RS 485 interface use connection of type bus between devices that is all devices connected through interface by one pair of wires A and B lines matched at two sides by matching resistors Figure 2 Resistor rating value is 620 Ohm They are set at first and at last devices in the line In Signal 20 Signal 20 series 02 Signal 20P S2000 4 S2000 SP1 and S2000 KDL devices matching resistance is set on the board and can be connected in the line by setting jumper In S2000 S2000
40. AINTENANCE GUIDE 2 2 1 Displaying viewing and printing device messages Console receives messages from device They include event name data number and text partition description device address number of alarm loops reader relay user identificator and time At LCD message indication in top line message name is displayed and in bottom its source Console messages arein the appendix C As a source depending on the message type and console configuration partition name alarm loop name user name device address alarm loop number user number partition number can be displayed Additional message information can be seen at pressure corresponded digit Key 0 is used viewing message time and date Data and time format is next DD NM HH MM SS where DD day NM month number HH hour MM minutes SS seconds If since event rise and until its receiving by console considerable time left for example device work independently the message is shown according to the inner device clock Indicator of device time is symbol instead as day and month separator Also device time cannot include data If main message displays text information about message source key 1 shows data in digit way partition number device address and alarm loop number for messages about ALs device reader user numbers for access messages partition and user numbers for partition arm disarm messages When keys 2 pressed console shows te
41. CH The launching of fire extinguishing equipment was blocked up e g due to the door opening to the LNCH BLOCK BLOCKED protected area The launching of fire extinguishing equipment was LAUNCH canceled e g due to the command Cancel CANCEL extinguish given from console or to the pressing PNCH CANCE RESET key of S2000 ASPT Two threshold detectors in an alarm loop have been activated or fire delay has elapsed or Fire threshold of quantity measured by addressable analogue zone temperature or smoke has exceeded FIRE ALARM FIRE ALARM There is probability of fire Threshold detectors in an alarm loop have been FIRE PREALARM activated or alarm acknowledgment from a smoke F PREALARM threshold detector or Prealarm threshold of quantity measured by addressable analogue zone temperature or smoke has exceeded SILENT ALARM or ATTACK Silent zone alarm usually controls alarm keys SLNT ALARM INTRUSION Intrusion zone alarm alarm loop has been broken ALARM ALARM or alarm addressable detector has been activated 57 BOLID SECURITY SYSTEMS State FIRE AND ALARM CONSOLE Entry zone alarm if entry delay has not elapsed ENTR ALARM Device enclosure tamper detector has been broken TAM ALARM 2WRE SHORT 2WRE TRBL DISCONNECT ENTRY ALARM ENCLOSURE TAMPERING 2 WIRE LINE SHORT CIRCUIT 2 WIRE LINE TROUBLE DISCONNECTED ALARM LOOP CONFIGURATION ERROR FIRE
42. DEFLT PROTECT ENT To edit parameter MAX PASSWORD press ENT CODE LENGTH 4 input new value and finish input by pressing ENT button AUX as BURGLAR This example demonstrate default parameter values 2 2 4 5 Password management Password management includes adding new passwords changing and removing available 1 Engineer password password number 1 can be only changed 2 If password already exists the password with the same number cannot be added 3 Several identical passwords cannot exist 4 If password is not exists it cannot be removed or changed Adding and changing password Enter in programming menu press PRG button Enter password number from 1 to 2047 or select valid value USER NUMBER by gt 4 keys and press ENT ENTER CODE Type engineer password Select SETTINGS menu item by gt 4 and ENT v 5 SETTINGS keys or press hot key 5 Select USER CODES menu item by gt 4 and ENT Ma v USER CODES keys or press hot key 2 LCD displays the first available action Scroll the action list by b 4 keys For example engineer password can only be CHANGE changed user s passwords can be changed or removed Not existing password can be added Select ADD NEW for ADD NEW 49 BOLID FIRE AND ALARM CONSOLE adding new password or CHANGE for changing existing password Type p
43. ENT key after typing If the entered password is incorrect the console will sound in 37 BOLID FIRE AND ALARM CONSOLE ERROR mode display the message ILLEGAL CODE and after that will indicate the time To avoid the password selection after four running wrong typing the console blocks up next password entering for 30 sec for 1 min after 5 typing for 2 min after 6 typing and etc After entering the legal password the blocking will be off Getting the partition state Enter the password with partition controlling rights ENTER CODE 1200 DISARMED If it is correct the console will display the state of first available partition The example demonstrates that the partition named Second Flore has the state DISARMED gt and 4 keys are suitable for getting other partition states Also it is possible to enter the partition number and press ENT key The partition has several states due to the states of all zones alarm loops addressable detectors and load circuits and all devices included Initially the console displays the state with the highest priority The list of priorities in decreasing order can be viewed below in appendix B The listed states can concern to zones e g Intrusion alarm devices e g 2 wire line short circuit or zones and devices both e g Power failed The console in current version monitors the tampering of the device case and so the tampering of case makes influence on all stat
44. ENTR message in the buffer and gives the user available access according with 2 2 2 1 2 2 2 3 items of this manual If the password is not recognized the ILLEGAL CODE message is saved in event buffer If the password entered has no required autrority level ACCESS DENIED message is storied The access will be denied if 1 User has not control privilegies for any parttion For example for empty authority level when partitions are not assigned or assigned partitions cannot be controlled from the device 2 Presented PIN code TM key or Proximity card has no proper authority level 3 Engineer password is typed 2 2 2 1 Console controlling of partitions The main controlling function of console is arming disarming of partition Additionally if the system includes S2000 ASPT device it would be possible to select automatic or manual launching modes of automatic fire extinguishing systems launch fire extinguishing system remotely or remotely cancel the launching Partition can be armed or disarmed if the password typed has properly authority level If arming disarming is not enabled nonetheless it is possible to get the state of partition Password can be typed in time indication mode or in password typing mode after pressing ENT Parameter CODE LENGTH determines the maximum number of digits in the password see 2 2 4 4 which is by default equal to 4 If there is less numbers in the password it is necessary to press the
45. LCD At the end of 20 min delay console configuration takes default value In any delayed time resetting can be cancelled by pressing button CLR 2 2 6 Console version update Console software can be updated The opportunity can be used for getting new options and remove possible current version bugs For update are required PC with Windows 98 2000 XP connection cable for RS 232 interface update program ORION_PROG exe and file with libraries for different S2000M console versions extention chp Console connection to the computer for version update is shown on the Figure 5 Cable has to correspond shown on the picture type ORION_PROG exe program and file with libraries can be gat by electronic mail on address info bolid ru Versions update steps Set S2000M console in programming mode Run ORION_PROG exe Select COM port connected to the consol Run device search pressing Start searching button Program have to detects S2000M console displayed as S2000 console version 2 04 and possible some other devices connected through RS 485 interface Select it from detected device list and press PRG Open file with console libraries Program displays list of versions for given console device Select required version and press Write key After few seconds program prepare data for writing and write new firmware Write operation console has to shows FIRMWARE LOADING on the indi
46. OL ENT keys or press hot key 4 Select EXTINGUISH menu item by 4 and ENT 42 EXTINGUISH keys or press hot key 2 Select LAUNCH CANCEL menu item by gt 4 and ENT keys or press hot key 2 Enter S2000 ASPT address valid value from 1 to 127 or ADDRESS 10_ select valid address value by gt 4 key and press ENT In this example address 10 was selected Console displays current state of S2000 ASPT device LAUNCH STATE controlling the extinguish equipment In the example below ARMED S2000 ASPT device is ready for extinguishing equipment launching if the fire alarm conditions has been detected by fire LAUNCH CANCEL EN 2 S2000M MAINTENANCE GUIDE detectors or manual alarm call pointhas been activated or manual launching command has been given LAUNCH Select LAUNCH for selecting launching command and press ENT CONFIRM LAUNCH Press ENT to confirm launch and launching procedure will be DEVICE 10 started The console will display the new state of S2000 ASPT device S2000 ASPT device enter the launching delay mode If it is necessary to cancel launching press ENT CANCEL then select CANCEL and press ENT LAUNCH STATE LNCH DELAY LAUNCH STATE POE i UNGES The extinguishing equipment launch has canceled gt z z 2 2 3 5 Request for loop state ENTE
47. Orion polls all the system devices but the console execute the RS 232 RS 485 convertor function without galvanic separation The console doesn t control devices doesn t show their states and is unresponsive to key pressions LCD displays the S2000 PC string and the READY indicator blinks to show the data transmission If the computer doesn t poll the devices during a given time period then the console automatically switches to the active mode The switching delay is nesessary against false switchings due to the polling intervals To configure this switching way set the RS 232 operating mode to the S2000 PC value and give the switching delay as described in section 2 2 4 8 It is recommended to set the switching delay at least 60 seconds Two above switching ways are just alike in terms of capabilities Their benefits in comparison with each other are as follows switching by means of S2000 SP1 switching from S2000 PC mode 1 The galvanic isolation is like to be at less 1 in case of sophisticated system it is more cost suitable for usage of several consoles for 2 Old messages stored by the console in redundancy backup mode are available 2 when switching the controlling from the 3 It is possible to connect printer to the console to the PC the console will not give console messages about device disconnections The second reserving mode called as S2000 amp PC is that the console is to be directl
48. R CODE _ Type password Select REQUEST INFO menu item by 4 and ENT keys or press hot key 5 Select ZONE STATE menu item by gt 4 and ENT 751 ZONE STATE keys or press hot key 1 5 REQUEST INFO ADDRESS 2 Enter device number valid value from 1 to 127 or select valid address value by 4 key and press ENT ENTER LOOP 17 Enter loop number or select valid address value by 4 key and press ENT If the state was got it is displayed in following format device address loop number state In this example selected loop has ARM FAILED state Each 0 5 seconds the console automatically reguests state of selected alarm loop Use the P 4 keys to view states of other loops of selected device The loop states are described in appendix B 002 017 ARM FAILED 2 2 3 6 Alarm loop resistance measurement This command allows estimating loop resistance value device power voltage the temperature or smokiness The estimated value depends on intrusion and fire alarm panels being in use The intrusion and fire alarm panels can return either non dimentional value given by ADC or measured value supplied by corresponding physical unit Type password Select REQUEST INFO menu item by 4 and ENT 5 REQUEST INFO keys or press hot key 5 Select ZONE ADC menu item by
49. SECURITY SYSTEMS FIRE AND ALARM CONSOLE S2000M q 8 gt cas m oe CIR 4 ro Ce e oe Ce dE fe Maintenance guide SECURITY SYSTEMS FIRE AND ALARM CONSOLE TABLE OF CONTENTS 1 Description of the product and its operability 1 1 Purpose 1 2 Specifications 1 3 Delivery set 1 4 Description the product and capabilities 2 Maintenance 2 1 Preparation the product 2 1 1 General information 2 1 2 Connection console and devices to RS 485 interface instructions 2 1 3 Setting device configuration parameters 2 1 4 Address setting of addressable expanders 2 1 5 Printer connection to console or ARM S2000 2 1 6 Using the console for ARM Orion redundancy 2 1 7 Console configuring 2 1 7 1 General information 2 1 7 2 Adding devices into console database and partition creation 2 1 7 3 Setting partition control rights and password programming 2 1 7 4 Setting control by system relay outputs 2 1 7 5 Setting message transmission 2 1 7 6 Entry zone settings 2 1 7 7 Setting user messages 2 1 7 8 Controlling S2000 BI devices settings 2 1 7 9 Using the console for creating of systems controlling gas powder or aerosol fire extinguishing installations based on S2000 ASPT devices 2 1 7 10 Using the console with sprinkler or drencher extinguishing units based on devices POTOK 3N 2 1 7 11 Using the console with the phone communicator S2000 IT 2 1 8 Console mounting 2 1 9 Preventi
50. TROUBLE LOOP OPEN CIRCUIT LOOP SHORT CIRCUIT ARMING HAS FAILED DISARMED AND NOT READY DISARMED DISARMED AND READY Short circuit in S2000 KDL 2 wire addressable line Trouble in S2000 KDL 2 wire addressable line usually it is abnormal overvoltage The communication between the console and alarm loop or addressable detector or addressable expander circuit being controlled has been lost The status of such zone is unknown and the console cannot monitor this one It is typically happens when 1 the communication between the console and intrusion and fire alarm panels or S2000 KDL controller connected via RS 485 line and monitored present zone has been lost 2 the communication between S2000 KDL and addressable detector expander connected to its 2 wire line and controlled zone in question has been lost Type mismatch of 2 wire line connected addressable device and value given in S2000 KDL configuration or mismatch of zone type and type of device connected to S2000 KDL Fire alarm system failure such as addressable device internal problem failure of DIP 34A optical system or S2000 KPB device mass and pressure checkout circuit trouble CONFIG ERR FIRE TRBL The breaking of alarm loop or addressable expander TRBL OPEN circuit being controlled The short circuit of alarm loop or addressable TRBL SHORT expander circuit being controlled Arming has failed due to the activat
51. arameter PC TIMEOUT to the value time period reguired for computer presense analysis was made If computer fails after this period READY indicator will blink see table 1 Give console address to work in the S2000 amp PC mode To work in the mode S2000 PC transition delay in active mode from interface conversion mode at personal computer turn off parameter PC TIMEOUT in menu RS232 SETTINGS need to be set Delay is given in Enter in programming menu press button PRG ENTER CODE _ Type engineer password Select SETTINGS menu item by 4 and ENT keys or press hot key 5 Select RS232 SETTINGS menu item by gt 4 keys and press ENT or press hot key 5 Select PC TIMEOUT menu item Indicator displays parameter value To change parameter value press ENT 5 SETTINGS RS232 SETTINGS PC TIMEOUT 80 Input new parameter value and press key ENT PC TIMEOUT _ 2 2 4 9 The ring RS 485 interface operative mode settings Console can work with devices through RS 485 line with ring topology Ring topology allows preventing the system operability loss when RS 485 line has been broken When ring Un 2 S2000M MAINTENANCE GUIDE topology using the console poll the devices from both ends of RS 485 line The ends of RS 485 line are alternately connected to the console with the help of S2000 SP1 relay unit Refer
52. are protected by password 1 1 12 Console figured for 24 hour work 1 1 13 Console must be protected from action of atmospheric condensations and mechanical damage 1 1 14 Temperature range for console is from 274 to 313 K from 1 to 40 C 1 2 Specifications 1 2 1 Voltage of direct current power supply of the console is from 10 2 to 28 4 V 1 2 2 Consumed current in standby mode is if supply voltage 12 V 70 mA if supply voltage is 24 V 35 mA 1 2 3 Liquid crystal two line indicator 16 symbols in the line with green highlight BOL D FIRE AND ALARM CONSOLE 1 2 4 Length of the RS 485 communication line is no more then 4000 m 1 2 5 Length of the RS 232 communication line is no more then 20 m 1 2 6 Values of created by console radio noise are fewer standards 1 2 7 Console is stable to the electromagnetic noise 1 2 8 Average work time is below 20000 hr that correspond the probability of non break work 0 95 per 1000 hr 1 2 9 Average console life time is 10 years 1 2 10 Mass no more then 0 3 kg 1 2 11 Dimensions 14011425 mm 1 2 12 Console s construction satisfies fire rules in the case of malfunction and in the case of violate of maintenance rules 1 2 13 Number of connected to console through RS 485 interface devices is no more 127 1 2 14 Current system event console shows on the indicator print and save in nonvolatile buffer Messages include event name shown in appendix D time hour minutes sec
53. as been canceled Zone is monitoring the detectors ALARM RESET 4 Detector status monitoring has been turned on ARMED 5 Exit delay begins after entering arming command ARM DELAY 5 The detector status is not monitored DISARMED 5 Device or detector case is opened TAMPER ALARM 3 Device or detector case is closed TAMPER RESTORE 3 Device power supply is out of range POWER FAILED 3 Device power supply is restored after failure POWER RESTORE 3 nN SECURITY SYSTEMS Event description FIRE AND ALARM CONSOLE Displayed event name Category Battery supply is out of range BATTERY FAILED 3 Battery supply is restored BATTERY RESTORED 3 AC power has been lost AC POWER FAILED 3 AC power has been restored AC POWER RESTORE 3 Device was restarted DEVICE RESTART 3 The console has no response from the device through RS 485 DISCONNECTED 3 interface The console has restored the connection with the device through RS CONNECTED 3 485 interface Device shutoff from ring interface RS 485 branch FAIL RS485 LINE 3 Device connection through RS 485 ring interface branch has restored RST RS485 LINE 3 Short circuit in 2 wire addressable line 2WIRE LINE SHORT 3 Open circuit failure in 2 wire addressable line 2WIRE LINE OPEN 3 Other troubles in 2 wire addressable line 2WIRE LINE TRBL 3 2 wire line restored after any failure 2WIRE LINE RST 3 The
54. assword and press ENT Typing symbols will be displayed as If signal Error has sounded it indicates after password typing it indicates that this password has already existed and if so enter another password NEW CODE CONFIRM Type password again If signal Error has sounded it indicates that first typed password differs from the second typed password W O PART CONTRL For direct device loop operation select W O PART W PART CONTROL CONTRL For partition operation select W PART CONTROL Now set password authority level ARM and DISARM Variant 1 Password for direct device loop operation ARM w o DISARM Select one of offered loop control access levels ARM and DISARM ARM w o DISARM MAX AUTHORITY MAX AUTHORITY de and press ENT Variant 2 Password for partition operation AUTHORITY _ Number of authority level has been requested Authority level describes the user rights for partitions operation Valid values are from to 252 Authority level settings are described in the item 2 1 7 3 Console allows password programming as PIN codes Touch Memory keys or Proximity cards Touch Memory keys and Proximity cards are entered from Touch Memory or Proximity readers connected to S2000 4 or S2000 2 device identically to the procedure described above replacing symbol typing by key touching or card reading IMPORTANT Touch Memory keys or Pr
55. ate determined by parameter Control program If output initial state has to be off parameter Control program has to have value 1 if on value 2 Parameters value Control program of initial state and Control program can be programmed in device both with the help of console and with the help of program uprog exe 29 BOLID BOOD FIRE AND ALARM CONSOLE Attention When output external control of S2000 4 Signal 20P and Signal 20 version 02 devices is used internal control has to be removed that is outputs have to be not connected to loops If internal output control is used it is prohibited to use external control that is outputs have to be not connected to partitions Relay output is set on the tab Relay of program pprog exe Tab contains two windows in top window Partitions relay is displayed partition tree where for each partition is shown connected relay list Bottom window Devices relay contains tree of all system devices with relays To connect relay output with partition drag the relay from device tree window Devices relay in corresponded partition in the tree window Partitions relays At that relay will be added to the connected partition list If output should be controlled by few partitions connect it with other partitions the same way It is possible group connection partitions and outputs Few output can be selected by left
56. ated ACCESS NORM MODE 6 Door is opened too long DOOR LEFT OPEN 6 Door is closed after blocking in open state DOOR CLOSED 6 Door has been opened without access granting DOOR FORCED 6 Depending on indicated device this message means either entering to the programming menu or to the password changing mode for the console or to the user s key programming mode for S2000 4 panel PROGRAMMING j or S2000 2 device The user has canceled the audible alert signal provided by fire or fault ALARM CANCEL 8 S2000 IT has detected the phone line fault PHONE LINE TRBL 8 S2000 IT connected phone line has been restored PHONE LINE REST 8 The messages haven t been transferred because the S2000 IT MSG BUF FULL 8 buffer storage is full The event buffer storage has overflowed with some messages having MSG BUF OVERFLOW 8 been lost The console is turned on S2000 STARTED 8 The printer is on PRINTER ON LINE 8 The printer is off or not ready PRINTER OFF LINE 8 The user has changed the current date DATE CHANGED 8 The user has changed the current time TIME CHANGED 8 Date stamp is formed by the console after date changing and once a DATE 8 day Time stamp is formed by the console after time changing TIME STAMP 8 63 SECURITY SYSTEMS Event categories 1 FIRES 2 ALARMS 3 FAULTS 4 ARM DISARM 64 FIRE AND ALARM CONSOLE 5 ZONE ARM DISARM 6 ACCESS 7
57. ature status else OFF output Turn on during ON for a given time during launching delay counting launching delay before automatic fire extinguishing system starting in Launching delay state else OFF Turn on during ON for a given time if launching pulse for automatic fire launching extinguishing system has been given Launching state else OFF Turn on during ON if launching has been confirmed in Extinguishing extinguishing state else OFF 11 BOLID BOLD FIRE AND ALARM CONSOLE Number Program description Turn on if launching ON if launching has been failed in Launch fault state failed else OFF ON in Auto extinguishing state autoextinguishing is on else OFF OFF in Auto extinguishing state autoextinguishing is on else ON Turn on if ON in Manual extinguishing state autoextinguishing is off else OFF 45 Turn off when OFF in Manual extinguishing state autoextinguishing is off else ON 44 Comments for executive programs 1 Devices S2000 SP1 ver 1 20 and S2000 4 ver 1 07 support extended relay output controlling e g delayed controlling or control time being given in the range from 0 to 8191 875 seconds and 1 8 second resolution In addition these devices support various types of blinking differing by period and pulse ratio If the equipment does not support extended output relay control it cannot allow delayed controlling blinking can
58. automatically launching mode of extinguishing equipment is off EX MODE MANUAL 4 The automatically launching mode of extinguishing equipment is on EX MODE AUTO 4 The pressure detector has signaled pressure rising GAS PRESS SIGNAL 8 There is no expected pressure increase after launching pulse PRESSURE FAILURE 8 Fire conditions have been detected FIRE SIGNAL 8 The service is required for the detector for example the smoke chamber of DIP 34A detector is dusted SERVIRE REANIRER i Temperature has exceeded the maximum value TEMPERATURE HIGH 8 Temperature has fallen below the minimum value TEMPERATURE LOW 8 Temperature has normal value TEMPERATURE NORM 8 The heat sensor failure has detected HEAT SENSOR FAIL 3 The heat sensor has been restored after failure HEAT SENSOR RST 3 Voice notification is starting NOTIFICATION ON 8 Voice notification is avoided NOTIFICATION OFF 8 The pump is starting PUMP ON 8 The pump cuts out PUMP OFF 8 The pressure or water level is rising LEVEL HIGH 8 The pressure or water level is falling LEVEL LOW 8 The pressure or water level is in normal state LEVEL NORMAL 8 The pressure or water level has exceeded the emergency threshold LEVEL TOO HIGH 3 The pressure or water level has fallen below the emergency threshold LEVEL TOO LOW 3 Auxiliary loop alarm AUX ZONE ALARM 9 Auxiliary loop restored AUX ZONE RESTORE 9 EE Arming is impossible due to detector being in NOT READY TO ARM 9 Zone disarmed Ready for arming READY TO ARM 9 The o
59. be realized with frequency 1 Hz and pulse ratio 2 only control time can be given in range from 0 to 255 seconds with 1 second resolution 2 One can give the the delayed controlling for all programs except NoNe 9 10 13 14 15 16 3 Outputs with permanent executive programs e g On or Alarm output are turned on both for opening and closing when meeting the appropriate conditions and retain in such state until the condition avoids After condition disapearing relay outputs return to initial state On the contrary to permanent executive programs outputs with time given programs that is with limited control time return to initial state not only when disappearing conditions but if the time has elapsed Time given programs will operate identically with permanent programs if given time has the maximum value being equal 8191 875 second 4 Programs NoNe 11 33 34 and 35 are designed to control the fire automatic equipment including autoextinguishing devices According to the autoextinguishing systems requirements one can activated the extinguishing equipment on premises when there is fire alarm in two independent fire alarm loops checking this premises To avoid the leak of extinguishing compound gas powder it is allowed to start the equipment only if all doors are opened In addition it is necessary to check the light and audible annunciators control circuits and block up the fire extinguishing launching when such circuits troubles T
60. boards PIN code and devices S2000 4 Touch Memory key or Proximity card 1 1 8 Console may use S2000 BI devices for partitions state indication 1 1 9 Console synchronizes time and date in devices It is necessary for normal time window operability in S2000 4 and S2000 2 devices Console provides connection between S2000 2 device It is necessary for normal operability network Anti pass back mode second passing prohibition in access control system on the basis of S2000 2 devices 1 1 10 Console controls by S2000 SP1 device relay outputs These output we will call system outputs in opposite to the alarm panel local outputs controlled by devices itself System output reaction depends on state of connected partitions and control program System relay outputs can be used for control by light and sound notificators operational device switching alarm message transmitting to the CGP Except S2000 SP1 device outputs S2000 KPB S2000 4 Signal 20P and Signal 20 series 02 device outputs can be used as system outputs 1 1 11 Console allows changing connected through RS 485 interface device addresses and also programming and changing address expanders addresses S2000 AP1 S2000 AP2 and address notificators IPR 513 3A S2000 SMK DIP 34A ver 01 S2000 IP ver 01 connected to the S2000 KDL controller two wired connection line Programming functions
61. cator and LED indicator READY blinks indication data transmission to the console 3 STORAGE 3 1 At console store acids alkalis corrosive gases and other noxious corrosive vapors have to absent 3 2 Storage life in package has to be below 12 monthes 4 TRANSPORTATION 4 1 Packed consoles transportation can be done by any transport in covered containers 5 CERTIFICATION INFORMATION 6 1 S2000M intrusion and fire alarm console corresponds to Russian Federation state standards and have certificate of conformity to Russian state standards on alarm and fire systems certificate of conformity to Russian fire norms 6 2 NVP BOLID s quality management corresponds to ISO 9001 standard 6 INFORMATION ABOUT MANUFACTURER NVP BOLID Pionerskaya st 4 Korolev Moscow region Russia 141070 Tel fax 7 495 513 4342 513 4351 516 9372 516 9373 777 4020 http www bolid ru E mail info bolid ru 54 S2000M MAINTENANCE GUIDE 7 WARRANTY Manufacturer warrants it S2000M product to be in conformance with specification under normal transportation storage mounting and maintenance Manufacturer warrants S2000M product to be free from defects in materials and workmanship for 18 months since putting in to operation but no more then 24 months since production under normal use and service S2000M fire and alarm console Product designation serial number produced tested by quality control depa
62. ce value alarm loop resistance 1 2 4 7 6 10 16 Open kOhm kOhm kOhm kOhm kOhm kOhm 1 ADC value for S2000 4 255 140 93 49 40 25 16 ADC value for S2000 4 01 255 229 153 8 66 42 27 This table can be found in maintenance guide of S2000 4 device Normal range for fire and alarm loops is from 2 0 kOhm to 6 0 kOhm B Correspondence between alarm loop resistance and Signal 20 device ver 1 60 1 61 and below ADC value alarm loop Resistance 0 2 0kOhm 82kOhm 11 0kOhm Open Normal range is from 2 0 kOhm to 11 0 kOhm x Correspondence between loop resistance and Signal 20 device series 2 ADC value alarm loop Resistance o 2 0 kOhm 4 7 kOhm 6 0 kOhm Open ADC value D a a fee 5 2 2 3 7 Console date and time setting Time setting ENTER CODE _ Type password gt cpr 04 gt i 6 AUX FUNCTIONS Select AUX FUNCTIONS menu item by and ENT keys or press hot key 6 61 SET TIME Select SET TIME menu item by gt 4 and ENT keys or press hot key 1 D 4 S2000M MAINTENANCE GUIDE Current time is displayed by LCD in HH MM format hours and minutes Enter new time TIME HH MM After changing time console forms two messages TIME CHANGED and TIME STAMP Message TIME CHANGED informs when user has changed time Message TIME STAMP shows user time value Date set ENTER CODE Type password c gt opr cd c
63. ceiving 8 control control Figure 4 Built star configuration with the help of interface repeaters Sometimes there is need to connect console to devices through radio channel radiorelay channel fiber or other connection lines To interface RS 485 channel with connection channel equipment with RS 232 input or RS 485 input and having next data transmission parameters and speed transmission 9600 bit s word length 8 bit without check even parity 1 stop bit If equipment with RS 232 output RS 485 interface signals have to be converted in RS 232 interface signals by RS 232 RS 485 converter for example S2000 PI Similarly at the other side of the connection line RS 232 signals need to be converted in the RS 485 interface signals As a tule at data receiving transmission equipment has own noises More over it may have significant receive transmit switching time If the timeouts are above acceptable values console will not detect devices or connection will be unstable For example if transmission equipment imports delay 3 ms then S2000M console receive reply from device more then 6 ms after request Because console waits reply from device no more 5 ms device will not be detected To solve these problems few connection parameters made customizable There are standby time at duty cycle poll device search at command and set of customizable delays before transmission If equipment distortion is only data transmission delay i
64. ching Launching delay Launching Extinguishing Launch fault 2 To control the status of fire extinguishing area turn auto manual launching mode and activate cancel remote launching from console itself or S2000 PT device These functions require password based access 3 The console has a number of relay control programs designed for operating in fire extinguishing systems Programs Turn on off when auto extinguishing is on off monitor the launching mode of fire extinguishing units and can be used in particular for controlling Manual extinguishing light box Programs Turn on during launching delay and Turn on during extinguishing can be used for Keep out x Get out light annunciator controlling The program Turn on during launching can be used for launching of extinguishing installation for several areas The program Turn on if launching failed can be used for standby fire extinguishing installation launching It is recommended to use S2000 ASPT versions 2 03 and above along with S2000M console The controlling of S2000 ASPT devices with versions less than 2 00 is limited by automatic launching control mode and remote launch in local control mode only out of partitions Such control doesn t require the configuring of the console and described in section 2 2 3 4 All zones of S2000 ASPT loops inner zones and output circuits should be combined into one partition which represents one area or fire extingu
65. dded to the console database by dragging from window Search to window Devices To add device manually press Add device button in the top right corner of the Devices window In Inspector window click the address line and type the required address the digit from 1 to 127 Click the type line and select the required value from the available list If it is necessary add the description that will be shown only from the configuration program New device will be added to the database To create partition it is necessary to add new partition assign it number from 1 to 4 digits and to include required zones The total number of partitions cannot be more then 511 Optionally one can assign any text descriptor no more 16 symbols to zones and to partition To add new partition select the tab Partitions This tab has two windows Top window Partition zones contains a partition s tree with zones the bottom window Device zones contains the device tree with zones Press button Add partition in the upper right corner of the Partition zones window In Inspector window click the line Number and type the unique number from 1 to 4 digits If it is necessary assign the text descriptor to the partition in Description line up to 16 symbols Parameter value input is finished by pressing key Enter on computer keyboard Adding zones to partition is made by drug and drop of zones from bott
66. diverse from ARMED Message UNKNOWN PART means that partition not exists Message ACCESS DENIED means that user has no privileges for controlling this partition by means of this device see the section 2 2 2 If the message OPERATION NOT COMPLETED is showed it means that partition control operation was not completed correctly It can happen as a result of disconnection of devices and interface RS 485 or zone absence in the partition or console database failure 38 S2000M MAINTENANCE GUIDE For example let the partition number 1200 named Second 1200 ARM FAILED floor failed arming and the message ARM FAILED was Second Flore displayed To show failed zones press TRBL and choose the state ARM FAILED by means of gt or 4 Second Flore To get the list of failed zones press ENT The console will ARM FAILED show the first zone By means of gt and 4 keys it can be possible to scroll all failed zones of partition ARM FAILED Door 1 If zone has no name then its number will be shown formed as ARM FAILED ZONE Device address The alarm loop or addressable ZONE 002 007 detector number 2 2 2 2 Partition control at S2000 K keyboards Partition arming and disarming at S2000 K keyboards is identical arming and disarming at panel See details in S2000 K documentation 2 2 2 3 Touch Memory and Proximity card partition control Partition can be armed disarmed by key Touch Memory
67. e by 4 keys and press ENT Enter new device address valid value from 1 to 127 or select valid address value by gt 4 keys and press ENT NEW ADDRESS 2 2 4 3 2 wire devices adresses changing and programming 2 wire devices addresses changing 2 wire devices address can be changed in case of it is known Enter in programming menu press button PRG ENTER CODE Type engineer password 3 ADDRESSES Select ADDRESSES menu item by gt 4 and ENT keys or press hot key 3 2 WIRE DEVICES Select 2 WIRE DEVICES menu item by gt 4 and ENT keys or press hot key 2 CHANGE ADDRESS Select CHANGE ADDRESS menu item by 4 and press ENT Enter S2000 KDL address valid value from 1 to 127 or RS485 ADDR select valid address value by 4 keys and press ENT Enter 2 wire device address valid value from to 127 to be changed or select valid 2 wire device address value by keys and press ENT Enter new 2 wire device address valid value from 1 to 127 or select new 2 wire device address value by 4 keys and press ENT If command has successfully completed console makes sound signal Success and S2000 KDL sends console the message about disconnecting of 2 wire device with old address 47 CURRENT ADDR _
68. ed status of detector For alarm zones being controlled if disarmed Zone is not armed with the detector having been activated and so being not ready for arming ARM FAILED NOT READY Zone has been disarmed and the detector status is DISARMED not monitoring For alarm zones being controlled if disarmed Zone is not armed but it is ready for following arming READY 58 S2000M ARMING DELAY ZONE ARMED BATTERY FAILED AC POWER FAILED POWER FAILED MANUAL EXTINGUISHING THE PUMP IS ON THE PUMP IS OFF AUTO EXTINGUISHING AUXILIARY ALARM AUXILIARE NORMAL RELAY DISCONNECTED OPEN RELAY OUTPUT RELAY OUTPUT SHORT CIRCUIT FIRE EQUIPMENT NORMAL MAINTENANCE GUIDE Zone is arming the arming command has been entered but the result of operation has not yet been known or arming delay is being counted Zone is normal armed for alarm loops or alarm addressable detectors or zone is normal controlled for another loops and addressable detectors including fire ones ARMED The backup power supply storage battery has BAT FAIL failed The primary AC power supply has failed AC FAIL The device power supply is out of range The pump is operating POWER FAIL The automatically launching mode of extinguishing EX MANUAL equipment is off PUMP ON The pump is off PUMP OFF The automatically launching mode of extinguishing EX AUTO equipment is on Auxiliary ala
69. en ON for a given time when arming else OFF output Turn off for a given If at least one zone is armed then OFF for a given time 20 ee time when arming else ON output Turn on for a given time If at least one zone is disarmed then ON for a given time 21 i ae when disarming else OFF output Turn off for a given If at least one zone is disarmed then OFF for a given time 22 re time when disarming else ON output Turn on for a given time If at least one zone is in the state Arm has failed then ON 23 if arming has failed for a given time else OFF output Turn off for a given If at least one zone is in the state Arm has failed then 24 time if arming has OFF for a given time failed else ON output Turn on for a given time If at least one zone is in the state Auxiliary alarm then 25 when auxiliary alarm ON for a given time else OFF output 10 S2000M MAINTENANCE GUIDE Program description Turn off for a given If at least one zone is in the state Auxiliary alarm then 26 time when auxiliary OFF for a given time alarm else ON output 27 Turn on when If at least one zone is disarmed then ON disarmed else OFF output 28 Turn off when If at least one zone is disarmed then OFF disarmed else ON output Turn on when armed If at least one zone is armed then ON 29 else OFF output 30 Turn off when armed If at least
70. es console address in programming mode This address is necessary when configuring the console with the help of pprog exe Enter in programming menu press button PRG ENTER CODE _ Type engineer password Select SETTINGS menu item by gt 4 and ENT keys or press hot key 5 Select RS485 SETTINGS menu item by gt 4 keys and press ENT or press hot key 4 Select S2000 ADDR menu item by and 4 keys To change address press ENT type new value and press ENT 5 SETTINGS RS485 SETTINGS S2000 ADDR 127 2 2 4 7 Console address setting in personal computer work mode Console address in this mode is the address for polling by ARM S2000 and ARM Orion Pro programs Enter to programming menu press button PRG ENTER CODE _ Type engineer password Select SETTINGS menu line by 4 and ENT keys or press hot key 5 Select RS232 SETTINGS menu item by gt 4 keys and press ENT or press hot key 5 5 SETTINGS RS232 SETTINGS S2000 ADDR 127 Select 2000 ADDR menu item by by CE and PA keys To change address press ENT type new value and press ENT 2 2 4 8 Console RS 232 interface operative mode settings RS 232 outputs of S2000M console GND DTR and TxD line can be connected to printer or personal computer supplied with ARM S2
71. es of the partitions to which device s zones belong The tampering of detector case on the contrary is not monitored and doesn t affect on the states of partition To get all the states of partition press TRBL The console will display the partition descriptor name or the number if no named in the first line and its state of highest priority Press gt for scrolling and showing the list of states in decreasing priority order Press to return the previous entry Use gt and 4 and press ENT to display all zones with such state for example with the state Intrusion alarm Use gt and keys to scroll zone descriptors The state of zone is displayed in the upper line but the descriptor of zone is displayed in the lower one name or device address with alarm loop number or addressable detector number or load circuit number Second Flore Partition arming disarming Enter the password with partition controlling rights Choose the required partition by means of or 4 keys or having entered its number Press ARM for arming or DISARM for disarming Or press ENT enter to menu select the necessary command and press ENT If partition has armed the console makes sound signal Success and displays new partition state 1200 ARMED Otherwise console makes sound signal Error and displays error message UNKNOWN PART ACCESS DENIED OPERATION NOT COMPLETED or another message
72. evels can have one partition or group Console has three default access levels for device control ARM and DISARM ARM w o DISARM MAX AUTHORITY Access level ARM w o DISARM gives the right for alarm loop individual or group arming and also alarm reset and alarm loop state request Access level ARM and DISARM gives also the right for alarm loop individual or group arming and disarming Access level MAX AUTHORITY has all control functions rights Comparing with the level ARM and DISARM there are accessible general arming and disarming manual device output control printing buffer events setting time and data request ADC Device control functions are described in item Note Access to the control functions is protected by passwords if option CODE REQUIRED is on If option CODE REQUIRED is off loop control functions are accessible without password By default console has one user password with number 2 it has value lt 1234 gt and access level MAX AUTHORITY Console allows setup password owner to add remove and change user passwords Users can change own password by console 1 2 19 States of LED indicator READY green in different modes of work through interface RS 232 are shown in the table 1 1 2 20 Console provides states indication of all system partitions on LED indicators ALARM FIRE TROUBLE and FAULT according to tables 2 5 Indicator s colou
73. f parameter is on resetting to the default values is prohibited otherwise configuration resetting is available as described in item 2 2 5 D EN OO S2000M MAINTENANCE GUIDE 5 CODE LENGTH maximum symbol number in user password from 1 to 8 Password accepted automatically when it length is equal to given value If the password is shorter then it needs to be finished by ENT key pressing 6 AUX as BURGLAR on off mode in which auxiliary loop is interpreted as intrusion alarm If this mode is on auxiliary alarm is interpreted as Intrusion alarm and recovery is interpreted as Armed Parameter is applied to all technological system loops It can be used in alarm systems which need auto recovering after alarm Enter in programming menu press button PRG ENTER CODE _ Type engineer password Select SETTINGS menu item by 4 and ENT v 5 SETTINGS keys or press hot key 5 Select EXTRA SETTINGS menu item by 4 and v EXTRA SETTINGS ENT keys or press hot key 1 Select parameter by and 4 keys Indicator displays current value of selected parameter Parameter ALARM SOUND CODE REQUIRED MAX PASSWORD has numerical value Other parameters USER CODE PRG have values ON and OFF Value ON as and value OFF is displayed as To inverse parameter value press
74. g instruction Printer is connected to S2000M console with the help of Printer cable see section 1 3 Connection circuit is shown on the Figure 1 19 BOL D FIRE AND ALARM CONSOLE It is possible use personal computer instead printer to log events To do this for example program Hyper Terminal from Windows or Telemax from Norton Commander 5 can be used COM port must have next parameters transmission speed 1200 bit s 8 bit without parity Console is connected with help of printer cable and connector to free computer COM port If computer has 9 contact COM port socket connector DB 25F DB 9F required and for 25 contact COM port socket DB 25F DB 25F connector At connection to the 9 pin computer COM port contact console outputs hav to be connected next way console output TxD is connected to 2 output COM port contact DTR output to 4 output output GND to output 5 ARM 82000 program is much more convenient provided by Bolid The target of the program is display and preview console events More over program has additional features Adding in event log additional information from device and console configuration files partitions and zones names user names Highlighting by different color messages of different categories fires alarms faults and so on Displaying states of partitions zones and devices Event filter allow select events by
75. he door state is controlled by means of alarm loops known as auxiliary If such loop is broken i e the door is opened it takes the Auxiliary loop alarm status but if close door condition restored this loop automatically restore its state after auxiliary loop recovery time To control light and audible annunciators one can use S2000 KPB outputs being able to control short or open failures of load circuit Output executive programs are realized so that launching is blocked up if auxiliary loop or output circuit is failed As mentioned above to create automatic fire extinguishing controlling the premises is to be controlled by at least two fire alarm loops the doors are to be monitored via auxiliary alarm loops and annunciators are to be controlled by means of S2000 KPB This loops and outputs form one fire partition associated with one or more outputs designated to give the launching pulse and being controlled by ASPT program It two or more fire loops in partition alarm the relay output turns on with given time and delay provided all doors are closed and annunciators are operative If at least one door is opened or at least one annunciator circuit is failed the relay does not start If two latter conditions disappear with fire alarm being retain then outputs 12 S2000M MAINTENANCE GUIDE supplied with Nell ASPT and No33 ASPT 1 programs will be turned on with given delay but outputs supplied with Ne34 ASPT A
76. hing system for several areas with the common extinguishing installation with each area being protected with singular S2000 ASPT device S2000 ASPT devices control fire detector statuses and in case of fire generate launching message and open gaseous discharge valve to protected area The console can activate the fire extinguishing system in Launching condition for any area giving out launching pulse to output provided with executive program Ne 39 Turn on during launching Program Ne 41 Turn on if launching failed can be used for launching of redundant fire extinguishing installation 1 2 23 Console allows assigning up to 32 entrance zones Entrance zone represents alarm loop with alarm delay ability Alarm delay permit to enter the protected area through entrance zone without immediate alarm and to disarm the premises The delay factor can be given from 0 to 254 s Entrance alarm loop being broken the console gets out the message ENTRY ALARM 13 BOLID FIRE AND ALARM CONSOLE If after delay elapsing entrance zone has been retaining in alarm that is was not armed or disarmed the console generates INTRUSION ALARM message Relay controlling programs operate INTRUSION ALARM and ENTRY ALARM states by different ways see Table 7 For example SIREN programmed output is not turned on in ENTRY ALARM partition state with Alarm output having being opened Entrance zones assigned with the help
77. ht corner of the Partition groups window In Inspector window click the line Number and type the unique number from to 4 digits If it is necessary assign the text descriptor to the group in Description line up to 16 symbols Parameter value input is finished by pressing key Enter on computer keyboard Adding partitions to the group is made by drug and drop of partitions from bottom partition list in correspondent brunch of upper group tree 2 1 7 3 Setting partition control rights and password programming Access to partition control functions is granted to users at password entering at S2000M console S2000 K keyboards or S2000 KS or at using Touch Memory key or Proximity card with S2000 4 or S2000 2 Signal 20P SMD version 2 01 and above S2000 KDL version 1 15 and above User gets access to partition control functions if he has corresponded control rights for these partitions and control is permitted for controlled device if he has rights User s 27 BOLID FIRE AND ALARM CONSOLE rights is determined by access level of its password Access level determines permitted partition list and control rights for each partition Device s rights are determined by permitted control partition list of this device All partition control right information access levels password and device rights are programming in the S2000M console Access levels and device rights ca
78. ime else OFF output 8 Blinking for a time If Intrusion alarm or Fire alarm blink 0 5 s ON 0 5 c Normal state ON OFF during given time else ON output 9 LAMP If Fire alarm Fire prealarm Intrusion alarm Entry alarm or Arm failed then blink 0 5 s ON 0 5 s OFF if Disconnected alarm loop Relay disconnected Fire trouble Loop open circuit Configuration error Open relay output Relay output short circuit Battery failed AC power failed Power failed 2 wire line short circuit or 2 wire line trouble then blink 0 25 s ON 1 75 s OFF if there is at least one armed zone then ON output if all zones are disarmed then OFF output 10 Alarm output 1 If all partitions are armed then ON close outputs else OFF open output 11 ASPT ON for a given time if at least two zones in partition have Fire alarm status and there are no zones having states Auxiliary alarm Relay disconnected Open relay output Relay output short circuit When the failure removed the relay output will be ON SECURITY SYSTEMS FIRE AND ALARM CONSOLE Number Program description 12 SIREN If Fire alarm then blink given time 1 5 s ON 0 5 s OFF if Attention then blink given time 0 5 s ON 1 5 s OFF if Intrusion alarm then
79. ishing It is necessary to assign some passwords for launch mode control operations and for activating canceling of the remote launch For this purpose when creating authority levels Authority levels tab in pprog exe define partitions that is permitted for controlling that is extinguishing areas and assign the permitted operations for each partition The permitted operations can be arming disarming and turning automatic equipment on turning automatic equipment off remote launching and launch canceling Arming is needed for resetting of activated S2000 ASPT loops Disarming is meaningless in the context of S2000 ASPT using Other operations are given when needed When using S2000 PT it is necessary to assign the partition number to each indicator group by means of uprog exe Hence the indicator group is associated with the specific extinguishing area and displays the status of that area The FIRE indicator shows either if some fire loops of S2000 ASPT have been activated being in FIRE or FIRE PREALARM status or control zone state when remote launching command from console has been received or manual call point activated FAULT indicator signals if there are various troubles in extinguishing area among them fire loop troubles output circuit troubles power outage and disconnection from S2000 ASPT LAUNCH BLOCKED indicator displays if there is extinguishing launching blocking up e g during launching delay doors to
80. isplay on the LED print or transmits to the S2000 K keyboards and S2000 IT informators 1 2 16 Console can translate system messages to the S2000 K keyboards and S2000 IT informators For any of the devices permitted message categories and partition list can be set 1 2 17 Partition number in the system is 511 Partition group number is up to 128 The number of alarm loops that can be grouped in partitions are up to 2048 Alarm loops can be included in partitions in arbitrary order but any alarm loop can be included in one partition only Any partition can be included in any group or in few groups up to maximal number 128 For each partition or partition group text description from 16 symbols can be set This description will be included in printing of the events and can be seen on the console LED 1 2 18 Console has passwords system for access restriction to the arming disarming and programming functions Password can has from 1 to 8 digits Console allows set passwords for 2047 users For each user text description name from 16 symbols can be set Name or password order number from 1 to 2047 identify user in the system User name is included in the event printing and can be seen on console LED Password with order 1 is engineer password It is unique password with the programming function access Engineer password owner can configure console and device parameters setting 6 S2000M MAINTENANCE GUIDE addresses of de
81. lect RS232 SETTINGS menu item by gt 4 keys and press ENT or press hot key 6 PROGRAMMING When LCD displays PROGRAMMING MODE the console enter the remote programming mode through RS 485 or RS 232 interfaces To exit from programming mode press key CLR 5 SETTINGS REMOTE PROGRAM 2 2 5 Reset settings to default values If the engineer password has lost there is mechanism for resetting into default value After console resetting the event buffer will be cleared and the configuration will be returned to default value with the engineer password being set to the default value lt 123456 gt Attention Resetting is possible only if option DEFLT PROTECT is off it can be available from menu 5 SETTINGS subitem EXTRA SETTINGS Default option DEFLT PROTECT value is OFF If resetting is to be prohibited then turn the option DEFLT PROTECT on If engineer password is lost and DEFLT PROTECT is set then CALL FOR NVP BOLID SERVICE To reset default values turn on console with pressed keys CLR and MEM LCD displays LOAD DEFAULT SETTINGS Key up the CLR and MEM keys Press ENT to confirm operation or CLR to exit from resetting procedure If the operation was 53 SECURITY SYSTEMS FIRE AND ALARM CONSOLE confirmed the 20 minutes delay will be counted with the time before password resetting being displayed by
82. lid address value by 4 key and press ENT Enter loop number valid value from 1 to 127 or select valid address value by 4 key and press ENT S2000M MAINTENANCE GUIDE ENTER CODE _ Type password Select DISARM menu item by gt 4 and ENT keys or press hot key 2 Select DISARM GROUP menu item by gt gt and ENT keys or press hot key 2 2 DISARM 22 DISARM GROUP ADDRESS Enter device number valid value from 1 to 127 or select valid address value by 4 keys and press ENT Common disarming Type password Select DISARM menu item by gt 4 and ENT keys or press hot key 2 Select DISARM ALL menu item by by gt 4 and ENT keys or press hot key 3 ADDRESS Enter device number valid value from 1 to 127 or select valid address value by 4 keys and press ENT gt 2 DISARM 23 DISARM ALL 2 2 3 2 Device alarm reseting At this command device with given address transmits alarm turned on external device utputs in initial state and arms alarm loop that in alarm or fire state ENTER CODE DE Type password Select ALARM RESET menu item by by gt and ENT keys or press hot key 3 3 ALARM RESET Enter device number valid value from 1 to 127 or select valid addres
83. lid address value by gt 4 keys and press ENT If S2000 KDL complete address programming command LCD will displays message ADDR PROGRAMM S2000 KDL enter the address programming mode Press CLR to cancel address programming To programming 2 wire device address make all reguired steps described in device maintenance guide The device address having set S2000 KDL automaticalle exit address programming mode the console makes sound signal Success and displays messages about device states If operation faults the console makes sound signal Error and displays diagnostic messages COMMAND ERROR DEVICE OFF LINE COMMAND ERROR UNKNOWN COMMAND COMMAND ERROR ADDR OCCUPIED or COMMAND ERROR 2 2 4 4 Console extra settings CURRENT ADDR _ ADDR PROGRAMM Console settings include next options 1 ALARM SOUND is alarm indication mode This mode can be on or off 2 CODE REQUIRED is device control function access restriction mode Device control functions are protected by passwords if parameter is on If parameter is off control functions are accessible without password by ENT key pressing 3 USER CODE PRG permission deny user password changing If parameter on user has opportunity to change its password at console key board see item 2 2 4 5 DEFLT PROTECT protection console configuration reset in default values I
84. mouse button and pressed key Shift for range selection or Ctrl for selective marking after that there can de added to the partition At dragging output or few outputs on the tree root Partition relays will be connected to the all partitions in the system At dragging device to the partition all device outputs will be connected to the partition Also control program start delay and control time for the outputs should be set For that in the window Devices relays in device tree select relay in the inspector window are displayed current parameter values correct them if necessary 2 1 7 5 Setting message transmission It is possible transmit events to S2000 K keyboard version 1 04 and above Keyboards allow indicating received events on LCD signalize by internal sound annunciator at alarm event have nonvolatile event buffer Messages can be transmitted to S2000 IT phone informators Messages should not sent to the other devices because they are not needed them for work and delay system operability For setting events transition to the devices select the devices which will receive messages from the console Messages can be sent independently translation to the address or like broadcast message to all devices at once common translation For each device message categories and partitions for transmission can be set It allows permitting some type message transitions for example alarms and
85. n be given by program pprog exe only Passwords can be set by both program pprog exe and by console In console up to 252 access levels with partition control rights can be set Access levels should be given before passwords programming At adding for each access level number from 1 to 252 list of permitted partition for control for each partition in the list control rights permit or not arm disarm have to be set If for access level arm and disarm are not permitted then password owner can only view the states of accessible partitions It has to take into account the restriction that just 8 access levels can have control rights for the same partition To create access level choose Authority levels tab of program pprog exe This tab consists of two windows Top window Authority levels contains tree of added to the console configuration access levels where each level has partition list that he gives right to control Bottom window Partitions contain list of all partitions added in configuration To create authority level press button Add athority level In the inspector window in line Number select authority level number Number has to be in the range from 1 to 252 and in line Description type text name this parameter is additional and not saved in console Further in created level it is need to add partitions for control Partition is added by dragging from bottom window Partitions
86. n programming mode allow to write and to read the configuration by means of program pprog exe When in programming mode the console should have a unique address in RS 485 interface address range Its default value equal 127 and can be changed see item 0 Refer to the pprog exe user s manual for procedures for console configuring To exit from programming mode press console key CLR The console will return to operating mode and 25 BOLID EC FIRE AND ALARM CONSOLE request the states of all connected devices loops and so on It can take few dozen seconds typically or even few minutes maximal value After that procedures console is ready Before reading and writing of S2000 console configuration by program pprog exe the communication between console and program has to be set Select Devices tab shoose the console communicated COM port number and press key Start searching Program searchs the connected devices showing addresses and types of founded devices in the lower window If the console will be founded the reading and writing of the console configuration will be able Main menu of S2000M include functions Write configuration and Read configuration for reading and writing current configuration to the console memory Read operation takes about 4 minutes Write operation about 4 min 20 sec Attention During writing of the configuration it is prohibited cut off the power of
87. of electro and fire safety Console has not dangerous voltage circuits Console construction provides its fire safety in accident regime and in the case violation of maintenance rules Mounting setup technical support have to be done when console power off Mounting and technical support of the console have to be done by personnel with corresponded qualification access 2 1 10 Console first starting Check mounting before console will be turn on After console has been turned on LCD should be highlighted and should display message about turning on At device connection through RS 485 interface console send device detection message Device reset is formed by device at power on and Power down is formed by some device if power supply below the norm messages can be shown Last message device forms if power is turned off and at next the device connection console read it and display on the LCD If printer is on then it should ptint the messages about console and printer turning on console connected device detection and other messages It is recommended to change setup password because user can get unauthorized access to program functions One or several user device control passwords have to be given see item 2 2 4 5 To set the modes it is required to set the parameters ALARM SOUND and CODES REQUIRED ALARM SOUND parameter needs to be on if inner sound annunciator messages should be alarmed otherwise it has to be
88. om device tree in correspondent brunch of upper partition tree Program allows dragging both one zone and group of zones For group selection use left mouse button with keyboard buttons Shift or Ctrl Key Shift is used for selecting zone range but Ctrl is used for selective marking If it reguires to drag all device zones into the partition one can drag the device itself from device tree Zones can be assigned with the text description Select the reguired zone in Device zones window and click the Description line in Inspector window Enter the text string up to 16 symbols Partitions can be integrated into groups There can be created up to 128 partition groups To create partition group it should add new group assign it with a group number from 1 to 4 digits and include required partitions Partition groups can be assigned with the text description up to 16 symbols One group can contain up to 511 of partitions and a partition can member into several groups Note Group controlling takes more time then partition one especially when a partition is included into few groups So it is not recommended if it is not really needed To add new partition group select the Partition groups tab This tab has two windows Top window Partition groups contains a partition group s tree with partitions the bottom window Partitions contains the partition list Press button Add group in the upper rig
89. on of this manual for procedures for relay output control settings 2 1 7 10 Using the console with sprinkler or drencher extinguishing units based on devices POTOK 3N The console can be used for displaying the status of sprinkler or drencher fire extinguishing system via the indication units S2000 BI 01 The indication unit S2000 BI 01 is designed to display only one area of fire extinguishing The extinguishing area is represented by the pump station one or two duty pumps standby pump and jockey pump Create the partition for pump station and one partition for each pump when configuring the console Include Potok 3N device zones controlling the status of pump station into the pump station partition and zones controlling the status of pumps into the pump ones For the first duty pump use zone Ne 1 which controls turning on off and pump faults zone Ne 11 controls the power outages and zone Ne21 automatic control mode For the second duty pump use zones with the numbers 2 12 and 22 respectively for the standby pump use the numbers 3 13 23 and finally for jockey pump use the numbers 4 14 and 24 Depending on Potok 3N device configuration some pumps may be absent and the corresponding zones controlling such pumps might be displayed as Disconnected alarm loop status So don t create any partition for lacking pumps The pump station itself is controlled by zones number 30 39 with specific zones numbers being depended on
90. on of the accidents at device installation 2 1 10 Console first starting 2 2 Using console 2 2 1 Displaying viewing and printing device messages 2 2 2 Partition arming and disarming 2 2 2 1 Console controlling of partitions 2 2 2 2 Partition control at S2000 K keyboards 2 2 2 3 Touch Memory and Proximity card partition control 2 2 3 Device control functions 2 2 3 1 Arming disarming control of device alarm loops 2 2 3 2 Device alarm reseting 2 2 3 3 Manual external device outputs control 2 2 3 4 S2000 ASPT device control 32 33 33 34 34 34 34 35 37 37 39 39 39 39 41 41 42 S2000M 2 2 3 5 Request for loop state 2 2 3 6 Alarm loop resistance measurement 2 2 3 7 Console date and time setting 2 2 3 8 Printing event buffer 2 2 3 9 S2000 IT phone communicator message buffer cleaning 2 2 3 10 Alarm message indication reset 2 2 4 Device and console programming functions 2 2 4 1 Date and time settings and clock correction 2 2 4 2 RS 485 device address changing 2 2 4 3 2 wire devices adresses changing and programming 2 2 4 4 Console extra settings 2 2 4 5 Password management 2 2 4 6 Console address setting in prorgamming mode 2 2 4 7 Console address setting in personal computer work mode 2 2 4 8 Console RS 232 interface operative mode settings 2 2 4 9 The ring RS 485 interface operative mode settings 2 2 4 10 Console entering into programming mode 2 2 5 Reset settings to default values 2 2 6
91. onds and data day month They can also include information about message source device address loop number reader or relay number and text partition description number and user text description Event buffer keep up to 1023 last events Buffer is ring i e last message is saved instead the oldest Console can print bath all current messages but also message categories There are following categories FIRES ALARMS FAULTS ARM DISARM LOOP ARM DISARM ACCESS RELAY SYSTEM INFO AUXILIARY Full event list presents shown in appendix D Printer prints messages immediately at receiving If console worked some time without printer then after printer connection saved in buffer events will be printed automatically Also there is a command for printing whole event buffer 1 2 15 Console allows setting displaying and printing events from device alarm loops and addres notificators Obligatory condition these loops should be saved in console database It has to be set message name console message receiving sound signal alarm level and has message to the one of the categories Message title is an arbitrary text line with length up to 16 symbols Sound signal is settled by selection from list of standard signals Alarm level determines message displaying priority on the LED console at receiving different alarm messages Through message category one can set save the message in the console buffer d
92. ort circuit segments of RS 485 interface 0 V circuits of isolate segments do not connected Also repeaters can be used to build star configuration Figure 4 Attention Each console connected through RS 485 interface device must have unique network address Network address saved in the nonvolatile device memory it is default value is 127 For each connected device unique address must be set To do this follow sequence of actions shown below a connect one device to the console b when panel detected device set personal network address by address set command item 2 2 4 2 Address values from 1 to 127 are valid 16 S2000M MAINTENANCE GUIDE c connect next device and by identical way set another network address different from first one d by this way connect the rest devices setting unique addresses below 3000 m PKP PKU console C2000M PKP alarm panel IP IP UPS 12V 24V Figure 2 Device RS 485 interface connection circuit Below 2000 m Below 2000 m Below 2000 m PKU console S2000M IP power supplier PKP alarm panel R matching resistance 620 Ohm P interface repeater Figure 3 Extend line length with the help of RS 485 interface repeaters 17 BOL D FIRE AND ALARM CONSOLE below 2000 m Receiving control device Receiving control I Receiving control device device N 2 ru 2 Receiving Re
93. oximity cards can be read by the console only if they are not writen in S2000 4 or S2000 2 device configuration Deleting password Enter in programming menu press button PRG ENTER CODE Type engineer password Select SETTINGS menu item by 4 and ENT keys or press hot key 5 Select USER CODES menu item by gt 4 and ENT keys or press hot key 2 5 SETTINGS USER CODES Enter password number from 1 to 2047 or select valid value by 4 keys and press ENT DELETE Select DELETE for deleting password USER NUMBER _ Un 0 S2000M MAINTENANCE GUIDE Changing own password by user When in system operating users can change own password values from S2000M console This function is available if parameter USER CODE PRG has value see item 2 2 4 4 By default user can t change his password User password change mechanism is described below Press button PRG ENTER CODE Type password to be changed Following by prompt CHANGE CODE press ENT to gt 9 T CHANGE COE continue password changing or CLR to canceling operation Type new password value NEW CODE CONFIRM Type password again If signal Error has sounded it indicates that first typed password differs from the second typed password 2 2 4 6 Console address setting in prorgamming mode This function chang
94. pen circuit failure of relay output load circuit has been detected RELAY TRBL OPEN 7 The short circuit failure of relay output load circuit has been detected RELAY TRBL SHORT 7 62 S2000M MAINTENANCE GUIDE Event description Displayed event name Category The relay output load circuit has been restored RELAY RESTORE 7 Addressable relay module fails to communicate to S2000 KDL or S2000 ASPT devices RELAY DISCONNECT 7 Addressable relay module restored communication with S2000 KDL or S2000 ASPT devices Rene ONE K Automatic fire extinguishing system was successfully started RELAY START ACK 7 exploder or valve circuit has broken Automatic fire extinguishing system was not successfully started exploder or valve circuit has no broken after launching pulse being RELAY START NACK 7 given The partition has been armed PART ARMED 4 The partition has been disarmed PART DISARMED 4 The user is arming the partition PART ARMING 4 The user is disarming the partition PART DISARMING 4 The user has entered arming disarming code USER S CODE ENTR 4 A person was passed into the access zone PASSED 6 Access was denied due to the illegal code ILLEGAL CODE 6 Access was granted ACCESS GRANTED 6 Access was denied due to the low code authority level ACCESS DENIED 6 Access is prohibited ACCESS CLOSED 6 Access control is deactivated ACCESS FREE MODE 6 Access control is activ
95. r Key card code should be read and showed in Code field S2000 KS or S2000 K keyboard PIN code should consisit from 4 digits Such password can be programmed without pprog exe from console S2000M Password programming is described in the item 2 2 4 5 To set device partition control privilegies select Controlling abilities tab of pprog exe program and drag reguired partition from Partition window to the corresponding device in the Controlling abilities window In such a way each device is to be assigned with the list of partitions available for controlling Note that TM or Proximity authority level should have controlling privilegies only for single partition 2 1 7 4 Setting control by system relay outputs Console allows organizing up to 255 system outputs open collector or relay which controlled according to the given algorithm on the basis of the partition states Because S2000 console control by system outputs let call such control external to differ from internal control when receive check device control by their outputs itself To customize outputs it is necessary select physical relays device address and relay number in device which will be used for system control Determine partitions that controlled by relay s state connect relay and partition Determine relay state dependence from state of connected partitions select control program These settings are run by p
96. r is red 1 2 21 Console sound signals are shown in the table 6 Table 1 Indicator READY green Work with printer Any On O Norm O Work with computer No connection with computer through RS 232 Blinks with frequency 1 Hz n n Computer does not poll devices Off On if computer sends data to the device else off Programming mode Mode PI Computer polls devices SECURITY SYSTEMS Norm FIRE AND ALARM CONSOLE Table 2 Indicator ALARM red Off SILENT ALARM Blink with frequency 2 HZ ALARM Blink with frequency 1 HZ INTRUSION ALARM State Norm Blink with frequency 4 HZ Table 3 Indicator FIRE red Indication Off FIRE Blink with frequency 2 HZ ATTENTION Norm On for Ya c frequency 1 HZ Table 4 Indicator TROUBLE red NOT ARMING Blink with frequency 1 HZ LOOP OPEN CIRCUIT LOOP SHORT CIRCUIT CONFIGURATION ERROR OPEN RELAY OUTPUT RELAY OUTPUT SHORT CIRCUIT BATTERY FAILED AC POWER FAILED POWER FAILED Norm On for 1 8 c frequency 1 HZ Table 5 Indicator FAULT DISCONNECTED ALARM LOOP RELAY DISCONNECTED 2 WIRE LINE SHORT CIRCUIT 2 WIRE LINE TROUBLE ENCLOSURE TAMPERING Event or state Norm Blink with frequency 2 HZ Table 6 Inner sound notificator Content Notificator off Button pressed Short sound signal Notificator is off if alarm was on Successful operation Two short signals
97. rm loop is broken AUX ALARM Auxiliary alarm loop is OK is not broken AUX NORM The communication between the console and relay output has been lost with it status being unknown and the console controlling being disabled It is typically happens when 1 the communication between the console and relay unit S2000 KPB connected to it via RS 485 line has been lost 2 the communication between S2000 ASPT and relay unit S2000 KPB connected to it via RS 485 line has been lost 3 the communication between S2000 KDL device and its 2 wired S2000 SP2 relay unit has been lost RL DISCONN Open circuit failure of controlling relay output RL TRBL O Short circuit failure of controlling relay output RL TRBL S Alarm loop controlled fire equipment is operative NO TROUBLE 59 BOLID BOLD FIRE AND ALARM CONSOLE HIGH EMERGENCY LEVEL LOW EMERGENCY LEVEL emergency threshold Potok 3N HIGH LEVEL o of the water or pressure level Potok LV HIGH LOW LEVEL S of the water or pressure level Potok LV LOW NORMAL LEVEL ne Pressure or water level is within normal range LV NORMAL Potok 3N TEMPERATURE Temperature sensor fails for temperature zone of SENSOR FAULT S2000 KDL SPAR OR NEE HIGH The temperature is above temperature high T HIGH TEMPERATURE threshold for temperature zone of S2000 KDL LOW The temperature is under temperature low T LOW TEMPERATURE thre
98. rogram pprog exe when console configured Control program number is selected according Table 7 If output belongs to device that support extended output control for example S2000 SP1 version 1 20 or S2000 KPB switching timeout can be set For outputs with time restricted program time control should be set Control time and switching delay are given in the range from 0 to 8191 875 seconds with interval 1 8 seconds If control time equal to 8191 875 seconds then output will be switching on without time limitation Setting these parameters run by program pprog exe when console configured If device do not support extended relay control then their outputs will be switched without delay and switching time will be equal to the value of configuration parameter Control time this relay Control time parameter is set with the help of the console or program uprog exe Also for relay outputs of 2000 SP1 it is necessarily to set value of Control program of initial state parameter This parameter output state after switching on power of the device It should be 0 off or 1 on depending on console output program If output control by programs operated on switching on for example programs On On for a time Siren ASPT Control program of initial state parameter value have to be 0 off Output S2000 4 Signal 20P and Signal 20 series 02 device initial st
99. rt S2000 SP1 unit allow the console controlling by their relay outputs through RS 485 interface and is design to contact system relay outputs S2000 BI indication block is design for indication at built in LED indicators and sound indicator states of system partitions S2000 IT phone phone communicator is design to transmit console messages through phone lines in form of voice or pager messages and also ADEMCO ID Contact format messages 1 1 3 Console displays at liquid crystal display LCD messages about fires alarms faults arm disarm and other system events There is the opportunity of sound alarm message signaling Console can log device messages on printer with c sequential RS 232 interface for example EPSON LX 300 LX 300 Console keeps messages in nonvolatile event buffer Its content can be viewed on LCD Console may print buffer content on the printer Console may transmit messages to the S2000 K keyboards for displaying and to the phone informators for transmission through phone 1 1 4 Console has set of standard messages displayed on LED indicators and printed and also allows set non standard alarm loop message displaying Console allows one to control by arm disarm of any alarm loop of connected devices and also check alarm loop states Access to the functions is password protected 4 S2000M MAINTENANCE GUIDE 1 1 5 Console may logically group alarm loops in partitions Partition is a set of alarm loop
100. rtment in compliance with state standards and specifications and packed by NVP BOLID company Q C STAMP Name Date 55 BOLID FIRE AND ALARM CONSOLE Appendix A S2000M console dimensions 114 25 BOLID 4x 5 56 S2000M MAINTENANCE GUIDE Appendix B Zone status list Zone statuses are listed in priority decreasing order If different zones of one partition have various statuses the resulting status of the partition will be defined by the zone status of the highest priority For example if the zone statuses are Zone armed Disarmed Loop short circuit and Fire prealarm then the resulting partition status is Fire prealarm Fire extinguishing is in process the launching pulse EXTINGUISHING was given out and outflow of fire extinguishing EXTINGUISH agent has been detected EMERGENCY The launching pulse was not given out but outflow LAUNCHING of fire extinguishing agent has been detected EMERG ENGH LAUNCHING The pulse for fire extinguishing equipment LAUNCHING launching was given out The fire extinguishing equipment was not successfully launched the launching pulse was LAUNCH FAULT ren LNCH FAULT given out but outflow of fire extinguishing agent has not been detected i The condition for launching of fire extinguishing LAUN HE equipment has met and launching delay is being LNCH DELAY DELAY counted LAUN
101. rved DC power supply For additional price printer and computer connection cables are supplied Typical connection circuit is shown on the Figure 1 Powa S2000M Printer Device C2000M fire check and control console Device one of the Signal 20 Signal 20P S2000 4 S2000 KDL S2000 SP 1 S2000 K S2000 KS S2000 BI S2000 IT or S2000 2 Printer printing device with serial interface RS 232 e g Epson LX 300 or LX 300 1 printer connection cable Power supply DC power supply from 10 2 to 28 4 V current supply no more than 150 MA Figure 1 Typical maintenance connection S2000M console circuit Attention On the console board there is 5 pin auxiliary slot It is prohibited to set pin tampers or shortly connect the pins if console power is on At mounting fire alarm signal system console and other devices has to be customized First of all each device connected to console through RS 485 interface has to have unique network address Panel cannot poll devices if they have identical addresses Address values from 1 to 127 are valid See item 2 1 2 for details More over each device has set of configuration parameters which determine its work algorithm Changing values of the parameters devices work algorithms can be changed according system requirements item 2 1 3 Addresses for 15 BOLID FIRE AND ALARM CONSOLE devices which connected to 2 Wire addressable line of S
102. s S2000 BI indication blocks S2000 IT phone informators S2000 ASPT extinguish control devices checking start S2000 KPB units S2000 2 access control devices Devices and console are jointed in the system through RS 485 interface In the system console plays role of central controller which gathers information from connected devices and controls by arm disarm alarm loops of devices and by system outputs relay outputs or open collector outputs One can be only one console S2000M in the system Receive checking devices Signal 20 Signal 20 version 02 Signal 20P S2000 4 analyze the state of the alarm loop control by their outputs transmit to the console through RS 485 interface information about state of alarm loop and allow arm disarm alarm loop by console commands through RS 485 interface Controller S2000 KDL analyzes the state of addressable detectors and connected via 2 wire addressable communication line expanders transmits the status information to the console and allows to arm disarm them by console command Keyboard S2000 K is design for additional partition control points and word under console control It also allows displaying transmitted by keyboard messages on the liquid crystal indicator with alarm message sound indication LED S2000 KS keyboard is also designed for additional control points It can show up to 20 partitions on the LED indicators Signal sta
103. s devices connected to the 2 wire addressable communication line each device unique address address set has to be set Expanders S2000 AR1 and S2000 AR2 addresses can be set with the help of console or uprog exe program It is strongly recommended to program extender s addresses before mounting because when address is programmed controlled extender circuits is used Description of the extender address changing with the help of console is shown in the item 2 2 4 3 PC S2000M RS 485 To devices COM DB9M PC personal computer S2000M check and control console S2000M 1 connection cable S2000 to the personal computer Figure 5 S2000 console connection circuit It is configured by personal computer through RS 232 interface Also it is shown using it as RS 232 RS 485 interface converter 2 1 5 Printer connection to console or ARM 82000 If console is used with printer the last one has to be set for next parameters according instruction Description Setting name in LX 300 Value in LX 300 Interface type I F mode Serial or Auto Transmission type Baud rate 1200 BPS Number bit Parity check Parity None Code page Character table PC 866 Auto line feed Auto line feed Off On the site www bolid ru one can download instruction for configuring S2000M consoles for working with printer Epson LX300 Epson LX300 and Epson LX300 printers have built in customizin
104. s value by 4 keys and press ENT ADDRESS 2 2 3 3 Manual external device outputs control Manual relay or open collector type outputs controlling given by sertain programs are realized as follows ENTER CODE Type password Select MANUAL CONTROL menu item by gt 4 and ENT keys or press hot key 4 Select RELAY menu item by gt 4 and ENT keys or press hot key 1 for quick transition gt 4 MANUAL CONTROL Enter device address valid value from 1 to 127 or select valid eee address value by and keys and press ENT Enter relay number valid value from 1 to 127 or select valid Ree address value by and keys and press ENT Enter relay command number valid value from 1 to 127 or select valid address value by gt and 4 keys and press ENT Presented control programs 0 return initial state l ON 2 OFF 3 ON for a time given when the device relay output being configured z gt lt COMMAND _ 41 SECURITY SYSTEMS FIRE AND ALARM CONSOLE 4 OFF for a time given when the device relay output being configured 5 blink 6 blink 7 blink Initial state is OFF 8 blink Initial state is ON Attention The intrusion and fire alarm panelss ignore outputs control commands from the console if they control
105. shold for temperature zone of S2000 KDL NORMAL The temperature is within preset range for T NORM TEMPERATURE temperature zone of S2000 KDL NORMAL ee OUTPUT Output circuit being controlled is normal operative RELAY NORM NORMAL POWER The device power supply is OK POWER NORM NORMAL AC AC power supply 220 V is OK AC NORM NORMAL BACKUP POWER Backup power supply e g storage battery is OK BAT NORM NORMAL ZONE Zone is in a fault free state NO TROUBLE The console doesn t know zone status and is going to request it from the device The pressure or water level has exceeded the emergency threshold Potok 3N LV TOO HI The pressure or water level is below the LV TOO LOW This state is possible for few seconds after console INITIALIZING power supply turning on unless the console detects REQUEST all system devices and requests its states The more devices and controlling zones being integrated into a system the more request response process is lasted 60 S2000M MAINTENANCE GUIDE Appendix C The list of messages being displayed Event description Displayed event name Category The condition for launching of fire extinguishing equipment was met LAUNCHING DELAY 4 and the launching delay is being counted The pulse for fire extinguishing equipment launching was given out LAUNCHING Fire extinguishing is in process the launching pulse was given out EXTINGUISHING and outflo
106. t is just enough to increase polling latency time In more complicated cases it is need to increase device delay before reply and console pauses if equipment switches from receive to transmission too long It is need to keep in mind that if pauses values increase then device polling time decrease Console connection parameters are customized by pprog exe program device connection parameters by uprog exe program Programs pprog exe and uprog exe are free and can be downloaded at site www bolid ru 2 1 3 Setting device configuration parameters One can configure such device parameters as alarm loop type transmission delays from one operating mode to another arm delay or fire delay alarm loop connection with output keys work algorithm control program of output keys and others Configuration parameter values saved in the device nonvolatile memory Program and control device configuration can be done 18 S2000M MAINTENANCE GUIDE with the help of personal computer and utility uprog exe To connect devices to personal computer RS 232 RS 485 interface converter needed PI PI GR or S2000 PI S2000M console can be used as interface converter transmitted in program mode Connection circuit of devices in programming at personal computer with S2000M using shown on Figure 5 2 1 4 Address setting of addressable expanders If S2000 KDL controller used in the system with addres
107. the outputs itself see intrusion and fire alarm panelss maintenance guides 2 2 3 4 S2000 ASPT device control The console allows users to select launching mode for S2000 ASPT device controlling fire extinguishing equipment launch fire extinguishing equipment and cancel launching Selecting fire extinguishing mode ENTER CODE _ Type password Select MANUAL CONTROL menu item by gt gt and ENT keys or press hot key 4 Select EXTINGUISH menu item by 4 and ENT keys or press hot key 2 Select LAUNCH MODE menu item by P 4 and ENT keys or press hot key 1 Enter S2000 ASPT address valid value from 1 to 127 or select valid address value by P 4 key and press ENT 4 MANUAL CONTROL 42 EXTINGUISH LAUNCH MODE ADDRESS Console displays current launching mode In this example S2000 ASPT controls the fire extinguishing equipment in manual mode Press ENT to select launching mode Select launching mode AUTO or MANUAL by gt and 4 keys then press ENT MODE MANUAL AUTO If command has succeeded panel displays new launching mode MODE AUT 9 ue In this example S2000 ASPT was switched to AUTO mode Extinguish equipment manual launch ENTER CODE _ TYDE Passwords Select MANUAL CONTROL menu item by gt 4 and v4 MANUAL CONTR
108. the protected 32 S2000M MAINTENANCE GUIDE premises were opening AUTOMATIC MODE indicator demonstrates the current launching mode is auto launching mode on or not EXTINGUISHING indicator demonstrates status of launching that is no launching launching delay launching or launching failure S2000 PT devices have some buttons for automatic mode controlling turn on off auto extinguishing mode and for remote launching or canceling of auto extinguishing equipment launch S2000 PT device is supplied by input for Touch Memory reader with Touch Memory keys being used for getting access control to extinguishing area controlling by means of buttons Touch Memory keys have to be recorded into the console configuration with authority level allowing extinguishing area controlling with the corresponding rights If the user has no rights the controlling by means of buttons is impossible S2000 PT may be supplied with inner password for extinguishing area controlling without Touch Memory key identification It can be used when S2000 PT unit is located in secured place The password PIN code can be recorded to S2000 PT device by means of uprog exe program This password with authority level allowing extinguishing area controlling has to be recorded to S2000M console The console allows controlling the additional relay outputs such as annunciators common for several areas or common extinguishing installation Refer to the 2 1 7 4 secti
109. time and date partition number event categories Connection of several clients operational places working with event log Connection is made by TCP IP protocol Printing event log and export in the HTML format Program can work periodically to read messages from S2000 console It is possible S2000 has buffer for 1023 events Connection console to personal computer with ARM S2000 is shown on the Figure 5 In program ARM S2000 S2000 1 2x source message and address should be set By perforce console address can be changed see item 2 2 4 7 Attention For work with S2000M consoles of version 1 20 ARM S2000 program must be version 1 06 or above 2 1 6 Using the console for ARM Orion redundancy S2000M console can be used in systems running ARM Orion for stand by controlling when PC fails It is very important with the aim of surviving and robustness for fire alarm and fire auto extinguishing systems There are two approaches or modes to build the backup controlling with the help of S2000M console each heaving some conveniences and disadvantages The first backup mode named S2000 PC is to make ARM Orion monitors all devices and registers states of them with S2000M console being aside If the computer has failed the console automatically connect the devices and take over the control When recovering the computer assume the control again This backup mode is
110. tton CLR Console exits from control mode automatically after 2 min of stopping work with console keyboard The most important of control functions are loop arm and disarm arming disarming of single loop group of loops and all device loops restore from alarms and viewing zone states User with device control privileges can control any device or zone in the system Also console has some other functions viewing of loop resistance temperatures levels of smoke content and other values being measured by the alarm panel manual control by alarm panel s outputs relays and S2000 ASPT devices time and date changing 2 2 3 1 Arming disarming control of device alarm loops Console allows arming and disarming device zones A command of individual group or common arming and disarming can be given to any connected device The single loop arming disarming command is designated for the given loop of the given device The group 39 BOL D SECURITY SYSTEMS FIRE AND ALARM CONSOLE arming disarming command is designated for all given device loops with group arming attribute The common arming disarming command is designated for all given device loops Single loop arming ENTER CODE _ 1 ARM 11 ARM LOOP ADDRESS ENTER LOOP _ Group arming 1 ARM 12 ARM GROUP ADDRESS Common arming 1 ARM 13 ARM ALL ADDRESS Single loop disarming ENTER CODE 2 DISARM 21 DISARM LOOP ADDRESS ENTER LOOP
111. vices and address expanders set change and remove user passwords change own password setup and change console configuration for work with the partitions and relay outputs at personal computer using program pprog exe ver 2 04 This password has no device and partition control rights Engineer password can has from 1 up 8 digits Default value is lt 123456 gt Change it before starting device operation Console allows reset the password in default value if it was forgotten User passwords can have numbers from 2 to 2047 and designed for arming disarming control PIN codes and Touch Memory keys and Proximity cards can be used as password PIN code is digit code input from the keyboard Maximal PIN default length is 4 digits but can be changed in range from 1 to 8 digits Touch Memory key and Proximity cards control is made by readers connected to the S2000 4 S2000 2 Signal 20P SMD and S2000 KDL devices Each user password has access level According to level password can have partition control rights or device control rights Access levels for partition control are determined accessible partitions and permitted for control actions partition arming disarming It can be set up to 252 access levels numbers from 1 to 252 Partition control rights are described in the item Note Access level can have control rights for any partition number up to 511 and partition groups up to 128 but up to 8 access l
112. w of fire extinguishing agent has been detected The fire extinguishing equipment was not successfully launched the LAUNCH FAULT launching pulse was given out but outflow of fire extinguishing agent has not been detected extinguishing agent has been detected The launching of fire extinguishing equipment was blocked up e g due to the door opening into the protected area The launching of fire extinguishing equipment was canceled e g LAUNCH CANCEL due to the command Cancel extinguish given from console or to the pressing RESET key of S2000 ASPT The fire extinguishing equipment was launched in emergency mode EMERGENCY LAUNCH the launching pulse was not given out but outflow of fire 1 Fire alarm FIRE ALARM 1 Fire signal has been received and fire alarm is probable FIRE PREALARM 1 Intrusion alarm INTRUSION ALARM 2 Silent zone alarm SILENT ALARM 2 Entry zone alarm ENTRY ALARM 2 Open circuit failure in the alarm loop LOOP TRBL OPEN 3 Short circuit in the alarm loop LOOP TRBL SHORT 3 Alarm loop has restored after any failure LOOP TRBL RST 4 Extinguishing equipment faults FIRE TROUBLE 3 Extinguishing equipment is in normal state FIRE TRBL RST 3 Zone configuration parameter error ZONE CONFIG ERR 3 Addressable detector or expander disconnection from S2000 KDL DISCONNECTED 3 Arming has failed due to the activated status of detector ARM FAILED 4 Zone fire alarm h
113. word and is available for user having engineer password password number 1 To get access to programming functions press key PRG and input engineer password Enter from 1 to 8 password digits and press key ENT If password is orrect console displays message PROGRAMMING and grants access to functions To return from programming mode into time displaying mode use button CLR Panel automatically exits from programming mode after 2 min if there were no key pressimgs during this time Console provides such functions as time setting and clock correction setting console date changing device network address programming and changing addresses of 2 wire devices setting console parameters password setting personal computer programming fe 2 2 4 1 Date and time settings and clock correction Time setting Enter the programming menu press button PRG ENTER CODE Type engineer password Select CLOCK SETUP menu item by 4 and ENT keys or press hot key 1 Select SET TIME menu item by 4 and ENT keys or press hot key 1 LCD displays current time in format HH MM hours and minutes Input new time 1 CLOCK SETUP SET TIME TIME HH MM Clock correction Clock correction allows time correcting for clock accuracy adjustment The correction value can be varied in range 120 120 seconds and will be added to the current time during every day
114. xt description of partition and loop If partition has not text description when key 2 pressed panel show partition number device address and alarm loop number When keys 3 pressed console shows user name if text user password description is not given console show its database number when key 3 pressed Pressing key 9 Message number in console buffer can be shown The last message has number 1 the oldest 1023 To print event log console output one message in the line Next information is printed mara n event number format is identical LCD message format full message name message source device address number of alarm loop reader or relay partition number name and text description user text description name Data prints like table After each 50 messages table heading is printing It has the following view Date Time Event Device Part Description User The displaying and printering information depends on event type Zone messages such as alarms fires arming disarming faults and so on have the following format e g intrusion alarm On LCD INTRUSION ALARM Corridor 1 floor where Corridor 1 floor is partition name Console shows message data and time if button 0 pressed 20 12 17 41 11 where 20 12 is the day and month 20 December 17 41 11 is the time 17 hours 41 minutes 11 seconds At button 1 pressure message name with source message is displayed
115. y connected to the computer via RS 232 interface with the the devices being connected to the console through RS 485 interface The console monitors all the devices and gets their states with the computer polling the concole or consoles and getting the device operative information Both the console and the computer can control the relay outputs and indication units If the computer fails the console will retain to execute the controlling functions This reserving mode has the following advantages 1 The devices are available for controlling by the console when the PC operates normally If the PC supplied with ARM Orion software failes the event messages are storied in the console buffer and can be readed after the computer restoring 2 Asaresult of absence of switching between the console and PC there is no switching delay 3 Delegating the console some controlling functions unloads the PC 21 SECURITY SYSTEMS Disconnected console and relay switching Passive console and automatic switching 3 Active console FIRE AND ALARM CONSOLE To realize the second reservation mode it is necessary to assign the console with the address and set the RS 232 operating mode to the value S2000 amp PC Refer to the section 2 2 4 8 for more details The following Table 9 summarizes the essentials of all available backup techniques Table 9 Available backup techniques Technique description The monitoring and controlling are