Technical Manual - Honeywell Process Solutions

image

Contents

1. 850 mbar and when the tank is empty it is possible to avoid disconnection of the sensor and to connect the pressure generator to the Inert Gas connection using a 1 8 coupling then proceed to calibration by vacuum generation 3 3 CT700 CT701 or CT702 is the electric pressure level transmitter CT700 R uses a remote electronic module Refer to the Installation and Maintenance Manual CB322409 or CB322535 for High Temperature model Doc No MT5023E Revision 4 ENG Test amp Calibration Kit Level Pressure Transmitter Technical 5 Honeywell To check the calibration Make sure to be allowed to proceed in compliance with current rules regarding hazardous area Switch off the CT700 power supply Disconnect the 4 20 mA output wires from the CT700 electronic module terminals or from the remote electronic module for CT700 R Depending of the CT700 installation configuration connect the pneumatic output of the calibrator to the test pressure inlet on flange with provided couplings sealed with PTFE ribbon or to the pressure inlet of the CT700 after disassembly using 4 x 6 mm tube with 3 8 coupling sealed with PTFE ribbon Connect the electrical input of the calibrator to the CT700 electronic module terminals or to the remote electronic module for CT 700 R use loop power mode Proceed to the calibration by pressure generation from the calibrator while reading the current calibration point inside the calibrator s range 3 4
2. PL3700 PL3700 PL3700 is the electric pressure level transmitter Refer to the Installation and Maintenance Manual MM5090 To check the calibration Make sure to be allowed to proceed in compliance with current rules regarding hazardous area Switch off the PL3700 power supply Disconnect the 4 20 mA output wires from the PL3700 remote electronic module terminals Connect the pneumatic output of the calibrator using 4 x 6 mm tube to the test pressure inlet on flange with provided couplings sealed with PTFE ribbon or to the pressure inlet of the PL3700 screwed model using the dedicated mechanical interface T35629 by taking care with the gasket for PL3700 C do not mount the adaptation reduction 49 5mm Connect the electrical input of the calibrator to the PL3700 remote electronic module terminals use loop power mode e Proceed to the calibration by pressure generation from the calibrator while reading the current value in mA If the transmitter s pressure range is higher than 2200 mbar select another calibration point inside the calibrator s range 3 5 T901P T901 PXX is the temperature pressure transmitter used in TA840 and EMx40 Radar gauging system for measurement of cargo s temperature and inert gas pressure For that last function it includes a pressure module Refer to the Manual MM5016 To check the calibration of the pressure module Make sure to be allowed to proceed in compliance with current rules regarding
3. 4 2 Personal Notes Doc No MT5023E Revision 4 ENG Test amp Calibration Kit Level Pressure Transmitter Technical 8 Honeywell Marine SAS 9 Rue Isaac Newton 18000 Bourges France Tel 33 0 2 48 23 79 01 Fax 33 0 2 48 23 79 03 E mail contact marine honeywell com www honeywellprocess com MT5023E rev04 ENG February 2014 2014 Honeywell International Inc Honeywell
4. 4mm male hexagonal spanner 3 16 male hexagonal spanner 1 4 male hexagonal spanner 2 5x 75 mm screwdriver 3 5 x 100 mm screwdriver The User s Manual of the pressure calibrator model 718 30G The present MT5023E Manual The pressure calibrator model 718 30G is provided with its initial calibration certificate Further periodic calibrations are to be carried out in compliance with the User s Quality Assurance program Refer to the calibrator own User Manual in order to look at the technical specifications and to operate The pneumatic output is to be equipped with a provided coupling 1 8 for 4 x 6 mm tube sealed with PTFE ribbon Doc No MT5023E Revision 4 ENG Test amp Calibration Kit Level Pressure Transmitter Technical 4 Honeywell 3 OPERATION 3 1 100 CT150 CT180 CT100M is the pneumatic bubbling modulator CT150 and CT180 are the level indicator gathering the CT100M modulator with a mechanical pointer manometer The flow meter allows controlling the bubbling flow while the calibrator allows to check the efficiency and leakproofness of the over pressure protection valve and to check the calibration Refer to the Technical Manual NT5004 for CT100M Technical Manual CT150 Installation Operating and Maintenance Manual NT5001 for CT180 To check the calibration e Disconnect the manometer s pneumatic 4 x 6 mm tube from the pneumatic module outlet e Connect the pneumatic output of the cali
5. Test amp Calibration Kit Honeywel a ea For Maintenance and Servicing of Electric and Electro pneumatic Level Pressure Transmitter Technical Manual SAS au Capital de 2 158 244 444 871 933 R C S Bourges APE 2651B Headquarter 9 rue Isaac Newton 18000 Bourges France Test amp Calibration Kit Technical Manual For Maintenance and Servicing of Electric and Electro pneumatic Level Pressure Transmitter 1 Edition Released February 2014 Honeywell TABLE OF CONTENTS INTRODUCTION ec KIT DESCRIPTION e c V er OPERATION ep UR CT1 80 cm 32 0 eee ee eee eee er ee es mas ad eee 39 4 PL3700 PL3700 ere eer ener eee eer ee entre errr gj rc ee 3 6 Temperature transmitter INFORMA TION 4 1 Reference of Honeywell Marine Customer 4 2 Personal tree tire rire rire trier rre rrre trier rre trier EEEE EEEren Honeywell 1 INTRODUCTION Specially designed for the maintenance servicing and calibration of Honeywell Marine s pneumatic electro pneumatic and electric transmitters th
6. brator to the manometer input using 4 x 6 mm tube with dual coupling e Proceed to the calibration by pressure generation from the calibrator If the transmitter s pressure range is higher than 2200 mbar select another calibration point inside the calibrator s range 3 2 801 CT801LB S CT801 is the electro pneumatic bubbling level transmitter The flow meter allows controlling the bubbling flow while the calibrator allows to check the efficiency and leakproofness of the over pressure protection and safety valves and to check the calibration Refer to the Maintenance Manual CB322382 for CT801 or MM5019 for CT801LB S To check the calibration e Make sure to be allowed to proceed in compliance with current rules regarding hazardous area e Switch off the CT801 power supply e Disconnect the 4 20 mA output wires from the CT801 electronic module terminals and the sensor s pneumatic tubes from the pneumatic module outlets e Connect the pneumatic output of the calibrator to the high pressure input of the CT801 s sensor using 4 x 6 mm tube with dual coupling Connect the electrical input of the calibrator to the CT801 electronic module terminals use loop power mode e Proceed to the calibration by pressure generation from the calibrator while reading the current value in mA If the transmitter s pressure range is higher than 2200 mbar select another calibration point inside the calibrator s range When the range is lower than
7. hazardous area Switch off the 8405 or 840 power supply Disassemble the pressure sensor from the flange unscrewing the two screws screw the sensor on the dedicated mechanical interface by taking care with the gasket Connect the pneumatic output of the calibrator using 4 x 6 mm tube to the interface pressure inlet Switch on the 8405 or 840 power supply Proceed to the calibration by pressure generation from the calibrator while reading the pressure value on the system Monitoring Doc No MT5023E Revision 4 ENG Test amp Calibration Kit Level Pressure Transmitter Technical 6 Honeywell 3 6 Temperature transmitter line The 100 ohms 3 wires resistance allows to check a temperature transmitter line connect the resistance instead of the temperature transmitter output wires and check that the reading is 0 0 4 C If different the line should be restored 4 INFORMATION 4 1 Reference of Honeywell Marine Customer Service For any request or help you can contact Honeywell Marine customer s services at the following references Tel 33 0 2 48 23 79 28 Fax 33 0 2 48 23 79 02 E mail service marine honeywell com For sending equipment to check or to repair Honeywell Marine SAS Customer s department 9 rue Isaac Newton 18000 BOURGES FRANCE Doc No MT5023E Revision 4 ENG Test amp Calibration Kit Level Pressure Transmitter Technical 7 Honeywell
8. is Test amp Calibration kit is provided with all necessary accessories and instruments insuring quick and efficient operation 2 KIT DESCRIPTION The Test amp Calibration kit is contained in a black polypropylene suitcase with shoulder strap It is composed of e pressure calibrator model 718 306 including pressure generation range 850 to 2200 mbar relative with integrated pump together with an electric current measurement with 24 Vdc loop power A set of spare batteries for above A flow meter for bubbling transmitters with coupling for 4 x 6 mm tube e A set of pneumatic couplings and tube 2couplings 1 4 for 4 x 6 mm tube couplings 1 8 for 4 x 6 mm tube 1 coupling 3 8 with coupling for 4 x 6 mm tube 2 dual coupling for 4 x 6 mm tube 1Te shape coupling for 4 x 6 mm tube meter 4 x 6 mm transparent plastic tube 0 5 meter 4 x 6 mm soft transparent plastic tube e An interface tool for PL3700 PL3700 C level pressure transmitter calibration except flange welded models composed of nut with coupling for 4 x 6 mm tube and screw and adaptation reduction ref 35629 e Aninterface tool for the pressure sensor of T901P transmitter with coupling for 4 x 6 mm tube ref T29195 e An equipped resistance of 100 ohms wires for temperature transmitter s line test ref T29235 e A set of specialized tools for above transmitters 7 mm spanner mixt type mm male hexagonal spanner