Data Sheet DB EN AXL AI 8 (-ME)
Contents
1. 12 Significant values in various formats 12 1 Significant values in IB IL format Input data OV 10V zx10V 0V 5V 5V 0 mA 20 MA 20 mA 4 mA 20 mA hex dec SB SB SB SB mA mA mA 8001 Overrange gt 10 837 gt 10 837 gt 5 419 gt 45 419 gt 421 6747 gt 421 6747 gt 421 3397 7FOO 32512 110 837 110 837 15 419 15 419 121 6747 421 6747 21 3397 7530 30000 10 0 10 0 5 0 5 0 20 0 20 0 20 0 0001 1 333 33 UV 333 33 uV 166 67 uV 166 67 uV 40 6667 pA 0 6667 pA 4 0005333 0000 O lt 0 0 lt 0 0 lt 0 0 4 0 43 2 FFFF 1 333 33 uV 166 67 uV 0 6667 pA 8ADO 30000 10 0 5 0 20 0 8100 32512 10 837 5 419 21 6747 8080 Underrange 10 837 5 419 21 6747 8002 Open circuit lt 3 2 The maximum measured value is 7FOOhe Depending on the format the minimum measured value is eit her 0000hex or 8100hex 122 Significant values in S7 compatible format Input data OV 10V zx10V 0V 5V 5V 0 mA 20 MA 20 mA 4 mA 20 mA hex dec SB SB SB SB mA mA mA 7FFF Overrange gt 11 759 gt 11 759 45 879 gt 45 879 gt 423 5157 gt 423 5157 422 8142 7EFF 32511 11 759 11 759 5 879 5 879 23 5157 423 5157 22 8142 6C00 27648 10 0 10 0 5 0 5 0 20 0 20 0 20 0 0001 1 361 69 uV 361 69 uV 180 85 uV 180 85 uV 0 7234 pA 0 7234 pA 4 0005787 0000 O lt 0 0 lt 0 0 lt 0 0 4 0 FFFF 1
2. 001944 ResetDiag Write Subindex Data type Length in Meaning Contents bytes 0 Unsigned 8 1 Reset diagnostics OOhex No action O2nex Deletes and acknowledges all pen ding malfunctions that not been read out O6nex Deletes and acknowledges the en tire diagnostics and allows no further diagnostic messages Other Reserved 14 4 Objects for process data management Index Object name Object Data type A L Rights Assignment hex code 0025 PDIN Var Octet string 1 16 R IN Process Data 0026 PDOUT Var Octet string 1 16 R OUT process data not applicable IN process data 0025hex PDIN You can read the IN process data of the module with this ob ject 0025hex PDIN Read Subindex Data type Length in Meaning Contents bytes 0 Octet string 16 IN Process Data The structure corresponds to the representation in the Process data section PHOENIX CONTACT 16 AXL AI 8 ME 15 Application objects Index Object name Object Data type A L Rights Assignment hex code 0080 _ ParaTable Array Unsigned 16 10 10 2 R W Parameter table 0082 Measured Value Array Octet string 8 8 6 R Measured values in the extended float Float format 15 4 Parameter table 0080 ParaTable Parameterize the module using this object The parameterization is permanently stored on the module After resetting the module works with the last permanently works with the d
3. 14 mA types Measured value 14 mA Abbreviation Meaning S7 compatible format A Numberat elemente L Length of the elements Resolution 20 mA 4 mA 27648 0 0005787 R Read Measured value PD IW x 0 0005787 mA 4 mA C Write Example 1 PD IW 6CO0hex 27648 ge Value x resolution 27648 x 0 0005787 mA 16 mA 4mA 16mA 4mA 20 mA Measured value 20 mA Example 2 PD IW F940nex gt FFFFrex F940nex 1 1728 dec Value x resolution 1728 x 0 0005787 mA 1 mA 4mA 1mA 4mA 3mA Measured value 3mA PHOENIX CONTACT 12 AXL Al 8 ME 14 a Standard objects Please refer to the basic profile for comprehen sive information 14 4 Objects for identification device rating plate Index Object name Object Data type A L Rights Meaning Contents hex code Manufacturer 0001 VendorName Var Visible String 1 16 R Manufacturer Phoenix Contact name 0002 VendorlD Var Visible String 1 7 R Manufacturer 00A045 identification 0003 VendorText Var Visible String 1 49 R Comment onthe Components and manufacturer systems for indus trial automation 0012 VendorURL Var Visible String 1 30 R URL of the manu http facturer www phoenixcon tact com Module special 0007 ProductName Var Visible String 1 12 R Product designa AXL Al 8 ME tion 0008 SerialNo Var Visible String 1 11 R Serial number XXXXXXXXXX E 9 12345123456 0009 ProductText
4. 361 69 uV 180 85 uV 0 7234 uA 3 9994 F940 1728 0 625 0 3125 1 25 3 0 9400 27648 10 0 5 0 20 0 8100 32512 11 759 5 879 23 5157 8000 Under lt 11 759 lt 5 879 lt 23 5157 lt 1 1852 range open circuit The maximum measured value is 7ZEFFhex Depending on the format the minimum measured value is eit her 0000pex or 8100hex PHOENIX CONTACT 11 AXL Al 8 ME 12 3 Calculation of the measured value from the pro 13 Parameter diagnostics and informa cess data input value tion PDI The following examples explain the calculation of the measu ER red value from the process data input value for the measuring Parameter and diagnostic data as well as other information is range 4 mA to 20 mA transmitted via the PDI channel PD IW Process data input word input data For information on PDI please refer to the IB IL format i UM EN AXL SYS PRO user manual Resolution 20 mA 4 mA 30000 0 0005333 Measured value PD EW x 0 0005333 mA 4 mA The standard and application objects stored inthe module are E described in the following section inis dia The following applies to all tables below jon 493F hex 18751 dec Please refer to the UM DE AXL SYS PRO User Manual orth ser Manual or the Value xresolution 18751 x0 000533 MA TORIA basic profile for an explanation of the object codes and data 4 mA 10 mA 4 mA
5. Bild 5 Passive pressure sensor at a differential current input 24 V O VA GND Bild 6 Differential voltage input with active 3 wire trans mitter 9 Connection notes Always connect the analog sensors using shielded twisted pair cables Unshielded cables may be out of the specified tolerances in environments with heavy noise Connect the cable shield to functional earth ground immedi ately when the cables enter the control cabinet If there is no closed control cabinet connect the shield to a shield bus For further information on shielding please re fer to the UM EN AXL SYS INST user manual PHOENIX CONTACT 8 AXL AI 8 ME 10 O00 O01 QUA O10 O11 O20 O21 E2 O30 O31 002 012 022 032 003 013 023 033 004 014 024 034 005 015 025 035 O06 O16 O26 036 007 017 027 037 Local status and diagnostic indica tors Bild 7 Local status and diagnostic indicators Designa Color Meaning State Description tion D Red Diagnostics of local bus communication yellow Power down OFF Device in power reset green Not connected Red flas Device operating but there is no connection to previous device hing Reset Red ON Application reset Device operating but there is still a connection to the previous de vice the application is rese
6. The drift values refer to the relevant measuring range final va lue Tolerances influenced by electromagnetic interfe rence Current Voltage Electromagnetic EN 61000 4 3 lt 1 0 lt 2 0 fields IEC 61000 4 3 Fast transients EN 61000 4 4 lt 1 0 lt 1 0 burst IEC 61000 4 4 Conducted interfe EN 61000 4 6 lt 40 5 lt 40 5 rence IEC 61000 4 6 Additional tolerances may occur due to the influence of high frequency electromagnetic interference caused by wireless transmission systems in the near vicinity The values speci fied refer to nominal operation in the event of direct interfe rence to components without additional shielding such as a steel cabinet etc The above mentioned tolerances can be reduced by provi ding further shielding measures for the I O module e g use of a shielded control box control cabinet etc PHOENIX CONTACT 6 AXL Al 8 ME 6 Internal circuit diagram Axio bus Microprocessor Optocoupler Power supply unit with electrical isolation Analog digital converter Multiplexer Input amplifier for current I or voltage U Reference voltage source Hardware monitoring 7 Terminal point assignment xil fl OD O00 001 GUA O10 O11 E1 020 021 E2 030 O31 ai 00101 OJOO a2 10 11 OO 20 21 002 003 0041 005 O06 007 012 013 014 015 016 017 022 023 024 025 026 027 032 033 034 035 036 037 02
7. Var Visible String 1 24 R Product text 8 analog input channels 000A OrderNumber Var Visible String 1 8 R 2688187 Order No 0037 DeviceType Var Octet string 1 8 R Module identifica O0 20 00 10 00 00 tion 00 AOhex 000B HardwareVersion Record Visible String 2 14 R Hardware version e g 2010 06 21 01 000C FirmwareVersion Record Visible String 2 16 R Firmware version e g 2010 06 21 V1 10 000D PCH version Record Visible String 2 24 R Parameter chan e g 2010 01 08 nel version V1 00 0006 ProductFamily Var Visible String 1 3 R Product family Axioline High speed I O system PHOENIX CONTACT 13 AXL Al 8 ME Index Object name Object Data type A L Rights Meaning Contents hex code Module general 0004 DeviceFamily Var Visible String 1 14 R Device family I O analog IN 000E CommProfile Var Visible String 1 4 R Communication 633 profile OOOF DeviceProfile Var Visible String 1 5 R Device profile 0010 0011 ProfileVersion Record Visible String 2 33 R Device profile ver 2009 10 22 sion Basic Profile V1 12 0013 DeviceDescFile Var Visible String 1 28 R File name ofthe AXL AI 8 FDCML device ME dtmvOO 1 00 description file xml 003A VersionCount Array Unsigned 16 4 2 R Version counter e g 0005 0000 0000 0000 0017 Language Record Visible String 2 14 R Language
8. ZBF 10 5 8 AXL UNPRINTED Type UM EN AXL SYS INST 53 6 mm 126 1 mm 51 6 mm Order No 2688064 2688187 Order No 2688129 2700518 0829579 0829580 Order No Pcs Pkt Pcs Pkt 5 1 25 50 Pcs Pkt The depth is valid when a TH 35 7 5 DIN rail is used according to EN 60715 Gray 204g 25 C 60 C 40 C 70 C 5 95 according to DIN EN 61 131 2 5 95 according to DIN EN 61131 2 PHOENIXCONTACT 3 AXL AI 8 ME General data Air pressure operation Air pressure storage transport Degree of protection Protection class Connection data Type of connection Conductor cross section solid Conductor cross section stranded Conductor cross section AWG Interface Axio bus Type of connection Transmission speed Communications power Communications power Upys Current consumption from Upys I O supply Supply of analog modules UA Maximum permissible voltage range Current consumption from UA Surge protection Protection against polarity reversal Transient protection Analog inputs Number of inputs Type of connection Connection method Current input signal Voltage input signal Resolution A D A D conversion time Limit frequency 3 dB Measured value representation Data formats Process data update Filtering Input filter Precision Transient protection of inputs differential inputs voltage Number of inputs Voltage input signal Inpu
9. downloaded at format acc to www phoenixcontact net download IEEE 754 2 Unsigned8 1 Status 3 Unsigned8 1 Unit code Structure of the float format according to IEEE 754 in the bit representation VEEE EEEE EMMM MMMM MMMM MMMM MMMM MMMM SB 1 sign bit 0 positive 1 negative E 8 bits exponent with offset 7Fhex M 23 bits mantissa Some example values for conversion from floating point to he xadecimal representation Floating point Hexadecimal representa tion 1 0 3F 80 00 00 10 0 41 20000 1 03965528 3F 85 136 1 0 BF 80 00 00 18
10. 03 o4 05 o6 07 OOJOOJOO 12 13 14 15 16 17 OOJOOJOO 22 23 24 25 26 27 OOJOOJOO O OJOO O 30 31 32 33 34 35 36 37 COTO OO CIC C Bild 2 Terminal point assignment Termi Color Assignment nal point Supply voltage input a1 a2 Red 24VDC Supply of analog modu UA les internally connected b1 b2 Blue GND Reference potential of the supply voltage inter nally connected Analog inputs 00 07 Orange U1 Positive voltage connec U8 tion for channels 1 8 10 17 Orange U1 U8 Negative voltage connec tion for channels 1 8 20 27 Orange 11 18 Positive current connec tion for channels 1 8 30 37 Orange l1 18 Negative current connec tion for channels 1 8 PHOENIXCONTACT 7 AXL AI 8 ME 8 Connection examples S m c Ds T a 1 Olli En N a ee lo Bild 3 Connection for voltage and current measure ment U1 U2 2 c ON s O N T om J T Bild 4 Connection of potentiometric position sensors The values of potentiometric position sensors can be acqui red with voltage measurement Supply the potentiometer via an external power supply unit U 10 V Ut u2 24V A GND
11. 4 Measured Value Float You can read the IN process data in Inline or S7 compatible format with the 00255 object The 00824 object is also available This object provides the measured value in the highest inter nal accuracy of the terminal in the float format Extended Float Format The Extended Float Format is a specially defined format It consists of the measured value in the float format a status and a unit code Status is necessary because the float format defines no pat terns providing information on the status of the numerical va lue Status corresponds to the LSB of the Inline diagnostic codes 0082hex Measured Value Float Read e g overrange Status 01 Inline diagnostic code Subindex Datatype X Lengthin Meaning 8001 4 If Status 0 the measured value is valid bytes 0 Array of Octet 8 6 Read all ele Unit code Code Strings ments Volt V 58 3Ahex 1 Octet string 6 Measured value Milliampere mA 39 27hex for channel 1 Status Code 8 Octet string 6 Measured value Measured value is valid OOhex for channel 8 Measured value is invalid Other channel 1 channel 8 measured value 16 Device descriptions lementi Datatype bi in Meaning The device is described in the FDCML files PC WORX or GSDML files S7 Hardware configurator The files can be 1 Float 32 4 Value in the float found at the bus coupler and can be
12. AXL AI 8 ME Axioline analog input module 8 inputs 2 wire connection method AUTOMATION 1 Description The module is designed for use within an Axioline station Itis used to acquire analog voltage and current signals Features Eightanalog bipolar input channels to connect either vol tage or current signals Connection of sensors in 2 wire technology Voltage ranges O V 10V 10 V O V 5V x5V Current ranges 0 mA 20 mA 4 mA 20 mA x20 mA Device type label stored Status and diagnostic indicators A This data sheet is only valid in association with the UM EN AXL SYS INST user manual DOGD OO GD GD OGD 0 OOD cmi OCDE INSPIRING INNOVATIONS AXL AI 8 ME Oo ON Oa FW nm eN EO X lE N O 13 14 Table of contents Description a ieper riisiin orian iniiao aAA EEA AAEE AAE EES KETEK EEE ASEAK EAE AA RAIEK a EEK ENNS 1 Table of contents ict teen iet aa e a edt E ce Ub eel e odds 2 Ordenmj dald cases senem ie emos ucc d Neg en o Mc IL AU 3 Technicaldatau ote E N E E A d ceu 3 Tolerance data ien ee Irc a a deri E S 6 internal CIRCUIT diagram E 7 Terminal point ASSIQMINIGN iscsi cess teehee eode ern t ori docent t eme ted ta aa b dn RU eed 7 Connection examples 4 54 ete lad il cae re deo otto cate dA a edades Lah adc dede 8 COnNECHON NOLES s oeste nre cd te abe ret bebe Enn 8 Local status and diagnostic Indicators dee etre ah ae etse te xir eat 9 ire
13. E1 LED E2 LED No error OFF OFF Underrange OFF ON Overrange OFF ON Open circuit OFF ON Faulty supply voltage ON ON Parameter table invalid OFF ON Device error OFF ON Flash format error OFF ON The error that can actually be reported de pends on the measuring range For additional information please refer to the tables with signi ficant measured values in various formats 11 The module uses eight input process data words Process data Each channel is mapped to a word Input words IN1 to IN8 The measured values are transmitted to the controller board or the computer by means of the IN process data words IN1 to IN8 The measured values are depicted in IB IL or S7 compatible format In both cases the measured value is displayed in 16 bit format The data type is Integer 16 from a technical pro gramming point of view 15 14 13 Analog value 12 11 10 9 8 7 6 5 4 3 2 1 0 In the IB IL format a diagnostic code is mapped to the input data in the event of an error Code Cause hex 8001 Measuring range exceeded overrange 8002 Open circuit 8004 Measured value invalid no valid measured value available 8020 Faulty supply voltage 8040 Device faulty 8080 Below measuring range underrange PHOENIX CONTACT 10 AXL AI 8 ME
14. efault data stored data If no permanent data was stored the module 0080hex ParaTable read write Subindex Data type Length in Meaning Default value bytes 0 Array of Unsigned 16 10 2 Read write all elements See subindices 1 Unsigned 16 2 Parameterization of channel 1 0000hex Unsigned 16 2 0000hex 8 Unsigned 16 2 Parameterization of channel 8 0000hex 9 Unsigned 16 2 Data format 0000h ex 10 Unsigned 16 2 Reserved 0000h ex Parameterization of channel 1 channel 8 Parameterization word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Mean value Code bin O JO O Fil O O Mean 0 0 0 0 Measu 16 sample default 00 ter value ring range No mean value 01 4 sample 10 Filter Code bin 32 sample 11 30 Hz default 0 12kHz 1 Data format Measuring range Code bin 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Io 0 V 10 V default 0000 o lo lo lo lo o Datafor O 0 O 0 0 O OO 10 V 0001 mat OV 5V 0010 5 V 0011 Data format Code bin 0 mA 20 mA 0100 IB IL default setting 00 20 mA 0101 Reserved 01 4mA 20 mA 0110 S7 compatible 10 Reserved 0111 1110 Reserved 11 Channel inactive 1111 PHOENIX CONTACT 17 AXL AI 8 ME 15 2 Measured value in extended float format 00824
15. en us English Use of the device 0014 Location Var Visible String 1 59 R W Installation loca Please fill in tion 0015 Equipmentident Var Visible String 1 59 R W Equipment identi Please fill in fier 0016 ApplDeviceAddr Var Unsigned 16 1 2 R W User defined de xx XXhex e g vice number 00 01 14 2 Object descriptions Index Object name Object Data type A L Rights Meaning hex code 0038 ObjDescrReq Record 2 3 Read Object whose description is requested write 0039 ObjDescr Record 16 Seesu Read Description of the object whose index bindices was requested 003B PDIN Descr Record 3 12 R Description of the IN process data 003C PDOUT Descr Record 3 12 R Description of the output process data These objects are only important for tools and are therefore not described in more detail here Please refer to the basic profile for comprehen sive information PHOENIXCONTACT 14 AXL AI 8 ME 14 3 Diagnostics objects Index Object name Object Data type A L Rights Assignment hex code 0018 DiagState Record 6 21 R Diagnostic state 0019 ResetDiag Var Unsigned 8 1 1 C Reset diagnostics Diagnostics state 00184 DiagState This object is used for a structured message of an error 0018hex DiagState Read Subindex Data type Length in Meaning Contents b
16. ne analog input module 8 inputs 0 10 V x10 V O 20 mA 4 20 mA x20 mA 2 wire connection method including bus base module and connector Axioline analog output module 8 inputs 0 10 V 10 V 0 20 mA 4 20 mA 20 mA 2 wire connection method electronic module as a repla cement for item 2688064 AXL AI 8 Accessories Axioline bus base module Replacement item Axioline shield connection set contains 2 busbar holders and 2 SK 5 shield connection clamps Zack marker strip for Axioline device labeling in 2 x 20 3 mm pitch un printed 25 section for individual labeling with B STIFT 0 8 X PEN or CMS P1 PLOTTER Marking Zack marker strip flat for Axioline connector slot labeling in 1 x 5 8 mm 4 x 10 0 mm pitch unprinted 50 section for individual labeling with B STIFT 0 8 X PEN or CMS P1 PLOTTER Marking Documentation User manual English Axioline System and installation 4 Technical data Dimensions nominal sizes in mm 53 6 126 1 lc o e lc o o OJO 0JO OJO OJO O Ol 00 0JO OJO O OJ ooJoOJOO O O OJO OJO OO OJO O Width Height Depth Note on dimensions General data Color Weight Ambient temperature operation Ambient temperature storage transport Permissible humidity operation Permissible humidity storage transport Type AXLAI8 AXL Al 8 ME Type AXL BS AXL SHIELD SET ZB 20 3 AXL UNPRINTED
17. re rei EE 10 Significant values in various formats sssssssseeeeeeneenm eene 11 12 1 Significant values in IB IL format ciere docere ida e teneor nn Ee e e nera AA nO da acean aa 11 12 2 Significant values in S7 compatible format eessssese eese ener nnn 11 12 3 Calculation of the measured value from the process data input VAIUC eceee eee eeeeceeeeeeeeeeeeeeeeeeeees 12 Parameter diagnostics and information PDI ssessssenene e 12 Standard Objects uos ien stet nen Oeo a a edic canens M e MeV N dan ef LOO N 13 14 4 Objects for identification device rating Plate ccccececeseceeeeeeeeeeeeeeeeeeeeeeseeeeeseeeeseeeeeseeeeseneeenes 13 14 2 Object descriptloris soraira canran IIT ere tete rer Tende cad esacuddnesdvevaceuessamuateegned ade reden RE 14 143 Diagnostics objects cere nee Ere RESTE EE TR RR ERR ERE ER T RET EE ERRARE XR RESTER EE TR ER ERA XR Fu ER 15 14 4 Objects for process data management issssssssssseesseeee eee mene nennen nnne 16 Application objects aien E N T TERN 17 15 1 Parameter table 0080hex ParaTable ssssssssunssnnsnrrurnrnnrrnnnnrnnnnnrnrnnunununnnnnnnnnnnnnnnnnnnnnnnn nnn 17 15 2 Measured value in extended float format 0082hex Measured Value Float ccccseeeeeeeeeeeeeeeseeeees 18 DENER eee aa meme rM MEE aces ade 18 PHOENIXCONTACT 2 AXL AI 8 ME 3 Ordering data Description Axioli
18. t Ready Yellow ON Device operating there is still a connection to the previous device but the device has not yet detected a valid cycle after power on Connected Yellow Valid data cycles have been detected but the device is not yet flashing part of the current configuration Device applica Green yel Valid data cycles are being detected tion not ready low alter The master application set the output data to valid however the nating slave application has not set the input data to valid as yet Active Green Device operating communications within the Axioline station is flashing OK The master application does not read the input data The connection to the controller has not yet been established for example Run Green ON Valid data cycles are being detected All data is valid UA Green Uanalog ON Supply of analog modules present OFF Supply of analog modules not present E1 Red Peripheral fault ON I O error present OFF No I O error E2 Red Channel error ON Channel error present OFF Channel error not present Channel errors are errors that can be associa ted with a channel Periphery errors are errors that affect the entire module For more information on the meaning of local diagnostic and status indicators please refer to the UM EN AXL SYS INST user manual PHOENIX CONTACT 9 AXL AI 8 ME Error code and status of the E1 and E2 LEDs Error
19. t resistance of voltage input 70 kPa 106 kPa up to 3000 m above sea level 70 kPa 106 kPa up to 3000 m above sea level IP20 Ill IEC 61140 EN 61140 VDE 0140 1 Spring cage connection with direct plug in method 0 2mm 1 5mm 0 2mm 1 5mm 24 16 Bus base module 100 Mbps 5 V DC via bus base module Typ 105 mA max 130 mA 24V DC 19 2 V DC 30 V DC including all tolerances including ripple Typ 35 mA max 45 mA Electronic 35 V 0 5 s Polarity protection diode Suppressor diode max 8 differential inputs voltage or current can be chosen separately Spring cage connection with direct plug in method 2 wire shielded twisted pair 0 mA 20mA 4 mA 20 mA 20 mA 20 mA 0V 5V 5V 5V 0V 10V 10V 10V 16 bits 2 us 30 Hz 12 kHz in fast mode 16 bits 15 bits sign bit IB IL S7 compatible 300 us RFI filtering passive TP 1st order 30 Hz 12 kHz and mean value generation can be parameterized 0 1 of measuring range final value for active mean value generation and 30 Hz filter Suppressor diode 8 differential inputs voltage 0V 5V 5V 5V 0V 10V 10V 10V 268 kQ typical PHOENIXCONTACT 4 AXL AI 8 ME differential inputs voltage Open circuit response Common mode voltage range signal ground Overload protection differential inputs current Number of inputs Current input signal Input resistance current input Open circ
20. trical asymmetrical 1 kV to shielded I O cables Criterion A Test voltage 10 V Class B PHOENIX CONTACT 5 AXL Al 8 ME 5 Tolerance data The following applies for tolerance values The data is valid for nominal operation U 24 V in the de fault configuration unless documented otherwise Default configuration Filter with 30 Hz 16 sample mean va lue IB IL format 300 us update time fast mode 12 kHz filter without mean value generation Tolerances at T4 25 C Absolute Relative Typ Max Typ Max OV 5V 45V 50 mV 80 mV 0 5 0 8 OV 10V 10V OmA 20 mA 100pA 160uA 0 5 0 8 4 mA 20 mA x20 mA 300 ps update time default 30 Hz filter value 16 sample average Tolerances at T4 25 C Absolute Relative Typ Max Typ Max OV 5V 45V 10 mV 30 mV 0 10 0 30 OV 10V 10V OmA 20 mA 20 uA 60 pA 0 10 0 30 4 mA 20 MA 20 mA Typical data contains offset error gain error and linearity error in the respective default setting All tolerances indicated as a percentage are related to the po sitive measuring range final value Please also observe the values for temperature drift and the tolerances under influences of electromagnetic interferences Tolerance and temperature response at T4 25 C to 60 C Drift Typical Maximum OV 5V 5V 40 ppm K 70 ppm K OV 10 V 10 V OmA 20 MA 45 ppm K x85 ppm K 4 mA 20 MA 20 mA
21. uit response Overload protection Electrical isolation isolation of the voltage areas 5 V communications power logic 24 V supply I O 5 V supply logic functional earth ground 24 V supply I O functional earth ground Mechanical tests Vibration resistance in acc with IEC 60068 2 6 Shock test in acc with IEC 60068 2 27 Bump endurance test according to EN 60068 2 29 Conformance with EMC Directive 2004 108 EC Noise immunity test in accordance with EN 61000 6 2 Electrostatic discharge ESD EN 61000 4 2 IEC 61000 4 2 Electromagnetic fields EN 61000 4 3 IEC 61000 4 3 Fast transients burst EN 61000 4 4 IEC 61000 4 4 Transient surge voltage surge EN 61000 4 5 IEC 61000 4 5 Conducted interference EN 61000 4 6 IEC 61000 4 6 Noise emission test according to EN 61000 6 3 Radio interference properties EN 55022 Approvals For the latest approvals please visit www phoenixcontact net catalog Goes to 0 V 50 V DC 50V DC x30 V DC maximum 8 differential inputs current 0 mA 20mA 4 mA 20 mA 20 mA 20 mA 104 Q typical Going to 0 mA open circuit detection from 4 mA 20 mA No 5 2 V DC maximum Imax 50 mA 500 V AC 50 Hz 1 min 500 V AC 50 Hz 1 min 500 V AC 50 Hz 1 min 5g 25 g 11 ms period half sine shock pulse 10g Criterion B 6 kV contact discharge 8 kV air discharge Criterion A Field intensity 10 V m Criterion B 2 kV Criterion B supply lines DC 0 5 kV 0 5 kV symme
22. ytes 0 Record 21 Diagnostic state Complete diagnostics information 1 Unsigned 16 2 Error number 0 65535gec 2 Unsigned 8 1 Priority O0hex No error One Error O2nex Warning 81nex Error removed 82nex Warning eliminated 3 Unsigned 8 1 Channel O0nex No error O1hex Channel 1 O8nex Channel 8 FFhex Entire device 4 Unsigned 16 2 Error code See table below 5 Unsigned 8 1 More follows OOhex not supported 6 Visible String 14 Text 14 characters See table below The message with the priority 8155 or 8255 is aone time internal message to the bus coupler thatis implemented onto the error mechanisms of the higher level system by the bus coupler Error code and associated text Error Error code Text Priority Channel No error 0000hex Status OK OOhex OOhex Underrange 8920hex Underrange O2hex Ot hex O8hex Overrange 891 0hex Overrange O2hex OT hex O8hex Open circuit 7710hex Open circuit O1hex OThex O8hex Faulty supply voltage 5160hex Supply fail O1hex FFnex Parameter table invalid 6320hex Invalid para Olnax FFhex Device error 6301 hex CS FLASH O1hex FFhex Flash format error 6302hex FO FLASH Ono FFhex PHOENIX CONTACT 15 AXL AI 8 ME Reset diagnostics 00194 ResetDiag You can delete the diagnostics memory and acknowledge the diagnostic messages with this object