INTERBUS DDE Server for IBS PC ISA SC/I-T
Contents
1. Opens a channel to a specific topic name defined in the Server in an application with name IBS_SC the executable name less the EXE and assigns the number of that opened channel to channel Note By using the channel INITIATE statement the word channel must be used in the POKE statement instead of the actual cell reference The applicationname and topicname portions of the formula must be enclosed in quotation marks POKE channel itemname Data_Reference POKEs the value contained in the Data_Reference to the specified item name some actual Interbus output via the channel number returned by the previously executed INITIATE function Data_Reference is the row column ID of the cell containing the data value For itemname use some of the valid item names described in the Item Point Naming section INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 17 TERMINATE channel Closes the channel at the end of the macro Some applications have a limited number of channels Therefore they should be closed when finished Channel is the channel number returned by the previously executed INITIATE function RETURN Marks the end of the macro The following is an example of Excel macro used to poke value from cell B2 to topic Top02 item QWO PokeMacro Ctrl a INITIATE IBS_SC Top02 POKE A2 QW0 B2 ON TIME NOW 0 01 Terminat
2. Getting Started Quickly with the Server It is assumed that IBS PC ISA SC I T controller board controller board driver IBS CMD SWT G4 and DDE Client e g InTouch are already installed as described in the respective documentation Follow these steps 1 Install the Server 2 Create IBS PC SC I T controller board parameterization file IBS_SC_1 SVC with IBS CMD SWT G4 tool 3 Start and configure Server 4 Start DDE Client Installing the Server The INTERBUS DDE Server installation package can be supplied 1 As a self extracting archive 26010xxx EXE if downloaded from Klinkmann s web site the xxx is the current latest version of the Server 2 From installation on CD 3 On two or three distribution disks floppies To install the INTERBUS DDE Server from the self extracting archive run the 26010xxx EXE and proceed as directed by the INTERBUS DDE Server Setup program To install the INTERBUS DDE Server from CD or distribution disks floppies on MS Windows NT 1 Insert the CD with Klinkmann Software into CD drive or insert INTERBUS DDE Disk1 into a floppy drive A or B 2 Select the Run command under the Start menu 3 Run STARTUP EXE if installing from CD or SETUP EXE if installing from distribution disks floppies 4 If installing from CD select Protocol Servers DDE SuiteLink OPC find INTERBUS DDE Server and click on Setup 5 Proceed as directed by the INTERBUS DDE Server Se
3. Read in connected bus configuration as described in IBS CMD SWT G4 Help Default Process Data Description and Process Data Reference List will also be created automatically Save board parameterization data in IBS_SC_1 SVC file located in the same directory as the Server configuration file IBS_ SC CFG saving data in ASCII SVC file is described in IBS CMD SWT G4 Help Configuring the Server After the Server is initially installed some configuration is required During configuration Server creates a IBS_SC CFG file which contains all entered topic definitions as well as some board settings This file will automatically be placed in the same directory as IBS_SC EXE unless the path where the configuration file must be placed is specified via the 7Contigure DDE Server Settings command To perform the required configuration start the IBS_SC EXE program IBS_SC main window will appear IBS_SC a Help To access the commands used for configuration open the Configure menu IBS_SC Configure Board Configuration Topic Definition DDE Server Settings Configure DDE Server Settings Command To change Server s internal parameters invoke the Configure DDE Server Settings command The DDE Server Settings dialog box will appear INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 6 DDE Server Settings Protocol
4. Select the tag type by clicking on the Type button The Choose tag type dialog box will appear Choose tag type Group Yar Hist Trend Tag ID Memory Discrete Memory Integer Memory Real Memory Message DDE Discrete DDE Integer DDE Real DDE Message Indirect Discrete Indirect Analog Indirect Message INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 12 To access Server items the type must be DDE Discrete or DDE Integer Select the DDE type The Details dialog box for the tagname will appear Initial Value jo Min EU fo MaxEU 3999 Deadband fo Min Raw fo Max Raw 3999 Conversion Eng Units Rel Linear DDE Access Name Unassigned Sere Hat Item CO Use Tagname as Item Name Log Deadband fo Select the Server topic by clicking on the DDE Access Name button The DDE Access Name Definition dialog box will appear DDE Access Name Definition DDE Access Names Select the appropriate topic name and click on Done If the DDE Access Name has not been defined as previously described click on Add and define the DDE topic now The Details dialog box will appear displaying the selected DDE Access Name Initial Value m Min EU fo Max EU 3999 Deadband fo Min Raw jooo Max Raw 3999 Conversion Eng Units goaa DDE Access Name 01 C Square Root Item Use Tagname
5. INTERBUS DDE Server for IBS PC ISA SC I T for Microsoft Windows and InTouch Applications User Manual Ver 1 x Rev 1 5 DR 260 10 KLINKMANN AUTOMATION P O Box 38 FIN 00371 Helsinki Finland tel int 358 9 5404940 fax int 358 9 5413541 www klinkmann com Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T i Table Of Contents hatis DDE Zra eke ie ag MP EN RNAP SND PENTEL SY SA ES RAN OR A OB TTA AS TE 1 INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 1 INTERBUS DDE Server The INTERBUS DDE Server for IBS PC ISA SC I T controller board hereafter referred to as the INTERBUS DDE Server or Server is a Microsoft Windows NT application program that acts as a DDE Dynamic Data Exchange Server and allows other Windows application programs clients to access input output data from INTERBUS devices The Server communicates with INTERBUS devices via the IBS PC ISA SC I T controller board installed in an IBM compatible PC The Server uses Device Driver Interface functions supplied by Phoenix Contact to access controller board via Process Data Interface Up to 512 devices with 4096 I O points can be accessed The Server is primarily intended for use with Wonderware InTouch but it may be used by any Microsoft Windows NT program that is capable of acting as a DDE client What is DDE DDE is a complete commun
6. Timer Tick 50 msec NetDDE being used Configuration File Directory C IBS_SCY The following describes each field in this dialog box Protocol Timer Tick This field is used to set the frequency at which the Server checks for work to do The minimum value is 50 milliseconds for Windows 3 x and 10 milliseconds for Windows NT NetDDE being used Select this option if you are networking using NetDDE Configuration File Directory This field is used to specify the path disk drive and directory in which Server will save its current configuration file Server will use this path to load the configuration file the next time it is started Note Only the path may be modified in this field The configuration file is always named IBS_SC CFG There is no limit to the number of configuration files created although each must be in a separate directory When using the Server with InTouch it is a good practice to place the configuration file in the application directory Board Configuration Command This command is used to set some board related parameters required by the Server Invoke the Configure Board Configuration command A list of configured boards will appear only one board is supported in this Server version Board Configuration Boards IBS PC ISA SC I T Delete Select a board and click on Modify to examine the characteristics of the selected Board INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x Us
7. as Item Name Log Deadband fo For integers fill in the Min EU Max EU Min Raw and Max Raw fields These fields control the range of values which will be accepted from the Server and how the values are scaled If no scaling is desired Min EU should be equal to Min Raw and Max EU should be equal to Max Raw INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 13 Enter the Server item point name to be associated with this tagname in the Item field in the Details dialog box Initial Yalue fo Min EU fo Max EU 65535 Deadband fo Min Raw fo Max Raw 65535 Eng Units PO Pov bees DDE Access Name 01 C Square Root Item 10 Use Tagname as Item Name Log Deadband fo Refer to the Item Point Naming section below for details When all entries have been made click on the Save button in the top dialog box to accept the new tagname To define additional tagnames click on the New button To return to the WindowMaker main screen select Done Topic STATUS Item For each DDE Topic there is a built in discrete item which indicates the state of communication for the topic The discrete item STATUS is set to 0 when communication fails and set to 1 when communication is successful From InTouch the state of communication may be read by defining a DDE Discrete tagname and associating it with the topi
8. bit 9 of input word 3 OUTP4INT output word 4 as unsigned integer INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 16 Notes on Using Microsoft Excel Data from Server may be accessed from Excel spreadsheets To do so enter a formula like the following into a cell on the spreadsheet IBS_SC topic item Sometimes Excel requires the topic and or item point to be surrounded by apostrophes In the formula topic must be replaced with one of the valid topic names defined during the Server configuration Replace item with one of the valid item point names described in the Item Point Naming section Reading Values into Excel Spreadsheets Values may be read directly into Excel spreadsheets by entering a DDE formatted formula into a cell as shown in the following examples IBS_SC Device1_0 12 7 IBS_ SC Top02 QWO0 Note Refer to the Microsoft Excel manual for complete details on entering Remote Reference formulas for cells Writing Values to IBS_SC Points Values may be written to the IBS_SC Server from Microsoft Excel by creating an Excel macro that uses the POKE command The proper command is entered in Excel as follows channel INITIATE IBS_SC topicname POKE channel itemname Data_Reference TERMINATE channel RETURN The following describes each of the above POKE macro statements channel INITIATE IBS_SC topicname
9. c and using STATUS as the item name Input Conversion On Msg Direct C Reverse Off Msg Initial Value CM On Off DDE Access Name S01 Item STATUS From Excel the status of the communication may be read by entering the following formula in a cell IBS_SC topic STATUS INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 14 Item Point Naming Supported DDE item types are Inputs and Outputs Inputs and Outputs can be accessed as bits bytes words or double words signed or unsigned Item point naming uses byte oriented addressing If word is addressed and byte number w is specified in item point name byte w will be word s high byte and byte w 1 will be word s low byte The following table describes item point naming conventions Data Format Item Suffix DDE Tag Type Range Prefixjwx Discrete Oori e e pe a KF Integer 128 to 127 Oe eee meger aaeoa KF Integer 128 to 127 High Byte Prefix Hw Integer 0 to 255 Integer 128 to 127 Lower 12 bits Prefix Aw tester 0 to 4095 ee eee Integer 0 to 65535 Integer 32768 to 32767 IE A Word Novena Integer 0 to 4294967295 Integer 2147483648 to 2147483647 Notes 1 b specifies byte address 0 to 511 w specifies address of word s higher byte 0 to 510 even number d specifies address of double word s h
10. c names defined during Server configuration INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 11 Request Initial Data This option may be selected if the Server is other than a Wonderware DDE Server and the Server does not return data values immediately when a window is displayed This option is not applicable to this Server Wait for Change This option should be selected when the DDE application is a Wonderware DDE Server Select it for this Server Advise all Items This option may be selected if the Server is to poll for all data regardless whether data are in visible windows alarmed logged or trended The use of the option is not recommended Advise only active Items Selecting this option will cause the Server to poll only items in visible windows and items that are alarmed logged or trended Defining the Tagnames To define the Tagnames associated with the new DDE Access Name invoke the Special Tag Name Dictionary command in WindowMaker The Dictionary Tagname Definition dialog box will appear Dictionary Tagname Definition Details C Alarms Both C None Tagname sAccessLevel System Integer System Read only Read Write Comment AccessLevel X Log Events Priority 999 Click on New and enter the Tag Name The tagname defined here is the name InTouch will use The Server will not use this name
11. ch d is used For example invoke the File Run command and enter the following command IBS_SC d c path Note There is no limit to the number of configuration files that may be created although each must be in a separate directory Topic Definition Command The following steps are taken to define the Topics 1 Invoke the Configure Topic Definition command The list of configured topics will appear Topic Definition INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 9 2 To modify an existing topic select the topic name and click on Modify To define a new topic click on New The Topic Definition dialog box will appear Topic Definition Topic Name Board Name IBS PC ISA SC I T Hax Supported Points 128 1 4096 Update Interval 50 msec 3 Enter Topic Name which corresponds to the DDE Topic Name The DDE Topic Name is entered in the Add DDE Access Name dialog box described in the Using the Server with InTouch section 4 Select board from Board Name list only one board is supported in this Server version 5 Set Maximum Supported Points for topic Set this value equal to number of actually used polled items points this will reduce the amount of memory used by the Server 6 Set Update Interval to indicate the frequency the items points on this topic will be read polled When all entr
12. data pre processing and sets its own output values these values cannot be read by the Server and may be overwritten by the Server Error Delay Defines time interval after which Server will try to resume communication stopped by error Saving Server Configuration File If the configuration file does not exist or a new configuration path has been specified the Server will display the Save Configuration dialog box INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 8 Save Configuration Configuration File Directory C IBS_SC X Make this the default configuration file This dialog box displays the path where the Server is going to save the current configuration file The path may be changed if necessary Also the path can optionally be recorded in the WIN INI file by selecting the Make this the default configuration option Doing so it will allow the Server to find the configuration file automatically each time it is started Configuration File Location When the Server starts up it first attempts to locate its configuration file by first checking the WIN INI file for a path which was previously specified If the path is not present in the WIN INI file the Server will assume that the current working directory is to be used To start the Server with configuration file other than the default configuration file a special swit
13. detected on device segment_number position_number Faulty device is identified by its bus segment number and position number in segment Communication will be stopped Server will try to resume communication after Error Delay specified during Board Configuration dialog Error peripheral failure detected on device segment_number position_number Faulty device is identified by its bus segment number and position number in segment Communication will not be stopped Error host is in STOP state Outputs will be reset to 0 Error synchronisation error Error single data cycle failed Error Bus Warning Time ended without a valid data cycle Error 20 invalid data cycles occurred in a total of 1 million data cycles INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 19 Error initialising of Board No 1 was unsuccessful Note Only one board is supported in this Server version Error InterBus S start was unsuccessful Server s attempt to start data transmission between IBS PC ISA SC I T and INTERBUS devices was unsuccessful Possible cause actual bus configuration does not match to configuration defined in IBS_SC_1 SVC file Error no data transmission Possible cause Start data transmission check box was not set in Board Configuration dialog during Server configuration and data transmission between IBS PC ISA SC I T and INTERBUS devices is no
14. eDDEChannel RETURN TerminateDDEChannel TERMINATE A2 RETURN Note Refer to the Microsoft Excel manual for complete details on entering Remote Reference formulas for cells INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 18 Error Messages Messages about errors detected by Server can be output either in Server window or in WWLogger window As a rule messages about errors detected during Server configuration dialog are output in Server window but messages about errors detected during communication are output in WWLogger window Most of communication errors are detected by controller board IBS PC ISA SC I T and corresponding error codes are returned to Server Below is a list of most important error messages with some commentary Most of the error messages are self explanatory and does not require commentary Error controller failure detected error code OxXXXX Error code is value returned to Server by IBS PC ISA SC I T controller board Communication will be stopped Server will try to resume communication after Error Delay specified during Board Configuration dialog Error searching for bus failure Informs that serious bus failure happened Outputs are reset to 0 and diagnostic routine is started to search for exact location of failure When failure location is found another error message will be written Error bus failure
15. ened by clicking on rectangle in upper left corner of the Server window select options Show Errors Show Send Show Receive Verbose Debug Start DDE Client In Server Control menu select command Dump Wait until error occurs Close Client and Server Please send us the obtained logger file Server configuration file IBS_SC CFG controller board parameterization file IBS_SC_1 SVC controller board driver configuration parameters board number O address MPM address IRQ IBS CMD G4 project Client e g InTouch application AUTOEXEC BAT CONFIG SYS and SYSTEM INI files INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 21 Mar 97 Apr 97 May 97 Aug 97 Aug 97 Mar 2002 Rev1 5 Rev 1 0 Rev 1 1 Rev 1 2 Rev 1 3 Rev 1 4 KLINKMANN AUTOMATION INTERBUS DDE Server for IBS PC ISA SC I T Revision History Release 1 0 Minor changes Support for Microsoft Windows NT added Improved error processing Minor changes Manual file name changed Minor changes Installation from CD information added INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15
16. er Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 7 The Board Configuration dialog box will appear Board Configuration Board Name TALAREN Start data transmission X Stop data transmission X Error Delay 10 sec The following describes each field in this dialog box Board Name This field is used to enter the board name Start data transmision Server will load controller board parameterization file IBS_SC_1 SVC created with IBS CMD SWT G4 tool to controller board and start data transmission between controller board and INTERBUS devices when first request from DDE Client is received If this check box is not set data transmission must be already started for example started from IBS CMD SWT G4 tool Stop data transmision Server will stop data transmission between controller board and INTERBUS devices when there are no more data requests from DDE Clients If this check box is not set data transmission between controller board and INTERBUS devices will be continued even if all DDE Clients and Server are closed It may be convenient if IBS CMD SWT G4 tool is used parallely with Server or if controller board is performing data pre processing which must not be stopped Note Server has no read access to output data on controller board It has its own output data image created from output values received from the DDE Client Therefore if controller board performs
17. ication protocol designed by Microsoft to allow applications in the Windows environment to send receive data and instructions to from each other It implements a client server relationship between two concurrently running applications The server application provides the data and accepts requests from any other application interested in its data Requesting applications are called clients Some applications such as InTouch and Excel can simultaneously be both a client and server To obtain data from another application the client program opens a channel to the server application by specifying three things the server application name the topic name and the specific item name For example in the case of Excel the application name is Excel the topic name is the name of the specific spreadsheet that contains the data and the item name is the specific cell on the spreadsheet With InTouch the application name is View the topic name is the word Tagname when reading writing to an InTouch tagname and the item name is a specific tagname in the InTouch Data Dictionary When a DDE client application sets up a link to the DDE server application it requests the server to advise the client whenever a specific item s value changes These data links will remain active until either the client or server program terminates the link or the conversation They are a very efficient means of exchanging data because when the link has been established no communica
18. ies have been made select OK to process the configuration for this topic INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 10 Using the Server with InTouch To access input output data from InTouch the following steps all performed in WindowMaker are required To define the DDE Access Names in WindowMaker invoke the Special DDE Access Names command The DDE Access Name Definition dialog box will appear DDE Access Name Definition DDE Access Names Modify Delete Click on Add The Add DDE Access Name dialog box will appear Add DDE Access Name DDE Access Name so DDE Application Server Name Cancel IBS_SC DDE Topic Name S01 Handling of initial data values _ Request initial data Wait for change When to advise server C Advise all items Advise only active items Note If Add is selected this dialog box will be blank when it initially appears Data has been entered here to illustrate the entries which are made The following three fields are required entries when adding a DDE Access Name DDE Access Name Enter an arbitrary name which will be used by InTouch to refer to the topic For simplicity it is recommended that the name defined for the topic in Server is also used here DDE Application Server Name Enter Server name IBS_SC DDE Topic Name Enter one of topi
19. igher byte 0 to 508 even number 2 For Bit data x 0 15 3 Inputs are Read Only and their Prefix is I or E Eingang 4 Outputs are Read Write and their Prefix is Q or A Ausgang Alternative item point naming is supported to enable use of old InTouch other applications earlier using other DDE Servers and INTERBUS boards Alternative item point naming uses word oriented addressing The following table describes item point naming conventions DDE Tag Type Prefix wBITx Lower 12 bits Prefix wAIN 0 to 4095 Prefix wiNT 0 to 65535 INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 15 Notes 1 w specifies word address 1 to 256 2 For Bit data x 0 15 3 Inputs are Read Only and their Prefix is INPT 4 Outputs are Read Write and their Prefix is OUTP Item Point Naming Examples 12 7 bit 7 of input word 2 bytes 2 and 3 IB3 input byte 3 as unsigned integer IB3KF input byte 3 as signed integer IW3 input word 3 bytes 3 and 4 as unsigned integer IW3KF input word 3 bytes 3 and 4 as signed integer Q3 0 bit O of output word 3 bytes 3 and 4 QB4 output byte 4 as unsigned integer QB4KF output byte 4 as signed integer QW4 output word 4 bytes 4 and 5 as unsigned integer QW4KF output word 4 bytes 4 and 5 as signed integer Alternative item point naming examples INPT3BIT9
20. t started by other means e g IBS CMD SWT G4 tool Error error during reading file path IBS_SC_1 SVC Check whether controller board parameterization file IBS_SC_1 SVC exists Warning actual Protocol Timer Tick is considerably longer then requested Time that passed since Server received control previous time is considerably longer than requested Protocol Timer Tick One of possible causes of this warning is some other program keeping control for a long time For example scrolling of along file in Wonderware Logger window with PgUp PgDn keys will cause this warning Note This warning is written to Wonderware Logger window only if mode Verbose is on in IBS_SC window control menu INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 20 Troubleshooting If you experience communication problems while using the INTERBUS DDE Server please try the following suggestions Minimise your project to a size at which problem still occurs It will help us to reproduce your environment and problem Gradually delete DDE Client e g InTouch application topics and items INTERBUS devices If Client application uses also other Servers delete topics related to these Servers Note what was deleted last when problem disappeared Obtain Wonderware Logger file as described below Start Wonderware Logger Start INTERBUS DDE Server In Control menu op
21. tion occurs until the specified data value changes INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 2 Accessing a Remote DDE Item from Server The DDE protocol identifies an element of data by using a three part address including Application Topic and Item Application refers to the name of the Windows program Server that knows how to access the data element For this Server the application part of the DDE address is IBS_SC Topic is an application specific sub group of data elements The user creates a meaningful name for each of them and use this name as the topic name for DDE references Topics can have different data update time However as in this case the total process data amount is comparatively small and all current process data on IBS PC ISA SC I T controller board are instantly available for the Server use of only one topic is recommended for this Server Item indicates a specific data element within the specified topic For the Server an item is an individual data bit byte word double word from the process data the item point naming is described in the Item Point Naming section of this manual Note In some cases the term point is used interchangeably with the term item INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 3
22. tup program When installation is finished the subdirectory specified as a folder where to install the IBS_SC DDE Server will contain the following files IBS_SC EXE The IBS_SC Server Program This is a Microsoft Windows 32 bit application program INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 4 IBS_SC HLP The IBS_SC Server Help file IBS_SC CFG An example configuration file LICENSE TXT Klinkmann Automation software license file WWCOMDLG DLL Dynamic Link Library necessary for IBS_SC Server ADDITION ZIP Contains additional files InTouch application examples etc For detailed information how to use these files read the README TXT file included To uninstall the IBS_ SC Server start Control Panel select Add Remove Programs and select the IBS_SC DDE Server from the list of available software products Click on Add Remove and proceed as directed by the UnInstallShield program Note The HASP key is needed for full time running of IBS_SC Server The HASP Driver setup is performed during the Server setup Without HASP Driver installed the IBS_SC Server will run only 1 hour with all features enabled INTERBUS DDE Server for IBS PC ISA SC I T Ver 1 x User Manual Rev 1 5 260xxm15 Klinkmann Automation INTERBUS DDE Server for IBS PC ISA SC I T 5 Creating Board Parameterization File Start IBS CMD SWT G4 tool