Contents

1. Name CST_Per_Pt Description Comm Format CIP Syne Per Point mce 10 FIFO Mode Revision CIP Syne Per Point CST FIFO Mode CST Per Point Open Module Properties Choosing the CST FIFO Mode Comm Format results in an input tag structure that facilitates retrieval of a single timestamp event per RPI as has always been done However choosing the CIP Sync 10x FIFO Mode option results in the creation of a 10 element array in the input tag area to facilitate the retrieval of 10 timestamp events per RPI as shown below Local3 1 Event Local 3 Event 0 Local 3 Event 1 Local3 Event 2 Local3 I Event 3 Local 3 Event 4 Local 3 1 E vent 5 Local 3 Event 6 Local 3 I Event Local 3 Event 8 Local 3 1 Event 3 Local 3 1 E vent 9 Number Local 3 1 E vent 9 Point Local 3 1 E vent 9 D ata Local 3 1 E vent 9 ReturningUCT Time Local 3 1 E vent 9 ReturmingCIPSyncTime Local 3 1 E vent 9 CIPSyncY alid Local 3 1 E vent 9 CIPSyncTimeout Local 3 1 E vent 9 Timestamp Local 3 E ventsQueuedCount Rockwell Automation Publication 1756 RN615E EN E October 2012 6 ControlLogix Sequence of Events Input Modules Firmware Revision 2 009 The CIP Sync 10x FIFO Mode option also results in the creation of two additional input tags to assist in timestamp corrections in a CIP Sync architecture I LocalClockOffset and I OffsetTimestamp The Comm Format selection does not define wh
2. DC 10 55V Sequence of Events Module Installation Instructions publication 1756 IN591 These documents contain additional information concerning related products Description Provides information for configuring and using the SOE module Provides instructions and wiring diagrams for the installation of the SOE module ControlLogix Sequence of Events Module Installation Instructions publication 1756 IN592 Provides instructions and wiring diagrams for the installation of the SOE module Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Provides general guidelines for installing a Rockwell Automation industrial system Product Certifications website http www ab com Provides declarations of conformity certificates and other certification details You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation contact your local Allen Bradley distributor or Rockwell Automation sales representative Rockwell Automation Publication 1756 RN615E EN E October 2012 ControlLogix Sequence of Events Input Modules Firmware Revision 2 009 11 Notes Rockwell Automation Publication 1756 RN615E EN E October 2012 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products At http www rockwellautomation com support you can find techni
3. 1SOE 1756 IH16ISOE Description CORRECTED The CIP Sync functionality that was inadvertently disabled in version 2 008 resulting in timestamps using CST when CIP Sync timestamping was selected has been re enabled Table 3 Corrected Anomaly with Revision 2 008 Cat No 1756 IB16ISOE 1756 IH16ISOE Description CORRECTED If the RPI is set to 2 ms or less and you cycle power to the rack or remove and insert the controller while under power RIUP could cause the module to fault The ControlLogix Sequence of Events module firmware revision 2 007 has these enhancements e The ability to timestamp by using either CST values or CIP Sync values in the FIFO and Per Point modes of operation e The ability in FIFO mode to retrieve 10 timestamps per RPI regardless of CST or CIP Sync timestamping choice These features are enabled starting in RSLogix 5000 programming software version 18 00 00 where new configuration profiles defaulted at Major Revision 2 are provided for the 1756 IBI1GISOE and 1756 IH16ISOE modules These profiles let you choose what type of timestamp you prefer CST or CIP Sync and provide two new CIP Sync communication formats These formats create additional offset tags in the input structure that allow for correction if necessary of the module s accumulated timestamps See the Integrated Architecture and CIP Sync Configuration Application Technique publication A AT 003 for details on h
4. Release Notes Allen Bradley ControlLogix Sequence of Events Input Modules Firmware Revision 2 009 Catalog Numbers 1756 IB16ISOE 1756 IH16 SOE Enhancements Topic Page Enhancements 1 Corrected Anomalies 2 Firmware 2 007 and Enhancements 2 Per Point Module Operation 3 FIFO Mode Operation 4 Tag Definitions 7 x10 Retrieval Example Download the Firmware 10 Additional Resources 10 IMPORTANT Firmware revisions now use three digits after the decimal point to indicate minor revisions for example revision 2 009 instead of revision 2 9 Software versions now use two sets of decimal points to denote minor and subminor versions for example version 21 00 00 not 21 00 The ControlLogix Sequence of Events module firmware revision 2 007 and later has these enhancements Table 1 Enhancements with Revision 2 007 Enhancement You can timestamp by using either CST values or CIP Sync values in the FIFO and Per Point modes of operation In FIFO mode you have the ability to retrieve 10 timestamps per RPI regardless of CST or CIP Sync timestamping choice 1756 IB16ISOE 1756 IH161SOE Rockwell Allen Bradley Rockwell Software Automation 2 ControlLogix Sequence of Events Input Modules Firmware Revision 2 009 i Corrected Anomalies Firmware 2 007 and Enhancements The following anomalies have been corrected Table 2 Corrected Anomaly with Revision 2 009 Cat No 1756 IB16
5. cal manuals technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools You can also visit our Knowledgebase at http www rockwellautomation com knowledgebase for FAQs technical information support chat and forums software updates and to sign up for product notification updates For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect support programs For more information contact your local distributor or Rockwell Automation representative or visit http www rockwellautomation com support Installation Assistance If you experience a problem within the first 24 hours of installation review the information that is contained in this manual You can contact Customer Support for initial help in getting your product up and running United States or Canada 1 440 646 3434 Outside United States or Canada Use the Worldwide Locator at http www rockwellautomation com support americas phone_en html or contact your local Rockwell Automation representative New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures United States Contact your distribu
6. ents If EventsQueuedCount tag lt 10 copy the last non zero Event x Number into O Event_Ack tag to acknowledge receipt Rockwell Automation Publication 1756 RN615E EN E October 2012 ControlLogix Sequence of Events Input Modules Firmware Revision 2 009 9 In this example the buffer has 23 events to retrieve SOE Module Controller cop 160 Event Buffer lEvent_ 10 O Event_Ack Locat 3 Evert Locat3 Eveni 0 Locat31 Event t Local 31 Even 2 Locat H Event 3 Local 31 Even 4 Locat H Event 5 Loca 21E vet Locat H Event 7 1 verte Locat H Event 3 Local I Eveni 9 Number Local 31 Event 3 Port 10 Event Array Lend Eee Local 31 ReturingJCT Time Transferred Every RPI aS Local 31 E vert 9 CIP SyrcV ald Locat 3 E wens 3 CIPSyricTimeout Local 31 Event 3 Timestamp Locat H EventsQueuedCount Before any acknowledgements occur the module sends the information related to events 1 10 in the array every RPI and the EventsQueuedCount tag 23 Because the EventsQueuedCount tag gt 10 you can copy Event 9 Number which has a value of 10 into the O EventAck tag to acknowledge receipt and queue up the next 10 events In the following update the module sends the information related to events 11 20 in the array and the EventsQueuedCount tag 13 Because the EventsQueuedCount tag is still gt 10 you can copy Event 9 Number which now has a value of 20 into O EventAck
7. ether the module time stamps by using CST or CIP Sync values It only affects what tags are generated This means that you can use the x10 retrieval mechanism and still time stamp in CST See below for details After a Comm Format is selected a checkbox on the Configuration tab of the profile defines how the module will perform timestamping E Module Properties Local 6 1756 IB16ISOE A 2 7 General Connection Module Info Configuration Backplane a Input Filter Time Enable CST Capture Chatter Detecti Off gt On On gt Off Off gt On On Off No of Events Time Module Configuration Bits Latch CST Timestamp in CIP Syne LN HAARAA 3 KS KS KS SS ES SE o o o o o o o o o 0 1 Z 3 4 5 6 ti 8 kuu When Timestamp in CIP Sync is checked for all Comm Formats the module time stamps by using CIP Sync values When Timestamp in CIP Sync is not checked the module time stamps by using CST values Use this table to determine which timestamping options to choose Desired Retrieval Method Communication Format CIP Sync Checkbox Timestamp CST 1 item at a time CST FIFO Mode Not checked 10 items at a time CIP Sync 10x FIFO Mode Not checked CIP Sync litem at a time CST FIFO Mode Checked 10 items at a time CIP Sync 10x FIFO Mode Checked For more information about FIFO mode see the ControlLogix Sequence of Events Module User Manual publication 1756 UM528 Rockwell Automation P
8. in the U S A
9. ly being received from Grandmaster normal state if CIPSyncValid bit 1 1 Timestamp tags contain CIP Sync values when Timestamp in CIP Sync is checked 2 For more information see the Integrated Architecture and CIP Sync Configuration Application Technique publication A AT003 CIP Sync Comm Formats provide these tags to monitor the offset between the Grandmaster and CST Tag Type Tag Description Input LocalClockOffset 64 bit value that displays in us the offset between current CST and CIP Sync value when a valid CIP Sync time is available ClPSyncValid 1 OffsetTimestamp 64 bit CIP Sync value of when LocalClockOffset was last applied Updates once per second when local time master is active and CTimestampClPSync 1 OffsetTimestamp 0 if the module is not time stamping in CIP Sync 1 Value in this tag should be recorded immediately following a large jump in time of the LocalClockOffset Rockwell Automation Publication 1756 RN615E EN E October 2012 8 ControlLogix Sequence of Events Input Modules Firmware Revision 2 009 A Grandmaster device change or Grandmaster clock being Hand Set during the SOE event timestamp recording process could cause an Event CIP Sync Time Source bump After this bump you need to add or subtract the timestamp offset value to the specific event timestamp This verifies that the timestamp is accurate compared to other event timestamps that were recorded before the shift in Gra
10. ndmaster time This is a list of time stamped events from an SOE module At 10 00 05 000000 a Grandmaster time change occurred at the fifth event recorded so the fifth and sixth event timestamps were recorded with old time These event timestamps will need to be adjusted with the offset timestamp delta SOEEvent SOETimestamps Collected SOE Offset Timestamp h m s us Offset Timestamp Delta ps Relative SOE Timestamp Number h m s ps h m s ps 2 10 00 01 102000 10 00 01 102000 0 10 00 01 102000 3 10 00 02 300000 10 00 02 300000 0 10 00 02 300000 4 10 00 03 999000 10 00 03 999000 0 10 00 03 999000 5 10 00 05 000000 10 00 04 999980 20 10 00 04 999980 6 10 00 05 001000 10 00 05 000980 20 10 00 05 000980 x10 Retrieval Example The retrieval mechanism for x10 FIFO mode operation operates exactly as it has in the past with the obvious exception of transferring 10 events instead of 1 per update As mentioned an array of 10 elements is now provided in the Input tag structure and each element contains an Event Number tag as shown below There is also a tag called EventsQueuedCount that indicates the number of events in the buffer This number decreases each time a retrieval is performed To retrieve events perform these checks e Copy and or store array information e Check the EventsQueuedCount tag and if gt 10 copy Event 9 Number into O Event_Ack tag to acknowledge receipt and queue the next 10 ev
11. ow to use the offset tags These acronyms appear in these release notes Acronym Definition SOE Sequence of Events module CST Coordinated System Time CIP Sync A system wide single time source RIUP Removal and insertion a module under power RPI Requested Packet Interval is a user configurable parameter that defines the maximum amount of time between the production of 1 0 data from the module Rockwell Automation Publication 1756 RN615E EN E October 2012 ControlLogix Sequence of Events Input Modules Firmware Revision 2 009 3 Per Point Module Operation Per Point mode module operation still provides a single On and Off timestamp for each input point on the module However with firmware revision 2 007 those timestamp values can be either in CST or CIP Sync format Per Point operation begins with the selection of the appropriate communication format in RSLogix 5000 software version 20 00 00 or earlier and Logix Designer application version 21 00 00 or later There are now two Per Point Comm Format selections CIP Sync Per Point and CST Per Point New Module Type 1756 IB16ISOE A 16 Channel Isolated 24V Input Sequence of Events Vendor Allen Bradley Parent Local Name CST_Per_Pt Description Comm Format CIP Syne Per Point CIP Sync 10 FIFO Mode Revision CIP Sync Per Point CST FIFO Mode CST Per Point Open Module Properties Choosing either Per Point Comm Format results in an input tag
12. structure with a single On and Off timestamp value per input point as well as some additional general purpose CIP Sync status tags However choosing the CIP Sync Per Point option results in the creation of two additional input tags to assist in timestamp corrections in a CIP Sync architecture I LocalClockOffset and I OffsetTimestamp The Comm Format selection does not define whether the module timestamps by using CST or CIP Sync values It only affects what tags are generated Rockwell Automation Publication 1756 RN615E EN E October 2012 4 ControlLogix Sequence of Events Input Modules Firmware Revision 2 009 After you choose a Comm Format a checkbox on the Configuration tab of the profile defines how the module will perform timestamping E Module Properties Local 6 1756 IB16ISOE A 2 7 General Connection Module Info Configuration Backplane a Input Filter Time Enable CST Capture Chatter Detecti Off gt On On gt Off Off gt On V On gt Off No of Events Time 0 E 0 0 Module Configuration Bits Latch CST Timestamp in CIP Syne o A HAAHKA KS KS KS KS KS KS ES ES 0 9 9 9 9 9 0 0 0 1 2 3 4 5 6 7 8 guu When Timestamp in CIP Sync is checked the module time stamps by using CIP Sync values When Timestamp in CIP Sync is not checked the module time stamps by using CST values Desired Timestamp Communication Format CIP Sync Checkbox CST CST Per Poin
13. t Not checked CIP Sync CIP Sync Per Point Checked For more information about Per Point mode see the ControlLogix Sequence of Events Module User Manual publication 1756 UM528 The Latch checkbox latches the CST or CIP Sync timestamps so that recorded events are not discarded until you acknowledge them As a result if latching is selected and new events occur they will be ignored until the existing event is acknowledged FIFO Mode Operation FIFO mode module functionality still provides these features e An onboard buffer that holds 160 timestamps and stores the Timestamp Event Number Status and Input Point number in the queue e Two Retrieval methods Standard FIFO and By Point However with firmware revision 2 7 those timestamp values can be either in CST or CIP Sync format and it is now possible to retrieve 10 timestamps per transfer versus the single timestamp per transfer Rockwell Automation Publication 1756 RN615E EN E October 2012 ControlLogix Sequence of Events Input Modules Firmware Revision 2 009 5 FIFO mode operation begins with the selection of the appropriate communication format in RSLogix 5000 software version 20 00 00 or earlier and Logix Designer application version 21 00 00 There are now two FIFO mode Comm Format choices CIP Sync 10x FIFO Mode and CST FIFO Mode New Module Type 1756 IB16ISOE 4 16 Channel Isolated 24V Input Sequence of Events Vendor Allen Bradley Parent Local
14. tag to acknowledge receipt and queue the next 10 events In the following transfer the module sends the information related to events 21 30 in the array though only 3 events are recorded and the EventsQueuedCount tag 3 Because the EventsQueuedCount tag is lt 10 you can search for the last non zero Event Number which in this case is Event 2 Number and copy its value which is now 23 into O EventAck tag to acknowledge receipt This same mechanism can be used for Retrieval by Point if desired For more information see the ControlLogix Sequence of Events Module User Manual publication 1756 UM528 Rockwell Automation Publication 1756 RN615E EN E October 2012 10 ControlLogix Sequence of Events Input Modules Firmware Revision 2 009 Download the Firmware To upgrade your SOE module firmware download the firmware from the Rockwell Automation Support Website at http www rockwellautomation com support Use ControlFLASH software to upgrade the module IMPORTANT All existing modules can be upgraded to revision 2 009 e For applications that require revision consistency you can load revision 1 5 instead of revision 2 009 e We recommend that all SOE modules are upgraded to firmware revision 2 009 for consistency across your system Additional Resources from Rockwell Automation Resource ControlLogix Sequence of Events Module User Manual publication 1756 UM528 ControlLogix 24 48V
15. tor You must provide a Customer Support case number call the phone number above to obtain one to your distributor to complete the return process Outside United States Please contact your local Rockwell Automation representative for the return procedure Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Allen Bradley Rockwell Software Rockwell Automation ControlLogix RSLogix 5000 Integrated Architecture TechConnect and ControlFLASH are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1756 RN615E EN E October 2012 PN 176418 Supersedes Publication 1756 RN615D EN E March 2012 Copyright 2012 Rockwell Automation Inc All rights reserved Printed
16. ublication 1756 RN615E EN E October 2012 ControlLogix Sequence of Events Input Modules Firmware Revision 2 009 7 Tag Definitions When Timestamp in CIP Sync is checked the following occurs e For CIP Sync Comm Formats the module time stamps with CIP Sync and provides I LocalClockOffset and I OffsetTimestamp tags e For CST Comm Formats the module time stamps with CIP Sync but does not provide I LocalClockOffset and I OffsetTimestamp tags This may be a good option if you plan to use CIP Sync in the future If you check this checkbox you do not have to delete and then reconfigure the module when you decide to use CIP Sync technology CIP Sync Tags All Comm Formats provide these CIP Sync tags Tag Type Tag Description Config TimestampCiPSync 1 The module time stamps in CIP Sync 0 The module time stamps in CST Input Returning CIPSyncTime 1 Timestamps are returned in terms of CIP Sync 0 Timestamps are returned in terms of backplane CST ClPSyncValid 1 CIP Sync is available on the backplane 0 CIP Sync is not available on the backplane CPSyncTimeout 1 The module was connected to a valid local in chassis time master that has timed out no CIP Sync update over a 6 second period The module is now using its own clock to time stamp drifting at a rate of 1 ps s versus being synched 0 Either e No local time master has ever been seen CIPSyncValid 0 e CIP Sync value is current

Download Pdf Manuals

image

Related Search

Related Contents

Vorbereitung Ihres neuen transportierbaren Wellnessbads  Istruzioni d`Uso - Amazon Web Services  - Frank`s Hospital Workshop  ACOUSTI-Q - PreSonus  EMI TSOP6 EVB Universal Evaluation Board User`s Manual  Casio Watch 3252 User's Manual  DMV-601H NTSC 取扱説明書    Manual do usuário - philips consumer life style  Implementing QoS for VoIP in a Local Area Network (LAN)  

Copyright © All rights reserved.
Failed to retrieve file