Home
        MOD9200BNT BACnet Transceiver User Manual
         Contents
1.      AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 2 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    Table of Contents  Mig EVE OG CUIONN s wut teuscavouncusaves E E sins E E 4  a  ACI MOD9200 Transceiver System ciescecesecssssizescenccececeesecesscccsesesecssiesvesceesedesssscsss 4  II  BACnet Transceiver Installation  amp  Network Setup        ssccsccsssssssseccccccccoccooosssssssssssceceee 5  a  Transceiver Installation            ecccccsssssceeeccccssssccceocccssssseccoccossssscccocssssssseceecssssssseceesoo 5  b  Network Setup for Transceiver Configuration               ccccccccccssssssssssccccccsssssssscees 6      SOUS A New IP Address sce cescuesvcsstecbevensecssvevtcewecesseessdasseacavescuesesepeneseucsceiedsseensenes 6  d  Manually Resetting The Factory Default IP Address                     sssssssscccceeeeseees 8  I Configuration SOUCW AU Cece ge cettccs coves cexevesvevnseesscecsssatecescenssexsssescessceusdeuessauucvsceuses sescssseveveuscs 9  a  Configuration Software Description               sssccscccccsssssssssssscccccscccssssssssccccssssssees 9  Pie V SUGIIN IS CONNEC meN iS ci ccaescccueceecsceteesscetssesessssuereeeteceagssssberssecsseuessssuersseteecasissitersseees 9  c  Configuration Software Installation                 cssssssssccccsssssssssssssccccscccessssssscssoeees 9  d  Creating A MOD9200 Configuration File                 ccss
2.     Network ID    Miscellaneous       AUTOMATION COMPONENTS  INC   2305 Pleasant View Road   Middleton  Wisconsin 53562 Page 23 of 37  www workaci com  888  967 5224    Version   1 0  10000674    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    Use the Serial Comm Port configuration dialog box to select the appropriate  internal communication parameters  Connect Speed  Connect Preferences  and  Transport Mode  for the Transceiver     E Serial Comm Port    Properties    Maximum Speed    33400 bal Modbus Transport    Connection Preferences    RTU    Data Bits  8      Panty  NO HE      Stop Bits  1        C ASCII       The MOD9200BNT requires internal communication parameters to be set  as follows     Maximum Speed   38400 BPS  This communication speed is set for  internal use by the MOD9200BNT Transceiver and it will not change the  external BACnet MSTP communication speed of 76800BPS     Data Bits   8   Parity   none   Stop Bit   1   Modbus Transport   RTU    The MOD9200BNT Transceiver transmission mode and serial port  parameters need to be exactly the same as shown above     AUTOMATION COMPONENTS  INC Version   1 0    2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 24 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    To Save the configuration file click on File  gt  Save  It is recommended that  the  cfg file be saved in the Trs folder already setup  i e  C  trs config      U a ic L   p
3.    User   s Manual    MOD9200BNT BACnet Transceiver  Configuration Software  Setup  amp  Configuration    MOD9200BNT BACnet Transceiver Installation  amp  Configuration    License Agreement for Automation Components  Inc  Software  IMPORTANT READ THESE TERMS CAREFULLY BEFORE INSTALLING THIS SOFTWARE     THESE TERMS AND CONDITIONS ESTABLISH A CONTRACT BETWEEN YOU INDIVIDUALLY IF YOU ARE AGREEING TO IT IN YOUR OWN CAPACITY  OR IF  YOU ARE AUTHORIZED TO AGREE ON BEHALF OF YOUR COMPANY OR ANOTHER ORGANIZATION  BETWEEN THE ENTITIY FOR WHOSE BENEFIT YOU  ACT     YOU      AND ACI  BY OPENING THE SEALED CD ROM PACKAGE IN THIS MANUAL  YOU ACKNOWLEDGE THAT YOU HAVE READ THIS LICENSE  AGREEMENT  THAT YOU UNDERSTAND IT  AND THAT YOU AGREE TO BE BOUND BY ITS TERMS  IF YOU DO NOT AGREE TO THE TERMS AND  CONDITIONS OF THIS LICENSE AGREEMENT OR IF YOU DO NOT UNDERSTAND THEM  PROMPTLY RETURN THE UNOPENED PACKAGE AND ALL  ACCOMPANYING ITEMS TO ACI FOR A FULL REFUND     1  Grant of License for Registered Users  ACI grants you a non exclusive  non transferable license to use the software program with which this license is distributed  the  Product    including any documentation files  accompanying the Product   Documentation   on any single computer  You may use the Product on a second computer so long as only one  1  is used at a time     2  Backup Copy  You may make one backup copy of the Product  You may use it only to reinstall the Product     3  Ownership   You have no ownership rights in t
4.   AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 12 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    File Settings Points Row RegisterEntry Register Bank  REG FUNCTION REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID  ANALOG_INPUTS 5th Floor  Conf Am 4       Assign a sensor transmitter to the data register by clicking in the TRANSMITTER ID  cell to open a drop down menu  Use the scroll bar to scroll to the correct address or  automatically scroll to the address by typing the hexadecimal address in the cell  To  select the address click on the appropriate ID in the drop down menu  Each ACI wireless  transmitter is factory configured with a unique ID     refer to the sensor product data sheet  for the location of the transmitter ID     or Conf Arm A       Assign the appropriate sensor transmission channel to the data register by clicking in the  cell to open a drop down menu  Click on the appropriate transmission channel  01 to 04        to select    NAME   TRANSMITTER ID   TRANS CHAN   TRANS TIMEOUT     JBE ha  AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 13 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    The active transmission channels are factory configured as follows                                                                 Device
5.   INCLUDING  WITHOUT  LIMITATION  INDIRECT  SPECIAL  PUNITIVE  OR EXEMPLARY DAMAGES FOR LOSS OF BUSINESS  LOSS OF PROFITS  BUSINESS INTERRUPTION  OR LOSS  OF BUSINESS INFORMATION  ARISING OUT OF THE USE OF OR INABILITY TO USE THE PROGRAM  OR FOR ANY CLAIM BY ANY OTHER PARTY  EVEN IF  ACI HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES  ACT    S AGGREGATE LIABILITY WITH RESPECT TO ITS OBLIGATIONS UNDER THIS  AGREEMENT OR OTHERWISE WITH RESPECT TO THE PRODUCT AND DOCUMENTATION OR OTHERWISE SHALL NOT EXCEED THE AMOUNT OF THE  LICENSE FEE PAID BY YOU FOR THE PRODUCT AND DOCUMENTATION  BECAUSE SOME STATES COUNTRIES DO NOT ALLOW THE EXCLUSION OR  LIMITATION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES  THE ABOVE LIMITATION MAY NOT APPLY TO YOU     8  Export Restrictions   THIS LICENSE AGREEMENT IS EXPRESSLY MADE SUBJECT TO ANY LAWS  REGULATIONS  ORDERS  OR OTHER RESTRICTIONS ON THE EXPORT FROM  THE UNITED STATES OF AMERICA OF THE PRODUCT OR INFORMATION ABOUT SUCH PRODUCT WHICH MAY BE IMPOSED FROM TIME TO TIME BY THE  GOVERNMENT OF THE UNITED STATES OF AMERICA  YOU SHALL NOT EXPORT THE PRODUCT  DOCUMENTATION  OR INFORMATION ABOUT THE  PRODUCT AND DOCUMENTATION WITHOUT CONSENT OF ACI AND COMPLIANCE WITH SUCH LAWS  REGULATIONS  ORDERS  OR OTHER  RESTRICTIONS     9  Termination   This License Agreement is e_ective until it is terminated  You may terminate this License Agreement at any time by destroying or returning to ACI all copies of the Product and  Documentation in you
6.  Analog CH 01 Analog CH 02   Digital CH 01  WT2630A Space Temp   Therm 20K   WT2630B Space Temp SetPoint Override  Discrete    Therm 20K   Analog  See page 15 to set the  Digital Capture Time  WT2630C Space Temp Override  Discrete    Therm 20K  See page 15 to set the  Digital Capture Time  WH2630A Humidity  WH2630B Space Temp Humidity   Therm 20K   OA2630A Outdoor Temp Outdoor   Therm 20K  Humidity  OST2630A Outdoor Temp   Therm 20K   DT2630A Duct Temperature   Therm 20K   DT2650A Ave Temperature   Therm 20K   DH2630A Duct Humidity  DH2630B Duct Temperature   Duct Humidity   Therm 20K   FT2630A Fluid Temperature   Therm 20K   RT2630A B C See Device Label for Analog  4  and Digital  4  Configuration  RT2620A See Device Label for Digital  4  Configuration  RT2602B Digital  2  Inputs  SST2630A Temperature  Therm 20K   SSTS5630AE Temperature  RTD 1K                 Note  For RT2630B  0 10V  0 5V  amp  4 Dig  Inputs   The    Data Format    shall be    ANALOG     for  the analog inputs  The values will be displayed as 0 to 409 5 with the transmitter input from O to  1OVDC  or 0 to SVDC     Select the appropriate DATA FORMAT value by clicking in the cell to open a drop down  menu     a ee    File Settings Points Row RegisterEntry    REG FUNCTION REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT  ANALOG_INPUTS D first floor room A 3D6F 1  i RTD 1k       AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 14
7.  E     e   o_  70 SSS EES    Organize    New folder       A    Ft Favorites  MB Desktop  m Downloads        Recent Places    Libraries    Name       LON B3 ini        LON F config ini      LON F test L ini    5  LON F test 2 ini    5  LON F test 3 ini    Date modified    5 11 2010 2 04 PM  4 16 2010 1 16 PM  4 2 2010 12 13 PM  4 13 2010 2 42 PM  5 11 2010 3 45 PM    Type    Configuration sett     Configuration sett     Configuration sett     Configuration sett       Configuration sett                 LON F test new prog L ini     Patterson Data input ini     square_d_rtu ini       square_d_tcip ini    E   Documents  a Music   E  Pictures  F Videos    4 16 2010 5 59 PM Configuration sett     8 13 2009 10 30 AM Configuration sett     6 2 2008 9 56 AM  6 2 2008 9 55 AM  4 5 2010 8 00 PM  9 3 2008 2 06 PM    Configuration sett       Configuration sett             4   template ini     Homegroup      amp  trickydicky ini    File name   Save as type    c  trs config   ini X    Configuration sett       Configuration sett       a Hide Folders          k  Sending The Configuration File To The MOD9200    Before sending the file to the MOD9200  it is important to ensure that the     Serial Transport    setting is checked as shown        Unit Identifier    5   GROUP NAME    POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT  1 THERM 20k   2 HUMIDITY   1 THERM 20k   1 THERM 20k   1 THERM 20k    1 THERM 20k     v Serial Transport  TCP IP Transport    Network ID       Miscellaneous       Alway
8.  File and select the    _config ini    file  Click on     Open    to open the file in the Editor  Confirm that the file is the same as the  original configuration file  Since the    Group Name    and the    Point Name    fields  are not used by the MOD9200 transceiver  these fields will now be blank  All the  other fields and settings should be the same as the original  ini file     AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 28 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration       File Settings Points Row RegisterEntry Register Bank  REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID   TRANS CHAN DATA FORMAT  ANALOG INPUTS   1 THERM 20k  ANALOG_INPUTS 2 HUMIDITY  ANALOG_INPUTS 1 THERM 20k  ANALOG_INPUTS 1 THERM 20k    ANALOG_INPUTS 1 THERM 20k  ANALOG_INPUTS 1 THERM 20k       NOTE  The    _config ini    file is a dynamic file  If multiple MOD9200  Transceivers are being administered from the same PC the    _config ini     file will be a copy of the configuration file from the last Transceiver    administered   AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 29 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    IV  Data Acquisition    a  BACnet Standard    BACnet refers to the open communications protocol  ANSI ASHRAE STD  135  created by the Ame
9.  current draw is less than 0 5 Amp     3  The Transceiver is shipped with an IP address of 192 168 0 1 and a subnet  mask of 255 255 255 0  see page 8 for instructions on changing the IP  address      4  To initially connect to the Transceiver the networked PC must have a  static IP address of 192 168 0 X  X can be any number except 1 or 2  with  a subnet mask of 255 255 255 0    5  Installing The MOD9200 Configuration Software   6  Configure the MOD9200BNT Transceiver   b  Installing the MSTP  RS485  Network   1  Choose a location close to the computer or RS485 loop    2  Mount the Transceiver on the wall using four  8 screws    3  MSTP  RS485    Use 20 gauge shielded twisted pair wire to connect the  Transceiver  Terminals A   amp  B   to the network  See Figure 1     4  Multiple RS485 Devices   If more than one RS485 device is used the devices  should be    daisy chained    or    straight line connected    by connecting all the     A     wires to the    A    terminals and the    B    wires to the    B    terminals  Do  not use spur lines or a star configuration    5  RS485 Terminating Resistor   If the MOD9200 is at the end of a RS485 loop  a terminating resistor should be installed to match the electrical impedance    characteristic of the twisted pair loop and prevent signal echoes from  corrupting the data     AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 34 of 37    www workaci com  888  967 5224    MOD9ON00
10.  is at the end of a RS485 loop a  terminating resistor should be installed to match the electrical impedance characteristic of  the twisted pair loop and prevent signal echoes from corrupting the data     b  Network Setup for Transceiver Configuration    A network connection using a RJ45 Crossover cable is required during the initial setup of  the Transceiver for transporting the Transceiver Configuration File via FTP     Connect the MOD9200 Transceiver  J2  to a 10 100Base T Ethernet network or use a  crossover cable to connect directly to the PC     Apply 24 VAC 60 Hz power to the MOD9200 Transceiver     c  Setting A New IP Address    The MOD9200 is shipped from the factory with an IP address of 192 168 0 1 anda  subnet mask of 255 255 255 0      Note  To initially connect to the Transceiver  the networked PC must have a static  IP address in the form of 192 168 0 X  where X is  gt  2 with a subnet mask of  255 255 255 0     The IP Address can be changed by changing the IP Address in the Transceiver Config  File  Open either an existing config file or a new config file using the ACI Programmer  Software     Click on Settings  gt  TCP IP Transport    a   N  Points Row RegisterEntry    E io    me   ile  Settings         Unit Identifier GROUP NAME POINT NAME TRANSMITTER ID   TRANS CHAN DATA FORMAT LOG    Serial Transport     TCP IP Transport          Miscellaneous    AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 6 o
11.  of 37   www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    To create a new data register row click on Row  gt  Append  Continue to do this for each  row data register that needs to be configured     The completed configuration example for an office building is as follows     i  Editor   _config ini    The columns may be resized by placing the cursor over one side of the column  When the       REG FUNCTION   ANALOG_INPUTS  ANALOG_INPUTS  ANASLOG_INPUTS  ANALOG_INPUTS  ANALOG_INPUTS  ANALOG_INPUTS         REG ADDRESS    File Settings Points Row RegisterEntry Register Bank    GROUP NAME  0 First Floor  1 First Floor  2 First Floor  3 Warehouse  4 Warehouse    5 Warehouse    YP Office   YP Office  general Office  North   West     East    TRANSMITTER ID    TRANS CHAN    DATA FORMAT  1 THERM 20k  2 HUMIDITY  1 THERM 20k  1 THERM 20k  1 THERM 20k  1 THERM 20k       cursor changes to two arrows hold down the left mouse button and drag the side of the  column to resize it     f  Digital Output  Coil  Register Configuration    Select the Digital Output  Coil  Register table by clicking the    RegisterBank       tab     File Settings Points Row RegisterEntry  Register Bank      AUTOMATION COMPONENTS  INC    2305 Pleasant View Road    Middleton  Wisconsin 53562  www workaci com  888  967 5224    Input Registers    Digital Output Coil  Registers    Analog Output Holding  Registers    Page 15 of 37    SMITTER ID       Version   1 0    1000067
12.  the specified time interval     Transmitter Timeout  min     Digital Capture Time  90    Seconds       Minutes    Digital Scaling    W Digital Scaling On Degrees F ie    Degrees C E    Register Yalue When Sensor Lost  C Retain Last   alue       Set to 19999    AUTOMATION COMPONENTS  INC   2305 Pleasant View Road   Middleton  Wisconsin 53562 Page 21 of 37  www workaci com  888  967 5224       Version   1 0  10000674    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    To select the timeout interval click on the appropriate value in the drop down  menu     The Digital Input Capture Time can be set to hold a momentary contact  closure such as the override button on the WT2630B C for a period of time   Default is 0 min   amp  recommended value is 1 min   so the controller has time  to recognize the contact closure     The Digital Capture Time can be set up to 240 minutes  4 hours  in  applications where an extended period of time is needed such as     unoccupied period by pass        Set the Digital Capture Time interval  seconds or minutes  by clicking on     Seconds    or    Minutes     Click in the Digital Capture Time cell to open a  drop down menu  Use the scroll bar to scroll down to the appropriate value  0  to 240  or type the value in the cell to automatically scroll to the appropriate  value  To select the timeout interval click on the appropriate value in the drop  down menu     Digital Scaling On check box     Should be checked when configuring the  MOD
13. 4    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    First we will assign the REG ADDRESS by clicking in the cell  Before entering register  addresses  ensure the    RegisterEntry    AutoSet is turned off as shown           RegisterEntry   Register Bank    REG ADDRESS GROU Turn AutoSet ON i   TRANSMITTER ID TRANS CHAN    Turn AutoSet OFF       Enter the Register address in the REG ADDRESS window  The valid range is 0 to 49     File         RegisterEntry Register Bank    REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN    0              Again use the mouse to move to the next column  Enter a GROUP NAME  if  desired  for the data set by typing the group name in the cell  Enter the name in the cell by using  the mouse to click on the next column     Note  DO NOT use commas or semicolons in the Group Name    File Settings Register Bank    I    REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN  0  Garage           AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 16 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    Enter a POINT NAME  if desired  for the data point by typing the name in the  Cell  Enter the name in the cell by using the mouse to click on the next  column     Note  DO NOT use commas or semicolons in the Point Name    File Settings Points Row RegisterEntry Register Bank    REG ADDRESS GROUP NAME POINT NAME TRANSMITTE
14. 8  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    I  Introduction    The ACI MOD9000BNT BACnet network receiver utilizes  reliable Spread Spectrum Radio technology  When used with  other ACI wireless sensors the system can transmit remote sensor  readings and status alarm indications to a centralized networked  monitoring station or controller without the need for extensive  wiring  The MOD9000BNT is compatible with any control   MOD9000BNT panels or automation systems that utilize the BACnet MSTP  BACnet Receiver communication protocol        a  ACI MOD9200 Transceiver System    MOD9200BNT BACnet MSTP Network Transceiver   Receives input from up to 50 remote wireless sensor modules and or wireless  output modules  RD2402  amp  RD2432  per Transceiver   ACI signal repeater router RR2552 can be used to extend the wireless   sensor transmission distance if needed   MSTP  RS485  network connection   MOD9200 Configuration Software    Wireless Wall Temp   amp  Humidity      Sensor bS H   Wireless Remote Digital Analog mf a F   7     BACnet   MSTP Wireless Digital    Input Modules  amp  Energy Totalizer  T   p          Network elay  Output   Wireless Immersion  amp  Eoo      t P i Thee Relay  5    Remote Sensors          afl MOD9200BNT  Wireless Outside Ar SS AF Bacuett Transceivers wm   Temperature  amp             Wireless Digital  Humidity    o  Repeater Increases  amp  Analog Outputs  Transmssion Distance  1f  needed    Sub Svstem Overview       AUT
15. 9200BNT BACnet   transceiver or the MOD9200LON LonWorks    Transceiver     Units   Select the appropriate default temperature scale F C   Register Value When Sensor Lost     The user has the options to select    whether the sensor value should remain unchanged or set to 19999 when the  communication link is lost with the sensor  after the transmitter timeout    period   AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 22 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    Configuring The Transceiver For MSTP  RS485  Network    The Transceiver needs to be assigned an Identifier Address for device internal  use  To enter the Transceiver Unit ID into the Configuration File click on the  Menu Comm  gt  Unit Identifier        SS 5   GROUP NAME POINT NAME TRANSMITTER ID           Serial Transport  TCP IP Transport    Network ID       Click on the drop down menu arrow and select the Transceiver Unit Default  ID of    1    from the drop down menu and click    OK          REG ADDRESS GAOUP NAME POINT NAME  rs 0 Ath Floor  Conf Am 4  rs 1 Bth Floor  Cont Am B    rs 2 Ath Floor Cont Am C  rs a O          wU nit Identifier    Cancel      oo    07 17 F to hope       Click on Menu   Comm  gt  Serial Transport to activate the Serial Comm Port  dialog box     RegisterEntry Register Bank      Unit Identifier 5   GROUP NAME POINT NAME        v  Serial Transport  TCP IP Transport   
16. BNT BACnet Receiver Installation  amp  Configuration    6  24 VAC Input   Connect 24VAC 60 Hz and earth ground to the input  terminals using 20 AWG wire as shown in the product data sheet     7  Power up the MOD9200 Transceiver with the BACnet MSTP network     8  Use BACnet Device Scan function to identify the MOD9200 Device Instance   amp  MSTP address     9  Verify there is no address conflict with other node in the subnet     10  Proceed to read object AIO  to AIXX  amp  AI101 to AI XX alarm property   where XX is the last data register configured using the Trs Programmer  Configuration software  For AIXX  XX   Trs MOD9200 data Register  Number   1       AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 35 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    For more information  please contact   ACI   2305 Pleasant View Rd    Middleton  WI 53562   Telephone  1 608 831 2585  Wwww workaci com    AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 36 of 37    www workaci com  888  967 5224    MOD9200BNT BACnet Transceiver Installation  amp  Configuration  MOD9200       BNT              4 00 00 00 6F   i  7    J       p00000  0            TALI Mayes         Switch   Switch   Switch   Switch   Switch   Switch   Switch   Switch   Network  Address    i   O1Z6 JW  28uLC       A8 A7 A6 A5 A4 A3 A2 Al  OFF   OFF   OF
17. F   OFF   OFF   OFF   OFF   0    titi   OFF   OFF   OFF   OFF   OFF   ON   OFF   OFF   4      OFF   OFF   OFF   OFF   OFF   ON   ON   OFF   6      OFF   OFF   OFF   OFF   ON   OFF   OFF   OFF   8    Ls    OFF   ON   OFF   ON   OFF   OFF   OFF   OFF   80      OFF   ON   OFF   ON   OFF   ON   OFF   OFF   84    a e e      os   a  B4 B3 B2 B1  OFF  60   OFF   OFF   ON   ON    Network Node or Instance  Address Setting  OFF  from Node  1 to Node  127 maximum   OFF  OFF  Caution  Unit should be powered down before  changes can be made without damaging the MOD9200  AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 37 of 37    www workaci com  888  967 5224    
18. OMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 4 of 37   www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    II  BACnet Transceiver Installation  amp  Network Setup    a  Transceiver Installation  Choose a location close to the computer  network hub or RS485 loop   Mount the Transceiver on the wall using four  8 screws     24 VAC Input  500 mA nominal    Connect 24V AC 60 Hz  no secondary ground  to the  input terminals using 20 AWG wire as shown in the product data sheet     TCP IP  Connection  J2  Connection  J1   Default IP com Cs 00002   oom  Jumper i   Pagooocen  jhe    A Z ry  HI   LO Bias 1   Resistors    TERM Termination  Resistor       24 VAC noes  Terminals  Input  Figure 1    MSTP  RS485    Use 20 gauge shielded twisted pair wire to connect the Transceiver   Terminals A   amp  B   to the network  See Figure 1      Multiple RS485 Devices   If more than one RS485 device is used the devices should be     daisy chained    or    straight line connected    by connecting all the    A    wires to the    A     terminals and the    B    wires to the    B    terminals  Do not use spur lines or a star    configuration  AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 5 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    RS485 Terminating Resistor   If the MOD9200
19. R ID TRANS CHAN    0 Garage Exhaust Far        Assign a sensor transmitter to the data register by clicking in the  TRANSMITTER ID cell to open a drop down menu  This is the device ID of  the remote output devices  RD2402  amp  RD2432   Use the scroll bar to scroll  to the correct address  or automatically scroll to the address by typing the  hexadecimal address in the cell  To select the address click on the appropriate  ID in the drop down menu     E Editor    File Settings  REG ADDRESS GROUP NAME POINT NAME TRANS CHAN    0 Garage Exhaust Fan 3       Assign the appropriate digital or relay output    TRANS CHAN    to the data  register by clicking in the cell to open a drop down menu  Click on the  appropriate transmission channel  O1 to 04  to select     File Settings Points Row RegisterEntry Register Bank  REG ADDRESS GROUP NAME POINT HAME TRANSMITTER ID TRANS CHAN  0 Garage Exhaust Fan 3456       AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 17 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    The active transmission channels or output number are factory set as follows                       Device Digital Analog  RD2402 1 to 2 for relay  1 NA Wireless relay   and relay  2 output module  RD2432 1 to 4 for relay  1 1 to 4 for analog   Wireless digital  amp    to relay  4 output   to 4 analog output module             g  Analog Output  Holding  Register Conf
20. ccess the Product from only one computer at a  time     6  Limited Warranty   ACI WARRANTS THAT THE PRODUCT WILL OPERATE SUBSTANTIALLY IN ACCORDANCE WITH THE THEN CURRENT DOCUMENTATION  SHOULD THE  PRODUCT NOT SO OPERATE  YOUR EXCLUSIVE REMEDY  AND ACT S SOLE OBLIGATION UNDER THIS WARRANTY  SHALL BE  AT ACT S SOLE  DISCRETION  CORRECTION OF THE DEFECT OR REFUND OF LICENSE FEES PAID BY YOU FOR THE PERIOD DURING WHICH THE DEFECT WAS NOT  CORRECTED AND MATERIALLY AFFECTED THE OPERATION OF THE PRODUCT  ANY USE BY YOU OF THE PRODUCT IS AT YOUR OWN RISK  THIS  LIMITED WARRANTY IS THE ONLY WARRANTY PROVIDED BY ACI REGARDING THE PRODUCT  EXCEPT FOR THE LIMITED WARRANTY ABOVE  THE  PRODUCT IS PROVIDED  AS IS   TO THE MAXIMUM EXTENT PERMITTED BY LAW  ACI DISCLAIMS ALL OTHER WARRANTIES OF ANY KIND  EITHER  EXPRESSED OR IMPLIED  INCLUDING  WITHOUT LIMITATION  IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR  PURPOSE  ACI DOES NOT WARRANT THAT THE FUNCTIONS CONTAINED IN THE PRODUCT WILL MEET ANY REQUIREMENTS OR NEEDS YOU MAY  HAVE  OR THAT THE PRODUCT WILL OPERATE ERROR FREE  OR IN AN UNINTERRUPTED FASHION  OR THAT ANY DEFECTS OR ERRORS IN THE  PRODUCT WILL BE CORRECTED  OR THAT THE PRODUCT IS COMPATIBLE WITH ANY PARTICULAR PLATFORM  SOME JURISDICTIONS DO NOT ALLOW  THE WAIVER OR EXCLUSION OF IMPLIED WARRANTIES SO THEY MAY NOT APPLY TO YOU     7  Limitation of Liability   IN NO EVENT WILL ACI BE LIABLE TO YOU OR ANY THIRD PARTY FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES
21. f 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    Enter the new IP Address and Subnet Mask and click OK  The new IP Address will take  affect when the Config File 1s downloaded to the Transceiver     192 168 0 1 IP Address  255 255 255 0 Subnet    Router Setup  Webserver Only    1 37 168 0 254 Router IP Address    Forwarded Port    800  OF    Cancel         Our recommendation is not to change the default factory IP address of the  transceiver since the Ethernet connection is used to configure the transceiver  only and will not be required when the MSTP network is up and running     Router Setup     Webserver Only     NOT USE  Applicable for RM9500    WebLogger Setup ONLY  AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 7 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    d  Manually Resetting The Factory Default IP Address    The Transceiver can manually be reset to the default IP Address by moving the jumper   J6  from    Norm    to    Init        Turn off the power to the Transceiver  and move the jumper from    Norm    to    Init     Turn  on power  and the Transceiver can be communicated with using the Factory Default IP  Address 192 168 0 1 Subnet Mask 255 255 255 0  The Config File is no longer active  while the jumper is in the    Init    position   A new Config File can be downloaded to the  Transce
22. for all the input  and output data points  AIO1 100  BV01 50 and AVO1 50   Each point  utilizes 6 binary bits of information representing the alarm conditions of  the    Input Registers AI Object        Digital Output  Coil  Register BV  Object    and    Analog Output  Holding  Register AV Object        AV Object AI Object   Bit 5  amp  6   Bit 1  amp  2     000000  H     BV Object   Bit 3  amp  4     The Present Value of each register displays a decimal value representing  the alarm status of all 3 point types  Each point type returns an individual  alarm value in decimal format  All 3 point types decimal values are added  together to represent the status of the 3 alarm status     The decimal values of different point types are     The Input Register AI Object alarms       0Q     Normal                 Low Battery Alarm  Bit 1 set   a    2     Lost Communication Alarm  Bit 2 set       The Digital Output  Coil  Registers BV Object alarm        Q    Normal        8     Lost Communication Alarm  Bit 4 set       The Analog Output  Holding  Registers AV Object alarm       0    Normal       32     Lost Communication Alarm  Bit 6 set     Alarm Status Examples       Example 1     AI108 returns a value of 33 representing AI08  Low  Battery Alarm   BVO8  Normal   amp  AVO8  Lost Communication        Example 2     AI108 returns a value of 40 representing AI08   Normal   BVO8  Lost Communication   amp  AV0O8  Lost    Communication    AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasa
23. he Product  Rather  you have a license to use the Product as long as this License Agreement remains in full force and e_ect  Ownership of the  Product  Documentation and all intellectual property rights therein shall remain at all times with ACI  Any use of the Product by any other person  business  corporation   government organization or any other entity is strictly forbidden and is a violation of this License Agreement  You may not make more copies of the Product than speci_ed in this  agreement or allowed by applicable law  despite this limitation  publish the Product for others to copy  or rent  lease or lend the Product     4  Copyright  The Product and Documentation contain material that is protected by United States Copyright Law as well as other intellectual property law and international treaty provisions  All  rights not granted to you herein are expressly reserved by ACI  You may not remove any proprietary notice of ACI from any copy of the Product or Documentation     5  Restrictions   You may not publish  display  disclose  rent  lease  modify  loan  distribute  or create derivative works based on the Product or any part thereof  You may not reverse engineer   decompile  translate  adapt  or disassemble the Product  nor shall you attempt to create the source code from the object code for the Product  You may not transmit the Product over  any network or between any devices  although you may use the Product to make such transmissions of other materials  You may a
24. hernet connection    1OGB of hard drive memory available    c  Configuration Software Installation    Extract  or unzip  the ACI Programmer zip file and click start the    setup exe     program to install the program  Follow the on screen instructions to complete  the installation     AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 9 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    d  Creating A MOD9200 Configuration File    To create anew MOD9200 configuration file open the ACI Programmer by clicking on  Start  gt  Programs  gt  Trs Programmer 6 XX     File Settings Points Row RegisterEntry Register Bank          To open a new configuration table Click on File  gt  New Gateway File  A blank  configuration table will open     File Settings Points Row RegisterEntry Register Bank    REG FUNCTION REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT       The default startup is the Input Register configuration table and System Setup page     By clicking the    RegisterBank    tab  you can go to the Digital Output  Coil  register  configuration table or Analog Output Holding  Register configuration table     AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 10 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    e  Input Register Config
25. iguration    Select the Analog Output  Holding  Register table by clicking the     RegisterBank       tab         e ADDRESS GROUP WAME       0 Garage          First we will assign the REG ADDRESS by clicking in the cell  Before  entering register addresses  ensure the    RegisterEntry    AutoSet is turned off  as shown     File     Settings Points Row    PERPEN  Register Bank       REG ADDRESS GAROU Turn AutoSet ON B TRANSMITTER ID TRANS CHAN  Turn AutoSet OFF       Enter the Register address in the REG ADDRESS window  The valid range is    0 to 49     Eile Settings Points Row RegisterEntry Register Bank        REG 4DDRESS GROUP HAME       AUTOMATION COMPONENTS  INC    2305 Pleasant View Road  Middleton  Wisconsin 53562    www workaci com  888  967 5224    POINT NAME TRANSMITTER ID    Page 18 of 37    TRANS CHAN    Version   1 0  10000674    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    Again use the mouse to move to the next column  Enter a GROUP NAME  if  desired  for the data set by typing the group name in the cell   Enter the name in the cell by using the mouse to click on the next column     Note  DO NOT use commas or semicolons in the Group Name           T Editor      File Settings Points Row RegisterEntry Register Bank    REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN    0 Office West       Enter a POINT NAME  if desired  for the data point by typing the name in the  cell  Enter the name in the cell by using the mouse to click on the ne
26. iver if desired     To reactivate the Config File   turn off the power to the Transceiver and move the jumper  back to    Norm     Turn the power back on and the Config File will become active  The  Transceiver will have the IP Address that was set in the Config File        AUTOMATION COMPONENTS  INC Version   1 0    2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 8 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    III  Configuration Software    a  Configuration Software Description  The data registers of the Transceiver need to be configured prior to use     The configuration program    Trs Programmer exe    can be downloaded from our website     www workaci com     The download instructions are included in the shipping document  of the MOD9200 Transceiver  The software will be used to configure the 3 different type  of data registers as follows       Assign the Input Register function     Analog or Discrete     Assign wireless Digital Output  Coil  Register function     Assign wireless Analog Output  Holding  Register function    Assign the register address     Assign the Wireless Sensor ID and transmission channel     Assign the data type    The MOD9200 Transceiver can have up to 100  addresses O to 99  data registers   configured to be either Analog or Discrete  50 digital outputs and 50 analog outputs   b  System Requirements   PC  Notebook or desktop  with Windows 98  XP  Vista or Windows 7    Et
27. n be set to    hold  momentary contact closures long enough to be     picked up by the system        AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 30 of 37   www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration      The Digital Capture Time can be set up to 240 minutes  4 hours  in  applications where an extended period of time is needed such as     unoccupied period by pass          For data types  DATA FORMAT as described previously  THERM 20k   RTD 1k  RTD 1k Ext  and HUMIDITY  the analog data will be received  and stored as real values with one decimal position  1 e  82 5 F        For the data type  DATA FORMAT as described previously  ANALOG   the data will be displayed in counts  0 to 409 5   In applications where  WT2630Bs are used  The setpoint adjustment is represented as analog  value from 0 to 409 5  Heat position to Cool position on the setpoint  adjustment scale        For the data type  DATA FORMAT as described previously   TOTALIZER  the data is displayed in counts  24 bits  with a value of 0 1  representing one count  When the count reaches 1 677 721 5  24 bits  the  count value rolls over to O and begins again     The Present Value of BVO1 through BV50 objects will correspond to the  MOD9200 Digital Output  Coil  Register 0 through 49  For BVXX  XX    Trs MOD9200 Register Num   1        The BVO1 to BV50 Objects are used for command remote wireless  digital 
28. nt View Road 10000674  Middleton  Wisconsin 53562 Page 32 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration      Example 3     AI128 returns a value of 42 representing AI28  Lost  Communication   BVO08  Lost Communication   amp  AV0O8  Lost  Communication        Example 4     AI128 returns a value of 9 representing AI28  Low  Battery Alarm   BVO8  Lost Communication   amp  AV08  Normal      The MOD9200BNT Device Instance and MSTP MAC address will be  preset from the factory and can be obtained using the BACnet Device  Scan function  To ensure no duplication of Instance address  verify  that no other node with the same address is present at the sub net  where the MOD9200BNT will be residing     For more implementation information please refer to the BACnet website  www BACnet org or the ASHRAE  American Society of Heating  Refrigeration   amp  Air conditioning Engineers  website www ashrae org     AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 33 of 37    www workaci com  888  967 5224    MOD9000BNT BACnet Receiver Installation  amp  Configuration    V  Quick Setup Instructions    a  Configuration of the MOD9200BNT    1  Connect the Transceiver to the TCP IP network using RJ45 Category 5  Ethernet cable or a crossover cable  see Fig  1 page 4  to a notebook or a  desktop PC     2  Apply 24 VAC 60 Hz power to the input terminals of the Transceiver  The  Transceiver
29. outputs  relays  module i e  ED2402D  amp  the SD2432D devices   Values to be entered  or sent  is l on and O off       The BV51 through BV100 Objects will be automatically assigned by the  MOD9200BNT  These 50 registers objects will display the status of the  relays commanded via the previous BV1 thru BV50 objects  After the  remote unit executed the command issued by the MOD9200  It will send  a feedback status of the relays to the MOD9200     The Present Value of AVOI through AV50 objects will correspond to the  MOD9200 Analog Output  Holding  Register 0 through 49  For AVXX  XX    Trs MOD9200 Register Num   1        The AVOI to AV50 Objects are used to command remote wireless analog  outputs  0 10VDC or 0 5 VDC  module such as the SD2432D devices   Value to be entered  or sent  is from 1 0 to 100 0 representing the  percentage of full output range       The AV51 through AV100 Objects will be automatically assigned by the    MOD9200BNT  These 50 registers objects will display the status of the  analog output commanded via the previous AV1 thru AV50 objects  After    AUTOMATION COMPONENTS  INC Version   1 0    2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 31 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    the remote unit executed the command issued by the MOD9200  It will  send a feedback status of the analog output value to the MOD9200     The AI101 through AI200 Objects are the alarm registers 
30. r possession or under your control  ACI may terminate this License Agreement for any reason  including  but not limited to  if ACI _nds that you have  violated any of the terms of this License Agreement  Upon noti_cation of termination  you agree to destroy or return to ACI all copies of the Product and Documentation and to  certify in writing that all known copies  including backup copies  have been destroyed  All provisions relating to con_dentiality  proprietary rights  and non disclosure shall survive  the termination of this Product License Agreement  Additionally  it is understood that termination of this Agreement will not e_ect a refund of any license fees paid or owed to  ACI     10  General   This License Agreement shall be construed  interpreted and governed by the laws of the State of Wisconsin without regard to con_icts of law provisions thereof  The exclusive  forum for any disputes arising out of or relating to this License Agreement shall be an appropriate federal or state court sitting in the State of Wisconsin  USA  This License  Agreement shall constitute the entire Agreement between the parties hereto  Any waiver or modi_cation of this License Agreement shall only be e_ective if it is in writing and  signed by both parties hereto  If any part of this License Agreement is found invalid or unenforceable by a court of competent jurisdiction  the remainder of this License Agreement  shall be interpreted so as to reasonably e_ect the intention of the parties   
31. res contig LON 6 3 ini File Hame    TCP IP    E 932 168 0 1 IP Address TCP IP oO    Comm Status     Disconnected    Connect   Disconnect      FR Fie Status    fle tne   cancel         Click on    Connect    and the status of the connection will be displayed in the  Comm Status window  When the Transceiver is connected click on    Send  File    to the send the config file to the Transceiver     AUTOMATION COMPONENTS  INC Version   1 0    2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 27 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    l  Activating The Config File    Once the config file has been sent to the Transceiver it will become active  immediately  If you have changed the IP Address in the config file you will  lose your connection and have to reconnect using the IP Address and Subnet  Mask that was sent in the new config file     Bitten  a         C 4trs contig _LON 6 3_im File Name    TCP IP    f 932 168 0 1 IP Address TCP IP o    Comm Status    Disconnected    Connect   Disconnect      File is ready to be sent File Status     a       To confirm that the appropriate configuration file is saved on the Transceiver      reopen the File Transfer Dialog and click on    Get File    to retrieve a copy of the  active configuration file from the Transceiver  The Editor will automatically save  this file in the folder    trs    with the file name of     _config ini        Click on File  gt  Open Config
32. rican Society of Heating  Refrigerating and Air   Conditioning Engineers  ASHRAE  and adopted shortly after its creation as a  standard by the American National Standards Institute  ANSI      The BACnet standard defines a protocol for transmitting messages between  various devices in a Building Automation or Control System  The standard  also specifies the networks over which these messages are exchanged     o BACnet Ethernet  amp  BACnet IP     Utilizing standard LAN technology    o BACnet MSTP  Master Slave Token Passing      relies on the EIA 485  serial communication signaling standard     o BACnet PTP  point to point      For temporary connections between  Devices    b  MOD9I200BNT BACnet Transceiver Parameters    The MOD9200BNT Transceiver BACnet MSTP device communicating at  76800BPS  It receives data from up to fifty  50  wireless sensors and updates  its data registers on a real time basis     BACnet Object Types Supported     AI  Analog Input  Objects     AIO1 to AI200  BV  Binary Value  Objects     BVO1 to BV100  AV  Analog Value  Objects     AVO1 to AV100    The Present Value of AI01 through AI100 will correspond to the MOD9200   data register 0 through 99  For AIXX  XX   Trs MOD9200 Register Num     1       All wireless sensor information  analog and discrete input  will be  displayed as numeric values       All digital status alarms will be received and stored by MOD9200 as 1 or  O  1 input contact closed  amp  O input contact open   The Digital Capture  Time ca
33. rop down menu  Select the appropriate function     ENTLY EDITING INPUT REG    6 SENSOR_CNTRL     _SENSOR_CNTRL      AUTOMATION COMPONENTS  INC  2305 Pleasant View Road   Middleton  Wisconsin 53562  www workaci com  888  967 5224    POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT       Version   1 0  10000674  Page 11 of 37    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    Use the mouse to move to the next column to assign the REG ADDRESS by clicking in  the cell  Before entering register addresses  ensure the    RegisterEntry    AutoSet is turned  off as shown            File Settings Points Row Register Bank    REG FUNCTION REG A Turn AutoSet ON Bg POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT  ANALOG_INPUTS Turn AutoSet OFF loor Conf Am A         Enter the Register address in the REG ADDRESS window and press down arrow to  enter        File Settings Points Row RegisterEntry  pee REGADDRESS  GROUP NAME POINT NAME TRANSMITTER ID   TRANS CHAN DATA FORMAT       Again use the mouse to move to the next column  Enter a GROUP NAME for the data set  by typing the group name in the cell  Enter the name in the cell by using the mouse to  click on the next column     Note  DO NOT use commas or semicolons in the Group Name        ANALOG INPUTS 0  5th Floor       Enter a POINT NAME for the data point by typing the name in the cell  Enter the name  in the cell by using the mouse to click on the next column     Note  DO NOT use commas or semicolons in the Point Name   
34. s save the configuration file to the folder    trs    before sending it to the  MOD9200 Transceiver     AUTOMATION COMPONENTS  INC  2305 Pleasant View Road   Middleton  Wisconsin 53562  www workaci com  888  967 5224    Version   1 0  10000674  Page 25 of 37    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    To send the new configuration file to the MOD9200 Transceiver click on  File  gt  File Transfer and a dialog box will appear     rEntry Register Bank  New Gateway File GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT  Open Gateway File 1 THERM 20k  2 HUMIDITY  1 THERM 20k  1 THERM 20k  File Transfer 1 THERM 20k    Exit 1 THERM 20k       C  trs contig LON  B3 im File Name    TCP IP     192 168 0 1   IP Address CPAP  amp   Comm Status  Connect   Disconnect    FFilistesdptobesent File Status    Get File  returned as Cend File Cancel  c 4tre contig   _config ini       Click on    Select File    and a window will open  Move to the Trs directory and  select the appropriate file from the list     Click on    Open    to automatically enter the selected file path as the File Name     AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 26 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    Enter the current IP Address of the Transceiver  Note  This can be different  than the IP Address entered into the configuration file             p x W    C 4t
35. sssssccccssssssssssssccccscssssees 10  e  Input Register Configuration         ecsccccecccssssssssscccececececoosossssssssesssececececossssssssssssoe 11  f  Digital Output  Coil  Register Configuration        ssscssssscececcccssssceccoccsssssseeeesosssse 15  g  Analog Output  Holding  Register Configuration         sssscececcccssssssececoccssssseceeooo 18  h  Setting the Mesh Network ID for the repeater router devices          eescssosssss000  20  Ds WV LISCOMAINCOUS MeMo ea E E 21  j  Configuring The Transceiver For MSTP  RS485  Network             cccccccsssssees 23  k  Sending The Configuration File To The MOD9200                     cccssssssssscscees 25  LAct  vatne Phe Conie File sassecsessiccicestusetusearacsnsaioasctsdssetecvanstacdeiutecesdsisticatisescsanets 28  EN PACA AX COMISIOIONN r E NS 30  PBASE geses veins stecnaternsdcduevacseitescaceonsateccatennadsdesatasestesesveuntetaaeataesstseeeatices 30  b  MOD9200BNT BACnet Transceiver Parameter                ccccsssscsssccccsssssssseees 30  Yy Quick Setip PIISOTU CLIOIG  ceccceencessacenscecccetusasscanceescweessteuseseavscusesstessesbaeseceenssusaesaersesueeateast 34  a  Configuration of the MOD9200BNT               ssssssssscccccccsssssscssccccccccsssssssscscsoses 34  b  Installing the MSTP  RS485  Network                 ssscsccsssssssssssssscccccccccsssssssscccsssssesees 34  AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 3 of 37    www workaci com  88
36. uration    Each row of the configuration table is a unique data register having eight    special attributes     REG FUNCTION    REG ADDRESS    GROUP NAME    POINT NAME    TRANSMITTER ID    TRANS CHAN    DATA FORMAT    LOG       Identifies the function of the register     Analog or Digital   Discrete  Note  If selecting the Digital  Discrete  function  be sure to set the appropriate Digital Capture Time  Page 15        Assigns the address of the data register  0 to 99         Assigns a group name to the data register  not used by  BACnet   Multiple data registers can have the same group  name  This is useful for monitoring and data logging  programs        Assigns a unique name to the data register to help identify  the location of the sensor transmitter  Not used by BACnet    Multiple point names can have the same group name        Assigns a wireless sensor transmitter address to the data  register  Each wireless sensor is factory configured with a  unique hexadecimal address        Assigns a wireless sensor transmitter data channel to the data  register  A wireless sensor transmitter may have up to four   4  analog channels and  4  digital status alarm channels        Assigns the data type to the register     temperature  RTD or  Thermistor 20K   analog voltage  totalizer or humidity  This  register is left blank if the REG FUNCTION is Digital   Discrete         Not used for MOD9200LON    First we will assign the REG FUNCTION by clicking in the REG  FUNCTION cell to open a d
37. utput module                   h  Setting the Mesh Network ID for the repeater router devices    w    Unit Identifier     POINT NAME TRANSMITTER ID   TRANS CHAN    TCP IP Transport    Network ID       e a    The mesh network ID of the MOD9200 Gateway can be set to specific  network   from   to 64  The MOD9200 functions as a network coordinator   Any repeater router that has the same network ID will be able to communicate  and channel sensor information to the MOD9200    AUTOMATION COMPONENTS  INC Version   1 0    2305 Pleasant View Road  Middleton  Wisconsin 53562    10000674  Page 20 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    i  Miscellaneous Menu    The transmitter timeout interval  default temperature degrees  C F   and  Digital Input Capture Time are set globally for all sensors using the    Miscellaneous Dialog Screen     Click on Settings  gt  Miscellaneous    Unit Identifier  _  POINT NAME TRANSMITTER ID      Vv _ Serial Transport sunshade  TCP IP Transport  Network ID    Miscellaneous                TRANS CHAN    Set the transmitter transmission timeout interval  requires a minimum of  30 min   by clicking in the Transmitter Timeout cell to open a drop down  menu  Use the scroll bar to scroll down to the appropriate value  1 to 60 min    or type the value in the cell to automatically scroll to the appropriate value   This will be used to generate an error message if the transmitter fails to    transmit in
38. xt  column     Note  DO NOT use commas or semicolons in the Point Name    File Settings Points Row RegisterEntry Register Bank      REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN  O Office Wrest SunShadel       Assign a sensor transmitter to the data register by clicking in the  TRANSMITTER ID cell to open a drop down menu  This is the device ID of  the remote output devices  RD2432   Use the scroll bar to scroll to the correct  address or automatically scroll to the address by typing the hexadecimal  address in the cell  To select the address click on the appropriate ID in the  drop down menu     File Settings Points Row RegisterEntry Register Bank      REG ADDRESS GROUP HAME POINT NAME TRANSMITTER ID TRANS CHAN  39E    O Office Wrest Sunshade       AUTOMATION COMPONENTS  INC Version   1 0  2305 Pleasant View Road 10000674  Middleton  Wisconsin 53562 Page 19 of 37    www workaci com  888  967 5224    MOD9ON00BNT BACnet Receiver Installation  amp  Configuration    Assign the appropriate digital or relay output    TRANS CHAN    to the data  register by clicking in the cell to open a drop down menu  Click on the  appropriate transmission channel  01 to 04  to select        The active transmission channels or output number are factory set as follows                 Device Digital Analog  RD2402 1 to 2 for relay  1 NA Wireless relay   and relay  2 output module  RD2432 1 to 4 for relay  1 1 to 4 for analog   Wireless digital  amp    to relay  4 output   to 4 analog o
    