1. HORE C e CR CRUCE hd 29 6 1 1 Meaning ofideograms EM e Ra es RR nce x ees a Rp D RR 30 6 1 2 Meaning Orie Dar 460 qd e eC do dr de qe d dod es dt e 32 O LO MIIWGBO el ues cae hase eh Oboe e Heed eee EOLA 32 6 2 Mimic panel concentrator isses es 41 6 2 1 Keyboard bloking BIBOBOUIBo x un X X cem pass d eu EX Xx tO We E Ed 41 2 socomec Innovative Power Solutions UPS IOMMASGPXX01 GB 00 5 INDEX MASTERYS Green Power 10 40 kVA 7 OPERATING PROCEDURES 4 15 etra odor dert te Re e ehh HE e aec 42 n Wb Ne ROUTER 42 42 Ta Extended outo SEI VICE 42 7A Switching onto manual HL REGS IEEE EL A E 43 7 5 Returntonormalmode RR he RRS ca RR RR aa d 43 75 Emergency s ua dds theo F3 0 TERT C HC dh vob SOS e EE teres 43 8 COMMUNICATION Z su e e t Aleta gd ee a Ce UR Tu E EROR E A 8 1 Multi Level COCHE OR D oon nasua rbi EE 45 lt ib e uc E e IPAS asa 45 822 Description of the functions available nonna ee mnn 46 8 3 AccessoriesandSWoptions RARO RU RR RR ROC RO
2. 4 MODES OF OPERATION MASTERYS Green Power 10 40 kVA 4 1 ON LINE OPERATIONS A special feature of the MASTERYS series is the ON LINE double conversion feature in conjunction with low dis tortion mains power absorption With ON LINE mode the UPS is able to supply a voltage that is fully stabilised in frequency and amplitude regardless of any interference in the mains power supply within the most stringent clas sification of UPS regulations ON LINE operation provides three operating modes according to mains and load conditions Normale mode This is the most frequent operating condition the energy is drawn from the primary mains power supply and is converted and used by the inverter to generate the output voltage to power the loads connected The inverter is constantly synchronised in frequency with the auxiliary mains to enable load transfer due to an overload or inverter shutdown without any break in the power supply to the load The battery charger supplies the energy required to maintain or recharge the battery Bypass mode In case of inverter failure the load is automatically transferred onto the auxiliary mains without any interruption in the power supply This procedure may occur in the following situations in the event of a temporary overload the inverter continues to power the load If the condition persists the UPS output is switched onto the auxiliary mains via the automatic bypass Normal operation
3. 5 8 IOMMASGPXX01 GB_00 either adequate neutral switching or protection system socomec Innovative Power Solutions UPS 10 OPTIONS MASTERYS Green Power 10 40 kVA 10 9 ADC CARD WITH TEMPERATURE SENSOR This card can be used to manage up to four normally closed or normally open outputs and up to three digital inputs in configurable mode If more than one ADC card is used simultaneously the dip switch configurations must be different 10 10 PROFIBUS On request the UPS can be provided with a Profibus protocol converter installation software configuration softwa re and user manuals If the RS232 485 serial connector is installed on the mimic panel it should be disabled 10 11 GSM MODEM Enables sending of SMS messages regarding the equipment s operating status ENGLISH 10 12 SERIAL CONNECTION PCB serial RS232 connector DB9 and an isolated RS485 connector are available on the card RTX4 and 10 13 MANAGEMENT OF EXTERNAL MANUAL BY PASS CONTACT Allows management of on off indication for the external manual by pass isolating switch socome Innovative Power Solutions UPS IOMMASGPXX01 GB_00 59 er v 2 TECHNICAL SPECIFICATIONS MASTERYS Green Power 10 40 kVA 10 15 20 30 40 Input Output phases 3 land3 3 3 1and3 3 3 1 3 3 3 3 33 Electrical specifications Input 10 15 20 30 40 Mains voltage 3P N 400 V 209 15 up to 35 97096 of nomina
4. If your system uses a generator connect the generator set ready no potential contact to connector IN 2 on the optional ADC PCB configured in standard or power safe mode see paragraph 10 1 This automatically extends the voltage and frequency value range when power is supplied by the generator set 3 7 EXTERNAL E S D CONNECTION A remote emergency shutdown system E S D can be installed by means of the optional ADC PCB see paragraph 10 1 Connect a normally closed zero potential contact to terminals IN1 and IN1 of the ADC PCB 3 8 ISOLATION TRANSFORMER The MASTERYS model of the MASTERYS range is fitted with an internal isolation transformer If an external isolation transformer cabinet is required the following instructions should be followed Refer to chapters 2 and 3 of this manual for indications on moving and installing the cabinet See paragraph 34 for details about protections The protection cable marked with the ground symbol is connected directly to the distribution panel The transformer can either be connected to the UPS input or output ENGLISH The UPS must not operate without the neutral connection to the input The transformer cannot be connected to the output on single UPS unit connected in parallel con figuration For details of the connections refer to the transformer terminal board diagram socome Innovative Power Solutions UPS IOMMASGPXX01 GB_00 1 9 UNPACKING AND INSTAL
5. 59 0 13 Management of external maual by pass aaa n 59 TEGEINICALSPECIEICATIONS es car eaea e aaa Re US 60 gt 4 IOMMASGPXXO01 GB 00 Innovative Power Solutions UPS CERTIFICATE AND CONDITIONS MASTERYS Green Power OF WARRANTY 10 40 KVA This SOCOMEC UPS continuous power system is guaranteed against any manufacturing and material defects The period of validity of the warranty is 12 twelve months from the date of commissioning if said activation is carried out by SOCOMEC UPS personnel or personnel from a support centre authorised by SOCOMEC UPS and not however more than 15 fifteen months from the date of shipment by SOCOMEC UPS The warranty is recognized within national territory If the UPS is exported out of national territory the warranty shall be limited to the cover of the parts used to repair the fault The warranty is valid ex works and covers labour and parts used to repair the fault The warranty shall not apply in the following cases Failures due to fortuitous circumstances or force majeure lightning floods etc Failures due to negligence or improper use use out of tolerance temperature humidity ventilation electric pow er supply applied load batteries Insufficient or inadequate maintenance Attempted maintenance repairs or modifications not carried out by SOCOMEC UPS personnel or personnel from a support cen
6. Consult the on line guide for details about the various icons The graphics interface shows a number of icons each of which is associated to a specific function P Connection to the www socomec com web site Regularly check the news that the SOCOMEC group lt publishes on the site so as to take full advantage of the MASTERYS unit UPS information Serial number type power etc Alarm present shows the alarms table this icon appears when the UPS detects an anomaly Generator operating mode this icon appears when the UPS is powered by the generator NY Technical support department e mail address This connection opens the e mail program and automati cally fills in the addressee and subject lines amp w Information on the network interface a help page in html is loaded 8 2 2 2 Menu bar The menu bar displays links to html pages that provide detailed information on the unit and describe how to con figure special options 8 2 2 3 List of alarms Shows the list of alarms present in table form 8 2 2 4 Statistics The counter folder shows the number of events that have occurred over a given period of time The average minimum and maximum values of a measurement can be seen by clicking on the measurement folder A sampling time from one to 10 weeks can be set by clicking on the period folder 8 2 2 5 UPS management The commands folder shows the commands that can be sent to the UPS
7. P RR ROO 20 SOV Genera 20 SOF THU TRE 20 39 3 Power connections 4 ia x ep dorem ep dob ag Reed 20 394 Control AGS ER Robb Kick ERU au dn bd 22 3 10 External battery cabinet 23 4 MODES OP OPERATION 5 eiae da Eh Re he d hd e e Re 0 s CC 24 AFON UNE ena Re dp Rr XE Y Recap o ERE Hp GG UY k See ees 24 42 Operation in high efficiecy TOU u sae i Sepe Y Y Gu CER Y G Y Ed CRY Re eda 24 4 3 Operation with manual maintenance bypass 25 44 Operation with external manual 2 25 45 Op rati min gas ci s peto dee Erbe PEER br eR PRX pied 26 46 Energy Saver WOE qwe E CLEP SOE EO PE Codd es drea 26 5 ACCESS TO CONTROLS AND COMMUNICATION INIERFACES II 27 5 1 Identifying the switches and 27 52 Functions sana ooo oe V bd dois oda ved VA eo ecd 28 read dew AE e oet n ER Re obe edo e Lo Ce go BOG 29 b L Advanced Mimic Paneles uos gt
8. The equipment houses electrolytic capacitors used in the rectifier and inverter section and filtering capacitors used in the output section whose life is dependent on using and environmental conditions The average expected life of these components is shown below Electrolytic capacitors 5 years Filtering capacitors 7 years In any case the effective state of the components is verified during preventive maintenance socome 54 IOMMASGPXX01 GB_00 Innovative Power Solutions UPS 10 MASTERYS Green Power 10 40 kVA Legend C1 Serial connector RS232 485 C2 serial connector RS232 for Modem C3 LAN connector RJ45 for Ethernet S1 Options slot 1 S2 Options slot 2 ENGLISH 10 1 ADC CARD Up to two cards can be installed per UPS in a vacant slot 1 or S2 The card enables configurable management of up to four normally closed or normally open outputs and up to three digital inputs Two dip switches allow the selection of up to four operating modes Standard Power Safe Security and Environmental which can be used to manage the following events battery low or imminent stop battery discharging ESD and ESD activation external alarm A39 external alarm A40 external alarm In2 general Alarm isolation controller management of energy consuption overheating overload loss of redundancy power safe plug 1 power safe plu
9. so as not to remove the power supply from the load or in the event of a serious failure while waiting for the equipment to be repaired Activate the procedure COMMANDS gt IMMEDIATE COMMANDS gt BYPASS PROCEDURE e Carry out the operations indicated on the mimic panel If there is an external manual bypass carry out the procedure described above before activat ing this switch 7 5 RETURN TO NORMAL MODE e Put switch Q2 into position 1 mains e Wait for the mimic panel to switch on Activate the procedure COMMANDS gt IMMEDIATE COMMANDS gt START PROCEDURE e Carry out the operations indicated on the mimic panel AN If there is an external manual bypass put the switch to position OFF 7 6 EMERGENCY SHUTDOWN E S D Should it be necessary to interrupt the continuous power supply provided by the UPS quickly emergency shut down this can be done by putting switch Q3 to position 0 or where applicable by activating the emergency button switch connected to the ADC PCB The UPS output can only be electrically disconnected by means of Q3 N If the UPS is operating from the manual bypass Q5 in position 1 with mains present the emer gency shutdown does not interrupt the power supply to the load In emergency conditions all the power supplies upstream of the UPS must be disconnected ive Power Solutions UPS IOMMASGPXX01 GB_00 43 ENGLISH e v 2 8 COMMUNICATION MASTERYS
10. 2 of this manual and paragraph 4 5 3 of the EN62040 1 1 2003 11 standard The label is supplied with the system The back feed protection device may be built into the system only on specific request or an electromechanical switch may be installed externally in the input of the UPS If the UPS incorporates this protection proceed with the connections as described in paragraph 3 5 of this manual To install the external back feed protection it is necessary to use the BKF card and an external electromechanical switch that should be installed For further information on the connection and the type of remote switch please read paragraph 10 9 of this manual XL a er v ATTENTION N The neutral is not disconnected as even in the event of a single fault on the UPS it never has high po tential when the mains and or auxiliary power supplies are disconnected upstream This is to prevent transformation of the power source to the UPS every time there is a power failure If in certain anomaly states or because of the installation upstream e g undetected and protec ted earth fault or high leakage in a phase or with IT systems there is a hazardous potential on neutral a suitable isolating switch must be provided on the neutral as well or else there must be a detection signalling and protection system NOTE N For equipment with separate Emergency Mains the neutral of the Emergency Mains line must be electri call
11. DISABLE CHECK UP Deactivates the periodic maintenance message visible only if alarm A44 is present S0comec 36 IOMMASGPXX01 GB 00 Innovative Power Solutions UPS 6 MIMIC PANEL MASTERYS Green Power 10 40 kVA 6 1 3 4 Parameters menu Displays only the configuration parameters set for the UPS The messages in this menu are identified by an asterisk in the configurations service menu The parameters can only be changed by entering the service configurations menu CURRENT DATA menu Message Description SINOTTICO dentifie the size the phases configuation input and output and the serial number SN 0000000000 of the UPS FW XXXX LAN SINOTTICO MAC ADDRESS dentifie the mac addres of LAN PCB T XX XX XX XX XX FW X XX UO SCHEDA DIGITALE dentifie the micro prosessor software version 5 UP RV000 CKS 0000 dentifie the mac addres of LAN PCB DSP RV 000 CKS 0000 6 1 3 5 Service menu This is used to change the configuration parameters insert the warranty activation code and display the service code Activation code menu During activation of the equipment a warranty activation code made up of four characters is requested to com plete the start up procedure The activation code is provided directly by the reference Support Centre upon communication of the serial number MANUFACTURER WARRANTY VALIDATION PLEASE INSERTTHE CODE ofthe equipment which
12. Green Power 10 40 kVA 8 1 MULTILEVEL COMMUNICATION MASTERYS is able to manage a variety of serial contact and Ethernet communication channels simultaneously The various PCBs and signalling accessories are inserted in the two standard communication slots This gives MASTERYS immediate interfacing and integration flexibility as soon as the unit is installed with no need for trained personnel The table below lists the possible connections between the communication channels and external devices 5 communication levels Slot 1 Slot2 5 232 485 RS232 RJ4510BT E service via Web required CTS 112V ot connected 12V w ADC card GSS card NetVision card 2 o E 4 UniVision pro i Legend pin RS232 485 C1 Legend pin Modem C2 Remote Panel 1 Not connected 1 Reserved BMS e e e 2 RX for RS232 2 RX for RS232 odem 6 3 TX for RS232 3 TX for 4 Data 4 Reserve LAN ethernet 5 GND for RS232 5 GND for RS232 Building Management System 6 Data 6 Notconnected Ethernet adapter with Web SNMP 10 100Mb functions 7 Reserved 7 RIS 8 8 9 9 For T service via telephone network By jbus tunnelling on TCP IP As each channel is independent simultaneous connections can be made to satisfy the different levels of signalling and remote monitoring See the options paragraph to access the detailed functions of the PCBs installed in the slots N Please note that
13. NiCd in a branch BATTERY RECHARGE ndicates the maintenance voltage value per cell 2 10 2 50 1 25 1 55 for NiCd FLOATING VOLTAGE BATTERY RECHARGE ndicates the second level recharge voltage value 2 20 2 50 1 25 1 70 for NiCd LEVEL TWO VOLTAGE BATTERY RECHARGE ndicates the current threshold in of C10 to pass 12096 FLOATING from maintenance voltage to recharge voltage BATTERY RECHARGE ndicates the current threshold in 96 of C10 to pass 122096 RECHARGE FLOATING from recharge voltage to maintenance voltage lt BATTERY RECHARGE ndicates the battery commissioning voltage 2 20 2 70 1 25 1 70 for NiCd FORMING VOLTAGE value 91 A SOCOmec 3 8 IOMMASGPXX01 GB 00 Innovative Power Solutions UPS MASTERYS Green Power 10 40 kVA 6 MIMIC PANEL CONFIGURATIONS menu A Parameter Description Allowed values BATTERY RECHARGE Indicates the battery commissioning current value 10 20 1 20 for NiCd FORMING CURRENT BATTERY RECHARGE Sets the equalisation voltage value 2 20 2 50 EQUALISATION VOLTAGE BATTERY RECHARGE Sets the recharge voltage compensation value YES NO TEMP COMPENSATION according to the battery temperature not present with external battery cabinets BACKFEED TYPE Sets the type of backfeed protection DISABLE 1 BYPASS T 2 BYPASS INPUT ALONE lt 3 BYPASS INPU
14. The setting folder shows the parameter settings on the UPS 8 2 2 6 Change language Click on the relative flag to choose a different language If the desired language is not listed see if itis downloadable from the www socomec com web site Refer to the chapter on software updating for instructions on how to install a new language socome Innovative Power Solutions UPS IOMMASGPXXO01 GB 00 47 ENGLISH a mr J 2 8 COMMUNICATION MASTERYS Green Power 10 40 kVA 8 2 2 7 Local network Enable the user to modify the network communication parameters Dynamic IP address if enabled the IP address is automatically assigned by the network server Static IP address the address is used if the dynamic IP address is disabled Network mask this is used if the dynamic IP address is disabled Gateway the gateway address used to send TCP IP data out of the local network Password allows the user to change the password to access the html To authorise access only to users that have a password Insert the new password and write it down in case of need JBUS TCP IP Port used to accept a JBUS frame through LAN tunnelling Client JBUS IP address to be authorised if a specific IP address is inserted in this box then only that address user will be able to access the html pages If the address 0 0 0 0 is used all the PCs on the network will be able to access the supervisor one client at a time If t
15. and their functions The displays are organised into menus and submenus as shown in the figure 6 1 3 1 to access a menu press the ENTER key to return to the higher level press ESC key Use the UPA and DOWN v keys to scroll the information available at each level When the UPS is connected in parallel the mimic panel shows the system information as if it were a single UPS Select the UPS number to display information on the individual units Legend A Current menu B Active sub menu C Additional values or information D Scrolling contextual help line E Scroll bar F Statistical graphics display 2 Socomec 32 IOMMASGPXX01 GB 00 Innovative Power Solutions UPS 6 MASTERYS Green Power 10 40 kVA MAIN SYSTEM 1 ALARMS 1 1 ACTIVE ALARMS Nm 1 2 EVENT LOG 2 MEASUREMENTS 2 1 PRESENT MEASURES m 2 2 STATISTICS am 3 2 EXTENDED COMMAND 4 PARAMETERS 4 1 PRESENT CONFIG 4 2 PRESENT DATA 5 SERVICE 5 1 COMMISSIONING 6 HYSTORY 6 1 HISTORY LOG 5 2 SETTING I 3 COMMANDS 3 1 IMMEDIATE COMMAND I I I I I I I I l l l l l l l 1 4 5 3 SERVICE CODE 1 1 1 I 1 I I I I MODULE 1 1 ALARMS 1 1 ACTIVEALARMS y 4 MODULE 2 2 MEASUREMENTS 2 1 PRESENT MEASURES MODULE 3 3 COMMANDS 3 1 IMMEDIATE COMMAND MODULE 4 MODULE 5 4 PARAMETERS 4 1 PRESENT C
16. for adequate ventilation see figure 3 3 1 The UPS switches are accessed from the front however a space of at least 1 5 metres should be left at the front of the UPS for maintenance purposes It is also recommended to ensure that the cable connections are sufficiently long and flexible so that the unit can be extracted during maintenance see figure 3 3 2 fitis not possible to leave sufficient space at the front adequate access must be ensured from both sides a mr J MASTERYS MASTERYS MASTERYS UPS OR UPS OR UPSOR MASTERYS MASTERYS OTHER OTHER OTHER UPS UPS CABINET CABINET CABINET socomec UPS IOMMASGPXXO01 GB 00 Innovative Power Solutions UNPACKING AND INSTALLATION MASTERYS Green Power OF THE UNIT 10 40 3 4 ELECTRICAL REQUISITES The installation and the system must comply with national plant regulations The electrical distribution panel must have a protection and sectioning system installed for the input mains and the auxiliary mains If a differential switch is installed on the mains power switch optional it must be inserted upstream from the distribution panel The table below show the size of the input protection devices recommended for correct installation Size of the input protection devices UPS Magneto thermal Magneto thermal Differential Input Output Battery Battery input Aux Mains input cable core size cable core s
17. for the application indicated by SOCOMEC UPS is granted to the recipient of such document All reproduction modification dissemination of this document whether in part or whole and by any manner are expressly prohibited except upon Socomec s express prior written consent This document is not a specification SOCOMEC UPS reserves the right to make any changes to data without prior notice The unit must be installed and activated only by qualified technical personnel and authorised by SOCOMEC UPS The UPS MUST only be moved by two people at least The people MUST take position at the sides of the UPS with respect to the direction of movement The unit must remain in a vertical position in all circumstances Connect the PE ground conductor first before you make any other connection Do not expose the UPS to rain or liquids in general Do not introduce external bodies Ifthe UPS is not equipped with automatic sectioning against back feed or if the switch is external to the UPS affix a label bearing the following words on all the external switches of the UPS power supply ISOLATE THE UPS BEFORE OPERATING ON THIS CIRCUIT Keep this manual handy for future consultation If the unit fails it must be repaired only by authorised technicians that have been specially trained for this pur pose This equipment conforms to the European Community directives for professional equipment and bears the ap proval mark C The UPS
18. is displayed in the next message by pressing ENTER Inserting the code does not limit the availability of the equipment functionality SEE INSTALLATION MANUAL FOR PROCEDURE SN 0000000000 When contact is made with the Support Centre for the activation code detailed information can be obtained on the UPS functions available and on the periodic preventive maintenance programmes Once the code is obtained enter it by pressing ENTER to activate the entry two asterisks will appear Select the first character with the UPA and DOWN V keys and confirm with ENTER to accept the character Then move on to the next character Pressing the ENTER key after selecting the fourth character activates code SEE INSTALLATION MANUAL FOR PROCEDURE CODE An error message is displayed if the code is incorrect Check that the code displayed corresponds to the one pro vided by the Support Centre and repeat the procedure socomec Innovative Power Solutions UPS IOMMASGPXX01 GB_00 37 xL ol 2 6 MIMIC PANEL Configurations menu MASTERYS Green Power 10 40 kVA This is used to change the configuration parameters Press ENTER Access is via the password MAST which is keyed in by using the UP A and DOWN YV keys and ENTER to go on to the next letter Note Column A shows whether the parameter is visible in the PARAMETERS CONFIGURATIONS menu CONFIGURATIONS menu A Parameter D
19. requires three phase plus neutral input connections 3P N Do not connect the output neutral to ground The UPS does not modify the neutral arrangements of the system the use of an isolation transformer is required should it be necessary to modify the neutral arrangements down stream of the UPS Before connecting any external battery cabinet ensure that it is fully compatible with the model of UPS it is to be used with The use of external battery cabinets not supplied by the manufacturers is not recommended Switch off and isolate the UPS and then wait for 5 minutes before removing the protection panels in order to carry out work on parts under dangerous voltage Danger of explosion if the batteries are replaced with others of the wrong type Replaced batteries must be disposed of at authorised waste disposal centres SOCOmecC UPS 6 IOMMASGPXX01 GB_00 Innovative Power Solutions 2 SAFETY MASTERYS Green Power 10 40 kVA It is very dangerous to touch any part of the batteries as there is no isolation between the batter ies and the mains power source The product you have chosen is designed for commercial and industrial use only In order to be used for particular critical applications such as life support systems medical applications commercial transportation nuclear facilities or any other application or systems where product failure is likely to cause substan tial harms to person or property the prod
20. stand by are not using any power while the active units with a high load are operating at maximum productivity When the load increases the units in stand by are immediately reactivated to guarantee continuous power supply Monitoring the hours of operation means that the hours are distributed on all the UPS alternating the units that are shut down from time to time This prolongs the life of the units and reduces the risk of failure Load sharing Load sharing Energy Saver load rate load rate A socome 26 IOMMASGPXX01 GB_00 Innovative Power Solutions UPS ACCESS TO CONTROLS MASTERYS Green Power AND COMMUNICATION INTERFACES 10 40 kVA This chapter identifies the electromechanical switches described below and used for start up shutdown and maintenance bypass procedures Access to the control area is from the front by opening the upper door using the red handle as shown in figure 5 1 The control area also contains the communication interface connectors and the slots for the optional sig nalling cards Please refer to the relevant chapter for more details on the connection and use of the related communication interfaces cards ENGLISH 5 1 IDENTIFYING THE SWITCHES AND INTERFACES Internal batteries External batteries Serial connector RS232 485 serial connector RS232 for Modem y LAN connector RJ45 for Ethernet Mimic panel Options slot 1 Opti
21. two Net Vision cards or two GSS cards cannot be connected simultaneously S0comec 44 IOMMASGPXXO01 GB 00 Innovative Power Solutions UPS 8 COMMUNICATION MASTERYS Green Power 10 40 kVA 8 2 STANDARD LAN WEB PAGE By connecting the UPS to a standard LAN network the operating status of the UPS can be monitored from any PC connected to the network through an html page 8 2 1 Activation Comply with the following operations to activate the monitoring system Connect the UPS to the LAN network connector in Fig 82 1 1 ENGLISH DID A Ifthe BOOT DHCP protocol is enabled in the local network verify the IP address shown in the PARAMETERS gt PRESENT CONFIG gt LOCAL AREA NETWORK IP menu on the UPS mimic panel go to point C B Ifthe BOOT DHCP protocol is not enabled in the local network Foreword the following is applicable only if the user is in possession of the administrator rights otherwise the procedure indicated below is only valid if using a stand alone PC i e not in a network of computers with admin istrator privileges and a network twisted cable Deactivate DHCP mode in the COMMAND gt EXT COMMAND gt DHCP DISABLE menu on the UPS mimic panel Read the IP address given in the PARAMETERS gt PRESENT CONFIG gt LOCAL AREA NETWORK IP menu on the UPS mimic panel by default 192 168 7 19 From a PC connected to the network add the address read by means of the following command Route add 19
22. 00 8 COMMUNICATION MASTERYS Green Power 10 40 kVA 4 P SERVICE This is a cutting edge supervision service ensuring 24 7 365 service It ensures effective prevention and constant monitoring of the system Communication between the UPS and the local Socomec Service Centre is via modem free air GSM or ANALOG fixed line The auto diagnostic system analyses UPS operating conditions identifies faults and monitors environmental conditions such as temperature overload avoid ing the risk of equipment stoppages In the event of a failure the system imme diately sends a diagnostic report via modem to the Service Centre Any emergency situation is managed and resolved extremely quickly and re motely by the Service Centre with immediate intervention on site if needed ENGLISH socome Innovative Power Solutions UPS IOMMASGPXX01 GB_00 51 9 PROBLEM SOLVING MASTERYS Green Power 10 40 kVA The alarm messages displayed enable an immediate diagnosis Alarms are divided into two categories Alarms related to the UPS external circuits input mains output mains temperature and environment Alarms related to the UPS internal circuits in this case the corrective actions will be carried out by the After Sales Department 9 1 SYSTEM ALARMS A02 output overload The power required by the loads is higher than the power available Check that the load is well balanced on the three phases by checking th
23. 2 168 7 19 210 67 192 147 assuming 210 67 192 147 to be the IP address of the PC being used C Open an internet browser and key in the address http XXX XXX XXX XXX and press send where 0000000009 is the IP address read on the mimic panel socome Innovative Power Solutions UPS IOMMASGPXX01 GB_00 45 8 COMMUNICATION MASTERYS Green Power 10 40 kVA D Alogin and a password will be requested fig 8 2 1 2 the default parameters are 2x login admin Immettere il nome utente e la password password public Sito 1721710162 Area autenticazione Socomec Sicon UPS Insert data and click OK The main web supervisor page will be displayed and Peswod the functions are described in the following para F Ja nene dea Dd A Ee a ol v 2 8 2 2 Description of the functions available The main web page shows the general status of the UPS This page like all the sub pages are dynamic i e the data images or type of messages shown vary in accordance with the UPS status and configuration LOAD PROTECTED List of alarms Statistic Information UPS Management B change language Local network e mail configuration Modem configuration Software upgrade Legend A Navigation bar B Menu bar C system information area socomec 46 IOMMASGPXX01 GB_00 Innovative Power Solutions UPS COMMUNICATION MASTERYS Green Power 10 40 kVA 8 2 2 1 Navigation bar
24. C 32A AC Q1 nput power switch 20 3 3 45 A AC 45 A AC Q2 Backup power switch 30 3 3 60A AC 60A AC XB1 Connector on BKF PCB 40 3 3 90 A AC 90 A ACT XB2 Connector on BKF PCB 2 SOCOmec Innovative Power Solutions UPS IOMMASGPXX01 GB_00 57 xL A i J 2 MASTERYS Green Power 10 40 kVA 10 OPTIONS 10 8 2 Protection on an UPS without auxilary mains supply Activating UPS protection on the mimic panel access the Configuration menu on the mimic panel see the Configu ration Menu section in the manual and set the BACKFEED TYPE parameter to 3 BYPASS INPUT Common Diagram of principle 10 72 UPS 3 3 without separate auxiliary supply Legend A Distribution panel B Coil remote switch L1 L2 L3 N Input power source 1 Attention The neutral on the input o the input power supply is Remote switches rated current Model T1 10 3 1 32 AAC 15 3 1 32 AAC 20 3 1 45 A AC 10 3 3 32A ACI 15 3 3 32 AAC 20 3 3 45 AAC 30 3 3 60 A ACI 40 3 3 90 A AC Input power switch Remote switch Connector on BKF PCB Input power terminal board the output of the UPS are identical Consequently there is no risk of high potential when absent However depending on the type of system connected in the output or in some failure conditions earth leakage significant phase dispersion or in case of non isolated neutral system high potential can be detected It will there fore be necessary to instal
25. ERYS Green Power 10 40 kVA 6 1 1 Meaning of ideograms v 2 3 0 0 Innovative Power Solutions 6 MIMIC PANEL MASTERYS Green Power 10 40 kVA Meaning of ideograms Code Description Condition 1 Load on bypass in Eco mode or Maintenance bypass closed Steady Automatic bypass alarm Flashing M2 nput rectifier active Steady nput rectifier general alarm Flashing 3 Battery OK Steady Battery alarm Flashing 4 M7 Remaining battery capacity Steps of 25 Battery recharging Sequence 7 M4 8 nverter on Steady A nverter general alarm Flashing T 9 Output voltage present Steady 10 nput mains OK Steady nput mains alarm Flashing 11 nverter on Steady jJ odule 1 present Steady odule 1 general alarm Flashing 13 odule 2 present Steady odule 2 general alarm Flashing 14 odule 3 present Steady odule 3 general alarm Flashing 15 odule 4 present Steady odule 4 general alarm Flashing 16 odule 5 present Steady odule 5 general alarm Flashing ly odule 6 present Steady odule 6 general alarm Flashing 18 Load present Steady Overload Flashing 19 M28 Output load indicator Steps of 1096 29 Periodic maintenance alarm warning Flashing 30 Activation code alarm Steady General alarm Flashing 31 LAN connection ready Cable Connected Steady socomec Innovative Power So
26. INSTALLATION AND OPERATING MANUAL MASTERYS Green Power 10 40 kVA IOMMASGPXX01 GB_00 H a S m eq i Innovative Power Solutions UPS INDEX MASTERYS Green Power 10 40 kVA 1 CERTIFICATE AND CONDITIONS OF WARRANTY uu e Ree s E e RC or e ae Rt eR 5 ES JC een ohh aa ad bal OR oe bee ba DEERE Ae he 6 ws bd e E dee ERGO 6 22 Description of the symbols used the labels applied 3 UNPACKING AND INSTALLATION OF THE sisse RRRRRRRRRRRRRRRRRRRRRRRRe 8 2 MOOG GAN doe rhet b ERREUR ed bayu qa gasas 8 3 2 P ss aysana phaea ESE 9 3 3 Environmental requirements 2 0 r es 12 P 3 sca s e py Eyyam su PEE p eg CROP OLE Sa 4 2 3 5 Installation procedure and instructions mmm 15 aa 3 6 Connection or thegenerator xa Rd tae px da sedg C aee 9 525950 pondo or ent od E E63 qusqa ERR BE ERE OE dE ERE REO ES aa 9 So Gla OR transformer usa srk oaths 19 3 9 UPS Parallel configurati sensy Fra e ERN
27. LATION MASTERYS Green Power OF THE UNIT 10 40 kVA 3 9 UPS PARALLEL CONFIGURATION 3 9 1 General Parallel connection enhances UPS system reliability performance and power All MASTERYS models can be installed in parallel configuration provided they have the special parallel kit that can be installed in factory or later by specialist personnel UPS modules for parallel operation are identical to standard UPS modules as a result safety shipping and installation recommendations in chapters 2 and 3 also apply 3 9 2 Installation UPS units operating in parallel are interconnected using control cables B fig 3 9 3 1 and are configured differently depending on the position they are assigned For this reason the units have a position label Fig 3 9 4 1 The LEFT label means that the unit must be positioned to the left The RIGHT label means that the unit must be positioned to the right The INTERNAL label used only on systems with three UPS means that this unit must be positioned between the two other cabinets The control cables supplied allow a maximum distance of about 3 metres between the UPS units This gives enough room for an external battery cabinet to be inserted beside each UPS D 3 9 3 Power connections power supply to each unit must be protected as indicated in the table in paragraph 3 4 The cross section and length of the input and output cables must be identical for all th
28. N Rab Rae ES 50 PROBLEM OLING S esac ut RR R ee oh ve cs tech Rune aes 52 Sea NG ae eek m ox ne eee eee EE Ree XOU Uie ERE db 52 UPS PAS 53 9 3 Preventive MAINTENANCE e dc VR Sg 54 Batterles ebd Seb Rb eee be CC od Rer dede ss d erede 54 vlc PT he donee haqa Q ase Ae eee etn haa Oe 54 OPS DAA af 54 PC 55 TCI err 55 102 GS Global 56 56 UA Pomorie haqa 56 10 5 Ext rndl maintenance DYNESS sassa 56 0 6 External maintenance bypass with backfeed protection iie 56 siu iram aS oh od ha BA EE ERR ee ha cie 56 DIGISEED 309 CIE died e ERR Y Wee eden ede EV 56 10 8 1 Protection on Mains Supply and on Auxiliary Mains Supply 57 10 8 2 Protection on an UPS without auxilary mains supply 58 10 9 ADC card with temperature sensor 4a uie bee Era dE Rd 59 OOO c Or 59 IO Tee wey 59 1012 Serialeonnection POB
29. NERATOR SET FAULT Major alarm on generator set A58 ESD ACTIVATED The remote emergency shutdown command has been activated A59 BATTERY CIRCUIT OPEN The battery switch is open A60 FAN FAILURE Fans faulty or blocked A61 PHASE ROTATION FAULT Wrong phase cycle direction 5S0comec 34 IOMMASGPXX01 GB_00 Innovative Power Solutions UPS 6 MIMIC PANEL MASTERYS Green Power 10 40 kVA 6 1 3 2 Measurements menu This menu is used to display all the measurements relating to the UPS input output and to the battery For models with single phase input or output the voltage and current displays are adjusted automatically MEASUREMENTS menu Type of measurements Value Value Value Note OUTPUT STAR VOLTAGE __V vV M OUTPUT PH PH VOLTAGE V V VM OUTPUT LOAD 9 22 22 OUTPUT ACTIVE POWER OUT APPARENT POWER _ _ T OUTPUT CURRENT _ __A a OUTPUT FREQUENCY OH AUXILIARY VOLTAGE V V V AUXILIARY FREQUENCY Hz PUT STAR VOLTAGE __V V PUT PH PH VOLTAGE V V PUT FREQUENCY Hz PUT APPARENT POWER _ _ BATTERY VOLTAGE Bl V B2 V CAPACITY CHARGING BACKUP T MIN DISCHARGING NTERNAL TEMPERATURE C BATTERY TEMPERATURE 2 Only with sensor present and set Statistical measurements menu Once a programmable reference period has been defined the syste
30. ONFIG MODULE 6 uo Rm my Sa ni eh Ee at f al ah GSS Wah Sa Je E ny ER UR re inm ca Sa TE ak A Sa an 2 socomec Innovative Power Solutions UPS IOMMASGPXXO01 GB 00 33 ENGLISH 6 MIMIC PANEL MASTERYS Green Power 10 40 kVA 6 1 3 1 Alarms menu This is used to display all the alarms that are active at the time of access The alarms menu is activated automatically when an alarm condition occurs ALARMS menu Code Mimic panel description Meaning A00 GENERAL ALARM A01 BATTERY ALARM Battery circuit failure or faulty operation A02 OUTPUT OVERLOAD Power required in output over the limits A06 AUXILIARY MAINS OUT OF TOLERANCE The voltage or frequency limits accepted by the bypass have been T exceeded mE A07 OVER TEMPERATURE Temperature excessive or ventilation problems A08 MAINTENANCE BYPASS ACTIVE Q6 in position 2 mE A17 IMPROPER CONDITION OF USE Improper conditions of use verified load mains and temperature A18 BLOCKING INVERTER FOR OVERLOAD Inverter shutdown due to overload A20 WRONG CONFIGURATION Error in the configuration parameters e g different parameters between several UPSs in par
31. PHHHB WAY TOW AY FT NYY IW mm mm T TT NN f mm IT n f AM At At itl f f U INI gt i LLL AE lc 15 40 kVA 15 m max 60 80 kVA 7 5 m max A System input switch B Parallel bus cable C Single UPS magneto thermal switch if a separate auxiliary power source is used add a magneto thermal switch for each UPS socomec Innovative Power Solutions UPS D Ext bypass magneto thermal switch E Output switch F System shutdown switch G Distribution H Main differential magneto thermal switch Internal UPS INTERNAL L Left UPS LEFT R Right UPS RIGHT IOMMASGPXX01 GB 00 2 1 UNPACKING AND INSTALLATION MASTERYS Green Power OF THE UNIT 10 40 kVA 3 9 4 Control connections In order for units connected in a parallel configuration to operate correctly control cables are required to exchange data between the various UPS units making up the parallel system for management of correct load sharing and synchronisation logic The cables in question are supplied with the UPS in case of standard parallel setting or are attached to the parallel kit in case of later upgrading of the system Parallel configuration must only be activated by
32. SOCOMEC UPS qualified personnel in each case arrange the running of the control cables in the relative cable run as shown in figure 3 9 4 1 leaving the connector s uncon nected in the central UPS one incoming and one outgoing control cable must be used XL J 2 Control cables cable run B Parallel bus cable leave approx a 20cm cable length at the exit of the cable run C Label for unit positioning 2 Socomec 22 IOMMASGPXXO01 GB 00 Innovative Power Solutions UPS UNPACKING AND INSTALLATION MASTERYS Green Power OF THE UNIT 10 40 kVA 3 10 EXTERNAL BATTERY CABINET CONNECTION If the UPS has internal batteries connecting external battery cabinets is prohibited Position the battery cabinet next to the UPS Before carrying out any operation ensure that the battery fuses located inside the battery cabinet are open the UPS is not live all mains or battery switches are open the switches upstream of the UPS are open Remove the terminal boards protection Connect the ground cable figure 3 10 1 Connect the cables between the UPS terminals and the battery cabinet terminals strictly observing the polarity of each individual string fi
33. STERYS Green Power 10 40 kVA Mechanical characteristics with standard batteries 1 400 1 000 ENGLISH Model T Model M Model S Weight 390 540 kg Weight 230 315 kg Weight 190 200 kg 7 495 981 13 66 61 http www entel ru E Mail sales entel ru
34. T COMMON BATTERY TEST Sets the frequency rate of the battery test in days 02180 TEST EVERY XX DAYS zero do not perform the test POWER SHARE PLUGI TYPE Selects the configuraton of power share required STANDARD see paragraph 10 5 EMERGENCY LIGHTING REMAINING TIME RESIDUAL CAPACITY POWER SHARE PLUGT VALUE Sets the required intervention value minutes for remaining time and Ah for capacity optional POWERSHAREPLUG2TYPE As plug type optional POWER SHARE PLUG2 VALUE As plug value optional SERIAL LINK BAUD RATE Inserts the serial communication parameters 1200 2400 4800 9600 SERIAL LINK PARITY Inserts the serial communication parameters odd even none STATICO Sets the static IP address of the LAN 255 255 255 255 SERIAL LINK JBUS Sets the mimic panel jbus node 1 15 SLAVE NUMBER DATE AND TIME Sets the date and time DD MM YY HH MM EXTENDED COMMAND Enables Disables the mimic panel extended commands YES NO REMOTE COMMAND Enables disables the remote controls YES NO BUZZER Enables Disables the buzzer YES NO LCD CONTRAST Sets the LCD display contrast 0 100 STATISTICS PERIOD Indicates the time in weeks for the calculation of statistics 10 GSS TIME DELAY Sets the generator start up delay time visible only when 1 60 MINUTES the GSS PCB is installed E SERVICE TYPE Select e service operating mode NONE MODEM SMS E SERVICE TELEPHONE NUMBER Insert the phone number to call
35. UPS output with an external power source another UPS even of a different brand generator or tran sformer 10 8 EXTERNAL BACK FEED PROTECTION External devices can be installed to protect against the backfeed of dangerous currents both on the MAINS SUPPLY and on the AUX MAINS SUPPLY These devices are controlled by the BKF PCB installed in the position shown in figure 10 8 1 Refer to the following paragraphs for details on the electrical connections and on activating the chosen protection socome 56 IOMMASGPXX01 GB_00 Innovative Power Solutions UPS 10 OPTIONS MASTERYS Green Power 10 40 kVA 10 8 1 Protection on Mains Supply and on Auxiliary Mains Supply Activating UPS protection on the mimic panel access the Configuration menu on the mimic panel see the Con figuration Menu section in the manual and set the BACKFEED TYPE parameter to 2 BYPASS INPUT Alone Diagram of principle UPS 3 3 with separate auxiliary supply UPS 3 1 with separate auxiliary supply ENGLISH Legend E Remote switches rated current A Distribution panel B Coil remote switch Model n n L1 L2 L3 N nput power source 103 1 32 45 L11 L21 L31 N1 Backup power source 15 3 1 32 AAC 45 A AC M1 nput power terminal board 20 3 1 45 A AC 60 A AC M2 Backup power terminal board 103 3 32AAC 32 AACI T1 Remote switch Tn Raemote switehi 15 3 3 32A A
36. according to the level of protection required by the application The Eco Mode operation provides very high efficiency since the application is powered directly from the auxiliary mains via the automatic bypass in normal operating conditions SOCOmeC UPS 24 IOMMASGPXX01 GB_00 Innovative Power Solutions MASTERYS Green Power 4 3 OPERATION WITH MANUAL MAINTENANCE BYPASS 10 40 kVA If the maintenance bypass is activated using the appropriate procedure the load is powered directly from the maintenance bypass while the UPS is separated from the power supply and can be switched off This operating mode can be selected for maintenance to be carried out on the system so that the necessary actions can be performed by service personnel without having to disconnect the power supply to the load 4 4 OPERATION WITH EXTERNAL MANUAL BYPASS The external maintenance bypass may be placed on the general distribution panel when the installing the bypass panel that is supplied on request By pass panel connection diagram If the UPS has an input for the auxiliary power supply the Q2 switch must be connected to th power supply input must be disconnected on the control panel If the maintenance bypass is activated with the appropriate procedure the load is powered di tenance bypass while the UPS is separated from the power supply and can be switched off UPS is installed or by isinputand the main ectly from the main This operat
37. allel A22 PUT MAINS OUT OF TOLERANCE The voltage or frequency limits accepted by the rectifier have been exceeded A23 RECTIFIER GENERAL ALARM Rectifier fault A25 VERTER GENERAL ALARM nverter fault A26 BATTERY CHARGER GENERAL ALARM Battery charger fault A29 BYPASS GENERAL ALARM Bypass fault A30 STOP FOR OVERLOAD The duration of the overload has inhibited the bypass A32 ODULE 1 GENERAL ALAR odule 1 failure A33 ODULE 2 GENERAL ALAR odule 2 failure A34 ODULE 3 GENERAL ALAR odule 3 failure A35 ODULE 4 GENERAL ALAR odule 4 failure A36 ODULE 5 GENERAL ALAR odule 5 failure A37 ODULE 6 GENERAL ALAR odule 6 failure A38 EXTERNAL ALARM 1 Signalling from ADC input A39 EXTERNAL ALARM 2 Signalling from ADC input A40 EXTERNAL ALARM 3 Signalling from ADC input A41 EXTERNAL ALARM 4 Signalling from ADC input A42 E SERVICE GENERAL ALARM Alarm that generates automatic sending of a signal to the support centre if the service has been activated A43 REDUNDANCY LOST The power required by the load no longer allows the preset redundancy N x to be maintained for UPSs in parallel only MA PERIODIC SERVICE CHECK UP Warning for periodic check by support service A47 MAX BATTERY TEMPERATURE Control of the temperature of battery cabinet A49 BATTERY DISCHARGED The energy available in the battery has been used up A51 OPTION BOARD GENERAL ALARM Fault related to the optional PCBs in the slots A56 GENERATOR SET GENERAL ALARM Minor alarm on generator set A57 GE
38. could be useful to add new languages orthe SNMP function Once the file has been acquired by requesting it from the support service select it with the browse button Click on the start update button once the update has been completed reload the html page 8 2 2 11 System Information Area This area of the screen page shows the measurements and the UPS op erating mode e Click on icon A to display the input measurements Click on icon B to display the bat tery measurements Click on icon C or D to display the output measurements socomec Innovative Power Solutions UPS IOMMASGPXX01 GB_00 49 2 i J Z 8 COMMUNICATION MASTERYS Green Power 10 40 kVA 8 3 ACCESSORIES AND SW OPTIONS A large number of SW solutions can be adopted on MASTERYS thanks to its advanced communication facilities These solutions have been specially designed for the efficient management of power protection devices one UNIVISION PRO is the solution for managing a UPS connected to the local server l VISION via RS232 interface or via LAN network It is normally used at departmental level to automatically shutdown the systems and ensure secure control of the UPS that in turn protect servers and workstations The main functions are Graphic monitoring of the UPS via web browser Local shutdown of a server connected via serial interface Remote shutdown via proxy agent and optional Ja
39. e mail will be sent 2 sSocomec 48 IOMMASGPXX01 GB_00 Innovative Power Solutions UPS 8 COMMUNICATION MASTERYS Green Power 10 40 kVA 8 2 2 9 Modem configuration This menu lets the user configure the parameters of a modem Rings before reply Set the number of rings after which the modem should respond Outgoing call sets the type of outgoing call SMS or E service to activate e service a contract to the support centre is required Reason for callout set the reasons for the call all alarms or for serious faults Installation text string used to describe the UPS installation site which is useful if there are more than one unit connected this value is inserted in SMS messages or e mails Telephone number insert the number to be called Modem initialisation initial string to be sent to the modem for special configurations or certain types of mo dem Connection period set the number of days between two calls even if no faults occur Force an outgoing call by selecting EXECUTE a test connection is immediately carried out ENGLISH 1 Activating one configuration excludes the other therefore if an E service T service contract is subscribed calls in output cannot be configured 2 Inthe event that the E service T service contains the control code provided by after sales personnel 8 2 2 10 Software updating This html page is used to update automatically the monitoring software which
40. e measurements on the display If needed disconnect any loads that do not need uninterruptible power Important The accepted overload time limit is defined in the technical specifications When this time limit is exceeded the loads will no longer be powered by the inverter A06 auxiliary mains out of tolerance The auxiliary mains exceeds the acceptable tolerance values Possible causes are No voltage or frequency present or voltage and frequency out of acceptable values see the technical specifica tions The frequency is subject to continuous variations typical with power supplied from an incorrectly sized GE A07 temperature over the limits The UPS internal temperature is higher than 50 C please refer to Measurements menu on the mimic panel Check the ventilation or air conditioning system in the UPS room A08 maintenance bypass activated The output disconnecting switch Q6 is in position 2 maintenance bypass The load is therefore powered directly by mains power supply A17 improper conditions of use This alarm does not indicate a malfunction or failure of the UPS but an incorrect use sizing of the system It is activated in the event of Operation for long periods at high temperatures battery deterioration High number of overloads wrong sizing Continuous battery discharging mains not stable High number of switches onto the bypass high impulsive loads A22 input mains out of
41. e units he phase rotation must be the same for each unit connected in parallel and also on any external manual bypass line Cables of the same length and cross section must be used for the connection between the general power switch A the switches and the respective UPS units The length of the cables from A to each UPS module must not exceed 25 meters Fig 3 9 3 1 The cables from the UPS module to circuit breaker must be of the same length max 15 metres with multi core cables differential switch is installed on the mains power switch optional it must be inserted upstream from the distribution panel see fig 3 9 3 1 detail H it must be a selective type and the trigger value must be 0 5 A by the number of UPS connected in parallel Only activate circuit breaker D after carrying out the procedure for switching onto the mainte nance bypass N Only activate circuit breaker E after turn off the UPS socome 20 IOMMASGPXX01 GB_00 Innovative Power Solutions UPS UNPACKING AND INSTALLATION OF THE UNIT MASTERYS Green Power 10 40 kVA RECOMMENDED PARALLEL CONFIGURATION 25 m max O 0 2 2 DI EX 0 ENGLISH P Le j j 1 mmm 1 1 II V M m Ji 5 BPHHHPHHHH
42. ear if necessary typically batteries fans and capacitors 9 3 1 Batteries The state of the battery is fundamental to UPS operation Thanks to the Expert Battery System the information relating to the state and the conditions of use of the battery are processed in real time and the recharging and discharging procedures are selected automatically in order to optimise battery life expectancy and offer maximum performance Furthermore during the operating life of the battery MASTERYS stores statistics on the conditions of use of the battery for analysis Since the expected life of the batteries is very much dependent on operating conditions number of charging and discharging cycles load rate temperature a periodic check by authorised personnel is recommended When replacing the batteries use the same type and configuration by placing them in the appro priate containers so as to avoid the risk of acid leakage The replaced batteries must be disposed of at authorised recycling and disposal centres Do not open the plastic cover of the batteries as they contain harmful substances 9 3 2 Fans The life of the fans used to cool the power parts is dependent on the using and environmental conditions tem perature dust Preventive replacement by an authorised technician is recommended within four years in normal operating condi tions N When needed fans should be replaced as per specifications by SOCOMEC UPS 9 3 3 Capacitors
43. escription Allowed values LANGUAGE SELECTION Selects the required language ENG FRA ITA NUMBER OF MODULES Only appears in case of parallel systems 1 6 Indicates the number of UPSs in the system REDUNDANCY LEVEL Only appears in case of parallel systems FROM 0 TO THE NUMBER Indicates the number of redundant UPSs OF MODULES LESS ONE OUTPUT VOLTAGE Sets the required output voltage value 208 220 230 240 OUTPUT FREQUENCY Sets the required output frequency value 50 60 CONVERTER Sets whether the UPS has to operate as a frequency YES NO converter WARNING Set only on UPS with mains power MAINS and auxiliary mains AUX MAINS separated and with the auxiliary mains AUaX MAINS disconnected Do not set on UPS with common mains lines as it could damage the load AUTO ON Sets whether the UPS has to restart automatically after YES NO shutdown due to minimum battery level BATTERY AVAILABLE Indicates whether the batteries are present YES NO BATTERY TEMP SENSOR Indicates if the battery sensor is present ON OFF BATTERYTYPE Selects the type of batteries used SEALED OPEN VENT NI CD BATTERY RECHARGE Selects the type of recharge required AUTO MAINTENANCE 2 LEVELS INTERMITTENT BATTERY CAPACITY Sets the battery capacity in Ah 6 50 1 000 x number of UPS BATTERY ELEMENTS ndicates the number of elements in series 108 144 180 228 for
44. for e service messages MAX 20 CHARACTERS AUX TRANSFORMER VOLTAGE Set the auxiliary voltage measure with transformer SETTABLE ONLY BY AFTER SALE SERVICES INPUT TRANSFORMER VOLTAGE Set the input voltage measure with transformer SETTABLE ONLY BY AFTER SALE SERVICES socomec Innovative Power Solutions UPS IOMMASGPXX01 GB 00 3 9 6 MIMIC PANEL MASTERYS Green Power 10 40 kVA Service code menu This displays the service code to be sent to the support service to make an accurate and rapid diagnostic of the problem In the event of a fault select the menu SERV ICE gt SERVICE CODE and inform the support centre of the code displayed a ol v 2 6 1 3 6 Event Log menu Shows a list of UPS events in chronological order It allows the user to analyse UPS operation with regard to variations in the power supply load or the environment Legend A Shows date and time of event B Shows the event code C Describes the event D ON OFF status of event E Progressive number of event socome 40 IOMMASGPXX01 GB_00 Innovative Power Solutions UPS 6 MIMIC PANEL MASTERYS Green Power 10 40 kVA 6 2 MIMIC PANEL CONCENTRATOR In systems with 2 or more UPS units connected in parallel advanced mimic panels can provide an overall view of the system and a detailed view of the UPSs in a single point During the installation phase one of the UPSs and the relative mimic panel is defined as the co
45. g2 power safe plug 3 supply from GenSet UPS on bypass 2 Socomec Innovative Power Solutions UPS IOMMASGPXXO01 GB 00 55 10 OPTIONS MASTERYS Green Power 10 40 kVA 10 2 KIT GSS GLOBAL SUPPLY SYSTEM This kit optimises generator sizing and control when connected to the UPS input The generator set can be instructed to start up automatically the moment the mains power is lost or alternatively following a user set time period without the mains power and or when the batteries have discharged to their residual capacit 10 3 ISOLATION CONTROLLER This device continually checks the transformer isolation displaying an alarm message on the mimic panel 10 4 REMOTE MIMIC PANEL This device monitors and interacts with the UPS through a serial link RS 485 maximum distance of 175 m 25 m cable supplied standard 50 m cable available as an option 10 5 EXTERNAL MAINTENANCE BYPASS This device will electrically exclude and isolate the UPS e g for maintenance operations without interrupting the power supplied to the load 10 6 EXTERNAL MAINTENANCE BYPASS WITH BACKFEED PROTECTION This device will electrically exclude and isolate the UPS e g for maintenance operations without interrupting the power supplied to the load 3 pole contactors are used for the back feed protection refer to paragraph 10 8 Note An additional option is available to bring the manual bypass signal back to the UPS 10 7 ACS PCB Synchronises
46. gure 3 10 1 and the cross sections indicated in table 34 ENGLISH Use double insulated cables or the cables supplied with the unit to connect the UPS to the Bat tery cabinet The lenght L of battery cable must not be more than 8 metres long if L gt 8 m please contact the support service Cabling errors with inversion of the battery polarity may cause permanent damage to the equip ment Replace the terminal board s protection If using cabinets not supplied by the manufacturers of the UPS it is the installer s responsibility to check the electrical compatibility and the presence of appropriate protection devices between the UPS and the battery cabinet fuses and switches of sufficient capacity to protect the cables from the UPS to the battery cabinet As soon as the UPS is switched on before closing the bat tery switches the battery parameters must be verified accordingly voltage capacity number of elements etc on the mimic panel menu If the values indicated on the battery cabinet data plate are different from those shown on the mimic panel use the SERVICE gt CONFIGURATIONS menu to correct the settings BATTERY CABINET 2 L22 L32 L21 L2 L3 Nt MAINS SUPPLY 2 socome Innovative Power Solutions UPS IOMMASGPXXO01 GB 00 23 a mr v 2
47. he address 255 255 255 255 is inserted access will be denied to all Users Software updating if on allows the supervisor to be updated Page refresh sec the page refresh rate can be set Installation text string used to describe the UPS installation site which is useful if there are more than one unit connected this value is inserted in SMS messages or e mails NTP Server indicates the IP address of the time server to automatically update the date and time on the system GMT Correction minutes indicates local time and the offset in minutes with respect to the zero meridian of Greenwich Apply the parameter settings restarts the monitoring system with the new settings 8 2 2 8 Configuring e mail This menu lets the user configure parameters for sending e mails Event that will send an e mail as required the e mail may be deactivated or activated to send a message in the event of serious alarms or for all alarm conditions E mail server address insert the IP address xxx xxx xxx xxx of the SMTP e mail server from which you wish to send messages e mail account Insert the UPS s dedicated user account which is often the same as the user s e mail address Addressee insert the e mail address to which the alarm messages will be sent Periodic connection set the frequency at which an e mail is to be sent to verify the connection Force an e mail to be sent now by selecting execute a test
48. ing mode can be selected for maintenance to be carried out on the system so that the necessary actions can be performed by service personnel without having to disconnect the power supply to the load Bypass panel connection diagram 3 phase input 3 phase output for UPS 3 3 Q2 Mains power ive Power Solutions UPS Q1 Bypass switch switch Q3 Output switch IOMMASGPXX01 GB 00 2 5 ENGLISH 4 MODES OF OPERATION MASTERYS Green Power 10 40 kVA 4 5 OPERATION IN GE CONFIGURATION MASTERYS can be operated in conjunction with a generator GE With a generator the frequency and voltage ranges of the auxiliary mains can be increased to accept the instabil ity of the GE and at the same time to avoid operation from the battery or risks of out of synchronisation switching onto the bypass The use of the GSS interface described in the options section also increases the amount of diagnostic information exchanged between the continuous power system and the generator 4 6 ENERGY SAVER MODE This mode ensures that the UPS system always operates at the highest load efficiency 40 7096 of the nominal power a mr v N This mode can only be activated on UPS connected in parallel and operating in normal mode In cases of low load the system shuts down any unnecessary UPS units thus increasing the load on the remaining units This leads to higher system efficiency as the UPS in
49. ious operating modes It can also be used to send extended commands to define some UPS settings To activate the commands select the command with UP A or DOWN v press ENTER select YES NO to execute and press ENTER to confirm Extended commands They can only be displayed if the extended commands item in the configurations menu has been activated s IMMEDIATE COMMANDS menu 9 Command Description lt START PROCEDURE UPS start up command STOP PROCEDURE UPS shutdown command AINTENANCE BY PASS Control to activate the manual bypass and shutdown of the UPS PROCEDURE HIGH EFFICIENCY MODE Activates Eco mode always on mode NORMAL MODE Activates normal double conversion operation ALARM RESET Resets all the alarms LEDS TEST Performs the test on the mimic panel LEDs Command Description MANUAL BATTERY TEST Activates the battery test BATTERY COMMISSION Activates battery commissioning use only if necessary for the type of battery SET LAN DEFAULT VALUE Resets all the values of the LAN JBUS TUNNELING ENABLE Enables the connection of advanced software BMS or Uni vision via the LAN network JBUS TUNNELLING DISABLE DHCP ENABLE Enables the automatic allocation of the IP address by the network server DHCP DISABLE FORCE MODEM DIAL OUT Forces sending of an immediate test modem call ENERGY SAVER ENABLE Enables energy save mode on a parallel system ENERGY SAVER DISABLE
50. ize protection kVA A A A mm mm A single parallel single parallel selective type Min Min 10 3 1 32 40 100 125 05 6 35 6 35 50 Gr 100 125 16 ifcommon if common aux mains input input and output mains mains 153 1 32 40 100 125 05 6 35 6 35 50 Gr 100 125 25 ifcommon if common aux mains input input and output mains mains e uscita 20 31 40 63 125 160 05 10 35 10 35 50 Gr 125 160 35 ifcommon if common aux mains input input and output mains mains e uscita 10 3 3 32 40 32 40 05 6 35 6 35 50 Gr 15 33 32 40 32 40 05 6 35 6 35 50 Gr 20 3 3 40 63 40 63 05 10 35 10 35 50 Gr 30 3 3 63 80 63 80 05 16 35 16 35 100 Gr 40 3 3 80 100 80 100 05 25 35 25 35 100 Gr 1 Recommended magneto thermal switch four poles with intervention threshold gt 10 In n systems with two or more UPSs operating in a redundant or power parallel configuration Determined by the size of the terminals protection on the external battery cabinet Caution Use type B four pole selective S circuit breakers Load leakage currents are added to those generated by the UPS and during transitory phases power failure and power return short current peaks may occur If loads with high leakage current are present adjust the differential protection It is advisable in all cases to carry out a preliminary check on the earth current leakage with the UPS installed and operational with the definitive load so as to prevent the sudden activation
51. l load Input frequency 50 60 Hz 10 Input power factor 0 99 THDI lt 2 506 Electrical specifications Output 10 15 20 30 40 230 V single phase selectable 208 220 230 240 V 1 400 V three phase selectable 360 380 400 415 V 1 50 60 Hz 2 from 196 to 8 if generator is used nominal output voltage 15 from 10 to 2096 selectable if generator is used Nominal power kW 9 135 8 27 36 Output voltage three phase neutral Frequency Automatic bypass Overload on mains power supply 125 10 minutes 150 1 minute Crest factor 31 Voltage distortion 1 with linear load Pout 90 Pnom 10 15 20 30 40 Operating temperature 0 40 1525 C recommended for longer battery Storage temperature 5 45 C Relative humidity 0 95 condensation free Max altitude 1 000 m 3 300 ft without derating 3 000 m 10 000 ft max Acoustic noise dB lt 52 lt 52 lt 52 lt 55 lt 55 Required cooling capacity m h 280 280 280 465 465 Dissipated power max W 680 900 1150 1750 2300 Dissipated power BTU h 2300 3050 4070 6050 7900 10 15 20 30 40 Safety TUV certified EN 62040 1 1 EN 60950 1 Type and performance EN 62040 3 VFI SS 111 EMC EN 62040 2 Product certification Protection level IP20 compliant with 60529 IP21 on request 2 Socomec 60 IOMMASGPXX01 GB_00 Innovative Power Solutions UPS 11 TECHNICAL SPECIFICATIONS MA
52. lutions UPS IOMMASGPXXO01 GB 00 3 a ol J 2 6 MIMIC PANEL MASTERYS Green Power 10 40 kVA 6 1 2 Meaning of the luminous bar The luminous bar figure 6 1 1 provides an immediate indication of the condition of the power supply to the load Red power supply not present or shutdown imminent flashing Yellow power supply present but unstable or temporary Green power supply safe and stable Meaning of the luminous bar Colour Conditions displayed RED flashing Imminent shutdown alarm the load will be disconnected in a few minutes RED Load not powered or battery circuit open YELLOW flashing UPS in stand by or Ups on manual by pass Alarm indicating request for ordinary maintenance according to conditions of use type of load temperature after over 25 000 30 000 hours of operation M29 flashing and alarm A44 YELLOW Warning for preventive maintenance according to conditions of use type of load temperature after over 10 000 12 000 hours of operation M29 flashing YELLOW Load on battery or battery discharging if M11 is on steady and M10 is off YELLOW On automatic bypass if M1 is on steady YELLOW First maintenance period expired 10 000 hours of operation UPS in maintenance mode GREEN flashing Battery test in progress GREEN Load powered from inverter or in high efficiency mod 6 1 3 Mimic panel menu The paragraph below describes the menus available on the mimic panel
53. m reports measurements that are made avail able in digital or graphical format The values that are represented graphically can be used to analyse the situation over the last 24 hours This information together with the programmed interval information provides an enhanced evaluation on the operating mode of the equipment in order to verify whether certain critical operating situations are repetitive or only casual STATISTICAL MEASUREMENTS menu Measurement Value Option Option INPUT APPARENT POWER IN AVERAGE MAX ENTER displays ENTER displays weekly graphics 24 hr graphics BACKUP TIME LESS THAN 2 MINUTES UMBER OF EVENTS BACKUP TIME BETWEEN 2 AND 5 MINUTES UMBER OF EVENTS BACKUP TIME MORE THAN 5 MINUTES UMBER OF EVENTS OUTPUT LOAD IN AVERAGE MAX ENTER displays ENTER displays weekly graphics 24 hr graphics OVERLOAD TIME LESS THAN 5 SECONDS UMBER OF EVENTS OVERLOAD TIME MORE THAN 5 SECONDS UMBER OF EVENTS REDUNDANCY LOST UMBER OF EVENTS INTERNAL TEMPERATURE IN AVERAGE MAX ENTER displays ENTER displays weekly graphics 24 hr graphics BATTERY TEMPERATURE IN AVERAGE MAX ENTER displays ENTER displays weekly graphics 24 hr graphics WORKING TIME ON GEN SET UMBER OF HOURS SOCOmec Innovative Power Solutions UPS IOMMASGPXXO01 GB 00 35 6 MASTERYS Green Power 10 40 kVA 6 1 3 3 Commands menu This is used to send some immediate commands to activate the UPS or var
54. n the mimic panel 7 2 SHUTDOWN Shutdown interrupts the power supply to the load and causes the UPS and the battery charger to stop Activate the procedure COMMANDS IMMEDIATE COMMANDS STOP PROCEDURE Wait approx 2 minutes for the UPS to shut down the controlled shutdown of any servers is managed with shutdown software e Carry out the operations indicated on the mimic panel 7 3 EXTENDED OUT OF SERVICE If the UPS is deactivated for some time the batteries must be recharged regularly they should be recharged every three months Supply the mains and auxiliary mains to the UPS e Put switch Q2 into position 1 mains Wait for the mimic panel to switch on Activate the procedure COMMANDS gt IMMEDIATE COMMANDS gt START PROCEDURE Put the external battery disconnectors into position 1 battery circuit closed Put or keep switches Q3 and Q5 in position 0 inverter in output OFF and bypass OFF battery must be charged for at least ten hours Once ten hours have elapsed carry out the STOP PROCEDURE to deactivate the UPS S5ocomec 42 IOMMASGPXX01 GB 00 tive Power Soluti 7 OPERATING PROCEDURES MASTERYS Green Power 10 40 kVA 7 4 SWITCHING ONTO MANUAL BYPASS Switching onto the manual bypass creates a direct connection between the UPS input and output completely excluding the equipment control part This operation is performed in the event of ordinary maintenance on the equipment
55. ncentrator It is then possible to manage and install in one step all the options required for external communication 6 2 1 Keyboard blocking procedure Is possible to block unblock the keyboard using the buttons in following sequence ENTER DOWN UP A ESC pressed for over 3 seconds The sequence must be done in no more than 15 seconds ENGLISH socome Innovative Power Solutions UPS IOMMASGPXX01 GB_00 4 a mr v 2 7 OPERATING PROCEDURES MASTERYS Green Power 10 40 kVA The operating modes to activate and manage the UPS are defined in this chapter please also refer to chapters 6 Mimic panel and 8 Menus For UPSs connected in parallel perform the switching operations on all UPSs before going on to the next operation each switching operation must be carried out on both UPSs within 30 seconds perform the operations on the mimic panel of UPS 1 7 1 START UP IN NORMAL MODE Supply the mains and auxiliary mains to the UPS e Put switch Q2 into position 1 mains Wait for the mimic panel to switch on Activate the procedure COMMANDS gt IMMEDIATE COMMANDS gt START PROCEDURE e Carry out the operations indicated o
56. ng the unit The UPS MUST only be moved by two people at least The people MUST take position at the sides of the UPS with respect to the direction of movement CAUTION IF DAMAGED BATTERIES NON SPILLABLE Packages crushed punctured or torn such that contents are revealed must be set aside in an isolated area and inspected by a qualified per son If the package is deemed to be not shippable the contents must Battery is NOT connected be promptly collected segregated and either the consignor or consignee contacted All packaging material must be recycled in compliance with the laws in force in the country where the system is installed ive Power Solutions UPS UNPACKING AND INSTALLATION MASTERYS Green Power OF THE UNIT 10 40 kVA 3 2 UNPACKING PROCEDURE 3 2 1 Models S h 800 mm and models M h 1 000 mm 61771757 Remove screws and screws B ENGLISH The UPS can be moved Place the UPS in the installation area Secure the UPS with feet D only when it is in position with cables connected a Socome ative Power Solutions UPS IOMMASGPXX01 GB_00 9 UNPACKING AND INSTALLATION MASTERYS Green Power OF THE UNIT 10 40 kVA 3 2 2 Models T h 1 400 mm Remove screws A and screws B ENGLISH Loosen screws B 322 6 Remove sc
57. of the above switches the building s electric circuit or if it is likely to be subject to transitory overvoltages in category lll installations further external protection must be provided either on the UPS or in the AC power supply network to the UPS In addition the Surge arrestor option specially designed to protect against residual overvoltages in category III installations can be installed in the external manual bypass cabinet If used the distance between the UPS and the centralised 4 kV SPD protections type 1 must be Up lt 4kV is 2 15m The UPS is designed for transitory overvoltages category installations If the UPS is part of In the event of three phase distorting loads connected in output the current on the neutral AN conductor may have a value that is 1 5 2 times the phase value also for the input bypass In this case size the neutral cables and the input output protection adequately 2 Socomec Innovative Power Solutions UPS IOMMASGPXX01 GB_00 1 3 ENGLISH UNPACKING AND INSTALLATION MASTERYS Green Power OF THE UNIT 10 40 kVA 3 4 1 Back feed protection If the UPS does not have an automatic protection device against current back feed the operator installer must add a warning label to all the mains power disconnecting switches installed at a distance from the UPS area This serves to remind technicians of the fact that the circuit is connected to a UPS see the CAUTION section in paragraph
58. ons slot 2 Battery switch for internal batteries Input circuit breaker Output disconnecting switch E S D AUX MAINS 2 Socomec Innovative Power Solutions UPS IOMMASGPXXO01 GB 00 2 ACCESS TO CONTROLS MASTERYS Green Power AND COMMUNICATION INTERFACES 10 40 kVA 5 2 FUNCTIONS OF THE SWITCHES Input switch Q2 The input switch provides the primary power supply to the UPS In normal operating conditions it should be in position 1 ON The position 0 OFF will cause the batteries to discharge In a configuration with separate mains the switch only interrupts the rectifier power supply Output disconnecting switch Q6 The disconnecting switch Q6 has three positions with the following functions Position 1 UPS this is the position for normal operation of the UPS for a continuous power supply to the load Position 2 MANUAL BY PASS This position should only be selected for ordinary or extraordinary maintenance operations manual bypass the load is connected directly to the mains power supply It may be used in the event of a UPS failure to power applications from the auxiliary mains while awaiting the intervention of technical person nel Position 0 OFF This completely isolates the UPS output by removing the voltage from the applications in any operating condition It is used for the emergency shutdown of the system internal E S D a mr J 2 Battery switch Q1 UPS batte
59. reen Power OF THE UNIT 10 40 kVA Connections if THE MAINS AND AUX MAINS ARE CONNECTED SEPARATELY 8 EXT BATTERY ENGLISH L12 OUTPUT AUX 111 MAINS 1 socome Innovative Power Solutions UPS IOMMASGPXXO01 GB 00 17 ENGLISH UNPACKING AND INSTALLATION MASTERYS Green Power OF THE UNIT 10 40 kVA 3 5 3 Divert any control cables from the front 85232 signalling relay contacts etc into the appropriate side cable run A 3 5 4 Remove the pre cut detail C and bend details B to pass the cables secure the terminal board cover with the four screws 3 5 5 Secure the cables to the couplings D located on the rack ensuring that the air vents are not obstructed in any way Once the cabling has been carried out secure the UPS with the fixing feet NOTE If the system is installed on a raised floor such as a data processing room leave a space of at least 20 cm between the power and the control cables avoid parallel channelling over long distances choose cables crossing at 90 instead mr A Power cables B Control cables 2 socome 18 IOMMASGPXX01 GB_00 Innovative Power Solutions UPS UNPACKING AND INSTALLATION MASTERYS Green Power OF THE UNIT 10 40 kVA 3 6 CONNECTION OF THE GENERATOR
60. rews C N The UPS can be moved Place the UPS in the installation Loosen screws B Secure the UPS with feet D only when it is in position with the cable connected 2 sSocome 10 IOMMASGPXX01 GB_00 Innovative Power Solutions UPS UNPACKING AND INSTALLATION MASTERYS Green Power OF THE UNIT 10 40 kVA Tighten screws B Tighten screws C Tighten screws A ENGLISH T For UPS 15 40kVA height 1 400mm without internal battery With battery cabinet fitted alongside remove leveller E from the cabinet Fasten the UPS to the cabinet using the bracket E supplied figure 3 2 2 12 Without battery cabinet fitted alongside secure the UPS to the floor figure 3 2 2 13 2 sSocome Innovative Power Solutions UPS IOMMASGPXXO01 GB 00 11 UNPACKING AND INSTALLATION MASTERYS Green Power OF THE UNIT 10 40 kVA 3 3 ENVIRONMENTAL REQUISITES The recommended operating temperature humidity and altitude values are listed in the technical specifications table see chapter 11 Cooling systems may be required to maintain these values Avoid dusty environments or areas where there is dust from conductive or corrosive materials e g metal dust chemical solutions e The UPS is not designed for outdoor use Do not expose the UPS to direct sunlight or to sources of excessive heat space of at least 40 cm must be left at the back
61. ries When closed this switch connects the batteries of the UPS to the DC DC converter stage to power the inverter in the event of a mains failure The normal operating position is 1 closed 28 IOMMASGPXX01 GB_00 ive Power Solutions UPS 10 40 kVA 6 MIMIC PANEL MASTERYS Green Power 6 1 ADVANCED MIMIC PANEL The LCD mimic panel figure 6 1 1 located on the upper part of the UPS provides all the information on operating status electrical measurements and access to controls and configuration parameters The information is grouped into four sections A ideograms that identify the subsets and the energy flow B multicoloured luminous bar that identifies the condition of the power supply to the load C alphanumeric information that uses a menu layout to provide details on any alarms that may occur and on the measurements controls and parameters D use of the buttons e ESC exit from the current menu parameter action UPA scrolls the available menus values upwards It increases the value each time it is pressed when chang ing a parameter DOWN V scrolls the available menus values downwards It decreases the value each time it is pressed when changing a parameter ENTER enters the menu displayed on the screen to confirm the choice changes made ESC Vv ENTER ee socome Innovative Power Solutions UPS IOMMASGPXX01 GB_00 29 ENGLISH 6 MAST
62. tely serviced This alarm indicates that a procedure for analysing the UPS failure has been activated by the support centre if an e service contract has been concluded A44 programmed control The equipment has to undergo periodic checks by the support service in order to ensure optimum perform ance and efficiency If the Programmed Control signal appears on the mimic panel the equipment should be inspected by an adequately trained technician A59 battery circuit open Battery switch open A60 fan failure Fault in the ventilation system check that the air inlet at the front and the air outlet at the back of the UPS are not obstructed 9 3 PREVENTIVE MAINTENANCE We would like to inform you that specialised periodic maintenance with yearly frequency is recommended for the socome Innovative Power Solutions UPS IOMMASGPXX01 GB_00 53 A i v 2 10 40 9 PROBLEM SOLVING MASTERYS Green Power MASTERYS in order to offer optimum operating efficiency and avoid downtime of the equipment It is strongly recommended to give due consideration to any requests for preventive maintenance automatically displayed with alarm message M29 refer to paragraph 6 2 3 1 All operations on the equipment must be only carried out by SOCOMEC UPS personnel or by authorised support personnel Maintenance consists of accurate functional checks on electronic and mechanical parts with replacement of parts subject to w
63. tolerance The input mains is not present or not sufficient voltage and or frequency values incorrect with reference to the technical data if there is no input mains outage check if no protections upstream of the UPS have tripped Check that the voltage applied and frequency values are in compliance with the values set on the mimic panel A38 A39 A40 A41 external alarm 1 2 3 4 One of the ADC PCB inputs has been activated check the situation of the devices connected to this PCB A56 A57 generator general alarm The generator has sent an alarm check directly on the GE socomec UPS 52 IOMMASGPXX01 GB_00 Innovative Power Solutions 9 PROBLEM SOLVING MASTERYS Green Power 10 40 kVA A61 wrong phase cycle direction The phase cycle sequence is incorrect In this case invert two phases of the input mains For a UPS with separate auxiliary mains exchange the two phases of the auxiliary mains only 9 2 UPS ALARMS A01 battery alarm Failure or problem on the battery circuit Check that the battery switch is closed A18 inverter blocked due to overload Reduce the load rate applied to the UPS and reset the alarms A20 wrong configuration Error in the configuration parameters please contact the support service ENGLISH A30 block due to overload Reduce the load rate applied to the UPS and reset the alarms A42 T Service general alarm The MASTERYS products can be remo
64. tre authorised by SOCOMEC UPS Ifthe battery has not been recharged in accordance with the terms indicated on the packaging and in the manual in cases of extended storage or UPS inactivity SOCOMEC UPS may at its own discretion opt for the repair of the product or for the replacement of the faulty or defective parts with new parts or with used parts that are equivalent to new parts with regard to functions and performance Defective or faulty parts replaced free of charge are to be put at the disposal of SOCOMEC UPS who becomes the sole owner Replacements or repairs of parts and any modifications to the product during the warranty period cannot extend the duration of the warranty In no case will SOCOMEC UPS be responsible for damages including without limitations damage for loss of earn ings interruption of activity loss of information or other economic losses deriving from the use of the product The present conditions are subject to Italian law Any dispute falls under the province of the Court of Vicenza socome Innovative Power Solutions UPS IOMMASGPXX01 GB 00 5 ENGLISH PJ SAFETY MASTERYS Green Power 10 40 kVA 2 1 IMPORTANT This document provides important instructions for the safe use movement and connection of the MASTERYS un interruptible power system UPS SOCOMEC UPS retains the full and exclusive ownership rights over this document Only a personal right to utilize the document
65. ucts may have to be adapted For such uses we would advise you to contact SOCOMEC UPS beforehand to confirm the ability of these products to meet the requested level of safety performance reliability and compliance with applicable laws regulations and specifications 2 2 DESCRIPTION OF THE SYMBOLS USED ON THE LABELS APPLIED TO THE UNIT All the precautions and the warnings on the labels and plates on the inside and outside of the equipment should be respected AN DANGER HIGH VOLTAGE BLACK YELLOW L GROUND TERMINAL LL READ THE USER MANUAL BEFORE USING THE UNIT ive Power Solutions UPS IOMMASGPXXO01 GB 00 7 ENGLISH UNPACKING AND INSTALLATION MASTERYS Green Power OF THE UNIT 10 40 kVA The packaging guarantees the stability of the UPS during shipping and physical transfer Carry the packaged unit as close as possible to the installation site AN When moving the unit on even slightly sloping surfaces use the blocking equipment and break ing devices to ensure that the unit does not fall over 3 1 SHIPPING AND MOVING XL a v 2 AN gt P 8 IOMMASGPXX01 GB_00 UPS must remain in a vertical position during all shipping and moving operations The unit has wheels that can be used to move it for short distances Ensure that the floor is strong enough to support the weight of the UPS and of the battery cabinet if used Avoid pressing on the front panels when movi
66. va shutdown clients Notification of anomalies via e mail to a maximum of 8 addresse NET VISION is a solution for managing UPS units connected directly to the local VISION network It is normally used on medium large complex networks and in multi server environments where the IT manager centrally controls all the network re sources The physical position of the UPS is not significant The main functions are 10 100Mb Ethernet connection RJ45 Graphic monitoring of the UPS web browser Remote shutdown of up to 40 computers Notification of anomalies via e mail to a maximum of 8 addresses UPS management using SNMP protocol Diagnostics via Internet offered by e Service Java amp NET shutdown Client JNC is an optional Java application to be installed Java on a server for the automatic shutdown of the computers on the network before amp NET Client the UPS stops due critical operating conditions imminent battery failure overload etc It is supplied as an option and can be associated to the UNI VISION PRO NET VISION communication solutions The main features functions are Use of the TCP IP standard network protocol Graphics interface for easy configuration Minimum use of CPU resources Personalisation of shutdown parameters and script Continuous monitoring of the efficiency of the connection to the UPS Innovative Power Solutions 5 0 IOMMASGPXX01 GB
67. which is from inverter returns automatically a few seconds after the overload disappears when the voltage generated by the inverter goes is out of tolerances due to a major overload or a fault on the inverter WWhen the internal temperature exceeds the maximum value allowed Battery mode In the event of a mains failure micro interruptions or extended black outs the UPS continues to power the load using the energy stored in the battery The Expert Battery System keeps the user constantly informed on the battery status and on the back up time available The disconnection of non mission critical applications during battery discharge can be programmed after a certain laps of time by using the Power Share option so that the battery resources can be reserved for the most critical applications 4 2 OPERATION IN HIGH EFFICIENCY MODE The UPS has selectable and programmable economy operating mode that can increase overall efficiency by up to 9896 for energy saving purposes With this mode of operation specific daily or weekly time intervals can be selected and programmed to power the applications directly from the auxiliary mains If the power supply outage the UPS will automatically switch onto the inverter and continue to supply power to the load by drawing energy from the battery This mode does not provide perfect stability in frequency and voltage like the ON LINE mode Thus the use of this mode should be carefully evaluated
68. y common with the neutral of the main input feed line 2 sSocome 14 IOMMASGPXX01 GB_00 Innovative Power Solutions UPS UNPACKING AND INSTALLATION MASTERYS Green Power OF THE UNIT 10 40 kVA 3 5 INSTALLATION PROCEDURES AND INSTRUCTIONS WARNING N Before carrying out work on the terminal board or on UPS internal parts ensure that the UPS is switched off remove the power supply open the external battery cabinet disconnectors isolate the system and wait 5 minutes Cable specifications stripping length 18 mm tightening torque 2 5 4 5 Nm ENGLISH T zl Connections if THE MAINS AND AUX MAINS ARE CONNECTED IN COMMON r coag EXT BATTERY L12 L22 OUTPUT 132 ative Power Solutions UPS IOMMASGPXXO01 GB 00 15 UNPACKING AND INSTALLATION MASTERYS Green Power OF THE UNIT 10 40 kVA Connections if THE MAINS AND AUX MAINS ARE CONNECTED SEPARATELY p 2 mr J 2 82 2 1 EXT BATTERY OUTPUT 16 IOMMASGPXX01 GB 00 tive Power Soluti UNPACKING AND INSTALLATION MASTERYS G

Download Pdf Manuals

image

Related Search

Related Contents

最小・最軽量の2スロットPocket PC。  取扱説明書  RFID Xpr3ss - User Manual  Guía de implementación de Dell Storage con Espacios de  Sistema Cosmos L  User Manual - Northeastern University Libraries  Télécharger le PDF  カーボン―FRP タンクパット 取扱説明書  BALL LOADER This Manual Contains: SPECIFICATIONS  Phonix S900CWA mobile phone case  