PA7300 LonWorks Application Manual - TECO
Contents
1. nciDrvSpeedScale Configure nviDrvSpeedScale default Bu EB SCPTdefScale value Men 8 18 7300PA T ECO LonWorks Application Manual Parameter Name Description Range ee nciEnergySave Configure energy saving available or ng SNVT_switch unavailable Get SE aged nciAuxSel Configure the functions of analog input g ECH SNVT_count Terminal Aux SCH GE age nciPID_Pgain z SNVT multiplier Configure proportion gain of PID function 0 01 10 00 Bn 14 Page 12 nciPID_Itime A i b SNVT_time_sec Configure integrate time of PID function 0 0 100 0 sec Bn 15 Page 12 nciPID_Dtime e etl g g SNVT_time_sec Configure differential time of PID function 0 0 1 0 sec Bn 16 Page 12 nciFeedBackScl SNVT_multiplier Configure PID feedback value gain 0 01 10 00 Bn 13 Page 12 nciProFreq1 ae Cn 16 SNVT_freq_hz Configure prohibit frequency 1 0 0 180 0 Hz n Page 12 nciProFreq2 Configure prohibit frequency 2 0 0 180 0 Hz Cn 17 Page 12 SNVT_freq_hz gurep ln g nciProFreq3 Configure prohibit frequency 3 0 0 180 0Hz Cn 18 Page 12 SNVT_freq_hz gure p quency 3 g nciProFreqBW sii S Cn 19 SNVT_freq_hz Configure range of prohibit frequency 0 0 25 5 Hz Page 12 nciAutoRstart f Cn 36 SNVT_count Configure number of auto restart attempt 0 10 Page 12 nciStalllevAcc Configure acceleration stall prevention g S Cn 28 SNVT_count level
2. 0 Set R2A R2C action It is available while Sn 20 0F only 1 Set DO1 action It is available while Sn 21 0F only 2 Set R1A R1C action It is available while Sn 22 0F only 3 15 Reserved 16 18 7300PA TEC LonWorks Application Manual 6 Multi function Analog Terminal Output nviAo1Command nviAo2Command e When Sn 26 0A nviAoiCommand is available for setting inverter analog input terminal Ao1 100 compares to Ao1 output 10V e When Sn 27 0A nviAo2Command is available for setting inverter analog input terminal Ao2 100 compares to Ao2 output 10V 7 Inverter Fault Status nvoFault e nvoFault can monitor the inverter fault status Bit Function 0 Over current OC or ground fault GF 1 Over voltage OV Inverter over load OL1 OL2 Inverter over heat OH 4 6 Reserved 7 External Fault EF3 EF5 EF6 EF7 EF8 Control loop exception CPFO2 EEPROM exception CPFO3 EEPROM code exception CPF04 or A D exception CPFO5 9 Motor over load OL3 10 11 Reserved Under voltage or instantaneous stop protection UV1 control loop voltage over lower UV2 or MC fault UV3 13 15 Reserved 12 8 Inverter Multi function Output Terminals Monitor nvoDoStatus e The following is the nvoDoStatus bit and content description Bit Function Multi function terminal R2A R2C output 0 Comply with Sn 20 Factory set runnin
3. 11 18 7300PA T ECO LonWorks Application Manual 9 PID Proportion Gain nciPID_Pgain Integrate Time nciPID_ITime Differential Time nciPID_Dtime and Feedback Scale nciFeedBackScl e nciPID_Pgain can configure PID proportion gain 10 nciPID_ITime can configure PID integrate time nciPID_Dtime can configure PID differential time nciFeedBackScl can configure PID feedback scale Before executing PID please ensure that nciAuxSel is set to 9 Prohibit Frequency1 nciProFreq1 Prohibit Frequency2 nciProFreq2 Prohibit Frequency3 nciProFreq3 and Prohibit Frequency Range nciProFreqBW Inverter 7300PA has three groups of prohibit frequency to prevent mechanical resonance frequency After setting the motor will accelerate decelerate in prohibit range frequency range but not running in constant speed in the range Any of the prohibit frequency setting to 0 means such function is invalid Prohibit frequency range setting to 0 means all the prohibit frequencies are invalid Setting of prohibit frequency should comply with the following regulation nciProFreq1 gt nciProFreq2 gt nciProFreq3 It is available for setting this property under PRGM mode only 11 Number of Auto Restart Attempt nciAutoRstart e nciAutoRstart can configure number of auto restart attempt in particular faults Such number set to 0 means auto restart is unavailable e For more information on auto restart function please refer to Cn 36 description in
4. Cn 03 Cn 01 set value It is also available for setting parameters provided by PA L using Config software now Then switching 7300PA inverter to DRIVE mode It is available for controlling the inverter 7300PA by LonWorks network 2 Inverter Communication Status If there is error in communication between PA L inverter card and 7300PA the digital operator will show the warning message Follow is the description 1 The digital operator will blink RS 485 comm Ready or CALL while receiving no data in 1s after inverter start Such message will disappear in receiving data 2 The digital operator will display warning RS 485 comm Fault 1 or CPF21 if receiving no data in 1s after communication succeed 3 If the baud rate data bits stop bit or parity of data received by the inverter is not correct the digital operator will blink RS 485 comm Fault 2 or CPF22 4 18 7300PA T ECO LonWorks Application Manual 7 LonWorks Communication Illustration PA L interface card applies LonMark object and LonWorks communication LonMark object of PA L interface card consists of two objects Node and VSD S N 6010 LonMark Functional Profile Definition as following figure PA L Interface Card Data of node and VSD objectors divided into two sorts 1 Network Variable NV also divided into Input Network Variable NVI and Output Network Variable NVO The former NVI can control status of LonWorks interface card and
5. Inverter 7300PA user manual e Itis available for setting this property under PRGM mode only 12 Stall Prevention Level during Acceleration nciStallLevAcc Stall Prevention Level during Running nciStallLevRun e nciStalllevAcc configure acceleration stall prevention level of Inverter inverter nominal current 100 e nciStallLevRun configure running stall prevention level of Inverter inverter nominal current 100 e Inverter nominal current is based on the one labeled on nameplate e Such parameter of Inverter 7300PA is available for setting under PROGRAM mode 12 18 7300PA TEC LonWorks Application Manual 2 Network Variable Description The following list on 20 network variables 6 input network variables and 14 network variables providing by PA L interface card is the detailed description Variable Name Description perto page nviDrvSpeedStpt To control run stop and provide low resolution frequency Page 15 SNVT_switch command frequency command is in nciNmIFreq percentage 9 nviDrvSpeedScale To control nviDrvSpeedStpt fine scale of frequency command Page 16 SNVT_lev_percent Negative value is the reverse running command 9 nvoDrvCurnt To monitor the output current Unit is 0 1A 2 SNVT_amp nvoDrvSpeed To monitor the output frequency Output frequency show in SNVT_lev_percent nciNmlFreq percentage nvoDrvVolt To monitor output voltage Unit is 1V es SNVT_volt To contro
6. Value e Monitor input of Multi function analog terminal VIN AIN with range 0 100 e nvoAil Value 0 100 compares to VIN input 0 10V or AIN input 4 20mA If both VIN AIN are input the inputs of VIN AIN will be added before transferring to percentage 18 18
7. function input terminals and multi function 1 4 providing by nviOpCommands are both available for switching Please refer to page 16 or Sn 15 Sn 18 description in Inverter 7300PA user manual for more information 4 Max Send Time nciSndHrtBt e nciSndHrtBt sets Max send time of PA L interface card sending data of nvoDrvCurnt nvoDrvSpeed and nvoDrvVolt e f network variables in PA L are bound with other network variables PA L interface card will inform the later to modify automatically as long as the former is modified Setting nciSndHrtBt can compel Pa L interface send network variables periodically even the said variables is not modified e Setting 0 to nciSndHrtBt indicates that max send time is invalid and PA L sends data only when the network variables are modified 10 18 7300PA T ECO LonWorks Application Manual 5 Max Receive Time nciRcvHrtBt nciRcvHrtBt sets Max receive time of PA L interface card receiving data of nviDrvSpeedStpt and nviDrvSpeedScale If the said variables have still not been refreshed by other module in the LonWorks network in the specified time the interface card will change them to default value and pause the communication with the inverter If there is any module sending operation and frequency command periodically such function will monitor the communication error of LonWorks network Setting 0 to nciSndHrtBt indicates that max receive time is invalid The inverter will run at th
8. inverter while the later NVO can monitor the status of them Each network variable has individual type On the LonWorks network network variables with same type can bind with each other When one of them is changed the others will correspondingly adjust Configuration Property to control inverter configuration and save the parameters and data S Configuration Property can be modified by LonWorks network configuration software as LonMaker Integration Tool etc only Other devices can not modify them VSD object content will be illustrated in the next section 5 18 7300PA T ECO LonWorks Application Manual 8 VSD Illustration VSD object provides 20 network variables 6 input network variables and 14 output network variables and 26 configuration properties The function of VSD object is briefly described Variable Speed Motor Drive Object 1 nviDrvSpeedSipt SNVT_ switch LonMark Mandatory Network Variables nvoDrvSpeed SNVT_lev_percent nviDrvSpeedScale nvoDrvCurnt SNVT_lev_percent SNVT_amp nvoDrvVolt SNVT_volt LonMark Optional Network Variables LonMark Mandatory Configuration Properties nciNmISpeed nciMinSpeed nciRampUpTm nciSndHrtBt nciNmIlFreq nciMaxSpeed nciRampDownTm LonMark Optional Configuration Properties nciRcvHrtBt nciMinOutTm nciLocation nciDrvSpeedScale nviOpCommands nvoOpStatus SNVT_state SNVT_state 7300PA nviDoCommands Network Variables nvoOpStatus
9. 2 SNVT_state SNVT_state Continued on the next page 6 18 7300PA TECO LonWorks Application Manual Continued from the previous page nviAo1 Command nvoDrvFreqHz SNVT_lev_percent SNVT_freq_hz nviAo2Command nvoDcVolt SNVT_lev_percent SNVT_volt nvoFault SNVT_ state nvoAi1 Value SNVT_lev_percent 7300PA Network Variables nvoAi2Value SNVT_lev_percent nvoDiStatus SNVT_state nvoDoStatus SNVT_ state nvoPIDCommand SNVT_lev_percent nvoP DFeedback SNVT_lev_percent 7300PA Configuration Properties nciEnergySave nciPID_Pgain nciPID_Dtime nciProFreq1 nciProFreq3 nciAutoRstart nciStallLevRun nciRampDownTm2 nciAuxSel nciPID_Itime nciFeedBackScl nciProFreq2 nciProFregBW nciStallLevAcc nciRampUpTm2 7 18 TECO 7300PA LonWorks Application Manual 1 Configuration Property Description The following are the configuration properties provided by PA L interface card The property type will be listed below the parameter name If the type begins with SNVT such property can be used as network variable Some of the configuration property has the one corresponding to inverter 7300PA Such property has two adjusting methods Refresh Method Adjusting via LonWorks Network Adjusting via inverter operation panel Refreshed right away Refreshed in the next start LonWorks Network Data Refreshed right away Inverter Parameter Refreshed right away The parameters Cn Sn in inver
10. Application Manual 7300PA TEC LonWorks TECO Frequency Inverter 7300PA LonWorks Communication Interface Application Manual Version 01 7300PA TEC LonWorks O a Ff WO N Application Manual Table of Content dee UI Le EN 2 SPOCHICAUON ii ciciniscnceaccuindcccevandwanswencuaccdenduancueaduasedendeeadsendwadsvandvan dandwassdencuaacdertuaatiuausuasidndetudue 2 Wire Connection Diagramm 0000000000000 00a anna aan nn nun han 2 Terminals LED and Button Description uunnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn 3 UE GUENIN 4 Inverter SEllINd E cicincecnisentencwindadnevenduensdincuicacentranautadwessdeadeentdancuaddencvacdedsedunkaianauaacundvtuaue 4 Te SOt MOH secaccscuceccccearcacssausncaedeuciaasteesnaucteuscencsastnandautiaadddadaanddesdaantaduaeesaedeanastadedeaaddediien mare 4 2 Inverter COMMUNICATION Status iciciciccsiscicccescaaccccacndsvencwandeenecaacsonssdecusaccancsonesdadwesceandeenade 4 Lonworks Communication illustration uuu044004000000000nnnnn nn nnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn 5 VGU e TR 6 1 Configuration Property Description uuursesssnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn 8 2 Network Variable Description ssu auuscuus0soaawunan nun nu dan annnnnann nun anna nnnannnnnn nnmnnn nenna 13 1 18 7300PA 1 Introduction T ECO LonWorks Application Manual The manual covers communication between PA L interface car
11. BIT 1 Multi function terminal DO1 output Page 17 e BIT 2 Multi function terminal R1A R1C output e BIT 8 15 Reserved nvoPIDCommand Reserved SNVT_lev_percent nvoDoStatus SNVT_state nvoP IDFeedback To monitor input of PID feedback value shown in percentage SNVT_lev_percent 0 means PID does not start 1 RUN STOP Command nviDrvSpeedSipt State e nviDrvSpeedSipt divides into State and Value to control RUN STOP command and frequency command e nviDrvSpeedSipt State content nviDrvSpeedSipt State 0 STOP command nviDrvSpeedSipt State 1 RUN command nviDrvSpeedStpt State 1 command idle default e Under following circumstances such variable will be default value e After power on the machine and before reading the network variable e No nviDrvSpeedStpt or nviDrvSpeedStpt commands received during the min receiving time nciRcvHrtBt 2 Frequency Command nviDrvSpeedSipt Value e nviDrvSpeedSipt Value and nviDrvSpeedScale control the frequency command The actual frequency command is as following Command nclNmlFreq x nviDrvSpeedStpt Value x nviDrvSpeedScale e the 1 unit of nviDrvSpeedStpt value shows 0 5 which range from 0 100 Thusly 0 means to 0 200 and above 200 means 100 15 18 7300PA TEC LonWorks Application Manual 3 Frequency Command Scale and Forward Reverse RUN nviDrvSpeedScale e nviDrvSpeedScale range from 163 84 to 163 84 Positive value repre
12. command loss e BIT 13 15 Reserved Page 18 nvoDrvFreqHz SNVT_freq_hz To monitor output frequency unit is 0 1Hz nvoDcVolt SNVT_volt To monitor DC voltage unit is 1V nvoFault SNVT_state To monitor present fault content e BIT O Over Current OC or ground fault GF BIT 1 Over Voltage OV BIT 2 Inverter Over Load OL1 OL2 BIT 3 Inverter Over Heat OH e BIT 4 Reserved e BIT 5 Reserved e BIT 6 Reserved BIT 7 External Fault EFxx e BIT 8 Control Loop Fault CPFxx e BIT 9 Motor Over Load OL3 e BIT 10 Reserved e BIT 11 Reserved e BIT 12 Under voltage or MC Damage UVx e BIT 13 15 Reserved Page 17 nvoAi1 Value SNVT_lev_percent To monitor multi function terminal VIN AIN input in percentage Page 18 nvoAi2Value SNVT_lev_percent To monitor multi function terminal AUX input 100 to input 10V 14 18 7300PA T ECO LonWorks Application Manual Refer to Variable Name Description Page To monitor multi function digital input terminal status e BIT 0 Terminal close e BIT 1 Terminal 2 close BIT 2 Terminal close nvoDiStatus BIT 3 Terminal close SNVT_state BIT 4 Terminal close e BIT 5 Terminal close BIT 6 Terminal close BIT 7 Terminal close BIT 8 15 Reserved To monitor multi function output terminal status e BIT O Multi function terminal R2A R2C output
13. d and 7300PA inverter installed with such card with other modules in LonWorks network 2 Specification Part Number 4H300D5960002 Transceiver Echelon free topology transceiver FTT 10A Baud Rate 78 kps Communicatio n Specification Connect Medium Twisted wire Communication Status 3 LED indicators Outline Dimension 63mm x 86mm Network Variables and Configuration Properties 20 Network Variables and 26 Configuration Properties Controlling Functions Inverter RUN STOP Forward Reverse RUN Frequency Command External Fault Fault Reset 4 Multi Function Commands All the Output of Analog Digital Output Terminal Monitoring Function Product Features Inverter status Fault Content Output Frequency Voltage Current and DC voltage All Outputs of Digital Output Terminal All Inputs of the Analog Digital terminal PID Feedback Value Setting Function AUX Function Setting PID Gain 3 Jump Frequency 2 Group Acceleration and Deceleration Time Stall prevention Level during Running and Acceleration Number of Auto Restart Attempt Energy saving 3 Wire Connection Diagram 7300 PA To Lon Networks 2 18 7300PA 4 Terminals LED and Button Description SO LED2 LED3 1 Terminals TECO LonWorks Application Manual ECHELON FTT 10A Description CN1 Connect with 7300PA 2CN ter
14. e default soeed as long as LonWorks network fault on communication 6 Min Send Time nciMinOutTm nciMinOutTm sets Min send time of PA L interface card sending data of nvoDrvCurnt nvoDrvSpeed and nvoDrvVolt If network variables in PA L are bounded with other network variables PA L interface card will inform the later to modify automatically as long as the former is modified Setting nciSndHrtBt can avoid certain network variables densely sending to influence the performance of LonWorks network Setting 0 to nciMinOutTm indicates that min send time is invalid 7 Energy saving Selection nciEnergySave nciEnergySave divides into State and Value while can configure the energy saving function is available or not State 0 or Value 0 such function is unavailable State 1 or Value 100 such function is available It is available for setting this property under PRGM mode only 8 Multi function Analog Input Terminal Aux Selection nciAuxSel nciAuxSel can configure the inverter multi function analog input terminal Aux function If nciAuxSel is set to 9 which starts PID function terminal Vin or Ain are set as PID feedback value For more information on multi function terminal Aux function please refer to Sn 19 description in Inverter 7300PA user manual For more information on PID function please refer to PID function in Inverter 7300PA user manual It is available for setting this property under PRGM mode only
15. eee EE nciStallLevRun Cn 30 SNVT_count Configure running stall prevention level 30 170 Page 12 nciRampUpTm2 AE p d SNVT_time_sec Configure 2nd acceleration time 0 0 6000 0 sec Bn 03 Page 10 nciRampDownTm2 rere g SNVT_time_sec Configure 2nd deceleration time 0 0 6000 0 sec Bn 04 Page 10 1 These parameters only can be modified after switching to Program mode 9 18 7300PA T ECO LonWorks Application Manual 1 Motor Rated Speed nciNmISpeed e nciNmISpeed can configure the rated speed of motor Please input the relevant data on the motor nameplate 2 Motor Rated Frequency nciNmlFreq e nciNmlFreq can configure the rated frequency of motor which is the base of the frequency command output frequency frequency lower limit and upper limit Please input the data comply with the motor nameplate e Itis available for setting this property under PRGM mode only 3 Acceleration Time 1 nciRampUpTm Deceleration Time 1 nciRampDownTm Acceleration Time 2 nciRampUpTm2 and Deceleration Time 2 nciRampDownTm2 e nciRampUpTm and nciRampUpTm2 can configure the running time from zero speed to nominal speed nciRampUpDown and nciRampUpDown 2 can configure the running time from nominal speed to zero speed Actual accelerate decelerate time is SET value of accel decel time x nviDrvSpeedStpt x nviDrvSpeedScale e Inverter 7300PA has two groups of acceleration and deceleration time The multi
16. g 4 Multi function terminal DO1 output Comply with Sn 21 Factory set zero Speed 2 Multi function terminal R1A R1C output Comply with Sn 22 Factory set frequency agree 3 15 Reserved 17 18 7300PA T ECO LonWorks Application Manual 9 Inverter Status Monitor nvoOpStatus nvoOpStatus2 e The following is the nvoOpStatus bit and content description Bit Function 0 1 Running 4 1 Reverse 0 Forward 2 1 Inverter is ready to operate DRIVE mode with no alarm fault 3 1 Exception but not CPF00 CPFO1 4 15 Reserved e The following is the nvoOpStatus2 bit and content description Bit Function 0 1 Running 4 1 Zero Speed 1 Frequency Agree lt Output frequency lt Frequency Command Frequency Command Cn 22 Cn 22 1 Frequency Agree and Cn 21 Cn 22 lt output frequency lt Cn 21 Cn 22 1 Frequency detection 1 Refer to right figure cn 22 A Ne Cn 21 1 Frequency detection 2 Refer to right figure Fdetection1 1 0 1 Fdetection2 o 1 Lo 6 Reserved 7 1 Under voltage detection 8 1 Inverter has no output 9 10 Reserved 11 1 Over torque detection Detection Level Cn 26 Detection Time Cn 27 12 1 Frequency command loss 13 15 Reserved 10 Inverter Analog Input Monitor nvoAi1
17. l following command BIT 0 External Fault EB e BIT 1 Fault Clear RESET nviOpCommands e BIT 2 Multi function command 1 Page 16 SNVT_state e BIT 3 Multi function command 2 g e BIT 4 Multi function command 3 e BIT 5 Multi function command 4 e BIT 6 15 Reserved To control output of multi function output terminals e BIT 0 R2A R2C output e BIT 1 DO1 output Page 16 e BIT 2 R1A R1C output e BIT 3 15 Reserved nviAo1Command To control the output of multi function analog output terminal nviDoCommands SNVT_state SNVT_lev_percent AO1 100 is corresponding to 10V Page 17 nviAo2Command To control the output of multi function analog output terminal Page 17 SNVT_lev_percent AO2 100 is corresponding to 10V g To monitor the inverter status e BIT O running nvoOpStatus e BIT 1 reverse running Page 18 SNVT_state e BIT 2 operation is ready g e BIT 3 fault e BIT 4 15 reserved 13 18 7300PA TECO LonWorks Application Manual Variable Name Description Refer to Page nvoOpStatus2 SNVT_state To monitor the inverter status BIT 0 Running BIT 1 Zero speed e BIT 2 Frequency Agree e BIT 3 Setting Frequency Agree e BIT 4 Frequency Detection 1 e BIT 5 Frequency Detection 2 e BIT 6 Reserved e BIT 7 Under Voltage detection e BIT 8 Inverter no output e BIT 9 10 Reserved BIT 11 Over Torque detection e BIT 12 Frequency
18. minal on control board TB1 Lon Network terminal 2 LED LED Function Description LED1 SERVICE Indicator an REST Sad witholt LED2 Sendindcator Blnkng indicates sending the data of LEDS Receive Indicator Blinking indicates the inverter receiving 3 Button SW1 LonWorks Service Pin 3 18 7300PA T ECO LonWorks Application Manual 5 Installation Method 1 Cut off inverter power supply 2 Plug two inside isolation pins in holes on 7300PA control PA L CN1 board Set up PA L interface card on the control board The two installation holes should be right to isolation pins CN1 to 2CN of the control board Connect the LonWorks net wire to terminal TB1 on PA L interface card w E mm Control Board 2CN X lt Isolation Pin Control Board 6 Inverter Setting 1 Set method 1 Start inverter 7300PA and switch to PRGM mode then set the following parameters 3 Sn 08 1100 Frequency and RUN STOP command provided by RS 485 continuously running in communication error Sn 23 1 Inverter Address 1 Sn 24 1100 Baud Rate 19200 BPS without parity check Cn 31 01 0 s communication checkout time 1s Restarting power supply after setting the parameters ensures normally communication between Inverter 7300PA and PA L interface card In stop mode switch inverter 7300PA to PRGM mode and set the following parameters Sn 02 4 V f pattern set by parameter
19. sents forward running command while negative value reverse command e Default value of nviDrvSpeedScale is determined by nciDrvSpeedScale e Here is an illustration on the relationship between frequency command said variable and actual frequency command nciNmlFreq nviDrvSpeedStpt Value nviDrvSpeedScale Actual Frequency 60Hz 100 100 Forward Run 60Hz 60Hz 80 75 Forward Run 36Hz 50Hz 80 100 Reverse Run 40Hz 4 Inverter Operation Command nviOpCommands e nviOpCommands can configure inverter external fault fault clear reset and multi function command Description is as following Bit Function Set external fault Malfunction terminals R3A R3C close as there is no output in inverter 1 Fault clear RESET It can clear fault while nviDrvSpeedStpt State 0 Multi function command 1 0 A Actual function is determined by Sn 15 default is Multi step speed 1 3 Multi function command 2 Actual function is determined by Sn 16 default is Multi step speed 2 4 Multi function command 3 Actual function is determined by Sn 17 default is JOG command 5 Multi function command 4 Actual function is determined by Sn 18 default is external fault 6 15 Reserved 5 Multi function Terminal Output nviDoCommands e nviDoCommands matching with 7300PA parameters setting can configure the output of multi function terminal DO1 R1A R1C and R2A R2C Bit Function
20. ter 7300PA only can be modified in PRGM mode If the configuration property corresponding to parameter Cn Sn is required modifying such action should be done after switching to PRGM mode when the inverter is in stop mode Parameter Name Description Range eats Bieler 10 arameter page nciNmISpeed Configure rated speed of the motor with SCPTnomRPM default 1800 RPM N ee nciNmIFreq Configure rated frequency of the motor Cn 02 SCPTnomFreq with default 60 0Hz Se ere foe reese nciMinSpeed Configure lower frequency limit on up SCPTminSetPoint percentage of rated frequency 200 SE nciMaxSpeed Configure upper frequency limit on Cn 14 SCPTmaxSetPoint percentage of rated frequency 1009007109 909 m nciRampUpTm DE SCPTrampUpTm Configure acceleration time of the motor 0 0 6000 0 sec Bn 01 Page 10 eee ee Configure deceleration time of the motor 0 0 6000 0 sec Bn 02 Page 10 nciSndHrtBt Configure max send time of nvoDrvCurnt SCPTmaxSendTime nvoDrvSpeed and nvoDrvVolt Default 0 s GOSS SRE u Page AR nciRcvHrtBt Configure max receive time of nviDrvSpeedStpt nviDrvSpeedScale 0 0 6553 4 sec Page 11 SCPTmaxRcvTime Default 0 s iMinOutT Configure min send time of nvoDrvCurnt SCPTminsen Time nvoDrvSpeed and nvoDrvVolt 0 0 6553 4 sec Page 11 Default 0 5 s nciLocation i String length SCPTlocation Label the location of the motor or inverter 24 characters