User`s Manual SVERKER 650
Contents
1. MEASUREMENT SECTION Timer Range 0 999 999 s Resolution 1 ms Accuracy 0 02 0 2 ms of displayed value Inde pendent of mains frequency Ammeter Built in 0 10 A 0 100 A Accuracy 3 Output for external ammeter connected to built in current transformer Accuracy 0 5 OTHER Application field The instrument is intended for use in high voltage substations and industrial environments Built in capacitor provides phase shift when testing directional protection and a set of resistors can be used to divide voltages Protection Thermal cut outs and miniature circuit breakers Mains voltage 115 or230 VAC 10 50 60 Hz Dimensions 280x 178x250mm 11 x7 0 x 9 8 Weight 115 V 15 3 kg 33 7 lbs 25 4 kg 56 lbs incl accessories and transport case Weight 230V 16 3 kg 35 9 Ibs 25 4 kg 56 lbs incl accessories and transport case Complies with IEC 348 and Dielectric strength TEC255 5 The above specifications are valid at nominal input voltage and an ambient temperature of 25 C 77 F Specifications are subject to change without notice The contents of this manual are the property of Programma Electric AB No part of this work may be reproduced or transmitted in any form or by any means except as permitted in written license agreement with Programma Electric AB Programma Electric AB has made every reasonable attempt to ensure the completeness and accuracy of this document However
2. the information contained in this manual is subject to change without notice and does not represent a commitment on the part of Programma Electric AB Any attached hardware schematics and technical descriptions or software listings that disclose source code are for informational purposes only Reproduction in whole or in part to create working hardware or software for other than Programma Electric AB products is strictly prohibited except as permitted by written license agreement with Programma Electric AB Subject to change without notice Printed matter No ZP BAO1E RO4B 2002
3. SVERKER 650 Relay Test Unit Programma Products Users Manual SVERKER 650 Ui U2 U3 ion OREN Ss S RE A 40 4 gt R wia ld U4 Sia ca 0 250V gt 0 350V E P3 i U5 10 u F 450V i mn E i F2 W2 ay w3 E2 s P2 P1 S4 U7 Mains output _ i U6 Fi El R5 ins input Mai p 5 RO1900 p tl 3 O gt 4 2 Programma 130 220V O i Terminals Unloaded 230 V E2 Yellow signal lamp in the trip circuit U1 0 10 A 85 90 V AC Settable with T1 P1 Electric timer independent of mains frequency U2 0 40 A 25 27 V AC Settable with T1 Measuring range 0 999 999 sec Accuracy 0 002 U3 0 100A 10 0 11 0V AC Settable with T1 of readout 0 2ms U4 0 250 V 3 A 250 270 V U5 0 350 V 2A 350 370 V DC Settable with T1 U6 20 220 V DC Settable with R5 The voltage is stabilized and variable in two steps with the switch S3 Characteristics at input voltage 220 V AC 10 Ripple peak to peak max 4 Load regulation 3 Line regulation less than 4 U7 110V 0 3 A 110 125 V AC F1 Automatic cut out for the mains voltage 4 A F2 Automatic cut out 3 A F3 Automatic cut out 0 5 A E1 Green indicator for mains voltage AC Settable with T1 P2 P3 c1 S1 S2 s3 S4 R5 Input for stop of timer Ammeter class 1 5 Capacitor 10 F 450 V AC for reactive power relays Main switch On off switch for terminals U6 and U7 Selector voltage range terminal U6 Make break switch for timer Voltage adjustment terminal
4. U6 W1 Terminal for connection of a resistor on the primary side of the output transformer W2 Terminal for an external ammeter W3 Terminal for external start and stop of timer Programma Electric AB ZP BAO1E RO4B General The power unit is a rugged instrument but it still should be handled with care The relay testing unit is electrically fully isolated in all measuring ranges except for the mains output The set of resistors is not connected with the rest of the relay testing unit set When current measurement is crucial use an external instrument with a more accurate resolution The external instrument can be connected to the built in current transformer terminal W2 Relays with non linear impedance can cause distortion of the current This can be restrained by connecting a resistance as high as possible in series with the primary winding of the output transformer terminal WI The output transformer is protected by a thermal contact If the thermal contact trips the display of the timer will go out The thermal contact will be reset automatically when the temperature drops The output U6 is provided with over current protec tion that will break the circuit in case of overload The protection is reset if S2 is switched off in aprox 30 seconds Instructions 1 Make sure that the switch and the variable transformer is set in position 0 2 Connect the test leads 3 The variable transformer should alw
5. ays be set in posi tion 0 when a test is started Attention The terminal of the current trans former shall always be short circuited when current is flowing from the instru ment either through the short circuit clamp or through an external ammeter nnn nnn nnn A N Do not leave the Sverker 650 switched on unattended Testing current relays 1 Set the variable transformer in position 0 2 Connect the circuit use output terminals 0 10 A 85 V 0 40 A 25 V or 0 100 A 10 V 3 Increase the current to the operating value using the variable transformer 4 Check the current on the ammeter or external instrument during the test Programma Electric AB ZP BAO1E RO4B SVERKER 650 Testing voltage relays 1 Set the variable transformer in position 0 2 Connect the circuit Output terminals 0 250 V or at a voltage below 10 V output terminals 0 100 A If you need a higher AC voltage terminals 0 250 V can be connected in series with the mains output terminals When testing DC voltage relays use terminals 0 350 V 3 Increase the current to the operating value using the variable transformer 4 Check the current on the ammeter or external instru ment during the test Use an external measuring instrument for better accu racy Testing power relays 1 Set the variable transformer in position 0 2 Connect the circuit Output terminals 0 10 A 0 40 A or 0 100 A are used for the current c
6. oil Use an external measuring instrument for better accuracy When testing reactive relays the current coil is to be connected in series with the built in 10mF capacitor that will give a 90 phase shift The voltage coil is to be connected directly to the 110 V AC terminals or across the set of resistors used as a voltage divider 3 Increase the current to the operating value using the variable transformer 4 Check the current on the ammeter or external instru ment during the test ee ee Note Shift polarity of the voltage or current if function has failed to appear Time measurement Connect the time measuring circuit to potential free terminals or DC voltage 3 350 V Note If the polarity is shifted the timer does not stop The timer is independ ent of mains frequency When the timer is stopped the circuit is broken and the yellow signal lamp is lit For continued measuring the main switch first has to be reset in position 0 If the tripping circuit is connected and the switch is set in position ON the yellow signal lamp is lit when the operating value is obtained without breaking the current The timer can be started externally by a make at terminal W3 The switch S1 should then be in position ON TIME or OFF TIME When using the timer internally the terminal W3 has to be short circuited Time measurement of over current and over voltage relays 1 Connect the c
7. urrent and tripping circuits 2 Set the switch in position ON 3 Increase the current voltage to 25 50 over the operat ing value and let the variable transformer be in that position 4 Reset the switch to position 0 5 Set the changeover switch for time measurement in position make break 6 Set the switch to position ON TIME Time measurement of under current and under voltage relays 1 Connect the tripping circuit 2 Set the changeover switch for time measurement in position make break 3 Set the switch in position ON 4 Increase the voltage current until the relay picks up 5 Then set the switch in position OFF TIME Specifications Other Output used to start external cycles Terminal for external start stop of built in timer Terminal for connect ing serial impedance when testing nonlinear protection AC Current outputs Range No load Output voltage Load unload times voltage min On max Off min min 0 10A 85V 75 V 10 A 2 minutes 30 minutes 0 40A 25V 19 V 40 A 20 seconds 15 minutes 0 100 A 10 V 7 7 V 100 A 20 seconds 5 minutes AC DC outputs Range Output voltage min 0 250 V AC 220 V 2 7 A 110 V AC fixed 110 V 0 3 A 0 350 V DC 280 V 2 A 20 220 V DC stab 220 V 0 25 A NOTICE OF COPYRIGHT amp PROPRIETARY RIGHTS 2002 Programma Electric AB All rights reserved