Home

humiFog- UA

image

Contents

1. O1 3 MODELS 3 1 ZONE CONTROL PANEL CODING GUIDE Zone Control Panels UA 0o YvYY U Zone Control Cabinet Type of Cabinet Available Sequencing Number O Duct A Ambient Page 7 of 32 4 ZONE CONTROL CABINET POSITIONING AND MOUNTING 4 1 ZONE CONTROL POSITIONING AND MOUNTING NOTES The humiFog zone control cabinets are designed to be wall mounted There are appropriate holes in the back of the cabinet for mounting to the wall Use appropriate fasteners for supporting the weight of the cabinet and its components Maintain clearances around the cabinet as noted below This allows for proper ventilation maintenance and user operation of the cabinet The cabinet should be placed locally centered to the pumping station and distribution zone points For ducted systems the zone control cabinet should be close to the duct AHU For ambient systems the zone control cabinet should be mounted centrally to the zone areas IMPORTANT NOTE The maximum distance between th
2. GND Zone Control REM Cabinet Cabinet UAZN UAZN Solenoid Solenoid Valve Valve Wiring Wiring AHU AHU High pressure water line Next zone if applicable Page 15 of 32 CAREL pCO platform manual for specific instructions WIRING FROM PUMPING STATION TO ZONE CONTROL CABINET S NOTES 1 Use a twisted pair shielded cable to zone control cabinets 2 Connect to terminal block J11 of PCO3 in each zone cabinet 3 Connect the shield to the GND at pumping station end only 5 11 DUPLEX CONTROL WIRING MULTIPLE ZONES PER AIR HANDLER WIRING FROM ZONE CONTROL CABINET TO DUPLEX PUMPING STATIONS pLAN CON N EC TION NOTES 1 Use a twisted pair shielded cable to pumping stations 2 Connect to terminal block J11 of PCO3 in each pumping station Pumping Pumping Station 1 Station 2 UAH 3 Connect the shield to the GND at zone control end Rx Tx must match on all PCO controllers Rx Tx must also match on all PCO controllers High pressure water line with check valves cae a Vini For a duplex system both pumping stations are wired to one or ca a more zone control panels by pLAN connections Please see diagram 6 6 as well as the CAREL pCO platform manual for specific instructions For multiple zones in the same air handler the same wiring rules apply for Fig 6 d the pLAN connections For multipl
3. Activated when one or more alarms is detected via a contact output that Cable bi Jtwo wire AWG 15 20 Electrical specifications power 500 VA of the relay voltage 250 V current 2 A resistive Inductive contact open contact closed Status and opera tion of the relay no alarm active active alarm alarms i P a LI i if i 1 a Velole blelelale elelo elol r I _ mem 16 ro G5 ii oo oS oc cR 5 ri E E 1 F ni Calf E 1 Er Connections humiFoq cabinet terminal 115 NOS 5 8 INPUTS FROM EXTERNAL DEVICES Cable two wire AWG 15 20 Electrical specifications voltage free contact of the relay Status and operation of contact open no alarm active the relay contact closed active alarm alarms 2 alarm input from AHU pressure sensor flow switch 5 9 SUPERVISOR NETWORK Supervisor network is through the pumping station unit Please see the pumping station manual Page 14 of 32 5 10 PUMPING STATION TO MULTI ZONES Pumping stations are wired to the multi zone control panels by pLAN connections Please see diagram below as well as the PLAN CONNECTION J11 RXTX Jn J11 RXTX RXTX RXTX RXTX GND RXTX Slave Pumping Station UA H Zone Control
4. Hum Starts bms Configuration e BMS config BMS PORT 1 Use ENTER to select Protocol Protocol lA and UP DOWN key to select Protocol type ENTER again to confirm selection ims Configurator Ems L E IPLE Ls Ne Use ENTER to select Address Address or Baud rate and UP DOWN Baud Rate cir key to change ENTER again to confirm selection Bms Lontiguration EMD Ems Configuration Loor Page 23 of 32 f Service Settings parsa Use UP DOWN key and Go to Service Settings ENTER key to input password enni Default code is 22 The Submenu word CPUId A password can be changed by the service technician g Manual Management 5 EH Use UP DOWN key and Go to Manual Management ENTER key to input password Default code is 22 The Submenu password can be changed by the service technician 7 4 1 Service Settings Submenu To access the Service Settings Submenu e Scroll through the G Service submenu to F Service Settings e Press ENTER when Service Settings Submenu is highlighted e Input the password List of Service Settings Submenu selections Use the UP DOWN arrows to scroll through this list a Working hour set b Probe adjustment c Regulation d User DEV Change PW1 a Working hour set STAGE 1 Use UP DOWN key and ENTER key to reset run hours Display will change momentarily to Yes and then will change back to No er IMP ut Use UP DOWN k d b Probe adiustme
5. 7 LH IT GNI M M luci ilL 3 IGNO 5 6 SOLENOID VALVE CONNECTION FOR DISTRIBUTION SYSTEM For the management of the distribution system the cabinet controls four Page 12 of 32 types of solenoid valves normally closed NC for capacity control of the manifolds normally open NO for draining the manifolds normally open vent valves Recommended connection cables two wire plus earth AWG 18 20 0 5 1 0 mm maximum length 100 m SOLENOI CABINET D fonti TERMINAL VALVE DESCRIPTION SOLENOID lam ce ee ee ce e e 7 5 1 5 5 5 2 VALVES A Tee Te Te TT PER STEP ae ze EE EE ME TIE 1 NC1 GOB 1 2 control sol 3 A GE GH GUB GUB COB CE Ge OL lola Jo o Jo o a JO Ja JO o On Valves 1st step j A AS XR amp X XM 4 TH 5 g g 3 5 sl lx Capacity Valves 2nd step Capacity 00 0 CO TOTO 00 002 00 LD m de 3 NC3 GOB 1 2 control sol Valves 3rd step 4 J MC NN 4c1 h AK Ce A E A Capacity Valves 4th step Capacity 5 NC5 GOB 1 2 control sol Valves 5th step Capacity NC6 GOB control sol Valves 6th step Drain solenoid Drain solenoid NOTES Diagram above for other models Dran N03 GOB 1 2 3 Valves 3rd step Drain solenoid Drain solenoid Drain solenoid Vent drain NOV GOB solenoid valves 5 7 CUMULATIVE ALARM RELAY J15 Page 13 of 32
6. Press the enter key and change this value to 18 32 This address must be different from the address of the PCO3 controller Press enter Press the up down and enter keys 3 keys on the right hand side of remote display for approximately 3 seconds You will be taken to the same screen as before but this time you will see I O Board Address displayed underneath Display address setting Press the enter button 2 times so the text box is blinking beside I O Board address Change this to the same address that you assigned to the PCO3 controller Then press enter The next screen displayed will show Terminal config press enter to continue The following screen will show P address of PCO3 controller in upper left corner Trm1 None will be blinking Change none to the addressed you entered in step 4 address of PGD display Press enter 1 time and change the next field to Pr Press enter 5 times and change ok From no to yes Press enter The PGD remote display is now addressed to your PCO3 controller Page 18 of 32 7 THE humiFog CONTROLLER The humiFog controller features a comprehensive information display that shows the operation of the system ata glance KAEA Program Up Down Escape Program Escape Alarm Pun ZONE Org OFF Turns off the buzzer and displays the first alarm screen in the alarm loop A red LED located under the Alarm button will be energized when there are
7. 5 7 Cumulative alarm lee iaia 13 5 8 Inputs from external devices e 14 5 9 Supervisor Network 14 5 10 Pumping Station to Multi Zones 03 de on ance ed ken aa 15 5 11 Duplex Control Wiring Multiple zones per Air HandleR i 16 ccm ic DV IW I I 17 6 1 Startup Checklist arse 17 6 2 Re addressing the Controllers and Displays for Multi zone or Duplex Systems 17 6 3 Re addressing PCO3 controller ee 18 6 4 Re addressingiPGD display ili Del 18 7 IHEhumiFog CONTROLLER cl TTT RTRT 19 7 1 Multi Zone in single AHU setup overviewW enne nnne n nnne nnne nnns 20 7 2 SYSTEM cM 20 7 3 Maln MenU s bia Or 21 7 4 Service nei Error Bookmark not defined 7 4 1 SERVICE Selmos silicio 24 74 2 Manual Management SUDMENU iii 25 7 5 Manufacturer Lhc 25 8 REPLACEMENT PART i la 27 8 1 See specific material list s provided with unit e 27 95 WIRING DIAGRAM 28 10 WARRANT ee 30 Page 3 of 32 1 HOW THE humiFog WORKS The humiFog humidification system is a high pressure atomizing system designed to produce a fine mist that readily evaporates
8. Jn1t address Switch to unit Displays information from the controller at the indicated address If enabled other controllers in a multi zone installation can be selected Up to 32 zones can be connected F CE Board Switch 1 Board Switch Access is granted to SERVICE MENU see 7 3 SERVICE MENU d Working Hours e BMS config below f Service Settings g Manual Management Page 22 of 32 7 4 SERVICE MENU To access the Service menu scroll to 3 A Maintenance from Main Menu and press ENTER when highlighted The factory default password is 22 List of Service Submenu selections Use the UP DOWN arrows to scroll through this list Selections a and c are not available b Information d Working Hours e BMS config f Service Settings g Manual Management b Information Information Displays information on controller software hardware and power Use the UP DOWN keys to alternate screens Ver t 2 8 2124180211 5 00 20 05 01 20 0501 Bios Boot Information Board Lyre Board size Built In tyre Jain cycle Dr Hoyle Control Power Status ast Uff Time A 1716711 17 28 53 a Un Time 1 i J aa E MF Displays cumulative run time for d Working Hours ela ki each stage Screen layout ela i Fr D varies with number of stages ela 5 ela ela E
9. Y 5 2 1 Main pumping SIatIOD ue lille ie 5 2 2 Microprocessor control SY SUCIM oed UA aa Iu iu as qp DEN DU E UE 5 2 3 Atomizing NOZZE S anioni DLL aisi nile ali rn 6 2 4 ENS eu ae le eee 6 2 5 ZONE Control Panels TD 6 2 6 Zone Control PaneL Dimensions and weights eene nnns 7 2 7 zone control cabinet Components dial ao ii 7 3 MODEESS ERE ETIN III SES 7 3 1 Zone Control PANEL CODING GUIDE alia 7 4 ZONE CONTROL CABINET POSITIONING AND MOUNTING ccccssscssccsscsscccsccssccsscssccssccsscesccescess 8 4 1 Zone Control Positioning and Mounting NOTES ei 8 4 2 Zone Control PANEL CLEARANCES l lll llll i i iii 8 4 3 Zone Control drilling template ii 8 5 ELECTRICAL WIRING eeieeesee ea Ue eov ERE SEERE 9 5 1 Power Wiring Connection LayOUts e 9 5 2 Details or Terminal ko t T N 9 5 3 EleciricalPOWel cc Cd MEETS 10 5 4 Control signals from external voltage free contact humidistat rn 11 5 5 Modulating control signal eee 12 5 6 Solenoid Valve connection For Distribution System 12
10. alarms present If the red LED is blinking that means an alarm has occurred but the condition has been corrected and the alarm can now be reset Shortcut to the Technician s Menu where all application settings can be reached If protected a password will need to be entered Escapes to previous screen loop When already in the Technician s Menu pressing ESC takes you to the main status screen If ESC s green LED is blinking part of the system is under Manual Control Cycles upward through the screens when cursor is in top left corner When cursor is in a field the value of the field is increased The longer the button is held the faster the value increases Cycles through fields in a screen When in a field pressing ENTER confirms the current value into the field and goes to the next field Cycles downward through the screens when cursor is in top left corner When cursor is in a field the value of the field is decreased The longer the button is held the faster the value decreases Shortcut to quickly see the Software Application s Version Number and Date It is in this screen from which you can restore the Factory Settings by pressing then s then and finally one last time Shortcut to quickly see the System Type and Number of Humidification Stages When in the Alarm History Screen pressing ESC PRG will erase the history Keyboard shortcut to reset all Manually controlled points to Automatic control Whe
11. caca ac gt gt omt t o 0 0 0 0 0 0 B B B B B B B 1 2 3 4 E 5 6 7 8r T 9 10 3 11 12 E 14 AIR FLOW SWITCH NQ OPEN CONTACT NO AIR FLOW peg enn HUMISTAT REMOTE ON OFF SWITCH OPEN CONTACT OFF COM FOR ONOF FLUX Page 29 of 32 10 WARRANT Y Limited Warranty All products manufactured by CAREL USA LLC are warranted to the original purchaser to be free from defects in materials and workmanship in the course of normal and reasonable use for a period of 2 years and 1 month from the date of shipment The OEM controls warranty is 2 years from date of manufacture humidifier replacement parts warranty is 90 days from date of Invoice Warranty replacement parts are warranted for remainder of original unit warranty or 90 days whichever is longer so long as the product has been installed and operated in accordance with all appropriate manuals and wiring diagrams and started up by a qualified CAREL USA technician Any product or part that is found to be defective will at the option of CAREL USA LLC be replaced or repaired CAREL USA LLC reserves the right to inspect any part or installation before replacing or repairing defective parts After start
12. done and tested Airflow switch is wired to open on air flow loss Hi limit humidistat is wired to open on humidity rise above set point _ Unit wires have been checked to make sure they and all connectors are tight from shipping L The high pressure water outlet piping is run correctly to the distribution system The proper capacities for each stage of the manifold system are installed in the zone control cabinet For a multi zone system the addresses of the zone controls cabinets are changed Fora duplex system the addresses of the pumping stations are changed 6 2 RE ADDRESSING THE CONTROLLERS AND DISPLAYS FOR MULTI ZONE OR DUPLEX SYSTEMS The default addresses for a zone control cabinet are 1 for the PCO3 controller and 30 for the PGD display The default addresses for the pumping station cabinet are 16 for the PCO3 controller and 32 for the PGD display For multi zone or duplex systems the additional cabinets on the pLAN must have their addresses changed before they can operate correctly When changing addresses the pLAN connections between each of the PCO3 controllers must be removed The connections are restored once the readdressing is completed e For multi zone system o the PCO3 controllers in the additional cabinets can be assigned addresses sequentially upward o thePGD displays in the additional cabinets can be assigned addresses sequentially downward e Fora duplex system o the PCO3 controller
13. in the additional pumping station cabinet must be changed to 17 o thePGD display in the additional pumping station cabinet must be changed to 31 pLAN ADDRESS TABLE PCO3 Sonn ole PGD SAY Default Defaut Pumping Zone 1 Control Page 17 of 32 6 3 RE ADDRESSING PCO3 CONTROLLER To change the address of the PCO3 controller the address of the PGD display must be set to 0 first The procedure for setting the address of the PGD back to the proper address is described in 6 2 2 QUO UT BI MN 8 9 10 Unplug J11 connector from PCO3 controller Press the up down and enter keys 3 keys on the right hand side of remote display for approximately 3 seconds The screen should show Display address setting Press the enter key and change value to 0 Press enter Shut down power to the PCO3 controller wait 3 sec and then turn power back on to the PCO3 controller As unit is powering on press and hold the up and alarm buttons top left and top right buttons on PGD remote display until pLAN address is displayed Change to desired address Press enter The PCO3 is now address to the value you last entered 6 4 RE ADDRESSING PGD DISPLAY Due ge mu 10 11 12 13 14 15 16 17 Unplug J11 connector from PCO3 controller Press the up down and enter keys 3 keys on the right hand side of remote display for approximately 3 seconds The screen should show Display address setting
14. PGD DISPLAY PGD1000FWO O CONTROL TERMINAL BLOCK PLUS FUSES Ch Page 27 of 32 9 WIRING DIAGRAM PGD f jf A Fo HE RE ee ee zx OPEN RELAY INDICATES Meu i OALLL SV VA VSSZSEN SYSTEM ALARM y TB NC5 TB N03 Eram Previous TB NC1 TB NC2 TB NC3 TB NC4 TB NC6 B S90 quin s To Next Zone T n i Li TENDI TEND TE NOS or PUMP _ e _ Capi 11 E AEN Cabinet J11 PI UID 8 MI 2 i b ded DIDO ZZZ 2 ZZZ 2 Z e Z Q eue Q Z Q Z Z Q Z Q ZZZ Q Q ZZZzz IE
15. Q QIQ 989g ES RUNI 900 oso 101310 zoooz ioooozi x x oA N N wo SUOI O0 OO Cc c C C C C C C c CO N N O N A C1 O N Co N CN v gp d c c c c N Ce c c c N un A N A C1 N Co co O lt e Qt lt 5 2 2 2 zzzz ZZZ Z Z G lt W IEEE Q Jg oU oj 8 8 8 5 958 S 2 s s s s SRBESBESES gB ga sg 25x 9S SEN SS SSS a 4 GA TB ONOF TERISI e FTN TS ry gt y z TB FLUX TERIS E TB NOV e Jm 0 10V LIMIT aan OUT H T PROBE e Me 0 10 AMBIENT OUT H T PROBE REE 0 10V EXT TR A GOA ied o uq d G o lt gt e F3 dm N N GA 24 5 120 T2 e h F4 L L VAC GR GND TR B DISCONNECT SWITCH FUSE AND LISTED Sob i T3 F3 PRIMARY OVER CURRENT PROTECTION 0 slc an TO BE PROVIDED BY INSTALLER 0 C 0 DISCONNECT CIRCUIT RATED NO LESS ES 4 amp F4 THAN 5 AMPS HAWG OR LARGER GB 24 5 120 T4 X amp i ori Panel Builder Wiring Page 28 of 32 Final Assembly or Customer Wiring NOTES PCO PCOS3000ASO 1 CABINE
16. T AND WIRING MUST BE UL508A ASSEMBLED PGD PGD1000FWO 2 CABINET SHALL BE CONTRUCTED WITH FINGERSAFE COMPONENTS 3 CABINET SHALL BE CONTRUCTED AS TYPE 12 G MAIN DISCONNECT SWITCH 4 WIRE COLORS SHALL BE AS FOLLOWS TR A TRANSFORMER PCO TR B TRANSFORMER RELAYS Black All ungrounded conductors operating at supply voltage wire numbers 1 4 2 FUSE 5X20 1A 250V FAST Red Ungrounded AC control conductors at below supply voltage all wires unless marked otherwise F3 4 FUSE 5X20 4A 250V SLOW F5 FUSE 6 3X32 3 15A 250V SLOW Orange or All ungrounded conductors that remain energized when the main disconnect switch is off FUSE 10 3X88 20A 600V FAST Blue blu Ungrounded DC control conductors at below supply voltage NC White All grounded AC current carrying conductors regardless of voltage FUSE 5X20 6 3A 250V FAST NO White w orange stripe All grounded AC current carrying conductors that remain energized when the NOV main disconnect switch is off NC NC FILL VALVES STAGE NO NO DRAIN VALVES STAGE White w blue stripe All grounded DC current carrying conductors regardless of voltage NOV NO VENT VALVE Green w or w o yellow stripe Earth grounding S90 PCO PGD CABLE NO9 NO18 NO10 NO20 de NOI9 NO4 SEE NOS NO16 ID10 NOI NOG NO11 NO17 NO21 NO23 4 NO2 i Y NO14 NO22 ia ID 2 SER NO12 NO15 TERMINAL JUMPER NC1 NC2 NC3 NC4 NC5 NC6 NO1 NO2 NO3 NO4 NO5 NO6 NOV 9 B ORIG aca
17. ctual state will E odo change to OFFbyKEY or UnitOn Change to SWITCH OFF Use the ENTER key to confirm SET POINTS B F Setpoint 1 Humidity Setpoint i gt Use the ENTER key and UP DOWN SP set Point 48 8 key to change the SET POINT When the desired value is reached use the ENTER key to activate new value dini Use the ENTER key and UP DOWN 1 Clock ay Thursda key to change the MONTH DAY iios ae 17 YEAR HOUR and or MINUTE When 8 the desired values are reached use hae 24 the ENTER key to activate the clock C EEE Clock Scheduler Page 21 of 32 Analog Input 1 Analog Input This screen displays the humidity sensor reading or DDC value TTR LAS 2 Digital Input 3 Relay Output D Input Output Aart SO Switch Displays the remote control state 12 Status The Off state results from a high voltage signal to the Remote On Off digital input port ay Output I3 3 Displays the state of the relays A dark box or On state indicates a high voltage signal to the solenoids for that stage Screen layout varies with number of stages Alarm History System Start This screen displays the most recent 1 Alarm History alarm The UP and DOWN keys 16 43 43 11162811 allows scrolling through the entire Hum 50 0 7 Out a alarm history E Data Logger Board switch
18. drop pan mandatory 2 drap separator mandatory A Duct AHU Distribution Ambient Room Distribution Direct manifolds Page 4 of 32 Fig 1 a 2 COMPONENTS A humiFog system is made up of the following components Pumping station containing the electrical panel and the volumetric piston pump Microprocessor control system Distribution system with the atomizing nozzles for ducts AHUs or rooms Zone control panels for controlling the distribution staging in each zone or AHU 2 1 MAIN PUMPING STATION The main pumping station features an energy efficient combination of an advanced Inverter Duty Motor and a Variable Frequency Drive This combination allows for the precise control of the volume of outlet water from the positive displacement pump The positive displacement pump is a reliable component that is designed for long life and minimal maintenance By adjusting the speed of the pump the pressure and the flow rate of the nozzles are precisely modulated according to the requirements of the application The station also incorporates a user friendly display allowing the user to visually change set points and other user modified fields The main pumping station controls the water output using Constant Pressure principles This type of control allows a single pumping station to supply humidification to multiple ducts AHUs or rooms In this setup the humiFog controller manages the speed of the pump according t
19. e zone control cabinet and the rack distribution is 50ft 15meters It is recommended that the unit be fixed in position so that the electrical connections do not become damaged AII connecting wiring is done by installer Certain clearances must be maintained around the unit for safety and maintenance The cabinet can be placed wherever the following conditions are met Cabinet protection index IP20 Nema Type 1 unless specified otherwise Operating conditions 20 80 RH non condensing 34 104 F 1 40 C Storage conditions 10 90 RH non condensing 34 122 F 1 50 C 4 2 ZONE CONTROL PANEL CLEARANCES 4l 2 OOO m LEFT SIDE B 4 RIGHT SIDE A M Tab 4 b 4 3 ZONE CONTROL DRILLING TEMPLATE rear of the cabinet Aj 445 Drilling Hole Conversion Table Upper Horizontal 17 32 Lower Horizontal Vertical Soace Between Horiz 390 15 35 Page 8 of 32 5 ELECTRICAL WIRING 5 1 POWER WIRING CONNECTION LAYOUTS Field Bus BMS ELEI FE 8 58 HERE EH IN Bg 133986333 3333 S333 7379 22233 Key L N GR Power supply Important make sure that the cable glands are fitted BKUP GOA ROEN COM ON OFF GOA RKEN GOA FLUX GOA do not run the control and signal cables through this cable gla
20. e zones each with multiple zone control cabinets the number of cabinets per each zone must be the same Contact the factory for additional details regarding this f next zone if applicable J11 eT Zone Control Zone Control Zone Control parsa Cabinet Cabinet Cabinet GND UAZN UAZN ipi olenoi olenoid olenoi Pumping Solenoid Sol Solenoid ION Valve Valve Valve Statio UA Wiring Win ng Wiring AHU High pressure water line Page 16 of 32 6 START UP IMPORTANT INSTRUCTIONS WARNINGS Before connecting the water to the pumping station flush the supply pipe for 10 minutes by piping water directly into the drain Before starting the pumping station verify that the humidifier is in full operational condition The hydraulic and electrical equipment should not be locked out There should not be any water leaks and the electrical components must be dry If a hazard does seem to exist the system should be locked out immediately and the problems corrected before continuing 6 1 STARTUP CHECKLIST Before starting the humidifier the following should be checked Water is connected the line has been flushed and external valves are open Drain is connected and run to an open drain Electricity is connected in accordance with instructions local codes and data labels in the unit L The external power fuses disconnect are installed and intact All control wiring is
21. erything Use the ENTER key and UP DOWN key to change access passwords ENTER will confirm the selected digit Page 26 of 32 8 REPLACEMENT PARTS 8 1 SEE SPECIFIC MATERIAL LIST S PROVIDED WITH UNIT 2 5 8 TAE 5 X T EA i i Y J s __ i gy Tab 8 1 Typical Zone Control Cabinet tem Description Part Number a ueecrewuwconsoum CENE ENTIRE G R rome sure Ton TE ER MAIN CONTROL TRANSFORMER P BEL TRANSFORMER B SECONDARY FUSE CONTACT CARRIER CAREL TRANSFORMER PRIMARY FUSE CARRIER pred CAREL
22. humiFog UA Pressure Atomizing Multi Point Zone Control Panel ENS User manual EP aci m Integrated Control Solutions amp Energy Savings We wish to save you time and money We can assure you that the thorough reading of this manual will guarantee correct installation and safe use of the product described WARNINGS BEFORE INSTALLING OR HANDLING THE HUMIDIFIER PLEASE CAREFULLY READ AND FOLLOW THE INSTRUCTIONS AND SAFETY STANDARDS DESCRIBED IN THISMANUAL AND ON THE LABELS ATTACHED TO THE humiFog CAUTION ALWAYS DISCONNECT THE MAIN POWER BEFORE OPENING OR SERVICING THE HUMIDIFIER This appliance has been designed exclusively to directly humidify in ducts and AHUs through the atomizing rack The quality of the water used affects the operation of this unit so the humiFog must be supplied with treated water Reverse Osmosis or Deionized The installation use and maintenance operations must be carried out according to the instructions contained in this manual and on the labels applied internally and externally IMPORTANT BEFORE beginning installation e Check for shipping damage to carton Mark the shipping waybill accordingly e Open cartons and check for any hidden damage Mark the shipping waybill accordingly e Check packing slip to ensure all items have been received Notify CAREL of any shortages or damaged parts You must notify CAREL within 5 working days of any shortages The conditions of the environment and the p
23. in the section 7 1 of this manual Page 6 of 32 2 6 ZONE CONTROL PANEL DIMENSIONS AND WEIGHTS 19 7 500 3mm Weight Table UAZN Ooo 22 9 580 5mm los kg 53 24 SST los kg 66 30 T 2 4 62 2mm 1 6 39 7mm a 1 2 30 0mm 9 9 500 PROBE CABLE INLETS m gh X i 59 7mm 3 5 89 6mm ACE 5 ON OFF SWITCH 7 6 193 4mm e llo 9 8 8 223 0mm 8 8 223 0mm Bs 4 8 122 5mm 8 3 82 6mm 4 8 122 5mm i i a cess basi l 2 1 52 3mm lo l l 2 51 0mm 2 7 ZONE CONTROL CABINET COMPONENTS power supply terminal block transformer primary fuse carrier TRA F1 F2 TRB F3 F4 transformer B secondary fuse carrier F8 E ui i nni amp transformer A y Q 8 electronic controller 9 control terminal block with fuses NM Co rw uns TTT Pelo T E ojoj P 2 D E deese
24. ion Ualue 7 5 MANUFACTURER SUBMENU To access the Manufacturer Submenu scroll through the Main Menu and select B Installer The settings in the Manufacturer Submenu are password protected Unauthorized users should contact their Carel representative before accessing the Manufacturer Submenu List of Manufacturer Submenu selections Use the UP DOWN arrows to scroll through this list Selection d is not available a Configuration b I O Configuration C Factory Settings e Initialization Use the ENTER key and 3 E UP DOWN keys to change a Configuration antral control type pump Pumps _ 5 PLAH communication group type quantity and type PARALLEL or STAGED Use the ENTER key and UP DOWN keys to change the water output for each stage to match the humiFog system being controlled Use the ENTER key and UP DOWN keys to change the delay time for stage activation Use the ENTER key and Chtil BOTH PID UP DOWN key to select and Times 14 change the Modulating Control Derivitive Time C values Consult Carel before Min 1008 ax making changes Qut eut Period aim AE 9 ini Use the ENTER key and Rame up delaui i UP DOWN keys to change the Rame down delas delay time for zone activation Page 25 of 32 Use the UP DOWN keys to b 1 0 Confi ae 11 p gt scroll through screens Use the US Seu Mele or ni hi ENTER and UP DOWN keys to j e Disable enable i
25. m fi E Fe pa p pa z p La pa ee Bia pi e 2 5 ZONE CONTROL PANELS The humiFog Zone Control Panels utilize the latest state of the art CAREL pCO programmable controller This controller operates the distribution system by interfacing with the selected control system and then controlling the water solenoid valves for appropriate modulation Control can be stand alone using humidity and temperature sensors or the system can be controlled by a DDC signal Modbus BACnet Echelon and TCP IP protocol interface is available A LAN Local Area Network connection allows up to 32 Controller devices to be connected to share sensor information or even operate redundantly The zone control cabinets are also used to control each zone in a multi point humiFog system In this type of system all of the zone control panels communicate to each other and to the pumping station panel by a pLAN network Multi zone setup configuration may involve multiple zones within the same air handler There are two primary methods of how to distribute water through a multi zone setup parallel or staged control With parallel control each zone connected to the pumping station will be activated simultaneously and operate at the same output level Staged control will run one zone to its maximum capacity before activating the next zone This choice will affect the zone demand display of the zone control cabinets as described
26. n in the System Run Hours screens pressing these keys will reset the currently selected Stage s Run Hours NOTE The standard humiFog display will have fields that can display values or fields that can accept values If pressing the ENTER key places the cursor next to the display field the UP and DOWN keys can be used to change that value Page 19 of 32 7 1 MULTI ZONE IN SINGLE AHU SETUP OVERVIEW Depending on the system setup variables there can be significant differences in the user interface options Some options may have more selections to choose from and some menu selections may be absent altogether 7 2 SYSTEM STATUS On initial power up the controller will go through a series of self tests and then activate the program bringing up the following screens The visibility of some screens is dependent on the configuration of the system 1 Power up Unit 1 Unit n 1 HUMFOG ZONE USA During power up the controller performs an alarm test The alarm key will be red and must be pushed twice to clear the alarms To check the Alarm History use DOWN key from System Status Screen The 1st alarm is a System Start Alarm and the 2nd alarm is a No Air Flow Alarm Note The No Air Flow Alarm occurs whether the AF digital input is open low voltage or closed high voltage at power up Actions that can be performed from the System Status Screen ZONE INFO ea est a lb No changes can be made at this Sys
27. nd Main humidity temperature probe Limit humidity temperature probe AUX probe temperature display only Cumulative alarm relay Pumping unit remote enabling signal Water treatment system alarm signal Backup cabinet signal Water treatment system control Control signals from external voltage free contact i e ON OFF humidistat Enable RACK production Air flow switch 3 NCI NC amp GOB Capacity control solenoid valves step NO1 NO6 GOB Drain solenoid valves ste Line drain solenoid valve NOV Vent solenoid valve rack 4 Field card input for Master Slave connection 5 Serial Card Serial card input for BMS Building Management Systems 5 2 DETAILS OF 2 AND 3 TERMINAL BLOCKS ONOF RKEN FLUX B O O O G 0 FE A Page 9 of 32 5 3 ELECTRICAL POWER Check that the power supply voltage to be connected matches the value indicated on the rating plate inside the electrical panel An external fused disconnect should be provided according to local and or national electrical codes NOTE To avoid unwanted interference the power cables should be kept separate from any control wiring AII wiring must be in accordance with local state and country electric codes NOTE Tolerance allowed on main voltage 15 to 10 Power is connected to the main switch inside the control panel at the bottom right Connect wires to the top of the switch terminal labeled L and N There is als
28. nputs 3x1 i e Change RH signal type Offset o 0 1 5 10 VDC o 4 20 mA o NTC 50T90 10T170 nu10 PT1000 SPKP o On Off Note other choices not used for RH e Change max min values SA ut of Range Alarm Power Delau ez Run Delay Enabling the Remote On Off by a supervisor requires a change to the Factory Settings zr E imi 1 Use the UP DOWN keys to Sola hi B scroll through screens Use the Minimum ENTER key and UP DOWN Maximum I E keys to Urtset e Disable enable inputs e Change the action A closed condition results in a high voltage signal to the digital input port e Change time delay up to 999 s SNR DOG gt Use the ENTER key and c Factory Settings Enable unit e Factory Setings Enable qnit Ott UP DOWN key to select and Ba BMS Jo change the Parameter values Consult Carel before making changes Jalue Factory settin9Is Use the ENTER key and Stage dn 1B lbeht UP DOWN key to select and change capacity setting Consult Carel before making changes to global settings To complete initialization turn unit off and on e Initialization Asc Use the ENTER key and iie UP DOWN key to reset all values Use the ENTER key and UP DOWN key to select SAVE options There is an identical screen for USER SAVE custom options ENTER will confirm the choice Use the ENTER key and UP DOWN key to YES or NO Exercise caution when accessing this screen since it can erase ev
29. nt antral Sensor se ey an ro Ju Input Bel ENTER key to choose Control Offset Ae Sensor or High Limit Sensor Use the UP DOWN key to ciis change the offset 0 53 5 Analog Inrut High Limit sensor Default setting disables High nrut Baz Limit Sensor causing Value 0 Use I O configuration on Manufacturer Submenu to enable the High Limit Sensor Use the ENTER key and UP DOWN key to select and change the Parameter values Consult Carel before making changes c Regulation Current Value Detault d User DEV Change Use the ENTER key and UP DOWN key to change the PWI Password When the desired Insert new service password 1 gt 25 value is reached use the ENTER key to activate Page 24 of 32 7 4 2 Manual Management Submenu To access the Manual Management Submenu e Scroll through main menu to G Service and then g Manual Management Press ENTER and input the password g Manual Management Manual Control Use the UP DOWN keys to scroll through screens Relay Output DEMAND STAGES DRAINS ST GE 1 RELAY OUTPUTS DIGITAL Manual kelas 3 INPUTS and ANALOG INPUTS Manual Positioni can all be controlled manually Co Use the ENTER key to select 3 Status the parameter being changed CUTE Tet Use the UP DOWN keys to Control um change the settings Screen Manual Control Bal OFF layout varies with number of stages kelay Manual Posit
30. o a ground bar lug labeled GR CONNECTIONS Master slave cabinet Power cable L F phase N W neutr 3l GR PE earth Power Table UAZN External Disconnect Size Voltage Current provided by Installer UAZN00106U 115 V 5 0 FLA at least 6 Amps UAZN00108U 115 V 4 1 FLA at least 5 Amps Page 10 of 32 5 4 CONTROL SIGNALS FROM EXTERNAL VOLTAGE FREE CONTACT HUMIDISTAT IMPORTANT NOTE When grouping cabinets in a staged cascaded or parallel system control signals sensors amp switches ONLY need to be connected to the master zone control cabinet of each group addressed at location 1 a ON OFF C control Cables up to 30 m two wire cables cross section 0 5 m AWG20 greater than 30 m shielded cables cross section 1 5 mm AWG 15 electrical specifications voltage free contact of the contact Contact open humiFog deactivated Contact closed humiFog activated humiFog Master cabinet ON OFF humidistat thermostat ON OFF INC NO GOA I COM Key 1 ON OFF humidistat thermostat 2 limit humidity temperature probe Page 11 of 32 5 5 MODULATING CONTROL SIGNAL IMPORTANT NOTE When grouping cabinets in a staged cascaded or parallel system control signals sensors amp switches ONLY need to be connected to the master zone control cabinet of each group addressed at location 1 The control signal input connections depend on the control algorithm activated Up
31. o the Constant Pressure set point increasing the speed if the pressure decreases opening more zones branches of the circuit and decreasing the speed if the pressure increases closing one or more branches of the circuit With this configuration the humiFog controller can manage the humidity control and distribution directly one zone AHU or the distribution control is managed by an additional external zone controller multiple zones AHUs Description 10 Drain water outletrelief valve 1 Water filter Tab 2 a fine p INDIE RT fa Lg p fo LL I 2 2 MICROPROCESSOR CONTROL SYSTEM The humiFog control system is based on the latest state of the art CAREL pCO programmable controller This controller operates a Variable Frequency Drive to modulate water pressure and water flow according to requirements Control can be stand alone using humidity and temperature sensors or the system can be controlled by a DDC signal Modbus BACnet Echelon and TCP IP protocol interface is available A LAN Local Area Network connection allows up to 32 systems to be connected to share sensor information or even operate redundantly Page 5 of 32 2 3 ATOMIZING NOZZLES The humiFog atomizing nozzles are constructed of stainless steel and are available in three capacities 3 3 6 2 vo 8 8 Ibs hr 1 5 2 8 amp 4 0 kg hr Working on the centrifugal whirljet principle they have no targets to drip or re
32. ower supply voltage must comply with the specified values listed on the data label in the humidifier All other uses and modifications made to the humidifier that are not authorized by the manufacturer are considered incorrect and the manufacturer assumes no liability for the consequences of any such unauthorized use Please note that the humidifier contains powered electrical devices and high pressure components All service and or maintenance operations must be performed by qualified personnel who are aware of the necessary precautions and are capable of performing the operations correctly Disconnect the humidifier from the main power supply before accessing any internal parts The humidifier must be installed in accordance with all local and national standards WARNING Your humidifier requires water to operate Do NOT mount it above materials or machinery that could be damaged if a leak occurs CAREL assumes no responsibility for consequential or inconsequential damage as a result of any leaks Disposal of the parts of the humidifier The humidifier is made up of metallic and plastic parts All parts must be disposed of according to the local standards on waste disposal Warranty on materials 2 years from the date of production excluding the consumable parts Page 2 of 32 TABLE OF CONTENTS 1 SHOW THE humiFog WORKS assesses 4 aee
33. quire adjustment An internal 60 micron filter is used to prevent jamming of the nozzle and a special internal valve closes the orifice to avoid dripping and prevent any ambient contamination when the nozzle is off The nozzles are mounted uniformly in the distribution manifolds IAtomizing nozzles 2 4 DISTRIBUTION The following diagrams illustrate the typical applications in ducts Fig 2 c or directly in the rooms Fig 2 d The ambient humidity is measured by a probe 1 or receives a command signal from an external controller and is read by the controller contained in the humiFog pumping station 6 The controller then compares the humidity measured in the room against the humidity set point starting when necessary the production of the pump The demineralized water produced by the water treatment system 7 is brought to high pressure by the humiFog pump 6 sent to the manifolds for distribution into the duct or directly into the room 5 and then atomized by the nozzles 4 The percentage of water fog evaporated depends on the temperature and speed of the air as well as on the relative humidity reached In duct applications any non evaporated droplets are separated by a mist eliminator filter or cooling coil 2 collected in the bottom tank 3 and immediately discharged The control system built into the pumping station controls the banks of nozzles supplied with solenoid zone valves Duct or AHU Ambient na 9 OG
34. tem Status Screen Production screen It provides a summary of the m High Limit gt 79 current zone and pump operation as Pump Pressure 51 well as system demand 15 22 45 11 16 2911 Use the ENTER key and UP DOWN key to change humidity SET POINT FUNCTIONING can be set to AUTO or OFF Use the ENTER key to activate new value A History Larm Histor Use the UP DOWN key to view alarms System Start ESC key will take you back to previous 3 30 1171672811 screen 24 0 4 Lut Aw IMPORTANT NOTE The System Status Screen can vary depending on the setup options in section 7 4 MANUFACTURER SUBMENU See section 5 11 for a review of multiple zone setup options If the setup involves multiple zones in the same air handler choosing parallel or staged setup will change the System Status Screen as follows Parallel Zone Control Each zone cabinet will display the same demand percentage because each cabinet is operating simultaneously at the same level of output The output level displayed is that of the entire zone amp pumping system Staged Cascaded Zone Control Zone control cabinets operate in a linear sequence with zone activation occurring only after the previous one has reached 100 Due to the variation in demand among cabinets the master cabinet address 1 will display the demand value of entire system capacity The remaining cabinet s will only display its own output relative to its capacity For example the zone at address 1 ma
35. to 30 m two wire cables cross section 0 5mm2 AWG20 The signal may Modulating control with external controller come from Modulating control with ambient humidity probe External controller and limit humidity probe To set the type of operation control and signal installer menu gt type of control see chap 9 11 Installer menu N B Shielded cables should be used The cables must not run near the 120 V power cables nor near the conductor cables this avoids measurement errors due to electromagnetic disturbance a Modulating control with external controller P control Oto1V OtolOV 2to 1OV 0 to 20 mA 4 to 20 mA FIELD CARD Fig 3 9 Key l extern mtn Connections d Modulating control with ambient humidity probe and limit humiFog cabinet External controller humidity and temperature probe HH HT control Bi IOUT Oto 1V 0 to 10V 2 to 10V 0 to 20 mA 4 to 20 mA GND Reference shield FIELD CARI 9 DM p m b Modulating control with ambient humidity probe H control es SSeS Rees Oto 1V 0to 10V 2to IOV O to 20 mA 4 to 20 mA Ti PER SRE TS SR LS T f JI Suk HT Fig 3 j age Key a MEE l limit humidity temperature probe TERA J ambient humidity probe Fig 3 h Key Connections E humizditvsanta humiFog cabinet External limit humidity controller probe 1 ni ll Connections 7 Ic GUT HA humiFog cabinet Ambient humidity probe I 7 TE Si r TF WE ta fi ha
36. to raise the relative humidity The atomizing humidifier is an efficient humidification system that is especially suitable for larger installations where high flow rates of water are required without the necessity of excessive energy expenditure When the humidity value in the environment is less then the desired value as measured by a probe or external controller the controller starts the volumetric piston pump which sends the treated water to the nozzles The treated water using a reverse osmosis or deionizer system is pumped at a pressure of 1000psi 75bar and sent via the connection pipes to the atomizing nozzles The nozzles then reduce the jet of water into a multitude of very fine water droplets 10 20 microns Because of the fine droplet size the water can then easily change its state and vaporize The energy required for this transformation is supplied by the ambient air at a rate of 690 W per liter hour Consequently there is a decrease in temperature in the environment being humidified and this process may be useful in many applications adiabatic transformation The humiFog unit must be supplied with treated water for the following reasons e To reduce the introduction into the environment of dust due to the mineral salts found in the untreated water e Tominimize the clogging of the nozzles probes external regulator ATOMIZING MANIFOLDS ATOMIZING NOZZLES 800 1 000 psi Mist Eliminator 1
37. up of the product labor for repairs or replacement of parts is not covered by this warranty Products not included in this warranty are NTC and PTC probes transformers TRA series and routinely replaceable parts such as filters nozzles pump parts and gaskets CAREL USA LLC assumes no liability for consequential or inconsequential damage or damage due to negligence or improper use Under the terms of this warranty the original purchaser may have certain legal rights and other rights which may vary from state to state The Warranty will not be considered valid if a product is damaged due to negligence mishandling or misapplication or if the product label is missing CAREL USA will attempt to repair or replace the products within two 2 months of the receipt of the returned goods NOTES Page 30 of 32 Page 31 of 32 CAREL CAREL INDUSTRIES HeadQuarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com CAREL USA 385 South Oak Street Tel 7174 664 0500 Fax 717 664 0449 e mail sales carelusa com www carelusa com Page 32 of 32 Agenzia Agency 2 0 03U222081 Rel
38. y read 50 indicating that the system capacity is 50 while the zone demand at address 1 is actually 100 For the subsequent zones however the demand displayed is the actual output of that zone Page 20 of 32 7 3 MAIN MENU To access the MAIN MENU press PRG from the System Status Screen shown above List of Main Menu selections Use the UP DOWN arrows to scroll through this list 1 User Installer Maintenance Space Humidity Alarms Use the ENTER key and UP DOWN at AB use Eset 19h dee key to change the HIGH LOW and sin ALARM DELAY values When the E desired value is reached use the ENTER key to activate new value DEA Use the ENTER key and UP DOWN 3 Wednesday key to change the MONTH DAY 11 16 11 YEAR HOUR and or MINUTE When 1 Service Password the desired values are reached use 1 Service Password the ENTER key to activate the clock Manufacturer SubMenu see below a Configuration b I O Configuration c Factory Settings e Initialization C Maintenance Use the UP DOWN keys to select password and ENTER to confirm Access is granted to SERVICE MENU see 7 3 SERVICE MENU below Insert sery e Password 2i lc Pld To access the Main Menu press PRG twice from the System Status Screen A on off Unit 1 On Off Unit mad Use the ENTER key and UP DOWN Unit address key to change to SWITCH OFF or x eure SWITCH ON The A

Download Pdf Manuals

image

Related Search

Related Contents

  Ville : mode d`emploi  2 Conteúdos da Embalagem    Samsung MM-C6 User Manual  Répertoire de l`Aide Sociale dans les CPAS Bruxellois  Origin Storage Dell Desktop series drive  nos rivières La vie de - Syndicat Mixte du bassin versant du Lignon  

Copyright © All rights reserved.
Failed to retrieve file