G1041 - Neoptix
Contents
1. The Neoptix T Guard products are CE marking certified This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Document no G1041r03 Copyright Neoptix Canada LP 3 1 END USER LICENSE SOFTWARE WARRANTY AGREEMENT PLEASE READ THIS SOFTWARE LICENSE CAREFULLY BEFORE DOWNLOADING INSTALLING OR USING ANY QUALITROL OR QUALITROL SUPPLIED SOFTWARE BY DOWNLOADING OR INSTALLING THE SOFTWARE OR USING THE EQUIPMENT THAT CONTAINS THIS SOFTWARE YOU ARE CONSENTING TO BE BOUND BY THIS LICENSE The following terms govern your use of the Software except to the extent a particular program a is the subject of a separate written agreement with Qualitrol or b includes a separate clickwrap license agreement as part of the installation and or download process To the extent of a conflict between the provisions of the foregoing documents the order of precedence shall be 1 the written agreement 2 the clickwrap agreement and 3 this Software License License Subject to the terms and conditions of and except as otherwise provided in this Agreement Qualitrol Systems Inc or the Qualitrol Systems Inc subsidiary licensing the Software if sale is not directly by Qualitrol Systems Inc Qualitrol and its suppliers grant to
2. Available devices T Guard 408 Serial Number 408 217A Document no G1041r03 Copyright Neoptix Canada LP 24 If you have more than one instruments connected then instead this window will look like this where more options are available to conditionally save specific channels Select from which device s you want to save logs Select a radio button in the group box below to log all channels for that device only Available devices Combine enable channels Y T Guard 408 Serial Number channels Y T Guard 408 Serial Number 408 2174 Save log Then you will need to enter a file name and select if you want to save your data as a text csv file or as a genuine Excel file already acquired in kept in memory and can be saved as any time using the menu item Log and then Save log or by using the Save Log button found in the lower right corner of the main window lt is also possible to save data directly to Excel if the file you select to save it is an xls file as illustrated here File name file name p Save as type Microsoft Excel spreadsheet xls Temperature log file tem lt Hide Folders umep preme Then all future data will be logged on your hard disk The latest version of OptiLink II now supports data transfers to an Excel file this transfer can be punctual or can proceed as temperature data is being acquired Make sure you download the
3. QUALITROL T Guard Link TGL FL Fiber Optic Thermometer Systems For Industrial amp Power Transformer Applications Fluorescence Technology 1 to 8 Channel Systems OptiLink Il version 1 40 With Modbus Neoptix Canada LP Qualitrol Company LLC 1415 rue Frank Carrel Suite 220 Qu bec QC G1N 4N7 Canada Tel 418 687 2500 Fax 418 687 2524 support neoptix com Proprietary notice Details of design and engineering are the exclusive property of Neoptix Canada LP and are strictly confidential The information given herein is subject to change at any time and without notice All rights are reserved The information in this document may not be reproduced or passed on in any manner without prior written consent of Neoptix Canada LP Neoptix Inc shall not be liable for technical or editorial errors or omissions contained herein nor for incidental or consequential damages resulting from the furnishing performance or use of this material All trademarks are the property of their respective owners Part number G1041R03 November 2014 Document no G1041r03 Copyright Neoptix Canada LP 1 TABLE OF CONTENTS END USER LICENSE amp SOFTWARE WARRANTY AGREEMENT csscssscssssscssccsccssscsccscsssscsnscsssenseees 4 1 1 T GUARD FAMILY AND NEOPTIX PROBE WARRANTY NOTICE sse 7 2 INTRODUCTION wis cssssssdesasscasssssesstecstacssiaacscaveccssavssasasassiassasesaasecassaaseasavassvecessacssavusoaeisasauseassinaseasssasac
4. 4 115 200 D parity O even default 1 odd 2 none a addr 1 to 247 dec Example mb 0 1 0 21 For RTU mode at 19200 even parity Modbus address 21 15hex e DETIT Toggle calibration n 0 for Neoptix n 1 for non Neoptix probes n 0 or n 1 This command can be used to change the calibration type that is active at any given time n 1 should be used to enable the non Neoptix calibration while n 0 should be used for Neoptix probes Warning It is possible that new calibration tables will be introduced in the future in this case calibration n 2 n 3 and so forth may become acceptable also e UNA Analog out if error 0 Max Min 1Hz 1 Max level 2 Min level This command can be used to change the behavior of the analog output s in a situation when the T Guard FL thermometer cannot read a temperature for this channel i can take one of three values o 120 This is the default value to assure compatibility with older Nortech Fibronic inc probes With this setting the analog output will oscillate between its maximum and its minimum value at a rate of approximately 1Hz o i 1 In case of a probe problem the analog output for this channel will be forced to its maximum possible value e g 10V or 20mA Document no G1041r03 Copyright Neoptix Canada LP 19 5 3 1 o 2 In case of a probe problem the analog output will be forced to its minimum possible value e g OV or 4mA re
5. terms contained in the purchase order If Customer has entered into a contract directly with Qualitrol for supply of the Products subject to this warranty the terms of that contract shall supersede any terms of this Warranty or the Warranty Card or the Software License which are inconsistent with that contract Customer acknowledges that the Internet URL address and the web pages referred to in this document may be updated by Qualitrol from time to time and the version in effect at the date of delivery of the Products to the Customer shall apply 1 1 T Guard Family and Neoptix Probe Warranty Notice Your T Guard unit model TGL FL is guaranteed Parts and Workmanship for one full year from the date of purchase Upon written notification of any defect Neoptix will either repair or replace any faulty product or components thereof A Return Authorization Number RMA must be obtained from Neoptix Canada LP or authorized distributor prior to any merchandise return Due to the unique nature of the fiber optic probes that are used with the Neoptix Conditioner system probes are not warranted When using any electrical appliance basic safety precautions should be followed including the following e Do not operate in wet damp environments e Do not operate in explosive atmospheres e Keep product surface dry and clean Always make sure all electrical installations are made in accordance with local authorities regulations and laws Document
6. 0x09 Calibration type Neoptix Other 00011 Ox0A Unit C F 00012 0x0B Reserved valid invalid 00013 0x0C Reserved valid invalid Document no G1041r03 Copyright Neoptix Canada LP 30 00014 Ox0D Reserved valid invalid 00015 Ox0E Reserved valid invalid 00016 OxOF Reserved valid invalid Function 0x02 code Type Read only Bit access Address Name 0 meaning 1 meaning Note 10017 0x10 Channel 1 status No signal Probe detected 10018 0x11 Channel 2 status No signal Probe detected 10019 0x12 Channel 3 status No signal Probe detected 10020 0x13 Channel 4 status No signal Probe detected 10021 0x14 Channel 5 status No signal Probe detected 10022 0x15 Channel 6 status No signal Probe detected 10023 0x16 Channel 7 status No signal Probe detected 10024 0x17 Channel 8 status No signal Probe detected 10025 0x18 Reserved valid invalid 10026 0x19 Reserved valid invalid 10027 Ox1A Reserved valid invalid 10028 0x1B Reserved valid invalid 10029 0x1C Reserved valid invalid 10030 0x1D Reserved valid invalid 10031 Ox1E Reserved valid invalid 10032 Ox1F Reserved valid invalid No probe or broken probe Function 0x03 code Type Read only 16 bits access Address Name Value Note 40033 0x20 Channel 1 temperature Signed 16 bit integer temperature 1 10 40034 0x21 Channel 2 temperature Signed 16 bit integ
7. 485 2W or 4W user configurable Modbus and Neoptix ASCII protocols Analog output 4 20mA TCP IP Ethernet External serial bridge module Selection must be specified at time of order The following figure gives a description of some probe configurations and options that are available from Neoptix Transformer Probe shown with feedthrough fi AM neoptix Temperature sensor inside transformer Part number T2 Mxx Optical feedthrough onto transformer tank wall or plate Extension cable up to Part number OFT Neoptix T Guard System Part number EXT Mxx Document no G1041r03 Copyright Neoptix Canada LP 10 General Purpose Fluorescence Probe WANT T2 Optical Probe Dust and solvent temporary protective cap ST connector 1 7 mm Secondar ma protective Teflon T Serial mnt A PTFE Teflon strain relief TA 4 1 21 mm F ms z 17 p 231 mm PTFE eflon spiral wrap Up to 25 meters OFT Coupling Feedthrough may be different for fluorescence technology for transformer wall application and other similar applications ST Coupling also called ST ST Mating for other general purpose applications ZOU gay vo J 576 MAX DIA TYP ST ST Extension Cable 3 mm Polyurethane cable zo reinforced with Kevlar threading ST connector ba K Other options and configurations are also possible contact Neoptix for
8. 7 6 for more information 7 1 Configuring the Modbus option Enabling and configuring the Modbus option must be done when the T Guard system is not in Modbus communication mode When the Modbus option has been purchased the help menu see Section 5 2 is slightly modified as the following line is added mb Modbus configuration tool type mb for help Typing mb gives Modbus configuration tool mb t b p a lt CR gt Where t type 0 RTU default 1 ASCI b baud 0 9600 1 19200 p parity 0 even default 1 odd 2 none a addr 1 to 247 dec Example mb 0 1 0 21 For RTU mode at 19200 even parity Modbus address 21 15hex Note for OptiLink Il software users The Modbus parameters can also be set up using OptiLink ll See Section 6 4 7 2 Supported serial transmission mode The transmission mode defines the bit contents of the message bytes transmitted along the network and how the message information is to be packed into the message stream and decoded The current implementation of Neoptix Modbus supports only the RTU mode ASCII mode is a future option Document no G1041r03 Copyright Neoptix Canada LP 29 7 3 RTU transmission mode Coding system Number of data bits per character 8 bit binary 10 bits start bits 1 data bits 8 parity bits 0 or 1 even or odd stop bits 1 2 if no parity bit used Parity Not used or even or odd parity Bit transfer rate 9600 or 19200 Baud Du
9. 9 6 Installing probes in power transformers Neoptix offers a complete line of T2 type probes that are specifically designed to be installed inside transformer windings to monitor temperatures of hot spots Please refer to the Neoptix Probe Installation Guide Inside Power Transformers document G1009rxx for recommendations and instructions on how to install and handle these probes to maximize your success rate for this application Document no G1041r03 Copyright Neoptix Canada LP 39 10 INDEX 20 48 volt DC connector Acquisition rate in OptiLink ll Agreement warranty Analog output Setting value if error using serial commands Span setting using serial commands Zero setting using serial commands Analog outputs Connector description How to adjust zero and span How to control behavior when no probe detected Specifications 4 20mA Bulkhead connector cleaning Calibration Annual re calibration Memory corruption NIST traceable Periodicity recommendation Requirements and description Calibration statement One point calibration using serial command Toggling using serial commands Cleaning connectors Client programs Modbus Configuration Recommendations for transformer applications Connector cleaning how to Converters from RS 485 to USB Coupling ST ST Data logging Using Modscan Modbus Description of RS 485 serial port Description ST connector Dielectric materials Dust caps Extension cables 11 External power sup
10. No signal possible LED Failure O Qn E GM Light parameter 3012 is a signal strength detected by the T Guard internal sensor going from a range of about 100 noise level to 4000 You can interpret it approximately as follows e 0 to 300 no probe is detected Temperature reading is rejected e 300 to 1000 a probe is present but exhibits a weak signal This corresponds to a power level ranging from 0 to 10 Temperature reading is rejected e 1000 to 3100 a good probe is present the higher the power the more healthy the probe The power will be more than 10 here e 3100 to 4000 probe saturation Electronic problems Tdecay parameter This is given for information only It gives no information regarding the performance of the probe To summarize a very good probe is characterized by a good power indicator gt 2500 and by a small LED intensity lt 3000 Also dirty connectors will contribute to lower probe strength always insure that all fiber connections are clean before evaluating probe performance Warning After a power on or after changing or exchanging probes or extension cords allow sufficient time for the T Guard optimization process to complete before invoking the y command it most cases it may take as much as 1 minute for this optimization to complete 5 4 Typical temperature reading sequence Once all parameters have been set the following sequence should normally be followed to extract temperature informat
11. PROTOCOL DESCRIPTION You can communicate with your T Guard thermometer via its standard RS 485 port A description of the cable requirements is given above under front panel item 1 Recommendation The use of OptiLink Il software is highly recommended as an alternative to the serial command protocol described in this chapter for more information on OptiLink ll see chapter 6 below Serial functions or commands can be accessed or simply with a computer and communication software such as Windows HyperTerminal or Tera Term or with OptiLink Console software package Your software should be set at 9600 Baud 1 Stop Bit and No Parity Furthermore the new OptiLink II software can also be sued to upload most parameters 5 1 Using HyperTerminal in Windows Hyper Terminal is a standard Windows program XP and previous versions that can be easily used to exercise your T Guard thermometer To use Hyper Terminal you first set its properties as follows 1 In the Connection Description window enter a name that suits you such as Neoptix T Guard Click OK 2 In the next window Connect To select COM1 or another COM port if you are planning to use another port than COM1 in the box called Connect using Click OK 3 Then the COM1 Properties window will come up As indicated above and as shown in the figure at right set the port parameters to 9600 Baud 1 Stop Bit and No Parity Flow control must be set to None Cli
12. bit integer 40055 0x36 Channel 7 status Signed 16 bit integer 40056 0x37 Channel 8 status Signed 16 bit integer 40057 0x38 Channel 1 light level Signed 16 bit integer 40058 0x39 Channel 2 light level Signed 16 bit integer 40059 Ox3A Channel 3 light level Signed 16 bit integer 40060 0x3B Channel 4 light level Signed 16 bit integer 40061 0x3C Channel 5 light level Signed 16 bit integer 40062 0x3D Channel 6 light level Signed 16 bit integer 40063 Ox3E Channel 7 light level Signed 16 bit integer 40064 Ox3F Channel 8 light level Signed 16 bit integer 40065 0x40 Channel 1 LED current Signed 16 bit integer 40066 0x41 Channel 2 LED current Signed 16 bit integer 40067 0x42 Channel 3 LED current Signed 16 bit integer 40068 0x43 Channel 4 LED current Signed 16 bit integer 40069 0x44 Channel 5 LED current Signed 16 bit integer 40070 0x45 Channel 6 LED current Signed 16 bit integer 40071 0x46 Channel 7 LED current Signed 16 bit integer 40072 0x47 Channel 8 LED current Signed 16 bit integer 40073 0x48 Reserved 0x0000 40074 0x49 Reserved 0x0000 40075 0x4A Reserved 0x0000 40076 0x4B Reserved 0x0000 40077 0x4C Reserved 0x0000 40078 0x4D Reserved 0x0000 40079 0x4E Reserved 0x0000 40080 0x4F Reserved 0x0000 40081 0x50 Channel 1 analog zero Signed 16 bit integer temperature 1 10 40082 0x51 Channel 2 analog zero Signed 16 bit integer temperature 2 10 40083 0x52 Channel 3 analog zero Signed 16 bit integer temperature 3 10 40084
13. no G1041r03 Copyright Neoptix Canada LP 7 2 INTRODUCTION The Qualitrol T Guard Link FL TGL FL is a multichannel fiber optic temperature monitoring system for power transformer hot spot measurements and other similar industrial applications It has been developed with long term performance and stability in mind This fiber optic temperature monitoring system offers accuracy toughness ease of use and long term resistance to failure Coupled with this 7 Guard system the Qualitrol fiber optic temperature probes provide accurate and direct temperature monitoring of transformer windings This solution provides a realistic real time view of winding conditions that is quicker and more accurate than WTI Winding Temperature Indicator top oil thermocouple measurements and greatly complements indirect measurements based on thermal models However the first intend of this system is to interface to existing fluorescence probes that are already installed in power transformers Since its inception Neoptix a member of the Qualitrol family has developed expertise in monitoring temperatures of hot spots in power transformers and is considered a world leader in this field Our user guide called Probe Installation Guide inside power transformers part number G1009rXX should be used by transformer manufacturers as a guide to safely install the probes inside windings of a power transformer Make sure you instruct all of your employees that fib
14. 00 00000 00000 00000 00000 00000 00 11 22 14 July 10 2007 30001 00238 00261 08888 08888 00000 00000 00000 00000 00238 00261 08888 08888 00000 00000 00000 00000 00000 00000 00000 00000 00000 00 11 27 15 July 10 2007 30001 00238 00262 08888 08888 00000 00000 00000 00000 00238 00262 08888 08888 00000 00000 00000 00000 00000 00000 00000 00000 00000 00 11 32 15 July 10 2007 30001 00237 00262 08888 08888 00000 00000 00000 00000 00237 00262 08888 08888 00000 00000 00000 00000 00000 00000 00000 00000 00000 00 11 37 15 July 10 2007 30001 00236 00260 08888 08888 00000 00000 00000 00000 00236 00260 08888 08888 00000 00000 00000 00000 00000 00000 00000 00000 00000 00 For Help press HL It is then easy to read this file as an Excel file Warning If you have multiple ModScan windows open then you will have to start multiple logging sessions 7 6 Using opto isolators to deal with grounding problems When experiencing communication problems with multiple Modbus RS 485 systems it is recommended to add opto isolators to your RS 485 lines One opto isolator module is required per T Guard system Neoptix part number NXP 349 is a complete opto isolator kit The installation instructions are summarized using the following two drawings The first one is applicable when you have a 2 wire RS 485 configuration while the second one is for 4 wire installations Refer to information given in Section 8 for more information regarding converters that have g
15. 0024 lt 02000 gt 40050 lt 65037 gt 40076 ST J RE gt 40026 lt 00000 gt 40052 65037 40078 lt 00006 gt For Help press FL Polls 805 Rezpa 805 Click update to write your new value 7 5 3 Data logging ModScan allows you to log either in a text file txt or a database file mdb Microsoft Access format Both are similar Here is a quick example saving to a text file Select Setup from the main menu and then Text Capture In the Save As box enter a proper file name if using Windows Vista or Windows 7 make sure your file is not saved in the Program File directory In the next window enter the frequency at which you want to log data Document no G1041r03 Copyright Neoptix Canada LP 35 Data logging will automatically start To end logging select Setup and then Capture Off The saved file can ModScan32 Data Capture Frequency Options C Save Each Scan Save Selected Scans C Save Running Average Frequency Es then be open using WordPad do not use Notepad Typically the saved data should look like this E JNB_Test_2 t WordPad foie ess File Edit View Insert Format Help Ds 42 4 a gt 11 12 13 July 10 2007 30001 00237 00260 08888 08888 00000 00000 00000 00000 00237 00260 08888 08888 00000 00000 00000 00000 00000 00000 00000 00000 00000 00 11 17 14 July 10 2007 30001 00236 00261 08888 08888 00000 00000 00000 00000 00236 00261 08888 08888 00000 00000 00000 000
16. 0x53 Channel 4 analog zero Signed 16 bit integer temperature 4 10 40085 0x54 Channel 5 analog zero Signed 16 bit integer temperature 5 10 40086 0x55 Channel 6 analog zero Signed 16 bit integer temperature 6 10 40087 0x56 Channel 7 analog zero Signed 16 bit integer temperature 7 10 40088 0x57 Channel 8 analog zero Signed 16 bit integer temperature 8 10 40089 0x58 Channel 1 analog span Signed 16 bit integer temperature 1 10 40090 0x59 Channel 2 analog span Signed 16 bit integer temperature 2 10 40091 Ox5A Channel 3 analog span Signed 16 bit integer temperature 3 10 40092 0x5B Channel 4 analog span Signed 16 bit integer temperature 4 10 40093 0x5C Channel 5 analog span Signed 16 bit integer temperature 5 10 40094 0x5D Channel 6 analog span Signed 16 bit integer temperature 6 10 40095 Ox5E Channel 7 analog span Signed 16 bit integer temperature 7 10 40096 Ox5F Channel 8 analog span Signed 16 bit integer temperature 8 10 Temperature if no signal Temperature if channel disabled Document no G1041r03 9996 999 6 9995 999 5 Copyright Neoptix Canada LP 32 Function 0x06 code Type Write single register 16 bits access Address Name Value Note 40081 0x50 Channel 1 analog zero Signed 16 bit integer temperature 1 10 40082 0x51 Channel 2 analog zero Signed 16 bit integer temperature 2 10 40083 0x52 Channel 3 analog zero Signed 16 b
17. 2
18. 20340 1060P 10045 00271 gt OIE lt 90000 gt sua 03004 20086 lt 00271 gt 39047 90270 SER 20047 00er MOLE cereo 20343 85 20048 902707 iais socero 30944 02608 30057 lt 00270 MOZO lt 0G219 gt 20945 ME 20079 lt 900c2 gt MEL sacom sorae MEL 30073 lt 00000 gt aoza lt 0G0NO 30347 109008 gt 20072 lt 90000 gt MT cocos 30348 103008 30073 lt eoaces oza lt OGONO gt 2094 ODGDE gt 30074 00410 MORE 20270 30350 MEL 39075 10397 7 5 2 Writing parameters To write data you must select either Holding Register or Coil Status Then from the main menu bar select Setup then Extended then Preset Regs Make sure the value of Number of Points is 1 you cannot write to multiple registers at once Make sure the Slave Device is corrected set node number and that the Address points to the register address you want to modify For example to change a temperature value say from 200 to 150 you will enter remember to multiply the temperature value by 10 EE sodScand ModScal ECN ema file Connection Setup View Window Help 2 olsa sjel EA TW SIS IS ma pie Device td 1 Mer pom MODBUS Point Type AR use Length 101 03 HOLDING REGISTER Reset Cte 00000 gt D Ae Teo gt 40099 lt 00000 gt 40022 lt 02000 gt 40048 lt 00000 gt 40074 lt 00002 gt 40100 lt 00000 gt 40023 lt 02000 gt 40049 lt 6S037 gt 40075 lt 00003 gt 40101 lt 00000 gt 4
19. Config to download the current information which will be displayed as follow for an 8 channel system Document no G1041r03 Copyright Neoptix Canada LP 26 TE orte version 1 28 fou DLL OL with JAT Frameset 10 Channel a c E _OptiLink M TS E E gt Once you have made the required changes to the displayed matrix of parameters you must upload these changes by clicking Apply Changes 6 4 Serial protocol parameters This tool is used to set other parameters such as parameters that are linked to the Modbus interface party baud rate etc OptLinied version 137 buit 2013 12 19 with NET Framework 45 1 Acquire tempersnures ome n r lt m re eee e we A _ OptiLink M Sonwa GE 6 5 Firmware update tool This tool provides a simple way to upgrade the TGL FL internal software code Please note that such upgrade can take 10 to 15 minutes or more when using the OptiLink Il software To get an upgrade file you must contact Neoptix support at support neoptix com 6 6 Troubleshooting The serial port is a wonderful thing but if you use it long enough you will soon start using a lucky cable and your working serial port settings will be saved in at least two separate safe places in case of fire Sometimes for seemingly no reason at all there are basic communication issues with the serial port Here are some things you can try to fix those issues 1 Make sure the serial protocol on th
20. Customer Customer a nonexclusive and non transferable license to use the specific Qualitrol program modules feature set s or feature s for which Customer has paid the required license fees the Software in object code form only In addition the foregoing license shall also be subject to the following limitations as applicable e Unless otherwise expressly provided in the documentation Customer shall use the Software solely as embedded in for execution on or where the applicable documentation permits installation on non Qualitrol equipment for communication with Qualitrol equipment owned or leased by Customer e Customers use of the Software shall be limited to use on a single hardware chassis on a single central processing unit as applicable or use on such greater number of chasses or central processing units as Customer may have paid Qualitrol the required license fee and e Customer s use of the Software shall also be limited as applicable and set forth in Customer s purchase order or in Qualitrol s product catalog user documentation or web site to a maximum number of a seats i e users with access to the installed Software b concurrent users sessions ports and or issued and outstanding IP addresses and or c central processing unit cycles or instructions per second Customer s use of the Software shall also be limited by any other restrictions set forth in Customer s purchase order or in Qualitrol s prod
21. Help pR OO Select the COM port connected to your TGL FL and click the Connect button Information confirms you have indeed communicated with the T Guard and you will be provided with additional menu items 6 2 Acquire and Display Temperature Data The Acquire Temperatures application will display up to 64 temperatures 16 temperatures for up to 4 instruments as follows E aot H verson 176 puik 2014 0619 wih NET amano A51 acs tempaisi pia Graph el OptiLink Il Software K O maoo R EEN EI et This window also includes a Graph button which will open an additional window that will show a trend graphic for all previously selected channels channel selection should be made prior to opening this second window See section 6 2 2 for more information The main window also includes a feature whereby the user can save the data acquired since this window was open this data file has the default extension tem and is a CSV type file that can be directly read by Excel Direct saving to an xls file is also possible Please note that data is being acquired ONLY when the Acquire temperatures window is active however the data will be saved only after the Save log button is clicked this will open the following window e ra x Save temperatu I Select from which device s you want to save logs Select a radio button in the group bax below to log all channels for that device only
22. ING one nn Ge isis ee 27 T THE MODBUS PROTOCOL sisccicccieccsuscsecthessseselicesectuscsssehecchesteesstilssestsescssessccesscsbescud shdssbesstestusscsssceesssccceecvesssseess 29 7 1 CONFIGURING THE MODBUS OPTION its 29 72 SUPPORTED SERIAL TRANSMISSION MODE ccsccccccsssssccessssccesscsccesssccesscsccessssccesssceessssccesusecesssccessssecessssecessssecens 29 7 3 RTU TRANSMISSION kd Le 30 7 4 MODBUS FUNCTION CODE AND REGISTER ADDRESSES sss eee 30 7 4 1 Register content TTT 30 7 5 MODSCAN EXAMPLES e e 33 7 5 1 Monitoring multiple T Guard sss 34 7 5 2 Wrinne DHE T T E 35 7 5 3 DGG IOS EME as BARA BAN ad Ra Baa as NS 35 7 6 USING OPTO ISOLATORS TO DEAL WITH GROUNDING PROBLEMS sese eee 36 8 RS 485 CONVERTERS ssssssssieessesteccsveadssaUesesteessuussestevesbuasovaieesvecesveadscaubeovecuwesevoesseusvouedbsbduaesscassceUscousdesssuvesedbessousees 37 8 1 RS 485 TO USB CONVERTER ia 37 9 USING THE TEMPERATURE PROBES vissiscosssesssessdesssesssesssssdesicessiesssossdesssestaesbsestcestsussensssessiesssesssesusssdaeseseseess 38 9 1 CAUTION A A 38 9 2 DESCRITOS 38 9 3 WEARING idad 39 9 4 WORKING WITH LONG PROBES ccsccccsssssccessssccesscsccssssccescsecessesecessusecessusececusecessusecesusececsesececsusececstsececsesecesesess 39 9 5 WORKING WITH CRYOGENIC PROBES ss ccessssccessssccessssccessssccesssecessusecessusecesesececsusececsusececsesececsusecessesecessesecessesecs 39 9 6 INSTALLING PROBES IN POWER TRANSFORMERS ccsss
23. NTIAL INCIDENTAL OR PUNITIVE DAMAGES HOWEVER CAUSED AND REGARDLESS OF THE THEORY OF LIABILITY ARISING OUT OF THE USE OF OR INABILITY TO USE SOFTWARE EVEN IF QUALITROL OR ITS SUPPLIERS HAVE BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES In no event shall Qualitrol s or its suppliers liability to Customer whether in contract tort including negligence or otherwise exceed the price paid by Customer The foregoing limitations shall apply even if the above stated warranty fails of its essential purpose BECAUSE SOME STATES OR JURISDICTIONS DO NOT ALLOW LIMITATION OR EXCLUSION OF CONSEQUENTIAL OR INCIDENTAL DAMAGES THE ABOVE LIMITATION MAY NOT APPLY TO YOU Document no G1041r03 Copyright Neoptix Canada LP 6 The Warranty and the Software License shall be governed by and construed in accordance with the laws of the State of New York without reference to principles of conflict of laws provided that for Customers located in a member state of the European Union Norway or Switzerland English law shall apply The United Nations Convention on the International Sale of Goods shall not apply If any portion hereof is found to be void or unenforceable the remaining provisions of the Warranty and the Software License shall remain in full force and effect Except as expressly provided herein the Software License constitutes the entire agreement between the parties with respect to the license of the Software and supersedes any conflicting or additional
24. PTION FOR THE TGL FL OptiLink II is a software tool that can be used to configure the TGL FL upload a new firmware version etc lt offers a medium that is friendlier than other tools such as HyperTerminal Furthermore it allows to produce real time graphic and to store the resulting acquired data into an Excel compatible file The goals and purposes of this software packages are as follows e Display temperature information for up to 8 channels e initialize and manage TGL FL optical channel and associated control parameters e Upload new 7GL FL firmware software upgrade Information At the time of this writing the TGL FL module is not compatible with the older OptiLink or NeoLink software This software is still in development contact Neoptix for the latest version January 2013 Version 1 37 is described below OptiLink Il can simultaneously support up to 4 Neoptix T Guard instruments either through their serial COM port or through their Ethernet port if available Currently this tool supports the T Guard models 408 405 and T Guard Link FL it is expected that compatibility to more instruments will be developed in the future 6 1 Installation and initial operation The Neoptix OptiLink 1 tool is installed using a standard Microsoft Windows setup exe package Double click on setup exe to launch and accept the usual Windows Security warning to proceed OptiLink Il requires the Microsoft NET Framework version 4 5 If this d
25. acsvassusaessscasaesasese 8 2 1 T GUARD LINK FL FLUORESCENCE TECHNOLOGY PRODUCT SPECIFIC ATIONS sese 10 2 2 CABRA K TO 12 2 3 TRANSFORMER APPLICATIONS a tii 12 NINO A AAA A A E E E EE E AE A E A 13 4 T GUARD TGL HARDWARE REFERENCE eseesesceescesessescescesescescesoescscesceseesescesceseecescesoeseesessesoeseesessescese 14 5 SERIAL COMMAND PROTOCOL DESCRIPTION eessescssescesoesescescesoesoscescesoecescescesceccsoesceseecessescoeseesessesoese 17 5 1 USING HYPER T ERMINAT IN WINDOWS A idos 17 5 2 SERIAL COMMAND HELP MENU dd 17 5 3 DETAILED DESCRIPTION OF THE ASCII COMMANDS sse 18 5 3 1 Recommended configuration for transformer dDpIIcdIIOHS sese esse essen 20 32 Interpretation of y command results sese s sese eee eee 21 5 4 TYPICAL TEMPERATURE READING SEQUENCE csccsssscessecssscessscessecessecessecssecessecessecessccssecessecessecessecsaecessecessecesecenees 21 5 5 ERROR CODES e tk 22 6 OPTILINK IIT SOFTWARE DESCRIPTION FOR THE TGL FL scssccsssssscsssssccssscsscssscssccsscssscsscensees 23 6 1 INSTALLATION AND INITIAL OPERATION ccccccsssssccsssssccsssssccesescesssssccessusccsssssccessusccesusccesusccessssecessusesesssseeessusess 23 6 2 ACQUIRE AND DISPLAY TEMPERATURE DATA 24 6 2 1 Data Acquisition Logging and Graphing Rates sss esse esse 25 6 2 2 TADS sees O EE 26 6 3 OPTICAL CHANNEL SETTINGS TOOL HHE ee ii 26 6 4 SERIAL PROTOCOL PARAMETERS e da aE 27 6 5 ERMWARE UPDATE DO e O 27 6 6 TROUBLESHOOT
26. an32 htm ModScan is a good and simple program that can be used to exercise Modbus links Furthermore it can also be used to perform some simple data logging Please note that this program must be purchased separately it is not supplied as a standard item with the T Guard system When started the following screen will appear uer peteti m fe Sovecian pr Ja e EDO atw Document no G1041r03 Y Copyright Neoptix Canada LP 33 Make sure your T Guard systems are connected to your PC computer Usually as a PC computer does not have a RS 485 port you will normally need a RS 232 to RS 485 adapter or a USB to RS 485 converter available as option from Neoptix You must first connect to your PC by selecting Connection from the main menu and then Connect The following window will open Make sure the Com port baud rate and parity are set correctly Word length should always be 8 Click OK Next make sure Device Id is set to the proper Modbus address You should now be connected and ready to monitor data For example the following figure shows values for all 101 input registers you can see that temperature on channel 1 is 23 6 C and so forth Temperature values are multiplied by 10 and are given as integers not floating point numbers sen perder M T MODAS Pelee Type N Longe TM 04 PUT REGISTER meraes kedar of Pellas 73 d Shave Reepoacec IB gt ered 3 7 5 1 Monitoring mul
27. aused by the fiber optic connector located on the thermometer unit you may have to use a matching gel optical couplant in the connector This gel is a grease like compound with high clarity good resolution properties and a refractive index close to quartz Apply the gel onto connector end faces Avoid disconnecting the connectors for which gel has been used In other words it is recommended to use the gel only for permanent installations If the connectors are disconnected many times you may have to clean entirely the connector assemblies that have had the gel this may require opening the instrument enclosure to remove the excess gel Note that it is not required to use this gel with connectors that are far away from the thermometer electronic unit 9 5 Working with cryogenic probes The use of a cryogenic probe required special attention In particular the probes become more brittle at very low temperatures Avoid cycling the probes quickly between cryogenic temp and ambient temperatures as this may cause material fatigue at the probe tips Warning Always wear protective gloves and clothing when working with cryogenic material Never use general purpose probes at cryogenic temperatures Neoptix sells special probes that can be used at cryogenic temperatures Please note that your T Guard thermometer will require a special factory calibration to be used at cryogenic temperatures below 80 C Consult Neoptix for more information
28. c channel can be disabled A disabled channel will show on its red LED display See the verbose prompt paragraph below to learn how to differentiate between a defective and disabled channel on the command line g f isj Set point adjustment This command forces an actual temperature reading j for channel i any resulting offset will be applied to all future measurements for that channel This is useful to compensate for small temperature deviations that may occur between sensors such as forcing older Nortech Fibronic Inc probes to read similar temperatures as the newer Neoptix probes A maximum offset of 5 degrees C is recommended if it is required for you to force a larger offset your thermometer probably requires a new factory calibration In that case please consult your distributor or Qualitrol Support for more information This procedure can also be called a one point calibration If the j parameter is not used the command will clear any previously entered offset for channel i Remember that this command alters the internal calibration of the instrument Always follow the following recommended procedure l Apply a stable and known temperature to the sensor tip Il Check the display reading for abnormal deviation from the known temperature Document no G1041r03 Copyright Neoptix Canada LP 18 I Send the T command followed by channel number a blank character and the reference temperature
29. ck OK 4 You are ready to go Type h E to test your setup see below Warning the characters that you enter are not echoed to you Connect To COM1 Properties e Neoptix Reflex Enter details for the phone number that you want to dial Port Settings Bits per second EE Y Data bits 8 v Country region Parity None v Area code Stop bits 1 v Phone number Connect using 159125 v Flow control None v Restore Defaults OK Cancel Apply 5 2 Serial command help menu To use the following commands you will need a properly configured serial port client such as HyperTerminal or Tera Term on the Windows platform or the like 3 Vista Win 7 and Win 8 users HyperTerminal is not included with Vista and subsequent Windows versions However an equivalent program HTPE can be downloaded for a fee at the following website http www hilgraeve com htpe download html Tera Term freeware has also given good results see http ttssh2 sourceforge ip Document no G1041r03 Copyright Neoptix Canada LP 17 We recommend HyperTerminal as it was used extensively during the development of the T Guard TGL FL and it provides file transfer functionalities that are not found in all such software tools However it should be noted that Tera Term is a newer program is friendlier for resizing windows copying and pasting as well as changing font and background color on the terminals command prompt and
30. cument no G1041r03 Copyright Neoptix Canada LP 12 3 UNPACKING Before using your T Guard thermometer check the box content to be sure all items have been included Your package should normally contain T Guard TGL FL signal conditioner unit Mating connectors for the power input RS 485 and for the analog outputs total 3 User manual this manual paper copy not included supplied as a PDF document on CD Neoptix OptiLink Pro software on CD supplied with an unlocking key to transformer OEMs only Neoptix OptiLink II software on CD Calibration Certificate Warning NO AC power supply is included with this T Guard unit a power supply must be ordered separately or supplied by the user Options Fiber optic temperature sensor probes Fiber optic extension cables Fiber optic coupling and feedthroughs USB to RS 485 communication interface NXP 349 Power supply module universal input 90 265 VAC 47 63 Hz or 110 370 VDC Table top and DIN mounted models are available Required output is 24 VDC 0 5 Amp Carrying case amp accessories Make sure all listed items have been received and are in good condition Note any evidence of rough handling in transit immediately report any damage to the shipping agent Should a part be missing or damaged please contact your distributor immediately Returns must be made with the original packaging accompanied by an return authorization number RMA Your distributor will provide you with in
31. de The operating mode Modbus or Neoptix ASCIl is confirmed by the LED located near the push button This LED will give the following information Solid green Modbus mode is currently active Solid yellow Neoptix mode ASCII serial terminal Green blinking 5x Temporary blinking 5 times at power on Neoptix calibration enabled Yellow blinking 5x Temporary blinking 5 times at power on Competition calibration enabled Yellow blinking Continuous blinking fatal error contact factory 5 Sensor connector s These are ST type connectors mating to each of the 8 optical temperature sensors If you need to extend a sensor fiber you should use optional extension cables that are available from your Neoptix supplier Warning It is mandatory to keep dust caps black on unused channels as light that might exist from the unused connectors can trigger false temperature readings on other channels It is very important that these caps be black keep the caps supplied with the instrument by Neoptix Warning The fiber type that is used with your T Guard thermometer is of a special type and it is recommended that you get ALL of your extension cables from Neoptix or a Neoptix authorized distributor 6 Ground connection screw For best performance and immunity to local electrical noise it is mandatory to hard wire the T Guard enclosure to the control cabinet local ground Document no G1041r03 Copyright Neoptix Canada LP 16 5 SERIAL COMMAND
32. e T Guard is set to Neoptix The Modbus mode is not supported by OptiLink ll 2 Make sure the COM port is listed correctly in the Windows Device Manager Check the port properties 3 Use the appropriate cables During the development of the tool the serial cabling we used was a USB to RS 485 converter Document no G1041r03 Copyright Neoptix Canada LP 27 The standard interface on the T Guard is a RS 485 port not a RS 232 port You will probably need a converter either a RS 232 to RS 485 converter or a USB to RS 485 converter the latter is recommended Neoptix part number NXP 349 Make sure your wiring matches your computer interface For example if your wiring is for 4 wires make sure the whole cabling and software setting are set for full duplex If part of your wiring follows the RS 232 protocol make sure its cable is kept to a maximum length of 2 meter 6 feet as the baud rate can be as high as 115 200 RS 485 cables can be as long as 1 km at these high baud rates 4 Make sure your duplex settings match 5 Try connecting to the port with a HyperTerminal client to see if it is responsive 6 Try rebooting Windows 7 Try re installing your USB to serial port drivers on Windows 8 When reinstalling OptiLink Il make sure you use the Programs and Features facility in Control Panel of Windows Document no G1041r03 Copyright Neoptix Canada LP 28 7 THE MODBUS PROTOCOL The MODBUS protocol is a messaging str
33. e date of delivery to Customer and continuing for a period of the longer of a ninety 90 days or b the period set forth in the Warranty Card accompanying the Product if any a the media on which the Software is furnished will be free of defects in materials and workmanship under normal use and b the Software substantially conforms to its published specifications The date of shipment of a Product by Qualitrol is set forth on the packaging material in which the Product is shipped Except for the foregoing the Software is provided AS IS This limited warranty extends only to the Customer who is the original licensee Customer s sole and exclusive remedy and the entire liability of Qualitrol and its suppliers under this limited warranty will be at Qualitrol or its service center s option repair replacement or refund of the Software if reported or upon request returned to the party supplying the Software to Customer if different than Qualitrol In no event does Qualitrol warrant that the Software is error free or that Customer will be able to operate the Software without problems or interruptions In addition due to the continual development of new techniques for intruding upon and attacking networks Qualitrol does not warrant that the Software or any equipment system or network on which the Software is used will be free of vulnerability to intrusion or attack Restrictions This warranty does not apply if the Product a has been al
34. ely RX and TX and RX and TX Document no G1041r03 Copyright Neoptix Canada LP 15 b The analog output is forced to its maximum value o1 this would indicate a too hot situation c The analog output is forced to its minimum value 02 this would indicate a too cold situation Warning 1 Do not connect any external voltages to these outputs this may cause permanent damage to the thermometer unit 2 Avoid shorting output leads together as this may destroy the electronic drivers inside the unit 16 position mating connectors are supplied with the T Guard system When using long wires to the analog outputs 4 20 mA it is recommended to use shielded twisted pairs size AWG 24 or 22 The shield should be grounded at one end only preferably the T Guard end 3 20 28 Volt DC power connector You must use an external DC power supply Internal electronic is protected against wrong polarity wiring This model has an internal fuse not user replaceable but does not have a power switch A 2 position mating connector is supplied with this T Guard system The provided Phoenix Contact connections are made to accept wire gauges ranging from 24 to 14 AWG Optimal torque is 0 22 to 0 25 N 4 1 button keypad This button can be used to switch operating mode from Modbus mode or Neoptix mode which can be useful to configure this T Guard serial commands or OptiLink can be used Push down for at least 3 seconds to toggle mo
35. ependency is not present on the target computer then it will be automatically installed first and a reboot will probably be required before resuming the installation On the T Guard TGL FL make sure you have set the protocol to Neoptix this is an easy thing to overlook Make sure your serial port parameters are correct and that your cable matches your port duplex settings Neoptix protocol serial settings are baud 9600 Parity None and Stop bits 1 The LED on the unit will confirm which mode is currently enabled yellow for Neoptix green for Modbus Warning To reinstall the software or install a new version you will need to first uninstall the older version This must be done by using the Program and Features found in Windows Control Panel After installing all the required software a master application window will open as follows a SS 6 Optitink ll version 1 30 but 2013 11 04 with NET Framework 4 5 1 1 lt lt ma eo Log Help QUALI OptiLink Il Software All applications will require that you know which serial com port will be used by OptiLink ll So each application has a COM port selector and a Connect button The COM port selector will only list the currently available ports on your Windows This is the same list of available ports you would view in your Windows Hardware Device Manager Document no G1041r03 Copyright Neoptix Canada LP 23 Optlink Il 8 8 acquire temperatures BR version L
36. er temperature 2 10 40035 0x22 Channel 3 temperature Signed 16 bit integer temperature 3 10 40037 0x24 Channel 5 temperature Signed 16 bit integer temperature 5 10 40036 0x23 Channel 4 temperature Signed 16 bit integer temperature 4 10 40038 0x25 Channel 6 temperature Signed 16 bit integer temperature 6 10 40039 0x26 Channel 7 temperature 40040 0x27 Channel 8 temperature Signed 16 bit integer temperature 8 10 40041 0x28 Internal temperature Signed 16 bit integer temperature 7 10 Signed 16 bit integer device internal temperature 10 40042 0x29 Number of channels Signed 16 bit integer 40044 0x2B Soft revision Signed 16 bit integer 40043 0x2A Soft version Signed 16 bit integer 40045 0x2C Device type Signed 16 bit integer 40046 0x2D Reserved 0x0000 40047 0x2E Reserved 0x0000 40048 Ox2F Reserved 0x0000 40049 0x30 Channel 1 status Signed 16 bit integer 40050 0x31 Channel 2 status Signed 16 bit integer 40051 0x32 Channel 3 status Signed 16 bit integer Document no G1041r03 Copyright Neoptix Canada LP 31 40052 0x33 Channel 4 status Signed 16 bit integer 40053 0x34 Channel 5 status Signed 16 bit integer 40054 0x35 Channel 6 status Signed 16
37. er optic components contrary to conventional copper wires are fragile Generally speaking fiber optics contrary to copper wires cannot be repaired once broken This Qualitrol T Guard gives the exact temperature of optical probes in as little as 250 milliseconds per channel Peak loads or emergency overloads are thus detected almost instantaneously The T Guard system is specifically designed to meet power transformer industry requirements extended intervals between servicing low maintenance rugged components and the ability to withstand the harshest conditions All components have been specifically selected for long term performance including the LED source that has an MTBF estimated at a minimum of 10 years The fiber optic probes compatible with this system must be fabricated with fluorescing material rare earth based this T Guard cannot read probes fabricated with the semiconductor GaAs technology both technologies offer probes that are made only with dielectric materials They are designed to withstand initial manufacturing conditions including kerosene desorption and heat runs as well as long term oil immersion and vibration This 7 Guard system is available with 1 to 8 optical channels As this system is intended to be used as an OEM system it does not have any temperature display LED indicators give immediate information about power on status mode Neoptix or Modbus and communication activity Signal conditioner power consum
38. formation concerning the return of merchandise The carrier will not honor damage claims unless all shipping material is saved for inspection After examining and removing contents save packing material and carton in the event reshipment becomes necessary Document no G1041r03 Copyright Neoptix Canada LP 13 4 T GUARD TGL HARDWARE REFERENCE The following figure shows the T Guard thermometer mechanical layout including dimensions and mounting hole positions 4 x 6 32 screws required 20 Y 41 1 4 20 UNC Y 26 100 99 116 50 3 98 4 59 ES pid FINGON LOdS LOH TVOLLAO Z 3 4X 11 THRU ALL 7 01 6 32 UNC THRU ALL 41 80 1 65 The following drawing gives more details on the electrical connectors as well as pin out information Document no G1041r03 Copyright Neoptix Canada LP 14 Right side Note 1 Input voltage 20 28 VDC 6 W Note 2 Analog output 4 20 mA i one per channel Analog outputs Power input S port ae He elai 400 Ohms per channel Note 2 Note 1 Note 3 Note 3 Serial port RS485 2W RS485 4W 11 GND GND l 2 TX RXa TX Left side 3 TXIRXb TX 4 TXIRXa RX 5 TX RXb RX Note on wiring Shielded cables are recommended Shield should be grounded at one end only preferably at the T Guard end Description of each pointed elements 1 RS 485 serial communication interface This port is used to configure and extract information for the instrument This modular co
39. ime of this writing Similar to the previous windows whereby one can display up to 64 channels from 4 instruments this window can also display up to 64 channels The example below shows a graph while data is being acquired Pomer eS A A R A r l ies enon The code behind this window is quite heavy so this window may sometime appear non responsive please be patient Description of some options that are offered to you e You can adjust the colors of the window background marker style etc With the 3D option more variances are available such as graph rotation etc s The graphic can be zoomed by first right clicking anywhere in the graphic area and select Zoom then select an area that you would like to zoom with your mouse The zoom is cancelled either after one minute or by clicking the Zoom out button e The graphic can be panned by first right clicking anywhere in the graphic area and select Pan then use your mouse to move the graphic area e The window can be saved as an image jpeg png or gif and can be printed s A Pause Graph option is useful if one want to examine in details some parts of the graphic The graphic can be later resumed without loss of data 6 3 Optical channel settings tool This tool is useful to set up parameters that are related to the optical channel of your T Guard system You need to connect only if you are not already connected and then Get
40. ion from your Neoptix thermometer 2 procedures can be used for this purpose The first method consists in using the ta command preferred while the second sequence would be a The host computer should send the t or TTI command followed by an E character b The thermometer responds by echoing the requested temperature values as indicated above the transmission is terminated by a character C When the character is received it is suggested to immediately terminate the dialog session by having the host computer issue the r command followed by a E character Document no G1041r03 Copyright Neoptix Canada LP 21 5 5 Error Codes The following error messages are displayed under certain error conditions ASCII Display Analog Out Description comment Internal memory checksum error Memory corruption When a channel has its calibration table corrupted the corresponding front panel LED will continuously flash to indicate the corruption problem Contact Neoptix Argument out of range Err6 Unrecognized command The exact analog output behavior is a function of the command o see previous Chapter Note that these error codes are not applicable when using the OptiLink software package This high level software package is programmed to automatically handle all types of errors as outlined in the next section Document no G1041r03 Copyright Neoptix Canada LP 22 6 OPTILINK Il SOFTWARE DESCRI
41. is free and Open Source http ttssh2 sourceforge p b Return enclosure temperature e l1 2 n Enable channels to scan if no argument scan all To disable use e channel number f i j Set point adjustment on channel i to j this will create an offset h Help menu this screen i Get factory and status Information mb Modbus configuration tool mb For help Usage mb t b p a b baud 0 9600 1 19200 2 38400 3 57600 4 115200 p parity O even default 1 odd 2 none a addr 1 to 247 dec Example mb 0 1 0 21 For RTU mode at 19200 even parity Modbus address 21 n i Set calibration 0 Neoptix probes 1 Competition o i Analog out if error 0 Max Min 1Hz 1 Max level 2 Min level resetoff Reset all offsets to 0 0 for all optical channels s i Specify analog output Span j for channel i tti Get Temperature reading channel i ulil Unit c Celcius f Fahrenheit y Signal strength z i J3 Temperature 3 for analog output Zero on channel i All commands must be terminated by a carriage return E and are case insensitive i e either upper case or lower case can be used for letter characters 5 3 Detailed Description of the ASCII Commands O Dacrers serim Return enclosure temperature Gives the temperature inside the T Guard TGL enclosure in units as specified by the u command e e 1 2 n Enable channels to scan By default all channels are enabled but a specifi
42. it integer temperature 3 10 40084 0x53 Channel 4 analog zero Signed 16 bit integer temperature 4 10 40085 0x54 Channel 5 analog zero Signed 16 bit integer temperature 5 10 40086 0x55 Channel 6 analog zero Signed 16 bit integer temperature 6 10 40087 0x56 Channel 7 analog zero Signed 16 bit integer temperature 7 10 40088 0x57 Channel 8 analog zero Signed 16 bit integer temperature 8 10 40089 0x58 Channel 1 analog span Signed 16 bit integer temperature 1 10 40090 0x59 Channel 2 analog span Signed 16 bit integer temperature 2 10 40091 Ox5A Channel 3 analog span Signed 16 bit integer temperature 3 10 40092 0x5B Channel 4 analog span Signed 16 bit integer temperature 4 10 40093 0x5C Channel 5 analog span Signed 16 bit integer temperature 5 10 40094 0x5D Channel 6 analog span Signed 16 bit integer temperature 6 10 40095 Ox5E Channel 7 analog span Signed 16 bit integer temperature 7 10 40096 Ox5F Channel 8 analog span Signed 16 bit integer temperature 8 10 Function code Name Usage 02 02h 03 03h 04 04h Read Discrete Input Read Holding Register Read Input Register Optical signal present Device configuration and temperatures Measured temperature values Exception code Description 01 02 Function not supported Register number out of range 7 5 ModScan examples ModScan be purchased from http Awww win tech com html modsc
43. ividually for each 2 200 channel S EE Analog Output Ano Adjust the analog output behavior when no probe is detected See 9 command probes description above Most of these command settings can be confirmed with the CRH l command Document no G1041r03 Copyright Neoptix Canada LP 20 5 3 2 Interpretation of y command results The Neoptix T Guard FL systems are fitted with a function that gives an evaluation about probe signal y strength or signal power in Neoptix jargon this is called the y command The easiest method to access this command is to use Windows HyperTerminal p Typically the y command will return the following information CH1 85 Light 3012 LED 840 status 1 24 5 Tdecay 1460 CH1 indicates the channel number typically 1 to 8 for an 8 channel T Guard system The percent value 85 is an evaluation of the probe signal strength based on calculations involving both parameters Light and LED LED parameter gives an indication about the light source intensity for this channel It ranges from 500 weak LED to 4000 intense LED A weaker source is usually preferred and indicates a healthy probe Status this is a code which value depends on the previous 2 parameters light and LED Probe connected no fault conditions Probe disconnected Probe recovery mode Probe connected Max LED current Probe connected low light level Subtle convergence problem or EEPROM Write
44. latest version from the Neoptix web site www neoptix com Warning this current implementation is weak in term of supporting user interaction with the Excel file during temperature acquisition make sure you do not write or handle anything in the Excel application while an acquisition is active Information This PC data logging never interferes with the instrument on board logging If the data logging is enabled on your 408 instrument this logging will continue uninterrupted whenever OptiLink ll is running 6 2 1 Data Acquisition Logging and Graphing Rates Logging and graphing rates or frequencies in OptiLink Il is very flexible but could be also a bit confusing This section explains the acquisition rate philosophy that is implemented in the software When the Display Temperature window is active the software will continuously acquire and temporarily store the data in a very large software buffer this buffer is being filled at a rate that is called Acquisition Rate now fixed at 1 per second averaging is possible and this will show down the acquisition rate to one per minute This buffer will keep filling as long as the Acquire temperatures window is active Document no G1041r03 Copyright Neoptix Canada LP 25 6 2 2 Graphs This window allows presenting in graphical form both data 1 that is now being acquired and 2 data previously acquired and that is saved in the instrument log memory not implemented at the t
45. more information Document no G1041r03 Copyright Neoptix Canada LP 2 2 Calibration Your T Guard thermometer comes factory calibrated Experience has shown that re calibration is not required over the whole product life however if your ISO rules state that an annual re calibration is required then it is your responsibility to comply with those rules For laboratory applications a new calibration is standard every 12 months or whenever performance verification indicates that calibration is necessary NIST traceable calibration certificates are available All calibrations are performed at the factory Contact your Neoptix Representative for further information 2 3 Transformer applications One of the main applications for the T Guard product is monitoring temperature of hot spots in power transformers Since its inception Neoptix has developed expertise in this application and is considered as a world leader in this field Sister products of the T Guard the T Guard2 T Guard Link T Guard 408 are fully dedicated to the power transformer industry Neoptix publishes a User Guide called Probe Installation Guide totally dedicated to the power transformer industry do not hesitate to ask for your copy if you are working in this field Neoptix document g1009 Please note that this guide discussed the application of T2 probes based on the GaAs technology however the techniques used to handle both type of probes are very similar Do
46. must be set as follows a Switch 1 must be on RS 485 mode b Switch 2 must be off Echo On c Switch 3 must be off 4 Wire mode d Switch 4 must be off 4 Wire mode Warning When dealing with very long cables e g more than 300 meters your RS 485 network might need a termination resistor typically 1200 Consult Neoptix for more details Document no G1041r03 Copyright Neoptix Canada LP 37 9 USING THE TEMPERATURE PROBES 9 1 Caution Each time you connect a temperature probe to the unit the probe optical connector should be cleaned beforehand Otherwise particles of grease or dirt may obstruct the device internal connector and affect the measurements by completely blocking the signal or by generating too much attenuation when using a long fiber length Never use a cloth other than the type recommended for fiber optic cleaning Dampening the cloth with pure isopropyl alcohol ensures good cleaning Occasionally clean the inside of the bulkhead connector attached to the thermometer with a wipe or cotton swab dipped in alcohol 2 5 mm mini foam swabs work best Locking nut Ferue key Ferie For very dirty connectors acetone can also be used but should be used very carefully as it is a very strong solvent Care should be exercised so you do not apply any on plastic materials etc 9 2 Description The optical connector used is a standard ST type connector Device comector Insert errule key here Pins BNC
47. nnector can be wired externally by the user in 2 wire mode half duplex or 4 wire mode full duplex See Chapter 5 for a complete description of the serial commands that are available Please note that all software packages that can be used with the 405 can be in either mode It is very important that your outside wiring and interface to computer match your selection of 2W or 4W 2 LEDs Transmit Receive can be used to monitor any communication activity especially useful when debugging a communication link 2 Analog output connectors There are a total of 16 connection pairs one pair for each channel Prior to shipment your T Guard thermometer was factory set to 4 20 mA analog output The minimum analog output value corresponds to minus 100 C and the maximum analog output value corresponds to 300 C The thermometer normal range is from minus 80 C to 250 C so a minimum value indicates an under range error likewise a maximum value indicates an over range error condition If there is a sensor problem for a given channel the analog output may take one of the following 3 states refer to the serial o command Section 5 3 It will toggle between the minimum and maximum values at approximately 0 5 Hz this indicates a sensor problem for that channel 00 This is the default setting to change it you will need to use the serial command o1 or o2 7 2 wire configuration can be done by shorting together respectiv
48. on It can be used as a diagnostic tool to confirm the good operation of a probe and its extension cable if applicable connected to a channel The Light parameter returned value should be around 3000 and the LED parameter should be less than 4000 a lower value is better A minimum of 2000 LED parameter is required for a channel to return a temperature For a more complete discussion regarding this parameter please refer to Appendix 5 3 2 AEE Mn ce ae Temperature j for analog output Zero on channel i This command is used in conjunction with the s command as it sets the temperature that corresponds to the analog zero minimum value of analog output The i parameter specifies the channel to which the command is addressed valid values are 1 2 3 and 4 The j parameter specifies the zero temperature value and can range from 100 0 to 1000 0 in units that are defined by the u command Factory default is 100 0 Recommended configuration for transformer applications For transformer applications it is recommended that the following parameters be set as follows Feature Benefit description Command Adjust the analog output Zero setting for each channel 71 50 Analog output zero Warning this command must be sent individually for each z2 50 etc channel Adjust the analog output span setting for each channel s1 200 Analog output span Warning this command must be sent ind
49. otices that appear on the original Protection of Information Customer agrees that aspects of the Software and associated documentation including the specific design and structure of individual programs constitute trade secrets and or copyrighted material of Qualitrol Customer shall not disclose provide or otherwise make available such trade secrets or copyrighted material in any form to any third party without the prior written consent of Qualitrol Customer shall implement reasonable security measures to protect such trade secrets and copyrighted material Title to Software and documentation shall remain solely with Qualitrol Term and Termination This License is effective until terminated Customer may terminate this License at any time by destroying all copies of Software including any documentation Customers rights under this License will terminate immediately without notice from Qualitrol if Customer fails to comply with any provision of this License Upon termination Customer must destroy all copies of Software in its possession or control Customer Records Customer grants to Qualitrol and its independent accountants the right to examine Customer s books records and accounts during Customer s normal business hours to verify compliance with this Agreement In the event such audit discloses non compliance with this Agreement Customer shall promptly pay to Qualitrol the appropriate licensee fees Export Software including technical da
50. plex Full or Half Error checking CRC cyclic redundancy check Polynomial CRC 16 101000000000001 Bit transfer order LSBit first MSByte first End of message Idle line for 3 5 or more characters The link layer includes the following properties oehaviours e Slave address recognition Start End of Frame detection CRC 16 generation checking Transmit receive message time out Buffer overflow detection Framing error detection Idle line detection 7 4 Modbus function code and register addresses Warnings e Registers can only be read in groups of up to 16 registers e Multiple write to more than one register is not supported Temperature if no signal 9996 999 6 Temperature if channel is disabled 9995 999 5 7 4 1 Register content details Function 0x01 0x05 Ox0F code Type R W Bit access Address Reg Name 0 meaning 1 meaning Note 00001 0x00 Channel 1 enable disable enable Not implemented 00002 0x01 Channel 2 enable disable enable Not implemented 00003 0x02 Channel 3 enable disable enable Not implemented 00004 0x03 Channel 4 enable disable enable Not implemented 00005 0x04 Channel 5 enable disable enable Not implemented 00006 0x05 Channel 6 enable disable enable Not implemented 00007 0x06 Channel 7 enable disable enable Not implemented 00008 0x07 Channel 8 enable disable enable Not implemented 00009 0x08 Reserved valid invalid 00010
51. ply for T Guard Factory and status information Ferrule connector cleaning Fiber optic probe care Fiber optic probe repair issues Fluo Transformer probe 10 Front panel description Blinking LED memory corruption Front panel description T Guard G1009 probe installation guide GaAs technology Graphing rate is OptiLink ll Graphing using OptiLink II software Grounding problems opto isolator use 29 Hardware reference 10 Heat run tests Help menu Modbus protocol Hyper Terminal serial communication HyperTerminal Tera Term alternative Vista users HyperTerminal Private Edition Document no G1041r03 16 25 4 19 20 20 15 15 15 38 22 14 25 26 36 14 19 29 17 17 17 Win7 and Vista users HyperTerminal Private Edition 17 Illustration Electrical connectors 14 Extension cable 11 Feedthrough 11 OFT coupling 11 T Guard outline 14 Transformer Fluo probe 11 Transformer probe 10 Installation Dealing with grounding applications 36 Modscan 33 OptiLink I 23 Performance verification probes 21 Windows HyperTerminal 17 Isopropyl alcohol for connector cleaning 38 Kerosene desorption 8 LED intensity verification 21 Logging rate in OptiLink Il 25 Logging temperatures to a file with ModScan 35 Mating sleeve ST ST 11 Memory corruption 22 Modbus option Modscan application 33 Modbus protocol 8 Configuration from OptiLink Il 27 29 How is it implemented in the T Guard 29 How to configure 29 ModScan moni
52. ption of the system is 15 watts This T Guard can be mounted in the back of a control cabinet using 4 screws or mounted directly on the cabinet swing door using the four bolt anchors The T Guard TGL FL system provides an easy to use interface to an existing SCADA or substation system through its 4 20 mA analog outputs or through its RS 485 serial port using either the Modbus protocol or the Neoptix native communication mode With its small footprint this TGL is a space efficient and versatile instrument All connections are made through detachable terminal blocks for easy and seamless installation and after sales service This T Guard Link system has been designed to monitor temperatures only it cannot control cooling or generate alarms thus it does not have any relay 1 Also called Temperature Rise Test Document no G1041r03 Copyright Neoptix Canada LP 8 The system s configuration is made through its industrial grade front panel keypad serial terminal or PC software OptiLink for Windows Document no G1041r03 Copyright Neoptix Canada LP 9 2 1 T Guard Link FL fluorescence technology product specifications Calibrated Temperature 40 to 200 C Range Supported probes Neoptix fluorescence probes and competitive probes Usable Temperature 80 to 250 C Range Number of channels 1 to8 Multiple modules can be linked together up to 256 channels Modbus probe configuration dependent Standard interface RS
53. round insulation Document no G1041r03 Copyright Neoptix Canada LP 36 8 RS 485 CONVERTERS 8 1 RS 485 to USB converter As most PC computers today don t have serial ports Neoptix recommends using a RS 485 to USB converter also called adapter It works great with all TGL FL T Guard T Guard2 T Guard 405 and T Guard 408 systems This converter works for both 2W and 4W RS 485 installations no external power supply is required It also offers 2000V RMS optical isolation which is great for electrically noisy applications or when grounding may be a problem The following figure shows this adapter when purchased form Neoptix the adapter will be fitted with a DB9 connector suitable for use for both 2W and 4W applications part number NXP 349 Note that this converter requires a special software driver that needs to be installed before you use the device you will find all details on the CD that comes with the unit Furthermore the converter has 4 dip switches that need to be configured depending on your exact installation there are 2 possibilities as follows a Ifyou have a 2W 2 wire also called half duplex installation then the four dip switches must be set as follows a Switch 1 must be on RS 485 mode b Switch 2 must be on Echo Off c Switch 3 must be on 2 Wire mode d Switch 4 must be on 2 Wire mode b If you have a 4W 4 wire also called full duplex installation then the four dip switches
54. s of this Agreement shall apply to any upgrades updates bug fixes or modified versions collectively Upgrades or backup copies of the Software licensed or provided to Customer by Qualitrol or an authorized distributor for which Customer has paid the applicable license fees NOTWITHSTANDING ANY OTHER PROVISION OF THIS AGREEMENT 1 CUSTOMER HAS NO LICENSE OR RIGHT TO USE ANY SUCH ADDITIONAL COPIES OR UPGRADES UNLESS CUSTOMER AT THE TIME OF ACQUIRING SUCH COPY OR UPGRADE ALREADY HOLDS A VALID LICENSE TO THE ORIGINAL SOFTWARE AND HAS PAID THE APPLICABLE FEE FOR THE UPGRADE 2 USE OF UPGRADES IS LIMITED TO QUALITROL EQUIPMENT FOR WHICH CUSTOMER IS THE ORIGINAL END USER PURCHASER OR LESSEE OR WHO OTHERWISE HOLDS A VALID LICENSE TO USE THE SOFTWARE WHICH IS BEING UPGRADED AND 3 USE OF ADDITIONAL COPIES IS LIMITED TO BACKUP PURPOSES ONLY Proprietary Notices Customer agrees to maintain and reproduce all copyright and other proprietary notices on all copies in any form of the Software in the same form and manner that such copyright and other proprietary notices are included on the Software Except as expressly authorized in this Agreement Customer shall not make any copies or duplicates or any Software without the prior written permission of Qualitrol Customer may make such backup copies of the Software as may be necessary for Customer s lawful use provided Customer affixes to such copies all copyright confidentiality and proprietary n
55. setoff Reset all offsets to 0 0 for all optical channels Please refer to command T described above This will reset the offset for all channels using a single command S i7 9 dd Specify analog output Span j for channel i This command will set the analog output span for the analog channel i the i parameter specifies the channel to which the command is addressed The j parameter specifies the span that can range from 1 0 to 1000 0 in temperature units Celsius or Fahrenheit that are defined by the u command cod sis Get Temperature reading channel i Without parameters the t command will display temperatures for all available channels in the temperature unit currently defined on the system If one provides a valid channel number only the temperature for that channel will be displayed An unavailable temperature will be displayed as Refer to the verbose prompt command to obtain more information on an unavailable temperature WIM RdC cise Unit c degrees Celsius f degrees Fahrenheit Set units of measurements to either Celsius i c or Fahrenheit i f Note that this unit selection is the same as the temperature unit selection made from the keypad if the display option is installed Ex uc followed by a carriage return to select C Celsius Yo Maus awe sees Signal Strength The y command can be used to confirm the signal strength of a probe and or its connecti
56. ssecessssccessssccessesecessssccesesecesusececssececusececsesecesstsecessesecesesess 39 10 ID PARA A O O 40 Document no G1041r03 Copyright Neoptix Canada LP 2 Warning Permanent damage may be done to the thermometer if the power supply connections are not done correctly In particular do not connect the power input 18 24 VDC to any of the analog output connectors Note that the 20 mA analog output options are self powered interfaces by opposition to loop powered interfaces and thus do not require any external supply Maximum loop impedance should be kept at 400 Q internal impedance is approximately 0 7 Q Fiber optic probes are fragile and will break if the bending radius becomes less than 1cm even temporarily Furthermore as probe tips are fragile exercise care to Make sure the last 1 cm of probes is free standing and not pressurized by any glue or by the spacers Avoid bending the last 1cm of probes Furthermore due to the unique construction of the Neoptix probes it is important that you avoid applying glue to the last 1 cm of the probes during their installation in transformer windings Probe breakages are not covered under the standard Neoptix warranty To assure cleanliness of optical connectors keep caps on unused connectors at all time This is also required during operation as parasitic light entering via unused connectors into the T Guard module may cause false temperature readings even on other channels
57. ta may be subject to U S export control laws including the U S Export Administration Act and its associated regulations and may be subject to export or import regulations in other countries Customer agrees to comply strictly with all such regulations and acknowledges that it has the responsibility to obtain licenses to export re export or import Software U S Government End Users The Software and associated software documentation qualify as commercial items as that term is defined at 48 C F R 2 101 consisting of commercial computer software and commercial computer software documentation as such terms are used in 48 C F R 12 212 Consistent with 48 C F R 12 212 and 48 C F R 227 7202 1 through 227 7202 4 Licensee will provide to Government end user or if this Agreement is direct Government end user will acquire the Software and software documentation with only those rights set forth herein that apply to nongovernmental customers Use of this Software and software documentation constitutes agreement by the government entity that the computer software and computer software documentation is commercial and constitutes acceptance of the rights and restrictions herein Document no G1041r03 Copyright Neoptix Canada LP 5 Limited Warranty Qualitrol Systems Inc or the Qualitrol Systems Inc subsidiary licensing the Software if sale is not directly by Qualitrol Systems Inc Qualitrol warrants that commencing from th
58. tered except by Qualitrol b has not been installed operated repaired or maintained in accordance with instructions supplied by Qualitrol c has been subjected to abnormal physical or electrical stress misuse negligence or accident or d is licensed for beta evaluation testing or demonstration purposes for which Qualitrol does not receive a payment of purchase price or license fee DISCLAIMER OF WARRANTY EXCEPT AS SPECIFIED IN THIS WARRANTY ALL EXPRESS OR IMPLIED CONDITIONS REPRESENTATIONS AND WARRANTIES INCLUDING WITHOUT LIMITATION ANY IMPLIED WARRANTY OR CONDITION OF MERCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE NONINFRINGEMENT SATISFACTORY QUALITY OR ARISING FROM A COURSE OF DEALING LAW USAGE OR TRADE PRACTICE ARE HEREBY EXCLUDED TO THE EXTENT ALLOWED BY APPLICABLE LAW TO THE EXTENT AN IMPLIED WARRANTY CANNOT BE EXCLUDED SUCH WARRANTY IS LIMITED IN DURATION TO THE WARRANTY PERIOD BECAUSE SOME STATES OR JURISDICTIONS DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS THE ABOVE LIMITATION MAY NOT APPLY TO YOU THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM JURISDICTION TO JURISDICTION This disclaimer and exclusion shall apply even if the express warranty set forth above fails of its essential purpose Disclaimer of Liabilities INNO EVENT WILL QUALITROL OR ITS SUPPLIERS BE LIABLE FOR ANY LOST REVENUE PROFIT OR DATA OR FOR SPECIAL INDIRECT CONSEQUE
59. tiple T Guard ModScan can be used to monitor either multiple T Guard systems as shown below or multiple type of variables for example the input registers and coil status To do this simply open multiple windows within ModScan from the main menu bar select File and then New Warning if you are opening many windows at once it may be a good idea to slow down the data refresh rate This can be done by selecting Setup from the main menu then Data Definition and then by entering something like 5 seconds in the Scan rate box please remember than you will need to perform this setting for each opened window Document no G1041r03 Copyright Neoptix Canada LP 34 Ri 71 Ek Semmector Setup Yew Diode Dae cial sjel EA oi tie ay aa aja ala a Device le 1 pede Me herbes of Pab 17 MODBUS Poist Type und Clove G 1 asper 9001 MOOS Pairs Type De UT REGSIEA pere Os Leag 05 TE INPUT REGISTER 3003 2 I 310 nant DEIA 30326 097460 th Sez 338 30337 es 9 esha 90033 00060 Hr E 38 isi icon E SK 36080 30330 MER s d Booe lt 2C0N0 30191 109000 K tt 24007 36080 30332 0I008 gt 190960 had DOO lt IG0IO 30939 lt 01008 gt strane T 34005 96z71 30334 109000 gt B SE soezags 3097 109007 B Daor lt 2C347 30336 E 90060 28032 96230 30997 lt 000 gt 390 2 lt 900cO 24037 596080 30330 MEL 39053 lt 00000 gt Bora sacom 30339 iocos soora 100000 HOLE cocoa
60. toring multiple T Guards 34 MTBF of light source 8 NIST traceable calibration 12 Offset on an optical channel How to reset on all channels serial command 20 Oil immersion 8 One point calibration using serial command 18 OptiLink Il software pacakge Acquisition vs Graphing rates 25 OptiLink I software package Acquisition vs Logging rates 25 Com port selection 23 Graphing 26 Logging to an Excel file 25 Option setting 26 Troubleshooting 27 Viewing temperature data 24 Options 13 OptiLink 1 graphing 26 Opto isolators what and when 36 Part 15 of the FCC rules 3 Patch cords See Extension cables Performance verification probes 21 Power connector description 16 Power consumption 8 Power input requirement 16 Power supply 100 240VAC for T Guard 13 Probe installation guide g1009 8 12 39 Copyright Neoptix Canada LP 40 Probe signal strength how to get using serial commands 20 Probes Connector cleaning 38 Performance verification 21 Testing using y command 21 Using cryogenic probes 39 Using long probes 39 Product specifications 10 Recommendations for transformer applications 20 Return authorization number RMA 7 13 RS 232 cable length limitations 28 RS 485 protocol 15 Cable length limitations 28 Dealing with grounding problems 36 RS 485 to USB converter 37 Sensor connectors ST type 16 Sensors See Probes Serial commands y command results 21 Serial communication HyperTerminal use 17 Set Point Adjustment 18 Signal intensi
61. ty verification probe 21 Signal Strength how to get using serial commands 20 Software Modscan application 33 OptiLink ll 17 Serial communication protocol 17 Tera Term 18 Software upgrade statement 5 Specifications 10 ST connector cleaning how to 38 ST coupling or mating ST ST mating sleeve or coupling Document no G1041r03 T2 probes working with long probes Temperature acquisition rate in OptiLink Il Temperature Channel Enabling Reading using serial commands Set Point Adjustment Temperature Unit Setting using serial commands Tera Term software Tera Term software Transformer application documentation Transformer probe Fluo Troubleshooting OptiLink ll Typical temperature reading sequence Universal power supply for T Guard Unpacking USB converters to serial port Vibration resistance Vista users HyperTerminal Private Edition Warranty Agreement Limitations on probes Warranty statement Probe not guaranteed What is in the box Win7 and Vista users HyperTerminal Private Edition Windows Device Manager Windows 7 users HyperTerminal Private Edition Working with cryogenic probes Working with long probes Copyright Neoptix Canada LP 12 10 41 Neoptix Canada LP 1415 rue Frank Carrel Suite 220 Qu bec City QC CANADA G1N 4N7 Tel 418 687 2500 Fax 418 687 2524 www neoptix com www qualitrolcorp com support neoptix com Document no G1041r03 Copyright Neoptix Canada LP Printed in Canada 4
62. type To install the comector Side the femue key gently into the above key Then turing insert the two BNC pins into Tha annrnrviata elate an tha CT edr Document no G1041r03 Copyright Neoptix Canada LP 38 9 3 Warning The T1 probe is quite fragile and it must be handled carefully Please note that any probe damages are not covered by the standard warranty The probe tip is made of silicone rubber Although silicone is resistant to a large number of chemical aggressors strong acids or alkali may damage it especially at high temperature and or if used for extended periods of time Warning Solvents and fuel oils can cause problems for silicone rubber Neoptix also manufactures probes that have their tips made of epoxy Just like silicone epoxy resin is resistant to a large number of chemical aggressors strong acids or alkali may damage it especially at high temperature and or if used for extended periods of time Contact your distributor for additional chemical compatibility information Do not expose your probes to temperatures that are higher than specified Permanent damage can be caused to probes that have been exposed to temperatures that are higher than their limits 9 4 Working with long probes This note is important when using probes or extension cables that have a combined length of 100 meters or more Working with long probes or extension cables may present special problems To limit the amount of back reflection c
63. uct catalog user documentation or web site for the Software NOTE For evaluation or beta copies for which Qualitrol does not charge a license fee the above requirement to pay a license fee does not apply General Limitations Except as otherwise expressly provided under this Agreement Customer shall have no right and Customer specifically agrees not to i transfer assign or sublicense its license rights to any other person or use the Software on unauthorized or second hand Qualitrol equipment and any such attempted transfer assignment or sublicense shall be void ii make error corrections to or otherwise modify or adapt the Software or create derivative works based upon the Software or to permit third parties to do the same or iii decompile decrypt reverse engineer disassemble or otherwise reduce the Software to human readable form to gain access to trade secrets or confidential information in the Software To the extent required by law at Customer s request Qualitrol shall provide Customer with the interface information needed to achieve interoperability between the Software and another independently created Document no G1041r03 Copyright Neoptix Canada LP 4 program on payment of Qualitrol s applicable fee Customer shall observe strict obligations of confidentiality with respect to such information Upgrades and Additional Copies For purposes of this Agreement Software shall include and the terms and condition
64. ucture developed by Modicon in 1979 used to establish master slave client server communication between intelligent devices It is a de facto standard truly open and the most widely used network protocol in the industrial manufacturing environment The Modbus protocol provides an industry standard method that Modbus devices use for parsing messages The Neoptix Modbus option has been developed to support Modbus over a Serial Line protocol A master slave type system has one node the master node that issues explicit commands to one of the slave nodes and processes responses Slave nodes such as the T Guard system will not transmit data without a request from the master node and do not communicate with other slaves At the physical level Modbus over Serial Line systems may use different physical interface RS 485 RS 232 RS 485 two wire interface is the most common As an add on option contact Neoptix RS 485 four wire interface may also be implemented Furthermore the Neoptix Modbus option has been successfully tested over a TCP IP network using a Lantronix device server Neoptix has experienced some communication problems when configuring multiple Modbus RS 485 systems together This is usually caused by unstable grounding problems such as what can be encountered when dealing with power transformers To solve these problems your RS 485 lines should be opto isolated before connecting them to the master Modbus bus Refer to Section
65. value example f2 27 0 followed by ENTER Temperatures must be entered in units as specified by the u command IV Wait a few seconds V Confirm that the readings correspond to the known temperature You can revert at any time to the factory calibration using the resetoff command This will in effect clear any offset that you may have entered for all channels Important always make sure you are reading a valid temperature value before using the T command otherwise your thermometer may display a random value for a channel where the T command has been used Oe eee Help menu This will list the first half of all available commands To see the second half as indicated enter the ltn letter p The listing will fit inside a HyperTerminal prompt window without cropping RX TEA Get factory and status Information Returns general information regarding the instrument including o Model number Unique serial number Number of Channels on device Calibration Type Neoptix probe or Nortech Fibronic Inc probe Internal Software version Factory Calibration Date Temperature unit degrees Celsius or Fahrenheit Analog out if error Analog Zero per channel Analog Span per channel Enabled or Disabled status per channel Temperature offset per channel 0000000000 0 o AAA Modbus configuration tool Modbus configuration tool mb t b p a Where t type 0 RTU default 1 ASCII b baud 0 9600 1 19200 2 38 400 3 57 600