Home
STS49 User Manual
Contents
1. with concentrated layout it should make the intrinsic side adjacent with the intrinsic side and non intrinsic side adjacent with the non intrinsic side to avoid the confusion d On the separate power supply debugging of isolate barrier it is important to pay attention to the model power polarity voltage grading and connector tab on the shell of isolate barriers e It is forbidden to test the insulation between the terminals of isolate barrier with insulation ohmmeter to check the insulation of the system lines it should disconnect all isolate barriers at first otherwise it would cause the fuse of internal instant fuse f If the internal module of isolate barrier is damaged and needs replacement it is needed to return to the factory for repairing The repaired isolate barriers should have a comprehensive re examination before being put into operation g The installation use and maintenance of isolate barrier should strictly abide by the relevant contents of GB3836 15 2000 Part 15 of Explosive Gas Electrical Equipment Dangerous place electrical installation except mine GB50058 1992 Electrical Equipment design code of Explosion and Fire Risk Environment and product brochures 8 Package and Storage 8 1 Isolate barriers should be packed with transparent plastic bags and put in the special packing boxes 8 2 Isolate barriers should be stored in a ventilation indoor environment with ambient temperature of 5 40 C and relative
2. BBO 467 012 10 1 Summary STS49 isolates and transfers 4 20mA of two way safety zone controller drivers two electrical converters electric valve positioner or any two other loads of not more than 750Q in two way danger zone 2 Technical Specifications Channel Double channels Fully floating Area of load Zone 0 IIC T4 6 danger zone Zone 1 Group A Danger zone Safety zone input Signal range 4 20mA Danger zone output Maximum load resistance 750Q Output resistance gt 1MQ Conversion precision 0 2 Temperature drift lt lpA C LED display Green Source indication Source 20 35 VDC Power consumption 20 mA signal at 24V 95mA 2 1 Condition of Use a b c d e Environmental temperature 10 C 50 C Relative humidity lt 90 25 C Atmospheric pressure 80kPa 110kPa No explosive dangerous gases Safety Barrier should be installed in the security zone Um the maximum voltage of non intrinsic side is 250V AC DC and may not have vibration shock and no large current sparks and other effects of electromagnetic induction and the surrounding environment does not have a strong sense of place corrosion The field instruments which connect to safety barrier should have passed the identification of National Anti explosive Testing Institute and got the anti explosive product certification 3 Safety specifications Uo 28V Io 93 mA Po 660mW 4 Signal Connections KN5049Connection Chart Dan
3. ger Zone Safety Zone a _ 4 20mi 6 ch2 BBO 467 012 10 5 STS49 Terminal Functions Terminal Function Terminal Function Safety Danger Zone Zone 1 Input V ch1 9 Empty 2 Input V ch1 10 Empty 3 Input r V ch2 11 Empty 4 Input V ch2 12 Empty 5 Power V 13 Output V ch1 6 Power V 14 Output V ch1 7 Empty 15 Output V ch2 8 Empty 16 Output V ch2 6 Dimensions 7 Installations 7 1 Guideway Isolate barrier is installed on the standard international generic M35 Guideway 7 2 Terminal lead Rubber insulated cables cable insulation strength should be above ACSOOV traverse number of lead should not less than30 and cross section area greater than 0 75mm 7 3 Installation notes a Isolate barrier should be put in a safe place to ensure the cleaning and no corrosive gas b The circuit wiring of intrinsic ends blue and non intrinsic ends yellow of the isolate barrier is prohibited from wrong and confusion The intrinsic safe leads should use the blue as the marking intrinsic leads and non intrinsic leads should be installed separately in the leads slot and use different casing tubes The intrinsic safety side of isolate barrier is not allowed to have a mixture of other power including other power supply with intrinsic safety current BBO 467 012 10 c When the isolate barriers are
4. humidity less than 85 and without corrosive gases in the air 8 3 Attachment A copy of product brochure A copy of product certification 9 Warranty The normal product warranty period is 18 months the damage caused by improper use is not within the scope of warranty
Download Pdf Manuals
Related Search
Related Contents
Nortel Networks Webcam N0060600 User's Manual NT1+Multi Montageanleitung EST 804 ¿Está Embarazada? Copyright © All rights reserved.
Failed to retrieve file