        manual electric fire pump controllers metron series mv600
         Contents
1.    PART I  PART II  PART II  PART IV  PART V  PART VI  PART VII    T    Z letron    Eledyne    MANUAL    ELECTRIC FIRE PUMP CONTROLLERS    METRON SERIES MV600  TABLE OF CONTENTS  GENERAL DESCRIPTION resset iesirea uree R Oer ATSA ETSAN TEASERS PAGE 2  FUNCTIONS arrire ER EE ER OE EE OK PAGE 2  INSTALLA THON ER EE EE ER EE EE EE PAGE 3  INITIAL INSTALLATION START UP          esse esse se se se ee eg ee ee ee Ge Re Re Re ee PAGE 3  OPERATION OF CONTROLLER sesse seek ve ee oe eie be Rek eg DR egg Geen Se eene PAGE 4  SEQUENCE O   OPERATION    ees se vee Ve EE Gee eke Gees ev bek N Nee ees EEE ee ke GE Rea Ee PAGE 5  NOMENCLATURE   a sssssssvesscsesesctaseceaes reba Tir Skei ees kepe Bee DERE EE ea r Age kes E Reeks PAGE 6          Telephone   44  0  1476 516120 FAX   44  0  1476 516121    METRON ELEDYNE LIMITED  18 Autumn Park  Dysart Road  Grantham  LINCS  NG31 7DD  United Kingdom    email  info metroneledyne co uk       www metroneledyne co uk          METRON  INC   1505 West Third Avenue  Denver  Colorado 80223    Telephone   303  592 1903 Fax   303  534 1947    PART I  GENERAL DESCRIPTION    The basic function of the Fire Pump Controller is to start the pump motor to maintain the water system pressure  The  MV600 Controller will automatically start the pump motor upon drop in pressure in the water main or from a number  of other demand signals  This unit can be started automatically  manually or by remote manual means but cannot be  stopped remotely  The controller can be se
2. CVD Current Voltage Display Module  1CT Current Transformer   2CT Current Transformer   3CT Current Transformer   1PR Phase Loss Relay   2PR Phase Reversal Relay    
3. IS LEVER IS FOR  EMERGENCY USE ONLY     Automatic Controller  The controller is now ready for Automatic operation  Timing relay 3TR  should be set for ten  10  seconds minimum  If multiple fire pump controllers are involved  the  timing relays  3TR  should be set for ten  10  second intervals between starting of individual fire  pumps  Refer to Part IV  Item C   Local requirements may dictate different time settings  For  controllers set for Automatic stop  set the running period timer  1TR  for a minimum of ten  10   minutes  To activate the automatic stop feature  the jumper between Terminals C and D must be  removed     Emergency Manual Operation  Emergency manual operation is provided in case of failure of  control circuitry  THIS LEVER IS FOR EMERGENCY USE ONLY  To stop the unit after it  has been started with the emergency start lever  press and hold the stop push button to open the  motor contact  if possible  and move the emergency start lever to the  Off  position     PART VI  SEQUENCE OF OPERATION    Introduction  The explanation of the sequence of operation will start with the assumption that the  controller has been properly installed  all external connections have been made  and the  Drawout Disconnect is in the engaged  closed  position  In other words  the controller is  operational  The power available pilot light should be on     Manual Operation  For manual operation  there is a start push button on the controller and  terminals for an optional remote start 
4. cable external control wires are connected to appropriate terminals as shown on the    schematic  Failure to make the proper connections will cause the controller to malfunction     After installation has been completed  perform the Initial Installation Start Up Procedure  Part IV before operating  the controller     Note  It is recommended that the Toshiba DV drawout unit user manual be read before proceeding     PART IV  INITIAL INSTALLATION START UP PROCEDURE    A  General  All but the final test can be made with the Test Off Run switch in the test position  and  the motor contactor  IMC  in the disengaged test position  This will eliminate the need for  starting and stopping the motor several times during testing  Refer to Part VII for nomenclature of  all controls  Refer to schematic for location of contacts for remote alarms     The controls and their functions are as follows     1  Drawout Disconnect  This assembly is connected in the circuit between the line and the  motor contactor  Its function is to connect disconnect the line voltage to from the cont   actor    2  Fuses  The fuses are electrically located between the motor contactor and the line voltage    stab connectors  They are physically located on top of the motor contactor     3  Emergency Start Lever  FOR EMERGENCY USE ONLY   This mechanical  control is used to start the fire pump in case of any malfunction within the control circuits   When operated  ensure that the lever is moved upward to its highest po
5. isplay the value of motor current that caused the 1OCM to trip  After the 10CM goes into a    locked rotor tripped condition  the display module will display the last current that caused the  1OCM to trip until the reset pushbutton is pressed     Electric Motor Lockout  Option M   Terminals are available to connect to an external switch to  lockout the electric motor  This may be necessary to prevent the motor from starting when the  engine is running or when a low suction cutoff panel is used  etc  The external switch will close to  energize 9CR  A N C  contact of 9CR will break the circuit to 3TR and keep the motor from  starting  With the electric motor lockout feature energized  it is still possible to start the motor  manually     Power Failure Start  Option P   On loss of reliable source of 120 VAC  relay 8CR will be de     energized  The N C  contact of 8CR will close and start the electric motor in the same manner as  for drop in water pressure described in Section C     PART VII  NOMENCLATURE    3CR Manual Start Relay   SCR Transformer Secondary Power Available Relay  7CR Deluge Start Relay  Option D    8CR Power Failure Start Relay  Option P   9CR Motor Lockout Relay  Option M   1TR Run Period Timer   3TR Sequential Start Timer   IMC Motor Run Contactor   IMCA Motor Contactor Auxiliary Contacts  1PB Stop Switch   2PB Start Switch   1PS Pressure Switch   1CPT Control Power Transformer   2CPT Control Power Transformer   1PM Power Monitor   10CM Overcurrent Monitor   1
6. or  1OCM   The overcurrent monitor  LOCM  senses the motor current  through a set of current transformers  CTs  in the controller  When the motor current exceeds  125  of normal a yellow LED illuminates on the monitor and a set of dry contacts change state   When the motor current exceeds 300  the monitor begins timing based on how much the current  exceeds 300  of normal and a red LED begins flashing  The greater the current the shorter the  time period such that at 600  of normal the monitor activates in approximately 14 seconds  When  the monitor activates  at the end of timing   a set of normally closed contacts open de energizing  the contactor coil circuit  In addition the Motor Tripped pilot light is illuminated  To reset the  overcurrent monitor in order to restart the controller  depress the reset pushbutton on the controller  door or press the reset pushbutton in the lower left corner of the 10CM     Current  amp  Voltage Display  1CVD   The 1CVD display unit provides a continuous display of  controller voltage and motor current  A Select pushbutton is provided to toggle the display  between three phase voltage readings and three phase current readings  Also  if the Select  pushbutton is held for 3 seconds the unit will display the highest motor current since the last reset   This value can be reset by holding the Select button for 15 seconds  This feature is especially  useful for monitoring the motor starting current  The unit  in conjunction with the 1OCM will  d
7. or  contactor should open after this time period  If the controller is set for manual stop   jumper between C amp D installed   push the stop button  motor contactor should open     9  For controllers supplied with Option D  repeat Step 8 except momentarily open deluge  valve switch instead of dropping pressure to close pressure switch     Sequential Starting  The sequential start timers provide a time delay between the pressure switch  contacts closing and the motor contactor closing  Set the sequential start timers to approximately  ten  10  second intervals if multiple fire pump controllers are involved  If only one fire pump  controller is involved  set the timer to a minimum of ten  10  seconds  Perform initial start up  procedure for appropriate controller and check for sequential start timing on Automatic starts     PART V  OPERATION OF CONTROLLER    After the installation and test procedure are completed  the unit is ready for normal operation     A     Turn the Test Off Run switch to  Off   Disconnect the external 120VAC power source which was  connected in Part IV     Close the Drawout Disconnect by moving the Drawout Disconnect lever to its highest position   Turn Test Off Run switch to the Run position     Manual Controller  Controller is now ready for manual operation  The controller is started by  pushing the start button  If for some reason the motor fails to start when the start button is pushed   the Emergency Start lever may be moved to the  On  position  TH
8. sition in one  motion with no hesitation  If lever does not latch into the ON position  return it to the  bottom of its travel and try again     4  Start Button  This push button starts the pump motor by exciting the contactor coil so  that it closes     2  Stop Button  This control is to stop the pump motor by opening the contactor coil circuit   thereby  disconnecting the current to the pump motor     B  MV600 Combined Manual Automatic   1  Be sure the isolation contactor section door is closed and latched   2  Operate the Drawout Disconnect lever to its lowest position  The release lever must be    operated in order to do this   3  Turn Test Off Run selector switch to the  Off  position     4  The three prong recessed male receptacle located in the low voltage control section will  have to be energized from a reliable 120 VAC power source of the proper polarity     5  Turn the Test Off Run switch to Test position  Note  The phase reversal and power  monitoring functions are inoperative when in the Test mode     6  Push the start button  the motor contactor should close   7  Push the stop button  the motor contactor should open   8  Drop water pressure at water inlet to controller so pressure switch will close  After a    short delay determined by timer 3TR  the motor contactor should close  Allow water  pressure to return to normal  If controller is set for automatic stop  jumper between C amp D  removed   set the running period timer  ITR  for a minimum of 10 minutes  Mot
9. switch  These switches have normally open contacts which  close to energize 3CR  3CR locks in on its own N O  contact and stays energized until the stop  push button is depressed  A N O  contact of 3CR closes the circuit to the motor contactor to start  the motor     Automatic Operation  Pressure Switch   On drop of water pressure  the N C  contact in the  pressure switch closes energizing the coil of 3TR  At the end of the timer period  a N O  contact of  3TR closes energizing the motor contactor     Automatic Operation  Deluge Valve   Option D   The deluge valve switch is a N C  switch   When it opens  7CR is de energized  The N C  contacts of 7CR in the automatic circuit close and  energize 3TR  The remaining sequence to start and stop the motor is the same as automatic  operation with the pressure switch closing     Remote Pump Running Signal  One  1  N O  and one N C  contact is available for remote  indication that the pump is running     Remote Loss of Power  Phase Reversal  One  1  SPDT contact is available for remote indication  of loss of line power or phase reversal     Motor Overload  One  1  SPDT contact is available for remote indication that the motor current  has exceeded 125  of full load     Engine Lockout  Option E   A N O  auxiliary contact on the motor contactor is provided to  prevent an engine type controller from starting if the electric motor is running  Circuitry for this is  provided in engine controllers supplied with Option E     Overcurrent Monit
10. t to stop automatically or require manual stop after an automatic start     PART II  FUNCTIONS    A  Automatic Starting From    1  Drop in water line pressure    2  Deluge valve operation  Option D    3  Supervisory power failure  Option P    B  Alarm and Signals    1  Remote indication of pump operation  One  1  set of normally open  N O   and normally  closed  N C   contacts located in the controller operate when the pump is running    2  Loss of power to the controller  One  1  Single Pole Double Throw  SPDT  contact located  in the controller operates for loss of power  loss of one phase  or loss of control power    3  Phase reversal of power to controller  One  1  SPDT contact located in the controller  operates for phase reversal of power to the controller    4  Motor Overload  One  1  SPDT contact located in the controller operates when the motor  current exceeds 125  of full load    5  Power ON pilot light  his light is on when the contactor is racked in  indicating that power is  available and the controller is set for operation    6  Phase reversal pilot light  This pilot light is on whenever there is a phase reversal of the  power to the controller    7  Motor Tripped pilot light  This pilot light is on when the Overcurrent Monitor has tripped  and deactivated the contactor coil circuit    8  Engine Lockout  Option E   When an engine drive system is used as a backup a normally    open auxiliary contact on the motor contactor is provided to prevent the engine from s
11. tarting if  the electric motor is running    9  Electric Motor Lockout  Option M   The electric motor lockout is generally used in con   junction with engine lockout above  If the engine is running due to a power outage  or other  reasons  the electric motor can be locked out until the engine is stopped     C  Sequential Starting  This feature is provided to allow a time delay between pressure drop and actual start   ing of the motor which guards against nuisance starts  It also allows for multiple motors to start at  delayed intervals to reduce inrush surges on the electrical line     D  Principal Components of Controller   1  Drawout Disconnect  2  Fuse Rack  3  Contactor  4 Pressure Switch    The incoming line is connected directly to the high voltage buss  From there  the power is fed to the line  side of the motor contactor  1MC  via the stab connectors   This is accomplished by the Drawout feature   The contactor is operated either manually or automatically to start the motor     PART III  INSTALLATION    The high voltage fire pump controller has been assembled and wired at the factory with the highest workmanship  standards  All wiring and functions have been thoroughly tested to ensure correct operation when properly installed   Before operating the controller  perform the Initial Installation Start Up Procedure  Part IV     The cubicle should be well grounded according to local standards  a ground buss is provided in the top of the  cubicle   Make sure that all appli
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Artwizz SeeJacket Clip  Dell G2410H User's Manual  Schmitz OPX mobilis Operating Table  ど便角竜退退 こ の取扱 説明書 を興ず 譜読み”と ”だ 〝さ い  Trevi TAB 0T78GQ01 8GB 3G White tablet  Samsung 2043WM Керівництво користувача  取扱説明書 - テスコム  MSDS受領書 FAXNo.052-443-4825    取扱説明書 PC2000pro - DST-i    Copyright © All rights reserved. 