1. BB0467 012 8 1 Summary STS44 STS44R provide a fully floating space DC power supply to the risk of second line 2 4 20 mA transmitters in two Aerostats Loop Current reproduced signal to drive the two security load The product meets the relevant regulations of GB3836 1 2000 Part 1 of Explosive Gas Atmosphere Electrical Equipment General requirement and GB3836 4 2000 Explosive Gas Explosion proof Electrical Environment Equipment Intrinsic Safety i and obtained a national explosion inspection agency issued certificate of explosion proof products can be applied to different intrinsic safety and explosion proof system 2 Technical Specifications Channel Double channels Fully floating Area of transmitters Zone0 IIC T4 6 danger zone Zone 1 Group A Danger zone Safety zone output Signal range 4 20mA Safety zone load resistance 0 5500 Output resistance in the loop gt 1MQ Danger zone input Signal range 4 20mA Voltage Distribution at 20mA gt 15 5V Conversion precision 0 1 Temperature drift lt luA C LED display Green Source indication Source 20 35Vdc Power consumption 20 mA signal at 24V 110mA 2 1 Condition of Use a Environmental temperature 10 C 50 C b Relative humidity lt 90 25 C c Atmospheric pressure 80kPa 110kPa d No explosive dangerous gases e Safety Barrier should be installed in the security zone Um the maximum voltage of non intrinsic side is 250V AC DC and
2. may not have vibration shock and no large current sparks and other effects of electromagnetic induction and the surrounding environment does not have a strong sense of place corrosion f The field instruments which connect to safety barrier should have passed the identification of National Anti explosive Testing Institute and got the anti explosive product certification 3 Safety Specifications Uo 28V Jo 93 mA Po 660mW 4 Signal Connections 5 STS44 STS44R Terminal Functions BB0467 012 8 Danger Zone EKZ9744 Connection Chart Safety Zone E ISSV em 1 5VDC erz Terminal Function Terminal Function Safety Danger Zone Zone 1 Output V chl 9 Empty 2 Output V chl 10 Empty 3 Output V ch2 11 Empty 4 Output V ch2 12 Empty 5 Power V 13 Input V 6 Power V 14 Input V 7 Empty 15 Input V 8 Empty 16 Input V 6 Dimensions BB0467 012 8 7 Installations 7 1 Guideway Isolate barrier is installed on the standard international generic M35 Guideway 7 2 Terminal lead Rubber insulated cables cable insulation strength should be above ACSOOV traverse number of lead should not less than 30 and cross section area greater than 0 75mm 7 3 Installation notes a b c d e f g Isolate barrier should be put in a safe place to ensure the cleaning and no corrosive ga
3. nts of GB3836 15 2000 Part 15 of Explosive Gas Electrical BB0467 012 8 Equipment Dangerous place electrical installation except mine GB50058 1992 Electrical Equipment design code of Explosion and Fire Risk Environment and product brochures 7 Package and Storage 7 1 Isolate barriers should be packed with transparent plastic bags and put in the special packing boxes 7 2 Isolate barriers should be stored in a ventilation indoor environment with ambient temperature of 5 40 C and relative humidity less than 85 and without corrosive gases in the air 7 3 Attachment A copy of product brochure A copy of product certification 8 Warranty The normal product warranty period is 18 months the damage caused by improper use is not within the scope of warranty
4. s The circuit wiring of intrinsic ends blue and non intrinsic ends yellow of the isolate barrier is prohibited from wrong and confusion The intrinsic safe leads should use the blue as the marking intrinsic leads and non intrinsic leads should be installed separately in the leads slot and use different casing tubes The intrinsic safety side of isolate barrier is not allowed to have a mixture of other power including other power supply with intrinsic safety current When the isolate barriers are with concentrated layout it should make the intrinsic side adjacent with the intrinsic side and non intrinsic side adjacent with the non intrinsic side to avoid the confusion On the separate power supply debugging of isolate barrier it is important to pay attention to the model power polarity voltage grading and connector tab on the shell of isolate barriers It is forbidden to test the insulation between the terminals of isolate barrier with insulation ohmmeter to check the insulation of the system lines it should disconnect all isolate barriers at first otherwise it would cause the fuse of internal instant fuse If the internal module of isolate barrier is damaged and needs replacement it is needed to return to the factory for repairing The repaired isolate barriers should have a comprehensive re examination before being put into operation The installation use and maintenance of isolate barrier should strictly abide by the relevant conte

Download Pdf Manuals

image

Related Search

Related Contents

BEDIENUNGSANLEITUNG USER MANUAL - SSH Party-Team  Hamilton Beach 52400 User's Manual  STX - manual - Elmes Elektronik  CEV 2013 REGLAMENTO TECNICO SUPERSTOCK 600  QCM n° 8 - orleans paramoteur  RPP-02 User Manual  

Copyright © All rights reserved.
Failed to retrieve file