User`s Manual - Douglas Lighting Control
Contents
1. 5 Name Settings Project name Maps 6 Page Displays Page Reload Cycle Maps and Lists Lighting System Errors Status Bar 7 Message Display Control Performing setup Message display duration 8 Monitoring and Warning of System Status System errors monitored 9 Control History LOG Number of Control history records Control History Subjects Applicable Points for Status Changes History 32 characters max iso 8859 1 CP932 32 characters max iSO 8859 1 CP932 30s 1 2 3 4 5 10 15 20 25 and 30 minutes 5 6 7 8 9 and 10s 30 min 1 hour 2 hours and 3 hours NCU connection error Date amp time out of control local bus error FULL 2WAY signal error and Pattern group configuration in progress Most recent 1 000 records per day for most recent seven days Web Window control schedule control status change of local controls and control errors Selected points from groups patterns and zones for the connected LIU The original information on status change will not be transmitted to the higher layer if the DIP switch pin for status change notification is set to No 0 on the NCU and LIU Number of System Error History Records System Error History Recorded files 10 Managed Data Files Data File Format Type of Data Files e File Transfers Most recent 1 000 records per day for most recent seven days NCU connection e
2. For details on terminal arrangement refer to Specifications 24 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Installation Section c Connections between Local Interface Unit LIU and NCU Always use the WR3388 8 Local Interface Unit The local bus network between the NCU and LIU requires a shielded cable CPEV S Connect the terminals labeled Network signal output on the NCU and Network signal input on the LIU with matching polarities When connecting multiple LIUs terminals labeled Network signal output must be connected in a bus configuration Connect the NCU to the end terminal of the local bus local network Bus terminating resistance is built in Do not connect anything to the terminals on the Configurator RS 232C d Connections between FULL 2WAY Remote Control System and LIU Always use the WRT2050 80 WRT2040 82 81 894 series Transmission Unit Communications cables such as CPEV are recommended for connections The output signal for the Transmission Unit must be sent to the FULL 2WAY signal terminal of the LIU FULL 2WAY devices such as circuit control devices T U and switches must be connected to the same communications cable Wire connections using a star or bus configuration Do not use a loop Doing so may cause malfunctions Do not wire signal lines parallel to power lines If unavoidable separate the cables by at l
3. 008 Group 008 Disabled v 072 Group 072 Disabled 009 Group 009 Disabled v 073 Group 073 Disabled 010 Group 010 Disabled v 074 Group 074 Disabled v 0il Group 011 Disabled Y 075 Group 075 Disabled 012 Group 012 Disabled 076 Group 076 Disabled 1 Select the LIU No for the system and click the Select Button The currently registered data will be displayed Only numbers enabled in LIU Connection Settings can be selected 2 Select enabled disabled for the level display If enabled the Get Level Button will be displayed on the following pages Control dialog boxes for symbols on maps and individual circuits in Monitor amp Control List Dimmer level pane in Advanced Control Individual Circuit 3 Click the Submit Button The settings will be applied to the page Dimming levels for groups will be displayed from 0 to 7 To obtain and display dimming levels dimmer T Us must be installed at the addresses included in the groups If the address included in the group happens to be a relay control T U the level will be displayed as 1 for ON and 0 for OFF Factory Settings Level Display Disabled for all addresses AL WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 11 Status Bar Manager some of setting functions for control and setting menus will affect other functions and therefore other users connected at the same time should be notified The S
4. 109 lt a401 gt 109 lt d30100IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII gt 08 lt d301 gt 07 lt d20101P1P1P1P1P2P1P1P1P1P1P1P1P1PiPiP gt 107 lt d201 gt 106 lt d1010QIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII gt WSU gt NCU 05 10 31 02 39 05 lt d101 gt WSU lt NCU 05 10 31 02 39 04 lt d4010IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII gt WSU gt NCU 05 10 31 02 39 04 lt Sd401 gt WSU lt NCU 05 10 31 02 39 03 lt d30107IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII gt WSU gt NCU 05 10 31 02 39 03 lt d301 gt WSU lt NCU 05 10 31 02 39 02 lt d20101P1P1P1P1P2P1P1Pi1Pi1PiPiPiPiPiPiP gt 602 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 14 Data Monitor The remaining storage capacity for saving data in the Web Server Unit can be checked Used Space Total memory space used by data and the system Unused Space Total unused memory space that can be used for data Supplemental Information Creation of map data requires separate special software Refer to Il Creation and Administration of Map Data for details 603 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 15 Maps Manager The Maps Manager is used to delete map data saved in the Web Server
5. 2 Enter the user name in the User name field 3 Enter a new password in the Password and Retype Password fields 4 Click the Submit Button Password changes can be performed by the user with the system administration right only If the system administration password has been changed a new login is required immediately after clicking the Submit Button Important notice The user name and password for the system administrator cannot be recovered by the user if they are ever forgotten after being changed They do not respond to initialization using the hardware switches for security Therefore be sure to store this information in a safe place iv Factory defaults values The factory default values for users and passwords are as described in the following table System Administration Be sure to change user names and passwords before operation for security User names and passwords can be reset to the above text in the Factory Settings Menu 44 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 3 Date amp Time Settings The clock inside the Web Server Unit can be adjusted in the Date amp Time Settings Dialog Box Date and time must be set for schedule control and log keeping Location name System Administration gt Date amp Time Settings Control Presenttime May 30th 2005 14 47 21 Date amp Time 2005 05 30 14 47 21 Syst Admini Sw Input
6. If enabled the Get Level Button will be displayed on the following pages Control dialog boxes for symbols on maps and individual circuits in Monitor amp Control List Dimmer level pane in Advanced Contol Individual Circuit 3 Click the Submit Button The settings will be applied to the page Dimming levels for individual circuits will be displayed between 000 to 128 To obtain and display dimming levels dimmer T Us must be installed at the addresses If the address happens to be a relay control T U the level will be displayed at the fixed level of 000 Factory Settings Level Display Disabled for all addresses 110 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings Location name Advanced Control amp Settings gt Dimmer Settings gt Groups Basic Monitori ss LIUNo 01 v Advanced Control amp Address Settings Mapi Submit Address Name Level Display Address Name Level Display Advanced Control 001 Group 001 Enabled 065 Group 065 Disabled Group Settings Pattern Settings 002 Group 002 Enabled 066 Group 066 Disabled X F i 003 Group 003 Disabled v 067 Group 067 Disabled Name Settings 004 Group 004 Enabled 068 Group 068 Disabled permease 005 Group 005 Enabled v 069 Group 069 Disabled Ser A 006 Group 006 Enabled 070 Group 070 Disabled 007 Group 007 Enabled v 071 Group 071 Disabled System Administration
7. Program data for schedule control is stored in the Web Server Unit 2 Program Execution WR3330 801 WR3387 8 WR3388 8 Web Server Unit NCU LIU 3 Transmission Unit Switch p p To lighting fixture D Timer control time D Contact output status 2 Request to NCU 2 Circuit address status AU 3 Request to subject LIU 3 Status acquisition by NCU SS FEE General purpose PC Monitor amp control configuration 4 Request to transmission unit 4 Status acquisition by Web Server Unit 5 Request to control T U Reloading browser page Operations are based on the clock inside the Web Server Unit WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Summary 3 Monitoring Circuit Status Changes Controlled by the Wall Switches of the Local System Transmission Unit Switch WR3330 801 WR3387 8 WR3388 8 Web Server Unit NCU LIU _ an 1 EA gt gt i To lighting fixture D Control operation from wall oO Contact output status switch control request to J Circuit address status AU Tranamission Malt Status acquisition by NCU D Request to control T U 4 Status acquisition by Web Server Unit General purpose PC Monitor Reloading browser page amp control configuration Basic monitoring is performed periodically on all circuits Data for groups patterns and zones however can be reported to the higher levels in the hierarchy only
8. e Name Names registered in Name Settings i Registering a New List 1 Click the Add New Button of the item to applicable list number Address sang The Address Setting Dialog Box will be displayed No 7 2 Select an address CC Select the address type in the Type field LIU number in the LIU field e and address number in the Address field of the Address Setting Modify Name Cancel Dialog Box sve pt Wino 3 Click the Submit Button The address will be added to the table under List 72 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings ii Changing the List Contents 1 Click the Edit Button for the applicable item in the List An address setting dialog Box will be displayed 2 Select another address z Enter the information in the Type LIU and Address fields again Submit Modify Name Delete Cancel 3 Change the name of the circuit m If the Modify Name Button is clicked the Name Setting Dialog Box will be displayed Enter the name in the Name field The name must be 32 o VE characters long or less Name setting Non Iso 8859 1 CP932 characters will be corrupted e er cian 4 Click the Submit Button Address 00 1 The change will be reflected in the list O B Names can also be modified under Name Settings menu in Cancel Advanced Control amp Setting dees Hone Wisin inn iii Deleting an Item in the Lis
9. Also simultaneous registration from multiple clients is not possible ii Deleting User Registrations Registered users can be deleted under Delete User 1 Select the displayed user names for Basic Monitoring and Basic Monitoring amp Control Users 2 Click the Delete Button Note that there must be at least one user registered for all types of users Also entries for the Advanced Control amp Settings User and System Administrator User cannot be deleted but can be overwritten under Add New User If another administrator concurrently logged in has changed deleted the registration the changes are not displayed until operating windows are reloaded Therefore even if operations have been completed actual registrations may not be stored in the Web Server Unit because the user registration has not yet been enabled A user registration may be deleted while a user is still logged in In this situation a window requiring the user authentication will be displayed to that user Also the Please wait for a moment message will be displayed on the task bar In that case the user must reopen the browser and log in again with another user name and password that are valid 43 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration ili Changing a Password Perform these settings under Add New User 1 Select the access right from the pull down menu in the Access Rights field
10. English User s Manual system Administration 17 Reboot Reboot is used to restart the Web Server Unit from the browser Some settings pages require rebooting to enable the submited parameters Location name System Administration gt Reboot Settings Reboot Date amp Time Setti Click the Reboot button in order to reboot the web server unit Settings that Require Rebooting Network Settings Project Display Settings RS 232C Connection Settings Factory Settings 1 Click the Reboot Button 2 Select OK or Cancel Microsoft Internet Explorer Click the OK Button in the Okay to Reboot Dialog Box to execute 2 okay to reboot Click the Cancel Button to cancel 3 Wait for rebooting to complete The Web Server Unit will start to reboot During this process _ messages such as Please wait fora moment and Initializing will be displayed in the status bar Wait until the process is completed ae ee and the message in the status bar changes to Connected System Administration gt Reboot Supplemental Information The display within the Main Frame remains the same even when rebooting is completed If the unit is rebooted while Performing setup status being activated Status Bar Manager Performing setup status will be deactivated after rebooting If another PC attempts connection during rebooting the Status Bar may not display anything because Java applets
11. Once this operation is done the lost data cannot be recovered Location name System Administration gt Factory Settings ic Monitori S daii al To enable c please reboot Network Settings Maps Delete Sett Monitor amp Control List Settings Initialize es 5 Address Setting Delete Project Display Settings Global Address Setting Delete ae Schedule Settings Delete View Special Day Settings Delete Upload Manager Astronomical Clock Settings Initialize Data N Name Settings Initialize Map Manager Network Settings Initialize a Authentication Initialize RS 232C Settings Initialize LIU Settings Initialize Page Reload Settings Initialize Project Display Settings Initialize Log Settings Initialize a Comed List of Items that can be initialized deleted Maps Map data transferred from The Screen Builder All map data will be deleted in one batch operation For details on deleting by window refer to Maps Manager page Monitor amp Control List Settings List setting data registered in Monitor amp Control List Settings page Data will be initialized Address Settings Address Settings data assigned to maps symbols in Address Settings page Data will be deleted Global Address Settings Global address settings data registered in Global Address Settings page Data will be deleted Schedule Settings Programs settings data registered in Programs
12. Zone Settings 003 Program 00 01 Individual Circuit 00 2 ON Sunrise From 01 00 until sunrise meee Te aa Peram M 004 Progam 004 Add New mmm Empty Spacia Days Calendar 005 Program 00 01 Group 002 OFF ON From 07 00 until 18 00 Mb o stronomscal Ciock OS Name Settings Dimmer Settings 006 Program 006 Empty Status Bar Manager 007 Progam 00 AddNew memm Empty 008 Program 00 an Empty i Viewing the Status of Programs Registered Programs are shown in a table No Number of the program 930 max e Name Name of program LIU No LIU number e Type Type of address Address Address Operation Time controls sunrise sunset controls inter day control and repetitive control Schedule Start and end times Days of the Week Days of the week for weekly control e Special Day Matrix displays of the special days to which the program is applicable 1 Included Denotes that the program will execute on that special day 0 Not Included Denotes the special day is excluded from program execution N A Special day is not applicable for the program The matrix display 10 x 3 correspond to special day numbers as follows Line 1 Special Day 01 Special Day 02 Special Day 03 Special Day 10 Line 2 Special Day 11 Special Day 12 Special Day 13 Special Day 20 Line 3 Special Day 21 Special Day 22 Special Day 23 Special Day 30 88 WR3330 801 FULL 2WAY Web Server Unit Panel Use
13. a Light adjustment control Dimmer 01 Dimmer 01 Java Applet Window E Light adjustment control Dimmer 01 Dimmer 01 Dimmer Level 001 ON OFF Cancel Java Applet Window WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control iti Viewing the Dimmer Level 1 Click the red green button in the Status column A dialog box will open with the dimmer level displayed if the status is ON The level may not be obtained and displayed immediately after the circuit is turned ON Dimmer Level Value Table Control Type ON Brightest Least Bright OFF 125 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control 2 Advanced Control Groups Group Addresses 001 to 127 Location name Advanced Control amp Settings gt Advanced Control A Control 001to064 065t0127 UNo 01 v Advanced Control amp Address Settings Groups Mapi Advanced Control Patterns T eaa Group 007 os Soup 039 Status Bar Manager v lt gt 1 Select the LIU number and click the Select Button 2 Click the 001 to 064 or 065 to 127 button The display of group addresses is split into 2 windows of 64 addresses each The statuses of the selected addresses are displayed in the Status Fields As shown in the figure ON is ety pele ai No T U or unregistered in gray and details are g
14. details Special days can be registered without execution days but no controls will be performed 11 Click the Submit Button The settings will be enabled If the Cancel Button is clicked registration will be aborted and you ll be switched to the programs select page If the Delete Button is clicked the content of the corresponding program number will be reset to unselected status The settings will be saved in the Web Server Unit Registration from another browser is disabled during registration Even while editing data for registration schedule controls will be performed except for the program being edited 9 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings b Programs Monitor Programs Monitor is used to confirm scheduled controls to be executed on specified days Times and values are displayed for only controls actually executed based on the combinations of the day of week special day sunrise Ssunset times disabled operations and other parameters Location name Advanced Control amp Settings gt Schedule Settings gt Programs Monitor Select Date Special Days May 30th 2005 v No Name Address Settings Map1 Select Programs Advanced Control Group Settings No Name LIU No Type Address Operation Details Pattern Settings Tonsotunz 001 Program 001 01 Individual Circuit 00 1 Sanset ON 0527 OFF bide si
15. female connector Terminal Ready Data Set Ready Ready to Send Clear to Send Carrier Detect Send Data Receive Data Signal Ground Frame Ground WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information Indicators Power ON Ethernet LINK Ethernet ACT NCU Connection Error Date amp Time Out of Order Terminals and Connectors 24 VAC power terminal Grounding terminal Ethernet connector e NCUconnector Applicable Cables 24 VAC power cable Grounding cable Ethernet cable e RS 232C cable Applicable crimp terminals Z a 2 z 3 units mm Structure roe do A O gt O Outer dimensions WxHxD 100x124 8x60 mm Sle gt ll JIS approved dim 5 i F Installation method Mounting Strap i HE WR9910 8 s el for Panel use a i e Weight Approx 325 g F F Material ABS plastic chassis Setting Unit connector for maintenance Red Green Orange Red M3 5 screw M3 5 screw RJ45 modular jack D sub 9 pin male inch screw D sub 9 pin male inch screw Solid 0 9 mm to 1 6 mm dia Stranded 0 75 mm to 2 0 mm Maximum extension 50 m Solid 1 6 mm dia Stranded 2 0 mm connecting PCs directly Maximum extension 100 m Modular cable for LAN category 5 E 6 twisted pair Straight connection Use cross connection when D sub 9 pin female inch
16. 0 00 Start End OFF ON Current day 0 00 Start End ON ON Current day 0 00 Start End OFF OFF Current day 4 0 00 Start End 2 Single Operation ON Current day 0 00 Start OFF Current day 0 00 Start ON Execute Sunset Execute and Sunrise Execute Current day 0 00 Start 3 Repetitions Controls are repeated from the start time to end time inclusive of end time at a fixed interval In repetition execution even if the start control was delayed for some reason the end control will be still be performed at the time originally set SAE WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings Current day 0 00 Star End Interval 90 to 90 minutes 4 Start Time End Time For Sunset ON OFF and ON Sunrise OFF start and end times may be set to the same time but no control will be performed if they are Furthermore the times may be different when settings are configured but they may become the same time as the sunrise Sunset time shifts In this case controls will not be performed either For fixed time ON and OFF the start and end times must be different when the settings are configured Current day 0 00 Start End 5 End Time lt Start Time Inter day Control End control will be performed the next day Sunset ON Sunrise OFF Sunset ON OFF ON Sunrise OFF and ON OFF Current day Next day Start 0 00 End OFF ON C
17. 17 Special Day 17 n Special Day 27 o SA 18 a z yia 08 Special Day 08 18 Special Day 18 2 Special Day 28 09 SPee DT N 19 SEeael Doy i 2 eaten ad 09 Special Day 09 19 Special Day 19 Special Day 29 10 een 2 ene 3 seal 10 Special Day 10 2 Special Day 20 30 Special Day 30 90 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 9 Select the times Select the start time end time and or repeat interval All of these may not be displayed for all operations If sunrise or sunset is selected for the operation the sunrise and sunset times will be automatically displayed as control times for the district Refer to Astronomical Clock for setting districts Although sunrise sunset times are displayed for the day the program is registered controls are based on the actual sunrise sunset times for the day the controls are performed Refer to Miscellaneous Information l Appendix Sunrise Sunset Timetable for sunrise and sunset times Minimum configurable control time unit is 1 minute The range of adjustments to sunrise sunset times is 90 minutes Minimum adjustable unit 1 minute The range of adjustments to repeat interval is 1 minute to 1 hour 30 minutes Minimum adjustable unit 1 minute An error will occur if the same fixed time is set for both ON and OFF If sunset or sunrise time is included the same start and end times for the day can be registered but if t
18. 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information Communications Interface 1 Ethernet Communications Interface Port number Connection Connection speed Communications standards media access Protocol Encryption Connector 2 NCU RS 232C Communications Interface Port number Hardware standard Connection Transmission Baud rate Transmission code Synchronization Protocol Polling selecting ratio Polling cycle Error correction Connector Pin connections Web Server Unit D sub Spin male connector Terminal Ready Data Set Ready Ready to Send Clear to Send Carrier Detect Send Data Receive Data Signal Ground Ring Indicate RS 232C Cable 137 1 MDI type MDI X is not supported 10Base T half full duplex 100Base TX half full duplex Auto negotiation 10 100 Mbps IEEE 802 3 IEEE 802 3u CSMA CD TCP IP HTTPS 443 Proprietary 6001 SSL 3 0 RSA 128 bit RJ 45type 8 pin connector 1 CCITT V24 JIS X 5101 Direct connection Half duplex 19 200 or 9 600 bps JIS 7 bit 1 parity Asynchronous with 1 start bit and 1 stop bit Polling selecting JIS X 5002 equivalent 2 0 4 second Vertical parity even parity horizontal parity LRC algorithm transmission time monitoring timer D Sub 9 pin male connector inch screws Shown below Network Control Unit NCW D sub 25pin
19. Address 08 Add New System Administration 09 Global Address 09 Add New 10 Global Address 10 Add New li Global Address 11 Add New 12 Global Address 12 Add New 13 Global Address 13 Add New 1 Select an address Click the Add new or Edit Button for the global address 32 maximum The page will move to the Global Address Setting Page Location name Advanced Control amp Settings gt Glohal Addresses Settings Basic Monitoring amp Control ON Status No Name Type Address Display Rule 0i cyexy Individual Circuit 00 1 AND Lat LIU No Advanced Control amp Settings 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Address Settings Map3 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Advanced Control Group Settings 2 Select the addresses to control Select the type and address of the addresses to control monitor as a group 3 Select the LIU numbers Select the 4 checkboxes of the corresponding LIU Only LIU numbers selected and registered in LIU Settings can be selected If LIU numbers are unselected in LIU Settings after being selected here settings will remain and the control commands will be sent 4 Select the ON status display rule For ON Status Display Rule Logical AND or Logical OR select the logic to use to determine the status for the global address based on multiple system statuses 5 Click the Submit Button Settings in the window will be registered in the Web Server Un
20. E Ciesla Senan E circ oma d SCSCSC Tnaividuel Cireuit 10 1 SERE E ciroate oe Cid Individual Circuit 10 4 EE circuses 03 2 4 d Taaividusl Circuit 11 2 Ee ee i Monitoring 1 Select the LIU number and click the Select Button 2 Click one of the individual circuits address range buttons 00 1 to 15 4 48 1 to 63 4 The display of addresses is split into 4 windows of 64 addresses each The statuses of the selected addresses are displayed in the Status Fields eR Lore e As shown in the figure ON is indicated in red OFF in green indeterminate No T U or unregistered in gray and details are given in text e g TIMER If the connection from the Web Server Unit to the NCU to the LIU to the Transmission Unit is cut all address statuses will be displayed as indeterminate Statuses of addresses disabled in the LIU Connection Settings will be displayed as indeterminate ii Controls 1 Click the red green button in the Status column 3 individual Circuit Control A dialog box as the one displayed below will open Individual Circuit 00 1 Symbols in indeterminate state cannot be selected wares Symbols cannot be used if a user with monitor rights only is logged in Does not apply to On timer and Off delay timer controls Does not apply to dimmer level controls 2 Click the button for the status to control ett ann The dialog box will close and the status will change Get Level C
21. Groups c Patterns d Zones e Global Addresses 6 Dimmer Settings a Individual Circuits b Groups 7 Status Bar Manager 71 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 1 Monitor amp Control List Settings The light circuit addresses that are used frequently in monitoring and control can be selected and displayed in a List List under Basic Monitoring amp Control can be used to register addresses to be displayed in a list if the user is logged in as the advanced user or administrator address registration cannot be performed if the user is logged in as a basic monitoring user or basic monitoring amp control user Refer to Il Operations on Monitor amp Control List PageT in Monitoring amp Control Section for details Location name Basic Monitoring amp Control gt List Basic itori ii F r 7 7 Basis Mantua a Status Action m mores Ica C w mamono LORE co ee ce Gomori cme rowan LE Tw Ti w Tew Tw Map2 List System Administration Ooo Oo pe Lan ou ooo Action Riese Specifications Address types that can be registered Individual circuits Dimmers Groups Patterns Zones Global Addresses Number of addresses that can be registered 256 max Address types can be mixed Number of addresses displayable in a page 16 max 16 pages Display e No Serial number 001 to 256
22. Ill Map Window Operations P 119 IV Advanced Control P 121 V Error Status Displays P 132 113 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control Basic Operations for Connection Login Follow the steps below to access the Web site through the browser Internet Explorer 1 Enter the address URL of the Server Unit u are about to view pages over a secure connection z o N G S fol lows Any information you exchange with this site cannot be viewed by anyone else on the Web J In the future do not show this warming https AAA 0 denotes the IP address digits of the Server Unit e g if the IP address is 192 168 0 1 enter httos 192 168 0 1 as the URL https is used at the beginning of the URL 2 Proceed to the Security Alert Window Two Security Alert Windows will be displayed because the data is encrypted SSL Click the OK Button in the first window Click the Yes Button in the second window The Start Window Web page will be displayed if connection is established 3 Login start operation Click the image in the Start Window to display the Login Window Log in as a registered user Enter a user name and password that have been set by the administrator in the Authentication page User name U Enter user ID Password P Enter password The Main Frame will be displayed if connection
23. NCU or LIU so manual registration is required by clicking the Submit button in Zone Settings From upload to completion of registration in the Zones Window the Settings inconsistencies message will be displayed Precautions Specific to Special Days The files for the 3 types of special days day of the week day of the month and dates are required at the same time for uploads The range for Special Days is January 1 2000 to December 31 2037 and the day must be within the month of upload plus the following 13 months Consider these restrictions when changing the clock settings and past data Error messages when uploading data files that Contain disconnected LIU numbers Monitor amp Control List Cannot specify unconnected LIU Groups Cannot specify unconnected LIU e Patterns Cannot specify unconnected LIU Zones Cannot specify unconnected LIU Global Addresses Cannot specify unconnected LIU for global address control Schedule Cannot specify unconnected LIU Address Cannot specify unconnected LIU 61 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual System Administration 13 Run Command This function is for manufacturer maintenance so descriptions is not provided WSU gt NCU WSU lt NCU WSU gt NCU WSU lt NCU WSU gt NCU WSU lt NCU 05 10 31 05 10 31 05 10 31 05 10 31 05 10 32 05 10 31
24. OK button in order to submit the new settings Clicking the Cancel button will close the confirmation window without any information being submitted 5 Go to the reboot page After submission of the new settings a Reboot of the Web Server Unit is necessary to enable changes to astronomical clock settings Click the Go to reboot page button and proceed to rebooting the Web Server Unit 99 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings PACIFIC Taris aes enero I uy a he x F s a n fi 3 r ci l i k z ji E p Pi gt z r pi i Me r ale ll F h 5 F i lt i ae a i i w zZ 2 Z i l P EERE T f a pec zz o uy Hil as z Ze 9 4 J fy a Vay eT h WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings Functional Specifications for Schedule Controls i Basic Functions The clock for programs sets the time to perform control commands from the Web Server Unit so circuits on the local system start functions several seconds behind the set time 1 Start and End Time Pairs Start time lt End time Even if the start control was not performed for some reason the end control will still be performed Sunset ON Sunrise OFF Sunset ON OFF ON Sunrise OFF and ON OFF Current day
25. P 19 15 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Product Description I Name and Function of Parts k MA Sz Euk 2 SOSU moana wa CON a ATED CURARE A act gt ma J Reu OATE TIVE ae mise EE 2 ERAD a Birk 5 HE TWOHE PARAR USER z IF ADDARES as S SUBNET MASK ea 7 a ka DEFAULT GATEWAY wi 1 FIXED 8 i eee P ADDRESS i ar i z SUBNET MASK 255 255 0 0 2 et 5 co E TE oo Front view amp Right side view 1 Power Terminals These terminals connect to the transformer WWR2301 811 WR2311 821 series and supply power to the product 2 Ground Terminal This terminal is connected to a ground of 100 2 or less class D grounding based on Internal Wiring Regulations and to ensure the electrical quality of the product 3 LAN modular jack This socket connects to the Ethernet cable plug This port is used for communications with PCs through the Ethernet 4 NCU Connector Male This connector connects to the D sub 9 pin female connector of the RS 232C communications cable This port is used for serial communications with the WR3387 8 series FULL 2WAY Remote Control Network Controller Unit NCU for Switchboards 5 Setting Unit Connector Male This connector is for maintenance purposes only 16 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Product Description 6 St
26. Remote Lighting Control System Network Control Units NCUs WR3387 8 Series Local Interface Units LIUs WR3388 8 Series Transmission Units WRT2050 80 WRT2040 82 WRT2040 81 WRT2040 894 Series Supported Client PC Environment OS Microsoft Windows XP Operating System SP1 or SP1a recommended Browser Microsoft Internet Explorer version 5 5 or later version 6 0 recommended Javaapplet Sun Microsystems Java 2 Platform Standard Edition 1 4 2 J2SE The Web Server Unit WR3330 801 may not function in response to operations from a Microsoft OS earlier than Microsoft Windows XP such as Microsoft Windows 2000 NT Me 98 95 or CE and from portable devices Update the OS and browser before hand to ensure normal functionality WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Safety Precautions Always observe these precautions to prevent injuries or accidents AN WARNING Tighten unit screws firmly Loose screws may cause overheating resulting in burning or fire Applicable tightening torque 0 5 N m to 1 0 N m 5 1 kgf cm to 10 2 kgf cm Donot repair disassemble or modify the product Doing so may cause electric shock fire or malfunction Do not exceed the rated current and voltage Doing so may cause overheating resulting in fire AN CAUTION Donot install the product outdoors or in any location subject to splashes of water Doing so may re
27. Server Unit NCU LIU Transmission Unit Switch gt To lighting fixture Selecting zone number Zone control content acquisition in a browser by Web Server Unit AQ Zone control request to NCU Reloading browser page General purpose PC Monitor amp control configuration Zone settings can be retrieved from the Web Server Unit and NCU Data on the Web Server Unit and that on the NCU must be identical 2 Zone Setting Control Content Content Change 5 lt CP ee eee a 1 Reeve eee eee a a T ee ee ee ee RC232C 0 P i i WR3330 801 WR3387 8 WR3388 8 Web Server Unit NOU LIU ie Transmission Unit Switch To lighting fixture Q Editing zone control in a browser Setting result acquisition by NCU es Setting zone control of NCU Setting zone control of subject LIU PEA lon General purpose PC Monitor 8 Reloading browser page amp control configuration Zone settings are stored in the Web Server Unit NCU and LIU Data displayed on the browser is the data used to synchronize the settings on the Web Server Unit NCU and LIU When replacing the Web Server Unit existing data in the NCU must be read into the browser page and set again to use the data in the NCU to write to the Web Server Unit 12 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Summary 7 Transmission of Settings Files 1 Patterns Gro
28. Settings Data Files 1 Patterns Groups P G Settings Data 2 Other Settings Data 8 Transfer of Map Data from the Drawing Software 1 Manual Control from a Web Browser i WR3387 8 NU WR3330 801 Web Server Unit Transmission Unit Switch j To lighting fixture a 1 Controlling from a browser oO Contact output status D Request to NCU D Circuit address status AU T 3 Request to subject LIU 3 Status acquisition by NCU ern IH ey aa eee SS n m 4 Request to Transmission Unit 4 Status acquisition by Web Server Unit O Request to control T U 65 Reloading browser page General purpose PC Monitor amp control configuration The Java applet running on the Web browser displays a window according to the operation Control requests from multiple Web browsers are stored on the Web Server Unit and executed sequentially If the present status of the circuit is already requested status the control request will still be issued WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Summary 2 Operation Controlled by a Schedule Timer 1 Program Setup Q pny T EEEE WR3330 801 WR3388 8 Web Server Unit NCU f LIU Transmission Unit Switch To lighting fixture Setting schedule control programs from a browser General purpose PC Monitor Confirming schedule control programs from a browser amp control configuration
29. Unit Location name System Administration gt Map Manager 01 Map 1 Network Set 02 Map 2 uthenticati 16 Map 16 933 Clean up delete all files that are not recognized as usable RS 232C Settings 7 for maps E S item No Serial number of maps e Name Name of maps registered in Project Display Settings 1 Select the item to delete Select M the checkboxes of items to delete 2 Click the Delete Button The data for all selected maps will be deleted Supplemental Information Creation of map data requires separate special software Refer to II Creation and Administration of Map Data for details The name for the map data file transferred from the special software is fixed as iiu _screenXX However it is still possible that invalid files file with an invalid file names be saved in the Web Server Unit In that case select 1 the Delete checkbox in the Clean up row at the bottom and click the Delete Button to delete those undesirable files Image files used in maps cannot be deleted because their use may be shared As a result these files can only be deleted in batch from the Factory Settings page Therefore consider the capacity management when using a large amount of image data 604 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 16 Factory Settings Settings data can be initialized or deleted to reset it to factory default settings
30. and time could not be kept e g after a power supply interruption longer than the clock s battery maximum time range When this error occurs it is suggested to verify and reset the date and time settings in the Date amp Time Settings 3 System error occurred Red e Indicates errors in the Web Server Unit or local system This error includes situations when the local system is being set using the patterns groups setting switches Details on the error can be checked in the System Errors Monitor o Systememoroceamed When this error occurs it is suggested to verify the following items FULL 2WAY signal error Pattern Group configuration in process 132 gt WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control 4 Settings inconsistencies Red Indicates normal monitoring and control has been disabled because the LIU Settings or Zone Settings are inconsistent with those of the NCU Consistency of the zone settings is checked on the following occasions When data is read from the NCU for Zone Settings When zone settings are uploaded in Upload Manager When the data is being uploaded this message is displayed regardless of the data on the NCU side When booting with the zone settings verification option enabled in the Zone Settings make sure the settings on the Web Server Unit match those on NCU This can be done in the LIU Connection Settings view or Z
31. be kept e g after a power supply interruption longer than the lock s battery maximum time range OFF NCU connection is normal and the date and time on the Web Server Unit are properly set 4 Integrated LED Indications NCU and LIU 1 The following communications errors can be detected Network error Communications error between the LIU and Transmission Unit Host computer post error Communications error between the Web Server Unit and NCU FULL 2WAY error Signal error between the LIU and Transmission Unit 134 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information I Hardware Specifications P 136 Il Software Specifications P 140 Ill Warranty P 148 IV Prohibited Matters for Safety Reasons P 149 V Precautions and Disclaimers P 150 135 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information Hardware Specifications Ratings Rated voltage Rated frequency Rated current consumption 24 VAC 50 Hz 60 Hz 300 mA Use the WR2301 811 WR2311 821 series Transformer for the power supply Applicable Unit Numbers WR3387 8 series WR3388 8 series WRT2050 80 WRT2040 82 WRT2040 81 WRT2040 894 For USA series 1 Unit One unit per Web Server Unit 1 to 31 Units One Unit per Transmission Unit 8 432 circuits max 31 Transmission U
32. being submitted 3 Go to the reboot page After submission of the new settings a Reboot of the Web Server Unit is necessary to enable changes to astronomical clock settings Click the Go to reboot page button and proceed to rebooting the Web Server Unit ii Specifying the longitude latitude time zone and daylight saving rule manually 1 Specify longitude and latitude From the Location drop down menu select Specify Longitude and Latitude option Proceed to the input of longitude and latitude 98 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 2 Select a time zone Select a time Zone If a daylight saving rule exist for the selected time zone a checkbox labeled Automatically adjust clock for daylight saving changes will be displayed It is possible to ignore the daylight saving rule by unselecting the Automatically adjust clock for daylight saving changes option Note that if a daylight saving rule does not exist for the selected time zone the checkbox will not be displayed 3 Click the submit button A confirmation window showing the specified values will be displayed If the specified values are correct click the OK button in order to submit the new settings Clicking the Cancel button will close the confirmation window without any information being submitted 4 Go to the reboot page After submission of the new sett
33. cannot be loaded In that case wait for a moment and then try to reconnect 6 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration I Creation and Management of Maps Lighting circuit status can be monitored and controlled visually on a map screen For example display and operation are possible on a window displaying a map depicting the physical layout of the facilities In this manual a window specially drawn for a facility is called a map EMIT FULL 2WAY Remote Lighting Control System Microsoft Internet Explorer File Edit View Favorites Tools Help Location Name 0 0 8 222 ee Menu Name Address https 192 168 128 150 contents frame htm v gt Go Links gt Frame napi mame z Main Frame ae ee tatus Bar M Menu Frame System Administration l a a Status Bar amp Local intranet Maps are accessible from Basic Monitoring amp Control but original map data must be registered first and configured or the maps drop down menu itself will not be displayed Map data is created with special drawing software and transferred to the Web Server Unit 1 Drawing Software Sold Separately Users must purchase the following product separately to create and manage map data for lighting control WR3339 801 FULL 2WAY Screen Builder for Web Server Unit Refer to the specifications and the user s manual for operating environment a
34. characters Default gateway The gateway for the network the Web Server Unit connects to Enter XXX XXX XXX XXX XXX Alphanumeric characters 40 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 3 Global network settings If not connecting to the Internet select Do not use global IP address If connecting to the Internet select Use global IP address and enter the IP address IP Address Global IP Fixed address provided by the Internet Provider Ports must be set for the router independently Port 6001 is used for the status displayed using symbols in the Monitor amp Control List and Maps Windows If this port is not supported realtime symbol refreshing is not supported in response to local circuits status changes but they can still be monitored by periodically reloading the Main Frame by selecting Enable automatic reload of basic monitoring amp control pages in the Page Reload Settings Menu 4 Submit button When the submit button is clicked the parameters specified and shown in the window will be submitted to the Web Server Unit as the user defined values 5 Enable the submitted parameters To enable the submitted values reboot the web server unit If the DIP switch pin is set to Default user defined values can be submitted and the web server unit can be rebooted But after rebooting the DIP switch settings will override the defined values Reboot
35. consult the network administrator of the network to which you are connecting 6 Click the OK Button to complete the procedure For Internet connections users need to subscribe to an Internet service provider ISP and obtain a user name and password Depending on the ISP the DNS server address may also be required ISPs may refer to user names and passwords by other names as follows User name Authentication ID Login ID Connection ID Network ID etc Password Authentication password Login password Connection password Network password etc Check with the ISP for details For the network connection speed ADSL or faster is recommended 32 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Installation Section 4 Set the browser on the PC Set the browser Internet Explorer as follows The details below are based on the TCP IP setup window of Microsoft Windows XP 1 Settings for Internet Option Internet Properties Right click the Internet Explorer icon and select Internet Properties Alternately left click Internet Properties and select Tool Internet Options Enable Java Sun A Select the Advanced Tab vane 3 E Us HTTP 1 1 Use HTTP 1 1 through proxy connections Select 1 Use Java 2 v1 4 2_05 for lt applet gt requires restart under Java Sun 2 te Java 2 1 4 2_05 for lt applet gt tequres restart 8 Secunty V Check tot publisher s cert
36. control settings data registered in Group Settings group01 csv to group31 csv Pattern control settings data registered in Pattern Settings patternO1 csv to pattern31 csv Zone control settings data registered in Zone Settings ZONe CSV Global address control settings data registered in Global Address Settings global csv Programs settings data registered in Programs Settings schedule csv Special days settings data registered in Special Days days of the week Special _week csv days of the month Special_day_every csv dates Special_day_once csv Address settings data assigned to maps symbols in Address Settings address csv Individual circuit and dimmer name settings data registered in Individual Circuit Settings 1i name01 csv to i_name31 csv Groups data registered in Groups g name01 csv tog name31 csv Patterns data registered in Patterns p name01 csv to p_name31 csv Patterns data registered in Zones Z name csv Global addresses data registered in Global Addresses gb_ name csv Activity data displayed in Activity yymmddco csv where yy denotes the year mm denotes the month and dd denotes the day System error data displayed in System Errors yymmddal csv where yy denotes the year mm denotes the month and dd denotes the day 58 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manu
37. drawing maps must therefore be connected to the Ethernet meaning that if network configuration of the map drawing PC is necessary it must be completed beforehand Transmission of map data to the Web Server Unit is initiated from the map drawing software but the following preparations must be followed on the Web Server Unit before the transmission Refer to II Network Connection and Configuration Installation in Installation Section for changes to user defined parameters and use with default values 1 Set pin 4 of the DIP switch on the Web Server Unit to 1 In normal operation this pin is set to O 2 Click the Reboot Button When rebooting has been completed the Web Server Unit will be ready to receive data 3 Start the map drawing software and open the map data file already edited compiled 4 Transfer to the Web Server Unit in the Transmit to Server Menu Refer to the user s manual of the drawing software for operating details Data files transferred to the Web Server Unit are not editable and the Web Server Unit does not have a function to transfer them to PCs Therefore original data that can be edited with drawing software had and accessed image files should be backed up by the user 5 Return pin 4 of the DIP switch on the Web Server Unit to 0 When the map data has been transferred set the switch to the normal position If it is not returned to the normal position the communications security level will be low
38. either as normal or as errors depending on the operating methods If a local bus error FULL 2WAY bus error or pattern group configuration in progress error occurs after an NCU connection error the error will not be displayed in the System Error Monitor because local errors cannot be detected under those conditions NCU connection errors are displayed at the time of recovery 52 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 9 Log Settings The history of status changes in response to local control can be recorded as a log for group pattern and zone addresses The logs can be selected deselected by address point 2 ae 2 5 Location System Administration gt Log Settings Location name System Administration gt Log Settings suc j Haze ontong amp Panrra Taataa Con ie Basic Monitoring amp Groups Control Sum ae Advanced Control amp LIUNo 01 y Select yer bait cap isim Nese Seine Astes Nic Semings Pen Bt uian u Pann ti p Pem F System Administration miaa Pent i Pa Network Settings Porn Pane i 4 Pannen 55 Avthentication Submit m me a Date T n Sett g ie mr Pater t a Patten 4 93 Sala rT Pune Patter 42 Eye Min Address Name Select Addres Name tant ah Page Reload Settings 001 Group 001 065 Group 065 onsems Pana Paane Project Display Settings hese _ asii System Ear Monit 002 Group 002 0 066 Group 066 a i Lo
39. error warning will be displayed The user must repeat the data submission after the system returns to normal condition 78 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 5 Pattern Settings Pattern Settings is used to configure pattern control settings for Transmission Units of each system Location name Advanced Control amp Settings gt Pattern Settings LTUNo 01 v Select TE Address Name Action Address Settings 02 Pattem 02 L 03 Pattem 03 Group Settings Pattern Settings 04 Pattem 04 Zone Settings 05 Pattem 05 Schedule Settings Name Settings Te 06 Pattem 06 Status Bar Manager 07 Pattem 07 ram a n pen 1 Select system LIU number Select a LIU No and click the Select Button The registration status of the Transmission Unit will be shown Only LIU numbers that have been registered in LIU Settings can be selected Settings are saved in the Transmission Unit LIUs and NCUs must be connected when these parameters are written These parameters are not stored in the Web Server Unit When the Web Server Unit has booted with local devices and channels in error status registered parameters cannot be obtained and they all will be shown as Add new If the system errors are then corrected the Add new indications will not be refreshed The menu command must to be selected to refresh the page after the system becomes normal A
40. htm x g o Links Frame Frame sic S oring amp List Advanced Control amp Ad s Stings Main Frame a e Lo eB Show room 1 1 Menu Frame ray amp p a Local intranet 2 Menu Configuration Menu Frame The menu that is displayed depends on the authentication rights of the user who logged in 1 Menu for Basic Monitoring Rights 3 Menu for Advanced Control 4 Menu for System amp Settings Rights Administration Rights Basic Monitoring Basic Monitoring amp Control Basic Monitoring amp Control Sel J Map1 Map2 Map2 List List Advanced Control amp Settings Advanced Control amp Settings Address Settings 4 4 Saal Systern Adrninistration Map1 Sear oe Authentication Advanced Control Date amp Time Settings Individual Circuits RS 232C Connection Settings Groups LIU Connection Settings Patterns Page Reload Settings 2 Menu for Basic Monitoring amp Control Rights Zones Project Display Settings Global Addresses System Errors Monitor Basic MIontoring Group Settings Log Settings Pattern Settings Log Viewer 5 Zone Settings Download Manager Global Addresses Setti Upload Manager Mapt w Time Schedule Settings Run Command Programs Monitor Maps Manager Special Days Configuration Data Manager Special Days Calendar Reboot stronomical Clock Individual Circuits Groups Patterns Zones Global Addresses Dimming Level Display Settings 1 Basic
41. is established 4 Proceed to the Java Warning Window Two warning windows and a login window will be displayed before the Main Frame is completely displayed This is related to the use of Java a i Sun Click the Yes Button in the Warning Security Window Enter the user name and password exactly the same as those entered in the Login Window in step 3 in the in the corresponding fields of the Password Needed Networking Window and then click the Yes Button Do not enter a user name or password authentication right aa different from those entered in the Login Window Click the Yes Button in the Warning HTTPS Window The Main Frame will be displayed normally if the connection has been established 5 Logout operation complete Logout by closing the browser window To login with a different authentication right close the browser window first The authentication right at login is retained even after returning to the Start Window until the browser is closed 114 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control Java Authentication Problems It may take a while before the Java Warning Authentication Dialog Box is displayed K If you ignore the Warning Authentication Dialog Box and minimize the browser before the dialog box is displayed the Warning Authentication Dialog Box will remain hidden even after maximizing the browser again
42. not result in group pattern or zone status changes depending on whether the individual circuit address or dimmer address is a part or the entire address contained in the settings Undefined system errors circuit status changes data being lost undetected data etc excluding date amp time out of order errors will not be recorded in the log 53 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual 10 Log Viewer The history log of circuit controls can be viewed for up to seven days a Activity The history log of group pattern or Zone status changes can be viewed in table format The origin of the control action WEB control from web page or schedule is also displayed Ti aneeanenageregenss CeGGGEEG EDGER EaGE b System Errors The history log of system errors can be viewed in table format 54 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 1 Select a date Activity log and System Error log After selecting a date the log content corresponding to that date will be displayed 2 Click the Select Button Activity log and System Error log The page is not automatically refreshed In order to obtain the latest data click the Select Button Also If the date changes during this operation the display will be disabled In that case click the Select button to refresh the window Items Displayed in the Activity Log Pa
43. obtain data from the NCU and compare the data with its own If they do not match an error message Settings inconsistencies will be displayed in the status bar Edit the settings and click the Submit Button The same data will be registered in both devices correcting the integrity problem Also editing LIU Settings will delete zone settings on the Web Server Unit and NCU Settings on the LIU however are not deleted at this stage Therefore if data is manually read from the NCU data on the NCU will be read through the LIU resulting in setting inconsistencies Zone settings stored in LIUs disabled in LIU Settings are not compared If LIUs are enabled in LIU Settings but not physically connected a local bus error system error will occur If this occurs zone settings will be registered in connected LIUs but disconnected LIUs that are enabled will result in errors Either connect the relevant LIUs or modify the LIU connection settings Perform zones configuration verification at boot time Yes No will determine whether comparison is automatically performed or not when booting Boot time includes turning ON the power rebooting and recovery from NCU connection errors No function is provided to perform periodical comparison Therefore if No is selected no mismatch will be detected until reading from the NCU is manually performed from the menu because even if setting data does not match the system keeps on functio
44. only for monitoring 3 Pattern A Pattern B Pattern C 4 Pattern A Pattern B Pattern C Pattern D 6 Pattern A Pattern B Pattern C Pattern D Pattern E Pattern F There also is indeterminate state While the status of a pattern has not been checked the status for the zone is not determined This also can be defined as a state iv Definitions of Status and Comparison The LIU verifies zone status according to the status of the corresponding pattern called pattern A through pattern F in this description Pattern A Corresponding pattern A matches ON Pattern B Corresponding pattern B matches ON Pattern C Corresponding pattern C matches ON or none of corresponding patterns A through F matches OFF Other status If zone status does not match any registered pattern the output will be the same as for pattern C so be careful of interpretation in modes 3 through 6 In mode 2 pattern C is used only for Other status Pattern D Corresponding pattern D matches ON Pattern E Corresponding pattern E matches ON Pattern F Corresponding pattern F matches ON Indeterminate More than one of corresponding patterns A through F is indeterminate Indeterminate status occurs when operational status has not been checked after the status of addresses has just been destroyed such as after booting Blank status of pattern settings results from checking addresses and is different from indeterminate status If a
45. repeated every year 96 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings d Special Days Calendar The Special Days Calendar is used to confirm special day settings and duplication of special days Special al Day 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 2598388 HH EE BREEEBERERBEEE PERE EEEEEREE EEEEEEEEEEEE 32868248383 EREREREREEBEE HHHH i 1 Select the month and year and click the Select Button One month of special days 1 through 30 set in Special Days Settings will be displayed in a table The current day is highlighted Gray Special day set Gray No special day set Orange Day set as next day execution Orange Day set as next day cancellation 9 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings e Astronomical Clock The Astronomical Clock is used to calibrate sunrise sunset and daylight savings time calculations In order to calculate the sunrise and sunset times it is necessary to specify the longitude and latitude Location name Advanced Control amp Settings gt Schedule Settings gt Astronomical Clock Basic Moutudns 4 Control Location NEW YORK New York v Advanced Control amp Latitude N0040 le 47 vi Address Settings i 58 Map1 Longitude W073 vie 58 v TimeZone GMT 05 00 Eastern Standard Time Unit
46. switches 2 Date amp Time out of order The clock became in out of order status and has to be reset in the Date amp Time settings 3 Local bus error Local bus error include broken connections between the NCU and LIU incorrect communications settings between the NCU and LIU mismatch power interruptions of the LIU and incorrect LIU number settings local network address 4 FULL 2WAY signal error FULL 2WAY signal error include disconnected channels short circuited signals Transmission Unit power interruptions and amplifier power interruptions 5 Pattern Group configuration in process The local system are being set into the setting mode Can also indicate errors in the FULL 2WAY remote terminal following a power interruption failure wiring problems or duplicated addresses setting 3 Integrated LED Indications Web Server Unit 1 Power Red ON Power is being supplied OFF Power is not being supplied 2 Ethernet LINK Green ON Ethernet is connected normally OFF Ethernet is not connected normally 3 Ethernet ACT Orange ON Data is being transferred via Ethernet OFF Data is not being transferred via Ethernet 4 NCU Connection Error Date amp Time Out of Order Indicator Red ON NCU connection is abnormal No relations with the clock status Flashing NCU connection is normal but the date and time are out of order Date amp Time Out of Order Status indicates that the date and time could not
47. the Network Connections Window Then select Property 7 4 Select Internet Protocol TCP IP in the General Tab Page oo o under Local Area Connection Properties ee Select Property The Properties Button will be displayed with a ir check mark 1 a gt Network Connections 4 Local Area Connection Properties Internet Protocol TCP IP Properties Favortes Took Advanced Heb yp Seach i Folders EJ General Authentication Advanced General You can get IP settings assigned automatically if your network supports this capability Otherwise you need to ask your network administrator for the appropiate IP settings Connect using v go Type Status B Broadcom NetXtreme 57xx Gigabit Controller LAN or High Speed Internet This connection uses the following items v S Client for Microsoft Networks i 8 File and Printer Sharing for Microsoft Networks v acs Packet Scheduler v Obtain an IP address automatically Use the following IP address IP address lh Local Area Connection LAN cr High Speed Internet Enabled Subnet mask Defauk gateway Use the following ONS serve addresses Preferred ONS server Description Transmission Control Protecol Intemet Protocol The default wide area network protocol that provides communication across diverse interconnected networks Alternate DNS server C Show icon in notification area when connected Advanced Cami 5 Select the General Tab in the Internet P
48. the Web Server Unit 3 Select addresses circuits to control Select the row number for individual circuit and dimmer address circuit for which to perform group control batch ON OFF control Content Exclude or Include for group control Timer Timer control is enabled when included is selected The following values can be applied up to 8 circuits per group On timer for 30 s 1 min 5 min 60 min or 120 min Off delay by 30 s 1 min 5 min or circuits without timers On timer Turns OFF when specified time elapsed after ON control Off delay Stays ON for specified time after OFF control and then turns OFF If Include All or Exclude All Button is clicked all individual circuit and dimmer addresses can be selected with identical parameters Select Group Settings from the Menu Frame to return to address selection page 4 Click the Submit Button Communications to transfer settings data from Web Server Unit to Transmission Units will start and switch to address selection page when communications have been completed Data transfer in progress Please wait will be displayed in the status bar until the editor window opens less than a minute Confirmation and registration from another browser will be disabled while the Transmission Unit is communicating with the Web Server Unit System errors cannot be detected while transmission is in progress If registration setting fails due to system errors an
49. the controls will keep on being performed after operations have been completed 5 Several tens of seconds are required to reflect the results of all local point control in the display windows 6 Duplicated addresses for devices and excessive connections to circuits cannot be detected 7 lf some error occurs during circuit control the aborted control will not resume nor will the whole control be repeated automatically even after error recovery 150 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information 8 Warnings during patterns groups configuration are displayed only while setting on the local system with patterns groups setting switches Of all FULL 2WAY system Patterns Groups settings those that can control circuits during configuration are not subject to warnings during configuration because they do not interfere with controls 9 Settings from a browser are disabled while setting local patterns groups 10 Controls from a browser may be ignored during local dimmer level up down control 11 High volume controls on the local side may delay the execution of new requests such as monitoring and control settings for Transmission Units and system errors 12 Continuous controls on the local side such as wall switches during system booting may be reported as FULL 2WAY signal errors because they congest LIU s checking of FULL 2WAY signals Suspending conti
50. the local lighting control system System diagram Power supply Power supply Power supply Full 2Way Remote Control Rco32c Ra RSS A 1 mms y 3 a 5 nee te ee ss 100 VAG WR3387 8 WR3388 K E WR3330 801 Web Server Unit Network Control Unit Local Interface Unit NCU LIU Coop uam 7 H Transmission Switch Unit Ethernet To lighting fixtures Te Y x i Power supply See EEE General purpose PC Monitor amp control configuration Full 2Way Remote Control x 00 B Local Interface Unit r ib E LIU Transmission Switch Panel computer Unit 4 To lighting fixtures FERE H H _ om C WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Summary The data flow for major functions is described here 1 Manual Control from a Web Browser 2 Operation Controlled by a Schedule Timer 1 Program Setup 2 Program Execution 3 Monitoring of Circuit Status Changes Controlled by the Wall Switches of the Local System 4 Address Settings for Symbols on the Web Browser 5 Patterns Groups P G Settings on the Web Browser 1 P G Number Selection Confirmation of Control Content 2 P G Setting Control Content Content Change 6 Zone Settings on the Web Browser 1 Zone Number Selection Confirmation of Control Content 2 Zone Setting Control Content Content Change 7 Transmission of
51. until the display is refreshed To enable refreshing select Enable Automatic Reload of Basic Monitoring amp Control Pages in the Page Reload Settings If the connection from the Web Server Unit to the NCU to the LIU to the Transmission Unit is cut all address statuses will be displayed as indeterminate Statuses of addresses disabled in the LIU Connection Settings will be displayed as indeterminate ii Controls 1 Click the red green button in the Status Field A dialog box as the ones displayed below will open Symbols in indeterminate state cannot be selected Symbols cannot be used if a user with monitor rights only is logged in er ern Individualoo 2 Dimmero1 Patterno1 Groupoo1 LIU Individual Circuit No 00 2 LIU Dimmer No 01 UU 1 Pattem No 01 UU 1 Group No 001 ON OFF Cancel e Sioned Execute Cancel ON OFF Cancel Java Applet Window ON j OFF Cancel E Applet Window zA Java Applet Window Java Applet Window Zone 02 Zone No 02 Zone No 03 Pattern A Pattern B Cancel Pattern B Pattern C Pattern D Pattern E Pattern F Cancel Global Address 02 Global Address 01 Global Address 02 Global Address No 01 Global Address No 02 OFF Cancel Cancel 2 Click the button for the status to control The dialog box will close and the status will change The status display uses port 6001 If the port is closed the status display will not be changed until the display is refres
52. unused pins to the values indicated on the nameplate Unused Pin 6 of switch 1 OFF Unused Pin 8 of switch 1 ON Unused Pin 2 of switch 2 OFF 6 Press the Reboot Button switch 3 When all settings have been completed always cycle the power or press the Reboot Button to enable the changed settings c Settings for FULL 2WAY Remote Control System Terminals Address settings for T Us and terminal switches installed in switchboards or on walls must be completed using the DIP switches on the terminals or through the light address configurator Addresses for these terminals cannot be set from the Web Server Unit It is possible to set the patterns and groups control content of Transmission Units using Pattern and Group Configurators if required For details refer to FULL 2WAY Remote Control catalogs and technical manuals 2 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Installation Section d DIP Switch Settings for the Web Server Unit Set the DIP switches on the front of the Unit as follows 1 Select the network settings Select the pre registered network settings IP address subnet mask default gateway and host name The Web Server Unit has two types of network settings fixed default settings and user defined user settings Select either type Network setting switch default user Pin 1 1 0 i Default Settings The network is connected to using the fixed conditions indicat
53. using the drawing software before map data is transmitted to the Web Server Unit Adress sting totes ees 2 Select the address type generic circuit symbols wp Zone circuit symbols are always set to Zone seri EA g cence 3 Select the LIU number for the system excluding global Java pet Winden addresses and zones 4 Select an address number E ee 5 Click the Submit Button Se Hees nomen The changes will be applied to the map odiy Delete Cancel E m Cancel ii Change the address parameters 1 Select a symbol icon A dialog box will be displayed showing the current values 2 Click the Modify Button The Address Setting Dialog Box will be displayed The remaining procedure is the same as for registering a new address 3 Select the address type generic circuit symbols Zone circuit symbols are always set to Zone 4 Select LIU number for the system excluding global addresses and zones 5 Select an address number 6 Click the Submit Button The changes will be applied to the map 75 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 3 Advanced Control Advanced Control can be used to monitor and control the circuit status of all addresses in a table list This menu is available to a user logged in as the advanced user or administrator only There are no parameters to set on this page Refer to Monitor amp Co
54. when the status changes due to local switch operations at registered addresses WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Summary 4 Address Settings for Symbols on the Web Browser i WR3330 801 WR3387 8 WR3388 8 Web Server Unit NCU LIU os 1 E Transmission Unit Switch a y 7 D Setting addresses and names in a browser Assignment of address numbers to icons only Assignment of addresses to terminals on the Full 2Way signal See EE must be performed separately le oO Confirming addresses and names in a browser To lighting fixture General purpose PC Monitor amp control configuration Address settings on the Web browser are only for the symbols buttons for monitoring and control located on the maps Therefore address settings for switches and devices such as the T U on the local system must be performed separately The mapping data between symbols on the window and addresses of FULL 2WAY Remote Control circuits is stored in the Web Server Unit 10 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Summary 5 Patterns Groups P G Settings on the Web Browser 1 P G Number Selection Confirmation of Control Content Q 2 m oo z i Reze A li WR3330 801 WR3387 8 WR3388 8 Web Server Unit NCU LIU TranemiesioniUnit Switch gt To lighti
55. 0 65mm to 1 6mm dia 1P Power Source SSS Ground Communication Cable Shielded CPEV S 1 2mm dia 1P LAN Cable el cati Tr o Cat 5 E 6 Twisted pair communication Straight or Cross RS 232C Cross Cable D sub 9 pin female inch screws FULL 2WAY D sub 25 pin male Signal Lines mil screws Network Control Unit NCU Local Bus Lines Ground Local Interface Transmission LIU To next LIU To FULL 2WAY T Us and Switches a Connections between the Web Server Unit and Network Ethernet Devices Requires LAN cables with modular plugs The Ethernet communications port is always used as an MDI type port and requires a straight cable when connected to normal ports MDI X type of hubs and routers Across cable can be used for connections to MDI type ports or ports that can be configured as MDI Use a cross cable when directly connecting to a PC MDI type b Connections between the Web Server Unit and the Network Control Unit NCU Always use the WR338 7 8 series Network Control Unit An RS 232C serial communications cable is required The connectors at the ends of the cable are a D sub 9 pin female and a D sub 25 pin male and are cross linked Connect the connector labeled NCU RS232C on the Web Server Unit to the connector labeled Host RS232C on the NCU Do not connect anything to the connectors labeled Setting Unit RS 232C
56. 2WAY Web Server Unit Panel Use English User s Manual system Administration This section provides information on the system administration functionalities of the system I System Administration Settings P 39 Il Creation and Management of Maps P 68 38 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration I System Administration Settings The following administrative functionalities are supported when logged in with the system administration rights These functions can be selected in System Administration Menu 1 Network Settings 2 Authentication 3 Date amp Time Settings 4 RS 232C Settings 5 LIU Connection Settings 6 Page Reload Settings 7 Project Display Settings 8 System Errors Monitor 9 Log Settings a Groups b Patterns c Zones 10 Log Viewer a Activity b System Errors 11 Download Manager 12 Upolad Manager 13 Run command 14 Data Monitor 15 Map Manager 16 Factory Settings 17 Reboot 39 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 1 Network Settings Specify Ethernet communications settings e g IP address in the Network Settings Window Host Name iiu 32 characters or less MAC Address 00 CO SF 7F D0 3B Fixed Nokes Settines Local Network Settings Authentication Date amp Time Settings Obtain an IP address automatically RS 2
57. 2WAY Web Server Unit Panel Use English User s Manual Installation Section 5 Logout operation complete Logout by closing the browser window To login with a different authentication rights close the browser window first The authentication rights at login are retained even after returning to the Start Window until the browser is closed Java Authentication Problems It may take a while before the Java Warning Authentication Dialog Box is displayed If you ignore the Warning Authentication Dialog Box and minimize the browser before the dialog box is displayed the Warning Authentication Dialog Box will remain hidden even after maximizing the browser again preventing the user from operating the browser In this situation press the ALT Tab keys simultaneously to display the Windows task switcher view Select the Java icon in the tag switcher view by pressing the ALT Tab keys This will bring back the Java warning authentication dialog box From there proceed as Ks described above If the user name or password that had been entered at login is not entered correctly three times in succession or if the Cancel Button is clicked the Authentication Required Window will be displayed In this situation the browser must be closed and then reopened Java applets and the browser run on the client computer so if the computer does not have sufficient resources they may not function properly 3 WR3330 801 FULL
58. 32C Settings Use the following IP address J Set LIU saiia IP Address 192 168 128 150 Project Display Settings System Error Monitor Subnet Mask 255 255 255 0 Log Settings Log Viewer Default Gateway Download Manager Upload Manager Global Network Settings Run Command Dala Mion Do not use global IP address F tory Setti O Use global IP address Reboot IP Address Rese To enable changes please reboot Go to Reboot Page 1 Basic settings Host Name Identification name for the Web Server Unit 32 characters or less excluding hyphens and underscores _ The host name becomes valid when the browser is reopened or the page is reloaded after rebooting the Web Server Unit The host name denotes a machine identification text string on a network and is used in a network environment with DNS The MAC address denotes the physical address of the Web Server Unit 2 Local network settings If the IP address is to be obtained dynamically select Obtain an IP address automatically If the IP address is to be specified directly select Use the following IP address and enter the following IP Address IP address to be assigned to the Web Server Enter XXX XXX XXX XXX XXX Alphanumeric characters Enter a global address if the IP unnumbered functionality is used by the router Subnet mask The subnet mask for the network the Web Server Unit connects to Enter XXX XXX XXX XXX XXX Alphanumeric
59. 4 wii 2 3 4 Group Setting r m 3 TOR e 2 Zone 02 1 b 2 j 12 J 5 J Zone Settings i l Global Address Settings 3 Zone 03 1 Vie mo 15 20 i21 22 23 Schedule Settings Name Settings 4 Zone 04 Select LIU v Dimmer Settings Status Bar Manager 5 Zone 05 Select LIU System Administration 6 Zone 06 Select LIU Fi Zone 07 Select UU v 8 Zone 08 Select U v 9 Zone 09 Select LIU v 10 Zone 10 Select LIU 11 Zone 11 Select LIU 12 Zone 12 Select LIU 13 Zone 13 Select LIU v 14 Zone 14 Select LIU 15 Zone 15 Select LU v 1 Select the Unit Retrieve the original data to edit on the browser by selecting Web Server Unit NCU Click the Select button to start retrieval When this page is selected from the menu data on the Web Server Unit will be automatically read and displayed Registered data will be saved in the Web Server Unit NCU and LIU Therefore when this process is in progress LIU and NCU must be physically connected 2 Select the LIU number Select the LIU No of the zone addresses up to 96 to work on Only LIU numbers that have been registered in LIU connection settings can be selected Select Select L U for zone addresses not to work on 3 Select the mode Select the number of states mode to assign patterns to one zone Six is the maximum number of states Mode 2 ON OFF 3 ON OFF Pattern 1 4 ON OFF Pattern 1 Pattern 2 6 ON OFF Pattern 1 Pattern 2 Pattern 3 Patter
60. 6 26 Special Day 26 07 Special Day 07 17 Special Day 17 n Special Day 27 07 Special Day 07 17 Special Day 17 7 Special Day 27 0g Special Day 08 12 Special Day 18 8 Special Day 28 08 Special Day 08 13 Special Day 18 23 Special Day 28 09 Special Day 09 19 Special Day 19 20 Special Day 29 09 Special Day 09 19 Special Day 19 29 Special Day 29 10 Special Day 10 Special Day 20 30 Special Day 30 10 Special Day 10 20 Special Day 20 30 Special Day 30 C Pattern Repetition Execution Example one Execute Sunset Example petition Execution Exampl D Zone Execute Sunset Exampl No Name LIU No Type Address Operation No Name LIU No Type Address Status Operation 001 Program 001 01 Patten 01 Repeat Execution 001 Program 001 E Zone 1 Pattern A Execute Sunset Start Time End Time Repeat Interval Start Time 00 xio ai 00 xio 00 v105 w At Sunset 59 v 16 29 Day Day Ho td a o w b Sa Mo Te We Th Fr Se a a a a C a CJ o o o o o o o Coot case ai 3 eon i 2 omen a Cot Special Day 01 1 Special Day 11 a Special Day 21 02 SPD 02 12 SPa Dey ia 2 special Dey 22 02 Special Day 02 12 Special Day 12 n Special Day 22 03 ett AY 13 sone a B Poets 03 Special Day 03 13 Special Day 13 B Special Day 23 04 ESS 14 POSSESS 24 ne 04 Special Day 04 14 Special Day 14 24 Special Day 24 05 seen at 15 Toket 25 rahti 05 Special Day 05 15 Special Day 15 25 Special Day 25 06 cient ten A 16 See ST 2 pees 06 Special Day 06 16 Special Day 16 Special Day 26 07 S 17 A 2 we EY 07 Special Day 07
61. 60 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Installation Section b DIP switch settings for the Local Interface Units LIU Set the DIP switches on the Unit as follows For details on DIP switch pin number assignments refer to the LIU product specifications 1 Set the local network address LIU address Assign addresses between 1 and 31 set a unique address for each interconnected LIU Addresses 1 to 31 Pins 1 to 5 of switch 1 10000 to 11111 Do not set address 00000 2 Set the baud rate on the local network m Set to 19 200 bps and Pin 7 of switch 1 ON aa 2 3 Set the terminating resistance d z 3 3 Set the terminating resistance to ON for the LIU at the end of the network t a E Terminating resistance ON OFF Pin 1 of switch 2 ON OFF B 5 If the LIU is not physically terminating the network always set to OFF 4 Set the status change notification for patterns groups and zones a Set the corresponding DIP switch to ON 1 if notifications are necessary a All status pins are set to ON in the example kn 5 Pattern status change notification Yes No Pin 3 of switch 2 ON OFF as E Group status change notification Yes No Pin 4 of switch 2 ON OFF 2 Zone status change notification Yes No Pin 5 of switch 2 ON OFF Status change notification DIP switches on the NCU must be set to the same values 5 Set unused pins Always set
62. English User s Manual Advanced Control amp Settings ii Enabling Disabling Programs 1 Select Enable Disable Programs can be disabled Disable Preset controls of programs will not be performed However the program will not be deleted Enable Preset controls of programs will be performed When newly registered programs are enabled by default If Select All Button is clicked all programs 930 in all will be enabled or disabled When the day changes enabled disabled status will be preserved 2 Click the Submit Button The entered data will be submitted and registered ili Registering and Deleting Programs Programs cannot be set if the date and time have not been set Set the correct date and time in Date amp Time Settings 1 Select the programs Click the Add new or Edit Button for the line number up to 930 The page will switch to the Address Selection Page Basic settings Basle settings No 2 Enter the program name coim The program name must be 16 characters or less Characters that are not iso 8859 1 CP932 will be corrupted 3 Select the LIU No for the system excluding zones and global addresses Select an individual circuit dimmer group or pattern LIU numbers selected and registered in LIU Connection Settings can be selected If LIU numbers are deselected in LIU Connection Settings program settings will remain so programs must be set again if LIU numbers selected for a program
63. Ill Software Specifications PC Client Requirements Applicable OS Applicable Web browser Applicable Java applet LAN port Input devices Memory Graphic display Microsoft Windows XP Operating System required SP1 or SP1a recommended Microsoft Internet Explorer version 5 5 or later required Version 6 0 recommended Sun Microsystems Java 2 Platform Standard Edition version 1 4 2 J2SE required Modular socket for Ethernet connection required Mouse and keyboard required 128 MB min recommended 1024 x 768 dots XGA 256 colors min recommended Monitoring and Control of Lighting Circuits 1 Number of Control Points Individual Circuits Dimmers Groups Patterns Zones Global Addresses 2 Monitored Status Individual Circuits Dimmers Groups Patterns Zones Global Addresses 7 936 circuits max in total 256 circuits max per Transmission Unit 496 circuits max in total 16 circuits max per Transmission Unit 3 937 circuits max in total 127 circuits max per Transmission Unit 2 232 circuits max in total 72 circuits max per Transmission Unit 96 zones max in total 36 max with mode 2 24 max with mode 3 18 max with mode 4 and 12 max with mode 6 per Transmission Unit 32 max ON OFF Timed No T U and Dimmer level ON OFF Timed No T U and Dimmer level ON OFF Not set and Dimmer level ON match OFF
64. Operating from wall switch 0 Contact output status Request to Transmission Unit 2 Circuit address status AO Request to control T U Status acquisition by NCU Status acquisition by Web Server Unit Reloading browser page To lighting fixture ii Status and Processing Definitions The status of global addresses is determined using logical ANDs and ORs of the statuses of the addresses 1 and 0 are used in logical operations and correspond to the status of the address as follows e 1 ON match and timing 0 OFF mismatch no T U No setup Unregistered Control failure Error response invalid Abnormal ON and Abnormal OFF Response of unknown status indeterminate lf the result of AND and OR operations is 1 ON is applied if 0 OFF is applied AND operation Logical product is 0 if one or more statuses are 0 Logical product is 1 only if all statuses are 1 OR operation Logical sum is 1 if one or more statuses are 1 Logical sum is 0 if all statuses are 0 Global status can be only either ON or OFF Example The following example is for a global control registered for individual circuit 00 1 of systems LIU 1 to L 4 By normal monitoring after global control the following data was obtained LIU 1 Individual circuit 00 1 ON 1 LIU 2 Individual circuit 00 1 OFF 0 LIU 3 Individual circuit 00 1 Indeterminate assumed OFF 0 LIU 4 Individual circuit 00 1 Timin
65. Pattern address 001 to 072 in ascending order Type individual circuits or D dimmers Address 00_1 to 63 4 individual circuits or 1 to 16 dimmers Status 1 ON or 0 OFF Timer O no timer 1 On timer for 30 s 2 On timer for 1 min 3 On timer for 5 min 4 On timer for 60 min 5 On timer for 120 min 1 Off delay by 30 s 2 Off delay by 1 min 3 Off delay by 5 min Dimmer level 1 to 128 ON state or 0 OFF state Fade 0 Instant 1 3 s 2 6 s 3 1 min If different fade values are specified in patterns when uploading the value in the last line will be used This applies to pattern addresses subject to downloads and uploads 155 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Miscellaneous Information e Zones File Name zone csv j confirmati Boost setting confirmation a 1 to 96 Zone address 01 to 96 Setting confirmed at boot 1 Executed or 0 Not executed Zone addresses 1 to 96 in ascending order LIU number 1 to 31 1 for global address ON to Pattern 4 1 to 72 Pattern number LIU number Pattern A Pattern B Pattern C Pattern D Pattern E and Pattern F are zeros for unused zone addresses e Global Addresses File Name global csv 01 to 32 Global address 1 to 32 in ascending order Type individual circuits D dimmers G groups or P patterns Address 00_1 to 63 _4 individ
66. Please store this document in a safe place Panasonic FULL 2WAY Web Server Unit Panel Use English WR3330 801 Users Manual 1st edition Thank you for purchasing the product Please read this manual thoroughly before using the product Please store this manual in a safe place for further reference WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Introduction Thank you for purchasing the WR3330 801 FULL 2WAY Web Server Unit Panel Use This document is the user s manual and installation manual for the Web Server Unit The Web Server Unit enables network connectivity to the FULL 2WAY Remote Lighting Control System functionalities Intended Audience This document is intended for the following users Users who install and configure the product or a system containing the product personnel in charge of indoor wiring and network administration Users who operate and maintain or configure the product or a system containing the product personnel in charge of server administration and lighting control system management Users who control lighting circuits using the product or a system containing the product general users WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Copyright 2006 Matsushita Electric Works Ltd All rights reserved This document cannot be copied or duplicated either in part or whole without the prior written permission of Mats
67. R3330 801 WR3387 8 Web Server Unit NCU y Creating Maps using specialized Map Drawing Software WR3339 To liahtna fixture After creating original data it is compiled to generate HTML data gang _ and other data Transferring maps e g HTML data Data in the Web Server Unit cannot be transferred to a PC and can not be converted back to editable data so be sure to save Personal computer runningMaps i Drawing Software forcustomized the original editable data map editing and management The customized maps displayed on the Web browser are created in a specialized Map Drawing Software The map data can be sent to the Web Server Unit using FTP from the PC running the Drawing Software via Ethernet Data formats on the Screen Builder e g HAD are different from those generated compiled for display on the Web browser e g HTML The data in formats to be displayed on the Web browser only are stored in the Web Server Unit Because the data cannot be converted back to editable state it is recommended to keep a backup of the original editable data e g HAD Refer to the Screen Builder for Web Server Unit WR3339 801 user s manual for further details 14 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Product Description This section describes the external appearance and other aspects of the product I Name and Function of Parts P 16 Il Page Layout
68. SL oe Click the OK Button in the first window Click the Yes Button in the second window The Start Window Web page will be displayed if connection is established Information you exchange with this site cannot be viewed or changed by others However there is a problem with the site s security certificate ti issued by a company you have o determine whether 3 Login start operation Click the image in the Start Window to display the Login Window Login with the system administration rights The following parameters are set for login as the factory settings xm 2108 User name U admin e Password P admin The Main Frame will be displayed if connection is established 4 Proceed to the Java Warning Window Two warning windows and a login window will be displayed before the Main Frame is completely displayed This is related to the use of Java Sun Click the Yes Button in the Warning Security Window Enter the user name and password exactly the same as those entered in the Login a Window in step 3 in the corresponding fields of the Password Needed Networking Window and then click the Yes Button Do not enter a user name or password authentication right different from those entered in the Login Window Click the Yes Button in the Warning HTTPS Window The Main Frame will be displayed normally if the connection has been established 36 WR3330 801 FULL
69. Settings e Global Addresses Global Addresses is used to set names for all global addresses by LIU system Submit Bo ccvaradaesso TB covas O TG covetadcesss TH ctosetadcressoe TG covatadaresss TH covaraccessos TW cosetadcess7 TW cosaracaessos T cosatadaessos TW covataccess0 O Tit Giovaraooressn BE ccvaradaess2 E cosaadaesss O O i fcoseradcess OO OOO OOOO The currently registered data will be displayed 1 Enter names Number of characters 32 characters or less Characters not included in iso 8859 1 CP932 will be corrupted If a comma is entered an error message will be displayed after the Submit Button is clicked Some names such as 32 characters long ones may be displayed with both ends truncated 2 Click the Submit Button The settings will be applied to the page Factory Settings Name Global XX XX 01 to 32 109 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 10 Dimming Level Display Settings Dimming Level Display Settings is used to set parameters to obtain dimming levels for individual circuits and for individual circuit addresses that are dimming devices in group settings For dimmer addresses dimmer 1 through 16 data is always obtained a Individual Circuits Location name Advanced Contro
70. Settings page Data will be initialized Special Days Special days settings data registered in Special Days page All Special Days Settings will be deleted in one batch operation Astronomical Clock Settings Location longitude latitude time Zone and daylight savings settings data registered in Astronomical Clock page Data will be initialized Names Settings Names Settings data registered in Names Settings page All Names Settings data will be initialized in one batch operation Network Settings Network Settings data registered in Network Settings page Date will be initialized 605 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration Authentication RS 232C Connection Settings LIU Settings also covers zone settings Page Reload Settings Project Display Settings Log Settings Activity Log Today Activity Log Past System Error Log Today System Error Log Past Temporary download files pattern and group settings How to initialized deleted items 1 Select data to be initialized deleted Select the checkbox M for the data 2 Click the Submit Button 3 Move to the Reboot Page and click the Reboot Button Click the Go to Reboot Page Button or select Reboot from the menu bar If you continue operations without rebooting unexpected operations may occur so be sure to reboot Authentication settings data registered in Au
71. Submit Button is clicked Some names such as 32 characters long ones may be displayed with both ends truncated 3 Click the Submit Button The settings will be applied to the page Factory Settings Name Group XXX XXX 00 1 to 127 106 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings c Patterns Patterns is used to set names for all patterns by LIU system Location name Basic Monitoring amp Advanced Control amp Settings gt Name Settings gt Patterns oe LUNe 01 v Advanced Control amp Address Settings Address Name Address Name Advanced Control 0l Pattern 01 37 Patten 37 Group Settings Pattern Settings 02 Pattern 02 38 Pattern 38 Zone Settings Global Address Settings 03 Pattern 03 39 Pattern 39 Name Settings 04 Pattern 04 40 Pattern 40 Individual Circuits Groups 05 Pattern 05 41 Pattern 41 Patterns Zones 06 Pattern 06 42 Pattern 42 Global Addresses Dimmer Settings 07 Pattern 07 43 Pattern 43 Status Bar Manager 0 Pattern 08 H Pattern 44 tem Administrati 09 Pattern 09 45 Pattern 45 10 Pattern 10 46 Pattern 46 11 Pattern 11 47 Pattern 47 1 Select the LIU No for the system and click the Select Button The currently registered data will be displayed All 31 systems can be set regardless of the status of the LIU connections 2 Enter the names Number of characters 32 characters or less Characters not inc
72. TCH in green and indeterminate No T U or unregistered in gray If the connection from the Web Server Unit to the NCU to the LIU to the Transmission Unit is cut all address statuses will be displayed as indeterminate Statuses of addresses disabled in the LIU Connection Settings will be displayed as indeterminate ii Controls 1 Click the red green button in the Status column A dialog box as the one displayed below will open a Symbols in indeterminate state cannot be selected Execute Cancel 2 Click the Execute Button The dialog box will close and the status will change Z Pattern control 1238 gt WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control 4 Advanced Control Zones Zone Addresses Points 01 to 96 Location name Advanced Control amp Settings gt Advanced Control Basic Monitoring amp Control Advanced Control amp Settings Address Settings Mapl Advanced Control Individual Circuits Global Addresses Group Settings Pattern Settings Zone Settings Global Address Settings Schedule Settings Dimmer Settings Individual Circuits Groups Status Bar Manager System Administration i Monitoring All 96 zone addresses are displayed in one window The statuses of the selected addresses are displayed in the Status Fields As shown in the figure ON is indicated in red OFF in green indet
73. Zone Controls i Concept of Zones Select LIU for all zone addresses Zones are a method of monitoring and control in terms of preset lighting patterns which considers the state a certain zone area must be in respect to the state it currently is in The states defined here correspond to pattern controls i e zones are controlled areas to which associated patterns are applied If only one state is defined it is identical to pattern control but zone control is characterized where one address can define multiple states That is it functions analogous to pattern control switching integrated into one pattern Lighting Status of Lighting Control Area Pattern Pattern A Pattern C For monitoring only Pattern D ae ii Requirements for Patterns Principles The areas of all associated patterns must be the same as the areas of the zone One zone must consist of pattern addresses for the same Transmission Unit system Each pattern address must have a unique pattern setting The pattern settings must match the name indicating the zone ON or OFF 83 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings ili Modes and States The number of states defined for a zone can be selected from 2 3 4 and 6 and is called a mode A different mode can be selected for each zone address Number of zone addresses 96 Mode 2 Pattern A Pattern B Pattern C
74. Zone operation results in matches ON for more than one pattern such as redundant pattern contents one pattern including part of another or indicating other area Zone matching will return various statuses including indeterminate Therefore take extra care when setting pattern controls associated with zone status as the basis for operation Comparisons of zones that include blank pattern numbers will be compared excluding blank patterns or set to pattern C Zone comparison is performed by comparing pattern status so if all pattern status included in the zone change in sync with local controls pattern C may be returned while the pattern statuses are being checked one by one 84 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 7 Global Address Settings Global Address Settings is used to configure global controls Refer to Global Address Settings for details on global address settings Locati m Advanced Control amp Settings gt Global Address Settings Basic Monitonng amp Control No Name Action Advanced Control amp 01 Global Address 01 Adonis Siap 02 Global Address 02 Mapil Select 03 Global Address 03 os Global Address 04 Advanced Control rio ee os Global Address 05 j 5 Soaps ee 06 Global Address 06 Schedule Settings Name Settings 07 Global Address 07 Add New Dimmer Settings _ Status Bar Manager os Global
75. a m 8 Reboot Switch This switch is used for example to enable changes made to network settings using the DIP switch Power is turned ON or the Unit is rebooted 17 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Product Description 9 User defined Network Value Fields These fields are used to record the user defined network values for the following parameters which are enabled for the Web Server Unit when it is restarted with pin 1 of the DIP switch set to user settings 0 P address Subnet mask e Default gateway USER Hostname IP ADDRESS 10 Default Network Settings Record ee Default network values which are enabled for the Web Server Unit SUBNET MASK when it is restarted with pin 1 of the DIP switch set to default settings Pra 1 are printed here When the default network settings are used DEFAULT GATEWAY the default gateway and host name are None R e P address 192 168 0 1 Subnet mask 255 255 0 0 HOST NAME FIXED IP ADDRESS 192 168 0 1 SUBNET MASK eA Us OU 18 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Product Description Il Page Layout 1 Frame Layout 4 EMIT FULL 2WAY Remote Lighting Control System Microsoft Internet Explorer E File Edit View Favorites Tools Help a Location Name nA Mn at Re lA i Menu Name Address https 192 168 128 150 contents frame
76. al system Administration i How to download a file Excluding Groups and Patterns 1 Select the type of data file When a button for a file type is selected in the upper ae ea Eo frame the file names will be displayed in the lower lt a Sa See Sa eed frame 2 Click on the file name eee The File Download Dialog Box will be displayed assar Se coma separated Vaise 3 Click the Save Button in the File Download Dialog Box e dort a The Save As Dialog Box will be displayed So 4 Enter the file destination and name in the Save in ea and File name fields and click the Save Button mm e When Zones data is downloaded data currently stored on the Web Server Unit is converted into a file Therefore downloaded data indicated by the message Settings inconsistencies is different from that on the NCU Monitor amp Control Lisf Group E Patt fi Zone Global Addresses _ ii How to download a file Groups and Patterns Soe mie m E SSS Data for groups and patterns is not stored on the Web Server Unit Therefore it must be retrieved from O OOO OE ce Transmission Units Eeg When groups and patterns data is downloaded sare NESAS communications with the Transmission Units occur during operation O a ne r Therefore LIU connection settings must be enabled and Transmission S Se Units must be connected coe 1 Click the Group or Patter
77. anced control functions can be used to monitor and control the lighting patterns of all the addresses of circuits in a table This function can be used if logged in with Advanced Control and Settings or System Administration rights Windows display each address type function as follows 1 Individuals Circuits amp Displays all 256 individual circuits and 16 dimmers addresses per LIU unit Dimmers 64 individual circuits addresses x 4 windows 16 addresses per window 16 dimmers addresses x 1 window 2 Groups Displays all 127 group addresses per LIU unit 64 addresses x 2 windows 3 Patterns Displays all 72 pattern addresses per LIU unit 36 addresses x 2 windows 4 Zones Displays all 96 zone point addresses 96 addresses x 1 window 5 Global Addresses Displays all 32 global point addresses 32 addresses x 1 window SLIS WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control 1 Advanced Control Individual Circuits and Dimmers a Individual Addresses 00 1 to 63 4 Location name Advanced Control amp Settings gt Advanced Control A Basic Monitoring amp Individual Circuit 11 3 v es r an 4 Pa dinei Bret Ri mente AN gt lt gt Control 00 1t015 4 16 1t0314 32 1t0474 48 1t063 4 Dimmers01to 16 iNo 01 v Select v Advanced Control amp Tyree EO Individual Circuits Map1 doo siea e E 05 3
78. ancel Individualoo 1 Individual Circuit 00 1 Java Applet Window ili Viewing the dimmer level The dimmer level can be verified manually for each address Only addresses whose level display has been enabled in the Dimmer Settings can be verified 1 Click the Get Level Button in the Dimmer Level Dialog Box A dialog box as the one displayed below will open SRS WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control 2 Click the Get Level Button The dialog box will close Individual Circuit 00 1 3 Wait for a while Inamduai Creu 00 4 Click the Get Level Button in the Dimmer Level Dialog Box A dialog box will open with the dimmer level being displayed Dimmer Level Value Table Control Type ON Brightest Least Bright OFF Retrieving dimmer level Cancel Individual Circuit 00 1 Individual Circuit 00 1 Dimmer Levek 001 Individual Circuit Displaying the dimmer level for individual addresses requires the dimmer T U for the address lf the address is to a relay control T U the level is displayed as 000 If the dialog box is closed by clicking the Cancel Button while the dimmer level is being retrieved start again from step 3 5 Click the Cancel Button The dialog box will close lf any button is clicked after the level has been displayed the value will be discarded The value will be retained if the dialog box is clos
79. and Administering Maps for details on map data ii When Monitor amp Control List is Selected The Monitor amp Control List will be displayed to the user after login Please refer to I Monitor amp Control List for details on the Monitor amp Control List 2 Enter the Project Name and Map Names Project Name Text displayed in the Project Name Frame Upper left corner of the window Map Name Names for maps 01 to 99 Entries must be 32 alpha numerical characters long or less Invalid characters entry will cause an error message to be displayed after the Submit Button is clicked Long text strings such as a 32 characters long may be displayed with both ends truncated 3 Select the maps to display The display of maps in the map list pull down menu in the Menu Frame can be enabled by selecting 4 the check boxes in the Enable Display column Maps can be disabled by unselecting the check boxes Maps can be disabled even if the corresponding map data has been transferred and remains on Web Server Unit 50 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration Supplemental Information In order to complete enabling of map display the web server unit must be rebooted after clicking the Submit button If none of the maps are enabled maps pull down list will not be displayed in the Menu Frame When map data has not been transferred to the web server unit
80. ar Month Week Day 1 of Week 6 Select the month and day Select M the days to be set in the special day zg setting 7 Click the Add Button Added days will be displayed in the lower pane ity Selected days can be deleted by selecting them and clicking the Delete Button 8 Repeat 6 through 7 Data has not yet been registered in the Web Server Unit 9 Return to 4 for other setting methods B Days of the Month 6 Select a month and a day 7 Click the Add Button Added days will be displayed in the lower pane Selected days can be deleted by selecting them and clicking the Delete Button 8 Repeat 6 through 7 Data has not yet been registered in the Web Server Unit 9 Return to 4 for other setting methods C Dates OCON na ans Domteang A Consol Advanced Control amp Sctomig Address Settings Advanced Cacar Baom Settings Zine Seegi Gien Ad csas Settings Schedule iungi Special Dasa Special Days Calendar Naot Step Dunant Seting Status thar Manages System Adnmutabon Advanced Control amp Settings gt Schedule Settings gt Special Days Advanced Control amp Settings gt Schedule Settings gt Special Days Special Day Serting Ne Name Special Day 03 Days ef the Month lt a 6 Select the month and year Selectable range for special days is January 1 2000 through December 31 2037 and it must be within 13 months of the current month If it were 2037 now 2038 could
81. are deleted 4 Select the type 5 Select the address Unregistered not set addresses can also be selected and control request will be submitted 6 Select the status for zones only With a zone status is selected from ON OFF Pattern 1 Pattern 2 Pattern 3 and Pattern 4 7 Select the operating method Select the method and controlled status for timed control sunrise sunset control inter day control or repetitive control There are two methods that can be selected depending on address type to control 89 WR3330 801 Advanced Control amp Settings FULL 2WAY Web Server Unit Panel Use English User s Manual A Individual Circuits Dimmers Groups and Global Addresses Patterns are excluded from Global Addresses Sunset ON Sunrise OFF ON operation at Sunset and OFF operation at Sunrise Sunset ON OFF ON operation at Sunset and OFF operation at End Time J ON Sunrise OFF ON operation at Start Time and OFF operation at Sunrise e ON OFF ON operation at Start Time and OFF operation at End Time OFF ON OFF operation at Start Time and ON operation at End Time ON ON ON operation at Start Time and ON operation at End Time OFF OFF OFF operation at Start Time and OFF operation at End Time e ON ON operation at Start Time OFF OFF operation at Start Time B Patterns Zones and Global Addresses Patterns Only for Global Addresses ON run Execute operation at Start Time o Sun
82. ation IV Prohibited Matters for Safety Reasons We will not be responsible for problems resulting from applications not satisfying the following conditions Prohibited Applications Observe the following prohibition when using the product The product and related products have been developed mainly for lighting control applications Therefore do not use the product for security applications such as crime prevention protection from disasters or other applications involving protection of human lives Requirements for applications other than general lighting control that require safety Implementation of redundancy in the system so that a single failure will not make it unsafe Installation of protective devices protective circuits or other means to ensure the safety of the system Switchboards or other systems incorporating the product must be clearly labeled indicating the above instructions to secure safety Installation Requirements 1 Screws for terminals must be tightened firmly to a torque of 0 5 to 1 0 N m Otherwise malfunction failure excessive heat or ignition may occur 2 Do not install outdoors or anywhere subject to splashes of water Doing so may result in malfunction failure excessive heat or ignition 3 Use applicable power sources only Do not mix different cables such as combination of solid and strand wires on the same terminal or combine wires of different radii Incorrect use may cause overh
83. atus Indicators LEDs Power Red e ON Power is being supplied e OFF Power is not being supplied Ethernet LINK Green e ON Ethernet is connected normally e OFF Ethernet is not connected normally Ethernet ACT Orange NCU DATE TIME e ON Data is being transferred via Ethernet UNCONNECT GA SETTING OFF Data is not being transferred via Ethernet UF POST ERROR ERROR Light Blink NCU Unconnection Or Post Error Date amp Time Setting Error Indicator Red ON NCU connection is abnormal Clock in the Web Server Unit may not be set Blink NCU connection is normal but the date and time are out of order Date amp Time Setting Error status indicates that the date and time could not be kept e g after a power supply interruption longer than the clock s battery maximum time range e OFF NCU connection is normal and the date and time on the Web Server Unit are properly set 7 DIP Switch One 8 pin DIP switch is provided 2 Pin 1 of this DIP switch is used to set the network settings and is assigned the following functions S gt 0 OFF User settings are used when the power is turned aS ON or the Unit is rebooted ig 1 ON The following default values are used when the power is turned ON or the Unit is rebooted e IP address 192 168 O 1 Subnet mask 255 255 0 0 Default gateway None e Host name None Always set pins 2 to 8 to 0 OFF 9000000 TI E am v
84. automatic configuration a Se Cee Antomatically detect settings Dialup and Vatual Private Network tot _ Use automatic configuration script Proxy server rae a proxy server for your LAN These settings wil not apply to distup or VPN connections Address webproxy mew Port 8080 advarced C Bypass proxy server for local addresses Click the LAN Settings Button a Make the settings under Proxy server in the Local Area Network LAN Settings Window Consult your network administrator for setup parameters Some applications such as direct connections do not require Use a proxy server for your LAN to be selected M 34 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Installation Section 5 Network peripheral devices Consult your network administrator for details of the network peripheral devices and their environments 1 Ports The product uses the ports listed below It is required that these ports be open on the firewalls and routers between this device and the remote PCs 443 for HTTPS services 6001 for proprietary If port 6001 is closed the refresh cycle of status display will take 30 seconds or more If the port 6001 is open it can be refreshed in real time Therefore it is recommended that this port be open 2 Firewalls and routers When connecting to the Internet firewalls and routers must be installed to maintain security bu
85. ble automatic reload of basic monitoring amp control pages and periodically refresh advanced control pages system error monitor page and the status bar Location name System Administration gt Page Reload Settings Enable automatic reload of basic monitoring amp control pages O Yes No RS 232C Settings Advanced control pages system error monitor and status bar Page Reload Settings 2 Es Log Viewer i Enabling Automatic Reloading of Basic Monitoring amp Control Pages These pages communicate through a proprietary port 6001 Even if this port is closed in the user s PC environment status monitoring is still possible 1 Select Yes No By selecting Yes in the Enable automatic reload of basic monitoring amp control pages field the Main Frame will be reloaded periodically and the status data can be automatically refreshed If the proprietary port is open this reloading is unnecessary It is set to No in the factory settings If Yes is selected the Page Reload Button will be displayed in both windows Clicking this button will reload the Main Frame once regardless of the reload cycle 2 If Yes is set select the reload cycle Reload Cycle Select from 30 seconds or 1 2 3 4 5 10 15 20 25 or 30 minutes 3 Click the Submit Button ii Set the advanced control pages system error monitor page and status bar reload cycles In order to be refreshed the advanced control pages the system error page and the
86. but maps display are enabled maps pull down list will be displayed in the Menu Frame but will be empty 4 Enable Disable the Monitor amp Control List display In order to enable display of the monitor amp control lists to the Basic Monitoring amp Control users in the last row of the map table select the Monitor amp Control List Enabled only when logged in with Basic Monitoring and Basic Monitoring amp Control rights check box When logged in as the advanced control amp setting user or as a system administrator Monitor amp Control List will be displayed regardless of selection of this item Enable Display is selected in the factory settings for this item 5 Click the Submit Button 6 Enable the submitted settings Rebooting will enable the submitted settings Factory Settings Initial Page Project Name Name 2 Enable Display Monitor amp Control List Maps Location name Map 1 to Map 99 All unselected display disabled Selected display enabled 51 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 8 System Error Monitor Errors related to the circuit status monitor and control such as communications errors between the Web Server Unit and local lighting systems can be checked Location name System Administration gt System Error Monitor Basic Monitonng amp Web Server Unit Settings NCU connection error Dat
87. connection settings Programs and special days cannot be set if the date and time are out of order 7 Monitor amp Control List Settings Number of selected points 256 max type and order are arbitrary Applicable points Individual circuits dimmers groups patterns zones and global addresses of connected LIUs LIU connection configuration must have been completed before monitoring and controls are set NCUs LIUs and Transmission Units must be connected for configuration Contents of the list will be retained even if the LIU is disconnected in the LIU connection settings 8 Dimmer Level Display Settings Applicable points Individual circuits dimmers and groups of connected LIUs Monitoring method Manually obtained by selecting points 9 Name Settings Applicable points Individual circuits dimmers groups patterns global addresses and zones Name settings 16 characters max iso 8859 1 CP932 144 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information System 1 Clock Day amp time Settings Timekeeping range 00 00 00 January 1 2000 to 23 59 59 December 31 2037 Range for settings 00 00 00 January 1 2000 to 23 59 59 December 31 2037 Smallest unit that can be set 1 second The clock will revert to January 1 2000 after December 31 2037 Booting when status is Date amp time out of order will re
88. cute Cancel 2 Click the button for the status to control The dialog box will close and the status will change Displaying control buttons varies in response to the addresses for global settings The dimming level cannot be monitored for a global address even if the global address is defined individually or in a group For details on global control refer to Global Control under Administration and Settings 131 gt WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control V Error Status Displays 1 Status Bar Statuses 1 to 8 shown as follows are displayed in the Status Bar If more than one state exists at the same time the lower numbered state has higher priority for display 1 Please wait for a moment Red Indicates the network connection to the Web Server Unit has been temporarily disconnected e g broken wire a device that has stopped etc When this error occurs it is suggested to verify the following settings Network status channels power supply for devices device settings etc Power to the Web Server Unit Connection status with the NCUs channels NCU power supply communications settings such as the NCU DIP switches and the RS 232C Settings of the Web Server Unit When this error occurs nothing will be displayed after connecting reconnecting from the Web browser 2 Date amp Time out of order Red Indicates that the date
89. d but only the OFF operation will be executed If the same day is registered as a special day more than once duplicated special day for a program and set as a Special Day i e set for execution and a Canceled Special Day in the other the Special Day registration will take priority and the control will be performed When special days are deleted they will no longer be displayed as a special day but if ON control has been executed the corresponding OFF control will be executed and the relevant program will remain in the list 93 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings c Special Days Special Days is used to configure holidays and days on which to execute special activities Location name Advanced Control amp Settings gt Schedule Settings gt Special Days Cones No Name Action ye 03 Special Day 03 Acteancad Conte n Speci Day 04 Patera Setiat Z isco _AddNew _ aal Address Settings 06 Special Day 06 Add New Sane eee Programs 07 Special Day 07 Add New Special Days 0s Special Day 08 a Special Days Calendar Nines Special Day 09 ranw J ae Status ar Mage 2 Special Day 10 _Add New ae System Administration il Special Day 11 Add New ae 12 Special Day 12 a 2 13 Special Day 13 Add New Sus ee O TTTTTResieead i Registering and Changing Special Days Special days cannot be set if the c
90. data up to that point is obtained 60 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration General Precautions Microsoft Excel is recommended to view and edit uploaded files Uploaded files with the wrong format or values are invalid CSV files use the Iso 8859 1 character set Other codes are invalid and will result in the message File data acquisition from CGI parameter failed Blanks in data files will cause the actual data to be deleted This does not include Groups and Patterns Any file name is valid as long as the extension is CSV Precautions Specific to Groups and Patterns The Transmission Unit must be connected for uploads The connected Transmission Unit will be updated with CSV file contents at the time of the upload operation While data is uploading uploads from other browsers are disabled System errors cannot be detected while uploading is in progress Addresses with descriptions will update data in the Transmission Unit but those without descriptions will not One registration takes 20 to 30 seconds The registration of all data on one Transmission Unit will take approximately 30 minutes Precautions Specific to Zones Contents described when uploading will be transferred to the Web Server Unit and registered as Data read from the Web Server Unit in Zone Settings At this point however this data is not registered in the
91. deleted the control will be performed if the clock is set back iii Adding the Next Day as a Special Day for One Day Only The next day can temporally be added to a special day setting that does not originally include the next day Special day settings that do not include the next day in the original settings including overriding execution and cancellations can be added to the program 1 Click the Submit Button for the next day The Next Day cell in the line will turn red Next Day indicates the day following the day when the next day setting operation is performed This operation can thus be performed only the day before the special day Next day settings will not persist and will not be saved as special day data This operation does not register special days to be repeated every year iv Disabling Special Day Setting for Next Day for One Day Only The next day can temporally be deleted from a special day setting Special days set for the next day in the Original program settings including overriding execution and cancellations can be disabled 1 Click the Next Day Disable Button red background The Next Day cell in the line will turn gray Next Day indicates the day following the day when the next day setting operation is performed This operation can thus be performed only the day before the special day Next day settings will not persist and will not be saved as special day data This operation does not disable special days
92. dual circuits dimmers groups and global addresses patterns excluded sunset ON sunrise OFF sunset ON OFF ON sunrise OFF ON OFF OFF ON ON ON OFF OFF and ON OFF Patterns zones and global addresses patterns only ON sunset sunrise and repetition Smallest increment to set clock 1 minute 143 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information Input method of districts for Astronomical Clock Latitude Longitude and time zone Sunrise sunset time adjustment range 90 minutes by increment of 1 minute Repetition interval adjustment range 1 minute to 1 hour and 30 minutes increments of 1 minute Units of programs that can be enabled 1 program or all programs Number of special day settings 30 max Special day name 16 characters max iso 8859 1 CP932 Special day setting format Yth Z day of the week Month X Day Y Every year and Month X Day Y Year Z Special day input method Using calendar Range of special days to be set January 1 2000 to December 31 2037 and13 months from current month Enabled special day display unit 1 month Setting clearing next day in special day range 30 max Daylight saving time adjustment 1 hour when enabled LIU connection configuration must have been completed before setting schedules Programs will be retained even if the LIU is disconnected in the LIU
93. dvanced Control amp Settings gt Pattern Settings n T LIU No 01 Pattem 01 Name Pattem 01 Fade Time No Fade v Advanced Control amp All OFF All Ignore Settings Individual Circuit N 5 T Dimmer level Map1 Address as ae 1 to 128 00 1 Individual Circuit 00 1 OFF v Advanced Control 00 2 Individual Circuit 00 2 OFF v Pattern Settings A 00 3 Individual Circuit 00 3 ON v v 128 Zone Settings i Global Address Settings 00 4 Individual Circuit 00 4 ON es Setti Dimmer Settings 01 1 Individual Circuit 01 1 ON v On timer for 30 s Status Bar Manager On timer for 1 min 01 2 Individual Circuit 01 2 ON Y On timer for 5 min System Administration On timer for 60 min 01 3 Individual Circuit 01 3 ON On timer for 120 min 01 4 Individual Circuit 01 4 ON v 02 1 Individual Circuit 02 1 ON v 02 2 Individual Circuit 02 2 ON v v 1128 02 3 Individual Circuit 02 3 ON v v i1128 te WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 2 Select an address number Click the Add new or Edit button for the address to register Communications for the Web Server Unit to obtain registered data from Transmission Units will start and the window will switch to an editor page when communications have been completed Data transfer in progress Please wait will be displayed in the status bar until the editor window opens less than a minute Conf
94. dvanced Monitoring amp Control User Enables setting in addition to monitoring and control of lighting circuits operations System Administrator Enables all operations including those related to system administration settings 2 Enter the user name and password and retype the password The following is a list of conditions for user names and passwords to be valid Valid user names and passwords can be of 4 and 8 characters long excluding hyphens underscores and other special characters Same user names cannot be used more than once regardless of whether the access rights are different User names are not case sensitive 4 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration The number of user accounts is limited depending on the user type as described in the following table Minimum number of user Maximum number of user User Type accounts accounts Basic Monitoring Basic Monitoring amp Control Advanced Control amp Settings System Administration Click the Clear Button to delete text entries in the User Name Password and Retype Password fields An Advanced User and Administrator can be registered by overwriting the default text 3 Click the Submit Button Registrations are disabled for a period of one minute after one registration deletion operation has beed performed This restriction applies when registering multiple users in Succession
95. e amp Time out of order Date amp Time S Local System Errors Types NCU connection errors RS 232C communications error between the Web Server Unit and NCU unmatched communications parameters broken unmatched cable NCU power interruption etc Date amp time outoforder Occurs when the clock has been re initialize after a power interruption longer than the clock s battery maximum time range Local bus error Communications error between NCU and LIU unmatched baud rate or addresses connection problem LIU power interruption etc FULL 2WAY signal errors Channel errors between LIU and Transmission Unit connection problem short circuit Transmission Unit power interruption etc Pattern Group Occurs when setting is in progress with the pattern group configurator configuration in progress Some configurators such as Web Server Units WWRT9600 and in process WRT9103 series Units employ configuration methods that do not affect monitoring and controls These configurations do not trigger error indications Supplemental Information X is displayed to indicate an error If any error occurs a message to that effect will be displayed in the Status Bar Unknown address status of circuits T U and patterns groups both red and green LEDs of wall switches are OFF due to disconnected terminals unregistered addresses nonexistent P G settings etc will not trigger errors because they can be defined
96. e Name XXXXXXco csv XXXXXX denotes two digits for the year two digits for the month and two digits for the day Control Log 1000 to 1 descending order No 1000 to 1 in descending order Time 0 00 to 23 59 LIU number 1 to 31 Type individual circuits D dimmers G groups P patterns Z zones or gb global addresses Address 00_1 to 63 4 individual circuits 1 to 16 dimmers 1 to 127 groups 1 to 72 patterns 1 to 96 zones or 1 to 32 global addresses Name 32 characters max Control result ON OFF Match Mismatch ON Pattern 1 Pattern 2 Pattern 3 Pattern 4 OFF Invalid Abnormal OFF Abnormal ON Control type Web Schedule or Local 160 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Miscellaneous Information e System Error Log File name XXXXXXal csv XXXXXX denotes two digits for the year two digits for the month and two digits for the day System Errors Log 1000 to 1 descending order No 1000 to 1 in descending order Time 0 00 to 23 59 Generating device Web Server Unit NCU or LIUO1 to LIU31 Date amp Time out of order Normal abnormal or boot complete NCU connection Normal or abnormal Local bus Normal or indeterminate FULL 2WAY signal Normal abnormal or indeterminate Patterns groups settings Normal abnormal or indeterminate 161 WR3330 801 FULL 2WAY Web Server Unit Panel Use En
97. e Web browser should be closed for security reasons In particular the browser should not be left logged in with the system administration right 27 To log in with a different access right the Web browser must be closed first Precautions and Disclaimers for Internet Connections 1 We have incorporated network security technology controls to prevent unauthorized access and encryption in SSL to connections between the Web Server Unit and customers facilities but should customers incur any damages resulting from information theft from unexpected wrongdoing or password misuse from theft on the Internet connections we will not be held responsible whatsoever except for cases where we are at fault 2 When connecting the Web Server Unit to the customer s facility we will not be responsible for necessary procedures and installation configuration and maintenance of equipment and their associated costs to maintain the security of the network The customer is responsible for them If the security measures mentioned above are not sufficient and result in damages we will not be held responsible unless we are at fault Communications fees will be borne by the customer 3 SSL is incorporated through encryption but SSL server authentication issuance of certificate is not provided 4 When connecting to the Internet secure a continuous connection network environment that offers open ports to be used and enables the Web Server Unit to set to a
98. e dimmer T U for the GetLevel Cancel address lf the addresses included in the group are to relay control T Us the level will be displayed as 1 for ON and 0 for OFF If the dialog box is closed by clicking the Cancel Button while the dimmer level is being retrieved start again from step 3 5 Click the Cancel Button The dialog box will close lf any button is clicked after the level has been displayed the value will be discarded The value will be retained if the dialog box is closed by clicking the Close Button in the upper right comer ae oe WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control 3 Advanced Control Patterns Pattern Addresses 01 to 72 Advanced Control amp Settings gt Advanced Control Basic Monitoring amp Control 37t072 UNo 01 v Select v Advanced Control amp Address Settings Mapil Co e o Advanced Control cou E a e Global Addresses se Zoos stian es Ce emn O erp Ce Dimmer Senn Ts Sates Status Bar Manager Ca ema OOOO E Ca ema OOOO i Monitoring 1 Select the LIU number and click the Select Button 2 Click 01 to 36 or 37 to 72 button The display of pattern addresses is split into 2 windows of 36 addresses each The statuses of the selected addresses are displayed in the Status Fields E ee As shown in the figure a pattern MATCH is indicated in red MISMA
99. e the settings for normal circuit symbols or zone circuit symbols defined with the drawing software using symbol numbers These definitions cannot be changed on a browser page Dimmer level symbols level gauge use the settings for normal circuit symbols defined with the drawing software using symbol numbers These definitions cannot be changed on a browser page Dimmer level symbols apply to individual circuits dimmer and groups Dimmer level symbols with their assigned normal circuit symbol addresses set to patterns or global addresses are not equipped with level monitoring function A symbol with multiple symbol numbers can be assigned the same address Name symbols and dimmer level symbols can be set to share symbol numbers with monitor amp control symbols on the drawing software If so their circuit address values will change in sync with those set for monitor amp control symbols Symbol numbers however cannot be changed on a Web browser 74 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings a Generic Status Symbols b Zone Status Symbols i Registering a New Address 1 Select a symbol icon ress setting Address setting Address setting Address setting dialog Box will be displayed apea Type Global Adress Symbols without symbol numbers assigned icon numbers eEIaEH Submit Cancel cannot be selected Symbol numbers must be assigned
100. east 30 cm or lay the cables in a metal conduit grounded to 1000 or less class D grounding Adistance of 30 cm or less is allowable within the power board The signal line however must be separated from the power line more than100 A by at least 5 cm For details on FULL 2WAY Remote Control refer to the specific catalog and technical manuals e Power Supply to Each Unit Use the WR2301 811 WR2311 821 series Transformer Panel Use for the power supply These items are NOT applicable to U S A market Required UL approval but NOT approval Input the secondary output of the Compact Remote Control Transformer to the 24 V terminals of the Web Server Unit NCUs and LIUs Use multiple transformers if the total rated current of the connected devices exceeds the capacity of a single Compact Remote Control Transformer 1 5 A f Grounding Units Always ground the ground terminals of the Web Server Unit NCUs LIUs and Transmission Units to 1000 or less 25 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Installation Section 2 Hardware Device Settings a DIP Switch Settings for Network Control Units NCUs Set the DIP switches on the Unit as follows For details on DIP switch pin number assignments refer to the NCU product specifications 1 Set host to host communications RS 232C RS 232C communications settings for the Web Server Unit can be changed from the browser make sure t
101. eating or bad connections 4 Use only the rated voltage Excessive voltage may cause overheating and ignition 149 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information V Precautions and Disclaimers Precautions and Disclaimers before Purchase 1 Refer to specifications for the following products in addition to this manual for information on system configuration and communications WR3387 8 FULL 2WAY Remote Control Network Control Unit NCU WR3388 8 FULL 2WAY Remote Control Local Interface Unit LIU 2 Connection of the Web Server Unit to the customer s facility may require configuration of the customer s network device environment Detailed discussions may be necessary to configure the network environment Consult Matsushita Electric Works Ltd for details 3 Specifications and exterior appearances may be changed without notice due to product improvement 4 Windows and symbols of the software shown in this document may be different from those actually displayed 5 PCs network devices and other peripheral devices are expected to be provided by the customer Precautions and Disclaimers for Installation 1 Please use the following power supply WR2301 811 WR2311 821 series Transformer Panel Use These items are NOT applicable to U S A market Required UL approval but NOT approval 2 The power supply for devices must be a non interruptive power s
102. eation and Administration of Maps The selection menu for map numbers in the Administration and Setting Window will be displayed if the corresponding map number checkbox is selected in the Project Display Settings under System Administration Monitoring and Control Symbols Status buttons symbols on the window provide functions equivalent to switches in order to control and monitor lighting circuits specific to FULL 2WAY Remote Control Systems If these symbols are placed on the maps they may be assigned addresses for FULL 2WAY Remote Controls from the Address Settings in the Web browser i Monitoring 1 Select the map name in the menu frame and click the Select Button The map will be displayed in the Main Frame The status of corresponding addresses will indicated by the status symbols In general the ON state is displayed in red OFF state in green timer state in red with a clock and indeterminate no T U or unregistered state in gray as shown in the figures below As for zone addresses there can be up to seven different status symbols Hyperlinks to other maps can be defined in the map drawing software 119 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control a Generic Status Symbols b Zone Status Symbols Pattern C match Pattern D match Pattern E match Patten F match The status display uses port 6001 If this port is closed the status display wil
103. ect Display Settings System Error Monitor Log Settings Groups Patterns Zones Log Viewer Activity System Errors Download Manager Upload Manager Run Command Data Monitor Map Manager Factory Settings Reboot Configures the display of dimmer levels Displays all individual circuit addresses with LIU units Displays all group addresses with LIU units Sets and clears the display to notify users that settings are in progress Configures Ethernet communications settings Configures login rights user name and password Configures the date and time of the clock in the Web Server Unit Configures serial communications setting between the Web Server Unit and NCU Configures LIU addresses for the communications link Configures reload intervals in the browser Configures project and map display Confirms information on current system errors Sets control points for local circuits for which changes in status are to be logged Displays all group addresses with LIU units Displays all pattern addresses with LIU units Displays all zones addresses Displays the activity log and system error log Displays window operation schedule and status change log by date Displays system error log by date Transfers data files from Web Server Unit to the client PC Transfers data files from the client PC to the Web Server Unit Reserved for maintenance Displays used and
104. ed States and Canada v Advanced Control v Automatically adjust clock for daylight saving changes cas Seth ally adju yligh g chang oe Current time status Daylight saving A ti Programs Programs Monitor Special Days Special Days C N Status Bar Manager ees A complete restart of the system is necessary for any changes to become effective System Administration Gotorebootpage _ to reboot page i Specifying the longitude latitude time zone and daylight saving rule from preset location 1 Select a location Select a preset location from the Location drop down menu Upon selection longitude latitude time Zone and daylight saving rule corresponding to the selected location will be automatically selected There may be some differences between the preset values and the actual location time Zone and applicable daylight saving rule of the system In order to increase the accuracy of the calculations longitude latitude time zone and daylight saving rule can be adjusted after selecting the location 2 Click the submit button If the input values for longitude latitude time Zone and daylight saving rules are different then the preset values for the selected location a confirmation window showing those differences will be displayed If the specified values are correct click the OK button in order to submit the new settings Clicking the Cancel button will close the confirmation window without any information
105. ed by clicking the Close Button in the upper right comer Java Applet Window 123 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control b Dimmer Addresses 01 to 16 Location name Advanced Control amp Settings gt Advanced Control Address Settings Mapil i Monitoring 1 Select the LIU number and click the Select Button 2 Click the Dimmers 01 to 16 button Zone Settings 16 Pos timer os This opens the display of the 16 dimmer addresses The statuses of the selected addresses are DENS ore ee As shown in the figure ON is indicated in red OFF in green indeterminate No T U or unregistered displayed in the Status Fields in gray and details are given in text e g TIMER If the connection from the Web Server Unit to the NCU to the LIU to the Transmission Unit is cut all address statuses will be displayed as indeterminate Statuses of addresses disabled in the LIU Connection Settings will be displayed as indeterminate ii Controls 1 Click the red green button in the Status column A dialog box as the ones displayed below will open Symbols in indeterminate state cannot be selected Does not apply to On timer and Off delay timer controls Does not apply to dimmer level controls 2 Click the button for the status to control The dialog box will close and the status will change 124
106. ed on the client PC Because this value is not automatically refreshed it should not be interpreted as a functional clock The clock will return to January 1 2000 after December 31 2037 The clock will start with 1980 01 01 00 00 00 on initialization after a power failure longer then the clock s batteries maximum longevity Date amp Time Out of Order When the clock is in Date amp Time Out of Order status the LED indicator on the Unit will be flashing and the error message will remain until a valid date and time are specified Value at rebooting 2000 01 01 00 00 00 46 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 4 RS 232C Settings This page provides an interface in order to set the RS 232C communications parameters between the Web Server Unit and NCU Defaut Submit L Go to Reboot Page 1 Select the values Use the following values Bits per Second 19200 or 9600 bps i e Data Bits 7 bits e Parity Even Polling Ratio 2 Polling Cycle 0 4 S The DIP switch on the NCU must be set to the same values Factory settings Bits per Second 19200 bps e Data Bits 7 bits e Parity Even Polling Ratio 72 Polling Cycle 0 4 S Click the Default Button to display the above values 2 Click the Submit Button 3 Enable the registered values Registered values are enabled by rebooting the web se
107. ed on the label Set the following settings if connecting for the first time or if user values are HOLMS Y ds LdV NOLLAS 100834 HSNd YSLIWV ud MYOMLAN unknown IP address 192 168 0 1 Subnet mask 255 255 0 0 Default gateway None Host name None ii User Settings Set the following settings when user defined network parameters registered under Network Settings are to be used 7 mn Cc Wa m rot Cc Cc CI Cc Cc Cc CI IP address Parameters set in Network Settings Subnet mask Parameters set in Network Settings Default gateway Parameters set in Network Settings Host name Parameters set in Network Settings For details on Network Settings refer to Administration and Setting Section Settings for System Administration The DIP switch is set to the default settings at the factory 2 Set unused switches Always set to 0 Unused 2 to 8 AllO 3 Press the Reboot Button When all settings have been completed always cycle the power or press the Reboot Button to enable the changed settings e Set the connections between the Web Server Unit and Ethernet devices Refer to II Network Connection and Settings Implementation 28 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Installation Section ll Network Connection and Settings Installation Communications settings for connection to network devices are explained he
108. er 6 Click the Reboot Button Wait for the Web Server Unit to reboot 7 Open the Web browser and log in with the system administration rights 8 Enable maps display in Project Display Settings under System Administration Enable the display of transferred map data in the window This step will enable display of the maps pull down menu in the Menu Frame If network settings have been changed for connection to the map drawing software reset the parameters 5 Deleting Data Files Map data can be deleted in the Web browser on the Web Server Unit Refer to Maps Manager or Factory Settings for details 609 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings This section provides information on the system advanced control and settings features I Advanced Controls amp Settings P 71 70 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings I Advanced Controls amp Settings The following functions can be used when logged in as the advanced control amp settings user or administrator 1 Monitor amp Control List Settings 2 Address Settings 3 Advanced Control a Groups b Patterns c Zones d Global Addresses 4 Schedule Settings a Programs b Program Monitor c Special Days d Special Day Calendar e Astronomical Clock 5 Name Settings a Individual Circuits b
109. erminate No T U or unregistered in gray and details are given in text e g TIMER The possible statuses of zone modes are explained in the following table Mode 2 Pattern A Pattern B and Pattern C in this case Pattern C is used to denote other conditions Pattern A Pattern B and Pattern C Pattern A Pattern B Pattern C and Pattern D Pattern A Pattern B Pattern C Pattern D Pattern E and Pattern F If the connection from the Web Server Unit to the NCU to the LIU to the Transmission Unit is cut all address statuses will be displayed as indeterminate Statuses of addresses disabled in the LIU Connection Settings will be displayed as indeterminate Zo WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control ii Controls 1 Click the red green button in the Status column A dialog box as the one displayed below will open Symbols in indeterminate state cannot be selected Zone 02 Zone 03 Zone 02 Zone 03 Pattern A Pattern B Cancel Pattern A Pattern B PatternC PatternD Pattern E Pattern F Cancel 2 Click the button for the status to control The dialog box will close and the status will change In mode 2 Pattern 1 can be monitored but cannot be controlled For details on zone control refer to Zone Control under Administration and Settings 130 WR3330 801 FULL 2WAY Web Server Unit Panel Use English Use
110. ern C Pattern D Pattern E and Pattern F Global Addresses ON and OFF The dimmer levels for individual circuits dimmers and groups cannot be increased or decreased from a browser Timers for individual circuits dimmers and groups cannot be controlled from a browser Pattern addresses are subject to only ON controls The same is true for global control of patterns Only individual circuits dimmers patterns and groups but not zones can be points of global controls The control method of global controls conforms to the control method of the point 4 Schedule Program Timer Controls Points addresses subject to controls Individual circuits dimmers groups patterns Zones and global addresses Number of control programs 930 max 930 max per Transmission Unit 5 Monitoring and Control by Symbols Number of Symbols for Monitoring and Control Normal circuits 256 max per map total of individual circuits dimmers groups patterns and global addresses Zones 40 max per map Number of Symbols Names Normal circuits 256 max per map total of individual circuits dimmers groups patterns and global addresses Zones 40 max per map Number of Symbols for Dimmer Level Normal circuits 256 max per map total of individual circuits dimmers and groups 141 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Informa
111. es for a single day the oldest log entry will be replaced by the newest log entry as the 1 000th case bottom of the table If the log exceeds seven days the oldest day s log data all 1 000 records will be deleted to make room for the current day s log If the date is changed in the Date amp Time Setting Window all seven days logs all 7 000 records will be deleted The log dates may not be correct arbitrary dates are logged if a date amp time out of order error has occurred 56 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual System Administration 11 Download Manager Download Manager is used when major settings data and history logs are to be back up on a client PCs 5 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration Downloadable Data File Types Data in CSV Comma Separated Value format can be generated and downloaded from the web server unit Microsoft Excel is recommended to view and edit these files Monitor amp Control List Group e Pattern e Zone Global Addresses Schedule Special day e Address Name Settings Individual Circuits Name Settings Groups Name Settings Patterns Name Settings Zones Name Settings Global Addresses e Control log System error log List data registered in Monitor amp Control List Settings list csv Group
112. escribed in the user s manual and labels attached to the product within the warranty period it will be repaired free of charge Disclaimer on the Warranty In principle repairs for the following failures will be charged for even if they occur within the warranty period 1 Failure or damage resulting from misuse or improper repair and modification 2 Failure or damage resulting from relocation transportation or dropping after the purchase 3 Failure or damage resulting from fire earthquake lightning or other acts of God or environmental pollution salt erosion or gas erosion such as hydrosulfuric gas 4 Failure or damage resulting from voltage and frequency of the power supply different from those specified 5 Failure or damage resulting from installation on a vehicle or ship 6 Failure or damage resulting from improper installation 7 Failure or damage resulting from negligence in the routine maintenance check required by regulations and user s manual 8 Failure or damage resulting from application exceeding the conditions and environments specified in product specifications catalogs and other documents 9 Failure or damage resulting from special applications in combination with other manufacturers products not specified by us 10 Failure or damage resulting from application outside of Japan 148 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Inform
113. f dek space touse Select Every visit to the page under Check for newer eS eae pages ae pee x Cee Click the OK Button to complete the procedure 33 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Installation Section 2 Installing Java Run the installer on the included CD Execute j2re 1_4 2 03 windows i586 p exe included in the CD to start installation and Follow the instructions from opto installer ies enero ava 2 Re won Setup Type 3 Inst sling Jove 2 Runtime tnewornment SE v1 42 _05 Mose the setup type that bet sas par S m S te wog e features ya simte are berg rA stent Please sainct a setup type Anaming feray papama ae m furtre A Sun Moecroeyetens Inc Jeary Code License Agreement Orma abe wed neaten L amas for the 8 A recommended teatres wll be wat det Prateg ratdir pame mat Tha may take several mron JAVA 2 RUNTIME EN TR JND seora oy STANDARD ED ITION VERSIO 3 Proxy Server Set the connection to the proxy server and other connections if needed Right click the Internet Explorer Icon and select Internet Properties Alternately left click Internet Properties and select Tool Internet Options PIR ff Local Area Network LAN Settings Internet Optio E Select the Connections Tab Sama Seay Pires GenCore Pape Aen tee cre j atomai pare EE To ensure the D 1 To set up an Internet connection cick Sen use of manual settings disable
114. for drawing software must be saved 2 Map Data File format Proprietary Number of symbols Normal circuit symbols 256 max per map total for individual circuits dimmers groups patterns and global addresses Zone symbols 40 max per map Number of symbols names Normal circuit symbols 256 max per map total for individual circuits dimmers groups patterns and global addresses Zone symbols 40 max Normal circuits include individual circuits dimmers groups patterns and global addresses Circuit name symbols conform to the settings for normal circuit symbols or zone symbols associated beforehand This association can be set only using the Screen Builder and cannot be changed in the Web browser Dimmer level symbols conform to the settings for normal circuit symbols associated beforehand This association can be set only using the Screen Builder and cannot be changed in the Web browser Dimmer level symbols are for individual circuits dimmers and groups only Addresses are not directly assigned to dimmer level and circuit name normal and zone symbols 147 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information Ii Warranty Warranty Period The product has a warranty for the period of one year from the data of purchase delivery date Scope of Warranty If the product fails to function properly under applications d
115. format Year Month Day Hour 24h Minutes Seconds Current time status Daylight saving Page Reload Setti Submit 1 Enter the date and time in the Date amp Time field The required format to enter the new date and time is as follows year month day hour 24 hours format minutes seconds e g December 1 2004 11 01 59 p m will be set as 2004 12 01 23 01 59 Always use four digits for the year two digits each for the month day hour minutes and seconds Also use a single byte slash 7 as the delimiter The maximum range for the date amp time settings is as follows 2000 01 01 00 00 00 to 2037 12 31 23 59 59 2 Click the Submit Button Changes to the Date amp Time Settings will affect the stored log data The logs recorded up to six days before the renewed date will be deleted If the date changes naturally due to the passing of time while this window is displayed before clicking the Submit Button a registration error will occur to protect the log Current Time Status Current time status daylight saving time or normal time is indicated below the date amp time setting field Supplementary Information Periodic adjustment is required due to the clock s precision 45 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration The time displayed in the Present time field is the time set on the Web Server Unit when Date amp Time Settings is display
116. g assumed ON 1 The result will be lf AND is selected 1 0 0O 1 0 OFF At least one system contains OFF or equivalent lf OR is selected 1 0 0 1 1 ON Atleast one system contains ON or equivalent 87 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 8 Schedule Settings Schedule Settings is used to configure schedule control programs Date and time addresses statuses and other settings to control automatically from the Web Server Unit are configured using the following menu commands a Programs Configures time schedule b Programs Monitor Monitors schedule settings for events to occur on specified days c Special Days Configures dates requiring special functions such as national holidays d Special Day Calendar Monitors special day settings and duplications of special days e Astronomical Clock Configures sunrise sunset functions and daylight savings time functions a Programs Programs are used to configure time schedules Location name Advanced Control amp Settings gt Schedule Settings gt Programs cena N Name 4 le LIUN T ddr Opera Schedul Da h k e a eee a oo i Program 001 OO 1 Individual Circuit 00 1 Sunset Sunrise From sunset until sunrise Wini Advanced Control 00 Program 00 01 Group 001 Sunset OFF From sunset until 22 00 os fQ ennnee se Pattern Settings ae
117. g Settings 003 Group 003 OD o Group 067 Sre 0 Group 004 a 068 Group 068 eng Log Viewer 005 Group 005 a 069 Group 069 Download Manager x 006 Group 006 070 Group 070 Upload Manager we oup c Zones x 007 Group 00 O 071 Group 071 Map M 7 n wae 008 Group 008 C 072 Group 072 EE ENE Reboot 009 Group 009 0 073 Group 073 010 Group 010 a 074 Group 074 aa 011 Group 011 B 075 Group 075 lt gt r maa A PRPEPPP PEEP TT 5 SECs ss 82282828 22 8 2 ee E zs cscs 8s ron BP2eseee 3 amp amp AER ES Ep 1 Select LIU No Groups and Patterns Log Settings Select an LIU number from the pull down menu and click the Select Button to display all corresponding items 2 Select the addresses Groups Patterns and Zones Log Settings The addresses of the items to be logged can be selected by selecting its check box a Group address range 001 to 127 per LIU b Pattern address range 001 to 72 per LIU c Zone address range 01 to 96 3 Click the Submit Button Groups Patterns and Zones Log Settings Supplemental Information Logs can only be checked and recorded for group pattern and zone addresses DIP switches on both NCUs and LIUs must be set to enable the Web Server Unit to obtain logs Refer to Installtion Section Connection and Configuration Installation of Device Unit for details Changes due to On timer Off delay controls included in the Patterns and Groups settings may
118. ge e No Serial number of the log entry listed in decreasing order e Time Time at which the control activity occurred listed in reversed chronological order e LIUNo Local LIU number where control activity occurred Type Address type as described in the following table Type Designation e Address Address number e Name Name of the corresponding address as set in Name Settings Operation Status of control address If the control command was not transmitted to the lower system and is invalid Invalid will be displayed Also if the control command was transmitted to the lower system but the result was the same as before the control Abnormal OFF Abnormal ON will be displayed Finally global addresses control do not have Abnormal ON OFF or Invalid statues Origin Origin of control command as described in the following table 55 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration Control command originated from a web page schedule Control command originated from a program Local Control command originated locally Local control command are logged as configured in the Log Settings Status changes of individual circuit and dimmer addresses are not logged Items Displayed in the System Error Log e No Serial number of the log entry listed in decreasing order e Time Time at which the error occurred listed in reversed chronological order e De
119. ger is used when settings data is transferred from PCs to the Web Server Unit Location name System Administration gt Upload Manager Name Settings Individual Circuits Name Settings Patterns Name Settings Zones Uploadable Data File Types The same file types can be uploaded as the downloadable files in Download Managerexcept Activity and System Errors Uploading requires the same format as that used for downloading Refer to Miscellaneous Appendix for details Operations 1 Select the type of data file When a button for a type is clicked in the upper frame the file name input field will be displayed in the lower ss frame aome J Uptec 2 Enter a file name When the Browse Button is clicked the Choose File Dialog Box will be displayed Select a file name and click the Open Button File names can also be entered manually 3 Click the Upload Button For Groups and Patterns communications to transmit data to the selected LIU s Transmission Unit will be initiated During this transmission the message Data transfer in progress Please wait will be displayed as the following Wait until the message changes to Connected and communications are SSS Sa completed 5 TEPEN Responses may be delayed or not occur during the operation a DDii When the Pause Button is clicked communications to the Transmission j Unit are interrupted but
120. glish User s Manual Miscellaneous Information Dimmer Level Specifications The 7 level shades and 128 level shades of dimmer levels correspond as follows Individual Number Circuit Level Level 3 Level 1 OFF Indeterminate 162 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Miscellaneous Information Il Troubleshooting Q A IP address among others have been changed from the initial values from network settings but connections fails Is pin 1 on the DIP switch on the body of the Web Server Unit set to User It is possible to register user defined values and reboot on the window even if the DIP switch is set to default but DIP switch setting will take precedence after rebooting so default network values will be enabled Be careful especially after installation PCs that connected successfully in the LAN environment failed to connect one to one Is the proxy server setting for the browser correct If IP addresses and subnet masks are set properly but if a nonexistent proxy server is specified connection will fail in the proxy server environment lf connecting to a PC directly be sure that Use proxy server in LAN is not selected Ethernet LINK indicator does not light The following causes are likely Network parameters are not properly set Do not match those on PC LAN cable is not properly plugged into a device LAN cable is broken Co
121. global IP address provided by the ISP 5 When connecting to the Internet the user is responsible for contracting with a provider for a user name and password Depending on the provider a DNS server address may be necessary 6 The connection speed of ADSL or better is recommended 7 The user is responsible for contracting with an ADSL carrier and an Internet service provider ISP who provides a fixed IP address service 8 The Web Server Unit is not equipped with PPPoE connection functionality If you subscribe to a service that requires the user authentication by PPPoE a router with PPPoE functionality or an ADSL modem with routing functionality will be needed in addition to an ADSL modem 152 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Miscellaneous Information I Appendix P 154 ll Troubleshooting P 163 153 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Miscellaneous Information I Appendix Data File Formats The formats of the CSV data files handled on the Download Manager and Upload Manager pages are shown below along with examples e Monitor amp Control List File Name list csv No 1 to 256 in ascending order LIU number 1 to 31 1 for global address Type individual circuits D dimmers G groups P patterns Z Zones or gb global addresses Address 00_1 to 63 4 individual circuits 1 to 16 dim
122. hed iii Display the Dimmer Level The dimmer level can be displayed manually for each address Only individual and group addresses whose level display has been enabled in the Dimmer Settings can be displayed 1 Click the red green button in the Status Field A dialog box as the ones displayed below will open Individual Circuit 00 1 Individual Circuit 00 1 Group 001 Dimmer 01 LIU 1 Individual Circuit No 00 1 LIU 1 Group No 001 LIU 1 Dimmer No 01 Dimmer Level Undefined G et Level Dimmer Level Undefined G et Level omme Levec nnn ON OFF Cancel ON OFF Cancel ON OFF Cancel Java Applet Window Java Applet Window Java Applet Window The first operation after connecting to the Web Server Unit takes more time than usual The dimmer address can be confirmed at this stage ae WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control 2 Click the Get Level Button The dialog box will close 3 Wait for a while 4 Click the status button A dialog box will open with the dimmer level being displayed Dimmer Level Value Table Control Type Individual Circuit Dimmer Group Displaying the dimmer level for individual addresses requires the dimmer T U for the address lf the address is to a relay control T U the level is displayed as 000 Displaying the dimmer level for group addresses requires the dimmer T U for the address lf the addre
123. hey are still the same on the day the control is scheduled for execution no control will be executed For inter day control the OFF time will be for the day after the ON time Refer to Schedule Control Program Specifications for details Repetitive controls will revert back to the originally set times even if the control on the start time was delayed for some reason 10 Select program execution days Day of execution of a program can be specified by selecting or clearing check marks M Execution Day of Week If the day of week is selected M control will be executed on that day every week Canceled Special Day of Week If the day of week is cleared U control will be canceled on that day every week Execution Special Day If the special day is selected control will be executed on the special day If the day falls on a Canceled Special day of week Execution Special Day will take priority and the control will be executed Canceled Special Day If the special day is cleared H control will be canceled on the special day If it falls on an Execution day of week canceled special day will override and it is canceled Special days are used to execute or cancel an operation as an exception such as for holidays or anniversaries for operations otherwise set to be executed on a day of week every week Special days can be specified as day of the month day of the week of as specific dates Refer to Special Day Settings for
124. ificate revocation Java Sun per aeaea aea Do not save encrypted pages to disk Use Java 2 v1 4 2 05 for applet gt requires restart C Empty Temporary Internet Files folder when browser is closed T Enable Integrated Windows Authentication frequees restart V Enable Profle Assistant Click the OK Button to complete the procedure To enable the changed settings close the browser Java Version 1 4 2 is required If this item is missing or another version is specified follow step 2 to install Java Setting for Microsoft VM does not require changes Enable SSL 3 0 G Security Select the Advanced Tab Use SSL 2 0 Select 1 Use SSL 3 0 under Security Use SSL 3 0 Click the OK Button to complete the procedure G Disable Cookies Select the Privacy Tab a pivacy pokey ma vet that 5 E a compact ti iak Kaen Pas DP rerevboprerbyets n the Intemet i ee joanne sen penny anor ae est y cookies thal ute pe y xdertiiad O0 Select Advanced kaanam cool Orne ses cen hanino Third party Cookies Select 4 Override automatic cookie handling in the Advanced Privacy Settings Window Select Block under First party Cookies and Third party Cookies Click the OK Button to complete the procedure Check for newer versions of stored pages Disable the Cache AFANA soy aoe Select the General Tab Oem ces STE eee Click the Settings Button under Temporary Internet T Reston artane et preat hot o
125. ind any errors or omissions please contact us in writing 164 Panasonic Matsushita Electric Works Ltd 1048 Kadoma Osaka 571 8686 Japan Telephone 81 6 6908 1860 2006 Matsushita Electric Works Ltd All rights reserved 791 C58 0000 1 Printed in Japan
126. ing can be performed either from this window or by setting the DIP switch on the Unit 6 Other Click the Reset Button to display the current network settings Click the Clear Button to clear all entries 7 Factory default values Host name host Local network Use the following IP address IP address 192 168 0 1 Subnet mask 255 255 0 0 Default gateway Blank Global address settings Do not use global IP address 41 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 2 Authentication The user s access rights user name and password can be registered or deleted in the Authentication Dialog Box Location name System Administration gt Authentication Add New User Access Rights Basic Monitoring User v User name Password Retype Password cear Delete User Basic Monitoring Users Basic Control amp Monitoring Users Advanced Users Administrators monitor control advanced admin cannot delete cannot delete onnecte i Registering a User Add Change Perform these settings under Add New User 1 Select the access right from the pull down menu in the Access Rights field Types of Access Rights are described as follows Basic Monitoring User Enables monitoring only of lighting circuits operations Basic Monitoring amp Control User Enables monitoring and control of lighting circuits operations A
127. ings a Reboot of the Web Server Unit is necessary to enable changes to astronomical clock settings Click the Go to reboot page button and proceed to rebooting the Web Server Unit iii Specifying a custom time zone and daylight saving rule It is possible to specify a custom time zone and daylight saving rule 1 Select custom time zone From the Time Zone drop down menu select Custom time zone option This will make visible the time zone editor controls just below the Time Zone drop down menu 2 Select GMT Select the difference in hours with the Greenwich Mean Time GMT also refered as Universal Time Coordinated UTC in the GMT drop down box The following chart maybe used to be determined the standard time zone 3 Specify the Daylight saving start and end rules From the Daylight saving start and Daylight saving end drop down menus specify the rules for daylight saving start and end e g for the following rules to be enabled selections should be made as the shown in the following picture s Daylight saving start rule April s first Sunday at 02 00 a m e Daylight saving end rule October s last Sunday at 03 00 a m Daylight saving start April v First v Sunday 02 ia OO vidal email Sic October fe Last __ ie Sunday 03 00 za 4 Click the submit button A confirmation window showing the specified values will be displayed If the specified values are correct click the
128. ini ccnn Sunise OFF Schedule Settings z R 20 20 0N Programs 002 Program 002 01 Group 001 Sunset ON OFF 22 00 OFF ape 006 Program 006 01 Individual Circuit 01 1 OFF ON VIRO CEF spans Da 5 S 18 00 ON Special Days Calendar i 7 7 i IES mains EE Manet 00 Program 00 01 Pattern 02 Repeat Execution 17 00 Start 30 min Dimmer Settings R cuit 01 3 2 g 06 00 OFF 008 Program 008 01 Individual Circuit 01 3 OFF OFF 08 00 OFF 1 Select the date Select the month day year and click the Select Button Clicking the lt lt or gt gt Button will move the selected date back and forward Clicking the Today Button will reset the date to the current day Programs Programs displays all the programs executed on the specified day in a table No Number of program to be executed e Name Name of program to be executed e LIU No LIU number Type Type of address 9 Address Address Control Value Status in zone controls Time Control start time to end time e Operation Time control sunrise sunset control inter day control or repetitive control Special Days Special Days display a list of special days e No Number of the special day 9 Name Name of the special day 902 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings If ON and OFF operations are specified for the same address at the same time both program contents are displaye
129. irmation and registration from another browser will be disabled while the Transmission Unit is communicating with the Web Server Unit 3 Select addresses circuits to control Select the row number for individual circuit and dimmer address circuit for which to perform pattern control control to replay the registration scene Content Exclude from pattern control or Circuit ON OFF Timer Timer control is enabled when ON The following values can beapplied up to 8 circuits per pattern On timer for 30 s 1 min 5 min 60 min or 120 min Off delay by 30 s 1 min 5 min or circuits without timers On timer Turns OFF when specified time elapses after turning ON Off delay When patterns match lighting turns ON first and then OFF control is performed turning OFF after the timer has timed out This behavior appears exactly the same as the On timer Off delay control is selected with timer value as ON Dimmer level Enter the dimmer level for ON status Range of values 1 to 128 for individual circuits addresses and 1 to 7 for dimmer addresses The smaller the number the brighter the light will be Refer to Miscellaneous Appendix for specifications of dimmers Devices not used as dimmers but as relay controls should be set to 128 Clicking All ON All OFF or All Ignore Button set all individual circuit and dimmer addresses to the same content By selecting Patterns Settings in the menu frame it is possible to retu
130. is responsible for the damages Revisions Information contained in this document is subject to change without notice WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Package Contents Check that the package contains the main unit and accessories before using the product If anything is missing please contact your retailer or Matsushita Electric Works Ltd FULL 2WAY Web Server Unit Pane Use User s Manual WR3330 801 1st edition WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Before Using This Product Read and understand this user s manual thoroughly before using the product Requirements for Use 1 Purpose and Usage of the product The product and related products have been developed mainly for lighting control applications Therefore do not use the product for security applications such as crime prevention protection from disasters or other applications involving protection of human lives Other general requirements Please ensure easy recovery of any system failure i e data backup etc Please ensure safety of system usage by installation of protective devices protective circuits or by any other means deemed appropriate Please ensure that incorporation of this product with any other components or products as a system is done with respect to the above mentioned safety instructions 2 Operating Environment Products compatible with the FULL 2WAY
131. it If the Cancel Button is clicked registration will be aborted and you ll return to the Address Setting Page If the Delete Button is clicked the contents of the global addresses will be reset to blank 85 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings Cautions on Setting Schedules If operations for global addresses in scheduling Programs include OFF controls such as ON OFF patterns cannot be selected for global address setting Pattern control will be restricted to ON match Scheduling in Programs must be changed first to enable using patterns Program numbers with registered global addresses are displayed as Registered Programs number XX in the editor page This display will be always shown regardless of the Enable Disable settings of schedule controls Factory Settings Action Add New For all global addresses Global Controls i Concept of Global Global controls are a method of monitoring and control where multiple local systems exist and specified multiple systems are managed using the same address Addresses controlled here can be individual circuits dimmer group and patterns Zones are not independent in terms of systems and therefore not applicable Control points addresses will be restricted to one address of one type Global control is characterized by the ability to define control points for multiple systems using the same add
132. iven in text e g TIMER If the connection from the Web Server Unit to the NCU to the LIU to the Transmission Unit is cut all address statuses will be displayed as indeterminate Statuses of addresses disabled in the LIU Connection Settings will be displayed as indeterminate ii Controls 1 Click the red green button in the Status column A dialog box as the one displayed below will open sere Symbols in indeterminate state cannot be selected E Does not apply to On timer and Off delay timer controls Does not apply to dimmer level controls 2 Click the button for the status to control anii The dialog box will close and the status will change a iii Viewing the Dimmer Level Dimmer level unknown Get Level Cancel The dimmer level can be verified manually for each address Jara ple Woden Only addresses whose level display has been enabled in the Dimmer Settings can be viewed 1 Click the Get Level Button in the Dimmer Level Dialog Box A dialog box will open such as the one below 126 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control 2 Click the Get Level Button The dialog box will close 3 Wait for a while 4 Click the Get Level Button in the Dimmer Level Dialog Box A dialog box will open with the dimmer level being displayed Dimmer Level Value Table Displaying the dimmer level for group addresses requires th
133. l amp Settings gt Dimmer Settings gt Individual Circuits ee LIUNo 01 y Advanced Control amp Settings Address Settings Map1 Address Name Level Display Address Name Level Display Advanced Control 00 1 Individual Circuit 00 1 Enabled v 32 1 Individual Circuit 32 1 Disabled v ear 00 2 Individual Circuit 00 2 Disabled v 32 2 Individual Circuit 32 2 Disabled areara E i 00 3 Individual Circuit 00 3 Disabled v 32 3 Individual Circuit 32 3 Disabled v we 00 4 Individual Circuit 00 4 Disabled v 324 individual Circuit 32 4 Disabled v Eee 01 1 Individual Circuit 01 1 Disabled v 33 1 Individual Circuit 33 1 Disabled v Groups y 01 2 Individual Circuit 01 2 Disabled 33 2 Individual Circuit 33 2 Disabled v T 01 3 Individual Circuit 01 3 Disabled v 33 3 Individual Circuit 33 3 Disabled v 01 4 Individual Circuit 01 4 Disabled v 33 4 Individual Circuit 33 4 Disabled v 02 1 Individual Circuit 02 1 Disabled v 34 1 Individual Circuit 34 1 Disabled v 02 2 Individual Circuit 02 2 Disabled v 34 2 Individual Circuit 34 2 Disabled 02 3 Individual Circuit 02 3 Disabled v 34 3 Individual Circuit 34 3 Disabied v 02 4 Individual Circuit 02 4 Disabled v 34 4 Individual Circuit 34 4 Disabled a Cod 1 Select the LIU No for the system and click the Select Button The currently registered data will be displayed Only numbers enabled in LIU Connection Settings can be selected 2 Select Enabled Disabled for the level display
134. l not be changed until the display is refreshed To enable refreshing select Enable Automatic Reload of Basic Monitoring amp Control Pages in the Page Reload Settings If the connection from the Web Server Unit to the NCU to the LIU to the Transmission Unit is cut all address statuses will be displayed as indeterminate Statuses of addresses disabled in the LIU Connection Settings will be displayed as indeterminate ii Controls Please refer to previous section II List Window Operations ii Controls for further details on how to use control windows iii Dimmer level monitoring and control The dimmer level at each address can manually controlled and monitored with the gauge display format such as described in the following figure J ea Numb C t Level Level Level The dimmer level can be easily retrieved and m displayed as described in II List Window PB fe e foe fom fo Operations ii Controls step 3 fe ff mee fom fe This status display uses port 60071 If this port is closed the display of status will not be changed until the window is refreshed The dimming level cannot be monitored for a global address even if the global address is defined individually Tee er oe ER P 120 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control IV Advanced Control When logged in with Settings or System Administration right adv
135. ll pattern addresses with LIU units Displays all zones Displays all global addresses Configures group settings with Transmission Units Configures pattern settings with Transmission Units Configures zone settings with NCU LIU Here zone is a method of controlling the set status pattern of the specified area Configures global settings Here global is a method of comprehensively controlling one global point shared by multiple systems Configures how circuits are automatically controlled on specified dates Configures the contents of schedule control programs Confirms control scheduling for specified data Configures days such as national holidays when Special functions are to be performed Confirms special day settings and overlapping Sets sunrise sunset functions and daylight savings time functions Sets names for control items Displays all individual and dimmer addresses with LIU units Displays all group addresses with LIU units Displays all pattern addresses with LIU units Displays Zones Displays global point addresses 20 e 7 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Product Description Dimmer Settings Individual Circuits Groups Status Bar Manager c System Administration Menu Network Settings Authentication Date amp Time Settings RS 232C Settings LIU Settings Page Reload Settings Proj
136. lock is not set Set the clock to the correct date and time in Date amp Time Settings 1 Select the special day Or ree eT Click the Add New or Edit Button of the line Up to mms 30 The page will switch to the Special Day Setting Page eae Programs including the day as an execution special Se ie Rea day will be displayed in the lower pane Disabled ee a eae programs are also displayed es Enen 2 Enter the name of the special day a ne Enter Text in Name field In 16 characters or less Characters that are not iso 8859 1 will be corrupted 3 Click the Next Button The page will switch to Special Day Setting Method Selection Page If the Cancel Button is clicked the registration will be aborted and the page will be switched to Special Day Number Selection Page 4 Select the special day setting method Select the following in the special day settings eee e eee Days of the Week Specify as Month X Week Y 2 an Day of week Z E Days of the Month Specify as Month X Day Y tome OO Dates Specify as Month Y Day Z Year X os Summary Will display special day settings in a table 94 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings Three methods can be mixed for one special day setting 5 Click the Select Button The page will switch to setting window for the selected method A Days of the Week Every Ye
137. luded in iso 8859 1 CP932 will be corrupted Ifa comma is entered an error message will be displayed after the Submit Button is clicked Some names such as 32 characters long ones may be displayed with both ends truncated 3 Click the Submit Button The settings will be applied to the page Factory Settings Name Pattern XX XX 01 to 72 107 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings d Zones Zones is used to set names for all zones by LIU system Submit SM zone fone SW zone id ones Zone 03 Zones Cid Zones 04 Zone 04 Zones o ooo da Zone52 o o o ooo O rs Zone 05 ZoneOS Zone53 O O o ooo 0 Zone 06 mo Zone 07 ZoneO7 sd Zone55 SSS O me Zone 08 Zoneo8 sd EA Zone 56 Zone56 sd P zones a e zone S Zone 13 Zone 61 The currently registered data will be displayed 1 Enter the names Number of characters 32 characters or less Characters not included in iso 8859 1 CP932 will be corrupted If a comma is entered an error message will be displayed after the Submit Button is clicked Some names such as 32 characters long ones may be displayed with both ends truncated 2 Click the Submit Button The settings will be applied to the page Factory Settings Name Zone XX XX 01 to 96 108 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp
138. mers 1 to 127 groups 1 to 72 patterns 1 to 96 zones or 1 to 32 global addresses LIU numbers types and addresses for unused list numbers are all Zeros e Address File Name address csv screen No 1 to 99 in ascending order Icon No 1 to 256 in ascending order LIU No 1 to 31 0 for zone and global address TYPE individual circuits D dimmers G groups P patterns Z zones or gb global addresses ADDR No 00_1 to 63 _4 individual circuits 1 to 16 dimmers 1 to 127 groups 1 to 72 Patterns 1 to 96 zones or 1 to 32 global addresses LIU numbers types and addresses for unused symbol numbers are all Zeros 154 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Miscellaneous Information e Groups File name groupXX csv XX denotes the two digit system LIU number 01 31 LIUXX LIUO1 to LIU31 Group address 001 to 127 in ascending order Type individual circuits or D dimmers Address 00_1 to 63 4 individual circuits or 1 to 16 dimmers Timer O no timer 1 On timer for 30 s 2 On timer for 1 min 3 On timer for 5 min 4 On timer for 60 min 5 On timer for 120 min 1 Off delay by 30 s 2 Off delay by 1 min or 3 Off delay by 5 min Described for group downloads and uploads only e Patterns File Name patternXX csv XX denotes the two digit system LIU number 01 31 LIUXX LIUO1 to LIU31
139. monitoring rights monitoring only 2 Basic monitoring amp control rights 1 control 3 Advanced control amp settings rights 2 advanced control amp settings for control amp monitoring 4 System administration rights 3 Settings for system administration 19 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Product Description 3 Menu Descriptions a Basic Monitoring amp Control Menu Maps selection Basic Monitoring amp Control list b Advanced Control amp Settings Menu Maps selection for Address Settings Advanced Conirol Individual Circuits Groups Patterns Zones Global Addresses Group Settings Pattern Settings Zone Settings Global Address Settings Schedule Settings Programs Program Monitor Special Days Special Day Calendar Astronomical Clock Name Settings Individual Circuits Groups Patterns Zones Global Addresses Selects maps to monitor and control Monitors and Controls the lighting status of items at specified addresses in a table format Addresses to display can be selected with either the advanced control amp settings or administration rights Selects maps by name to allocate addresses to symbols Monitors and controls the lighting status of all circuit addresses in a table format Displays all individual and dimmer addresses with LIU units Displays all group addresses with LIU units Displays a
140. n or 120 min Off delay 30 s 1 min 5 min Dimmer level of the circuits 1 Dark to 128 Bright Fading dimmer time Immediate No fading 2 s 6 s and 1 min LIU connection configuration must have been completed before setting patterns NCUs LIUs and Transmission Units must be connected for configuration Up to eight timers total can be used per pattern for On timers and Off delays combined 4 Zone Settings Number of registrations 96 max Applicable points Patterns of connected LIUs 72 max per Transmission Unit Modes 2 3 4 and 6 LIU connection configuration must have been completed before setting zones NCUs and LIUs must be connected for configuration Modes can be arbitrarily selected for each zone number Zone settings will be retained even if the LIU is disconnected in LIU connection settings 5 Global Address Settings Number of registrations 32 max Applicable points Individual circuits dimmers groups and patterns of connected LIUs Operations on statuses Logical AND and logical OR LIU numbers can be configured regardless of LIU connection setting status Controls do not apply to zones 6 Schedule Settings Number of programs 930 max No limit per Transmission Unit Program names 16 characters max iso 8859 1 CP932 Applicable points Individual circuits dimmers groups patterns global addresses and zones of connected LIUs Operations Indivi
141. n 4 4 Enter the pattern address number to assign to each zone status The pattern number selected for the LIU system Transmission Unit in 2 is set to the same Zone number line Range of number 1 to 72 The same pattern number cannot be set more than once in the same LIU system regardless of zone numbers 81 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 5 Repeat 2 to 4 for other addresses 6 Click the Submit Button The contents shown on the page will be registered in the Web Server Unit NCU and LIU If registration is performed during successive control operations or system errors such as an NCU interconnection errors occur processing will be interrupted due to timeouts and System error occurred or communications with FULL 2WAY system congested with other controls will be displayed in the status bar If the Web Server Unit is shut down while registration communications are in progress rebooting will still result in unsuccessful registration Reboot NCU and LIU Zone Setting Data Integrity Zone settings are stored in the Web Server Unit NCU and LIU If they are not identical monitoring and control will not function properly When connecting to a NCU and LIU that underwent zone setting separately their settings must be checked for integrity When NCU is selected for the unit and the Select Button clicked the Web Server Unit will
142. nd other information 2 Map Data File Format Proprietary format Number of maps that can be managed 99 max Window data created in excess of the maximum number of maps cannot be transferred to the Web Server Unit Map data volume Approximately 8 MB Web Server Unit available storage space Map data files to be transferred to the Web Server Unit have the following extensions html ezs hsl hpf iiu_screenXX where XX is the map number from 01 to 99 jpg gif The number of maps that can be stored transferred will decrease as the data per map increases It is recommended to verify the web server unit unused memory capacity in Data Monitor before adding map data to the Web Server Unit Data in Web Server Unit memory can be deleted in Data Manager or Factory Settings 68 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 3 Monitoring and Control Symbols Buttons symbols that have special functions to process lighting circuits specific to the FULL 2WAY Remote Control system are used on the windows lf these symbols are placed on the maps they may be assigned addresses of FULL 2WAY Remote Controls from Address Settings on the Web browser providing functionality equivalent to switches 4 Transferring Data Files Data files are transferred between the PC on which the map drawing software is running and the Web server Unit via Ethernet The PC for
143. ng fixt Selecting P G number in a browser P G control content a ai 2 P G control request to NCU P G control content acquisition P G control request to LIU by NCU Confirming P G control from P G control content acquisition by Transmission Unit Web Server Unit General purpose PC Monitor Reloading browser page Reloading browser page or amp control configuration 2 P G Settings Control Content Content Change o WR3330 801 WR3387 8 WR3388 8 Web Server Unit NCU LIU ERER mi om 1 P Transmission Unit Switch lt p To lighting fixture D Editing P G control in a browser Contact output status D P G control setting request to NCU Status acquisition by NCU AU 3 P G control setting request to LIU Status acquisition by Se e ee SSS eee SEE SN A a a ee 4 P G control setting request to Web Server Unit Transmission Unit Reloading browser page General purpose PC Monitor Reloading browser page or amp control configuration Pattern and group settings are stored in the Transmission Units 11 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Summary 6 Zone Settings on the Web Browser In principle zone controls in this system are performed on the Web window in the Web Server Unit 1 Zone Number Selection Confirmation of Control Content a T lt RC232C i WR3330 801 WR3387 8 WR3388 8 H Web
144. ning using the setting data on the Web Server Unit Comparison of zone settings takes about a minute and a half at most so it is recommended to select Yes Under normal operating conditions comparison need not be performed once the zone settings are registered When zone settings are uploaded to the Web Server Unit in Upload Manager page the data is registered as the settings for the Web Server Unit but not for NCU and LIU yet It will thus be necessary to register them manually by moving to the zone setting page and clicking the Submit Button Whenever zone settings are uploaded error message Setting data inconsistencies will be displayed in the status bar Requirements for Zone Operations Conditions on the Contents of Patterns In zones multiple conditions in one zone within address range of the circuit are assigned as patterns but in principle patterns contained in one zone should have the following characteristics otherwise 8 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings monitoring and control may produce unexpected results Control areas for the patterns must be the same That is the areas excluded from pattern settings must be the same The contents for patterns must all be distinct Additionally ON and OFF must be suitably set in the pattern Factory Settings Zones configuration verification at boot time No LIU No
145. nits 256 individual 16 dimmer circuitsx 31 systems 5 max This is the maximum number of CGls concurrently executed and not the maximum number of connected PCs Accesses exceeding this limit will wait in a queue and displays will be delayed Simultaneous operations from multiple browsers on one CGI may suffer from display problems and operational delays due to applet specifications and client PC performances Network Control Units Local Interface Units Transmission Units Capabilities NCU WR338 7 8 connections LIU WR3388 8 connections controls Individual Control Circuits Simultaneous accesses Time required for booting Network error detection time Network recovery detection time NCU connection error detection time NCU connection recovery detection time Local bus error detection time Local bus recovery detection time FULL 2WAY signal error detection time FULL 2WAY signal recovery detection time Pattern group setting detection time Pattern group recovery detection time Web window reload time Approx 2 to 7 minutes 1 minute max 1 minute max 1 minute max 30 seconds max 1 minute max 3 seconds max 3 seconds max 3 seconds max 3 seconds max 3 seconds max 5 seconds or more when using PORT443 and 6001 30 seconds or more when NOT using PORT6001 Depends on the connection status of user network environment 136 WR3330 801 FULL
146. no match and Not set Pattern A Pattern B Pattern C Pattern D Pattern E and Pattern F ON and OFF Timed denotes a status controlled by the timer function of a Transmission Unit and not by the schedule program timer control function of the Web Server Unit Dimmer levels for individual circuits dimmers and groups can be monitored only if they are defined with points Dimmer levels are 128 gradations for individual circuits and dimmers and 7 gradations for groups 140 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information If the status of a zone does not match the status defined in each mode other status it is assumed to be pattern C When zones are used in mode 2 other zone statuses are monitored with pattern C Refer to the product specifications of NCU WR338 7 8 for details on Zones Only individual circuits dimmers groups and patterns but not zones can be set as points to be monitored with global addresses Statuses of global addresses are logical AND or logical OR of the points For these logical operations timed status is treated as ON match and No T U Not set is treated as OFF no match Dimmer levels of global addresses cannot be monitored 3 Control Status Individual Circuits ON and OFF e Dimmers ON and OFF Groups ON and OFF e Patterns ON execution Zones Pattern A Pattern B Patt
147. normal Address Settings Map1 Advanced Control amp Settings gt Group Settings LIU No 01 Group 001 Name Group 001 SelectAll Unselect All Individual Circuit Adieu Name Status Timer 00 1 Individual Circuit 00 1 Unselect v 00 2 Individual Circuit 00 2 Unselect v 00 3 Individual Circuit 00 3 Unselect 00 4 Individual Circuit 00 4 Unselect v 01 1 Individual Circuit 01 1 Select lf v 01 2 Individual Circuit 01 2 Unselect lon imer for 30 s 01 3 Individual Circuit 01 3 Unselect Mone for 1 min 014 Individual Circuit 01 4 Unselect ee niga 02 1 Individual Circuit 02 1 Unselect v ae i ace 02 2 Individual Circuit 02 2 Unselect v LOf delay by 5 min 02 3 Individual Circuit 02 3 Unselect v 4 Individual Circuit 004 LIincelert v 7 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 2 Select an address number Click the Add new or Edit Button for the address to register The communications for the Web Server Unit to obtain registered data from Transmission Units will start and the window will switch to an editable page when communications have been completed Data transfer in progress Please wait will be displayed in the status bar until the editable window opens less than a minute Confirmation and registration from another browser will be disabled while the Transmission Unit is communicating with
148. not be selected 7 Click the Select Button The calendar for the selected month will be displayed 8 Select M the desired days 9 Click the Add Button Switching calendar pages without clicking the Add Button will clear the check marks M 10 Repeat 6 through 9 Data has not yet been registered in the Web Server Unit 11 Return to 4 for other setting methods 12 Click the Submit Button Special days selected in all three methods will be registered 95 Special Day Settings Dates gt Always press the Submit Button on following occasions Before charging the special day type Before specifying special days for another month WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings If the Cancel Button is clicked the registration will be aborted and the page will be switched to the Special Day Number Selection Page If no special days are selected after the name is entered the name will be initialized when the special day is registered If a past date is selected for a special day for a date setting it will be retained until the date is set again ii Deleting Special Days 1 Click the Delete Button The selected lined up to 30 will be reset to Blank Schedule control by programs specifying execution special days will not be performed after special days have been deleted but if the control start time has passed when the special day is
149. ns Button Sanaa 2 Select a LIU number 3 Select the address range groups patterns 4 Cli ck th e D ownl oa d Butt on lacks specu or you do ret uly tust the sore do not open File name list csv Communications to transmit data from the selected at LIU system Transmission Unit to the Web Server Unit T Open Save Cancel More Info will be initiated When this transmission is in progress the Data transfer in progress Please wait message is displayed Wait until the message changes to Connected and the communications are completed Responses may be delayed or not occur during the operation When the Pause Button is clicked communications with the Transmission Unit are interrupted but data up to that point is obtained While data is downloading downloading from other browsers is disabled System Errors cannot be detected while downloading is in progress Old CSV files are also displayed so delete them under Temporary download files in Factory Settings 5 Click on the file name The File Download Dialog Box will be displayed 6 Click the Save Button in the File Download Dialog Box The Save As Dialog Box will be displayed 7 Enter the file destination and name in the Save in and File name fields and click the Save Button 59 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 12 Upload Manager The Upload Mana
150. ntrol Section IV Advanced Control Operations for details on window operations for monitoring and controlling 7 6 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 4 Group Settings Group Settings is used to configure group control settings for Transmission Units of each system Location name Advanced Control amp Settings gt Group Settings ee ene LiUNo 01 Settings Address Name Action Address Settings Mapi 001 Group 001 Adv trol 003 Group 003 Group Settings Sao o on Sctedle Stings 005 Group 005 007 Group 007 EE System Administration a aout 009 Group 009 010 Group 010 011 Group 011 012 Group 012 1 Select the system LIU number Select a LIU No and click the Select Button The registration status of the Transmission Unit will be shown Only LIU numbers that have been registered in LIU connection settings can be selected Settings are saved in the Transmission Unit Therefore LIUs and NCUs must be connected when these parameters are written Those parameters are not stored on the Web Server Unit When the Web Server Unit has booted with local devices and channels in error status registered parameters cannot be obtained and they all will be shown as Add new If the system errors are then corrected the Add new indications will not be refreshed The menu command must be selected to refresh the page after the system becomes
151. nuous operation will reset the error condition and disable the errors even when continuous operation is resumed 13 If controls are run locally or from a browser while transmitting patterns groups settings and download upload settings processing will result in longer that usual execution times for both 14 Download upload transmissions for patterns groups settings will cause error displays after a forced termination of the Web Server Unit 2 minutes but the LIUs that continue processing may complete the process before the LIUs are forced to terminate 15 If controlled addresses do not actually exist or are not recognized registration errors and address setting errors in the controlled T U or disconnection in patterns groups controls system errors FULL 2WAY signal errors may be reported Check that individual circuit devices subject to controls function normally beforehand 16 Local bus errors or FULL 2WAY signal errors may not be reported during patterns groups settings made asdescribed in 1 to 4 below until forced termination is completed 2 minutes 1 The Edit or Add new Button is clicked in the Patterns Groups Settings Page 2 Submitting Patterns Groups Settings 3 Downloading of Patterns Groups CSV Files 4 Uploading of Patterns Groups CSV Files 17 Settings and registration during the power down period during the reboot operation in the browser will not be completed and will not be effective after rebooting 18 LIU
152. o much the settings for the baud rate 19 200 bps word length 7 bits and parity even and set the same parameters on the NCU Baud rate 19 200 bps Pin 1 of switch 1 ON Pin 2 OFF Pin 3 ON Pin 4 of switch 1 OFF Pin 5 of switch 1 OFF Pin 6 of switch 1 OFF The word length of 7 bits cannot be set if parity is set to none 2 Set the baud rate on the local network Set to 19200 bps Baud rate 19 200 bps Word length 7 bits Even parity Se E mE M Pin 7 of switch 1 ON 3 Set zone command specifications Set to 1 Zone command specifications 1 Pin 2 of switch 2 ON 4 Set the status change notification for patterns groups and zones Set the corresponding DIP switch pins to Yes ON if notifications are necessary All pins are set to Yes in the example Pattern status change notification Yes No Group status change notification Yes No Pin 4 of switch 2 ON OFF Zone status change notification Yes No Pin 5 of switch 2 ON OFF Status change notification DIP switch pins on the LIU must be set to the same values Pin 3 of switch 2 ON OFF 5 Set unused pins Always set unused pins to the values indicated below Pin 8 of switch 1 OFF Unused Pin 1 of switch 2 OFF Unused 6 Press the Reboot Button switch 3 When all settings have been completed always cycle the power or press the Reboot Button to enable the changed settings 2
153. ols will be retained even if the LIU is disconnected in the LIU connection settings Addresses cannot be assigned to actual circuits T U in a browser page Layout of symbols for lighting circuit controls must be performed using the separately available the Screen Builder for Web Server Unit WR3339 801 If the symbol number of the circuit symbol is assigned to a circuit name symbol and dimmer level symbol and they share the same circuit the circuit addresses will be interlocked 2 Group Settings Applicable circuit address Number of connected LIU Dimmers 256 circuits 16 circuits max per Transmission Unit Value to set for the circuit Out of area ON and timer Value for the circuit timer On timer for 30 s 1 min 5 min 60 min or 120 min Off delay 30 s 1 min 5 min LIU connection configuration must have been completed before group settings are made NCUs LIUs and Transmission Units must be connected for configuration Up to eight timers total can be used per group for On timers and Off delays combined 142 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information 3 Pattern Settings Applicable circuit address Number of connected LIU Dimmers 256 circuits 16circuits max per Transmission Unit Value of status for the circuit Out of area OFF ON and timer Value for the circuit timer On timer for 30 s 1 min 5 min 60 mi
154. on from a web Ses inte rnet v Web Server Unit NCU LIU Control can be erformed from a web rowser Control history canbe recorded displayed and downloaded in CSV format to aPC A spreadsheet eae can be used o comprehend and manage ON OFF Using IT enables conservation of energy and power in multiple buildings patterns Lighting in not only one but also multiple buildings can E be comprehensively controlled through the network nagy saying products imara and sensors for je E Full 2 Vay Remote Control can continue to be used Without physically going to each building lighting patterns can be changed enabling sophisticated energy conservation and system diagnosis and backups can be performed in a web browser Central Control of Large scale Systems Multiple FULL 2WAY lighting systems can be controlled from a single or multiple PC Network Connection Remote control is possible from a Web browser through an intranet or the Internet Customized Interface Monitoring and control windows maps that match the actual facility can be easily constructed Programmable Controlling A timer inside the Web Server Unit enables detailed schedule control Data Management and Editing Various data can be downloaded and uploaded in CSV format WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Summary Functions The functions of the Web Server Unit can be split de
155. one Settings view 5 Initializing Red Indicates that the Web Server Unit is being initialized It is recommended that you wait until the initialization process has been completed before performing any operation 6 Data transfer in progress Please wait Red Indicates communications with the NCU such as group settings pattern settings zone settings and LIU Settings are in progress It is recommended that you wait until the initialization process has been completed before performing any operation If connection become disabled this message might be displayed for approximately 5 minutes 7 Performing setup Red Indicates that the Performing setup status has been enabled The display of this status message is not a result of any setting operations but is enabled intentionally by a user with Advanced Control amp Settings righs System Administration rights It is presumable that the display of this message is done concurrently with some setting operation 8 Connected Green Indicates that normal operations can be performed This status is not displayed until all errors and warnings have been cleared 133 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control 2 System Error Monitor Displays 1 NCU connection error NCU communication error include NCU power interruptions a broken RS 232C cable incorrect wiring and or a communication setting error in the NCU DIP
156. onnect the Web Server Unit directly to the PC 4 Set the network parameters for the PC For details refer to 3 Setting network parameters for PC 5 Configure the Web browser on the PC For details refer to 4 Setting browser parameters for PC 6 Enter the address URL of the Web Server Unit in the browser and connect to it For details refer to 6 Opening the home page of the Web Server Unit 7 The start page will be displayed if it is connected Log in with the system administration right User name admin Password admin Other windows will appear for other authentication rights but always click the Yes Button to proceed For details refer to 6 Opening the home page of the Web Server Unit 8 Set the actual network parameters user defined in the Network Settings window For details refer to System Operation and Administration in Administration and Setting 9 Set the Network Configuration to user setting by changing pin 1 of the DIP switch on the front of the Unit to user settings and press ON the Reboot switch The steps above will reboot the Web Server Unit with user defined parameters b If network parameters user defined have been set for the Web Server Unit 1 Set the Network Configuration to user setting by changing pin 1 of the DIP switch on the front of the Unit to user settings and press ON the Reboot switch 2 The Web Server Unit will reboot with user defined network parameters It will take 2 to 7 minutes to
157. out descriptions when uploading will be deleted unregistered Start time and end time for sunset sunrise will be ignored when uploading Names LIU numbers and Enable Disable are blank for unused schedule numbers 157 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Miscellaneous Information e Special Days Annual Month X Yth Z Day of Week File Name Special_ Week csv Special day number 1 to 30 in ascending order Name 16 characters max Month 1 to 12 Week 1to5 Sun to Sat O not special day or 1 special day Descriptions are provided only for special days o Special Days Annual Month X Day Y File Name Special_day__every csv Special day number 1 to 30 in ascending order Name 16 characters max Month 1 to 12 Day 1 to 31 Descriptions are provided only for special days sh te Days Year X Month Y Day Z File Name Special_ day_once csv Special day number 1 to 30 in ascending order Name 16 characters max Year 2000 to 2037 Month 1 to 12 Day 1 to 31 Error occurs if date in not within 13 months of upload date Descriptions are provided only for special days 198 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Miscellaneous Information e Individual Circuit Names File Name i_ nameXxX csv XXdenotes the two digit system LIU number 01 31 4 Address Name D Individual Circ
158. pending on the different user rights as follows Advanced Control amp Settings Address Settings Advanced Control M aps Individual Circuits Bones CZonesetings CD C siny Special Day Calendar E a clock CO Ra css CO zone C oiov Adsense C Groups O WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Summary System Administration i Network Settings Authentication Date amp Time Settings RSAC Settings LIU Settings WE Page Reload Settings 3 Project Display Settings System Error Settings eyetem Errors Download Manager Upload Wanager Run Command Map Monitor Map Manager Factory Settings Reboot WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Summary ll Operating Principles of Major Functions The system configuration and data flow are explained here The system configuration is based on the system shown in the following diagram The actual control of lighting fixtures requires devices on the lighting control local system namely a FULL 2WAY Remote Control consisting of Network Control Units NCUs WR3387 8 Local Interface Units LIUs WR3388 8 Transmission Units WRT2050 80 WRT2040 82 81 894 Series and their terminal circuits T Us Switches etc The Web Server Unit functions as the interface between the PC client connected through the Ethernet on the network side of the system and
159. preventing the user from operating the browser In this situation press the ALT Tab keys simultaneously to display the Windows task switcher view Select the Java icon in the tag switcher view by pressing the ALT Tab keys This will bring back the Java warming authentication dialog box From there proceed as described above If the user name or password that had been entered at login is not entered correctly three times in succession or if the Cancel Button is clicked the Authentication Required Window will be displayed In this situation the browser must be closed and then reopened Java applets and the browser run on the client computer so if the computer does not have sufficient resources they may not function properly 115 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control Il List Window Operations In this section monitoring control and setting operations in the List Window are described The List Window provides access to frequently monitored and controlled lighting circuit addresses which are displayed conveniently in a list as a table The List window accessed by clicking the List item in the side menu frame allows monitoring control and setting of addresses as described in the following table Basic Monitoring Rights Monitoring only Basic Monitoring and Control Rights Monitoring and control Advanced Control amp Settings Rights Monitoring control and setting
160. r s Manual Monitoring amp Control 5 Advanced Control Global Addresses Global Addresses Points 01 to 32 Advanced Control amp Settings gt Advanced Control Location name Basic Monitorning amp Global Addresses Control Ades Stings o cioban Address 02 Map fes Covet adress os fea CStcbat Adcress ofS fos CSch dares os CS Agcansed Control fes CStcha Adcress 6 CS ee fr C Ccba cress OCCOC C C CS CSCSCS Pattems Ca o CCSC C d Cinta Addresses fea S CStcba Acres 09 CCS Group Settings fo SCS Adress to CCSC C d ee Ca Global Address Settings Ea 2 CC d ae ES Global marese 17 l Global Mareas 19 oan Pi mkt a awnwnwn DA i Monitoring All 32 global addresses are displayed in one window The statuses of the selected addresses are displayed in the Status Fields Individual Dimmer Group Patterns ON Lore e me fe As shown in the figure ON is indicated in red OFF in green indeterminate No T U or unregistered in gray and details are given in text e g TIMER If the connection from the Web Server Unit to the NCU to the LIU to the Transmission Unit is cut all address statuses will be displayed as indeterminate ii Controls 1 Click the red green button in the Status column A dialog box as the one displayed below will open every Gtobato2 Symbols in indeterminate state cannot be selected sesso Global Addresses02 ON OFF Cancel Exe
161. re 1 Check the operating environment of the PC Users must prepare the following client PC environment The information provided in this manual assumes that this environment is being used 1 Hardware Requirements The following must be used LAN port Modular socket to connect to Ethernet requires a LAN card or board to be installed in advance Input device Mouse and keyboard The following are recommended Memory 128 MB min Graphic adapter 1024 x 768 dots XGA 256 colors or better 2 Software Requirements The following are all required OS Microsoft Windows XP Operating System SP1 or SP1a recommended Web Browser Microsoft Internet Explorer Version 5 5 or later Version 6 0 recommended Java applets Sun Microsystems Java 2 Platform Standard Edition Version 1 4 2 J2SE Java installer is included in the accompanying CD 29 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Installation Section 2 Set the network address for the Web Server Unit a If network parameters user defined have not been set for the Web Server Unit 1 Set the Network Configuration using pin 1 of the DIP switch on the front of the Unit to default and turn ON the Reboot switch 2 The Web Server Unit will start up with the following parameters e P address 192 168 0 1 Subnet mask 255 255 0 0 Rebooting takes about 2 to 7 minutes 3 With these parameters set c
162. reboot 3 Connect the Web Server Unit to the actual onsite network and check the settings for peripheral devices such as routers For details refer to 5 Setting network peripheral devices 4 to 8 Same as the procedure in the preceding section so refer to the previous section a to 9 To enable the settings reboot the Web Server Unit in the Reboot menu The steps above will reboot the Web Server Unit with user defined parameters 30 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Installation Section 3 Set the network parameters for the PC Set the IP address subnet mask and default gateway Set the parameters according to the connected network in the Internet protocol TCP IP properties window as described below For details consult the network administrator of the network to which you are connecting The details below are based on the TCP IP setup window of Microsoft Windows XP Operating System a Connecting to an Intranet 1 Select Control Panel from the Start Menu 2 Select Switch to Category View in the Control Panel Then E yaa select Network and Internet Connections under Pick a _ San category Next select Network Connections under or pick a o a eal ex Control Panel icon in the Network and Internet Connections yen Window oro Alternately select Switch to Classic View in the Control Panel Then select Network Connections 3 Right click Local Area Connection in
163. ress That is it functions analogous to control switches for integrated into one address for multiple systems a Global Control on a Web Browser Page Two system Example D BE Transmission Unit Switch T U T U i WR3388 8 LIU R3330 801 Web Server Unit WR3387 8 NCU To lighting fixture rrr a oe a_a ba a a a a a a kan a ENEN ee Se oj FATE Transmission Unit Switch T U T U General purpose PC Monitor amp control configuration gt To lighting fixture D Controlling from a browser Oj O Contact output status D Request to NCU D D Circuit address status 3 Request to subject LIU 3 tatus acquisition by NCU DQ Request to Transmission Unit D Status acquisition by Web Server Unit QO Request to control T U Reloading browser page 86 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settin b Monitoring on Circuit Status Controlled by Wall Switches of Multiple Local Systems Two system Example WR3330 801 Web Server Unit WR3387 8 NCU Al Transmission Unit Switch T U e To lighting fixture RS485 y y y ipigi A nn eee me ee oe a a eee a a lt Ua ee se EEE ee A General purpose P i C Monitor amp control configuration 5 x a e fie IO 3 m kd i mi te SS iraneniseion Unit Switch gt D D
164. rn to Address selection page 4 Select the fade Fade Time it takes to converge from point of control to the specified dimmer level specified in 3 Instant no fade 3 s 6s 1 min 5 Click the Submit Button Communication to transfer settings data from Web Server Unit to Transmission Units will start and switch to address selection page when it is complete Data transfer in progress Please wait will be displayed until the editor window opens less than a minute Confirmation and registration from another browser will disabled while the Transmission Unit is communicating with the Web Server Unit System errors cannot be detected while transmission is in progress If registration fails due to system errors an error warning will be displayed The user must repeat the registration after the system returns to normal condition 80 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 6 Zone Settings Zone Settings is used to configure zone control settings Refer to Zone for details on Zone settings Location name Advanced Control amp Settings gt Zone Settings Basic Monitoring amp Web Server Unit Control Badda Perform verification of zone settings at boot time Yes O No Advanced Control amp Settings Address Settings Mapl No Name LIU No Mode PattemA PattemB PattemC PattemD PattemE Pattem F EE E 1 Zone 01 1 vill
165. rotocol TCP IP Properties Window If a fixed IP address is to be used select Use the following IP address and then enter the IP address subnet mask and default gateway For the actual values and the IP address of the DNS server consult the network administrator of the network to which you are connecting 31 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Installation Section If pin 1 of the DIP switch is set to default settings set the following parameter values IP address 192 168 0 X X is any value between 2 to 255 Subnet mask 255 255 0 0 Default gateway leave blank If an IP address is obtained from the DNS server DHCP select Obtain an IP address automatically For the IP address of the DNS server consult the network administrator of the network to be connected to 6 Click the OK Button to complete the procedure b Connecting to the Internet 1 For step 1 to 4 Refer to the preceding section 1 to 4 5 Select the General Tab in the Internet Protocol TCP IP Properties Window lf a fixed IP address is to be used select Use the following IP address and enter the IP address subnet mask and default gateway For the actual values and the IP address of the DNS server consult the network administrator of the network to which you are connecting lf an IP address is obtained from DNS server DHCP select Obtain an IP address automatically For the address of the DNS server
166. rror date amp time out of order local bus error FULL 2WAY signal error pattern group being set 1 file per day 00 00 through 23 59 is counted as a day CSV Monitor amp Control list settings group settings pattern settings zone settings global settings schedule control programs special day settings address settings symbol circuit name settings individual circuit dimmer groups patterns zones global addresses control log and system errors Downloads and uploads Control log and system error log can be saved only on the PC downloaded 146 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information Maps 1 Map Data Management Number of managed maps 99 pages Map data area capacity Approx 8 MB area of memory in the Web Server Unit Map drawing software WR3339 801 FULL 2WAY Screen Builder for Web Server Unit e Data transfers From the Screen Builder to Web Server Unit only Maps display enable disable Per page from Web page Map data deletion One page all pages from Web page As the size of each map increases the number of maps that can be stored transmitted decreases If maps have been created exceeding the maximum number they cannot be transmitted to the Web Server Unit Data transmitted to the Web Server Unit is not in an editable format To enable subsequent editing Original files
167. rver unit 4 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 5 LIU Settings This page provides the interface for configuring LIU connections An LIU can be physically connected but communications with it can be disabled in these settings Location name System Administration gt LIU Settings Basic Momtonng amp Web Server Unit v Select Advanced Control amp Waming Disabling LIU connection will also disable all controls programs and other configurations related to this LIU Settings Itis advisable to verify your settings before performing any changes in LIU connections Network Settings Submit Authentication Date amp Time Settings After submutting data please reboot the system RS 232C Sett Go to Reboot Page LIU Settings Page Reload Settings Project Display Settings LIU No Connection LIU No Connection System Error Monitor optin 01 Enabled v 17 Disabled v Upload M 02 Disabled v 18 Disabled oe 03 Disabled 19 Disabled ee 0 Disabled 20 Disabled factory settings Reboot 05 Disabled 21 Disabled 06 Disabled 22 Disabled 0 Disabled 23 Disabled 08 Disabled 24 Disabled v no Mieahiad w 34 Piesahiad w 1 Check the data Select a Unit in the drop down list at the top of the view and click the Select Button Data will be displayed When the window opens values stored on the Web Server Unit are displayed LIU connection set
168. s Administration Rights Monitoring control and settings If logged in with a monitoring rights only the window title is Basic Monitoring gt List Location name Basic Monitoring amp Control gt List Basic Mentoring amp Map2 Oooo O o Individual Circuit 00 1 o2 Individual Circuit 00 2 List Advanced Control amp Individual Circuit 00 3 Individual Circuit 00 4 0s Group 001 Group 002 System Administration 07 Group 003 008 Group 004 Pattern 01 010 Pattern 02 The List menu item will not be displayed unless the Monitor and Control List for users with basic monitor and control right only option of Project Display Settings is selected The List menu is always displayed regardless of this setting if a user with Advanced Control amp Settings rights or System Administration rights is logged in For details refer to System Administration and Setting and Setting List i Monitoring 1 Click one of the buttons from 001 016 to 241 256 The statuses of the selected addresses range are displayed in a table format As shown in the figure below ON is indicated in red OFF in green indeterminate No T U or unregistered in gray Other statuses are displayed as text a Example of Status WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control The status display uses port 6001 If this port is closed the status display will not be changed
169. same address with different status controls 104 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 9 Circuit Name Settings Circuit Name Settings is used to configure names for circuit addresses Configure from the following menus by address type a Individual Circuit Names All addresses for Individual Circuits and Dimmers b Groups All Groups c Patterns All Patterns d Zones All Zones e Global Addresses All Global Addresses a Individual Circuits Including Dimmers Individual Circuits is used to set names for all individual circuits and dimmers by LIU system Location name Advanced Control amp Settings gt Name Settings gt Individual Circuits Location name Advanced Control amp Settings gt Name Settings gt Individual Circuits ED dividual Cacun 30 2 SED Individual Circut 62 2 Basie Morstorng amp ea Basc Morstorng amp UUN 01 Select Control 303 individual Cacut 30 3 623 individual Circuit 62 3 Advanced Control amp Advanted Control amp 304 individual Cacut 304 624 individual Circuit 624 Sethngs Address Settings Address Settings Sl individual Circuit 31 1 63 1 individual Circuit 63 1 S Submit Map 31 2 individual Circut 31 2 63 2 Individual Circuit 63 2 Select shes Name Ad res Name See 33 individual Cercut 31 3 633 Indrvedusl Cireutt 63 3 Advanced Control O21 individual Circu
170. screw to D sub 25 pin male metric screw cross connection Maximum extension 15 m As shown below 138 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information Quality Assurance Tests were conducted at room temperature 0 to 35 C and room humidity 45 to 85 Operating voltage 18 to 30 VAC Current consumption 300 mA Temperature rise 30 C max at exterior Insulation resistance 100 MQ between charged metal and non charged metal Withstand voltage 500 V for 1 minute between charged metal to non charged metal Terminal strength 1 2 N m 12 2 kgf cm min Power backup time 24 hours Clock precision 30 seconds per month 25 C 1 C Values in use conventional units as opposed to international SI units Operating Environment 1 Operating temperature range _ 10 C to 50 C inside panel 2 Grounding Connect a ground of 100Q or less class D grounding based on Internal Wiring Regulations to the grounding terminal on the chassis 3 Operating Location Use indoors Do not install in high temperature or high humidity environments Maintain a distance of 10 cm min from wires carrying a 15 Aor higher current 139 gt WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information
171. se English User s Manual Summary This section provides an overview of the whole system I Functions and Characteristics P 3 ll Operating Principles of Major Functions P 6 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Summary I Functions and Characteristics The FULL 2WAY Remote Control takes advantage of a Web browser on a PC to provide a control history and schedule control in addition to conventional monitoring and control offering the best user interface for daily administration It is designed not only for new installations but enables upgrading existing systems thereby enabling full utilization of the previous FULL 2WAY Lighting Control System and network infrastructure If FULL 2WAY has already been installed upgrading to this new system b hieved at littl t FULL 2WAY Remote Lighting Control can be achieved at little cos System works in tandem with PCs FULL 2WVAY Remote Control can be displayed and pees on familiar web pages and customization of maps enables intuitive operations Web Server Unit takes advantage i of web technology to connect tothe Internet intranet enabling lighting j d monitoring and control from a general purpose PC General purpose i PCs can also be used for other purposes providing a very economical i ad solution intranet Perform central monitoring control and configurati
172. set Execute Execute operation at Sunset e Sunrise Execute Execute operation at Sunrise Repetition Execute Execute operation periodically from Start to End Times Repetitive Control 8 Click the Next Button The window will switch to the Date amp Time Setting Page If the Cancel Button is clicked the process will end without registration and switch to the Programs Selection Page A Group Sunset ON Sunrise OFF Example B Global Address OFF ON Example No Name LIU No Type Address Operation No Name LIU No Type Address Operation 001 Program 001 01 Group 001 Sunset ON Sunrise O 001 Program 001 Global Addresses 01 OFF ON Start Time End Time Start Time End Tie From 00 amp until an 00 A Prom 00 v 00 v 00 vito v Day Day Su Mo Tu We Th Fr Sa Su Mo Ta We Th Fr Sa o o o o o o o CJ L CJ CJ CJ CJ CJ Mo Special Day 01 u Special Day 11 4 Special Day 21 Jot Special Day 01 il Special Day 11 21 Special Day 21 02 Special Day 02 12 Special Day 12 n Special Day 22 02 Special Day 02 12 Special Day 12 n Special Day 22 03 Special Day 03 13 Special Day 13 x Special Day 23 03 Special Day 03 13 Special Day 13 B Special Day 23 04 Special Day 04 14 Special Day 14 24 Special Day 24 04 Special Day 04 14 Special Day 14 24 Special Day 24 05 Special Day 05 15 Special Day 15 25 Special Day 25 05 Special Day 05 15 Special Day 15 25 Special Day 25 06 Special Day 06 16 Special Day 16 26 Special Day 26 06 Special Day 06 16 Special Day 1
173. set the date and time to 00 00 00 January 1 1980 The indicator on the chassis will keep on flashing and message on the page remains until the date amp time will be set within the above range 2 Rights and User Setting Types of rights level Basic Monitoring Basic Monitoring amp Control Advanced Control amp Settings and System Administration Number of registered user Basic Monitoring Right 5 max at least 1 Basic Monitoring amp Control Right 5 max at least 1 Advanced Control amp Settings Right Only 1 System Administration Right Only 1 Username and password 4 to 8 characters 3 Network Connection Settings Hostname 32 alphanumerics max IP address User defined for user defined or 192 168 0 1 default Subnet mask User defined for user defined or 255 255 0 0 default Default gateway User defined for user defined or None default MAC physical address 00 CO 8F XX XX XX The Web Server Unit does not have PPPoE connection capability 4 NCU Connection RS 232C Settings Settings on the NCU must be set with DIP switches on the main body Bits per second 19200 bps recommended e Data bits 7 bits recommended e Parity Even recommended Polling ratio 2 recommended Polling cycle 0 4 Second recommended 145 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information
174. settings and zone settings may be deleted if the Web Server Unit is turned OFF while setting zones Repeat the LIU and zone settings after booting 19 The renew button in the browser and its equivalent functions in the menu will return to the initial window after login because the whole page will be reloaded 20 Do not use forward backward buttons of the browser likewise do not use Display Move Go forward Go backward in the menus to avoid inconsistency between frame displays 21 Ita screen saver is running on the PC system errors will not release it If monitoring regularly disable the screen saver 22 If PC performance is low dragging borders in Java applet generated pages may distort displayed figures 23 Opening more than 5 instances of the Web browser at a time may slow down processing or cause transmission errors 24 Powering down or rebooting the Web Server Unit during configuration may disable operations on the 151 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Specifications amp Important Information Web browser If that happens reopen the menu from the menu frame or close the browser first and reopen it 25 Due to the nature of Web pages it is possible to log in from multiple PCs with one user name and password at the same time so passwords must be managed with care especially for advanced control amp settings and system administration rights 26 When logging out th
175. sses included in the group are to relay control T Us the level will be displayed as 1 for ON and 0 for OFF If the dialog box is closed by clicking the Cancel Button while the dimmer level is being retrieved start again from step 3 5 Click the Cancel Button The dialog box will close If any button is clicked after the level has been displayed the value will be discarded The value will be retained if the dialog box is closed by clicking the Close Button in the upper right corner 118 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control Ill Map Window Operations Lighting circuit status can be monitored and controlled visually on a map screen For example display and operation are possible on a window displaying a map depicting the physical layout of the facilities In this manual a window specially drawn for a facility is called a map Monitoring and control operations using maps are described here Location name Map 2 Basic Monitoring amp Control 1F gt n EA Fw Np List Advanced Control amp gt a Settings hy ae Address Settings Entrance Map 16 Advanced Control oup Setti Pattern Settings i Settings Status Bar Manager System Administration Maps must have been prepared with special software and transmitted to the Web Server Unit For details refer to Administration and Setting under II Cr
176. status bar communicate through http service 443 1 Select Reload Cycle Reload Cycle Select from 5 6 7 8 9 or 10 seconds 2 Click the Submit Button 49 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 7 Project Display Settings Text displayed in Project Name Frame names for each Map Window and displays of Maps and Monitor amp Control List can be setup Location name System Administration gt Project Display Settings a Basic Monitorning amp Control Submit Initial Page Maps Monitor amp Control List Advanced Control amp Network Settings Authentication Date amp Time Settings LIU Setti Item no Name Enable Display Map 1 Map 2 Log Viewer 03 Map 3 N Upload Manager 04 Map 4 Data Monitor 05 Map 5 Factory Settings wes a 07 Map 7 Project Name Location name lt 0s Map 8 09 Map 9 10 Map 10 S eee e ee ele 11 Map 11 __ 1 Select the initial page Select either Maps or Monitor amp Control List as the initial page to be shown to the user after login i When Maps Is Selected The first item in the map list will be displayed to the user after login regardless to its display status enabled display checkbox If the map data of the first item has not been transferred to the Web Server Unit an empty background will be displayed to the user after login Please refer to II Creating
177. sult in smoking ignition or malfunction Donot touch live units Doing so may cause electric shock About FCC FULL 2WAY Web Server Unit WR3330 801 This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation vi WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Table of Contents Summary Functions and Characteristics ll Operating Principles of Major Functions Product Description Name and Function of Parts ll Page Layout Installation Section Device Unit Connection and Configuration Installation ll Network Connection and Settings Installation System Administration System Administration Settings ll Creation and Management of Maps Advanced Control amp Settings Advanced Controls amp Settings Monitoring amp Control Basic Operations for Connection Login Il List Window Operations IIl Map Window Operations IV Advanced Control V Error Status Displays Specifications amp Important Information Hardware Specifications ll Software Specifications Il Warranty IV Prohibited Matters for Safety Reasons V Precautions and Disclaimers Miscellaneous Information Appendix ll Troubleshooting WR3330 801 FULL 2WAY Web Server Unit Panel U
178. t 1 Click the Edit Button for the item in the list to delete The Address Setting Dialog Box will be displayed 2 Click the Delete Button The item will be deleted from the list 713 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 2 Address Settings A symbol for lighting circuit monitoring on a page that was created with map drawing software will not function unless it is assigned an address This setting page is used to assign an address to each symbol on the map Refer to I Creation and Management of map data and Monitoring amp Control Section II Operation on Maps Advanced Control amp Settings gt Address Settings gt Map 2 samedi a Lae Ge eS s M Selecting the Map Number Select a map number under Address Settings in Advanced Control amp Settings and click the Select Button The menu will be displayed if the checkbox for the map number in Project Display Settings in Systems Administration is selected M after the map data has been transferred to the Web Server Unit Applicable Symbols Icons Addresses can be set for the following symbols Normal Circuit Symbols 256 max total of individual circuits dimmers groups patterns and global addresses Zone Symbols 40 max Addresses are not directly assigned to name symbols generic and zone and dimmer level symbols Name symbols us
179. t 00 1 S21 indevidual Circuit 32 1 Advaaced Control 314 individual Cecut 314 634 indridual Circuit 63 4 Group Seteegs Group Settings Prom Satbegs individual 100 2 522 Indrvidual Circuit 32 2 Pattern Settings Zone Settings 3 Zon Uttag Address Name Addins Name Grts Address Saning 993 individual Cicut 00 3 523 Indrvidual Circuit 32 3 Global Address Setters n 9 Ssb ce Serting Schade Setting Oinmer immer Name tung G4 individual Cic 4 t Name seag F Dim Gms OLI individual Circut 0 33 1 t Soups 83 i Ze Ol dividual Cxcut 0 33 2 t Zones u Bi Dim Diametr Settings i ndividual Cucua 0 333 t Dimmer Settings Sterus Bar Macaget Samua Bar Manage 2 Ee O14 individual Cec 334 t HD System Admnttraton System Administration Amm 02 1 dividual C 1 tH y l m Dimm 0 individual C 342 t342 amp D gt Dimmer 9 dividual Cecua 0 343 t 1 Select the LIU No for the system and click the Select Button The currently registered data will be displayed All 31 systems can be set regardless of the status of the LIU connections 2 Enter the names Number of characters 32 characters or less Characters not included in iso 8859 1 CP932 will be corrupted Ifa comma is entered an error message will be displayed after the Submit Button is clicked Some names such as 32 characters long ones may be displayed with both ends truncated 3 Click the Submit Button The settings will be applied to the page Factory Se
180. t be sure to enable the ports listed in 1 3 Internet connection Requirements for the Internet Connection to Web Server Unit Publishing to the Web Always ON network connection Availability of fixed Global IP address Connection speed ADSL or faster Recommended Carrier and ISP The user is responsible for entering a contract with an ADSL carrier and an Internet service provider ISP that provide a fixed IP address service PPPoE The Web Server Unit is not equipped with PPPoE connection functionality If you subscribe to a service that requires the user authentication by PPPoE a router with PPPoE functionality or an ADSL modem with routing functionality will be needed in addition to an ADSL modem 35 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Installation Section 6 Open the home page of the Web Server Unit Follow the steps below to access the Web site through the browser Internet Explorer 1 Enter the address URL of the Server Unit As follows https denotes the IP address digits of the Server Unit e g if the IP address is 192 168 0 1 enter httos 192 168 0 1 as the URL https is used at the beginning of the URL 2 Proceed to the Security Alert Window Jp tomtom oct Any information you exchange with this site cannot be viewed by anyone else on the Web Two Security Alert Windows will be displayed because the data is encrypted S
181. tatus Bar Manager is used when the status bar which is a common interface among browsers is used to display a Performing setup message in the status bar Location name Advanced Control amp Settings gt Status Bar Manager Activate status Performing setup Over a penod of 30min v Deactivate status Performing setup Mapi Execute i Activating the Performing setup Display 1 Select Activate status Performing setup 2 Select the maximum period of display Set the maximum period of display after which the display will be deactivated Over a period of 30 min 1 hour 2 hours or 3 hours 3 Click the Execute Button The following message will be displayed in the status bar Although the message will be displayed it cannot restrict operations on other connected windows due to the characteristics of Web connections To prevent unexpected settings from taking place configurations should be performed from one place ii Deactivating the Performing setup Display 1 Select Deactivate status Performing setup 2 Click the Execute Button The setting will be applied in the status bar a I Se WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Monitoring amp Control Operations on windows to monitor and control are described in this section I Basic Operations for Connection Login P 114 Il List Window Operations P 116
182. thentication page Data will be initialized and execution will transfer to the start Login Window NCU connection Settings data registered in RS 232C Settings page Data will be initialized LIU connection and zone settings registered in LIU Settings page and Zone Settings page Data will be initialized LIU Settings disabled and Zone Settings unregistered Page Reload Settings data registered in Page Reload Settings page Data will be initialized Project Display Settings data registered in Project Display Settings page Data will be initialized Logs Settings data registered in Logs Settings page Data will be initialized Current day activity log enteries Activity Log Data will be deleted All activity Log entries except current day ones Activity Log Data will be deleted Current day system error log entries System Error Log Data will be deleted All system error log entries except current day ones System Error Log Data will be deleted Remaining temporary files created when downloading patterns and group settings data DownloadManager page The original data for pattern and group settings is stored in the Transmission Units Therefore temporary files is generated each time the data is downloaded Those temporary files are not deleted automatically and remain in the Web Server Unit Data will be deleted 66 WR3330 801 FULL 2WAY Web Server Unit Panel Use
183. tings are set in the Web Server Unit and NCU and the settings must be identical If not they can be matched using this page lf the settings of the Web Server Unit and NCU remain different monitoring and control will not function normally The NCU must be connected to the Web Server Unit in order to check the Web Server Unit s data 2 Enable disable the connection Select Enabled or Disabled for each of the LIU 01 to 31 3 Click the Submit Button The values shown in the window will be submitted and saved to the Web Server Unit and the NCU The NCU must be connected when values are submitted Saving and Resetting Zone Settings Zone settings data will be deleted when the LIU connection is set Therefore when the Submit Button is clicked a warning message to that effect will be displayed Zone settings data that have already been set will not be lost if the user follows the following instructions To prevent loosing zone settings first save the zone settings data to the client PC in the Download Window prior to modifying LIU connections settings Once LIU Connection Settings modifications are completed transfer the zone data back to the Web Server Unit in the Upload Window Edit the zone settings in the Zone Settings Window to correspond with the new LIU Connection Settings 48g WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual system Administration 6 Page Reload Settings This window is used to ena
184. tion Normal circuit symbols apply to individual circuits dimmers groups patterns and global addresses Circuit name symbols conform to the settings for associated normal circuit symbols or zone symbols These associations must have been set with the Screen Builder for Web Server Unit and cannot be changed on the Web page Dimmer level symbols conform to associated normal circuit symbols These associations must have been set on the map drawing software and cannot be changed on the Web page Dimmer level symbols apply to individual circuits dimmers and groups Levels cannot be monitored for dimmer level symbols if the symbols are associated with patterns and global addresses Addresses are not directly assigned to dimmer levels and circuit symbols normal symbols and zones 6 Monitoring and Control by Lists Number of Symbols for Monitoring and Control 256 points max 16 points x 16 windows Configuration of Lighting Circuits 1 Address Assignment to Symbols Applicable symbols Circuits symbol for normal symbols or zones e Addresses for control Individual circuits dimmers groups patterns global addresses and zones of connected LIUs LIU connection configuration must have been completed before assigning addresses One address can be assigned to multiple symbols Global addresses and zones can be configured regardless of status of LIU connection configuration Assignments of addresses to symb
185. ttings Name Individual Circuit XX X XX X 00 1 to 63 4 and Dimmer XX XX 01 to 16 105 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings b Groups Groups is used to set names for all groups by LIU system Location name Advanced Control amp Settings gt Name Settings gt Groups Basic Monitoro Control LIUNo 01 Advanced Control amp Settings Address Settings Address Name Address Name Advanced Control 001 Group 001 065 Group 065 Group Settings Pattern Settings 002 Group 002 066 Group 066 Zone Settings Global Address Settings 003 Group 003 067 Group 067 Schedule Settings Name Settings 004 Group 004 068 Group 068 Individual Circa Groups 095 Group 005 069 Group 069 Patterns Zones 006 Group 006 070 Group 070 Global Addresses Dimmer Settings 007 Group 007 071 Group 071 Status Bar Manager 008 Group 008 072 Group 072 009 Group 009 03 Group 073 010 Group 010 074 Group 074 oit Group 011 015 Group 075 1 Select the LIU No for the system and click the Select Button The currently registered data will be displayed All 31 systems can be set regardless of the status of the LIU connections 2 Enter the names Number of characters 32 characters or less Characters not included in iso 8859 1 CP932 will be corrupted If a comma is entered an error message will be displayed after the
186. ttings inconsistencies Red Indicates normal monitoring and control has been disabled because the LIU Settings or Zone Settings are inconsistent with those of the NCU 5 Initializing Red Indicates that the Web Server Unit is being initialized 6 Data transfer in progress Please wait Red Indicates communications with the NCU such as group settings pattern settings zone settings and LIU Settings are in progress 7 Performing setup Red Indicates that setup operations have been started in the Status Bar Manager 8 Connected Green Indicates that normal operations can be performed 22 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Installation Section This section describes installation procedures for electrical connections and network connections I Device Unit Connection and Configuration Installation P 24 ll Network Connection and Settings Installation P 29 23 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Installation Section I Device Unit Connection and Configuration Installation This section describes installation of the main unit and connections to peripherals 1 Connections between Devices Power Line Transformer 24V AC Power Line 24 VAC 0 9mm to 1 6mm dia Single 0 75mm2 to 2 0mm2 Stranded Ground Line 1 6mm dia Single 2 0mm2 Stranded Communication Cable CPEV for example
187. ual circuits 1 to 16 dimmers 1 to 127 groups or 1 to 72 patterns AND or OR 0 AND or 1 OR LO1 to L31 O Subject or 1 not subject Type address AND OR and L01 through L31 are zeros for unused global addresses 156 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Miscellaneous Information e Schedule File Name schedule csv Scheduler Schedule number 1 to 930 in ascending order Name 16 characters max LIU number 1t031 1 for global address Type individual circuits D dimmers G groups P patterns Z zones or gb global addresses Address 00_1 to 63 4 individual circuits 1 to 16 dimmers 1 to 127 groups 1 to 72 patterns 1 to 96 Zones or 1 to 32 global addresses Control value ON Pattern 1 Pattern 2 Pattern 3 Pattern 4 or OFF Zones numbers are single byte Input values when uploading addresses other than zones will be ignored Operation Sunset Sunrise Sunset OFF ON Sunrise ON OFF OFF ON ON ON OFF OFF ON OFF ON Execute Sunset Execute Sunrise Execute Repeat Execute Start time 0 00 to 23 59 Start adjustment time 90 to 90 End time 0 00 to 23 59 End adjustment time 90 to 90 Sun to Sat 0 Canceled date or 1 Execution date Special day 01 to Special day 30 O Canceled date or 1 Execution date Enable Disable 0 Disable 1 Enable Schedule numbers program numbers with
188. uit Address 00 1 to 63 4 Dimmer Address 01 to 16 LIUXX LIUO1 to LIU31 Address 00_1 to 63 4 individual circuits or 1 to 16 dimmers in ascending order Name 32 characters max The initial values for names are individual circuit00 1 to individual circuit63 4 and dimmer01 to dimmer16 e Group Names File Name g_nameXX csv XX ponies the ee wid number 01 31 Address Name GroupAddress 001 to 127 LIUXX LIUO1 to LIU31 Address 001 to 127 in ascending order Name 32 characters max The initial values for names are group001 to group127 e Pattern Names File Name p_nameXx csv XX denotes the two digit system LIU number 01 31 Address Name PatternAddress 01 to 72 LIUXX LIUO1 to LIU31 Address 01 to 72 in ascending order Name 32 characters max The initial values for names are patternO1 to pattern72 159 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Miscellaneous Information e Zone Names File Name z_name csv Address Name Zone Address 01 to 96 Address 01 to 96 in ascending order Name 32 characters max The initial values for names are zone01 to zone96 e Global Address Names File Name gb_name csv Address Name Global Address 01 to 32 Address 01 to 32 in ascending order Name 32 characters max The initial values for name are global address01 to global address32 e Control Log Fil
189. unterpart device or devices on the way or LAN switch failed Ethernet ACT indicator does not flash The following causes are likely The PC is not sending data due to incorrect settings or other cause The LAN adapter failed and frames are not transmitted LAN switch failed I have forgotten the user name and password for the administrator changed Should a user forget the user name and password for the administrator he she cannot recover it by him herself once it has been changed Please contact Matsushita Electric Works Ltd in that situation For security initialization with a hardware switch is not supported so please maintain this information carefully 163 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s manual Date of Issue November 1 2006 1 edition Issued by Matsushita Electric Works Ltd 1048 Kadoma Osaka 571 8686 Japan Telephone 81 6 6908 1860 2006 Matsushita Electric Works Ltd All rights reserved Printed in Japan This document may not be copied or duplicated either in part or whole without the prior written permission of Matsushita Electric except for personal use We cannot answer to questions relating to the operation of PCs or software unrelated to the product or this document This document has been created with careful attention to details but if you have any questions or f
190. unused space reserved for map data Erases map data by page Initializes and erases user data Reboots Web Server Unit 21 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Product Description 4 Main Frame Once a menu has been selected all operations including Basic Monitoring amp Control Advanced Control amp Settings will be processed within the main frame Buttons pull down menus panes for key input and other elements are displayed as necessary 1 Basic Monitoring amp Control screen Maps 2 Basic Monitoring amp Control Window List ae a Fl SS Timia c Bj Bj m ES S S et ii 5 Status Bar Statuses 1 to 8 shown below can be displayed in the status bar lf more than one status exists at the same time the lower numbered status has higher priority for display 1 Please wait for a moment Red Indicates the network connection to the Web Server Unit has been temporarily disconnected e g broken wire a device that has stopped etc 2 Date amp Time out of order Red Indicates that the date and time could not be kept e g after a power supply interruption longer than the clock s battery maximum time range 3 System error occurred Red Indicates errors in the Web Server Unit or local system This error includes situations when the local system is being set using the patterns groups setting switches 4 Se
191. upply Switching time less than 10 ms It should output a sine curve Waveforms other than sine waves may damage the remote control transformer specified above 3 Outdoor wiring must be enclosed in a metal conduit to shield it from lightning 4 Do not perform an insulation test on the wiring Do not perform an insulation test on the signal lines 5 Only devices designed specially for the FULL 2WAY Remote Control System can be used for the FULL 2WAY multiplex signal lines 6 The Web Server Unit is not compatible with auto MDI MDI X functions Therefore a straight cable must be used Direct connection between PCs however requires a cross cable 7 Configurator ports are reserved for manufacturer maintenance and customers cannot use them Precautions and Disclaimers for Usage 1 Initialization after turning ON the power supply requires about 2 to 7 minutes for the maximum number of connections 2 Determinations and monitoring are disabled for up to 3 minutes after restarting Transmission Units recovering from signal errors and completing pattern group settings from a local configuration Errors during this period are not recorded 3 Short circuits on the secondary side of the amplifier cannot be detected and failures in control or monitoring under this condition although very unlikely will not be recorded in the error log 4 When control operations are continuously performed in excess of the maximum circuit control speed
192. ups P G Settings i i mm RC232C i WR3330 801 WR3387 8 WR3388 8 Web Server Unit NCU LIU Transiniesion Uni Switch Downloading uploading data file Setting result data To lighting fixture in a browser Setting result data acquisition P G control setting request to NCU by NCU 8 P G control setting request to subject LIU Setting result data acquisition by P G control setting in Transmission Unit Web Server Unit General purpose PC Monitor Reloading O Reloading browser page browser page or amp control configuration When data in the Web Server Unit is downloaded to a PC settings contained in the Transmission Unit are collected into a file and then transferred When a valid data file on a PC is successfully uploaded to the Web Server Unit setting of Transmission Units automatically takes place from the Web Server Unit 2 Other Settings Data rian 0 0 8 7 oy WR3387 8 WR3388 8 WR3330 80 Web Server Unit NY LIU Transmission Unit Switch gt To lighting fixture Downloading uploading data file Transferring of data file from in a browser Web Server Unit to PC or from AQ PC to Web Server Unit General purpose PC Monitor amp control configuration 13 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Summary 8 Transfer of Map Data from the Screen Builder RC232C W
193. urrent day Next day Start 0 00 End 6 12 00 lt OFF Time lt Sunset ON Time in Sunset ON OFF Item 5 is a special case Neither the start nor the end control will be performed Sunset ON OFF Current day Next day 12 00 End Start 12 00 End Start OFF Sunset OFF Sunset ON 7 Sunrise OFF Time ON Time lt 12 00 in ON Sunrise OFF Item 5 is a special case Neither the start nor the end control will be performed ON Sunrise OFF Current day Next day x x End Start 1 12 00 0 00End Start 12 00 Sunrise OFF ON Sunrise OFF ON 102 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 8 Multiple Programs Controlling Different Addresses Simultaneously Program will be executed in order of their serial numbers Current Day Program 1 Address B First 0 00 ON Program 2 Address A I After 0 00 OFF 9 Multiple Programs Controlling the Same Addresses Simultaneously with Different Statuses Only OFF controls will be executed for the address and not the ON controls Current day Program 1 Address A Not executed 0 00 ON Program 2 Address A MY Executed 0 00 OFF ii Complex Operations If the start time for a program has already passed when a new schedule is set changes are made to special day normal day settings or the clock is adjusted the program will ignore the start control but will exec
194. ushita Electric Works Ltd except for personal use Trademarks and Registered Trademarks Ethernet is a registered trademark of Xerox Corporation Microsoft Microsoft Internet Explorer and Windows are either registered trademarks or trademarks of Microsoft Corporation in the United States and or other countries Sun Microsystems Java and J2SE are trademarks or registered trademarks of Sun Microsystems Inc in the United States and other countries Other company or product names given in this document are the registered trademarks or trademarks of the relevant companies The official name for Microsoft Windows XP is the Microsoft Windows XP Operating System Screen shots are used according to the guidelines of Microsoft Corporation Further Inquiries Matsushita Electric Works Ltd 1048 Kadoma Osaka 571 8686 Japan Telephone 81 6 6908 1860 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Disclaimer The changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment Repair disassembly upgrade or modification of the product without written permission from Matsushita Electric Works Ltd shall void any rights entitled to the customer regarding the product and Matsushita Electric Works Ltd shall not be liable for any damages resulting from these actions except when Matsushita Electric Works Ltd
195. ute the end control When controls are in progress from a Web page at the scheduled control time the scheduled control may be delayed by a small margin 1 Interday Controls before or after Special Days 1 Normal Day Crossing to Special Day An end time control falling on a special day will be executed Current day normal day Next day special day Start 0 00 End 2 Special Day Crossing to Normal Day The end time control falling on a normal day will be executed Current day special day Next day normal day Stare 0 00 End 103 WR3330 801 FULL 2WAY Web Server Unit Panel Use English User s Manual Advanced Control amp Settings 2 Changes to Special Normal Days 1 Programming Beginning on a Special Day Changed to a Normal Day on that Day Cleared Special Day If the controls had already started when the change was made the end control will be performed after the change 2 Programming Beginning on a Normal Day Changed to a Special Day on that Day Even if the program had started before change was made the end control will not be performed after the change 3 Changes to Daylight Savings Time Setting When Automatically adjust clock for daylight saving changes is selected all scheduled controls for the hour that is advanced will be executed Programs will be executed in order of program number and only OFF controls will be executed and none of the ON controls if there are multiple programs for the
196. vice Device in which the error occurred Including channels Date amp Time Out of Order Error is displayed if an error has occurred and Normal when it has recovered Reboot Completed is displayed when the Web Server Unit has rebooted NCU Connection Error is displayed if an error has occurred and Normal when it has recovered Indeterminate is displayed for all items in the local system if an error has occurred e Local Bus Indeterminate is displayed for all items in the local system if an error has occurred and Normal when it has recovered FULL 2WAY Signals Error is displayed if an error has occurred and Normal when it has recovered Pattern Group Settings Error is displayed when pattern group settings have started on a local system and Normal when settings have been completed The types of errors that can be recorded are identical to those that can be checked in the System Error Monitor Refer to 8 System Error Monitor for details Indeterminate is displayed for lower items whose data cannot be collected when an error has occurred in the higher part of the system When the Web Server Unit is started errors are logged independently from logs before startup Therefore identical logs may be displayed Supplemental Information Maximum number of log entries 1 000 entries day x 7 days including the current day Time 00 00 through 23 59 is counted as one day If there are more then 1 000 log entri
Download Pdf Manuals
Related Search
Related Contents
Live Meeting 2007 - Programando una Reunión PTR-PTI mode d`emploi Entreprise Zalman CNPS14X Gecko STAR PALMANN BA DT 14-02-2012 08 R350 MANUAL GB I -MANUALE DI ISTRUZIONE PER APPARECCHIO DI TAGLIO AL Copyright © All rights reserved.
Failed to retrieve file