Home

cpx 020.qxd - Electrocomponents

image

Contents

1. 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 P s rogram tees With the display showing Zones 2 Press No five times The display will show Program pe Digicom 3 Press Yes The display will show Program Digicom Type or Test 4 Press Yes The display will show for example Digicom Type Mod FF 5 Press No until the display shows Digicom Type Mod PID Or As required Digicom Type Mod SIA 6 Press Yes The display will show VoComm Off 7 Press No until the setting you require is displayed Then press Yes The display will show Program Digicom Type or Test 8 Press No The display will show Program Digicom Delay Part 9 Press No The display will show Program Digicom Channels 10 Press Yes The display will show Program Triggers Page 91 CPX Engineer s Reference Guide 11 Press Yes the display will show You MUST turn On the Triggers you require 12 Use the Yes amp No keys to accept or change the options on the following screens 13 Press Yes The display will show Page 92 Set Off Alrm Off UnSet Off PA Off Set Off Alrm Off UnSet Off PA Off 24Hr Off E E Off 12Hr Off Bat Off Tamp Off AC Off
2. For programming details on PID Point ID Protocol and SIA please refer to page 91 Page 48 CPX Engineer s Reference Guide 5 Press No until the required setting is displayed then press Yes The display will show VoComm Note If On is selected the Vo Comm menu will now appear in the USER Off mode Please refer to CPX User Guide for further programming information 6 Press No until the setting you require is displayed Test Digicom then press Yes The display will show Channels i Program Digicom 7 Press No The display will show Type or Test 8 Press No The display will show Program Digicom Delay Part 9 Press Yes The display will show p ay Fire Zone Delay 90 Secs 10 Press No twice The display will show Fire Zone Delay gt Secs 11 Enter the number of seconds you require for the Fire Zone Delay followed by Yes Digi Delay 00s The display will show Part Alarm On With Digi Delay programmed the alarm transmission to Central Station will be delayed for the number of seconds programmed With Part Alarm programmed to Off there will be no transmission of Alarm Alarm B or Alarm Abort if the system is Part Set 12 Press No twice The display will show Digi Delay __s Part Alarm On 13 Enter the number of seconds you require for the Digi De
3. Engineer ReSet cceseccsesereeeeeeeeees Wiring Proximity E amp I Readers Clearing Test Fail Indication 5 Specifications cecceeecesesseeeseeseeeeeseeeeeeenees Power Supply Rating cccceeeeeeeee 6 4 Wire Contour RKP Wiring Information Page 1 CPX Engineer s Reference Guide IMPORTANT Input AC230V 10 50Hz 125mA Max 35W Max Nominal Temp Range 0 50 aig eur sec Plastic Versions For Indoor Use Only This equipment is intended only for use as a Security Alarm Control Panel Adequate ventilation away from heat and humidity must be provided The unit must be fixed securely to a non flammable surface using suitable fixings All mains wiring must conform to the relevant current IEEE wiring regulations or appropriate international regulatory standards See Mains Supply Connection section within this manual for more detailed instructions All wiring must be protected from sharp or jagged edges All low voltage alarm wiring must be to the appropriate international regulatory standards and comply to good wiring practice and should be routed away from the mains cables Replacement fuses should be of the same type and rating conforming to IEC 127 The maximum current draw from the unit for all output combinations must not exceed 1A Please see note Power Supply Rating in Specifications chapter
4. Program Confirm Bell Mode Program Confirm Strobe Mode Strobe Trigger Unconfirmed Program Confirm Strobe Mode Program Confirm Start Delay Start Delay 000m Start Delay gt __ om Program Confirm Start Delay CPX Engineer s Reference Guide 34 Press No 35 Press Yes The display will show The display will show 36 Press No until the required setting is displayed then press Yes The display will show 37 Press No 38 Press Yes The display will show The display will show Always On Keypad is always active Off in Entry Keypad is disabled during Entry Time Of in Ent Alm Keypad is disabled during Entry time or if Entry Time goes through into Alarm 39 Press No until the required setting is displayed then press Yes The display will show 40 This concludes the Program Diagnostics Press 0 zero three times to return to Page 88 Program Confirm Comms Restore Comms Restore On Program Confirm Comms Restore Program Confirm Keypad Opening Keypad Opening Always On Program Confirm Keypad Opening 01Jan 00 00 01 CPX Engineer s Reference Guide N
5. Code Unlocked Be careful if you lock your code in If the code is forgotten you may have to return the control panel to the factory to have it unlocked this will be a chargeable service 5 Press No until the required setting is displayed then press Yes The display will show 6 This concludes the Program Engineer Code Press 0 zero twice to return to Page 72 Program Engineer Code 01 Jan 00 00 01 CPX Engineer s Reference Guide Programming Service Within this section you will program the Service Timer Also if required uploading downloading data to the control panel via the PTM Program Transfer Module The Service Timer has the ability to Lock a user out of the system when the Service Time expires Trading Standards may take action if a Lockout occurs and no Service Contract exists Please use with care 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Program Zones 2 Press No thirteen times The display will show Programi si Service PTM F Save Panel NVM 3 Press Yes The display will show poate ene 4 Press Yes if you require to save to PTM Otherwise 5 Press No The display will Load Panel NVM from PTM 6 Press Yes if you require to load from the PTM Otherwise 7
6. 10 Press Yes The display will show Alert 2 Off 7 amp 9 Keys Off 11 Press No until the required setting is displayed 9 and Alert 2 Off then press Yes The display will show 789 Keys gt Off Alert 2 Off 12 Press No The display will show 789 Keys gt On 13 Press Yes The display will show Program Keypad Alert 2 Keys 14 Press No The display will show Program Keypad Quick Key 15 Press Yes The display will show Quick Key Off Page 45 CPX Engineer s Reference Guide The available options for the Quick Key are Off The Quick Key is disabled Quick Set Reduces the Exit Time after Exit has started Full Set Enter user code then Quick Key Part Set Enter user code then Quick Key for Part 1 Set 16 Press No until the required setting is displayed then press Yes The display will show 17 Press No The display will show Program Keypad Quick Key Program Keypad Number This option is used to program the Number of Keypads you have on the system It should be noted the there are no jumpers in the RKP to ident them this is done from the program option 18 Press Yes The display will show 19 Press Yes The display will show 20 Enter the Number of the keypad you wish to program onto the system 1 to 4 then press Yes The display will show 21 Press t
7. L Fused Spur Control Panel Mains Terminal Block Page 5 CPX PCB iagrams D iring CPX Engineer s Reference Guide Ww Default Engineer Code Note 680 Ohm resistor shoul AMATERI 1234 e fitted to mm of the RKPs If paniis Default User RKPs are wired F2 AUX 20mm 1A QUICK BLOW X30NVdX3 OIVA S8rS4 o TELEPHONE CONNECTIONS in daisy chain this should be To Default Panel the last RKP in j Power Up thelline Note Only replace fuses eave ilst version No 6g0Ohm g a with correct type amp valie is displayed enter 6 Yes No 3 25 i m OER This will not Default 2 of Se 250mA QUICK BLOW the Engineer Code 2 3 if it has been locked Neb Connections available are model dependant INTERNAL SPEAKERS OTHER MIN 16 OHM SOCKETS ON PREMISES be ova ov 12v REMOTE KEYPAD S MAY BE WIRED IN STAR OR DAISYCHAIN FORMAT Bell Trigger Strobe Trigger Tamper Return Bell Strobe Hold Off Bell Hold Off Supply EXTERNAL SOUNDER 7 STROBE MODULE GTAG PROXIMITY READER S Page 6 CPX Engineer s Reference Guide Remote Keypads Up to four remote keypads may be fitted to the eur sec CPX control panel Each Keypad offers a 32 character backlit LCD A four core connection will be required between the control panel and remote keypad s keypads may be in a daisy chain or star format Note 680 Ohm resistor must
8. Use ENGNR Mode Program Zones Program Zone Types Enter Zone 001 Ent Ex Remove 001 gt Ent Ex Remove CPX Engineer s Reference Guide Zone Types available are 12 Hour Full Alarm if Control Panel is Set Access Will allow to pass through on exit Will allow to pass through on entry only if E E is opened first 24 Hour Internal Sounder if Unset Full alarm if Set Remains active in Engineer Programming Mode Entry Exit or E E Zone used as last exit point will terminate exit time if setting mode is set to E E or Time E E Will start E E time if opened when Control Panel is Set Part E E As Access if Control Panel is Full Set As Entry Exit if Control Panel is Part Set Panic 24Hour Personal Attack or Panic Attack Active if Control Panel is Set Unset or in Engineer Programming Mode May only be tested via Engineer code if programmed as testable Alert Internal Sounder Only Recorded to Log when Unset Recorded to Log when SET Fire Will give Fire alarm when activated pulsed sounders with Control Panel Set or Unset Remains active in Engineer Programming Mode ET Exit terminator Used for final setting of the system Exit Mode must be programmed for ET Monitor Will write to the log once only in any one set or unset unless chime is allocated then all activations are written to the log KS
9. Custom 1 to 8 Int Sounder E E Timed 1 Alert Page 62 CPX Engineer s Reference Guide cont Alarm B Confirmed Alm Abort Alarm Abort Any Fire Any Panic Gen Tamper General Tamper Zone 24Hr Power Fail Power OK Const LoBat Radio Low Battery Radio Lost Lost Radio Detector etc Const Jamm Radio Signal Jamming Any Fault Any Mask Watchdog Off Pulse Off Pulse On Any Set Alarm Unconfirmed After Alarm Open Close Pulse Set Part Set Walktest Mains Fail PGM2 O P 5 Press No until the required setting is displayed Seer Say then press Yes The display will show for example With the PGM2 programmed as Bell the output will operate with the Bell when this is set as V With this set as V the output will be inverted e g On turning Off with the Bell PGM3 O P 6 Press No until the required setting is displayed Strobe gt V then press Yes The display will show Program PGM2 3 7 Press No until the required setting is displayed Operating Modes then press Yes The display will show Page 63 CPX Engineer s Reference Guide 8 10 11 12 13 14 15 Press No The display will show Press Yes The display will show Press twice No The display will will show Enter the On Time hours followed by Yes The display will show Press No The display will show Enter the
10. N C Devices N E N C Devices a o oa gt NIC Devi N Seer a N C Devices __ _ gt o a7 N C Devices N gt D rd N C Devices N y 0 0 0 N C Devices D multiple devices are in series N ZL End of Line Zone Wiring Standard 2 Wire Zone Wiring Multiple units can only be used with BS Standard If using EN2 one unit per zone Page 9 CPX Engineer s Reference Guide Typical Wiring Modes Where Anti Mask detectors are used one of the following wiring 12K modes may be used Fault Alarm Tamper Mask 6K8 4K7 ELF1 wiring is used for detectors that have a relay output a pair of terminals for Fault or Mask ELF2 wiring is used for detectors that have a transistor output a single terminal for Fault or Mask AZx The installer should check what output type AZx the detectors are noting that all the dectectors should be of the same type with regards to the Fault Mask output Note For ELF2 wiring format the 12K resistor must be linked to the positive Side of the zone terminals Typical ELF1 Typical ELF2 More Zone Wiring Methods Zone Wiring 2 Wire Zone Wiring EOL Zone Doubling 8 8 TZ Tamper AZ Alarm AZ Alarm AZ Alarm AZx 4K7 6K8 a N C Tamper N C Alarm N C Tamper N C Alarm Contact Contact Contact Contact Alarm N C Tamper N C Alarm N C Tamper N C 1st Detector 2nd Detector Zo
11. Press No The display will show ae ae 8 Press No twice The display will show oF i Next Service due 9 Press Yes The display will show in 00 Weeks Note To transfer data to and from the PTM a cable part number 04 091 will be required Cut off the BLUE plug at one end and wire to the RS485 terminal block on the CPX control panel PCB following the colour code Connect the other end to the PTM Note When data transfer is in progress the LED on the PTM will flash rapidly Page 73 CPX Engineer s Reference Guide 10 11 Note 12 13 14 15 16 Press No twice The display will show Enter the number of weeks you require to the next Service then press Yes The display will show The system will start to warn the end user that the Service is due two weeks before the time expires Press No The display will show Enter the Telephone Number you wish your customer to dial for service followed by Yes The display will show With Lock Out turned On the system will Lock the users out when the Service Time expires With Lock Out turned Off the system will continue to warn of Service until the Service Timer is reset Press No until the required setting is displayed then press Yes The display will show With Engineer Mode programmed as Constant the panel will remain in Engineer Mode until the Engineer exits With Engineer Mode programmed as timed the panel will jump
12. The unit is intended for use with a suitable re chargeable lead acid battery permanently connected to the appropriate terminals All documentation and manuals must be thoroughly read by suitably qualified installation personnel prior to installation The unit has no user serviceable parts inside Internal access should only be by suit ably qualified personnel Provision is provided for an earth connection within the mains input connector block this connection is for protection of the wiring only and is not functional for the unit Battery Fuse An in line Battery Fuse has now been incorporated into this product The fuse rating is 2 Amp Anti Surge The fuse holder is spring loaded therefore you should ensure that the battery lead is not under tension in order to maintain a good connection between the fuse and the holder To change the fuse push the two halves of the hold er together and twist anti clockwise Please ensure correct battery charge on comple tion of the installation and during each service visit Page 2 CPX Engineer s Reference Guide 1 INTRODUCTION The eurdsec CPX Control Panel is a microprocessor based unit that has been designed to be suitable for all types of domestic and commercial installations All zones are fully programmable by the engineer On power up reset the Control Panel can be set to the old BS or EN2 Grade 2 operating standards It is ESSENTIAL that a 4 6 YES NO reset is done to all new sys
13. Volts The Line Monitor will check the Dial Tone and the Line Voltage This setting should be used when the control panel is connected to a dedicated telephone line Off Line Monitor is turned Off Dial Tone The Line Monitor will only monitor the Dial Tone This setting should only be used on a dedicated telephone line Line Volts Then Line Monitor will monitor the Line Voltage This setting should be used when the control panel is connected to a telephone line that has other telephone equipment on it shared line 54 Press No until the required setting is displayed then press Yes The display will show Line Security High Settings available for Line Security are High Low The Line Voltage is monitored at a High Level This setting should be used on dedicated lines only The Line Voltage is monitored at a Low Level This setting should be used when the control panel is sharing the line with other telephone equipment Page 55 CPX Engineer s Reference Guide 55 Press No until the required setting is displayed then press Yes The display will show Channel 12345678 R Rep 00010000 This option determines what Digi Channels will send a Restore Signal to Central Station when the system is Reset Most Central Stations will require a Restore Report for all channels 56 Press No The display will show Channel 12345678 R Rep __ 57 Enter eight o
14. in seconds followed by Yes The display will show for example P1 Exit time 20s gt Set by TIME Page 32 CPX Engineer s Reference Guide 13 Use the No key to scroll through the Setting Modes 14 When the Setting Mode you require is displayed press Yes The display will show Program Setting for PART 1 set 15 Press No The display will show Program Setting for PART 2 set 16 Press Yes The display will show P2 Exit time 30s Set by TIME 17 Press No twice The display will show DO Exittime gt s Set by TIME 18 Enter the time you require as the Exit Time in seconds followed by Yes The display will show for example P2 Exit time 20s gt Set by TIME 19 Use the No key to scroll through the Setting Modes 20 When the Setting Mode you Require is displayed ress Yes The display will show p p ay Program Setting for PART 2 set Page 33 CPX Engineer s Reference Guide 21 22 23 24 25 26 27 28 The Final Set Delay is a period of time in seconds after the expiry of the Exit Time and is intended to allow any PIRs for example that are on the Exit Route to settle before the system finally Sets The majority of PIRs will settle within the Default Time of 3 seconds but some may need a Final Setting Delay of up to 10 Press No
15. Event 3 Open Entry Door entry time starts Event 4 Entry Time Expires inc Entry Time 2 Unconfirmed Alarm Transmitted Event 5 Any subsequent zones triggered No Confirmed Signals Transmitted Or Event 1 System Set Event 2 Entry Door Forced Open entry time starts Event 3 Entry Time Expires inc Entry Time 2 Unconfirmed Alarm Transmitted Event 4 non entry access Zone Triggered Event 5 Second non entry access Zone Triggered Confirmed Transmitted To achieve the above Confirm on entry On ET Mode Door Lock Door Lock Zone programmed as ET Page 83 CPX Engineer s Reference Guide c Event 1 Event 2 Event 3 Event 4 Scenario Opening the initial entry door disables all means of conformation 6 4 4 DD243 2002 System Set Entry Door Opened entry time starts Confirmed Alarms Disabled Entry Time Expires inc Entry Time 2 Unconfirmed Alarm Transmitted Any subsequent zones triggered No Confirmed Signals Transmitted To achieve the above Confirmed on entry Off Programming Alarm Confirm 1 2 3 4 5 6 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 i i mat Program ee With the display showing Zones Press No sixteen times The display will show Program Alarm Confirm Press Yes The display will show Program Confirm Window Time Confirm Window Press Yes The display will sh
16. On Time minutes followed by Yes The display will show Press No The display will show Repeat for Timer 1 Off Time Press Yes The display will Show Page 64 Program PGM2 3 Timer 1 On Time Timer 1 On Time 00 00 Hrs Timer 1 On Time gt __ 00 Hrs Timer 1 On Time 10 gt 00 Hrs Timer 1 On Time 10 gt __ Hrs Program PGM2 3 Timer 1 On Time Program PGM2 3 Timer 1 Off Time Program PGM2 3 Timer 1 Off Time CPX Engineer s Reference Guide 16 This concludes the programming for PGM2 3 Timer 17 Press 0 zero to return to Program oo PGM2 3 Timers Or Press 0 zero until the display shows 01 Jan 00 00 01 Page 65 CPX Engineer s Reference Guide Programming Reset Modes 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 F eee rogram ae With the display showing Zones 2 Press No nine times The display will show Program mns Reset Mains 3 Press Yes The display will show yak Fail Delay 20m 4 Press No twice then enter the Mains Fail Delay time you require Then press Yes The display will Alarm Reset show Master Note Default is set at 20 minutes Will delay the display
17. Program zane Descriptors Page 21 CPX Engineer s Reference Guide 21 Press No The display will show Program Zone Wiring 22 Press Yes The display will show Zone Response Note Zone Response time is defaulted to 400ms and may not 400 mS be changed Fault Mask Zones Response Norm 23 Press Yes The display will show Note Zone response time may be programmed as a global parameter The default time is 400ms and may be reprogrammed from 2 to 14 seconds increments of 2 seconds The time programmed for this option will apply to all zones there is no option for individual response times per zone It is a global setting Once the Fault Mask as been triggered the response time for the Fault Mask will revert to the default time of 400ms until the fault mask problem has cleared 24 Press No until the required settings you require are i z z On Board Zones displayed then press Yes The display will show 9 lt FOL gt Wiring Modes available are 8 2 Wire Two wires are used for the zone and a global tamper is used 9 EOL Two wires are used in conjunction with two resistors to give End Of Line wiring this is the most secure wiring format 8 8 EOL This wiring method uses double EOL format to give 16 Zones from the control panel Note For information on how to wire for the various wiring modes please refer t
18. The display will show Press Yes The display will show Press No twice The display will show Enter the time you require as the Exit Time in seconds followed by Yes The display will show for example Use the No key to scroll through the Setting Modes When the Setting Mode you Require is displayed press Yes The display will show Press No The display will show Press Yes The display will show seconds Page 34 Program Setting for PART 3 set P3 Exit time 30s Set by TIME P3 Exit time gt __s Set by TIME P3 Exit time 20s gt Set by TIME Program Setting for PART 3 set Program Setting Delay Final Set Delay 03s CPX Engineer s Reference Guide 29 Press No twice The display will show Final Set Delay gt 30 Enter the Time required in seconds followed by Yes The display will show Program Setting Delay 31 Press No The display will show Program Setting Sounders Setting Sounders refers to Part Sets Only The Setting Sounders option determines if any or all Part Sets are audible Exit Tones or not This is a useful feature when part of the family may already be asleep when the system is being Part Set 32 Press Yes The display will show Exit So
19. This will be logged but no further action is taken If the second zone to alarm during the same set period is also a Secondary Zone then it will be logged and the Secondary Time Window will be restarted If the time set within the Secondary Time Window is still running and a zone that is not allocated as a Secondary Zone is triggered the event will be logged an Alarm A un confirmed and Alarm B confirmed will be transmitted This feature is not mandatory for DD243 Perimeter Zones Within the Program Zone Attribute section you are able to allocate zones as Perimeter Zones that are entered as Perimeter will follow the chain of events below When activated an unconfirmed alarm will be transmitted to the central station An output or digi channel may be programmed as perimeter or if using Point ID a new signal type of perimeter will be sent This will allow central station to inform the keyholder that an unconfirmed alarm has been received and is a perimeter type device i e window backdoor etc etc This feature is not mandatory for DD243 Scenarios Relating to DD234 Sounder Bell Considerations Please note careful consideration should be given when programming Confirm Sounder and Confirm Bell Modes If both are programmed for confirmed and any of the above scenarios occur no local sounders will activate Other DD243 Notes to Consider When a system auto re arms with a zone in fault condition The GardTec control panel will omit the zon
20. and the necessity to reset a mains fault for the time programmed 5 Press No until the required setting is displayed Then press Yes The display will show Tamper Reset Eng Anti When Alarm Restore is turned On the Digi channels programmed with Restore On will be restored when the system is unset rather than when the system is Reset 6 Press No until the required setting is displayed Am RESIS ON then press Yes The display will show for example Abort Time 60s 7 Press No The display will show os na O Ime gt S 8 Press No until the required abort time is set passa idl followed by Yes 0 180 seconds in increments of See 20 seconds Program Reset Mains 9 The display will show Page 66 10 11 This concludes the programming for Reset Modes To return to Press 0 zero twice Page 67 CPX Engineer s Reference Guide 01 Jan 00 00 01 CPX Engineer s Reference Guide Programming Sounder Levels 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Press No ten times The display will show Press Yes The display will show Press Yes The display will show Press No twice The display will show Enter a value 1 to 9 1 Low 9 High followed by Yes The display will show Press No The di
21. be covered in the Step by Step sections After completing the sections you should be confident to program the remaining options Page 16 CPX Engineer s Reference Guide Common Options with Menu Numbers You are able to jump to various common options when programming by entering the relevant menu numbers With a Header showing key in the appropriate menu number then press Yes Menu Jumps to PGM 1 Output Timer 1 On Time Timer 1 Off Time PA Mode Chime Level Entry Exit Level Exit Sounder Mode Final Set Delay Full Set Setting Time Setting Mode Part 1 Set Setting Time Setting Mode Part 2 Set Setting Time Setting Mode Part 3 Set Setting Time Setting Mode Alert 1 Keys Mode On Off Alert 2 Keys Mode On Off Install Keypads Bell Delay No of Bell Arms Bell Ring Time Sounder Mode NovActive On Off Bell Tamper Ring On Off Entry Time 1 Entry Time 2 Warning Bell Fire Zone Delay Digicom Type Key Beep Level Zone Re Arm Double Knock Time Engineer Code Line Fault Sounders Line Fault Mode Line Fault Log PGM 1 Output Main Fail Delay Tamper Reset Mode Backlight Mode Zone Response Zone Types Test Zone Attributes Save Panel NVM to PTM Service Timer Service Due Weeks Zone Log Limit Digicom Channels Alarm Restore Abort Time Test Digicom Channels E E Zones in Part Set Engineer Code Locked Unlocked Strobe Confirm Page 17 Menu 69 70 71 72 75 92 97 1
22. been programmed as engineer and Unconfirm reset is Normal then an engineer reset will be required for Un confirmed alarms Confirm Secondary Time Window default 60 minutes This time window may be programmed between 1 and 120 minutes we would suggest a time between 30 and 60 minutes but should typically be the same time as the confirm time window This option affects zones that have been allocated as secondary zones only For functionality please refer to Secondary Zones Below Page 80 CPX Engineer s Reference Guide ET Exit Terminator Mode default Set If ET Mode Set then the exit terminator zone will terminate the exit procedure If ET Mode Door Lock and the ET zone door lock is operated on entry then all confirmed alarms will be disabled Bell Mode default Unconfirmed This option controls the bells fitted to the system options are confirmed or un confirmed If Bell Trigger Confirmed then Bell will only trigger with a confirmed alarm If Bell Trigger Unconfirmed then Bell will trigger with un confirmed alarms This feature is not mandatory for DD243 Strobe Mode default Unconfirmed This option controls the Strobe s fitted to the system options are confirmed or un confirmed If Strobe Trigger Confirmed then Strobe will only trigger with a confirmed alarm If Strobe Trigger Unconfirmed then Strobe will trigger with un confirmed alarms This gives the ability to show to the keyholder from outsid
23. 3 omitted with tamper 15 Engineer Eng 1234 User 5678 4 5 or 6 digits 9 Characters Page 97 CPX Engineer s Reference Guide Custom Screen 32 Characters Maximum Output Current 1A See Power Supply Rating Log Size 250 Event Log 31 Event Modem Log Time amp Date Log amp Display Non Volatile Memory Yes Quiescent Currents Conirol Panel plus Keypad 150mA 12V d c Power Supply Rating It should be noted that the eur sec CPX has 1 Amp available for the full system However for the purpose of compliance to EN and PD6662 standard the capacities of the power supply have to be specified differently For a Grade 2 system you have 72 hours to charge the battery With the CPX Control Panel 90mA is available for battery charging This defines a theoretical maximum standby battery capacity of 8 0Ah and a maximum of 666mA available for system power If a smaller capacity battery is used then the rating has to be reduced accordingly For example If a 7Ah battery is used it will recharge in 72 Hrs and will theoretically provide 910mA 1000 90mA for the system However the supply rating for that system under PD6662 is still 7 0Ah 12hrs 583mA Sounders detectors and other auxiliary items should be included when calculating current drawn by the system Any damage caused through overloading the Control Panel Supply will not be covered by the warranty We recommend that additional power supplies are used to supply detectors on lo
24. 31 139 153 155 156 157 158 159 160 161 162 164 165 166 167 168 169 170 171 172 173 174 Jumps to Auto Part Set Part Set Bells Zone Types Enter Zones On Board Pairing Program Zone Wiring LCD Status List Event Log NovActive PSU Test Time Test Zones Confirm Time Window DD243 Section Secondary Time Window Confirm on Entry On Off Sounder Trigger Unconfirm Reset Mode E T Mode Bell Trigger Confirm Start Delay Strobe Timer Strobe Trigger Custom 1 OP Mode Custom 2 OP Mode Custom 3 OP Mode Custom 4 OP Mode Custom 5 OP Mode Custom 6 OP Mode Custom 7 OP Mode Custom 8 OP Mode Comms Restore On Off CPX Engineer s Reference Guide Programming Zones 1 2 3 4 5 6 7 8 9 With the display showing Enter the Engineer code 1234 default The display will show Enter the Authorisor code The Authorisor code is the Master User default 5678 The display will show Press YES The display will show This is Engineer Mode Press Yes The display will show Press Yes The display will show Enter the zone number you wish to program e g 1 followed by Yes The display will show for example Press No The display will show Note the chevron has now appeared before the Zone Type Now press the No key until the Zone Type you require is displayed Page 18 01 Jan 00 00 01 Enter Authorisor Do you want to
25. Choose from the following settings No Return Return PC Return 1 or 2 Return 1 Only Return 2 Only From Site Only Off Communication to the panel is from GardTec Remote via Patch Lead or PC Modem The panel will ring the PC back on the number the PC has passed to the panel The panel will ring back the PC on the 1 or 2 number programmed into the panel The panel will ring back the PC on the 1 number programmed into the panel The panel will ring back the PC on the 2number programmed into the panel Remote Access will be initialised by the user On Site Modem Functions are disabled 39 Press No until the required setting is displayed then press Yes The display will show Double Ring Off This option may be used when when the panel is on a shared line and GardTec Remote is also used 40 Press No until the required setting is displayed then press Yes The display will show Keypad Lock Of In Use Text Off You may continue to program other Modem options if required For the purpose of this Step by Step section 41 Press 0 zero The display will show 42 Press Yes The display will show Comms Off Program Comms Functions Page 53 CPX Engineer s Reference Guide 43 Press No twice The display will show Comms On 44 Press Yes The display will show for exam
26. LF Off Alert Off Fire Off W D Off Duress Off Zone Remove Off Alrm Restore Off AC Restore Off LF Restore Off After Alarm Off Abort Call Off Perimeter Off PA Restore Off Radio Lost Off Radio Jamm Off Zone Fault Off Zone Mask Off Program Digicom Channels CPX Engineer s Reference Guide 14 Press 0 zero three times The display will show 01 Jan 00 00 01 Linefault Sounders Description The Linefault Sounder option determines how the system sounders speakers will react when a Linefault is detected Below are the options available and a description of each option On if Set Linefault Sounders will operate when the system is Set and a Linefault is detected may be silenced by User Code On if Unset Linefault Sounders will operate when the system is Unset and a Linefault is detected may be silenced by User Code FLT if Off A fault tone will be generated when the system is Unset and a Linefault is detected may not be silenced by User Code Beep if Off A periodic beep will be generated when the system is Unset and a Linefault is detected may not be silenced by User Code Always On Linefault Sounders are always On Set or Unset may not be silenced by User Code Page 93 CPX Engineer s Reference Guide Engineer Res
27. Press Yes The display will show Press No until the display shows the required setting then press Yes The display will show Page 58 Program Zones Program Linefault Modes Program Linefault Sounders Linefault Sounders ON if Un Set Program Linefault Sounders Program Linefit Mode in Exit Lineflt Mode Detect in Exit Program Linefit Mode in Exit CPX Engineer s Reference Guide 9 Press No The display will show Program Linefit Log Mode 10 Press Yes The display will show Linefit Log Note Line Fault is defaulted to Limited and may not be changed Limited This limit is set to 3 events Program Linefit 11 Press Yes The display will show Log Mode i Program Lineflt 12 Press No The display will show Detect Time Detect 13 Press Yes The display will show San Sas With Detect programmed as 00 Linefault detection is instant or it may be delayed if required Detect 14 Press No twice The display will show gt __ Secs 15 Enter the time you require in seconds followed iel RA by Yes The display will show elect ime 16 This concludes the programming for Program ent Linefau
28. Set Please note we recommend that the Test Attribute is only used on 12Hr type zones To clear the display proceed as follows 1 Enter the Engineer Code The display will show Enter Authorisor 2 Enter a valid User Code The display will show Do you want to Use ENGNR Mode 3 Press No The display will show Do you want to SET the System 4 Press Yes The system will start to Set 5 Allow the system to fully Set 6 Enter the Engineer Code again to Unset the system The display will show 01 Jan 00 00 01 Page 96 5 SPECIFICATIONS CPX Engineer s Reference Guide Power Input Max Loop Resistance Loop Delay Time FUSES Mains Supply Fuse Battery Fuse Aux Fuse Keypad Fuse Battery Fuse Lead Low Voltage Output Battery Sizes Construction Complies with Conforms with Number of Zones Standard Expansion Type Number of Keypads Zone Descriptors Max No of Users Default Codes Code Length User Names 230V a c 10 50Hz 2K not with E O L 400mS 20mm 125mA Anti Surge 20mm 2A Anti Surge 20mm 1A Quick Blow 20mm 250mA Quick Blow 20mm 2A Anti Surge 13 8V dc Regulated 12V 1A2 2A 3A 7A 3mm Polycarbonate EN50131 1 PD6662 2004 CE tested EMC Directive 89 336 EEC amp LVD Directive 73 23 EEC 8 2 Wire 9 EOL 8 8 EOL 1 Radio Expander may be fitted 4 Normal 16 Characters last
29. W Bat When used zone should be connected to the trouble status output of third party radio equipment that is capable of giving a low battery signal Line Fault When used acts as a Line Fault input to the control panel Fault When used will act as an Fault input to the control panel when an internal fault has been detected within the PIR Mask When used will act as an input to the control panel if the detector has been blocked or covered Note Fault and Mask are treated as 24Hr but trigger a Fault Sound in Day Unset Mode The Fault sound is a three tone sounder Page 19 CPX Engineer s Reference Guide 10 When you are satisfied with your selection press Yes The display will show for example 001 Ent Ex gt Remove We will now be changing the Zone Attributes Options available are Remove The zone may not be Removed Omitted by the end user Part Sets are still allowed Remove DK Zone may be Removed Omitted by the end user and is a Double Knock Zone 2 activations required within time window or zone left open for 15 seconds Remove DK Zone may not be Removed by end user Part Sets are still allowed and is Double Knock Zone Off Zone is turned Off Use with caution Norm Key Zone is a Keyswitch Zone for a normal type Keyswitch Bias Key Zone is a Keyswitch Zone for a Bias momentary type Keyswitch Remove Zone may be Removed by end user 11 Press No until the setting you requ
30. be fitted to ONE RKP If the RKPs are wired in daisy chain format this should be the last RKP in the line Note Each keypad must be programmed onto the system in order for it to be recognised by the system Note Depending on the variant of keypad fitted external G Tag Proximity Reader s may be fitted to each Remote Keypad ol Note 680 Ohm resistor should be fitted to ONE of the RKPs If RKPs are wired in daisy chain this should be the last RKP in the line SNOILOSNNOO 4aqNvdXa Oldve sevSy za NYO 334 one aay 680 Ohm g 8 g gt 2 D z ta CvdA3y SLOWSY SNOILOANNOOD YAAA M AO D2 B D1 A OV 12V REMOTE KEYPAD S MAY BE WIRED IN STAR OR DAISYCHAIN FORMAT PROXIMITY READER S Note Please refer to the back of this manual if the Control Panel has been supplied with a 4 Wire Contour RKP with added zones for wiring information Page 7 CPX Engineer s Reference Guide Control Panel Output Connections facrarararalaalala BELL SAB J PGM1 SPR SPR AUX 12V Bell Trigger INTERNAL SPEAKERS MIN 16 OHM Strobe Trigger Bell Strobe Hold Off Bell Hold Off Supply Tamper Return EXTERNAL SOUNDER STROBE MODULE Digi Modem The eurdsec CPX control panels feature an onboard Digi modem The Digi provides all the features of an eight channel communicator whilst the Modem provides facilities for Ga
31. de PGM3 Mode Timer 1 On Time Timer 1 Off Time Reset Modes Mains Fail Delay Alarm Reset Tamper Reset Alarm Restore On Off Abort Time CPX Engineer s Reference Guide Headers amp Options Sounder Levels Chime Level Entry Exit Level Key Beep Level PGM1 Custom PGM1 O P Custom Output 1 Custom Output 2 Custom Output 3 Custom Output 4 Custom Output 5 Custom Output 6 Custom Output 7 Custom Output 8 Engineer Code Engineer Code Engineer Code Locked Unlocked Page 15 CPX Engineer s Reference Guide Headers amp Options Service Service Timer PTM Time To Next Service Service Tel No Lock Out On Off Engineer Mode Constant Timed Custom Screens LCD Status Display LED Status Display Diagnostics Log List Event Log Change List Diagnostics Headers amp Options Alarm Confirm Window Time On Entry Sounder Mode Reset Mode Secondary Time ET Mode Bell Mode Strobe Mode Start Delay Comms Restore Keypad Opening In conclusion the Yes and No Keys are used to navigate The No Key is also used to change a value may also require a numeric input and the Zero Key is used to move back a level not when display is expecting a numeric input If you are confident in programming the CPX Control Panel please use the headers and options above to continue Otherwise Please continue with the next section for a Step by Step Guide to programming the CPX Control Panel Only the major options will
32. e 1 and 2 have expired Press No to change the setting followed by Yes The display will show This concludes the programming for Entry Times Press 0 zero to return to Or Press 0 zero until the display shows Page 39 Program Entry Time 2 Program Entry Times 01 Jan 00 00 01 CPX Engineer s Reference Guide Programming Bells Sounders 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 Program _ With the display showing Zones 2 Press No three times The display will show Program ae Bells Sounders 3 Press Yes The display will show Program Bell Type 4 Press Yes The display will show NovActive Off For information on NovActive refer to page 89 5 This option should remain Off unless you are using a NovActive Bell Box Type SAB Press Yes The display will show Normal Two Types of Bell may be programmed SAB Self Actuating Bell The Bell terminal stands at 12V and the Bell terminal switches negative on activation SCB Self Contained Bell The Bell and Bell stand at 12V and Ov The OV is removed on activation The majority of Bells sold in the UK are SAB you should only change the Bell Type if you are sure the Bell Type you have is SCB The other option on this screen may be programmed a
33. e 41 CPX Engineer s Reference Guide 13 Press No The display will show Program Bell amp Sounder Ring Bell Ring 10 m Sounder Constant 14 Press Yes The Display will show 15 Press No twice The display will show Belling Som Sounder Constant 16 Enter the Bell Ring Time you require in minutes Bell Ring 15m followed by Yes The display will show Sounder gt Constant Note Bell Ring is defaulted to 10 minutes and is programmable from a minimum of 1 minute to a maximum of 15 minutes The term Sounder refers to the Internal Speakers fitted to the system and also the speaker s fitted to the RKPs Options available for Sounder are Constant Will continue after the Bell Time has elapsed Timed Will Time out with the Bell Time 17 Press No until your required setting is displayed then press Yes The display will show Strobe Timer 000m The Strobe light will normally continue after the Bell Time has elapsed You may Time the Strobe if required To do so 18 Press No twice The display will show Strobe Timer So 7M 19 Enter the time required in minutes followed by Program Bell Yes The display will show amp Sounder Ring Note Strobe Timer is defaulted to 0 minutes but is programmable to a maximum of 120 minutes Page 42 CPX Engineer s Reference Guide 20 P
34. e concerned A signal should be sent to the central station indicating that a detector s has have been isolated To achieve this a Digi channel should be programmed as Zone Exclude this will automatically send the required signal as the detector is omitted See A 3 1 DD243 IAS Incorporating Sequential Conformation Technology Only New Output Option Status A new output option of Status has been added this option has three operating modes and is intended to provide a visual indication of the system status System Set Output On for 10 seconds System Unset Output On for 1s Output Off for 1s for a 10 second period Confirmed Alarm Output On for 3 seconds Output Off for 1s until system reset It is envisaged that this status output would be fitted to an indicator i e LED that can be seen from outside the premises Page 82 CPX Engineer s Reference Guide a Scenario specific to systems using completion of unsetting with ACE 6 4 5 DD243 Event 1 System Set Event 2 Entry Time Starts Event 3 Access Zone Triggered Event 4 Entry Expired including Entry Time 2 Unconfirmed Transmitted Event 5 non entry access Zone Triggered Event 6 Second non entry access Zone Triggered Confirmed Transmitted To achieve the above Confirm on entry On Ace Low Battery On b Scenario Unlocking the initial entry door disables all means of conformation 6 4 3 DD243 Event 1 System Set Event 2 Entry Door Unlocked Confirmed Alarms Disabled
35. e the premises that a previously unconfirmed alarm is now confirmed This feature is not mandatory for DD243 Confirmed Start Delay default 000m May be programmed between 0 amp 120 minutes default 0 If programmed to anything other than O the panel cannot send confirmed signals until the time programmed has expired This time starts when the system has set and will prevent confirmed alarms being generated in situations when a person has been accidentally locked in the building This feature is not mandatory for DD243 Ace Low Battery default On Options are On or Off This option allows for the use of new control panel boards with V5 1 or later software to be used with earlier keypads If older non DD243 compliant type keypads are used with V5 1 or later this option should programmed to Off It is a requirement of DD243 2002 that when using ACE Low Battery is reported to the end user if the system is set using ACE Secondary Zones The Program Part Test Chime option has now been renamed to Program Zone Attributes Within this section you are able to allocate zones as Secondary Zones Secondary type zones would be used for detectors that may be deemed as having an over sensitive nature this will stop unwanted user call outs Zones that are entered as Secondary will follow the chain of events below Page 81 CPX Engineer s Reference Guide During a set period triggering a Secondary Zone will start the Secondary Time Window
36. ect Standard 1 BS 2EN2 Selecting 1 BS Panel may be programmed to comply with the old BS4737 Standards DD243 requirements will still apply Selecting 2 EN2 Panel may be programmed to comply with EN50131 1 for Grade 2 Systems DD243 requirements will still apply 5 Select 2 EN2 The display will then show This may show for several minutes Note This document assumes that 2 EN2 has been selected The display will then show 6 Enter Engineer code 1234 default The display will show 7 Enter the Authorisor code The Authorisor code is the Master User default 5678 The display will show Note It may be required that an engineer has to be authorised by a user before access to the engineer mode is granted 8 Press Yes The display will show Page 13 Please Wait 01 Jan 00 01 50 Enter Authorisor Do you want to Use ENGNR Mode Program Zones Zones CPX Engineer s Reference Guide 4 PROGRAMMING Moving Around Enter Engineer mode as described on page 13 The display will show Program Zones Whenever three underscores are shown on the display the screen is a header Pressing the NO key will move to the next header Pressing the YES key whilst viewing a header will enter into the options under that header Pressing 0 will escape back one step except w
37. equired setting is displayed Press Yes The display will show Ch2 Panic Ch3 gt Alarm shem Press No until the required setting is displayed Press Yes The display will show Ch5 Off Ch6 Off Press No until the required setting is displayed Press Yes The display will show Ch5 Off Ch6 gt Off Press No until the required setting is displayed Press Yes the display will show Ch7 Off Ch8 Off Page 51 CPX Engineer s Reference Guide 29 30 31 32 33 34 35 36 37 38 Press No until he required setting is displayed Press Yes The display will show Press No until the required setting is displayed Press Yes The display will show Press No The display will show Press Yes The display will show Press No The display will show Press Yes The display will show Press Yes if you require connection to a local PC The display will show Otherwise Press No The display will show Page 52 Ch7 Off Ch8 gt Off Program Digicom Channels Program Digicom Functions View Modem Log Program Modem Functions Access Via Local PC Remote Access Modem Mode Off CPX Engineer s Reference Guide
38. ess Yes The display will show Press No The Display will show Press Yes The display will show Press No twice The display will show Enter the time required then press Yes The display will show Press No The display will show Press Yes The display will show Press No until the required setting is displayed then press Yes The display will show Press No The display will show Page 86 Program Confirm Reset Mode Program Confirm Secondary Time Secondary Window 060m Secondary Window Program Confirm Secondary Time Program Confirm ET Mode ET Mode Set Only Program Confirm ET Mode upili Program Confirm Bell Mode 25 26 27 28 29 30 31 32 33 CPX Engineer s Reference Guide Press Yes The display will show Press No until the required setting is displayed then press Yes The display will show Press No The display will show Press Yes The display will show Press No until the required setting is displayed then press Yes The display will show Press No The display will show Press Yes The display will show Press No twice The display will show Enter the time required followed by Yes The display will show Page 87 Bell Trigger Unconfirmed
39. et If the system is programmed as Engineer Reset the system will need to be Reset by the Engineer Code Please follow the procedure below to effect the Reset 1 If the system is still set unset it via a valid User Code 2 Enter the Engineer Code The display will show ae Authornson 3 Enter a valid User Code The display will show Do you want to Use ENGNR Mode 7 Do you want to 4 Press No The display will show SET the System 5 Press Yes The system will start to Set 6 Enter the Engineer Code again This will Abort the Setting 7 The System is now Reset The display will show for example O1Jan 00 00 01 Details of User Code Reset and Anti Code Reset are given in the User Manual Page 94 CPX Engineer s Reference Guide Wiring Proximity E and I Readers T Reader Terminals RKP Terminals Single E Reader up to 7 5m E Reader Wiring RKP Terminals 2 RED m BLUE m 3 YELLOW A ia BLACK gt iu Single E Reader 7 5m to 15m E Reader Wiring RKP Terminals 2 RED m GREEN a 3 YELLOW A fd BLACK gt iu Details on wiring multiple Readers are provided with the Reader Page 95 CPX Engineer s Reference Guide Clearing Test Fail Indication If the display shows Unset Test Fail 01 Jan 00 00 01 The system has a zone On Test that has failed when the system was
40. eurosec GPX Control Panel Engineer s Reference Guide CPX Engineer s Reference Guide CONTENTS IMPORTANT icescieetist cece snesscteesscemuteeievereiectes INtFOCUCTION ececeseseeensteeeenseeessneeenseeenensnenenne System Installation Wiring sseeeeee Resetting Factory Defaults ssseessseseees Programming ccseeeeeseseeeeseeeeeseeeeeeseeeeenseeneneees Moving Around seere Headers amp Options ceeeeeeeeeeeeeeeeee kh WON Common Options with Menu Numbers Programming ZONES sseeeseeeeseeeees Reporting a Mains Fail on a PSU Programming Setting Modes Programming Entry Times eee Programming Bells Sounders Programming Keypad esee Programming Digicom Vo Comm Off On Programming Linefault Modes Programming Panic eeseeeeseeeees Programming PGM2 PGM3 Timers Programming Reset Modes 6 Programming Sounder Levels Programming PGM 1 Timers Programming Engineer Code Programming Service s es Programming Custom Screens Programming Diagnostics Log Programming Alarm Confirm Notes Programming Alarm Confirm Scenarios Programming Alarm Confirm 06 NovActive Description amp Programming Programming Point ID amp SIA Protocols Linefault Sounders Description
41. gineer s Reference Guide Reporting a Mains Fail on a PSU In order to report a Mains Fail on a PSU the Fault output on Program Zone the PSU would be wired to a Zone on the Control Panel Event Tags 2 The Zone Type would be programmed as Fault Program the Zone Descriptor as External PSU At the end of the Program Zones menu we have a menu called Program Events Tags enter this option and select the Zone number you have programmed as Fault Program the Tag as Mains Fail Then program a Digi Channel as Mains Fail This will allow for full reporting of External PSUs Page 30 CPX Engineer s Reference Guide Programming Setting Modes Setting Modes are the modes that the control panel will use to set the system for a particular type of set An example of this may be that the Full Set Modes is programmed as Final Exit Door door opening and closing during exit will set te panel whilst the Setting Mode for Part Set 1 is timed Each type of Set Full Part 1 Part 2 Part 3 may have its own Setting Mode 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Program yo Zones 2 Press No The display will show Program Setting Modes 3 Press Yes The display will show Program Setting for FULL set 4 Press Yes The display will show F Exit time 30s Set b
42. he No amp the Yes buttons together on the selected keypad The display will show Page 46 Install Keypad Enter Keypad _ then YES or NO Press NO YES on Selected Keypad Keypad Installed OK 22 23 24 25 26 27 28 29 30 CPX Engineer s Reference Guide Then Repeat from Step 19 until all the RKPs have ben installed onto the system Press 0 zero The display will show Press No The display will show Press Yes The display will show Press No until the setting you require is displayed then press Yes The display will show Press No The display will show Press Yes The display will show Note Use of this option will require a compatible G Tag RKP Enter Keypad _ then YES or NO Program Keypad Number Program Keypad Backlight Mode Backlight On if EE Key Program Keypad Backlight Mode Program Keypad ACE Prox Prox Tamp Detect Off Default is Off but maybe changed to On It is intended for use with the external prox reader E Reader and monitors the antenna of the reader for being disconnected Press No until the setting you require is displayed then press Yes The display will show This concludes the programming for Keypad Press 0 zero to ret
43. hen a numeric entry is required You are able to jump to various common options when programming by entering the relevant menu numbers With a Header showing key in the appropriate menu number then press Yes See Page 17 for Common Options with Menu Numbers Below is given a complete list of headers Shown in Bold Underline and options that appear under each header Headers amp Options Program Zones Zone Types Zone Descriptors Zone Wiring Zone Attributes Test Part Chime Zone Double Knock Arm Log Zone E E Mode Event Tags Setting Modes Setting For Full Sets Setting For Part 1 Sets Setting For Part 2 Sets Setting For Part 3 Sets Setting Delay Setting Sounders Setting Conformation Auto Part Set Headers amp Options Entry Times Entry Time 1 Entry Time 2 Bells Sounders Bell Type Bell Delay No Arms Bell amp Sounder Ring Bell Tamper Mode Bell For Part Set Keypad Keyswitch Keypad Alert 1 Keys Keypad Alert 2 Keys Quick Key Number of Keypads Keypad Backlight Mode Ace Prox Page 14 Headers amp Options Digicom Type or Test Vo Comm Start Delay Channels Digicom Modem Functions Line Fault Modes Line Fault Sounders Line Fault Mode in Exit Line Fault Log Mode Line Fault Detect Time Panic Duress PA Mode Testable Non Testable Duress Off To conform with EN standards Duress is defaulted to Off and cannot be changed PGM2 PGM3 Timers PGM 2 Mo
44. ial power up will revert the Master Code and Engineer Code not locked engineer code back to factory defaults b Pressing 3 7 YES NO during initial power up will revert all system settings back to defaults with the exception of the User Names and Zone Descriptors c Pressing 4 6 YES NO during initial power up will revert all system settings back to factory defaults It is ESSENTIAL that a 4 6 YES NO reset is done to all new systems before commencement of programming d Pressing 5 5 YES NO during initial power up will revert all system settings to factory defaults and will also set the comms options up for GardTec Remote ie Modem On No Return For commissioning systems for use with GardTec Remote use this option Page 12 CPX Engineer s Reference Guide Reset of the factory defaults and entering Engineer Mode Note Itis ESSENTIAL that a 4 6 YES NO reset is done to all new systems before commencement of programming 1 Remove all power from the system for at least ten seconds 2 Apply mains power to the control panel The display will show for example Display will differ dependant on panel version 3 Whilst this display is showing the first five seconds press the keys shown in a b c or d for the reset required E g 4 6 Yes No The display will show This may show for several minutes 4 The display will then show Eurosec CPX xx xx Please Wait Sel
45. ied out at the time interval set here and each time you leave Engineer Mode This may be turned Off by setting the Time interval to O zero Press No twice The display will show Enter the time you require in hours followed by Yes The display will show Press Yes The display will show In this example any voltage over 14V or below 13V will create a warning when the PSU test is performed by the system To change these limits Press No until the required setting for V Max is displayed then press Yes The display will show Page 77 List Event Log Change List Diagnostics PSU Diagnostics PSU Test Time 01 Hrs PSU Test Time __Hrs Change List Test Limits Aux VMax 14 0V Aux VMin 13 0V Aux VMax 14 0V Aux VMin gt 13 0V CPX Engineer s Reference Guide 14 15 16 17 18 19 20 Press No until the setting required for V Min is displayed then press Yes The display will show Press No until the required setting for On Charge Volts max Battery is displayed then press Yes The display will show Press No until the required setting for On Charge Volts min Battery is displayed then press Yes The display will show Press No until the required setting for Off Charge Volts max Battery is displayed then pre
46. ire is displayed then press Yes 12 The display will show the next zone to program You should repeat from Step 7 until you have programmed all the zones 13 When all required Zones have been programmed press 0 zero key twice The display will show Program Zone Types z f Program Zone 14 Press No The display will show Descriptors 15 Press Yes The display will show Enter Zone ___ Page 20 16 17 18 19 20 CPX Engineer s Reference Guide Enter the Zone number you wish to program the Descriptor for followed by Yes Zone 001 Name The display will show for example Zone 001 Press No The display will show Zone 001 Name You should now program the Descriptor you require using the template below for the key allocation in a similar way that you you would type a text message on a mobile telephone As the desired character is displayed press the Yes key to move on to the next character Continue until the line is complete 1 2 3 ABC DEF GHI 4 5 6 JKL MNO PQR 7 8 9 STU VWX YZ Space No 0 Yes Delete 1234567890 Enter Character As you enter the last character the display Zone 001 Name will move on to the next Zone For example Zone 001 Repeat from Step 16 until all the Descriptors you require have been programmed Then press 0 zero key twice The display will show
47. lay in Part Set followed by Yes Digi Delay 99s The display will show for example Part Alarm gt On 14 Press No until the required setting is displayed Program Digicom then press Yes The display will show Delay Part Program Digicom 15 Press No The display will show Channels Page 49 CPX Engineer s Reference Guide 16 Press Yes The display will show Ch1 Off Ch4 Off When programming Digicom Channels Channel 1 is normally Fire Channel 2 is normally PA Panic Channel 3 is normally Alarm unconfirmed and Channel 4 is normally Open Close Channels 5 6 7 amp 8 will be advised by your Central Station Other signals you may require for DD243 are Alarm Abort Zone Exclude Alarm B Confirmed Channel settings available are Off Zone 24Hr Gen Tamper Alert Fire Part Set Open Close Panic Alarm Alarm B Alarm Abort Power Fail Watchdog Mains Fail Perimeter Zone Exclude Const Lo Bat Radio Radio Lost Radio Const Jjam Radio 17 Press No until the required setting is displayed 18 Press Yes The display will show Ch1 Off Ch4 gt Off Page 50 19 20 21 22 23 24 25 26 27 28 CPX Engineer s Reference Guide Press No until the required setting is displayed Pr Yes The display will show WEEMS e display Ch2 Panic Ch3 Alarm Press No until the r
48. ll terminals Up to 8 custom outputs may be programmed on to PGM 1 to 3 A custom output may be used so that the output can follow a zone or a user code 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Program aoa Zones 2 Press No eleven times The display will show Program eee PGM1 Custom 3 Press Yes The display will show PGM1 O P Pulse Off V The options available for PGM1 are shown on page 62 4 Press No until the required setting is displayed BGI OIE then press Yes The display will show Pulse Off sey With the PGM2 programmed as Bell the output will operate with the Bell when this is set as V With this set as V the output will be inverted e g On turning Off with the Bell 5 Press No until the required setting is displayed then press Yes The display will show Cus 1 Zone 000 Day Fol t 00 6 Press No to change the Cus 1 to Zone Code or Group as required to follow Press Yes Cus 1 Z gt 000 The display will show RURAN Day Fol t 00 Page 70 10 11 12 13 14 CPX Engineer s Reference Guide Press No The display will show Enter the Zone Number or Customer Number that you wish the output to follow then press Yes The display will show for example Press No to select when you
49. lt Sounders Press 0 zero to return to Linefault Modes Or Press 0 zero until the display shows olan 00 00 01 For information on Linefault Sounders refer to page 93 Page 59 CPX Engineer s Reference Guide Programming Panic Note Duress is defaulted to Off and cannot be changed Duress 7 is now no longer available You should also check current legislation if Panic signals are allowed for the grade of system that you are fitting 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 ee ae Semen With the display showing ones i j i ag Program am 2 Press No seven times The display will show Sane Dawe 3 Press Yes The display will show PA Bells Only Non Testable It should be noted that with PA Bells Only no PA signals will be sent to Central Station Available setting for PA are Bells Only Activating a Panic will only sound the Bells Bells Always Activating a Panic will Sound the Bells and send a signal to Central Station provided that a Digi Channel is programmed as Panic Silent Always Activating a Panic will only send a signal to Central Station providing that a Digi Channel has been programmed as Panic Bells if LFIt As Silent Always but will revert to Bells if a Linefault is present Page 60 CPX Engineer s Reference Guide Press No until the required setting is displayed then pres
50. m Setting for Auto Part Auto Part Set allows the system to decide if the Setting should be Full Set or Part 1 Set In order to use this option the Setting Mode for Full Set MUST be Time E E and a Door Contact must be fitted to the door If the system sees the door open and close during a setting procedure the system will Full Set If the system does not see the door open and close during a setting procedure the system will Part 1 Set It is not possible to use Silent Part Sets with this option as the decision to do a Part 1 set is taken after the Entry Time has expired Page 36 40 41 42 43 CPX Engineer s Reference Guide Press Yes The display will show To change this press No twice The display will show Press Yes The display will show This concludes the programming for Setting Modes Press 0 zero to return to Or Press 0 zero until the display shows Page 37 Auto Part Set Off Auto Part Set On Program Setting for Auto Part Program Setting Modes 01 Jan 00 00 01 CPX Engineer s Reference Guide Programming Entry Times Two Entry Times are available Entry Time 1 amp Entry Time 2 On entry to the premises via the Entry Door Entry Time 1 will start If deviation from Entry Route during Entry Time 1 then Entry Time 2 starts Entry Time 2 is 30
51. ne Doubling Detector on Zone 1 will be Zone 1 and the Doubled Zone will be Zone 9 Zone 2 will be Zone 2 and the Doubled Zone will be Zone 10 E g Zone number 8 Zone number for Doubled Zone The Zone triggered will be identified through the resistor value by the system Page 10 CPX Engineer s Reference Guide Radio Zone Expander One GardTec Radio Zone Expander may be fitted directly to the RS485 Bus connec tions on the control panel PCB without the need for any interface card A Radio Expander card will allow eight wireless zones amp eight wireless Fobs Radio Zone Programming When programming Radio Zones the zone numbering for the Radio Zones will start at 91 When programming Radio Fobs the numbering of the Fobs will start at 81 RADIO EXPANDER WIRING amp SWITCH SETTINGS SNOILOANNOD 43QNVdxX4 O1dVY S8vSY NYS THA a Gay KEY ZONE RECEIVER ID ID DIP SWITCH SETTINGS Resistor Colour Codes 6K8 12K 16K 27K 4K7 Blue Brown Brown Red Yellow Grey Red Blue Violet Violet Red Orange Orange Orange Red Brown Brown Brown Brown Brown Page 11 CPX Engineer s Reference Guide 3 RESETTING FACTORY DEFAULTS Several reset to factory default routines are available to the engineer at system power up but it should be noted that none of these routines will Un Lock a Locked Engineer Code The following default routines are available a Pressing 1 9 YES NO during init
52. nes so the display shows Channel 12345678 R Rep 11111111 58 Press Yes The display will show Open Close Channel s 4 Channel 4 normally needs an inversion of the signal that is sent to Central Station By having 4 as the setting for this option channel 4 will be inverted If you have reports from the Central Station that the Open Close channels are the wrong way around proceed as follows to remove the inversion on the control panel 59 If you do not need to change this option press Yes and jump to Step 61 Or To change the setting Press No The display will show Open Close Channel s gt _ _ 60 Press 0 followed by Yes The display will show Program Advanced Functions Page 56 CPX Engineer s Reference Guide You may continue to program other Advanced options if required For the purpose of this Step by Step section Program 61 Press 0 zero three times The Display will show Digicom Page 57 CPX Engineer s Reference Guide P 1 rogramming Linefault Modes Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Press No six times The display will show Press Yes The display will show Press Yes The display will show Press No until the required setting is displayed then press Yes The display will show Press No The display will show
53. ng cable runs Page 98 CPX Engineer s Reference Guide AUX 12V Terminals This pair of terminals supply the and supply for the detectors 1A is available from these terminals see power supply rating above Strobe Terminals This pair of terminals are the output for the Strobe The negative terminal is switched during an alarm period A maximum of 600mA may be drawn from these terminals see power supply rating above Bell Terminals This pair of terminals are the output for the Bell or external sounder The negative terminal is switched during an alarm period A maximum of 1A may be drawn from these terminals see power supply rating on previous page Page 99 CPX Engineer s Reference Guide 6 4 WIRE ContouR RKP WIRING INFORMATION CPXkeypad Connection Details Note 680 Ohm resistor should be fitted to ONE of the RKPs If RKPs are wired in daisy chain this should be the last RKP in theline g00hm 8 219 2 ry za 2 20 2 Ay a os 4 2 AO 36 3 z x z0 6 A1 amp A2 if used are connected to the first reader antenna If using an second reader remove the link and connect between A3 amp A4 Remove 2K2 if using Keypad Zones and use resistor EOL za 10 ao fazano 22 S Q P O Q Q O 4 Wire Contour RKP REMOTE KEYPADIS MAY BE WIRED GTAG IN STAR OR PROXIMITY DAISYCHAIN READER S FORMAT Note Keypad zones are Keypad Zone Wiring Detail
54. o the wiring section within this manual If selecting 9 EOL follow steps 24 through to 26 If selecting 8 8 EOL jump to step 28 On Board Zones 25 With the display showing ea aa Press Yes On Board EOL Norm 26 The display will show Page 22 CPX Engineer s Reference Guide Three wiring options are available under 9 EOL Norm Standard GardTec wiring configuration without Mask or Fault detection Note Does not give any Fault or Masking detection and should only be used with Zone pairing ELF1 ELF1 wiring is used for detectors that have a relay output a pair of terminals for Fault or Mask ELF2 ELF2 wiring is used for detectors that have a transistor output a single terminal for Fault or Mask Note We would recommend that either ELF1 Format or ELF2 Format dependant on detector output type Relay or Transistor is used ELF1 or ELF2 wiring modes will allow for Alarm Tamper Fault and Masking to be monitored from a single zone without the need for zone pairing Note The installer should check what output type the detector are noting that all the detectors should be of the same type with regards to the Fault Mask output 27 Press No until the setting you require is displayed Radio ZEX then press Yes The display will show Off If 8 8 EOL wiring option is required On Board Zones 28 With the display showing 9 lt EOL gt Press N
55. o until 8 8 lt EOL gt is displayed On Board Zones The display will show gt 8 8 lt EOL gt 29 Press Yes The display will show On Board Pairing Off Zone Pairing A zone is used to monitor Masking and Fault This is achieved by selecting Zone Pairing as on Zone Pairing cannot be used in ELF1 or ELF2 wiring modes When using Zone Pairing each zone will have a corresponding paired zone that will be used for Masking and Fault signals This is done by using the Odd numbered zones for the normal alarm detection and the Even numbered zones for Masking and Fault Detection For example Alarm Zone Zone 1 Pared Zone for Mask Fault Zone 3 Zone 2 Zone 5 Zone 4 Zone 7 Zone 6 etc Zone 8 Please note that half the zones on the system would be lost for processing the Mask and Fault signals and it would be more prudent to use the ELF1 or ELF2 modes as described previously Page 23 CPX Engineer s Reference Guide 30 31 32 Press No until the setting you require is displayed Then press YES The display will show With the display showing If you are not using Radio Detectors press Yes and jump to Step 33 Otherwise Press No until the display shows Page 24 Radio ZEX Off Radio ZEX Off Radio ZEX On CPX Engineer s Reference Guide Comprehensive instructions on how to setup and
56. or the Zone Programming You may continue within this section to program Secondary Zones Perimeter Zones Double Knock Time Window Zone Re Arm Zone Log Limit Zone E E Mode Event Tags Press 0 zero twice to return to Program rat Zones At this point you may press No to move to the next Header Or Press 0 zero until the display shows 01 Jan 00 00 01 Secondary Zones Zones programmed as secondary will not active any sounders or comms until a normal zone activates This will then trigger a confirmed signal and activate the sounders as programmed Perimeter Zone Zones programmed as perimeter will activate the alarm as normal but will also activate a comms channel programmed as perimeter DKnock Arm Log Note Note Zones on double knock are required to activate within the double knock time window or stay active for fifteen seconds to generate an alarm condition Arm is used to program the zones to automatically re arm after an activation It should be noted that a zone still violated when the system times out after an alarm will not re armed Zone Log Limit is defaulted to On and may not be changed Only five activations from any one zone will be recorded in the log during any set period E E in part set entry exit zones will start the entry timer if opened in part set 12Hr in part set entry exit zones will be instant when opened in part set Page 29 CPX En
57. out of Engineer Mode after 1 hour if all the Tampers are clear This prevents the Engineer accidentally leaving the panel in Engineer Mode Press No until the required setting is displayed then press Yes The display will show This concludes the Program Service Press 0 zero twice to return to Page 74 Next Service due in _ _ Weeks Service Tel No is Un Programmed Service Tel No LOCK OUT On Engineer Mode Constant Program Service PTM 01 Jan 00 00 01 CPX Engineer s Reference Guide Programming Custom Screens 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Program eee Zones 2 Press No fourteen times The display will show Program he Custom Screens 3 Press Yes The display will show LCD Status None Note The LCD Status is defaulted to None and may not be changed The display will only show the Set Unset status of the system for ten seconds after a Set or Unset 4 Press Yes The display will show eee The LED Status refers to the LED in the G Tag E or P reader Choose from Off The reader LED will only show for ten seconds after a Set Unset On The reade
58. ovActive Description amp Programming NovActive utilises a four core bus to the NovActive sounders that are fitted to the system This allows each individual Bell to to programmed and also gives access to unique Diagnostic Features that allow the individual NovActive sounders to be diagnosed from either the control panel or via GardTec Remote PC Software GardTec Remote may be used from either a remote location via a Modem or on site via a GardTec Modem Patch Lead To program the NovActive sounder s please follow the instructions below Wiring of the NovActive should be carried out in conjunction with the instructions supplied with the unit 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Program ae Zones 2 Press No three times The display will show Program Bells Sounders 3 Press Yes The display will show Program Bell Type 4 Press Yes The display will show NovActive Off 5 Press No twice The display will show NovActive gt On 6 Press Yes The display will show Select NovActive 1 8 Page 89 CPX Engineer s Reference Guide 7 8 9 10 11 12 13 14 Press the number of the NovActive you wish to program The display will show Press No twice to turn NovActive 1 On Then press Yes The display will show To
59. ow Z oim Confirm Window Press No twice The display will show iH S Enter the time you require followed by Yes The time MUST be between 30 amp 60 minutes Page 84 10 11 12 13 14 15 CPX Engineer s Reference Guide The display will show Press No The display will show Press Yes The display will show Confirm on Entry may be On only if you are using an ACE device to Unset the system Press No until the required setting is displayed then press Yes The display will show Press No The display will show Press Yes The display will show The term Sounder relates to the system speaker s Press No until the required setting is displayed then press Yes The display will show Press No The display will show Press Yes The display will show Page 85 Program Confirm Window Time Program Confirm On Entry Confirm on Entry On Program Confirm On Entry Program Confirm Sounder Mode Sounder Trigger Unconfirmed Program Confirm Sounder Mode Program Confirm Reset Mode Unconfirm Reset Any CPX Engineer s Reference Guide 16 17 18 19 20 21 22 23 24 Press No until the required setting is displayed then pr
60. ple Site ID Code Is Un Programmed In the UK the Site ID Code is normally a four digit number your Central Station may have supplied you with a six digit number If this is so please use the last four digits 45 Press No The display will show Site ID Code 46 Enter your Site ID Code followed by Yes The display will show Phone Number 1 is Un Programmed We will be entering two Phone Numbers If your Central Station has only supplied you with one Phone Number please use the same one twice 47 Press No The display will show Phone Number 1 48 Enter Phone Number one followed by Yes The display will show Inhibit Display of New Number 49 Press Yes The Display will show Phone Nimber is Un Programmed 50 Press No The display will show Sees NIMBE Page 54 51 Enter Phone Number 2 followed by Yes The display will show 52 Press Yes The display will show CPX Engineer s Reference Guide Inhibit Display of New Number Dial Tone This option refers to the line mode of the telephone line In the UK most telephone lines are Tone Dial 53 Press No until the required setting is displayed then press Yes The display will show Line Monitor Tone Volts Settings available for Line Monitor are Tone
61. program the LED pattern press No until the setting required is displayed Choose from 0 Alternating LEDs 1 1 Static LED 2 2 Pulsing LEDs 3 No LEDs When you are happy with your selection press Yes The display will show To program the Setting Confirmation press No until the required setting is displayed then press Yes The display will show To programme the sound press No until the required setting is displayed then press Yes The display will show for example Repeat for Alm Tmp until the required settings are displayed Then press Yes The display will show Press No The display will show Enter the text required E g Front Wall Bell Then press Yes The display will show Note See Page 10 for entering text instructions NovA1 Off LEDS 0 Confirm Off NovA1 On LEDS gt 0 Confirm Off NovA1 On LEDS gt 0 Confirm gt Off NovA1 A PA 0 Alm 0 Tmp 0 PA 3 Alm gt 0 Tmp 0 NovA1 A NovA1 Text NovActive NovA1 Text I V Select NovActive 1 8 You should now repeat until all the NovActives on the system have been programmed When you have finished programming all the NovActives press 0 until the display shows Page 90 01 Jan 00 00 01 CPX Engineer s Reference Guide Programming Point ID amp SIA Protocols
62. program the Radio Expansion are given in the document Hybrid Wireless Set Up amp Programming Guide supplied with the Radio Receiver 33 Press Yes The display will show Program Radio Functions 34 Press No The display will show Program Zone Wiring 35 Press No The display will show Program Zone Attributes 36 Press Yes The display will show Test None Any 12Hr type zone s may be placed on Test A Zone on Test will never trigger an alarm or send a central station signal If the Zone s fails the Test when the system is Set the display will show Test Fail when the user Un Sets the system After 20 successful Sets and Un Sets the Zone s will be taken out of Test by the system To reset a Test Failed display FULLY Set then Unset the system 37 If you do not wish to put a Zone s on Test press Yes and jump to Step 43 Otherwise 38 Press No The display will show Enter Zone __ then YES or NO 39 Enter the Zone number you wish to place on Test followed by Yes The display will show for example Test 003 40 To add more Zone s to the Test repeat from Step 38 Page 25 CPX Engineer s Reference Guide 41 When you have finished adding Zones to Test press Yes 42 The display will show Pt 1 None Three Part Sets are available on the CPX cont
63. r LED will always be active 5 Press No until the setting you require is displayed Program wan then press Yes The display will show Custom Screens 6 This concludes the Program Service Press 0 zero twice to return to 01 Jan 00 00 01 Page 75 CPX Engineer s Reference Guide Programming Diagnostics Log The CPX control panel has some limited diagnostic features available to the engineer To access these proceed as follows 1 2 3 4 5 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Press No fifteen times The display will show Press Yes The display will show Press Yes if you wish to view the Event Log The display will show for example This is the last event in the Log Use the No key to move backward in the Log Use the Yes key to move forward in the Log When you have finished viewing the Log press O zero The display will show Page 76 Program Zones Program Diagnostics Log List Event Log Eng Code 01 Jan 01 18 12 Program Diagnostics Log 10 11 12 13 CPX Engineer s Reference Guide Press Yes the display will show Press No The display will show Press Yes The display will show Press Yes The display will show A PSU Battery test will be carr
64. rdtec Remote Upload Download software package Telephone Connections lo Terminal 5 Serial z on other extension sockets Telephone Connection Q amp on fe case sockets Depending on model AS B2 IN IN 2 Terminal 3 on other extension sockets Terminal 5 Terminal 3 on existing BT Master socket on existing BT Master socket Terminal 2 on existing BT Master socket Standard S 2 Telephone Connection als a mM We Terminal 5 Terminal 2 on sa s BT socket on existing BT socket OR seen A Terminal B on BT Terminal Block on BT Terminal Block Page 8 CPX Engineer s Reference Guide Typical Novagard 2G 2G Connections NovaGard 2G 4G CPX Control Panel Strobe terminals omitted Control Panel Input Zone Connection where Anti Mask detectors are used Ori Ak N C Devices C 4 7 N C Devices S gt is N C Devices N je L4 a F gt i N C Devices N Y j 6k8 Please see following page for further wiring modes 7 E N C Devices wi o k7 2 N C Devices A r 6k8 A Oo i hg N O Devices PA etc IE 4k7_ _ connect across Tamper amp Zone S N C Devices N Tamper Zone T 4 becomes Zone 9 ONLY when 9 EOL is selected 8ZV gt AKT N C Devices N ay gt o td N C Devices N ie gt O AKT
65. ress No The display will show Program Bell Tamper Mode 21 Press Yes The display will show Bell Tamper Ring On With the Bell Tamper Ring On tampering the Bell Box will also trigger the Bell Output from the control panel With Bell Tamper Ring of the Bell Trigger from the panel is not activated 22 Press No until your required setting is displayed then press Yes The display will show Program Bell Tamper Mode 23 Press No The display will show Program Bell for Part Set 24 Press Yes The display will show eer On 25 Press No until the required setting is displayed then press Yes The display will show Program Bell for Part Set 26 This concludes the programming for Bells amp Sounders Press 0 zero to return to ry rogram Bells Sounders Or Press 0 zero until the display shows 01 Jan 00 00 01 Page 43 CPX Engineer s Reference Guide Programming Keypad Up to 4 RKPs Remote Keypads may be fitted to The CPX control panel on a 4 wire BUS A four core connection will be required between the control panel and the remote keypad s keypads maybe in a daisy chain or star format Note A 680 Ohm resistor must be fitted to ONE RKP If the RKPs are wired in the daisy chain format then this should be the last in the line No
66. rogrammed into Ch2 When the system is Unset opening the Front Door will produce a Chime Opening the Rear Door will produce a different Chime It should be noted that Chime must be programmed as On from the user mode Please refer to the User Manual for details Page 27 CPX Engineer s Reference Guide 53 54 55 56 57 58 59 If you do not wish to enter Ch1 Zone press Yes and jump to Step 57 Otherwise Press No The display will show Enter the Zone number you require for Ch1 followed by Yes The display will show for example To add more Zones to Ch1 repeat from Step 53 When you have finished adding Zones to Ch1 press Yes The display will show If you do not wish to enter Ch2 Zone press Yes and jump to Step 62 Otherwise Press No The display will show Enter the Zone number you require for Ch2 followed by Yes The display will show for example Page 28 Enter Zone _ then YES or NO Ch1 001 Ch2 None Enter Zone ____ then YES or NO Ch2 006 60 61 62 63 64 65 CPX Engineer s Reference Guide To add more Zones to Ch2 repeat from Step 58 When you have finished adding Zones to Ch2 press Yes The display will show See notes on Sec amp Per after step 65 Sec None This concludes the Step by Step instruction f
67. rol panel Zones added to the PT 1 Part 1 screen will be Removed Omitted when the system is Part 1 Set Zones added to the PT 2 Part 2 screen will be Removed Omitted when Part Set 2 is used When Part Set 3 is used Parts 1 amp 2 are combined and Removed Omitted 43 If you do not wish to enter PT 1 Zone press Yes and jump to Step 47 Otherwise Press No The display will show Enter Zone __ then YES or NO 44 Enter the Zone number you require for PT 1 followed by Yes The display will show for example Pt 1 004 45 To add more Zones to PT 1 repeat from Step 43 46 When you have finished adding Zones to PT 1 press Yes 47 The display will show Pt 2 None Page 26 48 49 50 51 52 CPX Engineer s Reference Guide If you do not wish to enter PT 2 Zone press Yes and jump to Step 52 Otherwise Press No The display will show Enter Zone then YES or NO Enter the Zone number you require for PT 2 followed by Yes The display will show for example Pt 2 005 To add more Zones to PT 2 repeat from Step 47 When you have finished adding Zones to PT 2 press Yes The display will show Ch1 None Two Chime suites are available on the CPX control panel so for example you would have the Front Door on Zone 1 programmed into Ch1 and the Rear Door on say Zone 6 p
68. s Normal Normal UK trigger for the UK Irish A Pull Up resistor is required on the Bell Trigger this option is only required for the Irish Republic Page 40 CPX Engineer s Reference Guide 6 Press Yes The display will show Program Bell Type 7 Press No The display will show Program Bell Delay No Arms 8 Press Yes The Display will show ET No Arms 99 9 Press No twice The display will show Bell Delay m No Arms 99 10 Enter the number of minutes you require for the Bell Delay followed by Yes Bell Delay 00 m The display will show No Arms gt 99 Note Bell delay is defaulted to 0 but maybe programmed to a maximum of 10 minutes Be careful when using Bell delay the Bell will not sound for the period programmed after the the alarm has been activated Bell Delay used to be a Police requirement but is now not often used in the UK 11 Press No The display will show Bell Delay 00 m No Arms gt _ Number of Arms is the number of times the bell is capable of sounding during a Set period It is normal to set this option to 3 or 4 If left at 99 the number of Arms is infinite Note If this option is programmed to 0 the bell will not activate 12 Enter the required Number of Arms followed by Yes The display will show Program Bell Delay No Arms Pag
69. s Yes The display will show Press No until the required setting is displayed then press Yes The display will show Note Duress is defaulted to Off and may not be changed Press Yes The display will show Press 0 zero until the display shows Page 61 PA Bells Only gt Non Testable Duress Off Program Panic Duress 01 Jan 00 00 01 CPX Engineer s Reference Guide Programming PGM2 3 Timers PGM2 refers to the PGM2 terminal on the control panel PCB situated near to the RKP terminals PGM3 Refers to the Strobe terminal if this is not used for the Strobe for example if a NovActive Bell Box is used it may be re programmed for other uses One Timer is also available It should be noted that the times programmed will operate seven days per week you are not able to program separate time for weekends etc 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Program ao Zones 2 Press No eight times The display will show Program ee PGM2 3 Timers 3 Press Yes The display will show Program PGM2 3 Operating Modes 4 Press Yes The display will show PGM2 O P Bell V Options available for PGM2 3 are Bell Strobe Latch Any Any Digi Status Perimeter Zone Exclude
70. s preset and cannot be changed E E 3K3 KP Zone 1 Part E E 5K6 KP Zone 2 EOL 2K2 Power AlarmN C Tamper N C Power AlarmN C Tamper N C 1st Detector 2nd Detector Note Both detectors must be run on a single cable Power Alarm N C Tamper N C radi from the Keypad to the first detector 2nd Detector Door Contact then the second The 2K2 resistor must be in the last final detector Note All keypads on the same system MUST be of the same type i e All four wire or all six Note All Keypads MUST be connected before powering up the Control Panel Page 100 CPX Engineer s Reference Guide Notes Page 101 CPX Engineer s Reference Guide Notes Page 102 Gard lec G R O U P RISCO Group UK Ltd Tel 0161 655 5500 Fax 0161 655 5501 Internet www riscogroup com e mail sales riscogroup co uk Technical Support 0161 655 5600 Technical Support Fax 0161 655 5610 RISCO Group UK Ltd reserve the right to amend the software and features without prior notice d V THE BRITISH SECURITY J UKAS INDUSTRY ASSOCIATION MARAGEMENT 5INEW021PR C PR5649 Rev1 2
71. seconds and cannot be changed Note that comms cannot take place until the later of the theoretical expiry of Entry Time 1 or the expiry of Entry Time 2 Note Entry Time 1 is defaulted to 30 seconds but maybe changed to a maximum of 45 seconds Note Entry Time 2 is defaulted to 30 seconds and may not be changed 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 piogia With the display showing Foes o P A Program oe 2 Press No twice The display will show Entry Times 3 s Program Entry 3 Press Yes The display will show A 4 Press Yes The display will show Entry Time sees i Entry Time 1 gt __s 5 Press No twice The display will show 6 Enter the Time required in seconds followed by Program Entry Yes The display will show maT Page 38 10 CPX Engineer s Reference Guide Press No The display will show Press Yes The display will show Note Entry Time 2 is defaulted to 30 seconds and may not be changed Program Entry Time 2 Entry Time 2 30s Warning Bell On Warning Bell Default is set to On but may be changed to Off If Warning Bell is On then Bells will operate during Entry Time 2 after the theoretical expiry of Entry Time 1 has been reached If set to Off the bells will activate only when both Entry Tim
72. splay will show Press Yes The display will show Page 68 Program Zones Program Sounder Levels Program Sounder Chime Level Chime Level 05 Chime Level Program Sounder Chime Level Program Sounder Ent Exit Level Ent Exit Level 05 CPX Engineer s Reference Guide 9 Press No twice The display will show Ent Exit Level 10 Enter a value 1 to 9 1 Low 9 High followed by Yes The display will show Program Sounder Ent Exit Level 11 Press No The display will show Program Sounder Keypad Level 12 Press Yes The display will show Keypad Level 05 13 Press No twice The display will show Keypad Level 14 Enter a value 1 to 9 1 Low 9 High followed by Yes The display will show Program Sounder Keypad Level 15 This concludes the program Sounder Levels press 0 zero to move back to Program Sounder Levels Then Press 0 twice to move back to lt lt lt lt UN SET gt gt gt gt 01 Jan 00 00 01 Page 69 CPX Engineer s Reference Guide Programming PGM1 Custom PGM1 is located on the control panel PCB close to the Be
73. ss Yes The display will show Press No until the required setting for Off Charge Volts min Battery is displayed then press Yes The display will show Press Yes The display will show Press Yes The display will show Page 78 On Chg max 14 0 On Chg min 12 6 On Chg max 14 0 On Chg min gt 12 6 Off Chg max 14 0 Off Chg min 12 6 Off Chg max 14 0 Off Chg min gt 12 6 PSU Diagnostics PSU Test Time 01 Hrs Change List Test Limits CPX Engineer s Reference Guide The readings given from this point on are intended as Indicator Only and should be confirmed with a calibrated Test Meter 21 Press No The display will show for example Ape Volts 13 6V 22 Press Yes The display will show for example Battery Volts On Charge 13 6V 23 Press Yes The display will show Battery Volts Off Charge 12 9V The backlight will Dim at this point 24 Press Yes The display will show Aux Volts 13 6V 25 This concludes the Program Diagnostics Press 0 zero until the display shows Page 79 CPX Engineer s Reference Guide Programming Alarm Confirm This section is used to program options that are relevant to DD243 Before programming these options please
74. take time to read the following notes that will help in your understanding of DD243 All communications systems that require a Police URN will need to conform to DD243 These notes intended as a guide only and should be read in conjunction with the relevant standards relating to the alarm system giving particular attention to EN50131 1and DD243 These may be obtained from the British Standards Institute DD243 options available are Confirm Time Window default 60 This time window may be programmed between 1 and 120 minutes To comply the required time should be between 30 and 60 minutes Confirm on Entry default On This option may be programmed to On or Off If Confirm on Entry Off then confirmed alarms to central station are disabled if the entry timer is started If ACE or G Tag is used then it is permissible to set this option to On Sounder Mode default Unconfirmed This option controls the system speakers fitted options are confirmed or un confirmed If Sounder Trigger Confirmed then internal sounder will only trigger with a confirmed alarm If Sounder Trigger Unconfirmed then internal sounders will trigger with un confirmed alarms This feature is not mandatory for DD243 Reset Mode default Any Choose from Any or Normal If Unconfirm Any then any code can be used to reset an un confirmed alarm If Unconfirm Normal then the programmed reset mode for alarm will still be required i e if alarm reset has
75. te Each keypad must be programmed onto the system in order for it to be recognised by the system Note Depending on the variant of the keypad fitted external G Tag Proximity Reader s may be fitted to each keypad 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing 2 Press No four times The display will show 3 Press Yes The display will show Alert 1 Keys refers to the PA keys being pressed together or keys 1 amp 3 being pressed together P amp F refers to PA keys 5 S ara 4 Press Yes The display will show 5 Press the No Key to scroll through the settings for Alert 1 When the setting you require is displayed press Yes The display will show 6 Press No The display will show 7 Press Yes The display will show Page 44 Program Zones Program Keypad Program Keypad Alert 1 Keys Alert 1 Off 1 amp 3 Off P amp F On Alert 1 Off 1 amp 3 gt Off P amp F On Alert 1 Off 1 amp 3 gt On P amp F On Alert 1 Off 1 amp 3 On P amp F gt On CPX Engineer s Reference Guide 8 Press Yes The display will show Program Keypad Alert 1 Keys 9 Press No The display will show Program Keypad Alert 2 Keys Alert 2 Keys refer to Key 7 amp 9 pressed together
76. tems before commencement of programming Upon completion of the installation the engineer may if required re program several factory set options so as to tailor the Control Panel to suit the requirements of the sys tem The CPX control panel uses 32 character LCD Remote Keypads for control of the system via User Code s and programming of the system via an Engineer Code The Factory Default Codes are Default Master User Code 5678 Default Engineer Code 1234 The Engineer code may be Locked into the system during engineer programming and it should be noted that if the Locked code is not known the only way to have it returned to the factory default is to return the PCB to the factory Option Formats When an option cannot be changed the display will show a rather than the usual sign Pressing the No key is disregarded and the panel will react as though the Yes key has been pressed i e it will move onto the next option Page 3 CPX Engineer s Reference Guide 2 SYSTEM INSTALLATION WIRING Planning the Control Panel Location Consideration in locating the fixing position of the Control Panel should be given to Access for the routing of cables for the system from detection devices sounders internal and external remote keypads mains etc The position of the underside retaining screw The fixing of a 3 amp fused spur with disconnection facility When fitting the RKP s consideration should be gi
77. under Always Audible 33 Press the No key to scroll through the options Options available for Setting Sounders are Always Audible Exit Sounder will be audible for Full Set and all Part Sets Silent If Part 1 Exit Sounder will be silent during a Part 1 Set Silent If Part 2 Exit Sounder will be silent during a Part 2 Set Silent If Part 3 Exit Sounder will be silent during a Part 3 Set Always Silent Exit Sounder will be silent during ANY Part Set When using a silent Part Set a single beep will be heard at the end of the Exit Time to confirm the system has Set 34 When you have the required setting displayed press Yes The display will show Program Setting Sounders Page 35 CPX Engineer s Reference Guide 35 Press No The display will show Predram Setia Confirmation Setting Confirmation uses the Strobe Light to confirm that the system has finally set 36 Press Yes The display will show Strobe Confirm Off 37 Press the No key to scroll through the options Available options for Strobe Confirm are Off Strobe Confirm is turned Off Full Set The Strobe will Confirm only on Full Set Any Set The Strobe will Confirm on Any Set Full or Part 38 When the required setting is displayed press Yes The display will show Program Setting Confirmation 39 Press No The display will show Progra
78. urn to Or Press 0 zero until the display shows Page 47 Program Keypad ACE Prox Program Keypad 01 Jan 00 00 01 CPX Engineer s Reference Guide Programming Digicom Vo Comm Off On Within this section we will program the Digicom and Modem Both of these devices are built on the main PCB of the control panel Only the main functions will be covered within this Step by Step section If required the 5 5 Yes No default may be used to set the basic comms configuration When this default is used all other settings that have been programmed will be returned to factory defaults When this default is used the following will be set Digicom Type Mod F F Modem Mode No Return This will allow for connection to GardTec Remote for programming functions 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 EER With the display showing ae 7 Sa 2 Press No five times The display will show one mee See s i Program Digicom 3 Press Yes The display will show Type or Test 5 Digicom Type 4 Press Yes The display will show Mod F F Digicom Types available are Mod F F Modem enabled and Ademco Fast Format Central Station protocol enabled Mod SIA Modem enabled and SIA Central Station protocol enabled Mod PID Modem enabled and Point ID Central Station protocol enabled
79. ven to Operation of the keypad Readability of the display The Panel should be fixed to the wall using appropriate wall plugs and No 8 screws at least 30mm long Do not tighten the screws at this stage wait until all your wiring is in place Wiring Considerations With the exception of the mains wiring all interconnections should be made with multicore 7 02 alarm cable Good wiring practice should be observed throughout the installation and the following tips may prove useful Never run alarm cables parallel to mains cables telephone cables or any other cables that may be carrying inductive loads Whenever you have to cross mains cables with alarm cables ensure that you do so at 90 Whenever possible wire the mains connection for the control panel back to the consumer unit via a 3A fused spur with disconnection facility Never tap into ring main circuits that have fridges freezers on them Never tap into lighting circuits that have fluorescent lighting units on them Page 4 Mains Wiring CPX Engineer s Reference Guide A 230V a c supply should be taken directly from the consumer unit In order to comply with the relevant current wiring regulations this should be via a 3 Amp fused spur with disconnection facility ata Consumer Unit Mains Connection Colours I Live Brown Red Neutral Blue Black Earth Copper J Yellow Green sleeving should be used for Copper Earth Conductor
80. want the output to operate followed by Yes The display will show Press No until the mode you require is displayed then press Yes The display will show Press No The display will show Enter the time required followed by Yes The display will show The t 00 setting only applies to Fol Fol Pul Pul Repeat Steps 5 to 13 until all the Custom Outputs you require have been programmed When you have programmed Custom 8 the display will show Press 0 zero until the display shows Page 71 Cus 1 Zone gt Day Fol t 00 Cus 1 Zone gt 009 gt Day Fol t 00 Cus 1 Zone gt 009 Day gt Fol t 00 Cus 1 Zone gt 009 Day Fol t gt 00 Cus 1 Zone gt 009 Day Fol t gt _ Cus 2 Zone 000 Day Fol t 00 Program PGM1 Custom 01 Jan 00 00 01 CPX Engineer s Reference Guide Programming Engineer Code 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing 2 Press No twelve times The display will show 3 Press Yes The display will show 4 Enter your New Engineer Code 4 5 or six digits followed by Yes The display will show Program Zones Program Engineer Code Now Enter Code Then YES
81. y TIME 5 Press No twice The display will show F Exit time gt _s Set by TIME 6 Enter the time you require as the Exit Time in seconds followed by Yes The display will show for example F Exit time 20s gt Set by TIME Page 31 CPX Engineer s Reference Guide 7 Use the No key to scroll through the Setting Modes Options available for Setting Modes are Set By Time Set By ET Set By E E Set By Time E E 8 When the Setting Mode you Require is displayed press Yes The display will show Program Setting for FULL set 9 Press No The display will show Program Setting for PART 1 set 10 Press Yes The display will show The system will Set after the Time shown in the Exit Time The system will set when the Exit Terminator Button outside the premises is pushed this option will require a Zone to be programmed as Exit Terminator Once the user has started to Set the system the Exit Tones will continue until the Final Exit Door is opened then closed This option will require a Door Contact Once the user has started to Set the system the system will Set on either the Time expiring or the door opening and closing This option may require a Door Contact P1 Exit time 30s Set by TIME 11 Press No twice The display will show P1 Exittime gt s Setby TIME _ 12 Enter the time you require as the Exit Time

Download Pdf Manuals

image

Related Search

Related Contents

Extron electronic SPA 12 AAP User's Manual  Samsung SL-M2070 Priručnik za korisnike      Samsung DIGIMAX A7 manual do usuário  Samsung 23" Monitor LED Dual View Full HD manual do usuário  

Copyright © All rights reserved.
Failed to retrieve file