User Manual - UPS ONLINE 6K/10K 2Ph ENGLISH

image

Contents

1. gt sl E INTEGRA 20150105 6K 10K 2PH EN 7 User Manual ups ONLINE 6K 10K 2Ph ENGLISH 3 UPS INSTALLATION SITE PLANING SAFETY INSTRUCTIONS A WARNING Before revising this section you must read and understand very well section 1 of this manual GENERAL SAFETY INSTRUCTIONS WARNINGS RECOMMENDATIONS AND LIABILITY LIMITATION REACH AND LIABILITY LIMITATION The preparation of the site wiring and all protection devices must be supplied by end user and it will not be responsibility neither the UPS distributor nor the UPS technician in charge of the start up The place will be conditioned be end user or electrical contractor and must fulfill with local normative and directives and UPS technical reguirements This manual describes minimal conditions and technical reguirements with which the site must accomplish Directives and reguirements described in this manual do not pretend to substitute in any way local electrical directives or normative In some cases local directives or regulations might be more exigent than UPS technical reguirements described by this manual In that case end user electrical contractor must be sure to comply with all related local electrical regulations and directives WARNING Power lines must be protected by protection devices against over current
2. User Manual ups ONLINE 6K 10K 2Ph ENGLISH UPS 6K 10K EX 2PH 6KEX 2Ph 10KEX 2Ph INDICATORS INDICADORES Estado del UPS Consumo Bater as Voltaje Entrada Salida Tiempo Descarga Diagnostico LCD Pantalla de Cristal Liquido LCD Fall allas ALARM ALARMAS For Battery Mode Low battery Overload UPS Failure Acoustic Beep Alarm Alarma sonora i Modo Bater a Baja bater a Sobrecargas Falla PRODUCT SIZE 8 WEIGHT DIMENSIONES Y PESOS DEL EQUIPO DxWxH Prof X Ancho X Altura UPS 6KEX 2Ph 8 10KEX 2Ph 592x250x576 mm 592x250x826 mm External batt cabinet Gabinete Externo Bater as 592x250x576 mm 592x250x576 mm Net Weight Peso Neto kgs UPS 6KEX 2Ph amp 10KEX 2Ph 79 100 External batt cabinet Gabinete Externo 126 optional 126 optional PACKING EMPAQUE DxWxH Individual UPS 6KEX 8 10KEX Small Pallet 73x39x82 cm Small Pallet 7 3x39x107 cm Individual External Battery Cabinet Small Pallet 73x39x82 cm Small Pallet 73x39x82 cm Gross Weight Peso Bruto kgs UPS 6KEX amp 10KEX 86 109 External Battery Cabinet 126 126 OPERATING AMBIENTALES Humidity Humedad lt 95 non condensing no condensante Temperature Temperatura 0 40 C Noise Level Ruido Producido lt 5008 1m lt 6008 1m COMMUNICATION COMUNICACION Smart RS 232 amp USB ports Windows 98 2000 2003 XPMsta 2008 Windows 7 Linux and MAC Intelligent Port SNMP Optional LAN card Comunicaci n LAN Ether
3. ENGLISH C PRO x 10x 2Ph USER MANUAL 2 PHASES 120Vac ONLINE DOUBLE CONVERSION UPS di EL Gm Gm Gs Q e dm ee YT i F Y a d gem gen gen emm e emm od GENER GENER dm ri TI I I TIT h U dT E E T 3 F 3 F 3 XI G cL i III IZ emm emm Se oo d F r 7 7 i 1 oo qum LL oS s l SUS En em emm TI mmm Ss x 7 A 7 7 j r m een m m emm ween de i Kn gn i x 7 D 1 1 AR User Manual ups ONLINE 6K 10K 2Ph ENGLISH TABLE OF CONTENTS 1 SAFETY 2 AVAILABLE MODELS 3 UPS INSTALLATION SITE PLANING SITE INSPECTION amp INSTALLATION CONDITIONS TOWER UPS INSTALLATION EXTERNAL CIRCUIT BREAKERS 8 WIRING SELECTION 4 UPS INSTALLATION SINGLE UPS TERMINAL BLOCK UPS AC LINES CONFIGURATION AC TERMINAL BLOCKS EXTERNAL BATTERY CONNECTION 9 UPS INSTALLATION PARALLEL UPS TERMINAL BLOCK GENERAL COMMENTS UPS AC LINES CONNECTION PARALLEL CONTROL CABLES CONNECTION 6 START UP SINGLE UPS INSPECTION BEFORE START UP SINGLE UPS START UP PROCEDURE 7 START UP PARALLEL UPS REQUIREMENTS FOR PARALLEL UPS SYSTEMS INSPECTION BEFORE START UP PARALLL UPS START UP PROCEDURE 8 OPERATION INTERFACE FRONT PANEL PUSH BUTTONS LEDS LCD 9 OPERATION SINGLE UPS 10 OPERATION PARALLEL UPS REMOVING UPS FROM PARALLEL SYSTEM ADDING UPS TO PARAL
4. 33 User Manual ups ONLINE 6K 10K 2Ph ENGLISH In ECO mode UPS output is not generated by the inverter Main input is used to supply UPS output In that way UPS inverter does not need to work and UPS energy performance is improved LI I 4 jos pare Ter Elke ec lt ES Y Dex g MODE gt B 413 493 r kia O Y M eu This UPS can be configured through CVCF mode to supply a fixed frequency output 50Hz or 60Hz no matter input frequency matches with the output frequency For example input frequency can be 60Hz but UOS can generate output at 5017 In 4th screen we can see input frequency in 62 3Hz but output at 50 0Hz NOTE Under this mode bypass function is not allowed na INO il EU ELE 523 00 ODA REA Under this mode alert triangle icon is flashing on LCD Red LED is blinking on front panel and warning message is displayed in LCD UPS works in normal mode generating output by inverter For this example warning codes 01 09 and SC are indicated on LCD WARNING ALARM user il say US 3L Cp Under ERROR or FAULT mode alert triangle is indicated fixed in LCD Red LED lights ON UPS inverter is stopped In this example 43 error code is indicated on LCD INTEGRA 20150105 6K 10K 2PH EN 34 User Manual ups ONLINE 6K 10K 2Ph ENGLISH 10 OPERATION PARALLEL UPS UPS operation modes for UPS in parallel are basically same than described for single U
5. Remove all jumpers between L1 and L2 at input and output terminal block 2 You MUST confirm Configuration MENU 03 and 04 in LCD panel are configured as follows 2 1 Configuration MENU 03 must be set as ATO automatic mode Output phase angle is same than input phase angle In normal conditions angle phase between separate phases is 120 2 2 Configuration MENU 04 is not available under this mode It is indicated as RESERVED Since UPS detects input has been wired as 2 separate phases output cannot be configured as 1 phase output ji m ec 1 NN a A Detailed instructions to check and configure function 03 04 available in Configuration section INTEGRA 20150105_ 6K 10K 2PH EN 15 User Manual ups ONLINE 6K 10K 2Ph ENGLISH CONFIGURATION 3 UPS 2 Ph 2 Input 120Vac 1 Output 208Vac 208Vac output can supply 100 of total UPS capacity 2 Input Ph 1 Output 220Vac 100 OUTPUT INPUT WC SE n at G L1 L2 N L1 L2 N 220V 120V 120V 100 WARNING To use this UPS as 2 phases UPS is MANDATORY to check there is NO jumpers connected between L1 and L2 at Input and output terminal block You must follow below instructions MANDATORY INSTRUCTIONS TO AVOID PERMANENT DAMAGE 1 Remove all jumpers between L1 and L2 at input and output terminal block 2 You MUST confirm Configuration MENU 03 and 04 in LCD panel are configured as follows 2 1 Configuration MENU 03 must be set as 41
6. UPS have external batteries Permanent damages will be produced in UPS if this warning is not followed A WARNING EXTERNAL BATTERIES INTEGRA 20150105_ 6K 10K 2PH EN 19 User Manual ups ONLINE 6K 10K 2Ph ENGLISH PARALLEL CONFIGURATION 1 1 INPUT 1 OUTPUT 1 INPUT 120Vac 1 OUTPUT 120Vac 100 CAPACITY Under this configuration output can supply 100 of total UPS capacity WARNING A To connect 2 outputs in one phase output we must be sure phase angle between outputs is 0 and only 1 phase line must be connected at UPS input Please follow below procedure MANDATORY INSTRUCTIONS TO AVOID PERMANENT DAMAGE IN YOUR UPS AND SYSTEM 1 Make sure L1 and L2 terminals at input terminal block are connected with a jumper 2 UPS must be connected to one phase input line only 3 Check to confirm function 03 in LCD panel is configured as ATO automatic mode In this mode inverter output Will follow input phase Phase angle read by UPS must be 000 in function 03 screen ATO is factory preconfigured value 4 Check to confirm function 04 in LCD panel is configured as ENA Enabled If not error alarms 1A and 1B will be generated by the UPS Note ENA is the factory preconfigured value C fl LI ja wa r r r r TEL LILILI Lef a Detailed instructions to check and configure function 03 amp 04 available in Configuration section A Only after configuring all UPS to be con
7. Manual ups ONLINE 6K 10K 2Ph ENGLISH z z z 2 SE st cN S N Q IN A iQ 35 E O 3 C O Novo z gt N N j a f e l amp E E gs E l Z D e u ch N U z 7 23 SES y E ZS 1 3 SS gt T EN ex lt ES CH s lt al INTEGRA 20150105 6K 10K 2PH EN 25 User Manual ups ONLINE 6K 10K 2Ph PARALLEL CONTROL CABLES ENGLISH 2 UPS Parallel System Control Wiring Parallel Cables gt D ame Ep dp alejo o olizzjo AJO o ADO e O am o Shared Current Cables 3 UPS Parallel System Control Wiring y ame apo Go ofa Parallel Cables Ti f Ti de O PPE o AJO kasaq Rl DH le im mz en NE malo s k 4 mm em mm i m mm Shared Curr Cables ared Curr Cables INTEGRA i Ge O am e GP GB m 20150105_ 6K 10K 2PH EN 26 User Manual ups ONLINE 6K 10K 2Ph ENGLISH 6 START UP SINGLE UPS INSPECTION BEFORE START UP 5 6 Make sure all wires are tightly connected to terminal block Any loose connection will produce overheating failures and damage to UPS Make sure all instructions of sections 3 and 4 have been performed correctly Put the terminal block cover back in its position
8. Z TH3TIVHVd amp ap UOIJEINBIJUOJ EI uJ 23 EN 20150105_ 6K 10K 2PH INTEGRA User Manual ups ONLINE 6K 10K 2Ph ENGLISH PARALLEL CONFIGURATION 3 2 INPUT 1 OUTPUT 208V 2 INPUTS 120Vac 1 0UTPUTI 208Vac Under this configuration output can supply 100 of total UPS capacity WARNING To use this UPS as 2 phases UPS is MANDATORY to check there is NO jumpers connected between L1 and L2 at Input and output terminal block You must follow below instructions MANDATORY INSTRUCTIONS TO AVOID PERMANENT DAMAGE IN YOUR UPS AND SYSTEM 1 Remove all jumpers between L1 and L2 at input and output terminal block 2 You MUST confirm Configuration MENU 03 and 04 in LCD panel are configured as follows 2 1 Configuration MENU 03 must be set as ATO automatic mode Output phase angle is same than input phase angle In normal conditions angle phase between separate phases is 120 2 2 Configuration MENU 04 is not available under this mode It is indicated as RESERVED Since UPS detects input has been wired as 2 separate phases output cannot be configured as 1 phase output B HER LA SJ De 1 E di mE ES e L 9 J ul Detailed instructions to check and configure function 03 amp 04 available in Configuration section A Only after configuring all UPS to be connected in parallel terminal block connections can be done according to following figure INTEGRA 20150105 6K 10K 2PH EN 24 User
9. breakers or leak currents with capacity and technology appropriate to effectively accomplish its function Moreover installation grounding must be correct WARNING Install the UPS in well ventilated locations and leave room enough between UPS and close objects and structures WARNING Do not connect to UPS eguipments or devices that exceed its capacity this would overload the UPS WARNING This product has been designed to be used indoors protected from water direct sun light dust and extreme temperature WARNING Do not put any object on the UPS do not apply any force over UPS Do not cover UPS ventilation WARNING This UPS must be connected to appropriate electrical service according to selected model Technical specs sticker in the UPS shows the UPS power ratings DO NOT connect this UPS to any of its own power outlets this could damage the unit permanently WARNING Do not connect AC motor based eguipments without a careful sizing of the UPS based on inrush current instead of average current Inrush current typical of motor based system could overload this UPS INTEGRA 20150105 6K 10K 2PH EN 8 User Manual UPS ONLINE 6K 10K 2Ph ENGLISH SITE INSPECTION AND INSTALLATION CONDITIONS REGULATIONS AND LEGAL DIRECTIVES It is necessary to check that installation site wiring and power protection in the installation supplied by end user fulfill technical parameters required by UPS A particular installation might accomplish with UPS req
10. jumper 31 If not under bypass mode input L1 and L2 will be short circuited Additionally functions 03 and 04 in LCD front panel MUST be revised and properly configured Check terminal block configuration in this section Z WARNING Configurable functions 03 and 04 of the configuration menu available on LCD must be revised and properly configured according to the output mode selected Revise Installation section and Configuration section of this manual Z WARNING WRONG INPUT OR OUTPUT CONNECTION MAY PRODUCE PERMANENT DAMAGE OF THIS PRODUCT OR YOUR SYSTEM THIS KIND OF DAMAGE IS NOT COVERED BY THE WARRANTY INTEGRA 20150105 6K 10K 2PH EN 13 User Manual ups ONLINE 6K 10K 2Ph ENGLISH CONFIGURATION 1 UPS 1Phase 1 Input 120Vac 1 Output 120Vac _ 1 phase output can supply 100 of total UPS capacity 1 Input Phase 1 Output Phase 120Vac 100 OUTPUT INPUT WT m aem E I G L1 L2 N LI L2 N 5 D mala D gs e i H N out uj Special Note Nota Especial 120V L1 amp L2 Outputs MUST be in phase 1 00 09 Check phase config in LCD e Las salidas L1 y L2 DEBEN estar en fase Revisar configuraci n en LCD WARNING To connect 2 outputs in one phase output we must be sure phase angle between outputs is 0 and only 1 phase line must be connected at UPS input Please follow below procedure MANDATORY INSTRUCTIONS TO AVOID PERMANENT DAMAGE 1 Make sure L1 and L2 terminals at input
11. of repairing or replacement of any hardware components that malfunction in conditions of normal use In no event will INTEGRA be liable for any damages caused by the product or the failure of the product to perform including any lost profits or savings or special incidental or consequential damages INTEGRA is not liable for any claim made by a third party to INTEGRA or to final user INTEGRA is not responsible for damage that occurs as a result of your failure to follow the instructions intended for this hardware product USA Headquarters SPAIN Headquarters Latin America Headquarters 10540 NW 26th St Ave Can Bordoll 60 Nave 4 Zona Ind San Vicente II Calle F A11 Doral FL 33172 Sabadell 08202 Maracay Tel 1 305 406 3664 Tel 34 93 745 9694 Tel 58 243 551 7023 INTEGRA 20150105 6K 10K 2PH EN 48
12. panel board UPS Input and Output Connection Connect input and output ground wires to proper place on the UPS chassis on both sides of terminal blocks Ground wires must be FIRST to be connected and LAST to be disconnected Connect UPS input and output wires according to your UPS model or configuration as described in following figures AVAILABLE CONFIGURATIONS This equipment can offer 3 different connection configurations 1 One Phase Input 120Vac One Phase Output 120Vac 1 x Input Line to Neutral Voltage 120Vac 1 x Output Line to Neutral Voltage 120Vac 2 Two Phases Inputs 120Vac Two Phases outputs 120Vac 2 x Input Line to Neutral Voltage 120Vac 2 x Output Line to Neutral Voltage 120Vac 2 Two Phases Inputs 120vac One Phase output 208Vac 2 x Input Line to Neutral Voltage 120Vac 1 x Output Line to Neutral Voltage 208Vac INTEGRA 20150105 6K 10K 2PH EN 12 User Manual ups ONLINE 6K 10K 2Ph ENGLISH SIMPLIFIED INTERNAL BLOCK AND AC TERMINAL BLOCKS Internal Bypass Line L1 Input Breaker L1 e Bypass gt Relay JI RECTIFIER INVERTER J2 L2 L2 D r JW m AW Bypass ROG i Internal Bypass Line L2 Relay N N pb INPUT OUTPUT WARNING If UPS will work in 1phase input 1 phase output configuration output L1 and L2 must be connected by a jumper J2 in output terminal block Under this configuration inputs Li L2 MUST be connected with a
13. total UPS capacity For example for a 6KVA UPS output L1 L1 N will drive 3KVA and L2 N will drive 3KVA max e Outputs L1 and L2 can be used in separate way with individual maximum capacity of 50 each but also they can be connected in parallel to offer 100 total power in one output e Line to Neutral UPS Output Voltage can be configured by front LCD panel User can select one of the 5 available output voltage values as follow 100Vac 110Vac 115Vac 120Vac 127Vac INTEGRA 20150105 6K 10K 2PH EN 3 User Manual ups ONLINE 6K 10K 2Ph ENGLISH 1 GENERAL SAFETY INSTRUCTIONS AX WARNING It is required to read and understand this manual Follow all instructions given in this manual for starting up and operating this product Only qualified technician must start up operate and maintain this product Keep manuals as a guide for future consults WARNING This product operates with dangerous voltages It must be installed operated and maintained ONLY by qualified technicians trained for this kind of products Service personnel MUST know and understand very well all electric risks related to this product UPS manufacturer or distributor will never be responsible for any accident produced by lack of knowledge or negligent practices at the moment of install starting up or maintain this product UPS manufacturer or distributor is not liable for any damage that might rise from misusing this unit or defective installation WARNING I
14. 07 automatic mode Output phase angle is same than input phase angle In normal conditions angle phase between separate phases is 120 2 2 Configuration MENU 04 is not available under this mode It is indicated as RESERVED Since UPS detects input has been wired as 2 separate phases output cannot be configured as 1 phase output Bi sss O H c A Detailed instructions to check and configure function 03 04 available in Configuration section INTEGRA 20150105 6K 10K 2PH EN 16 User Manual ups ONLINE 6K 10K 2Ph ENGLISH SPECIAL CONFIGURATION FOR 2 ALTERNATIVE INPUT SOURCES POWER GENERATORS WITH OUTPUTS AT 180 There are some applications where 2 different input sources are used to power to the UPS Main input source is usually AC Utility and Auxiliary source could be a motor generator Main AC Utility offers a 1207 phase shift between R S amp T phases but sometimes auxiliary sources supply phases shift different to 120 for example there are some 2 phases motor generators with 180 phases shift Some other times 3 phases motor generators are used but phases connected to UPS are not consecutive so phases shift is different to 120 UPS is expecting In those cases when input goes from Main Utility to Auxiliary Source UPS detects a phase shit change and depending on configuration of function 03 an alarm 39 could be generated and UPS could go to battery mode to protect connected load against a not adequate phases shift U
15. BOUT FREQUENCY CONVERSION FUNCTION CF When CF function is enable to generate an output with a different frequency value than input bypass mode will be automatically disable When CF function is activated maximum power output is de rated to 60 of standard power output For example for 10KVA UPS when CF is activated max output power is 6KVA o 03 Output Phase LCD Parameter 2 Constant Output Phase CP Sets UPS to CP mode If selected the output phase will be fixed at 0 120 180 or 240 according to setting in parameter 3 No matter input phase SPECIAL NOTE if CP is activated all BYPASS modes are disabled We suggest to keep this function configured as ATO CP mode is used when 2 alternative input sources operates with different phase angle as explained in section 04 special mode for motor generators ATO In this mode output phase angle will be fixed according to the input phase angle detected when UPS starts up 7 I A LI ILU Parameter 3 Phase setting In GP mode Vou mav select the phase angle between output lines In ATO mode parameter 3 shows phase angle saved as read in the input when UPS was powered up INTEGRA 20150105 6K 10K 2PH EN 38 User Manual ups ONLINE 6K 10K 2Ph ENGLISH o 04 Output parallel function setting o Interface Seng lt gt When UPS input lines are not in parallel Jumper between input L1 and input L2 is removed MENU 04 will be not available since out
16. E 6K 10K 2Ph ENGLISH TROUBLESHOOTING PROBLEM DESCRIPTION PROBABLE ROOT CAUSE SUGGESTED ACTION LCD does not show input voltage value Input power cord is not connected Check input power cord connection AC input failure alarm active EENEG Input power cord is connected into UPS Check input power cord connection outlet EPO function is active Re establish emergency power off Switch and set UPS in normal mode UPS cannot be powered on even AC input is OK Beep alarm 1 beep s amp LCD shows EP UPS cannot be powered on even AC input is OK ON push button is not been selected Push ON button during 2 seconds or properly longer 1 beep s alarm is active and LCD shows Internal or external batteries are not Check battery connection N a ATT FAULT properly connected Code 02 Input Neutral not connected or input Check input Neutral connection Reset 1 beep s phase fuse open alarm in parameter 03 on LCD If input phase fuse is broken replace it UPS overloaded Disconnect devices from UPS outlets VER LOA l Intermittent until solving overload 2 beeps per second OVER LOAD UPS overloaded UPS has changed to Intermittent BYPASS mode to avoid internal until solving overload 2 beeps per second damage By Pass activated After repetitive small overloads UPS Disconnect devices from UPS until has changed to BYPASS mode solving overload Then power off UPS ka AR Code 43 UPS has been automat
17. ENGLISH START UP FOR PARALLEL UPS SYSTEM WARNING Make sure all requirements and previous inspection have been revised and complied 1 Make sure all equipments to be protected and connected to UPS output are in OFF condition 2 Check AC input breaker located in UPS rear panels is in OFF position in all UPS of the system 3 Power on external main AC input in electrical panel Set to ON position all external AC input breakers 4 If UPS are using external battery packs set to ON all DC breakers to connect external DC packs to UPS 5 For UPS No 1 Set to ON AC input breaker located in rear panel of UPS No 1 Wait until UPS No 1 completes auto checking and Bypass LED lights continuously 6 For UPS No 2 Set to ON AC input breaker located in rear panel of UPS No 2 Wait until UPS No 2 completes auto checking and Bypass LED lights continuously 7 In case of having 3 UPS in the system proceed in similar manner with UPS No 3 IMPORTANT AC input breakers activation must be done in one by one and not at same time First for UPS No 1 then for UPS No 2 and finally for UPS No 3 if you have a parallel system with 3 UPS If AC input breakers are activated all at same time warning message 3F could be activated If it occurs reinitiate procedure sequentially Warning 31 message must be previously reset according to warning and error section in this manual 8 When rear panel AC breaker is set to ON This UPS recognizes all o
18. LEL SYSTEM 11 UPS CONFIGUIRATION 12 ERROR CODES ALARMS 8 TROUBLESHOOTING 13 TECHNICAL SPECIFICATIONS 14 LIMITED WARRANTY INTEGRA 20150105 6K 10K 2PH EN 2 User Manual ups ONLINE 6K 10K 2Ph ENGLISH A INPUT OUTPUT CONFIGURATION e Thisisa 2 Phases UPS 2 phases input 2 phases output Nominal Line to Neutral Voltage is 120Vac e This UPS can work as 2 Phases UPS but also as 1 Phase UPS under following configurations 1PH input 120V L N amp 1PH output 120V LN 2PH input 120V L1 N 120V L2 N 8 2PH output 120V L1 N 120V L2 N 2PH input 120V L1 N 120V L2 N 8 2PH output without neutral 208V L1 L2 e Any other input output configuration is not allowed Any other configuration could generate error alarms and even damages in the UPS It is explicitly not allowed 1PH input 2PH output mode It is not allowed 2PH input amp 1PH output e 1PH mode When it is configured to work as single phase UPS it has to be specially configured for that Input L1 and L2 must be connected using a jumper between L1 L2 at input terminal block and only one phase 1 1 must be connected to UPS Output L1 and L2 also must be connected using a jumper between them e 2PH mode L1 and L2 must not be connected between them neither in input nor in output sides e This UPS generates 2 separate phases outputs Neutral L1 L2 and N Output voltage is 120Vac from Line to Neutral Each output can only drives 50 of
19. PS However it is important to remark all UPS in parallel system must work under same mode at same time Parallel function does not allow different operation modes between UPS of the system Removing an UPS from a Parallel System i There are 2 procedures to isolate and remove one UPs from operative parallel system A Total Power Off Powering off all UPS of the system This is the less risky procedure B Keeping Parallel system in ONLINE mode First check all below requirements are complied before trying to follow this procedure Requirements for removing one UPS in operative UPS 1 This operation must be performed only by qualified and trained personnel 2 This operation must be coordinated with the system administrator System administrator must know about the related risks of this procedure since the system could be shut down during operation because external reasons like H during this operation occurs a failure in main AC line battery backup of remaining UPS could not be enough to keep system running before reconnecting removed unit External breakers could be activated randomly during operation so system could be tripped 3 There must be a detailed plan to perform this procedure identifying all maintenance activities to be performed on removed unit before reconnecting it 4 Remaining UPS must be able to support the power system after selected unit is removed 5 Each UPS must have their own external protections to al
20. User Manual ups ONLINE 6K 10K 2Ph ENGLISH Configuration menu texts eee TEXT DESCRIPTION Enable ns im um wer CVCF mode Subtract ON On OFF ff ON PY O OPP INTEGRA 20150105 6K 10K 2PH EN 37 User Manual ups ONLINE 6K 10K 2Ph ENGLISH Configuration menu functions and screens eee e 01 Qutput Voltage Configuration LCD Parameter 3 Output Voltage Value Output can be selected from following options 100 100Vac 110 110Vac 115 115Vac 120 120Vac 127 127Vac Default is 120Vav 60 Hz CVCF mode Parameter 2 Output Frequency x Output can be selected from following choices n Z ba Udo 50 0Hz 50 0Hz MEE Ti re 60 0Hz 60 0Hz JU mi ATO Automatic Under this mode output freguency is selected according to input 50177 if input is 46Hz y 54Hz and x frequency A 60Hzif input is 56Hz y 64Hz 50 Hz Normal mode ATO mode is factory default value N oc es Parameter 3 Frequency Mode x un m mr x Adjusting parameter 3 can be selected CF Mode which is frequency converter mode or LLLI o IL F NGF in NON converter mode LI CF This mode allows fixing a fixed output frequency in parameter 2 NCF This mode allows output frequency was selected according to the input meanwhile input frequency is inside allowed range If input frequency is out of range UPS will go to battery mode ATO NIe 1 L e Cf IMPORTANT NOTE A
21. al UPS ONLINE 6K 10K 2Ph ENGLISH EXTERNAL BATTERY CABINETS CONNECTION PROCEDURE UPS Tower type WARNING Make sure EXBATT model to be connected is compatible with UPS model For 2Ph 6K and 10K UPS models battery pack voltage is 120Vdc Measure and verify DC voltage supplied by battery pack before making connections 1 Check all DC breakers are in OFF position 2 Remove all DC connector covers in UPS and EXBATT cabinets 3 Using appropriate cable supplied with the EXBATT connect UPS with EXBATT 1 In case of more than 1 EXBATT connect EXBATT 1 with EXBATT 2 and so on until last EXBATT 4 Activate DC breakers one by one in EXBATT cabinets to connect EXBATT batteries with internal UPS Main batteries UPS EXBATT 1 EXBATT 2 iw m V l i S L k i II e L H i z 4 z Ge al fi o el INTEGRA 20150105 6K 10K 2PH EN 18 User Manual ups ONLINE 6K 10K 2Ph ENGLISH 5 UPS INSTALLATION PAR UP RMINAL BLO GENERAL COMMENTS FOR PARALLEL SYSTEMS 6K y 10KVA models allow installation of up to 3 units in parallel Units to work in parallel must be connected as indicated in this section Parallel system must be configured and started up according to instructions given dedicated section of this manual Any mistake in connection configuration or starting up procedure could produce permanent damage UPS PARALLEL UPS CONNECTION A e Make sure the UPS is Off before starting the installation e Rememb
22. al applications batteries should be revised and replaced periodically Long storage longer than 6 months without required recharging will wear out batteries This situation is not covered by this limited warranty since this is not considered as a defect Check recharging instructions on user manual Warranted Products EPRO series 1K to 10KVA 1 phase or 2 phases models Conditions Limited Warranty PRO11 1 Subject to the conditions of this limited warranty this product is warranted to be free from defects in materials and workmanship at the time of its original purchase by end user In Europe Warranty time is 2 years on electronic parts and 2 years on batteries In America warranty time is 1 year on electronic parts and 1 year on internal batteries Standard warranty times could vary depending on country region or extended by purchasing warranty options Please check warranty conditions by country region in our web www integra ups com 2 If during the warranty period this product fails to operate under normal use and service due to defects in materials or workmanship authorized distributor or service center will at their option either repair or replace the product in accordance with terms and conditions stipulated herein Transportation expenses are not covered by this limited warranty 3 Warranty is valid only if the original purchasing document issued to original purchaser by authorized distributor or dealer specifying date
23. between UPS and any wall or object It will allow better ventilation and it will allow service UPS when required Do not put any object on the UPS do not apply any force over UPS Do not cover UPS ventilation 100cm min 40 min 100cm min 40 min 100cm min 40 min ELECTRICAL REQUIREMENTS MANDATORY All Power lines must be protected by magneto thermal protection devices against over current breakers with capacity and technology appropriate to effectively accomplish its function as indicated in this manual Moreover installation grounding must be correct This UPS must be connected to appropriate electrical service according to selected model Technical specs sticker in the UPS shows the UPS power ratings DO NOT connect this UPS to any of its own power outlets this could damage the unit permanently Connect only computer related equipments to this UPS DO NOT connect medical equipments or critical availability equipments to this UPS DO NOT connect AC motor based equipments DO NOT connect home appliances ovens vacuum cleaners refrigerators etc to this UPS INTEGRA 20150105 6K 10K 2PH EN 10 User Manual ups ONLINE 6K 10K 2Ph ENGLISH CIRCUIT BREAKERS AND WIRING SELECTION Breakers and Gauge of the wires used in the installation must be rated to drive current values as indicated in below tables NOTE every country could have local electrical requirements and regulations If local electrical r
24. block 2 You MUST confirm Configuration MENU 03 and 04 in LCD panel are configured as follows 2 1 Configuration MENU 03 must be set as ATO automatic mode Output phase angle is same than input phase angle In normal conditions angle phase between separate phases is 120 2 2 Configuration MENU 04 is not available under this mode It is indicated as RESERVED Since UPS detects input has been wired as 2 separate phases output cannot be configured as 1 phase output ji Ja L Z S U Ela 1 y Tu f eem i FEE SELO 120 res res l Detailed instructions to check and configure function 03 amp 04 available in Configuration section A Only after configuring all UPS to be connected in parallel terminal block connections can be done according to following figure INTEGRA 20150105 6K 10K 2PH EN 22 ENGLISH UPS ONLINE 6K 10K 2Ph User Manual NOZI A0ZL N 17 a eda yanvaue ov gadi yanvaYe ov KR ei N LAdNI INdLNO 7501 Ecce a adi u3yy3ug OV San IEP E 0 BID uajod ej ep 3406 J8 OJOS JB 9005 9608 sinuuns ep zedeo se epyes OZEL AOZL Epe2 JEAOZL ap SEDIJES N 614 Ll Aysedes sen JEJO JO 9 05 sepinold Ajuo jndino yoes uonguanDuyuoo jndino SeAOZL sindino z uj VION3183AQV 9NINHVM o ed DV N cl LfYdNI LI N Zi KI INndino 75011 uoee Ayoeded 09 ILAOZL SLNAdLNO Z SLINN
25. dden FBD and ON button in front panel has not been activated 2 UPS has been connected by first time to main but input is out of operative range by voltaje or by frequency LCD shows there is no output 3 digits value is 000 at right side of the LCD UPS displays these 4 screens in alternative manner to show L1 L2 L to L and frequency values Le a rw Ont ULL NO OUTPUT MODE CUP Ugo y E UPS is in bypass mode UPS outputs are supplied directly from the input Main LCD shows input main is conducted directly through bypass line with any intervention of the inverter This mode is typical when UPS is connected to the main but ON button is not activated The UPS is like OFF but providing output from the input main or because UPS has detected either an overload or an internal error BYPASS mode must be allowed in function 10 Sar Va eno BYPASS MODE FEE UPS is connected to main source Main source is OK UPS is generating output by inverter LCD figures show output comes from inverter Input is used for supplying rectifier and charging batteries Le fen NORMAL AC OE MODE im n nn nie DO G 00 48 UPS goes to battery mode when input failure is detected In battery mode LCD shows battery voltage in Vdc 135Vdc in below figures instead of AC input voltage Additionally output voltage is indicated in right side of the LCD Fourth screen shows time in battery mode BATTERY MODE INTEGRA 20150105 6K 10K 2PH EN
26. e low frequency for bypass LI Lee 50 Hz system Setting range is from 46 0Hz to 49 0Hz a 60 Hz system Setting range is from 56 0Hz to 59 0Hz q 55 Hz 5 38 Hz The default value is 46 0Hz 56 0Hz Parameter 3 Set the acceptable high frequency for bypass 50 Hz Setting range is from 51 0Hz to 54 0 Hz 60 Hz Setting range is from 61 0Hz to 64 0Hz The default value is 54 0Hz 64 0Hz o 07 ECO mode enable disable EN Interface Seng I 7 Parameter 3 Enable or disable ECO function Vou mav choose following two options DIS disable ECO function ENA enable ECO function If ECO function is disabled voltage range and frequency range for ECO mode still can be set but itis meaningless unless the ECO function is enabled e 08 Voltage range for ECO mode mu Interface Seting o Parameter 2 Low voltage point in ECO mode The setting range is from 5 to 10 of the nominal voltage Parameter 3 High voltage point in ECO mode The setting range is from 5 to 10 of the nominal voltage INTEGRA 20150105 6K 10K 2PH EN 39 User Manual ups ONLINE 6K 10K 2Ph ENGLISH 09 Freguency range for ECO mode Interface 11 Batterv backup time setting e 13 DC battery voltage meter calibration Interface O INTEGRA Seting Parameter 2 Set low frequency point for ECO mode 50 Hz system Setting range is from 46 0Hz to 48 0Hz 60 Hz system S
27. ection 5 of this manual 7 Make sure total available capacity in Watts of all UPS to be connected in parallel is higher than load to be connected to UPS system It is recommendable total UPS power is at least 25 higher to total load If UPS system will work as n 1 redundant system make sure total UPS capacity after removing one UPS is higher than maximum load to be connected If not remaining UPS will not be able to support connected load when one of the units was removed INSPECTION BEFORE START UP 1 Make sure all wires are tightly connected to terminal block Any loose connection will produce overheating failures and damage to UPS 2 Make sure all instructions of sections 3 and 5 have been performed correctly 3 Put the terminal block cover back in its position to avoid access to wiring 4 Check EPO connections e EPO Port closed Wired EPO function disabled e EPO port connected to an emergency switch EPO function available by activation of Emergency Switch which must be Normally Closed type in order to guarantee that UPS will shut down when circuit opens 5 Check Maintenance Bypass Switch MBS located in UPS rear panel is in UPS position and its cover is duly installed 6 Make sure all external protection devices in input and output lines are in open OFF position 7 Check control parallel cables are connected according to section 5 of this manual INTEGRA 20150105 6K 10K 2PH EN 28 User Manual ups ONLINE 6K 10K 2Ph
28. egulations require higher rates than values suggested in this section please follow local directives 1 PHASE 1 PHASE INPUT 1 PHASE OUTPUT EXT BATT L1 L2 in Parallel L1 L2 in Parallel Ext Batt MODELU 120Vac 120Vac 120Vdc AWG or thicker 8AWG or thicker 10AWG or thicker 63 Amp 63 Amp 90 Amp curve D curve D curve C 6AWG or thicker 6AWG or thicker 10AWG or thicker 125 Amp 125 Amp 90 Amp curve D curve D curve C 2 PHASES 2 PHASES INPUT 2 PHASE OUTPUT EXT BATT MODELO L1 N L2 N L1 N L2 N Ext Batt u _120Vac_ 12018 120Vac 120Vac 120Vd 10AWG or 10AWG or 10AWG or 10AWG or thicker thicker thicker thicker 10AWG or thicker 2Ph 32 Amp 32 Amp 32 Amp 32 Amp 50 Amp curve D curve D curve D curve D curve C 8AWG or 8AWG or 8AWG or 8AWG or thicker thicker thicker thicker TOAWG or thicker 63 Amp 63 Amp 63 Amp 63 Amp 50 Amp curve D curve D curve D curve D curve C IMPORTANT When using 2 separate outputs each individual output drives only 50 of total UPS capacity For example for 6KVA UPS Max output 1 is 3KVA and Max output 2 is 3KVA IMPORTANT Before connecting 2 outputs in parallel is mandatory to check both outputs are in phase 0 This parameter is configured through menu by LCD and front panel Check installation section in this manual IMPORTANT If external battery cabinets are connected to UPS it is necessary to install one DC breaker between UPS and each external battery cabinet Orig
29. er to check all wires to be connected including external batteries are not powered before manipulating them UPS TERMINAL BLOCK PREPARATION Remove cover of terminal block at the UPS rear panel identified as 11 in rear panel section of this manual DO NOT use a wall power outlet to plug UPS to AC Line as usually ratings of this kind of outlets are not enough to power 6KVA UPS UPS Input wire must be connected directly to electric panel board UPS INPUT AND OUTPUT CONNECTIONS Connect input and output ground wires to proper place on the UPS chassis on both sides of terminal blocks Ground wires must be FIRST to be connected and LAST to be disconnected Refer to Figures 3A and 3B a Grounding Wires Connect AC Input and Output ground of both UPS according to figures b AC Input Wires AC Input wires must come from individual electrical circuit breakers on electrical panel board before being connected to UPS terminal block C AC Output Wires AC output wires must be connected directly to external circuit breakers of bigger capacity d If UPS is EX model external battery banks must be connected to dedicated connector located in rear panel of UPS e Control Cables for Parallel Connection Connect Parallel Cable and shared current according to figures If UPS to be connected in parallel have external batteries it is mandatory each UPS counts with its own battery pack Parallel connection cannot be performed if only one of two or two or three
30. etting range is from 56 0Hz to 58 0Hz The default value is 48 0Hz 58 0Hz Parameter 3 Set high frequency point for ECO mode 50 Hz Setting range is from 52 0Hz to 54 0 Hz 60 Hz Setting range is from 62 0Hz to 64 0Hz The default value is 52 0Hz 62 0Hz Parameter 2 OPN Bypass allowed When selected UPS will run at Bypass mode depending on bypass enabled disabled setting FBD Bypass not allowed When selected neither manual nor automatic Bypass mode will not be available under any situations Parameter 3 ENA Bypass enabled When selected Bypass mode is available when required DIS Bypass disabled to work in following manner Automatic bypass is available for overload or error causes Manual bypass is NOT allowed Manual bypass means users can force to Bypass mode when pressing OFF button in front panel If ENA is set UPS will go to bypass mode when OFF button is selected by user If DIS was set UPS will Turn OFF when OFF button is selected Parameter 3 000 999 Set the maximum backup time from Omin to 999min UPS will shut down to protect battery after backup time arrives The default value is 990min DIS Disable battery discharge protection and backup time will depend on battery capacity UPS will be working in battery mode until low battery level is detected Seting 1 1 1 1 Parameter 2 N L Indicates Neutral Loss Detection Function Parameter 03 Can be configured as DIS ATO or CHE DIS Disable UPS wi
31. f you are not qualified technician do not try to install operate or repair this product WARNING Do not try to install operate or repair this product if you are not accompanied by another qualified person able to offer first aid support in case of emergency or accidents WARNING Internal area of this product is locked by screws Do not try to access inside the UPS unless you are a qualified technician UPS must be checked repaired and maintained by qualified personnel only CAUTION There are dangerous voltages in the UPS power outlets although the equipment is not plugged to power line CAUTION Inside this equipment due to internal batteries there are ALWAYS dangerous voltages thought the UPS is OFF and unplugged of power line CAUTION There are dangerous voltages in DC Direct Current Capacitors Please Check Capacitor location in Figure 8 4 1 Wait at least 10 minutes after turning off UPS before opening it to access inside DANGER Power off UPS and unplugged it from AC Line before opening it to Access inside this unit CAUTION Before starting the opening procedure remove all jewelry and metallic objects such as Rings Watches Bracelets etc because they could contact conductive parts and components inside the UPS and this might cause discharges and or short circuits Make sure using tools properly isolated to avoid electrical risks Transportation and Storage Warnings and Recommendations A WARNING This UPS must be
32. following modes ONLINE NORMAL Mode When UPS is turned off by selecting ON push button in front panel and AC Line is normal it enters into ONLINE NORMAL mode Under this mode UPS Inverter powers outputs and the energy is taken from DC voltage coming from AC DC converter Batteries are charged by AC Line if required BATTERY Mode Also known Inverter Mode Under ONLINE NORMAL mode when UPS detects a problem in AC input Line or black out it enters in battery mode Under this mode UPS takes energy from its batteries to power outputs There are no transfers neither micro cuts on UPS outputs as inverter was already working the only difference is that energy for outputs is now coming from batteries Transfer time is actually Zero 0 ms UPS also can enter in battery mode when it is turned on without an acceptable AC input ECO Mode There is an energy saving function that makes UPS to power its outputs with AC Line directly If under this mode UPS detects AC input is out of acceptable range it enters into Normal Online mode If an AC failure occurs under ECO mode the UPS s inverter starts working draining energy from batteries There is a transfer time of 4 ms typical This mode is configured and activated from LCD panel There is specific input voltage range and input frequency range to configure for ECO mode BY PASS Mode Under BYPASS mode UPS outputs are powered by AC Line UPS is out of the circuit This mode can be caused by
33. ically powered Disconnect devices from UPS outlets Continuous beep Code 14 15 0r 17 r UPS has been automatically powered Check short circuit problem in devices Active SHORT off because short circuit detected at Continuous beep output Parallel communication lost Check parallel cables and PAR 00X text on each LCD If problem is solved reset Intermittent OF alarm with UP and DOWN simultaneous 1 beep s key selection Any of the error codes activated Probable internal UPS failure Contact service center Backup time is lower than expected Batteries are not fully charged or maybe Let UPS recharge batteries during 6 they are worn out hours If it does not solve the problem batteries maybe need to be replaced INTEGRA 20150105 6K 10K 2PH EN 45 User Manual ups ONLINE 6K 10K 2Ph ENGLISH 13 TECHNICAL SPECIFICATIONS UPS 6K 10K EX 2PH Capacity Capacidad INPUT ENTRADA Input Voltage Voltaje de Entrada Input Range Rango de Entrada Frequency Range Rango de Frecuencia Phase Fases Power Factor Factor de Potencia THDi Slew Rate Segumiento de Frecuencia OUTPUT SALIDA Rated Output Voltage Regulation Regulaci n de Salida Frequency Frecuencia Batt Mode Current Crest Ratio Factor de Cresta THDv Transfer Times Tiempos Transferencia Waveform Forma de Onda Power Outlets Salidas OVERLOAD SOBRECARGA AC Mode Modo Normal Battery Mode M
34. igital multi meter and confirm all output voltages are similar Maximum acceptable deviation should be 3Vac or lower Typically 1Vac f difference between output voltage values is higher than 3Vac we suggest to adjust them by function 15 for inverter output L1 and function 16 for inverter output L2 You can reduce Sub or increase Add voltage output voltage for each of 2 inverters in each UPS as required P 16 dibo 1 2 LI x 14 If AC output voltages are as expected please set to ON external output breakers for all UPS progressively Start with UPS N 1 then UPS N 2 etc After that all UPS outputs are connected in parallel 15 Check to confirm there are no error or alarm messages on LCDs At this moment all UPS are working in NORMAL Online mode and connected in parallel 16 It is time to power on equipments connected to UPS output Power on progressively one by one Check on UPS LCDs how power output rises meanwhile equipments are powered on Once all output load is connected check power output is below 100 xx At this moment UPS parallel system is powering your system in NORMAL Online mode INTEGRA 20150105 6K 10K 2PH EN 29 User Manual ups ONLINE 6K 10K 2Ph ENGLISH 8 OPERATION INTERFACE UPS FRONT PANEL PUSH BUTTON FUNCTION DISPLAY PA ET BATTERY FALILT OFF ESC TEST UP MUTE DOWN ON ENTER d ES di de Y qe RACK FRONT PANEL TOWER FRONT PANEL Both Rack and Tower ty
35. inal External Battery cabinets normally include ts own input breaker WARNING The correct wire gauge or section is strongly affected by diverse factors such as Operation temperature wire length type of wire and kind of installation UPS user and or his electrical contractor must assure an appropriate selection for wire and protection devices for complying with local regulations and directives for electrical installations Wiring colors must be selected according to local directives and regulations LEAK CURRENT PROTECTION In many countries now a day it is legally required to install protections against current leakage to protect human beings in cases of leaks o discharges to ground It is responsibility of the end user and or electrical contractor selecting and including these protection devices in the electrical circuit of the UPS INTEGRA 20150105 6K 10K 2PH EN 11 User Manual ups ONLINE 6K 10K 2Ph ENGLISH AG LINES CONNECTION PROCEDURE e Make sure the UPS is Off before starting the installation Remember to check all wires to be connected are not powered including external batteries UPS terminal block preparation Remove cover of terminal block at the UPS rear panel identified as 12 in rear panel section of this manual DO NOT use a wall power outlet to plug UPS to AC Line as usually ratings of this kind of outlets are not enough to power 6KVA UPS UPS Input wire must be connected by breaker protected line to electric
36. ll not check for input neutral connection ATO Automatic UPS will detect input neutral connection If detected no action is required If NOT detected Alarm is generated If UPS is turned on with this condition it will turn on in battery mode When neutral is detected UPS will go back to normal AC mode and alarm will be muted automatically CHE Works similar to ATO but after neutral is detected UPS will not go to normal AC mode automatically User action is required to mute alarm and put UPS in normal mode Manual action is to enter in this menu for selecting CHE value to make a manual neutral search by pressing enter twice ATO is pre configured value at factory Battery DC value indicated on LCD can be calibrated by this function This function does not changes real battery charger output Only LCD value Parameter 2 Select Add or Sub function to adjust battery voltage to real figure Parameter 3 the voltage range is from OV to 9 9V the default value is OV 20150105 6K 10K 2PH EN 40 User Manual ups ONLINE 6K 10K 2Ph ENGLISH 14 Charger output voltage adjustment m Interface Seting 0 i U i Parameter 2 you may choose Add or Sub to adjust charger voltage output paje Parameter 3 the voltage range is from OV to 9 9V the default value is OV get the accurate charger voltage We strongly suggest to use the default value 0 Any modification should be suitable to battery s
37. llel System eee e For adding a new UPS to an operating system all UPS must be turned off and all equipments must be disconnected from UPS outputs Total UPS guantity must be 3 or lower Firmware of all UPS must be compatible for allowing parallel functionality New UPs must be configured with similar LCD configuration menu than current UPS of the system Follow the procedure explained in Installation Section of this manual INTEGRA 20150105_ 6K 10K 2PH EN 35 User Manual ups ONLINE 6K 10K 2Ph ENGLISH 11 UPS CONFIGUIRATION LO E ll LJ w Ui ae ke Ur U Wem Im d This menu is activated by simultaneous selection of Test Up Mute Down keys during 1 second or longer when UPS is in OFF or BYPASS mode Configurable functions according to UPS mde C GC Bypass AC ECO bod Battery Battery m Description mode mode mode mode mode Test pe pe 6 Frequency range for bypass e 7 JECOmodeenablerdisable e Voltage range for ECO mode el B setting 11 Battery backup time setting Reserved Neutral Loss CRETE 7 L u Charo maoan s s mer L L T EC 1 1 e configurable parameter according to each UPS working mode INTEGRA 20150105 6K 10K 2PH EN 36
38. low total electrical isolation 6 There must be enough physical room to allow comfortable access to all UPS of the system Note if any of the above requirements cannot be complied below procedure must not be performed In case all requirements can be complied proceed as follow 1 Power off selected UPS by OFF button in front panel Note OFF button must be selected twice If OFF is selected only one time UPS will not respond Once UPS is turned off it will shut down its outputs but remaining LCD on This UPS will not go to bypass mode since it is working in UPS system with other UPS generating their output from their inverters At this moment any failure in AC main line must be supported by operative UPS 2 Set AC input breaker located in rear panel of the selected UPS to OFF position 3 Set external output breakers of selected UPS to OFF position 4 Set external input breakers of selected UPS to OFF position 5 Once LCD is turned Off in selected UPS to be isolated disconnect control parallel cables parallel cables and current share cables from its rear panel Other operative UPS must keep their control parallel cables connected NOTE If you disconnect parallel control cables in any of the operative UPS of the system a communication problem will occur and the parallel system will be shut down At this moment selected UPS is currently powered off and isolated so that it can be serviced or simply removed Adding an UPS to a Para
39. ltaneous selection of UP and DOWN keys in front panel meanwhile UPS is in BYPASS mode connected to AC source previous to select ON command INTEGRA 20150105 6K 10K 2PH EN 42 User Manual ups ONLINE 6K 10K 2Ph ENGLISH ERROR FAILURE CODES ON LCD ERROR ERROR BEEP ALARM CODE DESCRIPTION a Hi BUS Voltage Low BUS Voltage 04 06 MEET META 13 M SHORT 15 SHORT L1 L2 Inverter output line to line short circuit detected SHORT IA Beep dB 2 24 29 91 36 output Bd CRTL board ALARM CODES ON LCD WARNING WARNING CODE DESCRIPTION 01 Battery unconnected 0 AA 0 OA _ 0 9 _ 0 0E _ 10 b HEN EA F 22 _ _ 24 O 25 28 3 _ 34 3 39 GA 3 INTEGRA 20150105 6K 10K 2PH EN 43 User Manual ups ONLINE 6K 10K 2Ph ENGLISH ALARM SYMBOLS ON LCD ASHING ICON ALARM DESCRIPTION BEEP Sec A OVER LOAD UPS Overload High power consumption in Watts at 2 beep s UPS output A BATT FAULT Batteries disconnected 1 beep s ws Battery Overload 1 beep ACOUSTIC BEEP Description Buzzer status Muted ESTADO Bypass mode Beeping once every 2 minutes ves Yes ALARM WARNING NO Beeping once every second FAILURE ERROR All failures and Error states Beeping continuously Yes INTEGRA 20150105 6K 10K 2PH EN 44 User Manual ups ONLIN
40. nected in parallel terminal block connections can be done according to following figure INTEGRA 20150105 6K 10K 2PH EN 20 ENGLISH User Manual ups ONLINE 6K 10K 2Ph NOZI N LI eletta N T N LNdANI LNdLNO 7501 95001 NOZL N LI GOT ue ugioeinByuoo ep nuaw unbes 0 esej ua sepeunDijuoo Jejsa z 1 A LI sepijes se7 epijes ej uo A epeyue ej ua Zr 9 Lr ajueipaw sepejoauoo Je s9 u q p Z7 L7 DEAOZL epijes ap UQIJEJN IJUOJ ej uz 091 ul nuaw uoneinBijuoo ul Biyuoo eseud 0 95200 ul aq 190 sjndjno ZI pue 7 HI indjno pue jndui je pue LI ui pajoeuuoo eq 18100 Z LC uoneunBijuoo 9eA0z indio ul VISNSLYSAGV ONINUVM LAdNI ER GR a INALNO L Sdf uoee foede 00L SEAOZL LNdLNO SLINN Z THTIVSVd 21 EN 20150105_ 6K 10K 2PH INTEGRA User Manual ups ONLINE 6K 10K 2Ph ENGLISH PARALLEL CONFIGURATION 2 2 INPUT 2 OUTPUTS 2 INPUTS 120Vac 2 OUTPUTS 120Vac Each output can supply only 50 of total UPS capacity WARNING A To use this UPS as 2 phases UPS is MANDATORY to check there is NO jumpers connected between L1 and L2 at Input and output terminal block You must follow below instructions MANDATORY INSTRUCTIONS TO AVOID PERMANENT DAMAGE IN YOUR UPS AND SYSTEM 1 Remove all jumpers between L1 and L2 at input and output terminal
41. net opcional AS400 optional interface board Interfaz AS400 opcional Specifications can be modified to comply with special project requirements Las especificaciones pueden modificarse para adaptarse a proyectos especiales Specificaions may change without further notice Por motivos comerciales o t cnicos las especificaciones pueden cambiar sin previo aviso EX included function for connecting external battery cabinets funci n b sica incluida que permite la conexi n de bater as externas originales 2PH 2 Phases 2 fases If CF function is active UPS output is de rated to 608 of total original capacity Si se activa la funci n CF la potencia de salida disminuye al 60 de la potencia original INTEGRA 20150105 6K 10K 2PH EN 47 User Manual ups ONLINE 6K 10K 2Ph ENGLISH 14 LIMITED WARRANTY Support If a failure or problem is detected please check troubleshooting section in user manual If problem cannot be solved please contact authorized service center or authorized dealer Batteries Rechargeable batteries can be charged and discharged hundreds of times However they will eventually wear out This is not a defect or failure so that batteries wear out is not covered by this warranty Battery lifetime will depend of operative conditions like working temperature type and frequency of discharging cycles Higher the temperature shorter will be the lifetime Frequent and deep discharging cycles also will short lifetime For critic
42. not exceed UPS capacity At this moment UPS working under NORMAL AC MODE and the system is supplied by UPS NOTE 1 If any error or warning message in indicated in LCD please revise Troubleshooting section of this manual NOTE 2 UPS batteries maybe are not fully charged UPS could require about 4 to 6 hours to recharge batteries up to 100 of their capacity INTEGRA 20150105 6K 10K 2PH EN 27 User Manual ups ONLINE 6K 10K 2Ph ENGLISH 7 START UP PARALLEL UPS REQUIREMENTS FOR PARALLEL SYSTEM WARNING Before starting up this parallel UPS system is mandatory to comply with all below requirements 1 Maximum quantity of UPS to be connected in parallel is 3 Do not try to connect more than 3 units in parallel 2 All UPS to be connected in parallel system must be same model all 6K or all 10K with same firmware version Please ask your distributor to confirm firmware is the same in case of doubts UPS belonging to same manufacturing batch have same firmware version 3 UPS configuration configuration parameters of LGD menu must be the same for all UPS 4 All MBS Maintenance Bypass Switch located in rear panels must be in UPS position and switch covers must be properly installed 5 In case of using external battery packs each UPS must has same external battery packs quantity and type 6 All control parallel cables parallel cables and current share cables must be properly connected in UPS rear panels as indicated in s
43. odo Bater a EFFICIENCY EFICIENCIA Eco Mode Modo ECO AC Mode Modo AC Battery Mode Modo Bater a BATTERIES BATERIAS Type and Qty Tipo y Cantidad Internal Battery Pack bater as Internas External batt cabinets Gabinetes Externos Typical Recharge T T de Recarga Internal Battery Pack bater as Internas External batt cabinet Gabinete Externo Charging Amps Corriente de Carga Charging Voltage Voltaje del cargador INTEGRA 6KEX 2Ph 10KEX 2Ph 6 000VA 4 800W 10 000VA 8 000W 2 phases 2 fases 120Vac L N G Rated Input Entrada Nominal 120 Vac 80Vac 150Vac 3 100 load 60Vac 150Vac 3 50 load 40 70 Hz L1 L2 N G gt 0 99 100 load lt 5 100 load 1 Hz s 2 phases L1 L2 N G 100 110 115 120 127 Vac L N 1 Batt Mode Modo Bater a 50 Hz 0 1 Hz 60 Hz 0 1 Hz 3 1 100 load lt 2 a Linear Load Carga Lineal lt 5 a No Linear Load Carga no Lineal 0 ms Sine Wave Sinusoidal Pura Terminal Block Regleta de Conexi n 100 110 10m 110 130 1m gt 130 1s 100 110 30s 110 130 10s gt 130 1s 96 90 88 120VDC 12V 7AH x 20 pcs 2 groups x 10pcs 120VDC 12V 9AH x 20 pcs 2 groups x 10pcs 120VDC 12V 9AH x 40 pcs gt 2 sets in parallel 2 x 10pcs 10pcs 3 5 H 90 4 H 90 Depending on external battery configuration depende de cantidad de bater as externas 2 0 A Max 136 5 Vdc 1 20150105 6K 10K 2PH EN 46
44. of purchase serial number and name of the dealer is presented with the product to be revised INTEGRA and authorized partners reserve the right to refuse warranty service if any of this information has been removed changed or missing in original purchasing document 4 If product is repaired or replaced repaired or replaced product will be warranted for the remaining time of the original warranty or for 90 days on repaired part from date of repair whichever is longer 5 INTEGRA or their distribution service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is out of warranty a reparation proposal will be sent to the user for his approval If proposal is not accepted service center will keep product available for the user during 60 continuous days After this period product would be disposed and user will not be able to rise any claim 7 Rechargeable batteries like included in this product will definitively wear out even under normal operation This is not a defect or failure so it is not covered by this warranty This warranty does not cover batteries wear out caused by improper or long storage over 6 months without required recharging indicated in product manual Even performing recharging procedure this product cannot be storage longer than 18 months Problems on batteries caused by this kind of long storage are no
45. ompatible with other 6K 10K models UPS 6K and 10K 2Ph require 120Vdc external battery packs Some other 6K and 10KVA models require 240Vdc external battery packs Make sure you will connect compatible external battery pack to your UPS to avoid permanent damages not covered by warranty INTEGRA 20150105 6K 10K 2PH EN 6 User Manual ups ONLINE 6K 10K 2Ph ENGLISH REAR PANEL 1 RS232 7 FAN ventilaci n Forzada 2 USB 8 FAN charger ventilaci n Forzada del cargador 2 058 j 3 EPO Emergency Stop Parada Emergencia 9 MBS Bypass Switch Interruptor Bypass 4 Share Current for parallel UPS para UPS paralelas 10 AC Input Breaker Breaker Entrada AC 5 Parallel Port for parallel UPS para UPS paralelas 11 Terminal block cover Tapa Regleta Conexiones 6 SNMP 14 EXBATT connector Conector Bater as Externas 6 SNMP
46. operator by means of the maintenance switch on the rear panel or from LCD panel when OFF button is activated but it may also happen automatically by UPS malfunction or overload detected at UPS outputs FREQUENCY CONVERSION Function This UPS offers a very sophisticated function named frequency conversion CF that allows UPS to generate power output at determined frequency value 50Hz or 60Hz no matter input frequency value UPs will be able to generate output at 50Hz even input source is at 60Hz or generate 60Hz even if connected to 50Hz source This function can be configured and activated by LCD Revise configuration section of this manual IMPORTANT NOTES 1 Under CF mode UPS will disable BYPASS mode Since UPS has been configured to generate output with frequency value different to input frequency BYPASS mode is disable to avoid a not acceptable frequency value at output 2 When CF function is activated maximum power output is de rated to 6096 of maximum nominal capacity For example for a 10KVA 8KW model when CF is activated maximum output is decreased to 6KVA 4 8KW INTEGRA 20150105 6K 10K 2PH EN 32 User Manual ups ONLINE 6K 10K 2Ph ENGLISH FUNCTION DISPLAY ACCORDING TO OPERATION MODE In each mode UPS will show 4 different alternating screens as described below UPS is connected to main input but UPS output is not powered on because one of the following reasons 1 BYPASS mode is not activated DIS or forbi
47. pe UPS offer same 4 function buttons as described below ON ENTER POWER ON Keep selected during 1 second to power UPS ON ENTER It Works as ENTER or confirmation function when LCD is in configuration menu mode OFF ESCAPE POWER OFF Keep selected to turn UPS OFF ESCAPE It Works as ESCAPE key when LCD is in configuration menu mode TEST UP BATTERY TEST When UPS is in normal mode by selecting TEST key UPS enters into battery test mode during 10 seconds UP It Works as UP key when LCD is in configuration menu mode MUTE DOWN ALARM MUTE It mutes alarm beep in progress DOWN It Works as DOWN key when LCD is in configuration menu mode TEST UP MUTE DOWN Simultaneous Activation CONFIGURATION MODE UPS enters into configuration menu when these 2 keys are activated at same time during 1 second INTEGRA 20150105 6K 10K 2PH EN 30 User Manual ups ONLINE 6K 10K 2Ph ENGLISH UPS FRONT PANEL LED INDICATOR LIGHTS There are 4 LED indication lights in front panel located below LCD These 4 LEDs describe UPS condition as follow UPS in Failure O LED ON OLED OFF UPS FRONT PANEL LCD This UPS has a sophisticated LCD able to display all important information related to input line UPS status and values operation mode and error and alarm messages It is a powerful information tool to know what is happening at any moment LCD is also the configuration interface for all configurable parameter
48. pecifications a d d m e 6 S NOTE Before making voltage adjustment be sure to disconnect all batteries first to UC A e 15 Inverter 1 output voltage adjustment Note available after March 2012 Interface a Seting Parameter 2 you may choose Add or Sub to adjust inverteri voltage Parameter 3 the voltage range is from OV to 9 9V the default value is OV Parameter 2 you may choose Add or Sub to adjust inverter2 voltage Parameter 3 the voltage range is from OV to 9 9V the default value is OV o 17 FAN Speed Adjustment i tea le JJ Parameter 2 Indicates always FAN e I 1 Parameter 3 E H r Ht P will allow FAN to adjust its speed automatically according to cooling FUL It will force FAN at full speed under any condition This function must be in ATO mode Any other configuration for service center only e 18 AC Voltage Meter Calibration for L1 Interface Setin AC voltage value for L1 output indicated on LCD can be adjusted by this function Parameter 2 you may choose Add to increase or Sub to reduce to adjust inverter voltage Parameter 3 the voltage range is from OV to 9 9V the default value is OV Seting AC voltage value for L2 output indicated on LCD can be adjusted by this function Parameter 2 you may choose Add to increase or Sub to reduce to adjust inverteri voltage Parameter 3 the voltage range i
49. puts cannot be connected in parallel Under this situation MENU 04 will show as reserved not available RES RES When UPS inputs are connected in parallel jumper connected between input n Ue YA L1 amp input L2 UPS outputs can be configured as 1 output line output L1 amp n output L2 in parallel or 2 separate output lines This configuration requires to LI FP da I 5 set parameter 03 and 04 of MENU 04 Parameter 2 OP P means output 1 and output 2 parallel function WK L Parameter 3 n DIS disable output parallel function Under this configuration output 1 and 2 OPP nA must NOT be connected in parallel TTT ENA enable output parallel function to allow connecting 2 outputs in parallel to get only one phase output with 100 of total UPS capacity It is MANDATORY to use one phase input connection when one phase output is reguired NOTE If ENA is configured and 2 different outputs configuration is used this setting will be ignored Interface eee Seting lt 1 n A Parameter 2 Set the acceptable low voltage for bypass Setting range is from 60V LI Dr ES to 99V and the default value is 60V a CH Ya uU Tu ves x Parameter 3 Set the acceptable high voltage for bypass Setting range is from LI I ILI 131V to 140V and the default value is 140V UJ e 06 Frequency range for bypass Interfase RR O O gt Parameter 2 Set the acceptabl
50. riodically tested to check capacity and assure and appropriate back up e Toenlarge batteries life expectancy it is recommendable to fully discharge UPS one every 2 to 3 months e During UPS storage recharge batteries according to the following table Storage Temperature Recharging Frequency Recharging Time 25 C a 30 C Every 4 months During 6 hours 30 C a 45 C Every 2 months During 6 hours SAFETY STANDARDS SAFETY IEC EN 62040 1 EMI Radiated EMS ESD TRANSPORTATION ISTA TA This product has been designed to operate in industrial and commercial applications If it is used in different application some considerations for avoiding interferences could be necessary INTEGRA 20150105 6K 10K 2PH EN 5 User Manual ups ONLINE 6K 10K 2Ph ENGLISH 2 AVAILABLE MODELS 6K EX 2Ph A 10K EX 2Ph UPS with internal batteries and connection for external battery cabinets to increase backup time EX Indicates connection for external batteries 2PH Indicates 2 Phases product Model Internal Batteries Ext Batt Connector Isolation Transformer SKEX 10KEX 20 Y EXTERNAL BATTERIES 2Ph models can operate with internal batteries but if extended backup time is required external batteries can be connected to UPS External Battery Cabinet for 6K 10K 2Ph Model EX BAT T6 T10 2PH Batteries 40 pieces x 12V 9AH 4 groups of 10 batteries in parallel DC Voltage 120Vdc WARNING External battery packs for 2PH models is not c
51. rnal batteries there must be also DC Circuit Breakers between UPS and battery bank some Models include a DC breaker on the rear panel for external battery pack protection otherwise an external DC Circuit breaker must be installed MATERIALS AND ELECTRICAL DEVICES WARNING Verify that all electrical lines involved in installation are open circuits and free of dangerous voltages before starting inspection tasks All switches related to these electrical lines must be in OFF position before starting UPS installation After disconnecting power from electrical lines involved in installation check again with a digital voltmeter that are free of dangerous voltages IMPORTANT Warning label must be placed on primary involved circuit breakers to alert there are maintenance personnel working on these circuits to avoid accidental actuation on involved breakers INTEGRA 20150105 6K 10K 2PH EN 9 User Manual ups ONLINE 6K 10K 2Ph ENGLISH TOWER UPS INSTALLATION SITE CONSIDERATIONS This product has been designed to be used indoors protected from water direct sun light dust and extreme temperature Install the UPS in well ventilated location or air conditioned room Temperature must be always in acceptable range according to technical specifications table of this manual It is strongly recommendable controlled room temperature between 21 C to 24 C for longer battery and UPS life There must be minimum 1 meter free room distance
52. s 3 saat H 6 K m im B s ili P i P p 1 1 BATTERY INFORMATION In this section is displayed battery charging level and battery alarms error icons 2 ELAPSED TIMER When UPS switches to battery mode elapsed time during battery mode is displayed in Hours Minutes Seconds 3 ERROR ALARM CODE In case of alarm or error 2 digits code is displayed in this section to describe the kind of error or alarm Revise error and alarm codes tables in this manual 4 BEEP STATUS It shows if audible alarm buzzer is active or muted 5 LOAD INFORMATION In this section is displayed load value connected to UPS by 4 segments displays 0 25 2590 5090 5090 7590 and 75 100 It also shows error and alarm icons related to UPS output 6 UPS MODE All possible UPS modes are indicated by this section in graphic way 7 INPUT OUTPUT VALUES Input and output voltage and frequency values can be monitored in this LCD section In battery mode this section shows battery DC voltage INTEGRA 20150105 6K 10K 2PH EN 31 User Manual ups ONLINE 6K 10K 2Ph ENGLISH 9 OPERATION SINGLE UPS This is a True On Line Double Conversion UPS and it is designed to offer clean bump less and highest quality power to your computer related equipments protecting also your valuable data Power delivered by UPS is 100 sine wave as main line According to AC Line status the UPS may operate in
53. s from OV to 9 9V the default value is OV INTEGRA 20150105 6K 10K 2PH EN 41 User Manual UPS ONLINE 6K 10K 2Ph ENGLISH ERROR FAILURE CODES ON LCD When a failure or alarm is detected by the UPS an alarm or error code is presented in front panel LCD This code or symbol will allow to identify the problem In case of failure or alarm service center must revise the problem In Alarm or failure state UPS shows a numeric code in the LCD There are some alarm code using similar numbers as failure codes for example alarm code 02 input neutral not connected and failure code 02 High DC BUS value so it is important to identify if the situation described is an alarm or a failure ALARMS Alarms shows Alert symbol blinking in the LCD Acoustic beep sounds intermittent not continuous Alarms are forced by external situations Alarms do not mean damage inside the UPS Usually alarm states allow UPS work in normal ONLINE mode Only few alarm states can block UPS in bypass mode ERROR FAILURES In a failure state Alert symbol is fixed in LCD not intermittent You will hear a continuous beep not intermittent Failure state usually mean internal damage in the UPS Usually UPS goes to BYPASS mode when a failure situation is detected WARNING Some alarms can block UPS avoiding normal operation of UPS until they are reset Technician must revise original error cause has been solved and then alarm must be reset by simu
54. sually factory setting allows UPS to generate 2 output lines with same phases shift than detected at input side This is done by Function 03 set as ATO Automatic Under this configuration UPS will not allow changes in input phases shift so if this situation is detected alarm 39 will be generated and UPS will go to battery mode If 2 alternative input sources with different phases shift will be used UPS must be configured with MENU 03 as CP Constant Phase instead of ATO Automatic Phase detection CP means UPS will fix output phases shift to a desired value no matter what happens at the input Under this setting UPS will allow changes input phases shift without generating alarms IMPORTANT NOTE Since under CP setting input and output phases shift could be different UPS will not be able to accept BYPASS modes BYPASS will be immediately disable by UPS when MENU 03 is set as CP Any external BYPASS devices must be removed by user to avoid potential short circuits between UPS input and output Example of how to configure FUNCTION 03 for accepting 2 different input sources with different phases shift MENU 03 CP 1200 This configuration will force UPS outputs to be shifted 1207 in phase no matter the phase of the inputs In that way UPS will manage any phase angle change at input without generating alarm 39 Deeper instructions to configure UPS in configuration section of this manual INTEGRA 20150105 6K 10K 2PH EN 17 User Manu
55. t covered by this warranty 8 This warranty does not cover failure caused by inadequate installation or maintenance misuse accidents fire or floods In these cases warranty will be considered void 9 This product can include protection devices like input fuse or input breaker Activation of this kind of devices is not a failure it is caused by an improper product installation Input fuse or breaker reset or replacement is not covered by this warranty 10 This warranty does not cover damages produced during transportation from user to technical service caused by improper packing of the product by user 11 This warranty does not cover product failures caused by installations modifications or repair performed by non authorized person H product is open by not authorized technician warranty will be considered void 12 Warranty time could be extended as an option depending on market or products Contact your authorized dealer or www integra ups com for additional information about official warranty extension plans 13 Warranty terms and conditions cannot be modified or extended by third parties without written approval of INTEGRA Limited Warranty PRO11 INTEGRA does not warrant that the operation of this product will be uninterrupted or error free during its lifetime If product fails to work the maximum liability of INTEGRA under this limited warranty is expressly limited to the lesser of the price you have paid for the product or the cost
56. terminal block are connected with a jumper 2 UPS must be connected to one phase input line only 3 Check to confirm function 03 in LCD panel is configured as ATO automatic mode In this mode inverter output will follow input phase Phase angle read by UPS must be 000 in function 03 screen ATO is factory preconfigured value 4 Check to confirm function 04 in LCD panel is configured as ENA Enabled If not error alarms TA and 18 will be generated by the UPS Note ENA is the factory preconfigured value B ri ja A B A U 1 E ULL mE EMA Detailed instructions to check and configure function 03 amp 04 available in Configuration section INTEGRA 20150105 6K 10K 2PH EN 14 User Manual ups ONLINE 6K 10K 2Ph ENGLISH CONFIGURATION 2 UPS 2 Ph 2 Input 120Vac 2 Output Wa Each output can supply only 50 of total UPS capacity 2 Inputs Ph 2 Outputs Ph 120Vac 50 50 OUTPUT INPUT HE a aM wos aw G L1 L2 N L L2 N L1 L2 N L1 L2 N Special Note Nota Especial 120V 120V 120V 120V Each output only offers 50 of total 0 0 UPS capacity in Watts 50 50 Cada salida SOLO ofrece el 50 de la capacidad total en Watts del UPS WARNING N To use this UPS as 2 phases UPS is MANDATORY to check there is NO jumpers connected between L1 and L2 at Input and output terminal block You must follow below instructions MANDATORY INSTRUCTIONS TO AVOID PERMANENT DAMAGE 1
57. ther UPS previously powered ON in the parallel system and will get its own parallel identification as PAR 00X where A is the position according to power on sequence PAR 001 for 1st UPS powered on PAR 002 for 2nd and PAR 003 for 3rd UPS This message is only indicated in UPS manufactured after Dec 2011 If UPs is before Dec 2011 continue without waiting for PAR 00X message 6 e Or OI zm Fi LILI HJ Jeg P E l P1 e 9 At this moment all UPS LCDs must turn on to indicate internal circuitry in UPS is been powered xx H bypass mode is allowed all UPS will go to bypass mode f bypass mode is not allowed by configuration all UPS will go to a kind of stand by mode with outputs open and powered off waiting until ON command is selected in UPS front panel 10 At this moment configuration menu in each UPS LCD must be revised to select desired configuration It is mandatory to use same configuration in all configuration parameters for all UPS of the system 11 Once configuration has been selected and verified all UPS can be started up by selecting ON push button in front panel Please press ON push button for each UPS One long beep will be generated ON message will be displayed on top side of LCD 12 All UPS will go to NORMAL Online mode at same time 13 Before setting to ON all external output breakers please revise AC voltage output on each UPS Please measure AC output voltage using a d
58. to avoid access to wiring Check EPO connections e EPO Port closed Wired EPO function disabled e EPO port connected to an emergency switch EPO function available by activation of Emergency Switch which must be Normally Closed type in order to guarantee that UPS will shut down when circuit opens Check Maintenance Bypass Switch MBS located in UPS rear panel is in UPS position and its cover is duly installed Make sure all external protection devices in input and output lines are in open OFF position SINGLE UPS START UP PROCEDURE e wee ARR Make sure all equipments connected to UPS are off Power AC input at electrical panel board by setting input AC Lines Circuit Breaker to ON Put Battery Bank breaker to ON Only for Ex Models If using external battery pack Put AC INPUT Breaker to ON in UPS rear panel LCD in front panel starts to show bypass mode UPS Outputs are powered although UPS is off because it is on By Pass mode At this moment output power is being supplied by AC Input Power Line Start up the UPS by pressing On push button in front panel until beep is heard and ON message displayed on top of the LCD Few seconds after the UPS leaves By Pass mode to enter in Normal Online Mode also known as AC Mode Power on sequentially each equipment connected to UPS output The front panel LCD should show the load increase as equipments start Once all equipments are on the total power consumption load should
59. transported only in its original package to be properly protected WARNING This eguipment must be storage in dry and ventilated site in upright position WARNING Before storage this UPS batteries must be recharged for 8 to 10 hours WARNING During long term storage UPS must be recharged periodically according to BATTERIES MAINTENANCE section WARNING EQUIPMENT DISPOSAL A Out of service units It is strongly recommended to dispose this piece of equipment according to valid directives in your country At the moment of disposing all pieces need to be managed appropriately to avoid possible environmental damage or for some materials to be recycled Batteries Do not throw it to fire risk of explosion Do not open the batteries there are dangerous liquids inside INTEGRA 20150105 6K 10K 2PH EN 4 User Manual ups ONLINE 6K 10K 2Ph ENGLISH WARNING BATTERIES MAINTENANCE e Batteries capacity in general of all kinds decrease with time and use e Our products contain high quality batteries only e X Batteries useful life in our UPS is between 4 and 5 years considering environment temperature under 25 C and optimal operational conditions This time can be dramatically reduced by high temperature and other adverse operation condition e Batteries life expectancy may be also affected by other operation conditions such as electrical service quality as well as number and kind of equipments connected to UPS e Batteries should be pe
60. uirements but not with local directives and regulations The end user and or electrical contractor will be responsible of watching for complying with electrical regulations and normative during electrical installation managed by end user Inspection performed by installation technician is not intended to confirm regulations and directives accomplishing but only with technical needs for optimal UPS operation SITE INSPECTION e During transport of this UPS from a cold place to a warmer and more humid one some condensation could be generated Leave the UPS for at least 2 hours to climate to new installation site e Do not install the UPS outdoors or near water sources nor in wet environment e Do not install the UPS in sites exposed to sun light or heat sources Temperature at operation site should never rise over 35 C Batteries life shortens over 25 C e Installation site must be dry fresh free of dust fibers and any other objects conductors or not suspended in the air that could get into the UPS thru the ventilation system Fan e Do not block UPS ventilations UPS INPUT AND OUTPUT POWER LINES PROTECTION AC LINES PROTECTIONS DEVICES All UPS Inputs and outputs must be protected by circuit breakers and current leak protections Protection capacity and type must fulfill local regulations as well as directives from this manual Grounding must be according to local directives as well DC PROTECTIONS DEVICES For Ex models with exte