Home
VAMP 265M manual
Contents
1. Application example of differential protection using VAMP 265M Figure 10 5 1 Differential protection of a motor using VAMP 265M Settings ConnGrp loCmps l oCmps Un U n Yy0 OFF OFF Generator nominal voltage Generator nominal voltage 176 V265M EN M A004 10 Applications 10 6 Trip Circuit Supervision 10 6 10 6 1 V265M EN M A004 Trip Circuit Supervision Trip circuit supervision is used to ensure that the wiring from the protective device to a circuit breaker is in order This circuit is unused most of the time but when a protection device detects a fault in the network it is too late to notice that the circuit breaker cannot be tripped because of a broken trip circuitry The digital inputs of the device can be used for trip circuit monitoring The dry digital inputs are most suitable for trip circuit supervision The first six digital inputs of VAMP 200 series relays are not dry and an auxiliary miniature relay is needed if these inputs are used for trip circuit Supervision Also the closing circuit can be supervised using the same principle In many applications the optimum digital inputs for trip circuit supervision are the optional inputs DI19 and DI20 They don t share their terminals with any other digital inputs Trip circuit Supervision with one digital input
2. 53 5 5 Differential overcurrent protection Al gt 87 5 Protection functions 5 5 54 Differential overcurrent protection Al gt 87 The differential overcurrent protection comprises two separately adjustable stages stage Al gt and stage Al gt gt The differential protection is based on winding currents difference between IL and lL side In YyO connection measured currents are also winding currents see Figure 5 5 1 In motor and generator applications the connection group is always Yy0 and measured currents are also winding currents WindingCurrentl IL1 winding TL1 winding pS TL2 winding ee Peon I LI IL2 IL3 L3 LQ Figure 5 5 1 Winding currents in connection group Yy0 Bias current calculation is only used in protection stage Al gt Bias current describes the average current flow in transformer Bias and differential currents are calculated individually for each phase difflslohko ILI I Diff amp s o B gt IL2 PA Z zl d Trip IL3 STX Bi ukom OEH TL lo I ompensation Diff amp TL3 E Bias J r Register 2 Harm Conngrp Iocmps T o cmps 2Harm Al gt Enable events setting setting setting Figure 5 5 2 Block diagram of the differential overcurrent stage Al gt The stage Al gt can be configured to operate as shown in Figure 5 5 3 This dual slope characteristic allows more differential current at higher currents before tripping V265M EN M A004 5 Protection functions 5 5
3. 6 S1 gt Arc sensor 1 positive connector S 7 S1 gt Arc sensor 1 negative connector Arc sensor itself is polarity free 190 V265M EN M A004 11 Connections 11 2 Auxiliary voltage 11 2 11 3 11 3 1 V265M EN M A004 Auxiliary voltage The external auxiliary voltage Uaux standard 40 265 V ac dc or optional 18 36 Vdc for the terminal is connected to the terminals X3 17 18 NOTE When optional 18 36 Vdc power module is used the polarity is as follows X3 17 negative X3 18 positive Serial communication connectors The pin assignments of communication connectors including internal communication converters are presented in the following figures and tables Front panel connector Figure 11 3 1 1 Pin numbering of the front panel D9S connector Pin RS232 signal Not connected Rx in Tx out DTR out 8 V GND DSR in activates this port and disables the X4 RS232 port RTS in Internally connected to pin 8 CTS out Internally connected to pin 7 O O N OD O11 oO PM No connected NOTE DSR must be connected to DTR to activate the front panel connector and disable the rear panel X4 RS232 port The other port in the same X4 connector will not be disabled 191 11 3 Serial communication connectors 11 Connections 11 3 2 Rear panel connector X5 REMOTE The X5 remote port communication connector
4. During tens of hours of synchronizing the device will learn its average error and starts to make small corrections by itself The target is that when the next synchronizing message is received the deviation is already near zero Parameters AAlntv and AvDrit will show the adapted correction time interval of this 1 ms auto adjust function Time drift correction without external sync If any external synchronizing source is not available and the system clock has a known steady drift it is possible to roughly correct the clock error by editing the parameters AAIntv and AvDrit The following equation can be used if the previous AAlIntv value has been zero 604 8 AAIntv DriftInOneWeek If the auto adjust interval AAIntv has not been zero but further trimming is still needed the following equation can be used to calculate a new auto adjust interval 1 1 DriftInOneWeek AADU previous 604 8 AAN yew The term DriftInOne Week 604 8 may be replaced with the relative drift multiplied by 1000 if some other period than one week has been used For example if the drift has been 37 seconds in 14 days the relative drift is 37 1000 14 24 3600 0 0306 ms s V265M EN M A004 121 6 5 System clock and 6 Supporting functions synchronization Example 1 If there has been no external sync and the relay s clock is leading sixty one seconds a week and the parameter AAlntv has been zero the parameters are set
5. Measured data The measured values can be read from the main menus and their submenus Furthermore any measurement value in the following table can be displayed on the main view next to the single line diagram Up to six measurements can be shown Value Menu Submenu Description IL1 Meas PHASE CURRENTS Phase current IL1 A IL2 Meas PHASE CURRENTS Phase current IL2 A IL3 Meas PHASE CURRENTS Phase current IL3 A L1 Meas PHASE CURRENTS Phase current I L1 A PL2 Meas PHASE CURRENTS Phase current I L2 A PL3 Meas PHASE CURRENTS Phase current I L3 A ILiw Meas WINDING CURRENTS Winding current IL1 xlmot IL2w Meas WINDING CURRENTS Winding current IL2 xIlmot IL3w Meas WINDING CURRENTS Winding current IL3 xImot PL1Iw Meas WINDING CURRENTS Winding current I L1 xIlmot PL2w Meas WINDING CURRENTS Winding current I L2 xlmot L3w Meas WINDING CURRENTS Winding current IL 3 xImot diL1 Meas CURRENT DIFF Differential current IL1 xImot dIL2 Meas CURRENT DIFF Differential current IL2 xImot dIL3 Meas CURRENT DIFF Differential current IL3 xImot AIL1 Meas CURRENT DIFF Differential angle IL1 F11 deg AIL2 Meas CURRENT DIFF Differential angle IL2 I l2 deg AIL3 Meas CURRENT DIFF Differential angle IL3 I l3 deg IL1 Meas ANGLES Measured phase angle L1 deg IL2 Meas ANGLES Me
6. The benefits of this scheme is that only one digital inputs is needed and no extra wiring from the relay to the circuit breaker CB is needed Also supervising a 24 Vdc trip circuit is possible The drawback is that an external resistor is needed to supervise the trip circuit on both CB positions If supervising during the closed position only is enough the resistor is not needed e The digital input is connected parallel with the trip contacts Figure 10 6 1 1 e The digital input is configured as Normal Closed NC e The digital input delay is configured longer than maximum fault time to inhibit any superfluous trip circuit fault alarm when the trip contact is closed e The digital input is connected to a relay in the output matrix giving out any trip circuit alarm e The trip relay should be configured as non latched Otherwise a superfluous trip circuit fault alarm will follow after the trip contact operates and the relay remains closed because of latching e By utilizing an auxiliary contact of the CB for the external resistor also the auxiliary contact in the trip circuit can be supervised e When using the dry digital inputs DI7 using the other inputs of the same group sharing a common terminal is limited e When using the wet digital inputs DI1 DI6 an auxiliary relay is needed 177 10 6 Trip Circuit Supervision 10 Applications 178 Using optional DI19 DI20 Note In the device only the optional
7. Vv NCO Fibre TX wC lt ACO Zo QN On oY X4 ProfibusDP Remote fibre Figure 11 3 2 3 Picture of rear Figure 11 3 2 4 Pin numbering of the communication port REMOTE FIBRE rear communication ports Profibus DP 195 11 3 Serial communication connectors 11 Connections E Ni E Col gt Figure 11 3 2 5 Dip switches in RS 485 and optic fibre options Dip switch Switch Function Function number position RS 485 Fibre optics 1 Left 2 wire connection Echo off 1 Right 4 wire connection Echo on 2 Left 2 wire connection Light on in idle state 2 Right 4 wire connection Light off in idle state 3 Left Termination On Not applicable 3 Right Termination Off Not applicable 4 Left Termination On Not applicable 4 Right Termination Off Not applicable 196 V265M EN M A004 11 Connections 11 4 Optional two channel arc protection card 11 3 3 11 4 V265M EN M A004 X4 rear panel connector local RS232 and extension RS485 ports Rear panel port Pin Signal LOCAL X4 1 No connection X4 2 Rx in RS232 local X4 3 Tx out RS232 local X4 4 DTR out 8 V X4 5 GND X4 6 No connection X4 7 B RS485 extension port X4 8 A RS485 extension port X4 9 No connection NOTE In the VAMP relays a positive RS485 voltage from A to B corresponds to bit value 1 In X4 connector the RS485 extension port
8. 5 7 Stall protection IST gt 48 5 Protection functions 5 7 1 66 Motor status Motor is defined as stopped starting or running e Motor sopped Motor average current is less than 10 of the motor nominal current e Motor starting To reach the starting position motor has to be stopped for least 500ms before starting Motor average current has to increase above the motor start detection current setting value within 200ms Motor will remain starting as long as the terms for turning into running condition are not filled e Motor running Motor is able to turn into a running position from both stopped and starting position Low limit for motor running is 20 of the motors nominal and the high limit for motor running is 120 of the motors nominal current MOTOR STATUS MOTOR STATUS TIME JIL BA Phase current IL oA DI Status Storred MOTOR STATUS Stopped DO SCntr A Motor start counter 0 ECntr A Motor run counter 0 193 2min Ist IMot strs Beh Elapsed time from motor start 191 8 min Motor starts in last hour 0 h Event enabling Mot start event Mot started event E Motor running event E Motor stopped event Li Figure 5 7 1 1 Motor status via Vampset and local panel The status of the motor can be viewed via Vampset software or by looking from the local panel of the relay Mstat Statuses Starting and running can be found from the output and block matrix Therefore it is possible t
9. Ambient temperature corrected max allowed continuous current Imax40 lmot Allowed load at Tamb 40 C Set Default 100 Imax70 lmot Allowed load at Tamb 70 C Set Tamb C Ambient temperature Editable Set Samb n a Default 40 C Samb Sensor for ambient temperature n a No sensor in use for Tamb Set ExtAl1 External Analogue input 1 16 16 For details of setting ranges see chapter 12 3 Set An editable parameter password needed C Can be cleared to zero F Editable when force flag is on V265M EN M A004 81 5 12 Second harmonic O C stage 5 Protection functions If2 gt 51F2 12 82 Second harmonic O C stage I2 gt 51F2 This stage is mainly used to block other stages The ratio between the second harmonic component and the fundamental frequency component is measured on all the phase currents When the ratio in any phase exceeds the setting value the stage gives a start signal After a settable delay the stage gives a trip signal The start and trip signals can be used for blocking the other stages The trip delay is irrelevant if only the start signal is used for blocking The trip delay of the stages to be blocked must be more than 60 ms to ensure a proper blocking Start Register event Register event Setting Delay Enable events 2 Harm Figure 5 12 1 Block diagram of the second harmonic stage Setting parameters of second harmonic blocking 2 Ha 51F
10. V265M EN M A004 73 5 10 Earth fault protection 10 gt 5 Protection functions 50N 51N Inverse operation time Ip gt stage only Inverse delay means that the operation time depends on the amount the measured current exceeds the pick up setting The bigger the fault current is the faster will be the operation Accomplished inverse delays are available for the Io gt stage The inverse delay types are described in chapter 5 17 The relay will show a scaleable graph of the configured delay on the local panel display Inverse time limitation The maximum measured secondary residual current is 10xloy and maximum measured phase current is 50xIn This limits the scope of inverse curves with high pick up settings See chapter 5 17 for more information Setting groups There are two settings groups available for each stage Switching between setting groups can be controlled by digital inputs virtual inputs mimic display communication logic and manually Parameters of the undirectional earth fault stage lo gt 50N 51N Parameter Value Unit Description Note Status Current status of the stage Blocked Start F Trip F TripTime s Estimated time to trip SCntr Cumulative start counter Clr TCntr Cumulative trip counter Clr SetGrp 1or2 Active setting group Set SGrpDI Digital signal to select the active setting group 2 None Dix Digital input Set Vix Virtual input LEDx LED indicator signal VOx Virtual out
11. eeeee 215 12 4 Supporting functions e eee eeeeeeee eee eeeeeeeeeeeeeeeeeeeeeeeees 216 12 4 1 Disturbance recorder DR cceeseeeeseeeeeeeeeees 216 13 Abbreviations and SYMbOIS cccccesesesesseeeeeeeeeeeeeneees 217 14 CONRSUUCHION iisiccacicsctecettet sea cttetceusedctccasadsscausntceacasacstacueacteess 218 15 Order information ccccccccsesseeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeees 219 16 REVISION history iss sstecces ccd edsienstsreecsiencnssiieimartercreedeinenniens 221 6 V265M EN M A004 1 General 1 1 Relay features 1 1 V265M EN M A004 General Chapter 1 3 of the publication contains general descriptions of the functions of the differential protection relay as well as operation instructions It also includes instructions for parameterization and configuration of the relay and instructions for changing settings Chapter 4 16 of the publication includes detailed protection function descriptions as well as application examples and technical data sheets Relay features VAMP 265M differential protection relay is ideal for motor differential protection The relay features the following protection functions List of protection functions IEEE IEC symbol Function name ANSI code 50 51 an 3r gt Overcurrent protection 37 l lt Undercurrent protection 87 Al gt Al gt gt Differential overcurrent protection 46 l2 gt Po
12. k 10 k 5 delay s 2 k 2 k 0 5 0 2 0 1 0 08 0 06 1 2 3 45678 10 20 T Iset Figure 5 17 1 8 ANSI IEEE moderately inverse delay inverseDelayIEEE1_MI IEEE STEI 600 400 100 delay s 0 2 k 20 0 1 k 10 0 08 0 5 k 1_ k 006 k 0 5 k 1 _ k 2 k 5 1 2 3 4 5678 10 20 T set Figure 5 17 1 10 ANSI IEEE short time extremely inverse delay inverseDelayIEEE1_STEI 101 5 17 Inverse time operation 5 Protection functions 102 IEEE2 inverse time operation Before the year 1996 and ANSI standard C37 112 microprocessor relays were using equations approximating the behaviour of various induction disc type relays A quite popular approximation is Equation 5 17 1 3 which in VAMP device is called IEEE2 Another name could be IAC because the old General Electric IAC relays have been modeled using the same equation There are four different delay types according Table 5 17 1 4 The old electromechanical induction disc relays have inverse delay for both trip and release operations However in VAMP device only the trip time is inverse the release time being constant The operation delay depends on the measured value and other p
13. By selecting the next smaller standard size we get 1 5 KQ V265M EN M A004 10 Applications 10 6 Trip Circuit Supervision The power rating for the external resistor is calculated using Equation 10 6 1 5 This equation includes a 100 safety margin to limit the maximum temperature of the resistor because modern resistors are extremely hot at their rated maximum power Equation 10 6 1 5 P 2 T2 R K1MAX P 2 0 0061 2x1500 0 11 W Select the next bigger standard size for example 0 5 W When the trip contacts are still closed and the CB is already open the resistor has to withstand much higher power Equation 10 6 1 3 for this short time P 1212 1500 9 8 W A 1 W resistor should be selected to withstand this short time peak power However if the trip relay can be closed for longer time than a few seconds a 20 W resistor should be used 10 6 2 Trip circuit supervision with DI19 and DI20 The benefits of this scheme is that no external resistor is needed The drawbacks are that two digital inputs from two separate groups are needed and two extra wires from the relay to the CB compartment is needed Additionally the minimum allowed auxiliary voltage is 48 Vdc which is more than twice the threshold voltage of the dry digital input because when the CB is in open position the two digital inputs are in series e The first digital input is connected parallel with the auxiliary contact of the open coil of the circui
14. Disabling several start and trip events of the same fault Several events are enabled Several events of an increasing fault is disabled Set ClrDly 0 65535 Duration for active alarm status AlrL1 Alr2 AlrL3 and Ocs Set 127 6 8 Combined overcurrent status 6 Supporting functions Parameter Value Unit Description Note LINE FAULT FItL1 FItL2 FItL3 Fault trip status for each phase O No fault since fault ClrDly 1 Fault is on Oct Combined overcurrent trip status FitL1 FItL2 FItL3 0 FitL1 1 orFltL2 1 or FItL3 1 LxTrip On Event enabling for FItL1 3 Events are enabled Events are disabled Set LxTripOff On Off Off Event enabling for FItL1 3 Events are enabled Events are disabled Set OCTrip On Event enabling for combined o c trips Events are enabled Events are disabled Set OCTripOff Off Event enabling for combined o c starts Events are enabled Events are disabled Set IncFltEvnt Disabling several events of the same fault Several events are enabled Several events of an increasing fault is disabled Set ClrDly 0 65535 Duration for active alarm status FItL1 Flt2 FItL3 and OCt Set Set An editable parameter password needed Used with IEC 60870 105 103 communication protocol The alarm sc
15. Operation time T Thermal time constant tau Setting value In Natural logarithm function l Measured rms phase current the max value of three phase currents lp Preload current I v8 xke xI If temperature rise is 120 gt 1 2 This parameter is the memory of the algorithm and corresponds to the actual temperature rise k Overload factor Maximum continuous current i e service factor Setting value k Ambient temperature factor Permitted current due to tamb See Figure 5 11 1 IMODE The rated current In or Imor C Cooling time coefficient cooling time constant C X T Time constant for cooling situation If the transformer s fan is stopped the cooling will be slower than with an active fan Therefore there is a coefficient ct for thermal constant available to be used as cooling time constant when current is less than 0 3xIN V265M EN M A004 5 Protection functions 5 11 Thermal overload protection T gt 49 V265M EN M A004 Heat capacitance service factor and ambient temperature The trip level is determined by the maximum allowed continuous current Imax corresponding to the 100 temperature rise Orrip i e the heat capacitance of the transformer Imax depends of the given service factor k and ambient temperature amep and settings Imaxao and Imax7o according the following equation Lax K Ke Iy The value of ambient temperature compensation factor kO depends on the ambient te
16. Un 110 kV U n 21 kV The relay setting is 0 20 pu 20 xly The rated current on HV and LV side will be same as in example 1 The corresponding secondary currents are Isec 0 20xIy 0 20x131 2x1 150 175 mA HV side l sec 0 20xl n 0 20x687 3x5 800 859 mA LV side Example 4 Per unit to secondary for Arcl gt CT 750 5 The relay setting is 2 pu 200 gt Secondary current is Isec 2x5 10A Example 5 Secondary to per unit for residual current Input is lo1 Or loz CTo 50 1 Current injected to the relay s input is 30 mA Per unit current is Ipu 0 03 1 0 03 pu 3 Example 6 Per unit to secondary for residual current Input is lo1 or loz CTo 50 1 The relay setting is 0 03 pu 3 gt Secondary current is Isec 0 03x1 30 mA 137 7 7 Primary secondary and per unit 7 Measurement functions scaling 138 Example 7 Secondary to per unit for residual current Input is locaic CT 750 5 Currents injected to the relay s IL input is 0 5 A ILo IL3 0 Per unit current is Ipy 0 5 5 0 1 pu 10 Example 8 Per unit to secondary for residual current Input is locaic CT 750 5 The relay setting is 0 1 pu 10 gt If IL2 Its 0 then secondary current to l4 is Isec 0 1x5 0 5A V265M EN M A004 8 Control functions 8 1 Output relays 8 1 V265M EN M A004 Control functions Output relays The output relays are also called digital out
17. X6 6 L gt X6 7 L en EANNA E N Serene AA AE i DI19D120_option_block_diagram Figure 11 8 2 1 Block diagram of optional DI19 DI20 module with one arc channel V265M EN M A004 12 Technical data 12 1 Connections 12 Technical data 12 1 Connections 12 1 1 Measuring circuitry Rated phase current 5 A configurable for CT secondaries 1 10 A Current measuring range 0 250 A Thermal withstand 20 A continuously 100 A for 10 s 500 A for 1 s Burden lt 0 2VA Rated phase current 1 A configurable for CT secondaries 1 10 A Current measuring range 0 50 A Thermal withstand 4A continuously 20 A for 10 s 100 A for 1 s Burden lt 0 1 VA Rated residual current optional 5 A configurable for CT secondaries 1 10 A Current measuring range 0 25A Thermal withstand 20 A continuously 100 A for 10 s 500 A for 1 s Burden lt 0 2VA Rated residual current 1 A configurable for CT secondaries 0 1 10 A Current measuring range 0 5A Thermal withstand 4 A continuously 20 A for 10 s 100 A for 1 s Burden lt 0 1 VA Rated frequency fn 45 65 Hz Terminal block Maximum wire dimension Solid or stranded wire 4 mm 10 12 AWG 12 1 2 Auxiliary voltage Type A Type B Voltage range Vaux 40 265 V ac dc 18 36 Vdc Note Polarity X3 17 negative X3 18 positive Start up peak DC 110V 15A
18. caused output Al to and the output has been activate e g the START activated by one of the signal is reset The signals For more resetting depends on the information about output type of configuration matrix please see chapter connected or latched 2 4 5 Trip LED lit One or several signals of The LED is switched off the output relay matrix have when the signal that been assigned to output Tr caused output Tr to and the output has been activate e g the TRIP activated by one of the signal is reset The signals For more resetting depends on the information about output type of configuration relay configuration please connected or latched see chapter 2 4 5 A C LED lit Application related status Configurable indicators V265M EN M A004 2 Local panel user interface 2 1 Relay front panel V265M EN M A004 Resetting latched indicators and output relays All the indicators and output relays can be given a latching function in the configuration There are several ways to reset latched indicators and relays e From the alarm list move back to the initial display by pushing a for approx 3 s Then reset the latched indicators and output relays by pushing ox e Acknowledge each event in the alarm list one by one by pushing equivalent times Then in the initial display reset the latched indicators and output relays by pushing a The latched indicators and relays can also be reset via a remo
19. ccceeeeeeeeeeeeeeteeeeeeeeeeeeeeees 177 10 6 1 Trip circuit supervision with one digital input 177 10 6 2 Trip circuit supervision with DI19 and D120 183 T1 COonnectiOn Sisi iiaii aeaiiai aidaa 187 11 1 Rear panel view secs ites ted ete ols ree bads twee teed caditecsieteeccayen nude 187 11 2 Auxiliary voltage 2 0 0 e cece eeeeeeeceeeeeeeeeeeeeeneeeeeeeeeeeeeeeeees 191 11 3 Serial communication Connectors ceeeeeeeeeeeeeees 191 11 3 1 Front panel connector sc trceciss tecstves cotesweitecicentsncsenate 191 11 3 2 Rear panel connector X5 REMOTE e 192 11 3 3 X4 rear panel connector local RS232 and extension RS485 POMS icictccctathcteiedhaieteutiatetaia dete tela ctcesiad et eat 197 11 4 Optional two channel arc protection Card eeee 197 11 5 Optional digital I O card DI19 DI20 eee 198 11 6 External I O extension modules eceeeeeeeeeeeeeees 199 11 6 1 External LED module VAM 16D eeeeee 199 11 6 2 External input output module ceeeeeeeee 199 Ihs7 BlOGK didgraMS innranet 205 11 8 Block diagrams of option modules ccceeeeeeeeee 206 Table of Contents 11 8 1 Optional arc protection cccccceeeeeseeeeeeteeeeeeeees 206 11 8 2 Optional DI19 DI20 eeecceeeeeeeeeeeeeeeeeeeetteeeeeeeees 206 12 Technical data siiani iadaaa aiiai eiai tida kiribdi inaa 207 12 l
20. values using the keypad and the guidance given in the display Furthermore the keypad is used to control objects and switches on the single line diagram display The keypad is composed of four arrow keys one cancel key one enter key and one info key o Figure 2 1 3 1 Keys on the keypad Enter and confirmation key amp Cancel key E Up Down Increase Decrease arrow keys UP DOWN Keys for selecting submenus selecting a digit in a numerical value amp gt 5 Additional information key INFO _ e o N NOTE The term which is used for the buttons in this manual is inside the brackets 2 1 Relay front panel 2 Local panel user interface Operation Indicators The relay is provided with eight LED indicators CO Power C Error Com Alarm Trip OA C B Oc Figure 2 1 4 1 Operation indicators of the relay LED indicator Meaning Measure Remarks Power LED lit The auxiliary power has Normal operation state been switched on Error LED lit Internal fault operates in The relay attempts to parallel with the self reboot REBOOT If the supervision output relay error LED remains lit call for maintenance Com LED lit or The serial bus is in use and Normal operation state flashing transferring information Alarm LED lit One or several signals of The LED is switched off the output relay matrix have when the signal that been assigned to output LA
21. 0 0515 0 1140 0 02 VI Very inverse 19 61 0 491 2 El Extremely inverse 28 2 0 1217 2 STI Short time inverse 0 16758 0 11858 0 02 Short time extremely STEI averse 1 281 0 005 2 99 5 17 Inverse time operation 5 Protection functions Example for Delay type Moderately inverse Ml k 0 50 4 pu lpickup 2 pu A 0 0515 B 0 114 C 0 02 0 0515 3j sj The operation time in this example will be 1 9 seconds The same result can be read from Figure 5 17 1 8 ee IEEELTI gg IEEE LTVI 400 400 200 100 80 60 40 20 delay s delay s 0 2 0 1 0 08 0 06 0 06 i Bo LI AA core B0 20 1 2 3 4567810 20 T Iset inverseDelayIEEE1_LTI V Iset inverseDelayIEEE1_LTVI Figure 5 17 1 5 ANSI IEEE long time Figure 5 17 1 6 ANSI IEEE long time inverse delay very inverse delay 100 V265M EN M A004 5 Protection functions 5 17 Inverse time operation V265M EN M A004 600 400 200 100 80 60 40 20 Doo delay s 0 8 0 6 0 4 0 2 0 1 0 08 0 06 1 2 3 45678 10 20 TIset Figure 5 17 1 7 ANSI IEEE long time extremely inverse delay 600 400 200 100 60 40 20 delay s 0 2 0 1 0 08 0 06 1 2 3 45678 10 20 T Iset Figure 5 17 1 9 ANSI IEEE short time inverse delay IEEE LTEI inverseDelayIEEE1_LTEI IEEE STI inverseDelayIEEE1_STI IEEE MI 400 200 100 20 k 20
22. 1 2 There are three different delay types according IEC 60255 3 Normal inverse NI Extremely inverse El Very inverse VI and a VI extension Long time inverse LTI Table 5 17 1 2 Constants for IEC inverse delay equation Delay t Parameter elay type A B NI Normal inverse 0 14 0 02 El Extremely inverse 80 Vi Very inverse 13 5 1 LTI Long time inverse 120 1 Example for Delay type Normal inverse NI k 0 50 4 pu constant current lPickup E 2 pu A 0 14 B 0 02 T 0 50 0 14 50 0 02 o V265M EN M A004 97 5 17 Inverse time operation 5 Protection functions The operation time in this example will be 5 seconds The same result can be read from Figure 5 17 1 1 eo IEC NI S IEC EI 400 400 200 200 100 100 80 80 60 60 40 40 20 20 10 1 8 8 A 2 6 2 6 4 4 z Ey D D 2 2 0 8 0 8 0 6 0 6 04 04 k 2 k 1 0 2 0 2 oi og 006 0 06 0 05 f k 0 1 k 0 2 1 2 3 4 5678 10 20 1 2 3 4 5678 10 20 TIset inverseDelayIEC_NI T Iset inverseDelayIEC_EI Figure 5 17 1 1 IEC normal inverse Figure 5 17 1 2 IEC extremely inverse delay delay ae IEEE VI ae IEC LTI 400 400 200 200 k 20 100 100 80 80 k 10 60 60 40 40 k 20 20 k 2 10 10 PEI 8 1 v 6 z 6 4 A k 0 5 2 B 2 k 0 2 4 1
23. 135 8 Control functions jescwcoisineiciinisscrvtcnaeinatatdaniewniuinateieneraanden 139 8 1 Output FOIAY S i dssic ices sreteidenbehes saealobdtebedeidaveedebniebebaeaaeads 139 O72 Digital HPUIS aee a ees ats core Ee aE E EEEE a iA TA 140 8 3 Virtual inputs and OUtDUIS cece cece eeeeetteeeeeeeeeeeeeee 142 8 4 Output matrix e eee cece eee eceeeeee eee eeeeeeeeeaaeeeeeeeeeeeeeeee 143 8 97 IOC V AU Naess tes cas Cacesuet edicts dave rees Colisuaddints ceeetenuweds 144 8 6 Controllable Obje CtS ccceccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeees 145 8 6 1 Local Remote Selection cceeeeeeeeeeeeeeeeeeeees 147 8 7 LOGIC UNCION S scsi csdetncs coeds aeaa e AEAEE ARTEAN TEAR 147 9 COMMUNICATION vevvcicscivsssisnesaciniivevoniniieawaniveineneenncunanieens 148 9 1 Communication ports ccccceeeeeeeeeeeeeeeeeeneeeeeeeeeeeeeee 148 also OCA ON OAS 2 cis cee cats cess toda ceed e E 149 9 1 2 Remote port AS x 8 iiate nds let a hicndd lta dendecmedeubliae tthe 151 V265M EN M A004 Table of Contents V265M EN M A004 Plate Extension DOU AA a 152 9 1 4 Ethernet DOLLA eMac eh fee ae ah eA hed Ate Ae 153 9 2 Communication protocols cccceeeeeeeeeeeeteeeeeeeeeeeeees 154 9 2 1 PC communication wiscteesncstehetnetelnatatnatiets 154 9 2 2 Modbus TCP and Modbus RTU eeeeees 154 Pesos Profibus BP cali cnaplinion vata ntevntscidy a 155 Del Ac RAE AOU Sissies iasbica ae eae aaa
24. 48 V dc Number of binary outputs 1 transistor controlled Operating voltage level 48 V dc NOTE Maximally three arc binary inputs can be connected to one arc binary output without an external amplifier 12 2 Tests and environmental conditions 12 2 1 Disturbance tests Emission EN 50081 1 Conducted EN 55022B 0 15 30 MHz Emitted CISPR 11 30 1 000 MHz Immunity EN 50082 2 Static discharge ESD EN 61000 4 2 class III 6 kV contact discharge 8 kV air discharge Fast transients EFT EN 61000 4 4 class III 2 kV 5 50 ns 5 kHz Surge EN 61000 4 5 class III 2 KV 1 2 50 us common mode 1 kV 1 2 50 us differential mode Conducted HF field EN 61000 4 6 0 15 80 MHz 10 V Emitted HF field EN 61000 4 3 80 1000 MHz 10 V m GSM test ENV 50204 900 MHz 10 V m pulse modulated V265M EN M A004 209 12 2 Tests and environmental 12 Technical data conditions 12 2 2 Test voltages Insulation test voltage IEC 60255 5 2 kV 50 Hz 1 min Class III Surge voltage IEC 60255 5 5 kV 1 2 50 us 0 5 J Class III 12 2 3 Mechanical tests Vibration IEC 60255 21 1 10 60 Hz amplitude 0 035 mm Class 60 150 Hz acceleration 0 5g sweep rate 1 octave min 20 periods in X Y and Z axis direction Shock IEC 60255 21 1 half sine acceleration 5 g duration 11 ms Class 3
25. 5 17 IEEE Set IEEE2 Pre 1996 RI PrgN Type Delay type DT Definite time NI Inverse time See chapter 5 17 Vi Set El LTI Paramet ers t gt s Definite operation time for Set definite time only k gt Inverse delay multiplier for Set inverse time only Dly20x s Delay at 20xlset Dly4x S Delay at 4xlset Dly2x s Delay at 2xlset Dly1x s Delay at 1xlset IncHarm On off Include Harmonics Set Delay Graphic delay curve picture curves A B C D User s constants for standard E equations Type Parameters See chapter 5 17 Recorded LOG1 Date and time of trip values Type Fault type Fit xlmot Fault current Load xlmot Pre fault current Edly Elapsed delay time SetGrp Active set group during fault For details of setting ranges see chapter 12 3 Set An editable parameter password needed C Can be cleared to zero F Editable when force flag is on 61 5 6 Overcurrent protection I gt 50 51 5 Protection functions Parameters of the overcurrent stages I gt gt I gt gt 50 51 Parameter Value Unit Description Note Status Current status of the stage Blocked Start F Trip F SCnir Cumulative start counter C TCntr Cumulative trip counter C SetGrp 1or2 Active setting group Set SGrpDI Digital signal to select the active Set setting group None Dix Digital input Vix Virtual input LEDx LED indicator signal VOx Virtual output Force Off Force flag for status forcing f
26. 641 Errors since the device has Clr restarted or since last clearing Tout Ogg Timeout errors since the Clr device has restarted or since last clearing Set An editable parameter password needed Clr Clearing to zero is possible 1 The communication parameters are set in the protocol specific menus For the local port command line interface the parameters are set in configuration menu V265M EN M A004 9 Communication 9 1 Communication ports 9 1 2 V265M EN M A004 Remote port X5 Physical interface The physical interface of this port depends of the communication letter in the order code See Figure 9 1 1 chapter 11 and the table below The TTL interface is for external converters and converter cables only It is not suitable for direct connection to distances more than one meter Parameters Parameter Value Unit Description Note Protocol Protocol selection for Set remote port None SPA bus SPA bus slave ProfibusDP Profibus DB slave ModbusSla Modbus RTU slave ModbusT CPs Modbus TCP slave IEC 103 IEC 60870 5 103 slave ExternallO Modbus RTU master for external I O modules DNP3 DNP 3 0 Msg 0 29 1 Message counter since the Clr device has restarted or since last clearing Errors oap 4 Protocol errors since the Cir device has restarted or since last clearing Tout o 2 61 Timeout errors since the Cir device has restarted or since last clearing Disp
27. Binary input of the arc card 48 Vdc e S1 BI Light sensor S1 or the binary input e S2 Bl Light sensor S2 or the binary input e 1 S2 Bl Light sensor S1 or S2 or the binary input Binary input The binary input BI on the arc option card see chapter 11 4 can be used to get the light indication from another relay to build selective arc protection systems The BI signal can also be connected to any of the output relays BO indicators etc offered by the output matrix See chapter 8 4 BI is a dry input for 48 Vdc signal from binary outputs of other VAMP relays or dedicated arc protection devices by VAMP Binary output The binary output BO on the arc option card see chapters 11 4 and 11 5 can be used to give the light indication signal or any other signal or signals to another relay s binary input to build 87 5 15 Arc fault protection 50ARC 50NARC optional 5 Protection functions 88 selective arc protection systems Selection of the BO connected signal s is done with the output matrix See chapter 8 4 BO is an internally wetted 48 Vdc signal for BI of other VAMP relays or dedicated arc protection devices by VAMP Delayed light indication signal There is a delayed light indication output signal available for building selective arc protection systems Any light source combination and a delay can be configured The resulting signal is available in the output matrix to be connected to BO output relays etc
28. C Can be cleared to zero F Editable when force flag is on V265M EN M A004 75 5 10 Earth fault protection 10 gt 50N 51N 5 Protection functions Parameters of the undirectional earth fault stages lo gt gt lo gt gt gt lo gt gt gt gt 50N 51N Parameter Value Unit Description Note Status Current status of the stage Blocked Start F Trip F TripTime Ss Estimated time to trip SCnir Cumulative start counter Clr TCntr Cumulative trip counter Clr SetGrp 1 or2 Active setting group Set SGrpDI Digital signal to select the active setting group None Dix Digital input Set VIX Virtual input LEDx LED indicator signal VOx Virtual output Force Off Force flag for status forcing for Set On test purposes This is a common flag for all stages and output relays too Automatically reset by a 5 minute timeout lo pu The supervised value according lo2 the parameter Input below loCalc lo gt gt A Pick up value scaled to primary lo gt gt gt value lo gt gt gt gt lo gt gt pu Pick up setting relative to the Set lo gt gt gt parameter Input and the ose corresponding CT value t gt s Definite operation time for Set definite time only Input lo1 X1 7 amp 8 See chapter 11 lo2 X1 9 amp 10 loCalc IL1 IL2 IL3 Set oCalc PL1 PL2 l L3 For details of setting ranges see chapter 12 3 Set An editable parameter password needed C Can be cleared
29. EN M A004 5 Protection functions 5 7 Stall protection IST gt 48 Istlohko Start Register event Register event Motor nom Delay Definite inverse Inverse delay Enable events start current time Figure 5 7 2 Block diagram of the stall protection stage lsr gt Parameters of the stall protection stage Ist gt 48 Parameter Value unit Description Status Status Status of the stage SCnitr Cumulative start counter TCnir Cumulative trip counter Force ON Off Force flag for status forcing for test purposes This is a common flag for all stages and output relays too This flag is automatically reset 5 minutes after the last front panel push button pressing Parameters Il A Phase current IL not settable Status Status of stage Ist gt A Motor start detection current scaled to primary value calculated by relay Ist gt xlmot Motor start detection current Must be less than initial motor starting current ImotSt A Nominal motor starting current scaled to primary value calculated by relay ImotSt xlmot Nominal motor starting current Type DT Operation charact definite time Inv Operation charact inverse time t gt S Operation time s tInv gt S Time multiplier at inverse time Recorded Log Start and trip time values Fit xlmot Maximum fault current EDly Elapsed time of the operating time setting 100 trip V265M EN M A004 65
30. M A004 9 Communication 9 2 Communication protocols V265M EN M A004 EtherNet IP main configuration parameters Parameter Range Description IP address IP protocol address identifing device in the network Multicast IP Multicast IP address used for sending IO messages Multicast TTL 1 100 Time to live of the IO messages sent to multicast address Vendor ID 1 65535 Identification of a vendor by number Device Type 0 65535 Indication of general type of product Product Code 1 65535 Identification of a particular product of an individual vendor Major Revision 1 127 Major revision of the item the Identity Object represents Minor Revision 1 255 Minor revision of the item the Identity Object represents Serial Number 0 4294967295 Serial number of device Product Name 32 chars Human readable identification Producing Instance 1 1278 Instance number of producing assembly Include Run Idle On Off Include or exlude Run Idle Header Producing Header in an outgoing IO messages Consuming 1 1278 Instance number of consuming Instance assembly Include Run Idle On Off Expect presence or absence of Header Consuming Run Idle Header in an incoming IO messages 165 10 1 Restricted earth fault protection 10 Applications 10 10 1 166 Applications Restricted earth fault protection Restricted earth fault REF protection is a sensitive way to p
31. Off On CT supervisor on event CT off On Off On CT supervisor off event Measured and recorded values of CT CT supervisor CTSV Parameter Value Unit Description Measured ILmax A Maximum of phase currents value ILmin A Minimum of phase currents Display Imax gt A Setting values as primary Imine values Recorded Date Date of CT supervision values alarm Time Time of CT supervision alarm Imax A Maximum phase current Imin A Minimum phase current 115 6 4 Circuit breaker condition monitoring 6 Supporting functions 6 4 116 Circuit breaker condition monitoring The relay has a condition monitoring function that supervises the wearing of the circuit breaker The condition monitoring can give alarm for the need of CB maintenance well before the CB condition is critical The CB wear function measures the breaking current of each CB pole separately and then estimates the wearing of the CB accordingly the permissible cycle diagram The breaking current is registered when the trip relay supervised by the circuit breaker failure protection CBFP is activated See chapter 5 14 for CBFP and the setting parameter CBrelay Breaker curve and its approximation The permissible cycle diagram is usually available in the documentation of the CB manufacturer Figure 6 4 1 The diagram specifies the permissible number of cycles for every level of the breaking current This diagram is parameterised to the condi
32. S1 7 G 9 lo2 Residual current lo2 S1 9 3 11 L1 Phase current I L1 S1 low voltage side 11 g 13 IrL2 Phase current I L2 S1 low voltage side 13 Ss 15 IPL3 Phase current I L3 S1 low voltage side 15 B 17 17 B 19 19 R o Terminal X1 right side No Symbol Description aD 5 2 IL1 Phase current L1 S2 high voltage side IS 4 IL2 Phase current L2 S2 high voltage side 5 a 6 IL3 Phase current L3 S2 high voltage side 2 6 Ig lo1 Residual current lo1 S2 E 8 10 102 Residual current lo2 S2 10 12 rL1 Phase current I L1 S2 low voltage side 12 14 PL2 Phase current I L2 S2 low voltage side X 14 16 PL3 Phase current l L3 S2 low voltage side amp 16 18 D J18 20 oe G2 20 o 188 V265M EN M A004 11 Connections 11 1 Rear panel view Terminal X2 without the analogue output No Symbol Description 1l S J ics i all 2l a ail ees 2 4l 4 I E 5 5 A5 Alarm relay 5 6 6 A5 Alarm relay 5 7 S 7 A4 Alarm relay 4 8 8 A4 Alarm relay 4 all ee ale a 10 Ze 10 A3 COM Alarm relay 3 common connector Fs S 11 A3 NC Alarm relay 3 normal closed connector 49 ea 12 A3NO Alarm relay 3 normal open connector 13 A2 COM Alarm relay 2 common connector 13 1
33. The scaling is done using the given CT and transformer generator name plate values The following scaling equations are useful when doing secondary testing Current scaling NOTE The rated value of the relay s current input 5 A and 1A does not have any effect in the scaling equations but it defines the measurement range and the maximum allowed continuous current See chapter 12 1 1 for details Primary and secondary scaling Current scaling _ CT pri secondary gt primary I pe Lsnc CT src 2 CT src primary secondary Lsge Lpr gt CT pri For residual currents to inputs Io or lo2 use the corresponding CTpri and CTgec values For earth fault stages using locaic Signals use the phase current CT values for CTpri and CTsec Example 1 Secondary to primary CT 500 5 Current to the relay s input is 4 A Primary current is IprRi 4x500 5 400 A Example 2 Primary to secondary CT 500 5 The relay displays lpr 400 A gt Injected current is Ilsec 400x5 500 4 A 135 7 7 Primary secondary and per unit 7 Measurement functions scaling 136 Per unit pu scaling For phase currents excluding Arcl gt stage 1 pu 1xln 100 where In is the rated current of the transformer The rated current for high voltage side HV and low voltages side LV are calculated by the device itself using Equation 7 7 1 1 Equation 7 7 1 1 Sy N B Uy Where In Th
34. Unit Description Note Runh 0 876000 h Total active time hours Set Note The label text Runh can be edited with VAMPSET 0 3599 Ss Total active time seconds Set Starts 0 65535 Activation counter Set Status Stop Current status of the selected Run digital signal DI Select the supervised signal Set None DI1 DI6 Physical inputs VI1 VI4 Virtual inputs LedAl Output matrix out signal Al LedTr Output matrix out signal Tr LedA Output matrix out signal LA LedB Output matrix out signal LB LedC Output matrix out signal LC LedDR Output matrix out signal DR VO1 VO6 Virtual outputs Started at Date and time of the last activation Stopped at Date and time of the last inactivation Set An editable parameter password needed Set An informative value which can be edited as well 124 V265M EN M A004 6 Supporting functions 6 7 Timers 6 7 Timers The VAMP protection platform includes four settable timers that can be used together with the user s programmable logic or to control setting groups and other applications that require actions based on calendar time Each timer has its own settings The selected on time and off time is set and then the activation of the timer can be set to be as daily or according the day of week See the setting parameters for details The timer outputs are available for logic functions and for the block and output matrix not in use Day sh en
35. and off every Friday Saturday The timer switches on and off every Saturday Sunday The timer switches on and off every Sunday MTWTF The timer switches on and off every day except Saturdays and Sundays MTWTFS The timer switches on and off every day except Sundays SatSun The timer switches on and off every Saturday and Sunday V265M EN M A004 6 Supporting functions 6 8 Combined overcurrent status 6 8 V265M EN M A004 Line fault parameters Combined overcurrent status This function is collecting faults fault types and registered fault currents of all enabled overcurrent stages Parameter Value Unit Description Note IFitLas X N Current of the latest overcurrent fault Set LINE ALARM AlrL1 AlrL2 AlrL3 Start alarm status for each phase O No start since alarm ClrDly 1 Start is on OCs Combined overcurrent start status AlrL1 AlrL2 AlrL3 0 AlrL1 1 orAlrL2 1 or AlrL3 1 LxAlarm On Event enabling for AlrL1 3 Events are enabled Events are disabled Set LxAlarm Off Off Event enabling for AlrL1 3 Events are enabled Events are disabled Set OCAlarm Off On Event enabling for combined o c starts Events are enabled Events are disabled Set OCAlarmOff On Off Off Event enabling for combined o c starts Events are enabled Events are disabled Set IncFltEvnt Off
36. event register can be read from the Evnt submenu 1 Push once 2 The EVENT LIST appears The display contains a list of all the events that have been configured to be included in the event register event_list EVENT LIST 44v Code 71E10 CB open timeout 2002 02 15 00 17 37 530 Figure 2 3 3 1 Example of an event register 3 Scroll through the event list with and v 4 Exitthe event list by pushing g It is possible to set the order in which the events are sorted If the Order parameter is set to New Old then the first event in the EVENT LIST is the most recent event V265M EN M A004 2 Local panel user interface 2 3 Operating measures 2 3 4 V265M EN M A004 Forced control Force In some menus it is possible to switch a signal on and off by using a force function This feature can be used for instance for testing a certain function The force function can be activated as follows 1 Move to the setting state of the desired function for example DO see Chapter 2 4 2 Select the Force function the background color of the force text is black force Pick RELAY OUTPUTS 1 Enable forcing Figure 2 3 4 1 Selecting Force function 3 Push Oa 4 Push or to change the OFF text to ON that is to activate the Force function 5 Push to return to the selection list Choose the signal to be controlled by force with and v for instance the T1 signal 6 Push to confi
37. for all stages and output relays too Automatically reset by a 5 minute timeout I2 In lIn The supervised value 12 gt ln Pick up setting Set t gt s Definite operation time Set Type DT Type DT Definite time Set INV Inverse time Equation K1 s Delay multiplier Type INV Set For details of setting ranges see chapter 12 3 Set An editable parameter password needed C Can be cleared to zero F Editable when force flag is on Recorded values of the latest eight faults There is detailed information available of the eight latest faults Time stamp unbalance current elapsed delay and setting group Recorded values of the current unbalance stage 8 latest faults 12 gt l 2 gt 46 Parameter Value Unit Description yyyy mm dd Time stamp of the recording date hh mm ss ms Time stamp time of day Fit ln Maximum unbalance current EDly Elapsed time of the operating time setting 100 trip SetGrp 1 Active setting group during the fault 71 5 10 Earth fault protection 10 gt 5 Protection functions 50N 51N 5 10 Earth fault protection lo gt 50N 51N Undirectional earth fault protection is used for earth faults in low impedance earthed networks In high impedance earthed networks compensated networks and isolated networks undirectional earth fault can be used as back up protection The undirectional earth fault function is sensitive to the fundamental freque
38. group parameters The changing of the setting parameters can be done easily When the desired submenu has been found with the arrow keys press to select the submenu Now the selected setting group is indicated in the down left corner of the display See Figure 2 2 3 2 Seti is setting group one and Set2 is setting group two When the needed changes to the selected setting group have been done press or to select another group amp is used when the active setting group is 2 and is used when the active setting group is 1 group2 SET I gt Setting for stage I gt ILmax Status I gt Figure 2 2 3 2 Example of I gt setting submenu 21 2 2 Local panel operations 2 Local panel user interface 2 2 4 Fault logs All the protection functions include fault logs The fault log of a function can register up to eight different faults with time stamp information fault values etc Each function has its own logs See Figure 2 2 4 1 log AV lt p I gt log buffer Log buffer 1 2003 04 28 11 11 52 251 1 2 0 55 xin 0 02 xin Figure 2 2 4 1 Example of fault log To see the values of for example log two press to select the current log log one The current log number is then indicated in the down left corner of the display See Figure 2 2 4 2 Log2 log two The log two is selected by pressing once log2 I gt log buffer Date 03 08 21 342 Log2 I gt Figure 2 2 4 2 Example of select
39. is not galvanically isolated Optional card NOTE When this option two channel arc protection card is installed the parameter Arc card type has value 2Arc BI O Please check the ordering code in chapter 15 NOTE If the slot X6 is already occupied with the DI19 DI20 digital input card this option is not available See c available but there is still one arc sensor channel hapter 11 5 The optional arc protection card includes two arc sensor channels The arc sensors are connected to terminals X6 4 5 and 6 7 The arc information can be transmitted and or received through digital input and output channels This is a 48 V dc signal Connections X6 1 X6 2 X6 3 X6 4 5 X6 6 7 Binary input BI Binary output BO Common for BI and BO Sensor 1 Sensor 2 The binary output of the arc option card may be activated by the arc sensors or binary output c by any available signal in the output matrix The an be connected to an arc binary input of another VAMP protection relay or manager 197 11 5 Optional digital I O card 11 Connections DI19 D120 11 5 Optional digital I O card DI19 DI20 NOTE When this option card is installed the parameter Arc card type has value Arc 2DI With DI19 DI20 option only one arc sensor channel is available Please check the ordering code in chapter 15 NOTE If the slot X6 is already occupied with the two channel arc sensor card chapter 11 4 this option i
40. level the password can contain four digits The digits are supplied one by one by first moving to the position of the digit using and then setting the desired digit value using f 3 Push o Password handling The passwords can only be changed using VAMPSET software connected to the local RS 232 port on the relay It is possible to restore the password s in case the password is lost or forgotten In order to restore the password s a relay program is needed The serial port settings are 38400 bps 8 data bits no parity and one stop bit The bit rate is configurable via the front panel Command Description get pwd_break Get the break code Example 6569403 get serno Get the serial number of the relay Example 12345 Send both the numbers to your nearest Schneider Electric Customer Care Centre and ask for a password break A device specific break code is sent back to you That code will be valid for the next two weeks Command Description set pwd_break 4435876 Restore the factory default passwords 4435876 is just an example The actual code should be asked from your nearest Schneider Electric Customer Care Centre Now the passwords are restored to the default values See chapter 2 2 5 V265M EN M A004 2 Local panel user interface 2 3 Operating measures 2 3 2 3 1 V265M EN M A004 Operating measures Control functions The default display of the local p
41. level is at least Operator e TCnitr 1 The stage has tripped two times since the last reset of restart This value can be cleared if the operating level is at least Operator e SetGrp 1 The active setting group is one This value can be edited if the operating level is at least Operator Setting groups are explained in chapter 2 2 3 e SGrpDI The setting group is not controlled by any digital input This value can be edited if the operating level is at least Configurator e Force Off The status forcing and output relay forcing is disabled This force flag status can be set to On or back to Off if the operating level is at least Configurator If no front panel V265M EN M A004 2 Local panel user interface 2 2 Local panel operations V265M EN M A004 button is pressed within five minutes and there is no VAMPSET communication the force flag will be set to Off position The forcing is explained in chapter 2 3 4 Second menu of I gt gt 50 51 stage second menu AV lt gt I gt gt SET 50 51 Stage setting group 1 ExDI ILmax 403A ExDO Status Prot gt gt 1013A gt gt 2 50xin t gt gt 0 60s Figure 2 2 2 2 Second menu next on the right of gt gt 50 51 stage This is the main setting menu The content is e Stage setting group 1 These are the group 1 setting values The other setting group can be seen by pressing push and then or lt Setting groups are exp
42. ms Reset time lt 95 ms Retardation time lt 50 ms Reset ratio 0 97 Transient over reach any t lt 10 Inaccuracy Starting Operation time 3 of the set value or 5 mA secondary 1 or 25 ms This is the instantaneous time i e the minimum total operational time including the fault detection time and operation time of the trip contacts Thermal overload stage T gt 49 Overload factor Alarm setting range Time constant Tau Cooling time coefficient Max overload at 40 C Max overload at 70 C Ambient temperature Resetting ratio Start amp trip Accuracy operating time 0 1 2 40 x Imot or In Step 0 01 60 99 step 1 2 180 min step 1 1 0 10 0 xTau step 0 1 70 120 lmot step 1 50 100 lmo Step 1 55 125 C step 1 0 95 5 or 15 Unbalance stage l2 gt I 2 gt 46 Setting range Definite time characteristic operating time Inverse time characteristic 1 characteristic curve time multiplier K Upper limit for inverse time Start time Reset time Reset ratio Inaccuracy Starting Operate time 2 70 step 1 1 0 600 0s s step 0 1 Inv 1 50 s step 1 1000s Typically 300 ms lt 450 ms 0 95 1 unit 5 or 200 ms Stage is operational when all secondary currents are above 250 mA V265M EN M A004 12 Technical data 12 3 Protection f
43. not directly editable Editing is done in the appropriate protocol setting menus The counters are useful when testing the communication LOCAL PORT X4 pins 2 3 and 5 This port is disabled if a cable is connected to the front panel connector e Communication protocol for the local port X4 Protocol For VAMPSET use None or SPABUS e Message counter Msg This can be used to verify that the device is receiving messages e Communication error counter Errors e Communication time out error counter Tout e Information of bit rate data bits parity stop bits This value is not directly editable Editing is done in the appropriate protocol setting menus For VAMPSET and protocol None the setting is done in menu CONF DEVICE SETUP PC LOCAL SPA BUS This is a second menu for local port X4 The VAMPSET communication status is showed e Message counter Msg This can be used to verify that the device is receiving messages e Communication error counter Errors e Communication time out error counter Tout e Same information as in the previous menu 37 2 4 Configuration and parameter 2 Local panel user interface setting EXTENSION PORT X4 pins 7 8 and 5 e Communication protocol for extension port X4 Protocol e Message counter Msg This can be used to verify that the device is receiving messages e Communication error counter Errors e Communication time out error counter Tout e Inform
44. options are shown in Figure 11 3 2 1 The connector types are listed in Table 11 3 2 1 Without any internal options X5 is a TTL port for external converters Some external converters VSE are attached directly to the rear panel and X5 Some other types VEA VPA need various TTL RS 232 converter cables The available accessories are listed in chapter 15 order information 2 amp 4 wire galvanically isolated RS 485 Figure 11 3 2 2 Internal options for fibre optic Figure 11 3 2 3 and Profibus Figure 11 3 2 4 are available See chapter 15 order information Table 11 3 2 1 Physical interface and connector types of remote port X5 with various options Serial interface A is the default Order Communication interface Connector Pin usage Code type A Serial interface for external D9S 1 reserved converters only REMOTE 2 TX_out TTL port 3 RX_in TTL 4 RTS out TTL 7 GND 9 8V out B Plastic fibre interface HFBR 0500 REMOTE port C Profibus interface D9S 3 RXD TXD P REMOTE port 4 RTS 5 GND 6 5V 8 RXD TXD N D RS 485 isolated REMOTE screw terminal 1 Signal ground port 2 Reciever 3 Reciever 4 Transmitter 5 Transmitter E Glass fibre interface ST 62 5 125 um REMOTE port F Plastic glass 62 5 125 HFBR 0500 ST Plastic Rx um fibre interface Glass Tx REMOTE port G Glass 62 5 125 um ST HFBR 0500 Glass Rx plastic fibre interface Plastic
45. password is not required for a remote control operation 8 7 Logic functions The relay supports customer defined programmable logic for boolean signals The logic is designed by using the VAMPSET setting tool and downloaded to the relay Functions available are AND OR XOR NOT COUNTERs RS amp D flip flops Maximum number of outputs is 20 Maximum number of input gates is 31 An input gate can include any number of inputs For detailed information please refer to the VAMPSET manual VVAMPSET EN M xxxx V265M EN M A004 147 9 1 Communication ports 9 Communication 9 9 1 148 Communication Communication ports The relay has three communication ports as standard A fourth port Ethernet is available as option See Figure 9 1 1 There are three communication ports in the rear panel The Ethernet port is optional The X4 connector includes two ports local port and extension port The front panel RS 232 port will shut off the local port on the rear panel when a VX003 cable is inserted COMMUNICATION PORTS LOCAL EXTENSION REMOTE PORT PORT DATA BUS PORT Default TTL for external adapters only i REMOTE Not isolated TTL is for external adapters only g Options Z RS 485 isolated A Fibre optic 2 Profibus X5 Ethernet and TTL S e FRONT PANEL Figure 9 1 1 Communication ports and connectors By default the X5 is a D9S type connector wi
46. secondary circuits first Failure to follow these instructions can result in death serious injury or equipment damage 8 V265M EN M A004 2 Local panel user interface 2 1 Relay front panel 2 1 V265M EN M A004 Local panel user interface Relay front panel The figure below shows as an example the front panel of the relay VAMP 265M and the location of the user interface elements used for local control Schneider VAMP ectri Figure 2 1 1 The front panel of VAMP 265M 1 LCD dot matrix display 2 Keypad 3 4 RS 232 serial communication port for PC LED indicators 2 1 Relay front panel 2 Local panel user interface 2 1 1 10 Display The relay is provided with a back lighted 128x64 LCD dot matrix display The display enables showing 21 characters in one row and eight rows at the same time The display has two different purposes one is to show the single line diagram of the relay with the object status measurement values identification etc Figure 2 1 1 1 The other purpose is to show the configuration and parameterization values of the relay Figure 2 1 1 2 VAMP265ski Figure 2 1 1 1 Sections of the LCD dot matrix display Freely configurable single line diagram Five controllable objects Six object statuses Bay identification Local Remote selection Auto reclose on off selection if applicable Freely selectable measurement
47. selected S1 Sensor 1 at terminals X6 4 5 S2 Sensor 2 at terminals X6 6 7 1 S2 Bl Terminals X6 1 3 1 Bl 2 Bl 1 S2 Bl Delayed light signal output Ldly s Delay for delayed light output Set signal LdlyCn Light indication source selection Set 5 No sensor selected S1 Sensor 1 at terminals X6 4 5 S2 Sensor 2 at terminals X6 6 7 1 S2 Bl Terminals X6 1 3 1 Bl 2 Bl 1 S2 Bl For details of setting ranges see chapter 12 3 Set An editable parameter password needed V265M EN M A004 89 5 15 Arc fault protection 50ARC 50NARC optional 5 Protection functions 90 C Can be cleared to zero F Editable when force flag is on Recorded values of the latest eight faults There are detailed information available of the eight latest faults Time stamp fault type fault value load current before the fault and elapsed delay Recorded values of the arc protection stages Arcl gt Arcl gt Arcloi gt Arclo2 gt SOARC 50NARC Parameter Value Unit Description yyyy mm dd Time stamp of the recording date hh mm ss ms Time stamp time of day Type pu Fault type value Only for Arcl gt stage Fit pu Fault value Load pu Pre fault current Only for Arcl gt stage EDly Elapsed time of the operating time setting 100 trip V265M EN M A004 5 Protection functions 5 16 Programmable stages 99 5 16 V265M EN M A004 Programmable stages 99 For special app
48. shocks in X Y and Z axis direction 12 2 4 Environmental conditions Operating temperature 10 to 55 C Transport and storage temperature 40 to 70 C Relative humidity lt 75 1 year average value lt 90 30 days per year no condensation permitted 12 2 5 Casing Degree of protection IEC 60529 IP20 Dimensions W x H x D 208 x 155 x 225 mm 8 19 x 6 10 x 8 86 in Material 1 mm 0 04 in steel plate Weight 4 2 kg Colour code RAL 7032 Casing RAL 7035 Back plate 12 2 6 Package Dimensions W x H x D 215 x 160 x 275 mm 8 46 x 6 30 x 10 83 in Weight Terminal Package and Manual 5 2 kg 210 V265M EN M A004 12 Technical data 12 3 Protection functions 12 3 Protection functions 12 3 1 Differential protection Differential overcurrent stage Al gt 87 Setting range 5 50 In Bias current for start of slope 1 0 50 x In Slope 1 5 100 Bias current for start of slope 2 1 00 3 00 x In Slope 2 100 200 Second harmonic blocking 5 30 or disable Reset time lt 95 ms Reset ratio 0 95 Inaccuracy 2 harmonic blocking 1 unit Starting 3 of set value or 0 02 x In when currents are gt 200 mA Operating time l4 gt 1 2 x Iser lt 60 ms Operating time l4 gt 3 5 X Iser lt 50 ms Differential overcurrent stage Al gt gt 87 Setting range 5 0 40 0 x In Reset time lt 95 ms Reset ratio 0 95 Inaccuracy
49. the latest VAMPSET exe from our web For more information about the VAMPSET software please refer to the user s manual with the code VVAMPSET EN M xxxx Also the VAMPSET user s manual is available at our web site V265M EN M A004 4 Introduction V265M EN M A004 Introduction The numerical VAMP differential protection include all the essential protection functions needed to protect asynchronous and synchronous motors for industry power plants and offshore applications including motor and generator differential protection Further the device includes several programmable functions such as arc option circuit breaker protection and communication protocols for various protection and communication situations The generator and motor differential protection relay VAMP 265M can be used for selective differential overcurrent short circuit protection of generators and motors in solidly or impedance earthed power systems The relay can also be used for single two or three phase overcurrent and or sensitive earth fault protection 43 4 1 Main features 4 Introduction 4 1 44 Main features The main features of VAMP 265M are Fully digital signal handling with a 16 bit microprocessor and high measuring accuracy on all the setting ranges due to an accurate 16 bit A D conversion technique Wide setting ranges for the protection functions e g the earth fault protection can reach a sensitivity of 0 5 The device ca
50. the old delay type doesn t exist in the new category See chapter 5 17 for more details Limitations The minimum definite time delay start latest when the measured value is twenty times the setting However there are limitations at high setting values due to the measurement range See chapter 5 17 for more details Table 5 17 1 1 Available standard delay families and the available delay types within each family Curve family Ee jo W mw Delay type oO uw m w DT Definite time X NI1 Normal inverse X X VI Very inverse X X X El Extremely inverse X X X LTI Long time inverse X X LTEI Long time extremely inverse X LTVI Long time very inverse X MI Moderately inverse X X STI Short time inverse X STEI Short time extremely inverse X RI Old ASEA type X RXIDG Old ASEA type X V265M EN M A004 5 Protection functions 5 17 Inverse time operation IEC inverse time operation The operation time depends on the measured value and other parameters according Equation 5 17 1 1 Actually this equation can only be used to draw graphs or when the measured value is constant during the fault A modified version is implemented in the relay for real time usage Equation 5 17 1 1 kA I B L picti T t Operation delay in seconds k User s multiplier Measured value IPickup User s pick up setting A B Constants parameters according Table 5 17
51. to zero F Editable when force flag is on Recorded values of the latest eight faults There is detailed information available of the eight latest earth faults Time stamp fault current elapsed delay and setting group 76 V265M EN M A004 5 Protection functions 5 10 Earth fault protection 10 gt 50N 51N V265M EN M A004 Recorded values of the undirectional earth fault stages 8 latest faults lo gt lo gt gt lo gt gt gt lo gt gt gt gt 50N 51N Parameter Value Unit Description yyyy mm dd Time stamp of the recording date hh mm ss ms Time stamp time of day Fit pu Maximum earth fault current EDly Elapsed time of the operating time setting 100 trip SetGrp 1 Active setting group during fault 77 5 11 Thermal overload protection T gt 5 Protection functions 49 5 11 78 Thermal overload protection T gt 49 The thermal overload function protects the transformer against excessive temperatures Thermal model The temperature is calculated using rms values of phase currents and a thermal model according IEC 60255 8 The rms values is calculated using harmonic components up to the 15 Trip time ae i t t In I a Alarm a k ky Tyope Valarm Alarm 60 0 6 Trip id cael ae eee Release time 1 t T C In a I Trip release g 0 95 x ko x Ione Start release 4q 0 95 x ko x Iopp x Valarm Alarm 60 0 6 T
52. ty dl Mody Tuesday U Wednesday a E Ln aaa Thusdy aaa a a U S Fiddy S U aaa Saturday aaa a a a a Sudy aaa aaa a a a a a Mints a G ake Le G Ss MIWES Lf af ee a SatSun U U Figure 6 7 1 Timer output sequence in different modes The user can force any timer which is in use on or off The forcing is done by writing a new status value No forcing flag is needed as in forcing i e the output relays The forced time is valid until the next forcing or until the next reversing timed act from the timer itself The status of each timer is stored in non volatile memory when the auxiliary power is switched off At start up the status of each timer is recovered V265M EN M A004 125 6 7 Timers 6 Supporting functions 126 Setting parameters of timers Parameter Value Description TimerN Timer status Not in use 0 Output is inactive 1 Output is active On hh mm ss Activation time of the timer Off hh mm ss De activation time of the timer Mode For each four timers there are 12 different modes available n The timer is off and not running The output is off i e O all the time Daily The timer switches on and off once every day Monday The timer switches on and off every Monday Tuesday The timer switches on and off every Tuesday Wednesday The timer switches on and off every Wednesday Thursday The timer switches on and off every Thursday Friday The timer switches on
53. with VAMPSET or local panel and there is temporarily an illegal combination of curve delay points For example if previous settings were IEC NI and then curve family is changed to IEEE the setting error will active because there is no NI type available for IEEE curves After changing valid delay type for IEEE mode for example Ml the Setting Error signal will release e There are errors in formula parameters A E and the device is not able to build the delay curve e There are errors in the programmable curve configuration and the device is not able to interpolate values between the given points Limitation The maximum measured phase current is 50Xin and the maximum directly measured earth fault current is 5xloy This limits the scope of inverse curves when the setting is more than 2 5xlyn overcurrent stages and earth fault stages using loca input or 0 25xloin earth fault stages using lo1 input or Io2 input The In and loin and loon depend on the order code See chapter 15 The table below gives the limit values in secondary amperes Example of limitation CT 750 5 In 577A CT 100 1 a cable CT for lo Secondary scaled Ignsec iS NOW 3 85 A For 5 A CT secondaries and 1 A residual current inputs VAMP relay VAMP 265 5D7AAA is used It has 5 A phase current inputs and 1 A residual inputs V265M EN M A004 5 Protection functions 5 17 Inverse time operation V265M EN M A004 For overcurrent stage I gt the t
54. 0 8 0 8 k01 0 6 0 6 0 4 0 4 k 0 05 0 2 0 2 0 1 0 1 0 08 0 08 0 06 0 06 1 2 3 4 5678 10 20 1 2 3 4 5678 10 20 T Iset inverseDelayIEEE1_VI T Iset inverseDelayIEC_LTI Figure 5 17 1 3 IEC very inverse Figure 5 17 1 4 IEC long time inverse delay delay 98 V265M EN M A004 5 Protection functions 5 17 Inverse time operation V265M EN M A004 IEEE ANSI inverse time operation There are three different delay types according IEEE Std C37 112 1996 MI VI El and many de facto versions according Table 2 12 1 3 The IEEE standard defines inverse delay for both trip and release operations However in the VAMP relay only the trip time is inverse according the standard but the release time is constant The operation delay depends on the measured value and other parameters according Equation 5 17 1 2 Actually this equation can only be used to draw graphs or when the measured value is constant during the fault A modified version is implemented in the relay for real time usage Equation 5 17 1 2 A t k aS I eae t Operation delay in seconds k User s multiplier Measured value Pickup User s pick up setting A B C Constant parameter according Table 5 17 1 3 Table 5 17 1 3 Constants for IEEE ANSI inverse delay equation Delat iyg Parameter LTI Long time inverse 0 086 0 185 0 02 LTVI Long time very inverse 28 55 0 712 2 Long time extremely LTEI herce 64 07 0 250 2 MI Moderately inverse
55. 157 9 2 5 IEC 60870 5 103 wennrtiatncciaciecusaataccunmentie 158 PO DNP ZO naaa pai lncupebis abe seeesae sends 160 9 2 7 JES OOS OO 10T scisthusaisncctnisietoncteigiiamtetstiaatetetiaass 161 9 2 8 External I O Modbus RTU mastet 0 00 162 9293 NES BIG DO Fiske ata yaad chant NER 162 7 ZNO EtherNet P seccostent teeter iets ato eat en aes 164 10 APPlICatlONS sairia aiiin arinina aaien asagat aeaea anant 166 10 1 Restricted earth fault protection ceeeeeeeeeeeeeees 166 10 2 Restricted earth fault protection for a transformer with neutral connection eseeeeseseesssssssssssssssssssssssesssseseeeeeees 167 10 2 1 CT Requirement ccccceeeeeeeeeseeseeeeeeeeeees 168 10 3 Calculating the stabilizing resistance Rs VDR value and actual sensitivity soit ts ede ees ee eee heehee kee 168 10 3 1 Value of stabilizing resistor Rg eeeeeseeeeeeeeeees 168 VO 3 2 VONAGE limitation 2s cess cee ee tsette tsetse ie ian seeeeies 169 10 3 3 Actual operating Sensitivity eeeeeeeeeeeeeeees 169 10 3 4 Example cates este ee Abia te seal A ota id eae 170 10 4 Current Transformer Selection sssssssesseeseseeees 171 10 4 1 CT classification according IEC 60044 1 1996 171 10 4 2 CT Requirement for Protection seeeeeeeee 174 10 5 Application example of differential protection using VAMP 265M 176 10 6 Trip Circuit Supervision
56. 2 Parameter Value Unit Default Description If2 gt 10 100 10 Setting value If2 lfund t_f2 0 05 300 0 s 0 05 Definite operating time S_On Enabled Enabled Start on event Disabled S_Off Enabled Enabled Start off event Disabled T_On Enabled a Enabled Trip on event Disabled T_Off Enabled Enabled Trip off event Disabled V265M EN M A004 5 Protection functions 5 12 Second harmonic O C stage If2 gt 51F2 V265M EN M A004 Measured and recorded values of second harmonic blocking 2 Ha 51F2 Parameter Value Unit Description Measured IL1H2 2 harmonic of IL1 values proportional to the fundamental value of IL1 IL2H2 A 2 harmonic of IL2 IL3H2 A 2 harmonic of IL3 Recorded Fit The max fault value values EDly Elapsed time as compared to the set operating time 100 tripping 83 5 13 Fifth harmonic O C stage 5 Protection functions If5 gt 51F5 5 13 Fifth harmonic O C stage Is5 gt 51F5 Overexiting a transformer creates odd harmonics This 5 harmonic overcurrent stage can be used together with the 5 harmonic blocking feature of the biased differential stage 87 While the 87 stage is blocked by 5 harmonic this stage can be used to finally trip the circuit breaker in case the overexcitation situation lasts too long Typically transformer over excitation causes about 20 50 of fifth harmonic co
57. 2 units Update rate Once a second The specified frequency range is 45 Hz 65 Hz 131 7 2 Harmonics and Total Harmonic 7 Measurement functions Distortion THD 7 2 7 3 132 Harmonics and Total Harmonic Distortion THD The device calculates the THDs as percentage of the base frequency for currents and voltages The device calculates the harmonics from the 2 to the 15 of phase currents and voltages The 17 harmonic component will also be shown partly in the value of the 15 harmonic component This is due to the nature of digital sampling The harmonic distortion is calculated using equation THD where hy Fundamental value he 15 Harmonics Example hy 100A hg 10A h7 3A h 8A rup 3 8 _ 130 100 For reference the RMS value is RMS V100 107 3 8 100 9A Another way to calculate THD is to use the RMS value as reference instead of the fundamental frequency value In the example above the result would then be 13 0 RMS values RMS currents Relay calculates the RMS value of each phase current The minimum and the maximum of RMS values are recorded and stored 2 2 2 Ln p L t Iys V265M EN M A004 7 Measurement functions 7 4 Demand values 7 4 Demand values The relay calculates average i e demand values of phase currents l1 IL IL3 The demand time is configurable from 10 minutes to 30 minutes with paramete
58. 2 Bl S 1 S2 Bl Operating time Light only 13 ms Operating time 4xlset light 17ms Operating time BIN 10 ms BO operating time lt 3 ms Reset time lt 95 ms Reset time Delayed ARC L lt 120 ms Reset time BO lt 85 ms Reset ratio 0 90 Inaccuracy Starting 10 of the set value Operating time 5 ms Delayed ARC light 10 ms 12 4 Supporting functions 12 4 1 Disturbance recorder DR The operation of disturbance recorder depends on the following settings The recording time and the number of records depend on the time setting and the number of selected channels Disturbance recorder DR Mode of recording Saturated Overflow Sample rate Waveform recording 32 cycle 16 cycle 8 cycle Trend curve recording 10 20 200 ms 1 5 10 15 30s 1 min Recording time one record 0 1 s 12 000 min must be shorter than MAX time Pre trigger rate 0 100 Number of selected channels 0 12 216 V265M EN M A004 13 Abbreviations and symbols 13 V265M EN M A004 Abbreviations and symbols ANSI CB CBFP coso CT CTPpri CTsec Dead band DI DO DSR DST DTR FFT Hysteresis loin loon lon In IEC IEEE IEC 103 LAN Latching NTP pu RMS SNTP TCS THD UTC WWW American National Standards Institute A standardization organisation Circuit breaker Circuit breaker failure protection Active power divided by apparent power P S S
59. 4 A2NC Alarm relay 2 normal closed connector 14 15 A2 NO Alarm relay 2 normal open connector 15 16 IF COM _ Internal fault relay common connector 16 17 IFNC Internal fault relay normal closed connector 17 18 IFNO Internal fault relay normal open connector 18 Terminal X2 with the analogue output V265M EN M A004 No Symbol Description 1I 1 AO1 Analogue output 1 common positive connector 2 2 AO1 Analogue output 1 negative connector 3l 3 AO2 Analogue output 2 common positive connector 4 4 AQ2 Analogue output 2 negative connector 5 5 AO3 Analogue output 3 common positive connector 6l 6 AO3 Analogue output 3 negative connector 71 7 AO4 Analogue output 4 common positive connector 8l 8 AO4 Analogue output 4 negative connector o P 1 10 10 A3 COM Alarm relay 3 common connector 11 11 A3 NC Alarm relay 3 normal closed connector 12 12 A3NO Alarm relay 3 normal open connector 13 13 A2COM Alarm relay 2 common connector 14 14 A2NC Alarm relay 2 normal closed connector 15 15 A2 NO Alarm relay 2 normal open connector 16 Q 16 IF COM _ Internal fault relay common connector on 17 IFNC Internal fault relay normal closed connector 2 18 IFNO Internal fault relay normal open connector 189 11 1 Rear panel
60. 400 8N1 While the front panel connector is in use the rear panel local port is disabled The communication parameter display on the local display will show the active parameter values for the local port Physical interface The physical interface of this port is RS 232 V265M EN M A004 149 9 1 Communication ports 9 Communication 150 Parameters Parameter Value Unit Description Note Protocol Protocol selection for the Set rear panel local port None Command line interface for VAMPSET SpaBus SPA bus slave ProfibusDP Profibus DB slave ModbusSla Modbus RTU slave ModbusTCPs Modbus TCP slave IEC 103 IEC 60870 5 103 slave ExternallO Modbus RTU master for external I O modules DNP3 DNP 3 0 Msg Cael Message counter since the Clr device has restarted or since last clearing Errors o 2 641 Protocol errors since the Cir device has restarted or since last clearing Tout o 2 641 Timeout errors since the Cir device has restarted or since last clearing Display of actual 1 communication parameters speed bit s speed DPS D number of data bits P parity none even odd Default S number of stop bits 38400 8N1 for VAMPSET VAMPSET communication Direct or SPA bus embedded command line interface TX bytes size Unsent bytes in transmitter buffer size of the buffer Msg 0 29 1 Message counter since the Clr device has restarted or since last clearing Errors o 2
61. 47 Modbus address of the I O device Maximum limit for lined value corresponding to Modbus Max 0 42x108 21 21x108 Minimum limit for lined value corresponding to Modbus Min Link selection 21x107 a 424x107 Minimum amp maximum output values Active value On Off Enabling for measurement V265M EN M A004 11 Connections 11 7 Block diagrams 11 7 Block diagrams X3 17 X3 18 Protection functions X1 1 X1 2 SON SIN X1 3 i X1 4 X1 5 X1 6 X1 11 X1 12 X1 13 X1 14 X1 15 Blocking and X1 16 output matrix X1 7 X18 Oo X1 9 X1 10 X6 1 X6 2 X6 3 X6 4 X6 5 X6 6 X6 7 X3 1 48V X3 2 D1 X3 3 DI2 X3 4 DIS X3 5 DM X3 6 DIS X3 7 DIG VAMP265blockdiagram Figure 11 7 1 Block diagram of VAMP 265M V265M EN M A004 205 11 8 Block diagrams of option modules 11 Connections 11 8 11 8 1 11 8 2 206 Block diagrams of option modules Optional arc protection X6 1 BI BI O X6 2 BO X6 3 comm X6 4 L1 X6 5 L1 X6 6 L2 X6 7 L2 o E VE AA AIEA DOR AE NTS hes ARC_option_block_diagram Figure 11 8 1 1 Block diagram of optional arc protection module Optional DI19 DI20 Options X6 1D119 DI X6 2 D119 X6 3 DI 20 X6 4 DI 20 X6 5 NC
62. 5s Average 1 10s Average 1 15s Average 1 30s Average 1 1min Average Time s Recording length Set PreTrig Amount of recording data Set before the trig moment MaxLen S Maximum time setting This value depends on sample rate number and type of the selected channels and the configured recording length Status Status of recording a Not active Run Waiting a triggering Trig Recording FULL Memory is full in saturated mode MantTrig Manual triggering Set Trig ReadyRec n m n Available recordings m maximum number of recordings The value of m depends on sample rate number and type of the selected channels and the configured recording length 112 V265M EN M A004 6 Supporting functions 6 2 Disturbance recorder V265M EN M A004 Parameter Value Unit Description Note AddCh IL1 IL2 IL3 PL1 PL2 PL3 lo1 lo2 f loCalc 11 12 12 11 I2 In loCalc 1 12 2 1 1 2 l n oCalc IL PL DO DI THDIL1 THDIL2 THDIL3 IL 1RMS IL2RMS ILSRMS ILmin ILmax Lmin Lmax AIL1 AIL2 AIL3 IL1w IL2w ILSw L1w PL2w L3w Add one channel Maximum Set simultaneous number of channels is 12 ClrCh Clear Remove all channels Set Ch List of selected channels Set An editable parameter password needed This is the fundamental frequency rms value of one cycle updated every 10 ms This is th
63. 771 247 Modbus address of the I O device 5550n Off Enabling for measurement 201 11 6 External I O extension modules 11 Connections 202 External digital inputs configuration VAMPSET only EXTERNAL DIGITAL INPUTS Range Description Communication read errors Bit number of Modbus register value CoilS InputS InputR or HoldingR Modbus register type 1 9999 Modbus register for the measurement 1 247 Modbus address of the I O device Active state On Off Enabling for measurement V265M EN M A004 11 Connections 11 6 External I O extension modules External digital outputs configuration VAMPSET only Range Description Communication errors E s 1 9999 Modbus register for the measurement E z 2 a Es f T 1 247 Modbus address of the I O device x mm 0 1 Output state 6 5 5 On Off Enabling for measurement V265M EN M A004 203 11 6 External I O extension modules 11 Connections 204 External analog outputs configuration VAMPSET only EXTERNAL ANALOG OUTPUTS HoldingR HoldingR Range Description Communication errors 32768 32767 0 65535 Modbus value corresponding Linked Val Max Modbus value corresponding Linked Val Min InputR or HoldingR Modbus register type 1 9999 Modbus register for the output 1 2
64. Applications 186 Figure 10 6 2 4 An example of logic configuration for trip circuit supervision with two dry digital inputs DIZ and DI13 Figure 10 6 2 5 An example of output matrix configuration for trip circuit supervision with two dry digital inputs V265M EN M A004 11 Connections 11 1 Rear panel view 11 Connections 11 1 Rear panel view Digital inputs 48V DI DI2 DB DI4 DIS DI6 i yw oa fe Al T2 T1 LOCAL RS 232 VAMP265rearPanel Figure 11 1 1 Connections on the rear panel of the relay The generator transformer and motor differential protection relay is connected to the protected object through the following measuring and control connections Figure 11 1 1 Phase currents IL1 IL2 and IL3 terminals X1 1 6 Phase currents I L1 PL2 and I L3 terminals X1 11 16 Earth fault current 101 terminals X1 7 8 Earth fault current 102 terminals X1 9 10 V265M EN M A004 187 11 1 Rear panel view 11 Connections Terminal X1 left side No Symbol Description 1 IL1 Phase current IL1 S1 high voltage side 5 3 IL2 Phase current IL2 S1 high voltage side 3 5 IL3 Phase current IL3 S1 high voltage side 5 E 7 lo1 Residual current lo1
65. C Active edge is 10 Alarm display no No pop up display Set yes Alarm pop up display is activated at active DI edge On event On Active edge event enabled Set Off Active edge event disabled Off event On Inactive edge event Set Off enabled Inactive edge event disabled V265M EN M A004 V265M EN M A004 8 Control functions 8 2 Digital inputs Parameter Value Unit Description Set NAMES for DIGITAL INPUTS editable with VAMPSET only Label String of max Short name for Dis on the Set 10 characters local display Default is DIn n 1 6 Description String of max Long name for Dls Default Set 32 characters is Digital input n n 1 6 Set An editable parameter password needed Summary of digital inputs DI Terminal Operating voltage Availability X31 48V pc supply for DI1 6 1 X3 2 2 X3 3 3 X3 4 VAMP 265M 4 X35 Internal 48Vpc 5 X3 6 6 X3 7 External 18 265 Voc 19 X6 1 2 50 250 Vac ARC card with 2 Dls 141 8 3 Virtual inputs and outputs 8 Control functions 8 3 142 Virtual inputs and outputs There are four virtual inputs and six virtual outputs The four virtual inputs acts like normal digital inputs The state of the virtual input can be changed from display communication bus and from VAMPSET For example setting groups can be changed using virtual inputs Parameters
66. COMNECtiNS en ada edni asa asn adadenn 207 12 1 1 Measuring circuitry cccncawaeiGueusigneiene 207 12 1 2 Auxiliary voltage ii ienris iiaeia 207 12 1 3 Digital inputs nseeeeeeeeseennnennreeseeerenrnnnrreserrrrrrnnn 208 PZT 4sTrip COntaCtS niuia 208 12 SAlam conta tS a e a a a died 208 12 1 6 Local serial communication port ceeeeeeees 208 12 1 7 Remote control CONNECTION eee eeeeeeeeetteeeeeeeees 209 12 1 8 Arc protection interface Option cceeeee 209 12 2 Tests and environmental ConditionS ccceeeeeee 209 12 2 1 Disturbance TESTS nssiescansecgsiacectasducstaveagecces tees eects 209 12 2 2 Test voltages ia tia a nee a i A a 210 12 2 3 Mechanical tests eecccceecceeeeeeeeeeeeeeeneeeeeeeeeees 210 12 2 4 Environmental COnditionS ccceeceeeseeeeeeeeees 210 IZ 2S CASNO ic sarees iat ia aaa a ane te at 210 1226 PACKag tt ktatiatiattastetie atta satiated a 210 12 3 Protection TUNCHONS xs c seen2sGucscceeinewexgsGenesttsctee xt aweeeic 211 12 3 1 Differential protection c ccceceeeeeeeeeeeeteeeeeeeees 211 12 3 2 Non directional current protection cceeee 211 12 3 3 Second harmonic function eee eeeettteeeeeeeees 214 12 3 4 Fifth harmonic fUNCtION c cceeeeeeeeeeeteeeeeeeeees 214 12 3 5 Circuit breaker failure protection cceeee 215 12 3 6 Arc fault protection stages Option
67. Clr device has restarted or since last clearing Display of actual 1 communication parameters speed bit s speed DPS D number of data bits P parity none even odd Default S number of stop bits 38400 8N1 for VAMPSET Set An editable parameter password needed Clr Clearing to zero is possible 1 The communication parameters are set in the protocol specific menus For the local port command line interface the parameters are set in configuration menu V265M EN M A004 9 Communication 9 1 Communication ports 9 1 4 V265M EN M A004 Ethernet port IEC61850 and Modbus TCP uses Ethernet communication Also VAMPSET SPA bus and DNP 3 0 communication can be directed via TCP IP Parameters Parameter Value Unit Description Set Protoc Protocol selection forthe Set extension port None Command line interface for VAMPSET ModbusTCPs Modbus TCP slave IEC 61850 IEC 61850 protocol Ethernet IP Ethernet IP protocol Port nnn Ip port for protocol Set default 102 pAddr n n n n Internet protocol address Set set with VAMPSET NetMsk n n n n Net mask set with Set VAMPSET Gatew default 0 0 0 0 Gateway IP address set Set with VAMPSET NTPSvr n n n n Network time protocol Set server set with VAMPSET 0 0 0 0 no SNTP VS Port nn IP port for Vampset Set KeepAlive nn TCP keepalive interval Set MAC nnnnnnnnnnnn MAC address Msg nnn Message counter E
68. Differential overcurrent protection Al gt 87 V265M EN M A004 Li i default setting Minimum trip area Setting area Z Tis SETTINGS Irau 5 50 Iy default 0 25 Slopel 5 100 default 50 Tuas 1 00 3 00xI default 2 00 Slope2 100 200 default 150 slopesC Figure 5 5 3 Example of differential overcurrent characteristics The stage also includes second harmonics blocking The second harmonic is calculated from winding currents Harmonic ratio is 100 x liz winding It1_winding Fast differential overcurrent stage Al gt gt does not include slope characteristics and second harmonics blocking 55 5 5 Differential overcurrent protection Al gt 87 5 Protection functions 56 Parameters of the biased differential stage Al gt 87 Parameter Value unit Measured SIA xlmot Current difference value values 1 SIA2 dIA3 AL1 AL2 AL3 Setting Al gt lmot Setting value values 2 Ibiasl lmot Bias current start of slope 1 Slope Slope 1 setting Ibias2 xlmot Bias current start of slope 2 Slope2 Slope 2 setting Harm2 gt On Off 2 harmonic blocking enable disable Harm2 gt 2 harmonic block limit TCnitr Cumulative trip counter Type 1 N 2 N Fault type single phase fault e g 1 3 N N fault on phase L1 1 2 2 3 Fault type two phase fault e g 2 3 1 3 fault between L2 and L3 1 2 3 Fault type three phase fault Bias xlmot Value of bia
69. EEE and IEEE2 GQUAMONS ine eaae aa ites hentia E EE denim ths hies 106 5 17 3 Programmable inverse time CUIVES cceeees 107 6 Supporting FUNCTIONS eceee cece eeeeeeeeeeeeeeeeeeeeeeeeeeeeeees 108 Gels Event logy ses iiine 108 6 2 Disturbance recorder sssssseeseeseseseernrnrrreeerrrtrrnnneeeeeee 110 6 3 Current transformer Supervision sseeeeeessssrrrrr neeese 115 6 4 Circuit breaker condition monitoring ccceeeeeee 116 6 5 System clock and synchronization cccceeeeeeeee 121 6 6 Running hour COUNIGI ces cutee eee ee Ae kite 124 57 IME S aia ech e E E E T 125 6 8 Combined overcurrent Status eeeeeeeeeeeeeeeeeeeeeeeeeee 127 6 9 Self supervision se ats Sie nis ae ie Be aes aie ie Atos 129 7 Measurement functions cccceseeeeeeeeeeeeeeeeeeeeeeseeeeneeeenees 130 7 1 Measurement accuracy ccccceeeeeeeeeeeeeteeeeeeeeeeeeeeennaeees 131 7 2 Harmonics and Total Harmonic Distortion THD 132 7 3 RMS VAlW CS 5 occu dcostecheccnbanaccdid cee rsabcaitead eps soietatetehlsahete 132 7 4 Demand Values cccecccceceeeeeeeeeeeeneeeeeeeeeeeeeeeeenaaeees 133 7 5 Minimum and maximum values cccceeeeeeeeeeeeeees 133 7 6 Maximum values of the last 31 days and twelve months134 7 7 Primary secondary and per unit scaling 0000 135 Fed Ne COMEMES CANIN Gis cae cates eve catd ectendesecltesintesemieemetiveienude
70. I NCT sec K yr Iyer Example 1 Transformer 16 MVA YNd11 Z 10 110 kV 21kV 84 A 440 A CT s on HW side 100 5 5P10 Winding resistance Rct 0 07 Q RCT depends on the CT type INCT and power rating Let s say that the selected CT type 100 A and an initial guess of 15 VA yields to 0 07 Q Safety factor c 4 Transformer differential earthed Y CTs on LV side 500 5 5P10 Max Short circuit curent is 4400 A 8 8 x 500 A Winding resistance Rcr 0 28 Q RCT depends on the CT type INCT and power rating Let s say that the selected CT type 500 A and an initial guess of 15 VA yields to 0 28 Q Safety factor c 3 Transformer differential A Differential current setting of the non stabilized stage Al gt gt Iset 9 X In RL 0 008 Q Typical burden of a VAMP relay current input Rwav 0 138 Q Wiring impedance of high voltage side 2x16 m 4 mm Rwiv 0 086 Q Wiring impedance of low voltage side 2x10 m 4 mm The needed CT power on HV side will be ve 49 84 0 07 0 138 0 008 0 07 5 14 6 VA 10 100 J 15 VA is a good choice for HV side And on the LV side 175 10 5 Application example of differential protection using VAMP 265M 10 Applications 39 440 N 10 500 15 VA is a good choice for LV side 0 28 0 086 0 008 0 28 5 15 2 VA 10 5 Application example of differential protection using VAMP 265M
71. ICK UP LEVEL gt PICK UP Figure 5 3 3 Behaviour of a greater than comparator For example in overcurrent and overvoltage stages the hysteresis dead band acts according this figure Hysteresis LT hysteresis PICK UP LEVEL lt PICK UP Figure 5 3 4 Behaviour of a less than comparator For example in under voltage and under frequency stages the hysteresis dead band acts according this figure 51 5 4 Frequent start protection N gt 66 5 Protection functions 5 4 Frequent start protection N gt 66 The simplest way to start an asynchronous motor is just to switch the stator windings to the supply voltages Every such start will heat up the motor considerably because the initial currents are significantly above the rated current If the motor manufacturer has defined the maximum number of starts within on hour or and the minimum time between two consecutive starts this stage is easy to apply to prevent too frequent starts When the current has been less than 10 of Imot and then exceeds gt setting in start up supervision stage the situation is recognized as a start When the current is less than 10 of Imot the motor is regarded as stopped The stage will give a start signal when the second last start has been done The trip signal is normally activated and released when there are no starts left Figure 5 4 1 shows an application STOP VAMP relay Output matrix I gt sta
72. IEEE2_MI Vset inverse DelayIEEE2_NI Figure 5 17 1 11 IEEE2 moderately Figure 5 17 1 12 IEEE2 normal inverse inverse delay delay V265M EN M A004 103 5 17 Inverse time operation 5 Protection functions IEEE2 VI IEEE2 EI 600 400 600 400 200 100 100 80 60 40 60 40 20 gt 0o00 PN 8 O Z 6 2 2 k 20 8 2 k 10 k 20 08 08 0 6 k 5 06 k 10 0 4 0 4 k5 0 2 Ke 0 2 k 2 oi a 0 06 k 0 5 oie K 0 5 1 1 2 3 45678 10 20 1 2 3 4 5678 10 20 TIset inverse DelayIEEE2_VI Tset inverse DelayIEEE2_EI Figure 5 17 1 13 IEEE2 very inverse Figure 5 17 1 14 IEEE2 extremely delay inverse delay RI and RXIDG type inverse time operation These two inverse delay types have their origin in old ASEA nowadays ABB earth fault relays The operation delay of types RI and RXIDG depends on the measured value and other parameters according Equation 5 17 1 4 and Equation 5 17 1 5 Actually these equations can only be used to draw graphs or when the measured value is constant during the fault Modified versions are implemented in the relay for real time usage Equation 5 17 1 4 RI k 0 236 al oe 0 339 Try Equation 5 17 1 5 RXIDG I teng 5 8 1 35In pickup t Operation delay in seconds k User s multiplier l Measured value lpickup User s pick up setting 104 V265M EN M A004 5 Protection functions 5 17 Inverse time operation V265M EN M A004 Example for Delay type RI G 2 The operat
73. If no digital input is used for synchronization select e UTC time zone for SNTP synchronization TZone Note This is a decimal number For example for state of Nepal the time zone 5 45 is given as 5 75 Daylight saving time for NTP synchronization DST Detected source of synchronization SySrc Synchronization message counter MsgCnt Latest synchronization deviation Dev CLOCK SYNC 2 The following parameters are visible only when the access level is higher than User e Offset i e constant error of the synchronization source SyOS e Auto adjust interval AAlntv e Average drift direction AvDrft Lead or lag e Average synchronization deviation FilDev SW OPTIONS e Application mode fixed Motor ApplMod e External led module installed Ledmodule e Mimic display selection MIMIC 36 V265M EN M A004 2 Local panel user interface 2 4 Configuration and parameter setting 2 4 8 V265M EN M A004 Protocol menu Bus There are three communication ports in the rear panel In addition there is a connector in the front panel overruling the local port in the rear panel REMOTE PORT X5 e Communication protocol for remote port X5 Protocol e Message counter Msg This can be used to verify that the device is receiving messages e Communication error counter Errors e Communication time out error counter Tout e Information of bit rate data bits parity stop bits This value is
74. In request more it is not possible to read continuously only one single data item Atleast two data items must be read in turn to get updated data from the device There is a separate manual for VPA 3CG with the code VMVPA ENXX available for the continuous mode and request mode Available data VAMPSET will show the list of all available data items for both modes A separate document Profibus parameters pdf is also available The Profibus DP communication is activated usually for remote port via a menu selection with parameter Protocol See chapter 9 1 V265M EN M A004 155 9 2 Communication protocols 9 Communication Parameters Parameter Value Unit Description Note Mode Profile selection Set Cont Continuous mode Reqst Request mode bit s 2400 bps Communication speed from the main CPU to the Profibus converter The actual Profibus bit rate is automatically set by the Profibus master and can be up to 12 Mbit s Emode Event numbering style Set Channel Use this for new installations Limit60 The other modes are for NoLimit compatibility with old systems InBuf bytes Size of Profibus master s 1 3 Rx buffer data to the master OutBuf bytes Size of Profibus master s 2 3 Tx buffer data from the master Addr 1 247 This address has to be Set unique within the Profibus network system Conv Converter type No converter recognized 4 VE Converter type VE is recognized Set An editab
75. L2 Alarm 1 phase L2 AliL3 Alarm 1 phase L3 Al2L1 Alarm 2 phase L1 Al2L2 Alarm 2 phase L2 Al2L3 Alarm 2 phase L3 Latest trip Date Time stamp of the latest trip time operation IL1 A Broken current of phase L1 IL2 A Broken current of phase L2 IL3 A Broken current of phase L3 CBWEAR SET Alarm1 Current 0 00 100 00 kA Alarmi current level Set Cycles 100000 1 Alarm1 limit for operations Set left Alarm2 Current 0 00 100 00 kA Alarm2 current level Set Cycles 100000 1 Alarm2 limit for operations Set left CBWEAR SET2 Al1On On Alarm1 on event enabling Set Off Al1 Off On Alarm1 off event enabling Set Off Al2On On Alarm2 on event enabling Set Off Al2Off On Alarm2 off event enabling Set Off Clear gt Clearing of cycle counters Set Clear Set An editable parameter password needed The breaker curve table is edited with VAMPSET V265M EN M A004 6 Supporting functions 6 5 System clock and synchronization 6 5 System clock and synchronization The internal clock of the relay is used to time stamp events and disturbance recordings The system clock should be externally synchronised to get comparable event time stamps for all the relays in the system The synchronizing is based on the difference of the internal time and the synchronising message or pulse This deviation is filtered and the internal time is corrected softly towards a zero deviation Adapting auto adjust
76. NT Description Local Communication panel protocols Code 30E2 Channel 30 Yes Yes event 2 U gt trip on Event text Yes No 112 0 Ugn Fault value Yes No 2007 01 31 Date Yes Yes 08 35 13 413 Time Yes Yes Type U12 23 31 Fault type Yes No Events are the major data for a SCADA system SCADA systems are reading events using any of the available communication protocols Event log can also be scanned using the front panel or using VAMPSET With VAMSET the events can be stored to a file especially in case the relay is not connected to any SCADA system Only the latest event can be read when using communication protocols or VAMPSET Every reading increments the internal read pointer to the event buffer In case of communication error the latest event can be reread any number of times using an other parameter On the local panel scanning the event buffer back and forth is possible Event enabling masking In case of an uninteresting event it can be masked which prevents the particular event s to be written in the event buffer As a default there is room for 200 latest events in the buffer Event buffer size can be modified from 50 to 2000 in all v 10 xx softwares Modification can be done in Local panel conf menu Alarm screen popup screen can also be enabled in this same menu when Vampset setting tool is used The oldest one will be overwritten when a new event does occur The shown resolution of a time stamp is one mil
77. Note ASDU23 On Enable record info Set Off message Smpls msg_ 1 25 Record samples in one Set message Timeout 10 10000 s Record reading timeout Set Fault Fault identifier number for IEC 103 Starts trips of all stages TagPos Position of read pointer Chn Active channel ChnPos Channel read position Fault numbering Faults Total number of faults GridFlts Fault burst identifier number Grid Time window to classify Set faults together to the same burst Set An editable parameter password needed 159 9 2 Communication protocols 9 Communication 9 2 6 160 DNP 3 0 The relay supports communication using DNP 3 0 protocol The following DNP 3 0 data types are supported e counters binary input binary input change double bit input binary output analog input Additional information can be obtained from the DNP 3 0 Device Profile Document and DNP 3 0 Parameters pdf DNP 3 0 communication is activated via menu selection RS 485 interface is often used but also RS 232 and fibre optic interfaces are possible Parameters Parameter Value Unit Description Set bit s bps Communication speed Set 4800 9600 default 19200 38400 Parity Parity Set None default Even Odd SlvAddr 1 65519 An unique address for the Set device within the system MstrAddr 1 65519 Address of master Set 255 default LLTout 0 65535 ms Link layer conf
78. Pick up scaling The per unit pu values for pick up setting are based on the current transformer values Arcl gt 1 pu 1xly rated phase current CT value Arcl gt 1 pu 1xl y rated phase current CT value Arclo1 gt 1 pu 1Xloin rated residual current CT value for input lot Arcloz gt 1 pu 1Xlo2n rated residual current CT value for input loo V265M EN M A004 5 Protection functions 5 15 Arc fault protection 50ARC 50NARC optional Parameters of arc protection stages Arcl gt Arcl gt Arcloi gt Arclo2 gt SOARC 50NARC Parameter Value Unit Description Note Status Current status of the stage Start Light detected according Arclin F Trip Light and overcurrent detected F LCntr Cumulative light indication C counter S1 S2 or BI SCntr Cumulative light indication C counter for the selected inputs according parameter Arclin TCntr Cumulative trip counter C Force Off Force flag for status forcing for Set On test purposes This is a common flag for all stages and output relays too Automatically reset by a 5 minute timeout Value of the supervised signal ILmax Stage Arcl gt Lmax Stage Arcl gt lot Stage Arcloi gt lo2 Stage Arclos gt Arcl gt pu Pick up setting xin Set Arcl gt pu Pick up setting xl x Arclo1 gt pu Pick up setting Xloin Arclo2 gt pu Pick up setting Xlozan Arclin Light indication source selection Set No sensor
79. Starting 3 of set value or 0 5 of rated value Operating time l4 gt 3 5 X Iset lt 40 ms 12 3 2 Non directional current protection Overcurrent stage I gt l gt 50 51 Pick up current 0 10 5 00 x Imode Definite time function DT Operating time 0 08 300 00 s step 0 02 s IDMT function Delay curve family DT IEC IEEE RI Prg Curve type EI VI NI LTI MI depends on the family Time multiplier k 0 05 20 0 except 0 50 20 0 for RXIDG IEEE and IEEE2 Start time Typically 60 ms Reset time lt 95 ms Retardation time lt 50 ms Reset ratio 0 97 Transient over reach any t lt 10 Inaccuracy Starting 3 of the set value or 5 mA secondary Operating time at definite time function 1 or 30 ms Operating time at IDMT function 5 or at least 30 ms El Extremely Inverse NI Normal Inverse VI Very Inverse LTI Long Time Inverse Ml Moderately Inverse This is the instantaneous time i e the minimum total operational time including the fault detection time and operation time of the trip contacts V265M EN M A004 211 12 3 Protection functions 12 Technical data 212 Overcurrent stages I gt gt and I gt gt 50 51 Pick up current 0 10 20 00 x Imode I gt gt Definite time function Operating time DT 0 04 1800 00 s step 0 01 s l gt gt I gt gt gt 0 04 300 00 s step 0 01 s Start time Typically 60
80. Tx REMOTE port 192 V265M EN M A004 11 Connections 11 3 Serial communication connectors Order Code Communication interface Connector type Pin usage Ethernet interface and Serial interface for external converters only REMOTE port D9S and RJ 45 D connector 1 reserved 2 TX_out TTL 3 RX_in TTL 4 RTS out TTL 7 GND 9 8V out RJ 45 connector 1 Transmit 2 Transmit 3 Receive 4 Reserved 5 Reserved 6 Receive 7 Reserved 8 Reserved 10Mbps Ethernet interface with IEC 61850 and Serial interface for external converters only REMOTE port D9S and RJ 45 D connector 1 reserved 2 TX_out TTL 3 RX_in TTL 4 RTS out TTL 7 GND 9 8V out RJ 45 connector 1 Transmit 2 Transmit 3 Receive 4 Reserved 5 Reserved 6 Receive 7 Reserved 8 Reserved 100 Mbps Ethernet fibre interface with IEC 61850 and Serial interface for external converters only REMOTE port D9S and LC OON 7a 3 O fe oO AD OO amp 4 Moko le D connector 1 reserved 2 TX_out TTL 3 RX_in TTL 4 RTS out TTL 7 GND 9 8V out Fiber connector TX Upper LC connector RX Lower LC connector Order Communication interface Connector Pin usage V265M EN M A004 193 11 3 Serial communication connectors 11 Connections 194 Code t
81. VAMP 265M Motor differential protection relay Publication version V265M EN M A004 User manual V265M EN M A004 Table of Contents Table of Contents Me SSNS ea E A A A A 7 1 1 Relay features thc eae ince ene m eaccenetd he Aa 7 1 2 User AMC ACS ysis hae ces heated ae exieted Mavetigiadeted ceeeetedbuotiteiete 8 1 3 Operating Safety cee sraccte citi aee a aE E AAEN 8 2 Local panel user interface ccccceesseeeseeeeeeeeeeeeeeneeeeeeeees 9 2 1 Relay front panel sseseeeeessennenneesseesrrnnnnnrrsssererrnnnnnneeee 9 DAG Display iaaiaee a a aiae 10 2 1 2 Menu navigation and pointers eeeeeeeeeeeeeeeeeees 11 DM se Keypad ario idinestino a ieai 11 2 1 4 Operation INdicators cccccceeeeeeeeeeeeeeeeeeeneeeeeeees 12 2 1 5 Adjusting display Contrast cccceeeeeeeeeeeeeeeeeeeees 13 2 2 Local panel operations c cccceeeeeeeeeeeeeeeeteeeeeeeeeeeeeees 14 2 2 1 Navigating in MENUS ceeeeeeeeeeeeeeeeeeeeteeeeeeees 14 2 2 2 Menu structure of protection functions 18 2 2 3 Setting CHOUDS sxicctectas Sesaieas Seance edt vce cen tas hides 21 2 2 4 Fault lOQS cccccccceeceeeeeeeeeeeeeeeeeeeeeeeeeseessneneeeeeeees 22 2 2 5 Operating NEV GlSitct tes cei ec tice tate setae eels 23 2 3 Operating MEASUMECS cccceeeeceeeeeeeeeeeeeeeeeeeeeeeeeeeeeees 25 2 3 1 Control fUNnCtIONS insta ccsecsiceete ie seteiti
82. able below gives 12 5 A Thus the maximum setting for l gt stage giving full inverse delay range is 12 5 A 3 85 A 3 25 xlen For earth fault stage Ip gt and input Io the table below gives 0 25 A Thus the maximum setting for Io gt stage giving full inverse delay range is 0 25 A 1 A 0 25 pu This equals a 25 A primary earth fault current When using input signal locaic the corresponding setting is 12 5 A 1 A 12 5 pu This equals a 9375 A of primary earth fault current RATED INPUT Maximum secondary scaled setting enabling inverse delay times up to 20x setting Order code I Pi lor loo lu h2 Fu lt loi lo2 hs amp Vis amp locatc l ocate VAMP 265 1 __ 1 1 2 5A 2 5A VAMP 265 3 _ 1 5 2 5A 12 5 A VAMP 265 4_ 5 1 12 5 A 2 5A VAMP 265 5_ 5 5 12 5 A 12 5 A VAMP 265 _A 5 5 1 25A 1 25A VAMP 265 _B 5 1 1 25A 0 25A VAMP 265 _C 1 5 0 25A 1 25A VAMP 265 _D 1 1 0 25A 0 25A 95 5 17 Inverse time operation 5 Protection functions 5 17 1 96 Standard inverse delays IEC IEEE IEEE2 RI The available standard inverse delays are divided in four categories IEC IEEE IEEE2 and RI called delay curve families Each category of family contains a set of different delay types according the following table Inverse time setting error signal The inverse time setting error signal will be activated if the delay category is changed and
83. address Set ALAddr 1 65534 ASDU address Set ALAddrSize 1 2 Bytes Size of ASDU address Set lOAddrSize 2 3 Bytes Information object address Set size 8 octet addresses are created from 2 octet addresses by adding MSB with value 0 COTsize 1 Bytes Cause of transmission size TTFormat Short The parameter determines Set Full time tag format 3 octet time tag or 7 octet time tag MeasFormat Scaled The parameter determines Set Normalized measurement data format normalized value or scaled value DbandEna No Dead band calculation Set Yes enable flag DbandCy 100 10000 ms Dead band calculation Set interval Set An editable parameter password needed 161 9 2 Communication protocols 9 Communication 9 2 8 9 2 9 162 External I O Modbus RTU master External Modbus I O devices can be connected to the relay using this protocol See chapter External input output module for more information IEC 61850 The relay supports communication using IEC 61850 protocol with native implementation IEC 61850 protocol is available with the optional inbuilt Ethernet port The protocol can be used to read write static data from the relay or to receive events and to receive send GOOSE messages to other relays IEC 61850 serve interface is capable of e Configurable data model selection of logical nodes corresponding to active application functions e Configurable pre defined data sets e Suppo
84. age 250 V ac dc Max make current 4s at duty cycle 10 15A Continuous carry 5A Breaking capacity DC L R 40ms at 48 V dc 1 33 A at 110 V dc 0 4 A at 220 V dc 0 2 A Breaking capacity AC 2 000 VA Contact material AgNi 0 15 goldplated Terminal Block Phoenix MVSTBW or equivalent Max wire dimension 2 5 mm 13 14 AWG Local serial communication port Number of ports 1 on front and 1 on rear panel Electrical connection RS 232 Data transfer rate 1200 38 400 kb s V265M EN M A004 12 Technical data 12 2 Tests and environmental conditions 12 1 7 Remote control connection Number of ports 1 on rear panel Electrical connection TTL standard RS 485 option RS 232 option Plastic fibre connection option Glass fibre connection option Ethernet 10 Base T option external module Data transfer rate 1 200 19 200 kb s Protocols Modbus RTU master Modbus RTU slave Spabus slave IEC 60870 5 103 Profibus DP option Modbus TCP option external module 12 1 8 Arc protection interface option Number of arc sensor inputs 2 Sensor type to be connected VA1 DA Operating voltage level 12 Vdc Current drain when active gt 11 9mA Current drain range 1 3 31 mA NOTE If the drain is outside the range either sensor or the wiring is defected Number of binary inputs 1 optically isolated Operating voltage level
85. al inputs menu The status of digital inputs DIGITAL INPUTS 1 6 Operation counters DI COUNTERS Operation delay DELAYs for DigIn The polarity of the input signal INPUT POLARITY Either normally open NO or normally closed NC circuit e Event enabling EVENT MASK 1 Configuring digital outputs DO The following functions can be read and set via the submenus of the digital outputs menu e The status of the output relays RELAY OUTPUTS1 and 2 e The forcing of the output relays RELAY OUTPUTS1 and 2 only if Force ON o Forced control 0 or 1 of the Trip relays o Forced control 0 or 1 of the Alarm relays o Forced control 0 or 1 of the IF relay e The configuration of the output signals to the output relays The configuration of the operation indicators LED Alarm and Trip and application specific alarm leds A B and C that is the output relay matrix NOTE The amount of Trip and Alarm relays depends on the relay type and optional hardware 2 4 6 Protection menu Prot The following functions can be read and set via the submenus of the Prot menu e Reset all the counters PROTECTION SET CIrAll e Read the status of all the protection functions PROTECT STATUS 1 x e Enable and disable protection functions ENABLED STAGES 1 x e Define the interlockings between signals Each stage of the protection functions can be disabled or enabled individually in the Prot menu When a stage is enabled it will be in oper
86. al overload stage is provided with a separately settable alarm function When the alarm limit is reached the stage activates its start signal Temperature rise emote Soverdoad ieee enetcceneees i 100 Omax Croc Oalarm 80 _ LY Reset ratio 95 Op 60 40 Settings T 30 minutes 20 k 1 06 alarm 90 0 Alarm 1 Trip oh r Why enn Tygx K ly Toverroan 1 05 Imax B I I I I L Time 100 min 200 min 300 min 400 min 500 min Figure 5 11 2 Example of the thermal model behaviour 80 V265M EN M A004 5 Protection functions 5 11 Thermal overload protection T gt 49 Parameters of the thermal overload stage T gt 49 Parameter Value Unit Description Note Status Current status of the stage Blocked Start F Trip F Time hh mm s Estimated time to trip s SCntr Cumulative start counter C TCntr Cumulative trip counter G Force Off Force flag for status forcing for Set On test purposes This is a common flag for all stages and output relays too Automatically reset by a 5 minute timeout T Calculated temperature rise F Trip limit is 100 MaxRMS Arms Measured current Highest of the three phases Imaxc gt A kxImot Current corresponding to the 100 temperature rise k gt xlmot Allowed overload service Set factor Alarm Alarm level Set tau Min Thermal time constant Set ctau Xtau Coefficient for cooling time Set constant Default 1 0 kTamb xlmot
87. alue of the current That is why the composite error defined by IEC 60044 1 is not ideal for VAMP relays However the difference is not big enough to prevent rough estimation Standard accuracy classes At rated frequency and with rated burden connected the amplitude error phase error and composite error of a CT shall not exceed the values given in the following table Amplitude error Phase displacement Composite error Accuracy at rated primary at rated primary ec at rated class current current accuracy limit 9 primary current 5P 1 1 5 10P 3 10 Marking The accuracy class of a CT is written after the rated power E g 10 VA 5P10 15 VA10P10 30 VA 5P20 Accuracy limit current laL Current transformers for protection must retain a reasonable accuracy up to the largest relevant fault current Rated accuracy limit current is the value of primary current up to which the CT will comply with the requirements for composite error e Accuracy limit factor Karr The ratio of the accuracy limit current to the rated primary current Equation 10 4 1 2 K ae ALF Iy The standard accuracy limit factors are 5 10 15 20 and 30 Marking Accuracy limit factor is written after the accuracy class E g 10 VA 5P10 15 VA 10P10 30 VA 5P20 172 V265M EN M A004 10 Applications 10 4 Current Transformer Selection V265M EN M A004 The actual accuracy limit factor ka depends on the actua
88. an be disregarded and the factory default settings can be left intact Set motor nominal current Settings of the differential protection Al gt 87 function shall be enabled for differential protection Al gt pick up setting range is user selectable from 5 to 50 Slope 1 can be set to 5 Ibias for start of slope 2 can be set to 3 x In Slope 2 can be set to 50 Al gt 2 harmonic block enable can be set OFF disabled Al gt 2 harmonic block limit can be disregarded and the factory default setting can be left intact V265M EN M A004 5 Protection functions 5 6 Overcurrent protection I gt 50 51 5 6 Overcurrent protection I gt 50 51 Overcurrent protection is used against short circuit faults and heavy overloads The overcurrent function measures the fundamental frequency component of the phase currents The protection is sensitive for the highest of the three phase currents Whenever this value exceeds the user s pick up setting of a particular stage this stage picks up and a start signal is issued If the fault situation remains on longer than the user s operation delay setting a trip signal is issued Two independent stages There are two separately adjustable overcurrent stages I gt I gt gt l gt and I gt gt The first stage I gt can be configured for definite time DT or inverse time operation characteristic IDMT The stage l gt gt has definite time operation characteristic By using t
89. anel is a single line diagram including relay identification Local Remote indication Auto reclose on off selection and selected analogue measurement values Please note that the operator password must be active in order to be able to control the objects Please refer to page 24 opening access Toggling Local Remote control 1 Push ox The previously activated object starts to blink 2 Select the Local Remote object L or R squared by using the arrow keys 3 Push ox The L R dialog opens Select REMOTE to enable remote control and disable local control Select LOCAL to enable local control and disable remote control 4 Confirm the setting by pushing M The Local Remote state will change Object control Push ox The previously activated object starts to blink 2 Select the object to control by using the arrow keys Please note that only controllable objects can be selected _ 3 Push ox A control dialog opens 4 Select the Open or Close command by using and v 5 Confirm the operation by pushing ox The state of the object changes Toggling virtual inputs Push ox The previously activated object starts to blink Select the virtual input object empty or black square The dialog opens Select Vlon to activate the virtual input or select Vloff to deactivate the virtual input ROND 25 2 3 Operating measures 2 Local panel user interface 2 3 2 26
90. arameters according Equation 5 17 1 3 Actually this equation can only be used to draw graphs or when the measured value is constant during the fault A modified version is implemented in the relay for real time usage Equation 5 17 1 3 B D E t k A z 5 I I I Ra c C C pickup Tiii Toig al t Operation delay in seconds k User s multiplier Measured value IPickup User s pick up setting A B C D Constant parameter according Table 5 17 1 4 Table 5 17 1 4 Constants for IEEE2 inverse delay equation Belay ies Parameter y YP A B C D E MI Moderately inverse 0 1735 0 6791 0 8 0 08 0 1271 NI Normally inverse 0 0274 2 2614 0 3 1899 9 1272 VI Very inverse 0 0615 0 7989 0 34 0 284 4 0505 El Extremely inverse 0 0399 0 2294 0 5 3 0094 0 7222 V265M EN M A004 5 Protection functions 5 17 Inverse time operation Example for Delay type Moderately inverse Ml k 0 50 4 pu Pickup 2 pu A 0 1735 B 0 6791 C 0 8 D 0 08 E 0 127 osina eg ET a Eo Eo The operation time in this example will be 0 38 seconds The same result can be read from Figure 5 17 1 11 IEEE2 MI IEEE2 NI 600 400 600 400 200 200 100 80 60 40 100 80 60 40 20 20 TaS 8 3 2 8 2 B 2 1 1 0 8 0 8 0 6 0 6 0 4 0 4 0 2 0 2 0 1 0 1 0 08 0 08 k 0 5 0 06 0 06 1 2 3 4 5678 10 20 1 2 3 4 5678 10 20 TIset inverse Delay
91. arthed networks l oca lti Le I L Additionally the stage lo gt have two more input signal alternatives to measure current peaks to detect a restriking intermittent earth fault e lotPeak to Measure the peak value of input lo1 e lo2Peak to Measure the peak value of input lo2 Intermittent earth fault detection Short earth faults make the protection to start pick up but will not cause trip When starting happens often enough such intermittent faults can be cleared using the intermittent time setting When a new start happens within the set intermittent time the operation delay counter is not cleared between adjacent faults and finally the stage will trip By using input signals lo1Peak Or lozPeak a single one millisecond current peak is enough to start the stage and increase the delay counter by 20 ms For example if the operating time is 120 ms and the time between two peaks does not exceed the intermittent time setting the sixth peak will cause a trip Four independent undirectional earth fault overcurrent stages There are four separately adjustable earth fault stages lo gt lo gt gt Ip gt gt gt and l gt gt gt gt The first stage lo gt can be configured for definite time DT or inverse time operation characteristic IDMT The other stages have definite time operation characteristic By using the definite delay type and setting the delay to its minimum an instantaneous ANSI 50N operation is obtained
92. as AvDrft Lead AAInty 3 995 61 With these parameter values the system clock corrects itself with 1 ms every 9 9 seconds which equals 61 091 s week Example 2 If there is no external sync and the relay s clock has been lagging five seconds in nine days and the AAIntv has been 9 9 s leading then the parameters are set as 1 AAIE yey 00 7 10 6 9 9 9 24 3600 AvDrft Lead NOTE When the internal time is roughly correct deviation is less than four seconds any synchronizing or auto adjust will never turn the clock backwards Instead in case the clock is leading it is softly slowed down to maintain causality 122 V265M EN M A004 6 Supporting functions 6 5 System clock and synchronization V265M EN M A004 System clock parameters Parameter Value Unit Description Note Date Current date Set Time Current time Set Style Date format Set y d m Year Month Day d m y Day Month Year m d y Month Day Year SyncDI The digital input used for clock rs synchronisation DI not used for synchronizing DI DIG Minute pulse input TZone 12 00 UTC time zone for SNTP Set 14 00 synchronization Note This is a decimal number For example for state of Nepal the time zone 5 45 is given as 5 75 DST No Daylight saving time for SNTP Set Yes SySrc Clock synchronisation source Internal No sync recognized since 200 s DI Digital input SNTP Prot
93. ast local panel push button activity The force flag also enables forcing of the output relays and forcing the optional mA outputs Start and trip signals Every protection stage has two internal binary output signals start and trip The start signal is issued when a fault has been detected The trip signal is issued after the configured operation delay unless the fault disappears before the end of the delay time Output matrix Using the output matrix the user connects the internal start and trip signals to the output relays and indicators For more details see chapter 8 4 V265M EN M A004 5 Protection functions 5 3 General features of protection stages V265M EN M A004 Blocking Any protection function except arc protection can be blocked with internal and external signals using the block matrix chapter 8 5 Internal signals are for example logic outputs and start and trip signals from other stages and external signals are for example digital and virtual inputs When a protection stage is blocked it won t pick up in case of a fault condition is detected If blocking is activated during the operation delay the delay counting is frozen until the blocking goes off or the pick up reason i e the fault condition disappears If the stage is already tripping the blocking has no effect Retardation time Retardation time is the time a protection relay needs to notice that a fault has been cleared during the operation tim
94. asured phase angle L2 deg IL3 Meas ANGLES Measured phase angle L3 deg L1 Meas ANGLES Measured phase angle L 1 deg PL2 Meas ANGLES Measured phase angle L 2 deg L3 Meas ANGLES Measured phase angle L 3 deg IL1 Meas WINDING ANGLES Measured winding angle L1 deg IL2 Meas WINDING ANGLES Measured winding angle L2 deg IL3 Meas WINDING ANGLES Measured winding angle L3 deg L1 Meas WINDING ANGLES Measured winding angle L 1 deg PL2 Meas WINDINGANGLES Measured winding angle L 2 deg PL3 Meas WINDING ANGLES Measured winding angle L 3 deg lo Meas lo f PHASE SEQ Primary value of zerosequence residual current lo A lo2 Meas lo f PHASE SEQ Primary value of zero sequence residual current lo2 A f Meas lo f PHASE SEQ Frequency Hz fAdop Meas lo f PHASE SEQ Adopted Frequency Hz Iseq Meas lo f PHASE SEQ l seq Meas lo f PHASE SEQ loCalc Meas SYMMETRIC Calculated lo A CURRENTS V265M EN M A004 2 Local panel user interface 2 3 Operating measures Menu Submenu Description Meas SYMMETRIC CURRENTS Positive sequence current A Meas SYMMETRIC CURRENTS Negative sequence current A l oCalc Meas SYMMETRIC CURRENTS Calculated lo A r1 Meas SYMMETRIC CURRENTS Positive sequence current A l2 Meas SYMMETRIC CURRENTS Negative sequence current A THDIL Meas HARM DISTORTION Total harmonic distortion of the mean value o
95. ation immediately without a need to reset the relay NOTE The relay includes several protection functions However the processor capacity limits the number of protection functions that can be active at the same time 34 V265M EN M A004 2 Local panel user interface 2 4 Configuration and parameter setting 2 4 7 V265M EN M A004 Configuration menu CONF The following functions and features can be read and set via the submenus of the configuration menu DEVICE SETUP e Bit rate for the command line interface in ports X4 and the front panel The front panel is always using this setting If SPABUS is selected for the rear panel local port X4 the bit rate is according SPABUS settings e Access level Acc LANGUAGE e List of available languages in the relay other than English CURRENT SCALING Rated phase CT primary current Inom Rated phase CT secondary current Isec Rated phase CT primary current nom Rated phase CT secondary current I sec Rated input of the relay linput 5 A or 1 A This is specified in the order code of the device e Rated input of the relay l input 5 A or 1 A This is specified in the order code of the device e Rated value of lo CT primary current lonom e Rated value of l CT secondary current losec e Rated 101 input of the relay loinp 5 A or 1 A This is specified in the order code of the device e Rated value of lo2 CT primary current lo2nom e Rated value
96. ation of bit rate data bits parity stop bits This value is not directly editable Editing is done in the appropriate protocol setting menus Ethernet port These parameters are used by the ethernet interface For changing the nnn nnn nnn nnn style parameter values VAMPSET is recommended Ethernet port protocol Protocol IP Port for protocol Port IP address IpAdadr Net mask NetMsk Gateway Gatew Network time protocol NTP server NTPSvr TCP Keep alive interval KeepAlive MAC address MAC IP Port for Vampset VS Port Message counter Msg Error counter Errors Timeout counter Tout MODBUS e Modbus addres for this slave device Addr This address has to be unique within the system e Modbus bit rate bit s Default is 9600 e Parity Parity Default is Even or details see the technical description part of the manual EXTERNAL I O protocol This is a Modbus master protocol to communicate with the extension I O modules connected to the extension port Only one instance of this protocol is possible e Bit rate bit s Default is 9600 e Parity Parity Default is Even For details see the technical description part of the manual 38 V265M EN M A004 2 Local panel user interface 2 4 Configuration and parameter setting V265M EN M A004 SPA BUS Several instances of this protocol are possible e SPABUS addres for this device Addr This address has to be unique within the sy
97. ays Operation LALILIvIvIGIGILA indicators HHHHHHHH 888g rm Block matrix S Relay matrix Reset all latches Figure 8 5 1 Blocking matrix and output matrix Stage 1 Digital Inputs 144 V265M EN M A004 8 Control functions 8 6 Controllable objects 8 6 Controllable objects The relay allows controlling of six objects that is circuit breakers disconnectors and earthing switches Controlling can be done by select execute or direct control principle The logic functions can be used to configure interlocking for a safe controlling before the output pulse is issued The objects 1 6 are controllable while the objects 7 8 are only able to show the status Controlling is possible by the following ways o through the local HMI o through a remote communication o through a digital input The connection of an object to specific output relays is done via an output matrix object 1 6 open output object 1 65 close output There is also an output signal Object failed which is activated if the control of an object fails Object states Each object has the following states Setting Value Description Undefined 00 Object state bel Actual state of the object Close Undefined 11 Basic settings for controllable objects Each controllable object has the following settings Setting Value Description DI for obj open None any digital Open informati
98. can be configured as latched or non latched A non latched relay follows the controlling signal A latched relay remains activated although the controlling signal releases There is a common release latched signal to release all the latched relays This release signal resets all the latched output relays and indicators The reset signal can be given via a digital input via a keypad or through communication Any digital input can be used for resetting The selection of the input is done with the VAMPSET software under the menu Release output matrix latches Under the same menu the Release latches parameter can be used for resetting OUTPUT MATRIX T1 T2 A A2 A3 A4 A5 Alarm Trip A B C DR vOo1 e connected connected and latched Z Z Z Z Z T Z b gt start I gt trip gt gt start gt gt trip lo gt start lo gt trip lo gt gt start lo gt gt trip OutputMatrix Figure 8 4 1 Output matrix 143 8 5 Blocking matrix 8 Control functions 8 5 Blocking matrix By means of a blocking matrix the operation of any protection stage can be blocked The blocking signal can originate from the digital inputs DI1 to DI6 or it can be a start or trip signal from a protection stage or an output signal from the user s programmable logic In the block matrix Figure 8 5 1 an active blocking is indicated with a black dot in the crossing point of a blocking signal and the signal to be blocked Output_matix Output rel
99. ce will accept e ASDU 6 Time synchronization e ASDU 7 Initiation of general interrogation and e ASDU 20 General command The data in a message frame is identified by e type identification e function type and e information number These are fixed for data items in the compatible range of the protocol for example the trip of I gt function is identified by type identification 1 function type 160 and information number 90 Private range function types are used for such data items which are not defined by the standard e g the status of the digital inputs and the control of the objects The function type and information number used in private range messages is configurable This enables flexible interfacing to different master systems 158 V265M EN M A004 9 Communication 9 2 Communication protocols V265M EN M A004 For more information on IEC 60870 5 103 in Vamp devices refer to the IEC 103 Interoperability List document Parameters Parameter Value Unit Description Note Addr 1 254 An unique address within Set the system bit s bps Communication speed Set 9600 19200 Measint 200 10000 ms Minimum measurement Set response interval SyncRe Sync ASDU6 response time Set Sync Proc mode Msg Msg Proc Set An editable parameter password needed Parameters for disturbance record reading Parameter Value Unit Description
100. cnede Whit ebsiceetores 25 2 3 2 Measured Cate excises ccsweeseessyee socceueetenuseedancgeneepecie 26 2 3 3 Reading event register cccccceeeeeeeesesseeeeeeeees 28 2 3 4 Forced control Force cccceeeeeeeeeeeeeeeeeeeeeees 29 2 4 Configuration and parameter setting ccceeeeeeee 30 2 4 1 Parameter Setting ceeeeecseeeceeeeeeeeeeesseneeeeeeeeeees 31 2 4 2 Setting range limits ceceeeeeeeeeeeeeeeeeeeeeeeeeeeeees 32 2 4 3 Disturbance recorder menu DR eeeeeeeeeeeees 33 2 4 4 Configuring digital inputs DI eeeeeeeeeeeee 34 2 4 5 Configuring digital outputs DO eceeeeeeeeeeees 34 2 4 6 Protection menu PlObs cccccts cect cetsceasswesceesceciated Gmecwesins 34 2 4 7 Configuration menu CONF ccceeeeeeeeeeeeeeeeeeeeees 35 2 4 8 Protocol menu BUS cceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeees 37 2 4 9 Single line diagram editing ccceeeeeeeeeeeeeees 41 2 4 10 Blocking and interlocking configuration 0 41 3 VAMPSET PG Softwa icciicccsincciccccsccisanantucweuiccctensencnewawenceins 42 A ANNTLOGUCHON seese enaa aea aA aaaea 43 4 1 Main features esssnnneeeeeeeeeennrnnrreneserrrrnnnnnnnssrrrrnnnnnneeeeee 44 4 2 Principles of numerical protection techniques 45 5 Protection functions ces ctitcsttratnnceseiuddilasbrateemabscabliabintitantensute 47 5 1 Maximum number of protection stage
101. context the per unit refers to any nominal value For example for overcurrent setting 1 pu 1Xlen Root mean square Simple Network Time Protocol for LAN and WWW Trip circuit supervision Total harmonic distortion Coordinated Universal Time used to be called GMT Greenwich Mean Time World wide web internet 217 14 Construction 14 Construction PANEL MOUNTING VAMP 200 SERIES 190 7 48 mm 1 06 SEMI FLUSH VAMP 200 SERIES Raising trame A Fixing bracket VYX076 40 mm 71 67 169 mm 6 65 Standard for 200 series 20 VYX077 60 mm 2 36 149 mm 5 87 Standard for 200 series 0 79 VYX233 100 mm 3 94 109 mm 4 29 2x VYX199 needed 21 0 83 ae R Semi flush Panel mounting 218 V265M EN M A004 15 Order information 15 Order information When ordering please state the ordering code ves OOOO Nominal current HV amp LV side A 1 1A amp 1A 3 1A amp 5A 4 5A amp 1A 5 SA amp 5A Nominal earth fault currents lo amp l o A 5A amp 5A 5A amp 1A 1A amp 5A 1A amp 1A 00ON LY Frequency Hz 7 Standard relay Supply voltage V A 40 265Vac de 18 36Vdc 40 265Vac dc ARC Protection 18 36Vdc ARC Protection 40 265Vac dc DI19 DI20 arc channel Optional 18 36Vdc DI19 DI20 arc channel Optional moog w 1 Optional hardware A None B Plastic Plastic se
102. control mode Frequency 50 000 Hz Note The sample rate of the comtrade file has to be 32 cycle 625 s when 50 114 Hz is used The channel names have to correspond to the channel names in Vamp relays IL1 IL2 IL3 lo1 lo2 U12 U23 UL1 UL2 UL3 and Uo V265M EN M A004 6 Supporting functions 6 3 Current transformer supervision 6 3 V265M EN M A004 Current transformer supervision The relay supervise the external wiring between the relay terminals and current transformers CT and the CT them selves Furthermore this is a safety function as well since an open secondary of a CT causes dangerous voltages The CT supervisor function measures phase currents If one of the three phase currents drops below Imin lt setting while another phase current is exceeding the Imax gt setting the function will issue an alarm after the operation delay has elapsed Setting parameters of CT CT supervisor CTSV Parameter Value Unit Default Description Imax gt A Upper setting for CT supervisor current scaled to primary value calculated by relay Imin lt A Lower setting for CT supervisor current scaled to primary value calculated by relay Imax gt 0 0 10 0 xin 2 0 Upper setting for CT supervisor Imin lt 0 0 10 0 xin 0 2 Lower setting for CT supervisor t gt 0 02 600 0 s 0 10 Operation delay CT on On
103. d for one of the serial ports Serial ports are configured in menu Bus 4 The menu is visible only if the stage is enabled 5 Objects are circuit breakers disconnectors etc Their position or status can be displayed and controlled in the interactive mimic display 6 There are two extra menus which are visible only if the access level operator or configurator has been opened with the corresponding password 7 Detailed protocol configuration is done with VAMPSET 17 2 2 Local panel operations 2 Local panel user interface 2 2 2 18 Menu structure of protection functions The general structure of all protection function menus is similar although the details do differ from stage to stage As an example the details of the second overcurrent stage I gt gt menus are shown below First menu of I gt gt 50 51 stage first menu AV gt I gt gt STATUS 50 51 ExDO Status SCntr TCntr SetGrp SGrpDI Force Figure 2 2 2 1 First menu of I gt gt 50 51 stage This is the status start and trip counter and setting group menu The content is e Status The stage is not detecting any fault at the moment The stage can also be forced to pick up or trip if the operating level is Configurator and the force flag below is on Operating levels are explained in chapter 2 2 5 e SCntr5 The stage has picked up a fault five times since the last reset of restart This value can be cleared if the operating
104. d secondary CT ratings are set according to the actual CT ratios Set motor nominal current Settings of the differential protection Al gt 87 function shall be enabled for differential protection Al gt pick up setting range is user selectable from 5 to 50 Slope 1 can be set to 5 Ibias for start of slope 2 can be set to 3 x In Slope 2 can be set to 50 If CTs are saturating at through faults the Slope 2 settings must be changed accordingly Al gt 2 harmonic block enable can be set OFF disabled Al gt 2 harmonic block limit can be disregarded and the factory default setting can be left intact 57 5 5 Differential overcurrent protection Al gt 87 5 Protection functions Motor differential protection using flux balancing principle Ll VAMP 265 X1 1 X1 2 X1 3 X1 4 X1 5 X1 6 Leave unconnected xe KK DA RG PE Figure 5 5 5 VAMP 265M connected as a motor differential protection using 3 core balance CT s connected using flux balancing principle In this application mode the settings in VAMP 265M relay s menu SCALING should be set as described in the following section NOTE If motor protection functions are used connect the differential 58 connection to the LV side CT inputs I L1 I L2 I L3 CT Settings CT Primary and CT Secondary settings shall be set according to the actual core balance CT ratios CT Primary and CT Secondary settings c
105. d stage 49 4 lo gt 5 1st earth fault stage 50N 51N 4 lo gt gt 3 2nd earth fault stage 50N 51N 4 lo gt gt gt 3 3rd earth fault stage 50N 51N 4 V265M EN M A004 2 Local panel user interface 2 2 Local panel operations Main menu Number of Description ANSI Note menus code lo gt gt gt gt 3 4th earth fault stage 50N 51N 4 Prg1 3 1st programmable stage 4 Prg2 3 2nd programmable stage 4 Prg3 3 3rd programmable stage 4 Prg4 3 4th programmable stage 4 Prg5 3 5th programmable stage 4 Prg6 3 6th programmable stage 4 Prg7 3 7th programmable stage 4 Prg8 3 8th programmable stage 4 CBFP 3 Circuit breaker failure protection 50BF 4 CBWE 4 Circuit breaker wearing supervision 4 CTSV 1 CT supervisor 4 CT SV 1 CT supervisor 4 Arcl gt 4 Optional arc protection stage for phase to phase faults 50ARC 4 and delayed light signal Arclo gt 3 Optional arc protection stage for earth faults Current 50NARC 4 input 101 Arclo2 gt 3 Optional arc protection stage for earth faults Current 50NARC 4 input 102 OBJ 11 Object definitions 5 Lgic 2 Status and counters of user s logic 1 CONF 10 2 Device setup scaling etc 6 Bus 13 Serial port and protocol configuration 7 Diag 6 Device selfdiagnosis Notes V265M EN M A004 1 Configuration is done with VAMPSET 2 Recording files are read with VAMPSET 3 The menu is visible only if protocol ExternallO is selecte
106. ddr 1 247 Modbus address for the Set device Broadcast address 0 can be used for clock synchronizing Modbus TCP uses also the TCP port settings bit s 1200 bps Communication speed for Set 2400 Modbus RTU 4800 9600 19200 Parity None Parity for Modbus RTU Set Even Odd Set An editable parameter password needed 154 V265M EN M A004 9 Communication 9 2 Communication protocols 9 2 3 Profibus DP The Profibus DP protocol is widely used in industry An external VPA 3CG or an internal Profibus module see the order code in chapter 15 is required Device profile continuous mode In this mode the device is sending a configured set of data parameters continuously to the Profibus DP master The benefit of this mode is the speed and easy access to the data in the Profibus master The drawback is the maximum buffer size of 128 bytes which limits the number of data items transferred to the master Some PLCs have their own limitation for the Profibus buffer size which may further limit the number of transferred data items Device profile Request mode Using the request mode it is possible to read all the available data from the VAMP device and still use only a very short buffer for Profibus data transfer The drawback is the slower overall speed of the data transfer and the need of increased data processing at the Profibus master as every data item must be separately requested by the master NOTE
107. de Ict Rated primary current of the CT primary side or secondary side Using slightly smaller safety factor than indicated in the table will increase the setting inaccuracy Protection application Safety factor c Overcurrent 2 Earth fault cable transformer 3 Earth fault overcurrent sum of three phase currents 2 6 Transformer differential A winding or unearthed Y 3 winding Transformer differential earthed Y winding 4 Generator differential 3 Formula to solve needed CT power SN By replacing the complex power terms with corresponding resistances in Equation 10 4 1 3 we get Equation 10 4 2 2 Reor Ry E Rep Ry R k k where the nominal burden resistance is _ Sy N 2 I nersec Ret Winding resistance See Figure 10 4 1 1 Rw Wiring resistance from CT to the relay and back RL Resistance of the protection relay input Sn Nominal burden of the CT NCTsec Nominal secondary current of the CT Sensitive earth fault current settings lt 5 x ly should be avoided in this configuration because a set of three CTs are not exactly similar and will produce some secondary residual current even though there is no residual current in the primary side V265M EN M A004 10 Applications 10 4 Current Transformer Selection V265M EN M A004 By solving Syn and substituting ka according Equation 10 4 2 2 we get Equation 10 4 2 3 cI Sy gt Sate Ry R Ror
108. de and phase when used near their nominal values At very low and at very high currents they are far from ideal For over current and differential protection the actual performance of CTs at high currents must be checked to ensure correct function of the protection relay CT classification according IEC 60044 1 1996 CT model Fee dy Rte So ELETE nh Aa E ait Aes Ss at meee r CTmodel Figure 10 4 1 1 A CT equivalent circuit Lm is the saturable magnetisation inductance L is secondary of an ideal current transformer Ror is resistance of the CT secondary winding Rw is resistance of wiring and R is the burden i e the protection relay Composite error c Composite error is the difference between the ideal secondary current and the actual secondary current under steady state conditions It includes amplitude and phase errors and also the effects of any possible harmonics in the exciting current Equation 10 4 1 1 1 T ate R dt 0 Ec 7 100 P T Cycle time Ky Rated transformation ratio Inprmary INsecondary is Instantaneous secondary current ip Instantaneous primary current Ip Rms value of primary current 171 10 4 Current Transformer Selection 10 Applications NOTE All current based protection functions of VAMP relays except arc protection thermal protection and 2nd harmonic blocking functions are using the fundamental frequency component of the measured current The IEC formula includes an RMS v
109. digital inputs DI19 and DI20 are dry see the ordering code for this option V ax 24 Vdc 240 Vdc i VAMP relay Digitalinput __ j ____ Trip relay AHH Alarm relay for trip circuit failure Trip circuit failure alarm relay compartment circuit breaker compartment Figure 10 6 1 1 Trip circuit supervision using a single dry digital input and an external resistor R The circuit breaker is in the closed position The supervised circuitry in this CB position is double lined The digital input is in active state when the trip circuit is complete This is applicable for dry inputs DI7 DI20 V265M EN M A004 10 Applications 10 6 Trip Circuit Supervision VAMP relay V x 24 Vdc 240 Vdc Digitalinput __ __ I I l l l L L l l Trip relay AF Alarm relay for trip circuit failure Trip circuit failure alarm relay compartment circuit breaker compartment close control eee TCS1Dlopen Figure 10 6 1 2 Trip circuit supervision using a single dry digital input when the circuit breaker is in open position Note If for example DI7 is used for trip circuit supervision the usage of DI8 DI14 is limited to the same circuitry sharing the Vaux in the common terminal DIGITAL INPUTS DIGITAL INPUTS Figure 10 6 1 3 An example of digital input DIZ configuration for trip circuit supervision with one dry digital input OUTPUT MATRIX 11 T2 T3 T4 al a2 connect
110. ding to the requirements of the intended application 5 1 Maximum number of protection stages in one application The device limits the maximum number of enabled stages to about 30 depending of the type of the stages For more information please see the configuration instructions in chapter 2 4 in the first part of this manual 5 2 List of protection functions IEEE IEC symbol Function name ANSI code 50 51 3I gt 31 gt gt 3l gt 3 gt gt Overcurrent protection 37 I lt Undercurrent protection 87 Al gt Al gt gt Differential overcurrent protection 46 l gt l o gt Current unbalance protection 47 l2 gt gt Phase reversal incorrect phase sequence protection 48 l gt Stall protection 66 N gt Frequent start protection 49 T gt Thermal overload protection l gt lo gt gt Earth fault protection 50N 51N l gt gt gt l gt gt gt gt 51F2 l gt Second harmonic O C stage 51F5 lis gt Fifth harmonic O C stage 50BF CBFP Circuit breaker failure protection 99 Prg1 8 Programmable stages 50ARC Arcl gt Arcl gt Optional arc fault protection 50NARC Arclo gt Arclos gt V265M EN M A004 47 5 3 General features of protection 5 Protection functions stages 5 3 48 General features of protection stages Setting groups Most stages have two setting groups Changing between setting groups can be controlled manually or using any of the digital inputs
111. e Undercurrent protection l lt 37 The undercurrent unit measures the fundamental frequency component of the phase currents The stage I lt can be configured for definite time characteristic The undercurrent stage is protecting rather the device driven by the motor e g a submersible pump than the motor itself 67 5 8 Undercurrent protection I lt 37 5 Protection functions Parameters of the undercurrent stage I lt 37 Parameter Value unit Description Status Status Staus of the stage SCnir Start counter Start reading TCntr Trip counter Trip reading SetGrp 1or2 Active setting group SetGrpDI Digital signal to select the active B setting group Dix None Vix Digital input LEDx Virtual input VOx LED indicator signal Virtual output Force On off Force flag for status forcing for test purposes This is acommon flag for all stages and output relays too This flag is automatically reset 5 minutes after the last front panel push button pressing Set ILmin A Min value of phase currents IL1 IL2 IL3 in primary value Status Status of protection stage I lt A Start detection current scaled to primary value calculated by relay I lt lmot Setting value in percentage of Imot t lt s Operation time delay s NoCmp lmot Block limit NoCmp 60A Block limit scaled to primary value calculated by relay Recorded Log Start and trip time value
112. e VAMPSET manual VVAMPSET EN M xxxx single line diagram 1 Bay OA 0 000A OkW OKvar K Figure 2 4 9 1 Single line diagram Blocking and interlocking configuration The configuration of the blockings and interlockings is done with the VAMPSET software Any start or trip signal can be used for blocking the operation of any protection stage Furthermore the interlocking between objects can be configured in the same blocking matrix of the VAMPSET software For more information please refer to the VAMPSET manual VVAMPSET EN M xxxx 41 3 VAMPSET PC software 42 VAMPSET PC software The PC user interface can be used for e On site parameterization of the relay e Loading relay software from a computer e Reading measured values registered values and events to a computer e Continuous monitoring of all values and events Two RS 232 serial ports are available for connecting a local PC with VAMPSET to the relay one on the front panel and one on the rear panel of the relay These two serial ports are connected in parallel However if the connection cables are connected to both ports only the port on the front panel will be active To connect a PC to a serial port use a connection cable of type VX 003 3 The VAMPSET program can also use TCP IP LAN connection Optional hardware is required There is a free of charge PC program called VAMPSET available for configuration and setting of VAMP relays Please download
113. e controlled by digital inputs virtual inputs mimic display communication logic and manually There are two identical stages available with independent setting parameters Parameters of the programmable stages PrgN 99 Parameter Value Unit Description Note Status Current status of the stage Blocked Start F Trip F SCnir Cumulative start counter C TCntr Cumulative trip counter C SetGrp 1 or2 Active setting group Set SGrpDI Digital signal to select the active Set setting group L None Dix Digital input VIX Virtual input LEDx LED indicator signal VOx Virtual output Force Off Force flag for status forcing for Set On test purposes This is a common flag for all stages and output relays too Automatically reset by a 5 minute timeout Link See Name for the supervised signal Set table above See table Value of the supervised signal above Cmp Mode of comparison Set gt Over protection lt Under protection Pickup Pick up value scaled to primary level Pickup pu Pick up setting in pu Set t s Definite operation time Set Hyster Dead band setting Set NoCmp pu Minimum value to start under Set comparison Mode lt Set An editable parameter password needed C Can be cleared to zero F Editable when force flag is on Recorded values of the latest eight faults There are detailed information available of the eight latest faults Time stamp
114. e delay This parameter is important when grading the operation time delay settings between relays I traorr jp lt 50 m DELAY SETTING gt tpu trer e a TRIP CONTACTS EES i Figure 5 3 1 Definition for retardation time If the delay setting would be slightly shorter an unselective trip might occur the dash line pulse For example when there is a big fault in an outgoing feeder it might start i e pick up both the incoming and outgoing feeder relay However the fault must be cleared by the outgoing feeder relay and the incoming feeder relay must not trip Although the operating delay setting of the incoming feeder is more than at the outgoing feeder the incoming feeder might still trip if the operation time difference is not big enough The difference must be more than the retardation time of the incoming feeder relay plus the operating time of the outgoing feeder circuit breaker Error Reference source not found shows an overcurrent fault seen by the incoming feeder when the outgoing feeder does clear the fault If the operation delay setting would be slightly shorter or if the fault duration would be slightly longer than in the figure an unselective trip might happen the dashed 40 ms pulse in the figure In VAMP relays the retardation time is less than 50 ms 49 5 3 General features of protection 5 Protection functions stages Reset time release time Figure 5 3 2 shows an example of re
115. e fundamental frequency rms value of one cycle updated every 20 ms 113 6 2 Disturbance recorder 6 Supporting functions Running virtual comtrade files with VAMP relays Virtual comtrade files can be run with VAMP relays with the v 10 74 software or a later version Relay behaviour can be analysed by playing the recorder data over and over again in the relay memory i of opening the VAMPSET setting tool Go to Disturbance record and select Open A Select the comtrade file from you hard disc or equivalent VAMPSET is now ready to read the recording 3 The virtual measurement has to be enabled B in order to send record data to the relay C 4 Sending the file to the relay s memory takes a few seconds Initiate playback of the file by pressing the Go button D The Change to control mode button takes you back to the virtual measurement a Zls olc v B able virtual measurement ate nem 2 ED EMTDC_Simulation 1 mee Readi d fil eading recor le yi Cycl ie a S i 1 lector mmm TT f Sending record data to device 078 1515457 mem C47F26 FD F4 FE O4 FE 12 FE OC FE 1A FE 16 FE 0O FEOS TD a 077 15 54 57 mem C47F40 FD F6 FD F4 FD EE FD ES FD E2 FD CA FD D4 FD C 085 155458 mem C49010 OS G7 0S A7 05 B1 OS 01 0S 1D 04 8578 40 5800 3A amaj oe Enable virtual measurement E E ET Protected target VAMP 52 Change to
116. e name time and firmware version Meas 13 Phase and winding current measurements current differential and angles winding angles lo f Phase sequence symmetric currents and harmonics Imax 9 Time stamped min amp max of currents Month 21 Maximum values of the last 31 days and the last twelve months Evnt 2 Events DR 2 Disturbance recorder 2 Runh 2 Running hour counter Active time of a selected digital input and time stamps of the latest start and stop TIMR 6 Day and week timers DI 5 Digital inputs including virtual inputs DO 4 Digital outputs relays and output matrix ExtAl 3 External analogue inputs 3 ExDI 3 External digital inputs 3 ExDO 3 External digital outputs 3 Prot 8 Protection counters combined overcurrent status protection status protection enabling event enabling overcurrent remote scaling and block matrix Mstat 1 Motor status N gt 4 Frequent start protection 66 4 Al gt 7 1 differential stages 87 4 Al gt gt 5 2 differential stage 87 4 I gt 5 1 overcurrent stage primary side 50 51 4 I gt gt 3 2 overcurrent stage primary side 50 51 4 r gt 5 1 overcurrent stage secondary side 50 51 4 gt gt 3 2 overcurrent stage secondary side 50 51 4 Ist gt 3 Stall protection stage 48 4 I lt 3 Undercurrent stage 37 4 12 gt 3 Current unbalance stage primary side 46 4 2 gt gt 3 Phase reversal incorrect phase 46 4 sequence stage 2 gt 3 Current unbalance stage secondary side 46 4 T gt 3 Thermal overloa
117. e rated current 1 pu Sn Rated apparent power of the protected device Un Rated line to line voltage of the protected device For residual currents and Arcl gt stage 1 pu 1xCTsec for secondary side and 1 pu 1xCTpr for primary side Phase current scaling Residual current 319 excluding Arcl gt stage scaling and phase current scaling for Arcl gt stage L sxc CT pry L sec secondary per unit p p a Pus oe CT src Ly CT sc Ty per unit gt secondary sge Lpy CT sec 27 I gnc Lpy CT sc CTs Example 1 Secondary to per unit and percent for phase currents excluding Arcl gt CTpri 150 1 CTsec 800 5 Sn 25 MVA Un 110 kV U n 21 kV Current injected to the relay s primary side input is 175 mA and 859 mA for the secondary side input The rated current on HV and LV side will be In 25 MVA V3 x 110 kV 131 2 A l n 25 MVA V3 x 21 kV 687 3 A Per unit currents are ley 0 175x150 1x131 2 0 20 pu 20 xly HV side I py 0 859x800 5x687 3 0 20 pu 20 LV side V265M EN M A004 7 Measurement functions 7 7 Primary secondary and per unit scaling V265M EN M A004 Example 2 Secondary to per unit for Arcl gt CT 750 5 Current injected to the relay s inputs is 7 A gt Per unit current is Ipy 7 5 1 4 pu 140 Example 3 Per unit and percent to secondary for phase currents excluding Arcl gt CTpri 150 1 CTsec 800 5 Sn 25 MVA
118. ed connected and latched DI Figure 10 6 1 4 An example of output matrix configuration for trip circuit supervision with one dry digital input V265M EN M A004 179 10 6 Trip Circuit Supervision 10 Applications 180 Example of dimensioning the external resistor R Uaux 110 Vdc 20 10 Auxiliary voltage with tolerance Upi 18 Vdc Threshold voltage of the digital input Ibi 3 mA Typical current needed to activate the digital input including a 1 mA safety margin Poot SOW Rated power of the open coil of the circuit breaker If this value is not known 0 Q can be used for the Rooil Umin Uaux 20 88 V Umax U aux 10 121 V Rooit U aux P 242 Q The external resistance value is calculated using Equation 10 6 1 1 Equation 10 6 1 1 U umn U pr I DI Rosi I DI R R 88 18 0 003 242 0 003 23 1 KQ In practice the coil resistance has no effect By selecting the next smaller standard size we get 22 KQ The power rating for the external resistor is estimated using Equation 10 6 1 2 and Equation 10 6 1 3 The Equation 10 6 1 2 is for the CB open situation including a 100 safety margin to limit the maximum temperature of the resistor Equation 10 6 1 2 P 2 I R P 2 0 003 2x22000 0 40 W Select the next bigger standard size for example 0 5 W When the trip contacts are still closed and the CB is already open the resistor has to withstand much higher pow
119. ed as Equation 10 3 1 2 Set Iser Setting value of the relay as secondary value Voltage limitation During heavy inside faults the voltage in the secondary circuit may rise to several kilovolts depending on the fault currents CT properties and the stabilizing resistor Rs If the secondary voltage would exceed 2 kV it should be limited using a voltage dependent resistor VDR The peak voltage according a linear CT model is Equation 10 3 2 1 CT V TL yax Bor Ry Rs PRIM Maximum fault current when the fault is inside the protected D gt xX T l zone CTsec Nominal secondary current of the CT CTpri Nominal primary current of the CT Ret Resistance of CT secondary Rw Total resistance of wiring connections relay input etc Rs Stabilizing resistor according Equation 10 3 1 2 The peak voltage of a saturating CT can be approximated using P Mathews formula Equation 10 3 2 2 Vp 24 2VkpVp Vrp Vkp 7 Knee point voltage of the CT The secondary voltage at which a 50 increase of primary current is needed to increase the secondary voltage by 10 Vp Peak voltage according linear model of a CT This approximating formula does not hold for an open circuit condition and is inaccurate for very high burden resistances Actual operating sensitivity The differential scheme will multiply the fault current by two thus increasing the sensitivity from the actual setting The quiescent cu
120. ed fault log 22 V265M EN M A004 2 Local panel user interface 2 2 Local panel operations 2 2 5 V265M EN M A004 Operating levels The relay has three operating levels User level Operator level and Configurator level The purpose of the access levels is to prevent accidental change of relay configurations parameters or settings USER level Use Possible to read e g parameter values measurements and events Opening Level permanently open Closing Closing not possible OPERATOR level Use Possible to control objects and to change e g the settings of the protection stages Opening Default password is 1 Setting state Push Os Closing The level is automatically closed after 10 minutes idle time Giving the password 9999 can also close the level CONFIGURATOR level Use The configurator level is needed during the commissioning of the relay E g the scaling of the voltage and current transformers can be set Opening Default password is 2 Setting state Push Qs Closing The level is automatically closed after 10 minutes idle time Giving the password 9999 can also close the level 23 2 2 Local panel operations 2 Local panel user interface 24 Opening access 1 Push O and on the front panel ENTER PASSWORD a kkO v Figure 2 2 5 1 Opening the access level 2 Enter the password needed for the desired
121. ee power factor PF Negative sign indicates reverse power Current transformer Nominal primary value of current transformer Nominal secondary value of current transformer See hysteresis Digital input Digital output output relay Data set ready An RS232 signal Input in front panel port of VAMP relays to disable rear panel local port Daylight saving time Adjusting the official local time forward by one hour for summer time Data terminal ready An RS232 signal Output and always true 8 Vdc in front panel port of VAMP relays Fast Fourier transform Algorithm to convert time domain signals to frequency domain or to phasors l e dead band Used to avoid oscillation when comparing two near by values Nominal current of the Io input of the relay Nominal current of the Io2 input of the relay Nominal current of lo input in general Nominal current Rating of CT primary or secondary International Electrotechnical Commission An international standardization organisation Institute of Electrical and Electronics Engineers Abbreviation for communication protocol defined in standard IEC 60870 5 103 Local area network Ethernet based network for computers and relays Output relays and indication LEDs can be latched which means that they are not released when the control signal is releasing Releasing of lathed devices is done witha separate action Network time protocol for LAN and WWW Per unit Depending of the
122. en 2 86 per unit e Load 0 99xIn The average load current before the fault has been 0 99 pu e EDly 81 The elapsed operation delay has been 81 of the setting 0 60 s 0 49 s Any registered elapsed delay less than 100 means that the stage has not tripped because the fault duration has been shorter than the delay setting e SetGrp 1 The setting group has been 1 This line can be reached by i K pressing Mid and several times s V265M EN M A004 2 Local panel user interface 2 2 Local panel operations 2 2 3 V265M EN M A004 Setting groups Most of the protection functions of the relay have two setting groups These groups are useful for example when the network topology is changed frequently The active group can be changed by a digital input through remote communication or locally by using the local panel The active setting group of each protection function can be selected separately Figure 2 2 3 1 shows an example where the changing of the I gt setting group is handled with digital input one SGrpDI If the digital input is TRUE the active setting group is group two and correspondingly the active group is group one if the digital input is FALSE If no digital input is selected SGrpDI the active group can be selected by changing the value of the parameter SetGrp group AV gt I gt STATUS Status SCnitr TCntr SetGrp SGrpDI Force Figure 2 2 3 1 Example of protection submenu with setting
123. er Equation 10 6 1 3 for this short time Equation 10 6 1 3 2 P U max R P 121 2 22000 0 67 W V265M EN M A004 10 Applications 10 6 Trip Circuit Supervision V265M EN M A004 A 0 5 W resistor will be enough for this short time peak power too However if the trip relay is closed for longer time than a few seconds a 1 W resistor should be used Using any of the non dry digital inputs DI1 DI6 In this scheme an auxiliary relay is needed to connect the wet digital input to the trip circuit Figure 10 6 1 5 The rated coil voltage of the auxiliary relay is selected according the rated auxiliary voltage used in the trip circuit The operating voltage range of the relay should be as wide as possible to cover the tolerance of the auxiliary voltage In this application using the other wet inputs for other purposes is not limited unlike when using the dry inputs V ax 110 Vdc VAMP 2xx relay Digital input 1 6 Alarm relay for trip ay i Trip circuit circuit failure failure alarm relay compartment circuit breaker compartment close control Relay K1 Phoenix Contact EMG 17 REL KSR 120 21 21 LC Au Coil 96 127 V 20 kQ Width 17 5 mm Assembly EN 50022 mounting rail TCS1DI closed Figure 10 6 1 5 Trip circuit supervision using one of the VAMP 200 series internally wetted digital input DI1 DI6 and auxiliary relay K1 and an external resistor R The circuit breaker is in the closed pos
124. f phase currents THDIL1 Meas HARM DISTORTION Total harmonic distortion of phase current IL1 THDIL2 Meas HARM DISTORTION Total harmonic distortion of phase current IL2 THDIL3 Meas HARM DISTORTION Total harmonic distortion of phase current IL3 THDI L Meas HARM DISTORTION Total harmonic distortion of the mean value of phase currents THDI L1 Meas HARM DISTORTION Total harmonic distortion of phase current L1 THDI L2 I HARM DISTORTION Total harmonic distortion of phase current L2 THDI L3 I HARM DISTORTION Total harmonic distortion of phase current I L3 Diagram HARMONICS of IL1 Harmonics of phase current IL1 see Figure 2 3 2 1 Diagram I HARMONICS of IL2 Harmonics of phase current IL2 see Figure 2 3 2 1 Diagram I HARMONICS of IL3 Harmonics of phase current IL3 see Figure 2 3 2 1 Diagram I HARMONICS of 1 L1 Harmonics of phase current L1 see Figure 2 3 2 1 Diagram I HARMONICS of I L2 Harmonics of phase current I L2 see Figure 2 3 2 1 Diagram I HARMONICS of I L3 Harmonics of phase current I L3 see Figure 2 3 2 1 V265M EN M A004 3579 11 13 15 Figure 2 3 2 1 Example of harmonics bar display 27 2 3 Operating measures 2 Local panel user interface 2 3 3 28 Reading event register The
125. fault value and elapsed delay V265M EN M A004 5 Protection functions 5 17 Inverse time operation 5 17 V265M EN M A004 Recorded values of the programmable stages PrgN 99 Parameter Value Unit Description yyyy mm dd Time stamp of the recording date hh mm ss ms Time stamp time of day Fit pu Fault value EDly Elapsed time of the operating time setting 100 trip SetGrp 1 Active setting group during fault 2 Inverse time operation The inverse time operation i e inverse delay minimum time IDMT type of operation is available for several protection functions The common principle formulae and graphic representations of the available inverse delay types are described in this chapter Inverse delay means that the operation time depends on the measured real time process values during a fault For example with an overcurrent stage using inverse delay a bigger a fault current gives faster operation The alternative to inverse delay is definite delay With definite delay a preset time is used and the operation time does not depend on the size of a fault Stage specific inverse delay Some protection functions have their own specific type of inverse delay Details of these dedicated inverse delays are described with the appropriate protection function Operation modes There are three operation modes to use the inverse time characteristics e Standard delays Using standard de
126. g 100 trip SetGrp 1 Active setting group during fault 2 63 5 7 Stall protection IST gt 48 5 Protection functions 5 7 64 Stall protection Isrt gt 48 The stall protection unit lst gt measures the fundamental frequency component of the phase currents Stage Ist gt can be configured for definite time or inverse time operation characteristic The stall protection stage protects the motor against prolonged starts caused by e g a stalled rotor The pick up setting Ist gt is the current detection level for a motor start While the current has been less than 10 of Ivor and then within 200 milliseconds exceeds Ist gt the stall protection stage starts to count the operation time T according to Equation 5 7 1 The equation is also drawn in Figure 5 7 1 When current drops below 120 x Imor the stall protection stage releases Stall protection is active only the start of the motor Equation 5 7 1 re I START I T Operation time Istant Start current of the motor Default 6 00xlmoT Measured current during start Maximum allowed start time for the motor Tsrarr where MEAS IMEAS Tsart TIME Tsrart IstartMin Figure 5 7 1 Operation time delay of the stall protection stage lsr gt ISTART CURRENT If the measured current is less than the specified start current Istart the operation time will be longer than the specified start time Tstart and vice versa V265M
127. g mode infoset_I Info SET I gt Setting for stage I gt Type i32 dd Range 0 10 5 00 ENTER password CANCEL back to menu Figure 2 4 2 2 Allowed setting ranges show in the display 32 V265M EN M A004 2 Local panel user interface 2 4 Configuration and parameter setting 2 4 3 Disturbance recorder menu DR Via the submenus of the disturbance recorder menu the following functions and features can be read and set DISTURBANCE RECORDER Manual trigger ManTrg Status Status Clear oldest record Clear Clear all records CIrAll Recording completion Stored Count of ready records ReadyRec RECORDER SETTINGS Recording mode Mode Sample rate SR Recording time Time Pre triggering time PreTrig Max length of one record MaxLen Count of ready records ReadyRec REC CHANNELS e Add alink to the recorder AddCh e Clear link ClrCh Available links IL1w IL2w IL3w PLiw L2w L3w IL1RMS IL2RMS ILSRMS IL1RMS IL2RMS ILSRMS ILmin ILmax I Lmin I Lmax T e 1IL1 IL2 IL1 PL1 L2 PL3 e 02 lo1 e f e loCalc l oCalc e 11 12 11 172 e 12 11 12 Imot 12 11 1 2 Imot e IL VL e DO DI e THD1 THD2 THD3 e diLi dIL2 dIL3 e e e e e V265M EN M A004 33 2 4 Configuration and parameter 2 Local panel user interface setting 2 4 4 Configuring digital inputs DI The following functions can be read and set via the submenus of the digit
128. ge or there is a communication problem between the main CPU and the Profibus ASIC For details see the technical description part of the manual 39 2 4 Configuration and parameter 2 Local panel user interface setting DNP3 Only one instance of this protocol is possible e Bit rate bit s Default is 9600 e Parity e Addres for this device SlvAddr This address has to be unique within the system Master s address MstrAdadr LLTout LLRetry APLTout CnfMode DBISup e SyncMode For further details see the technical description part of the manual IEC 60870 5 101 e Bit rate bit s Default is 9600 e Parity e Link layer address for this device LLAddr e LLAddrSize e ASDU address ALAddr e lOAddrSize e COTSize e TTFormat e MaasFormat e DbandEna e DbandCycle For details see the technical description part of the manual DEVICENET e Bit rate bit s Default is 125kbps e Slave address SlvAdadr e ActSlvAddr e Prolnst e ProSize e Conlnst e ConSize 40 V265M EN M A004 2 Local panel user interface 2 4 Configuration and parameter setting 2 4 9 2 4 10 V265M EN M A004 ETHERNET IP e Mcast IP e McastTTL e Prolnst e InclHeader e ProSize e Conlnst e InclHeader e ConSize Single line diagram editing The single line diagram is drawn with the VAMPSET software For more information please refer to th
129. gt Current unbalance protection 47 lo gt gt Phase reversal incorrect phase sequence protection 48 I gt Stall protection 66 N gt Frequent start protection 49 T gt Thermal overload protection lo gt 50N 51N l gt Earth fault protection lo gt gt gt lo gt gt gt gt 51F2 l2 gt Second harmonic O C stage 51F5 ls gt Fifth harmonic O C stage 50BF CBFP Circuit breaker failure protection 99 Prg1 8 Programmable stages 50ARC Arcl gt Arcl gt Optional arc fault protection 50NARC Arcloi gt Arclo2 gt Further the relay includes a disturbance recorder Arc protection is optionally available The relay communicates with other systems using common protocols such as the Modbus RTU ModbusTCP Profibus DP IEC 60870 5 103 SPA bus DNP 3 0 DNP Ethernet IEC 61850 and IEC 60870 5 101 Devicenet and EtherNetIP 1 2 User interface 1 General 1 2 User interface The relay can be controlled in three ways e Locally with the push buttons on the relay front panel e Locally using a PC connected to the serial port on the front panel or on the rear panel of the relay both cannot be used simultaneously e Via remote control over the remote control port on the relay rear panel 1 3 Operating Safety AWARNING HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH A live current transformer secondary circuit must not be opened without turning off the primary side of the transformer and short circuiting transformer
130. he IO devices After changing EXTENSION port protocol to ExternallO restart the relay and read all settings with VAMPSET 199 11 6 External I O extension modules 11 Connections 200 External analog inputs configuration VAMPSET only Description EXTERNAL ANALOG INPUTS HoldingR HoldingR Communication read errors X 32000 32000 Y2 Scaled value Y 1000 1000 Point 2 X2 Modbus value gt Y1 Scaled value Point 1 8 X1 Modbus value eit 32000 32000 Subtracted from Modbus Off value before running XY set scaling InputR or HoldingR Modbus register type 1 9999 Modbus register for the measurement 1 247 Modbus address of the I O device C F K mA Ohm or V A Unit selection Active value On Off Enabling for measurement V265M EN M A004 11 Connections 11 6 External I O extension modules V265M EN M A004 Alarms for external analog inputs Analog input alarms have also matrix signals Ext Alx Alarm1 and Ext Alx Alarm2 ange Description aj 2 2 10000 Hysteresis for alarm limits 3 3121x107 a 21x107 Limit setting A A E amp hs lt Alarm Active state 3 j2 3 2121x107 oe n 24x107 Limit setting Z A z E E amp E l lt Alarm Active state JBE i A Active value 1 1 9999 Modbus register for the measurement
131. he definite delay type and setting the delay to its minimum an instantaneous ANSI 50 operation is obtained Figure 5 6 1 shows a functional block diagram of the I gt overcurrent stage with definite time and inverse time operation time Figure 5 6 2 shows a functional block diagram of the I gt gt overcurrent stage with definite time operation delay Inverse operation time Inverse delay means that the operation time depends on the amount the measured current exceeds the pick up setting The bigger the fault current is the faster will be the operation Accomplished inverse delays are available for the I gt stage The inverse delay types are described in chapter 5 17 The relay will show the currently used inverse delay curve graph on the local panel display Inverse time limitation The maximum measured secondary current is 50xlyn This limits the scope of inverse curves with high pick up settings See chapter 5 17 for more information Setting groups There are two settings groups available for each stage Switching between setting groups can be controlled by digital inputs virtual inputs mimic display communication logic and manually V265M EN M A004 59 5 6 Overcurrent protection I gt 50 51 5 Protection functions 3visblock Start Register event Trip Register event Setting gt s Delay Definite inverso Inverse time Multiplier Enable events characteristics Figure 5 6 1 Block diagram of the three phase
132. his means that all the signal filtering protection and control functions are implemented through digital processing The numerical technique used is primarily based on an adapted Fast Fourier Transformation FFT algorithm Synchronized sampling of the measured voltage and current signals is used The sample rate is 32 samples cycle within the frequency range 45 Hz 65 Hz The frequency is measured from the current signals L1 and L2 and used to synchronize the sampling rate Therefore secondary testing of a brand new device should be started by injecting stabile system frequency current signal in nominal magnitude The learned frequency is used for sampling rate synchronization when the measured current is less than 20 of nominal value The local network frequency can also be manually given for the relay Apart from the FFT calculations some protection functions also require the symmetrical components to be calculated for obtaining the positive negative and zero phase sequence components of the measured quantity For example the function of the unbalanced load protection stage is based on the use of the negative phase sequence component of the current Figure 4 2 1 shows a hardware block diagram of the relay The main components are the current and voltage inputs digital input elements output relays A D converters and the microcomputer and a power supply unit Figure 4 2 2 shows the inputs and outputs of a general protection functio
133. ible V265M EN M A004 10 Applications 10 2 Restricted earth fault protection for a transformer with neutral connection 10 2 Restricted earth fault protection for a transformer with neutral connection Figure 10 2 1 shows and example where three phase current CTs are connected parallel with each other and then in series with the CT in the neutral point VAMP 265 Restricted Earth Fault 3 Figure 10 2 1 Overcurrent and restricted earth fault protection of transformer s wye winding All the CTs have the same ratio and the nominal secondary current is 1 A In through fault the residual secondary currents of phase CTs and the neutral CT cancel each other and in inside fault the two residual secondary currents are summed up and forced to flow through the Ip input of the relay and the voltage limiting VDR V265M EN M A004 167 10 3 Calculating the stabilizing 10 Applications resistance RS VDR value and actual sensitivity 10 2 1 10 3 10 3 1 168 CT Requirements Any difference between the CTs will give a misleading residual current signal to the relay Especially during heavy through faults i e the fault is outside the protected zone the dissimilar saturation of the CTs should not yield to a REF trip On the other hand a very high fault current causing an unselective earth fault start or trip is not a fatal error Class X CT In restricted ear
134. ime delay only If more than one definite time delay stages are needed for current unbalance protection the freely programmable stages can be used chapter 5 16 69 5 9 Current unbalance protection 12 gt 2 gt 46 5 Protection functions 70 Setting groups There are two settings groups available Switching between setting groups can be controlled by digital inputs virtual inputs mimic display communication logic and manually CurrentUnbalanceChar Operation time s 2000 1000 500 200 So Ur 40 60 Negative sequence current I 100 Figure 5 9 1 Inverse operation delay of current unbalance stage l gt The longest delay is limited to 1000 seconds 16min 40s V265M EN M A004 5 Protection functions 5 9 Current unbalance protection 12 gt 2 gt 46 V265M EN M A004 Parameters of the current unbalance stage l2 gt I 2 gt 46 Parameter Value Unit Description Note Status Current status of the stage Blocked Start F Trip F SCntr Cumulative start counter C TCntr Cumulative trip counter C SetGrp 1or2 Active setting group Set SGrpDI Digital signal to select the active Set setting group z None Dix Digital input VIX Virtual input LEDx LED indicator signal VOx Virtual output Force Off Force flag for status forcing for Set On test purposes This is a common flag
135. in main menu DI 7 Configure blocking and interlockings for protection stages using the block matrix This can be done in main menu Prot although VAMPSET is recommended for block matrix editing Some of the parameters can only be changed via the RS 232 serial port using the VAMPSET software Such parameters for example passwords blockings and mimic configuration are normally set only during commissioning Some of the parameters require the restarting of the relay This restarting is done automatically when necessary If a parameter change requires restarting the display will show as Figure 2 4 1 autoboot D Pick PROTOCOL Change will cause autoboot Press CANCEL Figure 2 4 1 Example of auto reset display Press to return to the setting view If a parameter must be changed press again The parameter can now be set When the parameter change is confirmed with ox a RESTART text appears to the top right corner of the display This means that auto resetting is pending If no key is pressed the auto reset will be executed within few seconds V265M EN M A004 2 Local panel user interface 2 4 Configuration and parameter setting 2 4 1 V265M EN M A004 Parameter setting 1 Move to the setting state of the desired menu for example CONF CURRENT SCALING by pushing ox The Pick text appears in the upper left part of the display 2 Enter the password associated with the configuration level by pushi
136. ion time in this example will be 2 3 seconds The same result can be read from Figure 5 17 1 15 k 0 50 4 pu lbickup 2 pu 0 5 ta a 2 3 0 339 0 236 Example for Delay type RXIDG k 0 50 4 pu IPickup 2 pu 4 tee 5 8 1 35In 3 9 The operation time in this example will be 3 9 seconds The same result can be read from Figure 5 17 1 16 600 RI d RXIDG 400 400 200 200 2E E e0 E x 60 40 k 10 40 20 ke5 20 a SI 9 I F ke2 k 20 a ae a s o e g a a2 kos 2 ket 08 08 s 0 6 EA P E 0 6 0 4 0 4 0 2 H 0 2 0 1 0 1 0 08 0 08 0 06 0 06 1 2 3 4 5678 10 20 1 2 3 4 5678 10 20 T Iset inverseDelayRI T Iset inverseDelayRXIDG Figure 5 17 1 15 Inverse delay of type Figure 5 17 1 16 Inverse delay of type RI RXIDG 105 5 17 Inverse time operation 5 Protection functions 17 2 106 Free parametrisation using IEC IEEE and IEEE2 equations This mode is activated by setting delay type to Parameters and then editing the delay function constants i e the parameters A E The idea is to use the standard equations with one s own consta
137. ip command If this time is longer than the operating time of the CBFP stage the CBFP stage activates another output relay which will remain activated until the primary trip relay resets The CBFP stage is supervising all the protection stages using the same selected trip relay since it Supervises the control signal of this relay See chapter 8 4 for details about the output matrix and the trip relays Parameters of the circuit breaker failure stage CBFP 50BF Parameter Value Unit Description Note Status Current status of the stage Blocked Start F Trip F SCnir Cumulative start counter C TCntr Cumulative trip counter C Force Off Force flag for status forcing for Set On test purposes This is a common flag for all stages and output relays too Automatically reset by a 5 minute timeout CBrelay The supervised output relay Set 1 Relay T1 2 Relay T2 t gt S Definite operation time delay Set For details of setting ranges see chapter 12 3 Set An editable parameter password needed C Can be cleared to zero F Editable when force flag is on This setting is used by the circuit breaker condition monitoring too See chapter 6 4 Recorded values of the latest eight faults There are detailed information available of the eight latest faults Time stamp and elapsed delay 85 5 14 Circuit breaker failure protection CBFP 50BF 5 Protection functions 86 Reco
138. irmation Set timeout LLRetry 1 255 Link layer retry count Set 1 default APLTout 0 65535 ms Application layer Set 5000 default confirmation timeout CnfMode Application layer Set EvOnly default confirmation mode All DBISup Double bit input support Set No default Yes SyncMode 0 65535 s Clock synchronization Set request interval 0 only at boot Set An editable parameter password needed V265M EN M A004 9 Communication 9 2 Communication protocols 9 2 7 V265M EN M A004 IEC 60870 5 101 The IEC 60870 5 101 standard is derived from the IEC 60870 5 protocol standard definition In Vamp devices IEC 60870 5 101 communication protocol is available via menu selection The Vamp unit works as a controlled outstation slave unit in unbalanced mode Supported application functions include process data transmission event transmission command transmission general interrogation clock synchronization transmission of integrated totals and acquisition of transmission delay For more information on IEC 60870 5 101 in Vamp devices refer to the IEC 101 Profile checklist amp datalist document Parameters Parameter Value Unit Description Note bit s 1200 bps Bitrate used for serial Set 2400 communication 4800 9600 Parity None Parity used for serial Set Even communication Odd LLAddr 1 65534 Link layer address Set LLAddrSize 1 2 bytes Size of Link layer
139. ition The supervised circuitry in this CB position is double lined The digital input is in active state when the trip circuit is complete DIGITAL INPUTS DIGITAL INPUTS 1 0 HC 0 5 s off off On 0 Figure 10 6 1 6 An example of digital input DI1 configuration for trip circuit supervision with one wet digital input 181 10 6 Trip Circuit Supervision 10 Applications 182 OUTPUT MATRIX T4 T2 T3 T4 A1 A2 connected connected and latched D Figure 10 6 1 7 An example of output matrix configuration for trip circuit supervision with one wet digital input Example of dimensioning the external resistor R Uaux 110 Vdc 5 10 Auxiliary voltage with tolerance Short time voltage dips more than 5 are not critical from the trip circuit supervision point of view Relay type for the K1 auxiliary relay Phoenix Contact 2941455 EMG 17 REL KSR 120 21 21 LC Au Ux 120 Vac dc 20 10 Coil voltage of the auxiliary relay K1 lk 6mA Nominal coil current of the auxiliary relay K1 Pcpcol SOW Rated power of the open coil of the circuit breaker Umin Uaux 5 104 5 V Umax Uaux 10 121V Uximn Uxi1 10 96V Rkicoi Uxi Iki 20 KQ K1MIN Ukimin Rki coil 48mA K1MAX Uk max RkK1Coil 6 1 mA Recoil U aux P 242 Q The external resistance value is calculated using Equation 10 6 1 4 Equation 10 6 1 4 R U uw U kimm Coil Ikim R 104 5 96 0 0048 242 1529 Q
140. kes longer than the time defined by Object timeout setting object fails and Object failure matrix signal is set Also undefined event is generated Controlling with DI firmware version gt 5 53 Objects can be controlled with digital input virtual input or virtual output There are four settings for each controllable object Setting Active DI for remote open control DI for remote close control DI for local open control DI for local close control In remote state In local state If the device is in local control state the remote control inputs are ignored and vice versa Object is controlled when a rising edge is detected from the selected input Length of digital input pulse should be at least 60 ms 146 V265M EN M A004 8 Control functions 8 7 Logic functions 8 6 1 Local Remote selection In Local mode the output relays can be controlled via a local HMI but they cannot be controlled via a remote serial communication interface In Remote mode the output relays cannot be controlled via a local HMI but they can be controlled via a remote serial communication interface The selection of the Local Remote mode is done by using a local HMI or via one selectable digital input The digital input is normally used to change a whole station to a local or remote mode The selection of the L R digital input is done in the Objects menu of the VAMPSET software NOTE A
141. l burden Equation 10 4 1 3 a7 Katr Si Sn Sa AL F IS S y S 5S Accuracy limit factor at rated current and rated burden Internal secondary burden Winding resistance Rer in Figure 10 4 1 1 Rated burden Actual burden including wiring and the load Effect of CT winding resistance Nominal ALF 10 LL 4 lt a 2 O lt 0 5 10 15 20 25 30 CT load VA Effect of CT winding resistance Figure 10 4 1 2 This figure of Equation 10 4 1 3 shows that it is essential to know the winding resistance Ror of the CT if the load is much less than the nominal A 10 VA 5P10 CT with 25 load gives actual ALF values from 15 30 when the winding resistance varies from 0 5 Q to 0 05 Q 173 10 4 Current Transformer Selection 10 Applications 10 4 2 174 CT Requirement for Protection When the through current equals and exceeds kaxln there may be enough secondary differential current to trip a relay although there is no in zone fault This is because the CTs are unique and they do not behave equally when approaching saturation To avoid false trips caused by heavy through faults the actual accuracy limit factor ka of the CTs should exceed the relative setting Iser of the non stabilized differential stage Equation 10 4 2 1 k gt c l Inra SET I ycr c Safety factor ler Relative setting of the non stabilized differential current stage Intra Rated current of the transformer primary side or secondary si
142. lained in chapter 2 2 3 e Ilmax 403A The maximum of the three measured phase currents is at the moment 403 A This is the value the stage is supervising e Status Status of the stage This is just a copy of the status value in the first menu e I gt gt 1013A The pick up limit is 1013 A in primary value e gt gt 2 50xIn The pick up limit is 2 50 times the rated current of the protected object This value can be edited if the operating level is at least Operator Operating levels are explained in chapter 2 2 5 e t gt gt 0 60s The total operation delay is set to 600 ms This value can be edited if the operating level is at least Operator 19 2 2 Local panel operations 2 Local panel user interface 20 Third menu of I gt gt 50 51 stage third menu AV lt gt gt LOG 2006 09 14 12 25 10 288 Type 1 2 Fit 2 86xIn CBWE Load 0 99xin EDly 81 Figure 2 2 2 3 Third and last menu next on the right of l gt gt 50 51 stage This is the menu for registered values by the I gt gt stage Fault logs are explained in chapter 2 2 4 e FAULT LOG 1 This is the latest of the eight available logs You may move between the logs by pressing push Mid and then or lt e 2006 09 14 Date of the log e 12 25 10 288 Time of the log e Type 1 2 The overcurrent fault has been detected in phases L1 and L2 A amp B red amp yellow R amp S u amp v e Fit 2 86xIn The fault current has be
143. lay characteristics by selecting a curve family IEC IEEE IEEE2 RI and a delay type Normal inverse Very inverse etc See chapter 5 17 1 e Standard delay formulae with free parameters Selecting a curve family IEC IEEE IEEE2 and defining one s own parameters for the selected delay formula This mode is activated by setting delay type to Parameters and then editing the delay function parameters A E See chapter 5 17 2 e Fully programmable inverse delay characteristics Building the characteristics by setting 16 current time points The relay interpolates the values between given points with 2nd degree polynomials This mode is activated by setting curve family to PrgN There are maximum three different programmable curves available at the same time Each 93 5 17 Inverse time operation 5 Protection functions 94 programmed curve can be used by any number of protection stages See chapter 5 17 3 Local panel graph The relay will show a graph of the currently used inverse delay on the local panel display Up and down keys can be used for zooming Also the delays at 20xXlset 4xlser and 2xlser are shown Inverse time setting error signal If there are any errors in the inverse delay configuration the appropriate protection stage will use definite time delay There is a signal Setting Error available in output matrix which indicates three different situations e Settings are currently changed
144. lay of current 1 communication parameters speed bit s speed DPS D number of data bits P parity none even odd S number of stop bits Debug Echo to local port Set No No echo Binary For binary protocols ASCII For SPA bus protocol Set An editable parameter password needed Clr Clearing to zero is possible 1 The communication parameters are set in the protocol specific menus For the local port command line interface the parameters are set in configuration menu 151 9 1 Communication ports 9 Communication 9 1 3 152 Extension port X4 This is a non isolated RS 485 port for external I O devices The port is located in the same rear panel D9S connector X4 as the local port but pins 7 8 5 are used instead of the standard RS 232 pins 2 3 5 used by the local port See Figure 9 1 1 Parameters Parameter Value Unit Description Note Protocol Protocol selection for the Set extension port None Command line interface for VAMPSET SPA bus SPA bus slave ProfibusDP Profibus DB slave ModbusSla Modbus RTU slave ModbusTCPs Modbus TCP slave IEC 103 IEC 60870 5 103 slave ExternallO Modbus RTU master for external I O modules DNP3 DNP 3 0 Msg 0 2 1 Message counter since the Clr device has restarted or since last clearing Errors 0 2 61 Protocol errors since the Clr device has restarted or since last clearing Tout 03 2 44 Timeout errors since the
145. le parameter password needed Clr Clearing to zero is possible 1 In continuous mode the size depends of the biggest configured data offset of a data item to be send to the master In request mode the size is 8 bytes 2 In continuous mode the size depends of the biggest configured data offset of a data to be read from the master In request mode the size is 8 bytes 3 When configuring the Profibus master system the length of these buffers are needed The device calculates the lengths according the Profibus data and profile configuration and the values define the in out module to be configured for the Profibus master 4 If the value is Profibus protocol has not been selected or the device has not restarted after protocol change or there is a communication problem between the main CPU and the Profibus ASIC 156 V265M EN M A004 9 Communication 9 2 Communication protocols 9 2 4 V265M EN M A004 SPA bus The manager has full support for the SPA bus protocol including reading and writing the setting values Also reading of multiple consecutive status data bits measurement values or setting values with one message is supported Several simultaneous instances of this protocol using different physical ports are possible but the events can be read by one single instance only There is a separate document Spabus parameters pdf of SPA bus data items available Pa
146. lete command Send command to clear dynamic all dynamic datasets datasets 163 9 2 Communication protocols 9 Communication 9 2 10 164 EtherNet IP The relay supports communication using EtherNet IP protocol which is a part of CIP Common Industrial Protocol family EtherNet IP protocol is available with the optional inbuilt Ethernet port The protocol can be used to read write data from the relay using request response communication or via cyclic messages transporting data assigned to assemblies sets of data EtherNet IP main features Static data model 2 standard objects Overload and Control Supervisor 2 private objects one for digital data and one for analog data and 4 configuration objects for protection functions configuration Two configurable assemblies one producing and one consuming with the maximum capacity of 128 bytes each EDS file that can be fed to any client supporting EDS files can be generated at any time all changes to EtherNet IP configuration see configuration parameters in table below or to assemblies content require generating of the new EDS file Three types of communications are supported UCMM one time request response Class 3 connection cyclic request response and Class 1 connection cyclic IO messages containing assemblies data EtherNet IP implementation on VAMP relay serves as a server and is not capable of initiating communication V265M EN
147. lications the user can built his own protection stages by selecting the supervised signal and the comparison mode The following parameters are available e Priority If operation times less than 60 milliseconds are needed select 10 ms For operation times under one second 20 ms is recommended For longer operation times and THD signals 100 ms is recommended e Link The name of the supervised signal see table below e Cmp Compare mode gt for over or lt for under comparison e Pick up Limit of the stage The available setting range and the unit depend on the selected signal e t Definite time operation delay e Hyster Dead band hysteresis e NoCmp Only used with compare mode under lt This is the limit to start the comparison Signal values under NoCmp are not regarded as fault Available signals to be supervised by the programmable stages Alarm stages link signals Task interval IL1 IL3 IL1W IL3W PL1W IPL3W IL PL 100ms lo lo2 localc l oCalc 11 12 12 11 I2 In P1 72 P2 P 1 P2 In dIL1 dIL2 dIL3 THDIL1 THDIL2 THDIL3 Eight independent stages The relay has eight independent programmable stages Each programmable stage can be enabled or disabled to fit the intended application 91 5 16 Programmable stages 99 5 Protection functions 92 Setting groups There are two settings groups available Switching between setting groups can b
148. lisecond but the actual resolution depends of the particular function creating the event For example V265M EN M A004 6 Supporting functions 6 1 Event log V265M EN M A004 most protection stages create events with 10 ms or 20 ms resolution The absolute accuracy of all time stamps depends on the time synchronizing of the relay See chapter 6 5 for system clock synchronizing Event buffer overflow The normal procedure is to poll events from the device all the time If this is not done the event buffer will eventually overflow On the local screen this is indicated with string OVF after the event code Setting parameters for events Parameter Value Description Note Count Number of events ClrEn Clear event buffer Set Clear Order Order of the event buffer for local display Set Old New New Old FVSca Scaling of event fault value Set PU Per unit scaling Pri Primary scaling Display On Alarm pop up display is enabled Set Alarms Off No alarm display FORMAT OF EVENTS ON THE LOCAL DISPLAY Code CHENN CH event channel NN event code Event description Event channel and code in plain text yyyy mm dd Date for available date formats see chapter 6 5 hh mm ss nnn Time 109 6 2 Disturbance recorder 6 Supporting functions 6 2 110 Disturbance recorder The disturbance recorder can be used to record all the measured signals that is currents voltages and
149. m should be filled with 1 00 0 00s Here is an example configuration of curve points Point Current I lpick up Operation delay 1 1 00 10 00s 2 2 00 6 50 s 3 5 00 4 00s 4 10 00 3 00s 5 20 00 2 00s 6 40 00 1 00s 7 1 00 0 00 s 8 1 00 0 00 s 9 1 00 0 00 s 10 1 00 0 00 s 11 1 00 0 00 s 12 1 00 0 00 s 13 1 00 0 00 s 14 1 00 0 00 s 15 1 00 0 00 s 16 1 00 0 00 s Inverse time setting error signal The inverse time setting error signal will be activated if interpolation with the given points fails See chapter 5 17 for more details Limitations The minimum definite time delay start latest when the measured value is twenty times the setting However there are limitations at high setting values due to the measurement range See chapter 5 17 for more details 107 6 1 Event log 6 Supporting functions 6 6 1 108 Supporting functions Event log Event log is a buffer of event codes and time stamps including date and time For example each start on start off trip on or trip off of any protection stage has a unique event number code Such a code and the corresponding time stamp is called an event The event codes are listed in a separate document VAMP2xx_Events pdf As an example of information included with a typical event an overvoltage trip event of the first 59 stage U gt is shown in the following table EVE
150. mperature Oame and settings max4o and Imax7o See Figure 5 11 1 Ambient temperature is not in use when kO 1 This is true when MAX40 is 1 0 e Samb is n a no ambient temperature sensor e TAMB is 40 C k AmbientTemperatureCompensation 10 20 30 40 50 60 70 80 Ory CC Figure 5 11 1 Ambient temperature correction of the overload stage T gt Example of a behaviour of the thermal model Error Reference source not found shows an example of the thermal model behaviour In this example t 30 minutes k 1 06 and kO 1 and the current has been zero for a long time and thus the initial temperature rise is 0 At time 50 minutes the current changes to 0 85xln and the temperature rise starts to approach value 0 85 1 06 64 according the time constant At time 300 min the temperature is about stable and the current increases to 5 over the maximum defined by the rated current and the service factor k The temperature rise starts to approach value 110 At about 340 minutes the temperature rise is 100 and a trip follows 79 5 11 Thermal overload protection T gt 5 Protection functions 49 Initial temperature rise after restart When the relay is switched on an initial temperature rise of 70 is used Depending of the actual current the calculated temperature rise then starts to approach the final value Alarm function The therm
151. mponent to the measured phase currents 100 g0 Default Sth hamonic block setting 5th hamonic component 100 110 120 130 140 150 160 Voltage Percent of Nominal Voltage Figure 5 13 1 Harmonic content of transformer exciting current as a function of the applied voltage This stage can also be used to block some other stages The ratio between the fifth harmonic component and the fundamental frequency component is measured on all the phase currents When the ratio in any phase exceeds the setting value the stage gives a start signal After a settable delay the stage gives a trip signal The trip delay of the stages to be blocked must be more than 60 ms to ensure a proper blocking 5th harmonic blocking limit is set to 35 of the fundamental component as a default This value can be used in most of the applications 84 V265M EN M A004 5 Protection functions 5 14 Circuit breaker failure protection CBFP 50BF 5 14 V265M EN M A004 Circuit breaker failure protection CBFP 50BF The circuit breaker failure protection can be used to trip any upstream circuit breaker CB if the fault has not disappeared within a given time after the initial trip command A different output contact of the relay must be used for this backup trip The operation of the circuit breaker failure protection CBFP is based on the supervision of the signal to the selected trip relay and the time the fault remains on after the tr
152. n The permitted number of operations for currents in between the defined points are logarithmically interpolated using equation Equation 6 4 1 C T where C permitted operations interrupted current a constant according Equation 6 4 2 n constant according Equation 6 4 3 Equation 6 4 2 In Ci Cua In Leth I n Equation 6 4 3 a C 1 In _ natural logarithm function Ck permitted operations k row 2 7 in Error Reference source not found lk corresponding current k row 2 7 in Error Reference source not found Ck permitted operations k row 2 7 in Error Reference source not found corresponding current k row 2 7 in Error Reference source not found let Example of the logarithmic interpolation Alarm 2 current is set to 6 kA What is the maximum number of operations according Error Reference source not found The current 6 kA lies between points 2 and 3 in the table That gives value for the index k Using k 2 Cx 10000 Ck 80 kat 31 kA Ik 1 25 kA V265M EN M A004 6 Supporting functions 6 4 Circuit breaker condition monitoring V265M EN M A004 and the Equation 6 4 2 and Equation 6 4 3 the relay calculates In 10000 80 90 __ n gg 15038 n 1250 a 10000 1250 8 454 106 Using Equation 6 4 1 the relay gets the number of permitted operations for current 6 kA 454 10 60001598 Thus the maximum numbe
153. n The FFT block is calculating the fundamental frequency phasors and also harmonics used by some protection functions The block matrix is used for simple interlocking More complex interlocking is done with the user s programmable logic The output matrix is used to connect the pick up and trip signals from protection blocks to the output relays and indicators Figure 4 2 3 shows a block diagram of a basic overcurrent or overvoltage function with definite and inverse operation time 45 4 2 Principles of numerical 4 Introduction protection techniques VAMP265K211 Display and keyboard Antialiasing 16 bit filter A D coonverter Trip relays Current inputs Alarm relays Digital inputs SPA bus Modbus Proflous DP fibre connectors Protection Calculation of functions Block matrix Output matrix symmetric components Output relay FFT calculation control Amplitude and phase shift of base freqency component 32 samples cycle Digital 6 18 inputs Settings Figure 4 2 2 Block diagram of signal processing and protection software 1VISblock2 Setting Delay Definite inverse Inverse time Multiplier Enable Ps time characteristic events Figure 4 2 3 Block diagram of a basic protection function 46 V265M EN M A004 5 Protection functions 5 1 Maximum number of protection stages in one application 5 Protection functions Each protection stage can independently be enabled or disabled accor
154. n be matched to the requirements of the application by disabling the functions that are not needed Flexible control and blocking possibilities due to digital signal control inputs DI and outputs DO Easy adaptability of the relay to various substations and alarm systems due to flexible signal grouping matrix in the relay Freely configurable display with six measurement values Freely configurable interlocking schemes with basic logic functions Recording of events and fault values into an event register from which the data can be read via a keypad and a local HMI or by means of a PC based VAMPSET user interface Latest events and indications are in non volatile memory Configuration parameterisation and reading of information via local HMI or with a VAMPSET user interface Easy connection to power plant automation system due to a versatile serial connection and several available communication protocols Built in self regulating ac dc converter for auxiliary power supply from any source within the range from 40 to 265 V dc or ac The alternative power supply is for 18 to 36 V dc Built in disturbance recorder for evaluating all the analogue and digital signals Eight 8 programmable stages for alarming or protection purposes V265M EN M A004 4 Introduction 4 2 Principles of numerical protection techniques 4 2 V265M EN M A004 Principles of numerical protection techniques The device is using numerical technology T
155. ncy component of the residual current 3lo The attenuation of the third harmonic is more than 60 dB Whenever this fundamental value exceeds the user s pick up setting of a particular stage this stage picks up and a start signal is issued If the fault situation remains on longer than the user s operation time delay setting a trip signal is issued i0s1 Setting Io gt s Delay Definite inverse Inverse time Multiplier Enable events time characteristics Figure 5 10 1 Block diagram of the earth fault stage lo gt 0ssblock Setting Io gt gt s Delay Enable events Figure 5 10 2 Block diagram of the earth fault stages Ip gt gt lo gt gt gt and Ip gt gt gt gt Figure 5 10 1 shows a functional block diagram of the Ip gt earth overcurrent stage with definite time and inverse time operation time Figure 5 10 2 shows a functional block diagram of the lo gt gt Ip gt gt gt and l gt gt gt gt earth fault stages with definite time operation delay 72 V265M EN M A004 5 Protection functions 5 10 Earth fault protection 10 gt 50N 51N Input signal selection Each stage can be connected to supervise any of the following inputs and signals e Input Io for all networks other than rigidly earthed e Input loz for all networks other than rigidly earthed e Calculated signal locaic for rigidly and low impedance earthed networks locale IE lL2 IL3 e Calculated signal I ocaic for rigidly and low impedance e
156. ng and then using the arrow keys and a default value is 0002 For more information about the access levels please refer to Chapter 2 2 5 3 Scroll through the parameters using and v A parameter can be set if the background color of the line is black If the parameter cannot be set the parameter is framed 4 Select the desired parameter for example Inom with s 5 Use and to change a parameter value If the value contains more than one digit use and to shift from digit to digit and and to change the digits 6 Push to accept a new value If you want to leave the parameter value unchanged exit the edit state by pushing the CANCEL key VAMP 200 series changing parameters CURRENT SCALING PICK CURRENT SCALING CT prima inom Isec Isec lonom lonom losec d losec loinp loinp lo2nom lo2nom OK OJ Edit VALUE CHANGE G9 enter cr o Figure 2 4 1 1 Changing parameters 31 2 4 Configuration and parameter 2 Local panel user interface setting 2 4 2 Setting range limits If the given parameter setting values are out of range values a fault message will be shown when the setting is confirmed with ox Adjust the setting to be within the allowed range illegal Edit VALUE CHANGE Illegal value Lim 0 10 5 00 Press CANCEL Figure 2 4 2 1 Example of a fault message The allowed setting range is shown in the display in the setting mode To view the range push O Push to return to the settin
157. nts instead of the standardized constants as in the previous chapter Example for GE IAC51 delay type inverse k 0 50 l 4 pu IPickup 2 pu A 0 2078 B 0 8630 C 0 8000 D 0 4180 E 0 1947 0 5 0 2078 0 8630 a 0 4180 r 0 1947 0 37 a Tee Tees The operation time in this example will be 0 37 seconds The resulting time current characteristic of this example matches quite well with the characteristic of the old electromechanical IAC51 induction disc relay Inverse time setting error signal The inverse time setting error signal will become active if interpolation with the given parameters is not possible See chapter 5 17 for more details Limitations The minimum definite time delay start latest when the measured value is twenty times the setting However there are limitations at high setting values due to the measurement range See chapter 5 17 for more details V265M EN M A004 5 Protection functions 5 17 Inverse time operation 17 3 V265M EN M A004 Programmable inverse time curves Only with VAMPSET requires rebooting The current time curve points are programmed using VAMPSET PC program There are some rules for defining the curve points e configuration must begin from the topmost row e row order must be as follows the smallest current longest operation time on the top and the largest current shortest operation time on the bottom e all unused rows on the botto
158. o use these signals for tripping or indication and for blocking purposes OUTPUT MATRIX 1 T2 T3 T4 A1 A2 A3 A4 A5 connected connected and latched Z A A Z Z Z Z Z Z Motor start Motor runnig BLOCK MATRIX b gt b gt p gt Ip gt Ip gt gt Ip gt gt gt Iep gt gt gt gt 12 gt Motor start Motor runnig Figure 5 7 1 2 Motor status in output and block matrix V265M EN M A004 5 Protection functions 5 8 Undercurrent protection I lt 37 5 8 V265M EN M A004 Softstart Frequency converter drives and soft starter applications will not initiate motor start signal due to the low current while starting motor Motor will change directly from stopped to running position when the current increases into a certain level MOTOR NOMINAL CURRENT 100 MOTOR RUNNING LIMT 20 MOTOR STOPPED LIMIT 10 MOTOR CURRENT II HL2 HL3 3 STOP STOP Figure 5 7 1 3 The terms of soft start Normal starting sequence As a default for the motor start detection relay uses value of 6 times motor nominal This value is editable STARTING MOTOR START DETECTION getting VAUS n nnou ae an oe an ne ee a ee MOTOR RUNNING UMT 1 20 nanne 222 ene dane cee ee eee eee eee eee E cence een nnn e a eens MOTOR NOMINAL CURRENT 100 MOTOR STOPPED LIMIT 10 MOTOR CURRENT ILI HL2 L3 3 e has to be less than 200ms Figure 5 7 1 4 The terms of normal starting sequenc
159. ocol sync SpaBus Protocol sync ModBus Protocol sync ProfibusDP Protocol sync IEC 103 Protocol sync DNP3 Protocol sync MsgCnt 0 65535 The number of received 0 etc synchronisation messages or pulses Dev 32767 ms Latest time deviation between the system clock and the received synchronization SyOS 10000 000 s Synchronisation correction for Set any constant error in the synchronizing source A positive value will compensate a lagging external sync and communication delays A negative value will compensate any leading offset of the external synch source AAlntv 10000 S Adapted auto adjust interval for 1 Set ms correction AvDrft Lead Adapted average clock drift sign Set ee FilDev 125 ms Filtered synchronisation deviation Set An editable parameter password needed Astronomically a range 11 12 h would be enough but for political and geographical reasons a larger range is needed 123 6 6 Running hour counter 6 Supporting functions If external synchoronization is used this parameter will be set automatically Set the DI delay to its minimum and the polarity such that the leading edge is the synchronizing edge 6 6 Running hour counter This function calculates the total active time of the selected digital input virtual I O or output matrix output signal The resolution is ten seconds Running hour counter parameters Parameter Value
160. of lo2 CT secondary current lo2sec e Rated 102 input of the relay lo2inp 5A 1 A or 0 2 A This is specified in the order code of the device The rated input values are usually equal to the rated secondary value of the CT The rated CT secondary may be greater than the rated input but the continuous current must be less than four times the rated input In compensated high impedance earthed and isolated networks using cable transformer to measure residual current lo it is quite usual to use a relay with 1 A or 0 2 A input although the CT is 5 Aor 1A This increases the measurement accuracy The rated CT secondary may also be less than the rated input but the measurement accuracy near zero current will decrease MOTOR CURRENT e Motor nominal current 35 2 4 Configuration and parameter 2 Local panel user interface setting FREQUENCY ADAPTATION The relay can automatically detect the correct network frequency User can also fix the frequency if the mode is set to manual and the frequency value is set e Automatic or manual mode of frequency adaptation MODE e Adopted frequency fAdop DEVICE INFO Relay type Type VAMP 265M Serial number SerNo Software version PrgVer Bootcode version BootVer DATE TIME SETUP e Day month and year Date e Time of day Time Date format Style The choices are yyyy mm dad dd nn yyyy and mm dd yyyy CLOCK SYNC e Digital input for minute sync pulse SyncDI
161. of virtual inputs Parameter Value Unit Description Set Vit VI4 0 Status of virtual input 1 Events On Event enabling Set Off NAMES for VIRTUAL INPUTS editable with VAMPSET only Label String of max Short name for VIs on the Set 10 characters local display Default is VIn n 1 4 Description String of max Long name for Vis Default Set 32 characters is Virtual input n n 1 4 Set An editable parameter password needed The six virtual outputs do act like output relays but there are no physical contacts Virtual outputs are shown in the output matrix and the block matrix Virtual outputs can be used with the user s programmable logic and to change the active setting group etc V265M EN M A004 8 Control functions 8 4 Output matrix 8 4 V265M EN M A004 Output matrix By means of the output matrix the output signals of the various protection stages digital inputs logic outputs and other internal signals can be connected to the output relays front panel indicators virtual outputs etc There are two LED indicators named Alarm and Trip on the front panel Furthermore there are three general purpose LED indicators A B and C available for customer specific indications In addition the triggering of the disturbance recorder DR and virtual outputs are configurable in the output matrix See an example in Figure 8 4 1 An output relay or indicator LED
162. on DI for obj close input virtual input or Close information DI for obj ready virtual output Ready information Max ctrl pulse length 0 02 600 5 Pulse length for open and close commands Timeout of ready indication Completion timeout 0 02 600 s Object control Open Close Direct object control If changing states takes longer than the time defined by Max ctrl pulse length setting object fails and Object failure matrix signal is set Also undefined event is generated Completion timeout is only used for the ready indication If DI for obj ready is not set completion timeout has no meaning V265M EN M A004 145 8 6 Controllable objects 8 Control functions Output signals of controllable objects Each controllable object has 2 control signals in matrix Output signal Description Object x Open Open control signal for the object Object x Close Close control signal for the object These signals send control pulse when an object is controlled by digital input remote bus auto reclose etc Settings for read only objects Each read only object has the following settings Setting Value Description DI for obj open None any digital Open information input virtual input or virtual output DI for obj close Close information Object timeout 0 02 600 5 Timeout for state changes If changing states ta
163. or Set On test purposes This is a common flag for all stages and output relays too Automatically reset by a 5 minute timeout ILmax A The supervised value Max of IL1 IL2 and IL3 I gt gt l gt gt gt A Pick up value scaled to primary value calculated by relay I gt gt I gt gt gt xlmot Pick up setting Set t gt gt t gt gt gt s Definite operation time Set IncHarm On off Include Harmonics Set For details of setting ranges see chapter 12 3 Set An editable parameter password needed C Can be cleared to zero F Editable when force flag is on Recorded values of the latest eight faults There are detailed information available of the eight latest faults Time stamp fault type fault current load current before the fault elapsed delay and setting group 62 V265M EN M A004 5 Protection functions 5 6 Overcurrent protection I gt 50 51 V265M EN M A004 Recorded values of the overcurrent stages 8 latest faults I gt I gt gt gt gt gt 50 51 Parameter Value Unit Description yyyy mm dd Time stamp of the recording date hh mm ss ms Time stamp time of day Type Fault type 1 N Ground fault 2 N Ground fault 3 N Ground fault 1 2 Two phase fault 2 3 Two phase fault 3 1 Two phase fault 1 2 3 Three phase fault Flt xlmot Maximum fault current Load xlmot 1 s average phase currents before the fault EDly Elapsed time of the operating time settin
164. order eas Available for Channel Description Wwaveloim IL1 IL2 IL3 Phase current Yes PL1 PL2 PL3 Phase current Yes lo1 lo2 Measured residual current Yes f Frequency loCalc Phasor sum lo IL1 IL2 IL3 3 l oCalc Phasor sum lo 2L1 PL2 PL3 3 11 11 Positive sequence current 12 l 2 Negative sequence current 12 11 V2 1 1 Relative current unbalance I2 In V2 l n Current unbalance xlen IL Average IL1 IL2 IL3 3 PL Average PL1 PL2 P L3 3 L DO Digital outputs Yes DI Digital inputs Yes THDIL1 Total harmonic distortion of IL1 THDI L1 Total harmonic distortion of I L1 THDIL2 Total harmonic distortion of IL2 THDI L2 Total harmonic distortion of I L2 THDIL3 Total harmonic distortion of IL3 THDI L3 Total harmonic distortion of I L3 IL1RMS IL1 RMS for average sampling IL2RMS IL2 RMS for average sampling IL3RMS IL3 RMS for average sampling ILmin Lmin ILmax I Lmax AIL1 AIL2 AIL3 IL1w IL2w IL3w L1w L2w L3w 111 6 2 Disturbance recorder 6 Supporting functions Disturbance recorder parameters Parameter Value Unit Description Note Mode Behaviour in memory full Set situation Saturated No more recordings are Overflow accepted The oldest recorder will be overwritten SR Sample rate Set 32 cycle Waveform 16 cycle Waveform 8 cycle Waveform 1 10ms One cycle value 1 20ms One cycle value 1 200ms Average 1 1s Average 1
165. overcurrent stage gt and I gt 3vIssblock Register event Q Trip Register 2 4 Setting I gt gt s Delay Enable events Figure 5 6 2 Block diagram of the three phase overcurrent stage gt gt and I gt gt Parameters of the overcurrent stage I gt and I gt 50 51 Parameter Value Unit Description Note Status Current status of the stage Blocked Start F Trip F TripTime s Estimated time to trip SCntr Cumulative start counter Clr TCntr Cumulative trip counter Clr SetGrp 1 or2 Active setting group Set SGrpDI Digital signal to select the active setting group J None Dix Digital input Set Vix Virtual input LEDx LED indicator signal VOx Virtual output Force Off Force flag for status forcing for Set On test purposes This is a common flag for all stages and output relays too This flag is automatically reset 5 minutes after the last front panel push button pressing 60 V265M EN M A004 5 Protection functions 5 6 Overcurrent protection I gt 50 51 V265M EN M A004 Parameter Value Unit Description Note ILmax A The supervised value Max of IL1 IL2 and IL3 Status Current status of the stage I gt A Pick up value scaled to primary value calculated by relay I gt xlmot Pick up setting Set Curve Delay curve family DT Definite time IEC Inverse time See chapter
166. put Force Off Force flag for status forcing for Set On test purposes This is a common flag for all stages and output relays too Automatically reset by a 5 minute timeout 74 V265M EN M A004 5 Protection functions 5 10 Earth fault protection 10 gt 50N 51N Parameter Value Unit Description Note lo pu The supervised value according lo2 the parameter Input below loCalc loPeak lo2Peak l oCalc lo gt A Pick up value scaled to primary value lo gt pu Pick up setting relative to the Set parameter Input and the corresponding CT value Curve Delay curve family DT Definite time IEC Inverse time See chapter 5 17 IEEE Set IEEE2 RI PrgN Type Delay type DT Definite time NI Inverse time See chapter 5 17 VI Set El LTI Parame ters t gt s Definite operation time for Set definite time only k gt Inverse delay multiplier for Set inverse time only Input lot X1 7 amp 8 See chapter 11 lo2 X1 9 amp 10 loCalc IL1 IL2 IL3 Set lo1 Peak X1 7 amp 8 peak mode lo2Peak X1 9 amp 10 peak mode l oCalc PL1 PL2 L3 Intrmt s Intermittent time Set Dly20x s Delay at 20xlset Dly4x s Delay at 4xlset Dly2x Ss Delay at 2xlset Dly1x S Delay at 1xlset A B C D User s constants for standard Set E equations Type Parameters See chapter 5 17 For details of setting ranges see chapter 12 3 Set An editable parameter password needed
167. puts Any internal signal can be connected to the output relays using output matrix An output relay can be configured as latched or non latched See output matrix for more details NOTE If the VAMP device has the mA option it is equipped with only three alarm relays from A1 to A3 The difference between trip contacts and alarm contacts is the DC breaking capacity See chapters 12 1 4 and 12 1 5 for details The contacts are SPST normal open type NO except alarm relays A1 A2 and A3 which have change over contacts SPDT Parameters of output relays Parameter Value Unit Description Note T1 T2 0 Status of trip output relay F 1 A1 A5 0 Status of alarm output relay F 1 IF Status of the internal fault F 0 indication relay 1 Force On Force flag for output relay Set Off forcing for test purposes This is a common flag for all output relays and protection stage status too Any forced relay s and this flag are automatically reset by a 5 minute timeout REMOTE PULSES A1 A5 0 00 99 98 s Pulse length for direct output Set or relay control via 99 99 communications protocols 99 99 s Infinite Release by writing 0 to the direct control parameter NAMES for OUTPUT RELAYS editable with VAMPSET only Description String of Names for DO on VAMPSET Set max 32 screens Default is characters Trip relay n Alarm relay n Set An editable parameter pass
168. r Demand time Demand value parameters Parameter Value Unit Description Set Time 10 30 min Demand time averaging time Set Fundamental frequency values ILida A Demand of phase current IL1 IL2da A Demand of phase current IL2 IL3da A Demand of phase current IL3 RMS values ILida A Demand of phase current IL1 IL2da A Demand of phase current IL2 IL8da A Demand of phase current IL3 75 Minimum and maximum values Minimum and maximum values are registered with time stamps since the latest manual clearing or since the device has been restarted The available registered min amp max values are listed in the following table Min amp Max Description measurement IL1 IL2 IL3 Phase current fundamental frequency value IL1RMS IL2RMS Phase current rms value IL8RMS lo1 lo2 Residual current f Frequency ILida IL2da IL8da Demand values of phase currents ILida IL2da IL8da Demand values of phase currents rms values rms value The clearing parameter ClrMax is common for all these values Parameters Parameter Value Description Set ClrMax Reset all minimum and maximum values S Clear V265M EN M A004 133 7 6 Maximum values of the last 31 7 Measurement functions days and twelve months 7 6 Maximum values of the last 31 days and twelve months Some maximum and minimum values of the last 31 days and the last t
169. r of current breaking at 6 kA is 945 This can be verified with the original breaker curve in Figure 6 4 1 Indeed the figure shows that at 6 kA the operation count is between 900 and 1000 A useful alarm level for operation left could be in this case for example 50 being about five per cent of the maximum 945 Example of operation counter decrementing when the CB is breaking a current Alarm2 is set to 6 kA CBFP is supervising trip relay T1 and trip signal of an overcurrent stage detecting a two phase fault is connected to this trip relay T1 The interrupted phase currents are 12 5 kA 12 5 kA and 1 5 kA How much are Alarm2 counters decremented Using Equation 6 4 1 and values n and a from the previous example the relay gets the number of permitted operation at 10 kA 454 10 Cion 12500150 313 At alarm level 2 6 kA the corresponding number of operations is calculated according Equation 6 4 4 A C starmMax C 945 Ay 4n 313 Thus Alarm2 counters for phases L1 and L2 are decremented by 3 In phase L1 the currents is less than the alarm limit current 6 kA For such currents the decrement is one Az l 119 6 4 Circuit breaker condition monitoring 6 Supporting functions 120 Local panel parameters of CBWEAR function Parameter Value Unit Description Set CBWEAR STATUS Operations left for Al1L1 Alarm 1 phase L1 Al1
170. r operation time RSTP support Harmonic driver to 10ms priority locacc driver to 10ms priority Logic outputs to GOOSE 10 85 Virtual output events added 10 106 GOOSE supervision signals added Automatic LED latch release added Disturbance recorder full event added Motor load current in per cent 10 108 Use of recorder memory in percents added Various additions to IEC 61850 10 116 IP and other TCP parameters are able to change without reboot Logic output numbering is not changed when changes are made in the logic NOTE Vampset version 2 2 97 required 10 118 Enable sending of analog data in GOOSE message Day light saving DST rules added for system clock HMI changes Order of the first displays changed 1 measurement 2 mimic 3 title timeout does not apply if the first 3 displays are active 221 Customers Care Center http www schneider electric com ccc Schneider Electric 35 rue Joseph Monier 92506 Rueil Malmaison FRANCE Phone 33 0 1 41 29 70 00 Fax 33 0 141 297100 www schneider electric com Publication version V265M EN M A004 Publishing Schneider Electric 12 2012 2012 Schneider Electric All rights reserved
171. rameters Parameter Value Unit Description Note Addr 1 899 SPA bus address Must be Set unique in the system bit s bps Communication speed Set 1200 2400 4800 9600 default 19200 Emode Event numbering style Set Channel Use this for new installations Limit60 The other modes are for NoLimit compatibility with old systems Set An editable parameter password needed 157 9 2 Communication protocols 9 Communication 9 2 5 IEC 60870 5 103 The IEC standard 60870 5 103 Companion standard for the Informative interface of protection equipment provides standardized communication interface to a primary system master system The unbalanced transmission mode of the protocol is used and the device functions as a secondary station slave in the communication Data is transferred to the primary system using data acquisition by polling principle The IEC functionality includes the following application functions station initialization general interrogation clock synchronization and command transmission It is not possible to transfer parameter data or disturbance recordings via the IEC 103 protocol interface The following ASDU Application Service Data Unit types will be used in communication from the device ASDU 1 time tagged message ASDU 3 Measurands ASDU 5 Identification message ASDU 6 Time synchronization and ASDU 8 Termination of general interrogation The devi
172. rameters each e Current The first alarm can be set for example to nominal current of the CB or any application typical current The second alarm can be set for example according a typical fault current e Operations left alarm limit An alarm is activated when there are less operation left at the given current level than this limit Any actual interrupted current will be logarithmically weighted for the two given alarm current levels and the number of operations left at the alarm points is decreased accordingly When the operations left i e the number of remaining operations goes under the given alarm limit an alarm signal is issued to the output matrix Also an event is generated depending on the event enabling Clearing operations left counters After the breaker curve table is filled and the alarm currents are defined the wearing function can be initialised by clearing the decreasing operation counters with parameter Clear Clear oper left cntrs After clearing the relay will show the maximum allowed operations for the defined alarm current levels Operation counters to monitor the wearing The operations left can be read from the counters AliLn Alarm 1 and Al2Ln Alarm2 There are three values for both alarms one for each phase The smallest of three is supervised by the two alarm functions V265M EN M A004 117 6 4 Circuit breaker condition monitoring 6 Supporting functions 118 Logarithmic interpolatio
173. rded values of the circuit breaker failure stage 8 latest faults CBFP 50BF Parameter Value Unit Description yyyy mm dd Time stamp of the recording date hh mm ss ms Time stamp time of day EDly Elapsed time of the operating time setting 100 trip V265M EN M A004 5 Protection functions 5 15 Arc fault protection 50ARC 50NARC optional 5 15 V265M EN M A004 Arc fault protection 50ARC 50NARC optional NOTE This protection function needs optional hardware in slot X6 More details of the hardware can be found in chapters 11 4 and 12 1 8 Arc protection is used for fast arc protection The function is based on simultaneous light and current measurement Special arc sensors are used to measure the light of an arc Three stages for arc faults There are three separate stages for the various current inputs e Arcl gt for phase to phase arc faults Current inputs IL1 IL2 IL3 are used e Arcl gt for phase to phase arc faults Current inputs PL1 L2 PL3 are used e Arcloi gt for phase to earth arc faults Current input lo is used e Arclos gt for phase to earth arc faults Current input loz is used Light channel selection The light information source to the stages can be selected from the following list a No sensor selected The stage will not work e Si Light sensor S1 e S2 Light sensor S2 e S1 S2 Either one of the light sensors S1 or S2 e BI
174. reen will show the latest if it s the biggest registered fault current too Not used with Spabus because Spabus masters usually don t like to have unpaired On Off events Used with SPA bus protocol because most SPA bus masters do need an off event for each corresponding on event 128 V265M EN M A004 6 Supporting functions 6 9 Self supervision 6 9 V265M EN M A004 Self supervision The functions of the micro controller and the associated circuitry as well as the program execution are supervised by means of a separate watchdog circuit Besides supervising the relay the watchdog circuit attempts to restart the micro controller in a fault situation If the restarting fails the watchdog issues a self supervision alarm indicating a permanent internal fault When the watchdog circuit detects a permanent fault it always blocks any control of other output relays except for the self supervision output relay In addition the internal supply voltages are supervised Should the auxiliary supply of the relay disappear an alarm is automatically given because the internal fault IF output relay functions on a working current principle This means that the IF relay is energized when the auxiliary supply is on and no internal fault is detected 129 6 9 Self supervision 7 Measurement functions 7 130 Measurement functions All the direct measurements are based on fundamental frequency values The excep
175. rial fibre interface C Profibus interface D RS 485 interface 4 wire E Glass Glass serial fibre interface F Rx Plastic Tx Glass serial fibre interface G Rx Glass Tx Plastic serial fibre interface H RJ 45 10Mbps ethernet interface M RJ 45 10Mbps ethernet inc IEC 61850 O LC 100 Mbps ethernet fibre interface inc IEC 61850 P _ RJ 45 100Mbps ethernet interface inc IEC 61850 R 2xLC 100 Mbps ethernet fibre interface inc IEC 61850 S 2xRJ 45 100 Mbps ethernet interface inc IEC 61850 Optional software A Version 2 firmware See firmware version history C Version 6 firmware E _ Standard firmware M Standard firmware Motor functions Ingress protection rating IP30 default l IP54 option Note Optional hardware A H available Optional hardware A G available V265M EN M A004 219 15 Order information Accessories Order Code Explanation Note VEA3CGi External ethernet interface module VPA3CG Profibus interface module VSE001PP Fiber optic Interface Module plastic plastic VSE002 RS485 Interface Module VSE003 RS485 Interface Module Ext I O interface VSE009 External DeviceNet interface module VIO 12 AB RTD Module 12pcs RTD inputs RS 485 Communication 24 230 Vac dc VIO 12 AC RTD mA Module 12pcs RTD inputs PTC mA inputs outputs RS232 RS485 and Optical Tx Rx Communication 24 Vdc VIO 12 AD RTD mA Module 12pcs RTD inputs PTC mA inputs outp
176. rip contacts Arc fault protection stages option The operation of the arc protection depends on the setting value of the Arcl gt Arclo gt and Arclos gt current limits The arc current limits cannot be set unless the relay is provided with the optional arc protection card Arc protection stage Arcl gt 50ARC option Setting range 0 5 10 0x In Arc sensor connection 1 S2 1 S2 BI S1 BI S2 BI 1 S2 Bl Operating time Light only 13 ms Operating time 4xIset light 17ms Operating time BIN 10 ms BO operating time lt 3 ms Reset time lt 95 ms Reset time Delayed ARC L lt 120 ms Reset time BO lt 85 ms Reset ratio 0 90 Inaccuracy Starting 10 of the set value Operating time 5 ms Delayed ARC light 10 ms Arc protection stage Arclo gt SONARC option Setting range 0 5 10 0x I Arc sensor connection 1 S2 1 S2 BI S1 Bl S2 Bl 1 S2 Bl Operating time Light only 13 ms Operating time 4xlset light 17ms Operating time BIN 10 ms BO operating time lt 3 ms Reset time lt 95 ms Reset time Delayed ARC L lt 120 ms Reset time BO lt 85 ms Reset ratio 0 90 Inaccuracy Starting 10 of the set value Operating time 5 ms Delayed ARC light 10 ms 215 12 4 Supporting functions 12 Technical data Arc protection stage Arclo2 gt SONARC option Setting range 0 5 10 0x I Arc sensor connection 1 S2 1 S2 BI S1 Bl S
177. rm the selection Signal T1 can now be controlled by force 7 Push or to change the selection from 0 not alert to 1 alert or vice versa 8 Push to execute the forced control operation of the selected function e g making the output relay of T1 to pick up 9 Repeat the steps 7 and 8 to alternate between the on and off state of the function 10 Repeat the steps 1 4 to exit the Force function 11 Push to return to the main menu NOTE All the interlockings and blockings are bypassed when the force control is used 29 2 4 Configuration and parameter 2 Local panel user interface setting 2 4 30 Configuration and parameter setting The minimum procedure to configure a relay is 1 Open the access level Configurator The default password for configurator access level is 2 2 Set the rated values in menu CONF including at least current transformers and a protected transformer rating Also the date and time settings are in this same main menu 3 Enable the needed protection functions and disable the rest of the protection functions in main menu Prot 4 Set the setting parameter of the enable protection stages according the application 5 Connect the output relays to the start and trip signals of the enabled protection stages using the output matrix This can be done in main menu DO although the VAMPSET program is recommended for output matrix editing Configure the needed digital inputs
178. rotect a zone between two measuring points against earth faults See Figure 10 1 1 Protected zone Figure 10 1 1 Principle of restricted earth fault protection The CT secondaries are wired to cancel each other s currents during through faults and to drive all to the relay when the fault is inside the protected zone Saturation of the CTs makes the situation a little more complicated than that The stabilizing resistor Rs guarantees that the relay will not trip during a through fault The VDR is used to protect the CTs and the wiring by limiting the voltage Vs during heavy inside faults When there is a fault outside the protected zone the CT secondaries will cancel each other s currents This is partly true even if both or only one of the CTs saturates because the impedance of a saturated CT secondary will collapse to near zero The non zero wiring impedance and CT impedance will however cause a voltage Vs but the resistor Rg will prevent the relay from tripping RS is called the stabilizing resistor During an inside fault the secondary currents of the two CTs have no other way to go than the relay The relay will trip when the current Vs Rs exceeds the setting Is of the relay The voltage dependent resistor VDR varistor METROSIL is used to protect the CTs and wiring by limiting the voltage Vs during heavy inside faults The resistance of the secondary loop connecting the CTs together should be as low as poss
179. rrent of the possible VDR will decrease the sensitivity from the actual setting value 169 10 3 Calculating the stabilizing 10 Applications resistance RS VDR value and actual sensitivity 10 3 4 Example CT 2000 1 Veep 100 V I MAXT 16 kA 8x Il REF 5 50 mA Setting value scaled to secondary level Ret 60 Rw 040 IMAXF 25 kA 170 Maximum secondary voltage during a through fault Equation 10 3 1 1 V 16000 6 0 4 51 2V 2000 Conclusion The knee point voltage of 100 V is acceptable being about twice the Vs Serial resistance for the relay input Equation 10 3 1 2 R gt _ 1024 Ax 10002 0 05 Maximum peak voltage during inside fault using a linear model for CT Equation 10 3 2 1 V 25000 6 0 4 1000 12 6kV f 2000 Approximation of peak voltage during inside fault using a non linear model for a saturating CT Equation 10 3 2 2 V 2 2 100 12600 100 3 2 kV This is a too high value and a VDR must be used to reduce the voltage below 3 kV A zinc oxide varistor i e VDR METROSIL of 1 kV will limit the voltage Using a 400 J model allows two 20 VA CTs feeding ten times their nominal power during one second before the energy capacity of the varistor is exceeded V265M EN M A004 10 Applications 10 4 Current Transformer Selection 10 4 10 4 1 V265M EN M A004 Current Transformer Selection Iron core current transformers CT are accurate in amplitu
180. rrors nnn Error counter Tout nnn Timeout counter Set An editable parameter password needed 153 9 2 Communication protocols 9 Communication 9 2 Communication protocols This protocols enable the transfer of the following type of data events status information measurements control commands clock synchronizing Settings SPA bus and embedded SPA bus only 9 2 1 PC communication PC communication is using a VAMP specified command line interface The VAMPSET program can communicate using the local RS 232 port or using ethernet interface It is also possible to select SPA bus protocol for the local port and configure the VAMPSET to embed the command line interface inside SPA bus messages For ethernet interface configuration see chapter 9 1 4 9 2 2 Modbus TCP and Modbus RTU These Modbus protocols are often used in power plants and in industrial applications The difference between these two protocols is the media Modbus TCP uses Ethernet and Modbus RTU uses asynchronous communication RS 485 optic fibre RS 232 VAMPSET will show the list of all available data items for Modbus A separate document Modbus parameters pdf is also available The Modbus communication is activated usually for remote port via a menu selection with parameter Protocol See chapter 9 1 For ethernet interface configuration see chapter 9 1 4 Parameters Parameter Value Unit Description Note A
181. rt I gt trip N gt alarm N gt motor start inhibit NStageAppl_40 Figure 5 4 1 Application for preventing too frequent starting using the N gt stage The relay A1 has been configured to be normal closed The start is just an alarm telling that there is only one start left at the moment 52 V265M EN M A004 5 Protection functions 5 4 Frequent start protection N gt 66 V265M EN M A004 Parameters of the frequent start protection N gt 66 Parameter Value unit Description Measured Status Disabled Stage status value Enabled SCnir Start counter Mot strs Motor starts in last hour t Min Elapsed time from motor start Force On Off Force flag for status forcing for test purposes This is a common flag for all stages and output relays too This flag is automatically reset 5 minutes after the last front panel push button pressing Setting Mot strs Max starts in one hour values t Min Elapsed time from motor start Status Stage status SCnir Start counter Sts h Max motor start per hour Interval Min Min interval between two consecutive starts Recorded LOG1 Date and time of trip values N st h Motor starts hour TimeFromSt Elapsed time from motor start Tot Mot Strs Number of total motor starts Type Fault type Event Alr_on Alarm on event Enabling Alr_off Alarm off Event MoSirt_dis Motor start disabled MotStrt_En Motor start enabled
182. rted dynamic data sets created by clients e Supported reporting function with buffered and unbuffered Report Control Blocks e Supported control model direct with normal security e Supported horizontal communication with GOOSE configurable GOOSE publisher data sets configurable filters for GOOSE subscriber inputs GOOSE inputs available in the application logic matrix Additional information can be obtained from the separate documents IEC 61850 conformance statement pdf IEC 61850 Protocol data pdf and Configuration of IEC 61850 interface pdf on our website V265M EN M A004 9 Communication 9 2 Communication protocols V265M EN M A004 IEC 61850 main config parameters Parameter Value Unit Description Set Port 0 64000 IP protocol port Set Check Yes No If the checkbox Check Set upper upper addresses is addresses checked the below parameters are also checked and used for addressing when the client is communicating to the device by default this is disabled The below parameters are ACSE association parameters described in the standard part 61850 8 1 AP ID nnn nann nnn nnn ACSE AP title value Set AE 0 64000 ACSE AE qualifier Qualifier P Selector 0 4200000000 Presentation selector S Selector 0 64000 Session selector T Selector 0 64000 Transport selector IED Name String Identifcation of the device Each device must have unique name De
183. s Type 1 N 2 N Fault type single phase fault e g 3 N 1 N fault on phase L1 1 2 2 3 Fault type two phase fault 1 3 e g 2 3 fault between L2 and L3 1 2 3 Fault type three phase fault Flt xlmot Min value of fault current as per times Imot Load xlmot 1s mean value of pre fault currents IL1 IL3 Edly Elapsed time as compared to the set operate time 100 tripping 68 V265M EN M A004 5 Protection functions 5 9 Current unbalance protection 12 gt 2 gt 46 5 9 V265M EN M A004 Current unbalance protection l2 gt 2 gt 46 The current unbalance stage protects against unbalanced phase currents and single phasing The protection is based on the negative sequence current Both definite time and inverse time characteristics are available The inverse delay is based on Equation 5 9 1 Only the base frequency components of the phase currents are used to calculate the negative sequence value Io Inverse delay The inverse delay is based on the following equation Equation 5 9 1 t where j ly t Operation time K Delay multiplier l gt Measured and calculated negative sequence phase current of fundamental frequency In Rated current K Pick up setting l2 gt in pu The maximum allowed degree of unbalance Example Ki 15s l2 22 9 0 229 xln K 5 0 05 XIn t E 300 4 2 2 E 1 The operation time in this example will be five minutes More stages definite t
184. s current of faulted phase as compared to Flt xlmot Max value of fault differential current as compared to ln Load xlmot 1 s mean value of pre fault phase currents IL1 IL3 1 Measurement ranges are described in section 12 1 1 2 Setting ranges are described in section 12 3 2 Parameters of the instant differential stage Al gt gt 87 Parameter Value unit Measured dL1 xlmot Current difference value values dL2 dL3 Setting Al gt gt xlmot Setting value values Recorded TCnir Cumulative trip counter values Type 1 N 2 N Fault type single phase fault e g 1 3 N N fault on phase L1 1 2 2 3 Fault type two phase fault e g 2 3 1 3 fault between L2 and L3 1 2 3 Fault type three phase fault Fit xlmot Max value of fault differential current as compared to Load xlmot 1 s mean value of pre fault phase currents IL1 IL3 V265M EN M A004 5 Protection functions 5 5 Differential overcurrent protection Al gt 87 V265M EN M A004 Differential Protection using 6 CT s Ll Figure 5 5 4 VAMP 265M connected as a motor differential protection using 6 CT s In this application mode the settings in VAMP 265M relay s menu SCALING should be set as described in the following section CT settings Here the motor high and low side primary an
185. s in one application47 5 2 List of protection functions cceeeeeeeeeeeeeeeteeeeeeeeeeeeees 47 5 3 General features of protection stages cccceeee 48 5 4 Frequent start protection N gt 66 ceeeeeeeeeeeeeeeeeees 52 5 5 Differential overcurrent protection Al gt 87 ee 54 5 6 Overcurrent protection l gt 50 51 0 0 22 eeeeeeeeeeeeeeeeeeeeeeeees 59 5 7 Stall protection Ist gt 48 eeeceeeeeeeeeeeeeeeeeeeeeeneeeeeeeeeeeeees 64 V265M EN M A004 3 Table of Contents 5 7 1 Motor status 22 2 scec te tegat scat Secet te based ses hres te 8 cae 66 5 8 Undercurrent protection I lt 37 cecceeeeeeeteeeeeeeeeeeeeees 67 5 9 Current unbalance protection l2 gt P gt 46 eee 69 5 10 Earth fault protection lo gt 50N 51N ceeeeeeeeeeeeeeeeeee 72 5 11 Thermal overload protection T gt 49 seeeeeeeeeeeeeees 78 5 12 Second harmonic O C stage lp gt 51F2 sessen 82 5 13 Fifth harmonic O C stage lis gt 51F5 eeceeeeeeeeeeeeeeeeeee 84 5 14 Circuit breaker failure protection CBFP 50BP 85 5 15 Arc fault protection 50ARC 50NARC optional 87 5 16 Programmable stages 99 cccccceeeeeeeeeeeeeeeeeeeeeeeeeeees 91 5 17 Inverse time Operation ccccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeees 93 5 17 1 Standard inverse delays IEC IEEE IEEE2 Rl 96 5 17 2 Free parametrisation using IEC I
186. s not available The DI19 D120 option enables two more digital inputs These inputs are useful in applications where the contact signals are not potential free For example trip circuit supervision is such application The inputs are connected to terminals X6 1 X6 2 and X6 3 X6 4 Connections X6 1 DI19 X6 2 DI19 X6 3 DI20 X6 4 DI20 X6 5 NC X6 6 L X6 7 L 198 V265M EN M A004 11 Connections 11 6 External I O extension modules 11 6 11 6 1 11 6 2 V265M EN M A004 External I O extension modules External LED module VAM 16D The optional external VAM 16D led module provides 16 extra led indicators in external casing Module is connected to the serial port of the relays front panel Please refer the User manual VAM 16 D VM16D ENxxx for details External input output module The relay supports an optional external input output modules used to extend the number of digital inputs and outputs Also modules for analogue inputs and outputs are available The following types of devices are supported e Analog input modules RTD e Analog output modules mA output e Binary input output modules EXTENSION port is primarily designed for IO modules This port is found in the LOCAL connector of the relay backplane and IO devices should be connected to the port with VSE003 adapter NOTE If ExternallO protocol is not selected to any communication port VAMPSET doesn t display the menus required for configuring t
187. s with any other digital inputs V ux 48 Vdc 240 Vdc VAMP relay 1 Trip relay ING Alarm relay for trip circuit failure trip Circuit failure alarm relay compartment circuit breaker compartment TCS2Diclosed Figure 10 6 2 1 Trip circuit supervision with two dry digital inputs The CB is closed The supervised circuitry in this CB position is double lined The digital input is in active state when the trip circuit is complete This is applicable for dry inputs DI7 D20 only V265M EN M A004 10 Applications 10 6 Trip Circuit Supervision V ux 48 Vdc 240 Vdc VAMP relay Trip relay Ne Alarm relay for trip circuit failure trip circuit failure alarm relay compartment circuit breaker compartment close control TCS2Dlopen Figure 10 6 2 2 Trip circuit supervision with two dry digital inouts The CB is in the open position The two digital inputs are now in series Note If for example DI13 and DI7 are used as the upper and lower digital inputs in the Figure 10 6 2 2 the usage of DI8 D114 is limited to the same circuitry sharing the Vaux in the common terminal and the DI14 DI18 cannot be used because they share the same common terminal with DI13 DIGITAL INPUTS Figure 10 6 2 3 An example of digital inout configuration for trip circuit supervision with two dry digital inputs DIZ and DI13 V265M EN M A004 185 10 6 Trip Circuit Supervision 10
188. set time i e release delay when the relay is clearing an overcurrent fault When the relay s trip contacts are closed the circuit breaker CB starts to open After the CB contacts are open the fault current will still flow through an arc between the opened contacts The current is finally cut off when the arc extinguishes at the next zero crossing of the current This is the start moment of the reset delay After the reset delay the trip contacts and start contact are opened unless latching is configured The reset time varies from fault to fault depending on the fault size After a big fault the time is longer The reset time also depends on the specific protection stage The maximum reset time for each stage is specified in chapter 12 3 For most stages it is less than 95 ms ReleaseTime top H tresET TRIP CONTACTS maaa e Figure 5 3 2 Reset time is the time it takes the trip or start relay contacts to open after the fault has been cleared Hysteresis or dead band When comparing a measured value against a pick up value some amount of hysteresis is needed to avoid oscillation near equilibrium situation With zero hysteresis any noise in the measured signal or any noise in the measurement itself would cause unwanted oscillation between fault on and fault off situations 50 V265M EN M A004 5 Protection functions 5 3 General features of protection stages V265M EN M A004 Hysteresis GT hysteresis P
189. sible navigating directions in the menu are shown in the upper left corner by means of black triangular symbols scroll ENABLED STAGES 3 U gt U gt gt U gt gt gt U lt U lt lt U lt lt lt Figure 2 2 1 1 Example of scroll indication V265M EN M A004 2 Local panel user interface 2 2 Local panel operations V265M EN M A004 Main menu Submenus I I I I z I V i Prot k protection enabling a a I I ft 2 I i y I l a I i l l pick up setting za a v 1 ot O l Yy I i moving in the menus_relay Figure 2 2 1 2 Principles of the menu structure and navigation in the menus 6 Push to obtain additional information about any menu item 7 Push to revert to the normal display 15 2 2 Local panel operations 2 Local panel user interface Main menu The general menu structure is shown in Figure 2 2 1 2 The menu is dependent on the user s configuration and the options according the order code For example only the enabled protection stages 16 will appear in the menu A list of the local main menu Main menu Number of Description ANSI Note menus code 1 Interactive mimic display 1 5 Double size measurements defined by the user 1 1 Title screen with devic
190. stem e Bit rate bit s Default is 9600 e Event numbering style Emode Default is Channel For details see the technical description part of the manual IEC 60870 5 103 Only one instance of this protocol is possible e Address for this device Addr This address has to be unique within the system Bit rate bit s Default is 9600 Minimum measurement response interval MeasInt ASDU6 response time mode SyncResMog e Debug mode SyncDebug For details see the technical description part of the manual IEC 103 DISTURBANCE RECORDINGS For details see the technical description part of the manual PROFIBUS Only one instance of this protocol is possible e Mode e Bit rate bit s Use 2400 bps This parameter is the bit rate between the main CPU and the Profibus ASIC The actual Profibus bit rate is automatically set by the Profibus master and can be up to 12 Mbit s e Event numbering style Emode e Size of the Profibus Tx buffer InBufl e Size of the Profibus Rx buffer OutBuf When configuring the Profibus master system the length of these buffers are needed The size of the both buffers is set indirectly when configuring the data items for Profibus e Address for this slave device Addr This address has to be unique within the system e Profibus converter type Conv If the shown type is a dash either Profibus protocol has not been selected or the device has not restarted after protocol chan
191. t breaker e Another auxiliary contact is connected in series with the circuitry of the first digital input This makes it possible to supervise also the auxiliary contact in the trip circuit e The second digital input is connected in parallel with the trip contacts e Both inputs are configured as normal closed NC e The user s programmable logic is used to combine the digital input signals with an AND port The delay is configured longer than maximum fault time to inhibit any superfluous trip circuit fault alarm when the trip contact is closed e The output from the logic is connected to a relay in the output matrix giving out any trip circuit alarm V265M EN M A004 183 10 6 Trip Circuit Supervision 10 Applications Note 184 e The trip relay should be configured as non latched Otherwise a superfluous trip circuit fault alarm will follow after the trip contact operates and the relay remains closed because of latching e Both digital inputs must have their own common potential Using the other digital inputs in the same group as the upper DI in the Figure 10 6 2 1 is not possible in most applications Using the other digital inputs in the same group as the lower DI in the Figure 10 6 2 1 is limited because the whole group will be tied to the auxiliary voltage Vaux In many applications the optimum digital inputs for trip circuit supervision are the optional inputs DI19 and DI20 because they don t share their terminal
192. te communication bus or via a digital input configured for that purpose Adjusting display contrast The readability of the LCD varies with the brightness and the temperature of the environment The contrast of the display can be adjusted via the PC user interface see chapter 3 2 2 Local panel operations 2 Local panel user interface 2 2 2 2 1 14 Local panel operations The front panel can be used to control objects change the local remote status read the measured values set parameters and to configure relay functions Some parameters however can only be set by means of a PC connected to one of the local communication ports Some parameters are factory set Navigating in menus All the menu functions are based on the main menu submenu structure 1 Use the arrow keys and to move up and down in the main menu 2 To move to a submenu repeatedly push until the required submenu is shown Correspondingly push the to return to the main menu 3 Push to confirm the selected submenu If there are more than six items in the selected submenu a black line appears to the right side of the display Figure 2 2 1 1 It is then possible to scroll down in the submenu 4 Push to cancel a selection 5 Pushing the or in any position of a sub menu when it is not selected brings you directly one step up or down in the main menu The active main menu selection is indicated with black back ground color The pos
193. th TTL interface The DSR signal from the front panel port selects the active connector for the RS232 local port By default the remote port has a TTL interface It can only be used together with external converters or converting cables Inbuilt options for RS 485 fibre optic plastic plastic plastic glass glass plastic or glass glass Profibus and Ethernet are available V265M EN M A004 9 Communication 9 1 Communication ports 9 1 1 Local port X4 The local port has two connectors e On the front panel e X4 the rear panel D9S pins 2 3 and 5 Only one can be used at a time NOTE The extension port is locating in the same X4 connector NOTE When the VX003 cable is inserted to the front panel connector it activates the front panel port and disables the rear panel local port by connecting the DTR pin 6 and DSR pin 4 together See Figure 9 1 1 Protocol for the local port The front panel port is always using the command line protocol for VAMPSET regardless of the selected protocol for the rear panel local port If other than None protocol is selected for the rear panel local port the front panel connector when activated is still using the plain command line interface with the original speed parity etc For example if the rear panel local port is used for remote VAMPSET communication using SPA bus default 9600 7E1 it is possible to temporarily connect a PC with VAMPSET to the front panel connector with the default 38
194. th fault protection the high and low side CTs should give similar responses even for high over currents Class X CTs will fulfil this requirement Their performance is defined in terms of a knee point voltage Vp the magnetizing current at the knee point voltage and the resistance of the secondary winding at 75 C Knee point voltage Vp is the secondary voltage at which a 50 increase of primary current is needed to increase the secondary voltage by 10 Calculating the stabilizing resistance Rs VDR value and actual sensitivity Value of stabilizing resistor Rs The voltage Vs Figure 10 1 1 is Equation 10 3 1 1 CT Vs I maxr ae Rer Ry PRIM IMAXT Maximum through fault current not to cause an REF trip CTsec Nominal secondary current of the CT CTpri Nominal primary current of the CT Ret Resistance of CT secondary Rw Total resistance of wiring connections etc 1 Selecting a low value helps to achieve more sensitivity and helps to avoid the usage of a voltage limiting VDR An unselective earth fault pick up trip is not always a problem if a fast overcurrent stage will clear the fault anyway V265M EN M A004 10 Applications 10 3 Calculating the stabilizing resistance RS VDR value and actual sensitivity 10 3 2 10 3 3 V265M EN M A004 The CT should be of class X see chapter 10 2 1 and the knee point voltage should be twice the calculated Vs The stabilizing resistor Rs is calculat
195. the status information of digital inputs DI and digital outputs DO The digital inputs include also the arc protection signals S1 S2 BI and BO if the optional arc protection is available Triggering the recorder The recorder can be triggered by any start or trip signal from any protection stage or by a digital input The triggering signal is selected in the output matrix vertical signal DR The recording can also be triggered manually All recordings are time stamped Reading recordings The recordings can be uploaded viewed and analysed with the VAMPSET program The recording is in COMTRADE format This means that also other programs can be used to view and analyse the recordings made by the relay For more details please see a separate VAMPSET manual Number of channels At the maximum there can be 12 recordings and the maximum selection of channels in one recording is also 12 limited in waveform recording The digital inputs reserve one channel includes all the inputs Also the digital outputs reserve one channel includes all the outputs If digital inputs and outputs are recorded there will be still 10 channels left for analogue waveforms V265M EN M A004 6 Supporting functions 6 2 Disturbance recorder V265M EN M A004 Available channels The following channels i e signals can be linked to a disturbance rec
196. tion monitoring function with maximum eight current cycles points See Table 6 4 1 If less than eight points needed the unused points are set to Ipic 1 where Isic is more than the maximum breaking capacity If the CB wearing characteristics or part of it is a straight line ona log log graph the two end points are enough to define that part of the characteristics This is because the relay is using logarithmic interpolation for any current values falling in between the given current points 2 8 The points 4 8 are not needed for the CB in Figure 6 4 1 Thus they are set to 100 kA and one operation in the table to be discarded by the algorithm Number of permitted operations 100 200 500 1000 10000 100000 Breaked current A CBWEARcharacteristics Figure 6 4 1 An example of a circuit breaker wearing characteristic graph V265M EN M A004 6 Supporting functions 6 4 Circuit breaker condition monitoring Table 6 4 1 An example of circuit breaker wearing characteristics in a table format The value are taken from the figure above The table is edited with VAMPSET under menu BREAKER CURVE Point Interrupted current Number of permitted kA operations 1 0 mechanical age 10000 2 1 25 rated current 10000 3 31 0 maximum breaking current 80 4 100 1 5 100 1 6 100 1 7 100 1 8 100 1 Setting alarm points There are two alarm points available having two setting pa
197. tions are frequency and instantaneous current for arc protection The figure shows a current waveform and the corresponding fundamental frequency component second harmonic and rms value in a special case when the current deviates significantly from a pure sine wave l i T 10 mann ee ak a EE Load 0 100 ae aS oN s P Spe Eo bo A E i 5t 10t 0 00 005 010 015 020 025 030 Time s InrushCurrentLoad0 Figure 7 1 Example of various current values of a transformer inrush current V265M EN M A004 7 Measurement functions 7 1 Measurement accuracy 7 1 V265M EN M A004 Measurement accuracy Phase current inputs ln h2 l3 Pu I t2 V ts Measuring range 25mA 250 A 5A 5mA 50 A 1A Inaccuracy 1 lt 7 5A 0 5 of value or 15 mA I gt 7 5A 3 of value The rated input In is 5A or 1A It is specified in the order code of the relay The specified frequency range is 45 Hz 65 Hz Residual current inputs loi loz Measuring range 0 5 xly Inaccuracy 1 lt 1 5 xln 0 3 of value or 0 2 of In gt 1 5 xl 3 of value The specified frequency range is 45 Hz 65 Hz The rated input I is 5A or 1A This must be specified when ordering the relay Frequency Measuring range 16 Hz 75 Hz Inaccuracy 10 mHz In VAMP 265M frequency is measured from current signals THD and harmonics Inaccuracy 10 1 PU
198. unctions V265M EN M A004 Stall protection stage 48 Setting range Motor start detection current Nominal motor start current 1 30 10 00 xlor step 0 01 1 50 10 00 xlmor step 0 01 Definite time characteristic operating time 1 0 300 0 s step 0 1 Inverse time characteristic 1 characteristic curve Inv Max allowed start time 1 0 200 0 s step 0 1 Minimum motor stop time to activate stall 500 ms protection Maximum current raise time from motor 200 ms stop to start Motor stopped limit 0 10 x Imor Motor running lower limit 0 20 x Imor Motor running limit after starting 1 20 x Imot Starting time Typically 60 ms Resetting time lt 95 ms Resetting ratio 0 95 Inaccuracy Starting Operating time at definite time function Operating time at IDMT function 3 of the set value or 5 mA secondary 1 or at 30 ms 5 or at least 30 ms This is the instantaneous time i e the minimum total operational time including the fault detection time and operation time of the trip contacts Earth fault stage lo gt 50N 51N Input signal lo input X1 7 amp 8 lo2 input X1 9 amp 10 locatc ILitILo li3 Setting range lo gt 0 02 8 00 When loor loz 0 05 20 0 When locaic Definite time function Operating time DT 0 08 300 00 s step 0 02 s IDMT function Delay curve family C
199. urve type Time multiplier k DT IEC IEEE RI Prg El VI NI LTI MI depends on the family 0 05 20 0 except 0 50 20 0 for RXIDG IEEE and IEEE2 Starting Peak mode Operating time at definite time function Operating time at IDMT function Start time Typically 60 ms Reset time lt 95 ms Reset ratio 0 95 Inaccuracy Starting 2 of the set value or 0 3 of the rated value 5 of the set value or 2 of the rated value Sine wave lt 65 Hz 1 or 30 ms 5 or at least 30 ms El Extremely Inverse NI Normal Inverse VI Very Inverse LTI Long Time Inverse Ml Moderately Inverse This is the instantaneous time i e the minimum total operational time including the fault detection time and operation time of the trip contacts 213 12 3 Protection functions 12 Technical data Earth fault stages lo gt gt lo gt gt gt lo gt gt gt gt 50N 51N Input signal lo input X1 7 amp 8 lo2 input X1 9 amp 10 locate lL1 lL2 l13 Setting range lo gt gt 0 02 8 00 When Ip or loz 0 05 20 0 When locaic Definite time function Operating time 0 08 300 00 s step 0 02 s Start time Typically 60 ms Reset time lt 95 ms Reset ratio 0 95 Inaccuracy Starting 2 of the set value or 0 3 of the rated value Starting Peak mode 5 of the set value or 2 of the rated value Sine wave lt 65 H
200. uts RS232 RS485 and Optical Tx Rx Communication 48 230 Vac dc VX003 3 RS232 programming cable Vampset VEA 3CGi Cable length 3m VX004 M3 TTL RS232 converter cable PLC VEA 3CGi Cable length 3m VX007 F3 TTL RS232 converter cable VPA 3CG Cable length 3m VA 1 DA 6 Arc Sensor Cable length 6m VAM 16D External LED module Disables rear local communication VYX076 Raising Frame for 200 serie Height 40mm VYX077 Raising Frame for 200 serie Height 60mm VYX233 Raising Frame for 200 serie Height 100mm V200W AF V200 wall aseembly frame 220 V265M EN M A004 16 Revision history 16 V265M EN M A004 Revision history Manual revision history Manual version Description V265M EN M A004 The first version Firmware revision history Firmware version Description 10 45 Motor differential functions 10 46 NVRAM event buffer size is user parameter 10 48 Support for HMS Profibus solution IRIG BOO3 10 49 Polarity added for relays VAMP265M support Read write MAC address to from EEPROM with new chip IEC 61850 DI counters are reported via deadband calculation 10 58 New features in IEC 61850 added Output vef files with Suomi amp Russian language packets 10 67 100 Mbps option card support 10 68 Default font sizes changed lo gt gt minimum delay setting changed to 0 05s 10 74 I gt and I gt l gt gt gt gt stages with faste
201. values max six values DOS O e o O VAMP260lcd2 Figure 2 1 1 2 Sections of the LCD dot matrix display Main menu column The heading of the active menu The cursor of the main menu Possible navigating directions push buttons Measured setting parameter Measured set value Doe D O V265M EN M A004 2 Local panel user interface 2 1 Relay front panel V265M EN M A004 Backlight control Display backlight can be switched on with a digital input virtual input or virtual output LOCALPANEL CONF Display backlight ctrl setting is used for selecting trigger input for backlight control When the selected input activates rising edge display backlight is set on for 60 minutes Menu navigation and pointers 1 Use and to move up and down in the main menu that is on the left hand side of the display The active main menu option is indicated with a cursor The options in the main menu items are abbreviations e g Evnt events 2 After any selection the arrow symbols in the upper left corner of the display show the possible navigating directions applicable navigation keys in the menu 3 The name of the active submenu and a possible ANSI code of the selected function are shown in the upper part of the display e g CURRENTS 4 Further each display holds the measured values and units of one or more quantities or parameters e g Il max 300A Keypad You can navigate in the menu and set the required parameter
202. view 11 Connections Terminal X3 Iai No Symbol Description MES 1 48V Internal wetting voltage for digital inputs 1 6 21 2 DIt Digital input 1 3l 3 DI2 Digital input 2 4 4 DIS Digital pul 3 5 5 DI4 Digital input 4 all 6 DI5 Digital input 5 ae 7 DIG Digital input 6 711 9 9 A1 COM Alarm relay 1 common connector a pa 10 A1NO Alarm relay 1 normal open connector i S 11 A1NC Alarm relay 1 normal closed connector 5 pal 12 T2 Trip relay 2 T a 13 T2 Trip relay 2 bd 14 T1 Trip relay 1 14 15 ITI Trip relay 1 15 SY 16 as ean 14 17 Uaux Auxiliary voltage 17 18 Uaux Auxiliary voltage 18 A Terminal X6 O No Symbol Description 1 BI External arc light input 2 2 BO Arc output g 3 COM Common for BI and BO 2 4 S1 gt Arc sensor 1 positive connector 5 S1 gt Arc sensor 1 negative connector 6 S2 gt Arc sensor 2 positive connector 7 S2 gt Arc sensor 2 negative connector Arc sensor itself is polarity f ree Terminal X6 with DI19 DI20 option No Symbol Description lt 1 DI19 Digital input 19 gt 2 DI19 Digital input 19 S 3 DI20 Digital input 20 4 DI20 Digital input 20 Q 5 a
203. virtual inputs virtual outputs or LED indicator signals By using virtual I O the active setting group can be controlled using the local panel mimic display any communication protocol or using the inbuilt programmable logic functions Forcing start or trip condition for testing The status of a protection stage can be one of the followings e Ok The stage is not detecting any fault e Blocked The stage is detecting a fault but blocked by some reason e Start The stage is counting the operation delay e Trip The stage has tripped and the fault is still on The blocking reason may be an active signal via the block matrix from other stages the programmable logic or any digital input Some stages also have inbuilt blocking logic For example an under frequency stage is blocked if voltage is too low For more details about block matrix see chapter 8 5 Forcing start or trip condition for testing purposes There is a Force flag parameter which when activated allows forcing the status of any protection stage to be start or trip for a half second By using this forcing feature any current or voltage injection to the relay is not necessary to check the output matrix configuration to check the wiring from the output relays to the circuit breaker and also to check that communication protocols are correctly transferring event information to a SCADA system After testing the force flag will automatically reset 5 minute after the l
204. welve months are stored in the non volatile memory of the relay Corresponding time stamps are stored for the last 31 days The registered values are listed in the following table Measurement Max Min Description IL1 IL2 IL3 X Phase current fundamental frequency value lo1 lo2 X Residual current The value can be a one cycle value or an average according parameter Timebase Parameters of the day and month registers Parameter Value Description Set Timebase Parameter to select the type of the S registered values 20ms Collect min amp max of one cycle values 3 200 ms Collect min amp max of 200 ms average values 1s Collect min amp max of 1 s average values 1 min Collect min amp max of 1 minute average values demand Collect min amp max of demand values see chapter 7 4 ResetDays Reset the 31 day registers S ResetMon Reset the 12 month registers S This is the fundamental frequency rms value of one cycle updated every 20 ms 134 V265M EN M A004 7 Measurement functions 7 7 Primary secondary and per unit scaling 7 7 7 7 1 V265M EN M A004 Primary secondary and per unit scaling Many measurement values are shown as primary values although the relay is connected to secondary signals Some measurement values are shown as relative values per unit or per cent Almost all pick up setting values are using relative scaling
205. with time constant of 1ms 220V 25A with time constant of 1ms Power consumption lt 7 W normal conditions lt 15 W output relays activated Max permitted interruption time gt 50 ms 110 V dc Terminal block Maximum wire dimension Phoenix MVSTBW or equivalent 2 5 mm 13 14 AWG V265M EN M A004 207 12 1 Connections 12 Technical data 12 1 3 12 1 4 12 1 5 12 1 6 208 Digital inputs Number of inputs 6 Operation time 0 00 60 00 s step 0 01 s Polarity NO normal open or NC normal closed Inaccuracy Operate time 1 or 10 ms Internal operating voltage 48 V dc Current drain when active max Approx 20 mA Current drain average value lt 1mA Terminal block Phoenix MVSTBW or equivalent Max wire dimension 2 5 mm 13 14 AWG Trip contacts Number of contacts 2 making contacts Rated voltage 250 V ac dc Continuous carry 5A Make and carry 0 5 s 30 A Make and carry 3s 15A Breaking capacity AC 2 000 VA Breaking capacity DC L R 40ms at 48 V dc 5A at 110 V dc 3A at 220 V dc 1A Contact material AgNi 90 10 Terminal block Phoenix MVSTBW or equivalent Maximum wire dimension 2 5 mm 13 14 AWG Alarm contacts Number of contacts 3 change over contacts relays A1 A2 and A3 2 making contacts relays A4 and A5 1 change over contact IF relay Rated volt
206. word needed F Editable when force flag is on 139 8 2 Digital inputs 8 Control functions 8 2 140 Digital inputs There are 6 digital inputs available for control purposes The polarity normal open NO normal closed NC and a delay can be configured according the application The signals are available for the output matrix block matrix user s programmable logic etc The contacts connected to digital inputs DI1 DI6 must be dry potential free These inputs use the common internal 48 Vdc wetting voltage from terminal X3 1 only Common Input group Wetting voltage input On Off X7 7 X7 1 6 DI 7 12 218 Voc or 250 Vac lt 10 Vpc or lt 5 Vac NOTE These digital inputs must not be connected parallel with inputs of an another device Label and description texts can be edited with VAMPSET according the application Labels are the short parameter names used on the local panel and descriptions are the longer names used by VAMPSET Parameters of digital inputs Parameter Value Unit Description Set DI1 DIG 0 Status of digital input 1 DI COUNTERS DI1 DIG 0 65535 Cumulative active edge Set counter DELAYS FOR DIGITAL INPUTS DI1 DIG 0 00 60 00 s Definite delay for both on Set and off transitions CONFIGURATION DI1 DI6 Inverted no For normal open contacts Set NO Active edge is O gt 1 yes For normal closed contacts N
207. ype P 100Mbps Ethernet interface with IEC 61850 and Serial interface for external converters only REMOTE port D9S and RJ 45 D connector 1 reserved 2 TX_out TTL 3 RX_in TTL 4 RTS out TTL 7 GND 9 8V out RJ 45 connector 1 Transmit 2 Transmit 3 Receive 4 Reserved 5 Reserved 6 Receive 7 Reserved 8 Reserved R 100 Mbps Ethernet fibre interface with IEC 61850 LC connector from top Port 2 Tx Port 2 Rx Port 1 Tx Port 1 Rx S 100Mbps Ethernet interface with IEC 61850 2 x RJ 45 e ie 1 Transmit 2 Transmit 3 Receive 4 Reserved 5 Reserved 6 Receive 7 Reserved 8 Reserved NOTE In the VAMP relays RS485 interfaces a positive voltage from Tx to Tx or Rx to Rx does correspond to the bit value 1 In X5 connector the optional RS485 is galvanically isolated NOTE In 2 wire mode the receiver and transmitter are internally connected in parallel See a table below V265M EN M A004 11 Connections 11 3 Serial communication connectors V265M EN M A004 ZA O 2 U X5 Sol QF X5 E O 3 lt oJ BE ol Be X 5 O OIA S X45 x 4 RS485 Figure 11 3 2 1 Pin numbering of the rear Figure 11 3 2 2 Pin numbering of the communication ports REMOTE TTL rear communication ports REMOTE RS 485 Fibre RX Lee a E Q _ E X5 OP 5 Be LL aw
208. z Operate time 1 or 30 ms This is the instantaneous time i e the minimum total operational time including the fault detection time and operation time of the trip contacts 12 3 3 Second harmonic function 2 Harmonic stage 51F2 Settings Setting range 2 Harmonic 10 100 Operating time 0 05 300 00 s step 0 01 s Inaccuracy Starting 1 unit NOTE The amplitude of second harmonic content has to be at least 2 of the nominal of CT If the moninal current is 5 A the 100 Hz component needs to exceed 100 mA 12 3 4 Fifth harmonic function 5 Harmonic stage 51F5 Settings Setting range 2 Harmonic 10 100 Operating time 0 05 300 00 s step 0 01 s Inaccuracy Starting 2 unit NOTE The amplitude of second harmonic content has to be at least 2 of the nominal of CT If the moninal current is 5 A the 250 Hz component needs to exceed 100 mA 214 V265M EN M A004 12 Technical data 12 3 Protection functions 12 3 5 12 3 6 V265M EN M A004 Circuit breaker failure protection Circuit breaker failure protection CBFP 50BF Relay to be supervised T1 T12 Definite time function Operating time 0 1 10 0 s step 0 1 s Reset time lt 95 ms Inaccuracy Operating time 20 ms This is the instantaneous time i e the minimum total operational time including the fault detection time and operation time of the t
Download Pdf Manuals
Related Search
Related Contents
Hamilton Beach 14970 Iron User Manual 【基礎プログラム】 Toshiba 6F3A4508 Computer Drive User Manual VGA to HDMI Converter with Scaler VC182 User Manual Dossierdepresse_Printempsdespoetes Method and apparatus for performing saturation instructions using Higrometros digitais e analogicos economicos 3427 Télécharger les informations concernant la garantie de Copyright © All rights reserved.
Failed to retrieve file