Home

Product Manual - American Biotech Supply

image

Contents

1. Hot humid weather increases condensation Make sure there is a water trap U shaped loop in the drain tube near the compressor This will trap a small amount of water in the loop and prevent air from entering the chamber through the tube Moisture collects on outside surface Hot humid weather increases condensation As humidity decreases moisture will disappear Odor inside the unit Interior needs to be cleaned See section on maintenance and cleaning in this manual Make sure product containers are tightly sealed to prevent leakage Door will not close The unit is not level Refer to the Leveling section at the beginning of this manual Check for dirt and debris or items passing through the door seal MOISTURE DURING THE SUMMER SEASON The amount of moisture condensation or high humidity related issues increase during the summer and in most cases will self resolve when the weather cools down Please note a refrigeration system will NOT generate moisture or water but simply condenses the moisture that is already in the chamber Keeping the unit in an air conditioned low humidity space will resolve many issues Other things you should check 1 Location of the freezer See Quick Troubleshooting Guide above 2 Door sealing and frequency of door opening event See Quick Troubleshooting Guide above 3 Make sure there is a water trap U shaped loop in the drain tube near the end
2. Celsius mode The display shows the current status F for Fahrenheit or C for Celsius Press up or down arrow to toggle between the F or C F or C Fahrenheit or Celsius Scale Press SET key again to access the set point mode The LCD will display the current set point and S1 will be blinking Press the up and down keys to adjust to the desired setting S1 blinking Set point Temperature Press SET key again to access the differential mode The LCD will display the current differential and DIF1 will be blinking Press the up and down keys to adjust to the desired setting DIF 1 blinking Differential Temperature Press SET key again to access the cooling or heating mode The LCD displays the current mode C1 for cooling or H1 for heating Press up or down key to toggle between C1 and H1 Press the SET key again to exit programming mode C1 H1 Cooling or Heating mode Part number 20079 Rev 0 14 Error Messages Display Messages Corrective Action E1 Appears when either the up or down key is pressed when not in the programming mode If the E1 message appears even when no keys are being pressed replace control E2 Appears if the control settings are not properly stored in memory Check all settings and correct if necessary EP Appears when the probe is open shorted or sensing a temperature that is out of range Check to see if the sensed temperature is out of range If not
3. This will trap a small amount of water in the loop and prevent air from entering the chamber through the tube Before calling the manufacturer s Technical Support Department please have the unit s model and serial number ready as well as the problem description The model and serial number is located on the serial tag which can be found on the interior left upper wall of the unit Part number 20079 Rev 0 17 MAINTENANCE AND CLEANING Manual Defrost Freezers All models except ABT 3020AP should be defrosted whenever to inch of frost has accumulated Use the procedures in the defrosting section starting at the bottom of this page for best results They should also be cleaned periodically Use the cleaning agents and suggestions in the table below for best results Model ABT 3020AP is an Auto Defrost Freezer and requires little maintenance Like the other models it should be cleaned periodically to keep it running efficiently Use the cleaning agents and suggestions in this table for best results CLEANING PART CLEANING AGENTS TIPS AND PRECAUTIONS Interior and Door Liners Soap and water Baking soda and water Use 2 tablespoons of baking soda in 1 quart of warm water Be sure to wring excess water out of sponge or cloth before cleaning around controls light bulb or any electrical parts Door Gaskets Soap and water Wipe gaskets and their seating surfaces with a clean soft cloth Shelves Soap and water Do no
4. 20079 Rev 0 8 The STATUS tricolor LED shows the status of the unit Green normal run mode Amber program mode Red temperature is out of range The light blinks off briefly each second to show the unit is active The ALARM TEST push button interrupts line power to allow testing of the battery and the alarm relay The bright red ALARM LED shows alarm conditions In alarm mode it flashes every half second In alarm mute mode it gives a short blink every second In battery mode it gives a short blink every two seconds The BEEPER shows alarm conditions and user activity In alarm mode it gives a long beep In alarm mute mode it gives a short chirp It gives an audible tick to indicate a button has been pressed The MUTE PROGRAM button has three functions In Normal Run mode if the unit is beeping pressing the button will mute the beeper for a preset time Each time the button is pressed the mute time resets Holding the button down for two seconds takes the unit out of Normal Run mode and into Programming mode At the same time it mutes the beeper When in Programming mode pressing the button steps the unit through the various programming parameters The UP button has a different function for each operating mode In Normal Run mode pressing the button causes the high temperature set point to be displayed In Programming mode pressing the button incre
5. Center will not declare an alarm until the out of range state has continued for a specified time the alarm delay This alarm delay time will prevent transient nuisance alarms The alarm delay time can be set for 0 to 30 minutes Part number 20079 Rev 0 11 rd Relay Delay If there is an alarm condition the relay contacts will switch The relay delay parameter allows the user to set the amount of time delay from the start of the alarm condition to the time the relay contact switches This keeps the relay from switching during short nuisance alarms The operator may set the relay delay time for 0 to 30 minutes SIL Alarm Silence or Alarm Mute Time This parameter sets the number of minutes the beeper will chirp when the mute button is pressed during an alarm condition After the Silence Time elapses if the alarm condition still exists the beeper will begin to sound at full volume again This parameter can be set from 5 to 120 minutes Remote Alarm Contacts The Remote Alarm Relay is a single pole double throw SPDT relay that changes state switches with the loss of line power or with the presence of an alarm condition NOTE The relay is rated for pilot duty operation only Do NOT use it for control switching The relay contacts and connections are rated at 30v 1A In normal applications the relay signals remote alarms or central monitoring systems that an alarm condition has occurred at the unit being monitored
6. Horizon Scientific Inc determines have been subjected after the date of manufacture to alteration neglect abuse misuse accident damage during transit or installation fire flood or other external causes It does not apply to defects resulting from failure to properly install operate or maintain the product in accordance with the printed instructions provided or damage caused by the storage of any corrosive material that comes in contact with the interior or exterior portions of the cabinet or the use of spark producing equipment or containers such as galvanized or carbonized steel containers that come in contact with any interior portion of the cabinet OUTSIDE U S CANADA This warranty does not apply to and Horizon Scientific Inc is not responsible for any warranty claims made on products sold or used outside the United States and Canada CHOICE OF LAW VENUE The laws of the State of South Carolina shall govern the validity interpretation and enforcement of this warranty regardless of conflicts of law principles Purchaser agrees that proper venue for any action to enforce the terms of this warranty shall be the Dorchester County District Courts South Carolina Purchaser submits the jurisdiction of such courts over the Purchaser and the subject matter of any such action Any action for breach of these warranty provisions must be commenced within one 1 year after that cause of action has accrued WARRANTY CLAIMS To obtain prompt
7. The relay will pull in when line power is present If an alarm condition lasts for a designated time the relay delay the relay will drop out causing the relay contacts to switch If the alarm condition does not last long enough for the relay delay to time out the relay will not go into its alarm position The relay will also drop out if power to the alarm is lost acting as a power loss detector The diagram below is an example of hooking up our external relay output to a remote alarm Part number 20079 Rev 0 12 DIGITAL MICROPROCESSOR TEMPERATURE CONTROLLER Product Description The digital microprocessor temperature controller is designed to provide on off control of refrigerators or freezers The controller also provides a constant readout of the air temperature inside of the unit A touch keypad allows the user to easily select the display units set point differential set point and heating or cooling mode Please Note The digital temperature controller has been factory set and tested to allow your unit to operate at its desired temperature cycle Adjusting the settings on the controller will alter these factory settings WE STRONGLY RECOMMEND YOU CONTACT THE MANUFACTURER S TECHNICAL SUPPORT DEPARTMENT BEFORE MAKING ANY ADJUSTMENTS TO THIS CONTROLLER Part number 20079 Rev 0 13 Programming Procedure Display Description Display To start programming press the SET key once to access the Fahrenheit
8. check for probe damage by comparing it to a known ambient temperature between 30 F and 220 F Replace the probe if necessary EE Appears if the EPROM data has been corrupted This condition cannot be field repaired Replace the control CL Appears if calibration mode has been entered Remove power to the control for at least five seconds Reapply power If the CL message still appeared replace the control Part number 20079 Rev 0 15 QUICK TROUBLESHOOTING GUIDE Check these items before calling for service PROBLEM POSSIBLE CAUSE SOULTIONS Unit does not run Electrical circuit is not 110 120V 60Hz The power cord is not plugged in No power at electrical outlet Check to make sure breaker is not tripped or fuse is not blown Additionally make sure unit is not plugged into a Ground Fault Circuit Interrupter GFCI type of outlet Unit does not maintain at the proper temperature Check the room temperature We recommend the refrigerator or freezer should be placed in the air conditioned room between 65 F to 85 F If the room temp is too warm the refrigerator or freezer may not be able to maintain the interior temp at proper range Door is not closed properly Amount of stored product is overloaded Product replacements are pushed against rear wall or interrupted the proper refrigerator air circulation For the proper air circulation place the products evenly on each s
9. equipment is delivered Unless subject to prior written agreement with Horizon Scientific Inc this warranty does not allow for any warranty start deferment greater than two weeks from date of shipment due to a delayed installation and or start up By purchasing any product from Horizon Scientific Inc you and any entity for which you are purchasing acknowledge and agree to each and every provision contained herein and all other Notices and Terms provided to Purchaser by Horizon Scientific Inc which are hereby incorporated Under this warranty Horizon Scientific Inc through its authorized service organizations will repair or at its option replace any part found to contain a manufacturing defect in material or workmanship without charge to the owner for parts and service labor Replacement or repaired parts will be warranted for only the unexpired portion of the original warranty Horizon Scientific Inc will not assume any shipping or cartage costs for parts under warranty These costs shall be paid by the customer ADDITIONAL THREE YEAR COMPRESSOR WARRANTY In addition to the two 2 year warranty stated above Horizon Scientific Inc warrants its hermetically and semi hermetically sealed compressors to be free from defects in both material and workmanship under normal use and service for a period of three 3 additional years from the end of the initial two 2 year warranty period but not to exceed five 5 years after shipment from
10. for best results These freezers come with 5 interior doors one for each shelf to help minimize the temperature transients resulting from opening the main door You should still minimize the time the freezer door is open On top of letting the cold air out you are also letting warm moist air in which will result in the buildup of more frost in the unit Model ABT 3020AP has an auto defrost feature Every 6 hours it will go into a defrost cycle to remove frost build up During this cycle which can last up to 25 minutes the compressor is turned off and defrost heaters are turned on in the evaporator section This will cause a temperature transient which will be seen in air temperature inside the unit but should not significantly affect product temperatures The other models need to be periodically defrosted This procedure is located in the Maintenance and Cleaning section of this manual Remember that the units are calibrated to the desired temperature range before leaving the factory We also do extensive testing to ensure that these temperatures will result in product temperatures in the desired band There should be no need to adjust the temperature control on these units but if it is necessary they can be adjusted using the manual thermostat on the back of the unit It is STRONGLY RECOMMENDED that you contact the manufacturer s Technical Support Department prior to performing any temperature adjustments to ensure the adjustment is nece
11. temperature goes back within range and there are no out of range readings for thirty seconds the chirping stops and the MUTE PROGRAM button resets If another out of range condition then occurs the beeper will again start at full volume After the user programmable SILENCE parameter times out if the alarm condition still exists the beeper will annunciate again at full volume until MUTE PROGRAM is pushed Battery Back Up B The Control Center has a battery back up option It ships with the battery in place and connected Remove the white nylon screw located on the lower left side of the module to activate the battery option When line power is present all of the normal features of The Control Center are operating When line power is lost the battery provides power to maintain two important functions Operate the audio and visual alarms They flash beep less frequently than usual in order to avoid draining the battery Continue to display the temperature of the area being monitored The display will flash to save power Part number 20079 Rev 0 10 Testing the battery The battery recharges when the unit is plugged into line power To test the battery push the ALARM TEST button on the front panel The following should happen The ALARM LED will flash red The beeper alarm will begin to chirp The remote alarm relay will switch PROGRAMMING To program The Control Center Monitor 1 Ho
12. HE PRODUCT S GIVING RISE TO THE CLAIM OR LIABILITY Part number 20079 Rev 0 20 WARRANTY IS NOT TRANSFERABLE This warranty is not assignable and applies only in favor of the original purchaser user to whom delivered Any such assignment or transfer shall void the warranties herein made and shall void all warranties express or implied including any warranty of merchantability or fitness for a particular purpose NO IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE There are no other warranties express implied or statutory except the two 2 year warranty and the additional three 3 year compressor warranty as described above These warranties are exclusive and in lieu of all other warranties including implied warranty and merchantability or fitness for a particular purpose There are no warranties which extend beyond the description on the face hereof whether based on contract warranty tort including negligence strict liability indemnity or any other legal theory and whether arising out of warranties representations instructions installations or non conformities from any cause Purchaser further acknowledges that the purchase price of the Product reflects these warranty terms and remedies ALTERATION NEGLECT ABUSE MISUSE ACCIDENT DAMAGE DURING TRANSIT OR INSTALLATION FIRE FLOOD OR OTHER EXTERNAL CAUSES Horizon Scientific Inc is not responsible for the repair or replacement of any parts that
13. Horizon Scientific Inc Compressors determined by Horizon Scientific Inc to have been defective within this extended time period will at Horizon Scientific Inc s option be either repaired or replaced with a compressor or compressor parts of similar design and capacity The three 3 year extended compressor warranty applies only to hermetically and semi hermetically sealed parts of the compressor and does not apply to any other parts or components including but not limited to cabinet paint finish temperature control refrigerant metering device driers motor starting equipment fan assembly or any other electrical components Horizon Scientific Inc s sole obligation under this warranty is limited to either repair or replacement of parts subject to the additional limitations below This warranty neither assumes nor authorizes any person to assume obligations other than expressly covered by this warranty NO CONSEQUENTIAL DAMAGES Horizon Scientific Inc is not responsible for economic loss profit loss or special indirect or consequential damages including without limitation losses or damages arising from contents spoilage claims whether or not on account of refrigeration failure electrical failure power failure or compressor failure HORIZON SCIENTIFIC INC S MAXIMUM CUMULATIVE LIABILITY RELATIVE TO ALL CLAIMS AND LIABILITIES INCLUDING OBLIGATIONS UNDER ANY INDEMNITY WHETHER OR NOT INSURED SHALL NOT EXCEED THE COST OF T
14. Part number 20079 Rev 0 1 PREMIERE SOLID DOOR FREEZERS ABT 2020MP ABT 2030MP ABT 3020MP ABT 3030MP ABT 3020AP OWNER S INSTRUCTIONS This manual describes how to operate and care for your appliance to get the best most efficient performance READ THIS BOOK Note to Customer This merchandise was carefully packed and thoroughly inspected before leaving our plant Responsibility for its safe delivery was assumed by the carrier upon acceptance of the shipment As directed on the side of your packing carton claims for loss or damage sustained in transit must be made on the carrier as follows A Visible Loss Damage Shortage External Evidence of Loss or Damage This type of damage must be noted on the freight bill and acknowledged by the carrier s agent driver at time of delivery Make sure you get a signed copy Send a written request for an inspection to the carrier B Concealed Damage This type of damage may not be discovered until the unit is being unpacked When concealed damage is discovered stop unpacking immediately and contact the carrier immediately to report the claim and request an inspection This should be done as soon as possible and in any case must be done within 15 days or receiving the merchandise If at all possible do not move the item and save all packaging material for carrier s inspection C FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN THE CARRIER REFUSING TO HONOR YOUR COMPANY S CLAIM
15. RATING This unit comes with an optional roller base so you can unpack it in an open area and then place it on the roller base to move to its normal location Remove the wooden planks or skid as shown These units come with a caster platform or roller base To place the unit on the roller base have one person tilt the machine forward and hold it while a second person slides the roller base in from the back Note that the side without a top lip goes towards the front of the unit Once it is in as far as it will go have the second person lock the rear wheels and hold the base firmly in place while the first person tilts the machine up and onto the roller base pushing it back until all 4 corners are on the base You can now unlock the rear wheels and move the unit to its final location The freezer should be placed as close as possible to a dedicated power outlet so an extension cord will not be needed This unit requires a minimum of 4 inches of air flow space in back and 3 inches on the sides and top Once the unit is in place the rear casters on the roller base should be locked to prevent inadvertent movement LEVELING Once the unit is in place either on or off of the roller base you can level it with the screw type adjustable leveling legs on the front corners of the unit Turn counterclockwise to raise the corner turn clockwise to lower it The unit may have a slight tilt from front to back after the legs are installed This is acceptable an
16. UNDER NO CIRCUMSTANCES SHOULD THE MERCHANDISE BE RETURNED TO THE MANUFACTURER NO RETURNS WILL BE ACCEPTED WITHOUT PRIOR AUTHORIZATION Horizon Scientific 125 Varnfield Drive Summerville SC 29483 Phone 800 648 4041 Fax 843 821 8051 Warranty Two Year Parts and Labor 5 Years Compressor Parts Revision Date 08 30 2012 Part number 20079 Rev 0 2 Table of Contents RECEIVING 3 INSTALLATION 4 FREEZER OPERATION 6 CONTROL CENTER TEMPERATURE MONITOR SYSTEM 7 DIGITAL MICROPROCESSOR TEMPERATURE CONTROLLER 12 QUICK TROUBLESHOOTING GUIDE 15 MAINTENANCE AND CLEANING 17 PRODUCT WARRANTY 19 BEFORE CALLING THE MANUFACTURER S TECHNICAL SERVICE DEPARTMENT please have the unit s model and serial number ready as well as the problem description The model and serial number is located on the serial tag which can
17. ases the displayed parameter value The DOWN button has a different function for each operating mode In Normal Run mode pressing the button displays the low temperature set point In Programming mode pressing the button decreases the displayed parameter value Part number 20079 Rev 0 9 BASIC OPERATION The Control Center Monitor has two modes NORMAL RUN MODE and PROGRAMMING MODE In Normal Run mode the display shows the temperature that the probe is reading to the lowest whole number i e if it shows a value of 10 0 the actual temperature can range from 10 0 to 10 9 Press the UP button to cause the display to show the high temperature set point Press the DOWN button to cause the display to show the low temperature set point The Control Center compares the probe s temperature reading to HIGH and LOW temperature set points The STATUS LED glows green when the probe reads an in range temperature between the two set points and red when the temperature is out of range equal to or outside the set points The Control Center will not declare an alarm until the out of range state has continued for a specified time the alarm delay This alarm delay time is designed to prevent transient nuisance alarms When an alarm condition is declared the BEEPER and ALARM LED will both activate Press the MUTE PROGRAM button to stop the beeper for a specified time changing the sound to short chirps When the
18. be found on the interior left upper wall of the unit For convenience you may want to record the following information here for easy access in the future Model number __________________________________ Serial number __________________________________ Date of delivery _________________________________ Part number 20079 Rev 0 3 RECEIVING Your unit was built packaged and inspected with extreme care We shipped it to you using carriers we trust with a proven track record of careful handling good customer service and on time delivery Unfortunately regardless of all of these efforts sometimes accidents happen and occasionally those accidents result in shipping damage When the carrier picked up the merchandise from us they assumed responsibility for its condition en route to you Thus any claims for shipping damage must be filed with the carrier Like anybody else carriers don t like to pay out on insurance claims so their claims procedures and requirements are very restrictive You should consult the carrier s website for their specific claims procedures You should also know that time is of the essence There are two general types of shipping damage The first is visible damage This type of damage includes visible loss damage shortage or any external evidence of loss or damage that is visible at time of delivery This type of damage must be noted in detail on your delivery receipt Make sure the
19. d is actually recommended POWER SOURCE The supply circuit to this cabinet must conform to all National and Local Electrical Codes Consult the cabinet Serial Data plate for voltage cycle phase and amp requirements before making connection VOLTAGE SHOULD NOT VARY MORE THAN 5 FROM SERIAL PLATE RATINGS A separate circuit is recommended to prevent possible loss of product due to over loading or failure of other equipment on the same circuit PROTECT THE CIRCUIT WITH A 20 AMP DELAY TYPE FUSE OR CIRCUIT BREAKER Do not use an extension cord Be sure your unit is properly grounded Use the 3 prong plug provided into a 3 prong grounded outlet Only this method complies with national electrical codes local codes and ordinances Unless the above grounding method is followed you are not protected against severe or lethal shock in the event of a short circuit of an electrical component or wiring of the unit STARTING There are no compressor shipping bolts to loosen or valves to open All that is necessary after the unit has been placed on the roller base and leveled is to plug the service cord into an electrical outlet When starting this new appliance allow the cabinet to operate a minimum of eight hours or until Part number 20079 Rev 0 5 it has started cycling normally before placing product in the cabinet The motor compressor may start and stop several times when the unit is first started or after defrosting especially if the weath
20. driver signs and dates the delivery receipt acknowledging the damage This has to happen at the time of delivery or it won t happen at all Keep a copy for your records and send another to the carrier s damage claims department along with a formal request for an inspection report Follow up with a phone call Their contact information can be found on the carrier s web site The second type of shipping damage is concealed damage This type of damage will probably not be apparent at time of delivery and may not be discovered until unpacking and inspecting the unit Remember time is of the essence here You should unpack and inspect the unit as soon as possible Each day that passes reduces the likelihood that the carrier will pay the claim As soon as the concealed damage is discovered stop unpacking and retain all packing materials Contact the carrier by phone to report the claim Note the date and time and person you spoke with Get a claim number Follow up with a written letter referencing the claim number and including a formal request for an inspection Again consult the carrier s website for specific claim instructions and follow them precisely AS STATED ABOVE THE CARRIER IS YOUR SOLE SOURCE FOR SATISFACTION OF A DAMAGE CLAIM UNDER NO CIRCUMSTANCES SHOULD THE MERCHANDISE BE RETURNED TO THE MANUFACTURER NO RETURNS WILL BE ACCEPTED WITHOUT PRIOR AUTHORIZATION Part number 20079 Rev 0 4 INSTALLATION UNC
21. er is very hot This is normal The motor compressor will cycle normally as soon as the excess heat has been removed DOOR BINS not applicable to all models Your unit may come equipped with storage bins in the door Because of the temperature characteristics of these units items stored in these bins may not be maintained in the desired temperature band Please restrict the use of these bins for non critical temperature storage ADJUSTABLE SHELF INSTALLATION not applicable to all models Hook shelf clips onto pilaster strips see Illustration Position all four shelf clips equal in distance from the floor for flat shelves Wire shelves are oriented so that cross support bars are facing down Place shelves on shelf clips making sure all corners are seated properly TEMPERATURE CONTROL NOTE The controls are preset at the factory to provide the desired air and product temperatures inside of the units and require no further adjustment Please contact the manufacturer s Technical Support Department before making any adjustment to make sure the adjustment is necessary and if so to ensure it is performed properly The Digital Microprocessor Temperature Controller is located inside the top of the unit behind the Control Center The operation of this controller is explained in the section starting on page 13 of this manual Part number 20079 Rev 0 6 FREEZER OPERATION After the unit is properly installed and power is applied it wil
22. garden hose adaptor available at most hardware stores can be used to drain the freezer directly into a floor drain Replace the drain plug when defrosting is complete so warm air does not enter the freezer through the hole Defrosting tips If the frost is soft remove it with a plastic scraper If the frost is glazed and hard fill deep pans with hot water and place them inside on the freezer bottom Close the freezer door Frost should soften in about 15 minutes Repeat this procedure as necessary until all frost is removed After defrosting replace the drain plugs if applicable and remove any towels tools or pans from the interior of the freezer Clean the interior and exterior of the unit using the cleaning suggestions on the previous page Plug the unit back in and restore it to service per the operation section of this manual Part number 20079 Rev 0 19 HORIZON SCIENTIFIC INC PRODUCT WARRANTY Horizon Scientific Inc warrants to the original purchaser every new Horizon Scientific Inc refrigerated unit the cabinet and all parts thereof to be free from defects in material or workmanship when such unit is installed used and maintained in accordance with provided instructions for a period of two 2 years The warranty period starts two weeks from the date of shipment from Horizon Scientific Inc This two week period allows ample shipping time so that the warranty will go into effect at approximately the same time your
23. helf Do not push against the refrigerator s rear or side walls Evaporator is blocked by frost or ice Remove the products unplug the refrigerator or freezer power and allow the unit to defrost If the problem still exists call for service 3rd party thermometer is placed incorrectly For proper temperature monitoring the thermometer should be place in the middle of refrigerator PLEASE NOTE Prior to shipment each refrigerator and freezer has been calibrated and tested at proper temperature range Appliance runs too long Prolong door openings Control set too cold Room temperature is high which will make the unit work harder to keep cool Temperature of external wall surface is warm The exterior walls can be as much as 30 degrees warmer than room temperature due to the embedded condenser coils This is normal when the unit is operating Part number 20079 Rev 0 16 PROBLEM POSSIBLE CAUSE SOULTIONS Compressor noises Compressor may be overheated Please check the room temp and ensure the range is within 65 F to 85 F If the problem still exists call for service Moisture collects inside Door gasket is not sealing properly Check for debris cracks and items passing through door at the gasket The freezer is facing a doorway or is underneath of air conditioning vent Relocate the unit or redirect air vent Too many door openings Minimize time door is open
24. l take some time before the system is cooled down to temperature and cycling normally You should wait 8 hours on the first startup before beginning to add product to the unit This ensures that the unit is installed and operating properly before being put into service On subsequent startups after cleanings for example this wait time can be reduced to about 4 hours After this wait time the unit should be cycling in the desired temperature range The units are calibrated before leaving the factory so no adjustment should be necessary Loading the units will again cause temperature to rise as the warmer product is introduced into the compartment If a large amount of product is to be introduced it is a good idea to do it in stages allowing several hours between stages to allow temperature to stabilize again before introducing additional warm product This will minimize the temperature transient while loading Other tips for successful loading include Leave about 2 3 inches of free space along the back and sides of the unit to allow for proper air flow and therefore more even cooling of the product When loading the top shelf avoid blocking the evaporator fan s if installed There should be at least 4 inches of clearance below the fan s to allow proper air flow Do not overload the unit Recommended maximum load is about 75 of the chamber volume Additionally the load should be distributed evenly from top to bottom and side to side
25. ld the MUTE button for two seconds to bring the unit into Programming mode 2 The display will show the first parameter that can be programmed high temperature limit The name of the parameter will flash then the current value of that parameter 3 To change the value of a parameter press the UP or DOWN buttons Pressing either button will change the parameter value by one count 4 Holding either button for half a second will change the parameter value by 10 counts It will continue to step by 10 for each push so long as the pushes occur within a short period 5 Once the Monitor is in Programming mode each time the Mute button is pressed the display steps to the next parameter As the display steps to the next parameter the value of the previous parameter is saved Once the final parameter is reached pressing the MUTE button returns the monitor to Normal Run mode saving the final parameter Description of Parameters for Control Center Hi High Limit In Normal Run mode the alarm will trigger if the probe reads a temperature equal to or above the high temperature limit The high temperature limit cannot be set above the operating temperature range of the unit Lo Low Limit When in Normal Run mode the alarm will trigger if the probe reads a temperature equal to or below the low temperature limit The low temperature limit cannot be set below the operating temperature range of the unit Ad Alarm Delay The Control
26. ssary and if so it is performed correctly Part number 20079 Rev 0 7 CONTROL CENTER Temperature Monitor System The temperature control center monitor system on the front of the unit provides the following functions to provide an indication of the sample temperature inside of the compartment to provide a local alarm at the unit in the event an out of range temperature exists to provide the ability to connect remote systems to provide remote alarms or notifications in the event of an out of range temperature to provide the ability to adjust set points as well as program and test other parameters associated with the alarm system i e delay times system status a battery backup which will maintain the alarm system for several hours after a power failure to allow for continued alarm and notification functions The temperature monitor system does NOT control the temperature of the unit That function is performed by the Microprocessor Digital Temperature Control which is preset at the factory and should not need to be adjusted by the user CONTROL CENTER PANEL The LCD Display shows the temperature in C In the event of a loss of power the display shows a BAT message to indicate that the monitor is running on the battery If the battery is low the BAT message will blink ALARM MUTE PROGRAM UP button DOWN button STATUS tri color LED ALARM TEST button Alarm beeper Part number
27. t wash removable shelves in dishwasher Exterior and Handles Soap and water Non Abrasive Glass Cleaner Do not use commercial household cleaners ammonia or alcohol to clean handles Use a soft cloth to clean smooth handles Do not use a dry cloth to clean smooth handles Manual Defrosting All models except ABT 3020AP It is important to defrost and clean the freezer when to inch of frost has accumulated Frost may tend to accumulate faster on upper part of the freezer due to warm moist air entering the freezer when the door is opened Between defrost evolutions you can minimize frost build up by using a plastic scraper to remove frost Scrape with a pulling motion Never use a metal Part number 20079 Rev 0 18 instrument to remove frost Never use a damp cloth or wet hands as they will stick to the inside surfaces when cold When defrosting becomes necessary disconnect freezer from power source by unplugging to avoid electrical hazard DO NOT ADJUST THE THERMOSTAT Remove the product and leave the door open while defrosting the freezer Remove the drain plug on the inside floor of the freezer by pulling straight out To access the external drain tube on models with a base panel first remove the two screws from the base panel Locate the drain tube near the left center under the freezer Place a shallow pan under the drain tube Defrost water will drain out Check the pan occasionally to ensure it does not overflow A inch
28. warranty service simply contact the manufacturer at 800 648 4041 Horizon Scientific Inc s shipping records showing date of shipment shall be conclusive in establishing the warranty period All claims should include model number of the refrigerator the serial number of the cabinet proof of purchase date of installation and all pertinent information supporting the existence of the alleged defect Any repairs must be authorized by Horizon in order for the warranty to be honored

Download Pdf Manuals

image

Related Search

Related Contents

  0843 FLEX Polyclonal Rabbit Anti-Human Prostate-Specific  Samsung 6kg 1200 apgriezieni priekšējā ielāde WF0602NCE/YLE Lietotāja rokasgrāmata  Focoltone ICCS Installation & User Manual  Samsung HT-DM150 manual de utilizador  Owner`s Manual  LRP Ventilation Control Processor  クロスメディアカッター CH SSCC  MANUEL D`UTILISATION ET D`ENTRETIEN ASPIRE    

Copyright © All rights reserved.
Failed to retrieve file