1.       PCORE      ELECTRIC  Tre Power To SERVE       PRC Bushings     Installation  amp  Handling    1  Scope    This instruction contains general procedures to be followed during  receiving  installation  storage and maintenance of all PCORE PRC  bushings  This instruction does not cover all contingencies that  may arise during installation  operation  or maintenance of such  equipment  If you require additional information regarding a  particular installation and the operation or maintenance of your  bushing contact PCORE or refer to the full online instruction manual  found at www PCOREelectric com  PCORE does not assume any  liability or responsibility for any damage or failure that would result  from improper transportation  application  installation  storage  or  maintenance     2  Safety    These tasks may cause safety hazards if they are not performed  properly  Those who are responsible for or involved in the  installation  maintenance  storage and operation of the bushings  must read this instruction and understand the details before they  perform the tasks  Required procedures and instructions must be  followed when installing bushings on apparatus or building   hereafter  any equipment or buildings on which bushings are to be  installed will be called apparatus      All applicable safety procedures such as OSHA requirements   regional and local safety requirements  safe working practices and  good judgment must also be used by personnel when installing   operating 
2.  lightly with silicone grease and tighten the  cap     6 4 Mounting Bushings   If the bushings are stored horizontally  it is important to remove all  entrapped air from the core  Place the bushing in the vertical  position and shake the oil end to force any air bubbles out of the  core area before Installation     6 4 1 Mounting Angle   PCORE bushings with oil level sight glasses are designed for safe  operation in vertical position or at angles up to 70 degrees from  vertical  Only bushings equipped with the integrated horizontal  mount reservoir or furnished with a supplementary oil reservoir  should be mounted in the horizontal position  refer to the  supplemental horizontal mounting instructions for details      6 4 2 Vertical Mounting   Lift the bushings in the same way as removing bushings from the  crates  If a flange adapter is required  install it before moving the  bushing to the mounting hole  Put the gaskets and or o rings on the  apparatus mounting surface per the apparatus instruction  Move the  bushing to the mounting hole of apparatus  Tighten the bolts to the  torque specified from the apparatus manufacturer     6 4 3 Draw Lead Connection   Bushings designed for draw lead applications have the draw lead  terminal  nut and pin in place  Before installation  you must remove  the top terminal  the draw lead nut  the retaining pin and the draw  lead terminal  Braze the apparatus cable to the draw lead terminal   Pass a wire or pull cord through the bushing cente
3.  steps for the gasket to set  Care  in tightening avoids possible damage or distortion of the mounting  flange  Normally  the torque values as listed will provide adequate  compression for sealing     Use the torque recommendations and mounting specification  of the apparatus manufacturer  Reduce torque if gasketed per  manufacturing recommendations for material being used  Adjust  torque for other metals for bolts in flange  Values below are for SAE  Grade 1 or 2     BUSHING FLANGE    Bolt Diameter Torque   inch   ft lb     PH 05 S  DRAW LEADS    Current Thread Size   ampere   inch   ft lb     REMOVABLE TOP TERMINALS    Torque           ft Ib        6 4 5 Bottom Terminal   If a bottom terminal is to be installed  pass the cable through the  hole in the shield and mount the bottom terminal  Mount the  terminal  Then push the shield to the bushing and mount the shield  on the bushing     6 4 6 Top Terminals  After power factor and capacitance tests are completed for the  apparatus  connect the top terminal for energization     7  Energization    During initial energization  you should monitor oil level changes  If  oil level changes excessively  contact the factory in LeRoy     8  Maintenance    Little maintenance is required other than periodically checking the  oil level as indicated in the sight glass  Unless a bushing is  damaged  the oil level should remain within the sight glass  fluctuating slightly with thermal and ambient conditions     Although we discourage the brea
4. HE RESERVOIR SHOULD BE  THE SAME TEMPERATURE AS THE OIL IN THE BUSHING   Use the dip stick to measure the oil level  The top mark is for  55  C  the second is 40  C  the middle for 25  C  the fourth for  10  C  and the bottom for  5  C oil temperature  If in doubt  use  slightly less oil  Interpolation between marks is not critical  If in  doubt  use slightly less oil    J  Tighten the oil fill plug in the bushing cover and install the oil fill  plug in the oil reservoir top  Make sure the O rings are properly  installed and seated on the plugs     Rev  Date 11 4 15    For more detailed information on all aspects of PCORE bushings  refer to the online instruction manual found at  www hubbellpowersystems com     
5. and maintaining such equipment     Specific hazards are defined and identified in more detail in the  online instruction manual for PCORE bushings found online at  www PCOREelectric com     3  Cable Connections    3 1 Bottom Connections   PCORE PRC bushings have one of the following bottom terminals   Flat spade or threaded stud  The bushings with a flat spade can be  directly connected to the apparatus  The bushings with a threaded  stud MAY need adapters to connect to the apparatus     3 2 Draw Lead Connections   Some bushings are designed with a hollow conductor through which  a flexible cable or a rod can be pulled  The cable is a part of the  apparatus on which the bushing is mounted and is not supplied with  the bushing  Most draw lead terminals have a flat spade for  brazing  crimp type  or tubular brazing terminals are available     3 3 Transformer and Oil Circuit Breaker Interchangeability  PCORE PRC bushings can provide maximum interchangeability  between transformer and oil circuit breaker applications     4  Receiving and Inspection    You should perform a visual inspection on the crate and the bushing  before unloading  When unloading crates  you must take extreme  care not to damage the crates or the bushings  Do not drop the  bushings  The bushings should be unpacked in a flat  dry area    To open the wire bound crate  the twisted wires should be  straightened with pliers  Remove any nailed covers carefully to  avoid damage     Some crates contain separate boxe
6. he  controlled conditions in the factory  Contact the factory if you  encounter any of the following     A  Measurement of power factor increases to 1 5 times the  original installation value    B  Measurement of capacitance increases by 10 percent over the  Original installation value     9  Re shipping or Returning Bushings    To ship the bushing to another site  you may re use the original  crate  Inspect the crate for damage and repair before using     Bushings with damaged porcelain or sight glasses pose a  some danger  Wrap broken porcelain or glasses with duct tape  and blankets  Burlap works well      It is recommended that bushings be returned to the factory for all  significant repairs  Inquiries concerning repairs should be addressed  to the factory at Le Roy  You MUST obtain a Return Authorization   RO  number before shipping bushings or bushing attachments to  PCORE  The handling of all requests will be expedited if the factory  is furnished the catalog number and the serial number which are on  the nameplate  The catalog number identifies the bushing rating   The first two digits of the serial number are the last two digits of the  manufacturing year     Do not attempt field repairs    A bushing experiencing a core problem may have  a high pressure and or hot oil inside  Do not  remove oil fill plug    Bushings are assembled using heavy clamping  pressures  A bushing with a shattered oil sight  glass must be wrapped with burlap and duct tape  before the bushing 
7. ight glass  More oil may have to be added to  the bushing    D  Loosen the oil filler plug in the top bushing cover to bleed off  the entrapped air  air bubble     E  Add oil to the bushing until oil comes out of the fill hole in the  top cover  Be sure the fill hole in the top cover is slightly higher  than the bottom of the bushing    F  Repeat steps B through E as necessary until the air bubble  that remains inside the sight glass is less than 1 4 inch in  diameter  DO NOT STORE THE BUSHING COMPLETELY  FILLED  Any oil expansion could cause the bushing to leak     Install the bushing in the apparatus and perform the following steps  immediately  It is important to keep the bushing in a horizontal  position during installation     G  Remove the oil reservoir plug from the flange and install the oil  reservoir  Be sure the O ring is properly installed on the  reservoir    H  Remove the oil filler plug from the oil reservoir top  IT IS  IMPORTANT TO DETERMINE THE TEMPERATURE OF THE  OIL IN THE BUSHING BEFORE ADJUSTING THE LEVEL   THIS MAY BE DIFFERENT THAN THE AMBIENT AIR  The  best method is to use a dial thermometer or a thermocouple  inserted as far into the reservoir as possible  Try to get into the  flange thorough the neck of the reservoir  DO NOT USE A  GLASS THERMOMETER  Wait a few minutes for the reading  to stabilize       Add oil to the reservoir until the oil level in the reservoir is at  the proper level  FOR PROPER OIL LEVEL INDICATION   THE OIL THAT YOU ADD TO T
8. is removed from installation     Supplemental Instructions    1  Horizontal Bushing with Integrated Tank    PCORE Insulator Company horizontal bushings with the integrated  tank design can be used in either the vertical or horizontal position   There is no need to adjust the oil level during installation for this  type of bushing  To install this type of bushing in the horizontal  position it is important to remember the following     WARNING    A  Place bushing into the vertical position prior to installation    B  Carefully shake the oil end of the bushing to help move any air  bubbles formed during shipment to the air space at the top of  the bushing    C  Keep the air end of the bushing elevated  above the oil end at all times during the  installation process  until the bushing is put  into the horizontal position  sight glass up    This will help to prevent air bubbles from  forming along the bushing core    D  Care should be taken to avoid tipping or  rotating the integrated tank sight glass forward or backward  during installation     as this may cause a properly filled bushing   s  oil level to appear high or low in the sight glass     B 303339 A       Page 3 of 3    2  Horizontal Bushing with External Reservoir    PCORE Insulator Company horizontal bushings with external  reservoirs are shipped with the oil reservoir mounting hole plugged  and with oil at the standard level for vertical mounting  The oil  volume in all bushings fluctuates significantly with temperatu
9. king of the seal of the oil fill plug in  the bushing reservoir  if the oil level over an observed period of time  remains low and ambient conditions are normal  oil may be added   However  contact the factory in LeRoy first    Removal of oil filler plug should be done only in a dry atmosphere   Provide oil that meets the IEEE C57  106 standard for new  transformer oil  If there is mechanical damage to the bushing which  results in loss of oil  or the oil level in the bushing is still indicating  low after the addition of oil the bushing should be taken out of  service     Rev  Date 11 4 15    For more detailed information on all aspects of PCORE bushings  refer to the online instruction manual found at  www hubbellpowersystems com     Never operate or test a bushing with a low  internal oil level  Under these conditions   operation may result in severe personal  injury  death or property damage    WARNING    Bushings exposed to salt spray  cements dust  and other abnormal  contamination deposits are subject to a special hazard and must be  cleaned regularly to prevent flashover and corrosion of metal parts   The sight glass should also be cleaned regularly  We endorse and  recommend the measurement of power factor and capacitance at  the time of installation and repeating the measurement regularly   These values should be used as a base to compare the TRENDS of  future measurements  Field measurements of power factor and  capacitance may differ from measurements made under t
10. n manual found at  www hubbellpowersystems com     The methods of measuring power factor and capacitance are in the  user manual of your power factor measuring device or consult IEEE  Standard C57 152 IEEE Guide for Diagnostic Field Testing of Fluid   Filled Power Transformers  Regulators  and Reactors  Only C    power factor and capacitance have meanings for the 25 kV through  69 kV class bushings  PCORE recommends against measuring C2  power factor and capacitance of this voltage class bushings for any  purpose     Do not operate the bushing without the test  tap or voltage tap cover in place     CAUTION    These measurements should agree with the nameplate values  within equipment tolerances and should be kept as reference  readings  When power factor and capacitance readings are in  disagreement with nameplate data beyond reasonable tolerances   you should contact the factory at Le Roy     Never test the bushing while in the shipping  crate     When possible  place the bushing in a grounded  test stand  It is important to isolate the flange  from the grounded stand using a good insulating  material  Wood can contain significant moisture  and should never be used     The readings may be taken with the bushing  installed in the equipment provided the top  terminal connections are not made or the  terminal is isolated from the main bus via a  Lapp Doble Test terminal     CAUTION    After the testing has been completed  reassemble the tap cover  after coating the    O ring   
11. nstallation    6 1 Removing Bushings from Crates   PCORE PRC bushings which are usually in the 25 kV through 69  kV class can be removed from the crate using a nylon choker  around the upper porcelain  Position the bushing vertically  and  check the oil level of the bushing before installation                                                                                      6 2 Cleaning   Bushings should be kept vertically in a secure stand and you must  remove all dust  grease  oil or particles of packaging from the  bushing with clean dry cloth  Especially the lower end and flange  should be wiped clean of dust or dirt to prevent contamination of  transformer oil  Before mounting bushings to the apparatus cover   inspect and clean the mounting surfaces of both the bushing and  apparatus     Check the inside wall of draw lead tube especially when the bushing  has been stored outdoors a long time  If it is dirty  remove all the  dirt  dust and other foreign materials from the wall     6 3 Electrical Tests   PCORE recommends that power factor and capacitance  measurements be performed on all bushings before installation   The measured values should be compared with those on the  nameplate  The nameplate values are of special importance in  asking PCORE questions about bushings  The bushing must be  kept vertically in a secure stand for the electrical tests     Rev  Date 11 4 15    For more detailed information on all aspects of PCORE bushings  refer to the online instructio
12. r conductor from  the top and attach it to the hole in the top end of the draw lead  terminal on the flexible cable  While lowering the bushing into the  opening in the cover  simultaneously pull the cable up through the  center conductor  Secure the draw lead terminal into the top of the  bushing by replacing the retaining pin through the conductor and  then replace the draw lead nut  A light coating of silicone should be  applied to the O ring of the top terminal before replacing  Refer to  the section Bolting and Terminal Torque Settings for terminal  tightness     B 303339 A    Page 2 of 3    Do not operate a bushing with the bushing oil level  not visible in the sight glass under normal ambient  conditions  This could result in serious damage to  the bushing and or apparatus on which the  bushing is being mounted     It is normal for the oil level to drop below the sight  glass in some bushings in extremely cold   WARNING conditions  Contact PCORE Electric Company if  you have any questions     6 4 4 Torque Specifications for Bolts   Before mounting bushings to the apparatus cover  inspect and clean  the mounting surfaces of both the bushing and apparatus  Install the  gasket or O ring supplied by the apparatus manufacturer  Secure  the bushing on the apparatus cover by tightening all the bolts  uniformly in several steps  Do not attempt to pull the bolts down to  the final setting on the first tightening  It is good practice to allow  time between the several tightening
13. re   PCORE PRC bushings are designed to operate with air ambient  from  50  C to  40  C  An oil reservoir tank mounted on the flange of  a horizontally mounted bushing accommodates the oil volume  change     lt is important to fill and install the bushing properly to guarantee  long life expectancy  Two things are extremely important  First  all  air must be out of the bushing  and secondly  the oil level must be  adjusted properly according to the bushing oil temperature  Failure  to follow these instructions can cause bushing failure     Before installing the bushing into the equipment  or wall   perform  the following steps while the bushing is held horizontally     A  Remove the oil filler plug in the stainless steel cover at the top  of the bushing    B  Add oil through the fill hole in the top cover until the bushing is  completely full  Tip the bushing slightly so the air bubble is at  the fill hole in the top cover  Fill with oil until some oil comes  out of the fill hole in the top cover  Use the extra oil supplied  with the bushing  or any NON PCB type   or type II transformer  oil  The oil must meet the minimum requirements for new  transformer oil per IEEE C57 106  latest revision     C  Replace the fill plug in the top cover and tighten slightly by  hand  Rock the bushing back and forth to release all entrapped  air inside the bushing into the sight glass area  Watch the sight  glass for air bubbles  Continue rocking until no the air is being  released into the s
14. s containing special terminal  adapters  oil reservoir tanks for horizontally mounted bushings  or  other special parts  These special parts should also be checked for  damage from shipment     Examine the top porcelain and bottom resin for cracks or chips   Check all seals for oil leakage  Although surface oil is removed  from the bushing after electrical testing  occasionally a gasket seal    B 303339 A    Page 1 of 3    may weep an oil film when received  To check for gasket seal  leakage  wipe the suspected joints clean and observe for a period of  48 hours  If oil leakage is detected  contact the factory at Le Roy   Any special parts should be checked for damage     If shipping damage is evident  you must file a claim with the  transportation carrier and notify PCORE of the claim immediately     5  Storage    The PRC bushing can be stored either horizontally or vertically in a  proper stand  which cannot be tipped over  The preferred location is  indoors  however bushings may be stored outdoors with bottom end  covered with an opaque plastic bag  The crates are not made for  extended outdoor storage  inspect the crates periodically for  weather damage     For long term outside storage  moisture or water may gather inside  the protective plastic bag that covers the upper and lower end   Suitable protection  such as water repellent grease should be  provided for top and bottom terminals  and mounting hardware to  protect the contact area from corrosion    6  Handling and I
    