ENDA ET4410 PID TEMPERATURE CONTROLLER
Contents
1. Input type J Fe CuNi Thermocouple K NiCr Ni Thermocouple T Cu CuNi Thermocouple R Pt13Rh Pt Thermocoup S Pt10Rh Pt Thermocouple Temperature range Accuracy C oF EN 60584 0 600 C 32 1112 F 0 5 of full scale 1 digit EN 60584 0 1300 C 32 2372 F 0 5 of full scale 1 digit EN 60584 0 400 C 32 752 F 0 5 of full scale 1 digit EN 60584 0 1700 C 32 3092 F 0 5 of full scale 1 digit EN 60584 0 1700 C 32 3092 F 0 5 of full scale 1 digit ENVIRONMENTAL CONDITIONS Ambient storage temperature 0 50 C 25 70 C with no icing Max Relative humidity 80 up to 31 C decreasing linearly 50 at 40 C Protection class According to EN 60529 Front panel IP65 Rear panel IP20 Height Max 2000m A Do not use the device in locations subject to corrosive and flammable gases ELECTRICAL CHARACTERISTICS Supply 230V AC 10 20 50 60Hz or 24V AC 10 50 60Hz Power consumption Max 5VA Wiring Power terminal 2 5mm screw terminal connections Signal terminal 1 5mm screw terminal Line resistance For thermocouple max 1000hm Data retention EEPROM minimum 10 years EMC EN 61326 1 1997 A1 1998 A2 2001 Performance criterion B for standard EN 61000 4 3 Safety requirements EN 61010 1 2001 Pollution degree 2 overvoltage category Il OUTPUTS C
2. Ac ot Time of full opening of the motorized valve Adjustable between 2 300sn A Co5E parameter this parameter is set to the selection of motored value is activated Ac C E Motorized valve control period Adjustable between 1 50 Ac ot time period of the control output as a percentage of the control value This parameter is how often to run the value setting often prevents unnecessary Cob parameter this parameter is set to the selection of motored value is activated Rol o Analog output lower limit Adjustable between 0 AloH CobE parameter this parameter is set to the selection of analog output is activated AloH Analog output upper limit Adjsutable between Alot 0 100 A Cob parameter this parameter is set to the selection of analog output is activated oF F 5 Offset value Offset value is added to the measuring value This feature which is the point of measurement due to its distance measurement probe is used to dink nonE Digital input is closed C2b5A Digital input is active 2 set value is used AAnu If the digital input is activated manual mode can be exceed d5Po If the di indicator mode can be exceed FFEL Function key setting parameter non Function key is closed C25 A The function key is used with the 2 set value AAlnu Manual mode can be exceed by using the function key d5Po Temperature indicator mode can be exceed by using function key D Os Coc
3. A itP bfnd sv ON sv ON i OFF SV ON OEE AlstsH OFF Aibt Lo t 7 t 1 i H A j H 1 i i i i i i f i i f i i i OFF A ibt Lo OFF i I i i ASV min 0 ASV max 300 Beginning Band alarm is possible Beginning Band alarm is possible SV Set point of CONT output ASV Set point of AL1 output ASV min 0 ASV max 300 Band Alarm With Inhibition A ltP bfn MODIFICATION OF CONTROL AND ALARM SET POINTS aan 3 seconds later C A SET ERROR MESSAGES PFR Temperature sensor 4 G D is broken Temperature value is higher than the scale r A cr L 5E t L LSE _3 seconds later _ A i a R a 2 T I Eara A Temperature value is g LESE 3secondslater A One of the L C5 parameter is set to d inL or FF EL this parameter is seen 399 400 A LSE A I5E 3 seconds ERA S i a e SEEEN um Co 5Eparameter this parameter is set according to the SSR or analogue outputs 3 4 ET4410 E 01 MOTORIZED VALVE CONNECTION AND ADJUSTMENT CIA2 AC 250V 2A RESISTIVE LOAD VALVE OPEN 2 A1 AC 250V 2A RESISTIVE LOAD VALVE CLOSE Motorized valve connection as shown in the figure above Output values of the electrical values of the value is not suitable ignition device additional contactor must be connected together Then this device p LobE parameter c on is set to the selection of motor value On full time motorized value co
4. C Pb parameter is different from 0 this parameter appears CP5E At C A1 Set value C A1 percent of power Adjustable between 0 100 CEPS At sensor failure C A1 percent of power Adjustable between 0 100 55E Soft starter timer set value This parameter indicates the time to reach set point value when the device is first energised Adjustable between 0 and 250 o A ibe A v h AA A 15 H Alarm1 set value upper limit Adjustable between A 5 L parameter value and upper scale value A tHY Hysteresis of the Alarm1 output Adjustable between 1 50 C A IEP Type of Alarm1 6 kinds of functions can be selected indE Independent alarm dE Deviation alarm bAnd Band alarm Band 6 An Band with inhibition info At output independent cooling control rElo A1 output relative cooling control A 15t Alarm1 output situation If Alarm1 output H A1 outputis above the Alarm1 set value on 4 o A1 outputis above the Alarm1 set value off A A lt Pparameter info or rELois selected this parameteris notseen A Er Alarm1 probe failure situation on A1 output probe failure on oF F a1 output probe failure off A Pb A1 output value of proportional band Adjustable between 0 100 A iPb 0 On Off control is selected A IEP parameter info or FEL a is selected this parameter is activated A I A1 output integral value Adjustable betw
5. Parameter of Sono menu security level non Invisible PYES Modification can be done P no Only visible Peele Keo mA wn Pe Os R 5c Parameter of AL to menu security level non Invisible PYES Modification can be done P no Only visible A2Sc Parameter of Ai co menu security level non Invisible PYES Modification can be done P no Only visible oD EEs Mi wn D Os 2050 kee mia wn gt Os Co 5c Parameter of L onF menu level Invisible PYES Modification can be done P no Only visible 5 5c Parameter of 5t un menu security level non Invisible PYES Modification can be done ta er La ico mu uA Ox A Co 5c Parameter of Conf menu security level no Parameter settings aren t changed ital input setting parameter al input is activated temperature fc 5 Retransmission output control parameter of F Retransmission output is closed O 2G 0 20mA Retransmission output is open 4 20 4 20mA Retransmission output is open A c o 5E parameter A2 or Ac on is selected this parameter is activated A ltd 0 00 effect of derivative disable A IEP parameter info or rELa is selected this parameter is activated minutes If 0 is selected soft start feature will be enable and the device reaches set point value quickly Setting Pb 0 sotf start feature will be disable elimin
6. A2 output Relay 250V AC 2A for resistive load NO NC Selectable as control and Alarm2 A1 output Relay 250V AC 2A for resistive load NO Selectable as Alarm1 and cooling control ANL SSR output Selectable as 0 20mA 4 20mA analog output and logic control output Life expectancy for relay Without load switching 30 000 000 mechanical operation 250V AC on the 2A resistive load 300 000 electrical switching CONTROL Control type Single set point and alarm control Contro algorithm On Off P selectable A D converter 12 bit Sampling time 500ms Proportional band Adjustable between 0 and 100 If Po 0 On Off control is selected Integral time Adjustable between 1 and 250 seconds Hysteresis Adjustable between 1 and 50 C F Output power The ratio of power at a set point can be adjusted between 0 and 100 HOUSING Housing type Suitable for flush panel mounting according to DIN 43 700 Dimensions W48xH48xD87mm Weight Approx 250g after packing Enclosure material Self extinguishing plastics A While cleaning the device solvents thinner benzine acid etc or corrosive materials must not be used 114 ET4410 E 01 SET gt SET Entering from the programming mode to the run mode SET D gt m aS gt If no key is pressed within 20 seconds during programming mode the data is stored automatically and the run mo
7. ope AG b 4 Line u gt 230V AC veya 24V AC Order Code ET4410 O00000 00 21 6 26 4V AC 4 Neutral e Supply 1 2 50 60Hz 5VA Fuse should Cable size 1 5mm 4 Supply Voltage SENSOR INPUT me connectee 230VAC 230V AC ron thermocouple r ee tO 24VAC 24V AC se suitable compensation cables on t use jointed cables Pay attention to the polarities of the re lt g e 2 Modbus Option thermocouple cables as shown in the figure right H RS RS 485 Modbus Communication are connected to the None Don t support RS 485 ModBus Communication SiSEL M HEND SL K ELEKTRONIK SAN VE TIC A Yukari Dudullu Barbaros Cd No 18 34775 UMRANIYE ISTANBUL TURKIYE ET4410 E 01 Tel 90 216 499 46 64 Pbx Fax 90 216 365 74 01 url www enda com tr 4 4
8. returned The same procedure is valid for the decrement key 2 4 ET4410 E 01 TERMS ET 4410 C A2 AN SSR 7 A1 EMPERATURE CONTROLLER 1 Measurement value and set value indicators Running mode Parameter name and value Programming mode 2 Value increment key Running and programming mode Parameter selection key Programming mode 3 Value decrement key Running and programming mode If only this key is pressed in normal operation software version number is seen Parameter selection key Programming mode 4 Selectable function key Running mode Menu selection key Programming mode 5 Control ve Alarm set selection key Running mode Parameter set key Programming mode 1 PV and SV display PV 7 segment 4 digits red SV 7 segment 4 digit yellow LED display Character heights PV display and SV display 7 2mm 2 3 4 5 Keypad Mikro switch 7 State indicator Control Alarm1 and SSR outputs for 3 red LEDs ALARM1 AND ALARM2 OUTPUT TYPES Independent Alarm A It P indE ON OFF AistsH A IHY SHED PHI i AHS i i l ASV PEE TENE SON p PER SV ASV SV ASV gt ASV min beginning of scale 300 SV ASV 4300 300 300 ASV max end of scale ASV min 300 ASV max 300 SV Set point of CONT output ASV Set point of AL1 output SV Set point of CONT output ASV Set point of alarm output Deviation Alarm Band alarm A lk P d EF
9. Read this document carefully before using this device The guarantee will be expired by damaging of the device if you don t attend to the directions in the user manual Also we don t accept any compensations for personal injury material damage or capital disadvantages ENDA ET4410 PID TEMPERATURE CONTROLLER Thank you for choosing ENDA ET4410 temperature controller 48 x 48mm sized Double set point can be selected Selectable thermocouple types Automatic calculation of PID parameters SELF TUNE The system before starting the first time the system PID parameters should be entered if known otherwise Self Tune property mustnot be operated Digital inputs can be assigned to 3 different feature Function key can be assigned to 3 different feature Soft Start feature Selectable analog SSR relay or motorized valve control output Selectable 0 20mA and 4 20mA retransmission output Selectable 0 20mA and 4 20mA analog control output Alarm2 or temperature control output can be programmed as C A2 relay output Alarm1 output or PID cooling output can be programmed ET 4410 C A2 AN SSR C A SET F ENDA TEMPERATURE CONTROLLER Selectable heating and cooling control For input offset feature In the case of probe failure periodical running or relay state can be selected Communication with RS 485 ModBus protocol CE marked according to European Norms TECHNICAL SPECIFICATIONS
10. ate errors that might occur Adjustable between 99 99 C Normal value 0 amp amp A ICE A1 output period time Adjustable between 1 250sn A IEP parameter info or r EL o is selected this parameter is activated AICE dAdr Device address For RS485 connection Adjustable between 1 247 This parameter is active devices with RS485 CE YP Control type selection ae a communications option CEYP HERE means heating control C5tA Cool means cooling control Modification Of Parameter Diagram SET Opec SS gt SET When holding C key the value of parameter flashes and using XO CIASET CDC keys the requested value can be adjusted A lf __ key is pressed and held 0 6 seconds the value of the selected b Aud ModBus baud rate For Rs485 connection Selectable off 2400 4800 9600 19200 ve 38400 This parameter is active devices with RS485 communications option a 8 fki A IPS At A Set value A1 output percent of power Adjustable between 0 100 A IEP parameter inL o or r EL o is selected this parameter is activated x gt A IEP At A1 Set value A1 output percent of power Adjustable between 0 100 It P parameter in o or r E L o is selected this parameter is activated C370 parameter changes rapidly If waited enough the value increases 100 at each step After 1 second following the release of the key initial condition is
11. de is entered i i i F i gt C ASET F if rey is pressed while holding key the programming mode is enabled Alternatively the same function occurs first pressing C key and then pressing si keys together CIA SET F C A SET F gt _ 5 CIA SET F gt gt inPE Type pf input selection oO gt a F Chloz ist imi Abl imi t Co Self tune control SL od Security menu access Adjustable between 0 and A 15H J P l0rss P IJr Rt i i g Parameter value can be set between 0 parameter value ir S type Lf ype YE 5 Self tune is started It should be 441 CSH i parameter value thermocouple selection CSH CIA1 output Control set value upper limit Chlo parameter value can be set between indicated value and the upper scale E Pb CIA1 output Proportional band value Adjustable between 0 100 E Pb 0 ise On Off control is selected CHYS Hysteresis of the C A1 output Adjustable between 1 50 C Pb 0 this parameter is seen E E CIA4 output integral value Adjustable between 0 0 100 0 minute E E 0 0 effect of integral disable AC Pb parameter is different from 0 this parameter appears C Ed CIA1 output derivative value Adjustable between 0 00 25 00 minute E Ed 0 0 effect of derivative disable C Pb parameter is different from 0 this parameter appears C CE CIA1 output period time Adjustable between 1 250sn
12. een 0 0 100 0 minute Alt 0 0 effect of integral disable AVA IEP parameter info or rELo is selected this parameter is activated A Itd A1 output derivative value Adjustable between 0 00 25 00 minute A25H Alarm2 set value upper limit Adjustable between A2 5 L parameter value and upper scale value ACHY Hysteresis of the Alarm2 output Adjustable between 1 50 C ACEP Type of Alarm2 4kinds of functions can be selected indE Independent alarm dE Deviation alarm bAnd Bandalarm bAn Band with inhibition ASE Alarm2 output situation H 1 A2 output is above the set value on az Lo A2 output is above the set value off ACE r Alarm2 probe failure situation on A2 output probe failure on of F A2 output probe failure off CO This parameter varies when changing some parameters Un E The temperature unit OC C OF F This parameter varies when changing some parameters FL tr Coefficient of digital filter Adjustable between 1 and 35 If this parameter is 1 digital filter runs most quick If the parameter is 35 the filter run most slow The value of parameter should be increased in interference Co 5E Control output selection C Ad cia2 Relay output selection 55f SSR output selection 0 20 0 20mA analog output selection 4 20 4 20 mA analog output selection AC on Motorized valve output selection
13. must be according to the relevant locally applicable regulations 45 Note 1 While panel mounting additional distance required for connection cables should be considered 2 Panel thickness should be maximum 9mm 3 If there is no 100mm free space at back side of the device it would be difficult to remove it from the panel CONNECTION DIAGRAM Logic output of the instrument is not electrically gt N ENDA wwoustriat ELECTRONICS ENDA wnoustriat ELECTRONICS insulated from the internal circuits Therefore ET4410 230VAC ET4410 24VAC when using a grounding thermocouple do not PID TEMPERATURE CONTROLLER PID TEMPERATURE CONTROLLER connect the logic output terminals to the ground T 230V AC 10 T 24V AC 10 C gO 50 60Hz 5VA 2 so oure SVA ol E Note 1 Mains supply cords shall meet the requirements SSR mA cia2 SSR mA E cia2 of IEC 60227 or IEC 60245 OUT Ac 250v 2A OUT e AC 250V 2A 2 In accordance with the safety regulations the DiN Save DPEN DN QS VAVE OPEN power supply switch shall bring the identification of At T Al the relevant instrument and it should be easily AC 250V 2A Tox RESISTIVE LOAD To RCA eTVE LOAD accessible by the operator VALVE CLOSE VALVE CLOSE SN 20000000X SN ee J Holding screw Equipment is protected throughout NOTE DATENA by DOUBLE INSULATION SUPPLY VOLTAGE Fuse Switch F 100 mA 250V AC
14. nnected to a device the Ac ot parameter is entered in seconds How often the introduction of the value is required this value is also entered in the AcLE parameter as a percentage of full time opening Minimum time between two contact output Ac CE value can be up to the period of time Power on Open t exact opening time Close DIMENSIONS 87mm 1 For removing the device from J the panel While pressing both side of the device in direction 1 push it in direction 2 ET 4410 CIA2 ANISSR 58mm 48mm ENDA ET4410 is intended for installation in control panels Make sure that the device 5 is used only for intended purpose The 2 shielding must be grounded on the instrument side 1 During an installation all of the cables that are A e Gonnection connected to the device must be free of energy The B 7 device mustbe protected against inadmissible humidity Panel cut out vibrations severe soiling and make sure that the Flush mounting clamp Panel a 2 0 6 mm t a CIA SET ENDA TEMPERATURE CONTROLLER 45 operation temperature is not exceeded All input and output lines that are not connected tothe supply network must be laid out as shielded and twisted cables These cables should not be close mm 80mm 0 6 to the power cables or components The installation and electricalconnectionsmust be carried on by a 51mm qualifiedstaff and