Home
        10 - Airside Design.indd - Oregon State Library: State Employee
         Contents
1.    Code Language continued from page 1       3  At least 75 percent of the energy for reheating  or for providing warm air in mixing systems  comes from a site   recovered or site   solar  energy source    4  Zones where specified humidity levels are  required to satisfy process needs  such as com   puter rooms  museums and areas of hospitals    5  Zones with a peak supply air quantity of 300  cfm  142 L s  or less     1318 2 6 Zone isolation controls  A system serving  multiple occupancies or floors in the same building  shall be independently zoned and equipped with isola   tion devices capable of automatically shutting off the  supply of conditioned air and outside air to and from  each isolated area  Each isolated area shall be con   trolled independently and satisfy temperature setback   Section 1317 4 2  and optimum start control require   ments  The central fan system air volume shall be re   duced through fan speed reduction     Exceptions  A cooling system less than 240 000 Btu   hr  70 kW  or a heating system with less than 300 000  Btu hr  88 kW  total capacity     1318 2 7 Separate air distribution systems  Zones  with special process temperature requirements and or  humidity requirements shall be served by separate air  distribution systems from those serving zones requir   ing only comfort conditions  or shall include supple   mentary control provisions so that the primary sys   tems may be specifically controlled for comfort  purposes only     Exceptions  Zones
2.  requiring only comfort heating or  comfort cooling that are served by a system primarily  used for process temperature and humidity control  provided that     1  The total supply air to those comfort zones is  no more than 25 percent of the total system  supply air  or   2  The total conditioned floor area of the zones is  less than 1 000 square feet  90 m       Continued from page 1    flow setpoint on VAV boxes  The code establishes an upper limit   and the intent is to reduce airflow as much as possible during low  cooling load periods before using reheat     There are three options for calculating this limit  and the designer  can apply the method that results in the highest airflow  There is  also an exception for zones with peak airflow no greater than 300  cfm  The first calculation option  30 percent of peak air flow  and  the third method  0 4 cfm per square foot  are fairly simple  The  second calculation method is more complicated than the other  two because it is based on overall system outdoor air ventilation  rate calculations     The second method typically applies to zones with high occupant  density  and it allows system designers to optimally solve Equa   tion 6 1 in ASHRAE Standard 62 1 2004  That equation shows  that the amount of outdoor air required for a system is a function  of how much air is supplied to the    critical zone    in the system   The higher the supply air rate to the critical zone  the less outdoor  air is required at the air handler  T
3. FE  NORTHWEST ENERGY EFFICIENCY ALLIANCE     3 www nwalliance org    Photo on page 1 c o Warren Gretz  DOE NREL  12 05 ODOE CF 125 Fact Sheet 10    Non residential code HVAC fact sheets include     Ventilation Controls System   Economizers    Exhaust Air Heat Recovery     Airside Design Requirements   e Hydronic Design  Controls     Airside Controls     Large Volume Fan Systems   Air Transport Energy      Simple vs  Complex HVAC Systems    Continued from page 3    clean rooms or other special manufacturing spaces  computer  rooms  or other special electronic equipment     The energy required to maintain conditions in these    process     spaces is typically greater than for spaces where human comfort is  the only criterion     The intent of section 1318 2 7 is that these spaces with process  requirements be served by separate systems so that energy is not  wasted by    overconditioning    the other portions of the building     In some cases  it may not be practical to provide separate systems   and the code allows some exceptions  These exceptions permit   a small amount of    comfort    conditioned space to be served by  systems that primarily serve the process areas  The comfort areas  must either receive no more than 25 percent of the air flow or  must be less than 1 000 sq  ft     For More Information    See also the fact sheets covering Airside Control Requirements   Air Transport Energy  Economizers  Ventilation Controls for High  Occupancy Areas  and Exhaust Air Heat R
4. Oregon Non Residential z    Building Energy Code        ne a    ve    Airside System Design Requirements    These sections fall under 1318 2 Complex Control Systems  They  are grouped here as the topic Airside Design because they affect  the fundamental system design  including system type selection  and system layout     Simultaneous Heating and Cooling    The intent of section 1318 2 1 is to minimize energy waste by limit   ing the amount of simultaneous heating and cooling that occurs in  HVAC systems  Simultaneous heating or cooling occurs when sup   ply air that has been previously cooled is reheated  supply air that  has been previously heated is recooled  or supply air that has been  cooled is mixed with supply air that has been heated  The most  important consequence of this requirement is that certain HVAC  system types are prohibited except under special circumstances   The following system types are generally not allowed     e Constant volume reheat system  A single air handler that pro   vides a constant flow of cool air to multiple zones  with a hot  water or electric resistance coil at each zone to reheat the air  and control space temperature     e Two deck multizone system  A single air handler that serves  multiple zones and delivers a mixture of heated and cooled air  to each zone in a separate duct  The ratio of heated and cooled  air is varied separately for each zone to control space tempera   tures     e Constant volume dual duct system  Similar in princ
5. ce with  separate air distribution  requirements must be  recorded on Form 4b   line 10     1  Variable air volume  VAV  systems which   during periods of occupancy  are designed to  reduce the air supply to each zone to a mini   mum before reheating  recooling or mixing  takes place  This minimum volume shall be  no greater than the larger of the following    1 1 Thirty percent of the peak supply volume    1 2 The minimum required to meet ventila   tion requirements  unless increasing the  volume to critical zones  zones with the  highest ratio of outside air to total supply  air  beyond the minimum ventilation re   quirements results in a decrease in overall  outside air required by the HVAC system   An increase beyond minimum ventilation  rates shall not be applied to more than 20  percent of the zones with reheat  on any    one system  or  V3    0 4 cfm ft   2 L s per m   of zone condi     tioned floor area    2  Zones where special pressurization relation   ships or cross   contamination requirements  are such that variable air volume systems are  impractical  such as some areas of hospitals  and laboratories  Systems which use this  exception and supply heated or cooled air to  multiple zones shall include controls which  automatically reset supply air temperatures  by representative building loads or by outside  air temperature unless it can be shown that  supply air temperature reset increases overall  building annual energy costs    Code Language continues on page 2 
6. ecovery     See the Advanced VAV System Design Guide for detailed recom   mendations on VAV box minimum airflow settings  Available at  http   www newbuildings org mechanical htm     See also ASHRAE Standard 62 1 2004 Ventilation for Acceptable  Indoor Air Quality and the Standard 62 1 2004 User   s Manual for  guidance in determining ventilation rates and in performing    criti   cal zone    calculations  Available at www ashrae org     Examples    An office building includes a 200 square foot retail   space adjacent to the lobby as well as a 2 000 square  foot cafeteria  May these spaces be served by the central  HVAC system     Yes  these zones can be served by the central system    The separate air distribution system requirements   1318 2 7  do not apply in this case because the primary system  serving the office spaces is being controlled only for comfort  purposes  However  the zone isolation requirements of Section  1318 2 6 require that the system be able to shut off air flow to  and from these different occupancies separately from the office  occupancies  In addition  if this is a multi story building  then  each floor must have isolation controls capability        Airside System Design Requirements    Oregon Non Residential Building Energy Code    
7. elocity of the buoyant warm  supply air will be too low to provide adequate mixing with room  air  Thermal stratification  warm air at the ceiling  cool air at the  floor  is more likely to occur as the supply air temperature gets  warmer  more buoyant  and the velocity of air leaving the diffuser  decreases     There are some strategies to combat stratification in heating  mode  Parallel fan powered VAV boxes have fans that turn on to  increase air flow in heating mode and draw the extra air from  the return air plenum  In addition to improving comfort in heat   ing mode  parallel fan powered boxes will reduce or eliminate  the need for reheat  Series fan powered VAV boxes are another     Continues on page 3    Continued from page 2    though less desirable option  which maintain constant discharge  air flow while allowing the primary  ventilation  airflow to de   crease to a minimum setpoint  A series fan powered box provides  good comfort performance but is generally less energy efficient  because it induces warm plenum air at all but peak cooling times   leading to increased cooling requirements as well as higher fan  energy  Another alternative is to use separate perimeter heating  systems such as radiant panels or baseboard heaters instead of  reheat coils in VAV boxes  In this strategy  the VAV box air flow  can be allowed to drop to a low minimum without concern of  stratification occuring  and the separate heating system prevents  overcooling     Zone Isolation Contr
8. ensity cases such as a  meeting room or classroom  If that is the case   then the ventilation rate can be used as the upper  limit  Finally  there is an exception in Section  1318 2 1 that allows the minimum flow to be set  even higher if doing so will reduce the overall  outdoor air ventilation rate for the central air  handler     Is a triple deck multizone system    which has hot deck  cold deck  and  neutral  no heating or cooling  deck  allowed  under the simultaneous heating and cooling  requirements of Section 1318 2 1     Yes  as long as the controls do not allow the   mixing of air from the cold and hot decks   In other words  the controls must ensure that the  air delivered to each zone is a mix of cold and  neutral or hot and neutral     Q The VAV system in a multi story   office building is being provided with  motorized dampers on the supply and return  ducts at each floor to provide zone isolation  control  The toilet rooms are exhausted by  central fan  Is it also necessary to provide  isolation dampers for the toilet exhaust at each  floor     Yes  Section 1318 2 6 requires that the air   flow to and from each isolation zone  in  this case each floor  is capable of being shut off   Therefore  motorized dampers in the exhaust  duct will be required at the connection to each  floor        Oregon Non Residential Building Energy Code    Airside System Design Requirements    Examples    A two story building is served by   a water loop heat pump system   consisting 
9. he designer would determine  which is more energy efficient  increasing outdoor air intake and  minimizing reheat at the critical zone  or increasing the supply   air rate and reheat energy required at the critical zone and mini   mizing the outdoor air rate  This    upsizing    of the minimum flow  may only be applied to a maximum of 20 percent of the zones with  reheat on each system  The designer should submit calculations  demonstrating that increasing the volume to critical zones reduces  overall outdoor air fraction  A detailed discussion of ventilation  rate calculations is beyond the scope of this fact sheet  and more  details are available in ASHRAE Standard 62 1 2004 and its User   s  Manual     When specifying VAV box settings  the designer should consider  the energy savings opportunities for minimum airflow set points  that are significantly lower than upper limits set by the energy  code  Reducing the minimum flow set point saves fan energy   as well as cooling and heating energy  Studies of real buildings  have shown that many zones operate at their minimum flow for  a majority of the time because cooling loads are often lower than  predicted by the designer  A good resource for recommendations  is the Advanced VAV System Design Guide     There are several potential design strategies that provide good  comfort and ventilation performance in heating mode while al   lowing low minimum settings in VAV boxes  The potential prob   lem with low air flow is that the v
10. iple to the  multizone system  except that the mixing occurs at the zone  level instead of within the air handler     Those system types are allowed in only three special cases    1  where constant airflow is necessary to maintain pressure rela   tionships between spaces in order to prevent cross contamination   2  where reheat is necessary to maintain special humidity condi   tions  and 3  where reheat is provided by recovered waste heat or  solar heat     This code section generally requires the use of one of the following  system types     e Variable air volume  VAV  with or without reheat  e VAV dual fan  dual duct    e Single zone systems  such as fan coils  packaged rooftop units   or water source heat pumps     For VAV systems  section 1318 2 1 regulates the minimum air     Continues on page 2    Code Language    1318 2 1 Simultaneous  heating and cooling   Zone thermostatic and  humidistatic controls  shall be capable of oper   ating in sequence the  supply of heating and  cooling energy to the  zone  Such controls  shall prevent reheating   recooling  and mixing  or simultaneous supply  of air that has been pre   viously mechanically  heated with air that has  been previously me   chanically cooled     Exceptions     OREGON    DEPARTMENT OF       ENERGY       Documentation     The simultaneous  heating and cool    ing requirements are  documented on Form  Ab  Line 4 as well as  Worksheet 4k     Zone isolation controls  are documented on  Form 4b  Line 11     Complian
11. ntrol  DDC  system  should be able to provide this level of control  However  the code  also requires that return air flow from the isolation zone be shut  off  and additional motorized dampers in the return air path will  still be necessary     The code also requires that central systems with zone isolation  controls use fan speed control to throttle back flow when one or  more zones is shut off  Most large central systems will already  meet this requirement because variable speed fan control is now  common for duct pressure control in new VAV systems     Separate Air Distribution Systems    Many buildings include spaces that require special environmental  conditions  Examples of such spaces include hospital operating  rooms  laboratories  special material storage such as rare books     Continues on page 4    Examples    A 1 000 square foot space is served   by a VAV box sized for 1 500 cfm  peak airflow  What is the upper limit on the  minimum air flow setting for the VAV box     Section 1318 2 1 sets the limit at the   largest of 30 percent of peak airflow  0 4  cfm per square foot  or the amount required for  ventilation  In this case  the 30 percent option  yields 450 cfm  30 percent of 1 500 cfm  and the  0 4 cfm per square foot option yields 400 cfm   Using the larger of these two results allows the  minimum VAV box flow to be set as high as 450  cfm  However  it is possible that the outdoor air  ventilation rate required for this space would  exceed 450 cfm for high d
12. of 25 heat pumps that total 100  tons of cooling capacity  A central air handler  delivers ventilation air to each heat pump   This air handler has a heating coil to temper  outdoor air during the winter  How do the zone  isolation controls apply     If the heating capacity of the central air   handler is 300 000 Btu hr or more  then  isolation capability is required for delivery of  outside air to each floor  and exhaust or return  air paths from each floor would require isolation  dampers     A data center consists of computer   rooms with special temperature and  humidity requirements as well as supporting  office and storage spaces  Can the support  areas be served by the same air handler that  serves the computer rooms     Section 1318 2 7 of the code allows the   support areas to share the computer room  air handler under two conditions  1  the total  floor area of the support rooms is less than 1 000  sq  ft  or 2  the air flow provided to the support  areas is less than 25 percent of the total system air  flow     Find OutMore          Copies of code   Oregon Building Officials Association  phone  503 873 1157 fax  503 373 9389    Technical Support   Oregon Department of Energy  625 Marion Street NE phone  503 378 4040    Salem  OR 97301 3737 toll free  800 221 8035  www oregon gov energy fax  503 373 7806    This fact sheet was developed with funding from  the Northwest Energy Efficiency Alliance  and the US Department of Energy  under contract DE FG51 02R021378     
13. ols    The intent of Section 1318 2 6 is to avoid conditioning the whole  building at times when only portions are occupied  These zone  isolation control requirements apply to systems that serve more  than one occupancy or multiple floors  At a minimum  such sys   tems must be able to serve each occupancy or each floor inde   pendently while shutting off air flow to and from the other areas  served by the system  In addition  each isolation area must have  independent time of day  setback  and optimal start controls     These requirements do not apply to small HVAC systems  Cooling  systems smaller than 20 tons  240 000 Btu hr  of cooling capac   ity are exempt  Heating systems with capacity of less than 300 000  Btu hr are also exempt     A straight forward option for complying with these requirements  is to include motorized dampers that shut off supply and return  ducts to each isolation zone  In a multi story building  this option  might consist of dampers located at the connections to the supply  and return air shafts to isolate each floor  The local fire official  may allow the use of fire smoke dampers to serve this purpose as  long as they are wired so that life safety controls take precedence  over off hour controls     A VAV system might comply if it has the capability to set the oper   ating schedule of each zone  or at least sets of zones  independent   ly  so that the VAV box damper may be shut on some zones while  others continue to operate  A direct digital co
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
  Manual del usuario  Tech air TANB0700  TravelMate 220/260 series    Instalación - Bosch Security Systems  Poulan 183159 Lawn Mower Accessory User Manual  取扱説明書 Rev.1.01  The Audit Plan – template user guide      Copyright © All rights reserved. 
   Failed to retrieve file