Hardware manual EPV4RBR
Contents
1. From step 9 press and release button UP or button DOWN to select the parameter Press and release button ENTER Press and release button UP or button DOWN to modify the value Press and release button ENTER to confirm the value Press and release button ESC to go back to the Main menu To modify the display s contrast operate as follows 20 21 22 23 24 From step 4 press and release button UP or button DOWN to select the Contrast submenu Press and release button ENTER Press and release button UP or button DOWN to modify the value Press and release button ENTER to confirm the value Press and release button ESC to go back to the Main menu To show the temperature and the relative humidity read by the sensor operate as follows 25 26 27 From step 4 press and release button UP or button DOWN to select the Analog IN submenu Press and release button ENTER the display will show the following frame Analog IN C 26 3 rH SA 52 6 Press and release button ESC to go back to the Main menu To modify the real date and time 28 29 30 31 32 33 From step 4 press and release button UP or button DOWN to select the item Real date and time Press and release button ENTER Press and release button UP or button DOWN to modify the value Press and release button ENTER or button RIGHT to confirm the value and modify the following field Repeat steps 26 and 27 Press and r
2. Evco S p A Power supply Vroom Hardware manual ver 1 00 Code 114VROOHWE00 according to the model 12 24 VAC min 11 4 VAC max 27 6 VAC 50 60 Hz 3 VA approximate isolated or 15 40 VDC 3 W approximate isolated 24 VAC min 20 4 VAC max 27 6 VAC 50 60 Hz 3 VA approximate non isolated or 20 40 VDC 2 W approximate non isolated supplied from a class 2 circuit The maximum length of the connecting cables of the power supply is 10 m 32 8 ft In the models with not isolated power supply this must galvanically be isolated from the one of the other devices connected in the network Protect the power supply with an UL listed or recognized fuse rated 80 mA T if the user interface is powered with 15 40 VDC 160 mA T if the user interface is powered with 12 19 VAC 125 mA T if the user interface is powered with 19 24 VAC Overvoltage category MI Real time clock data maintenance in absence of power supply 2 days will battery fully charged Battery charging time 2 min without interruptions the battery is charged by the power supply of the interface Alarm buzzer incorporated incorporated according to the model temperature sensor temperature and humidity sensor Temperature sensor Kind of sensor digital Sensors Working range from 10 to 70 C Accuracy 1 5 C Humidity sensor Kind of sensor digital Working range fr
3. programming port connector 2 V Every Control Group Vroom connector 1 Position micro switch 4 on position ON to plug in the termination of the CAN port micro switches 1 2 and 3 are reserved The following tables show the meaning of the connectors Connector 1 CAN port Terminal Meaning 1 ground 2 signal 3 signal A The maximum length of the connecting cables of the CAN port of the interface depends on the baud rate of the CAN communication as follows 1 000 m 3 280 ft with baud rate 20 000 baud 500 m 1 640 ft with baud rate 50 000 baud 250 m 820 ft with baud rate 125 000 baud 50 m 164 ft with baud rate 500 000 baud Connect the CAN port of the interface using a twisted pair According to the default settings the interface recognizes the baud rate automatically on condition that it is one of the those mentioned above hereinafter one suggests setting the same baud rate of the others devices in the network Connector 2 power supply not isolated 24 VAC or 20 40 VDC or isolated 12 24 VAC or 15 40 VDC according to the model Terminal Meaning 4 power supply 5 power supply page 8 of 22 Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 A The maximum length of the connecting cables of the power supply is 10 m 32 8 ft In the models with not isolated power supply this must galvanically be isolated from the one of the other devices connect
4. after this time without CAN communication with a device this will be excluded by the network Network CAN NW Node 32 127 Remote or of the devices in the network CAN nodes address example for 2 1 node 2 node s address Network Modbus Address 247 Lue page 13 of 22 Modbus address reserved Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 Modbus communication parity reserved Network none no parity Parity even Modbus odd odd even even Modbus communication baud rate reserved 1200 1 200 baud 2400 2 400 baud 4800 4 800 baud Network Baudrate 9600 9600 9 600 baud Modbus 19200 19 200 baud 28800 28 800 baud 38400 38 400 baud 57600 57 600 baud Network Modbus communication stop bit number Bit Stop 1 bit Modbus reserved page 14 of 22 Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 4 4 Configuring a device through the interface Operate as follows l ei 19 Switch off the power supply of the device and of the interface Connect the device to the interface through the CAN port look at chapter 3 ELECTRICAL CONNECTION Switch on the power supply of the device and of the interface Operate on the interface to set parameter NW Node look at chapter 4 CONFIGURATION Parameter NW Node belongs to the Network CAN s
5. display shows the following menu hereinafter called Main menu release buttons ESC and RIGHT Parameters Contrast Network Analog IN Info Real date and time It is also possible to show the Main menu operating as follows 5 Make sure the power supply is switched on 6 Keep pressed 2 s buttons LEFT and ENTER the display will show the following men hereinafter called Network Status menu gt gt Loc 99 OK back to the Main menu 1 1 gt gt 2 0 gt gt 3 0 gt gt 4 0 gt gt 5 0 gt gt 7 Press and release button ENTER the display will show the Main menu page 10 of 22 Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 To gain access a submenu operate as follows 8 9 A From step 4 press and release button UP or button DOWN to select the submenu Press and release button ENTER The access to the Network submenu is protected by password To gain access to the Network submenu operate as follows From step 4 press and release button UP or button DOWN to select the submenu Network Press and release button ENTER Press and release again button ENTER Press and release over and over again button DOWN to set 19 Press and release button ENTER To modify a configuration parameter belonging to the Parameters submenu to the Network CAN submenu or to the Network Modbus submenu operate as follows 15 16 17 18 19
6. 0 0 944 D 40 8 1 606 41 8 1 645 42 8 1 685 2 2 Installation The installation is possible by panel built in by wall in traditional box like 506 by BTicino by wall on the support CPVW00 by Evco to order separately look at chapter 6 ACCESSORIES The following drawing shows the installation by panel with 4 screws supplied by the builder page 6 of 22 Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 At the front of the interface one can apply the plates CPVP by Evco to order separately made in plastic material and available in two different colorations white and black look at chapter 6 ACCESSORIES 2 3 Additional information for installation working conditions working temperature humidity etc must be between the limits indicated in the technical data do not install the interface close to heating sources heaters hot air ducts etc devices provided with big magnetos big speakers etc locations subject to direct sunlight rain humidity dust mechanical vibrations or bumps according to the safety legislation the protection against electrical parts must be ensured by a correct installation of the interface the parts that ensure the protection must be installed so that you can not remove them if not by using a tool page 7 of 22 Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 3 ELECTRICAL CONNECTION 3 1 Electrical connection
7. Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 EVEO EveryControlGroup Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver 1 00 CODE 114VROOHWE00 page of 22 Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 Important Important Read these instructions carefully before installing and using the instrument and follow all additional information for installation and electrical connection keep these instructions close to the interface for future consultations The interface must be disposed according to the local legislation about the collection for electrical and electronic equipment page 2 of 22 Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 Index 1 MRO VOTON 0 RI RA E RE IRE IR RO RE RI RR ERI 4 1 1 IEC Az E AAA EA A 4 122 Avatlable tm Odes RARO RR RR NO 5 2 SIZE AND INSTALLATION Boe ee eee ee uf nilo ele eil SAI io illo 6 2 1 Sire ala a O I SITA RAISI 6 2 2 SAA AA AS AAA A A RI Re 6 23 Additional information for installationi cara anal i AA Aa 7 3 ELECTRICAL CONNECTION visscsecacansstasssscosnveisccdeusaisenvescsseusascaevenabaseos usssunvsaczeedsgraseneveaesanouenscsscosdeasceseusaseunyasastes asaaeveyeeasesonssuaceenesauessaeass 8 3 1 Electrical connection se aliante ela RR LORA Aaa 8 3 2 Additional information for electrical Connect On i au AA eats 9 4 CONFIGU
8. RATION octanos oe agi Ani Ai 10 4 1 PLA pelo EE ser cena paves ei aN LA ra ea aoe oe 10 4 2 Configuring the MiS AC Riise iano 10 4 3 Tist of Configuration parameters sus aa strilla Aa e a ORALE ini 12 44 Configuring A device through the interface es 15 5 SIGNALS tii A az lic edili nn edile E A sant io US 16 5 1 SMA OO III AAA E SII E TRO A tnt 16 6 ACCESSORIES NL O A NERA RIEN ORA ana val 17 6 1 Frontal platesGPVP By Evico vuitton E E EE ARES TNA pde TASSA SEE SEEEN EEEE REA RARA ARIA 17 DE Available modelne AAA AAA Ad 17 2 IZA O RIONI ORSI IRR 17 6 2 Support for wall mountm GPVWOQ ssis sesser seseratan nico DFAE RI EEEE Es EO daa EENS ESO IKES ARAN EOUN EESE TEASEE SEER RASOS ETRA ITERS 17 Avallable modelst ic ira all AAA A O REE 17 4 Size niet lele ono EI a 18 6 3 Gasket 002 7000009 fc rotaia nl Alioni AG A Ola Al oli nie dba ds io naro ai 18 5 Available models pitt gpii eel a ill ui dillo alii all ili lil ili iii ili ito ill ll ie lillo 18 6 O O Ria La 18 7 TECHNICAL DATA esi RN E E II RI RR RI RO ina tte 19 7 1 LECCE A A iS 19 page 3 of 22 Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 1 INTRODUCTION 1 1 Introduction Vroom is a new and innovative user interface for the programmable controllers of the family c pro 3 The main features of the interface are the possibility to communicate to the user a great deal of information and the remarkable ease of control these features are due to
9. ed in the network 3 2 Additional information for electrical connection do not operate on the terminal blocks with electrical or pneumatic screwers if the interface has been moved from a cold location to a warm one the humidity could condense on the inside wait about an hour before supplying it test the working power supply voltage working electrical frequency and working electrical power of the interface they must correspond with the local power supply disconnect the local power supply before servicing the interface do not use the interface as safety device for repairs and information on the interface please contact Evco sales network page 9 of 22 Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 4 CONFIGURATION 4 1 Preliminary information The following table shows the main meaning of the buttons Button Meaning esc button escape hereinafter called button ESC lt button move to left hereinafter called button LEFT A button increase hereinafter called button UP Y button decrease hereinafter called button DOWN D button move to right hereinafter called button RIGHT button confirm hereinafter called button ENTER 4 2 Configuring the interface To gain access to the procedure operate as follows 1 Switch off the power supply 2 Keep pressed buttons ESC and RIGHT 3 Switch on the power supply 4 When the
10. elease button ESC to go back to the Main menu page 11 of 22 Evco S p A To quit the procedure Vroom Hardware manual ver 1 00 Code 114VROOHWE00 34 Press and release over and over again button ESC possible modifications will not be saved A Switch off the power supply and then switch it on after the modification of the configuration 4 3 List of configuration parameters Submenu Parameter Min Max Unit Default Description Parameters DateCharSep Date separator ASCII character Year format Parameters Year format YY YY two numbers for example 0 YYYY four numbers for example 20 0 Date format ymd year month and day Parameters Date format dmy mdy month day and year dmy day month and year Parameters TimeCharSep Time separator ASCII character Showing the seconds in the real time Parameters TimeWithSec 0 1 1 1 yes Time format Parameters Time AM PM 0 1 0 0 24h for example 15 20 1 12h for example 3 20 PM Backlight mode OFF backlight is never lit ON backlight is always lit Parameters Back Mode TIME TIME backlight is lit the time one has set with parameter BackTimeout since the last operation with the buttons Backlight duration only if parameter Back Mode Parameters BackTimeout 0 240 s 60 has value TIME Local or of the interface CAN communication time out after this time without CAN Para
11. els The following table shows the available models and the respective main features Code Main features CPVP00 plastic material white CPVPOI plastic material black 1 1 2 Size Size in mm in 112 0 4 409 133 0 5 236 6 2 Support for wall mounting CPVW00 1 1 3 Available models The following table shows the available models and the respective main features Code Main features CPVWO00 plastic material white page 17 of 22 Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 1 1 4 Size Size in mm in Ya O A O 92 0 3 622 116 0 4 566 O_O E pe da i 94 0 3 700 138 0 5 433 gt 6 3 Gasket 0027000007 1 1 5 Available models The following table shows the available models and the respective main features Code Main features 0027000007 black to get a frontal protection degree IP65 only in case of panel mounting 1 1 6 Size Size in mm in k 106 0 ia ir 118 0 ue er page 18 of 22 Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 7 TECHNICAL DATA 7 1 Technical data Purpose of control user interface for programmable controllers Construction of control electronic device to be incorporated Box self extinguishing transparent 3 118 0 x 111 0 x 26 7 mm 4 645 x 4 370 x 1 051 in ize Size refers to the i
12. f 22 Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 1 2 Available models The following table shows the available models and the respective main features Code Main features Not isolated power supply 24 VAC or 20 40 VDC 128 x 64 pixel LCD graphic display real time EPV4QBR p pply p grap play clock alarm buzzer temperature sensor Isolated power supply 12 24 VAC or 15 40 VDC 128 x 64 pixel LCD graphic display real time EPV3QBR p pply p grap play clock alarm buzzer temperature sensor Not isolated power supply 24 VAC or 20 40 VDC 128 x 64 pixel LCD graphic display real time EPV4RBR p pply p grap play clock alarm buzzer temperature and humidity sensor Isolated power supply 12 24 VAC or 15 40 VDC 128 x 64 pixel LCD graphic display real time EPV3RBR p pply p grap play clock alarm buzzer temperature and humidity sensor For further models contact the Evco s sales network Evco at the address sales evco it page 5 of 22 Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 2 SIZE AND INSTALLATION 2 1 Size Size in mm in panel cut out 111 0 4 370 T i i gt Ce lt a JEJEJ Lod LLM S a 00 Q S n one bie suini Size Minimum Typical Maximum A 104 0 4 094 104 0 4 094 104 8 4 125 B 70 0 2 755 70 0 2 755 70 8 2 787 C 22 0 0 866 23 0 0 905 24
13. meters T O Timeout 0 240 s 60 communication the display will show page 12 of 22 Checking and the VO of the interface will be disabled Evco S p A Parameters PW Timeout 240 s Vroom Hardware manual ver 1 00 Code 114VROOHWE00 60 Netwok CAN submenu access password time out after this time without one has operated with the buttons to gain access again to the submenu one has to set the password again Parameters Contrast 63 ngs 25 Display s contrast Parameters Buzz On Key Uttering a beep while pressing a button 1 yes Parameters PrintLoad Showing the indication Loading while loading a page 1 yes Parameters Print Frame Showing frames instead small size pages 1 yes Network CAN MyNode 127 99 Local or of the interface CAN node s address Network CAN Master YES The interface always works as master Network CAN Baud Auto CAN communication baud rate 20K 20 000 baud 50K 50 000 baud 125K 125 000 baud 500K 500 000 baud Auto the interface recognizes the baud rate automatically on condition that it is one of the those mentioned above One suggests modifying the value of the parameter and assign each device in the network the same baud rate Network CAN Net Timeout 240 s Remote or of the devices in the network CAN communication time out
14. nterface with connector 1 and connector 2 properly plugged the installation is possible by panel built in by wall in traditional box like 506 by BTicino by wall on the support CPVWO00 by Evco to order separately look at chapter Installation 6 ACCESSORIES Fixing screws are always supplied by the builder At the front of the interface one can apply the plates CPVP by Evco to order separately made in plastic material and available in two different colorations white and black look at chapter 6 ACCESSORIES IP40 IP65 for panel mounting with gasket 0027000007 to order separately look at chapter Frontal protection degree 6 ACCESSORIES extractable male female terminal blocks power supply and CAN port 6 poles telephone connector programming port The maximum length of the connecting cables of the CAN port of the interface depends on the baud rate of the CAN communication as follows 1 000 m 3 280 ft with baud rate 20 000 baud Connections i 500 m 1 640 ft with baud rate 50 000 baud 250 m 820 ft with baud rate 125 000 baud 50 m 164 ft with baud rate 500 000 baud According to the default settings the interface recognizes the baud rate automatically on condition that it is one of the those mentioned above Working temperature from 0 to 50 C 32 to 120 F 10 90 of relative humidity without condensate Pollution situation 2 or more page 19 of 22
15. om 5 to 95 of relative humidity Accuracy 3 of relative humidity from 20 to 80 5 otherwise Display 128 x 64 pixel single colour LCD graphic display black with rearlighting through white LED Communication ports 2 ports 1 non optoisolated CAN port 1 programming port page 20 of 22 Evco S p A Vroom Hardware manual ver 1 00 PT March 2011 Code 114VROOHWE00 Vroom Hardware manual ver 1 00 Code 114VROOHWE00 This document belongs to Evco unless you are authorized by Evco you can not publish this document Evco does not take any responsibility about features technical data and possible mistakes related in this document Evco does not take any responsibility about damages coming by the non observance of additional information Evco reserves the right to make any change without prior notice and at any time without prejudice the basic safety and operating features page 21 of 22 Evco S p A A y EveryControlGroup Evco S p A Via Mezzaterra 6 32036 Sedico Belluno ITALIA Tel 0437 852468 Fax 0437 83648 info evco it www evco it page 22 of 22 Vroom Hardware manual ver 1 00 Code 114VROOHWE00
16. the use of a 128 x 64 pixel single colour LCD graphic display black with rearlighting through white LED to the 6 buttons with preset functions membrane keyboard and to the CAN bus for the connection to the controllers This last also allows the use of the interface in multimaster networks The user interface incorporates a temperature sensor or a temperature and humidity one the values read by these sensors are transmitted via CAN bus making easier the wiring Thanks to its constructive features Vroom offers several mounting typologies this is possible by panel at the front of units of machines for refrigeration or for air conditioning of electrical panels and as well as in all those applications where a frontal protection degree IP65 is required built in by wall in traditional box like 506 by BTicino by wall on the support CPVW00 by Evco to order separately Also the necessity to customize the interface in order to integrate it aesthetically in residential and commercial environments is satisfied by Vroom since at the front of the interface one can apply both the plates CPVP by Evco to order separately made in plastic material and available in two different colorations white and black and the numerous plates series Living and Light by BTicino Vroom also has got real time clock alarm buzzer evco v room O v room o i Checking Less IIL AJL VILE Je page 4 o
17. ubmenu According to the default settings the CAN node s address of a controller has value 7 so operate on the interface to set parameter NW Node to 1 1 and the CAN node s address of an expansion has value 2 so operate on the interface to set parameter NW Node to 2 2 Keep pressed 2 s buttons LEFT and ENTER of the interface the display will show the Network Status menu Network Status Loc 99 OK 2 1 1 OK gt gt 2 2 OK gt gt 3 0 gt gt 4 0 gt gt 5 0 gt gt Press and release button UP or button DOWN to select the device Press and release button ENTER the display will show the device s Main menu Operate as indicated in paragraph 4 2 Configuring the interface Switch off the power supply of the device and then switch it on after the modification of the configuration page 15 of 22 Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 5 SIGNALS 5 1 Signals The following table shows the meaning of the LEDS at the back of the interface LED Meaning POWER if it is lit the interface will be turned supplied CAN RY it provides information on the status of the receiving line of the CAN port CAN Na i tee it provides information on the status of the transmitting line of the CAN port TX page 16 of 22 Evco S p A Vroom Hardware manual ver 1 00 Code 114VROOHWE00 6 ACCESSORIES 6 1 Frontal plates CPVP by Evco 1 1 1 Available mod