1. 2 12 AA8 Description Read LED Configuration Syntax AA8 CHK cr delimiter character AA address of reading module 00 to FF 8 command for setting LED configuration Response Valid Command AAV CHK cr Invalid Command 2AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF V LED configuration 1 module control 2 host control Example Command 018 Receive 011 Read address 01 LED configuration return module control Command 028 Receive 012 Read address 02 LED configuration return host control Related Command Sec2 13 AA8V Sec2 18 AAZ Data Note The command is for I 7011D 11PD only 2 13 SAA8V Description Set LED Configuration Syntax AA8V CHK cr delimiter character AA address of setting module 00 to FF 8 command for setting LED configuration V 1 Set LED to module 2 Set LED to host Response Valid Command AA CHK cr Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Example Command 0182 Receive 01 Set address 01 LED to host control return success Command 0281 Receive 02 Set address 02 LED to module control return success Related Command Sec2 12 AA8 Sec2 18 AAZ Data N
2. delimiter for invalid command AA address of response module 00 to FF SS Module Status The status will store into EEPROM and only may reset by the command HAAI Reserved 2 Reserved 1 Host watchdog status 0 Disable 1 Enable 2 Host watchdog timeout flag 0 Clear 1 Set Example Command 010 Receive 0104 Read address 02 module status return 04 host watchdog timeout flag is set Related Command Sec 2 34 lt AAI Related Topic Sec 3 2 Module Status Sec 3 3 Dual Watchdog Operation 2 34 AAN Description Reset Module Status Syntax AA1 CHK er delimiter character AA address of setting module 00 to FF l command for reset module status Response Valid Command IAA CHK Ter Invalid Command AA CHK Ter Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Example Command 010 Receive 0104 Read address 01 module status return 04 host watchdog timeout flag is set Command 011 Receive 01 Reset address 01 module status return success Command 010 Receive 0100 Read address 01 module status return 00 Module Status is clear Related Command Sec 2 32 Sec 2 33 AA0 Related Topic Sec 3 2 Module Status Sec 3 3 Dual Watchdog Operation 2 35 AA2 Description Read Host Watchdog Timeout Interval Syntax AA2 CHK cr delimiter ch
3. 1 4 Block Diagram 7011 11D 11P 11PD EEPROM Embedded Controller iW RS 485 Interface E Power Regulator Motion Sensors Converters Keyboards SCADA _ Telemetr 1 5 Wire Connection I 7011 11D 11P 11PD Analog I 7011 11D 11P 11PD Digital Input Wire Connection Output Wire Connection A NS Vas TM 18 mv V e palle YS rs O 8 IN rom n 8 mA chal ete sigd em S I 7018 18P Analog Input Chan I 7011 11D 11P 11PD Digital nel 0 to 5 Wire Connection Input Wire Connection oOo A ia ni O 8 INx PC e 0 p sd TTL GND U S B GND at O 8 INx O U 8 DIO EV hi OF DO 8 INx O S B GND hen suide D 3 sii chela elle O B GND IKS I 7018 18P Analog Input Chan nel 6 and 7 Wire Connection while the jumper JP1 setting is 8 differential mode JP ele ele Vin 6 Vin 6 Vin 7 INIT Vin7 Vin 6 Vin 6 Vin 7 INIT Vin7 Vin 6 Vin 6 Vin 7 INIT Vin7 I 7018 18P Analog Input Chan nel 6 and 7 Wire Connection while the jumper JP1 setting is INIT mode JP o ele el Vin 6 Vin 6 Vin 7 INIT Vin7 Vin 6 Vin 6 Vin 7 INIT Vin7 1 6 Quick Start Refer to I 7000 Bus Converter User Manual and Get ting Start for more detail 1 7 Default Setting Default setting for I 7011 11D 11P 11PD 18 18P Address 01 Analog Input Type Type 05 2 5 to 2 5 V Baudrate 9600
4. cr delimiter character AA address of reading module 00 to FF 3 command for reading CJC temperature Response Valid Command gt Data CHK cr Invalid Command 2 AA CHK cr Syntax error or communication error may get no response gt delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Data CJC temperature in degree Celsius Example Command 033 Receive gt 0025 4 Read address 03 CJC temperature return 25 4 C Related Command Sec 2 14 AA9 Data 2 9 AA4 Description Read Synchronized Data Syntax AA4 CHK cr delimiter character AA address of reading module 00 to FF 4 command for reading synchronized data Response Valid Command gt AAS Data CHK cr Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command or the module does not re ceive command before the command AA4 AA address of response module 00 to FF S status of synchronized data 1 first time reading 0 has been readed Data synchronized data format reference Sec 1 10 Example See example of Sec 2 2 Related Command Sec 2 2 Note The command is for I 7011 11D 11P 11PD only 2 10 AASVV Description Set Channel Enable Syntax AASVV CHK er delimiter character AA address of setting module 00 to FF 5 command for settting chan
5. cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command or the calibration is not enabled AA address of response module 00 to FF Example Command 011 Receive 01 Perform address 01 zero calibration return success Command 021 Receive 02 Perform address 02 zero calibration return the calibration is not enabled before perform calibration command Related Command Sec 2 5 A A0 Sec 2 20 AAEV Related Topics Sec 1 9 Calibration 2 7 AA2 Description Read Configuration Syntax AA2 CHK cr delimiter character AA address of reading module 00 to FF 2 command for reading configuration Response Valid Command IAATTCCFF CHK er Invalid Command 2AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF TT type code of module reference Sec 1 10 CC baudrate code of module reference Sec 1 10 FF data format of module reference Sec 0 Example Command 012 Receive 101050600 Read address 01 configuration return success Command 022 Receive 02030602 Read address 02 configuration return success Related Command Sec2 1 NAANNTTCCFE Related Topics Sec 1 10 Configuration Tables Sec 3 1 INIT pin Operation 2 8 AA3 Description Read CJC Temperature Syntax AA3 CHK
6. 11D 11P 11PD 18 18P Baudrate Setting CC Gel ele ele ea ee esel me 200 60 sae 120 3 5 1520 Analog Input Type Setting TT Fine coeso fo fe oe ee an is sv mer swel iv 25v vm iu 3150 som ton my soon av wesw anna Fe cole e o CC ice i Je rfefefsjefsjefi u artene 30 20 mm o o 0 am EE x tp 70 172 50 nn ra en n 100 smo o The temperature is shown in degree Celsius T C Type L and M for I 7011P 11PD 18P only Data Format Setting FF 1 Filter Select 0 60Hz rejection 1 50Hz rejection 2 Checksum Bit 0 Disable 1 Enable 3 00 Engineer Unit Format 01 Percent Format 10 2 s Complement HEX Format Switches Motion Sensors Converters Keyboards SCADA _ Telemetr ati site i PLCs Acquisition Instruments Data logger Power HMIs Analog input type and data format table Type rma eke Hede 2 s complement HEX 7FFF 0000 8000 1 0000 0 0000 1 0000 04 I to 1 V of FSR 100 00 000 00 100 00 2 s complement HEX 7FFF 0000 8000 2 5000 0 0000 2 5000 2 5 to 2 5 05 of FSR 100 00 000 00 100 00 2 s complement HEX 7FFF 0000 8000 20 000 00 000 20 000 20 to 20 er of FSR 100 00 000 00 100 00 2 s complement HEX 7FFF 0000 8000 Switches Motion Sensors Converters Keyboards SCADA _ Telemetr ati site i PLCs Acquisition Instruments Data logger Power HMIs d Type e e FRE 7
7. Data data for show on the LED from 19999 to 19999 The data need sign 5 digits and decimal point Response Valid Command AA CHK cr Invalid Command 2AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command or LED not set to host con trol AA address of response module 00 to FF Example Command 01Z 123 45 Receive 01 Send address 01 LED data 123 45 return success Command 02Z 512 34 Receive 202 Send address 02 LED data 512 34 return the LED is not set ting in the host mode Related Command Sec 2 12 AA8 Sec2 13 AA8V Note The command is for I 7011D 11PD only 2 19 AAO Data Description Set Module Name Syntax AAO Data CHK cr delimiter character AA address of setting module 00 to FF O command for setting module name Data new name for module max 6 characters Response Valid Command AA CHK cr Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Example Command 0107018 Receive 01 Set address 01 module name to 7018 return success Command 01M Receive 017018 Read address 01 module name return 7018 Related Command Sec 2 17 AAM 2 20 AAEV Description Enable Disable Calibration Syntax AAEV CHK cr delimiter cha
8. GBE N ee 47 D OND I NE 48 22T OMD re 49 AE AG dd de EA 50 Re 51 200 ARE 32 EE RACE ir 53 E EE ee Te ee ee DI 2 36 AA3EVV Lui 58 NN 59 NNN 60 SAPPIA NO issie EES Re ENE REG 61 3 1 INE pin Operation hue 61 3 2 Module SERS soog de EI 61 3 3 Dual Watchdog Operation 62 3 4 Digital Input and Event Counter 62 DALTON 62 3 6 High Low Nr 63 3 7 Thermocouple Measurement 63 1 Introduction I 7000 is a family of network data acquisition and control modules They provide analog to digital digital to analog digital input output timer counter and other functions These modules can be remote controlled by a set of commands The common features of I 7011 11D 11P 11PD 18 18P are given as following e 3000VDC Isolated analog input e 24 bits sigma delta ADC to provide excellent accuracy e Thermocouple direct connect with build in CJC e Software calibration The I 7011 is a single channel analog input module The I 7011D is the I 7011 with a 44 digit LED display The I 7018 is a 8 channel analog input module The I 7011P 11PD 18P is the en hanced version of I 7011 11D 18 The I 7011P 11PD 18P support more thermocouple types and enhanced the measure range of some types 1 1 More Information Refer to I 7000 Bus Converter User Manual chapter 1 for more information as following 1 1 I 7000 Overview 1 2 I 7000 Related Documentation 1 3 I 7000 Command Fe
9. 60 00 00 000 210 00 210 to 760 of FSR 100 00 000 00 027 63 ES dae Venus 2 s complement HEX 7FFF 0000 DCA2 Lia 1372 0 00 000 0270 0 270 to 1372 of FSR 100 00 000 00 019 68 E6DO fs 2 s complement HEX 7FFF ripe Engineer Unit 400 00 000 00 270 00 270 to 400 of FSR 100 00 000 00 067 50 une Engineer Unit 1000 0 000 00 0270 0 270 to 1000 of FSR 100 00 000 00 027 00 degree Celsius n complement HEX 7FFF 0000 DD ra Engineer Unit 1768 0 0000 0 0000 0 0 to 1768 of FSR 100 00 0000 0 0000 0 degree Celsius gt complement HEX 7FFF 0000 0000 ew Engineer Unit 1786 0 0 0000 0000 0 0 to 1768 of FSR 100 00 000 00 0000 0 deeree CSAS 25 complement HEX 2 s complement HEX 7FFF 0000 0000 R Engineer Unit 1820 0 00 000 0000 0 0 to 1820 of FSR 100 00 000 00 0000 0 degree Celsius gt complement HEX 7FFF 0000 0000 n Engineer Unit 1300 0 00 000 0270 0 270 to 1300 of FSR 100 00 000 00 20 77 degree Celsius n complement HEX 7FFF 0000 E56B Er zas eS E Switches Motion Sensors Converters Keyboards SCADA _ Telemetr ati site i degree Celsius Fst omplement HEX 7FFF 0000 A99A PLCs Acquisition Instruments Data logger Power HMIs Type eke Dee C Type 2320 0 00 000 00 000 0 to 2320 ofFSR 100 00 000 00 000 00 degree Celsius 2 com
10. CHK cr delimiter character AA address of setting module 00 to FF EA command for enable alarm T alarm type M momentary alarm L latch alarm Response Valid Command AA CHK cr Invalid Command 2AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Example Command 01EAM Receive 01 Set address 01 momentary alarm return success Related Command Sec 2 26 AADA Sec 2 27 AACA Related Topic Sec 3 6 High Low Alarm Note The command is for I 7011 11D 11P 11PD only 2 24 AAHI Data Description Set High Alarm Syntax AADI CHK cr delimiter character AA address of setting module 00 to FF HI command for setting high alarm value Data high alarm values data format is in engineer unit format Response Valid Command AA CHK cr Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Example Command 01HI 2 5000 Receive 01 Set address 01 high alarm 2 5000 return success Related Command Sec 2 23 AAEAT Sec 2 28 AARH Related Topic Sec 3 6 High Low Alarm Note The command is for I 7011 11D 11P 11PD only 2 25 AALO Data Description Set Low Alarm Syntax AADI CHK cr delimiter character AA addre
11. Command AA CHK er Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Example Command 01DI Receive 10120101 Read address 01 digital input return latch alarm mode low alarm is set Command O1CA Receive 01 Clear address 01 latch alarm return success Command 01DI Receive 10120001 Read address 01 digital input return latch alarm mode both alarms are clear Related Command Sec 2 21 AADI Sec 2 23 AAEAT Sec 2 26 AADA Related Topic Sec 3 6 High Low Alarm Note The command is for I 7011 11D 11P 11PD only 2 28 AARH Description Read High Alarm Syntax AARHICHK er delimiter character AA address of reading module 00 to FF RH command for reading high alarm Response Valid Command AA Data CHK cr Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Data high alarm value in engineer unit format Example Command 01RH Receive 01 2 5000 Read address 01 high alarm return 2 5000 Related Command Sec 2 24 AAHI Data Related Topic Sec 3 6 High Low Alarm Note The command is for I 7011 11D 11P 11PD only 2 29 AARL Description Read Low Alarm Syntax QAARH CHK cr delimiter character AA addres
12. Example Command Q01DI Receive 10100001 Read address 01 digital I O status return alarm disable digital outputs all off and digital input high level Command 02DI Receive 10210100 Read address 02 digital I O status return momentary alarm enable high alarm is clear low alarm is set and digital input is high Related Command Sec 2 22 AADO Data Set 2 23 AAEAT Sec 2 26 AADA Related Topic Sec 3 4 Digital Input and Event Counter Sec 3 5 Digital Output Sec 3 6 High Low Alarm Note The command is for I 7011 11D 11P 11PD only 2 22 AADO Data Description Set Digital Output Syntax AADI CHK cr delimiter character AA address of setting module 00 to FF DO command for setting digital output Data output value 00 DO0 off DOI off 01 DO0 on DOI off 02 DO0 off DO1 on 03 DO0 on DO on Response Valid Command AA CHK cr Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command While the alarm is enabled the command will return invalid AA address of response module 00 to FF Example Command 01D000 Receive 101 Set address 01 digital output 00 return success Related Command Sec 2 21 AADI Set 2 23 AAEAT Sec 2 26 AADA Related Topic Sec 3 5 Digital Output Note The command is for I 7011 11D 11P 11PD only 2 23 AAEAT Description Enable Alarm Syntax QAAEAT
13. Impedance 20M Ohms Isolation 3000VDC Digital Output 2 channel Open Collector to 30V Output Load sink 30mA max Power Dissipation 300mW Digital Input I channel Logic Level 0 1V max Logic Level 1 3 5 to 30V Event Counter Max Input Frequency 50 Hz Min Pulse Width 1 mS Displayed LED 42 digits for I 7011PD Power Supply Input 10 to 30 VDC Consumption 0 9W for I 7011P 1 5W for I 7011PD 1 7018 Analog Input Input Channel 8 differential or 6 differen tial and 2 single ended Jumper select Input Type mV V mA with external 125 ohms resistor Thermocouple Type J K T E R 8 B N C Sampling Rate 10 Samples Second Bandwidth 15 7 Hz Accuracy 0 1 Zero Drift 0 5uV C Span Drift 25ppm C CMR 50 60Hz 150dB NMR S50 60Hz 100dB Input Impedance 20M Ohms Overvoltage Protection 35V Isolation 3000VDC Power Supply Input 10 to 30 VDC I 1 0W I 7018P Analog Input Input Channel 8 differential or 6 differen tial and 2 single ended Jumper select Analog Input Type mV V mA with external 125 ohms resistor Thermocouple Type J K T E R S B N C L M Sampling Rate 10 Samples Second Bandwidth 15 7 Hz Accuracy 0 1 Zero Drift 0 5uV C Span Drift 25ppm C CMR 50 60Hz 150dB NMR S50 60Hz 100dB Input Impedance 20M Ohms Overvoltage Protection 35V Isolation 3000VDC Power Supply Input 10 to 30 VDC Consumption 1 0W
14. Invalid Command AA CHK Ter Syntax error or communication error may get no response delimiter for valid command Pa delimiter for invalid command AA address of response module 00 to FF Example Command 0150003 Receive 101 Set address 01 PowerOn Value is DO0 off DO1 off Safe Value is DO0 on DO1 on return success Related Command Sec 2 37 AA4 Related Topic Sec 3 2 Module Status Sec 3 3 Dual Watchdog Operation Note The command is for I 7011 11D 11P 11PD only 3 Application Note 3 1 INIT pin Operation Each I 7000 module has a build in EEPROM to store con figuration information such as address type baudrate and other information Sometimes user may forget the configuration of the module Therefore the I 7000 have a special mode named INIT mode to help user to resolve the problem The INIT mode is setting as Address 00 baudrate 9600bps no checksum To enable INIT mode please follow these steps Stepl Power off the module Step2 Connect the INIT pin with the GND pin Step3 Power on Step4 Send command 002 cr in 9600bps to read the configura tion stored in the module s EEPROM Refer to 7000 Bus Converter User Manual Sec 5 and Getting Start for more information 3 2 Module Status PowerOn Reset or Module Watchdog Reset will let all output goto PowerOn Value And the module may accept the host s command to change the output value Host Watchdog Time
15. LE ictus e Your Automation Site Automation Site I 7011 11D I 7011P 11PD I 7018 I 7018P User Manual Warranty All products manufactured by factory are warranted against defective materials for a period of one year from the date of delivery to the original purchaser Warning Logicbus assume no liability for damages consequent to the use of this product Logicbus reserves the right to change this manual at any time without notice The information furnished by Logicbus is believed to be accurate and reliable However no re sponsibility is assumed by Logicbus for its use nor for any in fringements of patents or other rights of third parties resulting from its use Trademark The names used for identification only maybe registered trademarks of their respective companies Table of Contents I Introductio Oe Ee 5 1 1 More Informations 5 RAS 6 LPer 8 1 4 Block DAT Nr 11 L Wire Ge ON rio 12 1 6 Quick Start Lunar 14 DS REKE DE EN ee EE 14 1 8 Jumper Se U 14 LUN 15 1 10 Configuration Tables 16 PR Ge EE 20 2 1 WAANNTTCCFEF eee 22 TJERN 23 EEE 24 ANN 25 NAM 26 MN 21 DEE EE 28 I aps cates ah EE 29 NE 30 2 10 AASVV ees ee esse ee ese ee ee ee ee de ee dee 31 EN JER 32 S K T o E E ET 33 NN a N 34 AA AA Da rina 35 ENN EEE 36 PR Le T N 37 EEE EE 38 2 18 AAZ Data seene 39 TENG IDE oa ER ee 40 22 040 OE 41 AE OG DEE 42 2 22 AADO Data iii 44 EN 45 2 24 AAHI Data sss 46 ROE
16. _ Telemetr S ep N N I AAEAT AARH AARL AARE KT E S N N w w N N 2 1 AANNTTCCFF Description Set module Configuration Syntax 4AANNTTCCFF CHK er a delimiter character AA address of setting module 00 to FF NN new address for setting module 00 to FF TT new type for setting module Ref Sec 1 10 CC new baudrate for setting module Ref Sec 1 10 FF new data format for setting module Ref Sec 1 10 When changing the baudrate or checksum it is necessary to short the pin INIT to ground Response Valid Command IAA CHK er Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command While change baudrate or checksum setting without shorting INIT to ground the module will return invalid command AA address of response module 00 to FF Example Command 0102050600 Receive 02 Change address from 01 to 02 return success Related Command Sec 2 7 AA2 Related Topics Sec 1 10 Configuration Tables Sec 3 1 INIT pin Operation 2 2 Description Synchronized Sampling Syntax CHK cr i a delimiter character a synchronized sampling command Response No response Example Command 014 Receive 01 Read synchronized sampling data return no data valid Command No response Send synchronized sampling command Command 014 Receive gt 011 025 123 First read
17. aracter AA address of reading module 00 to FF 2 command for reading host watchdog timeout interval Response Valid Command IAAVV CHK cr Invalid Command AA CHK er Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF VV timeout interval in HEX format each count for 0 1 second 01 0 1 second and FF 25 5 seconds Example Command 012 Receive 01FF Read address 01 host watchdog timeout interval return FF host watchdog timeout interval is 25 5 seconds Related Command Sec 2 32 Sec 2 36 AA3EVV Related Topic Sec 3 2 Module Status Sec 3 3 Dual Watchdog Operation 2 36 AA3EVV Description Set Host Watchdog Timeout Interval Syntax AA3EVV CHK cr delimiter character AA address of setting module 00 to FF 3 command for set host watchdog timeout interval E 1 Enable 0 Disable host watchdog VV timeout value from 01 to FF each for 0 1 second Response Valid Command AA CHK cr Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command E delimiter for invalid command AA address of response module 00 to FF Example Command 013164 Receive 01 Set address 01 enable host watchdog and timeout interval is 64 10 0 seconds return success Command 012 Receive 0164 Read address 01 host watchdog timeout interval re
18. atures 1 4 I 7000 System Network Configuration 1 5 I 7000 Dimension 1 2 Pin Assignment B GND 10 OT ANS C SA QD VLYAO VIVO A LUIA LINI UIA 9 UIA 9 UIA S UIA S UIA O 5 v E E k HMIs Switches Motion Sensors Converters Keyboards Power Instruments Data logger Acquisition PLCs 1 3 Specifications I 7011 1 7011D Analog Input Input Channel 1 Input Type mV V mA with external 125 ohms resistor Thermocouple Type J K 1ERSBNG Sampling Rate 10 Samples Second Bandwidth 5 24 Hz Accuracy 0 05 Zero Drift 0 5uV C Span Drift 25ppm C CMR 50 60Hz 150dB NMR S50 60Hz 100dB Input Impedance 20M Ohms Isolation 3000VDC Digital Output 2 channel Open Collector to 30V Output Load sink 30mA max Power Dissipation 300mW Digital Input I channel Logic Level 0 1V max Logic Level 1 3 5 to 30V Event Counter Max Input Frequency 50 Hz Min Pulse Width I mS Displayed LED 41 digits for I 7011D Power Supply Input 10 to 30 VDC Consumption 0 9W for I 7011 1 5W for I 7011D I 7011P I 7011PD Analog Input Input Channel 1 Input Type mV V mA with external 125 ohms resistor Thermocouple Type J K T E R S B N C L M Sampling Rate 10 Samples Second Bandwidth 5 24 Hz Accuracy 0 05 Zero Drift 0 5uV C Span Drift 25ppm C CMR 50 60Hz 150dB NMR S50 60Hz 100dB Input
19. bps Checksum disable 60Hz rejection engineer unit format I 7018 18P set as INIT mode and the analog input is 6 differ ential and 2 single ended 1 8 Jumper Setting I 7018 18P Jumper JP1 for select the pin INIT Vin 7 Select 8 differential mode the pin INIT Vin7 is set to Vin7 JP olo ele Select INIT mode the pin INIT Vin7 is set to INIT JP1 1 9 Calibration Don t Perform Calibrate Until You Really Understand Calibration Requirement for I 7011 11D 11P 11PD 18 18P Co KEENE SEAN NE in pt om 15 50 100 500 Meme LAP av ZA Notification 1 While calibrate type 06 need connect external shunt resistor 125 ohms 0 1 Ref Sec 1 5 2 Connect calibration voltage or current signal to module s input For I 7018 18P connect to channel 0 Wire connect ref Sec 1 5 3 Before calibration warm up module about 30 minutes for bet ter accuracy Example Calibration Sequence for Type 00 I Setting Type to 00 gt Ref Sec 2 1 2 Enable Calibration gt Ref Sec 2 20 3 Apply Zero Calibration Voltage 0mV 4 Preform Zero Calibration Command gt Ref Sec 2 6 5 Apply Span Calibration Voltage 15mV 6 Perform Span Calibration Command gt Ref Sec 2 5 7 Repeat stepl to step three times Calibration sequence for other type is similiar but different in step 1 to set different type rs Keyboards SCADA Telemetr icbus 1 10 Configuration Tables Configuration Table of I 7011
20. ecause we must first connect a voltmeter to the thermocouple and the voltmeter leads themselves create a new thermoelectric circuit Therefore we need to eliminate the junction thermoelec tric to measure the correct Seebeck voltage and this is called Cold Junction Compensation For most thermocouples the Seebeck voltage is OV while in 0 C One simple way to cancel the junction voltage is to put the junction into 0 C enviroment and the junction voltage is OV Normally this is not a good method for most application Typical method is to measure the junction temperature by thermistor and measure the junction voltage from the junction temperature Then we may get the Seebeck voltage from measured thermocouple voltage and junction voltage and we may calculate the tempera ture from the Seebeck voltage E p PLCs Acquisition Instruments Data logger Power HMIs B Po 2 SE Switches Motion Sensors Converters Keyboards SCADA _ Telemetr ati site i
21. ent counter Response Valid Command IAA CHK er Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Example Command 01RE Receive 10101234 Read address 01 event counter return 1234 Command 01CE Receive 01 Clear address 01 event counter return success Command 01RE Receive 0100000 Read address 01 event counter return 0 Related Command Sec 2 30 AARE Related Topic Sec 3 4 Digital Input and Event Counter Note The command is for I 7011 11D 11P 11PD only AI EE Description Host OK Host sends this command to all modules for broadcasting the in formation Host OK Syntax CHK cr delimiter character ia command for all modules Response No response Example Command No response Send Host OK to all modules Related Command Sec 2 33 AA0 Sec 2 34 AA1 Sec 2 35 AA2 Sec 2 36 AA3EVV Sec 2 37 AA4 Sec 2 38 AASPSS Related Topic Sec 3 2 Module Status Sec 3 3 Dual Watchdog Operation 2 33 AA0 Description Read Module Status Syntax AA0 CHK cr delimiter character AA address of reading module 00 to FF 0 command for reading module status Response Valid Command AASS CHK cr Invalid Command 2AAICHK cr Syntax error or communication error may get no response delimiter for valid command
22. et to PowerOn Value If the host watchdog timeout flag is set the module will 3 6 High Low Alarm Some analog input modules like I 7011 equip with the high low alarm function When the alarm function is enabled the digital output DOO is the low alarm indicator DO1 is the high alarm indicator and the digital output command for changing digi tal outputs DOO DOI is ignored The alarm function is to com pare the analog input value with given high alarm value and low alarm value And there are two alarm types as follows e Momentary alarm the alarm status is cleared while the ana log input is not over the alarm value If Analog Input Value gt High Alarm DO1 High alarm is on else DO is off If Analog Input Value lt Low Alarm DOO Low alarm is on else DOO is off e Latch Alarm the alarm is cleared only the user send com mand to clear If Analog Input Value gt High Alarm DO 1 High alarm is on else if Analog Input Value lt Low Alarm DOO Low alarm is on 3 7 Thermocouple Measurement When two wires composed of dissimilar metal are joined at one end and heated the open circuit voltage is a function of the junction temperature and the composition of the two metals All dissimilar metals exhibit this effect The voltage is called Seebeck voltage For small changes in temperature the Seebeck voltage is linearly proportional to temperature To measure the Seebeck voltage directly is not available b
23. f response module 00 to FF Data analog input value reference Sec 1 10 for its format Example Command 032 Receive gt 02 513 Read address 03 channel 2 get data success Command 029 Receive 02 Read address 02 channel 9 return error channel number Related Command Sec 2 1 AANNTTCCFF Sec 2 7 AA2 Related Topics Sec 1 10 Configuration Tables Note The command is for I 7018 18P only 2 5 AA0 Description Perform Span Calibration Syntax AA0 CHK cr delimiter character AA address of setting module 00 to FF 0 command for performing span calibration Response Valid Command IAA CHK er Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command or the calibration is not enabled AA address of response module 00 to FF Example Command 010 Receive 01 Perform address 01 span calibration return success Command 020 Receive 202 Perform address 02 span calibration return the calibration is not enabled before perform calibration command Related Command Sec 2 6 AA1 Sec 2 20 AAEV Related Topics Sec 1 9 Calibration 2 6 SAAI Description Perform Zero Calibration Syntax AA1 CHK cr delimiter character AA address of setting module 00 to FF l command for performing zero calibration Response Valid Command AA CHK cr Invalid Command 2 AA CHK
24. get status 1 first read Command 014 Receive gt 010 025 123 Second read get status 0 have readed Related Command Sec 2 9 AA4 Note The command is for I 7011 11D 11P 11PD only 2 3 HAA Description Read Analog Input Syntax FAA CHK er amp delimiter character AA address of reading module 00 to FF Response Valid Command gt Data CHK cr Syntax error or communication error may get no response 2 delimiter for valid command Data analog input value reference Sec 1 10 for its format For I 7018 18P the data is the combination for each chan nel respectively Example Command 01 Receive gt 02 635 Read address 01 return data success Command 02 Receive gt 4C53 Read address 02 return data in HEX format success Command 04 Receive gt 05 123 04 153 07 234 02 356 10 000 05 133 02 345 08 234 Module address 04 is I 7018 Read address 04 get analog in put data of 8 channels Related Command Sec 2 1 NAANNTTCCFEF Sec 2 7 AA2 Related Topics Sec 1 10 Configuration Tables 2 4 HAAN Description Read Analog Input from channel N Syntax FAAN CHK cr F delimiter character AA address of reading module 00 to FF N channel to read from 0 to 7 Response Valid Command gt Data CHK cr Invalid Command 2 AA CHK cr Syntax error or communication error may get no response gt delimiter for valid command delimiter for invalid command AA address o
25. n Read Firmware Version Syntax AAF CHK er delimiter character AA address of reading module 00 to FF F command for reading firmware version Response Valid Command AA Data CHK cr Invalid Command 2AAICHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Data firmware version of module Example Command 01F Receive 01A2 0 Read address 01 firmware version return version A2 0 Command 02F Receive 01B1 1 Read address 02 firmware version return version B1 1 2 17 SAAM Description Read Module Name Syntax SAAM CHK cr delimiter character AA address of reading module 00 to FF M command for reading module name Response Valid Command IAA Data CHK cr Invalid Command 2AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Data Name of module Example Command 01M Receive 017018 Read address 01 module name return name 7018 Command 03M Receive 037011D Read address 03 module name return name 7011D Related Command Sec 2 19 AAO Data 2 18 SAAZ Data Description Set LED Data Syntax AAZ Data CHK cr delimiter character AA address of setting module 00 to FF Z command for setting LED data
26. nel enable VV channel enable disable 00 is all disabled and FF is all enabled Response Valid Command IAA CHK er Invalid Command AA CHK er Syntax error or communication error may get no response delimiter for valid command i delimiter for invalid command AA address of response module 00 to FF Example Command 0155A Receive 01 Set address 01 enable channel 1 3 4 6 and disable channel 0 2 5 7 return success Command 016 Receive 015A Read address 01 channel status return channel 1 3 4 6 enable and channel 0 2 5 7 disable Related Command Sec 2 11 AA6 Note The command is for I 7018 18P only 2 11 AA6 Description Read Channel Status Syntax AA6 CHK cr delimiter character AA address of reading module 00 to FF 6 command for reading channel status Response Valid Command IAAVV CHK ecr Invalid Command 2AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF VV channel enable disable 00 is all disabled and FF is all enabled Example Command 015A5 Receive 01 Set address 01 enable channel 0 2 5 7 and disable channel 1 3 4 6 return success Command 016 Receive 01A5 Read address 01 channel status return channel 0 2 5 7 enable and channel 1 3 4 6 disable Related Command Sec2 10 AASVV Note The command is for I 7018 18P only
27. ote The command is for I 7011D 11PD only 2 14 AA9 Data Description Set CJC Offset Value Syntax AA9 Data CHK cr delimiter character AA address of setting module 00 to FF 9 command for setting CJC offset value Data CJC offset value comprises a sign and 4 hexadecimal digits from 1000 to 1000 each count is 0 01 C Response Valid Command AA CHK cr Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command i delimiter for invalid command AA address of response module 00 to FF Example Command 019 0010 Receive 01 Set address 01 CJC offset increase 16 counts 0 16 C return SUCCESS Related Command Sec 2 8 AA3 2 15 AAB Description Thremocouple Open Detection Syntax AAB CHK cr delimiter character AA address of reading module 00 to FF B command for reading thremocouple open status Response Valid Command IAAS CHK er Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF S 0 close loop detection 1 open circuit detection need to check the thermocouple Example Command 01B Receive 010 Read address 01 thermocouple open status return the thermo couple is close loop Note The command is for I 7011 11D 11P 11PD only 2 16 AAF Descriptio
28. out will let all digital output goto Safe Value The host watchdog timeout flag is set and the output command will be ignored The module s LED will go to flash and user must reset the Module Status via command to restore normal operation 3 3 Dual Watchdog Operation Dual Watchdog Module Watchdog Host Watchdog The Module Watchdog is a hardware reset circuit to moni tor the module s operating status While working in harsh or noisy environment the module may be down by the external signal The circuit may let the module to work continues and never halt The Host Watchdog is a software function to monitor the host s operating status Its purpose is to prevent the network com munication from problem or host halt While the timeout occurred the module will turn the all output into safe state to prevent from unexpected problem of controlled target The I 7000 module with Dual Watchdog may let the con trol system more reliable and stable 3 4 Digital Input and Event Counter The digital input DIO may work as event counter The counter updates while the input changes from high level to low level The counter is 16 bit width and useful for low speed count frequency is lower than 50Hz 3 5 Digital Output When the module power on the host watchdog timeout flag is checked first If the status is set the digital outputs DOO and DO1 of module will set to Safe Value If the flag is clear the digital outputs will s
29. plement HEX 7FFF 0000 0000 L Type Engineer Unt 800 00 00 000 200 00 200 to 800 025 00 200 to 100 100 00 1 Only available for I 7011P I 7011PD and I 7018P Switches Motion Sensors Converters Keyboards SCADA _ Telemetr ati site www logicbus com E p PLCs Acquisition Instruments Data logger Power HMIs i Your av 2 Command Command Format Leading Address Command CHK er Response Format Leading Address Data CHK cr CHK 2 character checksum cr end of command character character return 0x0D Read Analog Input from S bee pa Se Camere fsee2i0 aw Read Ciani i sec 21r br faw pa mem fa src oma we senn Saab as fre Open Dese sers sar AAC Rend Fare ern sec216 sewn paapaa Jeni 527 EE ME CT E Poe wl PLCs Acquisition Instruments Data logger Power HMIs Switches Motion Sensors Converters Keyboards SCADA _ Telemetr HE General Command Sets Continued AAO Data IAA Set Module Name Sec 2 19 IAA Enable Disable Calibration Sec 2 20 Digital Input Output Alarm and Event Counter Command Sets IAASOOII i voed and 0 2 21 ET Er a 50022 AA AA n T i JE we 2 AA0 Read Module Status Sec 2 33 AAD l A AV Read Host Watchdog Sec 2 35 Timeout Value IAA Set Host Watchdog 2 Timeout Value Read PowerOn Value and I AASPPSS IAA PO VE Vg Safe Value Motion Sensors Converters Keyboards SCADA
30. racter AA address of setting module 00 to FF E command for enable disable calibration V 1 enable calibration 0 disable calibration Response Valid Command AA CHK cr Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Example Command 010 Receive 01 Perform address 01 span calibration return it is not ready for calibration Command 01E1 Receive 01 Set address 01 to enable calibration return success Command 010 Receive 01 Preform address 01 span calibration return success Related Command Sec 2 5 AA0 Sec 2 6 SAAI Related Topic Sec 1 9 Calibration 2 21 AADI Description Read Digital I O and Alarm Status Syntax AADI CHK cr delimiter character AA address of reading module 00 to FF DI command for reading digital I O and alarm status Response Valid Command IAASOON CHK er Invalid Command AA CHK er Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF S alarm enable status O alarm disable 1 momentary alarm enabled 2 latch alarm enabled OO digital output status 00 DO0 off DO1 off 01 DO0 on DO1 off 02 DO0 off DO1 on 03 0D0 on DO on II digital input status 00 input low level 01 input high level
31. s of reading module 00 to FF RL command for reading low alarm Response Valid Command AA Data CHK cr Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Data low alarm value in engineer unit format Example Command 01RL Receive 01 2 5000 Read address 01 low alarm return 2 5000 Related Command Sec 2 25 AALO Data Related Topic Sec 3 6 High Low Alarm Note The command is for I 7011 11D 11P 11PD only 2 30 AARE Description Read Event Counter Syntax QAARE CHK cr delimiter character AA address of reading module 00 to FF RE command for reading event counter Response Valid Command AA Data CHK cr Invalid Command 2AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Data event counter value from 00000 to 65535 Example Command 01RE Receive 10101234 Read address 01 event counter return 1234 Related Command Sec 2 31 AACE Related Topic Sec 3 4 Digital Input and Event Counter Note The command is for I 7011 11D 11P 11PD only 2 31 AACE Description Clear Event Counter Syntax MAACE CHK er delimiter character AA address of setting module 00 to FF CE command for clear ev
32. ss of setting module 00 to FF LO command for setting high alarm value Data high alarm values data format is in engineer unit format Response Valid Command AA CHK cr Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Example Command 01LO 2 5000 Receive 101 Set address 01 low alarm 2 5000 return success Related Command Sec 2 23 AAEAT Sec 2 29 AARL Related Topic Sec 3 6 High Low Alarm Note The command is for I 7011 11D 11P 11PD only 2 26 AADA Description Disable Alarm Syntax AADA CHK cr delimiter character AA address of setting module 00 to FF DA command for disable alarm Response Valid Command AA CHK cr Invalid Command 2 AA CHK cr Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF Example Command 01DA Receive 01 Disable address 01 alarm return success Related Command Sec 2 23 AAEAT Related Topic Sec 3 6 High Low Alarm Note The command is for I 7011 11D 11P 11PD only 2 27 MAACA Description Clear Latch Alarm Syntax AACA CHK cr delimiter character AA address of setting module 00 to FF CA command for clear latch alarm Response Valid Command IAA CHK er Invalid
33. turn timeout interval is 64 10 0 seconds Related Command Sec 2 32 Sec 2 35 AA2 Related Topic Sec 3 2 Module Status Sec 3 3 Dual Watchdog Operation 2 37 AA4 Description Read PowerOn Value and Safe Value Syntax AA4 CHK er delimiter character AA address of reading module 00 to FF 4 command for reading PowerOn Value and Safe Value Response Valid Command IAAPPSS CHK cr Invalid Command AA CHK er Syntax error or communication error may get no response delimiter for valid command delimiter for invalid command AA address of response module 00 to FF PP PowerOn Value 00 DO0 off DO1 off 01 DO0 on DO off 02 DO0 off DO1 on 03 DO0 on DOI on SS Safe Value data format is same as PP Example Command 014 Receive 010000 Read address 01 PowerOn Safe Value return PowerOn Value is DOO off DO1 off Safe Value is DOO off DO off Related Command Sec 2 38 AASPPSS Related Topic Sec 3 2 Module Status Sec 3 3 Dual Watchdog Operation Note The command is for I 7011 11D 11P 11PD only 2 38 AASPPSS Description Set PowerOn Value and Safe Value Syntax AASPPSS CHK cr delimiter character AA address of setting module 00 to FF 5 command for setting PowerOn Value and Safe Value PP PowerOn Value 00 DO0 off DO1 off 01 DO0 on DOI off 02 D00 off DO1 on 03 DO0 on DOI on SS Safe Value data format is same as PP Response Valid Command IAA CHK Ter