Home
        User`s manual ATV28H - RS Components International
         Contents
1.               1  Assigning this function displays the corresponding settings in the SEt  menu so that they can be adjusted        77    ENGLISH    Configuration          I O assignment menu     O     continued                             no  not assigned    OCr   motor current  20 mA corresponds to twice the nominal motor thermal  current ItH    rFr  motor frequency  20 mA corresponds to the maximum frequency tFr    OLO   motor torque  20 mA corresponds to twice the nominal motor torque    OPr   power supplied by the speed controller  20 mA corresponds to twice the nominal  motor power     Code   Assignment Factory  setting    E r L  Minimum value on input AIC  adjustable from 0 to 20 mA  4mA    C r H  Maximum value on input AIC  adjustable from 4 to 20 mA  20 mA  These two parameters are used to configure the input for 0 20 mA  4 20 mA  20 4 mA  etc   Frequency                    l  ase    a it  Cri CrH 20 A CIMA   If the input used is Al2  these parameters remain proportionally active    4mA   2V  20 mA   10V  For a 0   10 V input  configure CrL at 0 and CrH       20    AD  Analog output rFr            ADE   Analog output  0  0 20 mA configuration  4  4 20 mA configuration             78    Configuration               assignment menu      D      continued                    Code  Assignment Factory  setting   r    Relay R2 SrA    no  not assigned   FtA   frequency threshold reached  The contact is closed if the motor frequency is  greater than or equal to the threshold set 
2.               Motor Line supply Altivar 28  Power Line Max  Line Max  Power Reference  indicated on current  3  prosp  current transient dissipated  plate  2  at U 1 atU2 line Isc current  4  at nominal  load   kW HP A A kA A A Ww  0 37 0 5 7 3 6 1 1 3 3 3 6 32 ATV 28HU09M2  0 75 1 9 8 8 2 1 4 8 6 45 ATV 28HU18M2  1 5 2 16 13 5 1 7 8 10 9 75 ATV 28HU29M2  2 2 3 22 1 18 6 1 11 15 107 ATV 28HU41M2  3 phase supply voltage  1  U1   U2   200   230 V 50 60 Hz  3   17 6 15 4 5 13 7 18 5 116 ATV 28HU54M2  4 5 21 9 19 1 5 17 5 24 6 160 ATV 28HU72M2  5 5 7 5 38 33 2 22 27 5 38 250 ATV 28HU90M2  75 10 43 5 36 6 22 33 49 5 343 ATV 28HD12M2  3 phase supply voltage  1  U1   U2   380   500 V 50 60 Hz  Motor Line supply Altivar 28  Power Line Max  Line Max  Power Reference  indicated on current  3  prosp  current transient dissipated  plate  2  atU1 atU2  linelsc  380 at500V current  4  at nominal   to 460V load  kW HP A A kA A A A Ww  0 75 1 3 9 3 5 5 2 3 2 1 3 5 33 ATV 28HU18N4  1 5 2 6 5 DT 5 4 1 3 8 6 2 61 ATV 28HU29N4  2 2 8 8 4 7 9 5 5 5 5 1 8 3 81 ATV 28HU41N4  3   10 3 9 1 5 71 6 5 10 6 100 ATV 28HU54N4  4 5 13 11 8 5 9 5 8 7 14 3 131 ATV 28HU72N4  5 5 75 22 1 20 4 22 14 3 13 2 21 5 215 ATV 28HU90N4  15 10 25 8 23 7 22 17 15 6 25 5 281 ATV 28HD12N4  11 15 39 3 35 9 22 27 7 25 5 41 6 401 ATV 28HD16N4  15 20 45 40 8 22 33 30 4 495 543 ATV 28HD23N4          52    Speed Controller References        1  Nominal supply voltages   min  U1  max  U2      2  These power ratings are for a maximu
3.               Next parameter        1  Configure bFr at the 1  power up  using the same procedure as for the other parameters  as  described above  Caution  bFr can only then be modified after a return to  factory settings         73    ENGLISH    Local control option       This option consists of a reference potentiometer and provides access to 2 additional buttons on the  speed controller  see documentation provided with the option              RUN button   controls the switching on of the motor  The direction of operation is determined by  parameter rOt in the settings menu SEt       STOP RESET button   controls the stopping of the motor and the clearing  resetting  of any  faults The first press on the button stops the motor  and if DC injection standstill braking  is configured  a second press stops this braking     The reference given by the reference potentiometer is summed with analog input Al1   Installing this option requires special factory setting of certain functions                tCC   OPt   LI1   no   LI2   PS2   LI3   PS4   LI4   PS8    not reassignable  not reassignable  reassignable  reassignable  reassignable      Drive   Atr   no  only reassignable at YES    This option cannot be removed once it has been fitted   The option must be connected with the speed controller powered down  otherwise it will trip on an InF    fault     Altivar 28  D  sovane          STOP    RUN  RESET    00090          74    Remote Display Module Option       This module can be mou
4.    Controls the stopping of the motor when there is a loss of line supply   following a ramp which automatically adapts according to the kinetic energy  restored    no   function inactive  YES   function active        no   YES       no          82    Configuration          Drive menu d r C     continued                 Code    Assignment    Adjustment  range    Factory  setting        Flr    Enables a smooth restart after the following events      loss of line supply or power off     fault reset or automatic restart     freewheel stop or injection stop with logic input   no   function inactive  YES   function active     no   YES    no        drn    Lowers the tripping threshold of the USF fault in order to operate on a line  supply with 40  voltage drops   no   function inactive   YES   function active      A line choke must be used   A    The performance of the speed controller can no longer be  guaranteed when operating at undervoltage     no   YES    no        545    Scale factor for the display parameter SPd   SUP menu   used to scale a  value in proportion to the output frequency  the machine speed or the motor  speed  For example     4 pole motor  1500 rpm       50 Hz      SdS   30    SPd  1500 at 50 Hz    1 to 200    30        FCS    Return to factory settings  no  no  YES   the next display will be Inlt then bFr  start of the menus        no   YES       no                   Parameter can be adjusted during operation        83       ENGLISH    ENGLISH    Settings      
5.   5 Pd  Display the value calculated by the speed controller  rFr x SdS       L Er  Display the motor current A z    DPr  Display the power supplied by the motor  estimated by the speed controller     72   100   corresponds to the nominal speed controller power  D    UL n  Display the line voltage    a   E Hr   Display the motor thermal state   100  corresponds to the nominal thermal state     Above 118   the speed controller triggers an OLF fault  motor overload     E Hd  Display the speed controller thermal state   100  corresponds to the nominal thermal state     Above 118   the speed controller triggers an        fault  drive overheated   It can be reset below 70     LFE  View the last fault which appeared  If there has been no fault  the display shows   noF        PU  Speed controller software version                Dd  Parameter which can only be seen and accessed using a remote display module option or PC software    Access code   0 to 9999  Value 0  factory setting  does not prevent access  All other values lock access   to the SEt   drC  and   O  menus    To lock access to the speed controller  the code can be incremented using  A Y  then saved using  ENT       Do not forget to make a note of the code  as once it has been saved  it is no longer    displayed      If a code other than 0 is configured  access to the menus requires a remote  display module option or PC software     To access the menus on a speed controller which is locked by a code  the code can be incre
6.   require the controller to be powered down    The fault is cleared when the logic input assigned to this function changes from 0 to 1     Forced local mode when using the serial link      Changes from line control mode  serial link  to local mode  control via the terminal block         67    ENGLISH    Configurable I O Application Functions       Analog input application functions  Input Al1 is always the reference     Assignment of Al2 AIC  Al2   0   10 V or AIC   X Y mA  X and Y can be configured from 0 to  20mA     Summing speed reference   The frequency reference from Al2 AIC can be summed with Al1     PI regulator   Can be assigned to     2         Allows a sensor to be connected and activates the Pl  regulator    The reference is input Al1 or an internal reference rPI which can be adjusted via the ATV 28 keypad   Parameters which can be accessed in the adjust menu       regulator proportional gain  rPG      regulator integral gain  rlG      Pl feedback multiplication coefficient  FbS    is used to adjust the max  value of the feedback so that t  corresponds to the max  value of the PI regulator reference      reversal of the direction of correction  PIC    if PIC   no  the motor speed increases when the error is  positive  if PIC   YES  the motor speed decreases when the error is positive     Ref              r PG ri  0 01to 100 0 01 to 100 x 1 S        Manual   Automatic  operation with Pl    This function combines the Pl regulator and reference switching by a logic i
7.  Adjust menu 5 E E      A                These adjustment parameters can be modified with the speed controller stopped or  running  Ensure that changes made during operation do not present any danger   Changes should preferably be made with the speed controller stopped                                         Code  Assignment Adjustment  Factory  range setting    L Fr   Speed reference via the display module  LSP to HSP  This parameter appears with the remote display module option if control of  the speed controller via the display module is enabled   LCC parameter in l   O  menu     r P       reference 0 0 to 100 0    0 0  This parameter appears if analog input            2 is assigned to the internal Pl  function  AIC   PII      r DE   Direction of operation  For   rrS For  This parameter appears if the  local control  option is present    It defines the direction of operation      forward   For    reverse   rrS     ACC   Acceleration and deceleration ramp times  0 0 to 3600s  35     dEC   Defined to range from 0 to nominal motor frequency  FrS  0 0 to 3600s  35     ALE   2nd acceleration ramp time 0 0 to 3600s  5s     dE     2nd deceleration ramp time 0 0 to 3600s  55  These parameters are accessible if the ramp switching threshold  Frt  parameter in the drC  menu  is other than 0 Hz or if a logic input is assigned  to ramp switching     L 5P  Low speed 0 to HSP 0 Hz     H5P   High speed   ensure that this setting is appropriate for the motor andthe  LSP to tFr bFr  applica
8.  current input Analog input X   Y mA  X and Y can be programmed from 0 to 20 mA   Al2 or AIC are assignable  impedance 450 Q    Use either  but not both   Resolution  precision  and sampling time of Al2 or AIC   Alt              AO Analog output Output can be programmed for 0   20 mA or 4  20 mA  e Precision   6  of the max  value  max  load impedance 800 Q   1 Logic inputs Programmable logic inputs   12     24 V power supply  max  30 V   LI3    Impedance 3 5       Ll4    State 0 if  lt  5 V  state 1 if  gt 11 V    Sampling time 4 ms max    24 Logic input power   24 V protected against short circuits and overloads  min  19 V  max   supply 30 V  Max  customer current available 100 mA                   59    ENGLISH    Wiring       Wiring diagram for factory settings    3 phase power supply    Single phase power supply    l  y y       Reference  potentiometer  Braking resistor   if used        1  Line choke  if used  single phase or 3 phase      2  Safety relay contacts  for remote indication of the speed controller status     3  Internal   24 V  If an external   24 V source is used  connect the 0 V from that source to the COM  terminal  and do not use the   24 terminal on the speed controller    Note   Fit interference suppressors to all inductive circuits near the speed controller or coupled to the  same circuit  relays  contactors  solenoid valves  etc     Choice of associated components    See Altivar 28 catalog        60    Wiring       Wiring recommendations    Power  Obs
9.  preset speeds  PS4   4 preset speeds  1   PS8   8 preset speeds  1   nSt  freewheel stop  Function active when the input is powered down   dCI   DC injection braking IdC  peak limited at 0 5      after 5 seconds  if the command is maintained  FSt  fast stop  Function active when the input is powered down   FLO   forced local mode  rst  fault reset  rFC   reference switching  when the input is powered down the speed reference is  AIC AI2 or that generated by the PI function if it is assigned     If tCC   3C  LI2   For  forward   cannot be reassigned   e Ifa function is already assigned to another input it still appears  but its storage using ENT   is inactive   e The 4 or 8 preset speeds must be configured in the following order of assignment   PS2  then PS4 then PS8  They must be cancelled in the reverse order  see Configurable I O  Application Functions              Analog input AIC   Al2 SAI  no  not assigned   SAI   summing with Al1  PII  Pl regulator feedback  the Pl reference being internal adjustment parameter rPI  1   PIA  Pl regulator feedback  the Pl reference being automatically assigned to Al1  1     SAI can only be assigned if a logic input is assigned to rFC  reference switching    e Pll and PIA cannot be assigned if a logic input is assigned to JOG or to PS2     If a logic input Llx is assigned to        reference switching  and AIC is assigned to PII or  PIA  the speed reference is taken on Al1 if Lix   0 and is the output of Pl if LIx   1        ENGLISH      
10.  value  in the memory    A Pressing      or  y  does not store the choices     Store  save the displayed choice    The display flashes when a value is stored     Normal display  with no fault present and no startup      Init   Initialization sequence      rdY   Speed controller ready     43 0   Display of the frequency reference     dcb   DC injection braking in progress     rtrY   Automatic restart in progress     nSt   Freewheel stop command      FSt   Fast stop command       72    Programming       Access to menus                                                                1  power up after factory configuration Subsequent power ups  Y    b F r  Nominal motor frequency    50 Hz  factory setting  or 60 Hz  ENT  bFR configuration  1   ENT y  rdY Display of speed controller status  4  ENT            Wait 3 seconds    Y A 0  ESC        A  SEE    Settings If it is not possible to access the   SEt     drC   9     j i A or  I O   menus  the speed controller is       ESC   protected by an access code  A remote display  dr        Drive module option or PC software is necessary to  Vv    i A access these menus  together with knowledge  1 0 ESC o of the code    f            See SUP  menu page 87              vi       5 u P    ES _ Display                      Access to parameters                                        Example    Menu ENT Parameter ENT Value or assignment  SEE   A YY 100  ESC ESC 1 flash  y   A        A tesc  save   ENT   UUU IDO    gt  I0 1 ESC                    
11. 0  1 J0  SP3  1 1 HSP 0 1 1 SP4  1  jo J0 1905  1 0 1 SP6  1 1 0 SP7  1 J1  1  HSP                              unassign the logic inputs  the following order must be observed   PS8  Llz   then PS4  Lly   then PS2   LIx      Reference switching    Two references are switched  Al1 reference and Al2 or AIC reference  by a command on a logic input   This function automatically assigns Al2 or AIC to speed reference 2    Connection diagram  Contact open  reference   Al2 or AIC  LIx  24 COM Ali  10 AIC Contact closed  reference   Al1    If AIZ AIC is assigned to the PI function  operation combines  both functions   see page 68           66    Configurable I O Application Functions       Freewheel stop    Stops the motor by the resistive torque only  The motor power supply is cut   Freewheel stop occurs when the logic input assigned to this function opens  state 0      DC injection stop  This can be activated in 2 ways        by activation of a logic input assigned to this function  state 1     automatically if the frequency is below 0 5 Hz       Fast stop      Braked stop with the current deceleration ramp time divided by 4 within the limits of the braking  possibilities   Fast stop occurs when the logic input assigned to this function opens  state 0      ENGLISH    Fault reset     Clears the memorized fault and resets the speed controller if the cause of the fault has disappeared   except for OCF  overcurrent   SCF  motor short circuit   EEF and InF  internal faults  faults  which
12. 56    Wiring       Access to terminals    To access the terminals  undo the screws on the cover and tilt     Diagram   Example showing ATV 28HU09M2    The speed controllers have a  removable plastic cable gland  with knock outs for running  cables through  if required   control and braking resistor                     ENGLISH                   1   Control  2   Power  1 or 2 terminals depending on the rating   3   Ground screw for motor cable  on low ratings only     Power terminals    Specifications of power terminals                      Altivar ATV 28H Maximum connection capacity Tightening torque in Nm  AWG mm2   U09M2  U18M2 AWG 14 25 0 8   U29M2  U18N4  U29N4   AWG 12 3 1 2   U41M2  U54M2  U72M2   AWG 10 5 1 2   U41N4  U54N4  U72N4   U90M2  D12M2  AWG 5 16 25   U9ON4  D12N4   D16N4  D23N4 AWG 3 25 4 5                   57    ENGLISH    Wiring       Functions of power terminals                                                 Terminal Function For Altivar ATV 28H     Altivar ground terminal All ratings   L1 All ratings   L2 Supply for power terminals   L3 3 phase only   PO DC bus   polarity All ratings   PA Output to braking resistor All ratings   PB Output to braking resistor All ratings   PC DC bus   polarity All ratings           Output to motor All ratings   Ww     Altivar ground terminal U90M2  D12M2  U90N4  D12N4   D16N4  D23N4       Arrangement of the power terminals  Do not remove the connector linking terminals PO and PA     ATV 28HU09M2  U18M2  U29M2 U49M2      P
13. Altivar 28   Telemecanique  Guide d exploitation    User s manual     Variateurs de vitesse pour  Bedienungsanleitung t h  Gu  a de explotaci  n           Variable speed controllers  for asynchronous motors   Frequenzumrichter  fur Drehstrom Asynchronmotoren   Variadores de velocidad  para motores as  ncronos     Square D    Telemecanique       Schneider    p Electric    ENGLISH    IT NEUTRAL POINT CONNECTION   In the event of use on a 3 phase network with a voltage greater  than 460V  10   with an isolated or high impedance system  IT   the internal EMC filter capacitors  which are connected to ground must be disconnected  Consult Schneider product support who are  the only people qualified to perform this operation    When the speed controller is powered up  the power elements and some of the control components  are connected to the line supply   t is extremely dangerous to touch them  The cover of the speed  controller must remain closed     In general  the speed controller power supply must be disconnected before any operation on either  the electrical or mechanical parts of the installation or machine    After the ALTIVAR has been switched off and the red LED has gone out  wait for 10 minutes before  working on the equipment  This is the time required for the capacitors to discharge    The motor can be stopped during operation by inhibiting start commands or the speed reference  while the speed controller remains powered up  If personnel safety requires prevention of sud
14. O   PA   PB   PC  U T1 V T2 W T3        LJ    ATV 28HU54M2  U72M2        R L1 S L2 T L3       U18N4  U29N4  U41N4  U54N4  U72N4         PO   PA   PB   PC  LJ   ATV 28HU90M2  D12M2      R L1 S L2 T L3          U T1  V T2  W T3    For the motor ground  use the ground screw  provided on the heatsink or on the EMC plate     For the motor ground  use the ground screw    provided on the heatsink or on the EMC plate     U9ON4  D12N4  D16N4  D23N4             PA   PB   PC  U T1 V T2  W T3             LJ       58    Wiring       Control terminals  Arrangement  specifications and functions of the control terminals                         mo  lt  Q on 2009 OTAN yw A   Maximum connection capacity                           1 5 mm2   AWG 16   0006569 9000900000000   ica    5 Nm   Terminal   Function Electrical specifications         Common point C O contact Min  switching capacity  R1B  R1C  of R1 fault relay    10 mA for 5 V          Max  switching capacity on inductive load     R2A N O contact of R2  cos       0 4 and L R  7 ms    2  R2C programmable relay   1 5 A for 250 V  and 30 V  D  COM  1O common  All Analog voltage input Analog input 0   10 V      impedance 30        e resolution 0 01 V     precision   4 3   linearity   0 2   of max  value     Sampling time 4 ms max     10 Power supply for potentiometer   10 V    8     0   10 mA max  protected against short circuits and       1 to 10 kQ overloads   Al2 Analog voltage input Analog input 0   10 V  impedance 30 kQ  or or   AIC Analog
15. by Ftd  1     CtA   current threshold reached  The contact is closed if the motor current is greater than  or equal to the threshold set by Ctd  1     SrA   speed reference reached  The contact is closed if the motor frequency is greater than  or equal to the speed reference              tSA   thermal threshold reached  The contact is closed if the motor thermal state is greater I  than or equal to the threshold set by ttd  1   2    Add   Address of the speed controller when it is controlled via the serial link  1  0     Z  Adjustable from 1 to 31           bdr   Serial link transmission speed   19 2    9 6   9600 bits   s or 19 2   19200 bits   s  Modification of this parameter is only taken into account after the speed controller has been  powered down then powered up               1  Assigning this function displays the corresponding settings in the SEt  menu so that they can be adjusted        79    ENGLISH    Configuration       Drive menu dr C                  The parameters can only be modified with the speed controller stopped and locked  except for       SFr   nrd and SdS  which can be adjusted with the controller running     Drive performance can be optimized by      entering the values given on the rating plate       performing an auto tune operation  on a standard asynchronous motor                             Code  Assignment Adjustment  Factory  range setting   Un 5   Nominal motor voltage marked on the rating plate   The adjustment range depends on the speed co
16. cial precautions        0  speed controllers mounted side by side    remove the protective cover from  the top of the speed controller  as shown below  the degree of protection becomes  IP20     e from 40  C to 50  C     d  gt  50 mm  remove the protective cover from the top of the speed controller  as  shown below  the degree of protection becomes IP20   If the cover is left on  derate  the nominal speed controller currentnominal speed controller current by 2 2   for  every   C above 40  C     d 0  remove the protective cover from the top of the speed controller  as shown  below  the degree of protection becomes IP20   and derate the nominal speed  controller current by 2 2   for every   C above 40  C      from 50  C to 60  C    d  gt  50 mm  remove the protective cover from the top of the speed controller  as  shown below  the degree of protection becomes IP20   and derate the nominal  speed controller current by 3   for every   C above 50  C              ENGLISH    ENGLISH    Mounting       Electromagnetic compatibility    EMC plate supplied with the speed controller       e C    0000                         4    screws for fixing  EMC clamps    Fit the EMC plate used for equipotential earthing on the holes of the  ATV28 heatsink using the 2 screws provided  as shown in the  drawing opposite           ATV 28H Ab Y  mm mm  U09M2  U18M2  U29M2  48 4    U41M2  U54M2  U72M2    U18N4  U29N4  U41N4    U54N4  U72N4   U90M2  D12M2  79   4  U90N4  D12N4  D16N4    D23N4             
17. contact on relay R2 closes  0 to HSP bFr      Ed  Current threshold beyond which the contact on relay R2 closes 0 1 ItH to 1 5 In  1    1 5 In  1      EE   Motor thermal state threshold beyond which the contact on relay R2 closes   1 to 118   100       EL 5  Low speed operating time 0 to 25 5 s 0  no time  Following operation at LSP for a defined period  a motor stop is requested limit   automatically  The motor restarts if the frequency reference is greater than  LSP and if a run command is still present    Caution   value 0 corresponds to an unlimited period        1  In is the nominal speed controller current shown in the catalogue and on the speed controller rating  plate     The parameters in shaded boxes appear if the corresponding functions have been configured  in the drC  or        menus           86    Settings          Display menu 5 U P     choice of parameter to be displayed during operation  view the last    fault  speed controller software version and access code    The display chosen is saved by       Pressing the ENT key once  the choice is temporary  it will be cleared at the next power up      Pressing the ENT key twice   the choice is permanent  The second press on ENT exits the SUP  menu              The following parameters can be accessed  with the speed controller stopped or running                                            Code  Parameter Unit    F r H   Display the frequency reference Hz   r Fr  Display the output frequency applied to the motor Hz  
18. control   The open or closed state of the input controls running or stopping     Wiring example        ATV 28  LI1   forward   24V Lit Lx    LIX   reverse         pe  A    3 wire control  pulse control    one pulse is all that is needed to control start up   Wiring example    LI1   stop   LI2   forward   LIx   reverse       Changing the assignment of tCC returns the logic inputs to  factory setting       tCC   2C   LI1    Forward   cannot be reassigned  LI2   rrS   Reverse      LI3   PS2 Ll4   PS4   tCC  3C LI1 Stop  cannot be reassigned  LI2  For   Forward    cannot be reassigned  LI3   rrS   Reverse   Ll4   JOG    1CC   OPt  LI1   no  cannot be reassigned LI2   PS2  LI3   PS4 LI4   PS8        LEC       Parameter only accessible with the remote display module option   no   YES   Enables control of the speed controller using the STOP RESET  RUN and FWD REV  buttons on the display module  The speed reference is then given by parameter LFr in the  SEt  menu  Only the freewheel  fast stop and DC injection stop commands remain active on  the terminal block  If the speed controller   display module link is broken  the speed controller  locks on an SLF fault        no          76    Configuration          I O assignment menu             continued                    Code  Assignment Factory  setting    L Ig  Logic inputs rrS    L Ij no  notassigned PS2    L 14   rrS  reverse rotation  2 operating directions  PS4    rP2  ramp switching  1   JOG    step by step  operation  1   PS2   2
19. controller  but do not give a run command    5   Configure       The nominal frequency  bFr  of the motor  if it is other than 50 Hz   e The parameters of the I O menu  and drC menus but if the factory configuration of the speed controller  is not suitable for the application   6   Set the following in the Set menu     If the speed controller factory settings are not suitable     e The acceleration  ACC  and deceleration  dEC  ramps   e The minimum  LSP  and maximum  HSP  speeds   e The motor thermal protection current  ItH       Other parameters as required  if the factory configuration has been changed  7   Start the speed coniroller    Practical recommendations          help with programming the speed controller  fill in the configuration and settings tables  page 92    in particular when the factory configuration has been changed    e Programming the Altivar 28 can be made easier by internal sequence selections and interlocks  In  order to gain the maximum benefit from this  it is recommended that the menus are accessed in the  following order     1   1 0 2  drC 3   Set   Not all steps are necessary in every case     Caution   A check must be made to ensure that the functions which have been programmed  are compatible with the wiring layout used        50    Factory Configuration       Factory settings    The Altivar 28 is factory set for the most common operating conditions       Display   speed controller ready  when stopped   motor frequency  when running     Line supp
20. ctivating this function automatically increases the deceleration time  if this  has been set at too low a value for the inertia of the load  thus avoiding the  controller going into ObF fault    no   function inactive  YES   function active    This function may not be compatible with position control on a ramp or with  the use of a braking resistor     no   YES    YES       SEE    Ramp switching frequency   When the output frequency becomes greater than Frt  the ramp times taken  into account are AC2 and dE2  If Frt   0  the function is inactive    This parameter does not appear if a logic input is assigned to the ramp  switching function rP2     0 to HSP    0 Hz       oP ir    Switching frequency   The switching frequency can be adjusted to reduce the noise generated by  the motor    Above 4 kHz  the speed controller output current must be derated       up to 12 kHz   derated by 10       above 12 kHz   derated by 20       2 to 15 kHz        nrd    This function randomly modulates the switching frequency to reduce the  motor noise  no   function inactive  YES   function active        no   YES       YES                   Parameter can be adjusted during operation        81       ENGLISH    ENGLISH    Configuration          Drive menu ld r C     continued                 Code    Assignment    Adjustment  range    Factory  setting        Atr    Automatic restart  after locking on a fault  if the fault has disappeared and the  other operating conditions permit the restart  The re
21. den  restarts  this electronic locking system is not sufficient   fit a device to remove the power circuit     The speed controller is fitted with safety devices which  in the event of a fault  can shut down the  speed controller and consequently the motor  The motor itself may be stopped by a mechanical  blockage  Finally  voltage variations  especially line supply failures  can also cause shutdowns    If the cause of the shutdown disappears  there is a risk of restarting which may endanger certain  machines or installations  especially those which must conform to safety regulations     In this case the user must take precautions against the possibility of restarts  in particular by using a  low speed detector to cut off power to the speed controller if the motor performs an unprogrammed  shutdown     The products and equipment described in this document may be changed or modified at any time   either from a technical point of view or in the way they are operated  Their description can in no way  be considered contractual    This speed controller must be installed and set up in accordance with IEC international standards and  with national standards  Bringing the device into conformity is the responsibility of the systems  integrator who must observe the European Union directives  especially the EMC directive    The specifications contained in this document must be applied in order to comply with the essential  requirements of the EMC directive     The Altivar 28 must be con
22. e motor load  the speed controller ventilation  speed controller   speed controller temperature too  and the environment  Wait for the controller to cool  overload high before restarting          Check the setting of the motor thermal protection   check the motor load  Wait for the controller to cool  before restarting         OSF  overvoltage in  steady state or  during acceleration      line voltage too high    disturbed line supply      Check the line voltage         USF      line supply too low      Check the voltage and the voltage parameter        during deceleration    undervoltage   transient voltage dip   Reset      damaged load resistor   Send the speed controller to be checked repaired    ObF   braking too sudden   Increase the deceleration time   overvoltage or driving load   Install a braking resistor if necessary       Activate the brA function if it is compatible with the  application         PHF  motor phase  phase failure      speed controller incorrectly  supplied or a fuse blown     transient phase fault     3 phase ATV28 used on a single  phase line supply      Check the power connection and the fuses       Reset    Use a 3 phase line supply              serial link failure       speed controller connector     OPF   loss of a phase at the speed   Check the connections from the speed controller to the  motor phase controller output motor    failure    5LF   incorrect connection on the   Check the serial link connection on the speed       controller connecto
23. erve the cable cross sectional areas recommended in the standards     The speed controller must be earthed  in order to comply with regulations concerning high leakage  currents  over 3 5 mA   When the use of an upstream  residual current device  for protection is required  by the installation standards  a  type B  device must be used  which will operate even in the presence of  DC components  If the installation has several speed controllers on the same line  each controller must  be earthed separately  If necessary  fit a line choke  consult the catalogue      Keep the power cables separate from circuits in the installation with low level signals  detectors  PLCs   measuring apparatus  video  telephone      Control  Keep the control circuits and the power cables apart  For control and speed reference circuits  we    recommend using shielded twisted cables with a pitch of between 25 and 50 mm  connecting the  shielding to ground at each end        61       ENGLISH    ENGLISH    Wiring       Electromagnetic compatibility  Principle      Grounds between speed controller  motor and cable shielding should have  high frequency   equipotentiality    e Use shielded cables with shielding connected to ground at 360   at both ends for the motor cable   braking resistor  if used  and control command cables  Conduit or metal ducting can be used for part of  the shielding length  provided that there is no break in continuity    e Ensure maximum separation between the power supply cable  
24. ey  must be in EMC shielded metal boxes    9   Ground screw for the motor cable with low ratings  as the screw on the heatsink is inaccessible           N    Note       If an additional input filter is used  it is mounted on the speed controller  and connected directly to the  line supply by an unshielded cable  Connection 3 on the speed controller is then made using the filter  output cable      Although there is an HF equipotential ground connection between the speed controller  the motor and  the cable shielding  it is still necessary to connect the PE protective conductors  green yellow  to the  appropriate terminals on each of the devices        63       ENGLISH    ENGLISH    Basic Functions       Fault relay  unlocking    The fault relay is energized when the speed controller is powered up and there is no fault  It has a  common point C O contact     The speed controller is unlocked after a fault by the following operations      Powering down the speed controller until the display and the red LED extinguish  then powering up  again      Automatically when the  automatic restart  function has been activated    Via a logic input when this input is assigned to the  fault reset  function    Speed controller thermal protection    Functions    Thermal protection by thermistor fitted on the heatsink or integrated in the power module     Indirect protection of the speed controller against overloads by current limit  Typical tripping points        motor current   185   of nomina
25. he screen   the speed controller locks and fault  relay R1 is tripped     ENGLISH    Clearing faults   Switch off the speed controller power supply in the event of a fault which cannot be reset   Wait for the LED and the display to go off completely    Find the cause of the fault in order to correct it    Restore the power supply   this will clear the fault if it has disappeared     In some cases there may be an automatic restart after the fault has disappeared if this function has been  programmed     Display menu      This is used to prevent and find the causes of faults by displaying the speed controller status and its  current values     Spares and repairs      Consult Schneider Electric product support        89    ENGLISH    Faults   Causes   Remedies       Speed coniroller does not start  no fault displayed    e The assignment of the  Fast stop  or  Freewheel stop  functions will prevent the controller from starting  if the corresponding logic inputs are not powered up  The ATV 28 then displays  nSt  in freewheel stop  mode and  FSt  in fast stop mode  This is normal since these functions are active at zero so that the  controller will be stopped safely if there is a wire break      On power up or a manual fault reset or after a stop command  the motor can only be powered once the   forward    reverse  and  DC injection stop  commands have been reset  If they have not been reset  the  speed controller will display  rdY  but will not start  If the automatic restart func
26. is memorized until the stop input is opened    On power up or a manual fault reset or after a stop command  the motor can only be powered once the   forward    reverse  and  DC injection stop  commands have been reset     Ramp switching   ist ramp   ACC  DEC   2nd ramp   AC2  DE2  This can be activated in 2 ways      By activating a logic input Llx or by detection of an adjustable frequency threshold Frt     Step by step operation  JOG   Low speed operation pulse   If the JOG contact is closed  then the operating direction contact activated  the ramp is 0 1 s whatever  the ACC  dEC  AC2 and dE2 settings  If the operating direction contact is closed  then the JOG contact  activated  the configured ramps are used     The minimum time between 2 JOG operations is 0 5 seconds  Parameter which can be accessed in the adjust menu      JOG speed       65       ENGLISH    ENGLISH    Configurable I O Application Functions       Preset speeds  2  4 or 8 speeds can be preset  and requiring 1  2  or 3 logic inputs respectively     The following assignment order must be observed   PS2  LIx   then PS4  Lly   then PS8  Llz               2 preset speeds 4 preset speeds 8 preset speeds  Assign   LIx to PS2 Assign   LIx to PS2  then Lly to PS4   Assign   LIx to PS2  then  Lly to PS4  then LIz to PS8  Lix_ speed reference Lly  Llx  speed reference Liz  Lly  LIx  speed reference  O  Reference min LSP   0  O  Reference  min LSP       O  O  Reference  min   LSP   1 HSP 0 1 SP2 o 10 1 SP2  1  0  SP3 
27. l speed controller current   2 seconds    motor current   maximum speed controller transient current   60 seconds     Speed controller ventilation    The fan is powered automatically when the speed controller is unlocked  operating direction    reference   It is powered down a few seconds after the speed controller is locked  motor speed  lt  0 5 Hz  and injection braking completed      Motor thermal protection    Function    Thermal protection by calculating  2       Caution   The motor thermal state memory is reset to zero when the speed controller is switched off        64    Configurable I O Application Functions       Logic input application functions    Direction of operation   forward   reverse  Reverse operation can be disabled for applications with a single direction of motor rotation     2 wire control     Run  forward or reverse  and stop are controlled by the same logic input  for which state 1  run  or 0   stop  is taken into account    On power up or a manual fault reset or after a stop command  the motor can only be powered once the   forward    reverse  and  DC injection stop  commands have been reset  If the automatic restart function  is configured  parameter Atr in the drC menu   these commands are taken into account without a reset  being necessary     3 wire control     Run  forward or reverse  and stop are controlled by 2 different logic inputs    LI1 is always assigned to the stop function  Stop occurs on opening  state 0     The pulse on the run input 
28. line supply  and the motor cable     Installation diagram             62    Wiring       1   Sheet steel grounded casing supplied with the speed controller  to be fitted as indicated on the  diagram    2   Altivar 28   3   Non shielded power supply wires or cables    4   Non shielded wires for the output of the safety relay contacts    5   Attachment and connection to ground of the shielding of cables 6  7 and 8 as close as possible to the   speed controller       strip the shielding     Use cable clamps of an appropriate size on the parts from which the shielding has been stripped    to attach them to the casing 1    The shielding must be clamped onto the casing sufficiently tightly to create a good contact      types of clamp   stainless steel    Shielded cable for connecting the motor  with shielding connected to ground at both ends    This shielding must be unbroken  and if there are intermediate terminals  they must be in EMC   shielded metal boxes    Shielded cable for connecting the control    For applications which require a large number of conductors  small cross sections must be used    0 5 mm      The shielding must be connected to ground at both ends  This shielding must be unbroken  and if   there are intermediate terminals  they must be in EMC shielded metal boxes    8   Shielded cable for connecting the braking resistor  if used  The shielding must be connected to  ground at both ends  This shielding must be unbroken  and if there are intermediate terminals  th
29. ly   50 Hz     Motor voltage   230V or 400V  depending on product    Ramps   3 seconds    Low speed   0 Hz    High speed   50 Hz     Frequency loop gain   standard    Motor thermal current   nominal speed controller current    Standstill injection braking current   0 7 x nominal speed controller current  for 0 5 seconds    Constant torque operation  with sensorless flux vector control    Automatic adaptation of the deceleration ramp in the event of overvoltage on braking    Switching frequency 4 kHz    Logic inputs    e LI1  LI2   2 directions of operation  2 wire control     LI3  LI4   4 preset speeds  0       10 Hz  15 Hz  50 Hz     Analog inputs    e Al1  0   10 V    speed reference        2  0   10 V  or AIC  0  20 mA    summing     1    Relay R2      speed reference reached    Analog output AO  0   20 mA     e motor frequency       ENGLISH    If the above values are compatible with the application  the speed controller can be used without  changing the settings     Labels    The speed controller is supplied with labels which are stored under the hinged cover    e 1 label fixed inside the hinged cover   wiring diagram    3 self adhesive labels to be fixed near the speed controller if required   programming of the  main parameters  meaning of the fault codes and customer settings  blank label         51    ENGLISH    Speed Controller References       Single phase supply voltage  1  U1   U2   200   240 V 50 60 Hz                                                              
30. m switching frequency of 4 kHz  in continuous operation  The  switching frequency is adjustable from 2 to 15 kHz    Above 4 kHz derate the nominal speed controller current  The nominal motor current should not exceed  this value     e Up to 12 kHz derate by 10      Above 12 kHz derate by 20       3  Typical value for a 4 pole motor and a maximum switching frequency of 4 kHz  with no additional line  choke         4  For 60 seconds     ENGLISH       53    ENGLISH    Mounting       Dimensions and weights                                                                                           29 49                                          l  l 0000   0000                 x            y       Y  Lo e   G   it            it  la El a y   ATV 28H a b c G H 20 4   weight  mm mm mm mm mm mm m kg  U09M2  U18M2 105 130 140 93 118 5 1 8  U29M2  U18N4  U29N4 130 150 150 118 138 5 25  U41M2  U54M2  U72M2  U41N4  U54N4 U72N4 140 195 163 126 182 5 9 8  U90M2  D12M2  U90N4  D12N4 200 270 170 180 255 6 6 1  D16N4  D23N4 245 330 19 225 315 6 9 6       Mounting recommendations    Install the unit vertically  at   10       Do not place it close to heating elements     Leave sufficient free space to ensure that the air required for cooling purposes can circulate from the    bottom to the top of the unit        54    Mounting       Mounting and Temperature Conditions       E    l    N  LS E Free space in front of the unit   10 mm minimum   IX            from  10  C to 40  C    d  gt  50 mm  no spe
31. mented using    A Y  and confirmed with  ENT      e If the correct access code is displayed  it flashes  and code 0 can then be configured in order to access  the menus    e If an incorrect code is displayed  the speed controller returns to the initial display  rdY                  87    Settings       ENGLISH       Display menu 5 LU P     continued              Code   Parameter                Display of speed controller status   the operating phase of the motor or a fault     Init   Initialization sequence     rdY   Speed controller ready     43 0   Display of the frequency reference     dcb   DC injection braking in progress     rtrY   Automatic restart in progress     nSt   Freewheel stop command     FSt   Fast stop command                   88    Maintenance       Servicing    The Altivar 28 does not require any preventative maintenance  It is nevertheless advisable to carry out  the following operations regularly      Check the condition and tightness of connections     Check that the temperature around the unit remains at an acceptable level and that the  ventilation is effective  average service life of fans   3 to 5 years depending on operating  conditions      Remove any dust from the speed controller     Assistance with maintenance       Ifthere is a problem when starting up or during operation  firstly check that the recommendations relating  to the environment  mounting and connections have been followed     The first fault detected is memorized and displayed on t
32. n power switching via line contactor      Avoid operating contactor KM1 frequently  premature ageing of the filter capacitors    A Use inputs LI1 to LI4 to control the speed controller      These instructions are vital for cycles  lt  60 s  otherwise the load resistor may be   damaged        User adjustment and extension of functions    ENGLISH    If necessary  the display and the buttons can be used to modify the settings and to extend the functions  described in the following pages  It is very easy to return to the factory settings    There are three types of parameter       display   values displayed by the speed controller     adjustment   can be changed during operation or when stopped     configuration   can only be modified when stopped and no braking is taking place  Can be displayed  during operation     A Check that changes to the current operating settings do not present any danger   Changes should preferably be made with the speed controller stopped        71    ENGLISH    Programming       Functions of the keys and the display  Altivar 28  E retemecanique  o  SQUARE D    e Red LED   powered up    4 seven segment displays     DC bus voltage         e Enters a menu or a  parameter  or saves the  displayed parameter or  value      Returns to the previous  menu or parameter  or  increases the displayed  value       Goes to the next menu or parameter  or   Exits a menu or parameter  or aborts the  decreases the displayed value displayed value to return to the previous
33. nput  The speed reference  is given by Al1 or by the PI function  depending on the state of the logic input        68    Configurable I O Application Functions       R2 relay application functions    Frequency threshold reached  FtA    The relay contact is closed if the motor frequency is greater than or  equal to the frequency threshold set by Ftd in the adjust menu     Speed reference reached  SrA    The relay contact is closed if the motor frequency is greater than or equal  to the speed reference value     Current threshold reached  CtA    The relay contact is closed if the motor current is greater than or equal  to the current threshold set by Ctd in the adjust menu     Thermal state reached  tSA    The relay contact is closed if the motor thermal state is greater than or equal  to the thermal state threshold set by ttd in the adjust menu     Analog output AO application functions  Analog output AO is a current output  which can be configured for 0   20 mA or 4   20 mA     Motor current  code OCr    supplies the image of the motor rms current   20 mA corresponds to twice the nominal motor thermal current Ith     Motor frequency  code rFr    supplies the motor frequency calculated by the speed controller   20 mA corresponds to the maximum frequency  parameter tFr      Motor torque  code OLO    supplies the image of the motor torque as an absolute value   20 mA corresponds to twice the nominal motor torque  typical value      Power  code OPr    supplies the image of the po
34. nted on the door of the wall mounted or floor standing enclosure  It has a cable  with connectors  which is connected to the speed controller serial link  see the manual supplied with  the display module   It has the same display and the same programming buttons as the Altivar 28 with  the addition of a switch to lock access to the menus and three buttons for controlling the speed controller         FWD RV   reversal of the direction of rotation     RUN   motor run command     STOP RESET   motor stop command or fault reset  The first press on the button stops the motor  and if DC injection standstill braking  is configured  a second press stops this braking        View of the front panel   View of the rear panel      H H 4 character  display           Y  D O Connector             ENGLISH                      Access switch       position a  settings and configuration not accessible     position A   settings accessible     position o   settings and configuration accessible          75    ENGLISH    Configuration            assignment menu     O                  The parameters can only be modified when the speed controller is stopped and locked   The functions are defined in the section  Configurable I O Application Functions               Code  Assignment Factory  setting    ECC  Configuration of terminal block control   2 wire or 3 wire control  20    20   2 wire  3C    wire  OPt   presence of the local control option  operation is then identical  to 3 wire control     2 wire 
35. ntroller model    ATV28    M2 200 to 240V  230 V  ATV28    N4 380 to 500 V  400 V if  bFr   50  460 V if  bFr   60   F r 5  Nominal motor frequency marked on the rating plate  40 to 400 Hz  50   60Hz  acc  to bFr       Un   Auto tuning no donE YES   no  Only active for V F ratios   n and nLd  Uft parameter     no    factory parameters of standard IEC motors     donE  auto tuning already done    use the parameters of the auto tune  which has already been done    YES   starts auto tuning  When autotuning is completed  rdY is displayed  On returning to tUn  donE  is displayed  If the fault inF appears  check that the motor is connected  correctly  If the connection is correct  the motor is not suitable   use the L or  the P ratio  Uft parameter    Caution   Auto tuning operation will only be performed if no command has  been activated  If a  freewheel  or  fast stop  function is assigned to a logic  input  this input must be set to 1  active at 0     E F r  Maximum output frequency 40 to 400 Hz  60 72 Hz   1 2 x bFr           80    Configuration          Drive menu dr C    continued                 Code    Assignment    Adjustment  range    Factory  setting        UFE    Selection of the type of voltage   frequency ratio     L   constant torque for motors connected in parallel or special motors    P   variable torque     n   sensorless flux vector control for constant torque applications     nLd   energy saving  for variable torque applications    L P n nLd    n        brHA    A
36. r           91       ENGLISH    ENGLISH    Configuration Settings Tables       Sp  ed Controller           A ici  Optional customer identification no    a  Software version  CPU parameter in the SUP Menu              eeeeeeeeteeeeeeseeeeeeeeeeeeeeeeeeeeetaeseeeetetaeaseeeeeeeaeeteee  Optionaliaccess code ici                                Local control option noO yes O          Menu     O     inputs outputs     Code Factory setting Customer setting a setting Customer setting                                           Menu      C     drive   Factory setting Customer  e Factory aa Customer i                                            92    Configuration Settings Tables                Menu 5E E      settings     Customer setting Code Factory setting Customer setting                                              ENGLISH                            The parameters in shaded boxes appear if the corresponding functions have been configured in  the drC  or   O  menus                 93    VVDED399062 W9 1494190 01 11 A01    27402 1999 11       
37. sidered as a component   it is neither a machine nor a device ready for use  in accordance with European directives  machinery directive and electromagnetic compatibility  directive   It is the responsibility of the end user to ensure that the machine meets these standards        48    Table of Contents                            Steps for Setting Up the Speed Controller 50  Factory Configuration 51  Speed Controller References 52  Mounting 54  Wiring     57  Basic Functions 64  Configurable I O Application Functions 65  Setup   Preliminary Recommendations 71  Programming 72 55  Local control option 74 z  Remote Display Module Option 75        5    Configuration       Settings 84  Maintenance 89  Faults   Causes   Remedies 90  Configuration Settings Tables 92          49    ENGLISH    Steps for Setting Up the Speed Controller       1   Delivery of the speed controller   e Check that the speed controller reference printed on the label is the same as that on the delivery note  corresponding to the purchase order      Remove the Altivar 28 from its packaging and check that it has not been damaged in transit    2   Fit the speed controller and attach its labels  page 51     3   Connect the following to the speed controller     e The line supply  ensuring that it is volt free   e The motor  ensuring that the terminal configuration corresponds to the supply voltage   e The control via the logic inputs   e The speed reference via the logic or analog inputs   4   Switch on the speed 
38. start is performed by a  series of automatic attempts separated by increasingly longer waiting  periods   1 s  5 s  10 s  then 1 min for the following attempts  If the restart has  not taken place after 6 min  the procedure is aborted and the speed  controller remains locked until it is powered down then powered up  The  following faults permit this function   OHF  OLF  USF  ObF  OSF  PHF  OPF   SLF  The speed controller fault relay remains activated if this function is  active  The speed reference and the operating direction must be maintained   This function can only be used in 2 wire control  tCC   20     Check that any accidental start does not present any danger to   A personnel or equipment      no   Function inactive     YES   Function active     USF   Function only active for the USF fault    no   YES    USF    no        OPL    Enables the motor phase failure fault     Inhibition of the fault if a switch is used between the speed controller and  the motor   no     no   function inactive  YES   function active     no   YES    YES         IPL    Enables the line supply phase failure fault    no   function inactive  YES   function active    This parameter does not exist on the ATV28HU09M2  U18M2  U29M2 and  U41M2 for a single phase line supply    The fault is only detected if the motor is on load  around 0 7 times the  nominal power   At low load  single phase operation does not cause  damage        no   YES    YES       SEP       Controlled stop on loss of line supply  
39. till braking time 0to 25 4 s 055  If the time is increased to 25 5 5   Cont  is displayed  The DC injection is then   Cont   continuous at standstill     JPF   Skip frequency prevents prolonged operation at a frequency range of 2Hz  0 to HSP 0 Hz  around JPF  This function prevents a critical speed which leads to resonance   Setting the function to 0 renders it inactive        ENGLISH                           JOG   Jog operating frequency 0 to 10 Hz 10 Hz   r PL   Pl regulator proportional gain 0 0119 100   1    r IG        regulator integral gain 0 01 to 100 s 1 s    F b 8   PI feedback multiplication coefficient 0 1 to 100 1    P        Reversal of the direction of correction of the PI regulator   no   YES no          no   normal  YES   reverse        1  In is the nominal speed controller current shown in the catalogue and on the speed controller rating  plate        The parameters in shaded boxes appear if the corresponding functions have been configured  in the drC  or l O  menus                 85    ENGLISH    Settings          Adjust menu 5         continued                                                        Code   Assignment Adjustment   Factory   range setting    5      2 0 preset speed LSP to HSP  10 Hz    5P3 3  preset speed LSP to HSP  15 Hz    5P4 4    preset speed LSP to HSP  20 Hz    5P5 5  preset speed LSP to HSP  25 Hz    5PB  6  preset speed LSP to HSP  30 Hz    5P7 7  preset speed LSP to HSP  35 Hz     FE d   Motor frequency threshold beyond which the 
40. tion      1E H   Current used for the motor thermal protection  Set      to the nominal current   0 50 to 1 15  In  1   marked on the motor rating plate  In  1   To disable thermal protection  increase the value to the maximum  ntH  displayed      1  In is the nominal speed controller current shown in the catalogue and on the speed controller rating plate        in the drC  or        menus     The parameters in shaded boxes appear if the corresponding functions have been configured       84    Settings          Adjust menu 5 E E     continued                          Code  Assignment Adjustment   Factory  range setting   UF r   Optimizes the torque at very low speed 0to100   20    5L P   Adjusts the slip compensation around the value set by the nominal motor  0 0 to 5 0 Hz   According  speed  This parameter only appears if parameter UFt   n in the drC  menu  to controller  output    F LG   Frequency loop gain 0to100   33    Linked to the inertia and the resistive torque of the driven mechanism       machines with high resistive torque or high inertia   gradually reduce the  gain in the range 33 to 0     machines with fast cycles  low resistive torque and low inertia   gradually  increase the gain in the range 33 to 100  Too high a gain may result in  operating instability      Id   Level of DC injection braking current 0 1 ItH to 0 7 In  1   After 5 seconds the injection current is peak limited at 0 5 Ith if it is set at a   In  1   higher value     E dE   DC injection stands
41. tion is configured   parameter Atr in the drC menu   these commands are taken into account without a reset being    necessary     Faults which cannot be reset automatically    The cause of the fault must be corrected before resetting by powering down and then powering up                 internal fault    Fault Probable cause Remedy   OCF   ramp too short   Check the settings   overcurrent   inertia or load too high   Check the motor speed controller load sizing     mechanical blocking   Check the state of the mechanism    SCF   short circuit or earthing at the   Check the cables connecting the speed controller to  motor short circuit   speed controller output the motor  and the insulation of the motor     InF   internal fault   Check the environment  electromagnetic    compatibility       Check that the  local control  option has not been  connected or disconnected with the controller powered  up      Send the speed controller to be checked repaired         EnF  auto tuning fault      special motor or motor whose  power is not suitable for the speed  controller      Use the L or the P ratio         EEF  internal fault            internal fault         Send the speed controller to be checked repaired           90    Faults   Causes   Remedies       Faults which can be reset with the automatic restart function  after the  cause has disappeared           DLF  motor overload      tripped by I t motor being too high    Fault Probable cause Remedy    OHF   Ft too high or   Check th
42. wer supplied to the motor by the speed controller   20 mA corresponds to twice the nominal speed controller power        69       ENGLISH    ENGLISH    Configurable I O Application Functions       Function compatibility table  The choice of application functions may be limited by the number of I O and by the fact that some  functions are incompatible with one another  Functions which are not listed in this table are fully    compatible                                o      5 c lo      Q  2   8 2 O  5      1 5  3 E 8  D         D     228 53     2      e 1  Sx E    2   a 2  o jE     8 18  e B  8          la je je E   fa  DC injection braking 1  Summing input 9 19  PI regulator 9 99  Reference switching 9 9  Freewheel stop e    Fast stop 1  JOG operation 9 E  Preset speeds 9 19 1                                  O  Incompatible functions       Compatible functions  N A          Priority functions  functions which cannot be active at the same time           lft The function marked with the arrow takes priority over the other                 Stop functions take priority over run commands   Speed references via logic command take priority over analog references        70    Setup   Preliminary Recommendations       Prior to powering up and configuring the speed controller      Power down the logic inputs  state 0  to prevent any accidental startup  Otherwise   A an input assigned to the run command may cause the motor to start immediately when  exiting the configuration menus     I
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
manuel d`utilisation chauffage d`appoint infrarouge  USER`S MANUAL  impianticondizionamento/scheda FLATPANELR  Sony BDV-E570 Marketing Specifications  Storage Options Scroll Excel II Operating Instructions  「デッキ」施工・取扱説明書  Accepte-Toi - Joyce Meyer FR    Copyright © All rights reserved. 
   Failed to retrieve file