         Contents
1.                      12    General    Upon receipt of the unit  verify that the catalog number and unit  options stated on the shipping container match those stated on  the order purchase form     Inspect the equipment upon delivery  Report any carton damage  to the carrier prior to accepting the delivery  Have this  information noted on the freight bill  Johnson Controls is not  responsible for damage incurred in shipping     Unpacking    Remove all packing material from the unit  Be sure to remove all  packing material from lug location  Also  make sure no packing  material is left behind that would block the airflow to the fan     Check the unit for any signs of shipping damage  If damage to  the product is found after unpacking  report it to the freight  company  Retain the packing materials for the carrier to review     Storage    It is recommended that the unit be stored in its original shipping  box crate until it is to be installed     The unit should be stored in a location where       The ambient temperature is between  40  F and 158  F    40  C and 70  C       The relative humidity is between 0  and 95    non condensing      The environment is dry  clean  and non corrosive      The unit will not be subjected to high shock or vibration  conditions    Mandatory Ground Wiring  See Appendix D on Page 18     Be sure to pull low impendance ground wiring from customer  power to drive and ground wire from drive to motor     Motor Ground   Inside Motor Conduit Box     Utili
2.       D1 3 Run Permisive  Step 2  Static check drive SCR  IGBT  DC Bus per Static Check  Damper Interlock    Page 20 and 21    Default     Step 3  Start up Wizard  Remote Input Application  24 Vdc Control    Step  4  Set Interlock Start P1 2 1  Programmable Options   0  Normal start with Interlock    1  Interlock start from one D1 2    D1 6  D1 3 Default  Damper Actuator OPTA2 Slot B    2  Interlock start and timeout supervision  If feedback is Input Terminals  not given in timeout request  the unit will not start     3  Delay start from Run command Closes on Run     Default        ks i i     Note Interlock damper controller works in drive or bypass 8 A 24 Vde  Step 5  Select Hand to test motor rotation  8 A 125 Vac         4 A 250 Vac  Step 6  To verify proper motor rotation  press start and to    increase speed in Hand mode  D1 3 Default     Step 7  To run in Remote Auto mode  run Remote Auto      Hit stop    Hit twice  enter    Send START Signal from Field Controller to start drive        Figure 12  Programming Example    16 For more information visit  www johnsoncontrols com LIT 1201858    Johnson Jj    Controls Powered by Eaton s Technology VSD Series Quick Start Guide    November 2009    Appendix C     Interlock Damper Start Example  Interlock Damper Start Example Using PID Duct Static Control Signal    Max WC   2 5             Slot A    Main WC   0 0  Actual  Setpt WC   2 0       12 To Drive Damper    Interlock Terminals A1 1  0    10           A1 1  Default    Set PT 
3.      This should read  OL ohms     6 Pulse Diode Mai Inverter Section  Bridge Rectifier ain  Converter Section Contactor     B   DC      Bus Dynamic Braking Output Transistors  Capacitors Transistor IGBT Section       Figure 25  Schematic for Static Checks  Sample for Frames 4 and 5     26 For more information visit  www johnsoncontrols com LIT 1201858    Johnson A i    Controls VSD Series Quick Start Guide    Powered by Eaton s Technology    November 2009    Appendix       Fault and Warning Codes    Table 10  Fault and Warning Codes Solutions    Fault  Code Fault pM Cause      in its   Check loading     Overcurrent lumens delete fa NORENIFER EI ne Series drive has detected    high current  24xl    output due to     sudden heavy load increase    short in the motor    short in the cables to the motor    unsuitable motor    Check motor   Check cables     Make the deceleration time longer    Use brake chopper and brake resistor  standard on some  models  available as options on others     Correct utility supply voltage  level is too high         Overvoltage The DC link voltage has exceeded its high limit due to     too short a deceleration time    high voltage levels or surges in the utility supply    Ground  Earth  Fault Current sensing indicates that the sum of motor phase  currents is not zero         insulation failure in motor or motor cables    5 Charging Switch The charging switch was open  when the START  command was given due to     faulty operation      component failu
4.     Decrease the motor load     If no motor overload exists  check the temperature model  parameters     Check the motor  check for a loose belt  broken coupling  or load problems     Confirm underload parameter settings     Upon reset of this fault  the VSD Series drive will  automatically reload the parameter default settings   Check all parameter settings after reset  If the fault  reoccurs  contact your Johnson Controls distributor        2b Microprocessor watchdog   faulty operation Reset the fault and restart  If the fault reoccurs  contact  fault   component failure your Johnson Controls distributor     LIT 1201858    For more information visit  www johnsoncontrols com 27    Appendix       Fault and Warning Codes  continued    Table 10  Fault and Warning Codes Solutions  continued     Fault  Code Possible Cause          Start up prevented Start up of the drive has been prevented  Check Start Enable Interlock settings   29    Thermistor fault    The thermistor input of an option board has detected a Check the motor cooling and the motor loading   high motor temperature Check the thermistor connection      If the thermistor input of an option board is not being  used  it must be short circuited         31 IGBT temperature hardware   IGBT Inverter Bridge overtemperature protection has Check loading   detected high short term overload current Check motor size   32 Fan cooling The VSD Series cooling fan did not start when Contact your Johnson Controls distributor   commande
5.    50 hp NEMA Type 3R  480V AC Variable    Frequency Drive     Contactor Overload   behind drive cover    si    24V DC Motor Overload  Terminal Block    Optional 3rd Contactor S1 Switch     Motor Ground Stud   provided for drive isolation        Figure 7  Identification of NEMA Type 12 and NEMA Type 3R Components    Note  You will need to consult the electrical schematic supplied with the drive and the appropriate wiring diagram in Appendix D     Table 4  VSD Series NEMA Type 12 Enclosed IntelliPass Drive Table 5  VSD Series NEMA Type 3R Enclosed IntelliPass Drive  Dimensions Dimensions    Drive Enclosure Approximate Dimensions in Drive Enclosure Approximate Dimensions in  Horsepower  VT  Box Inches  mm  Horsepower  VT  Box Inches  mm         B je       B je      208V  1  15 hp            FR6    16 92 29 00 18 60 208V  1     15 hp            FR6    21 05 33 00 19 57  230V  1     15 hp     4   FR6  429 8   736 6   472 4  230V  1  15 hp  534 7   838 2   497 0   480V  1     30 hp            FR6 480V  1   30 hp   575V  3 30 hp FR6 575V  3 30 hp   208V  20   30 hp FR6   FR7 2092  4000   19 10 o E              cu fee  ons  230V  20   30 hp  531 3   1016 0     485 1  p    480V  40     75 hp 480V  40     75 hp   575V  40   50 hp 575V  40     50 hp   208V  40     60 hp FR8 C 30 92 52 00 19 10 208V  40     60 hp FR8 C 37 73 58 09 20 08  230V  40     60 hp  785 3   1320 8     485 1  230V  40   60 hp  958 3   1475 5     510 0   480V  100     150 hp 480V  100     150 hp       Floor Stands
6.    P1 10 7 Preset Speed 7       Figure 20  Parameter Menu Structure Example    Figure 19  Main Menu Navigation    20 For more information visit  www johnsoncontrols com LIT 1201858    Johnson          Controls Powered by Eaton s Technology VSD Series Quick Start Guide    November 2009    Appendix G     Start Up Wizard  Start Up Wizard    Duct Static  Building Static  Pressure Control  Temperature Control  Generic PI    Upon initial power up  the Start Up Wizard guides the commissioner through the basic VSD Series setup   The Start Up Wizard may be set to function upon power up by setting parameter P5 5 3  or by pressing the  STOP RESET button for 5 seconds while in the  Operate Menu   The display will read  Start Up Wizard  Activate   after 5b seconds                UP WIZARD Start of the Start Up Wizard    PRESS ENTER       LANGUAGE Language selection      enter J    APPLICATION  5  Duct  Building  Pressure  Temperature  Generic PI  REMOTE INPUT  D    enter oJ  SETUP STARTS By pressing setup will start  PRESS ENTER By pressing the setup will be stopped    ENGLISH    U5  METRIC UNITS US Metric units are used only in Duct   us Building  Pressure and Temperature applications       enter oJ    MOTOR NP CURRENT Motor Name Plate current in Amps  XX X A   Default will vary depending    enter oJ    on drive size  MOTOR NP VOLTAGE  XXX V    XX X A    Motor Name Plate voltage in Volts  XXX V   Default is same as drive nominal  voltage    enter J    Continued       Figure 21  Start Up 
7.   Johnson H    VSD Series Quick Start Guide Controls    Powered by Eaton s Technology    November 2009    Appendix F     Main Menu Navigation    Main Menu Navigation Parameter Menu Structure Example    C9       M1 Programming M1 Programming Menu    G1 1 See Figure 3     Menu Navigation     Up Arrow    The up arrow advances  to the next menu item   For example  pressing the  up arrow once will  advance from M1 to M2     Down Arrow    The down arrow backs up to  the previous menu item   For example  pressing the  down arrow once will back  up from M2 to M1     Right Arrow    The right arrow will advance  to the next level in the menu   For example  pressing the  right arrow once will  advance from M2 to R2 1     Left Arrow    The left arrow will back up   one level in the menu structure   For example  pressing the   left arrow once will back   up from R2 1 to M2     G1x  M2 Keypad Control  R2 1 Keypad Reference    P2 x Stop Button Active    M3 Active Faults  A3 1 Active Fault 1        Operation Days  13 1 13 Zero Speed  A3 x Active Fault x    M4 Fault History  H4 1 Most Recent Fault    LE Operation Days  T4 1 13 Zero Speed  H4 1 x Oldest Saved Fault    M5 System Menu  55 1 Language   5 2 Application   5 3 Copy Parameters  55 4 Compare Parameters   5 5 Security  55 6 Keypad Settings   5 7 Hardware Settings  55 8 System Information    6 Expander Boards  G6 1 Slot A Board    G6 5 Slot E Board    M7 Mlonitor  V7 1 Actual Speed  V7 2 Output Frequency  V7 3 Speed Setpoint  V7 4 Motor
8.   Use a flat blade screwdriver to carefully remove the low   voltage 1 0 terminal block     21  Reinsert the I O terminal block into the control board     22  Terminate control wiring to the OPTA9 and OPTA2 board   Terminals 1     26      Note  Use 1 8  flat blade     A CAUTION    e Run 110 Vac and 24        control wiring in separate conduit     Communication wire to be shielded         RS 232 keypad cable must be less then 25 feet  to prevent  nuisance trips      Optional Spacer Heater    Drive Motor  Ground Ground    F  Bypass E      Contactor Starter              4      P     111 Overload  Coralie   312 MERE    3L3 Reset     Reference Output  Analog Input Voltage   Range 0   10V DC   Customer         Ground  Ground i Analog Input Current  i  Range 4 20 mA   2 Control Voltage Output            Ground  Start Stop  External Fault  Reversing Run Permisive Damper Interlock  Starter DIN1  DIN3 Common  OPTB5 Relay Control Voltage Output   Slot C       Ground    RY1  Drive Run  14 Speed Select 1     Fire Mode      Bypass Overload Fault               DIN6 Common xs  i Output Frequency    RY2  Bypass     Analog Output  I     I     I       2 26 Digital Output Ready  26 OPTA2 Slot B    Relay Output 1  RY3  OL1 Reset    p Pp       in Note  See Figure 3  5 Relay Output 2 for Dip X1  X2          Faul X3  X6 Switch    OPTB5 Slot C  Drive Run settings       Ec  Drive Power   terminals  Off On 7          factory    2 Bypass  connections     Located Inside OL1 Reset    Door Cover     NIIN N
9.   ui Bur qe  uNY       920N uonoeuuo   1030 A  S920N uonoeuuo  JAMO          2                    SNINOONI    Figure 16     LIT 1201858    For more information visit  www johnsoncontrols com    18    Johnson          Controls Powered by Eaton s Technology VSD Series Quick Start Guide    November 2009    Appendix E     Keypad Navigation  Keypad Navigation    run    D e     ready  ByPass Mode D  when flashing         O eG   e  O            Figure 17  Keypad and Display    One Touch Operate Menu Navigation    Note   Freq Ref Up HOA OFF MODE OR HAND MODE      Up and down arrows are used to  A adjust speed setpoint  Monitor Display Monitor Display HOA AUTO MODE  Navigation Left Navigation Right e Up and down arrows are used to    adjust Pl Setpoint    Freq Ref Down         Password   Programming Menu      Note    While in Programming  M1 Parameters Menu the display will  automatically return to  default Operate Menu  display after 1 minute  M4 Fault History of inactivity   Time can  be adjusted with  Parameter P5 6 3      Exit Operate Menu by navigating   to Programming display and M2 Keypad Control  pressing ENTER button or simply M3 Active Faults   press ENTER button 1 second    Acknowledgement password  value if defined  M5 System Menu   M6 Expander Boards    M7 Monitor    Return to Operate or time delay         See User Manual  LIT 1201828  for complete parameter list     Figure 18  Operate Menu Navigation    LIT 1201858 For more information visit  www johnsoncontrols com 19  
10.  2 RMS    Analog Outputs Output Frequency  0 f max         0 20 mA Default          500     Resistor to be Added  for 0 10V DC    Applications    Remote Input  Duct Static  Building Static  Pressure Control  Temperature  Generic PI    Analog Input   0 10V DC Factory Default Source Auto    Com    4 20 mA Default  Setpoint Software Selectable  in Start Up Wizard            PI Feedback Pressure 0 10V DC Out  0 10V DC Transducer  Connection Com GND Com   Pressure  Transducer PI Feedback Sensor      Used for the following  24V DC Power CRBDICSHONS  Duct Static         PI Feedback Pressure Com GND  4 20 mA Pressure  Transducer Pressure    Transducer       Figure 10  Wiring Diagrams  Default     For more information visit  www johnsoncontrols com    Building Static  Pressure Control  Temperature  Generic Pl    Card is programmable for a 0     10V DC with change in jumper  Add X6 jumper on Board      from A B to C D     15    Johnson JJ    VSD Series Quick Start Guide Controls Powered by Eaton s Technology    November 2009    Appendix B     Interlock Damper Start Example    Interlock Damper Start Example Using 4     20 mA Control Signal    y    Field OPTA9 Slot A  Controller  To Drive Damper Terminals    Interlock Terminals    A1 2  Speed    A1 2  Ref    24 Vdc Control  Close Terminal   6     8  to start VFD       Figure 11  Interlock Damper Start Example with  Remote 4     20 mA Application    Step 1  Wire Load  Line  Digital In Out per example and verify    voltage and amperage    
11.  Common     Note  Optional Communication Cards can be  supplied with the Drive or as a Field Option     X2 Jumper Setting  Analog Input 2      2     Oto 20mA   ABCD     to 10V  ABC Current Input 2125      Voltage Input   e         0 to 10V  Voltage Input    0 to 10V   Differential     X1 Jumper Setting  Analog Input 1           ABCD    0to20mA  ABCD  Current Input        o    Figure 2     X6 Jumper Setting  Analog Output 1  A01     Powered by Eaton s Technology    0 to 10V   Differential   Voltage Input     10 to 10V  Voltage Input    ABCD    Voltage Input     10 to 10V Bu  Voltage Input   e e       Current    0to20mA     ABCD  Output HEHE  0 to 10V ABCD  Output   e  BK    Voltage    Es    X3 Jumper Setting  CMA and CMB Grounding    CMB Connected to Ground   CMA Connected to Ground      CMB Isolated from Ground       CMA Isolated from Ground    CMB and CMA Internally  5  Connected and Isolated    from Ground      Designates Default Jumper Settings    Figure 3  Option Board A9 Location and Settings    Start Up Wizard See Appendix G        For more information visit  www johnsoncontrols com    LIT 1201858    Johnson           Controls Powered by Eaton s Technology VSD Series Quick Start Guide    November 2009    NEMA Type 1 IntelliPass IntelliDisconnect Drive    b        Circuit Breaker Endplate    Circuit Breaker  Extension Bar    Circuit Breaker E 2v DC Power Supply      Ribbon    Cable Hinge        Optional 3rd Input Contactor      Output  amp  Bypass    Contactor   Contacto
12.  DO NOT RUN CONTROL WIRING in same conduit   with power wiring      Provide low impedance ground connection to drive   chassis        DO NOT CONNECT B   B   R terminal     Reserved for Braking Resistor only     7  Connect the incoming power leads to circuit breaker  terminals labeled L1  L2 and L3    8  Using the torque wrench  tighten each terminal to  the torque value found in the appropriate user s  manual supplied with the drive      Connect the power ground wire to the ground stud   Connect motor ground to ground stud     Setting Space Heater    10  If applicable  set the space heater  See the space heater  user s manual supplied with the drive  p     Note  The space heater is used to prevent condensation from LL  x  damaging the equipment when the drive is not operating Lie ed T   OFF      Space Heater  Temperature  Setting       LIT 1201858 For more information visit  www johnsoncontrols com 11    Johnson          VSD Series Quick Start Guide Controls    Enclosed NEMA Type 12 3R    Table 6  Bypass Power Wiring Instructions     NEMA Type 12 3R  continued   Motor Wiring    11  Use your first and second fingers and simultaneously  push down to release the two orange retaining clips  one  on each side of the 24V DC motor overload terminal  block      If necessary  use a flat blade screwdriver to carefully Bypass             Contactor  remove the terminal block in a straight plane to avoid Assembly  damaging it     Setting Motor Overload    13  Lift to open the cover on the
13.  Output  Analog Input Voltage   Range 0   10V DC          Ground   Analog Input Current   Range 4 20 mA    Control Voltage Output            Ground   Start Stop   External Fault   Run Permisive Damper Interlock  DIN1     DIN3 Common  Control Voltage Output       Ground   Speed Select 1   Fire Mode   Bypass Overload Fault    Output Frequency  Analog Output  Digital Output Ready       RE            RY3  OL 1 Reset        V    OPTA2 Slot B  Relay Output 1  Run    Relay Output 2  Fault       Contactor   Note  All 2     23  25      PTB5  Drive Power P      terminals  Off On 5 i   are factory  connections  LO oo    1   H   only  28  29    26   Located Inside 2  Door Cover                     OPTB5 Slot C  Drive Run    Output Contactor    Overload    Relay    Manual  Reset     See Figure 3  for Dip X1  X2   X3  X6 Switch  settings     OPTC2 Slot D or E   Shield     5V Supply Voltage    RxD TxD   Minus    RxD TxD   Plus    Bus Common     OPTC4 Slot 51  orE     Lonworks     23 OSHIELD   Shield    Note  Optional COMM cards can be supplied  with the drive or as a field option     Figure 6  VSD Series IntelliPass with Three Contactors       For more information visit  www johnsoncontrols com    LIT 1201858    Johnson Pi    Controls Powered by Eaton s Technology VSD Series Quick Start Guide    November 2009    NEMA Type 1 IntelliPass IntelliDisconnect Drive    able 3  Bypass Power Wiring Instructions     NEMA Type 1  continued   Static Check    27  Make sure power is off  and perform stat
14.  Pi  Controls    November 2009    Powered by Eaton s Technology VSD Series Quick Start Guide    NEMA Type 1 12 Open Drives  1   250 HP     Table 1  Control Wiring Instructions  continued   Power Wiring    If conduit is being used  attach the wiring plate to it     Pass the motor and input power wires cables through the  holes of the wiring plate     If shielded cable is used  connect the shields of the input  line power cable and the motor cable to the motor and  power ground terminals of the VSD Series drive     Power Wiring Grounding    7  Wire power terminals  motor terminals  and grounding  terminals per diagram  Power and Motor leads must be in  separate conduit     Note  Do not wire motor loads to B  B4 R   This will cause  damage     GROUND WIRING    Run motor cables in separate conduit   DO NOT RUN CONTROL WIRES in same conduit    Cables sized per NEC   Provide low impedance ground between drive and  motor     Utility Drive Motor Ground   Inside Motor Conduit Box     IMPORTANT  Improper grounding could result in damage to the  motor and or drive and could void warranty    Control Wiring    8  Wire the control terminals following the details for the  specific option boards shown on the following pages     Note  For ease of access  the option board terminal blocks can  be unplugged for wiring     Note  If using conduit or Seal Tite for control wiring for Frame  4  you must order NEMA Type 12 kit        ce          LIT 1201858 For more information visit  www johnsoncontr
15.  Speed  V7 5 Motor Current  V7 6 Motor Torque  V7 7 Motor Power  V7 8 Motor Voltage  V7 9 DC Bus Voltage  V7 10 Unit Temperature  V7 11 Motor Temperature  V7 12  A  Al 1  V7 13  A  Al 2  V7 14 DI 1 DI 2 DI 3  V7 15 DI 4 DI 5 DI 6  V7 16 DO 1 RO 1 RO 2  V7 17  A  AO 1  V7 18 ActFaultCode  V7 19 ActWarnCode  V7 20 Status Word  V7 21 Pl Setpoint  V7 22 Pl Input  V7 23                 V7 24 Pl Output  V7 25 RO 1 RO 2 RO 3  G7 26 Multimonitor    M8 Operate Mode  O1 Output Frequency  O2 Actual Speed    Ox Motor Temperature       G1 1 Quick Setup    P1 1 1 Minimum Frequency  P1 1 2 Maximum Frequency    P1 1 26 Pl Contr  I Time    G1 2 Input Signals  P1 2 1 Start Mode  P1 2 2 Intlk Timeout    ill    P1 2 15 Setpoint Scale Max    G1 3 Output Signals  P1 3 1  A  AO 1 Function  P1 3 2  A  AO 1 Filter    iji    P1 3 21 Start Relay OFF Delay    1 4 Drive Control   P1 4 1 Start Function  P1 4 2 Stop Function  P1 4 3 Brake Choppper    G1 5 Prohibit Frequency  P1 5 1 Range 1 Low Limit               P1 5 13 PH Acc Dec Ramp    1 6 Motor Control  P1 6 1 Motor Control Mode  P1 6 2 V Hz Optimization    iil    P1 6 12 Identification    G1 7 Protections  P1 7 1 Input Phase Supv  P1 7 2 4 mA Fault Response    ijl    P1 7 19 Automatic Restart    G1 8 Fieldbus  P1 8 1 FB Data Out 1  P1 8 2 FB Data Out 2         P1 8 8 FB Data Out 8    1 9 PI Control     P1 9 1 Setpoint Min  P1 9 2 Setpoint Max           1 9 14 Auto S Curve Time    1 10 Preset Speed  P1 10 1 Preset Speed 1  P1 10 2 Preset Speed 2      
16.  available on Box C only and can be purchased and shipped separately o    Stands available on        C only               be purchased        shipped separately  as kit  as kit        NEMA Type 12 NEMA Type 3R       Figure 8  VSD Series Enclosed Drive Dimensions    10 For more information visit  www johnsoncontrols com LIT 1201858    Johnson Jl  Controls    Powered by Eaton s Technology VSD Series Quick Start Guide    November 2009    Enclosed NEMA Type 12 3R    Table 6  Bypass Power Wiring Instructions     NEMA Type 12 3R    Mounting Drive  Keypad Cable Circuit Circuit    Mount driv r dimensions  Page 10  Breaker Breaker  SUE                   Extension Bar Set Screw      Verify that the main power source is removed upstream   Remove the keypad cable from the drive     Remove the screws from the drive cover  and remove the  cover     A CAUTION    The circuit breaker extension bar is sharp and can cause injury   5  Calibrate the circuit breaker amperage  so it is 1 25 times  the value on the motor nameplate  by turning the red set  screw located below the circuit breaker extension bar  See  the circuit breaker user s manual supplied with the drive     Power and Ground Wiring         ncoming ower    6  Using a Greenlee conduit cutter  recommended   cut three Power Leads Ground Wire  holes in the drive   s enclosure for the incoming power   motor and low voltage control leads     POWER WIRING    Note  Power  motor and control leads must each be  located in separate conduit     
17.  motor overload  and use a  1 8  flat blade screwdriver to set the overload amperage  to match the value on the motor nameplate     14  Turn the auto manual reset  factory default is manual  on  the motor overload 90  to the auto position     Motor Wiring    15  Connect the motor leads to the motor overload terminals  labeled 1TA  1     and 1TC     16  Using the appropriate metric Allen wrench  2 5 mm  3 mm  or 4 mm   tighten each overload terminal per the  specifications in the contactor user s manual     MOTOR WIRING    An SAE allen wrench will damage the terminals   and the motor overload will need to be replaced   not covered by warranty      17  Using the torque wrench  tighten each terminal to  the torque value found in the appropriate user s  manual supplied with the drive     18  Reinsert the motor overload terminal block   19  Connect the motor ground wire to the ground stud     Note         Run motor cables in separate conduit        Do not run control wires in same conduit     Size motor leads per NEC      Provide low impedance ground     12 For more information visit  www johnsoncontrols com    Powered by Eaton s Technology    November 2009    Orange  AM Retaining Clips    Auto Manual  Reset    Bypass  Contactor  Assembly       LIT 1201858    Johnson pi    Controls Powered by Eaton s Technology VSD Series Quick Start Guide    November 2009    Enclosed NEMA Type 12 3R    Table 6  Bypass Power Wiring Instructions     NEMA Type 12 3R  continued   Control Wiring    20
18. 9 1015  58140          11195 uowwo9 ENIG LNIC      ooj 1e1u  Jadweq                    UNY    M3luvis       YIUMS 9X    EX          jeep M     ZX    LX iq 404 T          ni 98S  9310N mee  ieu yu Bof  punoJ5 0 1 poc punoJr          A01 0             Jawojsny                        1ndu                                     DEC  MOIOVINOO                   ET WV                  NNSIS jeuondo jeuondo          p                 8      v LOIS  6  180      TEMA  1   771   f            u NM         13538  w  NVW  cid      AN T38                                NEM              walls    SINOWYVH GALNNOW             I                       1                           10              310W33M WNOLLdO            1             1             aa                 amp                          310W33    WNOLLdO MOLOVINOO    punojr punog    YALYVLS                  SJO Ioede    aseud     JOO           9 Buls 40 Buljesg                  10           aie                               pue 9sou    5               y     g     g 01199uu02 JON        u    m   g uonoouuo  PUNOIDH eouepeduyJ                        SISSeu               JAN Jed pezigs      01                   uonoeuuo  punoip eouepeduuJ                               Se qe  JAMO  JO             041002        ung                 JAN Jed pezig      01 sajqes      eJ    M  Se qe  10310 A JO         0431002 UUAA uny                  10 JINPUOZ  e1e N                    Ul se qe2  JOJO UNY                     10              jeza                
19. ING    High Voltage is present on L1  L2  L3  B   B   BT  T1  T2  T3     Starting Drive    26  Make sure that the drive s 3rd contactor S1 switch  if  present  is in the ON position  shown in OFF position      Note  The bypass mode operates with the switch in the OFF  position  however the drive will not run  Yet the keypad  will operate     27  Reinsert the keypad cable and control board on  small drives     Starting Drive    28  Close the drive door  and turn the circuit breaker handle in  a clockwise direction     29  Go to Appendix E for keypad operation     Note  If the circuit breaker latch is locked  use a flat blade  screwdriver to turn the screw to release the handle     A WARNING    High Voltage      Always work with another person     Be sure equipment is properly grounded     Wear safety glasses     Start Up Wizard See Appendix G        14 For more information visit  www johnsoncontrols com LIT 1201858    Johnson AJ    Controls    Powered by Eaton s Technology    November 2009    VSD Series Quick Start Guide    Appendix A     Main Control Board Wiring    Main Control Board Wiring Default in Slot A and B    Digital Input  24V DC    OPTA9 Slot A  Close Terminal  6 8     to Start VFD    Damper External Interlock       Control Relay    Outputs  22 21  Opens on Run  Default           2 Slot B    22 23  Closes on Run  Default   CR Ratings  8A  24V DC  24 25  Opens on Fault  Default   4A 125V DC  25 26  Closes on Fault  Default    8A 250V AC       Continuous Capacity  lt
20. ININ  13  53  2  218     Auxiliary contacts        customer  use rated 10 Amps at 600V AC aa                  5V Supply Voltage   Lonworks     R F       RxD TxD   Minus  peter  3   4  a    RxD TxD     Plus    Bus Common    OSHIELD   Shield  Motor Motor       On Inverter On Bypass Note  Optional COMM cards can be supplied    supplied with the drive or as a field option     Figure 9        LIT 1201858 For more information visit  www johnsoncontrols com 13    vos     VSD Series Quick Start Guide nn E    Powered by Eaton s Technology    November 2009    Enclosed NEMA Type 12 3R    Table 6  Bypass Power Wiring Instructions     NEMA Type 12 3R  continued   Static Check  High Voltage    23  Usea Phillips screwdriver to remove all the faceplate   n      Faceplate  screws on the high voltage faceplate  and remove the     faceplate     Note  Location of the screws may vary from the drive         E    j   Optional Bottom  illustrated  There may be screws securing a bottom faceplate  1      ary Faceplate  which also need to be removed        E NI    Static Check  L1  L2  L3 B   B   BT T1  T2  T3  24  Make sure power is off  and perform static checks as   FEN s   described in Table 7  for the converter   Table 8   E     for the inverter  and Table 9  for the DC bus   Refer to  Page 21  Appendix H     Note  Static check shown is for L3 and B  terminals     25  Once the pre power static checks are completed   reinstall the drive s outer and side covers  tightening  all the screws     A WARN
21. Johnson          Controls    Powered by Eaton s Technology    November 2009    VSD Series Quick Start Guide    VSD Series Quick Start Guide       n  E             EM  Li    ER   af               4    Open Drive Bypass Drive    IMPORTANT  This guide is intended to provide a quick reference to  the VSD Series drive s Application Software features for start up     programming and service  It does not replace the need to thoroughly  read and understand the User Manual        Table of Contents    Description Page  NEMA Type 1 12 Open Drives  1   250                      2  NEMA Type 1 IntelliPass IntelliDisconnect Drive           5  Enclosed NEMA Type 12 3R                            10  Appendix A     Main Control Board Wiring               15  Appendix B     Interlock Damper Start Example   Using 4   20 mA Control Signal                     16  Appendix C     Interlock Damper Start Example   Using PID Duct Static Control Signal                17  Appendix D     Bypass Wiring Diagram                  18  Appendix E     Keypad Navigation                      19  Appendix F     Main Menu Navigation                   20  Appendix G     Start Up Wizard                         21  Appendix        Static Checking                         25  Appendix       Fault and Warning Codes                  27    Technical Support Phone Numbers  Branch  800 281 3792  Option 1     Third Party  ABCS DIST   800 445 4757  Option 1     LIT 1201858    B Os               5         NEMA Type 3R           
22. Keypad Default    Error 24 Vdc Control  Power Close Terminal  Actual PI Feedback Pressure  618  to Start VFD    A1 1  0 10 Vdc Default    01 1       Figure 13  Interlock Damper Start with PID Duct Static Example mm  D1 3 Run Permisive    Damper Interlock    Step 1  Wire load line  digital 1 0 per example and verify l     Factory  Default     voltage and amperage LN s    Jumper    Step 2  Static check drive SCR  IGBT  DC Bus per Static Check   Page 20 and 21    24 Vdc Control Voltage    Step 3  Start up wizard  Duct static application       Closed  Step 4  Select hand to check motor rotation Run on  Step 5  Press Start and to increase speed in Hand mode poo  Step 6  Select Remote to run in Auto Damper Actuator 8    24          l Input Terminals  8 A 125 Vac  Step 7  Tune PID per diagram below A A 250 Vac    Figure 14     PI Setpoint  Hand Mode  M1  Auto Mode  M1   P1 1 13 P1 1 15  Output    A1 1 A1 1  As 79      Frequency    Keypad P10 Parameter  Adjustments    Motor Pot Motor Pot    Fieldbus  PID Gain  M1     P1 1 20  PID I Time  P1 1 21    Actual PI  M1   Feedback    Fieldbus   Min A1 1  A1 2  Max A1 1  A1 2  Ave   1 1  A1 2    Sensor Parameter  Adjustments    LIT 1201858    Sensor  Output  Signal    Figure 15  PID Flow Chart    PID Control D  P1 1 22         Ref Rise T    1 1 23        Ref Fall Time  P1 1 24   PI Ref Max  P1 1 19   PI Ref Min  P1 1 18       For more information visit  www johnsoncontrols com 17    Powered by Eaton s Technology    Controls    Johnson Aj    V
23. SD Series Quick Start Guide    November 2009    Appendix D     Bypass Wiring Diagram    3961007  D N                               ue                     HEJS  9 qeu3                         A1012eJ si                     9181S peziDJou3 eq               5           W                                     UNI      1snuu   Spo N oin Y UI  HA HEIS 0         snonuimnuoo y  Jenue A             5     ees  CL 01810 8 01 9                  95015  e   pepunour  aq 1sn N  s 40310 JAN pue aunso 2u3       seoN    1994 0            5597 e qe                ZEZ SH    NOlLdO 9133 V SV                                                            VO SOUNO NNOD  MNOLLGO    ALON            e1e1edeg ul  na        ain              041U02  OPA pz pue        OLL ung   viva  SMa   ax axu      S   ON                    O I        viva  SANIN     axi axu    39VL10A              AS        3       aaiHs   a 1015  02190     SHYOMNO1                        43A09           3QISNI Q31v201   AINO                      l     SSVdA8 AMOLOV3        STVNIAM3L               TIY    ALON   NO   330    M3MOd JANG    NOY IAYO IS    9 1015 98190    Linvs   OVA 009      SdWV OL Q3lVM  Z INdINO AVIY 3SN YSNOLSND NOS SLOVINOO          mae O ALL    L 1           AVY  8 1015 2 190  v                         Apeeg             eu6iq d     indino Bojeuy SSVdA8 NO YALYSANI NO  AouenbaJ4            YOLOW SOLON              9NIQ vNIG  jjne4                ssed  g  apo 9114    Wales peeds  punol5 0 1 Ee    indino eBeyoA              
24. Wizard Navigation  1 of 3     Note  Use    for changing parameter  Then press ENTER to save and move forward     LIT 1201858 For more information visit  www johnsoncontrols com 21    VSD Series Quick Start Guide    22    Steps                        Johnson JJ     Controls Powered by Eaton s Technology                     NP FREQ Motor Name Plate Frequency     default 60 00 Hz  50 00 HZ           e    MOTOR NP RPA Motor Name Plate Speed  1720 rpm  Med RPN    N                AIN  FREQUENCY Drive Minimum Output Frequency    default 12 00 Hz  10 00 HZ     AOX  FREQUENCY Drive Maximum Output Frequency  default 60 00 Hz  50 00     AUTO ACCEL TIRE Acceleration time from zero to Max  Frequency   when running in auto mode and Pl regulator is not active   60 05 default 60 0 seconds     AUTO DECEL TIRE Deceleration time from Max  Frequency to zero   cue when in auto mode and drive is stopped   i default 60 0 seconds     PI INPUT SOURCE PI Input Feedback Auto source  when PI is active   Al 1  0 10V DC   Al 2  0 20 mA   Fieldbus  idis default Al 1     PID Input Feedback device min  value  SENSOR MIN  SCALE This value corresponds to the min  value of the sensor  XXXX output and to P1 2 10 or P1 2 14   not available in Remote Input and Generic PI applications      BI 1 FIN  Analog Input 1 min  value  0 00    OV  0 0   not available in Remote Input and Generic PI applications      PID Input Feedback device max  value  SENSOR         SCALE This value corresponds to the max  value of the sen
25. ads to each other     Note  Set the multimeter to the diode function  and check each power terminal  consecutively with each DC bus terminal as indicated in Table 7     Table 7  Static Checks of Converter    DC Bus Termina Powerfemial O O O  Muhimeter  oe   B   1st Overload Check  Insert black     Insert black     Insert black     OL   Insert red     multimeter lead  multimeter lead  multimeter lead  multimeter lead    B   2nd Overload Check  Insert red     Insert red     Insert red     OE   Insert black     multimeter lead  multimeter lead  multimeter lead  multimeter lead     B   1st Voltage Check  Insert black     Insert black     Insert black      25      55V DC  Insert red     multimeter lead  multimeter lead multimeter lead multimeter lead   1076   B   2nd Voltage Check  Insert red     Insert red     Insert red      25      55V DC  Insert black     multimeter lead  multimeter lead  multimeter lead  multimeter lead    10    Note  Set the multimeter to the diode function  and check each motor terminal  consecutively with each DC bus terminal as indicated in Table 8        Table 8  Static Checks of Inverter    DC Bus Terminal Motor Terminal on Contactor if Bypass or Output Contactor Multimeter        B   1st Overload Check  Insert black     Insert black     Insert black     OL   Insert red     multimeter lead  multimeter lead  multimeter lead  multimeter lead    B   2nd Overload Check  Insert red     Insert red     Insert red     OL   Insert black     multimeter lead  mult
26. ation visit  www johnsoncontrols com 23    VSD Series Quick Start Guide    Remote Input Application    Johnson JJ    Controls Powered by Eaton s Technology    The Remote Input application uses a slightly different Start Up Wizard     24    Steps   1  to  4   and  6  to are exactly the same     New ACCELERATION TIME Acceleration time from min  Frequency  Steps  12 s to max  Frequency             DECELERRTIDN TIRE Deceleration time from max  Frequency    to min  Frequenc  50 5 9 P              Keypad  START SRCE AUTO DI Start    Biel START      3 wire  Fieldbus      A  Al 1  STPT SOURCE AUTO  A  Al 2   Al 81 1 Keypad StPt    Fieldbus       Start source location    Set point of Auto Source    Figure 24  Remote Input Start Up Wizard    For more information visit  www johnsoncontrols com    November 2009       LIT 1201858    Johnson          Controls Powered by Eaton s Technology VSD Series Quick Start Guide    November 2009    Appendix H     Static Checking    Static Checking    Static checking tests the integrity of the power carrying components  diodes  capacitors  and IGBTs  within the drive assembly  Performing these static checks ensures that no  damage occurred during shipping or installation that could cause a failure when the drive  Is powered     Make sure there is no power to the drive before proceeding with any of the static checks     After checking each set of terminals  zero out the multimeter by touching the metal tips of  the red  positive  and black  negative  le
27. contactor user s manual  Overlusd     Terminals    MOTOR WIRING    An SAE allen wrench will damage the terminals    and the motor overload will need to be replaced    not covered by warranty     17  Using the torque wrench  tighten each terminal to the  torque value found in the appropriate user s manual  supplied with the drive     Reinsert the motor overload terminal block     Grounding    19  Use a flat blade screwdriver to connect the motor ground  wire to the ground stud  located at either the top or  bottom of the drive s enclosure    Mandatory  Ground  connection main power ground must be connected to  other ground screws     GROUND WIRING    Run motor cables in separate conduit    DO NOT RUN CONTROL WIRES in same conduit  Cables sized per NEC    Provide low impedance ground between drive and  motor     Utility Drive Motor Ground   Inside Motor Conduit Box     IMPORTANT  Improper grounding could result in damage to the  motor and or drive and could void warranty       LIT 1201858 For more information visit  www johnsoncontrols com 7    VSD Series Quick Start Guide    johnson        Controls    Powered by Eaton s Technology    November 2009    NEMA Type 1 IntelliPass IntelliDisconnect Drive    Table 3  Bypass Power Wiring Instructions     NEMA Type 1  continued     Setting Overload    20  Lift to open the cover on the motor overload  and use a  1 8  flat blade screwdriver to set the overload amperage to  match the value on the motor nameplate     Turn the auto manual re
28. d  34 CAN bus communication Sent message not acknowledged Ensure that there is another device on the bus with the  appropriate configuration     Control unit Control unit cannot control the power unit and vise versa   Change control unit   Device change   option board changed Reset     different power rating of drive Note  No fault time data record   Device added   option board added Reset     drive of different power rating added Note  No fault time data record   Device removed   option board removed Reset     drive removed Note  No fault time data record     Unknown option board or drive Contact your Johnson Controls distributor     7  8  4 IGBT temperature software IGBT Inverter Bridge overtemperature protection has Check loading   detected high short term overload current Check motor size   7     4  4       50 Analog input     lt  4 mA Current at the analog input is Check the current loop  signal source and wiring    for signal range 4to 20 mA     4mA     control cable is broken or loose     signal source has failed    External fault Digital input set as an external fault input has been Check source of trigger   triggered   Keypad communication fault   The connection between the control keypad and the VSD   Check keypad connection and keypad cable   Series drive has been lost   53 Communication bus fault veel  master and the communication bus board has failed If installation is correct  contact your Johnson Controls  distributor     Slot fault Defective option board or sl
29. ic checks as  described in Table 7  for the converter   Table 8   for the inverter  and Table 9  for the DC bus   Refer to  Page 25  Appendix H     L1  L2  L3 B   B   BT T1  T2  T3    Note  Static check shown is for L3 and B  terminals     28  Once the pre power static checks are completed   reinstall the drive s outer and side covers  tightening  all the screws     A WARNING    High Voltage is present on L1  L2  L3  B   B   BT  T1  T2           Starting Drive    29  Make sure that the drive s 3rd contactor S1 switch  if  present  is in the ON position  shown in OFF position      Note  The bypass mode operates with the switch in the OFF  position  however the drive will not run  Yet the keypad  will operate     Starting Drive    30  Turn the circuit breaker handle in a clockwise direction   A WARNING    High Voltage Handle    Circuit Breaker      Always work with another person     Be sure equipment is properly grounded     Wear safety glasses     Start Up Wizard See Appendix G        LIT 1201858 For more information visit  www johnsoncontrols com 9    Johnson lj    VSD Series Quick Start Guide Controls Powered by Eaton s Technology    November 2009    Enclosed NEMA Type 12 3R    Optional NEMA Type 3R Hood   Hood not present on    NEMA Type 12 drive  Power Ground Stud    Circuit Breaker       Circuit Breaker eye POW ee Supp    Handle    Optional 3rd Input Contactor    Keypad Cable                                          electrical schematic     Output  amp  Bypass Contactor 
30. imeter lead  multimeter lead  multimeter lead     B   1st Voltage Check  Insert black     Insert black     Insert black     25      40V DC   10    Insert red     multimeter lead  multimeter lead multimeter lead multimeter lead  B   2nd Voltage Check  Insert red     Insert red     Insert red      25      40V DC   10    Insert black     multimeter lead  multimeter lead  multimeter lead  multimeter lead        LIT 1201858 For more information visit  www johnsoncontrols com 25    Johnson 7l    VSD Series Quick Start Guide Controls Powered by Eaton s Technology    November 2009    Appendix H     Static Checking  continued    Note  Set the multimeter to the ohm function  and check the power guround terminal and  DC bus terminals as indicated in Table 9     Note  Frame 6 and larger use a  Hybrid  rectifier section   Shown in Service Manual    Readings will be different when taking measurements from  B   DC     Table 9  Static Checks of DC Bus    DC Bus Terminal DC Bus Terminal  B   Ground Terminal  Power  Multimeter Reading    B4  Overload Check  Insert black     multimeter lead  Not used  OL  Insert red     multimeter lead     B   1st Ohm Check  Not used  Insert red     multimeter lead  O L  Insert black     multimeter lead   B   2nd Ohm Check  Not used  Insert red     multimeter lead  O L  Insert black     multimeter lead     Figure 25 is a detailed schematic to aid in performing the static checks        Continuity Test to Ground    Test L1  L2  L3 to ground   T1  T2  T3 to ground
31. ols com 3    VSD Series Quick Start Guide    Johnson H    Controls    November 2009    NEMA Type 1 12 Open Drives  1   250 HP     Table 1  Control Wiring Instructions  continued     Control Wiring    Incoming Power    9  Wire control to the OPTA9 Control Board and OPTA2   Note  Drive default is programmed for Damper Interlock     Note  Option Boards OPTC2  N2 XT SA Bus  and OPTCA   LonWorks  are optional     Mandatory Ground Wiring    Be sure to pull low impendance ground wiring from  customer power to drive and ground wire from drive  to motor     Motor Ground   Inside Motor Conduit Box     Utility    Note  Must pull  dedicated  ground wire  to drive  and motor     I O Connection      Run 110 Vac and 24        Control wiring in separate  conduit   e Communication wire to be shielded   e RS 232 Keypad cable less than 20 feet     Data  Data  Shield    EN OPTA9 SIGNAL Slot A  X1    Reference Output  Analog input Voltage   Range 0 10V DC         Ground   Analog Input Current   Range 4 20mA      See Figure 3    for Dip X1  X2   X3  X6 Switch  settings     Control Voltage Output         Ground       Start Stop  External Fault  Run Permisive Damper Interlock  DIN 1 DIN3 Common  Control Voltage Output       Ground  Speed Select 1  Fire Mode  Bypass Overload Fault  DIN4 DIN6 Common  Output Frequency  Analog Output  Digital Output Ready  OPTA2 Slot B  Relay Output 1  Run    Relay Output 2    OPTC2 Slot D or E   Shield      45V Supply Voltage    RxD TxD   Minus    RxD TxD   Plus    Bus
32. ot Check that the board is properly installed and seated in       9   1   2 Brake resistor Brake resistor overtemperature protection has detected Set the deceleration time longer   overtemperature excessive braking Use an external brake resistor    3   1   2    Encoder fault Note  the exceptional Fault data record  See Active Fault   Check encoder channel connections   Menu for more information  Additional codes  Check the encoder board   1 Encoder 1 channel A is missing  2 Encoder 1 channel B is missing  3 Both encoder 1 channels are missing  4 Encoder reversed    3  3  3  5  5    The data connection between the communication bus Check installation        slot  If installation is correct  contact your Johnson  Controls distributor        82 BypassOverLoad The motor has been overloaded while connected to the Decrease the motor load   bypass Disable the Current Imbalance feature   see the IT   manual        Controls Powered by Eaton s Technology  Controls Group    2009 Johnson Controls  507 E  Michigan Street All Rights Reserved  PO  Box 423 Printed in USA    LIT 1201858  www johnsoncontrols com  November 2009    Milwaukee  WI 53201    
33. r Overload      Manual Auto Reset      24V DC Motor Overload  Terminal Block      Ground Studs       ntelliPass only         Drive Enclosure Endplate       located at bottom     Optional 3rd Contactor S1 Switch     provided for drive isolation        Figure 4  Identification of NEMA Type 1 Components    Table 2  VSD Series NEMA Type 1 IntelliPass IntelliDisconnect Drive  Dimensions    Drive Approximate Approx  Distance  Horsepower  VT  Dimensions in Weight Between  Inches  mm  in Ibs   kg    Drives in   Inches  mm        208V  1     3      5 04   18 25  13 24   21 9 5    5 3 134 6   230V  1     3       128    464     336   480V  1    7 1 2 hp    208V  5     7 1 2 hp 5 50   23 25   1324   35 159   5  144 8   230V  5     10 hp  140     591     336    480V  10     20 hp   208V  10   20 hp FR6 7 50   29 38   15 25   67 30 4   7 5 190 5   230V  15 and 20 hp  191     746     387    480V  25   40 hp   208V 25and30hp   FR7 9 10   37 53   15 25   108 49 0    9 0  228 6   230V  25 and 30 hp  231     953     387    480V  50 75 hp     D If mounting two or more IntelliPass Drives next to each other  make sure to use the  proper spacing between the drives for hinged door operation        Figure 5  VSD Series IntelliPass IntelliDisconnect Drive Dimensions    LIT 1201858 For more information visit  www johnsoncontrols com 5    Johnson Jl    VSD Series Quick Start Guide Controls Powered by Eaton s Technology    November 2009    NEMA Type 1 IntelliPass IntelliDisconnect Drive    Table 3  Bypas
34. re    Add input impedance to limit surges     Check motor and motor cables     Reset the fault and restart  Should the fault re occur   contact your Johnson Controls distributor        mE Emergency stop An Emergency stop signal was received from one ofthe   Determine reason for the Emergency stop and remedy it   digital inputs    Saturation trip   defective component      motor or motor cable short       System fault   component failure    faulty operation  Note  exceptional fault data record  see Active Fault Menu  for more information    Undervoltage DC link voltage is less than the minimum safe operating  voltage limit    most probable cause  too low a utility supply voltage    VSD Series internal fault    Cannot be reset from the keypad    Switch off power    IF THE PROBLEM IS NOT IN THE MOTOR ORITS CABLES   DO NOT RE CONNECT POWER    Contact your Johnson Controls distributor    If this fault appears simultaneously with Fault 1  check the  motor and motor cables     Reset the fault and restart  Should the fault re occur   contact your Johnson Controls distributor     If there was a supply voltage loss or dip  reset the fault  and restart the VSD Series drive  Check the supply  voltage  If it was within specification at the time of the  fault  an internal failure has occurred  Contact your  Johnson Controls distributor        10      Input line supervision Input line phase is low or missing  Check the utility supply voltage  cables and connections     e front phase supervi
35. s Power Wiring Instructions     NEMA Type 1  Mounting Drive    Mount drive per dimensions   See Page 5      Verify that the main power source is removed upstream     Using a flat blade screwdriver  remove the four screws  securing the outer cover of the drive and remove the    cover  Outer Cover    Using the same screwdriver  remove the two center    screws securing the side cover     A Two Screws on    Make sure there is adequate room  and open the hinged Side Cover  side cover     Power Wiring    6  Using a flat blade screwdriver  remove the screws  securing the endplate at the bottom of the drive enclosure   and remove the endplate     Using a Greenlee conduit cutter  recommended   cut one  or more holes in the endplate  located at the bottom of the  drive s enclosure  for the motor and power leads     Bottom  Endplate    Note  If bringing the power leads in through the top of the  drive s enclosure  go to step 8  If not  proceed to step 10     Power Wiring    8  Using a flat blade screwdriver  remove the screws  securing the endplate for the circuit breaker enclosure   and remove the endplate     Circuit Breaker  Endplate    Using a Greenlee conduit cutter  recommended   cut one  hole in the circuit breaker endplate for the power leads     Power Wiring   l  ncoming    10  Calibrate the circuit breaker amperage  so it is 1 25 times Power Leads i Circuit Breaker  the amperage on the motor nameplate  by turning the Terminals  red set screw located below the circuit breaker e
36. set  factory default is manual  on  the motor overload 90  to the auto position     Control Wiring    22  Use a flat blade screwdriver to carefully remove the low   voltage I O terminal block     Insert the incoming control leads into the terminal block   Refer to the electrical schematic supplied with the drive     Reinsert the I O terminal block into the control board     Verify that all other wires to the terminal block are  connected     Terminate control wiring to the OPTA9 and OPTA2 board   Terminals 1     26      23     24   25     26     CONTROL WIRING        Run 110 Vac and 24        control wiring in separate  conduit       Communication wire must be shielded       RS 232 keypad cable must be less then 25 feet     Auxiliary contacts for customer  use rated 10 Amps at 600V AC    R F    3   4   3   4    Motor Motor  On Inverter On Bypass    F  Bypass  Contactor   L1   L2    Auto Manual  Reset    Drive Motor  Ground Ground    Starter             1 LINE      FUSES        Tra   20   da ap tat  Lo E ray  2 fa ol          B 75   L3     Line   CONTACTOR        Incoming  Power       23 1  Optional Optional   10V  Vin   GND  Lin   Lin   24Vout  GND  DIN1  DIN2  DIN3  CMA  24Vout  GND  DIN4  DIN5  DIN6  CMB  Lout   Lout   DO1    Customer  Ground       2                        Blo  N    gt     Reversing  Starter       OPTB5 Relay   Slot C     RY1 Drive Run        22        3123        RY2  Bypass      L3    Tri    L1  112 12  173 113             OPTA9 SIGNAL Slot A    Reference
37. sion Current sensing indicates that there is no current in one Check the motor cables  connections and motor   motor phase      no brake resistor installed    brake resistor is broken    brake chopper failure    Brake chopper supervision    Check the brake resistor  If the resistor is ok  the chopper  is faulty  Contact your Johnson Controls distributor        VSD Series under  Heatsink temperature is under  10 C Provide supplemental heating or relocate the VSD Series  temperature drive to a warmer location     VSD Series overtemperature   Heatsink temperature is over 90  C       motor or load mechanical failure    load too high    stall parameter settings incorrect      motor is overloaded      motor overheating has been detected by VSD Series    motor temperature model    Motor overtem perature    Motor underload    EEPROM checksum fault  23      mechanical or load problem    underload parameter settings incorrect    ul Motor stalled      Parameter save fault    faulty operation    component failure    An overtemperature warning is issued when the heatsink  temperature exceeds 85  C  a fault occurs at 90  C  Check  for the correct amount and unrestricted flow of cooling  air    Check the heatsink for dust or dirt buildup    Check the highest ambient temperature level    Make sure that the switching frequency is not set too high  in relation to the ambient temperature and motor load     Check the motor  mechanical system and load level   Confirm the stall parameter settings 
38. sor  XXX X output and to P1 2 11 or P1 2 15   not available in Remote Input and Generic PI applications      HI 1 FX  Analog Input 1 max  value  100 0095   10V  100 00   not available in Remote Input and Generic PI applications   Continued    Figure 22  Start Up Wizard Navigation  2 of 3     For more information visit  www johnsoncontrols com    November 2009    LIT 1201858    Johnson Aj i    Controls Powered by Eaton s Technology VSD Series Quick Start Guide    November 2009    PI CONTR  P GBIN PI control gain value  Steps  E  default will vary depending on application           e    PI CONTR  I TIRE PI control integration time    default 30 00 second  30 00              lt      PI STPT PI Setpoint if source is fieldbus   not available in Remote Input application     8      e    Jump to  x           REPEAT SETUPP     no EO     SETUP DONE  Q3 PRESS ENTER    When keypad is used for copying  parameters to or from another drive               NEW               PRESS ENTER    COPY PARAMETERS     no     ss             COPY FROM KEYPAD       no EO        DOWNLOADING       UR          COPY TO AESPRD       no EO        UPLOADING       UR       OPERATE MENU  DEFALLT PAGE    Figure 23  Start Up Wizard Navigation  3 of 3        Note  Start Up Wizard can be cancelled with the STOP RESET button  If pressed  the text    EXIT     is shown  on the display along with    No    and    Yes        Note  In Pressure Control application  inverse selection is an option     LIT 1201858 For more inform
39. ty Drive    For more information visit  www johnsoncontrols com 1    Johnson Mi    VSD Series Quick Start Guide Controls Powered by Eaton s Technology    November 2009    NEMA Type 1 12 Open Drives  1     250 HP     Table 1  Control Wiring Instructions  Mounting Drive    1  Mount Drive   See Table below for dimensions                                          Knockouts             Figure 1     VSD Series Open Drive Dimensions    Medi hp  VT  Approximate Dimensions in Inches  mm  His                                                    FR4 230V 3 4     3 12 9 12 3 11 5 7 5 5 0 5 0 3 9 11   327   313   292   190   126   128   100   13  3   5     E 5     7 1 2 Lu Lu La um    71 2     15 Lu Lu La Wa        Ma Wo s o um 1            10     15 22 0 21 3 20 4 9 3 6 7 7 7  480V 20     30  558   541   519   237  168   171   195  Um i18  yn i    24 8 24 2 23 3 10 1 7 5 77 2    630   614   591   257   68   189   237   190   18   35    29 7 28 8 28 4 Dru 11 0 11 2 10 0 127 8   45 3 44 1 m 3 5 4 18 9 15 7 7 4 321 9  FR10 44 33 5 23 6 23 6 16 7 9 47 550 7   ERHCEERDEIEEEELIE     Power Wiring    Notice  Do not discard the plastic bag containing the wiring plate     2  Remove the bottom cover by rotating the cover toward  you on the base hinges  then lifting the cover away from  the base     Power Wiring    3  Locate the plastic bag shipped with the drive containing  the wiring plate  and remove the wiring plate        2 For more information visit  www johnsoncontrols com LIT 1201858    Johnson
40. xtension  bar  See the circuit breaker user   s manual supplied with  the drive     Connect the incoming power leads to circuit breaker    terminals labeled L1  L2 and L3  Cables sized per NEC  ao Breaker  e crew  Using the torque wrench  tighten each terminal to the    torque value found in the appropriate user s manual  supplied with the drive     POWER WIRING    Circuit Breaker       5                              Run cabling in separate metal conduit or wiring tray     DO NOT RUN CONTROL WIRING with incoming  power wiring    Provide low impedance ground connection to drive  chassis    DO NOT CONNECT to B   B   R terminals        6 For more information visit  www johnsoncontrols com LIT 1201858    Johnson YG  Controls    Powered by Eaton s Technology VSD Series Quick Start Guide    November 2009    NEMA Type 1 IntelliPass IntelliDisconnect Drive    Table 3  Bypass Power Wiring Instructions     NEMA Type 1  continued   Motor Wiring    13  Use your first and second fingers and simultaneously  push down to release the two orange retaining clips  one  on each side of the 24V DC motor overload terminal  block      If necessary  use a flat blade screwdriver to carefully  remove the terminal block in a straight plane to avoid  damaging it     Motor Wiring    15  Connect the motor leads to the motor overload terminals  labeled 1TA  1     and 1TC     16  Using the appropriate metric Allen wrench  2 5 mm  3 mm  or 4 mm   tighten each overload terminal per the  specifications in the 
    