Home
        caution! - Climatemaster
         Contents
1.        Electric water heaters are recommended  If a gas  propane   or oil water heater is used  a second preheat tank must be  installed  Figure 15   If the electric water heater has only a  single center element  the dual tank system is recommended  to insure a usable entering water temperature for the HWG     Typically a single tank of at least 52 gallons  235 liters  is  used to limit installation costs and space  However  a dual  tank  as shown in Figure 15  is the most efficient system   providing the maximum storage and temperate source water  to the HWG     Itis always advisable to use water softening equipment on  domestic water systems to reduce the scaling potential and  lengthen equipment life  In extreme water conditions  it may  be necessary to avoid the use of the HWG option since the  potential cost of frequent maintenance may offset or exceed  any savings  Consult Table 3 for scaling potential tests     Figure 14  Typical HWG Installation                       Shut Off  Valve  1    Cold Inlet From  Domestic Supply    a   e    Shut Off Valve  4    Shut Off  Valve  2       Upper      element to    120   130  F   49   54  C   Powered  Water Heater    b  Lower  element to    100   110  F     38   43  C                 Ep     sia  ass Nipple  and T   Insulated Water Lines     Figure 15  HWG Double Tank Installation       Shut Off Cold Inlet From Hot Outlet  Domestic Supply To House          Hot Outlet  Cold Inlet    Upper  element to    LL Wo   180   49   54  C    
2.        Shut Off Valve  4    Powered  Water Heater    Lower  element to  110   120 F    Field Supplied  3 4  Brass Nipple  43   49  C   and T     Unpowered  Water Heater               Insulated Water Lines    5 8  OD  50 ft Maximum    16mm OD  15 Meters Maximum     Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012       Installation   The HWG is controlled by two sensors and a microprocessor  control  One sensor is located on the compressor discharge  line to sense the discharge refrigerant temperature  The  other sensor is located on the HWG heat exchanger s  Water  In  line to sense the potable water temperature     A WARNING  A    WARNING  UNDER NO CIRCUMSTANCES SHOULD  THE SENSORS BE DISCONNECTED OR REMOVED    AS FULL LOAD CONDITIONS CAN DRIVE HOT  WATER TANK TEMPERATURES FAR ABOVE SAFE  TEMPERATURE LEVELS IF SENSORS HAVE BEEN  DISCONNECTED OR REMOVED        The microprocessor control monitors the refrigerant and  water temperatures to determine when to operate the HWG   The HWG will operate any time the refrigerant temperature  is sufficiently above the water temperature  Once the   HWG has Satisfied the water heating demand during a   heat pump run cycle  the controller will cycle the pump at  regular Intervals to determine if an additional HWG cycle  can be utilized  The microprocessor control Includes 3 DIP  switches  SW10  HWG PUMP TEST   SW11  HWG TEMP    and SW12  HWG STATUS      SW10 HWG PUMP TEST  When this switch is in the    ON     position  the HWG
3.     Stage 2 heating        G  Y1  Y2  W    Stage 3 heating       Stage 3 heating       N A       G W    Emergency heat    Emergency heat    Emergency heat       G Y orY1 0    Stage 1 cooling       Stage 1 cooling       Cooling        G  Y1  Y2  0    Stage 2 cooling                   Stage 2 cooling    N A    1 Stage 1  1st stage compressor  1st stage fan operation  Stage 2  2nd stage compressor  2nd stage fan operation  Stage 3  2nd stage compressor  auxiliary electric heat  2nd  or 3rd stage fan operation  depending on fan settings   2 Stage 1  1st stage compressor  1st stage fan operation  reversing valve  Stage 2  2nd stage compressor  2nd stage fan operation  reversing valve  3 Stage 1  compressor  1st stage fan operation  Stage 2   compressor  2nd stage fan operation  Stage 3   compressor  auxiliary electric heat  2nd or 3rd stage fan operation  depending on fan settings   4 Stage 1   compressor  1st stage fan operation  reversing valve  Stage 2   compressor  2nd stage fan operation  reversing valve  5 Stage 1   compressor  fan  Stage 2   compressor  auxiliary electric heat  fan  6 Cooling 2 compressor  fan  reversing valve    31    32       Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012       CXM Controls    Table 7  Nominal resistance at various temperatures    Resistance   kOhm     85 41  84 16  81 43  61 70  58 40  55 30  52 40  49 60  47 00  44 60  42 30  40 10  38 10  36 10  34 30  32 60  31 00  29 40  28 00  26 60  25 30  24 10  23 00  21 90  20 80
4.    36 41  37 42  38 43    21 2 23 2  15 7 17 7  10 2 12 2    19 25  20 26  21 27    88 98  94 104  100 110    306 326  311 331  317 337    10 15  10 15  11 16    8 13  8 13  9 14    11 13  8 3 10 3  5 5 7 5    23 29  24 30  25 31       135 145  133 143  132 142    300 320  285 305  270 290    12 17  14 19  16 21    20 3 22 3  15 17  10 12    21 27  21 27  22 28    112 122  122 132  130 140    333 353  342 362  351 371    12 17  14 19  15 20    10 15  10 15  11 16    14 16  10 5 12 5  7 3 9 3    28 34  30 36  32 38       139 149  138 148  138 148    390 410  370 390  350 370    8 13  8 13  8 13    19 3 21 3  14 3 16 3  9 3 11 3    20 26  21 27  21 27          144 154  143 153  142 152    488 508  468 488  448 468           Based on 15  Methanol antifreeze solution    40    8 13  7 12  7 12          18 4 20 4  13 6 15 6  8 8 10 8       147 157  154 164  160 170    369 389  377 397  385 405          15 20  18 23  19 24       10 15  10 15  11 16       17 7 19 7  13 4 15 4  9 11       36 42  37 43  38 44       Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       Unit O perating Conditions    Table 12  GT PG Series Typical Unit Operating Pressures and Temperatures  Continued  070 Full Load Cooling   without HWG active Full Load Heating   without HWG active       Entering Water Suction Discharge end Air Temp Suction Discharge Water Air Temp  Water Flow Pressure Pressure   Superheat   Subcooling Rise Drop   F Pressure Pressure   Superheat   Subcooling Temp Drop Rise   
5.    ALITIAVIT LORLLS NI YO 32ONS  STTOSIN SOPIITTHVO 2104 AO AJNV BPIVM ANV JO HOVHS   AHL 804 LOV3LINOO JO HO VIS AOA WALAAVI LSNIVOV YASVHOUNd AO AAANA AHL AO AGAWAA AAISATOXA ANV TIOS AHL SI AGAWAN STH L HVO Jo Ariqer  umumxeur ap 3q eys punja  preg   s poos pos ou  Jo umjo1 oq  Joy o3uvupxo  Ur JoL1e   0  pred oorid oseqoand oq punjo  preys Joe  osodind  erjuosso sy Jo s mj Apouro  og  pue  onrej 1910 JO uorjounjpeur  129jop IP 3221100 0 IIVO Aq Sdwa jo 19quinu o qvuoseo1 v pue  amre  IIO JO uorjounjpeur  359jop Youd Jo euroqepro    AUD euroqepio   ur K10329  SIALE 0  IOYOU UMUM Joye JJ  pom sey qorqA jrun Jo Ped oy  Joy o3uvgoxo ur UN 10 ped 3pnqor 10 Aou v qsrumg 0  10    yun 10 Wed po mj ou 11edo  0  uondo s 19u10 W pojesrqo 3q   juo  TA JoWIED  AjuerxmA  ssaidxzp pojrurT oy  jo qovaiq v Jo JUA  ou UT    SUMAWANA 4O NOLLV LIIATT     Ajueim M  ssoidxg pojurT ot jo uonenp oy  0  pojrurn 3q  eus  Aimqejueqorour pue osodind 1e nonied Joy ssouyg Jo sonuenm    pordu Aue 10 sonueimA ssoxdxo Aue uonejrum jnoqira aurpnjour  Auer ssoaidxo yons Aue  jsrxo sonueimA JOYIO jeu poururojop st 3r  uro1oq pourejuoo SIOUITE OSIP oq Surpuejsujr  jou    JJ  sonuenmeA IIO JPL JO NOT  ur UDATS sr AjuermA  Ssoidxg poyrumT sr WOVE ATT     MO 9q Sso1ppr 10 1oquinu  ououd oq qe JOLTED 32u09    paseyoind oavy NOK Jonpoad oq 0  sorde KyueeA  ssordxsy posu sig jt amsun am NOK FT     IOTEWS pue A192  WIM Suruurdoq sioquinu eros YIM SHUN peuaoqioor  19r  opnpout Kqpe19098 proa srp  QT0C    T Inr 0  10
6.   10 12    20 26  20 26  20 26    122 132  133 143  144 154    353 373  365 385  378 398    12 17  14 19  16 21    11 16  11 16  11 16    15 17  11 5 13 5  8 10    29 35  31 37  33 39       133 143  132 142  132 142    390 410  368 388  345 365    8 13  9 14  9 14    8 13  6 11  5 10    19 21  14 16  9 11    19 25  19 25  19 25          141 151  140 150  140 150    497 517  472 492  447 467        Based on 1596 Methanol antifreeze solution    060    Full Load Cooling   without HWG active    6 11  7 12  8 13          8 13  6 11  5 10       18 20  13 5 15 5  8 7 10 7       18 24  18 24  18 24    166 176  173 183  181 191    397 417  407 727  417 437          16 21  18 23  19 24       9 14  9 14  10 15       19 5 21 5  14 7 16 7  9 9 11 9       37 43  38 44  40 46       Full Load Heating   without HWG active       Entering  Water  Temp F    Water  Flow  GPM ton    Suction  Pressure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water  Temp Rise  oF    Air Temp  Drop   F  DB    Suction  Pressure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water  Temp Drop  oF    Air Temp  Rise   F DB       30     1 5  2 25  3    98 108  97 107  96 106    160 180  149 169  137 157    40 45  41 46  42 48    20 22  14 3 16 3  8 5 10 5    19 25  19 25  20 26    62 72  66 76  70 80    276 296  280 300  284 304    6 11  6 11  7 12    6 11  6 11  6 11    8 10  6 8  4 6    17 23  18 24  19 25       1 5  2 25    118 128  117 127  115 125    225 245  210 230  195 215 
7.   19 90  18 97  18 09  17 25  16 46  15 71  15 00  14 32  13 68  13 07  12 49  11 94  11 42  10 92  10 45  10 00  9 57  9 17  8 78  8 41  8 06  7 72  7 40  7 10  6 81  6 53  6 27  6 02  5 78  5 55  5 33  5 12  4 92  4 73  4 54  4 37  4 20  4 04  3 89  3 74  3 60  3 47  3 34  3 22  3 10                                                                                                                                                                                                                                  CXM Thermostat Details   Thermostat Compatibility   Most all heat pump thermostats  can be used with the CXM control  However Heat Cool  stats are NOT compatible with the CXM     Anticipation Leakage Current   Maximum leakage current  for  Y  is 50 mA and for  W  is 20mA  Triacs can be used   if leakage current is less than above  Thermostats with  anticipators can be used if anticipation current is less than  that specified above     Thermostat Signals        Y  and  W  have a 1 second recognition time when  being activated or being removed       O  and  G  are direct pass through signals but are   monitored by the micro processor     R  and  C  are from the transformer     AL1  and  AL2  originate from the alarm relay     A  is paralleled with the compressor output for use   with well water solenoid valves    The  Y  1 4  quick connect is a connection point to the    Y  input terminal P 1 for factory use  This  Y  terminal   can be used to drive panel mounted relays such 
8.   276 296  278 298  280 300    10 15  10 15  10 15    10 15  10 15  10 15    7 2 9 2  5 3 7 3  3 5 5 5    17 23  18 24  18 24       136 146  136 146  136 146    211 231  197 217  183 203    11 16  11 16  11 16    6 11  5 10  5 10    20 6 22 6  14 8 16 8  9 11    17 23  17 23  17 23    99 109  103 113  108 118    302 322  306 326  311 331    10 15  10 15  10 15    13 18  13 18  13 18    10 6 12 6  7 7 9 7  5 7    22 28  23 29  23 29       137 147  137 147  137 147    275 295  260 280  245 265    9 14  9 14  9 14    10 15  9 14  9 14    19 21  13 8 15 8  8 10    18 24  19 25  19 25    127 137  133 143  139 149    332 352  338 358  344 364    10 15  10 15  10 15    15 20  15 20  15 20    13 5 15 5  10 1 12 1  6 7 8 7    27 34  28 35  29 36       142 152  142 152  142 152    373 393  352 372  332 352    7 12  8 13  8 13    10 15  6 11  6 11    19 5 21 5  13 9 15 9  8 3 10 3    17 23  17 23  17 23          147 157  147 157  147 157    467 487  448 468  430 450        Based on 15  Methanol antifreeze solution       6 11  6 11  6 11       10 15  8 13  7 12    16 2 18 2  11 9 13 9  7 6 9 6          16 22  16 22  16 22    164 174  172 182  181 191    365 385  372 392  379 399       11 16  11 16  12 17          15 20  15 20  15 20       17 4 19 4  13 2 15 2  9 11    34 42  35 43  36 44          39    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012    Unit O perating Conditions    Table 12  GT PG Series Typical Unit Operating Pressures and Temperatures  Continued  042    F
9.   parts and accessories which make  up the installation shall be in accordance with the regulations  of ALL authorities having jurisdiction and MUST conform to  all applicable codes  It is the responsibility of the installing  contractor to determine and comply with ALL applicable  codes and regulations     Horizontal Installation    Mounting Horizontal Units   Horizontal units have hanger kits pre installed from the factory  as shown in Figure 1  Figure 3 shows a typical horizontal unit  installation     Horizontal heat pumps are typically suspended above a ceiling  or within a soffit using field supplied  threaded rods sized to  support the weight of the unit     Use four  4  field supplied threaded rods and factory provided  vibration isolators to suspend the unit  Hang the unit clear   of the floor slab above and support the unit by the mounting  bracket assemblies only  DO NOT attach the unit flush with the  floor slab above     Pitch the unit toward the drain as shown in Figure 2 to improve  the condensate drainage  On small units  less than 2 5  tons 8 8kW  ensure that unit pitch does not cause condensate  leaks inside the cabinet     Figure 1  Hanger Bracket    3 8   10mm  Threaded  Rod  by others             Vibration Isolator   factory supplied     Washer   by others        Double Hex Nuts   by others     Figure 2  Horizontal Unit Pitch    _L 1 4     6 4mm   r  for drainage          Connection    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       Ho
10.  1  Place unit in well lit area  Remove the screws as shown in  Figure 4 to free top panel and discharge panel    2   Liftoutthe access panel and set aside  Lift and rotate  the discharge panel to the other position as shown  being  careful with the blower wiring    3  Check blower wire routing and connections for tension or  contact with sheet metal edges  Reroute if necessary    4    Check refrigerant tubing for contact with  other components    5   Reinstall top panel and screws noting that the location for  some screws will have changed    6  M Manually spin the fan wheel to ensure that the wheel is  not rubbing or obstructed    7    Replace access panels     Back to Side Discharge Conversion   If the discharge is  changed from back to side  use above instruction noting that  illustrations will be reversed     Left vs  Right Return   It is not possible to field convert return  air between left or right return models due to the necessity of  refrigeration copper piping changes  However  the conversion  process of side to back or back to side discharge for either  right or left return configuration is the same  In some cases    it may be possible to rotate the entire unit 180 degrees if the  return air connection needs to be on the opposite side  Note  that rotating the unit will move the piping to the other end of the  unit     Field Conversion of Air D ischarge    Figure 4  Left Return Side to Back    Remove Screws    Water  Connection End         Move to Side    Replace 
11.  19  C  68  F  20  C  80 6 66 2  F  27 19  C  68  F  20  C  Max  entering air  DB WB 100 75 F  38 24 C 80  F  27  C 95 75  F  35 24  C 80  F  27  C  Water Limits  Min  entering water 30  F   1  C  20  F   6 7  C  30  F   1 C  20  F   6 7  C   Normal entering water 50 110 F  10 43 C    30 70 F   1 to 21  C    50 110  F  10 43 C  30 70  F   1 to 21 C   Max  entering water 120 F  49 C 90  F  32  C 120 F  49 C 90  F  32  C   1 5 to 8 0 gpm   ton 1 5 to 3 0 gpm   ton  Normal vate Clerk 1 6 to 3 2 Vm per kW 1 6 to 3 2 I   m per kW    Rev   20 May  2009S             Commissioning Conditions    Consult Table 8b for the particular model  Starting conditions vary depending upon model and are based upon the following  notes     Notes    1  Conditions in Table 8b are not normal or continuous operating conditions  Minimum maximum limits are start up conditions  to bring the building space up to occupancy temperatures  Units are not designed to operate under these conditions on a  regular basis    2  Voltage utilization range complies with AHRI Standard 110     Table 8b  Building Commissioning Limits    CER ed GT PX GT PG  Commissioning Limits Cooling Heating    Air Limits   Min  ambient air  DB 45  F  7  C  39  F  4  C   Rated ambient air  DB 80 6  F  27  C  68  F  20  C   Max  ambient air  DB 110  F  43  C  85  F  29  C   Min  entering air  DB WB  BO  F  10  C  40  F  4 5  C     Rated entering air  DB WB   80 6 66 2  F  27 19  C     Max  entering air  DB WB 110 83  F  43 28  C  Water Lim
12.  5  up to Max ESP shown with wet coil and standard 1  fiberglass filter   Do not select Dehumidification mode if HP CFM is on setting 1   All units AHRI ISO ASHRAE 13256 1 rated HP  Cooling  Delay  Heating  CFM Setting 3       Note  See the ECM Blower Control section for information on setting taps     Residential Packaged Units   60Hz Puron     Rev   4Jan   2012    GT PG  50YE  Series PSC Blower Performance D ata    Airflow in CFM with wet coil and clean air filter    Airflow  cfm  at External Static Pressure  in  wg        0 20    0 25    0 30    0 35    0 40    0 45    0 50    0 60    0 70       693    692    690    683    675    658    640    598       581    583    585    573    560    547       517    512    506    495    462       931    914    882    842    492    515       809    763    731       698    656       185       007       874       378                                                                   0 80   0 90   1 00    1856   1752       1670   1582                                     Black areas denote ESP where operation is not recommended   Units factory shipped on medium speed  Other speeds require field selection     All airflow is rated and shown above at the lower voltage if unit is dual voltage rated  e g  208V for 208 230V units                                      27    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       GT PG  50YE  Series ECM Blower Performance D ata    Residential  Airflow in CFM with wet coil and clean air f
13.  60Hz Puron     Rev   4 Jan   2012       Revision History    Date    Page       Description       4 Jan  11    Various    Deleted References to YEO70 with PSC motor       10 March  11    16    HWG Piping Drawings Revised       4 Oct   10    19    ECM Electrical Data Updated       29 July  10    Wiring Diagram  Pages    Wire Diagram revision  water side high pressure switches added       1 July  10    Various    Warranty  Nomenclature  Unit Photos Updated       14 June  10    Various    Compressor isolation upgrade from Springs to grommets       30 April  10    16    HWG Piping Drawings Revised       15 April  10    18    HWG Piping Length Table Added       30 Oct   09    45    Functional Troubleshooting Table Updated       15 Sept   09    30    Safety Features   CXM DXM Controls Section Updated       02 June  09    R22 Information Removed       01 Jan  09    Reformatted Document Size       21 Aug  07    Updated with Model 072 Information       01 Oct  06          First Published       ama      lh    ISO 9001 2000 P X   LisTEO    Certified  Quality  First  amp  Always PAL a  Intertek    97B0046N03       7300 S W  44th Street  Oklahoma City  OK 73179  Phone  405 745 6000  Fax  405 745 6058    The Manufacturer works continually to improve its products  As a result  the design and specifications of each product at the time for order may  be changed without notice and may not be as described herein  Please contact the Manufacturer s Customer Service Department at 1 405   745 6000 
14.  Air Temp  Drop   F  DB    Discharge  Pressure  PSIG    Superheat    Subcooling    Water   Temp   Drop  F       30     1 5  2 25  3    112 122  111 121  111 121    187 207  167 187  147 167    22 27  22 27  23 28    14 19  1247  11 16    20 7 22 7  5 5 17 5  0 2 12 2    18 24  18 24  18 24    66 76  69 79  72 82    286 306  289 309  292 312    7 12  7 12  7 12    8 10  6 8  4 6       1 5  2 25  3    125 135  123 133  122 132    242 262  224 244  205 225    13 18  13 18  14 19    10 15  9   7     20 9 22 9  5 6 17 6  0 2 12 2    19 25  19 25  19 25    93 103  98 108  103 113    314 334  320 340  326 346    8 13  8 13  8 13    11 5 13 5  8 7 10 7    5 9 7 9       1 5  2 25  3    133 143  132 142  131 141    310 330  290 310  270 290    8 13  8 13  9 14    8   T   5     20 5 22 5  5 2 17 2  9 9 11 9    19 25  19 25  19 25    123 133  130 140  137 147    344 364  354 374  361 381    9 14  9 14  9 14    15 17    11 5 13 5    7 9 9 9       1 5  2 25  3    138 148  137 147  136 146    396 416  374 394  352 372    7 12  7 12  7 12    7     9 2 21 2  4 3   9 3 1    18 24  18 24  18 24    165 175  175 185  185 195          1 5  2 25  3    144 154  143 153  142 152    497 517  472 492  447 467        Based on 15  Methanol antifreeze solution    7 12  7 12  1 12           o 9    2mjlomo ms          18 20  3 3 15 3  8 5 10 5             17 23  17 23  17 23       390 410  401 421  413 433       13 18  15 20  17 22             19 6 21 6    15 17    10 3 12 3          37    Residential Packa
15.  PG Units Aux Emerg Heat settings  GT PX and GT PG Units  Version   Version Il 17B0019N01 Version   Version Il 17B0019N01 Version    Version Il 17B0019N01  69243707  Version Ill 17BO034N01  AUX CFM DIP Switch  Setting         CFM Adjust settings  GT PX and GT PG Units Dehum Mode settings  GT PX and GT PG Units  Version   Version Il 17B0019NO1 Version   Version Il 17B0019NO1    CFM Adj DIP Switch Dehumid DIP Switch    Jumper W9  O  F    Dehumid pins 2 3 OF       Figure 26b  ECM Version   Interface Layout                                                                                                                                                                                                    1 4  Spade  pomeren E T 1 4  Spade  o or ermostal E  DXM Board Input LEDs  gt  Connections  r to CXM or  DXM Board  l    Thermostat  G Y  Ty je  Input LEDs  CFM Counter CFM Counter  Thermostat 1 flash per 100 CFM Sl  1 flash per 100CF  Connections Thermostat X iw  Connections ojo  ECM Motor oje ECM Motor  2 Low Voltage Eje z    Low Voltage  D Connector Blas Connector  D prs  D         Se    vie El  Dehumidification       2 z   E  D 3   ooojj sz ooojjis  S oooQj s  ooolg s    g Ol    frt    Dehumidification  EMS PES  noe LED  z ooologlez  ooo ol e  ooolgs     ooolgl    Fan Speed Selection DIP Switch             Fan Speed Selection Jumpers    Figure 26c  ECM Version Ill Interface Layout    Compressor Dehumidification  HWG LED Discharge Sensor Hot Water Sensor LED    1 4  Spade  Pei ECM M
16.  after  20 minutes     CXM Troubleshooting Process Flowchart Functional   Troubleshooting Chart   The    CXM Functional Troubleshooting Process Flowchart      is a quick overview of how to start diagnosing a suspected   problem  using the fault recognition features of the CXM   board  The    Functional Troubleshooting Chart    on the   following page is a more comprehensive method for   identifying a number of malfunctions that may occur  and is   not limited to just the CXM controls  Within the chart are five   columns      The    Fault    column describes the symptoms      Columns 2 and 3 identify in which mode the fault is likey to  occur  heating or cooling      The  Possible Cause column  identifies the most likely  sources of the problem      The  Solution  column describes what should be done to  correct the problem     A WARNING  A    WARNING  HAZARDOUS VOLTAGE  DISCONNECT  ALL ELECTRIC POWER INCLUDING REMOTE    DISCONNECTS BEFORE SERVICING   Failure to disconnect power before servicing can cause  severe personal injury or death        43    44    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012    CXM Process Flow Chart       A WARNING  A    WARNING  HAZARDOUS VOLTAGE  DISCONNECT  ALL ELECTRIC POWER INCLUDING REMOTE    DISCONNECTS BEFORE SERVICING   Failure to disconnect power before servicing can cause  severe personal injury or death         Start  CXM Functional  Troubleshooting Flow Chart    Did Unit Check Main    Attempt to power  see power  Start  
17.  and Temperatures  026    Entering  Water  Temp   oF    Water  Flow  GPM ton    Full Load Cooling   without HWG active    Full Load Heating   without HWG active       Suction  Pressure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water  Temp  Rise  oF    Air Temp   Suction  Drop  F   Pressure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water   Temp   Drop  oF       18   18   18     28  28    159 179  146 166  132 152    6 7 18 7  2 3 14 3  7 9 9 9    72 83  75 85  78 88    273 293  275 295  277 297    5 9 7 9  4 2 6 2  2 7 4 7       28   28     186 206  172 192  158 178    6 3 18 3  2 1 14 1  7 8 9 8    102 112  106 116  110 120    302 322  303 323  305 325    8 9 10 9  6 7 8 7  4 5 6 5       281 301  267 287  253 273    5 7 17 7  1 6 13 6  7 6 9 6    128 138  134 144  141 151    330 350  332 352  334 354    11 3 13     8 5 10 5    5 8 7 8    3       368 388  354 374  340 360    4 9 16 9  11 13  7 2 9 2    162 172  166 176  171 181                   465 485  450 470  433 453        Based on 15  Methanol antifreeze solution          3 9 15 9  0 2 12 2  6 5 8 5          Full Load Cooling   without HWG active             367 387  372 392  377 397             14 4 16   10 8 12   7 1 9 1       Full Load Heating   without HWG active    4  8          Entering  Water  Temp   oF    Water  Flow  GPM ton    Suction  Pressure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water  Temp  Rise  oF    Air Temp   Suction  Drop   F   Pr
18.  as follows   HR  TD x GPM x 500  where TD is the temperature  difference between the entering and leaving water   and GPM is the flow rate in U S  GPM  determined  by comparing the pressure drop across the heat  exchanger to Tables 9a through 9b    f  Check air temperature drop across the air coil when  compressor is operating  Air temperature drop should  be between 15  F and 25  F  8  C and 14  C     g  Turn thermostat to    OFF    position  A hissing noise  indicates proper functioning of the reversing valve     6  Allow five  5  minutes between tests for pressure to    equalize before beginning heating test    a  Adjust the thermostat to the lowest setting  Place the  thermostat mode switch in the    HEAT    position    b  Slowly raise the thermostat to a higher temperature  until the compressor activates    c  Check for warm air delivery within a few minutes after  the unit has begun to operate    d  Referto Table 10  Check the temperature of both  entering and leaving water  If temperature is within  range  proceed with the test  If temperature is outside  of the operating range  check refrigerant pressures  and compare to Tables 11 through 12  Verify correct  water flow by comparing unit pressure drop across  the heat exchanger versus the data in Tables 9a  through 9b  Heat of extraction  HE  can be calculated  and compared to submittal data capacity pages  The  formula for HE for systems with water is as follows   HE  TD x GPM x 500  where TD is the temperature  diff
19.  be changed  For airflow  charts  consult specifications catalog for the series and  model of the specific unit     If the unit is connected to existing ductwork  a previous  check should have been made to insure that the ductwork  has the capacity to handle the airflow required for the unit   If ducting is too small  as in the replacement of a heating  only system  larger ductwork should be installed  All existing  ductwork should be checked for leaks and repaired as  necessary     Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012       Vertical Unit Location   Units are not designed for outdoor installation  Locate   the unit in an INDOOR area that allows enough space for  service personnel to perform typical maintenance or repairs  without removing unit from the mechanical room closet   Vertical units are typically installed in a mechanical room   or closet  Never install units in areas subject to freezing or  where humidity levels could cause cabinet condensation   such as unconditioned spaces subject to 100  outside air    Consideration should be given to access for easy removal of  the filter and access panels  Provide sufficient room to make  water  electrical  and duct connection s      If the unit is located in a confined space  such as a closet   provisions must be made for return air to freely enter the  space by means of a louvered door  etc  Any access panel  screws that would be difficult to remove after the unit is  installed should be removed prio
20.  clogging should be referenced in Table 3     Pressure Tank and Pump   Use a closed  bladder type pressure tank to minimize  mineral formation due to air exposure  The pressure tank  should be sized to provide at least one minute continuous  run time of the pump using its drawdown capacity rating to  prevent pump short cycling  Discharge water from the unit  is not contaminated in any manner and can be disposed  of in various ways  depending on local building codes  e g   recharge well  storm sewer  drain field  adjacent stream   or pond  etc    Most local codes forbid the use of sanitary  sewer for disposal  Consult your local building and zoning  department to assure compliance in your area    The pump should be sized to handle the home s domestic  water load  typically 5 9 gpm  23 41 I m   plus the flow rate  required for the heat pump  Pump sizing and expansion  tank must be chosen as complimentary items  For example   an expansion tank that is too small can causing premature  pump failure due to short cycling  Variable speed pumping  applications should be considered for the inherent energy  savings and smaller pressure tank requirements     Water Control Valve   Note the placement of the water control valve in figure 13   Always maintain water pressure in the heat exchanger by  placing the water control valve s  on the discharge line   to prevent mineral precipitation during the off cycle  Pilot  operated slow closing valves are recommended to reduce  water hammer  If w
21.  illustrate typical slow closing water control valve  wiring for Taco 500 series  ClimateMaster P N AVM      and Taco SBV series valves  Slow closing valves take  approximately 60 seconds to open  very little water will flow  before 45 seconds   Once fully open  an end switch allows  the compressor to be energized  Only relay or triac based  electronic thermostats should be used with slow closing  valves  When wired as shown  the slow closing valve will  operate properly with the following notations     1  The valve will remain open during a unit lockout    2  The valve will draw approximately 25 35 VA through the     Y    signal of the thermostat   Note  This valve can overheat the anticipator of an  electromechanical thermostat  Therefore  only relay or  triac based thermostats should be used     Two stage Units   Tranquility 27     TT  two stage units should be designed with  two parallel valves for ground water applications to limit water  use during first stage operation  For example  at 1 5 gpm   ton  2 0 I m per kW   an 049 unit requires 6 gpm  23 l m  for  full load  2nd stage  operation  but only 4 gpm  15 l m  during  1st stage operation  Since the unit will operate on first stage  80 90  of the time  significant water savings can be realized  by using two parallel solenoid valves with two flow regulators   In the example above  stage one solenoid would be installed  with a 4 gpm  15 l m  flow regulator on the outlet  while stage  two would utilize a 2 gpm  8 l m  f
22.  line  WHEN A VENT IS INSTALLED IN THE DRAIN LINE  IT  MUST BE LOCATED AFTER THE TRAP IN THE DIRECTION  OF THE CONDENSATE FLOW     Figure 6  Horizontal Condensate Connection        3 4  FPT        Trap Depth  1 5   38mm  s eR  94 PMG OE Os  Copper by others  21 s per m   drain slope    Some units include a painted drain  connection  Using a threaded pipe or  similar device to clear any excess paint  accumulated inside this fitting may  ease final drain line installation  Rev   4 30 10B    A CAUTION  A    CAUTION  Ensure condensate line is pitched toward  drain 1 4 inch per ft  21mm per m  of run        DUCT SYSTEM INSTALLATION    Duct System Installation   The duct system should be sized to handle the design  airflow quietly  Refer to Figure 3 for horizontal duct system  details or figure 8 for vertical duct system details  A flexible  connector is recommended for both discharge and return  air duct connections on metal duct systems to eliminate   the transfer of vibration to the duct system  To maximize  sound attenuation of the unit blower  the supply and return  plenums should include internal fiberglass duct liner or be  constructed from ductboard forthe first few feet  Application  of the unit to uninsulated ductwork in an unconditioned  space is not recommended  as the unit s performance will be  adversely affected     At least one 90  elbow should be included in the supply  duct to reduce air noise  If air noise or excessive air flow is  a problem  the blower speed can
23.  pump is forced to operate even if there   is no call for the HWG  This mode may be beneficial to  assist in purging the system of air during Initial start up   When SW10 is in the  OFF  position  the HWG will operate  normally  This switch is shipped from the factory in the   OFF   normal  position  NOTE  If left in the  On  position for  5 minutes  the pump control will revert to normal operation     SW11 HWG TEMP  The control setpoint of the HWG can  be set to either of two temperatures  125  F or 150  F  When  SW11 is in the    ON    position the HWG setpoint is 150  F   When SW11 is in the  OFF  position the HWG setpoint is    A WARNING  A    WARNING  USING A 150  F SETPOINT ON THE   HWG WILL RESULT IN WATER TEMPERATURES  SUFFICIENT TO CAUSE SEVERE PHYSICAL INJURY  IN THE FORM OF SCALDING OR BURNS  EVEN  WHEN THE HOT WATER TANK TEMPERATURE  SETTING IS VISIBLY SET BELOW 150  F  THE 150  F  HWG SETPOINT MUST ONLY BE USED ON SYSTEMS  THAT EMPLOY AN APPROVED ANTI SCALD VALVE   PART NUMBER AVAS4  AT THE HOT WATER  STORAGE TANK WITH SUCH VALVE PROPERLY  SET TO CONTROL WATER TEMPERATURES  DISTRIBUTED TO ALL HOT WATER OUTLETS ATA  TEMPERATURE LEVEL THAT PREVENTS SCALDING  OR BURNS        Hot W ater Generator    ANTI SCALD         COLD WATER  VALVE PIPING SUPPLY  CONNECTIONS CHECK VALVE  ANTI SCALD    VALVE Ne    HOT WATER  TO HOUSE    WATER HEATER    125  F  This switch Is shipped from the factory in the  OFF    125  F  position     SW12 HWG STATUS  This switch controls operatio
24.  static  0 15 in  w g   37P a  on medium  speed and rated airflow at a higher static  0 4 to 0 5 in  w g    100 to 125 Pa   on high speed for applications where higher  static is required  Low speed will deliver approximately 8596  of rated airflow at 0 10 in  w g   25 Pa         Figure 16  GT PX GT PG Single Phase Line Voltage  Field Wiring    un    Unit Power Supply   see electrical table for wire  and breaker size     Special Note for AHRI Testing  To achieve rated airflow for  AHRI testing purposes on all PSC products  it is necessary  to change the fan speed to  HI  speed  When the heat pump  has experienced less than 100 operational hours and the coil  has not had sufficient time to be  seasoned   it is necessary  to clean the coil with a mild surfactant such as Calgon to  remove the oils left by manufacturing processes and enable  the condensate to properly  sheet  off of the coil     Figure 17  PSC Motor Speed Selection    Connect the blue wire to   H for High speed fan    M for Medium speed fan  Blu eee L for Low speed fan  Medium is factory setting         Fan Motor    HWG Wiring  Split Units Only    The hot water generator pump power wiring is disabled at  the factory to prevent operating the HWG pump    dry     After  all HWG piping is completed and air purged from the water  piping  the pump power wires should be applied to terminals  on the HWG power block PB2 as shown in the unit wiring  diagram  This connection can also serve as a HWG disable  when servicing t
25.  uonrod10   JOLTED   q oper sjuourayis  uere v se poynuopt K eoyroods st juouroyois v ssopun yey poojsropun    ssoxdxo st I     HONVMOTTV 3IOSV I HLIA SLOQGO Id TWWAAHLOWD  amp    IVILNCIGIS  TI XOA ALT TIISVE I ANV SHIQHIASESI AO NOLLVILEATT A LNV PPIVM SSH2Id XH AALIWIT  NOLLV IOd 1IOO AAINAVO    QQ QQ vvv vovv 0009009000090 c    9  99   9999    9  9  9    9  98 99 9999    M ah P6 P P P P P a P P P P ul og uf ad of SSS ul o uf ud P ul od f ad SESS P ul o DOGG XARA AA AAA AAA AeA    9 6064606404004004004000040000400406040040600000000000000 0     1000000000000    9900 06 00  0 0 0 010    Bee 002000200 00 99 9 99 9 P PP PP PP PPP    86 6 0 00 0 000 80 00 0 000 0 00 0 0 00 0 000 0 0 0 0 0 6 0 0 00 0 0 0 0 0 0 0 0 0 00 0 0 00 0 0 0 0 00 0 0   eg 09999999999999999999999999999900          9 999 9 9 99     9 9 9 9          0 9  QUNM MM P X  lF ll I vg NNOOOOERSOCE SERES  9 664064004000409090409004000040900409004090409 5000000005050       Q  cS  cS  CS  CS  CS  CS  CS  CS  CS  CS  CS  CS  dm   CS  CS  CS  CS  cS  cS  cS  cS      CS  CS  CS  CS  CS  CS  CS  CS  CS  C    or  C2  C2                                                                                                     or        e       48    Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012       N otes    49    Resident  Rev   4Jan   20       N otes    50    ial Packaged Units   60Hz Puron   12    Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012       N otes    51    Residential Packaged Units  
26.  with ALL applicable  codes and regulations     Vertical Installation    Figure 7  Vertical Unit Mounting                      Air Pad or extruded  polystyrene insulation board    B                Figure 8  Typical Vertical Unit Installation Using Ducted  Return Air    Internally insulate supply      duct for first 1 2 m each way    to reduce noise         Use turning vanes in  supply transition        Flexible canvas duct        connector to reduce  noise and vibration    __ Rounded return  transition                      Rev   6 2 09S       Internally insulate return  transition duct to reduce  noise    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       Vertical Installation    Sound Attenuation for Vertical Units   Sound attenuation Condensate Piping for Vertical Units   Vertical units utilize   is achieved by enclosing the unit within a small mechanical a condensate hose inside the cabinet as a trapping loop    room or a closet  Additional measures for sound control therefore an external trap is not necessary  Figure 10a shows   include the following  typical condensate connections  Figure 10b illustrates the   1  Mount the unit so that the return air inlet is 90   to the internal trap for a typical vertical heat pump  Each unit must be  return air grille  Refer to Figure 9  Install a sound baffle installed with its own individual vent  where necessary  and a  as illustrated to reduce line of sight sound transmitted means to flush or blow out the condensa
27. 1 5VAC  Over under voltage shut down is a   self  resetting safety  If the voltage comes back within range   for at least 0 5 seconds  normal operation is restored  This is   not considered a fault or lockout  If the CXM is in over under   voltage shutdown for 15 minutes  the alarm relay will close    Over under voltage shut down code  7   Unit Performance Sentinel UPS  patent pending   The UPS   feature indicates when the heat pump is operating inefficiently    A UPS condition exists when    a  In heating mode with compressor energized  FP2 is  greater than 125  F  52  C  for 30 continuous seconds  or    b  In cooling mode with compressor energized  FP1 is  greater than 125 F  52 C  for 30 continuous seconds  or    c  In cooling mode with compressor energized  FP2 is less  than 40  F  4 5  C  for 30 continuous seconds  If a UPS  condition occurs  the control will immediately go to UPS  warning  The status LED will remain on as if the control  is in normal mode  Outputs of the control  excluding LED  and alarm relay  will NOT be affected by UPS  The UPS  condition cannot occur during a compressor off cycle   During UPS warning  the alarm relay will cycle on and  off  The cycle rate will be  on  for 5 seconds   off  for 25  seconds   on  for 5 seconds   off  for 25 seconds  etc    UPS warning code  8   Swapped FP1 FP2 thermistors  During test mode  the control   monitors to see if the FP1 and FP2 thermistors are in the   appropriate places  If the control is in test mode  the 
28. 1d 1201 Woy po1opio  sjonpoad Aue 01 oArovorjar jou sr pur     AOI pue AOT ZC   WM Suruursoq sroqumu  eros qr SHUN PEULO JOLTED opnyour K pr9uo8 prnom STL  OTOZ  T ATE 49v 10 uo 1o1e   WOI pozopzo sjonpoid  eunoq1008  eriuoprso1 10nv   o  sordde Kuere ssaidxgp posu smi      eouvuojureur  PULIOU JO sjs00 oq   p  10  jueireA  ssoudxzp poyrurT s  1orzv   Aq paroAoo jou j1 ped Jey  jo UMIA OY  JO JO ALL 03 NIS uone  ejsur oq  WOI Jed oAr9jop ou  s1s00 uoneyodsuery   c   ued pouredo  10 mau oq  Surovjdo1 pue Surureygo ur 10  1ed 2An29jop oq JO LAOU pue sisouSerp ur po1mour 2orAJos JO s eriojeur  jue19811o1 IOE JO s soo oq   Z       ueare M ssaidxg poytur s  1or1m     q po19400 Led 2Arj29jop v Jo 3jnso1 v se pormour  SI gory    oures oq oov do1 10 aredar 0  10qe  poreroosse 10  s1ogjo   q porjddns syuouoduioo urojs amp s 10 jueroSr1jo1    spiny Aue jo sjs00 oq   T  OF o qisuodsoz jou ST ILIV    OsTMIDYIO   2A0q  YUOJ 195 9319400 douBMoy e Joey poji ay  soprAo1d AjuvamA  ssoidxqp porwr sni      JoA90S 0 A Uosvar   ue 10   oures ur sSurAvs pozi varun 1o sosvo1our Ku 10  sjsoo  ong 10   A  c1  40  sjonpoid s  1oruve   Jo osn 10    uoneresur  uoreorjdde 1odo1duir 10 ustsop urojsKs 10dodurr jo ynsor v se oouvunro prod juorognsur SAY YOIyA sjonporg  Z1    uononrgsur pojurid s  Jorame   0  Arenuoo uue v ur poyerodo uooq oat  YM stonporg  TT     S190   q porjddns sjonporg  01   ionpoid oq jo uorseiqe 10 uorso10    6   soSvurep vr1ojoeq 10 snunj    pro  8    ouuoszod poyrpenbun   q 1oaro ju
29. 6 5 8 5 16 22       Air Temp  Rise   F DB                                                        Based on 15  Methanol antifreeze solution    38    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012    Unit O perating Conditions    Table 12  GT PG Series Typical Unit Operating Pressures and Temperatures  Continued  024    Full Load Cooling   without HWG active    Full Load Heating   without HWG active       Entering  Water  Temp F    Water  Flow  GPM ton    Suction  Pressure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water  Temp Rise  oF    Air Temp  Drop   F  DB    Suction  Pressure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water  Temp Drop  oF    Air Temp  Rise   F DB       30     1 5  2 25    115 125  115 125  115 125    154 174  141 161  127 147    40 45  40 45  40 45    8 13  6 11  6 11    16 5 18 5  12 1 14 1  77 7 9 7    19 25  20 26  20 26    73 83  75 85  78 88    283 303  285 305  287 307    8 12  8 12  8 12    aaa    5 9 7 9  4 2 6 2  2 7 4 7    16 22  17 23  18 24       115 120  115 120  115 120    209 229  195 215  181 201    24 29  24 29  24 29    10 15  8 13  8 13    15 7 17 7  11 6 13 6  7 6 9 6    18 24  18 24  18 24    102 112  106 116  110 120    313 333  314 334  316 336    8 12  8 12  8 12    8 9 10 9  6 7 8 7  4 5 6 5    22 28  23 29  23 29       136 146  136 146  136 146    275 295  261 281  247 267    6 11  6 11  6 11    6 11  5 10  4 9    15 74 7 7  11 6 13 6  7 6 9 6    18 24  18 24  18 24    12
30. 69 489  448 468          427 447     Based on 15  Methanol antifreeze solution    048    6 11  6 11       6 11    6 11  5 10  4 9       14 16  11 13  7 9       16 22  16 22  16 22    Full Load Cooling   without HWG active    175 185  177 187  180 190    393 413  401 421  409 429          19 24  20 25  22 27       17 6 19 6  13 2 15 2  8 7 10 7       36 42  37 43  38 44          Full Load Heating   without HWG active       Entering  Water  Temp F    Water  Flow  GPM ton    Suction  Pressure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water  Temp Rise  oF    Air Temp  Drop   F  DB    Suction  Pressure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water  Temp Drop  F    Air Temp  Rise F  DB       30     1 5  2 25    108 118  107 117  107 117    180 200  161 181  142 162    27 32  28 33  29 34    12 17  10 15  9 14    19 8 21 8  14 8 16 8  9 8 11 8    19 25  19 25  19 25    65 75  68 78  72 82    293 313  297 217  301 321    7 12  8 13  9 14    9 14  9 14  9 14    8 2 10 2  6 2 8 2  4 2 6 2    17 23  18 24  19 25       123 133  122 132  122 132    236 256  218 238  200 220    16 21  17 22  17 22    8 13  7 12  6 11    20 2 22 2  15 2 18 2  10 2 12 2    21 27  21 27  21 27    92 102  100 110  108 118    321 341  330 350  340 360    10 15  11 16  12 17    11 16  11 16  11 16    11 6 13 6  8 9 10 9  6 8    23 29  24 30  26 32       130 140  129 139  129 139    305 325  285 305  265 285    10 15  11 16  11 16    8 13  6 11  5 10    20 22  15 17
31. 8 138  134 144  141 151    340 360  342 362  344 364    9 14  9 14  9 14    11 3 13 3  8 5 10 5  5 8 7 8    27 34  28 35  28 35       140 150  140 150  140 150    361 381  347 367  333 353    6 11  6 11  6 11    6 11  5 10  4 9    14 9 16 9  11 13  7 2 9 2    18 24  18 24  18 24          144 154  144 154  144 154    460 480  445 465  428 448        Based on 15  Methanol antifreeze solution       6 11  6 11  6 11       6 11  4 9  4 9       13 9 15 9  10 2 12 2  6 5 8 5       17 23  17 23  17 23    Full Load Cooling   without HWG active    162 172  166 176  171 181       370 390  376 396  383 403       14 19  15 20  16 21       eee ooeo ooo ooo  ARRRBRROOO       14 4 16 4  10 8 12 8  7 1 9 1       32 40  84 42  84 42       Full Load Heating   without HWG active       Entering  Water  Temp   F    Water  Flow  GPM ton    Suction  Pressure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water  Temp Rise  oF    Air Temp  Drop   F  DB    Suction  Pressure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water  Temp Drop  oF    Air Temp  Rise   F  DB       30     1 5  2 25    116 126  115 125  115 125    146 166  138 158  128 148    27 32  27 32  27 32    7 13  6 11  6 11    19 6 21 6  14 3 16 3  8 10    16 22  17 23  17 23    69 79  73 83  76 86    275 295  277 297  279 299    7 12  7 12  7 12    6 11  6 11  6 11    7 2 9 2  5 4 7 4  3 5 5 5    16 22  17 23  17 23       129 139  128 138  128 138    217 237  203 223  189 209    6 11  5 10  5 10    20 
32. 8 22 8  15 17  9 2 11 2    17 23  18 24  18 24    96 106  100 110  105 115    300 320  304 324  309 329    10 15  10 15  10 15    9 14  9 14  9 14    10 5 12 5  7 6 9 6  4 8 6 8       132 142  131 141  131 141    293 313  274 294  256 276    6 11    20 1 22 1  14 4 16 4  8 6 10 6    17 23  18 24  18 24    123 133  129 139  135 145    327 347  333 353  339 359    11 16  11 16  11 16    11 16  11 16  11 16    13 2 15 2  9 8 11 8  6 4 8 4       137 147  137 147  137 147    383 403  362 382  342 362    19 4 21 4  13 8 15 8  8 2 10 2    16 22  16 22  16 22          143 153  143 153  143 153    475 495  457 477  439 459        Based on 15  Methanol antifreeze solution    036          18 2 20 2  13 14  7 7 9 7          16 22  16 22  16 22    Full Load Cooling   without HWG active    155 165  162 172  169 179    355 375  362 382  369 389       13 18  14 19  16 21       11 16  11 16  11 16          16 8 18 8  12 7 14 7  8 6 10 6       Full Load Heating   without HWG active       Entering  Water  Temp F    Water  Flow  GPM ton    Suction  Pressure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water  Temp Rise  F    Air Temp  Drop F  DB    Suction  Pressure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water  Temp Drop  oF    Air Temp  Rise   F  DB       30     1 5  2 25    117 127  116 126  116 126    142 162  134 154  124 144    33 38  33 38  33 38    8 14  7 12  7 12    19 3 21 1  13 8 15 8  7 4 9 4    15 22  15 22  15 22    69 79  73 83  76 86  
33. C  Clip JW3 jumper for antifreeze  10  F   12 C   use   B  Ci  Cl  Cl    heck fan motor operation and airflow restrictions        Too high of external static  Check static vs blower table        Air Temperature out of range    Too much cold vent air  Bring entering air temp within design parameters        Improper temperature limit setting  30  F vs  10  F   1 C vs  12 C      Normal airside applications will require 30  F   1   C  only        Bad thermistor  Blocked drain    heck temp and impedance correlation per chart   heck for blockage and clean drain        Improper trap       Poor drainage    heck for piping slope away from unit        heck slope of unit toward outlet        C  C  Check trap dimensions and location ahead of vent   C  C  P    oor venting  Check vent location        Moisture on sensor       Plugged air filter    Check for moisture shorting to air coil   Replace air filter        Restricted Return Air Flow    Under Voltage    ind and eliminate restriction  Increase return duct and or grille size   power supply and 24VAC voltage before and during operation        power supply wire size        compressor starting  Need hard start kit        24VAC and unit transformer tap for correct power supply voltage        Over Voltage  Heating mode LT2 gt 125  F  52  C     power supply voltage and 24VAC before and during operation        24VAC and unit transformer tap for correct power supply voltage   heck for poor air flow or overcharged unit        Cooling Mode LT1 g
34. F   Temp   F   GPM ton PSIG PSIG oF DB PSIG PSIG  F DB   i 110 120 177 197 36 41 15 20 20 2 22 2 21 27 61 71 290 310 12 18 9 14 8 10 19 25   30  a 109 119 162 182 37 42 13 18 15 17 21 27 65 75 292 312 12 18 10 15 6 8 20 26   107 117 147 167 38 43 11 16 9 7 11 7 22 28 68 78 296 316 12 18 10 15 4 6 21 27    128 138   246 266 18 23 11 16 21 23 22 28 88 98 320 340 11 17 13 18 11 7 13 7 26 32  128 138   228 248 19 24 9 14 15 6 17 6 23 29 96 106 330 350 11 17 11 16 9 11 27 33  127 137   210 230 20 25 6 11 10 2 12 2 24 30 105 115   338 358 11 17 9 14 6 8 29 35    134 144   305 325 9 14 11 16 20 8 22 8 23 29 118 128   355 375 10 16 14 19 15 2 17 2 33 39  133 143   289 309 9 14 9 14 15 4 17 4 23 29 130 140   368 388 12 18 13 18 11 7 13 7 35 41  131 141   273 293 9 14 6 11 10 12 23 29 141 151   380 400 15 21 11 16 8 10 37 43    140 150   390 410 10 15 11 16 19 6 21 6 22 28 158 168   401 421 9 15 13 18 19 5 21 5 41 47  139 149   373 393 10 15 9 14 14 5 16 5 168 178   412 432 10 16 12 17 14 8 16 8 43 49  138 148   355 375 10 15 6 11 9 3 11 3 178 188   423 443 12 18 12 17 10 12 45 51    144 154   488 508 10 15 9 14 18 4 20 4  143 153   468 488 10 15 6 11 13 6 15 6  142 152   448 468 9 14 5 10 8 8 10 8                                                        Based on 15  Methanol antifreeze solution    42    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       Preventive Maintenance    Water Coil Maintenance    Direct ground water applications only    If the system is  install
35. GT PX Series  50YDV  50YDH  50YDD Models  GT PG Series   SOYEV  50 YEH  50YED Models     Installation  Operation and Maintenance Instructions    Residential Horizontal  amp  Vertical Packaged  Geothermal Heat Pumps         97B0046N03  Revised 4 Jan   2012    Table of Contents    Model Nomenclature Water Valve Wiring  Storage Thermostat Wiring  Pre Installation ECM Blower Control    Horizontal Installation Blower Data    Field Conversion of Air Discharge CXM Controls  Duct System Installation CXM Control Features    Condensate Piping Installation Unit Commissioning  Vertical Installation and Operating Conditions    Water Connections Unit and System Checkout    Ground Loop Applications Unit Start Up Procedure  Open Loop   Ground Water Systems Unit Operating Conditions  Water Quality Standards Preventive Maintenance  Hot Water Generator Troubleshooting   Electrical   Line Voltage Functional Troubleshooting  Electrical   Power Wiring Troubleshooting Form  Electrical   Low Voltage Wiring Warranty   Low Water Temperature Cutout Selection Revision History    This page was intentionally left blank     Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       Model Nomenclature  General O verview    1  32 3 5     SJ  VE  IV  OY 2T4                                            UNIT TYPE  SIZE   YE   GT PG SINGLE STAGE PURON   REFRIG 018    YD   GT PX TWO STAGE PURON   REFRIG  M    036  CONFIGURATION  e  V   VERTICAL UPFLOW 060  H   HORIZONTAL     072  D   VERTICAL DOWNFLOW    A
36. IR FLOW CONFIGURATION   ECM     AIR FLOW CONFIGURATION   PSC     PACKAGING   1   SINGLE PACK  DOMESTIC    REVISION LEVEL   1   CURRENT REVISION    VOLTAGE   3   208V  230V 1PH 60Hz       VERTICAL UPFLOW 50YD 50YE ONLY     OPTION   RETURN   DISCHARGE   MOTOR    VERTICAL UPFLOW    OPTION   RETURN   DISCHARGE   MOTOR    HEAT EXCHANGER OPTIONS   COATED AIR COIL       STANDARD       J LEFT TOP  K RIGHT  TOP    TOP PSC  TOP PSC    W HOT WATER GENERATOR       VERTICAL DOWNFLOW 50YD 50YE ONLY  VERTICAL DOWNFLOW    OPTION   RETURN   DISCHARGE   MOTOR    RETURN   DISCHARGE   MOTOR    WHOLE HOUSE DEHUMIDIFICATION    WHOLE HOUSE DEHUMIDIFICATION  W HOT WATER GENERATOR       J LEFT DOWN  K RIGHT  DOWN    DOWN PSC  DOWN PSC       HORIZONTAL 50YD 50YE ONLY     OPTION   RETURN   DISCHARGE   MOTOR    HORIZONTAL    RETURN   DISCHARGE   MOTOR    CONTROLS   C   CXM       N RIGHT LEFT  P RIGHT  BACK  w                NOTE  YEV070 not available with PSC motor       LEFT RIGHT  LEFT BACK    NOTE  Some options configurations not available on all series  Please consult Specification Catalogs for model specific options     Safety    Warnings  cautions and notices appear throughout this  manual  Read these items carefully before attempting any  installation  service  or troubleshooting of the equipment     DANGER  Indicates an immediate hazardous situation  which    if not avoided will result in death or serious injury  DANGER  labels on unit access panels must be observed     WARNING  Indicates a pote
37. LIAYIOIH orae  jo sjusuoduroo JMN JULIJA po eos  c  pue    oyeq uondooug AueumeM IY  WOI sivo  Z  OM  10     SHUN  RULIDYIOAH Jorv   WIM  po  oisur uoqA    nep   q pros 10  mq so npour Surdurd peusoyjoos pue s1ojeog oroopo Krerny  Z     q uondooug ALAA oq WOI SIV    Z  0 1 10  SHUN JEUN 1orue    T   sA o  0j se  uo pue juour redo   ueIwm s  Iouo   q poprAoid o npous oouvAo pe Joqvi  Sunsrxo uot oq ur q19J Jos Ajveogroods juojxo ou 0  ATUO Aue  ssadxg poi  si Aq paroAoo sr jeu Hed AjuvueA poiredo  JO MoU v jo uonvujsut oq  YIM uoroouuoo ur  ouuos1od oorAos pozrogine IILI Aq pounour JOge  IP 1900  Jes uere ssoidxq pojrurT stg     pouod Kyuexre  eurduo oq  jo puo  oq w sondxo Ajuem 1opun poov dor 10 poaredo  ued Aue uo Kueuem oq    predaid 443121   euroqepio    AND eurogepio URI   gO  uonvzrues1o IAI 10 1o eop    IO NGLASIP pozru02o1 K1019j t 0  tns umo    pastedas 10 poov doz IYN uooq seq ied qons UYM    feys IURI     Queue ssaidxr porum s 19ruv   UYUM pue 9An29jop oq 0  Ped og  souruojop JOLTED JI    aed oy  Jo omn mj ou  jo IWP ou 19   s amp ep  06  Hutu uey 197 ou  predoid 303101   euroqepio    AUD euroqeprO ur IHO 0  poungo1 oq jsnur syed  juvrm srt 1opun uro v ILU OL       ISIH souroo J9A9QoIQA LVH WOI juouidrgs jrun Jo ojep uro3j squou  9  xrs 10  uonv pejsur JUN  eUTSIIO Jo ALP ou 9q  Teus IWA uondooug Aue  IYL TILO Woy   quourdrys jo ojp ot WO1     T  ouo 10     SHUN  euroqoos  IOUT YUM paesu UYM JLN   q p os 10  mq syed pue sorossooov 1900  p  pue     mojaq pougop se  
38. PSIG PSIG                                                        Based on 15  Methanol antifreeze solution    072 Full Load Cooling   without HWG active Full Load Heating   without HWG active  Entering   Water Water Water    Du   rew Pressure   Pressure   Superheat   Subcooling anga Pressure   Pressure   Superheat   Subcooling EE   Temp   GPM  Rise Drop  PSIG PSIG PSIG PSIG   ar ton F F   119 129 155 175 25 30 18 20 61 71 292 312 11 16 13 18 7 2 9 2   117 127 150 170 25 30 13 2 15 2 65 75 296 316 11 16 14 19 5 4 7 4   115 125 144 164 28 32 8 4 9 4 68 78 300 320 10 15 15 20 3 5 5 5    131 141 210 230 10 15 18 5 20 5 89 99 327 347 10 15 19 24 10 9 12 9  130 140 205 225 11 16 14 16 98 108 337 357 10 15 14 19 8 3 10 3  129 139 200 220 13 18 9 5 11 5 106 116 348 368 10 15 9 14 5 7 7 7    135 145 300 320 10 15 17 6 19 6 119 129 365 385 10 15 21 26 14 7 16 7  131 141 295 315 11 16 13 8 15 8 132 142 380 400 10 15 16 21 11 3 13 3  128 138 290 310 13 18 10 12 144 154 395 415 10 15 11 16 7 9 9 9    139 149 390 410 10 15 16 7 18 7 162 172 418 438 10 15 19 24 19 4 21 4  137 147 370 390 10 15 12 6 14 6 172 182 430 450 10 15 19 24 14 7 16 7  135 145 350 370 10 15 8 5 10 5 182 192 444 464 11 16 19 24 10 1 12 1    145 155 490 510 10 15 15 9 17 9  145 155 470 490 10 15 11 7 13 7  144 154 452 472 9 14 7 4 9       Suction   Discharge Suction   Discharge                                                        Based on 15  Methanol antifreeze solution    Table 12  GT PG Series Typical Unit Operatin
39. Particulate Size and velocity of 1 8 m s      t velocity of 1 8 m s  Filtered for maximum 841 micron 0 84 mm   Erosion Bo T ron IO BATH 20 mesh  size  Any particulate that is not removed can potentially  20 mesh  ER   clog components        Notes  Rev   4 6 2011    Closed Recirculating system is identified by a closed pressurized piping system      Recirculating open wells should observe the open recirculating design considerations      NR   Application not recommended         Na desian Mavimiim    16    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       Hot W ater Generator    The HWG  Hot Water Generator  or desuperheater option  provides considerable operating cost savings by utilizing  excess heat energy from the heat pump to help satisfy  domestic hot water requirements  The HWG is active  throughout the year  providing virtually free hot water when  the heat pump operates in the cooling mode or hot water at  the COP of the heat pump during operation in the heating  mode  Actual HWG water heating capacities are provided in  the appropriate heat pump performance data     Heat pumps equipped with the HWG option include a built   in water to refrigerant heat exchanger that eliminates the  need to tie into the heat pump refrigerant circuit in the field   The control circuit and pump are also built in for residential  equipment  Figure 14 shows a typical example of HWG water  piping connections on a unit with built in circulating pump   This piping layout red
40. Screws  Water  Connection End    Return Air    Drain    T            Back Discharge Discharge Air    Figure 5  Right Return Side to Back    Connection End       Return Air    Water  Connection End       Discharge Air    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       Horizontal Installation    Condensate Piping     Horizontal Units   Pitch the unit toward the drain as shown in Figure 2 to  improve the condensate drainage  On small units  less  than 2 5 tons 8 8 kW   insure that unit pitch does not cause  condensate leaks inside the cabinet     Install condensate trap at each unit with the top of the trap  positioned below the unit condensate drain connection as  shown in Figure 6  Design the depth of the trap  water seal   based upon the amount of ESP capability of the blower   where 2 inches  51mm  of ESP capability requires 2 inches   51mm  of trap depth   As a general rule  1 1 2 inch  38mm   trap depth is the minimum     Each unit must be installed with its own individual trap and  connection to the condensate line  main  or riser  Provide  a means to flush or blow out the condensate line  DO NOT  install units with a common trap and or vent     Always vent the condensate line when dirt or air can collect  in the line or a long horizontal drain line is required  Also vent  when large units are working against higher external static  pressure than other units connected to the same condensate  main since this may cause poor drainage for all units on the 
41. aeq uondooug Auer og uoi s    QT  UO  107  ootAop Surojour juvzosrjo1 pue   poq 2A VA Surs1Ao1   s1oduvqoxo JV 19je A11  0  jue1osrar  10ssaiduroo ay  opnjour Apuo sjuauoduroo qorq    SHUN jeuuoroor  ILEN jo sjueuoduroo moro juv19311j91 po eos  E  t o oq pougop se  aeq uondooug KjuermA IY  WI SIEI    QT  UD  10     SHUN  euuoqgoor  1orue   YIM payfeysur uym     Ioe   q pios 10 ying so npour Surduind  euuoqiooS pue s  y ornoo o Arerrxny  Z    Ao oq pougop sv  aeq uondoou Kurerrej oui Wor svo  01  UO  104  SHUN peuuogioor  JoLuv      Xov     q pos 10 ying ore jeg AS tnr Suruurdoq sroquinu  opour qyra sd  umd yeoy 10   pue Survog  Suruonrpuoo Ie  eur9093  enuoprso   T   SMOT OJ sv ooueuojureur pue osn  eULIOU IPUN drusueun10A pue  eTI9 CUI UT   29 9p WOI 991J 9q 0   epeuv   puv BOLIOUTY Jo says poi  ou  ur pouro1 pue poseqound  sjonpoid  euuoyjoas  enuUSpIsol S   SJUCIIEA IIUI  AINVIIVA SST3dXI Q3 LEATT J0 LNV3     asOd3Ind AVTNOLLAVd    ANV YOU STOOD AHL AO SSANLIA AHL AO XO STOOD AHL AO ALITIAVINVHOYAW JO ALNVYAVM ON SAV TADITIVO   SLO9LT4G INALVT LSNIVOV ALNVAAVM ON SAVIN EABIIEVO  SLO  GO Id SGrIpHVO AO ANV OL SV    AINVAAVM SSH3dX31 ON SI AVAL    NIAAAH H L303 LAS XTIVOLIIO3dS SV LATDXA  sonpoid s  19110 jo uonepuounuoo 10 uorurdo s  oru  Apo1our ore jnq  urereq ot Jo stseq oq Jo Ped v uoy jou op pue sonuvamA sso1dxo jou ame  juouioo18v 10 Zope     OILIN so vs Aue ur poureauoo 0 uon peo IAPAA  sjonpoud SIATA 0 ZUNE    soanequasordos SII 10    J0110       uoraodioo amerad v 
42. are rated for 450 psi  3101 kPa  operating  pressure  The connections have a rubber gasket seal  similar to a garden hose gasket  which when mated to the  flush end of most 1    threaded male pipe fittings provides   a leak free seal without the need for thread sealing tape or  joint compound  Insure that the rubber seal is in the swivel  connector prior to attempting any connection  rubber seals  are shipped attached to the swivel connector   DO NOT  OVER TIGHTEN or leaks may occur     W ater Connection Installation    The female locking ring is threaded onto the pipe threads  which holds the male pipe end against the rubber gasket   and seals the joint  HAND TIGHTEN ONLY  DO NOT  OVERTIGHTEN     Figure 11  Water Connections    m Swivel Nut                                     Hand Tighten  usesecsess  Pate Only   Stainless steel Do Not  snap ring Overtighten    lt  lt   Gasket          aN    Brass Adaptor    GROUND LOOP HEAT PUMP APPLICATIONS    Figure 12  Typical Ground Loop Application              Flow  Controller    Unit Power Se  0  a          Disconnect    Insulated  Hose Kit          Q  High and ro  Low Voltage  o  Knockouts    ooo                P T Plugs    Rev   06 02 09S  Vibration Isolation Pad    A CAUTION  A    CAUTION  The following instructions represent industry  accepted installation practices for closed loop earth  coupled heat pump systems  Instructions are provided  to assist the contractor in installing trouble free ground    loops  These instructions a
43. as the   loop pump relay     Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       Unit Commissioning And O perating Conditions    Operating Limits   Environment     Units are designed for indoor installation only  Never install units in areas subject to freezing or where humidity levels  could cause cabinet condensation  such as unconditioned spaces subject to 100  outside air     Power Supply     A voltage variation of       10  of nameplate utilization voltage is acceptable     Determination of operating limits is dependent primarily upon three factors  1  return air temperature  2  water temperature   and 3  ambient temperature  When any one of these factors is at minimum or maximum levels  the other two factors should be  at normal levels to insure proper unit operation  Extreme variations in temperature and humidity and or corrosive water or air  will adversely affect unit performance  reliability  and service life  Consult Table 8a for operating limits     Table 8a  Building Operating Limits    Operating Limits pe GTR X  ee    GEBOT o c x  p 9 Cooling   Heating i   Heating    Air Limits  Min  ambient air  DB 45  F  7  C  39  F  4  C  45  F  7  C  39  F  4  C  Rated ambient air  DB 80 6  F  27  C  68  F  20  C  80 6  F  27  C  68  F  20  C  Max  ambient air  DB 110  F  43  C  85  F  29  C  110  F  43  C  85  F  29  C   Min  entering air  DB WB 60 45  F  16 7  C  40  F  4 4  C  60 50  F  16 10  C  45  F  7  C     Rated entering air  DB WB   80 6 66 2  F  27
44. at  exchanger is recommended  In ground water situations  where scaling could be heavy or where biological growth  such as iron bacteria will be present  an open loop system  is not recommended  Heat exchanger coils may over time  lose heat exchange capabilities due to build up of mineral  deposits  Heat exchangers must only be serviced by a  qualified technician  as acid and special pumping equipment  is required  Desuperheater coils can likewise become scaled  and possibly plugged  In areas with extremely hard water   the owner should be informed that the heat exchanger   may require occasional acid flushing  In some cases  the  desuperheater option should not be recommended due to  hard water conditions and additional maintenance required     Water Quality Standards   Table 3 should be consulted for water quality requirements   Scaling potential should be assessed using the pH Calcium  hardness method  If the pH   7 5 and the Calcium hardness  is less than 100 ppm  scaling potential is low  If this method  yields numbers out of range of those listed  the Ryznar  Stability and Langelier Saturation indecies should be  calculated  Use the appropriate scaling surface temperature  for the application  150  F  66  C  for direct use  well water   open loop  and DHW  desuperheater   90  F  32  F  for  indirect use  A monitoring plan should be implemented in    these probable scaling situations  Other water quality issues  such as iron fouling  corrosion prevention and erosion and 
45. ata for  fuse sizes  Consult wiring diagram for field connections that  must be made by the installing  or electrical  contractor     All final electrical connections must be made with a length of  flexible conduit to minimize vibration and sound transmission  to the building     General Line Voltage Wiring   Be sure the available power is the same voltage and phase  shown on the unit serial plate  Line and low voltage wiring  must be done in accordance with local codes or the National  Electric Code  whichever is applicable     Power Connection   Line voltage connection is made by connecting the  incoming line voltage wires to the    L    side of the contactor  as shown in Figure 16  Consult Tables 4a through 4b for  correct fuse size     208 Volt Operation   All residential 208 230 Volt units are factory wired for 230  Volt operation  The transformer may be switched to the 208V  tap as illustrated on the wiring diagram by switching the red   208V  and the orange  230V  wires at the contactor terminal     Blower Speed Selection     Units with PSC Motor   PSC  Permanent Split Capacitor  blower fan speed can be  changed by moving the blue wire on the fan motor terminal  block to the desired speed as shown in Figure 17  Optional  ECM motor speeds are set via low voltage controls  see     ECM Blower Control      Most units are shipped on the  medium speed tap  Consult specifications catalog for  specific unit airflow tables  Typical unit design delivers rated  airflow at nominal
46. ater hammer persists  a mini expansion  tank can be mounted on the piping to help absorb the excess  hammer shock  Insure that the total  VA  draw of the valve  can be supplied by the unit transformer  For instance  a slow  closing valve can draw up to 35VA  This can overload smaller  40 or 50 VA transformers depending on the other controls   in the circuit  A typical pilot operated solenoid valve draws  approximately 15VA  see Figure 22   Note the special wiring  diagrams for slow closing valves  Figures 23  amp  24      Flow Regulation  Flow regulation can be accomplished by two methods  One  method of flow regulation involves simply adjusting the ball    13    14    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       Ground W ater Heat Pump Applications    valve or water control valve on the discharge line  Measure the  pressure drop through the unit heat exchanger  and determine  flow rate from tables 9a through 9c  Since the pressure is  constantly varying  two pressure gauges may be needed   Adjust the valve until the desired flow of 1 5 to 2 gom per ton   2 0 to 2 6 I m per kW  is achieved  A second method of flow  control requires a flow control device mounted on the outlet of  the water control valve  The device is typically a brass fitting  with an orifice of rubber or plastic material that is designed   to allow a specified flow rate  On occasion  flow control  devices may produce velocity noise that can be reduced by  applying some back pressure fr
47. chart  Replace   Check pump operation or water valve operation setting        Plugged strainer or filter  Clean or replace        Check water flow  Adjust to proper flow rate        Water temperature out of range     Bring water temperature within design parameters        Reduced air flow in cooling     Check for dirty air filter and clean or replace        Check fan motor operation and air flow restrictions        Too high of external static  Check static vs  blower table        Air temperature out of range    Too much cold vent air  Bring entering air temperature within design parameters        Insufficient charge  Too high of air flow    Check for refrigerant leaks   Check fan motor speed selection and air flow chart        Poor performance  Too high of air flow    See  Insufficient Capacity        Check fan motor speed selection and airflow chart                 Unit oversized          Recheck loads  amp  sizing  Check sensible clg load and heat pump capacity     Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012       Troubleshooting Form    Date        Customer  Antifreeze           Model   Serial   Loop type              Complaint        SAT          HEATING CYCLE ANALYSIS    y           EXPANSION FILTER  VALVE DRIER        SAT       FP2  HEATING FLASH FP1     F     F  LIQUID LINE GASLINE SENSOR Bet PSI    WATERIN   WATEROUT Look up pressure drop in  poo   O M  or spec  catalog to  determine flow rate   COOLING CYCLE ANALYSIS   PSI SAT             Refrigera
48. control   will lockout  with code 9  after 30 seconds if    a  The compressor is on in the cooling mode and the FP1  sensor is colder than the FP2 sensor  or    b  The compressor is on in the heating mode and the FP2  sensor is colder than the FP 1 sensor    Swapped FP1 FP2 thermistor code   9                    Diagnostic Features   The LED on the CXM board advises the technician of the  current status of the CXM control  The LED can display either  the current CXM mode or the last fault in memory if in test  mode  If there is no fault in memory  the LED will flash Code 1   when in test mode      Residential Packaged Units   60Hz Puron     Rev   4Jan   2012    CXM Controls       CXM Control Start up Operation   The control will not operate until all inputs and safety controls  are checked for normal conditions  The compressor will   have a 5 minute anti short cycle delay at power up  The first  time after power up that there is a call for compressor  the  compressor will follow a 5 to 80 second random start delay   After the random start delay and anti short cycle delay    the compressor relay will be energized  On all subsequent  compressor calls  the random start delay is omitted     Table 6b  Unit Operation    T stat signal    GT PX    GT PG GT G    GT PG GT G       ECM fan    ECM fan    PSC fan       G    Fan only    Fan only    Fan only       G YorYl    Stage 1 heating       Stage 1 heating     Stage 1 heating          G  Y1  Y2    Stage 2 heating       Stage 2 heating 
49. d  Therefore  continuity on pressure switches  for  example can be checked at the board connector     The thermistor resistance should be measured with the  connector removed so that only the impedance of the  thermistor is measured  If desired  this reading can be  compared to the thermistor resistance chart shown in  the CXM AOM manual  An ice bath can be used to check  calibration of the thermistor     Outputs   The compressor relay is 24VAC and can be verified using a  voltmeter  The fan signal is passed through the board to the  external fan relay  units with PSC motors only   The alarm  relay can either be 24VAC as shipped or dry contacts for use  with DDC controls by clipping the J W1 jumper  Electric heat  outputs are 24VDC  ground sinking    and require a volt meter  set for DC to verify operation  The terminal marked  24VDC   is the 24VDC supply to the electric heat board  terminal    EH1     is stage 1 electric heat  terminal  EH2  is stage 2 electric heat   When electric heat is energized  thermostat is sending a  W   input to the CXM controller   there will be 24VDC between  terminal  24VDC  and  EHI   stage 1 electric heat  and or   EH2   stage 2 electric heat   A reading of OVDC between     24VDC    and    EH1    or  EH2  will indicate that the CXM board  is NOT sending an output signal to the electric heat board     Troubleshooting    Test Mode   Test mode can be entered for 20 minutes by shorting the test  pins  The CXM board will automatically exit test mode
50. e and verify any hot water generator  HWG   hanger   or other accessory kit located in the compressor section  or blower section     A CAUTION  A    CAUTION  DO NOT store or install units in corrosive  environments or in locations subject to temperature or  humidity extremes  e g   attics  garages  rooftops  etc     Corrosive conditions and high temperature or humidity can  significantly reduce performance  reliability  and service  life  Always move and store units in an upright position   Tilting units on their sides may cause equipment damage     A CAUTION  A    CAUTION  CUT HAZARD   Failure to follow this  caution may result in personal injury  Sheet metal parts  may have sharp edges or burrs  Use care and wear  appropriate protective clothing  safety glasses and  gloves when handling parts and servicing heat pumps     Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012       Horizontal Unit Location   Units are not designed for outdoor installation  Locate   the unit in an INDOOR area that allows enough space for  service personnel to perform typical maintenance or repairs  without removing unit from the ceiling  Horizontal units   are typically installed above a false ceiling or in a ceiling  plenum  Never install units in areas subject to freezing or  where humidity levels could cause cabinet condensation   such as unconditioned spaces subject to 100  outside air    Consideration should be given to access for easy removal of  the filter and access panels  Pr
51. e power or  fuel supply     Initial Start Up   1  Make sure all valves in the HWG water circuit are  fully open    2  Tum on the heat pump and allow it to run for  10 15 minutes    3  Set SW12 to the  OFF  position  enabled  to engage the  HWG    4  The HWG pump should not run if the compressor is not  running    5  The temperature difference between the water entering  and leaving the HWG coil should be approximately  5 10  F  3 6  C     6  Allow the unit to operate for 20 to 30 minutes to insure  that it is functioning properly     Table 7  HWG Water Piping Sizes and Length    Unit Nominal  Nominal   HWG Flow  Tonnage  gpm     1 5 0 6 50  2 0 0 8 50  2 5 1 0 50  3 0 1 2 50  3 5 1 4 50  4 0 1 6 45  5 0 2 0 25    1 2  Copper   max length      3 4  Copper   max length                                     Maximum length is equivalent length  in feet  one way of type L cop   per     Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012      Electrical   Line Voltage       A WARNING  A A CAUTION  A    WARNING  To avoid possible injury or death due to CAUTION  Use only copper conductors for field installed  electrical shock  open the power supply disconnect switch electrical wiring  Unit terminals are not designed to accept  and secure it in an open position during installation  other types of conductors     Table 4a  GT PX  50YD  Series Electrical Data    50YD Units  ECM  with Whole House                                              All 50YD Units with Emerson ECM Fan Mot
52. ed  the control will continue on  as if no fault occurred  If 3 consecutive faults occur without  satisfying the thermostat input call  the control will go into     lockout    mode  The last fault causing the lockout will be  stored in memory and can be viewed by going into test mode   Note  FP 1 FP2 faults are factory set at only one try   Lockout  In lockout mode  the status LED will begin fast  flashing  The compressor relay is turned off immediately   Lockout mode can be  soft  reset by turning off the  thermostat  or satisfying the call   A  soft  reset keeps   the fault in memory but resets the control  A  hard  reset   disconnecting power to the control  resets the control and  erases fault memory    Lockout with emergency heat  While in lockout mode  if W  becomes active  CXM   emergency heat mode will occur    High pressure switch  When the high pressure switch opens due  to high refrigerant pressures  the compressor relay is de energized  immediately since the high pressure switch is in series with the  compressor contactor coil  The high pressure fault recognition is  immediate  does not delay for 30 continuous seconds before de   energizing the compressor     High pressure lockout code  2   Example  2 quick flashes  10 sec pause  2 quick flashes  10  sec  pause  etc    Low pressure switch  The low pressure switch must be open  and remain open for 30 continuous seconds during    on    cycle  to be recognized as a low pressure fault  If the low pressure  switch is o
53. ed in an area with a known high mineral content    125 P P M  or greater  in the water  it is best to establish a  periodic maintenance schedule with the owner so the coil  can be checked regularly  Consult the well water applications  section of this manual for a more detailed water coil material  selection  Should periodic coil cleaning be necessary  use  standard coil cleaning procedures  which are compatible  with the heat exchanger material and copper water lines   Generally  the more water flowing through the unit  the less  chance for scaling  Therefore  1 5 gpm per ton  2 0 I m per  kW is recommended as a minimum flow  Minimum flow  rate for entering water temperatures below 50  F  10 C is 2 0  gpm per ton  2 6 I m per kW      Water Coil Maintenance    All other water loop applications    Generally water coil maintenance is not needed for closed  loop systems  However  if the piping is known to have   high dirt or debris content  it is best to establish a periodic  maintenance schedule with the owner so the water coil can  be checked regularly  Dirty installations are typically the result  of deterioration of iron or galvanized piping or components   in the system  Open cooling towers requiring heavy chemical  treatment and mineral buildup through water use can also  contribute to higher maintenance  Should periodic coil  cleaning be necessary  use standard coil cleaning procedures   which are compatible with both the heat exchanger material  and copper water lines  G
54. ed with construction dirt  and debris  which may cause system damage     Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       General Information    Inspection   Upon receipt of the equipment  carefully check the shipment  against the bill of lading  Make sure all units have been  received  Inspect the packaging of each unit  and inspect each  unit for damage  Insure that the carrier makes proper notation  of any shortages or damage on all copies of the freight bill and  completes a common carrier inspection report  Concealed  damage not discovered during unloading must be reported   to the carrier within 15 days of receipt of shipment  If not filed  within 15 days  the freight company can deny the claim without  recourse  Note  It is the responsibility of the purchaser to file  all necessary claims with the carrier  Notify your equipment  supplier of all damage within fifteen  15  days of shipment     Storage   Equipment should be stored in its original packaging in a  clean  dry area  Store units in an upright position at all times   Stack units a maximum of 3 units high     Unit Protection   Cover units on the job site with either the original packaging  or an equivalent protective covering  Cap the open ends   of pipes stored on the job site  In areas where painting   plastering  and or spraying has not been completed  all due  precautions must be taken to avoid physical damage to the  units and contamination by foreign material  Physical damage  and contam
55. enerally  the more water flowing  through the unit  the less chance for scaling  However  flow  rates over 3 gpm per ton  3 9 I m per kW  can produce water   or debris  velocities that can erode the heat exchanger wall  and ultimately produce leaks     Hot Water Generator Coils   See water coil maintenance for ground water units  If the  potable water is hard or not chemically softened  the high  temperatures of the desuperheater will tend to scale even  quicker than the water coil and may need more frequent   inspections  In areas with extremely hard water  a HWG is  not recommended     Filters   Filters must be clean to obtain maximum performance   Filters should be inspected every month under normal  operating conditions and be replaced when necessary  Units  should never be operated without a filter     Washable  high efficiency  electrostatic filters  when dirty   can exhibit a very high pressure drop for the fan motor and  reduce air flow  resulting in poor performance  It is especially  important to provide consistent washing of these filters  in  the opposite direction of the normal air flow  once per month  using a high pressure wash similar to those found at self   serve car washes     Condensate Drain   In areas where airborne bacteria may produce a  slimy   substance in the drain pan  it may be necessary to treat the  drain pan chemically with an algaecide approximately every  three months to minimize the problem  The condensate pan  may also need to be cleaned pe
56. erence  the operating charts for pressures and temperatures  Verify  that air and water flow rates are at proper levels before  servicing the refrigerant circuit     Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       General   If operational difficulties are encountered  perform   the preliminary checks below before referring to the   troubleshooting charts      Verify that the unit is receiving electrical supply power      Make sure the fuses in the fused disconnect switches  are intact    After completing the preliminary checks described above    inspect for other obvious problems such as leaking   connections  broken or disconnected wires  etc  If everything   appears to be in order  but the unit still fails to operate   properly  refer to the  CXM Troubleshooting Process   Flowchart  or  Functional Troubleshooting Chart      CXM Board   CXM board troubleshooting in general is best summarized  as simply verifying inputs and outputs  After inputs and  outputs have been verified  board operation is confirmed and  the problem must be elsewhere  Below are some general  guidelines for troubleshooting the CXM control     Field Inputs   All inputs are 24VAC from the thermostat and can be verified  using a volt meter between C and Y  G  O  W  24VAC will be  present at the terminal  for example  between  Y  and  C   if  the thermostat is sending an input to the CXM board     Sensor Inputs   All sensor inputs are  paired wires  connecting each component  to the boar
57. erence between the entering and leaving water   and GPM is the flow rate in U S  GPM  determined  by comparing the pressure drop across the heat  exchanger to Tables 9a through 9b    e  Check air temperature rise across the air coil when  compressor is operating  Air temperature rise should  be between 20  F and 30  F  11  C and 17  C     f  Check for vibration  noise  and water leaks    7  If unit fails to operate  perform troubleshooting analysis    see troubleshooting section   If the check described   fails to reveal the problem and the unit still does not   operate  contact a trained service technician to insure  proper diagnosis and repair of the equipment    When testing is complete  set system to maintain   desired comfort level    BE CERTAIN TO FILL OUT AND RETURN ALL   WARRANTY REGISTRATION PAPERWORK        Unit Start U p Procedure    Note  If performance during any mode appears abnormal   refer to the CXM section or troubleshooting section of this    manual  To obtain maximum performance  the air coil should    be cleaned before start up  A 1096 solution of dishwasher  detergent and water is recommended     A WARNING  A    WARNING  When the disconnect switch is closed  high  voltage is present in some areas of the electrical panel     Exercise caution when working with energized equipment     A CAUTION  A    CAUTION  Verify that ALL water control valves are open  and allow water flow prior to engaging the compressor   Freezing of the coax or water lines can permane
58. essure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water   Temp   Drop  oF       30     1 5  2 25  3    20   19   19     30  29    156 176  148 168  138 158    25 30  25 30  25 30    22 1 24 1  6 8 18 8  0 5 12 5    69 79  73 83  76 86    293 313  297 317  300 320    7 12  7 12  7 12    14 19  14 19  14 19    8 9 10 9    6 7 8 7  4 5 6 5       1 5    29   28     225 245  211 231  197 217    15 20  15 20  15 20    21 9 23 9  6 1 18 1  0 3 12 3    96 106  100 110  105 115    322 342  326 346  331 351    10 15  10 15  10 15    17 22  17 22  17 22    12 2 14     9 3 11 3    6 4 8 4    2       302 322  283 303  265 285    9 14  9 14  9 14    21 5 23 5  5 8     123 133  129 139  135 145    352 372  358 378  364 384    11 16  11 16  11 16    19 24  19 24  19 24    15 17    11 6 13 6  8 2 10 2       390 410  369 389  349 369    7 12  8 13  8 13       157 167  169 179  181 191        Based on 15  Methanol an    Entering  Water  Temp   oF             488 508  467 487  447 467       ifreeze solution    7 12  8 13  8 13          4  3  3  5  4  4  8  7  7  8  3  3  8          8 13          Full Load Cooling   without HWG active          390 410  399 419  408 428       13 18  13 18  14 19       18 23  16 5 21 5  15 20       21 23  15 5 17   10 5 12     Full Load Heating   without HWG active    5  5          Water  Flow    GPM ton    Suction    Pressure    PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water  Temp  Rise  oF    Suction  Pressure  PSIG   
59. est Mode   CO Fault in memory   Flashing Code 6    Test Mode   Over Under  shutdown in memory    ing Code 5  ing Code 6    Flashing Code 7 ing Code 7       Test Mode   UPS in memory Flashing Code 8 ing Code 8             Test Mode   Swapped Thermistor  hing Code 9 ing Code 9     Flash code 2 2 2 quick flashes  10 second pause  2 quick  flashes  10 second pause  etc    On pulse 1 3 second  off pulse 1 3 second    Figure 27  Test Mode Pins       Short test pins  together to enter Test      Mode and speed up  e 36 ou timing and delays for  e     amp  S49          BR BRG CCG CC    Cm i   m  20 minutes        R Cm  C JW3     N FPI  Jw2  amp  po    29    30    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       CXM Controls    Safety Features     CXM Control   The safety features below are provided to protect the  compressor  heat exchangers  wiring and other components  from damage caused by operation outside of design  conditions    Anti short cycle protection  The control features a 5 minute  anti short cycle protection for the compressor    Note  The 5 minute anti short cycle also occurs at power up   Random start  The control features a random start upon  power up of 5 80 seconds    Fault Retry  In Fault Retry mode  the Status LED begins  slowly flashing to signal that the control is trying to recover  from a fault input  The control will stage off the outputs and  then  try again  to satisfy the thermostat input call  Once the  thermostat input call is satisfi
60. for specific information on the current design and specifications  Statements and other information contained herein are not express  warranties and do not form the basis of any bargain between the parties  but are merely Manufacturer   s opinion or commendation of its products     The management system governing the manufacture of Manufacturer   s products is ISO 9001 2000 certified      LSB  Inc  2009    
61. g Pressures and Temperatures  018 Full Load Cooling   without HWG active Full Load Heating   without HWG active    Entering Water Suction Discharge Water Air Temp Suction Discharge Water  Water Flow Pressure Pressure   Superheat   Subcooling   Temp Rise Drop   F Pressure Pressure   Superheat   Subcooling   Temp Drop  Temp   F   GPM ton PSIG PSIG F DB PSIG PSIG  F    1 5 120 130   155 175 27 32 11 16 16 9 19 9 16 22 73 83 268 288 8 13 2 6 1 8 1 15 21  30  2 25 120 130   142 162 27 32 9 14 12 5 14 5 17 23 75 85 270 290 8 13   4 4 6 4 16 22  120 130   128 148 27 32 9 14 8 1 10 1 17 23 78 88 272 292 8 13   2 9 4 9 16 22    137 147   220 240 16 21 10 15 17 19 16 22 102 112   295 315 8 13 9 1 11 1 20 26  137 147   206 226 16 21 8 13 12 6 14 6 17 23 106 116   297 317 8 13 6 9 8 9 21 27  137 147   192 212 16 21 8 13 8 4 10 4 17 23 110 120   299 319 8 13 4 7 6 7 21 27    142 152   287 307 7 12 10 15 15 9 17 9 16 22 131 141   324 344 9 14   12 1 14 1 25 33  142 152   273 239 7 12 8 13 11 8 13 8 17 23 137 147   326 346 9 14   9 3 11 3 26 34  142 152   259 279 7 12 8 13 7 8 9 8 17 23 144 154   328 348 9 14   6 6 8 6 26 34    146 156   375 395 6 11 10 15 14 9 16 9 16 22 174 184   360 380 10 15   15 8 17 8 32 40  146 156   361 381 6 11 8 13 11 13 17 23 180 190   367 387 11 16   11 9 13 9 33 41  146 156   347 367 6 11 8 13 7 2 9 2 17 23 187 197   374 394 12 17    8 10 33 41    154 164   478 498 6 11 10 15 14 16 16 22  154 164   461 481 6 11 8 13 10 2 12 2 16 22  154 164   445 465 6 11 8 13 
62. ged Units   60Hz Puron     Rev   4Jan   2012    Unit O perating Conditions    Table 11  GT PX Series Typical Unit Operating Pressures and Temperatures  Continued    064 Full Load Cooling   without HWG active Full Load Heating   without HWG active  Entering Water Water  Water Temp Temp  Rise Drop  oF oF  1 5 117 127 170 190 27 32 15 20 18 2 20 2 66 76 282 302 10 16 9 14 8 10  2 25 116 126 143 163 28 33 13 18 12 6 14 6   69 79 285 305 10 16 9 14 6 8  115 125 135 155 29 34 12 17 7 9 72 82 289 309 10 16 10 15 4 6    128 138 238 258 16 21 14 19 20 5 22 5 90 100 310 330 11 17 12 17 11 3 13 3  126 136 222 242 21 26 13 18 14 9 16 9 95 105 313 333 11 17 12 17 8 5 10 5  125 135 205 225 26 31 12 17 9 2 11 2 99 109 316 336 11 17 12 17 5 7 7 7    135 145 315 335 10 15 14 19 21 23 115 125   337 357 12 18 14 19 14 16  134 144 296 316 12 17 13 18 15 5 17 5 2 120 130   341 361 12 18 14 19 10 6 12 6  133 143 276 296 15 20 11 16 10 12 126 136   345 365 12 18 15 20 7 3 9 3    139 149 408 428 10 15 15 20 20 1 22 1 157 167   390 410 15 20 14 19 18 2 20 2  138 148 386 406 10 15 13 18 14 8 16 8 161 171 394 414 15 20 14 19 13 9 15 9  138 148 364 384 10 15 11 16 9 5 11 5 166 176   398 418 15 20 15 20 9 6 11 6    144 154 515 535 8 13 14 19 19 21  143 153 493 513 8 13 13 18 14 16  142 152 469 489 8 13 12 17 9 11       Water Suction   Discharge  Flow Pressure   Pressure   Superheat   Subcooling  GPM ton PSIG PSIG    Air Temp   Suction   Discharge  Drop   F   Pressure   Pressure   Superheat   Subcooling  
63. he unit     Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012       Thermostat Connections   The thermostat should be wired directly to the CXM board   units with PSC fan   Units with optional ECM motor include  factory wiring from the CXM board to the ECM interface  board  Thermostat wiring for these units should be connected  to the ECM interface board  Figure 18 shows wiring for   50Y D 50YE units with PSC or optional ECM motor  See     Electrical   Thermostat    for specific terminal connections     Figure 18  GT PX GT PG Low Voltage Field Wiring        ECM board  will not be   4  present      S    Low voltage field wiring for units with ECM fan    Electrical   Low Voltage W iring    Low Water Temperature Cutout Selection   The CXM control allows the field selection of low water  or  water antifreeze solution  temperature limit by clipping jumper   J W3  which changes the sensing temperature associated with  thermistor FP 1  Note that the FP1 thermistor is located on   the refrigerant line between the coaxial heat exchanger and  expansion device  TXV   Therefore  FP1 is sensing refrigerant  temperature  not water temperature  which is a better indication  of how water flow rate temperature is affecting the refrigeration  circuit     The factory setting for FP1 is for systems using water  30  F    1 1  C  refrigerant temperature   In low water temperature   extended range  applications with antifreeze  most ground  loops   jumper J W3 should be clipped as show
64. ications    Table 2  Antifreeze Percentages by Volume    Minimum Temperature for Low Temperature Protection       Type  10  F   12 2  C     15  F   9 4  C  20  F   6 7  C  25  F   3 9  C        Methanol 25   100  USP food grade Propylene Glycol 38   Ethanol  29            Must not be denatured with any petroleum based product       21  16  10   25  22  15   25  20  14           GROUND WATER HEAT PUMP APPLICATIONS    Open Loop   Ground Water Systems   Typical open loop piping is shown in Figure 13  Shut off  valves should be included for ease of servicing  Boiler drains  or other valves should be    tee   d    into the lines to allow acid  flushing of the heat exchanger  Shut off valves should be  positioned to allow flow through the coax via the boiler drains  without allowing flow into the piping system  P T plugs  should be used so that pressure drop and temperature can  be measured  Piping materials should be limited to copper  or PVC SCH80  Note  Due to the pressure and temperature  extremes  PVC SCH40 is not recommended     Water quantity should be plentiful and of good quality   Consult table 3 for water quality guidelines  The unit can   be ordered with either a copper or cupro nickel water   heat exchanger  Consult table 3 for recommendations   Copper is recommended for closed loop systems and open  loop ground water systems that are not high in mineral  content or corrosiveness  In conditions anticipating heavy  scale formation or in brackish water  a cupro nickel he
65. ilter Units Only    Cooling Mode Dehumid Mode Heating Mode Aux     RUX Emerg       Stg 1   Stg2   Fan   Stg1   Stg2   Fan   Stg1   Stg2   Fan CFM Mode       620 750 380 480 590 380 620 750 380  570 700 350 450 550 350 570 700 350  510 620 310 400 480 310 510 620 310  530 270 430 530 270  950 470 870 1060 470  850 420 780 950 420  770 360 670 820 390  670 300 570 690 340  1130 560 1000   1230 560  1000 500 900 1100 500  900 450 800 980 450  800 400 700 850 400  1400 700 1150   1400 700  1250 630 1020   1250 630  1080 540 890 1080 540  900 450 750 920 450  1580 790 1290   1580 790  1400 700 1150   1400 700  1280 640 1020   1240 640  1120 560 900 1080 560  1730 870 1520   1850 865  1550 780 1350   1650 775  1440 720 1190   1450 720  1280 640 1020   1250 640  2050 1030 1870   2280 1030  1830 910 1680   2050 910  1700 850 1480   1800 850  1580 790 1270   1550 790  2230 1100 1830   2230 1100  1950 980 1720   2100 980  1750 880 1670   1950 880  1580 790 1460   1780 790    750  700  650  650  1060  950  820  690  1230  1100  980  850  1400  1350  1350  1350  1580  1400  1350  1350  1850  1650  1450                                                                                                                                                                                                                e JN Juw  A Jje  N  A je INI  WIRITRP INJ  A Je INJ  A Je INJ   AJe In   wir ini wits  e JN Jw  A TRF IN juu  A je IN WIR Jje INJ  A Je INJ  AJe INJ   AJe INu  AJe ini wis       Bold nu
66. ination may prevent proper start up and may  result in costly equipment clean up     Examine all pipes  fittings  and valves before installing any of  the system components  Remove any dirt or debris found in  or on these components     Pre Installation   Installation  Operation  and Maintenance instructions are  provided with each unit  Horizontal equipment is designed for  installation above false ceiling or in a ceiling plenum  Other  unit configurations are typically installed in a mechanical  room  The installation site chosen should include adequate  service clearance around the unit  Before unit start up    read all manuals and become familiar with the unit and its  operation  Thoroughly check the system before operation     Prepare units for installation as follows    1  Compare the electrical data on the unit nameplate with  ordering and shipping information to verify that the correct  unit has been shipped    2  Keepthe cabinet covered with the original packaging until  installation is complete and all plastering  painting  etc  is  finished    3  Verify refrigerant tubing is free of kinks or dents and that it  does not touch other unit components    4  Inspect all electrical connections  Connections must be  clean and tight at the terminals    5  Remove any blower support packaging  water to air  units only     6  Loosen compressor bolts on units equipped with  compressor grommet vibration isolation until the  compressor rides freely on the grommets        7  Locat
67. iping is complete and purged of air  Water  Freezing of the coax or water lines can permanently  piping is clean   Q Antifreeze has been added if necessary  damage the heatpump   Q Entering water and air  Insure that entering water and air  temperatures are within operating limits of Table 8  A CA UTION   A  Q Low water temperature cutout  Verify that low water R      temperature cut out on the CXM DXM control is properly CAUTION  To avoid equipment damage  DO NOT  set  leave system filled in a building without heat during the  Q Unit fan  Manually rotate fan to verify free rotation and winter unless antifreeze is added to the water loop  Heat  insure that blower wheel is secured to the motor shaft  exchangers never fully drain by themselves and will  Be sure to remove any shipping supports if needed  freeze unless winterized with antifreeze   DO NOT oil motors upon start up  Fan motors are pre   oiled at the factory  Check unit fan speed selection and  compare to design requirements   Q Condensate line  Verify that condensate lineis open and Unit Start up Procedure  properly pitched toward drain  ca 1  Turn the thermostat fan position to    ON     Blower  Q HWG pump is disconnected unless piping is completed should start   and air has been purged from the system  2  Balance air flow at registers   Q Water flow balancing  Record inlet and outlet water 3  Adjust all valves to their full open position  Turn on the  temperatures for each heat pump upon startup  This line power t
68. its    Min  entering water 30  F   1  C  20  F   6 7  C   Normal entering water 50 110  F  10 43  C  30 70  F   1 to 21  C   Max  entering water 120  F  49  C 90  F  32  C    1 5 to 3 0 gpm   ton  1 6 to 3 2 l m per kW   If with active Whole House Dehumidification 70 61  F  21 16  C     Normal Water Flow       33    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       Unit Start Up and O perating Conditions    Flow Controller pump s   Verify that the pump s  is wired   purged of air  and in operating condition   Q System controls  Verify that system controls function and    Unit and System Checkout a  BEFORE POWERING SYSTEM  please check the following     34    UNIT CHECKOUT             Q Balancing shutoff valves  Insure that all isolation valves Q Low water temperature cutout  Verify that low water  are open and water control valves are wired  temperature cut out controls are set properly  Q Line voltage and wiring  Verify that voltage is within  FP 1   J W3    an acceptable range for the unit and wiring and fuses  Q Miscellaneous  Note any questionable aspects of  breakers are properly sized  Verify that low voltage wiring the installation   is complete   Q Unit control transformer  Insure that transformer has the  properly selected voltage tap  Residential 208 230V units A CA UTION   A  T wired for 230V operation unless specified CAUTION  Verify that ALL water control valves are open  TN ERE   and allow water flow prior to engaging the compressor   Q Se ck p
69. low regulator  When stage  one is operating  the second solenoid valve will be closed     When stage two is operating  both valves will be open   allowing full load flow rate     Figure 23 illustrates piping for two stage solenoid valves   Review figures 20 22 for wiring of stage one valve  Stage two  valve should be wired between terminal    Y2     ECM board   and terminal  C      Note  When EWT is below 50  F  10  C   a minimum of 2  gpm per ton  2 6 I m per kW  is required     Figure 21  AVM Valve Wiring       Y1    Oo                     2 AVM    1 3  SAAN Switch Taco Valve                       gt   Thermostat    Q Q                 Figure 22  Taco SBV Valve Wiring       Capacitor   Motor           End Switch         TACO SBV VALVE          Figure 23  Two Stage Piping          Solenoid  Valve    Flow  Regulator    From Water Source    To Discharge  Stage 1    NOTE  Shut off valves  strainers and  other required components not shown     Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012       A CAUTION  A    CAUTION  Many units installed with a factory or field  supplied manual or electric shut off valve  DAMAGE WILL  OCCUR if shut off valve is closed during unit operation  A  high pressure switch must be installed on the heat pump  side of any field provided shut off valves and connected to  the heat pump controls in series with the built in refrigerant  circuit high pressure switch to disable compressor  operation if water pressure exceeds pressure switch se
70. mbers indicate factory settings    During Auxiliary operation the CFM will run at the higher of the Heating  Delay jumper  or AUX settings   Airflow is controlled within 5  up to the Max ESP shown with wet coil    Do not select Dehumidification mode if HP CFM is on setting 1    All units AHRI ISO ASHRAE 13256 1 rated HP CFM Setting 3        Note  See the ECM Blower Control section for information on setting taps     Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012       CXM Control   For detailed control information  see CXM Application   Operation and Maintenance  AOM  manual  part   97B0003N12      Field Selectable Inputs   Test mode  Test mode allows the service technician to   check the operation of the control in a timely manner  By  momentarily shorting the test terminals  the CXM control  enters a 20 minute test mode period in which all time delays  are sped up 15 times  Upon entering test mode  the status  LED will flash a code representing the last fault  For diagnostic  ease at the thermostat  the alarm relay will also cycle during  test mode  The alarm relay will cycle on and off similar to the  status LED to indicate a code representing the last fault  at  the thermostat  Test mode can be exited by shorting the test  terminals for 3 seconds    Retry Mode  If the control is attempting a retry of a fault   the status LED will slow flash  slow flash   one flash every 2  seconds  to indicate the control is in the process of retrying     Field Configurati
71. n in Figure   19 to change the setting to 10  F   12 2  C  refrigerant  temperature  a more suitable temperature when using   an antifreeze solution  All residential units include water   refrigerant circuit insulation to prevent internal condensation   which is required when operating with entering water  temperatures below 59  F  15  C      Figure 19  FP1 Limit Setting          e BR BRG CCG CC  c    Comp  C e pins Relay    Test       La       J W3 FP1   R    jumper should    JWws       FPi be clipped for  Jw2      rp low temperature  CXM PCB operation    21    22    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       Electrical   Low Voltage W iring    Accessory Connections   A terminal paralleling the compressor contactor coil has  been provided on the CXM control  Terminal    A    is designed  to control accessory devices  such as water valves  Note   This terminal should be used only with 24 Volt signals   and not line voltage  Terminal    A    is energized with the  compressor contactor  See Figure 20 or the specific unit  wiring diagram for details     Figure 20  Accessory Wiring  Terminal Strip    Orm   Typical  Water  Valve   A        Water Solenoid Valves   An external solenoid valve s  should be used on ground  water installations to shut off flow to the unit when the  compressor is not operating  A slow closing valve may be  required to help reduce water hammer  Figure 20 shows  typical wiring for a 24VAC external solenoid valve  Figures  21 and 22
72. n of   the HWG  When SW12 is in the  ON  position the HWG is  disabled and will not operate  When SW12 is in the  OFF   position the HWG is in the enabled mode and will operate  normally  This switch is shipped from the factory in the   ON   disabled  position  CAUTION  DO NOT PLACE THIS  SWITCH IN THE ENABLED POSITION UNITL THE HWG  PIPING IS CONNECTED  FILLED WITH WATER  AND  PURGED OR PUMP DAMAGE WILL OCCUR     When the control is powered and the HWG pump output   is not active  the status LED  AN1  will be    On     When the  HWG pump output is active for water temperature sampling  or HWG operation  the status LED will slowly flash  On 1  second  Off 1 second      If the control has detected a fault  the status LED will flash a  numeric fault code as follows     Hot Water Sensor Fault 1 flash   Compressor Discharge sensor fault 2 flashes  High Water Temperature  21609F  3 flashes  Control Logic Error 4 flashes    Fault code flashes have a duration of 0 4 seconds with   a 3 second pause between fault codes  For example  a   Compressor Discharge sensor fault  will be four flashes  0 4 seconds long  then a 3 second pause  then four flashes  again  etc     17    18    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       Hot W ater Generator    Warning  The HWG pump Is fully wired from the  factory  Use extreme caution when working around  the microprocessor control as it contains line voltage  connections that presents a shock hazard that can  cause severe inj
73. ne  ejsu  ILO oq 0j Iojar oseo q    C       D     eourAoid uerpeur   oj oourAoJd uvrpeut   WO pue 9jejs 0  9jjs uro1j ATRA YOTYA SYFU 190 oAeq ose   ew noA pur  sju3u jega  oyroods noX soars Ajuenma sm  nok oj A dde jou Kew suonejrun pue suorsnjoxo Surosaioy ou os  sogeurep  ejuoprour 10  enuonbosuoo jo suorsnpoxo JO uorejruip ou  JO  sjse Aue pordurr ue Suo  moy uo suonejmu MOTTE JOU op soourAoid uerpeue   JO sojejs IWS  HLON     OCGC SVL  SOP     GLIEL vuoqepio    AUD PWOPO   19ANS Wry MS OOEL   IMAS IWON   v2 10 oym  oouvuuo god    Kyuexrem Surureiqo ur pombal st oouvjstsse J   Uorrztues1o ooIA1os 10 Jo vop  10 nqustp poztudooar 19111v   Kuv JRIUOD  o qe reAeun oq ao visur oq PINOYS    JUNO ot 10J oouvunojod Kyuexe optaoid  IA sionpoid oq poj eisur OYM uoneziues1o o21AJ9 10 Jo eop op      J TEULON  SONVINSOJ33d XINVSNVA SNINIVLSO     ALFIIS VITILOISLES SV YO HONHOTTIOGHN S WHIWHVO 380  SHH LHHA    LAOL NI YO    ALNV NAVM AAMINI YO SSH IdXH ANV HO HOVE2IG  UOA LOV3INOO NI HOVWVG TVLNSGIONI YO TWILNANOASNOD AOA ALFIISVET ANV SAANTOXA ANY SIV TOSKI XTISSH2IdXH AALAAVO RO Jo  onus opos oq puooq uoseo1 1940  amp ue 10 poo Jo soe  1oqe  10   erojeur    ony tuoneyodsuea Jo sogeuoqs   juoproot    poop    ory  soSeddojs yO 10    SINUS  sjurnso1 JO SUONSLSAI JUSUUIOAOS SAUN  IATO Jem Aue  0  pourr jou jnq    se qons juoAo Aue   q ju9jxo Aue 0  pojuoAoi1d st JO uoseo1 Aue 10  po  v op st ooueunoj1od s  ep J  soSeurep Kuv Joy Aj Iqei  ou savy preys JOLIN     ALFIISVETAO NOLLVLIATT    
74. ng   This may be accomplished by flushing water through the  HWG  as In Figures 14 and 15  or by Installing an air vent  at the high point of the HWG piping system    2  Insulate all HWG water piping with no less than 3 8    10mm  wall closed cell insulation    3  Open both shut off valves and make sure the tank drain  valve is closed     Water Tank Refill   1  Close valve  4  Ensure that the HWG valves  valves  2  and  3  are open  Open the cold water supply  valve  1   to fill the tank through the HWG piping  This will purge air  from the HWG piping    2  Open a hot water faucet to vent air from the system until  water flows from faucet  turn off faucet  Open valve 74    3  Depress the hot water tank pressure relief valve handle to  ensure that there is no air remaining in the tank    4  Inspect all work for leaks        5  Before restoring power or fuel supply to the water heater   adjust the temperature setting on the tank thermostat s   to insure maximum utilization of the heat available from  the refrigeration system and conserve the most energy   On tanks with both upper and lower elements and  thermostats  the lower element should be turned down  to 100  F  38  C  or the lowest setting  the upper element  should be adjusted to 120 130  F  49 54  C   Depending  upon the specific needs of the customer  you may want  to adjust the upper element differently  On tanks with a  single thermostat  a preheat tank should be used  Fig 15     6  Replace access cover s  and restor
75. nit series and model to correlate  speed tap setting to airflow in CFM        Auxiliary Emergency Heat Settings  The auxiliary   emergency heat setting determines the CFM when the unit  is in auxiliary heat or emergency heat mode  This setting   is used for residential units with internal electric heat   When auxiliary electric heat is energized  i e  compressor  and electric heat   the greater of the auxiliary emergency  or heating setting will be used  A    G     fan  signal must be  present from the thermostat for electric heat to operate   Consult the submittal data or specifications catalog for the  specific unit series and model to correlate speed tap setting  to airflow in CFM        CEM Adjust Settings  The CFM adjust setting allows  four selections  The NORM setting is the factory default       position  The  or   settings adjust the airflow by     15    The     settings are used to    fine tune    airflow adjustments   The TEST setting runs the ECM motor at 70  torque  which  causes the motor to operate like a standard PSC motor  and  disables the CFM counter     Dehumidification Mode Settings  The dehumidification  mode setting provides field selection of humidity control   When operating in the normal mode  the cooling airflow  settings are determined by the cooling tap setting above   When dehumidification is enabled there is a reduction in  airflow in cooling to increase the moisture removal of the  heat pump  Consult submittal data or specifications catalog  fo
76. ns    Operation outside these limits is not recommended     Scaling indexes should be calculated at 66  C for direct use and HWG applications  and at 32  C for indirect HX use   A monitoring plan should be implemented   Ryznar 6 0   7 5    Stability Index If 27 5 minimize steel pipe use     Langelier If  lt  0 5 minimize steel pi bus di 66 C HWG and        U o minimize steel pipe use  basea upon an  Saturation Index Direct well  29  C Indirect Well HX  Iron Fouling    Iron Fe    Ferrous       0 2 ppm  Ferrous    Bacterial Iron potential     If Fe   ferrous  gt 0 2 ppm with pH 6   8  O2  5 ppm check for iron bacteria     ea LL a o 1   0 5 ppm of Oxygen  Iron Fouling Above this level deposition will occur      Corrosion Prevention    6 8 5 6 8 5  H    F Monitor treat as Minimize steel pipe below 7 and no open tanks with pH  lt 8  needed    p so  lt 0 5 ppm    At H5S  0 2 ppm  avoid use of copper and copper nickel piping or HX s    Hydrogen Sulfide  H2S  2 Rotten egg smell appears at 0 5 ppm level    Copper alloy  bronze or brass  cast components are OK to  lt 0 5 ppm   Ammonia ion as hydroxide  chloride   nitrate and sulfate compounds  lt 0 5 ppm    Maximum Allowable at maximum water temperature     24  C  Maximum Copper  lt 20ppm  Chloride Levels Cupronickel  lt 150 ppm  304 SS  lt 400 ppm  316 SS  lt 1000 ppm  Titanium  gt 1000 ppm  Erosion and Clogging     lt 10 ppm of particles    and a maximum  lt 10 ppm   lt 1 ppm  sandfree    for reinjection  of particles and a maximum  
77. nt Type           HFC 410A denk   E  M   COMPRESSOR  EXPANSION FILTER  VALVE     DRIER  DISCHARGE  Voltage   Comp Amps     oF   Total Amps  Y PSI SAT   FP2 FLASH OTHERSIDE FP1 CLG   F  F   GAS LINE OFFILTRDR  LIQLINE PSI PSI       WATERIN   WATEROUT Look up pressure drop in  pn 1 0 M  or spec  catalog to  determine flow rate     Heat of Extraction  Absorption  or Heat of Rejection      flow rate  gpm  x   temp diff   deg  F  x        fluidfacto   __   Btu hr   Superheat   Suction temperature   suction saturation temp     deg F   Subcooling   Discharge saturation temp    liquid line temp     deg F   t Use 500 for water  485 for antifreeze  Rev  12 08    Note  Never connect refrigerant gauges during startup procedures  Conduct water side analysis using P T ports to determine  water flow and temperature difference  If water side analysis shows poor performance  refrigerant troubleshooting may be  required  Connect refrigerant gauges as a last resort     47    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012    W arranty    HQ YQVOLVQEVOQVOLOQVOLOQVOLOQVOLQQVOQQOLOQVOLY O QOQQOQOQQOQQ0Q0000000000000000000000000000 Q2    SOAR AGI III n 9l Pl gl  l ol lC pl ol IAI IAI IAI ISI pl ol gl Plo p ol nl p af m    v16 070707076 6 670 6 6 6 6 UU 6 o o 66 o o o o o o oo o Joe oe eee eo ee    0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 4    VECVO    ON Hed  01 9 PAT  suononngsur oouvuojureur pue 3urjeredo Joy  enue  ooueuojureJAr pue uoreede   uo
78. ntially hazardous situation  which  if not avoided could result in death or serious injury     A WARNING  A    WARNING  The Puron   Application and Service Manual  should be read and understood before attempting to  service refrigerant circuits with HFC 410A     A WARNING  A    WARNING  To avoid the release of refrigerant into the  atmosphere  the refrigerant circuit of this unit must be  serviced only by technicians who meet local  state  and  federal proficiency requirements           Rev   Jan  4  2012    CAUTION  Indicates a potentially hazardous situation or an  unsafe practice  which if not avoided could result in minor or  moderate injury or product or property damage           NOTICE  Notification of installation  operation or maintenance  information  which is important  but which is not hazard   related     A WARNING  A    WARNING  All refrigerant discharged from this unit must  be recovered WITHOUT EXCEPTION  Technicians must  follow industry accepted guidelines and all local  state   and federal statutes for the recovery and disposal of  refrigerants  If a compressor is removed from this unit   refrigerant circuit oil will remain in the compressor  To  avoid leakage of compressor oil  refrigerant lines of the  compressor must be sealed after it is removed     A CAUTION  A    CAUTION  To avoid equipment damage  DO NOT use  these units as a source of heating or cooling during the  construction process  The mechanical components and  filters will quickly become clogg
79. ntly  damage the heat pump        35    Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012       U nit O perating C onditions    Table 9a  GT PX Coax Water Pressure Drop Table 9b  GT PG Coax Water Pressure Drop    Pressure Drop  psi  Pressure Drop  psi           50  F 70  F    1 3  2 6  3 4  43    1 0  2 5  4 2  5 2    50  F 70  F                                                             Table 10  Water Temperature Change Through Heat  Exchanger    Rise  Cooli Drop  Heati  Water Flow  gpm  I m  ECC    ECC  S  For Closed Loop  9 12 4 8  Systems at 3 gpm per ton  3 9 I m per kw   5   6 7   2 2   4 4     Antifreeze Correction Table                         Cooling Heating       Antifreeze WED  Antifreeze Type EWT 90  F EWT 30  F Corr  Fct     E EWT 30 F       Total Cap   Sens Cap Htg Cap   Power    Water 1 000 1 000 1 000 1 000 1 000  0 995 0 995 0 989 0 997 1 070  Propylene Glycol 0 986 0 986 0 968 0 990 1 210  0 978 0 978 0 947 0 983 1 360  0 997 0 997 0 989 0 997 1 070  Methanol 0 990 0 990 0 968 0 990 1 160  0 982 0 982 0 949 0 984 1 220  0 998 0 998 0 981 0 994 1 140  Ethanol 0 994 0 994 0 944 0 983 1 300  0 986 0 986 0 917 0 974 1 360  0 998 0 998 0 993 0 998 1 040  Ethylene Glycol 0 994 0 994 0 980 0 994 1 120  0 988 0 988 0 966 0 990 1 200                                                                   36    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012    Unit O perating Conditions    Table 11  GT PX Series Typical Unit Operating Pressures
80. number ATP 32U04  See Whole House  Dehumidification AOM for more details         Electrical   Thermostat W iring    Figure 24  Units With Optional ECM Fan     Connection to ECM Control  ATP32U06 Thermostat       Units with CXM or DXM board and ECM fan motor  utilizing ECM dehumidification  mode  without ClimaDry option     Notes  1  Units with whole house dehumidification option have slightly different   thermostat wiring Terminal DH at the thermostat is connected to terminal H at  the DXM board   2  ECM dehumidification mode slows down fan speed in the cooling mode when  dehumidification output from thermostat is active  Normal heating and cooling fan  speeds are not affected    3  ECM board DIP switch SW9 must be in dehumid  mode for  ECM dehumidification mode     Figure 25  Typical Thermostat 2 Heat 1 Cool  PSC Fan     Connection to CXM Control  ATM21UO1 Thermostat       23    24    Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012       ECM Blower Control    The ECM fan is controlled by an interface board that  converts thermostat inputs and field selectable CFM  settings to signals used by the ECM motor controller    Units manufactured before J uly 2005 have version I  P N  69243707   Units manufactured between J uly 2005 and May  11  2009 have version II  P N 17B0019N 01   Fan speeds are  selected with jumpers for version   or via a nine position DIP  Switch for version Il and Ill  To take full advantage of the ECM  motor features  a multi stage thermostat 
81. o all heat pump units   check can eliminate nuisance trip outs and high velocity 4  Room temperature should be within the minimum   water flow that could erode heat exchangers  maximum ranges of Table 8b  During start up checks   Q Unit air coil and filters  Insure that filter is clean and loop water temperature entering the heat pump should  accessible  Clean air coil of all manufacturing oils  be between 30  F   1  C  and 95  F  35  C    Q Unit controls  Verify that CXM field selection options are 5  Two factors determine the operating limits of water  properly set  Low voltage wiring is complete  source heat pumps   a  return air temperature  and  b   Q Blower speed is set  water temperature  When any one of these factors is ata  Q Service access panels are in place  minimum or maximum level  the other factor must be at       SYSTEM CHECKOUT    system  Air in the system can cause poor operation or  system corrosion  Water used in the system must be  potable quality initially and clean of dirt  piping slag   and strong chemical cleaning agents  Some antifreeze  solutions may require distilled water     operate in the proper sequence           normal level to insure proper unit operation   a  Adjustthe unit thermostat to the warmest setting     Q System water temperature  Check water temperature Place the thermostat mode switch in the    COOL     for proper range and also verify heating and cooling set position  Slowly reduce thermostat setting until the  points for proper o
82. om the ball valve located on  the discharge line  Slightly closing the valve will spread the  pressure drop over both devices  lessening the velocity noise   NOTE  When EWT is below 50  F  10  C   a minimum of 2  gpm per ton  2 6 l m per kW  is required     Water Coil Low Temperature Limit Setting   Forall open loop systems the 30  F   1 1  C  FP 1 setting   factory setting  water  should be used to avoid freeze  damage to the unit  See  Low Water Temperature Cutout  Selection  in this manual for details on the low limit setting     Figure 13  Typical Open Loop Well Application             Unit Power  Disconnect    Water Flow  Control Regulator                                Air Pad or  Extruded  polystyrene  insulation board                 P T Plugs    Boiler  Drains    CAUTION  Refrigerant pressure activated water regulating  valves should never be used with this equipment     Pressure  Tank          Water Out    Shut Off  Valve       Filter       A CAUTION  A       Water In    Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012    W ater Q uality Standards       Table 3  Water Quality Standards    Water Quality HX Closed      Parameter Material Recirculating Open Loop a  d Recirculating  wel    Scaling Potential   Primary Measurement    Above the given limits  scaling is likely to occur  Scaling indexes should be calculated using the limits below  prcaeium Warnes  H  lt  7 5 and Ca Hardness  lt 100ppm  Method E SUBE    Index Limits for Probable Scaling Situatio
83. on Options   Note  In the following field configuration options  jumper  wires should be clipped ONLY when power is removed from  the CXM control     Water coil low temperature limit setting  J umper 3  J W3 FP1  Low Temp  provides field selection of temperature   limit setting for FP1 of 30  F or 10  F   1  F or  12  C    refrigerant temperature     Not Clipped   30  F   1 C  Clipped  10  F   12  C    Air coil low temperature limit setting  J umper 2    W2 FP2  Low Temp  provides field selection of temperature limit  setting for FP2 of 30  F or 10  F   1  F or  12  C   refrigerant  temperature   Note  This jumper should only be clipped  under extenuating circumstances  as recommended by  the factory    Not Clipped   30  F   1 C  Clipped  10  F   12  C    Alarm relay setting  J umper 1    W1 AL2 Dry  provides field  selection of the alarm relay terminal AL2 to be jumpered to  24VAC orto be a dry contact  no connection     Not Clipped  AL2 connected to R  Clipped  AL2 dry  contact  no connection            DIP Switches   Note  In the following field configuration options  DIP  switches should only be changed when power is removed  from the CXM control    DIP switch 1  Unit Performance Sentinel Disable   provides  field selection to disable the UPS feature    On   Enabled  Off   Disabled    DIP switch 2  Stage 2 Selection   provides selection of  whether compressor has an    on    delay  If set to stage 2  the  compressor will have a 3 second delay before energizing   Also  if 
84. on in test mode    Set for cooling demand and check 24VAC on RV coil and at DXM2 board        If RV is stuck  run high pressure up by reducing water flow and while operating  engage and disengage RV coil voltage to push valve        Thermostat setup    Check for  O  RV setup not  B         Thermostat wiring    Check O wiring at heat pump  Jumper O and R for RV coil    click    when  compressor starts                    Thermostat wiring    Possible Cause       Put thermostat in cooling mode  Check 24 VAC on O  check between C and  O   check for 24 VAC on W  check between W and C   There should be voltage  on O  but not on W  If voltage is present on W  thermostat may be bad or wired  incorrectly     Solution       Insufficient capacity  Not  cooling or heating    High Head Pressure    Low Suction Pressure    Low Discharge Air Temperature  in Heating    High humidity    Dirty filter    Replace or clean        Reduced or no air flow in heating    Check for dirty air filter and clean or replace        Check fan motor operation and airflow restrictions        Too high of external static  Check static vs  blower table        Reduced or no air flow in cooling    Check for dirty air filter and clean or replace        Check fan motor operation and airflow restrictions        Too high of external static  Check static vs  blower table        Leaky duct work    Check supply and return air temperatures at the unit and at distant duct registers  if significantly different  duct leaks are 
85. ooling for a number of minutes to  condition the loop to a homogenous temperature  This is   a good time for tool cleanup  piping insulation  etc  Then   perform final flush and pressurize the loop to a static  pressure of 50 75 psi  345 517 kPa   winter  or 35 40 psi   241 276 kPa   summer   After pressurization  be sure to  loosen the plug at the end of the Grundfos loop pump  motor s  to allow trapped airto be discharged and to insure  the motor housing has been flooded  This is not required  for Taco circulators  Insure that the Flow Controller provides  adequate flow through the unit by checking pressure drop  across the heat exchanger and compare to the pressure  drop tables at the back of the manual     Antifreeze  In areas where minimum entering loop temperatures drop    below 40  F  5  C  or where piping will be routed through  areas subject to freezing  antifreeze is required  Alcohols  and glycols are commonly used as antifreeze  however your  local sales manager should be consulted for the antifreeze  best suited to your area  Low temperature protection should  be maintained to 15  F  9  C  below the lowest expected  entering loop temperature  For example  if 30  F   1  C   is  the minimum expected entering loop temperature  the  leaving loop temperature would be 25 to 22  F   4 to  6  C   and low temperature protection should be at 15  F   10  C    Calculation is as follows    30  F   15  F  15  F   1  C   9  C   10  C      All alcohols should be premixed and pum
86. or 50YD Units  ECM  Standard Dehumidification  Whole  Min House ClimaDry Min  Circuit   Dehumid  Pump Circuit  Amps Pump FLA Amps  FLA  21 2 30 0 8 22 0  29 2 45 0 8 30 0  37 8 50 1 07 38 9  1 07 38 0 44 4  1 07 39 6 46 4  Rated Voltage of 208 230 60 1 Min Max Voltage of 197 254  HACR circuit breaker in USA only All fuses Class RK 5    Table 4b  GT PG  50YE  Series Electrical Data    50YE Unit with Whole House    Standard 50YE Unit Dehumidification       Compressor Hwe   EX Fan   Total   Min Whole Total Min    Pump EE Motor   Unit   Circuit P Unit Circuit BACH  RLA   LRA FLA FLA FLA Pump FLA FLA Amps                         ECM Electrical Data   17 3 19 6 25   21 1 24 8 35  25 2 35  26 7 40  27 6 40  36 9 50  44 9 70  48 9 70                                                             Rated Voltage of 208 230 60 1 Min M ax Voltage of 197 254  HACR circuit breaker in USA only All fuses Class RK 5    20    Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012       Electrical   Line Voltage    A WARNING  A    WARNING  Disconnect electrical power source to prevent  injury or death from electrical shock     A CAUTION  A    CAUTION  Use only copper conductors for field installed  electrical wiring  Unit terminals are not designed to accept  other types of conductors        Electrical   Line Voltage   All field installed wiring  including electrical ground  must  comply with the National Electrical Code as well as all  applicable local codes  Refer to the unit electrical d
87. otor  DXM Board Da CIDOOOO Fuss  ZDOOO000  HWG Pump  Oo    Relay    9  9  9  9           DIP Switches Thermostat CFM Counter  Connections 1 flash per 100 CFM    25    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012    GT PX  50YD  Series ECM Blower Performance D ata    Residential  Airflow in CFM with wet coil and clean air filter Units Only    Cooling Mode Dehumid Mode Heating Mode          Stg 1   Stg2   Fan   Stg1   Stg2   Fan   Stg1   Stg2   Fan       810 950 475 630 740 415 920 1060 415  725 850 425 560 660 425 825 950 425  620 730 370 490 570 370 710 820 370  520 610 300 600 690 300  1120 1400 700 1120 1400 700  1000 1250 630 1000 1250 630  860 1080 540 860 1080  730 900 450 730 900  1460 1730 870 1560 1850  1300 1550 780 1400 1650  1120 1330 670 1200 1430  940 1120 560 1010 1200  1670 2050 1020 1860 2280  1500 1825 920 1650 2050  1280 1580 790 1430 1750  1080 1320 660 1200 1470  1620 2190 1050 1690 2230  1500 1950 980 1600 2100  1400 1830 910 1400 1850  1320 1700 850 1240 1620                                  LA     N                                                                                                    e JNJ  A jJje INJ  A Je IN   WIR TRIN    AJjer IN  Wl  sts  e JN Jw  A TRIN WIT IN juw  A TRIN    AJjer IN  Wl  s    e  e je jejejejejeje jejejlje    Factory shipped on Tap Setting 2  During Auxiliary operation  residential units only  the CFM will run at the higher if the heating  delay jumper  or AUX settings  Airflow is controlled within    
88. ovide sufficient room to make  water  electrical  and duct connection s      If the unit is located in a confined space  such as a closet   provisions must be made for return air to freely enter the  space by means of a louvered door  etc  Any access panel  screws that would be difficult to remove after the unit is  installed should be removed prior to setting the unit  Refer to  Figure 3 for an illustration of a typical installation  Refer to unit  specifications catalog for dimensional data     Conform to the following guidelines when selecting   unit location    1  Provide a hinged access door in concealed spline or  plaster ceilings  Provide removable ceiling tiles in T bar  or lay in ceilings  Refer to horizontal unit dimensions for  specific series and model in unit specifications catalog   Size the access opening to accommodate the service  technician during the removal or replacement of the  compressor and the removal or installation of the unit  itself    2  Provide access to hanger brackets  water valves and  fittings  Provide screwdriver clearance to access panels   discharge collars and all electrical connections    3  DO NOT obstructthe space beneath the unit with piping   electrical cables and other items that prohibit future  removal of components or the unit itself    4  Usea manual portable jack lift to lift and support the  weight of the unit during installation and servicing     The installation of water source heat pump units and all  associated components
89. p assemblies prior to  installation  P ressures of at least 100 psi  689 kPa  should be  used when testing  Do not exceed the pipe pressure rating   Test entire system when all loops are assembled     Flushing the Earth Loop   Once piping is completed between the unit  Flow Controller  and the ground loop  Figure 12   the loop is ready for final  purging and charging  A flush cart with atleast a 1 5 hp    1 1 kW  pump is required to achieve enough fluid velocity  in the loop piping system to purge air and dirt particles  An    11    12    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       Ground Loop Heat Pump Applications    antifreeze solution is used in most areas to prevent freezing    All air and debris must be removed from the earth loop piping   before operation  Flush the loop with a high volume of water   at a minimum velocity of 2 fps  0 6 m s  in all piping  The  steps below must be followed for proper flushing    1  Fill loop with water from a garden hose through the flush  cart before using the flush cart pump to insure an even fill    2  Once full  the flushing process can begin  Do not allow  the water level in the flush cart tank to drop below the  pump inlet line to avoid air being pumped back out to  the earth loop    3  Try to maintain a fluid level in the tank above the return  tee so that air cannot be continuously mixed back into  the fluid  Surges of 50 psi  345 kPa  can be used to help  purge air pockets by simply shutting off the retu
90. parameters        Reduced or no air flow in heating    heck for dirty air filter and clean or replace        heck fan motor operation and airflow restrictions        C   e   C  C  Check pump operation or valve operation setting   C  B  C  C  Di    irty Air Coil  construction dust etc        Too high of external static  Check static vs blower table        Air temperature out of range in heating    ring return air temp within design parameters        Overcharged with refrigerant    heck superheat subcooling vs typical operating condition table        Bad HP Switch       heck switch continuity and operation  Replace        Water pressure too high       Bad high pressure water switch  Insufficient charge    eplace HPWS    B  Ci  Ci  Reduce water pressure to below 300 psig  R  Check for refrigerant leaks       Compressor pump down at start up    Reduced or no water flow in heating    Check charge and start up water flow     heck pump operation or water valve operation setting        ugged strainer or filter  Clean or replace         heck water flow adjust to proper flow rate        Inadequate antifreeze level    heck antifreeze density with hydrometer        Improper temperature limit setting  30  F vs  10  F   1   C vs  2 C         Water Temperature out of range    ring water temp within design parameters        Bad thermistor    Reduced or no air flow in cooling    heck temp and impedance correlation per chart  heck for dirty air filter and clean or replace           Ci  P  Ci  
91. ped from a  reservoir outside of the building when possible or introduced  under the water level to prevent fumes  Calculate the   total volume of fluid in the piping system  Then use the  percentage by volume shown in Table 2 for the amount   of antifreeze needed  Antifreeze concentration should be  checked from a well mixed sample using a hydrometer to  measure specific gravity     Low Water Temperature Cutout Setting   CXM Control  When antifreeze is selected  the FP1 jumper  JW3  should  be clipped to select the low temperature  antifreeze 10  F    12 2  C   set point and avoid nuisance faults  see    Low  Water Temperature Cutout Selection    in this manual   Note   Low water temperature operation requires extended range  equipment     Table 1  Approximate Fluid Volume  gal   per 100  of Pipe    Fluid Volume  gal  liters  per 100     30 meters  Pipe        Pipe Size Volume  gal   liters   1    4 1  15 3  6 4  23 8  2 5  9 2  34 3  Rubber Hose 1    3 9  14 6  3 4  IPS SDR11 2 8  10 4  1    iPS SDR11 4 5  16 7  1 25    IPS SDR11 8 0  29 8  1 5    IPS SDR11 10 9  40 7   2    IPS SDR11 18 0  67 0   1 25    IPS SCH40 8 3  30 9   1 5    IPS SCH40 10 9  40 7   2    IPS SCH40 17 0  63 4   1 0  3 8           Copper                            Polyethylene                Typical    10  Dia x 3ft tall   254mm x 91 4cm tall     Unit Heat Exchanger       Flush Cart Tank 10  37 9              Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       Ground Loop Heat Pump Appl
92. pen for 30 seconds prior to compressor power up it  will be considered a low pressure  loss of charge  fault  The low  pressure switch input is bypassed for the initial 60 seconds of a  compressor run cycle    Low pressure lockout code  3   Water coil low temperature  FP 1   The FP 1 thermistor  temperature must be below the selected low temperature limit  setting for 30 continuous seconds during a compressor run  cycle to be recognized as a FP 1 fault  The FP1 input is bypassed  for the initial 120 seconds of a compressor run cycle  FP1 is  set at the factory for one try  Therefore  the control will go into  lockout mode once the FP 1 fault has occurred    FP1 lockout code  4                   Air coil low temperature  FP 2   The FP2 thermistor temperature   must be below the selected low temperature limit setting for   30 continuous seconds during a compressor run cycle to be   recognized as a FP2 fault  The FP2 input is bypassed for the   initial 120 seconds of a compressor run cycle  FP2 is set at the   factory for one try  Therefore  the control will go into lockout   mode once the FP2 fault has occurred    FP2 lockout code  5   Condensate overflow  The condensate overflow sensor   must sense overflow level for 30 continuous seconds to   be recognized as a CO fault  Condensate overflow will be   monitored at all times    CO lockout code  6   Over under voltage shutdown  An over under voltage   condition exists when the control voltage is outside the range   of 18VAC to 3
93. peration  compressdractivates    Q System pH  Check and adjust water pH if necessary to b  Check for cool air delivery at the unit grille within a  maintain a level between 6 and 8 5  Proper pH promotes few minutes after the unit has begun to operate   longevity of hoses and fittings  see Table 3   Note  Units have a five minute time delay in the   Q System flushing  Verify that all air is purged from the control circuit that can be bypassed on the CXM     DXM control board as shown below in Figure 27  See  controls description for details    c  Verify that the compressor is on and that the water  flow rate is correct by measuring pressure drop  through the heat exchanger using the P T plugs and  comparing to Tables 9a through 9b    d  Check the elevation and cleanliness of the  condensate lines  Dripping may be a sign of a    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012    blocked line  Check that the condensate trap is filled  to provide a water seal    e  Referto Table 10  Check the temperature of both  entering and leaving water  If temperature is within  range  proceed with the test  If temperature is outside  of the operating range  check refrigerant pressures  and compare to Tables 11 through 12  Verify correct  water flow by comparing unit pressure drop across  the heat exchanger versus the data in Tables 9a  through 9b  Heat of rejection  HR  can be calculated  and compared to catalog data capacity pages  The  formula for HR for systems with water is
94. present        Low refrigerant charge    Check superheat and subcooling per chart        Restricted metering device    Check superheat and subcooling per chart  Replace        Defective reversing valve       Perform RV touch test        Thermostat improperly located    Check location and for air drafts behind stat        Unit undersized    Recheck loads  amp  sizing  Check sensible clg  load and heat pump capacity        Scaling in water heat exchanger    Perform scaling check and clean if necessary        Inlet water too hot or too cold    Reduced or no air flow in heating    Check load  loop sizing  loop backfill  ground moisture   Check for dirty air filter and clean or replace        Check fan motor operation and air flow restrictions        Too high of external static  Check static vs  blower table        Reduced or no water flow in cooling    Check pump operation or valve operation setting        Check water flow  Adjust to proper flow rate        Inlet water too hot       Check load  loop sizing  loop backfill  ground moisture        Air temperature out of range in heating    Bring return air temperature within design parameters        Scaling in water heat exchanger    Perform scaling check and clean if necessary        Unit overcharged    Check superheat and subcooling  Re weigh in charge        Non condensables in system    Vacuum system and re weigh in charge        Restricted metering device     Reduced water flow in heating     Check superheat and subcooling per 
95. problems     RE Check fault LED code  Start up  on control board        No fault  shown                 No  See  Unit    short Unit hor Replace  cycles  Cycles  CXM  No       See    Only   Yes Only F See FP2 See See Over   Fan unt Ei Fault Condensate Under  Fault Voltage    N    See  Only   Yes Only  Comp Compressor    Runs  Runs                     Did unit lockout  after a period of  operation   No    See  Does Does unit  not Operate operate in  in Clg  cooling                    Unit is OK      See Performance  Troubleshooting  for  further help    Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012    Functional Troubleshooting    Main power problems    HP HPWS Fault  Code 2    High Pressure    LP LOC Fault  Code 3    Low Pressure   Loss of Charge    LT1 Fault  Code 4    Water coil low  temperature limit    LT2 Fault  Code 5    Air coil low  temperature limit    Condensate Fault  Code 6    Over Under  Voltage Code 7     Auto resetting     Unit Performance Sentinel  Code 8    No Fault Code Shown    Unit Short Cycles    Only Fan Runs    Possible Cause    Green Status LED Off    Reduced or no water flow in cooling    Solution  heck line voltage circuit breaker and disconnect        heck for line voltage between L1 and L2 on the contactor        heck for 24VAC between R and C on DXM2       heck primary secondary voltage on transformer        heck water flow adjust to proper flow rate        Water Temperature out of range in cooling    ring water temp within design 
96. r the specific unit series and model to correlate speed   tap to airflow in CFM  The dehumidification mode can be  enabled in two ways        1  Constant Dehumidification Mode  When the  dehumidification mode is selected  via DIP switch or  jumper setting   the ECM motor will operate with a  multiplier applied to the cooling CFM settings  approx   20 25  lower airflow   Any time the unit is running in  the cooling mode  it will operate at the lower airflow  to improve latent capacity  The    DEHUM    LED will be  illuminated at all times  Heating airflow is not affected   NOTE  Do not select dehumidification mode if  cooling setting is tap 1    2  Automatic  Humidistat controlled  Dehumidification  Mode  When the dehumidification mode is selected   via DIP switch or jumper setting  AND a humidistat is  connected to terminal DH  version Il  or HUM  version  I   the cooling airflow will only be reduced when the  humidistat senses that additional dehumidification is  required  The DH  or HUM  terminal is reverse logic   Therefore  a humidistat  not dehumidistat  is required   The  DEHUM  LED will be illuminated only when  the humidistat is calling for dehumidification mode   Heating airflow is not affected  NOTE  Do not select  dehumidification mode if cooling setting is tap 1           Residential Packaged Units   60Hz Puron     Rev   4Jan   2012    ECM Blower Control       Table 5  ECM Board Tap Settings    Cooling settings  GT PX and GT PG Units Heating settings  GT PG and GT
97. r to setting the unit  Refer to  Figures 7 and 8 for typical installation illustrations  Refer to  unit specifications catalog for dimensional data    l  Install the unit on a piece of rubber  neoprene or other  mounting pad material for sound isolation  The pad  should be at least 3 8   10mm to 1 2   13mm  in  thickness  Extend the pad beyond all four edges of the  unit    2  Provide adequate clearance for filter replacement  and drain pan cleaning  Do not block filter access  with piping  conduit or other materials  Refer to unit  specifications for dimensional data    3  Provide access for fan and fan motor maintenance and  for servicing the compressor and coils without removing  the unit    4  Provide an unobstructed path to the unit within the  closet or mechanical room  Space should be sufficient to  allow removal of the unit  if necessary    5  Provide access to water valves and fittings and  screwdriver access to the unit side panels  discharge  collar and all electrical connections     Downflow units may be installed directly on the floor  The  optional internal electric heat is rated for zero clearance to  combustible materials     The installation of water source heat pump units and all  associated components  parts and accessories which make  up the installation shall be in accordance with the regulations  of ALL authorities having jurisdiction and MUST conform to  all applicable codes  It is the responsibility of the installing  contractor to determine and comply
98. re recommendations only   State provincial and local codes MUST be followed and  installation MUST conform to ALL applicable codes  It is  the responsibility of the installing contractor to determine  and comply with ALL applicable codes and regulations        Pre Installation   Prior to installation  locate and mark all existing underground  utilities  piping  etc  Install loops for new construction before  sidewalks  patios  driveways  and other construction has  begun  During construction  accurately mark all ground loop  piping on the plot plan as an aid in avoiding potential future  damage to the installation     Piping Installation   The typical closed loop ground source system is shown in  Figure 12  All earth loop piping materials should be limited to  polyethylene fusion only for in ground sections of the loop   Galvanized or steel fittings should not be used at any time  due to their tendency to corrode  All plastic to metal threaded  fittings should be avoided due to their potential to leak in earth  coupled applications  A flanged fitting should be substituted   P T plugs should be used so that flow can be measured using  the pressure drop of the unit heat exchanger    Earth loop temperatures can range between 25 and   110  F   4 to 43  C   Flow rates between 2 25 and 3 gpm  per ton  2 41 to 3 23 I m per kW  of cooling capacity is  recommended in these applications     Test individual horizontal loop circuits before backfilling   Test vertical U bends and pond loo
99. riodically to insure indoor  air quality  The condensate drain can pick up lint and dirt   especially with dirty filters  Inspect the drain twice a year to  avoid the possibility of plugging and eventual overflow     Compressor   Conduct annual amperage checks to insure that amp draw  is no more than 1096 greater than indicated on the serial  plate data     Fan Motors   All units have lubricated fan motors  Fan motors should  never be lubricated unless obvious  dry operation   is suspected  Periodic maintenance oiling is not  recommended  as it will result in dirt accumulating in the  excess oil and cause eventual motor failure  Conduct annual  dry operation check and amperage check to insure amp  draw is no more than 1096 greater than indicated on serial  plate data     Air Coil   The air coil must be cleaned to obtain maximum  performance  Check once a year under normal operating  conditions and  if dirty  brush or vacuum clean  Care must  be taken not to damage the aluminum fins while cleaning   CAUTION  Fin edges are sharp     Cabinet   Do not allow water to stay in contact with the cabinet for  long periods of time to prevent corrosion of the cabinet sheet  metal  Generally  vertical cabinets are set up from the floor   a few inches  7   8 cm to prevent water from entering the  cabinet  The cabinet can be cleaned using a mild detergent     Refrigerant System   To maintain sealed circuit integrity  do not install service  gauges unless unit operation appears abnormal  Ref
100. rizontal Installation    Figure 3  Typical Horizontal Unit Installation    a    3 8   10mm  threaded rods   by others  A ct    Return Air             Optional Low Pressure Drop Water    Control Valve     can be internally mounted    Thermostat    on some models     Wiring          Power Wiring Stainless steel braid hose    with integral  J  swivel    Supply Air        Optional Balancing Valve             Building  X 44 Loop  Insulated supply duct with bcne Duct d  onnector    at least one 90 deg elbow Unit Powe Water Out  to reduce air noise Disconnect Water In     by others   Unit Hanger    Ball Valve with optional  integral P T plug    u    Air Coil   To obtain maximum performance  the air coil should  be cleaned before start up  A 1096 solution of dishwasher  detergent and water is recommended for both sides of the coil   A thorough water rinse should follow  UV based anti bacterial  Systems may damage e coated air coils     Residential Packaged Units   60Hz Puron     Rev   4 Jan   2012       Overview   Horizontal units can be field converted between  side  straight  and back  end  discharge using the instructions  below     Note  It is not possible to field convert return air between left or  right return models due to the necessity of refrigeration copper  piping changes     Preparation   It is best to field convert the unit on the ground  before hanging  If the unit is already hung it should be taken  down for the field conversion     Side to Back Discharge Conversion  
101. rn valve  going into the flush cart reservoir  This  dead heads  the  pump to 50 psi  345 kPa   To purge  dead head the pump  until maximum pumping pressure is reached  Open the  return valve and a pressure surge will be sent through the  loop to help purge air pockets from the piping system    4  Notice the drop in fluid level in the flush cart tank when  the return valve is shut off  If air is adequately purged from  the system  the level will drop only 1 2 inches  2 5   5 cm   in a 10   25 cm  diameter PVC flush tank  about a half  gallon  2 3 liters   since liquids are incompressible  If the  level drops more than this  flushing should continue since  air is still being compressed in the loop fluid  Perform the     dead head    procedure a number of times Note  This    fluid level drop is your only indication of air in the loop     5  Consult Whole House Dehumidification AOM  for flushing instructions for units equipped with  Whole House Dehumidification Whole House  Dehumidification option     Antifreeze may be added before  during or after the flushing  procedure  However  depending upon which time is chosen   antifreeze could be wasted when emptying the flush cart  tank  See antifreeze section for more details     Loop static pressure will fluctuate with the seasons   Pressures will be higher in the winter months than during  the cooling season  This fluctuation is normal and should  be considered when charging the system initially  Run the  unit in either heating or c
102. set for stage 2  the alarm relay will NOT cycle during  test mode    On   Stage 1  Off   Stage 2   DIP switch 3  Not Used    DIP switch 4  DDC Output at EH2   provides selection for       CXM Controls    DDC operation  If set to    DDC Output at EH2     the EH2  terminal will continuously output the last fault code of   the controller  If set to    EH2 normal     EH2 will operate as  standard electric heat output    On  EH2 Normal  Off   DDC Output at EH2    NOTE  Some CXM controls only have a 2 position DIP switch  package  If this is the case  this option can be selected by  clipping the jumper which is in position 4   of SW1    Jumper not clipped  EH2 Normal  J umper clipped   DDC  Output at EH2    DIP switch 5  Factory Setting   Normal position is    On     Do  not change selection unless instructed to do so by   the factory     Table 6a  CXM LED And Alarm Relay Operations    Description of Operation    Normal Mode    On  Normal Mode with UPS Warning On Cycle  closed 5 sec   Open 25 sec    CXM is non functional Open  Fault Retry Slow Flash Open  ast Flash Closed    Open  Closed after 15 minutes     Alarm Relay          Over Under Voltage Shutdown Slow Flash    Test Mode   No fault in memory   Flashing Code 1  Test Mode   HP Fault in memory   Flashing Code 2    ing Code 1       ing Code 2    ing Code 3    Test Mode   LP Fault in memory  Flashing Code 3  Test Mode   FP1 Fault in memory   Flashing Code 4 ing Code 4       Test Mode   FP2 Fault in memory   Flashing Code 5    T
103. should be used   2 stage heat 2 stage cool or 3 stage heat 2 stage cool      HFC 410A packaged units built after May 2009 have ECM  controller version Ill  P N 17B0034N01   This controller  includes logic and a relay to control the HWG functions     Note  Power must be off to the unit for at least three  seconds before the ECM motor will recognize a speed  change  The motor will recognize a change in the CFM  Adjust or dehumidification mode settings while the unit is  powered     There are four different airflow settings from lowest airflow  rate  speed tap 1  to the highest airflow rate  speed tap 4    The charts below indicate settings for both versions of the  ECM interface board  followed by detailed information for  each setting        Cooling Settings  The cooling setting determines the  cooling  normal  CFM for all units with ECM motor   Cooling  normal  setting is used when the unit is not in  dehumidification mode  Tap 1 is the lowest CFM setting   while tap 4 is the highest CFM setting  To avoid air coil  freeze up  tap 1 may not be used if the dehumidification  mode is selected  Consult submittal data or specifications  catalog for the specific unit series and model to correlate  speed tap setting to airflow in CFM     Heating Settings  The heating setting determines the  heating CFM for GT PX  50YD  and GT PG  50YE  units   Tap 1 is the lowest CFM setting  while tap 4 is the highest  CFM setting  Consult submittal data or specifications  catalog for the specific u
104. t 125  F  52  C  OR LT2 lt   40  F  4 C    No compressor operation    for poor water flow  or air flow          Only Fan Operates         Compressor overload    heck and replace if necessary        Control board  Dirty air filter    power and check operation   and clean air filter           Unit in  test mode        power or wait 20 minutes for auto exit        Unit selection    nit may be oversized for space  Check sizing for actual load of space        Compressor overload  Thermostat position    heck and replace if necessary  nsure thermostat set for heating or cooling operation        Unit locked out    heck for lockout codes  Reset power        Compressor Overload       heck compressor overload  Replace if necessary                 Thermostat wiring       Check thermostat wiring at heat pump  Jumper Y1 and R for compressor operation  in test mode        45    46    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012    Functional Tro ubleshooting    Only Compressor Runs    Unit Doesn t Operate  in Cooling    Performance Troubleshooting    Thermostat wiring    Check G wiring at heat pump  Jumper G and R for fan operation          Fan motor relay    Jumper G and R for fan operation  Check for voltage at blower relay        Check fan power enable relay operation  if present         Fan motor    Check for line voltage at motor  Check capacitor        Thermostat wiring    Reversing valve    Check thermostat wiring at heat pump  Jumper Y1 and R for compressor  operati
105. te drain line  Do not  through return air grilles  install units with a common trap and or vent     2  Mount the unit on a Tranquility Unit Isolation Pad to  minimize vibration transmission to the building structure   For more information on Tranquility Unit Isolation Pads     AES Figure 10a  Vertical Condensate Drain  contact your distributor      3 4  FPT  Figure 9  Vertical Sound Attenuation Vent           3 4  PVC    1 4    per foot  21mm per m   slope to drain    Water Alternate  Connections Condensate  A Location                   Isolation Pad                           Some units include a painted drain connection  Using a  7  threaded pipe or similar device to clear any excess paint  Insulated Sound Baffle accumulated inside this fitting may ease final drain line installation      Open Both Ends and Bottom              Return Air Louver or Grille  Figure 10b  Vertical Internal Condensate Trap    m Drain pan connection                                 Dashed lines trace  routing of internally  trapped condensate    drain tubing    3 Above photo shows bottom half of typical vertical packaged unit    Residential Packaged Units   60Hz Puron     Rev   4Jan   2012       External Flow Controller Mounting   The Flow Controller can be mounted beside the unit as  shown in Figure 12  Review the Flow Controller installation  manual for more details     Water Connections Residential  Distributor  Models  Residential models utilize swivel piping fittings for water  connections that 
106. tting  The field installed high pressure switch shall have a cut out  pressure of 300 psig and a cut in pressure of 250 psig  This  pressure switch can be ordered with a 1 4    internal flare  connection as part number 39B0005N02     A CAUTION  A    CAUTION  Refrigerant pressure activated water regulating  valves should never be used with this equipment     Thermostat Installation   The thermostat should be located on an interior wall in a  larger room  away from supply duct drafts  DO NOT locate  the thermostat in areas subject to sunlight  drafts or on  external walls  The wire access hole behind the thermostat  may in certain cases need to be sealed to prevent erroneous  temperature measurement  Position the thermostat back  plate against the wall so that it appears level and so the  thermostat wires protrude through the middle of the back  plate  Mark the position of the back plate mounting holes  and drill holes with a 3 16     5mm  bit  Install supplied  anchors and secure plate to the wall  Thermostat wire must  be 18 AWG wire  Wire the appropriate thermostat as shown  in Figures 24 and 25 to the low voltage terminal strip on the  CXM  units with PSC motor  or ECM control board  units  with ECM motor   Practically any heat pump thermostat will  work with these units  provided it has the correct number of  heating and cooling stages     NOTICE  Units with Whole House Dehumidification whole  house dehumidification option require a separate humidistat  or thermostat part 
107. uces scaling potential     The temperature set point of the HWG is field selectable   to 125  F or 150 F   The 150  F set point allows more heat  storage from the HWG  For example  consider the amount  of heat that can be generated by the HWG when using the  125  F set point  versus the amount of heat that can be  generated by the HWG when using the 150 F set point     In a typical 50 gallon two element electric water heater   the lower element should be turned down to 100  F  or the  lowest setting  to get the most from the HWG  The tank will  eventually stratify so that the lower 8096 of the tank  or 40  gallons  becomes 100  F  controlled by the lower element    The upper 2096 ofthe tank  or 10 gallons  will be maintained  at 125  F  controlled by the upper element      Using a 125  F set point  the HWG can heat the lower 40  gallons of water from 100  F to 125  F  providing up to 8 330  btu s of heat  Using the 150  F set point  the HWG can heat  the same 40 gallons of water from 100  F to 150  F and the  remaining 10 gallons of water from 125  F to 150  F  providing  a total of up to 18 743 btu s of heat  or more than twice as  much heat as when using the 125  F set point     This example ignored standby losses of the tank  When    those losses are considered the additional savings are even  greater     A WARNING  A    WARNING  A 150  F SETPOINT MAY LEAD TO    SCALDING OR BURNS  THE 150  F SET POINT MUST  ONLY BE USED ON SYSTEMS THAT EMPLOY AN  APPROVED ANTI SCALD VALVE 
108. ull Load Cooling   without HWG active    Full Load Heating   without HWG active       Entering  Water  Temp   F    Water  Flow  GPM ton    Suction  Pressure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water  Temp Rise  oF    Air Temp  Drop   F  DB    Suction  Pressure  PSIG    Discharge  Pressure  PSIG    Superheat    Subcooling    Water  Temp Drop  F    Air Temp  Rise F  DB       30     1 5  2 25    114 124  113 123  113 123    170 190  150 170  131 151    27 32  27 32  27 32    10 15  9 14  7 12    17 2 19 2  12 7 14 7  8 2 10 2    17 23  17 23  17 23    69 79  72 82  75 85    286 306  289 309  292 312    5 10  5 10  6 11    5 10  6 11  6 11    4 5 6 5  3 9 5 9  3 2 5 2    16 22  17 23  18 24       130 140  129 139  129 139    226 246  208 228  190 210    10 15  10 15  10 15    6 11  5 10  4 9    17 8 19 8  13 3 15 3  8 8 10 8    20 26  20 26  20 26    100 110  105 115  110 120    315 335  322 342  330 350    7 12  8 13  10 15    6 11  6 11    9 11  7 9  5 7    22 28  23 29  24 30       132 142  131 141  131 141    290 310  273 293  255 275    6 11  6 11  6 11    6 11  5 10  4 9    17 3 19 3  12 8 14 8  8 3 10 3    19 25  19 25  19 25    131 141  138 148  145 155    347 367  358 378  369 389    11 16  13 18  16 21    13 4 15 4  10 12  6 9 8 9    29 35  30 36  31 37       136 146  135 145  135 145    370 390  350 370  330 350    6 11  6 11  6 11    6 11  5 10  4 9    16 18  11 8 13 8  7 6 9 6    17 23  17 23  17 23          143 153  142 152  141 151    4
109. ury or death     The heat pump  water piping  pump  and hot water tank  should be located where the ambient temperature does   not fall below 50  F  10  C   Keep water piping lengths at a  minimum  DO NOT use a one way length greater than 50 ft    one way   15 m   See Table 7 for recommended piping sizes  and maximum lengths     All installations must be in accordance with local codes  The  installer is responsible for knowing the local requirements   and for performing the installation accordingly  DO NOT  connect the pump wiring until  Initial Start Up  section   below  Powering the pump before all installation steps are  completed may damage the pump     Water Tank Preparation   1  Turn off power or fuel supply to the hot water tank    2  Connect a hose to the drain valve on the water tank    3  Shutoffthe cold water supply to the water tank    4  Openthe drain valve and open the pressure relief valve  or a hot water faucet to drain tank    5  When using an existing tank  it should be flushed with  cold water after it is drained until the water leaving the  drain hose is clear and free of sediment    6  Close all valves and remove the drain hose    7  Install HWG water piping     HWG Water Piping   l  Using atleast 5 8   16mm  O D  copper  route and install  the water piping and valves as shown in Figures 14 or  15  Install an approved anti scald valve if the 150  F HWG  setpoint is or will be selected  An appropriate method  must be employed to purge air from the HWG pipi
110. v193jo1 ot Jo Suruodo 10    sayer  MOV JO samgje1oduro  prbr 10 11e  eurrouqe ye uonerodo  Apddns prnbr  10 ste oA1501100 10 pojeurumuoo  uongorddi  uone1oe pozuouneun  Suruqai    poop    ory  osnqe  oouosi 8ou  osnsrur  juoprooe 03 pajoofqns sjonpoaq  L  suonrpuoo o8ej oA 10 Sut  1redor  oouvuojureur   uonv pojsur ojenbopeur 10 1odo1duir 03 pojoofqns sjonpoaq  9   3pvjop ur st  10 2v 3u00 Sur ejsur JO IS   19U 0 I  0  JO    TOLLED 0  juouiKed qorq   uo sjonpoaq  s   poovjop JO poAoura1 uooq JAVY STALI JO s3e  uorjeagnuopr PUN oq  gor uo sjonpoJq  p  3ueuoduroo 10  uoruod yons jo am mej ot Jo osneo ay  jo ssojpae301 soue Aq porddns you st yey  urojs amp s Aue Jo juouoduoo 10 uonrod Kuy  c  tuonv posur  enmur 12v pojeoojo1 sionpoq  Z     TO    spiny 3uv1931321    sasny  sroy ary  T   03   jdde ju soop pue 19400 jou soop Aure1reA smi      ex q uondoour jue   ou Joye ude13vaed sg ur quj Jos spond our oy  uet o10ur pounour ore Kou 10  AjuermA  sso1dxgq pojuirT sip Aq po19400 jou ped v ym uoroouuoo ur paunour are Kor   ouuosred oora1os pozrioqne IV Aq pouro piod   x10A jo  nsa oy  Jou oe Ko  o npouos ooueaoqe  pres ur 10  poprAo1d Aq eogroods jou ore Aay  o npouos souemoyye pres Japun pomoje junoum og  poooxo fou juojxo AP 03 uee y ssoidxzq pour si Aq pa1oA00 jou am sjsoo 1oqe T  enjoy    Aeq uondooug AjuermA  ou uiorj SI  c  DAY JOJ  AIP Suri9jour juv1o3rigor   pur Apog AJLA Suts19A901  s1o8ueqoxo JVA ojuA II 0  JUBIDSTYOI  105s91duroo oq  opnjour ATUO sjuouoduroo qorqA  SMUN  BU
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
INVERTEC 135S, 150S & 170S  Samsung UE22D5010 User manual  Pol Switch user manual  17600LBFF Epic Top Score LBFF Base Highlights  Turbine Service Manual 10-11  Dell Data Protection    Ford 2008 Expedition Automobile User Manual    Copyright © All rights reserved. 
   Failed to retrieve file