Home
        Service
         Contents
1.                                                                    f    prem  1      LT TD   E EES EH E Yu         E    j     E                     i             E E            4 e       E    rJ r  4    V V    VA  y  gt  m  eE pa ee at Ke              Fig  6 3    The control sequences in c h  function are illustrated in  detail in section 6 7     EX Setting the boiler control function modes    Itis possible to select the various boiler control function  modes hereafter named  parameters  by using the  keys of the control panel p c b        Fig  6 4    1 To enter in the parameters setting mode press  contemporary the 3 keys  A     B     C Fig  6 4  for  10 second until the display shows Fig  6 5    13    Main electronic control ignition p c b     VAN                       d  a a     p    I       y Fig  6 9  A Ek 7 To exit for setting without modifing the set press  Fig  6 5 the keys  B     C Fig  6 10     2 To move through the parameters press c h  set  keys  A or C Fig  6 6        Fig  6 10       To reset the boiler to the normal operation press con   temporary the 3 keys  A     B     C Fig  6 4  for 10 sec   3 The display shows Fig  6 7 ond     Fig  6 6    1 1 The following table gives details of each parameter and  AAA NANA NAIA NVI the possible value that can be set       ml        gt  rm   Important  atthe end ofthe setting operation it is im   yu  4          Lf   portant to fill update the table in the installation    manual see chapter COMMISSIONING section  Set   LAAN 
2.                         JH    Ton Bee is                   Ht                                                                                                    Fig  9 2    EF Checks    Lk  Temperature resistance relationship    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component     Disconnect the cable from the Temperature probe     Measure the temperature of the pipe C  ch flow Tem   perature probe   Fig  9 3  or of the pipe D  c h  return  Temperature probe   Fig  9 4  where the Temperature  probe is located and check the electrical resistance ac   cording to the graph in Fig  9 1     EE Removal of the c h flow Temperature  probe    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component     1 Remove all the case panels     2 Remove the electric connector E and remove the  c h  Temperature probe A     Fig  9 3    3 Reassemble the c h  flow Temperature probe  carrying out the removal operations in reverse  order                    Fig  9 3    EX Removal of the c h  return Temperature  probe    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component     Remove all the case panels     2 Remove the electric connector F and c h  return  Temperature probe B     Fig  9 4    3 Reassemble the c h  return Temperature probe  carrying out the removal operations in reverse  order     25    Temperature probe          Fig  9 4
3.                         arene                                                                                 udin dir          o0000                                                             ES   gt                                                                                                  jan d                           230                                         Supply network Fan Safety  thermostat       Fault finding    4       Components to check       12 2   12 2   13 1    9 2 10 11 4    8 4    6 5    Section of the manual     note ref  in brackets     pafejap je soulay  WOOY  eqoud duet   eula x3    euajxe ongf eunsseJg  Jeu1ejxe anyen Ajayes   eujejxe   assea uoisuedx3  OLN eqoid duet an   10 911 S91 Sec    esow  uy    jejes  epoJjpeje uonoejeq  opourpeje uou   10 911 S91 11e   ue4   eqoud duet una  y    eqoud duet wou uo   INEA SEL     q o d joeje jeued ouo  sbumes Joo    q o d oiuodoeje UIEN    qr o d oiuo4o9 3  sesny  duund  euJe1x3   goDueuoxe yeay Buisuepuo   mom    y O   den pue edid urep    puoy  sedid any   au   iddns seo    au A ddns 160g    Defect            x  1n0  x90  eoueiddy          Er 01  Er 02  Er 03  Er 04  Er 05  Er 06  Er 08  Er 09  Er 10  An 11                                  Er 14  Er 15       Er 16    Er 17  Er 18    e  Air                     13  Sajeo  pur   ejdsiq          indu  yeay jeuruiou   y  yoes   useop joq   y 8   jenueuu uonej eisui osje ees   N  enau pue  7  au ueeweq  AOEZ 10  204D      Dui 1094100 Sy Auen pue INDIO ay  j
4.                     32  FUNCION  e saya sitet totaque qa dedit 32  Check the cleanness of the trap          32  REMOVAL  uere 32  Short spare parts list                  33    Overall information    EX Overall View    1           C h   water return                                                                                           C h   water flow                                                                                                                                                 o o 929 o  Q ER o 2  38 22 23 3   o pa oF SS  ag cg D   GBS  Oo E co o  g Os ix  8   2 0 o  wo   C 2   8  cos   2 od    i Ss 2  Cot OF cg  oco oc og ES     esa Us      2  o   P  Eh o5 52    Ox  T fa     w  o    EN c  5 23 O    ES t     2  o 62   El H  a o  a Q        O  gt  N  ne  c  DOWN t  y e 9  WAL S     7 e Ee  ANN DG ED END E Lal AN 2    4  A Ze os B   A  gt  a a LE  MINERO Y SR WA  S LIE ait  d   Y M NS OVA AN D  o    1 EY 5  TIU        XS RE ISLAS vw m   Gei B Moi  x ERA X SSS   U     US   X RON     NIU     QA E a E Y 5   gt  TIT  o D N Ue WIA E Ped MUR  5 1 MM A d d KA c annn  BO    ENY A o E     a    s  5                      T 4 d       j  Ge bebe A LA o  F e  go 7 WRI  oa 7  z  3 d  iL                      S   7    pen   A o o    i  eg co L 3 o   Ed D o o Oo SE   2   ome  co c 59 c 8 5 G   E oo be   bai o o  gt    Sr OX 3 go  ne  06 2 o   Ao eo m       ID o      ES HS ao   Gd oO  SS 3 0    ER Hydraulic diagram    2 General access and emptying  hydraulic circuits    PX Nomen
5.     26       10 Fan and Air box  HERR Function    The function of the Fan A  Fig  10 1  is to force the mix   ture of air and gas into the burner     The function of the Air box B is to mix the gas and the  air in the right proportion     The flow rate of the air   gas mixture and consequently  the input power ofthe boiler is proportionalto the speed  of the fan that is controlled by the electronic control  p c b                                                                                                                                                                        J  TN  CTI i  x  ogl  RRA 1 h      gl B  AA  Hi  AY  m    Uf  A      ot  Fig  10 1    ER Removal of the Fan and the Air box    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component     1 Turn off the gas supply   2 Remove all the case panels  see section 2                     3 Disconnect the rubber pipe C  Fig  10 2      Unscrew the gas connectors D and remove the  gas pipe E     5 Disconnect the connector F    Disconnect the fan connector G by pressing the  plastic hook placed on the side of the connector     Unscrew the screws H   8 Remove the fan A with the air box B     9 Remove the screws  and the air box B  Fig  10 3         Fig  10 3    10 Open the strip J by sliding the edges with the help  of a screwdriver and remove the Air box  Fig  10 4        Fig  10 4    11  Assemble the Fan and the Air box carrying out  the removal operations in reve
6.    Fig  12 2    4 Reassemble the safety thermostat carrying out  the operations in reverse order     5 Apply an adequate quantity of heat conducting  compound between the condensing heat ex   changer and the thermostat     Warning  After cleaning or replacement as  detailed above  it is deemed necessary to  undertake a combustion analysis as detailed  in chapter 8 3 section 11        13  Flue temperature probe NTC and  Safety thermal fuse    ES Function    The Flue temperature probe NTC A in Fig  13 1 and  Fig  13 2 senses the temperature of the combustion  products that flow through the condensing heat ex   changer        SSS a2   uf  M      e     W i             n                                                                                                                                                             Fig  13 1    If the temperature of the combustion products circuit  reaches the limit temperature  the Flue temperature  probe NTC reduces the gas flow rate to the burner  The  temperature of the combustion products should de   crease to a safe value temperature     In the case that the temperature of the combustion  products reaches a potentially dangerous value  it  stops the boiler operation  lock     out      This allows the use of plastic materials for the flue outlet  pipes and bends     The use of kits different from the original isn   t however  allowed  since the flue pipes are integral parts of the  boiler                          Fig  13 2    ERR Rem
7.    Wall hung  fan flue  room sealed  high efficiency gas boiler    Service manual    ActivA   Models  G C  Appl  No   Activ A 120V   Activ A 150V   Activ A 200V   Activ A 250V    Leave this manual adjacent to the gas meter    Warning   Service   repairs must be carried out  only by a qualified Gas  Safety Registered Engineer  who will be responsible for the cur   rent Regulations for gas appliances        recommended          Table of contents    N     ech  mb  NOOROM A oio A Mi A  o ES a    A 009090000 AAA PA WWA NN    NN  a    DESEN  oR w    Overall information                    1  Overall View      1  Hydraulic diagram      1  General access and emptying   hydraulic circuits                      2  Nomenclature        o oooocooccoooccooo   2  Case panels               cece eee eee 2  Control panel      2  Main electronic p c b  box               3  Emptying the primary circuit             4  Diagrams                 eene 5  Wiring diagram            ssssseeseess 5  Circuit voltages              sssusuususue 6  Fault finding                          7  Display diagnostic                      9  Condensing heat exchanger            10  Function opes ce bd Re EN re a 10  RE ue VC 10  Gleaning  eet eee a eee ok 11  Main electronic control ignition p c b    12  FUNCION  o ud ri operant 12  Selection and adjustment devices        12  Checking the temperature               13    Setting the boiler control function modes 13  Checks  Removal of the electronic control p c b    15  
8.   Condensate trap    EAN Function    The condensate trap A in Fig  14 1 and Fig  14 3 allows  the discharge of the condensate via the condensate  drain pipe avoiding in the mean time the escape of  combustion products     A plastic ball closes the trap outlet in case that the trap  is empty                                                                                                                                                                              MAS  i   ISS a   ES EEE       Ia  A  L       AM   A    M nl  Fig  14 1    If the drain pipe becomes blocked  or condensate can   not drain  the condensate level it the trap rises until it re   aches the screw attached to the flame detection elec   trode  this will cause the boiler lock     out      EEN Check the cleanness of the trap    1 Unscrew the screws B and remove the plate C   Fig  14 2               Fig  14 2    32    Unscrew the plug D on the bottom ofthe trap A and re   move dirt eventually deposit  Fig  14 3       TEN Removal    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component    1 Remove the front and right case panels     2 Unscrew the screws B and remove the plate C   Fig  14 2     3 Unscrew the threaded locking ring E and remove  the flexible pipe F  Fig  14 3     4 Disconnect the electric connector G  Fig  14 3      Fig  14 4        Fig  14 3    5 Remove the forks H and remove the condensate  trap A moving it downwards  Fig  14 3                
9.   Fig  14 4    6 Reassemble carrying out the removal operations  in reverse order           15 Short spare parts list    Key    1       G C  part no     E83   101  H58   661  E23   792       Description    Burner  mod  Activ A 12OV  Activ A 150V  Activ A 200V     Burner  mod  Activ A 25OV     Condensing heat exchanger   mod  Activ A 12OV  Activ A 15OV  Activ A 200V     Condensing heat exchanger  mod  Activ A 25OV   Fan   Gas valve   Main Electronic control ignition p c b    Control panel electronic p c b    Temperature probe  main circuit    Overheat thermostat    Flue temperature probe NTC  Fuse 2 AF 250VAC 5x20  Detection electrode   Ignition electrode  Condensate trap                                                 Q ty    2a 2      2 mi 2 2 2 2 23 2 23            Manufac   turer part no     BI1313 100    Bl1313 101  Bl1462 101    Bl1462 102  Bl1313 102  BI1313 103  BI2035 1138  BI2035 101  Bl1442 106  Bl1172 105  Bl1432 102  Bl1165 112  Bl1313 104  Bl1313 105  Bl1462 104       Manufacturer   s reference    SIT 848 Sigma 0848135    ELTH     type 261       33          32  32  ES    17962 2017 0 1710 36A4 UK    Biasi UK Ltd   Commercial Road  Leamore Enterprise Park  WALSALL   WS2 7NQ   Tel   01922 714600  www biasi co uk    
10.   Fig  2 5                  Fig  2 5    4 To access to the parts located inside the control  panel turn it as shown in Fig  2 6              ei  Ke  7    S    Ze     t  med  NO S           e       Qu   LJ                Fig  2 6    EXI Main electronic p c b  box    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component     To gain access to the parts located into main electronic  p c b  box proceed as follows    1 Remove the front panel of the case    Terminal block lid removal    2 To remove the terminal block lid E  Fig  2 7   free  the front hooks        General access and emptying hydraulic circuits                                              Fig  2 7    3 Slightly rotate the lid as indicated by the curved  arrow and free the rear hooks     4 Remove the lid   Main electronic p c b  lid removal    To get access to the main electronic p c b      5 Pull the box that contains the electronic p c b   and rotate it  Fig  2 8            SFA        Fig  2 8    6 Remove the terminal block lid E  Fig  2 7      7 Free the hooks placed on the three sides indi   cated and rotate the lid towards left  Fig  2 9      3    General access and emptying hydraulic circuits       Fig  2 9   EX Emptying the primary circuit   1 Close the c h  circuit flow and return cocks    2 Remove the front and right panels of the boiler    3 Open the drain tap F  Fig  2 10  until the boiler is  completely emptied           Fig  2 10    4 To help the drain
11.   Thermal control in the  c h   mode       17  Control panel electronic p c b          18  Eupen   Ecl Ede DEUDA 18  Normaly information                    18  Info modality      19  Function modes setting modality         19    Removal of the control panel electr  p c b 19    10 1  10 2    11    11 1  11 2    11 8  11 4  12    12 1  12 2  12 8    13    13 1  13 2  13 8    14    14 1  14 2  14 8    15    Gas valve  volu ox EI t cR Rats 21  FutietlOnizs cud bens vacet et dp teta 21  Description of the parts                 21  Adjustment      21  CHECKS onu che Hath Manes stre memi iss cats 23  Removal of the gas valve                23  Temperature probe                    25  FUNCION vida ara weet une  an 25  CHECKS 2152 reme os IDEE 25  Removal of the c h flow temp  probe      25  Removal of the c h  return temp  probe   25  Fan and Air box               seeeee 27  FutrietlOn   zcez eres e NIU ed wants 27  Removal of the Fan and the Air box       27  Ignition and detection electrodes   and burner               ee eee eee 28  FUNCION geao eise es Cortona 28  Removal of the Ignition and detection  electrodes  cis id 28  Removal of the burner                  28  berechent AES Mem td s 28  Safety thermostat                     30  A uS SEL MS Me 30  Checks   eidbek a baat rani teste 30  Removal  cuasi cia 30  Flue temperature probe NTC   and Safety thermal fuse                31  Functlori    uui ose Sam oak eS 31  Removal    31  CHECKS ahs bue en dii eth 31  Condensate trap  
12.   a oi SI e g 5  alle    3 P  a 3 lo e 8  3  es      8    8  g  2  2 S  8   2   3 8  3   2 0 ei al SI   i sl 2  g  a 3 9 9 ae 3  lt   a    2 9  amp le 8    i Ss  8  3  2      2 s el2d 83g El T   8  2  oa  e s  al  g 8 g so  es  P e T v  S Ed   2 T  2  S  2  2  e    4  gt  z  g a o  g n e  Se E E A a S  3 z aj p 8 a 5  5 S 3 o o H D z t E  a m o    o  E 2 1oejeq   2   v           Q    D  Syexpeuq ul Jas eyou       E SS   ELI CCL   ook vi OL c6 v8 H S9 em S SS Vol      BR SS     enueu ay  jo uonoes       y98Uy9 0  sjueuoduio5       EXI Display diagnostic  The display indications provide help in the diagnosis of    fault finding     The control panel display gives other information forthe    user     The following table gives fault code  error and the reson    for the fault     Er 01   RESET   Lack of burner ignition  Er 02   RESET   Safety thermostat lockout  Er 03   RESET   Other faults    Er 04  4  Er 05 c   Er 06  4    Er 08  4  Er 09  4    Er 10   RESET    Er 14   RESET  Er 15   RESET    Er 16   RESET    Er 17   RESET    Er 18   RESET    Faulty primary circuit  no water or  absence of flow     Faulty fan control system    Faulty c h  temperature probe  NTC    Faulty external temperature probe  NTC  if fitted     Faulty flue temperature probe  NTC    Lockout     flue temperature probe  NTC  Flue temperature  gt  120  C     Faulty pump  absence of water  flow in the main circuit  or primary    temperature above 105   C    None or too low water flow  Faulty  pump  temp  differ
13.  00   Depends on  room thermostat   factory set    04   Always running    00   99  0 100296   factory set     Natural gas  G20   30   Activ A 120V  30   Activ A 15OV  30   Activ A 200V  40   Activ A 250V    Propane  G31    40   Activ A 120V  40   Activ A 150V  40   Activ A 200V  40   Activ A 250V    01   0 1   60   6 0   K value   factory set    00   Off    00   Burner off at  fixed d h w    65  C   factory set    01   Brurner off at  set point  5   C    00   Probe not pres   ent    factory set    01   Probe present    Main electronic control ignition p c b     owed     pr  mees E IN  Norused     prz                  Norused a              Norused     prz          Norused prar          Norused     prz              Noued     prz                    Ch minimum set   Pr27  25   45  factory set  point 25   C     Tab  6 1     XN Checks      Check that the fuses are complete    If the Main electronic control ignition p c b  does not  supply any device  pump  fan  etc   check that the  fuses 10  Fig  6 2  are complete     If afuse has blown replace it with one that has the same  characteristics after having identified the reason for fail   ure        Lock sequence  Start the boiler until the burner is ignited     With the burner firing  interrupt the gas supply  The  Main electronic control ignition p c b  must carry out  four complete ignition cycles and then  after about 4  minutes  goes to lock     out state     Switch off and on the electricity supply to the boiler  by  means of 
14.  2      Important  after the gas pressure checks and any  adjustment operations  all of the test points must be  sealed     EX Checks    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component     Activ A 150V  Activ A 200V  Activ A 250V    Tab  8 2          Fig  8 10    Check the on    off operators coils  Remove the front panel of the case   Disconnect the electrical connector 4  Fig  8 2      Measure the electrical resistance between the  connector pins of the on   off operators as illus   trated in Fig  8 11     Qo mx        ON  OFF Operator  approx  6 400 Q     ON  OFF Operator  approx  920 Q       at ambient temperature   Fig  8 11    EE Removal of the gas valve    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component     1 Remove the front panel of the case as explained  in the section 2 3 of this manual     2 Disconnect the connector D  Fig  8 12      3 Unscrew the screws E and disconnect the earth  connector F                    Fig  8 12    4 Turn off the gas supply and disconnect the gas  isolation cock connector from the inlet port of the  gas valve     5 Using pliers  remove the spring G and the rubber  pipe H  Fig  8 12     6 Unscrew the connectors    Fig  8 12  and remove  the pipe J     7 Unscrew the screws K and remove the valve   Fig  8 12      8 Reassemble the valve carrying out the removal  operations in reverse order     Before fitting a new valve  
15.  a dan   gerous temperature  the safety thermostat opens the  electric circuit that supplies the on    off operators of the  gas valve     Consequently  the full sequence ignition device at   tempts to light the burner and  at the end  locks the  boiler and lights the lock   out on the display                       ule  M   gt      TEETEESER                                                                                                                                                                                     Fig  12 1    IEEJ Checks       Overheat temperature value    1 Run the boiler and set the temperature at maxi   mum by pressing the appropriate key     2 Allow the boiler to reach its maximum operating  temperature  The boiler should maintain a tem   perature below that of the safety thermostat and  no overheat intervention should occur     30    Nx Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component      Electrical function   Remove all the case panels     2 Disconnect the safety thermostat and check its  electrical function  Normally  no intervention  the  contact must be closed  electrical resistance zero  Q       PEN Removal    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component    1 Remove all the case panels    2 Disconnect the wiring B  detail in Fig  12 2      3 Unscrew the screws C and remove the safety  thermostat     ech                      
16.  access to the parts located inside the Con   trol panel electronic p c b  as explained in the  section 2 3 of this manual    3 Remove all the wiring A connected to the Control  panel electronic p c b   Fig  7 3      19    Control panel electronic p c b                    Fig  7 3    20    Unscrew the screws B   Delicately flex the hooks C in the directions indi   cated  Fig  7 3  in order to release the circuit from  the box    Remove the Control panel electronic p c b    Reassemble the Control panel electronic p c b   carrying out the removal operations in the reverse  order        8 Gas valve    EXI Function    The Gas valveA in Fig  8 1 controls the gas inflow to the  boiler burner            Kd RM                                             be   ES   m                   Eza  Le E ES  X  Y  A  Y                                           JM                                                                                                       Fig  8 1    By means of an electric command given to the on off  operators the passage ofthe gas through the Gas valve  can be opened or closed     EX Description of the parts  Fig  8 2                    Fig  8 2    Maximum gas pressure adjustment  Minimum gas pressure adjustment  On  off operators   On  off operators electric connector  Gas valve inlet pressure test point    EEN Adjustment    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component     aR WD      Check the supply pre
17. AAAS 252492 ting record     v PARAMETER DIGIT   VALUES    Boiler type  to be up  00   No power Er 99    EI    mr  wl plete range  19   Activ A 150V  ng Je 4 a 20   Activ A 200V  21   Activ A 250V    EE  GE EE LECH E  Fer  Norused         Pros   A  4 To modify the parameter press contemporary the  Notused  Pros      keys  A     B Fig  6 8     Gas type 00   G20 Natural  05   G31 Propane                   mes pros   gt     C h  flow max Pr07  85   45  factory set  temperature   C 85   C     Factory parameters  Pr 08  00   No reset  04   All parameters  return to factory set  with the exclusion of       Fig  6 8 Pr 01 and Pr 05  39   All parameters  5 To change the parameters press c h  set keys  A return to factory set  or C Fig  6 6  included Pr 01  6 To memorize the setting press the key  B Fig  6 9  and Pr 05    14    PARAMETER DIGIT   VALUES    Chimney  function    sweep    Ch reignition fre   quency    C h  pump post cir   culation    Max  useful output in  c h  mode    C h  pump working  type    Ignition power    K value  external  probe diagram     D h w  burner turn off   Pr 17  function   NTC on the c h  re    turn        No chimney  Soe fun  factory  set     01   Low power    Sweep  test  C h  power    04    sweep test  07   D h w  power  sweep test    00   99  0 600 sec     factory set 30   3  minutes     00   99  0600 sec     factory set 10   1  minute     00   99  0 100    factory set    99   Activ A 120V  99   Activ A 150V  99   Activ A 200V  99     Activ A 25OV   
18. Cleaning    If there are deposits of dirt between the fins of the Con   densing heat exchanger  clean with a bristle paintbrush  and remove the dust with a hoover     Warning  After cleaning or replacement as  detailed above  it is deemed necessary to  undertake a combustion analysis as detailed  in chapter 8 3 section 11     Fig  5 4   20  Unscrew the screws T and remove the plate U   Fig  5 5     21 Remove the forks V and remove the condensate  trap W moving it downwards  Fig  5 4      t          Fig  5 5    11       6    Main electronic control ignition    p c b     EX Function    Fig  6 1  12    Inlet Information    On the Main electronic control ignition    p C D           Function control  C h  temperature adjustment  Boiler reset button     printed circuit board p c b      From other boiler devices        C h  flow temperature probe NTC  C h  return temperature probe NTC  Flue temperature probe NTC  Safety thermostat   Flame detection electrode   Room thermostat  if fitted    Time switch  if fitted        Outlet command    External Pump   Gas valve   Fan   Ignition electrodes  Display indicates  Er       control panel electronic p c b        The fundamental function of the Main electronic con   trol ignition p c b  is that of controlling the boiler in rela   tion to the external needs  i e  heating the dwelling  and  operating in order to keep the temperature of the hy   draulic circuits constant     This is obviously possible within the useful power and  maximum worki
19. be NTC    8 Connector     remote control  optional      9 Connector     display and function control   c h   temperature adjustment control panel p c b     10 Fuse F1  F2 2AF    11 Connector     electric supply Main electronic con   trollignition p c b     12 Connector     electric supply control panel p c b   13 Connector     gas valve  external pump and fan     EEN Checking the temperature    The Main electronic control ignition p c b  makes it  possible adjust the c h  water flow temperature     The temperature of the water is converted into an elec   tric signal by means of temperature probes   The user  setting the desired temperature with the con     trol panel p c b  key A MWS    If the power requested is lower than 4096 of the maxi   mum power output then control is achieved by switch   ing ON the burner at minimum power  then switching  OFF  ON OFF function   If the power requested is  higher  then the burner is switched ON at maximum  power and will control by modulating to 40  of the  maximum power output     During the c h  operation  Fig  6 3   the signal coming  from the c h  temperature probe is compared to the sig   nal given by the control panel p c b  through the adjust   ment made by the user  key  A MISZ   The result of  such a comparison operates the fan speed thus regu   lating the gas flow rate and consequently changing the  useful output of the boiler                                                                                                       
20. clature             Fig  2 1   Right side panel   Main electronic p c b  box  Front panel   Control panel    ao A UO N      Left side panel      N Case panels    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component     For the most part of the check and maintenance oper   ations it is necessary to remove one or more panels of  the case     The side panels can be removed only after the removal  of the front panel     To remove the front panel loosen screws A  Fig  2 2         Fig  2 2     bottom view of the boiler    Pull the lower part of the front panel and lift it upwards   Fig  2 3      2             Fig  2 3    To remove the side panels loosen the screws B   Fig  2 2  andC  Fig  2 3      Pull the side panels towards the outside   To Fit the case panels    Fit the side case panels  Warning   Fit the front panel hooking it on the upper side     Push the front case panel until it is completely hold in  place  Fig  2 4      Ensure that the front panel edge is close fitting to the  side panels     Lock in place the panel with the appropriate screws              Fig  2 4    PEN Contro  panel    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component     To gain access to the parts located inside the control  panel proceed as follows    1 Remove the front panel of the case    2 Unscrew the screw D  Fig  2 5     3 Free the hooks indicated and rotate the lid to   wards left
21. ence between  probes higher than 35   C     Possible exchange of NTC probes   Flow or Return  or pump wrongly  mounted  upside     down     Faulty c h  temperature probe  NTC  Flow or Return     Faulty primary circuit  no water or  absence of flow     Useful output limitation  tempera   ture difference between probes  higher than 25    C    Boiler test  performing    Td Thermostat Delayed   Boiler test  performing    An 11       Parasite flame       5 Condensing heat exchanger    EXI Function    The Condensing heat exchanger A in Fig  5 1 has the  function of transferring heat produced from combus   tion of the gas and from the flue exhausted gas to the  water circulating in it                        gt  2   nim AY               X  bed                                                 TIT TIT ae  Y  WM DUT  FA  du  Rui Wi    ES   gt                                                                                            ae PS      A q  C c y  al i   Je  B      Fig  5 1    By reducing the combustion products temperature  the  latent heat of the vapour is transferred to the water cir   cuit  allowing an extra gain of useful heat     The condensed vapour is then drained through the  condensate trap B and the draining pipe C     EFI Removal    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component    Turn off the gas supply    Remove all the case panels  see section 2    Disconnect the flue system from the boiler   Disconnect 
22. ig  6 12    17    7 Control panel electronic p c b     Function    bas    LH    e  O pes    A  C h  temperature increase key   B  C h  temperature reduce key   C  Reset Stand     by Winter Summer key   D  Display   The Control panel electronic p c b  can give to the ser   vice 3 levels of informations    O Normally information   O Info modality   O Function modes setting modality    Normaly information  KEY       The symbol indicates that the boiler  can be directly reactivated by the user   by pressing the reset button     The symbol indicates that the fault re   quires intervention on behalf of specia     lised technical assistance         Y All symbols represented with lines that   N  surround them  indicate that the sym      MI   bolis flashing     SIGNAL DISPLAYED BY THE LCD       FUNCTION    Lack of burner ignition on safety  Er 01   RESET iockotit   Safety thermostat intervention  Er 02   RESET iock  ut    Er 03   RESET  General lockout  Er 10   RESET  Flue probe interven lockout    Faulty pump or primary tempera   Er PEE RESET ture above 105   C    None or too low water flow  Faulty  Er 15   RESET   pump  temp  difference between  probes higher than 35   C     Possible exchange of NTC probes  Er 16   RESET    Flow or Return  or pump wrongly  Ge  upside     down     18                       Lco  FUNCTION    GE c h  RS probe NTC    Er 18   RESET   primary Zen  no water or    gien absence of flow   Er 04 4 Faulty primary circuit  no water or  absence of flow       DO   B
23. ing of the primary circuit loose  the condensing heat exchanger air purger valve  G  Fig  2 11        Fig  2 11    Attention  some water could remain in the condens    ing heat exchanger    5 Close drain tap once the emptying has been  completed        3 Diagrams    EXI Wiring diagram    Gas valve Fan Condensate  trap           Ignition Flame detection  electrodes electrode                   e    wh    Q    lt   2e   lr                                        t    C h  return temp   probe NTC                                                             t Flue temp   probe NTC                                                                   C h  flow temp   probe NTC                                                                                  Safety  N thermostat                                                                                              Time switch  option     miti       Remote  External temp                             probe  terminal block                            Electric supply  terminal block                                                    Room thermostat  Pump  terminal block                                     bn   brown gn   green   bu   blue ye   yellow   bk   black vt   violet   wh   white Og   orange   rd     red gnye   green yellow  9y   grey rdwh   red white    Diagrams    EEJ Circuit voltages                   Electrical voltages with burner on              during c h  operation  C h  external  pump         Gas valve             230     
24. it is advisable to pre set  it as follows     9 Remove the brass plug and turn the plastic screw  inside it fully clockwise until it stops  Do not over   tight     10 Turn it counter   clockwise 2 and 3 4 turns   23    Gas valve       11  Adjustthe gas valve using the flue analyser as de   scribed in section 8 3     After any service operation on the components of  the gas circuit check all the connections for gas  leaks     Warning  After cleaning or replacement as  detailed above  it is deemed necessary to  undertake a combustion analysis as detailed  in chapter 8 3 section 11     24       9 Temperature probe    EXI Function    The Temperature probe has the function of converting  the temperature of the water in the hydraulic circuit  where itis installed into an electrical signal  resistance      The relation between temperature and electrical resis   tance is stated in Fig  9 1     Q EA A      12000  11500  11000  10500  10000  9500  9000  8500  8000 i  7500  7000  6500                      1000     500                                     20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100  C  Fig  9 1    On the boiler there are two Temperature probes  One  on the output of the primary condensing heat ex   changer  c h  flow Temperature probe  Ain Fig  9 2 and  Fig  9 3  one on the inputof the primary condensing  heat exchanger  c h  return Temperature probe  B in  Fig  9 2 and Fig  9 4     c h  c h                       flow return       JW On          r  3 wei          
25. mm  2      Fig  8 2   by rotating it clockwise the CO2   increases      Checking the maximum gas valve setting                      20  Presskey Ato vary the output in chimney sweep  mode  when the display shows the letters cP that  alternate with the heating water temperature  value  e g 60   the  chimney sweep function    is at  maximum output in heating mode  Fig  8 8     VAN   E EI b  Li        p   di            N  GE  D  I   202 2492  Fig  8 8  21  Pressfurther key A  The display shows the letters    dP that alternate with the heating water tempera   ture value  e g 60   Fig  8 9   On this models this  step is not relevant and the value shown is the  same of the step 20  No setting is needed on this  step     Gas valve       Avra  JL  RU       Y          EN  y      LILI      elek ky             Fig  8 9    22 Allow the analyser to give a stable reading     23 Read the CO     value   It should be between     Type gas CO    value   range   Activ A 120V Natural  G20  8 9    9 8  Propane  G31   9 9     10 8    To adjust the CO     value rotate screw  1     Fig  8 2    by rotating it clockwise the COs 96 decreases      24 Press keys A     B     C  Fig  8 5  at the same time  again to exit the  chimney sweep mode  and re   turn to the previously set boiler status  Fig  8 10                 function  cal la 3    25 Switch off the boiler and turn off the room ther   mostat     26 Close the air   flue sampling points   27 After adjustment fit the protective brass plug  2   Fig  8
26. ng temperature limits foreseen     Generally  the Main electronic control ignition p c b  re   ceives inlet information coming from the boiler  the  sensors  or from the outside  printed circuit board  p c b   room thermostat  etc    processes it and conse   quently acts with outlet commands on other compo   nents of the boiler  Fig  6 1      The Main electronic control ignition p c b  is also a full  sequence ignition device and does a sequence of oper   ations  ignition cycle  which lead to the ignition of the  gas at the burner    It checks the presence of the flame during the entire  period in which itis activated and supplies the fan regu   lating its speed     The Main electronic control ignition p c b  has a safety  function and any incorrect interventions or tampering  can result in conditions of dangerous functioning of the  boiler     The Main electronic control ignition p c b  can lock the  functioning of the boiler  lock state  and stop its func   tioning up to the resetting intervention  The lock    out is  signalled on the display of the control panel electronic  p c b  and can be reset only by using the boiler reset  button placed on the printed circuit board p c b   see  section 7 1      Some components which are connected to the device  can activate the lock state  The causes of a lock state  could be     The intervention of the safety thermostat  over   heat of the primary circuit      The intervention of the flue temperature probe   overheat of the combusti
27. ntrol ignition  p c b  properly set the parameters     Warning  After cleaning or replacement as  detailed above  it is deemed necessary to  undertake a combustion analysis as detailed  in chapter 8 3 section 11     Main electronic control ignition p c b        EY Thermal control in the  eh   mode    Switch in the c h  function mode       NO Request for heat from                circulator off  s  8              fan still    room thermostat        circulator on          Temp  difference  between probes  higher than 35   C 2    Is primary circuit  temperature higher than that  selected            YES NO       NO       YES NO    lock memorised     YES    YES  gt   stop circulator  3min           starts fan  checks fan rpm    Is fan rpm  exact              NO       YES  L             temperature higher than 110  C     beginning of wait period    cancels lock       NO             YES    I               flame presence     End of wait          period  NO              starts ignition discharges  Opens gas valve  beginning of ignition period       flame presence           closes gas valve  stops fan  interrupts ignition discharges  memorizes lock  display show lock out          End of ignition    NO  period              NO       reset key       interrupts ignition discharges  gas valve open    fan runs                                       temperature probe lock out     Is ech d NO pressed  YES E  Safety thermostat or flue YES flame presence  NO                                       F
28. o sseupunos 10J YOO   san  ea 1edoJd JO  jenueuJ uomne  ejsur TEE bM MR AG    E oe     Ly uonooes oos                          eut 01 JAJOY      essea uoisuedxe   y  JO uonezunsseJd eui 429 elloq eui Aq xoeq pexons jou si seb jsneuxe ey  auns  SE A AO  TEE dl pue  seoueJeojo ees  pej ersul   OSJJOO s   EUILU9  eni ay  Aejdsip eoueijdde ay  Aq uaAiB uoneoipur jeondo  l  Bumes   nea seb oul 104 anje  eoua19j81 e S  Bulpees siu jeu Aya   suononajsqo jo eouesqe pue sseupunos 10  Y29049     au  LOA  osje peurejqo aq ues uoneuuoJur  njesf  seseD any eui jo anjea  02 eurxoeuo  ezAjeue enjeurDulst  9   sseujybn ses Jo  de  uonejos pue edid Ajddns seb eui y2  y   Zz     YEISOWWAU  Ajejes   y  JO UOHUSA9 U  eui pue WOU uonoeuuoo  ejneu pue au  jo Ajuejod eui Y28049 SION  urew   y  jo Duneeu    Je o ay  esneo pjnoo ssed    q pauwely e  Soen   eusajxe pue Bnid    ajqeo Ajddns jo AjuDeiur eui Ae     Ae dsip ay  uo  43  se pejeoipur si no 4907 x     o siJajloq      In H ay  ueuM eA eA   jejes ay  LUJO  Syed  JSJEmM  y o uo uonejedo    8H HH MH mH Buunp eA eA Ajeyes ay  Wo  Spa Ja  z      E E EJ E L  mnm Jayjoq Asion   D  3  a  CH  Sin E H uoneinpoui joaJJoou    E  3  o  2   lins ue4   2  340   ejdsip jeued   o1uos eu    Y     Hu     peys Jou seop Jejog eu    2  19  a Oo  S E s dme Sog S SIS E ELS S mI S e  O a  gt   o  o  o I  S o o  o   o    a     o 3 o Es   D 3   3 o o   5  ala  2 3   oe   2 2 18  2  3 CS EC E EES ECH al    eS s  el 2  3  lt  21 3  8    OG 3    el  z z     8 a   ml     2
29. oiler Stand By  anti   freeze  protection activaded     Boiler waiting for heat request     Boiler in winter mode   The primary circuit temperature is  displayed     Boiler on demand for c h  power    A  AW    C    Burner ignition  spark   ow Flame present  Burner on     Boiler in anti freeze phase  bP  L ao flasching   temperature flashing   UI Ka     E       mi   Boiler in antifrost phase  AF   ni L m  flasching   temperature flashing   IZ    Set c h    all other symbols are disabled     Pump activated for the post   cir   culation phase  Po flashing    temperature flashing     FUNCTION    Delayed burner ignition for setting  the system  uu flashing   tem   perature flashing     Boiler in chimney sweep function   ing mode    The chimney sweep is activated  by setting  parameter 09 01   and is visualised by the switching  on of the hand and alternate  flashing between the tempereture  and the communication and radi   ator symbol     Thermostat Delayed   Boiler test performing     Useful output limitation  temp  dif   ference between probes higher  than 25  C     Boiler test performing     Flame detection error  An flasch   ing   error flashing number     Info modality    The INFO mode allows the display of some information  on the boiler functioning status  In case of malfunction   ing of the boiler  it may be useful to communicate such  information to the Authorised Service Centre Engineer  so that the causes can be understood     In order to access the INFO mode  press key
30. on products      A fault on gas supply     Faulty ignition  faulty ignition electrodes  their wir   ing or connection      Faulty flame detection  faulty detection electrode   its wiring or connection      Faulty condensate drainage     Faulty gas valve  faulty on   off operators or not  electrically supplied      O Faulty Main electronic control ignition p c b      Other components like the c h  temperature probes  NTC switch can temporarily stop the ignition of the  burner but allow its ignition when the cause of the inter   vention has stopped     NO TAG and Fig  6 12 show the sequence of the oper   ations that are carried out at the start of every ignition  cycle and during normal functioning     CHN Selection and adjustment devices    On the Main electronic control ignition p c b  several  selection  adjustment and protection devices are lo   cated   Fig  6 2      Qs MOT  OU  CEOs 05    Main electronic control ignition p c b        Some of these devices are directly accessible by the  user  function control  temperature adjustment etc    others  like the fuses  are accessible by removing the  main electronic p c b  lid        Fig  6 2   1 Connector     ignition electrode    2 Connector     flame detection electrode    3 Connector     controler fan    4 Connector    c h  return temperature probe NTC  5 Connector     flue temperature probe NTC    6 Connector     external temperature probe  op     tional     7 Connector     safety thermostat and c h  flow tem   perature pro
31. oval    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component            Remove all the case panels     Disconnect the connector B from the Flue tem   perature probe NTC by pressing the plastic hook  placed on the side of the connector     3 Unscrew and remove the flue temperature probe  A  Fig  13 2  from the condensing heat ex   changer     4 Assemble the Flue temperature probe NTC carry   ing out the removal operations in reverse se   quence      EEN Checks       Overheat temperature value    ech    Run the boiler and set the temperature at maxi   mum by pressing the appropriate key     2 Allow the boiler to reach its maximum operating  temperature  The boiler should maintain a tem   perature below that of the Flue temperature  probe NTC and no overheat intervention should  occur        Temperature resistance relationship           Remove the Flue temperature probe NTC  see  section 13 2      2 Measurethe Flue temperature probe NTC electri   cal resistance at the ambient temperature and  check it according to the graph in Fig  13 3    Q 12500        _   _         _   _      J   z gt J    gt    J  gt                            12000  11500  11000  10500  10000   9500  9000  8500  8000 D  7500  7000  6500  6000  5500  5000  4500  4000  3500  3000  2500  gt   2000  gt   1500     1000 LZ   500                                                       20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100  C    Fig  13 3  31    14
32. rom the mains  electricity supply before removing any  covering or component     1 Remove the air box and the fan  see section 10 2     2 Unscrew the screws    Fig  11 1  and remove the  fan   burner duct A     3 Remove the burner by sliding it forward     locating tab             burner gasket    Fig  11 3    4 Assemble the burner carrying out the removal  operation in reverse order  Ensure the burner is  correctly located by lining up the locating tab   Fig  11 3      Before reassembling ensure the burner gasket is  correctly located     Warning  After cleaning or replacement as  detailed above  it is deemed necessary to  undertake a combustion analysis as detailed  in chapter 8 3 section 11     EN Checks      Check the position of the electrode edges    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component     1 Remove the ignition electrodes  see section 11 2     2 Check for the correct distance between the me   tallic edges of the ignition electrode  see  Fig  11 4      earth electrode       Ignition electrode  Fig  11 4    Ignition and detection electrodes      Check the connection wires     29       12 Safety thermostat  IAN Function    The safety thermostat A in Fig  12 1 is a device that  senses the temperature of the primary circuit water  which flows in the outlet pipe ofthe condensing heat ex   changer     If the temperature control system of the boiler fails and  the temperature of the primary circuit reaches
33. rse sequence     Before reassembling ensure the fan gasket   Fig  10 2  is correctly mounted     After any service operation on the components of  the gas circuit check all the connections for gas  leaks     Warning  After cleaning or replacement as  detailed above  it is deemed necessary to  undertake a combustion analysis as detailed  in chapter 8 3 section 11     27    11 Ignition and detection electrodes  and burner    URBI Function    Three electrodes are fitted on the fan   burner group   Two of them  fitted on the right side of the fan    burner  group A  are the ignition electrodes B    On the left side is the detection electrode C and it de   tects the presence of the flame                       Fig  11 1    The burner D is fitted on the rear of the fan   burner  group A                                                        Fig  11 2    AER Removal of the Ignition and detection  electrodes    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component     1 Remove all the case panels  see section 2     28    2 Disconnect the ignition electrodes connector E  and the earth wire F  Fig  11 1  and disconnect  the detection electrode connector G     3 Unscrew the screws H and remove the ignition  electrodes B and the detection electrode C   Fig  11 1     4 Assemble the Ignition and detection electrodes    carrying out the removal operation in reverse or   der     IK Removal of the burner    NN Warning  isolate the boiler f
34. s A and C   Fig  7 1  at the same time until the letter di appears on  the display that alternates with a code  Fig  7 2      VAN        NI          a   SS                    i      a   V  l J   299 42    Fig  7 2    To scroll the values press B  reduce  and A  increase    keys  Fig  7 1   In order to exit the INFO mode  hold  keys A and C  Fig  7 1  pressed at the same time   The following table gives details of each parameter and  the possible value that can be show     Control panel electronic p c b     External temperature   C    if fitted    K value  external probe dia    gram  n   value is x 10    Offset  Transaltion of K diagram     15  C    Ch temperature   C  calcu    lated by external sensor    C h  flow temperature   C  d  78      C h  return temperature  C de  44    Flue temperature   C  d   Je      Fan speedy  the value has to   be x 100   4400 rpm    SW version BC  burner control     de 0  SW version MB  main board   dd  03      Tab  7 1       Function modes setting modality    Itis possible to select the various boiler control function  modes hereafter named  parameters  by using the  keys of the control panel p c b    During the function modes setting  the boiler does not  operate     To get in function modes setting modality see section  6 4    Removal of the control panel electronic  p c b    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component     Remove all the body panels  see section 2 2      2 Gain
35. ssure before making any ad   justment to the gas valve     1 Close the gas inlet valve     2 Remove the front panel of the case and lower the  control panel  see sections 2 2 and 2 3      3 Loosen the internal screw on the Inlet Pressure  Test Point 5  Fig  8 2  of the Gas valve and con   nect a pressure gauge using a suitable hose   Open the gas inlet valve    5 Turn on the electricity supply to the boiler  switch   ing on the fused spur isolation switch     6 Set the boiler in c h  function as illustrated in  Fig  8 3     PF       D XU  function  E    7 Make sure thatthe room thermostat is in the    heat  request    position     8 Read the inlet pressure value and ensure that it is  within the limits given in the table Gas supply  pressures  of the user installation manual  If it does not comply with the required pressure  check the gas supply line and governor for faults  and or correct adjustment     9 Switch off the boiler close the gas inlet valve     10  Disconnect the pressure gauge and close the  Inlet Pressure Test Point 5  Fig  8 2      Gas valve adjustment          Fig  8 3    The person carrying out a combustion  measurement should have been assessed as  competent in the use of a flue gas analyser  and the interpretation of the results    The flue gas analyser used should be one  meeting the requirements of BS7927 or  BS EN50379 3 and be calibrated in  accordance with the analyser manufacturers   requirements  and have a current calibration  certificate     11 Fi
36. t the probe of the flue analyser in the flue ex   haust sampling point located on the exhaust  pipes of the boiler  Fig  8 4      21    Gas valve    air intake  sampling point    flue exhaust  sampling point         Fig  8 4    12    13  14    Turn on the boiler  switching on the fused spur    isolation switch     Open the gas inlet valve     Turn on the boiler and operate for 2 minuets to    pre   heat the flue  before commencing any ad     justments       Fig  8 5    15    To enter in the parameters setting mode press  contemporary the 3 keys  A     B     C Fig  8 5  for  10 second until the display shows Fig  8 6     amp  Pi z N     II          LANN AANS       l                     NN       Fig  8 6    Adjusting minimum gas valve setting    16    22    Press keys A and C  Fig  8 5  at the same time  until the display shows the letters LP that alter   nate with the heating water temperature value   6 9 45   indicating the activation of the  chimney  sweep function  at minimum output  Fig  8 7      ATZA TY  o   rm    Li  LL  VENT   NN           y S                 299 1499  Fig  8 7  17  Makesurethatthe room thermostat is in the  heat  request  position   18 Allow the analyser to give a stable reading   19 Read the CO     value     Activ A 120V  Activ A 15OV    Activ A 200V  Activ A 250V       It should be between     CO2     range     value    Type gas       Tab  8 1    To adjust the CO     value remove the brass plug by un   screwing it and rotate the Allen key screw    4 
37. the air manifold D  Fig  5 4  by pulling  it    Disconnect the rubber pipe E  Fig  5 2    Unscrew the gas connectors F    Remove gas pipe G      Unscrew the screws and remove the detection  electrode connector H     9 Unscrew the screws and remove the ignition elec   trodes connector  I     10 Unscrew the screw and remove the overheat  thermostat J     11 Disconnect the connector K by pressing the plas   tic hook placed on the side of the connector     12 Disconnect the connector L    WD      D YN O O           ATA Hp          Fig  5 2    13 Disconnect the fan connector M by pressing the  plastic hook placed on the side of the connector   Fig  5 4                     Fig  5 3   14 Empty the primary circuit of the boiler    15 Remove the forks N  Fig  5 2     16 Loosen the connection O and remove the pipe P     Fig  5 3  from the Condensing heat exchanger     10    Condensing heat exchanger       17 Loosen the connection Q and remove the pipe R 22  Loosen the screws X  Fig  5 4     Fig  5 2     Fig  5 4  from the Condensing heat exchanger  23  Unscrew the screws Y  Fig  5 2    18 Unscrew the screws     24  Removethe Condensing heat exchanger slightly  19 Remove the fan   burner group  move it upwards  turn it frontwards freeing it from    the below screws X  Fig  5 4     Fig  5 2  and then  extract it forwards    25  Reassemble the Condensing heat exchanger  carrying out the removal operations in reverse  order        Ensure to tighten the screws S     Fig  5 2 firmly    EXHN 
38. the fused spur isolation switch  the device  must not unlock and the burner must not turn on       CU  Removal of the electronic control p c b    NN Warning  isolate the boiler from the mains  electricity supply before removing any  covering or component     When replacing the Main electronic control ignition  p c b  all parameters must be correctly checked    adjusted accordingly with the values noted in table  in the installation manual see chapter COMMIS   SIONING section  Setting record  for information on  parameters see also section 6 4      1 Remove all the body panels  see section 2 2      2 Gain access to the parts located inside the Main  electronic p c b  box as explained in the section  2 4 of this manual    3 Remove allthe wiring connected to the Main elec   tronic control ignition p c b      15    Main electronic control ignition p c b        4 Delicately flex the hooks D in the directions indi   cated  Fig  6 11  in order to release the circuit  from the box    5 Remove the Main electronic control ignition  p c b                        16    6 Re assemble the Main electronic control igni   tion p c b  following the removal procedures in  the reverse order     Important    When re   assembling the Main electronic control  igni   tion p c b      7 It is not necessary to utilise static protections but  it is advisable to ensure that the pcb is handled  with care and held atthe edges and with clean dry  hands     Attention    After installing the Main electronic co
    
Download Pdf Manuals
 
 
    
Related Search
 Service  servicenow  service titan  service titan login  services msc  services app  service tag dell  service ontario  service channel  servicenow kp  service desk  service credit union  service manager  service channel login  service fusion  servicenow login  service center  service fusion login  service finance login  service finance company  service tag  service dog  servicehub  services mcs  service level agreement  service platform 
    
Related Contents
Wiley Photoshop CS2 Bible, Professional Edition  Manuel d`instructions  Dixon Zeeter 14295-0804 User's Manual  Manual em Português Comando á distancia com 10 frequências  Gato de botella  手押しポンプ総合カタログ  Sony DSC-W800/B Instruction Manual  Force Computers SYS68K / CPU-6 Manual  Wii Fit U  Samsung i7 Felhasználói kézikönyv    Copyright © All rights reserved. 
   Failed to retrieve file