Home
GUIV Service Man
Contents
1. MANIFOLD ALTERNATE GAS LINE LOCATION 12 k o DRAIN TRAP PLUGIN ALTERNATE GAS LINE HOLE HORIZONTAL UPFLOW MODEL ALTERNATE GAS LINE LOCATION DRAIN TRAP PLUG IN ALTERNATE GAS LINE HOLE HORIZONTAL COUNTERFLOW NOTES 1 WHEN GAS LINE IS IN THE ALTERNATE LOCATION SWAP THE POSITION OF THE PLUG AND GROMMET 2 DRIP LEG MAY TERMINATE WITH A 1 2 X 1 8 PIPE PLUG TO ACCOMMODATE LINE GAS PRESSURE MEASUREMENT Gas Piping Connections 90 Furnace Shown 80 Furnace Similar 67 PRODUCT DESIGN Gas Piping Checks Before placing unit in operation leak test the unit and gas connections To AVOID THE POSSIBILITY OF EXPLOSION OR FIRE NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS Check for leaks using an approved chloride free soap and water solution an electronic combustible gas detector or other approved testing methods NOTE Never exceed specified pressures for testing Higher pressure may damage the gas valve and cause subsequent overfiring resulting in heat exchanger failure Disconnect this unit and shutoff valve from the gas supply piping system before pressure testing the supply piping system with pres s
2. pue amod A pz pue A GL eunssy uonoy yams JOOP JO 12euuoosip eui yno peydnueiur si 18MOd eseeo epoo USE 031 2 NOY BUO YOO 19691 0 pejoeuuoosiu 10 25001 jewo q yeap peonpui 10 adid 1 pexoolq eue enp uedo 5 1 pejoeuuoosiu 10 9s007 10 peeds 5 SANOUISEI eq esneo jeDueuoxe eui 1940 pejoeuuoosiu 10 95007 sjoejuoo uos JO uiod 19 eunsseJd 5 1291024 Jo ujeis s ureJp peioeuuoos 10 esou uos eunsseJg ensseid 51045 09 peonpul eoueuuojed Jo
3. Style A Style B 60 N B2 Second Delay 205 B1 o 4 90 B2 Second Delay 5 4 120 2 Delay 2 E B3 o B4 180 e B2 Second B4 Heat Off Delay Adjustments 80 amp 90 Two Stage Variable Speed Furnaces All items in this section refer to the air circulation blower not to the induced draft blower The timing sequence for the induced draft blower is not adjustable Cooling Fan Timing The cooling system may be attached in one of two ways The following will explain the two possible operations If Y from the thermostat is connected to Y on the Two stage Integrated Furnace Control then the following on and off sequences will occur Air Circulator Blower Operation 100 Cooling On Delay 5 seconds Cooling On Ramp Up 30 seconds 50 Cooling Off Delay 45 seconds Cooling Cooling Off Ramp Down 30 seconds Speed a x Rs Call 45 75 sec Call For Cool Satisfied If Y from the thermostat is connected to Y Y2 on the air circulation motor interface board then the following on and off sequences will occur Air Circulator Blower Operation 100 Cooling On Delay 0 seconds Cooling On Ramp Up 30 seconds Cooling Delay 0 seconds cooling Cooling Off Ramp Down 30 seconds Speed Call Call For Satisfied Cool NOTE This option of no cooling ON o
4. ue seu ue seu j pue i jredei 440 uin E E Aressaoou Bunies 10 uonoeuuoo ye SOWJ98Y jeufiis ON eufiis ou elis v se pue UI SUOUS 015504 10 18 891q 10 9 redeg Syno ve UL Ys eir 1 2 IP asny esoo ejnpoui JO PAJIMSIW S9JIM A pZ 10 uedo A pZ pue Jamod A pue A 91 55 100P 440 12euuoosip 10 A GLL ON pue jredai 104 440 Jamod uin UONOY sasney 415504 s uonduosaq 1 q31 jeuuougy 0055 jo suioidu AS
5. E tenons EE 7 EEEE ____ 0SLYH 0 1 0 2 ZOSLVH 1 LOSLVH uoisJeAuo eDejs o epniniv aa 60d1VH seo epniniv al amp T ce V 0 14 Wy BuiuuiM x lo x 10 x 2 10 ri lo xp x x 10 x M e o 2 9 10833 sova sauea 9 21u01129 3 x NM EN x x x EN 2 T vioSsV eseqqns aiqeisnipy uonduoseg 2 5 z o 5 tat Jol x NEN E x x 101 x NN __ 10 4151150 50 10 __ te 10 EM x 1 x o BEN INN T T lol o te lof x x x x eX Xx x x EM xp x x 10 x EN I
6. j9ejuoo pue JUIOd 195 uos 55 1edoud AONO onuoo Buidid 10 Uulejs s UOIJEUILUIS pue 1q yeup suods ui 95019 yeap Jo 5 uonsnquio pue 1edoud 10 Buidid zaju 10 pue 5 jou pexooiq edid 1 Jo pue uonejedo eoeuunj 1 yeda 440 uin 1284109 pue peioeuuoosiu ou suni Jo esou YAMS eunsseJg peonpu 394314 2 seuse ped Si 037 Jedoud ui 5 eunssejd 1991109 pue 10 YMS ul SOUS Buryesado jou 5 onsouBeip sjoejuoo 9 009 Sao mod ums U9 IMS yeap peonpu S U9 I
7. 10 edid 10 pue pue peuijesiu si 01 1edoud 10 jejui 10 pue Y99849 jnojjo1 enp uedo 8 1nojou 10 091 Jedoud sjrejop 10 5 uonsnquio pue redau 1054 440 1981109 pu pejoeuuoosiui JO 98001 eoeuunj ressooeu 10 peeds 1991109 49Mo q ou pue peeds 1 10 YO9YD peeds Suni JO 2 5 pexoo q eq 10 pue sie eu 1910 peuonipuoo peeds pue esu 10 19945
8. euo si 037 jou 81 Asnonuquoo s 31 pue ejejedo 0 jo onejsoujoe 3 ul suonneoeud umouy ue seu ite Sei Jeda 019 440 se Je1souueuj ON 10 uonoeuuoo 1940 4 A pz pue A 911 SHOUS 415504 10 10 037 5 v oo D ne Seu 10 ejnpoui gt ado UST Soo A pz pue pue eoeuun amod A pZ pue A 1 1 einssy uon 430 HMS n ou 10 18MOd A GLL ON 0
9. Black Wire INTEGRATED FURNACE CONTROL TIME DELAY 165 ACCESSORY WIRING DIAGRAMS HIGH VOLTAGE WARNING DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DE HUMIDISTAT DEHUM1 This wiring diagram is for reference only Not all wiring is as shown above refer to the appropriate wiring diagram for the unit being serviced GUIV CA DX or GUVA AX Two Stage Variable Speed Furnaces 1 N N DE HUMIDISTAT di 27 WHITE RODGERS DE HUMIDISTAT RH Thermostat Connections OOD O YN2 Yi Ri DEHUM BLOWER INTERFACE ENARE C2 Ci R3 R2 EMW2 Wi CFM TF EST Jour To IDEHUMIDIF Dehumidify Enable Jumper ramum 166 ACCESSORY WIRING DIAGRAMS HIGH VOLTAGE WARNING DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DE HUMIDISTAT DEHUM1 This wiring diagram is for reference only Not all wiring is as shown above refer to the appropriate wiring diagram for the unit being serviced GUVA BX CX amp GUIV FX Two
10. 15 y eda 440 99S 3A991109 sesne9 415504 s juonduoseq 1neJ q31 LATIN pereioossy jo suioidu As pue suonneg SIO1jU09 05 104 39Vd 4 SYSTEM OPERATION NORMAL SEQUENCE OF OPERATION 80 Models with White Rodgers 50A52 Radiant Sense Ignition Control Power Up The normal power up sequence is as follows 1 115 VAC power applied to furnace Integrated control module performs internal checks Integrated control module monitors safety circuits con tinuously 4 Furnace awaits call from thermostat Heating Mode The normal operational sequence in heating mode is as fol lows 1 Rand W thermostat contacts close initiating a call for heat Integrated control module performs safety circuit checks Induced draft blower is energized causing pressure switch contacts to close Humidifier terminals are energized with induced draft blower 4 warm up begins upon close of pressure switch contacts It will heat for at least 17 seconds and will continue to heat until the radiant sensor determines the ignitor is hot enough i e until a heat signal is
11. DEHUMIDISTAT 38 ACCESSORIES CONCENTRIC VENT CONVERSION KIT Vertical VCVK Horizontal HCVK Pipe to Furnace Connection for 227 Combustion 4 Fresh Air Intake p i Air Intake Pipe Vent Flue Termination Pipe to Furnace 8 5 F with Tee 2 gt 2 3 Vent Flue ie N Termination A Tee Pipe amp 2 to 4 Reducer a Combustion Air Intake Pipe A S ei 1 2 Connection for M 2 kn IAM Seal Penetration Y 12 Minimum Above E 298 NC 12 Minimum Above with Caulking Grade or Highest M Roof or Highest Anticipated Snow Level Anticipated Snow Level Inside pe 5 Seal Penetration C VA La with Flashing and Caulkin ERE Wall Thickness Outside 9 3 4 Minimum c 13 3 4 Maximum CIN Inside Roof Thickness HVCK Installation 22 Maximum Concentric Vents Kits HVCK and VCVK are suitable for use Interior Section of Concentric Vent Assembly with the following Amana 90 efficient furnace products Must Be Adequately Secured and Supported Sanitary Used Models GUCA GCCA GUVA GCVA Connection for 27 Fresh Air Intake lt GUSA Pipe to Furnace GULA cepe From Furnace DER VCVK Ins
12. Equipment Located in Confined Spaces Air from Outdoors Inlet Air from Ventilated Crawl Space and Outlet Air to Ventilated Attic See 5 3 3 b 2 Whencommunicating with the outdoors through vertical ducts each opening shall have a minimum free area of 1 square inch per 4 000 BTU per hour of total input rating of all equipment in the enclosure Chimney Gas Vent Ventilation louvers each end of attic NOTE The inlet and outlet air openings must each have a free area of not less than one square inch per 4000 BTU of the total input rating of all equipment in the enclosure S RE Outlet Air Water Heater Inlet air duct ends 1 ft 300 mm above floor Equipment Located Confined Spaces All Air from Outdoors Through Ventilated Attic See 5 3 3 b 3 When communicating with the outdoors through horizontal ducts each opening shall have a minimum free area of 1 square inch per 2 000 BTU per hour of total input rating of all equipment in the enclosure PRODUCT DESIGN lt Chimney Gas Vent NOTE The air duct openings must have a free area of not less than one square inch per 2000 BTU of the total input rating of all equipment in the Outlet air duct enclosure Inlet air duct Ifthe appliance room is located against an outside wall and the air openings communicate direct
13. edau 1019 440 10 uedo si Ad 10 95007 8914 ped jueureoe doei Buum 1204109 pue 510602 U91IMS si 031 onsouBeip Jedoud youms ainsseid pue Jas 1669 4 juiod 198 uoneJedo Buidid 10 uejs s uap pue swoqje JOMO G yeam 10 5 esuodsei pue uonsnquio pue 998 ujbue 1edoud 10 Duidid pexoojq adid pexoolg eoeuunj edau 1oud 440 esou uoiMs einsseid 1981109 pue H98U9 peioeuuoosiui Jo esou suni juawsoe das 1081109 pue 10 einsseud 511046 jou si MU 5 or 1edoud
14. aoud 440 uin peeds 1ewo q pue esu 10 2905 ees aoud 440 uin ped 1ueujeoejdoj Jedoud uoyws Buidid 10 pue 295 rede aoud 440 Jamod uin ed 4edoud yoyms rede aoud 440 Jamod uan Buidid 10 uonoes pue ees 100 19945 10SU8S 2189 si oyub aoud 440 Jamod uan jo 1 ui peay wedau aoud 440 Jamod uin asny alls jojjuoo eoe dey aoud 440 uin ji 6 esnj JOOP JO oeuuoosip eu eui Jewod Ji epoo usej 141 OM 19521 0 22 noy
15. 126 SYSTEM OPERATION 440 ped ui yoyms einsseid 10 pue en 440 ped uooi is 1edoJd 440 seinsseJd 566 20 ees sep pue en Josues aoud 440 redau 440 S9 JON pue anfen 866 jo awel 10 49949 Buyum JOSU S 10 JOSU S 5 JUON 964100 pue xpeuo 39ejuoo pue juiod 19 yoyms eBeis Aya uoneuiuue pue swoqje ui amp uel Jedoud 104 1ejur any 49949 esou eunsseud 1981109 pue Buum 1981109 pue Bum 1064400 pue sensseJd 10 Y90949 u
16. 5 Gas valve opens at end of ignitor warm up period deliv ering gas to burners and establishing flame One sec ond after the gas valve opens the ignitor is de energized 6 Theradiant sensor monitors the flame As long as flame is present and the call for heat continues the gas valve will remain open Either a hot ignitor or a flame can pro duce a heat signal Gas valve will remain open only if flame is sensed 7 Circulator blower is energized on heat speed 45 sec onds after the gas valve opens 8 Furnace runs integrated control module monitors safety circuits continuously 9 Rand W thermostat contacts open completing the call for heat 10 Gas valve closes extinguishing flame and the induced draft blower is de energized 11 Circulator blower is de energized 90 seconds after the gas valve closes 12 Furnace awaits next call from thermostat 96 Cooling Mode The normal operational sequence in cooling mode is as fol lows 1 R and Y thermostat contacts close initiating a call for cool 2 Integrated control module performs safety circuit checks 3 Outdoor fan and compressor are energized 4 Circulator blower is energized on cool speed following a fixed five second on delay 5 Furnace circulator blower and outdoor cooling unit run integrated control module monitors safety circuits con tinuously 6 Rand Y thermostat contacts open completing the call for cool 7 Outdoor fan a
17. uonsnquioo uonoujse1 10 ensseud seb seurejj 4ze Ajddns eq Jaye eure JO 5507 Josues pejoeuuoosiul 10 pezipixo pereoo 10 10 uado yonjs uos eunsseJd 1001 5 01 ou sneg oj eine jeujejur ue s 10 jejsouueuy 940 4 19H891q pejoeuuoosiuu 10 A 10 uado JOOP 440 YMS 9euuoosip sasneg e qissod uedo s ne uedo si Heip 0 esuodsei 809 jou seop YOUMS eBejs jou s yeup SI ensseJg SION ees sejoKoe1 6101 BAY 5 10 jezo uoniu jo jequinu enp noxoo eoeunJ ue sey jeisouuou ON J0X 9Jq
18. Pipe or Nominal Pipe Size Tubing Tubing Size O D Type L Schedule 40 jc 3 8 1 2 5 8 3 4 7 8 1 18 1 2 3 4 1 1 1 4 1 1 2 10 39 92 199 329 501 935 275 567 1 071 2 205 3 307 20 26 62 131 216 346 630 189 393 732 1 496 2 299 30 21 50 107 181 277 500 152 315 590 1 212 1 858 40 19 41 90 145 233 427 129 267 504 1 039 1 559 50 18 37 79 131 198 376 114 237 448 913 1 417 60 16 35 72 121 187 340 103 217 409 834 1275 80 13 29 62 104 155 289 89 185 346 724 1 066 100 11 26 55 90 138 255 78 162 307 630 976 125 10 24 48 81 122 224 69 146 275 567 866 150 9 21 43 72 109 202 63 132 252 511 787 200 8 19 39 66 100 187 54 112 209 439 665 250 8 17 36 60 93 172 48 100 185 390 590 Data accordance with NFPA pamphlet NO 54 Propane Gas Piping Charts When installing a propane storage tank the contractor must consider proper tank sizing safety efficiency ground char acteristics and aesthetics For a residential customer the size may range from 100 1 000 gallons depending on house hold use Typically a 500 gallon tank is ample for an aver age four bedroom home However it is best to consult your local propane supplier to ensure the proper sizing for pro pane storage requirements Determining the correct tank size for eac
19. xx 019 fetal EEE Ex x GciBraoaso CL ttt X Available for this model 1 7 501 to 9 500 ft 3 0 to 7 500 ft Not used in this application 2 7 501 to 11 000 ft 4 9 501 to 11 000 ft Note All installations above 7 500 ft require a pressure switch change GUIB090CX30 GUIB090A50 GUIB090B50 GUIB090CX50 GUIB115A40 GUIB115CX40 GUIB115A50 GUIB115B50 GUIB115CX50 ee eee 39292323233 381951 GUIBO45A30 GUIBO45B30 GUIBO45CX30 GUIBO7OAS0 GUIBO70B30 GUIBO7OCX30 GUIBO70A40 GUIBO70B40 GUIBO7OCX40 GUIBOS0AS0 GUIB090B30 GUIBO90CX30 GUIBOS0AS0 GUIB090B50 GUIBOSOCXSO GUIB115A40 GUIB115CX40 GUIB115A50 GUIB115B50 GUIB115CX50 GUIB140A50 GCIBO45A30 a e pe pe Pe Pe Pp Pe e ee n n s Note For installations in Canada the Amana 80 furnace is certified only to 4 500 ft 27 Joueo 2 UOISJBAUOD Sed ion Wy SLY 41 sed Se euedoug zisarovH 6 ainssaig epniniy ubiH UOUMS epniniv uonduoseg Model Number ACCESSORIES jaurcoaspa
20. 149 Checking Gas Valve Redundant 150 Checking Hot Surface eda Gu ipd a aee cn dade 150 Checking White Rodgers 50A50 50A51 50A65 50M61 or 50V61 and Heatcraft HSI 1 1A or HSI 2 Integrated Ignition Controls 151 Checking WR50A52 Integrated Ignition Control Radiant 152 Checking Flame Rectification Flame Sensor ss 153 Checking Radiant Sense Flame Sensor ss 154 Checking Main oun ccu 155 155 High Altitude Application USA 155 Checking Gas Presse Dm 156 Checking For Delayed 159 Checking for Flashback gen na apud Eg te ble rade 159 Checking 159 Checking Temperature RISC tant S tubes 160 137 SERVICING S 1 CHECKING VOLTAGE HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 Remove the burner door on 80 furnace or blower com partment door on 90 furnace to gain entry to Junction Box
21. Open High Low Off High Low Off 0 10 27 28 31 61 91 0 15 30 60 90 90 120 120 or 150 or Time sec 180 210 SYSTEM OPERATION COOLING TIMING CHART FOR WHITE RODGERS 50A51 225 amp 50A51 235 TWO STAGE VARIABLE SPEED INTEGRATED IGNITION CONTROL OPERATION With Y from the Thermostat Connected to Y on Integrated Ignition Control On Indoor Fan Off Outdoor Fan And A Compressor On Thermostat Off 0 35 Time sec 0 45 75 With Y from the Thermostat Connected to Y Y2 on Circulator Blower Interface Board On Indoor Fan Off Outdoor Fan And e Compressor On Thermostat Off 0 30 Time sec 0 30 111 SYSTEM OPERATION Abnormal Operation 80 Two Stage Variable Speed Models with White Rodgers 50A51 225 Ignition Control 90 Two Stage Variable Speed Models with White Rodgers 50A51 235 Ignition Control The following presents the probable causes of questionable furnace operation and how to fix them Look through the observation window in the blower access door and make a note of the number of flashes in sequence between pauses Next refer to the Troubleshooting Chart on the following page for an interpretation of the LED signals and to the infor mation in this section for a description of the problem 1 Internal Control Fail
22. einsseud 2949 PNO 4045 lyse 037 91 Ip 5 sjoejuoo Jeiod tun 5 einsseid eoe deg Uo1IMS SI YMS eje1edo 0 d 29 2 Joye JO 5501 pezipixo pejeoo ji Josuas pues esues josues ZB 5 10 eoe dog pejoeuuoosiui JO pezipixo pajeoo 10 592110 1240 S sejo 201 10 sjdwaye 198109 19ejuoo 1610 jo jequinu esou uonejedo einsseid 18109 1001 onis 5 18400 1104 s1euunq 0 ue ANP 1noxoo eoeuun uondnuuejui se 1921109 pue 272907 886 ou Swel usiiqeise eJnjreJ s rejep 10 pue 1 995 100 9915 10SUSS PUBS 2189 YIM e pueu si 10106 redau 104 440
23. pue Z ISH SSVOS 10 jeu SYSTEM OPERATION 95 WO 9504 JOOP JO eui uBnojui 5 ji 031 noy INO YOO 19521 0 SALON snonuguoo si 31 jojuoo 10 pesues u q seu eoeuunj pue seb jo 1edoud Aya anea seb MOIS Aredei aoud 440 eurej 10 eurej 10sues 10 108498 POUS 1281102 esues 0111045 1281109 pu Messooou 95007 p eoueuuojied 1 10 yelp
24. 2 42949 yeys uo 1401 si IYEN JUNOW 800 10 Y92949 dD Jeduunf 159 uo suid 10 42949 40100 9 H M A 9 suonoeuuoo 9 01 OBA J0jouJ amod GLL uonoy aAn22a1105 Bumes peeds 1ewojq 1981109UI 10 Ajddns 1284109U 5 10 12 100 JO4JU09 JOJOWW UI 109894 81N SION 10 uonoeuuoo 16160191 W49 S10 12euuoo ssousey ui suid payeasun JOJOW 0 DEA GLL peg uo 1401 100 JOJOW 95001 JO UI 10969494 peg S10 J99UU09 ssousey suid payeasun S9JIM 14 40 esnj uedo JOOP JO U9iIMS 1oeuuoosip sesne9 ajqissod peeds W49 18 50 10 S UNH juegiuuejur
25. 10 suing Y92949 1981109 pue 49949 Aesseoau 10 peeds 1981109 pue peeds 10 yOaYD 10 819 10 HIOMJONP pue 1991109 pue uonou 19ejuoo pue 4104 jas yoyms jedoud Aya 5 Urejp pue 10 asoy eunsseJd 1921109 pue peuous 1981109 pue 10 Y49949 pue 15009 ujBue 1edoud 10 Buidid any pezipixo pejeoo jiaosues pueg esues YII 10 resseoeu 1981109 2602 1u0JJ YII uondnaiejui 1921109 pue 872907 UMOUY iesseoeu se A pZ pue A GILL SOUS ejqissod 10 ejnpoui
26. Y88FA 3 i FAN LED TWINNING T Stat Connections Vil BLK SENSOR CONTROL INPUT GYWRO R THERMOSTAT C COM CONNECTIONS 1ST STAGE HEAT W HEAT MPUTS STAGE FEAT W2 Y COOL 2 1ST STAGE COOL Y1 1 EAN 2ND STAGE COOL Y2 FAN G Y COOL FURNACE U SUPPLY W HEAT TSTAT R R 24V INPUTS N COMMON FOR SINGLE STAGE OPERATION C COM HEATING JUMPER W1 W2 WHT FAN LED E COOLING JUMPER 1 2 GY WR BLK SENSOR INPUT 24VAC 50 60 Hz WHT RED INPUTS OUTPUTS 2 MAX EACH FUNCT Remote LED T Stat Connections FAULT T STAT ANTICIPATION SETTING 0 16 A Optional BLK 5 SIGNAL OUTPUT J R e Furnace 1 SEE INSTRUCTIONS FOR ELECTRICAL ASN N Speed RED N SPECIFICATIONS OF REMOTE DEVICE PATENTS FENDING 2 Heat i e 5 Fan LED Sensor WHT with terminal WHT without terminal Tape wire ends if not used 163 ACCESSORY WIRING DIAGRAMS HIGH VOLTAGE WARNING DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH FOSSIL FUEL KIT FFK03A This wiring diagram is for reference only Not all wiring is as shown above refer to the appropriate wiring diagram for the unit being serviced For use with Amana brand Heat Pumps in co
27. INLET PRESSURE PRESSURE REGULATOR JU TMENT SIPE GFEVALNE UNDER CAP SCREW White Rodgers Model 36E35 Type 205 GUIB GCIB SYSTEM OPERATION GAS VALVE ON OFF CONTROL LEVER TL IN ON POSITION O PRESSURE TAP SIDE OF VALVE e 9 A INLET b D b OUTLET PRESSURE REGULATOR ADJUSTMENT INLET PRESSURE TAP UNDER CAP SCREW SIDE OF VALVE Robertshaw Model 7222 GUID GAS VALVE ______ ON OFF 07 SELECTOR SWITCH D OUTLET OUTLET MANIFOLD PRESSURE TAP SIDE OF VALVE INLET PRESSURE PRESSUER REGULATOR SIDE OF VALVE ADJUSTMENT UNDER CAP SCREW White Rodgers Model 36E22 GUIA GCIA GUIC GCIC GUID HIGH MANIFOLD REGULATOR ADJUSTMENT SCREW UNDER CAP INLET PRESSURE TAP SIDE OF VALVE OUTLET MANIFOLD PRESSURE TAP LOW MANIFOLD GAS VALVE REGULATOR ADJUSTMENT SIDE OF VALVE ON OFF SCREW UNDER CAP CONTROL KNOB White Rodgers Model 36E96 GUIS GCIS GUIV OUTLET MANIFOLD LOW MANIFOLD GAS VALVE PRESSURE REGULATOR ADJUSTMENT ON OFF SELECTOR SWITCH SIDE OF VALVE SCREW UNDER CAP De INLET PRESSURE TAP SIDE OF VALVE HIGH MANIFOLD REGULATOR ADJUSTMENT SCREW UNDER CAP White Rodgers Model 36E54 GUIS GCIS GUIV GUSA GCVA GUVA Gas Valve CC On Off Selector 1 Switch X E INLET b Inlet Pressure Side of Valve Outlet
28. 60 Elbows and or Tees used in the terminations must be included when determining the number of elbows in the piping system 2 Number of elbows tabulated are for each Vent Flue amp Combustion air intake pipe 3 Minimum length of each Vent Flue amp Combustion Air Intake pipe is five feet and one elbow tee 8 3 diameter pipe can be used in place of 2 diameter pipe Vent Flue and Combustion Air Pipe Terminations 90 Furnaces Only The vent flue and combustion air pipes may terminate verti cally as through a roof or horizontally as through an out side wall Vertical pipe terminations should be as shown in the follow ing figure Refer to Vent Flue Pipe and Combustion Pipe Termination Locations section in this manual or the installa tion instructions The penetrations through the roof must be sealed tight with proper flashing such as is used with a plas tic plumbing vent TEE VENT FLUE 90 MEDIUM RADIUS ELBOWS COMBUSTION AIR INTAKE 12 MINIMUM 1 5 12 MINIMUM TO ROOF OR HIGHEST ANTICIPATED SNOW LEVEL 24 MAXIMUM 3 MINIMUM 9096 Furnace Vertical Terminations Dual Pipe Horizontal terminations should be as shown in the following figure Refer to Vent Flue Pipe and Combustion Pipe Ter mination Location section in this manual or the installation instructions for location restrictions 2 3 8 diameter wall penetration is required for 2 diameter pi
29. 1981109 pue peioeuuoosiu ou 10 esou YAMS Sun peonpu Seuse OM 5 1981109 pue 10 5 eunsseud ui SOUS jou 1 Buyse si 041 5 Burgos sjoejuoo nou peonpur IMS J8MOIQ peonpu s eunssag ejeJedo eoeuunJ eoueuuojed eoueuuojed peonpur 1edoud Aya Buiuedo 1 19409 Buidid Jo seb pue 104 Buidid Ajddns seb 2 10 ees pezipixo pejeoo 1 5 95 pues esues Jaye jo 5507 101 S 10 10 10SUSS SEI 101 6 jo 1equunu Kre
30. PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing Please use these numbers when requesting service or parts information Airflow Capability 30 1 510 3 0 Tons Product Type G Gas Furnace Supply Type C Counterflow Horizontal U Upflow Horizontal 40 2 5to 4 0 Tons 50 3 0 to 5 0 Tons Additional Features X NOx Models Design Series A First Series Nominal Input 045 45 000 Btuh Furnace Type C Condensing 9096 S 2 Stage Condensing 9096 Model Family A Air Command 90 40 Height 070 70 000 Btuh 090 90 000 Btuh 115 115 000 Btuh 90 GUCA AX GCLA AX GUVA AX GUCA AX GCLA CxX GUVA AX GUCA CX GUVA BX GCCA AX GCVA CX GUVA BX GCCA AX GULA AX GUVA CX GCCA AX GULA CX GCCA BX GUSA BxX GCCA CX GUSA BX GUSA CX PRODUCT IDENTIFICATION This section will identify the models covered and the changes per each model group from one release to the next Model Manufacturing Description Gas Furnace Upflow Horizontal Induced Draft A Air Command 80 SSE Furnace Initial Design Series GUIA A P1177301F P1177308F 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor electrodepositioned textured steel cabinet and 409 st
31. 10 OYA 51 10 sesne9 o qissod SH LON snonunuoo si 487 ojuoo pue uomejedo Jeuuny ou una pue peonpu seuselj q31 uowesedo 6 2 yeap 0 esuodsai jou seop Jo einssoid 5 yeap eBejs yy ym 526 eBejs moj uo eoeuunJ seuse 8 1 s 037 jou 10 pesues seu ELLE seuse Z seusell Si 037 9nsouBeip si esues uome1edo eoeuunj ELON seuse SMS Tostonot xis Buiuse si emod A peine a34 peredbeju SI 81 JO
32. fo KR ABRE ata IN SAS lt gt I gt 1 Z 15 15 5 x x x 1 8 iXI xIxIx 2 lol x x x x xix 1 1 1 1 1 1 GCIC115FX50 1 1 1 Lx Lx Lx Lx Lx Lx LL xix 1 1 LXEOLX X Available for this model 1 6 001 to 8 500 ft 3 010 6 000 ft C3 Not used in this application 2 6 001 to 11 000 ft 4 8 501 to 11 000 ft Note All installations above 6 000 ft require a pressure switch change gt fox fox gt lt Common Vent Kit CVK6 fm Common Vent Ki X 2 221223 02 22222222 999 f f f f f f f 2222225 95989559 mmm Gcicorocxao Gcicoronxao Gcicnsexao jacicrsscxso Gcicnsxso Note For installations in Canada the Amana 80 furnace is certified only to 4 500 ft 30 ACCESSORIES EN DNE F r SSSR wiosno sowo Se EG EE EEE EEE EEE
33. 1 Protect connectors and semi rigid tubing against physi cal and thermal damage when installed Ensure alumi num alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry plaster or insulation or subjected to repeated wetting by liquids such as water except rain water detergents or sewage 66 EDGES OF SHEET METAL HOLES MAY BE SHARP USE GLOVES PRECAUTION WHEN REMOVING HOLE PLUGS Direct Standard Inlet Piping When gas piping enters directlyto the gas valve through the standard inlet hole upflow through the right side panel the installer must supply straight pipe with a ground joint union to reach the exterior of the furnace NOTE The rigid pipe must be long enough to reach the outside of the cabinet to seal the grommet cabinet penetration on the 90 amp 95 furnaces A semi rigid connector to the gas piping can be used outside the cabinet per local codes Indirect Alternate Inlet Piping When gas piping enters indirectly to the gas valve through the alternate gas inlet hole the installer must supply the following fittings starting from the gas valve to reach the outside of the cabinet NOTE On the 90 amp 95 furnaces the installer must swap the alternate inlet hole plug with the standard inlet grommet in order to seal the cabinet e Coupling 90degree elbow e 2inch close nipple 90degree elbow Straight pipe with a ground joint
34. A copy of the National Fuel Gas Code 54 ANSI Z223 1 can be obtained from any of the following American National Standards Institute 1430 Broadway New York NY 10018 42 National Fire Protection Association 1 Batterymarch Park Quincy MA 02269 CSA International 8501 East Pleasant Valley Cleveland OH 44131 A copy of the CAN CGA B149 Installation Codes can be obtained from CSA International 178 Rexdale Boulevard Etobicoke Ontario Canada M9W 1R3 The rated heating capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated The total heat loss should be calculated by an approved method or in accordance with ASHRAE Guide or Manual J Load Calculations published by the Air Conditioning Con tractors of America Location Requirements and Considerations PREVENT POSSIBLE EQUIPMENT DAMAGE PROPERTY DAMAGE PERSONAL INJURY OR DEATH THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT Follow the instructions listed below when selecting a fur nace location Refer also to the provided in the Combustion and Ventilation Air Requirements section in this manual or the installation instructions for details e Centrally locate the furnace with respect to the pro posed or existing air distribution system Ensurethe temperature of the return air entering the furnace is between 55 F and 100 F when the furnace is heating Provide pro
35. 5 10 1981109UI uanza 10 Ajddns 1981109U peeds 1 peeds 1991109 1sn py edau 440 JONP 1994109 499u2 BOe das yoouy SIOU M 20 A O 40 1618 10 499u2 eDexee juang ANUS aleo 01 U09 10 0W Buiuedo Jamod Bunoeuuoosip sejnuiu ureda 440 4 2 1101 041u09 10 0UJ WIOH d ejep si ue 39 uiu 5 15 eun S Ajeoneue Sunu 1nq 511615 4010 IM 011U09 10 OU 9 juaw oejd SI ueJ 1 10 009 5 ues Fey 10 pajoeuuoo JO 122 ul jou SI Jamo
36. APPLIANCE POUR COUPER L ADMISSION NI DE GAZ DE L APPAREIL 1 R gler le thermostat la temp rature la plus basse 2 Couper l alimentation lectrique de l appareil s il faut proc der des op rations d entretien 3 Torner le robinet a gaz dans le sens des aigilles d une montre en position OFF ARRET Ne pas forcer 4 Remettre en place le panneau d acces 11072702 OPERATING INSTRUCTIONS FOR YOUR SAFETY LIRE AVANT DE METTRE READ BEFORE OPERATING EN MARCHELIRE WARNING If you do not follow these instructions AVERTISSEMENT Quiconque ne respecte pas explosion may result causing property damage la lettre les instructions dans le pr sent manuel ersonal injury or loss of life risque de d clecher un incendie ou une explosion entrainant des dammages mat riels des l sions A This appliance does not have a pilot It is equipped corporelles ou la perte de vies humaines with an ignition device which automatically lights the burner Do not try to light the burner by hand Cet appareil ne comporte pas de veilleuse Il est muni d un dispositif d allumage qui allume B BEFORE OPERATING smell all around the appliance automatiquement le br leur Ne pas tenter area for gas Be sure to smell next to the floor d allumer le br leur manuellement because some gas is heavier than air and will B AVANT DE LE FAIRE FONCTIONNER settle on the floor renifler tout autour de l appa
37. Gas Furnace Upflow Horizontal Induced Draft C Air Command 80 SSE Furnace D Fourth Design Series A Standard Unit not NOx certified 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor and 409 stainless steel tubular heat exchanger Use of smooth cold rolled steel substrate a smooth top coat for furnace cabinet to replace prepainted furnaces until new coating is approved for prepainted material Gas Furnace Upflow Horizontal Induced Draft C Air Command 80 SSE Furnace Fourth Design Series X NOx Certified 40 8096 furnace featuring integrated electronic ignition control silicon carbide ignitor and 409 stainless steel tubular heat exchanger Use of smooth cold rolled steel substrate a smooth top coat for furnace cabinet to replace prepainted furnaces until new coating is approved for prepainted material Gas Furnace Upflow Horizontal Induced Draft C Air Command 80 SSE Furnace E Fifth Design Series A Standard Unit not NOx certified 40 8096 furnace redesign incorporating feature changes introduced by the new 40 9096 GUIC EA P1234001F 1234008 furnaces Changes include standardized blower decks access door blower door scroll wrap burner bracket Norton mini igniter and plug connect wiring harness The furnaces also feature an integrated electronic ignition control prepainted textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Ho
38. SYSTEM OPERATION NORMAL SEQUENCE OF OPERATION 80 or 90 Models with White Rodgers 50A50 or HSI 1 1A Integrated Ignition Control Power Up The normal power up sequence is as follows 115 VAC power applied to furnace Integrated control module performs internal checks Integrated control module flashes LED one time gt D Integrated control module monitors safety circuits con tinuously 5 Furnace awaits call from thermostat Heating Mode The normal operational sequence in heating mode is as fol lows 1 R and W thermostat contacts close initiating a call for heat 2 Integrated control module performs safety circuit checks Induced draft blower is energized causing pressure switch contacts to close Humidifier terminals are energized with induced draft blower 4 warm up begins upon close of pressure switch contacts 5 Gas valve opens at end of ignitor warm up period deliv ering gas to burners and establishing flame 6 Integrated control module monitors flame presence Gas valve will remain open only if flame is sensed 7 Circulator blower is energized on heat speed following a fixed thirty second blower on delay Electronic air cleaner terminals are energized with circulator blower 8 Furnace runs integrated control module monitors safety circuits continuously 9 Rand W thermostat contacts open completing the call for heat 10 Gas valve closes extinguishin
39. The alternate combustion air intake location is the large hole not in line with the induced draft blower outlet Refer to the following Alternate Combustion Air Intake Location figure for details SURE NOT TO DAMAGE INTERNAL WIRING OR OTHER COMPONENTS WHEN REINSTALLING COUPLING AND SCREWS For non direct vent installations installed horizontally a minimum of one 90 elbow must be installed on the com bustion air intake coupling to guard against inadvertent block age No elbow is required on the alternate combustion air intake of upright installations however a minimum clear ance of 2 inches is required to assure proper air supply For direct vent installations secure field supplied combus tion air intake pipe directly to the air intake coupling pote 9 BENE 2 4 SCREWS REMOVE Pa 4 SCREWS REQUIRED 2 NON DIRECT REMOVE __ 5 VENT AND CUT n 4 2 D i 7 8 REMOVE 4 5 REMOVE 3 SCREWS ose RELOCATE 3 ADDITIONAL PLUG FROM DRAIN KIT RELOCATE UPFLOW SECURE TO CABINET UPFLOW HORIZONTAL SHOWN COUNTERFLOW SIMILAR 9096 Furnace Alternate Combustion Air Intake Location NON DIRECT VENT SINGLE PIPE PIPING 90 FURNACES ONLY Non direct vent installations require only a vent flue pipe The vent pipe can be run horizontally
40. gt GCCA090__50 GCCA115 50 GCLAO90 50 GCLA115 50 18 9 16 lt gt 23 3 4 23 3 4 24 1 2 19 23 1 11 32 1 11 32 dimension in inches COUNTERFLOW SUBBASE D 28 1 4 5 01 or 01A SUBBASE DIMENSIONS Dim A Dim B Dim C Subbase Plenum Floor Width Chamber O Dim D Floor Model GCI 070 17 16 1 8 21 1 4 GCI 115 All dimensions given in inches Subbase adjustable to fit all 3 cabinet sizes Detailed installation instructions ship with the subbase 20 1 8 21 1 4 24 1 8 21 1 4 35 ACCESSORIES EXTERNAL FILTER RACK KIT SLOTS IN FILTER CLEAR SCREWS U o o 9 ON UNIT INTERNAL FILTER RETAINER SCREWS 80 MODELS ONLY BLOWER DECK SCREWS 14 500 UNIT SIDE Ma UA PANEL S ma a An o 2 01 EXTERNAL FILTER RACK KIT Used on Models 80 Upflow Model Furnaces 4 INTERNAL 90 Upflow Model FILTER m RETAINERS FILTER RACK ASSEMBLY FACE FILTER OPENING TOWARDS FRONT OF UNIT OF UNIT RETURN AIR CUTOUT AREA LOWER EDGE SCREW ACCOMODATOR FILTER HOUSING ACG1625 3 6 ACG2025 3 6 amp ACG2424 3 6 ACCOMODATOR FILTER HOUSING DIMENSIONS ACCOMODATOR FILTER HOUSING Model Overall Opening Top Filter 1 1 2 1 26 26 26 26 2025 6 2
41. 2 5 z 5 z GUVA045AX30 GUVA070AX40 GUVA090AX50 GUVA115AX50 GUVA045BX30 GUVA070BX40 GUVA090BX50 GUVA115BX50 ACCESSORIES 3 0 to 7 000 ft 1 7 001 to 9 000 ft 2 7 001 to 11 000 ft Note All installations above 7 000 ft require a pressure switch change X Available for this model 4 9 001 to 11 000 ft Not used in this application Note For installations in Canada the Amana 90 furnace is certified only to 4 500 ft 34 ACCESSORIES COUNTERFLOW FLOOR BASE lt 4 76 gt gt Plenum B Furnace Floor Base E Floor B E Plenum 3 4 F 3 4 Front View Floor Base Part Numbers Used On Models GCCA045 30 070 30 GCLAO45 30 GCLAO70 30 Floor Opening Side View Plenum Size H J 16 1 2 23 3 4 K L 18 9 16 070 40 GCCA090 40 GCLAO70 40 GCLAO90 40 20 1 2 23 3 4 18 9 16 Floor Base Used On GCCA090 50 GCCA115 50 GCLAO90 50 GCLA115 50 24 1 2 23 3 4 All dimension are in inches 18 9 16 Part Numbers CFB16 Models GCCAO045 30 GCCAO70 30 GCLA045 30 GCLAO70 30 GCCAO070 40 GCCAO090 40 GCLA0O70 40 GCLAO90 40 18 9 16 18 9 16 23 3 4 29 17 1 2 16 1 2 20 1 2 1 11 32 20 24 ve 21 1 8 8 0 6 21 32
42. 45 42 39 36 115 000 Standard 3 49 46 43 40 37 34 31 28 Alternate 3 35 32 29 26 23 20 17 14 GUSA Model Furnaces Direct Vent Dual Pipe Venting Table Maximum Allowable Length of Vent Flue amp Combustion Air Intake Pipe ft Unit Input Termination Bus Number of Elbows 0 9 Btu Style inch 1 2 3 4 5 6 7 8 70 000 Standard 2 71 68 65 62 59 56 53 50 Alternate 2 57 54 51 48 45 42 39 36 90 000 Standard 2 61 58 55 52 49 46 43 40 Alternate 2 47 44 41 28 35 32 29 26 115 000 Standard 2 71 68 65 62 59 56 53 50 Alternate 2 57 54 51 48 45 42 39 36 GCVA Model Furnaces Direct Vent Dual Pipe Venting Table Maximum Allowable Length of Vent Flue amp Combustion Air Intake Pipe ft Pipe Number of Elbows Unit Input Termination Btu Style inch 1 2 3 4 5 6 8 2 49 46 43 40 37 84 81 28 Standard 3 71 68 65 62 59 56 53 50 70 000 2 36 33 30 27 24 21 18 15 Alternate 3 57 54 51 48 45 42 39 36 Standard 2 61 58 43 52 49 46 43 40 90 000 3 71 68 65 62 59 56 53 50 Alternate 2 48 45 30 39 36 33 30 27 3 57 54 51 48 45 42 39 36
43. 49 PRODUCT DESIGN KA IE 2 Min Wall or Parapet Ching 10 or Less Chimney Termination 10 Feet Or Less From Ridge Wall Parapet than 10 2 NOTE No Height 3 above Wall required when distance Chimney from walls or parapet is more than 10 feet than 10 Parapet Height above any roof surface within 10 feet horizontally Chimney i Termination More Than 10 Feet From Ridge Wall or Parapet Check 2 Any solid or liquid fuel appliances vented into this chimney channel Solid fuel appliances include fireplaces wood stoves coal furnaces and incinerators Liquid fuel appliances include oil furnaces oil fired boilers and oil fired water heaters Appliances which burn propane sometimes referred to as LP liquefied petroleum gas are considered gas fired appli ances 50 Check 3 Chimney Crown Condition Damage from condensate usually shows up first in the crown If any of the following trouble signs are present the condi tion of the crown is not satisfactory 8 Crown leaning b Bricks missing Mortar missing Tile liner cracked Da No tile liner f Salt staining at mortar joints White stains and mor tar becomes sandy and or erodes For problems a b or c see Fix 3 If problems d e orf are present see Fix 4 IMPORTANT It may be ne
44. 69 a messem 1 1 LIS sels S sie sex euedoug BES 51541974 wi einssoid BBBBE YOUMS 5 BEEEE uonduoseg D070CA30 D070DA30 D070CX40 D070DX40 D090DA30 D090CA50 D090DX50 D115CX50 D070EA30 D045GA30 GUIDO70GA30 D090GA50 HIXIICNNESESESESESESESES javieo7oexao X X x x X UID070GA40 UIDO90GA30 U GUIE115Ex50 x x x x x x x x e e X X Model Number GUID045CA30 GUID045CX30 GUIDO70CA40 GU GUIDO70DA40 GU GUIDO90CA30 GUIDO90CX30 GU GUIDO90CX50 GUID090DA50 GU GUID115CA50 GUID045DA30 GUID045DX30 GU GUID115DA50 GU GUID070CX30 GU GUIDO70DX30 GUIDO90DX30 GU GU GU G G G 5 4 501 to 11 000 ft 6 001 to 8 500 ft 2 6 001 to 11 000 ft 3 0 to 6 000 ft 1 Available for this model Not used in this application X 6 7 501 to 11 000 ft 7 0 to 7 500 ft 4 8 501 to 11 000 ft Note All installations above 6 000 ft require a pressure switch change Note For installations in Canada the Amana 80 furnace is certified only to 4 500 ft 31
45. CX P1207701F P1207707F 40 80 furnace featuring electronic ignition control silicon carbide ignitor radiant flame sensor electrodepositioned textured steel cabinet and aluminized steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft C Air Command 80 SSE Furnace C Third Design Series A Standard Unit not NOx certified GUIC CA P1207601F P1207608F 140 80 furnace featuring integrated electronic ignition control silicon carbide ignitor electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft C Air Command 80 SSE Furnace C Third Design Series A Standard Unit not NOx certified GUIC CA 1229101 P1229108F 40 8096 furnace featuring integrated electronic ignition control silicon carbide ignitor electrodepositioned textured steel cabinet 409 stainless steel tubular heat exchanger Change from embossed bottom knock out to perforated bottom knock out and addition of internal side filter retention Gas Furnace Upflow Horizontal Induced Draft C Air Command 80 SSE Furnace C GUIC CA Pi229001F P1229008F Third Design Series Standard Unit not NOx certified 40 8096 furnace featuring integrated electronic ignition control silicon carbide ignitor prepainted textured steel cabinet and 409 stainless steel tubular heat exchanger PRODUCT IDENTIFICATION This section will identify the mod
46. P1212507F 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor electrodepositioned textured steel cabinet and aluminized steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft D Air Command 80 SV Furnace C Third Design Series X NOx Certified 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor electrodepositioned textured steel cabinet and aluminized steel tubular heat exchanger Release of Fasco induced blower to replace Jakel induced draft blower Gas Furnace Upflow Horizontal Induced Draft D Air Command 80 SV Furnace C Third Design Series A Standard Unit not NOx certified P1229601F P1229607F 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor prepainted textured steel cabinet and aluminized steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft D Air Command 80 SV Furnace C Third Design Series X NOx Certified P1229701F P1229705F 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor electrodepositioned textured steel cabinet and aluminized steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft D Air Command 80 SV Furnace D Fourth Design Series A Standard Unit not NOx certified 40 80 furnace featuring integrated electronic ignition control silicon P1226901F P1226911F carbide ignitor
47. Q GCI GCI GCI 1 1 1 1 lt 1 1 1 1 1 1 GCI A B C 115 50 699 699 768 960 GCI A B C 140 50 _ 838 838 838 960 GCISO70 35 o 55 56 1 0 GCIS090 50 LL 576 672 76 60 Mimimum Filter Area Based on Heating Airflow Requirement NOTE The dashed areas indicate not used in this application 85 PRODUCT DESIGN Minimum Filter Requirement in Disposable Filters Airflow Requirements Nominal 000 500 000 00 400 000 000 CLA070CX30 GCLA090CX40 GCLA115CX50 GCVA070CX40 GCVA090CX50 GULA045CX30 GULA070CX30 GULA070CX40 GULA090CX40 GULA090CX50 GULA115CX50 384 GUIE045EX30 GUIEO70EX40 GUIEO90EX40 GUIEO90EX50 GUIE115EX50 335 364 sea sev 97 5 see 6 ser 568 soe 9 _ ____ __ 79 Css sw 89 1 or 18 COLLE 960 384 480 76 49 5 768 90 EN 800 800 672 672 940 Mimimum Filter Area Based on Heating Airflow Requirement NOTE The dashed areas indicate not used in this application Electronic Air Cleaner EAC5 or Media Air Cleaner 1 The electronic air cleaner and media cleaner are multi positional high efficiency air filtra
48. To PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE THE INLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING Gas inlet and manifold pressures should be checked and adjusted in accordance to the type of fuel being consumed The line pressure supplied to the gas valve must be within the range specified below The supply pressure can be mea sured at the gas valve inlet pressure tap or at a hose fitting installed in the gas piping drip leg The supply pressure must be measured with the burners operating To measure the gas supply pressure use the following procedure Disconnect ALL ELECTRICAL POWER AND SHUT OFF GAS SUPPLY BEFORE SERVICING OR INSTALLING 1 Afterturning off gas to furnace at the manual gas shutoff valve external to the furnace remove burner compart ment door to gain access to the gas valve 2 Connect a calibrated water manometer or appropriate gas pressure gauge at either the gas valve inlet pres sure tap or the gas piping drip leg as shown in the follow ing two figures NOTE At either location a hose fitting must be installed prior to making the hose connection GAS VALVE CONTROL ON Off SWITC ATMOSPHERE INLET PRESSURE TAP OUTLET MANIFOLD PRESSURE TAP SIDE OF VALVE SIDE OF VALVE MANOMETER HOSE PRESSURE REGULATOR ADJUSTMENT 4 UNDER SCREW MANOMETER Measuring Inlet Gas Pressure
49. flue pipe a single 90 elbow must be secured to the com bustion air intake to prevent inadvertent blockage The tee or elbows used in the vent flue termination must be included when determining the number of elbows in the piping sys tem GUCA 8 GCCA Model Furnaces Non Direct Vent Single Pipe Venting Table Maximum Allowable Length of Vent Flue Pipe ft T 6 ooo 1 2 15818562 581 5 5 50 90 000 2 60 57 55 52 50 47 45 0 4 500 ft 111 107 104 100 97 93 90 4 500 11 000 ft GUVA Model Furnaces Non Direct Vent Single Pipe Venting Table Maximum Allowable Length of Vent Flue Pipe ft ma 4 Number of Elbows neis des eese esee 4500 2 71 68 65 62 59 56 53 50 22 88 46 48 40 37 24 26 s fr es os 59 5e 50 s 65 9 56 50 1159 s 40 37 94 91 28 GUSA Model Furnaces Non Direct Vent Single Pipe Venting Table Maximum Allowable Length of Vent Flue Pipe ft Unit Input Btu Unit Input 5 Number of Elbows 6 CEL 2 Le er 5 55 52 40 46 43 es 62 se 56 53 50 1500 3 71 68 65 62 59 56 53 50 GULA GCLA Model Furnaces Non Direct Vent Single Pipe Venting Table Maximum Allowable Length of Vent Flue Pipe ft Number of Elbows 9 Unit
50. gized for 27 seconds The gas valve will be energized on low stage flow rate If flame is not sensed in 7 seconds the gas valve will be de energized and another purge will occur The control will cycle the gas valve a total of three tries before it determines it cannot establish measur able combustion and enters a locked out state If flame is sensed but lost after 10 seconds the control will recycle this series of three tries four more times before locking out The diagnostic light code for this problem is one short flash followed by a longer pause The control can be reset and brought out of lockout mode by turning the thermostat off and then back on It can also be reset by turning off the electrical disconnect switch to the fur nace for 30 seconds NOTE The control board will automatically reset two hours after the lockout occurs If the furnace frequently has to be reset it means that a problem exists that should be cor rected 3 Pressure Switch Stuck Closed If the control senses that either pressure switch is closed when the induced draft blower is off it waits until the fault is corrected The diagnostic light code for this problem is two short flashes followed by a longer pause The probable cause is either a faulty pressure switch or miswiring 4 Pressure Switch Stuck Open If after the induced draft blower is energized the appropriate pressure switch does not close the control will keep the blower on and wait for the
51. 4 56 113 225 450 1125 45 21 4 86 172 459 106 212 424 1059 167 41 50 10 200 400 1000 44 41 8 164 40 19 47 95 19 37 947 4 20 40 80 160 40 29 45 90 160 36 900 46 157 391 21 483 8e 345 857 4 19 38 183 383 gt 41 164 327 86 48 75 50 35 5 5 35 73 77 3 7 255 720 7 35 26 34 69 16 277 6 5 amp 155 36 2 3s 7 135 265 667 53 1171 34 1 850 12 27 645 5 33 33 29 31 62 124 248 821 5 3 39 39 60 120 240 800 56 16 32 4 129 35 12 15 16 36 32 122515 113 25 563 62 124 30 385 206 545 12 305 34 5 16 212 52 6 5 30 6 129 30 35 sf _ 13 2615 5 1 _ 135 SERVICING Complaint 136 POSSIBLE CAUSE DOTS IN ANALYSIS GUIDE INDICATE POSSIBLE CAUSE SYMPTOM Power Failure Burner Won t Ignite System Will Not Start Burner Ignites Locks Out Burner Shuts Off prior to T Stat being Satisfied Unsatisfactory Heat Short Cycles Long Cycles Soot and or Fumes Too Much Heat Not Enough He
52. 6 Thecontinuous fan speed may be selected from one of three speeds Knowing the heating speed selection look up the heating based continuous fan air flow see Speci fication Sheet Knowing the cooling speed selection look up the cooling based continuous fan air flows op tions A amp B see Specification Sheet NOTE Option B is NOT applicable if a two stage cooling system is used Knowing the three possible continuous fan speeds se lect the speed that best fits the application The lower CFM will use less electricity and minimize operating sound levels EXAMPLE With the GUVAO70AXAO0 set to A Minus on heating the heating based continuous fan speed will be 756 CFM refer to specification sheet or technical manual for airflows The cooling speed was set to C Minus so the cooling based continuous fan speeds are 743 CFM Option A or 644 CFM Option B Because the cooling based continuous fan speed is lower it should be selected 7 Knowing the continuous fan speed desired the unit should be wired to accommodate this speed If the con tinuous fan speed desired is based on the heating speed connect G from the thermostat to G on the two stage integrated control module If the continuous fan speed desired is based on the cooling speed option A connect from the thermostat to on the air circulating blower interface board If the continuous fan speed desired is based on the cooling speed Option B connect G from t
53. 8 7 4321 Cooling Speed Taps et H indicates factory setting TapA 00 FF FF 87 4321 Heating Speed 00 FN F 8 7 4321 Heating I Speed TapC 87 4321 Heating Speed pu TapD NN Heating Speed Taps indicates factory setting Circulator Blower Speed Tap DIP Switches GUVA BX CX Models amp GUIV FX Models CIRCULATOR BLOWER TIMINGS Single Stage 80 amp 90 Furnaces and 80 Two Stage Furnaces All items in this section refer to the air circulation blower not to the induced draft blower The timing sequence for the induced draft blower is not adjustable When a call for cooling occurs the circulation fan will come on It will remain on for 45 seconds after the call for cooling ends This fan timing is not adjustable Blower Heat Off Delay Timing The integrated control module provides a selectable heat off delay function The heat off delay period may be set to 60 90 120 or 180 seconds using the DIP switches or jumper need onthe control module The delay is factory shipped at 90 seconds but may be changed to suit the installation requirements and or homeowner preference Refer to the fol lowing figures for switch positions and corresponding delay times
54. The HSI 2 ignition control has an initial ignitor warmup time of 7 seconds In the event of a retry the warmup time will be increased by two seconds and that duration will remain effective until another retry In which case the warmup time is again increased by two seconds but never more than 11 seconds At the end of the heat cycle the warmup time is reset back to the minimum time setting NOTE The White Rodgers 50M61 and 50V61 ignition con trols have an ignitor warmup time of 20 seconds These con trols have a built in learning routine that gradually reduces the ON time of the ignitor The effect is that the ignitor operates at a cooler temperature The learning routine will eventually reduce the ignitor ON time to a point at which the ignitor is too cold to ignite the gas The control will then increase the ON time and initiate an ignition retry The furnace will light The control will remain at this point for 256 thermostat cycles after which it will re enter the learning routine IMPORTANT The ONLY way to determine if the ignitor ON time is changing is to view the ignitor voltage wave form with an oscilloscope 6 Ifproofofflame was established voltage will be provided to the air circulation blower following the heat on delay period 152 a Checkfor 120 volts from the CIR terminal WH wire on GUIA GCIA GUIC GCIC GUID GUCA GUIE GCCA GCLA GULA and GUSA models or WH 33 wire on GUIS and GCIS m
55. The on off switch may affect the resistance measurement 1 Remove the switch panel and measure the coils directly 2 Using an ohmmeter test across the coils A coil s resis tance increases with increasing temperature Nominal Coil Resistance Main 95 ohms Redundant 98 ohms 2nd Stage 180 ohms 3 Allow atleast 20 tolerance for temperature and meter variation Most of the time coils will fail as open circuit If not as above replace the entire valve S 12 CHECKING HOT SURFACE IGNITOR The 80 furnaces use a 120V silicone carbide resistive ele ment ignitor for ignition The normal operating temperature is approximately 2550 F The 90 GUCA GCCA GCLA 150 GUIE EX GULA AX CX and GUVA AX model fur naces use a 120V ceramic metallic composite mini ignitor for ignition The normal operating temperature is approxi mately 2192 2642 F The 90 GCVA BX CX GUSA BX GUIS FX GUIV FX GUIC FX GCIC FX and GUVA BX model furnaces use a 80V Silicon Nitride SiNi ignitor for ignition The nominal operating temperature is approximately 2174 NOTE The Silicon Nitride Ignitoris not interchangeable with carbide ignition controls DISCONNECT ELECTRICAL POWER SUPPLY 1 Remove burner compartment door to gain access to the ignitor 2 Ignitor cool approximately 70 77 F 3 Disconnectthe ignitor from the Ignition Control 4 Using an ohmmeter measure the resistance of the igni tor 8096 Furnaces
56. connected to the venting system are not in operation Sealany unused openings in the venting system b Inspect the venting system for proper size and horizontal pitch as required by the National Fuel Gas Code ANSI Z223 1 or the CAN CGA B149 Installation Codes and these instructions Determine that there is no blockage or restriction leakage corro sion and other deficiencies which could cause an unsafe condition c Inso faras practical close all building doors and windows and all doors between the space in which the appliance s connected to the venting system are located and other spaces of the building Turn on clothes dryers and any appliance not connected to the venting system Turn on any exhaust fans such as range hoods and bathroom exhausts so they shall operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers d Follow the lighting instructions Place the appliance being in spected in operation Adjust thermostat so appliance shall oper ate continuously 44 e Test for draft hood equipped appliance spillage at the draft hood relief opening after 5 minutes of main burner operation Use the flame of a match or candle f After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above return doors windows exhaust fans fireplace dampers and any other gas burning appliance to their previous conditions of use g Ifimproper
57. eseg 10014 uonduoseg FFEEFEFEEEFEFFEEFEFEEFFEFEEFEEFE jactaosoaxeo x x x Gciaomexo x Gucaozo xso GUCA115BX50 1 0454 201 1 1 x x Gccaosoaxso 115 50 ccamsexso x Gucaosoaxso ucansaxso ucaosexso GUCA045AX30 GUCA070AX30 GUCA070AX40 GUCA090AX40 Tx 10 1L 1011 Jet Tx 1011 1 19 xj ___ 2 101 4 9 001 10 11 000 1 10 10 icvaoogxo xi Jor olio j xixixixixi xi iol 1 1011 Ixiorxti GUSAO7OBX35 XX xX 0 70 x fe 508 1158 50 X Available for this model eusasoxe Jo GUSA090BX50 xixix Jo GCVAO7OAx40 x txt o 3 0 to 7 000 ft 1 7 001 to 9 000
58. knob counterclockwise V to the On position for ei ther the Honeywell VR 8205 gas valve or the White Rodgers 36E35 36E36 and 36E96 gas valves The knob should turn easily Do not use excessive force For the Robertshaw 7222 gas valve push in and slide the valve lever on the lefthand side of the valve to the On position and for the White Rodgers 36E22 36E54 36F22 and 36G22 gas valve push the selector switch on top of the valve to the On position 9 Replace the door on the front of the furnace 10 Open the manual gas valve external to the furnace 11 Turn on the electrical power supply to the furnace 12 Setthe room thermostat to the desired temperature NOTE There is approximately 20 second delay between thermostat energizing and burner firing 128 PRESSURE REGULATOR ADJUSTMENT OUTLET MANIFOLD UNDER CAP SCREW m _ PRESSURE TAP Honeywell D OUTLET INLET PRESSURE TAP GAS VALVE ON OFF CONTROL KNOB Honeywell Model VR 8205 GUIA GCIA GUIC GCIC GAS VALVE ON OFF CONTROL 22 OUTLET PRESSURE REGULATOR OUTLET MANIFOLD ADJUSTMENT PRESSURE TAP UNDER CAP SCREW INLET PRESSURE TAP SIDE OF VALVE White Rodgers Model 36E36 Type 230 GUIA GCIA GUIC GCIC GAS VALVE ON OFF CONTROL INLET b b OUTLET OUTLET MANIFOLD PRESSURE TAP
59. uonduoseg C045EA30 C045EX30 C070EA30 070 070 40 070 40 090 50 090 50 115 40 115 40 115 50 115 50 140 50 140 50 045 0 C045FX30 070 0 070 40 070 0 070 40 090 0 090 50 090 090 50 115 40 115 50 115 40 115 50 140 50 140 50 GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU 1 0 to 7 500 ft 3 4 501 to 11 000 ft Available for this model X 2 7 501 to 11 000 ft Not used in this application Note All installations above 6 000 ft require a pressure switch change furnace is certified only to 4 500 ft Note For installations in Canada the Amana 80 29 ACCESSORIES Model Number ASB01A 250052 23882 22222 HAC1PS11 HAC1PS12 07 Description Adjustable Subbase Electronic Air Cleaner External Filter Rack Furnace Twinning Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Propane Gas Kit High Altitude Natural Gas Kit LP Gas Low Pressure Kit Propane Gas Conversion Kit Media Air Cleaner X x GCIC070CX40 GCICO70DX40 x x x GCIC115CX40 GCIC115CX50 GCIC140CX50 gt gt
60. 2 Remove cover from Junction Box and gain access to incoming power lines With Power ON LINE VOLTAGE NOW PRESENT 3 Using a voltmeter measure the voltage across the hot and neutral connections NOTE To energize the furnace the Door Interlock Switch must be engaged at this point 4 Noreading indicates open wiring open fuse no power or etc from unit to fused disconnect service Repair as needed 5 With ample voltage at line voltage connectors energize the furnace blower motor by jumpering terminals R to G on the integrated ignition control 6 With the blower motor in operation the voltage should be 115 volts 10 percent 7 reading falls below the minimum voltage check the line wire size Long runs of undersized wire can cause low voltage If wire size is adequate notify the local power company of the condition 8 After completing check and or repair replace Junction Box cover and reinstall burner compartment door on 8096 or blower compartment door on 90 furnace 9 electrical power and verify proper unit operation S 2 CHECKING WIRING DISCONNECT ELECTRICAL POWER SUPPLY 1 Check wiring visually for signs of overheating damaged insulation and loose connections 2 Use an ohmmeter to check continuity of any suspected open wires 138 3 If any wires must be replaced replace with AWM 105 C 4 64 thick insulation of the same gauge or its equivalent S 3 CHECKIN
61. 2 Turn off all electric power to the appliance if service is to be performed 3 Turn the gas control knob clockwise 4 OFF Position Do not force 4 Replace control access panel TURN OFF GAS EN POUR COUPER L ADMISSION NE DE GAZ DE L APPAREIL 1 R gler le thermostat la temp rature la plus basse 2 Couper l alimentation lectrique de l appareil s il faut proc der des op rations d entretien 3 Torner le robinet a gaz dans le sens des aigilles d une montre en position OFF ARRET Ne pas forcer 4 Remettre en place le panneau d acc s 11072708 OPERATING INSTRUCTIONS READ BEFORE OPERATING FOR YOUR SAFETY LIRE AVANT DE METTRE EN MARCHELIRE ersonal injury or WARNING If you do not follow these instructions explosion may result causing property damage loss of life A settle on the floor Do not try to Do not touch If you cannot Never use tools If or explosion Immediately call a the appliance and This appliance does not have a pilot It is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand System and any gas control which has been underwater AVERTISSEMENT Quiconque ne respecte pas la lettre les instructions dans le pr sent manuel risque de d clecher un incendie ou une explosion entrainant des dammages mat riels des l sions corp
62. 90 seconds the furnace will lock out Flame lost later than 90 seconds If the heat signal is lost while the call for heat continues more than 90 sec onds after the gas valve opens the system will recycle During a recycle the gas valve closes and a new igni tion sequence begins No matter how many recycles may occur this alone will not cause the furnace to lock out Trip on High Limit or Auxiliary Limit If the high limit or auxiliary limit control opens during a heating cycle the gas valve closes The induced draft blower runs and the air circulator blower runs at Heating speed This continues until the limit closes Note Auxiliary limit is manual reset so it will never close on its own When the limit closes the induced draft blower shuts off im mediately but the air circulator blower continues to run for 90 seconds After this 90 second cool down is com pleted a normal heating sequence can begin The prob able cause is either low airflow due to dirty filter dirty Coil or restricted ductwork or blower speed set too low gas input set too high faulty limit or faulty blower Interruption of Power Supply If the line voltage power is interrupted the gas valve closes It will remain closed until line voltage power is restored and a low voltage call for heat occurs at the room thermostat At that time a new ignition sequence will begin Open Rollout Thermostat If the rollout thermostat opens during a heating
63. AUTO position the air circulator blower will start and stop at the same time as the compressor No fan time delay will occur Fan On Off Timings are as described above They are not adjustable IMPORTANT If the furnace frequently has to be reset it means that a problem exists that should be corrected SYSTEM OPERATION NORMAL SEQUENCE OF OPERATION 80 Two Stage Models with White Rodgers 50A51 215 Integrated Ignition Control Power Up The normal power up sequence is as follows D 115 VAC power applied to furnace Integrated control module performs internal checks Integrated control module flashes LED one time Integrated control module monitors safety circuits con tinuously Furnace awaits call from thermostat Heating Mode The normal operational sequence in heating mode is as fol lows 1 R and W1 or R and W1 and W2 thermostat contacts close initiating a call for heat The induced draft blower is energized on high speed for a 10 second prepurge Humidifier terminals are energized with induced draft blower The induced draft blower steps to low speed following prepurge Low stage pressure switch contacts are closed The ignitor is energized and is allowed to preheat for 17 Seconds The gas valve is energized delivering gas to the burners at the low stage heat flow rate The control checks for a signal from the flame sensor within seven seconds after the gas valve is energized opens G
64. Bos STOP Follow B in the safety plancher pour d celer une odeur de gaz Si c est le cas information above on this Label ROBINET A GAZ ARRETER Passer l tape B des instructions de s curiti If you don t smell gas go to MANUEL POS sur la portion sup rieure de cette tiquette next step S il n y a pas d odeur de gaz passer l tape suivant 7 Tourner le robinet a gaz dans le sens inverse des ki 1 Velum gas control nee aigilles d ne montre F en pos counterclockwise F to ON GAS 8 Remettre en place le panneau d acc s 9 Mettre l appareil sous tension power ike 10 R gler le thermostat la temp rature desir e 10 Set thermostat to desired setting ARRIVEE Si l appareil ne mat pas en marche les instructions intitul es Comment coupler l admission 11 If the appliance will not operate ME follow the instructions To Turn de gaz de l appereil et appeler technicien oer lS L MANUAL GAS qualifi ou le fourrnisseur de gaz Off Gas To Appliance and call your KNOB SHOWN service technician or gas company IN ON POSITION TURN OFF GAS APPLIANCE EBENE POUR COUPER L ADMISSION NI DE GAZ DE L APPAREIL 1 Set the thermostat to lowest setting 1 R gler le thermostat la temp rature la plus basse 2 Turn off
65. Buidid 10 uonoes pue 998 edau 1054 440 uin peeds pue esu 10 998 5 998 1054 440 ped Jedoud 5 eunsseJd Buidid 10 uonoes pue 998 1054 440 ped dej Jedoud 1054 440 uin Buidid 10 uoyoes did pue 998 191 105095 pues ejpueu s redau 0 aoud 440 4 Jenueui jo suonneoed 1054 440 esnj e Ajs y YIM 0 1054 440 uin pue suonneg 1981109 pue 49949 194044 10 pue eDexoojq 10 jueuiuBije
66. CX and aluminized steel tubular heat exchanger and stainless steel recouperative coil P1253204F id P1253206F Models listed utilize a 2 row secondary recouperative coil the next to the manufacturing P number indicates the furnaces using a 2 row secondary recouperative coil GCLA units are shipped non direct vent but can be installed as direct vent by adding the intake air coupling and appropriate field supplied pipe P1242203F P1242205F ignition control silicon nitride ignitor two stage gas valve two speed induced draft blower variable speed circulator blower prepainted steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Counterflow Horizontal Variable Speed 2 Stage Condensing A Standard 40 Line C Third Design Series X NOx Certified Gcva cx p1253003F P1253005F 40 95 two stage variable speed furnace featuring intell ignition integrated electronic Gas Furnace Counterflow Horizontal Variable Speed 2 Stage Condensing A Air Command 95 II Q Furnace Second Design Series NOx Certified P1237408F P1237405F 40 95 two stage variable speed furnace featuring intell ignition integrated electronic ignition control silicon nitride ignitor two stage gas valve two speed induced draft blower 316L Header Plates prepainted steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal E Distinction 92 A Standard Line Furnace
67. Certified cus cx 1211103 1211107 40 80 two stage furnace featuring integrated electronic ignition control silicon carbide ignitor two stage gas valve two speed induced draft blower electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft S 2 Stage Air Command 80 SSE Furnace D Fourth Design Series A Standard Unit not NOx certified 40 80 two stage furnace featuring integrated electronic ignition control silicon GUISO70DA35 P1227103F carbide ignitor two stage gas valve two speed induced draft blower and 409 stainless Steel tubular heat exchanger Use of smooth cold rolled steel substrate a smooth top coat for furnace cabinet to replace prepainted furnaces until new coating is approved for prepainted material Gas Furnace Upflow Horizontal Induced Draft S 2 Stage Air Command 80 SSE Furnace C Third Design Series Standard Unit not NOx certified GUIS CA P1229803F P1229808F 140 80 two stage furnace featuring integrated electronic ignition control silicon carbide ignitor two stage gas valve two speed induced draft blower prepainted textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft S 2 Stage Air Command 80 SSE Furnace C Third Design Series A Standard Unit not NOx certified 40 80 two stage furnace featuring integrated electronic ignitio
68. Chart below for an inter pretation of the LED signals and to the information in this section for a description of the problem 1 Internal Control Failure with Integrated Ignition Con trol If the control determines it has an internal fault it enters a locked out state and the diagnostic light will light continuously with no flashes The control should be replaced System Lockout If a flame is not sensed during the first seven 7 seconds after the gas valve is energized the control turns off the gas There will then be a 60 second delay while the induced draft blower is energized to purge the heat exchanger The ignitor will next be energized and preheated for 27 seconds The gas valve will then be energized If flame is not sensed in seven 7 seconds the gas valve will be de energized and another purge will occur The control will cycle the gas valve a total of three 3 times before it determines it cannot establish measurable combustion and enters a locked out state If flame is sensed but lost after ten 10 sec onds the control will recycle this series of three tries four 4 more times before locking out The diagnostic light code for this problem is one short flash followed by alonger pause The control can be reset and brought out of lockout mode by turning the thermostat off and then back on It can also be reset by turning off the elec trical disconnect switch to the furnace for 30 seconds NOTE The control board will
69. Induced Draft High Blower Low Off Thermostat High Low Off 0 10 27 28 31 61 91 0 15 30 60 90 90 120 120 150 Time sec 180 210 Example 2 Continuous Call For High Stage Heat Only High Circulator Low Blower Off High Gas Valve Low Off Igniter On Off PS2 Closed Pressure PS1 Closed Switches Open High Induced Draft Low Blower Off High Thermostat Low Off 0 10 27 28 31 61 91 0 15 30 60 90 90 120 Ti 120 or 150 ime sec 180 210 109 SYSTEM OPERATION Circulator Blower Gas Valve Igniter Pressure Switches Induced Draft Blower Thermostat Circulator Blower Gas Valve Igniter Pressure Switches Induced Draft Blower Thermostat 110 HEATING TIMING CHARTS FOR WHITE RODGERS 50A51 235 TWO STAGE INTEGRATED IGNITION CONTROL OPERATION Example 3 Initial Call For Low Heat Change In Call To High Heat Call Change to High Heat High Low Pm Off PS2 Closed PS1 Closed Open 41 High Low Off High Low Off 0 10 27 28 31 61 91 0 15 30 60 90 90 120 120 or 150 or Time sec 180 210 Example 4 Initial Call For High Heat Subsequent Call To Low Heat Call Change to Low Heat 30 Seconds After Call Change to Low Heat High Low High Low Off PS2 Closed PS1 Closed
70. Input Btu 4509 2 68 65 62 59 56 53 50 7000 2 fes 65 62 59 56 53 50 9000 2 60 57 55 52 50 47 45 58 GCVA Model Furnaces Non Direct Vent Single Pipe Venting Table Maximum Allowable Length of Vent Flue Pipe ft Pipe ps pe prie of terre 58 55 52 49 46 43 40 3 71 68 65 62 59 56 53 50 2 61 58 55 52 49 46 43 40 3 7 68 65 62 59 56 53 50 70 000 90 000 1 One 90 elbow must be secured to the combustion air intake con nection 2 Minimum vent length is five feet and one elbow tee 3 Tee or elbows used in the vent flue termination must be included when determining the number of elbows in the piping system 4 3 diameter pipe can be used in place of 2 diameter pipe Vent Flue Pipe Terminations 90 Furnaces Only The vent flue pipe may terminate vertically as through a roof or horizontally as through an outside wall Vertical vent flue pipe termination should be as shown in the following figures Refer to Vent Flue Pipe and Combustion Air Pipe Termination Locations section in this manual or the installation instructions for details concerning location restrictions The penetration of the vent through the roof must be sealed tight with proper flashing such as is used with a plastic plumbing vent 12 MINIMUM TO ROOF OR
71. KIT CVK4 7 8096 Furnaces with White Rodgers 50A55 Integrated Ignition Control This wiring diagram is for reference only Not all wiring is as shown above refer to the appropriate wiring diagram for the unit being serviced For use only with 8096 Single Stage Furnaces N O NORMAL SERVICE VENT DAMPER HIGH ps VOLTAGE JUNCTION BOX WH COMBUSTION BLOWER VT 03 4 1 BK Point to Point Wiring 162 ACCESSORY WIRING DIAGRAMS HIGH VOLTAGE WARNING DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH FURNACE TWINING KIT FTK03A This wiring diagram is for reference only Not all wiring is as shown above refer to the appropriate wiring diagram for the unit being serviced For use only with 8096 or 9096 Single Stage Furnaces WHT with terminal WHT without terminal BLK Sensor Twinning Control _ Cool RED FAULT FLASH 1 FURNACE 1 Furnace 2 Speed SIGNAL FLASH S
72. Mea sure voltage from Pin 9 MV M1 terminal GY 47 wire to Pin 12 C C2 terminal BR 21 wire on the ignition control 12 Pin connector No voltage replace ignition control b On GUIS GCIS and GUIV models Measure voltage from either Pin 7 PM terminal GY 47 wire or Pin 1 HI terminal YL 11 wire to Pin 8 C terminal BR 21 wire on the ignition control 12 Pin connector No voltage replace ignition control c On GCCA GCLA GCVA GUCA GUIE and GULA models Measure voltage from Pin 9 C2 terminal BR 13 wire to Pin 12 M1 terminal GY 12 wire on the ignition control 12 Pin connector No voltage replace ignition control d On GUVA and GUSA models Measure voltage from either Pin 7 PM terminal GY 12 wire or Pin 2 HI ter minal YL 20 wire to Pin 8 C terminal BR 13 wire on the ignition control 12 Pin connector no voltage re place ignition control IMPORTANT The GCLA GCVA GUCA GCCA GULA GUSA and GUVA model furnaces have a Coil Cover Pres sure Switch in series with the M1 side of the gas valve NOTE The White Rodgers 50A55 control has an adaptive algorithm that adjusts the duration of ignitor warmup for the purpose of extending igniter life Following application of power the warmup time will be 17 seconds for the first 64 successful ignitions Each subsequent warmup time will be decreased by 1 second until flame fails to be achieved re sulting in a retry or until the minimum of 5 seconds is achieved NOTE
73. Measuring Manifold Gas Pressure Gas Valve Tap LINE VOLTAGE NOW PRESENT 3 Turn ON the gas and electrical power supply and oper ate the furnace 4 Measure gas manifold pressure with burners firing Ad just manifold pressure using the table below Manifold Gas Pressure Natural Gas 35 10 0 w c The final manifold pressure must not vary more than 0 3 W C from the above specified pressures Any necessary major changes in gas flow rate should be made by changing the size of the burner orifice 5 To adjust the gas valve pressure regulator remove the regulator cap 6 Turn the adjustment screw clockwise to increase the pressure or counterclockwise to decrease the pressure 7 Securely replace the regulator cap warning HIGH VOLTAGE Disconnect ALL ELECTRICAL POWER AND SHUT OFF GAS SUPPLY BEFORE SERVICING OR INSTALLING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 8 Disconnect manometer after turning off gas at manual shutoff valve Reinstall gas valve outlet pressure tap plug before turning on gas to furnace 157 SERVICING GAS VALVE CONTROL ON Off SWITC ATMOSPHERE INLET PRESSURE TAP SIDE OF VALVE OUTLET MANIFOLD PRESSURE TAP SIDE OF VALVE MANOMETER HOSE PRESSURE REGULATOR ADJUSTMENT 4 UNDER SCREW MANOMETER Measuring Inlet Gas Pressure White Rodgers 36E Gas Val
74. S 2 Stage Air Command 80 SSE II Furnace C Third Design Series X NOx Certified acis cx P1230708F P1230705F 40 80 two stage furnace featuring integrated electronic ignition control silicon carbide ignitor two stage gas valve two speed induced draft blower electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Counterflow Horizontal Induced Draft S 2 Stage Air Command 80 SSE II Furnace Sixth Design Series X NOx Certified P1247003F P1247005F 40 80 two stage furnace featuring a new integrated electronic ignition control new silicon nitride ignitor new wire harnesses two stage gas valve two speed induced draft blower electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft Variable Speed 2 Stage Air Command 80 SSE Q Furnace D Fourth Design Series X NOx Certified GUIV DX P1227403F P1227408F 40 80 two stage variable speed furnace featuring integrated electronic ignition control silicon carbide ignitor two stage gas valve two speed induced draft blower variable speed circualtor blower electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft Variable Speed 2 Stage Air Command 80 SSE II Furnace C Third Design Series X NOx Certified GUIV CX P1230203F P1230
75. Sequence of Operation section of this manual for corresponding timing charts The ignition control is capable of diagnosing many furnace failures to speed troubleshooting A flashing red or green diagnostic indicator light on the control flashes a code for any discovered failures When the control is powered up normally the light will flash once for about one second This can be used to test for 120 volts and 24 volts to the control since both must be present for the light to flash If this step fails check for 120 volts to the control and check the transformer and its associated wiring If this step is successful give the control a call for heat and wait five 5 seconds or until the furnace goes into lockout If the control detects a failure it will now be shown on the diagnostic indicator light Refer to the Abnormal Op eration section in the Sequence of Operation section of this manual for more detail on failure codes The indicator light may be viewed by looking through the sight glass in the blower compartment door If the blower compartment door is removed failure to hold the door switch closed while removing the blower compartment door will re sult in the loss of the stored failure code In most cases recycling the ignition control will result in the same failure code originally displayed 1 Check for 120 volts from Line 1 BK 6 wire on GUIA GCIA GUIC GCIC GUID GUIS GCIS and GUIV mod els or BK 4wire on GUCA GULA GCCA
76. automatically reset one hour after lockout occurs If the furnace frequently has to be re Set it means that a problem exists that should be corrected Pressure Switch Stuck Closed If the control senses the pressure switch is closed when the induced draft blower is off it waits until the fault is corrected The di agnostic light code for this problem is two short flashes followed by a longer pause The probable cause is either a faulty pressure switch or wiring Pressure Switch Stuck Open If after the induced draft blower is energized the pressure switch does not close the control will keep the blower on and wait for the switch to close The diagnostic light code for this problem is three short flashes followed by a pause The probable cause is either disconnected hose to the pressure switch faulty pressure switch or wiring or restricted air intake or flue piping Open Limit Control If the limit control opens the air circulator and induced draft blower will be turned on until the limit closes The diagnostic light code for this prob lemis four short flashes followed by a pause The prob able cause is either low conditioned air flow due to dirty filter or resistance in duct work faulty limit faulty blower or blower speed set to low Open Rollout Control If the rollout control opens the air circulator blower and induced draft blower will be en ergized all the time The diagnostic light code for this problem is five
77. blower Furnace circulator blower and outdoor cooling unit run and integrated control module monitors safety circuits continuously Dehumidistat opens on humidity rise Motor applies a dehumidification factor of 80 to the cooling airflow de mand causing the motor to operate at 80 of cooling airflow demand When humidity level falls below setting on dehumidistat the dehumdistat closes allowing the motor to return to set cooling speed R and Y thermostat contacts open completing the call for cool Outdoor fan and compressor are de energized Electronic air cleaner terminals are de energized Circulator blower is de energized following a fixed forty five second cool off delay period The air circulator blower will ramp down for another 30 seconds and shut down Furnace awaits next call from thermostat SYSTEM OPERATION Air Circulator Blower Gas Valve Ignitor Pressure Switches Induced Draft Blower Thermostat Air Circulator Blower Gas Valve Ignitor Pressure Switches Induced Draft Blower Thermostat HEATING TIMING CHARTS FOR WHITE RODGERS 50 51 225 TWO STAGE INTEGRATED IGNITION CONTROL OPERATION Example 1 Continuous Call For Low Stage Heat Only High Low Off High Low Off On Off PS2 Closed PS1 Closed Open High Low Off High Low Off 0 10 27 31 34 64 94 0 5 30 60 90 90 120 120 150 180 210 Example 2 Continuous Call For High Stage He
78. blower is set for continuous operation Note The Amana Media series of air cleaners can easily be upgraded to a highly efficient EAC5 Electronic Air Cleaner with a permanent washable collecting cell Media Air Filter The filter in Amana Media Air Cleaner MAC1 must be replaced periodically The filter cartridges should be replaced with a Trion Air filter P1221901F cartridge These come from Amana in cartons of three The frequency of filter replacement if best determined by visual examination With typical residential use the approximate replacement period is 9 12 months Two Stage Relay Kit For use with Amana two stage furnace models GUIS GCIS GUIV and GUVA AX This kit enables the use of a single stage thermostat with any Amana two stage furnace The time delay activates the second stage of heat after the TSRKO1 P1232601F furnace has run a set period of time adjustable on low stage heat The time delay is adjustable from 6 to 20 minutes The time delay starts the moment the thermostat initially calls for heat Longer time delays will be more energy efficient while shorter time delays will heat the home faster when the heating demand is high Vertical Concentric Vent Kit For use with Amana furnace models GUCA GULA GCLA GCVA GCCA GUVA and GUSA This kit is designed to allow terminations of a direct vent furnace to be concentrically vented through the roof This kit allows a single VCVK P1211402F penetration to su
79. control No power check BR 10 wire 6 When the Radiant Sensor senses sufficient heat it will close the N O contacts Power should now be read at pin 4 MV FS VT 12 wire No power check VT 12 wire replace Radiant Sensor if necessary 7 After check and or replacement of radiant flame sensor reinstall burner compartment door and verify proper unit operation SERVICING 5 15 CHECKING MAIN BURNERS The main burners are used to provide complete combustion of various fuels in a limited space and transfer this heat of the burning process to the heat exchanger Proper ignition combustion and extinction are primarily due to burner design orifice sizing gas pressure primary and secondary air vent and proper seating of burners HIGH VOLTAGE Disconnect ALL ELECTRICAL POWER AND SHUT OFF GAS SUPPLY BEFORE SERVICING OR INSTALLING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH In checking main burners look for signs of rust oversized and undersized carry over ports restricted with foreign mate rial etc refer to previous drawing S 16 CHECKING ORIFICES A predetermined fixed gas orifice is used in all of these fur naces That is an orifice which has a fixed bore and position as shown the following drawing No resizing should be attempted until all factors are taken into consideration such as inlet an manifold gas pressure alignment and positioning spe
80. delay or OFF delays Circulator blower will operate on selected Low Stage Heating speed tap Circulator blower will operate at 7596 of selected High Stage Cooling speed tap NOTE EAC terminals on the two stage Integrated Control Module will not energize with this method Circulator blower will operate at 6596 of selected High Stage Cooling speed tap NOTE EAC terminals on the two stage Integrated Control Module will not energize with this method Circulator blower will operate at 6596 of selected High Stage Cooling speed tap NOTE EAC terminals on the two stage Integrated Control Module will not energize with this method Circulator blower will operate on selected High Stage Cooling speed tap a E DEBERE PRODUCT DESIGN ADJUST NORM COOL gt ojojo DEHUMDIFICATION LED GREEN TEST E CUT TO ENABLE DEHUMDIFICATION JUMPER WIRE CUT TO ENABLE DEHUMIDIF Air Circulating Motor Interface Board GUIV CA DX amp GUVA AX Models DEHUMDIFICATION LED YELLOW DEHUMDIFICATION J UMPER WRE CUT TO ENABLE 50V61 Integrated Ignition Control Module GUVA BX CXModels Once the jumper wire is cut the dehumidify function is en abled during a combination cal
81. each furnace that is common vented into type B 1 vent system Only Amana Air Command SSE and SV models listed can be common 4 7 P1210001F P1210004F vented with this kit and may not be common vented with any other type furnaces common vent kit is not intended for use on other appliances When the correct venting system has been designed for the installation a Common Vent Kit is selected These kits come in 4 5 6 and 7 inch versions Dehumidistat For use with Amana two stage variable speed furnace models GUVA and GCVA Wall mounted 24 volt humidity control available as a Dehumidistat used to reduce the airflow in the air conditioning mode when necessary to lower the P1227801F humidity in an occupied home to prevent dew build up associated with high humidity levels This control features a moisture sensitive nylon element and also provides positive ON OFF settings for manual operation The control is a normally closed switch that opens on humidity rise causing the blower to switch to a lower speed to control the humidity within the structure P1123001F Electronic Air Cleaner External Filter Rack Kit For use with Amana upflow furnace models GUIA GUIB GUIC GUID GUIE GUIS GUCA GULA GUVA and GUSA This kit is intended to provide a P1221001F location external to the furnace casing for installation of a permanent filter The rack is mounted over the indoor air blower compartment area of either side panel and pro
82. esnj Jamod A pz 10 A GLL ON suonduoseg S8JON seuse J seusej 037 sayn ou seuse 4 q31 onsouBeip pue Jjeuun ou sejnuiu 10 440 pue euo 10 NO seuse J si 437 einpoui pejebeju pue euo s q31 pue jou si jsnonuQuoo 37 jojuoo ooeuinJ euBis ou sepi oud 141 ayesado 0 eoeuunJ 10 ees day payeloossy jo 111020 1171 sjo1uo uoniub 882 19 06 PUL 882 191106 10
83. filter requirement in for either perma nent or disposable filters multiply the required airflow CFM by 144ft and then divide this number by rated velocity of the filter either 300ft min for disposable filter or 600ft min for permanent filter EXAMPLE m Required Airflow x 14482 Fil ie 300 Disposable or 600 Permanent o 1400 14412 Fil lier Size 1117 300 Disposable or 600 Permanent Filter Size 672in Disposable Filter Size 336in Permanent For air delivery of less than 1800 CFM Use one side return or one bottom return ductwork connec tion For air delivery of 1800 CFM or higher Use two side returns or one side return and one bottom return connection Guide dimples locate the side and bottom return cutout lo cations Use a straight edge to scribe lines connecting the dimples Cut out the opening on these lines An undersized opening will cause reduced airflow For bottom return con nection remove the bottom of the cabinet before setting the furnace on the raised platform or return air duct 81 PRODUCT DESIGN A closed return duct system must be used with the return duct connected to the furnace NOTE Ductwork must never be attached to the back of the furnace Supply and return connections to the furnace may be made with flexible joints to reduce noise transmission if desired If a central return is used a connecting duct must be installed betwee
84. flashes followed by a pause The prob able cause is either restricted flue piping or improper air requirements Flame Sensed with No Call for Heat If the control senses a flame when the gas valve is de energized it will run the air circulator blower and the induced draft blower continuously The diagnostic light code for this problem is continuous light flashing The probable causes are either a short to ground in flame sense cir cuit miswiring lingering burner flame or a slow closing gas valve 50A50 or HSI 1 1 INTEGRATED IGNITION CONTROL DIAGNOSTIC SIGNAL CHART FOR CORRECTIVE ACTION REFER TO Internal Control Failure System Lockout Pressure Switch Stuck Closed Pressure Switch Stuck Open Open Limit Control Open Rollout Control Continuous Flashing Flame Sensed No Call For Heat 89 SYSTEM OPERATION NORMAL SEQUENCE OF OPERATION 80 or 90 Models with White Rodgers 50A55 50T55 or HSI 2 Integrated Ignition Control Power Up The normal power up sequence is as follows 115 VAC power applied to furnace Integrated control module performs internal checks Integrated control module flashes LED one time D Integrated control module monitors safety circuits con tinuously 5 Furnace awaits call from thermostat Heating Mode The normal operational sequence in heating mode is as fol lows 1 Rand W thermostat contacts close initiating a call for heat Integrate
85. furnace featuring integrated electronic ignition control silicon carbide mini ignitor electrodepositioned steel cabinet and 409 stainless steel tubular heat exchanger and stainless steel recouperative coil Gas Furnace Counterflow Horizontal Condensing A Air Command 90 Furnace A First Design Series X NOx Certified 40 9096 furnace featuring integrated electronic ignition control silicon carbide mini ignitor electrodepositioned steel cabinet and 409 stainless steel tubular heat exchanger and stainless steel recouperative coil Gas Furnace Counterflow Horizontal Condensing Air Command 90 Furnace A First Design Series X NOx Certified 40 9096 furnace featuring integrated electronic ignition control silicon carbide mini ignitor electrodepositioned steel cabinet and 409 stainless steel tubular heat exchanger and stainless steel recouperative coil electrical junction box relocation from blower compartment to the burner compartment and incorporation of coarser threaded thumb screw and U clips instead of clinched inserts for engagement Gas Furnace Counterflow Horizontal Condensing A Air Command 90 Furnace Second Design Series X NOx Certified 40 9096 furnace featuring integrated electronic ignition control silicon nitride ignitor electrodepositioned steel cabinet and 409 stainless steel tubular heat exchanger and stainless steel recouperative coil electrical junction box relocation from blower compartment to the burner compartm
86. furnace operation Remember that dirty filters are the most common cause of inadequate heating or cooling performance Disconnect ALL POWER BEFORE SERVICING Maintenance Improper filter maintenance is the most common cause of inadequate heating or cooling performance Filters should be cleaned permanent or replaced disposable every two months or as required It is the owner s responsibility to keep air filters clean When replacing a filter it must be replaced with a filter of the same type and size Filter Removal Depending on the installation differing filter arrangements can be applied Filters can be installed in the central return register the bottom of the blower compartment upflow only a side panel external filter rack kit upflow only or the ductwork above a counterflow furnace A media air filter or electronic air cleaner can be used as an alternate filter The filter sizes given in the Product Design section of this manual or the product Specification Sheet must be followed to en sure proper unit performance Refer to the following informa tion for removal and installation of filters Upright Upflow Filter Removal To remove an internal filter from the bottom of the blower compartment 1 Setthe thermostat to the OFF position or turn OFF elec trical power to furnace 2 Remove blower compartment door 3 Push back and up on the wire filter retainer to release it from under the front lip of the furnace
87. gaz de l appereil et appeler un technicien qualifi ou le fourrnisseur de gaz 2 Turn off all elect 3 Push the gas co Do not force 4 Replace control 1 Set the thermostat to lowest setting if service is to be performed 1 power to the appliance 2 ntrol lever to OFF Position 3 access panel 4 TURN OFF GAS APPLIANCE POUR COUPER L ADMISSION E DE GAZ DE L APPAREIL R gler le thermostat la temp rature la plus basse Couper l alimentation lectrique de l appareil s il faut proc der des op rations d entretien Pousse le levier du contr le du gaz OFF ARRET position Ne pas forcer Remettre en place le panneau d acc s 11072710 25 ACCESSORIES Model Number HAC1PS01 HAC1PS02 1 503 1 504 1 505 1 506 HAC1PS07 HAC1PS08 HAC1PS09 HAC1PS10 1 513 1 514 07 CVK6 CVK7 Description Adjustable Subbase Common Vent Kit Common Vent Kit Common Vent Kit Electronic Air Cleaner External Filter Rack Furnace Twinning Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Swit
88. in this manual or the installations instructions for further details Setthe 90 furnace on a level floor to enable proper condensate drainage If the floor becomes wet or damp at times place the furnace above the floor on a con crete base sized approximately 1 1 2 larger than the base of the furnace Refer to the Horizontal Applica tions and Considerations section in this manual or the installation instructions for leveling of horizontal furnaces e Ensure upflow or horizontal furnaces are not installed directly on carpeting or any other combustible mate rial The only combustible material allowed is wood A special accessory subbase must be used for up right counterflow unit installations over any combus tible material including wood Refer to subbase in structions for installation details NOTE A subbase will not be required if an air conditioning coil is located beneath the furnace between the supply air opening and the combustible floor e Exposure to contaminated combustion air will result in safety and performance related problems Do not install the furnace where the combustion air is ex posed to the following substances chlorinated waxes or cleaners chlorine based swimming pool chemicals water softening chemicals deicing salts or chemicals carbon tetrachloride halogen type refrigerants cleaning solutions such as perchloroethylene printing inks paint removers varnishes hydrochloric acid c
89. instructions To Turn Off Gas To Appliance and call your safety information above on he burner by hand a LEVIER A GAZ MANUEL EN POS don t smell 1 GAS INLET 7 8 10 DU GAZ not operate Z MANUAL GAS LEVER SHOWN Skoas IN ON POSITION lt Lisez les instructions de s curit sur la portion sup rieure de cette tiquette R gler le thermostat la temp rature la plus basse Couper l alimentation lectrique de l appareil Cet appareil m nager tant dot d un syst me d allumage automatique ne pas essayer allumer le br leur manuellement Pousse le levier du contr le du gaz OFF ARRET position Attendre cinq 5 minutes pour laisser echapper tout le gaz Renifler tout autour de l appareil y compris pr s du plancher pour d celer une odeur de gaz Si c est le cas ARRETER Passer l tape B des instructions de s curiti sur la portion sup rieure de cette tiquette S il n y a pas d odeur de gaz passer l tape suivant Pousse le levier du contr le du gaz ON MARCHE position Remettre en place le panneau d acc s Mettre l appareil sous tension R gler le thermostat la temp rature desir e Si l appareil ne se met pas en marche suiyre les instructions intitul es Comment coupler l admission de
90. junction box located in side the burner compartment on 8096 furnaces and inside the blower compartment on 90 furnaces To make electri cal connections through the opposite side of the furnace the junction box must be relocated to the other side of the burner compartment on 80 furnaces and to the other side of the blower compartment on 90 furnaces prior to making electrical connections refer to the following figures WARNING EpcEs OF SHEET METAL HOLES MAY BE SHARP Use GLOVES AS A PRE CAUTION WHEN REMOVING HOLE PLUGS 2 A INCTION DE ALTERNATE JUNCTION BOX LOCATION JUNCTION BOX BN LOCATION STANDARD ALTERNATE JUNCTION BOX JUNCTION BOX LOCATION LOCATION b 9096 Furnace Junction Box Relocation 70 115 VOLT LINE CONNECTION OF ACCESSORIES HUMIDIFIER AND ELECTRONIC AIR CLEANER warnine HIGH VOLTAGE Disconnect ALL POWER BEFORE SERVICING OR CHANGING ANY ELECTRICAL WIRING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH All 8096 amp 90 furnaces except the 80 GUIB amp GCIB model furnaces have an integrated ignition control that is equipped with line voltage accessory terminals for control ling power to an optional field supplied humidifier and or elec tronic air cleaner Accessory Load Specification
91. local codes or in their absence with the latest edition of The National Electric Code ANSI NFPA 70 and or The Canadian Electric Code CSA C22 1 Use a separate fused branch electrical circuit containing properly sized wire and fuse or circuit breaker The fuse or circuit breaker must be sized in accordance with the maxi mum overcurrent protection specified on the unit rating plate An electrical disconnect must be provided at the furnace location 69 PRODUCT DESIGN NOTE Line polarity must be observed when making field connections 90 FURNACE UPRIGHT UPFLOW INSTALLATIONS THE DRAIN TRAP MUST BE MOUNTED ON THE OPPOSITE SIDE OF THE UNIT FROM THE JUNCTION BOX THIS WILL REDUCE THE RISK OF WATER REACHING THE JUNCTION BOX IN THE EVENT OF A BLOCKED DRAIN CONDITION NOTE Wire routing must not interfere with circulator blower operation filter removal or routine maintenance To AVOID THE RISK OF INJURY ELECTRICAL SHOCK OR DEATH THE FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN THEIR ABSENCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE Connect hot neutral and ground wires as shown the wir ing diagram located on the unit s blower door Line polarity must be observed when making field connections Line volt age connections can be made through either the right or left side panel The 80 and 90 furnaces are shipped configured for a left side electrical connection with the
92. models GUIA GUIB GUIC GUID GCIA GCIB and GCIC These kits are required when installing Amana Air Command 80 SSE and SV furnaces above their maximum rated altitude These kits contain propane gas orifices The orifices in the kit have been selected as a result of testing with the American Gas Association They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installation instructions of the kit High Altitude Propane Gas Conversion Kit For use with Amana furnace models GUCA and GCCA This kit is required when installing Amana Air Command 90 SSE furnaces above their maximum rated altitude This kit HALP10 P1129112F contains propane gas orifices The orifices in the kit have been selected as a result of testing with the American Gas Association They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown 5 09 P1129105F P1129111F in the installation instructions of the kit High Altitude Propane Gas Conversion Kit For use with Amana furnace models GUVA This kit is required when installing Amana Air Command 95 SSE furnaces above their maximum rated altitude These kits contain HALP11 P1129113F propane gas orifices The orifices in the kit have been selected as a result of testing with the American Gas Association They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installation instructi
93. pipe and 4 9 16 minimum for 3 pipe PRODUCT DESIGN PROPER VENT FLUE AND COMBUSTION AIR PIPING PRACTICES 90 FURNACES ONL Y Adhere to these instructions to ensure safe and proper fur nace performance The length diameter and number of el bows of the vent flue pipe and combustion air pipe when applicable affects the performance of the furnace and must be carefully sized All piping must be installed in accordance with local codes and these instructions Piping must be adequately secured and supported to pro hibit sagging joint separation and or detachment from the furnace Horizontal runs of vent flue piping must be supported every three feet and must maintain a 1 4 inch per foot down ward slope back towards the furnace to properly return condensate to the furnace s drain system Allowances should be made for minor expansion and contraction due to tem perature variations For this reason particular care must be taken to secure piping when a long run is followed by a short offset of less than 40 inches Precautions should be taken to prevent condensate from freezing inside the vent flue pipe and or at the vent flue pipe termination All vent flue piping exposed to freezing tempera tures below 35 F for extended periods of time must be insu lated with 1 2 thick closed cell foam Also all vent flue pip ing exposed outdoors in excess of the terminations shown in this manual or in unheated areas must be insulated with 1
94. pue i ejejedo oj eoeuunJ suonduoseg 4 jo z 1 ees day payeloossy 882 19 0 pue 88Z LOINOS 40 Heyo 39Vd SNOIA3Hd NOY LHVHO 127 SYSTEM OPERATION OPERATING INSTRUCTIONS 1 Close the manual gas valve external to the furnace Turn off the electrical power supply to the furnace Set room thermostat to lowest possible setting Remove the door on the front of the furnace RON This furnace is equipped with an ignition device which automatically lights the burner Do not try to light burner by hand 6 Turn gas control valve clockwise to the Off po sition for either the Honeywell VR 8205 gas valve or the White Rodgers 36E35 36E36 and 36E96 gas valves The knob should turn easily Do not use excessive force For the Robertshaw 7222 gas valve push in and slide the valve lever on the left and side of the valve to the Off position and for the White Rodgers 36E22 36F22 36G22 and 36E54 gas valve slide the switch on top of the valve to the Off position Do not force 7 Waitfive 5 minutes to clear out any gas then smell for gas including near the floor 8 If you smell gas following the five 5 minute waiting pe riod in Step 7 follow the instructions on Pages 20 through 25 If you do not smell gas then turn the gas control
95. pue dn yeys uo OU 060 01 JO 2101 811 HEJS 1 UOM ING S4901 1010 ON peeds e qeueA 10 dn ueis jeuuou SI 51 117 23130118 WINNI 104 51615 JOJO Jo pasa 8 dn sejej oso 1010 N 5 1010 Bues 5900 1010 N jewiouqy yo swo dwAs 146 SERVICING urejp ejesuepuoo 5 80 jeuiqeo JO oui pejoedxeun eonpoud pue 3 LON LNV LHOdWI sjonp ui Syee pue ouo Jepun doo dup sesseureu eDueuy peoejdei jojuoo 10joui ULI jeu 5 juo eu 5 paads 991 uonipuoo 10 s Ag tet Aypeuonouny oye yoo Aay Ayoedeo 001 10 YOOUD M93H9 3HN1LSIONW 10 Ady eouis ejnpou
96. rated altitude This kit contains natural gas orifices The orifices in the kit have been selected as a result of testing with the American Gas Association They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installation instructions of the kit High Altitude Natural Gas Kit For use with Amana furnace models GUSAO070 X35 GUSA090 X40 GUSA090 X50 GUSA115 X50 GCVA090 X50 GCVA115 X50 These kits are P1210310F required when installing Amana Air Command 90 furnaces above their maximum rated altitude This kit contains natural gas orifices The orifices in the kit have been selected as a result of testing with the American Gas Association They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installation instructions of the kit High Altitude Pressure Switch Kit For use with Amana furnace models GUCA GCCA and P1210518F P1210520F GUVA This kit contains a high altitude pressure switch that must be used at altitudes above the rated altitudes because of reduced air density High Altitude Pressure Switch Kit For use with Amana furnace models GUSA070 X35 1210521 GUSAO090 X40 GUSA090 X50 GUSA115 X50 This kit contains high altitude pressure switch that must be used at altitudes above the rated altitudes because of reduced air density High Altitude Pressure Switch Kit For use with Amana furnace models GCVAO90 X50 HAPS31 P1210522F GCVA
97. regulator should be adjusted to give 11 water column with all other gas con suming appliances running The dissipation of the heat transferred to the heat exchanger is now controlled by the amount of air circulated over its surface The amount CFM of air circulated is governed by the exter nal static pressure in inches of water column of duct work cooling coil registers and etc applied externally to the unit versus the motor speed tap direct drive or pulley adjust ments of the motor and blower belt drive A properly operating unit must have the BTU input and CFM of air within the limits shown to prevent short cycling of the equipment As the external static pressure goes up the temperature rise will also increase Consult the proper tables for temperature rise limitation SERVICING 1 Million 100 Thousand 10 Thousand 1 Thousand CUBIC O FEET GAS RATE CUBIC FEET PER HOUR Size of Test Dial Size of Test Dial 1 2 1 2 5 1 2 1 2 5 cu ft cu ft cu ft cu ft cu ft 1 Revolution Revolution 19 180 56 720 1800 3 25 50 100 200 50 11 82 164 327 65 1636 37 1 37 195 45 160 300 60 1500 38 25 47 19 474 158 277 555 1385 185 462 14 54 129 267 514 1288 40 22 45 180 45 o 120 240 480 1200 a 176
98. replace any part of the control d clencher une explosion ou un incendie System and any gas control which has been underwater D Ne pas se servir de cet appareil s il a t plong dans l eau compl tement ou en partie Appeler un technicien qualifi pour inspecter l appareil et remplacer tout partie du syst me de contr le et toute commande qui ont t plong s dans l eau B INSTRUCTIONS L SE EN STOP Read the safety information above on ARRET RI Lisez les instructions de s curit sur this label la portion sup rieure de cette tiquette 2 Set the thermostat to lowest setting 2 R gler le thermostat a la temp rature la plus basse 3 Turn off all power to the appliance 3 Couper l alimentation lectrique de l appareil 4 This appliance is equipped with an ignition 4 cel appareil m nager tant dot d un syst me device which automatically lights the burner d allumage automatique ne pas essayer Do not try to light the burner by hand allumer le br leur manuellement T Turn the gas control knob clockwise to 5 Torner le robinet a gaz dans le sens des aigilles OFF Position Do not force d une montre en position OFF ARRET Wait five 5 minutes to clear out any gas Then 6 Attendre cing 5 minutes pour laisser echapper tout le smell for gas including near the floor If you gaz Renifler tout autour de l appareil y compris pr s du
99. selected Low Stage Heating speed tap Circulator blower will operate on selected High Stage Heating speed tap Circulator blower will operate on selected High Stage Cooling speed tap 5 second ON delay and 45 second OFF delay Circulator blower will operate at 6596 of selected High Stage Cooling speed tap Circulator blower will operate on selected High Stage Cooling speed tap 5 second ON delay and 45 second OFF delay Circulator blower will operate at 5696 of selected High Stage Cooling speed tap 75 PRODUCT DESIGN GENERAL HEATING CONTINUOUS FAN COOLING 76 GUIV CX DX amp GUVA AX Two Stage Variable Speed Furnace Thermostat Wiring Reference Chart Furnace Circulator Blower Operation Mode Thermostat Connection Connection Options During Call From Thermostat 24 Volts HOT 24 Volts COMMON Low Stage Connection For Two Stage Heating High Stage Connection For Two Stage Heating Connection For Single Stage Cooling Low Stage Connection For Two Stage Cooling High Stage Connection For Two Stage Cooling Continuous Fan Connection Any Application Contiuous Fan Connection HEAT W SINGLE STAGE COOLING ONLY Continuous Fan Connection HEAT ONLY NO COOLING From Room Thermostat From Room Thermostat From Room Thermostat From Room Thermostat From Room Thermostat From Room Thermostat From Room Thermostat From Room
100. space it must also be suspended from the floor joist or supported by a concrete pad Never install the furnace on the ground or allow itto be exposed to water The length of rod will depend on the application and the clearances necessary N CENTER ROD AND FURNACE N TO ALLOW FOR CIRCULATOR BLOWER REMOVAL ALTERNATE ASSURE FURNACE IS LEVEL FROM GAS PIPING END TO END ON 90 FURNACES MAKE SURE THE UNIT HAS A SLIGHT FORWARD TILT WITH THE FRONT OF THE FURNACE 0 3 4 y BELOW THE BACK OF THE FURNACE 3 8 DIAMETER X THREADED ROD 6 PLACES f HOLD DOWN NUTS SUPPORT NUTS CONDENSATE 2 GAS PIPING d DRAIN 2 x2 x1 8 ANGLE IRON 3 PLACES TILT OUTWARD TO ALLOW FOR DOOR AND CIRCULATOR BLOWER REMOVAL 2 POSITION AS CLOSE AS POSSIBLE TO BLOWER DECK TO ALLOW FOR CIRCULATOR BLOWER REMOVAL 90 Suspended Furnace Shown 8096 Furnace Similar EXISTING FURNACE REMOVAL NOTE When an existing furnace is removed from a venting System serving other appliances the venting system may be too large to properly vent the remaining attached appli ances The following vent testing procedure is reproduced from the American National Standard National Standard of Canada for Gas Fired Central Furnaces ANSI 721 47 1998 CAN CGA 2 3 M98 Section 1 23 1 The following steps shall be followed with each appliance connected to the venting system placed in operation while any other appliances
101. state If flame is sensed but lost after ten 10 seconds the control will recycle this series of three tries five 5 more times be fore locking out The diagnostic light code for this prob lem is one short flash followed by a longer pause The control can be reset and brought out of lockout mode by turning the thermostat off and then back on It can also be reset by turning off the electrical disconnect switch to the furnace for 30 seconds NOTE The control board will automatically reset one hour after lockout occurs If the furnace frequently has to be re set it means that a problem exists that should be corrected Refer to Troubleshooting Chart on the following pages for aid in determining the cause 3 Pressure Switch Stuck Closed If the control senses the pressure switch is closed when the induced draft blower is off it waits until the fault is corrected The di agnostic light code for this problem is two short flashes followed by a longer pause The probable cause is either a faulty pressure switch or wiring 4 Pressure Switch Stuck Open If after the induced draft blower is energized the pressure switch does not close the control will keep the induced draft blower on and wait for the switch to close The diagnostic light code for this problem is three short flashes followed by a pause The probable causes are either a blocked pinched or disconnected hose to the pressure switch faulty pres sure switch or loosse or misco
102. the Two Stage Relay Kit TSRKO1 for use with a single stage ther mostat These units have a thermostat jumper pin selector on the control board for selecting the use of either a single stage or two stage thermostat DEHUMIDISTATREQUIREMENTS A dehumidistat can be used in conjunction with either the two stage 80 or 90 furnaces with variable speed circula tor blowers to lower the humidity in the conditioned space The dehumidistat will improve dehumidification of the condi tioned air by prompting the furnace to reduce the speed of the circulator blower during operation in the cooling mode To be compatible with these furnaces a dehumidistat must operate on 24 VAC and utilize a switch which opens on humidity rise Refer to Electrical Connections 24 Volt Dehumidistat Wiring section in this manual or the installa tion instructions for correct installation procedure PRODUCT DESIGN THERMOSTAT AND DEHUMIDISTAT LOCATION In an area having good air circulation locate the thermostat and dehumidistat if applicable about five feet high on a vi bration free inside wall Do not install the thermostat or dehumidistat where it may be influenced by any of the fol lowing Drafts or dead spots behind doors in corners or un der cabinets Hotor cold air from registers e Radiant heat from the sun e Light fixtures or other appliances e Radiantheat from a fireplace e Concealed hot or cold water pipes or chimneys e Uncond
103. the chimney Fix 4 Next measure the size of the liner It may be possible to do this from the cleanout The liner must be at least as large as the minimum size established by the tables in National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition and in the National Standard of Canada CAN CGA B149 1 and CAN CGA B149 2 latest editions and amendments If the liner is too small or too large then the chimney must be relined Fix 4 Check 6 Dilution Air If gas fired appliances are to be vented into a clay tile liner a source of dilution air is required Dilution air cannot be obtained through Induced draft appliances Natural draft appliances with vent dampers Sufficient dilution air can ordinarily be obtained through the draft hood of a natural draft appliance only if the appliance s vent connector does not include a vent damper If dilution air will not be available the chimney must be re lined Fix 4 Check 7 Complete the Installation If Checks 1 through 6 have been satisfactory and the liner is an acceptable size as determined by the tables Na tional Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition and in the National Standard of Canada CAN CGA B149 1 and CAN CGA B149 2 latest editions and amendments then the clay tile liner can probably be used as a vent for the gas appliances However the installer must keep in mind the following factors which may render the tile liner unsuit able for use as a
104. the chimney walls must be covered at the top of the chimney by a weatherproof corrosion resistant flash ing The B vent should then be topped with a listed vent cap The listed vent cap will when installed per the manufacturer s instructions prevent problems due to rain birds or wind effects A B vent installed as described in this section is considered to be an enclosed vent system and the sizing tables in National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edi tion and in the National Standard of Canada CAN CGA B149 1 and CAN CGA B149 2 latest editions and amend ments may be used If a flexible liner is to be used it must be made of the proper materials most residential applications an aluminum liner should be acceptable fthe combustion air supplied to the furnace will be contaminated with compounds containing chlorine or fluorine a liner of AL294C stainless steel should be used Common sources of chlorine and fluorine com pounds include indoor swimming pools and chlorine bleaches paint strippers adhesives paints varnishes sealers waxes which are not yet dried and solvents used during construction and remodeling Various com mercial and industrial processes may also be sources of chlorine fluorine compounds Heavier gauge 300 and 400 series stainless steel lin ers were developed for use with oil or solid fuel appli ances They are not suitable for use with gas fired appliances Flexib
105. the ductwork above an upright counterflow installation 1 Turn off electrical power to furnace 2 Remove access door in ductwork above furnace 3 Remove filters 4 Remove blower compartment door Vacuum compart ment Replace blower compartment door Replace filters opposite of removal 6 Replace access door in ductwork 132 Horizontal Unit Filler Removal Filters in horizontal installations are located in the central return register INDUCED DRAFT AND CIRCULATION BLOWERS The bearings in the induced draft blower and circulator blower motors are permanently lubricated by the manufacturer No further lubrication is required Check motor windings for ac cumulation of dust which may cause overheating Clean as necessary CONDENSATE DRAINAGE SYSTEM QUALIFIED SERVICER ONLY The drain tubes standpipe and field supplied drain line must be checked annually and cleaned as often as necessary to ensure proper condensate drainage FLUE PASSAGES QUALIFIED SERVICER ONL Y At the start of each heating season inspect and if neces sary clean the furnace flue passages CLEANING FLUE PASSAGES QUALIFIED SERVICER ONLY 1 Turn OFF the electrical power and gas supply to the furnace 2 Disconnectthe gas line and remove the burner manifold assembly by removing the screws securing the assem bly to the partition panel 3 Disconnect the flue pipe system from the induced draft blower 4 Remove the induced draft blower a
106. the floor renifler tout autour de l appariel pour d celer WHAT TO DO IF YOU SMELL GAS une odeur de gaz Renifler pr s du plancher car certains gaz sont plus lourds que l air et Do not try to light any appliance peuvent s accumuler au niveau du so l Do not touch any electric switch do not use any phone in your building QUE FAIRE S IL Y A UNE ODEUR DE GAZ Immediately call your gas supplier from a neighbor s Ne pas tenter d allumer l appariel phone Follow the gas supplier s instructions Ne toucher aucun interrupteur lectrique If you cannot reach your gas supplier n utiliser aucun t l phone dans le b timent call the fire department Appeler imm diatement le fournisseur de gaz en employant le t l phone d n voisin Respecter la lettre les instructions du C Use only your hand to turn the gas control knob fournisseur de gaz Never use tools If the knob will not turn by Si personne ne r pond appeler le service des hand don t try to repair it call a qualified service incendies technician Force or attempted repair may result in a fire C Ne pousser ou tourner le robinet d admission du gaz or explosion qu la main ne jamais emploer d outil cet effet Si la manette reste coinc e ne pas tenter de la D Do not use this appliance if any part has been underwater r parer appeler un technicien qualifi Quiconque Immediately call a qualified service technician to inspect tente de forcer la manette o
107. the induced draft blower continuously with no further furnace operation The diagnostic flash code for this is a continuous flash The probable causes are either a shortto ground in flame sense circuit miswiring lingering burner flame or a slow closing gas valve 119 SYSTEM OPERATION NORMAL SEQUENCE OF OPERATION 90 Two Stage Variable Speed Models with White Rodgers 50V61 288 Integrated Ignition Control Power Up The normal power up sequence is as follows 1 115 VAC power applied to furnace 2 Integrated control module performs internal checks 3 Integrated control module flashes LED one time 4 Integrated control module monitors safety circuits con tinuously 5 Furnace awaits call from thermostat Heating Mode The normal operational sequence in heating mode is as fol lows 1 R and W1 or R and W1 and W2 thermostat contacts close initiating a call for heat Integrated control module performs safety circuit checks Induced draft blower is energized on high speed for a 10 second prepurge Humidifier terminals are energized with induced draft blower 4 Induced draft blower steps to low speed following prepurge Low stage pressure switch contacts are closed 5 gnitor warm up 20 seconds begins upon step to low speed and presence of closed low stage pressure switch contacts 6 After 20 second ignitor warm up period low stage gas valve is energized 4 second ignition trial delivering gas to burne
108. the right In this case use the standard flue and combustion air piping connections ALTERNATE ELECTRICAL AND GAS LINE CONNECTIONS The 80 amp 90 furnaces have provisions allowing for elec trical and gas line connections through either side panel In horizontal applications the connections can be made either through the top or bottom of the furnace DRAIN PAN 90 FURNACES ONLY A drain pan must be provided if the furnace is installed above a conditioned area The drain pan must cover the entire area under the furnace and air conditioning coil if applicable FREEZE PROTECTION 90 FURNACES ONL Y If the drain trap and drain line will be exposed to tempera tures near or below freezing adequate measures must be taken to prevent condensate from freezing NOTE The use of insulation and or heat tape is recommended Failure to provide proper condensate drainage can result in property damage 53 PRODUCT DESIGN Propane Gas and or High Altitude Installations PossiBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH MAY OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED THE APPROPRIATE KITS MUST BE APPLIED TO INSURE SAFE AND PROPER FURNACE OPERATION ALL CONVERSIONS MUST BE PERFORMED BY A QUALIFIED INSTALLER OR SERVICE AGENCY This furnace is shipped from the factory configured for natu ral gas at standard altitude Propane gas installations re quire an orifice change to compensate for the energy con tent difference betwe
109. vent e Extremely cold weather Long vent connectors e Masonry chimneys with no air gap between the liner and the bricks In practice this can be difficult to detect e Exterior chimneys The tables in National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition and in the National Standard of Canada CAN CGA B149 1 and CAN CGA B149 2 latest editions and amend ments assume interior chimneys If in the judgment of the local gas utility installer and or local codes one or more of the above factors is likely to present a problem the chimney must be relined Fix 4 Fix 1 Liner Termination Any cap or roof assembly used with a liner must be ap proved by the liner manufacturer for such use The liner and cap roof assembly must then terminate above the roof in accordance with the manufacturer s instructions In some cases a shorter extension above the roof may be possible with a liner than would be required with a masonry chimney For further information on relining see Fix 4 Fix 2 Change Venting Arrangements If the masonry chimney has more than one channel it may be possible to vent the gas appliances into one channel and vent the solid or liquid fuel appliance s into another channel s Do not vent an Air Command 80 inside of a metal liner with other appliances vented outside the liner Alternatively the homeowner may agree to discontinue use of the fireplace solid fuel appliance If so the tile liner
110. venting is observed during any of the above tests the common venting system must be corrected Corrections must be in accordance with the latest edition of the National Fuel Gas Code NFPA 54 ANSI Z223 1 and or CAN CGA B149 Installation Codes If resizing is required on any portion of the venting system use the appropriate table in Appendix G in the latest edition of the National Fuel Gas Code ANSI Z223 1 and or CAN CGA B149 Installation Codes THERMOSTAT REQUIREMENTS A single stage furnace requires a single stage thermostat while the two stage furnace requires a two stage thermostat for proper operation The single stage thermostat provides W1 for only one stage of heat while the two stage thermo stat provides W1 and a W2 terminals for control of low stage and high stage heat Refer to Electrical Connections 24 Volt Thermostat Wiring section in this manual or the installation instructions for correct installation procedure for these thermostats NOTE A single stage thermostat can be used with the two stage furnace models GUIS GCIS GUIV and GUVA AX if a Two Stage Relay Kit TSRKO01 is installed The TSRKO1 does not offer true thermostat driven two stage operation It does however provide a timed transition from low to high fire For complete details on the TSRKO 1 refer to installation instructions provided with the kit NOTE The GUVA BX and GUSA BX GUIS FX GCIS FX GUIV FX model furnaces do not require the use of
111. voisin Respecter la lettre les instructions du fournisseur de gaz Si personne ne r pond appeler le service des incendies Ne pousser ou tourner le levier d admission du gaz qu la main ne jamais emploer d outil cet effet Si la manette reste coinc e ne pas tenter de la r parer appeler un technicien qualifi Quiconque tente de forcer la manette ou de la reparer peut d clencher une explosion ou un incendie Ne pas se servir de cet appareil s il a t plong dans l eau compl tement ou en partie Appeler un technicien qualifi pour inspecter l appareil et remplacer tout partie du syst me de contr le et toute commande qui ont t plong s dans l eau STOP Read the this label Boo Do not try to light t Do not force on this label if you gas go to next ste to ON 9 Turn on all electric 11 If the appliance wil Service technician OPERATING INSTRUCTIONS Set the thermostat to lowest setting Turn off all power to the appliance This appliance is equipped with an ignition device which automatically lights the burner 5 Push the gas control lever to OFF Position 6 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you then smell gas STOP Follow B in the safety Information above 7 Push gas control lever 8 Replace access panel power to the appliance 10 Set thermostat to desired setting follow the
112. while the induced draft blower is energized to purge the heat exchanger The ignitor will next be energized and preheated for 20 seconds The gas valve will then be energized If flame is not sensed in seven 7 seconds the gas valve will be de energized and another purge will occur The control will cycle the gas valve a total of three 3 times before it determines it cannot establish measurable combustion and enters a locked state If flame is sensed but lost after ten 10 sec onds the control will recycle this series of three tries five 5 more times before locking out The diagnostic light code for this problem is one short flash followed by alonger pause The control can be reset and brought out of lockout mode by turning the thermostat off and then back on It can also be reset by turning off the elec trical disconnect switch to the furnace for 30 seconds NOTE The control board will automatically reset one hour after lockout occurs If the furnace frequently has to be re set it means that a problem exists that should be corrected Refer to Troubleshooting Chart on the following pages for aid in determining the cause 3 Pressure Switch Stuck Closed If the control senses the pressure switch is closed when the induced draft blower is off it waits until the fault is corrected The di agnostic light code for this problem is two short flashes followed by a longer pause The probable cause is either a faulty pressure switch or
113. will not ener gize using this method To energize the EAC terminals the G wire from the thermostat must be connected directly to the G terminal on the two stage integrated control module 3 Intwo stage heating only no cooling applications If G from the thermostat is connected to Y on the furnace two stage integrated control module then the Continuous Fan blower speed will be the same as the selected high stage cooling speed tap Depending on the heating input of the furnace and the ca pacity of the accompanying cooling system one continu ous fan speed may be preferable to another The lower the continuous fan speed the lower the electrical consumption When using an electronic air cleaner make sure the con tinuous fan speed s CFM is within the CFM range listed for the electronic air cleaner Refer to Fan Speed Charts in the furnace Technical Manual or the product Specification Sheet for proper blower speed pin selection 80 GUIV FX amp 90 GUVA BX CX Two Stage Variable Speed Furnaces 1 Continuous Fan Mode If G from the thermostat is connected to G on the furnace two stage integrated control module then the continuous fan blower speed will operate at 56 of se lected High Stage Cooling speed tap following a five 5 second delay The EAC Electronic Air Cleaner termi nals are now energized 2 Low Stage Heating Mode If W1 from the thermostat is connected to W1 on the Two Stage Integrated Control
114. 0 COLLE 336 480 Mimimum Filter Area Based on Heating Airflow Requirement NOTE The dashed areas indicate not used in this application 305 1 1 1 1 279 1 1 1 1 1 1 83 PRODUCT DESIGN Minimum Filter Requirement in Permanent Filters Airflow Requirements Nominal CFM CFM CFM CFM CFM CFM CFM 288 282 282 38 o 376 96 96 384 _ o4 480 p CCE Ce Ce me 192 zo 288 zem zw ze 3 oz 26 se we ove e 2 0 192 168 240 Mimimum Filter Area Based on Heating Airflow Requirement NOTE The dashed areas indicate not used in this application 84 PRODUCT DESIGN Minimum Filter Requirement in Disposable Filters Airflow Requirements Nominal 600 er 322 460 e 564 sea 58 62 sear 5647 672 8 1 752 752 7527 768 C U CA090 50 752 768 380 0 8115 50 CL 9407 9407 960 GUVA045 30 564 564 564 762 GUVAO70 40 __ 752 752 752 768 GUVA090 50 752 75 768 960 GUVA115 50 __ _ 940 940 940 960 GUSA070 35 376 384 480 56 poo 67 627 672 768 pee
115. 1 Improper gas pressure adjust to proper pressure See 5 18 CHECKING GAS PRESSURE 2 Improper burner positioning burners should be in locat ing slots level front to rear and left to right 3 Carry over lighter tube or cross lighter obstructed clean 4 Main burner orifice s deformed or out of alignment to burner replace 5 20 CHECKING FOR FLASHBACK Flashback will also cause burning in the burner venturi but is caused by the burning speed being greater than the gas air flow velocity coming from a burner port Flashback may occur at the moment of ignition after a burner heats up or when the burner turns off The latter is known as extinction pop Since the end results of flashback and delayed ignition can be the same burning in the burner venturi a definite attempt should be made to determine which has oc curred If flashback should occur check for the following 1 Improper gas pressure adjust to proper pressure See S 18 CHECKING GAS PRESSURE 2 Check burner for proper alignment and or replace burner 3 Improper orifice size check orifice for obstruction S 21 CHECKING DUCT STATIC The maximum and minimum allowable external static pressures are found in the specification section These tables also show the amount of air being delivered at a given static by a given motor speed or pulley adjustment The furnace motor cannot deliver proper air quantities CFM against statics other than thos
116. 1 1 1 1 2 3 d d DID m Ex 242202222220 D 5 BS KS 21 B BS 5 xx _ 10301111 setae x x x x 1 4 aar x MI x x o NNNM aar 01011 aard wo B BS 5 m 5 gt ala Ww m GUIA070A40 CIA140A50 1 140 50 xix pod p lola X Available for this model 1 7 501 to 9 500 ft 3 0 to 7 500 ft Not used in this application 2 7 501 to 11 000 ft 4 9 501 to 11 000 ft Note All installations above 7 500 ft require a pressure switch change Note For installations in Canada the Amana 80 furnace is certified only to 4 500 ft 26 ACCESSORIES Model Number HAC1PS01 HAC1PS02 HAC1PS03 HAC1PS04 HAC1PS05 HAC1PS06 HAC1PS07 HAC1PS08 HAC1PS09 HAC1PS10 HAC1PS13 HAC1PS14 9 07 Description Adjustable Subbase Common Vent Kit Common Vent Kit Common Vent Kit Common Vent Kit Electronic Air Cleaner External Filter Rack Furnace Twinning Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressur
117. 1 3 8 28 3 8 5 3 4 18 7 8 1 1 21 1 20 25 ACG2424 3 25 3 8 28 3 8 3 3 4 18 7 8 1 1 21 1 24 24 ACG2424 6 25 3 8 28 3 8 5 3 4 18 7 8 1 121 1 24 24 dimensions given in inches Short base handles 1 amp 2 filters Height 3 3 4 Tall base handles 1 2 amp 4 filters Height 5 3 4 36 ACCESSORIES HORIZONTAL FILTER HOUSING MODEL HRB HORIZONTAL FILTER HOUSING DIMENSIONS HR20 amp HR25 Model Filter HORIZONTAL FILTER HOUSING Number A B D Size Used on Models 80 Upflow Furnaces dimensions given in inches Uses Standard Filter Sizes 1 2 or 4 MEDIA AIR CLEANER MAC1 SPECIFICATIONS CAPACITY 600 2000CFM MEDIA SERVICE LIFE 12 MO NOMINAL DIMENSION lt gt a INCHES W C MEDIA AIR CLEANER Used On Models 80 Furnaces Y 90 Furnaces 37 ACCESSORIES ELECTRONIC AIR CLEANER 5 SPECIFICATIONS 2000 3400 oge HI MAX PRESSURE 13 in w g 2000 iue POWER 48 watts maximum B 3 1 2 i ELECTRICAL INPUT 120 V 60 HZ 1 PH ELECTRICAL 3 2 MA 6200 DIMENSIONS All dimensions are in inches 2 1 8 C EAC5 ELECTRONIC AIR CLEANER gt lt gt lt D 90 Furnaces DEHUMIDISTAT DEHUM1 ET DEHUMIDISTAT SPECIFICATIONS b S Model Number 2274W 21 Differential 5
118. 1 34 64 0 5 30 60 90 120 190 Initial Call For High Heat Subsequent Call To Low Heat Call Change to Low Heat f 30 Seconds After Call Change to Low Heat 6 27 31 34 64 0 5 30 60 90 120 190 SYSTEM OPERATION COOLING TIMING CHART FOR WHITE RODGERS 50 51 215 TWO STAGE INTEGRATED IGNITION CONTROL OPERATION Indoor Fan ON OFF Outdoor Fan and ON Compressor OFF Thermostat ON OFF Seconds 0 5 0 45 103 SYSTEM OPERATION ABNORMAL OPERATION 80 Two Stage Models with White Rodgers 50A51 215 Integrated Ignition Control The following presents the probable causes of questionable furnace operation and how to fix them Look through the observation window in the blower access door and make a note of the number of flashes in sequence between pauses Next refer to the Diagnostic Signal Chart below for inter pretation of the LED signals and to the information in this section for a description of the problem 1 Internal Lockout If during a self test cycle the control determines an internal fault the control stops and the diagnostic light will light continuously The control should be replaced 2 External Lockout flame was not sensed during the first 7 seconds after the gas valve was energized the control turns off the gas There will be a 120 second delay with the induced draft blower motor energized to purge the heat exchanger The ignitor will then be ener
119. 10 sieuung eurejj enp uedo 5 seuse Seuse T 10 95001 Si 037 1991109 pue 19MOJQ pelle 10 peeds Gay Aiessoseu eoejdai 10 peeds 1981109 peeds pue Jemo q 107e n9119 10 101 u09 eoueuuojed pue peeds 1940 4 10 yOOYD esu 10 19945 500 pexoojq uedo si yeda aoud 440 uin Homs uomneJedo asoeuny 10 UE 10 pue S13 1940 5 ou suns 1 4 5 4109UI 10 95007 sSeuse 619 YO n 1 pred 1981109 pue Sioejuoo si q3 10 195 5 eunsseud Gay JedoJd
120. 115 X50 This kit contains a high altitude pressure switch that must be used at altitudes above the rated altitudes because of reduced air density High Altitude Two Stage Conversion Kit For use with Amana furnace models GUIS GCIS and GUIV These kits are required when installing Amana Air Command 80 SSE II furnaces above their maximum rated altitude These kits contain a pressure switch assembly and natural gas 501 09 P1220406F P1220414F orifices The orifices in the kit have been selected as a result of testing with the American Gas Association They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installation instructions of the kit A different pressure switch must be used at altitudes above the rated altitudes because of reduced air density Horizontal Concentric Vent Kit For use with Amana furnace models GUCA GCCA GUVA and GUSA This kit is designed to allow terminations of a direct vent furnace to be concentrically 1211401 vented through a wall This kit allows a single penetration to support terminations for both the vent flue and the combustion air intake pipe Horizontal concentric vent kits can be installed through walls having a minimum thickness of 3 4 inch to a maximum of 13 3 4 inches thickness This kit is not certified for and must not be applied to any furnace not listed above LP Gas Low Pressure Kit Designed for application on Amana s gas fired fur
121. 120 or 180 seconds Elec tronic air cleaner terminals are de energized 13 Furnace awaits next call from thermostat Cooling Mode The normal operational sequence in cooling mode is as fol lows 1 R and Y thermostat contacts close initiating a call for cool 2 Integrated control module performs safety circuit checks 3 Outdoor fan and compressor are energized 4 Circulator blower is energized on cool speed following a fixed five second on delay Electronic air cleaner termi nals are energized with circulator blower 5 Furnace circulator blower and outdoor cooling unit run integrated control module monitors safety circuits con tinuously 6 Rand Y thermostat contacts open completing the call for cool 7 Outdoor fan and compressor are de energized 8 Circulator blower is de energized following a fixed forty five second cool off delay period Electronic air cleaner terminals are de energized 9 Furnace awaits next call from thermostat Fan Only Mode The normal operational sequence in fan only mode is as follows 1 R and G thermostat contacts close initiating a call for fan Integrated control module performs safety circuit checks 3 Circulator blower is energized on cool speed Electronic air cleaner terminals are energized 4 Circulator blower runs integrated control module moni tors safety circuits continuously 5 Rand thermostat contacts open completing the call for fan 6 Circul
122. 15 000 Standard 2 26 23 20 Not Recommended Alternate 2 7 10 Not Recommended 115 000 Standard 3 88 87 80 76 72 68 64 Alternate 3 74 70 66 62 58 54 50 Unit Input Termination 5 Number of Elbows 9 Style inch 2131415167 8 45 000 Standard 2 68 65 62 59 56 53 50 Alternate 2 55 52 49 46 43 40 37 70 000 Standard 2 68 65 62 59 56 53 50 Alternate 2 5 52 49 46 43 40 37 90 000 Standard 2 55 52 49 46 43 40 37 Alternate 2 42 39 36 33 30 27 24 115 000 Standard 2 26 23 20 Not Recommended 2 7 10 Not Recommended 115 000 Standard 3 88 87 80 76 72 68 64 Alternate 3 74 70 66 62 58 54 50 GUVA Model Furnaces Direct Vent Dual Pipe Venting Table Maximum Allowable Length of Vent Flue Pipe amp Combustion Air Intake Pipe ft Pipe Unit Input Termination Number of Elbows 0 9 9 Btu Style Size inch 1 2 3 4 5 6 7 8 45 000 Standard 2 71 68 65 62 59 56 53 50 Alternate 2 58 55 52 49 46 43 40 37 Standard 2 49 46 43 40 37 34 31 28 70 000 3 71 68 65 62 59 56 53 50 2 36 33 30 27 24 21 18 15 Alternate 3 57 54 51 48 45 42 39 36 90 000 Standard 3 71 68 65 62 59 56 53 50 Alternate 3 57 54 51 48
123. 2 Turn off all electric power to the appliance 2 Couper l alimentation lectrique de l appareil s il if service is to be performed faut proc der des op rations d entretien Turn the gas control lever clockwise 4 to 3 Torner le levier a gaz dans le sens des aigilles OFF Position Do not force d une montre 4 en position OFF ARRET 4 Replace control access panel Ne pas forcer 4 Remettre en place le panneau d acces 11072706 22 OPERATING INSTRUCTIONS mm FOR YOUR SAFETY READ BEFORE OPERATING LIRE AVANT DE METTRE ENMARGHELRE WARNING If you do not follow these instructions explosion may result causing property damage ersonal injury or loss of life AVERTISSEMENT Quiconque ne respecte pas la lettre les instructions dans le pr sent manuel risque de d clecher un incendie ou une explosion A This appliance does not have a pilot It is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire de
124. 2 thick closed cell foam such as Armaflex or Insultube Inspect piping for leaks prior to installing insulation TERMINATION LOCATIONS 90 6 FURNACES ONL Y NOTES Referto Location Requirements and Considerations section of this manual or the installation instructions for com bustion air contaminant restrictions The following bullets and diagram describe the restrictions concerning the appropriate location of vent flue pipe and com bustion air intake pipe when applicable terminations Re fer to Non Direct Vent Single Pipe Piping and Direct Vent Dual Pipe Piping sections located in this manual or the installation instructions for specific details on termination construction All terminations must be located at least 12 inches above ground level or the anticipated snow level Ventterminations must terminate at least 3 feet above any forced air inlet located within 10 feet NOTE This provision does not apply to the combus tion air intake termination of a direct vent application Theventtermination of a non direct vent application must terminate at least 4 feet below 4 feet horizon tally from or 1 foot above any door window or gravity air inlet into any building Theventtermination of a direct vent application must terminate at least 12 inches from any opening through which flue gases may enter a building door window or gravity air inlet e Theventtermination of vent pipe run vertically through a
125. 208F 140 80 two stage variable speed furnace featuring integrated electronic ignition control silicon carbide ignitor two stage gas valve two speed induced draft blower prepainted textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft Variable Speed 2 Stage Air Command 80 SSE II Q Furnace C Third Design Series X NOx Certified 40 80 two stage variable speed furnace featuring integrated electronic ignition GUIV CX P1230308F P1230308F control silicon carbide ignitor two stage gas valve two speed induced draft blower variable spped circulator blower electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Change from embossed bottom knock out to perforated bottom knock out and addition of internal side filter retention Gas Furnace Upflow Horizontal Induced Draft Variable Speed 2 Stage Air P1246903F Command 80 SSE II Q Furnace D Fourth Design Series X NOx Certified GUIV FX P1246905F 40 80 two stage variable speed furnace featuring integrated electronic ignition P1246907F control silicon nitride ignitor two stage gas valve two speed induced draft blower variable speed circualtor blower electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger 11 PRODUCT IDENTIFICATION This section will identify the models covered and the changes per each model group from one rele
126. 36 wire and the negative side of the meter is to sensor terminal 153 SERVICING WARNING LINE VOLTAGE NOW PRESENT 4 Place the unit into a heating cycle 5 As soon as flame is established a micro amp reading should be evident once proof of flame micro amp read ing is established the hot surface ignitor will be de energized 6 The Integrated Ignition controls will have 1 to 4 micro amps If the micro amp reading is less than the mini mum specified check for high resistance wiring con nections sensor to burner gap dirty flame sensor or poor grounding 7 If absolutely no reading check for continuity on all com ponents and if good replace ignition control module NOTE Contaminated fuel or combustion air can create a nearly invisible coating on the flame sensor This coating works as an insulator causing a loss in the flame sense signal If this situation occurs the flame sensor must be cleaned with steel wool S 14A CHECKING RADIANT SENSE FLAME SENSOR The Radiant Sensor is a single pole double throw switch that is activated by a combination of the heat radiating from the burner flame and the reflected heat from the ignitor Once the pressure switch contacts close power is supplied through the N C contacts of the Radiant Sensor to the gas valves terminal 4 GN 7 wire When the Radiant Sensor senses sufficient heat from the ignitor the sensor will switch to the N O position suppling 24V to the ga
127. 5 Tons Determine the proper air flow for the cooling system Most cooling systems are designed to work with air flows between 350 and 450 CFM per ton Most manufacturers recommend an air flow of about 400 CFM per ton EXAMPLE 2 5 tons X 400 CFM per ton 1000 CFM The cooling system manufacturer s instructions must be checked for required air flow Any electronic air cleaners or other devices may require specific air flows consult installation instructions of those devices for requirements Knowing the furnace model locate the high stage cool ing air flow charts in the specification sheet Look up the cooling air flow determined in step 2 and find the re quired cooling speed and adjustment setting EXAMPLE A GUVA070AX40 furnace installed with a 2 5 ton air conditioning system The air flow needed is 1000 CFM Looking at the cooling speed chart for GUVAO070AXAO find the air flow closest to 1000 A cooling airflow of 990 CFM may be attained by setting the cooling speed to and the adjustment to mi nus Locate the circulator blower interface board on the con trol panel in the blower compartment On the circulator blower interface board find the COOL speed tap se lector pin and move it to the proper speed Next find the ADJUST tap selector pin and move it to the proper adjust level Verify CFM by counting blinks of the RED CFM LED Refer to the following figure CFM LED RED CIRCULATOR BLOWEI
128. A First Design Series X NOx Certified 40 90 furnace featuring integrated electronic ignition control insulated blower compartment 4 speed blower motor silicon carbide mini GULA AX P1245801F P1245806F jignitor electrodepositioned steel cabinet and aluminized steel tubular heat exchanger and stainless steel recouperative coil GULA units are shipped non direct vent but can be installed as direct vent by adding the intake air coupling and appropriate field supplied pipe Gas Furnace Upflow Horizontal LDistinction 9296 A Standard Line Furnace C Third Design Series X NOx Certified 40 9096 furnace featuring integrated electronic ignition P1253101F control insulated blower compartment 4 speed blower motor silicon carbide mini pisos Wek ignitor 3161 Header Plates electrodepositioned steel cabinet and aluminized steel SUAE P1253103F P1253104F tubular heat exchanger and stainless steel recouperative coil Select models utilize a 2 P1253105F row secondary recouperative coil ONLY the next to the manufacturing P number P1253106F indicates the furnaces using a 2 row secondary recouperative coil GULA units are shipped non direct vent but can be installed as direct vent by adding the intake air coupling and appropriate field supplied pipe 14 PRODUCT IDENTIFICATION This section will identify the models covered and the changes per each model group from one release to the next Model Manufacturing Descri
129. AC power applied to furnace Integrated control module performs internal checks Integrated control module flashes LED one time gt D Integrated control module monitors safety circuits con tinuously 5 Furnace awaits call from thermostat Heating Mode The normal operational sequence in heating mode is as fol lows 1 Rand W thermostat contacts close initiating a call for heat Integrated control module performs safety circuit checks 3 Induced draft blower is energized causing pressure switch contacts to close Humidifier terminals are energized with induced draft blower 4 Ignitor warm up begins upon close of pressure switch contacts 5 Gas valve opens at end of ignitor warm up period deliv ering gas to burners and establishing flame 6 Integrated control module monitors flame presence Gas valve will remain open only if flame is sensed 7 Circulator blower is energized on heat speed following a fixed thirty second blower on delay Electronic air cleaner terminals are energized with circulator blower 8 Furnace runs integrated control module monitors safety circuits continuously 9 Rand W thermostat contacts open completing the call for heat 10 Gas valve closes extinguishing flame 11 Induced draft blower is de energized following a fifteen second post purge Humidifier terminals are de energized 12 Circulator blower is de energized following a selectable heat off delay period 60 90
130. AGE INTEGRATED IGNITION CONTROL OPERATION Air Circulator Blower Gas Valve Ignitor Pressure Switches Induced Draft Blower Thermostat Air Circulator Blower Gas Valve Ignitor Pressure Switches Induced Draft Blower Thermostat High Low Off On Off On Off PS2 Closed PS1 Closed Open High Low Off High Low Off GUIS GCIS Example 2 Continuous Call For High Stage Heat Only High Low Off High Low Off On Off PS2 Closed PS1 Closed Open High Low Off High Low Off GUIS GCIS Example 1 Continuous Call For Low Stage Heat Only 0 10 27 31 34 27 31 34 64 64 30 30 60 90 120 180 60 90 120 180 101 SYSTEM OPERATION Air Circulator Blower Gas Valve Ignitor Pressure Switches Induced Draft Blower Thermostat Air Circulator Blower Gas Valve Ignitor Pressure Switches Induced Draft Blower Thermostat 102 HEATING TIMING CHARTS FOR WHITE RODGERS 50A51 215 TWO STAGE INTEGRATED IGNITION CONTROL OPERATION GUIS GCIS Example 3 Initial Call For Low Heat Change In Call To High Heat High Low Off On Off On Off PS2 Closed PS1 Closed Open High Low Off High Low Off GUIS GCIS Example 4 High Low High Low Off On Off PS2 Closed PS1 Closed Open High Low Off High Low Off 10 10 Call Change to High Heat 27 3
131. Alternate Horizontal Vent Termination Dual Pipe Vent Intake Terminations for Installation of Multiple Direct Vent Furnaces 90 Furnaces Only If more than one direct vent furnace is to be installed verti cally through a common roof top maintain the same mini mum clearances between the exhaust vent and air intake terminations of adjacent units as with the exhaust vent and air intake terminations of a single unit 61 PRODUCT DESIGN If more than one direct vent furnace is to be installed hori zontally through a common side wall use the alternate ter mination style and maintain the clearances as shown in the following horizontal venting of multiple units Always termi nate all exhaust vent outlets at the same elevations and always terminate all air intakes at the same elevation 90 Furnace Horizontal Venting of Multiple Units Dual Pipe CONCENTRIC VENT TERMINA TION 90 FURNACES ONLY The Concentric Vent Kits HCVK and VCVK are designed to allow the terminations of a direct vent furnace to be con centrically vented through a wall HCVK or roof VCVK These kits allow a single penetration to support termina tions for both the vent flue pipe and the combustion air in take pipe HCVK is designed for horizontal through the wall terminations while the VCVK is designed for vertical through the roof terminations The appropriate kit must be used for a given termination placement horizontal or vertical Concentric Ve
132. Buum pejoeuuoosiu JO S007 uoneJedo eoeuunj eoejda 10 peeds 1921109 JOMO Q ou eoueuuoped pue paads Jamojq 044 10 10 paeds 1ewo q Sun 40 e n21I uononujsqo 10 eq 10 pue 1810 peuonipuoo juerornsu 10 uedo si 10 95007 sayse 4 Seuse 3914 Buum 1991109 pue sjoejuoo si 037 onsouBeip 19ejuoo pue 195 1edoud 10 ulod 498 ensseid uoneJedo Uuejs s YOOYD pue peonpur uejs s pue 1edoud eBexoo q 10 jeu ureJp edid eju pexoolg jou YMS eoeuunj IYUN uoiiMs
133. C Power Connector ps 1 and 2 will be connected applications only POWER CONNECTOR 1 2 HP MOTORS Motor Viewed from Plug End inductor AC Line Hot Connection AC Line Neutral Connection Gnd r 120VAC Power Connector je 1 and 2 will be connected applications only POWER CONNECTOR 3 4 amp 1 HP MOTORS 145 SERVICING 440 440 8189 10 0 e pueH Buiuedo Bunoeuuoosip Jaye 1019 440 19 10 0 010 Jaye redau aoud 440 pue jxeu uo eyg Buas peeds 1991109 1sn py suonouisei JONP 1291109 09 09 Je 0949 10 jeued seoq ADOYI 21NISION ul payeasun 9 H M A 0 10 10
134. CA DX amp 90 GUVA AX Two Stage Variable Speed Furnaces As a two stage furnace the furnace s integrated control mod ule and or circulator blower interface board provide termi nals for both W1 and W2 and Y1 and Y Y2 thermo stat connections This allows the furnace to support the fol lowing system applications Two Stage Heating Only Two Stage Heating with Single Stage Cooling and Two Stage Heating with Two Stage Cooling Refer to the following fig ures and also the table on the following page for proper con nections to the integrated control module and or circulator blower interface board Options applicable to the connec tion of Y and G from the thermostat are discussed in Circulator Blower Timings and Continuous Fan Operation section of this manual Two Stage Heating Thermostat NOTES 6 Indicate connection options Refer to Circulator Blower Timings and Gj Ga Speeds Cooling Operation and 8 Continuous Fan Operation Section for details concerning and Y connection options 62 69 69 9 9 9 09 Circulator Blower Interface Board Furnace Two Stage Integrated Control Module Furnace Two Stage Heating Only Application Two Stage Heating Single Stage Cooling i G NOTES Indicate connection options kerk 11 Ie ul Refer to Circulator Blower Timings G
135. CFM R to G to Y will cause the fan to come on at cooling speed and R to G to W will cause the fan to come on at heating speed If motor does not respond as noted ICM control unit is bad and should be replaced Replacing ICM Control Module Use the following steps to replace the control module for the GE variable speed indoor blower motor 1 You must have the correct replacement module The controls are factory programmed for specific operating modes Even though they look alike different modules may have completely different functionality Using the wrong control module voids all product warranties and may produce unexpected results 2 Remove all power from the unit being serviced Do not work on the motor with power applied Wait at least 5 minutes after disconnecting power from the equipment before opening the motor 148 3 Itis usually not necessary to remove the motor from the blower assembly However it is recommended that the whole blower assembly with the motor be removed Unplug the two cable connectors to the motor There are latches on each connector Do not pull on the wires The plugs remove easily when properly released 4 Observethe flat end of the motor control module casting and locate the two standard 14 hex head bolts Remove these bolts from the motor while holding the control mod ule Do not remove the two torx head screws 5 The control module is now free of the motor but still at tached by a plu
136. Changes include standardized blower decks access door blower door scroll wrap burner bracket Norton mini igniter and plug connect wiring harness The furnaces also feature an integrated electronic ignition control prepainted textured steel cabinet insulated blower compartment aluminized steel tubular heat exchanger along with the blower compartment door being sealed to minimize the amount of air leakage less then 196 air leakage and the blower compartment insulated with the same insulation as used in the 9096 furnace blower comparement Note The filter rails are not installed in the cabinet but are taped to the basepan for shipment PRODUCT IDENTIFICATION This section will identify the models covered and the changes per each model group from one release to the next Model GUCA AX GUCA AX GUCA CX GCCA AX GCCA AX GCCA AX GCCA BX Manufacturing P1219301F P1227501F P1228801F P1228901F P1239301F 1219306 1227506 1228806 1228906 1239306 1252601 P1252602F P1252603F P1252604F P1252605F P1252606F P1227601F P1232401F P1239401F P1241701F P1227606F P1232406F P1239406F P1241706F Description Gas Furnace Upflow Horizontal Condensing Air Command 90 Furnace First Design Series Certified 40 90 furnace featuring integrated electronic ignition control silicon carbide mini ignitor ele
137. D IGNITION CONTROL OPERATION On Off On Off 0 5 Time sec 0 SYSTEM OPERATION Abnormal Operation 90 Two Stage Variable Speed Models with White Rodgers 50V61 288 Ignition Control The following presents the probable causes of questionable furnace operation and how to fix them Look through the observation window in the blower access door and make a note of the number of flashes in sequence between pauses Next refer to the Troubleshooting Chart on the following page for an interpretation of the LED signals and to the infor mation in this section for a description of the problem 1 Internal Control Failure with Integrated Ignition Control If the control determines it has an internal fault it enters a locked out state and the diagnostic light will light continuously with no flashes The control should be replaced 2 System Lockout If a flame is not sensed during the first four 4 seconds after the gas valve is energized the control turns off the gas There will then be a 60 second delay while the induced draft blower is energized to purge the heat exchanger The ignitor will next be energized and preheated for 20 seconds The gas valve will then be energized If flame is not sensed in four 4 seconds the gas valve will be de energized and another purge will occur The control will cycle the gas valve a total of three 3 times before it determines it cannot establish mea surable combustion and enters a locked out
138. D WITH DRAFT HOOD EQUIPPED APPLIANCE THE POTENTIAL FOR CONDENSATION DAMAGE MAY STILL EXIST WITH EXTREMELY COLD CONDITIONS LONG VENT CONNECTORS EXTERIOR CHIMNEYS OR ANY COMBINATION OF THESE CONDITIONS THE RISK OF CONDENSATION DAMAGE IS BEST AVOIDED BY USING THE MASONRY CHIMNEY AS PATHWAY FOR PROPERLY SIZED METAL LINER OR METAL VENT PRODUCT DESIGN Crown Wash 7 Roof Line WN Clay Tile Size 8 x 8 x12 Each x 24 Length Clay Tile Size Generally 12 x 12 24 Length Attic Floor 1 2 to 1 Air Space Second Floor hroa First Floor Water Heater F A F Vent Vent Connector Connector Breech Natural Draft Water Heater Fan Assisted Forced Air Furnace Clean Out Basement Floor Typical Multiple Flue Clay Tile Chimney Checklist Summary This checklist serves as a summary of the items to be checked before venting an Air Command 80 furnace into a masonry chimney In addition we recommend that a quali fied serviceman use this checklist to perform a yearly in spection of the furnace venting system This checklist is only a summary For detailed information on each of the procedures mentioned see the paragraph referenced with each item This inspection is based upon a draft topical report Ma sonry Chimney Inspection and Relining issued by the Gas Research Institute While not yet finalized we believe this report represents the best information on this sub
139. EED TAPS MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH All 80 90 single stage and two stage furnaces ship at high speed for cooling and the speeds listed in the Specifi cation Sheet for heating These speeds should be adjusted by the installer to match the job requirements See Specifi cation Sheet or Technical Manual for details Connect the correct motor leads to the COOL LO HEAT HI HEAT and PARK terminals If high heating soeed equals cooling speed use the jumper wire provided All unused motor leads that are not connected to PARK terminals on the control must be taped to prevent shorts All 80 amp 90 Two Stage Variable Speed furnaces are shipped with heating speed set at B and cooling speed set at Use the following procedure to select the heating and cooling speed needed for your unit PRODUCT DESIGN To airflow quantity use the RED CFM LED on the circulator blower interface board on GUIV CA DX amp GUVA AX models or GREEN CFM LED adjacent the integrated control module fuse on GUVA BX CX models to verify air flow quantity The red or green CFM LED blinks once for each 100 CFM of airflow 1 Determine the tonnage of the cooling system installed with the furnace If the cooling capacity is in BTU hr di vide it by 12 000 to convert capacity to EXAMPLE Cooling Capacity of 30 000 BTU hr 30 000 12 000 2
140. FLOW COUNTERFLOW 9096 Furnace Vent Flue amp Combustion Air Standard Connections ALTERNATE FURNACE CONNECTIONS 90 FURNACES ONL Y If the standard locations are undesirable for a specific instal lation alternate side panel locations are available for both combustion air inlet and vent flue pipe connections These locations may be of particular benefit to upright upflow in stallations requiring additional access to an A coil or to hori zontal installations desiring vent flue and combustion air intake piping run vertically from the side of the cabinet NOTE Standard and alternate locations can be combined an installation may use the standard combustion air intake location but use the alternate vent flue location or vice versa if needed caution EDGES OF SHEET METAL HOLES MAY BE SHARP USE GLOVES PRECAUTION WHEN REMOVING HOLE PLUGS The alternate vent flue location is the large hole directly in line with the induced draft blower outlet Refer to the follow ing Alternate Vent Flue Location figure for details THE RUBBER ELBOW IS NOT DESIGNED TO SUPPORT A LOAD WHEN THE RUBBER ELBOW IS MOUNTED EXTERNALLY TO THE FURNACE CABINET EXTREME CARE MUST BE TAKEN TO ADEQUATELY SUPPORT FIELD SUPPLIED VENT FLUE PIPING 5 DAMAGE CAN RESULT IN LEAKS CAUSING BODILY INJURY OR DEATH DUE TO EXPOSURE TO FLUE GASES INCLUDING CARBON MONOXIDE For upright installations externally mount the rubber el bow to the vent
141. G THERMOSTAT WIRING AND ANTICIPATOR S 3A Thermostat and Wiring DISCONNECT ELECTRICAL POWER SUPPLY 1 Remove the blower compartment door to gain access to the thermostat low voltage wires located at the furnace integrated control module terminals 2 Remove the thermostat low voltage wires at the furnace control panel terminal board 3 Jumper terminals R to W W1 and W2 on the integrated ignition control With Power On and Door Interlock Switch closed LINE VOLTAGE NOW PRESENT 4 Induced Draft Motor must run and pull in pressure switch 5 Ifthe hot surface ignitor heats and the end of the this ignitor warm up period the gas valve opens and the burn ers ignite the trouble is in the thermostat or wiring 6 With power off check the continuity of the thermostat and wiring Repair or replace as necessary If checking the furnace in the air conditioning mode pro ceed as follows 7 With power off Jumper terminals R to Y Y1 or Y2 to G 8 Turnon the power 9 If the furnace blower motor starts and the condensing unit runs then the trouble is in the thermostat or wiring Repair or replace as necessary 10 After completing check and or repair of wiring and check and or replacement of thermostat reinstall blower com partment door 11 Turn on electrical power and verify proper unit operation S 3B Heating Anticipator The heating anticipator is a wire wound adjustable heater which is energized du
142. GCLA GUIE GUVA and GUSA models to line 2 neutral WH 33 wire on GUIA GCIA GUIC GCIC GUID GUIS GCIS and GUIV models or WH 5 wire on GUCA GCCA GCVA GUVA and GUSA models at the ignition control No voltage check the door switch connections and wire harness for continuity 2 Check for 24 volts from W to C at the thermostat con nections on the ignition control No voltage check trans former room thermostat and wiring 3 Checkfor 120 volts to the induced draft blower by mea suring voltage between terminals IND V7 55 wire on GUIA GCIA GUIC GCIC and GUID models or BK and RD wires on GUIS GCIS and GUIV models or BK 3 wire on GUCA GUIE GULA GCCA and GCLA els or RD 15and BK 3 wires on GCVA GUVA and GUSA models and neutral No voltage replace ignition con trol 4 f voltage is present in Steps 1 through 3 and the in duced draft blower is operating check for 120 volts to the ignitor during the preheat cycle Measure voltage be tween terminals IGN RD 22 wire on GUIC GCIC GUID GUIS GCIS and models RD 2 wire on GCCA GCLA GCVA GUCA GUIE GULA GUVA and GUSA models and neutral No voltage check pressure switch 5 After the ignitor warmup time see notes below begin checking for 24 volts to the gas valve Voltage will be present for seven seconds only if proof of flame has been established 151 SERVICING a On GUIA GCIA GUIC GCIC and GUID models
143. Gas Valve Tap 156 Gas Valve On Off Selector Switch Outlet Pressure Tap 4 INLET OUTLET 4 E A Open to Atmosphere Pressure Regulator Adjustment Under Screw Inlet Pressure Tap Side of Valve Manometer Hose Manometer Measuring Manifold Gas Pressure 36G Valve GAS LINE GAS SHUTOFF VALVE GAS LINE TO FURNACE OPEN TO ATMOSPHERE DRIP LEG CAP MANOMETER HOSE MANOMETER Measuring Inlet Gas Pressure Alternate Method 3 Turn ON the gas and electrical power supply and oper ate the furnace and all other gas consuming appliances on the same gas supply line 4 Measure furnace gas supply pressure with burners fir ing Supply pressure must be within the range specified in the following table Inlet Gas Supply Pressure Minimum 5 0 W C Maximum 10 0 W C Minimum 11 0 W C Maximum 13 0 W C NaturalGas If supply pressure differs from above make necessary ad justments to pressure regulator gas piping size etc and or consult with local gas utility SERVICING warninea HIGH VOLTAGE Disconnect ALL ELECTRICAL POWER AND SHUT OFF GAS SUPPLY BEFORE SERVICING OR INSTALLING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 5 Disconnect manometer after turning off gas at manual shutoff valve Reinstall plug before turning on gas to f
144. Gp and Speeds Cooling Operation and Continuous Fan Operation Section 1 for details concerning and Y 5 1 connection options 11 KOO Ya 80066 Circulator Blower Interface Board Remote Condensing Furnace Unit Single Stage Two Stage Integrated Control Module Furnace Two Stage Heating with Single Stage Cooling Two Stage Heating Two Stage Cooling Thermostat r See NOTES 7 Indicate connection options KT 5 2 Refer to Circulator Blower Timings and Speeds Cooling Operation and Continuous Fan Operation Section for TE ep details concerning and Y connection options 1 Ya 1 1 69 S 0 9 6 Circulator Blower Interface Board Furnace Two Stage Integrated Control Module Furnace Two Stage Condensing Unit Two Stage Heating with Two Stage Cooling Typical Field Wiring for GUIV CA DX amp GUVA AX Two Stage Variable Speed Gas Furnaces 24VAC Control Circuit Thermostat Wiring 9096 GUVA BX CX Two Stage Variable Speed Furnaces As a two stage furnace the furnace s integrated control mod ule and or circulator blower interface board provide termi nals for both W1 and W2 and YLO and Y thermostat connections This allows the furnace to support the follow ing system applications Two Stage Heating Only Two Stage
145. HIGHEST ANTICIPATED SNOW LEVEL 90 Furnace Standard Vertical Termination Single Pipe PRODUCT DESIGN 90 MEDIUM RADIUS ELBOW m 12 MINIMUM 90 Furnace Alternate Vertical Termination Single Pipe Horizontal vent flue pipe terminations should be as shown in the following figure Refer to Vent Flue Pipe and Combus tion Air Pipe Termination Locations section in this manual or the installation instructions for details concerning loca tion restrictions A 2 3 8 diameter wall penetration is re quired for 2 diameter pipe while a 3 1 2 diameter hole is required for 3 diameter pipe To secure the pipe passing through the wall and prohibit damage to piping connections a coupling should be installed on either side of the wall and solvent cemented to a length of pipe connecting the two couplings The length of pipe should be the wall thickness plus the depth of the socket fittings to be installed on the inside and outside of the wall The wall penetration should be sealed with silicone caulking material UE INSIDE OUTSIDE MINIMUM 12 FROM WALL ELBOW OR COUPLING 12 TO GROUND OR HIGHEST ANTICIPATED SNOW LEVEL 90 Furnace Horizontal Termination Single Pipe 4 12 MINIMUM VENT FLUE TEE 90 ELBOW TURNED DOWN 12 MINIMUM ABOVE HIGHEST ANTICIPATED SNOW LEVEL 9096 Furnace Horizontal Termination Single Pipe Above Highest Anticipated
146. Heating with Single Stage Cooling and Two Stage Heating with Two Stage Cooling Refer to the following fig ures for proper connections to the integrated control module and or circulator blower interface board Thermostat Single Stage Heating with Single Stage Cooling Furnace Integrated Control Module Dehumidistat Optional Remote Condensing Unit Single Stage Cooling Single Stage Heating with Single Stage Cooling NOTE To apply a single stage heating thermostat the thermostat selector jumper on the integrated Control module must be set on single stage 73 PRODUCT DESIGN p Thermostat Two Stage Heating ith g 67 Single Stage Coolin 9 6 90 Remote Condensing Unit Single Stage Cooling Two Stage Heating with Single Stage Cooling P NEU mm mms N n 4 O Furnace Integrated Control Module Thermostat Two Stage Heating with Two Stage Cooling Furnace Integrated Control Module 5 9 69 69 O D Remote Condensing Unit Two Stage Cooling Two Stage Heating with Two Stage Cooling Typical Field Wiring for GUVA BX CX Two Stage Variable Speed Gas Furnaces 24VAC Control Circuit Single Stage Thermostat Application 90 GUSA BX CX Two Stage and GUVA BX CX Two Stage Variable Speed Models Only A single stage thermostat with only one heating stage can be used to control this fu
147. INFORMATION Pride and workmanship go into every productto provide our customers with quality products Itis possible however thatduringits lifetime a product may require service Products should be serviced only by aqualified service technician who is familiar with the safety procedures required in the repair and whois equipped with the proper tools parts testing instruments and the appropriate service manual REVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE SERVICEMANUAL BEFORE BEGINNING REPAIRS IMPORTANT NOTICES FOR CONSUMERS AND SERVICERS RECOGNIZE SAFETY SYMBOLS WORDS AND LABELS THIS UNIT SHOULD NOT BE CONNECTED TO OR USED IN CONJUNCTION WITH ANY DEVICES THAT ARE NOT DESIGN CERTIFIED FOR USE WITH THIS UNIT OR HAVE NOT BEEN TESTED AND APPROVED BY GooDMAN SERIOUS PROPERTY DAMAGE OR PERSONAL INJURY REDUCED UNIT PERFORMANCE AND OR HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF DEVICES THAT HAVE NOT BEEN APPROVED OR CERTIFED BY GOODMAN AH na MEETING TAF REQUIREMENTS 2 ever PREVENT THE RISK OF PROPERTY DAMAGE PERSONAL INJURY OR DEATH DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER TECHNICIAN AS SPECIFIED BY THE AIR CONDITIONING AND REFRIGERATION FLAMMABLE LIQUIDS INTHE GE THIS APPLIANCE INSTITUTE ARI ATTEMPTING TO INSTALL OR REPAIR THIS UNIT WITHOUT SUCH BACKGROUND MAY RESULT IN PRODUCT DAMAGE PERSONAL INJURY OR DEATH GOODMAN WILL NOT BE RESPONSIBLE FOR ANY INJURY
148. ISK OF WATER REACHING THE JUNCTION BOX IN THE EVENT OF A BLOCKED DRAIN CONDITION FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK Follow the bullets listed below when installing the drain sys tem Refer to the following sections for specific details con cerning furnace drain trap installation and drain hose hook ups The drain trap supplied with the furnace must be used Thedrain line between furnace and drain location must be constructed of 3 4 PVC or CPVC The drain line between furnace and drain location must maintain a 1 4 per foot downward slope toward the drain e Donottrapthe drain line any other location than atthe drain trap supplied with the furnace e Donotroute the drain line outside where it may freeze Ifthe drain line is routed through an area which may see temperatures near or below freezing precau tions must be taken to prevent condensate from freezing within the drain line e air conditioning coil is installed with the furnace a common drain may be used An open tee must be installed in the drain line near the cooling coil to relieve positive air pressure from the coil s plenum This is necessary to prohibit any interference with the function of the furnace s drain trap PRODUCT DESIGN UPRIGHTINSTALLATIONS In an upright installation drain hoses are connected to drain ports on the rubber e
149. If this occurs a qualified servicer must carefully clean the flame sensor with steel wool After cleaning the flame sensor output should be as listed on the specification sheet BURNERS warning HIGH VOLTAGE ELECTRICAL COMPONENTS ARE CONTAINED IN BOTH COMPARTMENTS TO AVOID ELECTRICAL SHOCK INJURY OR DEATH DO NOT REMOVE ANY INTERNAL COMPARTMENT COVERS OR ATTEMPT ANY ADJUSTMENT CONTACT A QUALIFIED PROFESSIONALLY TRAINED SERVICE AGENT AT ONCE IF AN ABNORMAL FLAME APPEARANCE SHOULD DEVELOP Periodically during the heating season make a visual check of the burner flames Turn the furnace on at the thermostat Wait a few minutes since any dislodged dust will alter the normal flames appearance Flames should be stable quiet soft and blue with slightly orange tips They should not be yellow They should extend directly outward from the burner ports without curling downward floating or lifting off the ports Check the burner flames for 1 Good adjustment 2 Stable soft and blue 3 Not curling floating or lifting off Burner Flame 133 SERVICING TEST EQUIPMENT Proper test equipment for accurate diagnosis is as essen tial as regulator hand tools The following is a must for every service technician and ser vice shop 1 Dialtype thermometers or thermocouple meter optional to measure dry bulb temperature 2 Amprobe to measure amperage and voltage 3 Volt Ohm Meter testing continuity
150. M LINE VOLTAGE TRANSFORMER sro NEUTRAL METER READS 120 VOLTS VOLT OHM VOLT OHM READS 96 VOLTS IN PHASE VOLT OHM METER READS 144 VOLTS OUT OF PHASE If meter reads approximately 96 volts the primary to secondary are in phase if reads approximately 144 volts out of phase reverse low voltage wires NOTE For flame rectification the common side of the secondary voltage 24 V is cabinet grounded If you were to bench test a transformer the primary neutral and secondary common must be connected together for testing purposes NEUTRAL 1 24 120 V R 1 L1 PHASING SYMBOL 130 Some transformers will display phasing symbols as shown in the illustration to the left to assist in determining proper transformer phasing Checking for polarization and phasing should become a habit in servicing Let s start now NOTE Newer integrated ignition controls have a diagnostic flash code for reversed polarity Refer to Troubleshooting Diagnostic Chartfor LED Codes MAINTENANCE waarnine HIGH VOLTAGE Disconnect ALL POWER BEFORE SERVICING REMOVING THE FILTER OR PERFORMING ANY OTHER MAINTENANCE MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH YOU MUST HANDLE THE IGNITOR HANDLE WITH CARE TOUCHING THE IGNITOR BODY WITH BARE FINGERS ROUGH HANDLING OR VIBRATION COULD RESULT IN EARLY IGNITOR FAILURE O
151. MS 55 pue ejesedo eoeuunJ usei d any jueuiusiqejse Jaye jo 5507 Buidid 10 5 y 1 euo Buyse SI 037 pezipixo pejeoo ji 105 5 pues esues Josues eurej Id pue 995 f onsouDeip 10 eoejdeg JO pezipixo pejeoo 10 101 S 10 siduieye 221 JOSUSS PUBS 103uoo e o bubi De SION 1981109 19ejuoo 101061 10 1011061 uedo 101 uoniui jo jequinu us SIDI SIDER esou yams eunsseJd 19409 1104 onis UOJIMS eJnsseJd 1001 5 eAISseoxe ANP jredei aoud 440 uin jou si pue ou eunjreJ enueui jo uonoes uO snonunuoo 1 11 ne une 22 3 umouy ym
152. Manifold Pressure Regulator Pressure Tap Adjustment Under Cap Screw White Rodgers Model 36F22 GUIE EX INLET gt M 11 OUTLET Gas Valve On Off Selector Switch White Rodgers Model 36G22 GULA GCLA 129 POLARIZATION AND PHASING As more and more electronic s are introduced to the Heat ing Trade Polarization of incoming power and phasing of primary to secondary voltage on transformers becomes more important Polarization has been apparent in the Appliance industry since the introduction of the three prong plug however the Heating Industry does not use a plug for incoming power but is hard wired Some ofthe electronic boards being used today with flame rectification will not function properly and or at all without polarization of incoming power Some also require phas ing between the primary and secondary sides of step down transformers To instill new working habits for our trade we recommend that these two items be checked during normal installa tion and or service calls See as follows INCOMING POWER METER READS METER READS 120 VOLTS 0 VOLTS VOLT OHM VOLT OHM METER METER THIS IS L1 OR THE THIS IS THE COMMON HOT POWER LEG OR NEUTRAL LEG These then should be wired to the furnace accordingly CHECKING FOR PHASING PRIMARY TO SECONDARY OF UNMARKED TRANSFORMERS METER READS 24 VOLTS VOLT OHM PRIMARY LINE VOLTAGE L1 HOT VOLT OH
153. Module the circulator 78 blower will operate on the selected Low Stage Heating speed tap following a fixed thirty 30 second on delay EAC Electronic Air Cleaner terminals are energized with the circulator blower 3 High Stage Heating Mode If W2 from the thermostat is connected to W2 on the Two Stage Integrated Control Module the circulator blower will operate on the selected High Stage Heating speed tap 4 Single Stage Cooling Mode If Y from the thermostat is connected to Y on the Two Stage Integrated Control Module the circulator blower will operate on the se ected High Stage Cooling speed tap with a 5 second ON delay and 45 second OFF delay Circulator blower requires 30 seconds to ramp up to full speed Electronic air cleaner terminals are energized with circulator blower 5 Low Stage Cooling Mode If YLo from the thermostat is connected to YLo on the Two Stage Integrated Control Module the circulator blower will operate at 6596 of selected High Stage Cool ing speed tap Electronic air cleaner terminals are ener gized with circulator blower 6 High Stage Cooling Mode If Y from the thermostat is connected to Y on the Two Stage Integrated Control Module the circulator blower will operate on selected High Stage Cooling speed tap with a 5 second ON delay and 45 second OFF delay CIRCULATOR BLOWER SPEED ADJUSTMENT HIGH VOLTAGE Disconnect ALL POWER BEFOR CHANGING SP
154. NG NEEDED WHEN RUNNING PIPE FROM THE METER TANK TO THE FURNACE When sizing a trunk line be sure to include all appliances which will operate simultaneously when sizing a trunk line The gas piping supplying the furnace must be properly sized based on the gas flow required specific gravity of the gas and length of the run The gas line installation must comply with local codes or in their absence with the latest edition of the National Fuel Gas Code NFPA 54 ANSI Z223 1 Natural Gas Capacity of Pipe In Cubic Feet of Gas Per Hour CFH Pipe in Feet is 11 4 11 2 132 278 1050 1600 20 92 190 730 1100 590 980 500 760 440 670 400 610 370 560 350 530 490 100 38 79 150 305 460 Pressure 0 5 psig or less and pressure drop of 0 3 W C Based on 0 60 Specific Gravity Gas 520 350 285 245 215 50 56 115 60 50 105 195 96 180 90 170 160 320 BTUH Furnace Input Heating Value of Gas BTU Cubic Foot 65 PRODUCT DESIGN To connect the furnace to the building s gas piping the in staller must supply a ground joint union drip leg manual shutoff valve and line and fittings to connect to gas valve In some cases the installer may also need to supply a transi tion piece from 1 2 pipe to a larger pipe size The following stipulations apply when connecting gas pip ing Refer to the following figures for typical gas line connec tions to the furnace 1 Use black iron or ste
155. NLY A QUALIFIED SERVICER SHOULD EVER HANDLE THE IGNITOR ANNUAL INSPECTION The furnace should be inspected by a qualified installer or service agency at least once per year This check should be performed at the beginning of the heating season This will ensure that all furnace components are in proper working order and that the heating system functions appropriately Pay particular attention to the following items Repair or service as necessary Flue pipe system Check for blockage and or leak age Check the outside termination and the connec tions at and internal to the furnace e Combustion air intake pipe system where applicable Check for blockage and or leakage Check the out side termination and the connection at the furnace e Heat exchanger Check for corrosion and or buildup within the heat exchanger passageways e Burners Check for proper ignition burner flame and flame sense Drainage system Check blockage and or leakage Check hose connections at and internal to furnace e Wiring Check electrical connections for tightness and or corrosion Check wires for damage Filters AIR FILTER NEVER OPERATE FURNACE WIHTOUT A FILTER INSTALLED AS DUST AND LINT WILL BUILD UP ON INTERNAL PARTS RESULTING IN LOSS OF EFFICIENCY EQUIPMENT DAMAMGE AND POSSIBLE FIRE Filters must be used with this furnace Filters do not ship with these furnaces but must be provided by the installer for proper
156. OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES YOU INSTALL OR PERFORM SERVICE ON THIS UNIT YOU ASSUME RESPONSIBILITY FOR ANY PERSONAL INJURY OR PROPERTY DAMAGE WHICH MAY RESULT MANY JURISDICTIONS REQUIRE A LICENSE TO INSTALL OR SERVICE HEATING AND AIR CONDITIONING EQUIPMENT HIGH VOLTAGE Disconnect ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH IMPORTANT INFORMATION PELIGRO THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE Do NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE WHAT TO DO IF YOU SMELL GAS Do NOT TRY TO LIGHT ANY APPLIANCE Do TOUCH ANY ELECTRICAL SWITCH DO NOT USE ANY CARBON MONOXIDE POISONING HAZARD PHONE IN YOUR BUILDING IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR S Special Warning for Installation of Furnace or Air Handling Units in Enclosed Areas such as Garages Utility Rooms or Parking Areas PHONE FOLLOW THE GAS SUPPLIER S INSTRUCTIONS YOU CANNOT REACH YOUR GAS SUPPLIER CALL THE FIRE Carbon monoxide producing devices such as an automobile space DEPARTMENT heater gas water heater etc should not be operated in enclosed areas such as unventilated garag
157. OVER OF THIS MANUAL FAILURE TO DO SO COULD RESULT IN SERIOUS PERSONAL INJURY OR DEATH PRODUCT DESIGN IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE Do Nor STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE WHAT TO DO IF YOU SMELL GAS Do Nor TRY TO LIGHT ANY APPLIANCE Do TOUCH ANY ELECTRICAL SWITCH DO NOT USE ANY PHONE IN YOUR BUILDING IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR S PHONE FOLLOW THE GAS SUPPLIER S INSTRUCTIONS YoU CANNOT REACH YOUR GAS SUPPLIER CALL THE FIRE DEPARTMENT INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER Sizing Between First and Second Stage Regulator Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting Capacities in 1 000 BTU hour Pipe or Tubing Nominal Pipe Size Tubing Size O D Type L Schedule 40 5 8 3 4 1 2 3 4 To convert to capacities at 15 psig settings multiply by 1 130 To convert to capacities at 5 psig settings multiply by 0 879 Sizing Between Single or Second Stage Regulator and Appliance Maximum Propane Capacities Listed are Based on 1 2 W C pressure drop at 11 W C setting Capacities in 1 000 BTU hour
158. SPEED TAP SELECTOR PINS TEST Jour To IDEHUMIDIFY Circulator Blower Speed Selector Pin Location GUIV CA DX amp GUVA AX Models EXAMPLE On the example used move the COOL speed tap selector pin to C and move the ADJUST tap selector to minus Do NOT move the Adjust pin to TEST 5 Select the heating speed from the heating speed chart in the specification sheet for your model The adjust set ting already established by the cooling speed selec tion will determine which set of speeds are available The selected speed must provide a temperature rise within the rise range listed with the particular model EXAMPLE The GUVA070AX40 is set for 990 CFM on cooling the ADJUST is setto minus The four heat ing speeds available are A Minus B Minus C Mi nus and D Minus A Minus has a rise of 56 F for both stages which is within the 30 60 F rise range for the GUVA070AX40 This setting will keep electrical con sumption to a minimum Move the Heat speed pin se lector to A In general lower heating speeds will reduce electrical con sumption lower operating sound levels of the blower and increase the outlet air temperature delivered to the home The speeds available allow the blower performance to be optimized for the particular homeowner s needs
159. Service ue Instructions 40 80 Gas Furnaces amp Accessories GUIA GCIA GUIB GUID GUIE GUIS GCIS GUIV 40 9096 Gas Furnaces amp Accessories GCCA GCLA GUCA GULA GUSA GUVA lt X 5 2 FN NEN Heating amp Air Conditioning de amd This manual is to be used by qualified professionally trained HVAC ana technicians only Goodman does not assume any responsibility for RS6600001 Rev 2 property damage or personal injury due to improper service November 2006 LASTS AND LASTS AND LASTS procedures or services performed by an unqualified person Amana a trademark of Maytag Corporation and is used under license to Goodman Copyright 1999 2006 Goodman Company L P Company L P All rights reserved 5 IMPORTANT INFORMATION 2 3 POLARIZATION amp PHASING 130 PRODUCT INFORMATION scans 4 19 MAINTENANCE onneen 131 133 OPERATING INSTRUCTIONS 20 25 134 160 ACCESSORIES 26 41 TROUBLESHOOTING antice 136 PRODUCT DESION 42 86 SERVICING TABLE OF CONTENTS 137 SYSTEM OPERATION 87 129 ACCESSORIES WIRING DIAGRAMS 161 167 IMPORTANT
160. Should read between 50 to 200 ohms 90 GUCA GCCA and GUVA AX Model Furnaces Should read between 50 to 300 ohms for mini ignitor part number 20165701 used in initial production of GUCA and GCCA models 9096 GUCA GCCA GULA AX CX and GUVA AX Model Furnaces Should read between 30 to 175 ohms for mini ignitor part number 20165702 used in later pro duction of GUCA GCCA and also used on GUVA mod els 90 GCLA AX CX GUID AX GA EX and GUIE EX Model Furnaces Should read between 30 to 300 ohms for mini ignitor part number 20165703 9096 GUSA BX and GUVA BX CX Model Furnaces Should read between a minimum of 10 9 to a maximum of 19 7 ohms for Silicon Nitride SiNi ignitor part number 11111701 5 Reconnectignitor warnine 6 Placeunitin heating cycle measure current draw of ig nitor during preheat cycle 8096 Furnaces Should read approximately 4 to 5 amps 90 GUCA GCCA GCLA AX BX GUIE EX GULA AX CX and GUVA AX Model Furnaces Should read ap proximately 1 amp maximum The steady state current at 120V is a nominal of 7 plus or minus 3 amps SERVICING 9096 GCVA BX CX GUSA BX and GUVA BX Model Fur naces Should read approximately 1 to 3 amps NOTE Due to the Adaptive Ignitor Modulation Routine of the 50M V61 and 50A65 integrated ignition controls the amp reading will fluctuate when reading with stan dard amp meter 7 After check and or replacement of hot surface ignitor reinstall burner compartmen
161. Snow Level In a basement installation the vent flue pipe can be run be tween joist spaces If the vent pipe must go below a joist and then up into the last joist space to penetrate the header two 45 elbows should be used to reach the header rather than two 90 elbows DIRECT VENT DUAL PIPE PIPING 90 6 FURNACES ONLY Direct vent installations require both a combustion air in take and a vent flue pipe The pipes may be run horizontally and exit through the side of the building or run vertically and exit through the roof of the building The pipes may be run through an existing unused chimney however they must extend a minimum of 12 inches above the top of the chim ney The space between the pipes and the chimney must be closed with a weather tight corrosion resistant flashing Both the combustion air intake and a vent flue pipe termina tions must be in the same atmospheric pressure zone Re ferto Vent Flue and Combustion Air Pipe Termination Lo cations or Concentric Vent Termination section in this manual or the installation instructions for specific details on termi nation construction For details concerning connection of pipes to the furnace refer to the Vent Flue Pipe and Com bustion Pipe Standard Furnace Connections or Alternate Furnace Connections section in this manual or the installa tion instructions Vent Flue and Combustion Air Pipe Lengths and Diameters 90 Furnaces Only Refer to the following tables for a
162. Stage Variable Speed Furnaces GREEN X BLACK WHITE 70 had 40 30 WHITE RODGERS DE HUMIDISTAT RH DE HUMIDISTAT UM Y wi w2 TWIN eee Y B 4351 0 G R wi OFF on CUT FOR M 87 4321 53 DEHUM OUO 990 3 non CIMET WHITE RODGERS 2 RON UOOOU LO HEAT COOL LINE XFMR XFMR LINE Lil d 1111 Lo Hear HIHEAT EAC COOL PARK LINE XFMR Hum CIRC EAC XFMR uve IOT NEUTRAL INTEGRATED IGNITION CONTROL 50V61 288 167
163. Standard Drain Hose Connections Left Side NOTE Ensure hoses and tubes maintain a downward slope for proper drainage and that they are not kinked or binding Alternate Vent Flue Drain Hose Connections Upright installations using the alternate vent flue outlet will require right side only drain hoses to be connected as shown in the following figure Refer to Vent Flue Pipe and Combustion Air Pipe section in this manual or the installa tion instructions for details on alternate vent flue pipe con nection A MC RUBBER ELBOW EXTERNALLY 97 MOUNTED _ RUBBER d 2 p ELBOW Pa DRAIN PORT ee P TUBE 1 HOSE JA CLAMPS 5 5 4 HOSE SIDE PANEL 15 HOLES DRAIN TRAP FRONT COVER HOSEA DRAIN PORT TUBE S 2 9096 Furnace Upright Alternate Drain Hose Connections Right Side Only NOTE Ensure hoses and tubes maintain a downward slope for proper drainage and are not kinked or binding For details concerning mounting of the drain trap refer to the following section Upright Drain Trap Mounting Left or Right Side Panel 1 Insert drain tubes into drain trap and position the drain trap against the side panel NOTE Drain tubes must reach the bottom of the drain trap 2 Secure drain trap to side panel at the mounting holes loc
164. Thermostat From Room Thermostat From Room Thermostat On Two Stage Integrated Control Module On Two Stage Integrated Control Module On Two Stage Integrated Control Module On Two Stage Integrated Control Module On Two Stage Integrated Control Module On Circulator Blower Interface Board Screw Terminal On Circulator Blower Interface Board Screw Terminal On Two Stage Integrated Control Module On Circulator Blower Interface Board Screw Terminal On Two Stage Integrated Control Module On Circulator Blower Interface Board Screw Terminal On Circulator Blower Interface Board Screw Terminal On Circulator Blower Interface Board Screw Terminal On Two Stage Integrated Control Module Circulator blower will operate on selected Low Stage Heating speed tap Circulator blower will operate on selected High Stage Heating speed tap Circulator blower will operate on selected High Stage Cooling speed tap 5 second ON delay and 45 second OFF delay Circulator blower will operate on selected High Stage Cooling speed tap No ON delay or OFF delays Circulator blower will operate at 6596 of selected High Stage Cooling speed tap No ON delay or OFF delay Circulator blower will operate on selected High Stage Cooling speed tap 5 second ON delay and 45 second OFF delay Circulator blower will operate on selected High Stage Cooling speed tap No ON
165. W to C at the thermostat con nections on the ignition control No voltage check trans former room thermostat and wiring 3 Check for 120 volts to the induced draft blower by mea suring voltage between IND VT 55 and neutral No volt age check for pressure switch stuck closed If pres sure switch in N O position replace ignition control 4 f voltage is present in Steps 1 through 3 and the in duced draft blower is operating check for 120 volts to the ignitor during the 17 second preheat cycle If the flame switch has not transferred the control will con tinue to power the ignitor until the flame switch trans fers or for 90 seconds Voltage will be present for one second after the gas valve has opened Measure voltage between terminals IGN RD 22 and neutral No voltage check pressure switch 5 Seventeen seconds after a call for heat begin checking for 24 volts to the gas valve Measure voltage from termi nal 5 YL 8 wire to terminal 3 RD 5 on the gas valve No voltage check flame switch and ignitor position 6 If proof of flame was established 120 volts will be pro vided to the air circulation blower 45 seconds after the gas valve opens Check for 120 volts from the CIR termi nal WH wire to the heat terminal on the ignition control No voltage replace ignition control NOTE If cycling the ignition control during testing the flame switch must be allowed to cool and switch back to the N C position befo
166. Y FROM ALL IGNITION SOURCES SPARKS OPEN FLAMES AND EXCESSIVE HEAT AS THEY ARE COMBUSTIBLE LIQUIDS AVOID BREATHING CEMENT VAPORS OR CONTACT WITH SKIN AND OR EYES Two or three inch nominal diameter PVC Schedule 40 pipe meeting ASTM D1785 PVC primer meeting ASTM F656 and PVC solvent cement meeting ASTM D2564 specifica tions must be used Fittings must be DWV type fittings meet ing ASTM D2665 and ASTM D3311 Carefully follow the manufacturer s instructions for cutting cleaning and sol vent cementing of PVC As an alternative to PVC pipe primer solvent cement and fittings ABS materials which are in compliance with the following specifications may be used Two or three inch ABS Schedule 40 pipe must meet ASTM D1527 and if used in Canada must be CSA listed Solvent cement for ABS to ABS joints must meet ASTM D2235 and if used in Canada must be CSA listed The solvent cement for the PVC to ABS transition joint must meet ASTM D3138 Fittings must be DWV type fittings meeting ASTM D2661 and ASTM D331 1 and if used in Canada must be listed Carefully follow the manufacturers instructions for cutting cleaning and solvent cementing PVC and or ABS All 90 elbows must be medium radius 1 4 bend DWV or long radius Long sweep 1 4 bend DWV types conforming to ASTM D3311 A medium radius 1 4 bend DWV elbow measures 3 1 16 minimum from the plane of one opening to the centerline of the other opening for 2 diameter
167. __ e 836 836 696 560 GUSA115 50 ee 1885 5541 460 J 576 J pode 506 909 576 ee poo 5035 576 672 768 L B10 J ewt e 610 672 768 960 C U C U C U 045 30 070 30 070 40 C U CA090 40 LE a gt 1 1 GUI A B C D 115 40 762 762 762 768 GUK AB C D115 50 762 762 768 960 GUI A B C D 140 50 838 838 838 960 GUISO70 35 ee ee 503 576 62 GUIS090 30 e gt GUIS090 50 pe 610 62 176 90 GUIS115 40 c 762 762 762 768 GUIS115 50 700 762 788 960 GUIS140 50 o _ _ 838 838 838 960 GUIVO70 40 5597 559 59 576 672 768 GUIVO90 50 _ 67 61 672 768 960 GUIV115 50 __ 838 838 838 960 GUIV140 50 c ose oo 888 838 838 960 045 30 5 5 0 070 30 419 419 480 56 070 40 480 l 576 672 090 30 59 697 57 GCI A B C D 090 50 56 672 768 960 GCKA B C D115 40 699 699 69 768 oe pe CEN
168. acement is relatively simple by merely removing the grille rather than going into the attic or crawl space Refer to the previous Upflow Horizontal Filter Size charts on Recommended Minimum Filter Sizes ADDITIONAL FILTERING ACCESSORIES External Filler Rack Kit EFRO1 The external filter rack kit is intended to provide a location external to the furnace casing for installation of a perma nent filter on upflow model furnaces The 15 designed to mount over the indoor blower compartment area of either side panel and provide filter retention as well as a location for attaching return air ductwork PRODUCT DESIGN Minimum Filter Requirement in Permanent Filters 188 192 240 288 eme 282 282 282 336 260 260 336 384 090 40 376 376 376 384 C U CA090 50 _ 376 376 384 480 C U CA115 50 1 470 470 470 480 GUVAO45 30 209 209 240 288 313 3135 336 384 GUVAO90 50 418 418 418 480 470 470 470 480 GUSA070 85 282 282 22 336 GUSA090 40 __ 1 3767 376 376 384 GUSA090 50 pee qoe smtp 86 1 9904 490 GUSA115 50 470 470 470 480 192 240 288 251 251 289
169. ages for an interpretation of the LED signals and to the information in this section for a description of the problem 1 Internal Control Failure with Integrated Ignition Control If the control determines it has an internal fault it enters a locked out state and the diagnostic light will light continuously with no flashes The control should be replaced 2 System Lockout If a flame is not sensed during the first seven 7 seconds after the gas valve is energized the control turns off the gas There will then be a 60 second delay while the induced draft blower is energized to purge the heat exchanger The ignitor will next be energized and preheated for 27 seconds The gas valve will then be energized If flame is not sensed in seven 7 seconds the gas valve will be de energized and another purge will occur The control will cycle the gas valve a total of three 3 times before it determines it cannot establish measurable combustion and enters a locked out state If flame is sensed but lost after ten 10 sec onds the control will recycle this series of three tries four 4 more times before locking out The diagnostic light code for this problem is one short flash followed by alonger pause The control can be reset and brought out of lockout mode by turning the thermostat off and then back on It can also be reset by turning off the elec trical disconnect switch to the furnace for 30 seconds NOTE The control board will automaticall
170. ainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft A Air Command 80 SSE Furnace B Second Design Series 1206601 P1206608F 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft A Air Command 80 SSE Furnace Third Design Series A Standard Unit not NOx certified P1207201F P1207208F 140 80 furnace featuring integrated electronic ignition control silicon carbide ignitor electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft B Air Command 80 SV Furnace A Initial Design Series P1186401F P1186408F 40 80 furnace featuring electronic ignition control silicon carbide ignitor radiant flame sensor electrodepositioned textured steel cabinet and aluminized steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft B Air Command 80 SV Furnace B Second Design Series GUIB B P1206801F P1206807F 40 80 furnace featuring electronic ignition control silicon carbide ignitor radiant flame sensor electrodepositioned textured steel cabinet and aluminized steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft B Air Command 80 SV Furnace C Third Design Series X NOx Certified GUIB
171. aken from the installation area or from air ducted from the outside or Direct vent dual pipe central forced air furnace in which all combustion air supplied directly to the furnace burn ers through a special air intake system outlined in this manual and the installation instructions IMPORTANT NOTE The 80 furnace cannot be installed as a direct vent furnace The burner box is present only to help reduce sound transmission from the burn ers to the occupied space To ensure proper installation operation and servicing thor oughly read the installation and service manuals for specif ics pertaining to the installation servicing and application of this product POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE EXPLOSION SMOKE SOOT CONDENSATION ELECTRICAL SHOCK OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION REPAIR OPERATION OR MAINTENANCE OF THIS PRODUCT PREVENT PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE DO NO INSTALL THIS FURNACE IN A MOBILE HOME TRAILER OR RECREATIONAL VEHICLE To ensure proper furnace operation install operate main tain and service the furnace in accordance with the installa tion operation and service instructions all local building codes and ordinances In their absence follow the latest edition of the National Fuel Gas Code NFPA 54 ANSI Z223 1 and or CAN CGA B149 Installation Codes local plumbing or waste water codes and other applicable codes
172. al shutoff valve Reinstall gas valve outlet pressure tap plug before turning on gas to furnace 11 Turn on gas to furnace and check for leaks If leaks are found repair and then reinstall burner compartment door 12 Turn on electrical power and verify proper unit operation Make sure furnace operates at the proper manifold pres sure at both high and low stage outputs Manifold Gas Pressure Rate Range Nominal High Stage 3 2 to 3 8 w c 1 610 2 2 w c Propane Gas Adjustments Disconnect ALL ELECTRICAL POWER AND SHUT OFF GAS SUPPLY BEFORE SERVICING OR INSTALLING 1 Afterturning off gas to furnace atthe manual gas shutoff valve external to the furnace remove burner compart ment door to gain access to the gas valve 2 Connecta calibrated water manometer or appropriate gas pressure gauge at the gas valve outlet pressure tap Refer to previous Measuring Manifold Gas Pressure figure for proper connection Ay warnine 3 Turn ON the gas and electrical power supply and oper ate the furnace 4 Remove the cap screw from the low stage manifold pres sure regulator 5 Using a 3 32 Allen wrench increase low fire manifold pressure by adjusting the ow stage manifold regulator sothe furnace will light and carryover 6 Remove the cap screw from the high stage manifold pres sure regulator adjustment location 7 Using a 3 32 Allen wrench adjust the high stage mani fold pressure regu
173. alers Your telephone company will bill you for the call PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing Please use these numbers when requesting service or parts information Airflow Capability 40 1 5 to 4 Tons 50 2 0 to 5 0 Tons Product Type G Gas Furnace Supply Type U Upflow Horizontal C Counterflow Horizontal Additional Features A Not NOx Certified X NOx Models Design Series C Third Design Series Furnace Type I Induced Draft 8096 2 Stage Variable Speed D Fourth Design Series Nominal Input 070 170 000 Btuh 090 90 000 Btuh 115 115 000 Btuh 140 140 000 Btuh Model Family V Air Command 80 SSE Category 1 80 GUIA A GCIA A GUIA B GCIA CX GUIA CA GCIB A GUIS DA GUIB A AIC oe GUIS CA GUIS CA GUIB CX GUIS CX GUIC CA acic ex GuIs Cx GUIC CA GCIC FX GUIS FA GUIC CA GUIS FX GUIC CX GUID CA GUIC CX GUID CA GUIC DA GUID CA GCIS CX GUIC DA GCIS FX GUIC DX GUID CX GUIV DX GUIC EA GUID CX GUIV CX GUIC EX GUID Cx GUIV Cx GUIC FA GUID CX GUIV FX GUIC FX GUID DA GUID DX GUID EA GUID GA
174. all electric power to the appliance 2 Couper l alimentation lectrique de l appareil s il if service is to be performed faut proc der des op rations d entretien 3 Turn the gas control knob clockwise 4 to 3 Torner le robinet a gaz dans le sens des aigilles OFF Position Do not force d une montre 4 en position OFF ARRET 4 Replace control access panel Ne pas forcer 4 Remettre en place le panneau d acc s 11072703 OPERATING INSTRUCTIONS FOR YOUR SAFETY LIRE AVANT DE METTRE EE READ BEFORE OPERATING EN MARCHELIRE WARNING If you do not follow these instructions AVERTISSEMENT Quiconque ne respecte pas explosion may result causing property damage la lettre les instructions dans le pr sent manuel ersonal injury or loss of life risque de d clecher un incendie ou une explosion entrainant des dammages mat riels des l sions A This appliance does not have a pilot It is equipped corporelles ou la perte de vies humaines with an ignition device which automatically lights the burner Do not try to light the burner by hand A Cet appareil ne comporte pas de veilleuse Il est muni d un dispositif d allumage qui allume B BEFORE OPERATING smell all around the appliance automatiquement le br leur Ne pas tenter area for gas Be sure to smell next to the floor d allumer le br leur manuellement because some gas is heavier than air and will B AVANT DELE FAIRE FONCTIONNER settle on
175. an unpainted metal surface of the furnace near the control Any tools held in a person s hand during grounding will be discharged 3 Service integrated control module or connecting wiring following the discharge process in Step 2 Use caution not to recharge your body with static electricity 1 6 do not move or shuffle your feet do not touch ungrounded objects etc If you come in contact with an ungrounded object repeat Step 2 before touching control or wires 4 Discharge any static electricity from your body to ground before removing a new control from its container Follow Steps 1 through 3 if installing the control on a furnace Return any old or new controls to their containers before touching any ungrounded object 41 PRODUCT DESIGN Product Application This product is designed for use as a residential home gas furnace It is not designed or certified for use in mobile home trailer recreational vehicle or commercial applications The 8096 and 9096 furnaces are CSA certified appliances and are appropriate for use with natural or propane gas NOTE If using propane gas a propane conversion kit is required One important difference between the 80 and 90 fur nace is that the 90 furnace is a dual certified appliance Dual certification means that the combustion air inlet pipe is optional and the furnace can be vented as a Non direct vent single pipe central forced air furnace in which combustion air is t
176. and W1 or R and W1 and W2 thermostat contacts open completing the call for heat 15 Gas valve closes extinguishing flame 16 Induced draft blower is de energized following a fifteen second post purge Humidifier terminals are de energized 17 Circulator blower continues running for the selected heat off delay period 60 90 120 or 180 seconds The speed run during this period depends on the last heat call pro vided by the thermostat If the last call for heat was a call for low heat the air circulator blower will run on low heat speed for the dura tion of the heat off delay period 60 90 120 or 180 sec onds If the last call for heat was a call for high heat the air circulating blower will run on the high heating speed for thirty seconds and then switch to the low heating speed for the balance of the heat off delay period 30 60 90 or 150 seconds 18 Circulator blower and electronic air cleaner terminals are de energized 19 Circulator blower ramps down to OFF during the 30 sec onds following the heat off delay period 20 Furnace awaits next call from thermostat SYSTEM OPERATION Cooling Mode The normal operational sequence in cooling mode is as fol lows 1 R and YLO or Y thermostat contacts close initiating a call for cool Integrated control module performs safety circuit checks 3 Outdoor fan and compressor are energized to their ap propriate speed 4 Circulator blower is energized
177. and aluminized steel tubular heat exchanger Use of smooth cold rolled steel substrate and a smooth top coat for furnace cabinet to replace prepainted furnaces until new coating is approved for prepainted material GUID CX P1220501F P1220507F Gas Furnace Upflow Horizontal Induced Draft D Air Command 80 SV Furnace D Fourth Design Series X NOx Certified 40 80 furnace featuring integrated electronic ignition control silicon P1227001F P1227009F carbide ignitor prepainted textured steel cabinet and aluminized steel tubular heat exchanger Use of 10x8 blower assembly on 070 40 model to upgrade airflow to a full 4 tons of air for air conditioning and also release of new circulation motor on 090 115 and 140 50 models PRODUCT IDENTIFICATION This section will identify the models covered and the changes per each model group from one release to the next Model Manufacturing Description Gas Furnace Upflow Horizontal Induced Draft S 2 Stage Air Command 80 SSE II Furnace C Third Design Series A Standard Unit not NOx certified GUIS CA P1211003F P1211008F 40 80 two stage furnace featuring integrated electronic ignition control two stage gas valve two speed induced draft blower silicon carbide ignitor electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft S 2 Stage Air Command 80 SSE Furnace Third Design Series X NOx
178. ange to Low Heat 64 0 15 60 90 120 4 second 180 maximum trial for ignition period 117 SYSTEM OPERATION COOLING TIMING CHART FOR WHITE RODGERS 50M61 288 TWO STAGE INTEGRATED IGNITION CONTROL OPERATION Circulator On Blower Off Outdoor Fan On And Off Compressor Thermostat On Call For Cool Off 0 5 Time sec 0 45 TIMING CHART FOR NORMAL FAN OPERATION Circulator On Blower Off On Thermostat Off Call For Fan Time sec 0 118 SYSTEM OPERATION Abnormal Operation 90 6 Two Stage Models with White Rodgers 50M61 288 Ignition Control The following presents the probable causes of questionable furnace operation and how to fix them Look through the observation window in the blower access door and make a note of the number of flashes in sequence between pauses Next refer to the Troubleshooting Chart on the following page for an interpretation of the LED signals and to the infor mation in this section for a description of the problem 1 Internal Control Failure with Integrated Ignition Control If the control determines it has an internal fault it enters a locked out state and the diagnostic light will light continuously with no flashes The control should be replaced 2 System Lockout If a flame is not sensed during the first seven 7 seconds after the gas valve is energized the control turns off the gas There will then be a 60 second delay
179. ard Unit not NOx certified GUID CA P1212401F P1212407F 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor electrodepositioned textured steel cabinet and aluminized steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft D Air Command 80 SV Furnace C Third Design Series A Standard Unit not NOx certified 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor prepainted textured steel cabinet and aluminized steel tubular heat exchanger Release of Fasco induced draft blower to replace Jakel induced draft blower GUID CA P1220601F P1220607F Gas Furnace Upflow Horizontal Induced Draft D Air Command 80 SV Furnace C Third Design Series A Standard Unit not NOx certified P1229401F 1229407 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor prepainted textured steel cabinet and aluminized steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft D Air Command 80 SV Furnace C Third Design Series A Standard Unit not NOx certified P1229501F P1229507F 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor electrodepositioned textured steel cabinet and aluminized steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft D Air Command 80 SV Furnace C Third Design Series X NOx Certified GUID CX P1212501F
180. as will only continue to flow if a signal is present The control checks the thermostat to see whether the call for heat is for low stage heat or high stage heat If the callis for high stage heat the induced draft blower is switched to high speed and the gas valve is energized on high flow rate The control waits 30 seconds and turns on the air circu lator blower to the appropriate speed high heat speed for high heat or low heat speed for low heat Electronic air cleaner terminals are energized with the circulator blower On some models the high heat air circu lator speed may be the same as the low heat circulator speed These models are factory shipped to be within the rise range on both stages with the same air circula tor speed 9 10 1 12 13 14 15 16 17 Thefurnace is now operating on the specified stage called out by the two stage thermostat If the two stage thermostat changes the call from low heat to high heat the control will immediately switch the vent blower motor gas valve and air circulating speed to their high stage setting If the two stage thermostat changes the call from high heat to low heat the control will immediately switch the induced draft blower motor to low speed and switch the flow rate on the gas valve to low The air circulator blower will remain on high heating speed for thirty seconds be fore switching to the low heat circulating spee
181. ase to the next Model Manufacturing 1234201 1234207 1244902 P1245901F P1245907F P1241001F P1241007F Description Gas Furnace Upflow Horizontal Induced Draft D Air Command 80 SSE Furnace E Fifth Design Series A Standard Unit not NOx certified 40 8096 furnace redesign incorporating feature changes introduced by the new 40 9096 furnaces Changes include standardized blower decks access door blower door scroll wrap burner bracket Norton mini igniter and plug connect wiring harness The furnaces also feature an integrated electronic ignition control prepainted textured steel cabinet and aluminized steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft D Air Command 80 SSE Furnace G Sixth Design Series A Standard Unit not NOx certified 40 80 furnace redesign incorporating feature changes which include standardized blower decks access door blower door scroll wrap burner bracket Norton mini igniter and plug connect wiring harness The furnaces also feature an integrated electronic ignition control White Rodgers G Gas Valve removal of internal filter capability prepainted textured steel cabinet and aluminized steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft E High Static Line Air Command 80 HS Furnace E Fifth Design Series X NOx certified 40 8096 furnace redesign incorporating feature changes introduced by the new 40 9096 furnaces
182. at Test Method Remedy Test Voltage See Service Procedure Reference Blown Fuse Test Voltage Loose Connection Check Wiring Shorted or Broken Wires No Low Voltage Check Wiring Check Transformer Faulty Thermostat Check Thermostat Faulty Transformer Check Transformer Poor or High Resistance Ground Improper Heat Anticipator Setting Measure Ground Resistance Adjust Heat Anticipator Setting Improper Thermostat Location Relocate Thermostat Faulty Limit or Roll Out Switch Test Control Faulty Flame Sensor Faulty Ignition Control Test Flame Sensor Test Control Gas Valve or Gas Supply Shut Off Turn Valves to On Position Faulty Induced Draft Blower Test Blower Broken or Shorted Ignitor Dirty Flame Sensor Low Test Ignitor Clean Flame Sensor Flame Sensor not in Flame Low Test Adjust Position of Flame Sensor Faulty Gas Valve Open Auxiliary Limit Replace Gas Valve Reset Control Improper Air Flow or Distribution Check Duct Static Cycling on Limit Check Controls amp Temperature Rise Test for Delayed Ignition Test for Flashback Check Orifices Check Gas Pressure Cracked Heat Exchanger Stuck Gas Valve Check Burner Flames Replace Gas Valve Furnace Undersized Replace with Proper Size Furnace Faulty Pressure Switch Test Pressure Switch 5 8 Blocked or Restricted Flue C
183. at Only High Low Off High Low Off On Off PS2 Closed PS1 Closed Open High Low Off High Low Off 0 10 27 31 34 64 94 0 5 30 60 90 90 120 120 150 180 210 107 SYSTEM OPERATION Air Circulator Blower Gas Valve Ignitor Pressure Switches Induced Draft Blower Thermostat Air Circulator Blower Gas Valve Ignitor Pressure Switches Induced Draft Blower Thermostat 108 HEATING TIMING CHARTS FOR WHITE RODGERS 50 51 225 TWO STAGE INTEGRATED IGNITION CONTROL OPERATION Example 3 Initial Call For Low Heat Change In Call To High Heat a Call Change to High Heat High Low Off On Off On Off PS2 Closed PS1 Closed Open High Low Off High Low Off 0 10 27 31 34 64 94 0 5 30 60 90 90 120 120 150 180 210 Example 4 Initial Call For High Heat Subsequent Call Low Heat Call Change to Low Heat 30 Seconds After Call Change to Low Heat High i Low Off High Low Off On Off PS2 Closed PS1 Closed Open High Low Off High Low Off 0 10 27 31 34 64 94 0 5 30 60 90 90 120 120 150 180 210 SYSTEM OPERATION HEATING TIMING CHARTS FOR WHITE RODGERS 50 51 235 TWO STAGE INTEGRATED IGNITION CONTROL OPERATION Example 1 Continuous Call For Low Stage Heat Only High Circulator Low Blower Off Gas Valve On Off Igniter On Off PS2 Closed Pressure PS1 Closed Switches Open
184. ated below the grommet drain holes 3 Attach PVC drain line to drain trap outlet with either a 90 elbow or coupling NOTE Ensure hoses and tubes maintain a downward slope for proper drainage and that they are not kinked or binding 63 PRODUCT DESIGN HORIZONTAL INSTALLATIONS Right Side Down Horizontal installations with the right side down require that the drain hoses be connected to the right side front cover drain port and the rubber elbow drain port FRONTCOVER DRAINPORT T 7 V CLAMP TENNE HOSE A 4 HOSEB SIDE PANEL PRESSURE RUBBER GROMMET N TAP gt F ELBOW HOLES bm EL TR ST 2 RIGHT CU SIDE TUBES2 PANEL 3 RUBBER ELBOW K P DRAIN PORT 1 DRAIN TRAP CLAMP irn Es 8 PLACES 9096 Furnace Horizontal Drain Hose Connections Right Side Down NOTE Ensure hoses and tubes maintain a downward slope for proper drainage and are not kinked or bound For details concerning mounting of the drain trap refer to Condensate Drain Lines and Drain Trap Horizontal Drain Trap Mounting section in this manual or the installation in structions Left Side Down Horizontal installations with the left side panel down will re quire drain hoses to be connected to the left side front cover drain port and the induced draft blower drain port NOTE On upflo
185. ated control module is reversed the 24V AC orange and gray wires to transformer are reversed or poor unit ground 7 Low Flame Sense Signal If the furnace continues to operate and the micro amp signal from the flame sensor falls below specified level The diagnostic light code for this problem is seven flashes followed by a pause The probable cause is either a coated oxidized sensor in correctly positioned senser in burner flame or lazy burner flame due to improper gas pressure or combustion air 8 Ignitor Circuit Problem If the furnace fails to operate due to a problem with the ignitor The diagnostic code for this problem is eight flashes followed by a pause The probable cause is either loose or misconnected wir ing or a bad ignitor 9 Furnace Operating on Low Stage Gas with High Stage Induced Draft Blower and High Stage Circu lator Blower If the furnaces high stage pressure switch circuit fails to close in response to high stage induced draft blower operation The diagnostic light code for this problem is nine flashes followed by a pause The prob able causes are either a blocked pinched or discon nected hose to the pressure switch faulty pressure Switch loose or misconnected wiring restricted air in take or flue piping blocked drain system or weak in duced draft blower 10 Flame Sensed with No Call for Heat If the control senses a flame when the gas valve is de energized it will run the air circulator blower and
186. ator blower is de energized Electronic air cleaner terminals are de energized 7 Furnace awaits next call from thermostat 93 SYSTEM OPERATION 39Vd LX3N NO LHVHO OZ JNO YOO 19591 oj 14 JOOP 10 12euuoosip eui 5 eseeo epoo USE 01 JnOU 4 90 19591 0 Jdwaye SALON seuse 4 6 Saysay ued jueuieoe dei 1981109 pue pejoeuuoosiui 10 95001 aay si edoJd Aesseoeu eoueuuojied 20 49809 1 10 pue Jo11uoo S rejop Buidid 10 uonoes i uedo SI edid ly uonsnquio2 pue pue seuung peufi esiuu o loud 440 uin 104 any nojos uogejedo Jen
187. basepan Do not remove To access the filter tilt the wire filter retainer upwards 4 Slide filter forward and out Vacuum blower compart ment Replace filter and secure retainer opposite of removal 6 Replace blower compartment door and turn ON thermo stat or electrical power to furnace To remove filters from an external filter rack in an upright upflow installation follow the directions provided with exter nal filter rack kit To remove internal filter s from the retaining rails on the side s of the blower compartment in an upright installation 1 Setthe thermostat to the OFF position or turn OFF elec trical power to furnace Remove the blower compartment door Grasping the lower portion of the filter disengage the filter from the lower railing by lifting it up and toward the blower Lower the filter down and pull outward 131 MAINTENANCE 4 Replace filter and blower compartment door opposite of removal and turn ON thermostat or electrical power FRONT OF FURNACE FRONT OF FURNACE BLOWER BLOWER GRAB AND LIFT a Lift filler above bottom b Tilt filter to clear rail rail FRONT OF FURNACE FRONT OF FURNACE BLOWER BLOWER d Slide filter out c Lower filter below top rail Filter Removal Procedure Media Air Filter or Electronic Air Cleaner Removal Follow the manufacturer s directions for service Upright Counterflow Filter Removal To remove filters from
188. been underwater Immediately call a qualified service technician to inspect the appliance and to replace any part of the control System and any gas control which has been underwater AVERTISSEMENT Quiconque ne respecte pas la lettre les instructions dans le pr sent manuel risque de d clecher un incendie ou une explosion entra nant des dammages mat riels des l sions corporelles ou la perte de vies humaines A Cet appareil ne comporte pas de veilleuse Il est muni d un dispositif d allumage qui allume automatiquement le br leur Ne pas tenter d allumer le br leur manuellement B AVANT DELE FAIRE FONCTIONNER renifler tout autour de l appariel pour d celer une odeur de gaz Renifler pr s du plancher car certains gaz sont plus lourds que l air et peuvent s accumuler au niveau du 50 QUE FAIRE S IL Y A UNE ODEUR DE GAZ Ne pas tenter d allumer l appariel Ne toucher aucun interrupteur lectrique n utiliser aucun t l phone dans le b timent Appeler imm diatement le fournisseur de gaz en employant le t l phone d n voisin Respecter la lettre les instructions du fournisseur de gaz Si personne ne r pond appeler le service des incendies C Ne pousser ou tourner le robinet d admission du gaz qu la main ne jamais emploer d outil cet effet Si la manette reste coinc e ne pas tenter de la r parer appeler un technicien qualifi Quiconque tente de forcer la manette ou de la reparer peut d cl
189. blower will be energized all the time The diag nostic light code for this problem is five flashes followed by a pause The probable cause is either restricted flue piping or improper air requirements 7 Reversed Polarity If the 115V or 24V AC power leads are reversed the furnace will fail to operate The diag nostic light code for this problem is six flashes followed by a pause The probable cause is either the 115V AC power to furnace or integrated control module is reversed the 24V AC orange and gray wires to transformer are reversed or poor unit ground 8 Low Flame Sense Signal White Rodgers 50A55 50T55 Control Only If the furnace continues to operate and the micro amp signal from the flame sensor falls below specified level The diagnostic light code for this problem is seven flashes followed by a pause The prob able cause is either a coated oxidized sensor incorrectly positioned sensor in burner flame or lazy burner flame due to improper gas pressure or combustion air 9 Pressure Switch Opened Five Times During A Single Call for Heat If the furnace fails to operate due to pressure switch opening five times during a single call for heat The diagnostic light code for this problem is eight flashes followed by a pause The probable cause is either the pressure switch hose is blocked pinched or misconnected blocked flue or drain system weak induced draft blower incorrect pressure switch set point or faulty pressure swi
190. by using the 90 phase relationship between the capacitor cur rent and voltage in conjunction with the motor windings so that the motor will give two phase operation when connected to a single phase circuit The capacitor also reduces the line current to the motor by improving the power factor to the load DISCHARGE CAPACITOR THROUGH 20 30 OHM RESISTO BEFORE HANDLING Two quick ways to test a capacitor are a resistance and a capacitance check Refer to the next two figures for proper meter connections for the resistance and capacitance test ing of the capacitor S 10A Resistance Check VOLT OHM Testing Capacitor Resistance varie HIGH VOLTAGE Disconnect ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 Remove blower compartment door to gain access to pacitor 2 Discharge capacitor and remove wire leads 3 Setan ohmmeter on its highest ohm scale and connect the leads to the capacitor a Good Condition indicator swings to zero and slowly returns toward infinity b Shorted indicator swings to zero and stops there replace Open no reading replace Reverse leads Check again no reading replace d Reverse leads and recheck S 10B Capacitance Check VOLT OHM METER 15 AMP FUSE AMMETER Testing Capacitance With pow
191. by turning the thermostat off and then back on It can also reset by turning off the electrical disconnect switch to the furnace for 30 sec onds The 50A51 225 control will reset after two hours and the 50A51 235 will reset after one hour IMPORTANT If you have to frequently reset your furnace it means that a problem exists that should be corrected Con tact a qualified servicer for further information 112 3 Pressure Switch Stuck Closed sticking pressure Switch can be caused by either a faulty pressure switch faulty wiring a disconnected hose or a restricted intake or flue piping In the case of a pressure switch sticking closed the probable cause is a faulty pressure switch or wiring If the ignition control senses that the pressure switch is closed and the induced draft blower is off it will shut down the unit until the fault is corrected The light code for this problem is two short flashes followed by a longer pause 4 Pressure Switch Stuck Open A sticking open pres sure switch can be caused by a faulty pressure switch a blocked pinched or disconnected hose to the pres sure switch a restricted air intake or flue piping or faulty wiring If the ignition control senses that the induced draft blower is energized but the pressure switch is not closed the control will keep the blower on and wait for the switch to close The diagnostic light code for this problem is three short flashes followed by a pause 5 Op
192. capacitors and mo tor windings 4 Inclined Manometer to measure static pressure pres sure drop across coils filters and draft 5 Water Manometer 12 to test gas inlet and manifold pressure Other recording type instruments can be essential in solv ing abnormal problems however in many instances they may be rented from local sources Proper equipment promotes faster more efficient service and accurate repairs resulting in fewer call backs HEATING PERFORMANCE TEST Before attempting to diagnose an operating fault run a heat ing performance test and apply the results to the Service Problem Analysis Guide To conduct a heating performance test the input to the furnace must be calculated After the heating cycle has been in operation for at least fifteen minutes and with all other gas appliances turned off the gas meter should be clocked To find the BTU input multiply the number of cubic feet of gas consumed per hour by the heating value of the gas be ing used The calorific value of the gas being used is found by contacting your local utility EXAMPLE It is found by the gas meter that it takes forty 40 seconds for the hand on the cubic foot dial to make one complete revolution with all appliances off except the fur nace Take this information and locate it on the gas rate chart Observe the forty 40 seconds locate and read across to the one 1 cubic foot dial column There we find the nu
193. ce may be used as a construction site heater ONLY if the following conditions are met The vent system is permanently installed per these installation instructions Aroom thermostatis used to control the furnace Fixed jumpers that provide continuous heating CANNOT be used Return air ducts are provided and sealed to the fur nace Areturn air temperature range between 60 F 16 and 80 F 27 C is maintained e Air filters are installed in the system and maintained during construction replaced as appropriate during construction and upon completion of construction are replaced The input rate and temperature rise are set per the furnace rating plate input rate and temperature rise are set per the furnace rating plate 10095 outside air is provided for combustion air re quirements during construction Temporary ducting can be used NOTE Do not connect the temporary duct directly to the furnace The duct must be sized according to the instructions under Section V Combustion and Venti lation Air Requirements Section 5 3 3 e Thefurnace heat exchanger components duct sys tem air filters and evaporator coils are thoroughly cleaned following final construction clean up e Allfurnace operating conditions including ignition in put rate temperature rise and venting are verified ac cording to these installation instructions NOTE The Commonwealth of Massachusetts requires that the fo
194. cessary to follow both Fix 3 and Fix 4 Check 4 Debris in Cleanout A cleanout dropleg must be present such that the upper edge of the cleanout cover is at least 12 inches below the lower edge of the lowest chimney inlet opening A chimney without a cleanout could become partially blocked by debris If no cleanout is present the chimney must be refined Fix 4 Remove the cleanout cover and examine the cleanout for debris If significant amounts of any of the following are found Fueloil residue e Bricks Mortar or sand Pieces ofthe tile liner e Rusted pieces of the metallic liner reline the chimney Fix 4 Check 5 Liner Condition If a metal liner is present it must be checked It cannot be assumed that all existing metal liners are correctly installed and in good condition Remove the lowest existing vent connector and examine the inside of the elbow or tee at the base of the liner A small amount of soot may be considered acceptable provided the installer vacuums it away If rusted pieces of the liner have collected here the metal liner must be removed and replaced Fix 4 Next gently tap the inside of the liner with a Phillips screw driver If the screwdriver perforates the liner or if the tapping does not sound like metal hitting metal the liner must be removed and replaced Fix 4 Remember that all appliances must be vented inside the liner Venting one appliance inside the liner and ano
195. ch Kit High Altitude Pressure Switch Kit High Altitude Propane Gas Kit High Altitude Natural Gas Kit Propane Gas Conversion Kit Media Air Cleaner UIA045A30 UIA045B30 UIA045CA30 UIA070A30 UIA070B30 x x x x LM M x 220 XI XI x 2 Moa x xt UIA070B40 UIA070CA40 UIA090A30 UIA090B30 UIA090CA30 UIA090B50 090 50 UIA115A40 UIA115B40 UIA115CA40 UIA115A50 UIA115B50 UIA115CA50 UIA140A50 UIA140B50 UIA140CA50 CIA045A30 CIA045CX30 CIA070A30 CIA070CX30 CIA070A40 CIA070CX40 CIA090A30 CIA090CX30 CIA090CX50 CIA115A40 CIA115CX40 CIA115CX50 gt lt Common Vent Kit CVK4 dd lololol x 161046 x Jola T T TT tole XI Tale el x xx TL L ILI 2 2 02 1 410 1601 1111 olol xt xixi 1010 xix LI xix 21010 4 4 4 3 1 1 2151 1
196. cific gravity and BTU con tent of the gas being consumed The only time resizing is required is when a reduction in firing rate is required for an increase in altitude Orifices should be treated with care in order to prevent dam age They should be removed and installed with a box end wrench in order to prevent distortion In no instance should an orifice be peened over and redrilled This will change the angle or deflection of the vacuum effect or entraining of pri mary air which will make it difficult to adjustthe flame prop erly This same problem can occur if an orifice spud of a different length is substituted warnina HIGH VOLTAGE Disconnect ALL ELECTRICAL POWER AND SHUT OFF GAS SUPPLY BEFORE SERVICING OR INSTALLING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 Check orifice visually for distortion and or burrs 2 Check orifice size with orifice sizing drills If resizing is required a new orifice of the same physical size and angle with proper drill size opening should be installed GAS STREAM P The length of Dimension A determines the angle of Gas Stream B DENT OR 74 BURR GAS A dent or burr will cause a severe deflection of the gas stream S 17 HIGH ALTITUDE APPLICATION USA When these furnaces are installed at high altitude the ap propriate High Altitude Orifice or Pressure Switch Kit must be applied This
197. ctrodepositioned steel cabinet and 409 stainless steel tubular heat exchanger and stainless steel recouperative coil Gas Furnace Upflow Horizontal Condensing A Air Command 90 Furnace First Design Series Certified 40 90 furnace featuring integrated electronic ignition control silicon carbide mini ignitor electrodepositioned steel cabinet and 409 stainless steel tubular heat exchanger and stainless steel recouperative coil electrical junction box relocation from blower compartment to the burner compartment and incorporation of coarser threaded thumb screw and U clips instead of clinched inserts for engagement Gas Furnace Upflow Horizontal Condensing A Air Command 90 Furnace C Third Design Series X NOx Certified 40 9096 furnace featuring integrated electronic ignition control silicon carbide mini ignitor 316L Header Plates electrodepositioned steel cabinet and 409 stainless steel tubular heat exchanger and stainless steel recouperative coil electrical junction box relocation from blower compartment to the burner compartment and incorporation of coarser threaded thumb screw and U clips instead of clinched inserts for engagement Select models utilize a 2 row secondary recouperative coil ONLY the next to the manufacturing P number indicates the furnaces using a 2 row secondary recouperative coil Gas Furnace Counterflow Horizontal Condensing A Air Command 90 Furnace A First Design Series X NOx Certified 40 9096
198. curit sur la portion sup rieure de cette tiquette R gler le thermostat la temp rature la plus basse Couper l alimentation lectrique de l appareil Cet appareil m nager tant dot d un syst me d allumage automatique ne pas essayer allumer le br leur manuellement Torner le robinet a gaz dans le sens des aigilles d une montre en position OFF ARRET Attendre cinq 5 minutes pour laisser echapper tout le gaz Renifler tout autour de l appareil y compris pr s du plancher pour d celer une odeur de gaz Si c est le cas ARRETER Passer l tape B des instructions de s curiti sur la portion sup rieure de cette tiquette S il n y a pas d odeur de gaz passer l tape suivant 7 Tourner le robinet a gaz dans le sens inverse des aigilles d ne montre F en pos Remettre en place le panneau d acc s Mettre l appareil sous tension 10 R gler le thermostat la temp rature desir e 11 Si l appareil ne se met pas en marche suiyre les instructions intitul es Comment coupler l admission de gaz de l appereil et appeler un technicien qualifi ou le fourrnisseur de gaz Bom 1 Set the thermostat to lowest setting 2 Turn off all electric power to the appliance if service is to be performed 3 Turn the gas control knob clockwise 4 to OFF Position Do not force 4 Replace control access panel TURN OFF GAS
199. cycle the gas valve closes The induced draft blower runs and the air circulator blower runs at Heating speed same symptoms as trip on high limit This will continue until the rollout thermostat is manually reset The probable cause is either incorrect gas pressures improper burner alignment faulty orifice s or restricted crossover gap s OTHER ITEMS A D Lockout see previous Numbers 1 4 5 The gas valve ignitor and induced draft blower are de energized imme diately Exception If a trip on high auxiliary rollout limit is combined with a lockout the induced blower will re main energized until the limit closes The air circulator blower runs for 90 seconds and then shuts off To manually end a lockout interrupt the call for heat for at least 1 second but not more than 20 seconds To automatically end a lockout wait three hours The control will automatically reset itself and try again Constant Fan During normal operation the air circula tion blower will continually run at Cooling speed as long as power is present at terminal If a call for heat occurs the blower will continue to run at cooling speed throughout the heating cycle If a trip on high auxiliary rollout limit occurs the air cir culation blower will run at Heating speed Even if power is present at the G terminal the blower will run at heat ing speed until the limit closes Cooling Operation With the thermostat in the COOL FAN
200. d The 30 second delay feature on the circulator speed eliminates the possibility of tripping the high primary limit when the high stage flue products are traveling through the heat exchanger upon a call for low stage heat R and W1 or R and W1 and W2 thermostat contacts open completing the call for heat The control turns the gas valve off extinguishing flame After a five second delay while flue products are purged from the heat exchanger the induced draft blower motor is turned off the induced draft blower is on low speed during the five second post purge Humidifier terminals are de energized The air circulator blower has an adjustable delay off tim ing of 60 90 120 or 180 seconds starting from the time the gas valve closes The speed s run during this period depend on the last heat call seen by the thermo stat If the last call for heat was a call for low heat the air circulator blower will run on the low heat speed for the duration of the adjusted delay off timing 60 90 120 or 180 seconds If the last call for heat was a call for high heat the air circulating blower run on the high heating speed for thirty seconds and then switch to the low heating speed for the balance of the adjusted delay off timing 30 60 90 or 150 seconds Electronic air cleaner terminals are de energized Furnace awaits next call from thermostat 99 SYSTEM OPERATION Cooling Mode The normal operational sequence in coo
201. d Bunoeuuoosip 9S00 10 OBA N32 Mol ye s eis re M o Jemod CAP PERS SWEM 11040 440 15 Salim jeuuouqv ajqissod 1ne4 io 5101010 WANNI 104 147 SERVICING Motor Viewed from Plug End OUT 8 116 OUT ADJUST 7 115 fan 1 6 14 2 15 113 HT W2 DELAY 4 12 24VAC 2 3 11 HEAT W Wi 2 10 Speed COMMON 1 1 9 Rev Valve CONTROL CONNECTOR Motor Viewed from connector end HiGH VOLTAGE ON CONTROL PINS WILL DESTROY MOTOR Do not apply 24 volts to terminals Out or Out Make sure connector is fully seated Make sure pins are fully seated in connector housing Verify C1 and C2 are connected to transformer common Verify R is connected to transformer hot After verifying above connections motor can be tested by applying 24 volts to control pins Example R to G will cause the fan to come at Fan Only
202. d control module performs safety circuit checks Induced draft blower is energized causing pressure switch contacts to close Humidifier terminals are energized with induced draft blower 4 warm up begins upon close of pressure switch contacts Note HSI 2 ignition control has a fixed standard seven secondignitor warm up period and the White Rodgers 50455 50T55 ignition control has a variable standard ignitor warm up period between a 17 second maximum and a five second minimum 5 Gas valve opens at end of ignitor warm up period deliv ering gas to burners and establishing flame 6 Integrated control module monitors flame presence Gas valve will remain open only if flame is sensed 7 Circulator blower is energized on heat speed following a fixed thirty second blower on delay Electronic air cleaner terminals are energized with circulator blower 8 Furnace runs integrated control module monitors safety circuits continuously 9 Rand W thermostat contacts open completing the call for heat 10 Gas valve closes extinguishing flame 11 Induced draft blower is de energized following a fifteen second post purge Humidifier terminals are de energized 12 Circulator blower is de energized following a selectable heat off delay period 60 90 120 or 180 seconds Elec tronic air cleaner terminals are de energized Note The 50T55 Ignition Control used on GCLA AX CX GULA AX CX GUIE EX mode
203. d the circuit between the igni tion control and gas valve will be interrupted LINE VOLTAGE NOW PRESENT 1 Remove the burner compartment door to gain access to the rollout switch es mounted to burner bracket The servicer should reset the ignition control by opening and closing the thermostat circuit Then look for the ignitor glow ing which indicates there is power to the ignition control Measure the voltage between each side of the rollout control and ground while the ignition control tries to power the gas valve 2 Measure the voltage between each side of the rollout control and ground during the ignition attempt Refer to the following figure VOLT OHM METER 9 COLOR IDENTIFYING TAB Checking Flame Rollout Switch 80 amp 9096 Furnaces a If no voltage is measured on either side of control it indicates ignition control or wiring to control problem SERVICING b If voltage is measured on one side of the control and not the other it indicates the control is open If voltage is measured on both sides of the control the wiring to gas valve or valve is a fault 3 After check and or replacement of rollout switch rein stall burner compartment door and verify proper unit op eration 5 8 CHECKING PRESSURE CONTROL The pressure control is a safety device to prevent the com bustion cycle from occurring with inadequate venting caused by a restricted or blocked vent pipe on the 80 and 90
204. duce air rush noise 3 High voltage is present at these motors all the time Motor operation is controlled through the low voltage motor in terface board On GUIV CA DX and GUVA AX models a motor interface board mounted on the control bracket is used to control blower operation in 3 modes of operation Fan only cooling speed and heating speed Refer to the Airflow Charts in fur nace Technical Manuals for details The cooling and heating speeds are adjusted by relocating the jumper pins on the motor interface board There is a LED located on the blower interface board on GUIV CA DX FX and GUVA AX models or on the integrated ignition control on GCVA and GUVA BX models that serves to indicate the airflow that the motor is supposed to be deliv ering depending upon the positioning of the pin selectors on the interface board on the GUIV CA DX FX and GUVA AX models or on the DIP switches on the integrated ignition control on the GCVA and GUVA BX models The number of blinks multiplied by 100 yields the programmed CFM Ex ample 10 Blinks x 100 1000 The indicated may vary depending on the mode of operation and the sig nals being sent to the control board at the time ECM ICM Control Connections Control functions G Y Y1 Y2 W W1 W2 may be active at less than 1 2 control voltage i e 12 volts Relay con tacts on control functions must reliably switch low currents less than 5 MA Some thermostats with t
205. e Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Pressure Switch Kit High Altitude Propane Gas Kit High Altitude Natural Gas Kit Propane Gas Conversion Kit Media Air Cleaner GUIB045A30 GUIB045B30 GUIB045CX30 GUIB070A30 GUIB070B30 GUIB070CX30 GUIB070A40 GUIB070B40 GUIB070CX40 GUIB090A30 E 2 EN E GUIB090B30 EZ z EN x Em le 6 111 1111 xt x x 1 11 BB o 1 2 T Tol Lx Lx BIB Ix x x x x x x Bl 2 Tae XIX X X xX 2 2 2 XIX X X xX 2 XIX X X xX 2 m 2 XIX X X xX XIX X X xX XIX X X xX XIX X X xX XIX X X X 1 4 LX x 2 GUIB140A50 fete lue cmozgago xx 19 CIBO70A40 IxIx x x B x x lolol CIB090A30 x BI 2 2 1 090 50 x BI x x 1 T 2 2
206. e listed Too great of an external static pressure will result in in sufficient air that can cause excessive temperature rise resulting in limit tripping etc Whereas not enough static may result in motor overloading To determine proper air movement proceed as follows 1 With clean filters in the furnace use a draft gauge inclined manometer to measure the static pressure negative pressure of the return duct at the inlet of the furnace Between the furnace and filter 2 Measure the static pressure positive pressure of the supply duct Between the furnace and evaporator Coil 3 Add the two 2 readings together for total external static pressure 159 SERVICING NOTE Both readings may be taken simultaneously and read directly on the manometer if so desired If an air condi tioning coil or Electronic Air Cleaner is used in conjunction with the furnace the readings must also include these com ponents as shown in the following drawing 4 Consult proper tables for the quantity of air If the total external static pressure exceeds the minimum or maximum allowable statics check for closed dampers reg isters undersized and or oversized poorly laid out duct work SUPPLY AIR gt CUTAWAY OF DUCTWORK _ TO EXPOSE COIL INCLINED MANOMETER RETURN AIR Checking Static Pressure 80 Furnace Shown 90 Similar S 22 CHECKING TEMPERATURE RISE The more ai
207. e minimum clearance information for this furnace is pro vided on the unit s clearance label These clearances must be permanently maintained Refer to Specification Sheet for minimum clearances to combustible materials Clearances must also accommodate an installation s gas electrical and drain trap and drain line connections If the alternate combustion air intake or vent flue connections are used on a 90 furnace additional clearances must be provided to accommodate these connections Refer to Vent Flue Pipe and Combustion Air Pipe section in this manual or the in stallation instructions for details NOTE In addition to the required clearances to combustible materials a minimum of 36 inches service clearance must be available in front of the unit A furnace installed in a confined space i e a closet or utility room must have two ventilation openings with a total minimum free area of 0 25 square inches per 1 000 BTU hr of furnace input rating One of the ventilation openings must be within 12 inches of the top the other opening must be within 12 inches of the bottom of the confined space In a typical construction the clearance between the door and door frame is usually adequate to satisfy this ventilation re quirement 43 PRODUCT DESIGN FURNACE SUSPENSION If suspending the furnace from rafters or joist use 3 8 threaded rod and 2 x2 x1 8 angle iron as shown in the fol lowing figure If the furnace is installed in a crawl
208. e secured using a PVC or ABS elbow or coupling using the appropriate glue see Materials and Joining Methods section in this manual or the installa tion instructions for further details NOTE For non direct vent installations a minimum of one 90 elbow must be installed on the combustion air intake coupling to guard against inadvertent blockage Combustion Air Pipe 90 Furnaces Only Direct Vent Installations On upflow units secure the combustion air intake pipe di rectly to the air intake coupling On counterflow units se cure the combustion air intake pipe to the air intake cou pling using the rubber coupling and worm gear hose clamps provided with the unit The counterflow rubber coupling al lows service removal of air intake piping internal to the fur nace blower compartment NOTE Because of probable ma terial conflicts do not use other commercially available no hub connectors The combustion air intake pipe can also be secured directly to the counterflow unit air intake pipe coupling Non Direct Vent Installations A minimum of one 90 elbow must be installed on the com bustion air intake coupling to guard against inadvertent blockage 56 COMBUSTION VENT FLUE PIPE Mcr VENT FLUE AIR PIPE DIRECT VENT ONLY PIPE DIRECT VENT ONLY 90 PVC ELBOW NON DIRECT VENT RUBBER ELBOW COUPLINGS NON DIRECT VENT WITH WORM E GEAR CLAMPS RUBBER COUPLING WITH WORM GEAR CLAMPS Vez UP
209. egrated electronic ignition control silicon nitride ignitor two stage gas valve two speed induced draft blower variable spped circulator blower prepainted steel cabinet and 409 stainless steel tubular heat exchanger GUVA BX P1234701F P1234706F Gas Furnace Upflow Horizontal Variable Speed 2 Stage Condensing A Air Command 95 Furnace B Second Design Series X NOx Certified 40 95 two stage variable speed furnace featuring intell ignition integrated electronic P1239601F P1239606F ignition control silicon nitride ignitor two stage gas valve two speed induced draft P1242101F 1242106 blower variable speed circulator blower prepainted steel cabinet and 409 stainless steel tubular heat exchanger electrical junction box relocation from blower compartment to the burner compartment and incorporation of coarser threaded thumb screw and U clips instead of clinched inserts for engagement GUVA BX Gas Furnace Upflow Horizontal Variable Speed 2 Stage Condensing Air Command 95 Il Q Furnace C Third Design Series X NOx Certified 40 95 two stage variable speed furnace featuring intell ignition integrated electronic ignition control silicon nitride ignitor two stage gas valve two speed induced draft blower variable speed circulator blower prepainted steel cabinet and 409 stainless steel tubular heat exchanger 316L Header Plates Silicon Gasket electrical junction box relocation from blower compar
210. el pipe and fittings for the building piping 2 Use pipe joint compound on male threads only Pipe joint compound must be resistant to the action of the fuel used 3 Use ground joint unions Install a drip leg to trap dirt and moisture before it can enter the gas valve The drip leg must be a minimum of three inches long 5 Install a 1 8 NPT pipe plug fitting accessible for test gage connection immediately upstream of the gas sup ply connection to the furnace 6 Usetwo pipe wrenches when making connection to the gas valve to keep it from turning The orientation of the gas valve on the manifold must be maintained as shipped from the factory 7 Install amanual shutoff valve between the gas meter and unit within six feet of the unit If a union is installed the union must be downstream of the manual shutoff valve between the shutoff valve and the furnace 8 Tighten all joints securely 9 Connectthe furnace to the building piping by one of the following methods Rigid metallic pipe and fittings Semi rigid metallic tubing and metallic fittings Alu minum alloy tubing must not be used in exterior locations In order to seal the grommet cabinet penetration rigid pipe must be used to reach the outside of the cabinet A semi rigid connector to the gas piping may be used from there 10 Use listed gas appliance connectors in accordance with their instructions Connectors must be fully in the same room as the furnace
211. els covered and the changes per each model group from one release to the next Model Manufacturing Description Gas Furnace Upflow Horizontal Induced Draft C Air Command 80 SSE Furnace Third Design Series X NOx Certified GUIC CX P1207401F P1207408F 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft C Air Command 80 SSE Furnace Third Design Series X NOx Certified 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor prepainted textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft C Air Command 80 SSE Furnace Third Design Series X NOx Certified 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Change from embossed bottom knock out to perforated bottom knock out and addition of internal side filter retention Gas Furnace Upflow Horizontal Induced Draft C Air Command 80 SSE Furnace Fourth Design Series A Standard Unit not NOx certified 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor prepainted textured steel cabinet and 409 stainless steel tubular heat exchanger
212. em may be too large to properly vent the remaining attached appliances For complete details refer to Existing Furnace Removal sec tion of this manual When resizing any portion of the common venting system use the appropriate table in Appendix in the latest edition of the National Fuel Gas Code 54 ANSI Z223 1 Upflow or Horizontal units are shipped with the induced draft blower discharging from the top of the furnace is as viewed for an upflow installation The induced draft blower can be rotated 90 degrees counterclockwise for Category I venting with the airflow horizontal left to right Refer to the following figure For horizontal installations a four inch single wall pipe can be used to extend the induced draft blower outlet 1 2 beyond the furnace cabinet Vent the furnace in accordance with the National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition In Canada vent the furnace in accor dance with the National Standard of Canada CAN CGA B149 1 and CAN CGA B149 2 latest editions and amend ments 8096 Upflow Rotated Induced Draft Blower 48 Counterflow units are shipped with the induced draft blower discharging from the top of the furnace Top as viewed for a counterflow installation The induced draft blower can be rotated 90 degrees counterclockwise for Category venting with the airflow horizontal right to left Figure 6 For horizon tal installations a three inc
213. ements and glues antistatic fabric softeners for clothes dryers and masonry acid washing materials Sealoff a non direct ventfurnace if it is installed near an area frequently contaminated by any of the above substances This protects the non direct ventfurnace from airborne contaminants To ensure that the en closed non direct ventfurnace has an adequate sup ply of combustion air vent from a nearby uncontami nated room or from outdoors Refer to the Combus tion and Ventilation Air Requirements section in this manual or the installation instructions for details e f the furnace is used in connection with a cooling unit install the furnace upstream or in parallel with the cooling unit coil Premature heat exchanger fail ure will result if the cooling unit coil is placed ahead of the furnace Ifthe furnace is installed in a residential garage posi tion the furnace so that the burners and ignition source are located not less than 18 inches 457 mm above the floor Protect the furnace from physical damage by vehicles Ifthe furnace is installed horizontally the furnace ac cess doors must be vertical so that the burners fire horizontally into the heat exchanger Do not install the unit with the access doors on the or down bottom side of the furnace CLEARANCES AND ACCESSIBILITY Installations must adhere to the clearances to combustible materials to which this furnace has been design certified Th
214. emperature rise Refer to Circulator Blower Speed section in the Product Design section of this manual for speed changing de tails Temperature rise is related to the BTUH output of the furnace and the amount of air CFM circulated over the heat exchanger Take motor amperage draw to de termine that the motor is not overloaded during adjust ments ACCESSORY WIRING DIAGRAMS HIGH VOLTAGE WARNING DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH FURNACE COMMON VENT KIT CVK4 7 8096 Furnaces with White Rodgers 50A50 Integrated Ignition Control This wiring diagram is for reference only Not all wiring is as shown above refer to the appropriate wiring diagram for the unit being serviced For use only with 8096 Single Stage Furnaces N O NORMAL SERVICE VENT DAMPER HIGH WH VOLTAGE 33 JUNCTION BOX WH COMBUSTION VT BLOWER Point to Point Wiring 161 ACCESSORY WIRING DIAGRAMS HIGH VOLTAGE WARNING DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH FURNACE COMMON VENT
215. en Thermal Protection Device If the primary high limit auxiliary limit or rollout limit control opens the gas valve is de energized Both the induced draft blower motor and air circulator blower are energized on low heat speed The diagnostic light code for this problem is four short flashes followed by a longer pause Ifthe primary or auxiliary limit is open the probable cause is either low conditioned air flow due to dirty filter or high resistance in duct work faulty limit faulty blower or blower speed set too low The primary limit will automatically reset while the auxiliary limit control must be manually reset If the rollout limit control is open the probable cause is insufficient combustion air restricted flue passage or restricted heat exchanger The rollout limit control must be manually reset 6 Flame Sensed with No Call for Heat If the control senses a flame when the gas valve is de energized it will run the induced draft blower and air circulator blower con tinuously on the low heat speed for each The diagnostic light code for this problem is continuous flashing The probable causes are either a short to ground in flame sense circuit miswiring lingering burner flame or a slow closing gas valve SYSTEM OPERATION wedau aoud 440 Jamod uin ped Jedoud yep peonpur sleep Buidid 10 uonoes pue
216. en natural and propane gas High altitude installations may require both a pressure switch and an orifice change These changes are necessary to com pensate for the natural reduction in the density of both the gas fuel and the combustion air at higher altitude Refer to the Accessories Charts in this manual or product Specification Sheet for a tabular listing of appropriate manufacturer s kits for propane gas and or high altitude in stallations The indicated kits must be used to insure safe and proper furnace operation All conversions must be per formed by a qualified installer or service agency Vent Flue Pipe and Combustion Air Pipe 9096 Furnaces Only FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN BODILY INJURY OR DEATH CAREFULLY READ AND FOLLOW ALL INSTRUCTIONS GIVEN IN THIS SECTION UPON COMPLETION OF THE FURNACE INSTALLATION CAREFULLY INSPECT THE ENTIRE FLUE SYSTEM BOTH INSIDE AND OUTSIDE THE FURNACE TO ASSURE IT IS PROPERLY SEALED LEAKS IN THE FLUE SYSTEM CAN RESULT IN SERIOUS PERSONAL INJURY OR DEATH DUE TO EXPOSURE TO FLUE PRODUCTS INCLUDING CARBON MONOXIDE condensing gas furnace achieves its high level of efficiency by extracting almost all of the heat from the products of combustion and cooling them to the point where condensa tion takes place Because of the relatively low flue gas tem perature and water condensation requirements PVC pipe is used as venting material This furnace must not be connected
217. encher une explosion ou un incendie D Ne pas se servir de cet appareil s il a t plong dans l eau compl tement ou en partie Appeler un technicien qualifi pour inspecter l appareil et remplacer tout partie du syst me de contr le et toute commande qui ont t plong s dans l eau BE OPERATING INSTRUCTIONS Bo 11 If the appliance will not operate STOP Read the safety information above on this label 2 Setthe thermostat to lowest setting Turn off all power to the appliance This appliance is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand 5 Turn the gas control knob clockwise to OFF Position Do not force 6 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you then smell gas STOP Follow B in the safety information above on this Label ROBINET A GAZ If you don t smell gas go to MANUEL EN POS next step 7 Turn gas control knob counterclockwise to GAS 8 Replace access panel _ INLET 9 Turn on all electric 9 2 lt power to the appliance CON 9 10 Set thermostat to desired setting ARRIVEE DU GAZ follow the instructions To Turn Off Gas To Appliance and call your service technician or gas company MANUAL GAS KNOB SHOWN IN ON POSITION ARRETER Lisez les instructions de s
218. ent and incorporation of coarser threaded thumb screw and U clips instead of clinched inserts for engagement 13 PRODUCT IDENTIFICATION This section will identify the models covered and the changes per each model group from one release to the next Model Manufacturing Description P1252701F Gas Furnace Counterflow Horizontal Condensing Air Command 90 Furnace C Third P1252702F Design Series X NOx Certified 40 9096 furnace featuring integrated electronic ignition GECA CX P1252703F control silicon nitride ignitor electrodepositioned steel cabinet and 409 stainless steel E tubular heat exchanger and stainless steel recouperative coil Select models utilize a 2 row secondary recouperative coil ONLY the next to the manufacturing number indicates the furnaces using a 2 row secondary recouperative coil Gas Furnace Counterflow Horizontal LCondensing Furnace A Air Command 90 Furnace A First Design Series X NOx Certified GCLA AX P1249802F P1249806F 40 90 single stage furnace featuring an integrated electronic ignition control prepainted textured steel cabinet Silicon Carbide Mini Igniter and aluminized steel tubular heat exchanger Gas Furnace Counterflow Horizontal LCondensing Furance A Air Command 90 Furnace C Third Design Series X NOx Certified 40 9096 furnace featuring integrated m electronic ignition control carbide mini nitride ignitor electrodepositioned steel cabinet GELA
219. er On and Door Interlock Switch closed LINE VOLTAGE NOW PRESENT 149 SERVICING Using a hookup as shown above take the amperage and voltage readings and use them in the formula Capacitance MFD 2650 x Amperage Voltage 4 After completing check and or replacement of capaci tor reinstall blower compartment door 5 electrical power and verify proper unit operation S 11 CHECKING GAS VALVE Redundant A combination redundant operator type gas valve which pro vides all manual and automatic control functions required for gas fired heating equipment is used The valve provides control of main burner gas flow pressure regulation and 100 percent safety shut off warnina HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH Remove wire connections from gas valve terminals 2 Using an ohmmeter test across the gas valve coil termi nals both the redundant and the main valve 3 Should read approximately 130 Ohms for the Robert shaw main valve operator coils and 100 Ohms for Honeywell The redundant coil will vary somewhat as well 4 Reverse leads some redundant coils have dividers di odes Resistance of the redundant and 2nd stage coils on White Rodgers 36E series gas valves can t be measured at the valve terminals with an ohmmeter because of diodes
220. er is de energized Electronic air cleaner terminals are de energized 7 Furnace awaits next call from thermostat SYSTEM OPERATION HEATING TIMING CHART FOR WHITE RODGERS 50 55 50 55 AND HEATCRAFT HSI 2 INTEGRATED IGNITION CONTROL OPERATION CIRCULATOR ON BLOWER OFF GAS VALVE OPEN CLOSED ON IGNITER OFF PRESSURE SWITCH CLOSED CONTACTS OPEN ON INDUCED DRAFT BLOWER ON THERMOSTAT OFF SECONDS 0 tign tcirc 0 15 d or cr 180 WARM UP PERIOD ON DELAY for 50A55 see note 30 SECONDS BO Sesonds Fixed for 50T55 NOTE HEATCRAFT INTEGRATED CONTROL MODULE HAS A FIXED STANDARD SEVEN SECOND IGNITER WARM UP PERIOD MINI IGNITER WHITE RODGERS INTEGRATED CONTROL MODULE HAS A VARIABLE STANDARD IGNITER WARM UP PERIOD BETWEEN A 17 SECOND MAXIMUM AND A FIVE SECOND MINIMUM COOLING TIMING CHART FOR WHITE RODGERS 50 55 50 55 AND HEATCRAFT HSI 2 INTEGRATED IGNITION CONTROL OPERATION Indoor Fan Outdoor Fan and Compressor Thermostat Seconds 0 5 0 45 91 SYSTEM OPERATION ABNORMAL OPERATION 80 or 90 Models with White Rodgers 50A55 50T55 or HSI 2 Integrated Ignition Control The following presents the probable causes of questionable furnace operation and how to fix them Look through the observation window in the blower access door and make a note of the number of flashes in sequence between pauses Next refer to the Troubleshooting Chart on the following p
221. ermostat can be connected to G on the furnace two stage integrated control module G on the cir culator blower interface board Y1 on the circulator blower interface board single stage cooling or no cooling or Y on the furnace tow stage integrated control module no cool ing In CONTINUOUS FAN mode the circulator blower speed will differ depending on which connection is used 77 PRODUCT DESIGN 1 application If G from the thermostat is connected to G on the furnace two stage integrated control module then the continuous fan blower speed will be the same as the selected ow stage heating speed tap If G from the thermostat is connected to G on the circulator blower interface board then the continuous fan blower speed will be 72 of the selected high stage cooling speed tap NOTE The EAC Electronic Air Cleaner terminals on the two stage integrated control module will not ener gize using this method To energize the EAC terminals the G wire from the thermostat must be connected directly to the G terminal on the two stage integrated control module 2 In two stage heating single stage or no cooling appli cations If G from the thermostat is connected to Y1 on the circulator blower interface board then the continuous fan blower speed will be 65 of the selected high stage cooling speed tap NOTE The EAC Electronic Air Cleaner terminals on the two stage integrated control module
222. es utility rooms or parking areas because of NSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER the danger of carbon monoxide CO poisoning resulting from the exhaust SERVICE AGENCY OR THE GAS SUPPLIER emissions If a furnace or air handler is installed an enclosed area such as a garage utility room or parking area and a carbon monoxide producing device is operated therein there must be adequate direct outside ventilation 4 WARNING This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing device continues to operate in the enclosed area Carbon monoxide emissions can be re circulated SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF TURN throughout the structure if the furnace or air handler is operating in any 5 mode OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY CO can cause serious illness including permanent brain damage or death B10259 216 To locate an authorized servicer please consult your telephone book or the dealer from whom you purchased this product For further assistance please contact CONSUMER INFORMATION LINE AMANA BRAND PRODUCTS TOLL FREE 1 877 254 4729 U S only email us at hac consumer affairs amanahvac com fax us at 931 438 4362 Not a technical assistance line for dealers Outside the U S call 1 931 433 6101 Not a technical assistance line for de
223. essure dropin lines between regulators and between second stage regulator and the appliance Pipe size will depend on length of pipe run and total load of all appli ances 68 Complete information regarding tank sizing for vaporization recommended regulator settings and pipe sizing is avail able from most regulator manufacturers and propane gas suppliers Since propane gas will quickly dissolve white lead and most standard commercial compounds special pipe dope must be used Shellac based compounds resistant to the actions of liquefied petroleum gases such as Gasolac Stalactic Clyde s or John Crane are satisfactory Refer to the following illustration for typical propane gas in stallations and piping 5 to 15 PSIG 20 PSIG Max First Stage Regulator Continuous 11 W C 200 PSIG Second Stage Maximum Regulato 5 Typical Propane Gas Installation THE GAS FURNACE IS INSTALLED IN A BASEMENT AN EXCAVATED AREA OR A CONFINED SPACE IT IS STRONGLY RECOMMENDED TO CONTACT A PROPANE SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK SINCE PROPANE GAS IS HEAVIER THAN AIR ANY LEAKING GAS CAN SETTLE IN ANY LOW AREAS OR CONFINED SPACES PROPANE GAS ODORANT MAY FADE MAKING THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE UNDETECTED GAS LEAK WILL CREATE A DANGER OF EXPLOSION OR FIRE THE PRESENCE OF GAS IS SUSPECTED FOLLOW THE INSTRUCTIONS ON THE C
224. etween each of the motor leads 4 Touch one probe of the ohmmeter to the motor frame ground and the other probe in turn to each lead If the windings do not test continuous or a reading is ob tained to ground replace the motor 5 After completing check and or replacement of circulator blower motor or induced draft blower motor reinstall blower compartment door 6 Turnon electrical power and verify proper unit operation S 9A CHECKING VARIABLE SPEED AIR CIRCU LATOR BLOWER MOTOR The 8096 and 9096 Two Stage Variable Speed furnaces in corporate the GE ICM or variable speed blower motors for greater efficiency ECM ICM motors vary the motor RPMs to provide a set volume of air over a wide range of conditions These motors use an electronic control module attached to the motor to control motor operation Some unique features of these motors 144 1 Constant Airflow These motors will maintain constant airflow in excess of 80 static In other words as the static increases so does the motors RPM so that a con stant CFM is maintained NOTE The motor in these units will move more air under higher static conditions than a similar sized unit using a PSC motor Because this motor does not load up and re duce airflow like a PSC motor in some undersized duct installations this may cause noise or high airflow complaints 2 Ramp up Ramp down feature These motors ramp up and down at the beginning or end of a cycle to re
225. euo 19591 22 1 SALON Buiusey si 037 10 pue OU pesues ueeq seu uoneJedo eoeuunj OU uni 1 pue Buiuse 4 enjeA 886 MOIS 10 eue 1euunq 10sues 10 108468 JIOUS 129410 esues 1046 Buum 198109 pue Messeoeu Buum pejoeuuoosiu JO 85007 Seuse 4 eoueuuoped 10 peonpul pee edid Tui ny seuse j 400 pue eq si 037 9nsouBeip 1edoud 104 Y90949 enp uedo 5 1edoud 10 sieuinq Y90949 pue 199 109 pue
226. ff PS2 Closed Bisse PS1 Closed Open Switches E High Induced Draft Low Blower High Thermostat Call for Heat Off 0 10 5 64 0 15 30 60 90 120 or 4 second Time 180 maximum trial for ignition period Example 2 Continuous Call For High Stage Heat Only Air High Circulator Low Blower High Gas Valve Low Off Igniter On Off PS2 Closed Pressure PS1 Closed Switches Open High Induced Draft Low Blower Off High Thermostat Low Call for Heat Off k i 0 10 5 64 0 15 30 60 90 120 4 second Time sec 180 maximum trial for ignition period 116 SYSTEM OPERATION HEATING TIMING CHARTS FOR WHITE RODGERS 50M61 288 TWO STAGE INTEGRATED IGNITION CONTROL OPERATION Example 3 High Circulator Low Blower Off High Gas Valve Low Off Igniter On Off PS2 Closed Pressure PS1 Closed Switches Open Induced Draft High Blower Low Off Thermostat High Call For Heat Low Off 0 10 Example 4 High Circulator Low Blower Off High Gas Valve Low Off Igniter On Off PS2 Closed Pressure PS1 Closed Switches Open High Induced Draft Low Blower Off High Thermostat Low Call For Heat 0 10 Initial Call For Low Heat Change To High Heat Call Change to High Heat 64 0 15 30 60 90 Time sec 120 4 second 180 maximum trial for ignition period Initial Call For High Heat Subsequent Call To Low Heat Call Change to Low Heat T 30 Seconds After Call Ch
227. flame or lazy burner flame due to improper gas pressure or combustion air 8 Ignitor Circuit Problem If the furnace fails to operate due to a problem with the ignitor The diagnostic code for this problem is eight flashes followed by a pause The probable cause is either loose or misconnected wir ing or a bad ignitor 9 Furnace Operating on Low Stage Gas with High Stage Induced Draft Blower and High Stage Circu lator Blower If the furnaces high stage pressure switch circuit fails to close in response to high stage induced draft blower operation The diagnostic light code for this problem is nine flashes followed by a pause The prob able causes are either a blocked pinched or discon nected hose to the pressure switch faulty pressure Switch loose or misconnected wiring restricted air in take or flue piping blocked drain system or weak in duced draft blower 10 Flame Sensed with No Call for Heat If the control senses a flame when the gas valve is de energized it will run the air circulation blower and the induced draft blower continuously with no further furnace operation The diagnostic flash code for this is a continuous flash The probable causes are either a shortto ground in flame sense circuit miswiring lingering burner flame or a slow closing gas valve 125 SYSTEM OPERATION 39Vd LX3N NO LHVHO jueujeoe de4 Jedoud peonpur
228. flue and combustion air piping are available for upflow furnaces with left discharge In these positions the flue and combustion air piping can be run vertically through the side of the fur nace Refer to the following figure Recommended Installa tion Positions for further detail The standard piping con nections may also be used in these positions Refer to Vent Flue Pipe and Combustion Air Pipe section in this manual or the installation instructions for details concerning the con version to the alternate vent flue and combustion air con nections on the 9096 furnace gt gt ALTERNATE FLUE AND COMBUSTION AIR PIPE LOCATIONS ALTERNATE FLUE AND AIR 4 DISCHARGE COMBUSTION AIR PIPE Bottom Return Duct Connection 9 DISCHARGE UPFLOW COUNTERFLOW UPRIGHT UPRIGHT ALTERNATE FLUE AND ALTERNATE FLUE AND COMBUSTION AIR PIPE COMBUSTION AIR PIPE LOCATIONS LOCATIONS I J Botti tom AIR lt a Bud AIR DISCHARGE KIN Connection DISCHARGE UPFLOW HORIZONTAL COUNTERFLOW HORIZONTAL LEFT AIR DISCHARGE RIGHT AIR DISCHARGE oN Jf Botom NE gt i D N J COUNTERFLOW HORIZONTAL UPFLOW HORIZONTAL RIGHT AIR DISCHARGE LEFT AIR DISCHARGE 9096 Furnace Recommended Installation Positions NOTE Alternate vertical piping connections can not be used when an upflow 90 furnace is installed with supply air discharging to
229. flue coupling using a worm gear hose clamp Secure field supplied vent flue piping to the rubber elbow using a worm gear hose clamp NOTE Use of the alternate vent flue location for upright installations requires the drain trap be installed on the same side of the unit as the flue pipe PRODUCT DESIGN For horizontal installations externally secure the field sup plied vent flue pipe directly to the vent flue coupling using a PVC or ABS coupling or elbow CD 8 MC REMOVE v4 VE ae REMOVE 45 5 uh 4 SCREWS 8 gt SAC x 3 SCREWS amp f M REMOVE d 8 AND RELOCATE REMOVE RELOCATE 6 DETACH RUBBER DETATCH RUBBER ELBOW FROM ELBOW FROM ID BLOWER AND ID BLOWER AND VENT FLUE VENT FLUE PIPE PIPE UPFLOW COUNTERFLOW ADDITIONAL PLUG o EE J SS FROM DRAIN KIT 7 T EXTERNALLY MOUNT RUBBER ELBOW 6 SECURE TO 5 ID BLOWER WITH RUBBER COUPLING AND HOSE CLAMPS COUNTERFLOW UPRIGHT UPFLOW SIMILAR 6 SECURE ID BLOWER WITH RUBBER COUPLING 6 SECURE TO AND HOSE CABINET WITH CLAMPS SCREWS EE UPFLOW HORIZONTAL COUNTERFLOW SIMILAR 90 Furnace Alternate Vent Flue Location Alternate Combustion Air Intake Location 90 Furnaces Only
230. fold assembly on 8096 amp 90 furnaces as shown in the following illustrations E FLAME ROLLOUT SWITCH i N Ne Flame Rollout Switch Location 8096 Upflow Furnace Shown Counterflow Similar FLAME ROLLOUT SWITCHES gt So So oe Z gt TK Flame Rollout Switch Location 90 Upflow Furnace Shown Counterflow Similar 142 The control is designed to open should a flame roll out oc cur An over firing condition or flame impingement on the heat shield may also cause the control to open If the rollout control opens the air circulation blower and vent blower will run continuously On models with the White Rodgers 50A51 50 61 and 50V61 ignition controls the diagnostic light will flash four times These symptoms are identical to a trip of the primary limit control On models with the White Rodgers 50 50 50A55 or Heatcraft HSI 1 1A or HSI 2 ignition con trol the diagnostic light will flash five times indicating a trip of the rollout switch To aid in identifying these controls color coded labels have been affixed to the back of these controls Refer to the Rollout Limit Charts in furnace Technical Manual for temperature settings and color codes Ifthe rollout control has opene
231. for thirty seconds be fore switching to the low heat circulating speed The 30 second delay feature on the circulator speed eliminates the possibility of tripping the high primary limit when the high stage flue products are traveling through the heat exchanger upon a call for low stage heat R and W1 or R and W1 and W2 thermostat contacts open completing the call for heat The control turns the gas valve off extingushing flame After a five second delay while flue products are purged from the heat exchanger the induced draft blower motor is turned off the induced blower is on low speed during the five second post purge Humidifier terminals are de energized The air circulator blower fan has an adjustable delay off timing of 60 90 120 or 180 seconds starting from the time the gas valve closes The speeds run during this period depend on the last heat call seen by the thermo stat If the last call for heat was a call for low heat the air circulator blower will run on the low heat speed for the duration of the adjusted delay off timing 60 90 120 or 180 seconds If the last call for heat was a call for high heat the air circulator blower will run on the high heating speed for thirty seconds and then switch to the low heating speed forthe balance of the adjusted delay off timing 30 60 90 or 150 seconds Example A GUIVO90DX50 has the heating blower off delay set to 120 seconds by the installer When the ther
232. formed 3 Push the gas control lever to OFF Position Do force 4 Replace control access panel POUR COUPER L ADMISSION GAZ DE L APPAREIL 1 R gler le thermostat la temp rature la plus basse 2 Couper l alimentation lectrique de l appareil s il faut proc der des op rations d entretien 3 Pousse le levier du contr le du gaz OFF ARRET position Ne pas forcer 4 Remettre en place le panneau d acc s 11072707 23 OPERATING INSTRUCTIONS 24 FOR YOUR SAFETY READ BEFORE OPERATING LIRE AVANT DE METTRE EN MARCHELIRE WARNING If you do not follow these instructions explosion may result causing property damage ersonal injury or loss of life A This appliance does not have a pilot It is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand B BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to turn the gas control knob Never
233. ft 2 7 001 to 11 000 ft Not used in this application Note All installations above 7 000 ft require a pressure switch change Note For installations Canada the Amana 90 furnace is certified only to 4 500 ft Note The GUSA High Altitude Kits have not been determined to date Information will be provided when received Note GULA GCLA are shipped non direct vent but can be installed as direct vent by adding the intake air coupling and appropriate field supplied pipe 33 15 9 Sex 5 5 5 515 5 5 9 HA 6 einssejg sls sls YMS fale HA 6 einssejg jenjen sed jeanjen epniniy 29 epniniv 29 epniniv ee et 529 epniniv 0141 set euedoJg epniniv ubiH MAOH 21u92U02 1402 bx x x x gt lt V 0x14 Buruuim ooeuin4 Je bx x x x oos 21u04129 3 bx x x b x x eseg 10014 eseg 10014 eseg 10014 uonduoseg x
234. furnaces Also on the 90 furnaces there is a pressure con trol that will prevent the combustion cycle from occurring with inadequate condensate drainage due to a partial or blocked recouperator coil or drain warning HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 Remove burner compartment door to gain access to pres sure switch es 2 Remove wires from the pressure switch es electrical ter minals 3 Using a VOM check from common terminal to NC Nor mally Closed should read closed Check from Com mon to NO Normally Open should read open If switch reads as above proceed to Step 4 otherwise re place control 4 Remove the pressure control hose from the control and interconnect with an inclined manometer as shown in the following figures 3 INDUCED DRAFT BLOWER PRESSURE SWITCH PRESSURE SWITCH HOSE OPEN TO ATMOSPHERE HOSE TO INDUCED DRAFT BLOWER TAP Bi Oe INDUCED DRAFT BLOWER ID Blower Pressure Switch Negative Pressure Measurement 80 Upflow Furnace Shown Counterflow Similar INDUCED DRAFT BLOWER m PRESSURE SWITCH PRESSURE SWITCH HOSE OPEN TO ATMOSPHERE 1 4 TEE COIL COVER PRESSURE SWITCH A
235. g and cable Carefully rotate the control soasto gain access to the plug on the end of the cable Squeeze the release latch and gently pull the plug out of the control module Do not pull on the wires Grip the plug only 6 The control module is now completely detached from the motor Verify with a standard ohmmeter that the resis tance from each motor lead in the motor plug just re moved to the motor shell is greater than 100k ohms Measure resistance to unpainted motor end plate If any motor lead fails this test do not proceed to install the control module The motor is defective and must be replaced Installing the new control module will cause it to fail also 7 Merify that the replacement control module is correct for your application If so orient the new module next to the motor and carefully insert the plug removed in step 5 Be sure the plug latches It will click when properly inserted 8 Install the new control module back on the motor being careful to engage the locating pin into the appropriate mating motor hole Replace the two 1 4 hex head bolts Tighten the bolts snugly It is not necessary to over tighten Note Before replacing the blower motor assembly it is im portant to look at the installation to see if some application fault has caused the motor to fail Is there any evidence of water damage to the failed control Corrosion on the inside or outside of the casting If yes do moisture check 9 Re
236. g drawing illustrates the different styles of limit switches used on the 80 fur naces 139 SERVICING STYLE 1 amp 3 STYLE 2 Primary Limit Control Styles 8096 Furnaces 90 furnaces use a nonadjustable automatic reset Klixon type limit control part number 201629 Refer to the following drawing for location of the primary limit on the 90 furnaces PRIMARY LIMIT _ CONTROL 23 Primary Limit Control Location 9096 Upflow Furnace Shown Counterflow Similar The following drawing illustrates the style of limit switches used on the 9096 furnaces FRONT VIEW SIDE VIEW Primary Limit Control Style 9096 Furnaces 140 ENCLOSED DISK varie HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 Remove burner compartment door to gain access to the primary limit Remove low voltage wires at limit control terminals 3 With an ohmmeter test between these two terminals as shown in the following drawing Should read continu ous unless heat exchanger temperature is above limit control setting If not as above replace the control COLOR IDENTIFYING Volt Ohm SLEEVES Me
237. g flame 11 Induced draft blower is de energized following a fifteen second post purge Humidifier terminals are de energized 12 Circulator blower is de energized following a selectable heat off delay period 60 90 120 or 180 seconds Elec tronic air cleaner terminals are de energized 13 Furnace awaits next call from thermostat Cooling Mode The normal operational sequence in cooling mode is as fol lows 1 R and Y thermostat contacts close initiating a call for cool 2 Integrated control module performs safety circuit checks 3 Outdoor fan and compressor are energized 4 Circulator blower is energized on cool speed following a fixed five second on delay Electronic air cleaner termi nals are energized with circulator blower 5 Furnace circulator blower and outdoor cooling unit run integrated control module monitors safety circuits con tinuously 6 Rand Y thermostat contacts open completing the call for cool 7 Outdoor fan and compressor are de energized 8 Circulator blower is de energized following a fixed forty five second cool off delay period Electronic air cleaner terminals are de energized 9 Furnace awaits next call from thermostat Fan Only Mode The normal operational sequence in fan only mode is as follows 1 R and G thermostat contacts close initiating a call for fan Integrated control module performs safety circuit checks 3 Circulator blower is energized on cool speed E
238. g or have a large number of elbows Localexperience indicates that flexible liners installed without insulation are likely to have condensation prob lems Insulation must be selected and installed in accordance with the liner manufacturer s instructions Finally cap the chimney and terminate the liner in accor dance with the liner manufacturer s instructions Horizontal Applications and Considerations Horizontal applications in particular may dictate many of the installation s specifics such as airflow direction duct work connections flue and or combustion air pipe connec tions etc The basic application of this furnace as a hori zontal furnace differs only slightly from an upright installa tion When installing a furnace horizontally additional con sideration must be given to the following FURNACE MUST BE LEVEL 9096 Furnaces Onl FROM END TO END ALTERNATE VENT FLUE AND COMBUSTION AIR gt Tm INTAKE 90 Furnaces FURNACE MUST LEVEL OR SLIGHTLY TILTED FORWARD a RN WITH THE DOORS 0 3 4 BELOW THE BACK PANEL 90 Furnaces Onl 4 8 4 MINIMUM 7 DRAIN TRAP ra CLEARANCE GAS LINE WITH N DRIP LEG 3 MINIMUM e 90 Furnaces DRAIN LINE WITH 1 4 PER DRAIN PAN DOWNWARD SLOPE 1 36 MINIMUM SERVICE CLEARANCE REQUIRED FURNACE MUST BE SUPPORTED AT BOTH ENDS AND MIDDLE 90 Horizon
239. g the call for fan 6 Circulator blower is de energized Electronic air cleaner terminals are de energized 7 Furnace awaits next call from thermostat NORMAL SEQUENCE OF OPERATION Dehumidification Mode The normal operational sequence for dehumidification is as follows 1 R and Y thermostat contacts close initiating a call for cool Integrated control module performs safety circuit checks 3 Outdoor fan and compressor energized 4 Circulator blower is energized following a fixed five sec ond on delay The circulator blower will take 30 seconds to ramp up to full speed Electronic air cleaner terminals are energized with circulator blower 5 Furnace circulator blower and outdoor cooling unit run and integrated control module monitors safety circuits continuously 6 Dehumidistat opens on humidity rise Motor applies a dehumidification factor of 80 to the cooling airflow de mand causing the motor to operate at 8096 of cooling airflow demand 7 When humidity level falls below setting on dehumidistat the dehumdistat closes allowing the motor to return to set cooling speed 8 R and Y thermostat contacts open completing the call for cool 9 Outdoor fan and compressor are de energized Electronic air cleaner terminals are de energized 10 Circulator blower is de energized following a fixed forty five second cool off delay period The air circulator blower will ramp down for another 30 seconds and shut do
240. gas tight NOTE Single Stage and Two Stage gas furnaces with induced draft blow ers draw products of combustion through a heat exchanger allowing in some instances common venting with natural draft appliances i e water heaters All installations must be vented in accordance with National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition In Canada the furnaces must be vented in accordance with the National Standard of Canada CAN CGA B149 1 and CAN CGA B149 2 latest editions and amendments NOTE The vertical height of the Category venting system must be at least as great as the horizontal length of the venting system To PREVENT POSSIBLE PERSONAL INJURY OR DEATH DUE TO ASPHYXIATION COMMON VENTING WITH OTHER MANUFACTURER S INDUCED DRAFT APPLIANCES IS NOT ALLOWED Common venting two 8096 furnaces is allowed only with Amana brand Category I 8096 Single Stage furnaces with the addition of a common vent kit CVK for each appliance Refer to the 8096 furnace Accessory Charts in this manual for a tabular listing of appropriate manufacturer s kits 47 PRODUCT DESIGN The minimum vent diameter for the Category venting sys tem is as shown in the following chart MINIMUM VENT DIAMETER MODEL GU 90 ann inch Under some conditions larger vents than those shown above may be required or allowed When an existing furnace is removed from a venting system serving other appliances the venting syst
241. gniter and plug connect wiring harness These furnaces also feature an integrated electronic ignition control prepainted textured steel cabinet and 409 stainless steel tubular heat exchanger P1229201F P1229208F GUIC CX P1229301F P1229308F GUIC DA P1222501F P1222508F GUIC DA P1226601F P1226608F P1226701F P1226708F PRODUCT IDENTIFICATION This section will identify the models covered and the changes per each model group from one release to the next Model Manufacturing Description Gas Furnace Counterflow Horizontal Induced Draft Air Command 80 SSE Furnace Initial Design Series GCIA A P1177401F P1177408F 140 80 furnace featuring integrated electronic ignition control silicon carbide ignitor electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Counterflow Horizontal Induced Draft A Air Command 80 SSE Furnace C Third Design Series X NOx Certified GCIA CX P1207301F P1207308F 140 80 furnace featuring integrated electronic ignition control electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Counterflow Horizontal Induced Draft B Air Command 80 SV Furnace Initial Design Series GCIB A P1186501F 1186508 140 80 furnace featuring electronic ignition control silicon carbide ignitor radiant flame sensor electrodepositi
242. h B vent pipe can be used to extend the induced draft blower outlet 1 2 beyond the fur nace cabinet Vent the furnace in accordance with the Na tional Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition In Canada vent the furnace in accordance with the National Standard of Canada CAN CGA B149 1 AND CAN CGA B149 2 latest editions and amendments Vent Supply Return Ar Air 80 Counterflow Rotated Induced Draft Blower TO PREVENT DEATH OR SERIOUS ILLNESS TO BUILDING OCCUPANTS DUE TO FLUE PRODUCTS LEAKING INTO THE BUILDING PROPER INSTALLATION OF GASKETS AND SCREWS IS ESSENTIAL FOR PROVIDING A GAS TIGHT SEAL BETWEEN THE PARTITION PANEL AND THE INDUCED DRAFT BLOWER Make sure all wires are at least one inch from flue pipe Relocate junction box to right side of cabinet if necessary Refer to Electrical Connections section of this manual for instructions Masonry Chimneys POSSIBILITY OF PROPERTY DAMAGE PERSONAL INJURY OR DEATH DAMAGING CONDENSATION CAN OCCUR INSIDE MASONRY CHIMNEYS WHEN A SINGLE FAN ASSISTED CATEGORY 1 APPLIANCE 80 AFUE FURNACE IS VENTED WITHOUT ADEQUATE DILUTION AIR DO NOT CONNECT AN 80 FURNACE MASONRY ULESS THE FURNACE 15 COMMON VENTED WITH T DRAFT HOOD EQUIPPED APPLIANCE OR THE CHIMNEY IS LINED WITH A METAL LINER OR B METAL VENT ALL INSTALLATIONS USING MASONRY CHIMNEYS MUST BE SIZED IN ACCORDANCE WTIH THE APPROPRIATE VENTING TABLES AN 80 FURNACE IS COMMON VENTE
243. h household is a function of demand economy efficiency and convenience It is a process that requires co operation between the propane supplier and customer Electrical Connections To AvoiD THE RISK OF ELECTRICAL SHOCK WIRING TO THE UNIT MUST BE POLARIZED AND GROUNDED Ay warnine HIGH VOLTAGE Disconnect ALL BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WiRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING WIRING HARNESS The wiring harness is an integral part of this furnace Field alteration to comply with electrical codes should not be re quired Wires are color and number coded for identification purposes Refer to the wiring diagram for wire routings If any of the original wire as supplied with the furnace must be replaced it must be replaced with wiring material having a temperature rating of at least 105 C Any replacement wir ing must be copper conductor 115 VOLT LINE CONNECTIONS Before proceeding with electrical connections ensure that the supply voltage frequency and phase correspond to that specified on the unit rating plate Power supply to the fur nace must be N E C Class 1 and must comply with all applicable codes The furnace must be electrically grounded in accordance with
244. he control senses thatthe pressure switch is closed while the induced draft blower is off it waits until the switch opens until then no heating components are energized The probable cause is either bad pressure switch or miswiring Pressure Switch Stuck Open If the induced draft blower is energized and the pressure switch does not close the control will keep the induced draft blower running until the switch closes until then no other heating com ponents will be energized The probable cause is either disconnected hose to pressure switch restricted vent system bad pressure switch or miswiring Ignitor failure If the ignitor will not produce a heat sig nal within 90 seconds the control will hold the gas valve closed and the system will lockout The probable cause is either cracked ignitor miswiring or faulty radiant sen sor Flame lost within 90 seconds If the heat signal is lost while the call for heat continues from 0 to 90 seconds after the gas valve opens the system will retry once The probable cause is either the gas valve manually closed air in gas line incorrect gas pressures incor rect burner alignment incorrect burner gap faulty gas valve or faulty radiant sensor During a retry the gas valve closes and the induced draft blower runs for 60 seconds After the 60 seconds are up a new ignition sequence begins The system will only retry once If the retry does not produce a flame that lasts for at least
245. he thermostat to Y 1 on the circulator board interface board 79 PRODUCT DESIGN NOTE The EAC Electronic Air Cleaner terminals on the two stage integrated control module on the GUIV CA DX amp GUVA AX models will not energize using this method To energize the EAC terminals the G wire from the thermo stat must be connected directly to the G terminal on the two stage integrated control module NOTE The GUVA BX CX and GUIV FX models do not use a separate circulator blower interface board The circulator blower speeds are adjusted by speed selection DIP switches located on the integrated ignition control module Refer to the following figure 8 7 4321 8 7 4321 Cooling Normal HH Speed TapA FF FF 8 7 4321 B 4321 Cooling Plus Oo Speed 1 Adjust FN FN F F 87 4321 7 4321 E Minus L1 Speed Adjust L 87 4321 Cooling Speed Adjust Taps TapD 00 indicates factory setting NN
246. heck Flue Drawdown Pressure S 8 S 7 Open Roll Out Switch Bouncing On Pressure Switch Test Control Test Negative Pressure 5 8 SERVICING S 1 5 2 5 3 5 5 3 5 3 5 4 5 5 5 6 5 7 5 8 5 9 5 10 5 10 5 10 5 11 5 12 5 13 5 13 5 14 5 14 3 15 5 16 5 17 5 18 5 19 5 20 5 21 5 22 SERVICING SECTION INDEX Checking 138 E E 138 Checking Thermostat Wiring and Anticipator 138 Thermostat and Wiring 138 eiie PT 138 138 Checking Transformer and Control Circuit 138 Checking Primary sereis E 138 Checking Auxiliary Limit Gontrol scene nre tbt i tant dra rabie simt a run bn nies 141 Checking Flame Rollout Control incest star ttn bti ne rr pna ritas 142 Checking Pressure A 143 Checking Variable Speed Air Circulator Blower 144 CHECKING Capacitor 149 Resistance CGHeCR ee 149
247. icon Gaskets electrical junction box relocation from blower compartment to the burner compartment and incorporation of coarser threaded thumb screw and U clips instead of clinched inserts for engagement Gas Furnace Upflow Horizontal Variable Speed 2 Stage Condensing A Air Command 9511 Q Furnace A First Design Series X NOx Certified 40 9595 two stage variable speed furnace featuring integrated electronic ignition control silicon carbide mini ignitor two stage gas valve two speed induced draft blower variable spped circulator blower electrodepositioned steel cabinet and 409 stainless steel tubular heat exchanger and stainless steel recouperative coil Gas Furnace Upflow Horizontal Variable Speed 2 Stage Condensing A Air Command 95 11 Furnace A First Design Series X NOx Certified 40 9595 two stage variable speed furnace featuring integrated electronic ignition control silicon carbide mini ignitor two stage gas valve two speed induced draft blower variable speed circulator blower electrodepositioned steel cabinet and 409 stainless steel tubular heat exchanger and stainless steel recouperative coil GUSA CX P1252802F P1252806F GUVA AX P1228301F P1228306F GUVA AX P1232501F P1232506F Gas Furnace Upflow Horizontal Variable Speed 2 Stage Condensing A Air Command 95 Furnace B Second Design Series X NOx Certified 40 9596 two stage variable speed furnace featuring intell ignition int
248. ilution of flue gases 5 3 5 Louvers and Grilles Incalculating free area in 5 3 3 consideration shall be given to the blocking effect of louvers grilles or screens protecting openings Screens used shall not be smaller than 1 4 inch mesh If the area through a design of louver or grille is known it should be used in calculating the size of opening required to provide the free area specified If the design and free area is not known it may be assumed that wood louvers will have 20 25 percent free area and metal louvers and grilles will have 60 75 percent free area Louvers and grilles shall be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation 5 3 6 Special Conditions Created by Mechanical Exhausting or Fireplaces Operation of exhaust fans ventilation systems clothes dryers or fireplaces may create conditions requiring special attention to avoid unsatisfactory operation of installed gas utilization equip ment Air from Inside Building See 5 3 3 a Category I Venting Vertical Venting 80 Furnaces Only PREVENT POSSIBLE PERSONAL INJURY OR DEATH DUE TO ASPHYXIATION AMANAG BRAND NON CONDENSING GAS FIRED WAR AIR FURNACES MUST BE VENTED Do NOT VENT USING CATEGORY VENTING Category Venting is venting at a non positive pressure furnace vented as Category l is considered a fan assisted appliance and does not have to be
249. install the blower motor assembly into the furnace 10 Plug the 16 pin control plug into the motor The plug is keyed Make sure the connector is properly seated and latched 11 Plugthe 5 pin power connector into the motor even though the plug is keyed observe the proper orientation Do not force the connector It plugs in very easily when properly oriented Reversing this plug will cause immediate failure of the control module 12 Final installation check Make sure the motor is installed as follows a As far into the blower housing as possible b Belly bands not covering vent holes or on the control module SERVICING c Motor connectors should oriented as to prevent the accumulation of moisture in the control d Use wire ties to create a drip loop in the motor cables 13 The installation is now complete Reapply power to the furnace and verify that the new motor control module is working properly For complete troubleshooting information on the variable speed air circulator blower motors refer to the Troubleshoot ing Chart for ECM ICM Variable Speed Air Circulator Blower Motors in this manual S 10 CHECKING CAPACITOR The direct drive motors are of the permanent split capacitor design A run capacitor is wired across the auxiliary and a portion of the main windings The capacitors primary func tion is to reduce the line current while greatly improving the torque characteristics of a motor This is accomplished
250. iring lingering burner flame or a slow closing gas valve 50 51 INTEGRATED IGNITION CONTROL DIAGNOSTIC SIGNAL CHART FOR CORRECTIVE ACTION REFER TO FIGHT SIGMAS ABNORMAL OPERATION NUMBER Continuous Light Internal Control Failure System Lockout Pressure Switch Stuck Closed Pressure Switch Stuck Open Thermal Protection Device Open Continuous Flashing Flame Sensed No Call For Heat Stat Recovery 1 4 Second on 1 4 Second Off 104 SYSTEM OPERATION NORMAL SEQUENCE OF OPERATION 80 Two Stage Variable Speed Models with White Rodgers 50A51 225 Integrated Ignition Control 90 Two Stage Variable Speed Models with White Rodgers 50A51 235 Integrated Ignition Control Power Up The normal power up sequence is as follows D 115 VAC power applied to furnace Integrated control module performs internal checks Integrated control module flashes LED one time Integrated control module monitors safety circuits con tinuously Furnace awaits call from thermostat Heating Mode The normal operational sequence in heating mode is as fol lows 1 R and W1 or R and W1 and W2 thermostat contacts close initiating a call for heat The induced draft blower is energized on high speed for a 10 second prepurge Humidifier terminals are energized with induced draft blower The induce draft blower steps down to low speed follow ing prepurge The ignitor is energized and is allowed t
251. is Label If you don t smell gas go to next step 7 Turn gas control knob INLET ARRETER Lisez les instructions de s curit sur la portion sup rieure de cette tiquette R gler le thermostat la temp rature la plus basse Couper l alimentation lectrique de l appareil Cet appareil m nager tant dot d un syst me d allumage automatique ne pas essayer allumer le br leur manuellement 5 Torner le robinet a gaz dans le sens des aigilles d une montre 4 en position OFF ARRET 6 Attendre cinq 5 minutes pour laisser echapper tout le gaz Renifler tout autour de l appareil y compris pr s du plancher pour d celer une odeur de gaz Si c est le cas ARRETER Passer l tape B des instructions de s curiti sur la portion sup rieure de cette tiquette S il n y a pas d odeur de gaz passer l tape suivant 7 Tourner le robinet a gaz dans le sens inverse des aigilles d ne montre en pos ON MARCHE AON 4 8 Remettre en place le panneau d acc s y 9 DU GAZ Mettre l appareil sous tension ARRIVEE 10 R gler le thermostat la temp rature desir e 11 Si l appareil ne se met pas en marche suiyre les instructions intitul es Comment coupler l admission de gaz de l appereil et appeler un technicien qualifi ou le fourrnisseur de gaz 1 Set the thermostat to lowest setting
252. is required due to the natural reduction in the density of both the gas fuel and combustion as alti tude increases The High Altitude Orifice Kit will provide the proper design certified input rate within the specified altitude range High Altitude Orifice or Pressure Switch Kits are purchased according to the installation altitude and usage of either natu ral or propane gas Refer to the Technical Manual or product Specification Sheet for a tabular listing of appropriate alti tude ranges and corresponding manufacturer s high altitude Natural or Propane Gas orifice or pressure switch kits Do not derate the furnace by adjusting the manifold pres sure to a lower pressure than specified on the furnace rating plate The combination of the lower air density and a lower manifold pressure will prohibit the burner orifice from draw ing the proper amount of air into the burner This may cause incomplete combustion flashback and possible yellow tip ping 155 SERVICING In some areas the gas supplier may artificially derate the gas in an effort to compensate for the effects of altitude If the gas is artificially derated the appropriate orifice size must be determined based on the BTU ft content of the derated gas and the altitude Refer to the National Fuel Gas Code NFPA 54 ANSI Z223 1 and information provided by the gas supplier to determine the proper orifice size S 18 CHECKING GAS PRESSURE Gas Supply Pressure Measurement
253. isions of the local building codes for deter mining the combustion air requirements for the appliances Most homes will require outside air be supplied to the fur nace area by means of ventilation grilles or ducts connect ing directly to the outdoors or spaces open to the outdoors such as attics or crawl spaces The following information on air for combustion and ventilation is reproduced from the National Fuel Gas Code NFPA 54 ANSI 7223 1 Section 5 3 5 3 1 General a The provisions of 5 3 apply to gas utilization equipment installed in buildings and which require air for combustion ventilation and dilution of flue gases from within the building They do not apply to 1 direct vent equipment which is constructed and installed so thatallairforcombustion is obtained from the outside atmosphere andall flue gases are discharged to the outside atmosphere or 2 enclosed furnaces which incorporate an integral total enclosure anduse only outside air for combustion and dilution of flue gases b Equipment shall be installed in a location in which the facilities for ventilation permit satisfactory combustion of gas proper venting and the maintenance of ambient temperature at safe limits under normal conditions of use Equipment shall be located so as not to interfere with proper circulation of air When normal infiltration does not provide the necessary air outside air shall be introduced c In addition to air needed for combustion pr
254. ission du gaz qu la main ne jamais emploer d outil cet effet Si la manette reste coinc e ne pas tenter de la r parer appeler un technicien qualifi Quiconque tente de forcer la manette ou de la reparer peut d clencher une explosion ou un incendie D Ne pas se servir de cet appareil s il a t plong dans l eau compl tement ou en partie Appeler un technicien qualifi pour inspecter l appareil et remplacer tout partie du syst me de contr le et toute commande qui ont t plong s dans l eau OPERATING INSTRUCTIONS STOP Read safety information above on this label Set the thermostat to lowest setting Turn off all power to the appliance This appliance is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand Push the gas control lever to OFF Position Do not force Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you then smell gas STOP Follow B a in the safety Information above on this label if you don t smell go to next step 7 Push gas control lever INLET 4 gt 8 Replace access panel ARRIVEE 9 Turn on all electric DU GAZ power to the appliance 10 Set thermostat to desired setting service technician or gas company MANUEL EN POS 11 If the appliance will not operate MANUAL GAS instructions inti
255. itioned areas behind the thermostat and dehumidistat such as an outside wall DRAFTS OR DEAD 5 5 BEHIND DOORS IN CORNERS UNDER CABINETS Pa M m Thermostat Influences Consult the instructions packaged with the thermostat and dehumidistat for mounting instructions and further precau tions Combustion and Ventilation Air Requirements PossiBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH MAY OCCUR IF THE FURNACE IS NOT PROVIDED WITH ENOUGH FRESH AIR FOR PROPER COMBUSTION AND VENTILATION OF FLUE GASES MOST HOMES REQUIRE OUTSIDE AIR TO BE SUPPLIED TO THE FURNACE AREA Improved construction and additional insulation in buildings have reduced heat loss by reducing air infiltration and es cape around doors and windows These changes have helped in reducing heating cooling costs but have created a prob lem supplying combustion and ventilation air for gas fired and other fuel burning appliances Appliances that pull air out of the house clothes dryers exhaust fans fireplaces etc increase the problem by starving appliances for air If this furnace is to be installed in the same space with other gas appliances such as a water heater ensure there is an adequate supply of combustion and ventilation air for the other appliances Refer to the latest edition of the National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 or CAN B149 Installation Codes Sections 7 2 7 3 or 7 4 or applicable prov
256. ject which is currently available Proper Chimney Termination Check 1 Line terminate with listed vent cap Fix 1 No Chimney channel free of solid and liquid fuel appliances Check 2 Change venting arrangements Fix 2 Crown in good Rebuild crown condition No m Check 3 34 Fix 4 Yes Cleanout free of Bel debris No 5 4 4 Yes Liner in good condition No icd Check 5 Dilution air available No 6 Yes Complete the installation Check 7 Check 1 Proper chimney termination A masonry chimney used as a vent for gas fired equipment must extend at least three feet above the highest point where it passes through the roof It must extend at least two feet higher than any portion of a building within a horizontal dis tance of 10 feet In addition the chimney must terminate at least 3 feet above any forced air inlet located within 10 feet The chimney must extend at least five feet above the high est connected equipment draft hood outlet or flue collar If the chimney does not meet these termination requirements but all other requirements in the checklist can be met it may be possible for a mason to extend the chimney If this will not be practical see Fix 1
257. jeisouueuj euis ON asny 19 891q 10 6S00 JO A pZ 10 amod uado 400p 44O YMS J08UU09SIP tZ OU 10 A GI ON pue JeMod A pz pue A 911 enssy uoniub GEzZ LSWOS SZZ LSWOS 40 ieu 113 SYSTEM OPERATION NORMAL SEQUENCE OF OPERATION 90 6 Two Stage Models with White Rodgers 50M61 288 Integrated Ignition Control Power Up The normal power up sequence is as follows D 115 power applied to furnace Integrated control module performs internal checks Integrated control module flashes LED one time Integrated control module monitors safety circuits con tinuously Furnace awaits call from thermostat Heating Mode The normal operational sequence in heating mode is as fol lows 1 R and W1 or R and W1 and W2 thermostat contacts close initiating a call for heat Integrated control module performs safety circuit checks Induced draft blower is energized on high speed for a 10 second prepurge Humidifier terminals are energized with induced draft blower Induced draft blower steps to low speed following prepurge Low stage pressure switch contacts are cl
258. k access door must be used in counterflow applications to allow filter removal If the filter rack is used the side of the plenum must be at least as tall as dimension A shown in the following illustration For di mension of A refer to the following chart COUNTERFLOW RETURN AIR FILTER SIZES Cabinet Width Filter Size Inches Filter Area in2 Dimension A 16 1 2 15 20 1 600 14 2 20 1 2 15 20 1 600 13 24 1 2 15 20 1 600 11 3 T6 1 2 20 20 1 800 19 7 20 1 2 20 20 1 800 18 8 24 1 2 20 20 1 800 17 7 16 1 2 25 X 20 X 1 1000 25 0 20 1 2 25 X20 X1 1000 243 24 1 2 25 20 1 1000 23 4 82 AIR FLOW CENTRAL RETURN gt GRILLE 47 ____ 7 EXTERNAL FILTER RACK KIT A 2 7 10 AL BOTTOM RETURN POSSIBLE UPRIGHT UPFLOW FILTER LOCATIONS OPTIONAL 0 J pee ACCESS N CENTRAL pn RETURN al Min GRILLE RETURN DUCT 5 JUNCTION 2 AIR FLOW POSSIBLE UPRIGHT COUNTERFLOW FILTER LOCATIONS 9096 Furnace Shown 8096 Similar Horizontal Installations Filter s must be installed external to the furnace casing for horizontal installations For most installations it is prefer able to use a central return with filters installed in the duct behind the return air grill In this way filter repl
259. kit will provide the proper design certified input rate within the speci fied altitude range High altitude kits are purchased according to the installa tion altitude and usage of either natural or propane gas Refer to the product Specification Sheet or Technical Manual for a tabular listing of appropriate altitude ranges and correspond ing manufacturer s high altitude Natural Propane gas and or Pressure Switch kits Do not derate the furnace by adjusting the manifold pres sure to a lower pressure than specified on the furnace rating plate The combination of the lower air density and a lower manifold pressure will prohibit the burner orifice from draw ing the proper amount of air into the burner This may cause incomplete combustion flashback and possible yellow tip ping In some areas the gas supplier may artificially derate the gas in an effort to compensate for the effects of altitude If the gas is artificially derated the appropriate orifice size must be determined based upon the BTU f content of the derated gas and the altitude Refer to the National Fuel Gas Code NFPA 54 ANSI Z223 1 and information provided by the gas supplier to determine the proper orifice size A different pressure switch may be required at high altitude regardless of the BTU f content of the fuel used Refer to the product Specification Sheet or Technical Manual for a tabular listing of appropriate altitude ranges and correspond ing manufacturer
260. l for cooling T Stat and de humidification Dehum Stat The green LED Located within the box labeled DEHUMIDIFY on the circulator blower in terface board on GUIV CA DX amp GUVA AX models or the yellow LED adjacent to the DEHUM screw terminal on GUVA BX CX models will be illuminated during dehumidifi cation Fossil Fuel Applications The 80 amp 90 Single Stage and Two Stage furnaces can be used in conjunction with a heat pump in a fossil fuel application A fossil fuel application is where an outdoor tem perature sensor determines the most cost efficient means of heating heat pump gas furnace or both A heat pump thermostat with two stages of heat is required to properly use the single stage furnace with a heat pump while a heat pump thermostat with three stages of heat is required to properly use the two stage furnace with a heat pump Refer to the fossil fuel kit installation manual for addi tional thermostat requirements To install strictly follow the wiring guidelines in the fossil fuel kit installation Do not connect the and lines from the heat pump or thermostat directly to the O and EM W 2 terminals on the air circulating motor interface board on GUIV CA DX or GUVA AX models All connections to the furnace must be to the two stage integrated furnace control board and must wire to the FURNACE terminal strip on the fossil fuel control board Space provisions on the control panel have been
261. lator to the required manifold pressure 8 Reinstall high stage manifold regulator cap screw Re check manifold pressure setting with cap on SERVICING 9 Using a 3 32 Allen wrench adjust the ow stage mani fold pressure regulator to the required manifold pressure 10 Reinstall low stage manifold cap screw and recheck mani fold pressure setting with cap on warnina HIGH VOLTAGE Disconnect ALL ELECTRICAL POWER AND SHUT OFF GAS SUPPLY BEFORE SERVICING OR INSTALLING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 11 Disconnect manometer after turning off gas at manual shutoff valve Reinstall gas valve outlet pressure tap plug before turning on gas to furnace 12 Turn on gas to furnace and check for leaks If leaks are found repair and then reinstall burner compartment door 13 Turn on electrical power and verify proper unit operation Make sure furnace operates at the proper manifold pres sure at both high and low stage outputs Manifold Gas Pressure oh Stage 9 7 to 10 3 wc Low Stage 5 7 to 6 3 w c S 19 CHECKING FOR DELAYED IGNITION Delayed ignition is a delay in lighting a combustible mixture of gas and air which has accumulated in the combustion chamber When the mixture does ignite it may explode and or rollout causing burning in the burner venturi If delayed ignition should occur the following should be checked
262. lbow and the recouperator coil front cover The drain lines are then routed through the right or left side panel and into the drain trap secured to the outside of the cabinet NOTE Refer to Condensate Drain Lines and Drain Trap Alternate Vent Flue Hose Connections section in this manual orthe installation instructions for upright installations using an alternate vent flue outlet Standard Right or Left Side Drain Hose Connections Upright installations using the standard vent flue outlet re quire drain hoses to be connected as shown in the following figures NOTE For left side drainage grommets will have to be relo cated to left side panel RIGHT SIDE PANEL RUBBER ELBOW RUBBER ELBOW DRAIN PORT HOSE CLAMP __ TUBE 1 SIDE PANEL 2 GROMMET AM 2 HOLES oR TUBE S 2 7 lt FRONT COVER en A GREEN TR pna DRAIN PORT HOSE CLAMPS 3 PLACES 90 Furnace Upright Standard Drain Hose Connections Right Side LEFT SIDE PANEL DO TO MEM CD RUBBER DRAIN PORT ELBOW RED HOSE M RUBBER CLAMP ELBOW HOSEA SIDE PANEL 7 t HOSE GROMMET CLAMP HOLES E TUBE 1 TUBE S 2 2 HOSE CLAMPS 3 PLACES DRAIN i A HOSE B 90 Furnace Upright
263. le liners specifically intended and tested for gas applications are listed in the UL Gas and Oil Equipment Directory UL Standard 1777 52 For sizing of flexible liners see Note 22 and the tables in the National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition and in the National Standard of Canada CAN CGA B149 1 and CAN CGA B149 2 latest editions and amend ments To install the liner read and follow the liner manufacturer s instructions and your local codes Excess liner length should be pulled out of the chimney and cut off Use caution when doing this as the cut edges of flexible liners may be sharp Do not spiral excess liner inside of the chimney Support the liner as recommended by the liner manufacturer Some manufacturers of flexible liners offer an insulation sleeve designed to be added to the liner before it is installed in the chimney Poured insulation either vermiculite or other ma terials is no longer recommended Insulation will need to be added to the flexible liner if e Itis required by the liner manufacturer s instructions e The previous liner was properly sized and installed and suffered from condensation damage e tis required by your local building codes Even if none of those three conditions exist which require additional liner insulation the installer may wish to consider it if The local climate is very cold Thechimney is very tall Theventconnectors used are very lon
264. lectronic air cleaner terminals are energized 4 Circulator blower runs integrated control module moni tors safety circuits continuously 5 Rand thermostat contacts open completing the call for fan 6 Circulator blower is de energized Electronic air cleaner terminals are de energized 7 Furnace awaits next call from thermostat 87 SYSTEM OPERATION HEATING TIMING CHART FOR WHITE RODGERS 50A50 AND HEATCRAFT HSI 1 1A INTEGRATED IGNITION CONTROL OPERATION AIR CIRCULATION su BLOWER OPEN GAS VALVE CLOSED ON IGNITOR OFF PRESSURE SWITCH INDUCED DRAFT BLOWER off ON THERMOSTAT EE SECONDS 0 17 21 23 54 0 15 90 e LL 322 gt gt Bs 5 65555 6 MIT 5 5 4 8 ox 08 9 5 gt 20 8 gt m ado LL t 2 LU COOLING TIMING CHART FOR WHITE RODGERS 50A50 AND HEATCRAFT HSI 1 1A INTEGRATED IGNITION CONTROL OPERATION Indoor Fan ON OFF Outdoor Fan and ON Compressor OFF Thermostat ON OFF Seconds 0 5 0 45 88 SYSTEM OPERATION ABNORMAL OPERATION 80 or 90 Models with White Rodgers 50A50 or HSI 1 1A Integrated Ignition Control The following presents the probable causes of questionable furnace operation and how to fix them Look through the observation window in the blower access door and make a note of the number of flashes in sequence between pauses Next refer to the Diagnostic Signal
265. ling mode is as fol lows 1 R and Y thermostat contacts close initiating a call for cool Integrated control module performs safety circuit checks Outdoor fan and compressor are energized Circulator blower is energized following a fixed five sec ond on delay Electronic air cleaner terminals are ener gized with circulator blower Furnace circulator blower and outdoor cooling unit run and integrated control module monitors safety circuits continuously R and Y thermostat contacts open completing the call for cool Outdoor fan and compressor are de energized Electronic air cleaner terminals are de energized Circulator blower is de energized following a fixed forty five second cool off delay period Furnace awaits next call from thermostat 100 Fan Only Mode The normal operational sequence in fan only mode is as follows 1 R and G thermostat contacts close initiating a call for fan Integrated control module performs safety circuit checks Circulator blower is energized on low heat speed Elec tronic air cleaner terminals are energized Circulator blower runs integrated control module moni tors safety circuits continuously R and thermostat contacts open completing the call for fan Circulator blower is de energized Electronic air cleaner terminals are de energized Furnace awaits next call from thermostat SYSTEM OPERATION HEATING TIMING CHARTS FOR WHITE RODGERS 50 51 215 TWO ST
266. llowing additional requirements must also be met Gas furnaces must be installed by a licensed plumber or gas fitter gas cock must be used e Ifthe unit is to be installed in an attic the passage way to and the service area around the unit must have flooring To ensure proper installation and operation thoroughly read this manual for specifics pertaining to the installation and application of this product POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE EXPLOSION SMOKE SOOT CONDENSTAION ELECTRICAL SHOCK OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION REPAIR OPERATION OR MAINTENANCE OF THIS PRODUCT ELECTROSTATIC DISCHARGE ESD PRECAUTIONS NOTE Discharge body s static electricity before touching unit An electrostatic discharge can adversely affect electri cal components Use the following precautions during furnace installation and servicing to protect the integrated control module from dam age By putting the furnace the control and the person at the same electrostatic potential these steps will help avoid exposing the integrated control module to electrostatic dis charge This procedure is applicable to both installed and uninstalled ungrounded furnaces 1 Disconnect all power to the furnace Do not touch the integrated control module or any wire connected to the control prior to discharging your body s electrostatic charge to ground 2 Firmly touch a cle
267. ls has a fixed 90 second circulator blower heat off delay 13 Furnace awaits next call from thermostat 90 Cooling Mode The normal operational sequence in cooling mode is as fol lows 1 R and Y thermostat contacts close initiating a call for cool 2 Integrated control module performs safety circuit checks 3 Outdoor fan and compressor are energized 4 Circulator blower is energized on cool speed following a fixed five second on delay Electronic air cleaner termi nals are energized with circulator blower 5 Furnace circulator blower and outdoor cooling unit run integrated control module monitors safety circuits con tinuously 6 Rand Y thermostat contacts open completing the call for cool 7 Outdoor fan and compressor are de energized 8 Circulator blower is de energized following a fixed forty five second cool off delay period Electronic air cleaner terminals are de energized 9 Furnace awaits next call from thermostat Fan Only Mode The normal operational sequence in fan only mode is as follows 1 R and G thermostat contacts close initiating a call for fan Integrated control module performs safety circuit checks 3 Circulator blower is energized on cool speed Electronic air cleaner terminals are energized 4 Circulator blower runs integrated control module moni tors safety circuits continuously 5 Rand thermostat contacts open completing the call for fan 6 Circulator blow
268. lt Opening i Opening Equipment Located in Confined Spaces All Air from Inside Building See 5 3 3 a b All Air from Outdoors The confined space shall communicate with the outdoors in accordance with one of the following two methods Two permanent openings one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure or One permanent opening commenc ing within 12 inches of the top of the enclosure where the equipment has clearances of at least 1 inch from the sides and back and 6 inches from the front of the appliance The openings shall communicate directly or by ducts with the outdoors or spaces crawl or attic that freely communicate with the outdoors 1 When directly communicating with the outdoors each open ing shall have a minimum free area of 1 square inch per 4 000 BTU per hour of total input rating of all equipment in the enclosure 46 lt Chimney Gas Vent Ventilation louvers each end of attic NOTE The inlet and outlet air openings must each have a free area of not less than one square inch per 4000 BTU of the total input rating of all equipment in the enclosure Outlet Air Water Heater Inlet Air Alternate air inlet P ae _ Ventilation louvers for unheated crawl space
269. ly with the outdoors each opening shall have a free area of notless than one square inch per 4 000 BTU per hour ofthe total input rating of all appliances inthe enclosure Equipment Located in Confined Spaces Air from Outdoors See 5 3 3 b 4 Whenducts are used they shall be of the same cross sectional areaas the free area ofthe openings to which they connect The minimum dimension of rectangular air ducts shall not be less than 3 inches NOTE The single opening must have a free area of not less than one square inch per 3000 BTU of the total input rating of all equip ment in the enclosure but not less than mL the sum of the areas of all vent Y connectors in the confined space lt Chimney or Gas Vent Opening Alternate Opening Location Equipment Located in Confined Spaces Air from Outdoors Single Air Opening See 5 3 3 b 5 When directly communicating with the outdoors the single opening shall have a minimum free area of 1 square inch per 3 000 BTU per hour of total input rating of all equipment in the enclosure 5 3 4 Specially Engineered Installations The requirements of 5 3 3 shall not necessarily govern when special engineering approved by the authority having jurisdic tion provides an adequate supply of air for combustion venti lation and d
270. m ber 90 which shows that ninety 90 cubic feet of gas will be consumed in one 1 hour Let s assume the local gas utility has stated that the calo rific value of the gas is 1025 BTU per cubic foot Multiplying the ninety 90 cubic feet per hour by 1025 BTU per cubic foot gives us an input of 92 250 BTUH Check the BTU input on the rating plate of the furnace being tested 134 EXAMPLE GUCAO090AX40 INPUT 92 000 BTU HR OUTPUT CAP 84 000 Should the figure you calculated not fall within five 5 per cent of the nameplate rating of the unit adjust the gas valve pressure regulator or resize orifices ALWAYS CONNECT A MANOMETER TO THE OUTLET TAP AT THE GAS VALVE BEFORE ADJUSTING THE PRESSURE REGULATOR NO CASE SHOULD THE FINAL MANIFOLD PRESSURE VARY MORE THAN PLUS OR MINUS 3 INCHES WATER COLUMN FROM 3 5 INCHES WATER COLUMN FOR NATURAL GAS OR 10 INCHES WATER COLUMN FOR PROPANE GAS To adjust the pressure regulator on the gas valve turn down clockwise to increase pressure and input and out coun terclockwise to decrease pressure and input Since normally propane gas is not installed with a gas meter clocking will be virtually impossible The gas orifices used with propane are calculated for 2500 BTU per cubic foot gas and with proper inlet pressures and correct piping size full capacity will be obtained With propane gas no unit gas valve regulator is used how ever the second stage supply line pressure
271. made to fasten the Amana brand FFKO3A Fossil Fuel Control Board onthe GUIV CA DX or GUVA AX Two Stage Variable Speed Furnace Models only Refer to the following FFK03A Fossil Fuel Mounting Kit Location figure Air Circulating Motor Interface Board E Integrated Furnace de Control a Fossil Fuel Kit Gem Mounting ES Location Amana Brand Fossil Fuel Kit Mounting Location GUIV CA DX amp GUVA AX Models Only CONTINUOUS FAN OPERATION 80 amp 90 Single Stage Furnaces The single stage furnace control will energize the cooling circulator fan speed when the fan switch on the thermostat is turned to the ON position 80 Two Stage Furnaces The two stage furnace control will energize the low heat cir culator fan speed when the fan switch on the thermostat is turned to the ON position This fan speed will provide cir culation with less electricity than conventional single stage equipment NOTE For two stage heat only no cooling applications the continuous fan speed may be increased by jumpering Y to G Thermostat must have a G terminal to make use of this feature 80 GUIV CA DX amp 90 GUVA AX Two Stage Variable Speed Furnaces G from the th
272. me INCLINED INDUCED DRAFT BLOWER ID Blower Pressure Switch Negative Pressure Measurement 9096 Upflow Furnace Shown Counterflow Similar HOSE TO INDUCED DRAFT BLOWER TAP INDUCED DRAFT BLOWER PRESSURE SWITCH OPEN TO ATMOSPHERE COIL COVER A 4 TEE PRESSURE SWITCH PRESSURE SWITCH SE HOSE HOSE INDUCED COVER TAP DRAFT BLOWER Coil Cover Pressure Switch Negative Pressure Measurement 9096 Upflow Furnace Shown Counterflow Similar Reconnect pressure switch electrical wires LINE VOLTAGE NOW PRESENT 4 Energize furnace for heating cycle The induced draft blower motor will begin to run The inclined manometer should read approximately the negative pressure shown in the Pressure Switch Trip Points and Usage Chart These charts can be found in furnace Technical Manual for each model furnace NOTE GUIA B and GCIA B furnaces can pull negative pres sures in excess of 3 0 WC Use appropriate manometer for measuring negative pressure Refer to the Pressure Switch Trip Points and Usage Charts in furnace Technical Manual for pressure switch usage and trip points 5 Remove and check the two electrical wires and using the VOM check from Common to NC Normally Closed should read open Check from Common to NO N
273. mmediately switch the induced draft blower and gas valve to their low stage settings The circulator blower will remain on high heat ing speed for thirty seconds before switching to the low heat circulating speed R and W1 or R and W1 and W2 thermostat contacts open completing the call for heat Gas valve closes extinguishing flame Induced draft blower is de energized following a fifteen second post purge Humidifier terminals are de energized Circulator blower continues running for the selected heat off delay period 60 90 120 or 180 seconds The speed run during this period depends on the last heat call pro vided by the thermostat If the last call for heat was a call for low heat the air circulator blower will run on the low heat speed for the duration of the heat off delay period 60 90 120 or 180 seconds If the last call for heat was a call for high heat the air circulator blower will run on the high heating speed for thirty seconds and then switch to the low heating speed for the balance of the heat off delay period 30 60 90 or 150 seconds Circulator blower and electronic air cleaner terminals are de energized Furnace awaits next call from thermostat SYSTEM OPERATION Cooling Mode The normal operational sequence in cooling mode is as fol lows 1 R and Y thermostat contacts close initiating a call for cool Integrated control module performs safety circuit checks Outdoor fan and comp
274. mostat is satisfied after a call for high heat the air circulator blower will run on high speed for 30 seconds and then switch to low circulator speed for 120 30 90 seconds The adjustable delay off timing allows for more heat trans ferred to the conditioned space from the furnace After the delay time has elapsed the air circulator blower is de energized The adjustable delay off timing feature al lows the installer to customize the comfort level based on the predominant staging requirements of the living space The air circulator blower will ramp down for another 30 seconds and shut down Electronic air cleaner terminals are de energized Furnace awaits next call from thermostat 105 SYSTEM OPERATION Cooling Mode The normal operational sequence in cooling mode is as fol lows 1 R and Y thermostat contacts close initiating a call for cool Integrated control module performs safety circuit checks 3 Outdoor fan and compressor are energized 4 Circulator blower is energized following a fixed five sec ond on delay The circulator blower will take 30 seconds to ramp up to full speed Electronic air cleaner terminals are energized with circulator blower Furnace circulator blower and outdoor cooling unit run and integrated control module monitors safety circuits continuously R and Y thermostat contacts open completing the call for cool Outdoor fan and compressor are de energized Electronic air cleaner
275. must be cleaned to remove creosote buildup The fireplace open ing must then be permanently sealed If oil fired appliance s are being replaced by gas fired appliance s the tile liner must first be cleaned to remove the fuel oil residue If none of the above options are practical the Air Command 80 may need to be vented vertically with B vent Under some conditions an Air Command 90 or 95 could be installed rather than an Air Command 80 The Air Command 90 or 95 can be vented horizontally or vertically through PVC pipe 51 PRODUCT DESIGN Fix 3 Rebuild the Crown If the chimney crown is damaged a qualified mason must repair it in accordance with nationally recognized building codes or standards One such standard which may be refer encedis the Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appliances ANSI NFPA 211 Fix 4 Relining Relining options include B vent and flexible liners If the chimney has diagonal offsets B vent probably cannot be used If B vent is to be used it must be supported adequately Supports such as fire stops or thimbles must be used to prevent the B vent from coming into direct contact with the tile liner or chimney walls Direct contact would result in higher heat loss with an increased possibility of poor vent ing system performance Itis not acceptable to vent one appliance inside the B vent and other appliances outside The excess space between the B vent and
276. n control silicon GUIS CA P1229903F P1229907F carbide ignitor two stage gas valve two speed induced draft blower electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Change from embossed bottom knock out to perforated bottom knock out and addition of internal side filter retention Gas Furnace Upflow Horizontal Induced Draft S 2 Stage Air Command 80 SSE cus cx 1230003 P1230007F Furnace C Third Design Series X NOx Certified 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor prepainted textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft S 2 Stage Air Command 80 SSE Furnace C Third Design Series X NOx Certified GUIS CX 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor P1230103F P1230107F electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Change from embossed bottom knock out to perforated bottom knock out and addition of internal side filter retention Gas Furnace Upflow Horizontal Induced Draft S 2 Stage Air Command 80 SSE Furnace Sixth Design Series not NOx Certified GUIS FA P1246708F P1246708F 40 80 furnace featuring a new integrated electronic ignition control silicon nitride ignitor new wiring harness electrodepositioned textured steel cabinet a
277. n du gaz qu la main ne jamais emploer d outil cet effet Si la manette reste coinc e ne pas tenter de la r parer appeler un technicien qualifi Quiconque tente de forcer la manette ou de la reparer peut d clencher une explosion ou un incendie D Ne pas se servir de cet appareil s il a t plong dans l eau compl tement ou en partie Appeler un technicien qualifi pour inspecter l appareil et remplacer tout partie du syst me de contr le et toute commande qui ont t plong s dans l eau BN OPERATING INSTRUCTIONS STOP Read the safety information above on this label Setthe thermostat to lowest setting Turn off all power to the appliance This appliance is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand Turn the gas control knob clockwise 4 to OFF Position Do not force Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you D o o counterclockwise to ON 2 7 8 Replace access panel 9 Turn on all electric power to the appliance 10 Set thermostat to desired setting 11 If the appliance will not operate M follow the instructions To Turn KNOB SHOWN Off Gas To Appliance and call your IN ON POSITION service technician or gas company ROBINET A GAZ then smell gas STOP Follow B in the safety MANUEL EN POS information above on th
278. n the unit and the utility room wall so the blower will not interfere with combustion air or draft The room closet or alcove must not be used as a return air chamber When the furnace is used in connection with a cooling unit the furnace should be installed in parallel with or on the up stream side of the cooling unit to avoid condensation in the heating element With a parallel flow arrangement the damp ers or other means used to control the flow of air must be adequate to prevent chilled air from entering the furnace and if manually operated must be equipped with means to pre vent operation of either unit unless the damper is in the full heat or cool position When the furnace is heating the temperature of the return air entering the furnace must be between 55 F and 100 F Upright Installations Depending on the installation and or customer preference differing filter arrangements can be applied Filters can be installed in the central return register the bottom of the blower compartment upflows a side panel external filter rack kit upflows or inside the side panel upflows or the ductwork above a counterflow furnace As an alternative a media air filter or electronic air cleaner can be used as the requested filter Refer to the following minimum filter requirement charts for determination of the minimum filter area to ensure proper unit performance The following figures show possible filter locations NOTE A ductwor
279. nace product installed on LP gas kit monitors gas line pressure with a pressure switch and disables the unit s gas valve if the line pressure drops below acceptable levels Application of the LPLP kit is aimed at reducing the occurnace of sooted heat exchangers in product installed on LP gas Propane Conversion Kit For use with Amana Air Command furnace models GUIB GUIC GUID GCIA GCIB GCIC GUIS GCIS GUIV GUCA GCCA GUVA and GUSA This kit converts Amana gas fired units from natural to propane gas The conversion from natural gas P1200108F 4 z shipped from the factory to propane gas requires replacing the burner orifices replacing gas valve regulator spring all single stage units removing NOx screens turbulators screens turbulators not used on all units and applying identification labels PRODUCT IDENTIFICATION Model Manufacturing Description Media Air Cleaner For use with Amana furnace models The Amana Media Air Cleaner Air Bear is a high efficiency air filtration device designed to remove dirt dust pollen and other microscopic particles from the air passing through it Flexible performance range up to 2 000 CFM capacity The air cleaner should be installed in the 1221801 system so that all the system air is circulated through the air cleaner The air cleaner will only remove the airborne contaminants delivered to it Maximum performance is obtained when the system
280. nd drain and pres sure tap hoses from the recuperator coil front cover 5 Remove the recuperator coil front cover to expose the coil tubes and turbulators 6 Remove the recuperator coil turbulators individually by slowly pulling each turbulator forward firmly 7 Clean the recuperator coil tubes using a long handle wire brush such as a gun cleaning brush 8 Clean the primary heat exchanger tubes using a wire brush attached to a length of high grade stainless steel cable such as drain cleanout cable Attach variable speed reversible drill to the other end of the cable Slowly rotate the cable with the drill and insert it into one of the heat exchanger tubes While reversing the drill work the cable in and out several times to obtain sufficient clean ing Repeat for each tube MAINTENANCE 9 Clean residue from furnace using a vacuum cleaner 10 Replace the parts removed in the previous steps in re verse order 11 Turn on electrical power and gas to furnace Check for leaks and proper unit operation 12 Severe heat exchanger fouling is an indication of an op erational problem Perform the steps listed in the Sys tem Operation section of this manual to reduce the chances of repeated fouling FLAME SENSOR QUALIFIED SERVICER ONL Y Under some conditions the fuel or air supply can create a nearly invisible coating on the flame sensor This coating acts as an insulator causing a drop in the flame sensing signal
281. nd 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft S 2 Stage Air Command 80 SSE Furnace F Sixth Design Series X NOx Certified GUIS FX P1246803F P1246807F 140 80 furnace featuring a new integrated electronic ignition control silicon nitride ignitor new wiring harness electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger PRODUCT IDENTIFICATION This section will identify the models covered and the changes per each model group from one release to the next Model Manufacturing Description Gas Furnace Counterflow Horizontal Induced Draft S 2 Stage Air Command 80 SSE II Furnace C Third Design Series X NOx Certified GCIS CX P1211203F P1211205F 40 80 two stage furnace featuring integrated electronic ignition control silicon carbide ignitor two stage gas valve two speed induced draft blower electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Counterflow Horizontal Induced Draft S 2 Stage Air Command 80 SSE II Furnace C Third Design Series X NOx Certified GCIS CX P1230603F P1230605F 140 80 two stage furnace featuring integrated electronic ignition control silicon carbide ignitor two stage gas valve two speed induced draft blower prepainted textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Counterflow Horizontal Induced Draft
282. nd compressor are de energized 8 Circulator blower is de energized following a fixed forty five second cool off delay period 9 Furnace awaits next call from thermostat Fan Only Mode The normal operational sequence in fan only mode is as follows 1 R and G thermostat contacts close initiating a call for fan Integrated control module performs safety circuit checks 3 Circulator blower is energized on cool speed 4 Circulator blower runs integrated control module moni tors safety circuits continuously 5 Rand thermostat contacts open completing the call for fan 6 Circulator blower is de energized Furnace awaits next call from thermostat SYSTEM OPERATION HEATING TIMING CHART FOR WHITE RODGERS 50A52 RADIANT SENSE IGNITION CONTROL m ON Air Circulator Blower OFF Gas Valve OPEN CLOSED ON Ignitor OFF Pressure Switch OPEN CLOSED ON Induced Draft Blower OFF Thermostat ON 0 T 1 45 0 90 T 17 Seconds Minimum 90 Seconds Maximum Normal Operation T 17 Seconds or Slightly Longer COOLING TIMING CHART FOR WHITE RODGERS 50A52 RADIANT SENSE IGNITION CONTROL Indoor Fan ON OFF Outdoor Fan and ON Compressor OFF Thermostat ON OFF Seconds 0 5 0 45 97 SYSTEM OPERATION ABNORMAL OPERATION 80 Models with White Rodgers 50A52 Radiant Sense Ignition Control 1 2 98 Internal Control Failure The system will lockout Pressure Switch Stuck Closed If t
283. njunction with 80 or 90 Single Stage or Two Stage Furnaces BU6 OUTDOOR THERMOSTAT BU6 1 SEE NOTE 1 RESISTOR DUAL FUEL ROOM ecd THERMOSTAT aE OES 8 2 MPER HEAT PUMP 5 9 THERMOSTAT Y Y D RELAY Ow W OR W2 G G CONNECTIONS d s Ws 2 20 CX wR R B B 3 FURNACE 12 RWGCY SEE NOTE 3 JUMPER C Y W2 GAS FURNACE THERMOSTAT CONNECTIONS SINGLE AND TWO STAGE FIELD SUPPLIED RELAY TYPICAL OIL FURNACE Notes 1 Resistor must be installed between W and C if an electronic room thermostat is used 2 Some room thermostats will require a jumper between E and W in order to energize furanace in emergency heat mode 3 Intall jumper from 1 to 2 for air tempering during defrost 164 ACCESSORY WIRING DIAGRAMS HIGH VOLTAGE WARNING DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH TWO STAGE RELAY KIT TSRKO1 This wiring diagram is for reference only Not all wiring is as shown above refer to the appropriate wiring diagram for the unit being serviced For use only with GUIV CA DX or GUVA AX Two Stage Furnaces White Wire Blue Wire
284. nnected wiring restricted air intake or flue piping blocked drain system or weak induced draft blower 5 Open Primary Auxiliary or Rollout Limit If the limit control opens the air circulator blower will be turned on until the limit closes The diagnostic light code for this problem is four short flashes followed by a pause The probable cause for either an open primary or auxiliary limit is low conditioned air flow due to dirty filter or resis tance in duct work faulty limit faulty blower blower speed set to low or loose or misconnected wiring The rollout limit s is are open due to flame rollout The probable cause for an open rollout limit is misaligned burners blocked flue and or air inlet pipe failed induced draft blower or loose or misconnected wiring 6 Reversed Polarity If the 115V or 24V AC power leads are reversed the furnace will fail to operate The diag nostic light code for this problem is six flashes followed by a pause The probable cause is either the 115V AC power to furnace or integrated control module is reversed the 24V AC orange and gray wires to transformer are reversed or poor unit ground 7 Low Flame Sense Signal If the furnace continues to operate and the micro amp signal from the flame sensor falls below specified level The diagnostic light code for this problem is seven flashes followed by a pause The probable cause is either a coated oxidized sensor in correctly positioned senser in burner
285. nt Kits HVCK and are suitable for use with the following Amana brand 90 efficient furnaces CONCENTRIC VENT KIT Used On Models GUCA GCCA GUVA GCVA GUSA GULA GCLA GCVA NOTE This kit is not certified for and must not be applied to any furnace not listed in the above table Refer to the directions provided with the concentric vent kit for installation specifications 62 Condensate Drain Lines and Drain Trap 90 Furnaces Only A condensing gas furnace achieves its high level of efficiency by extracting almost all of the heat from the products of combustion and cooling them to the point where condensa tion takes place The condensate which is generated must be piped to an appropriate drain location In upright installations the furnace s drain hoses may exit either the right or left side of the furnace NOTE If the alter nate vent flue outlet is utilized in an upright installation the drain trap and drain connections must be located on the same side as the alternate vent flue outlet In horizontal installations the drain hoses will exit through the bottom down side of the unit with the drain trap sus pended beneath the furnace The field supplied drain sys tem must be in accordance with all local codes and the instructions in the following sections UPRIGHT UPFLOW INSTALLATIONS THE DRAIN TRAP MUST BE MOUNTED ON THE OPPOSITE SIDE OF THE UNIT FROM THE JUNCTION BOX THIS WILL REDUCE THE R
286. nt flashing The vent shall notbe located Lessthan 12 inches above the finished grade line Less than 36 inches from any building opening or any gas service regulator For gas service regulators in the Province of Ontario 72 inches 55 PRODUCT DESIGN Less than 72 inches from the combustion air intake of another appliance Directly above a gas utility meter or service regulator e Overawalkway unless located 84 inches above grade STANDARD FURNACE CONNECTIONS 90 FURNACES ONL Y It is the responsibility of the installer to ensure that the pip ing connections to the furnace are secure airtight and ad equately supported As shipped attachment couplings for vent flue and com bustion air intake pipe connections are provided on the furnace s top cover upflow To use the standard connec tions field supplied vent flue pipe and combustion air intake pipe when applicable should be secured directly to the fur nace at these locations Vent Flue Pipe 90 Furnaces Only Vent flue pipe can be secured to the vent flue coupling us ing the rubber coupling and worm gear hose clamps pro vided with this furnace Torque hose clamps to 20 inch lbs see Standard Connections figure The rubber coupling allows separation of the vent flue pipe from the furnace dur ing servicing NOTE Do not use other commercially able no hub connectors due to possible material conflicts The vent flue pipe can also b
287. o preheat for 17 seconds The gas valve is energized delivering gas to the burners at the low stage heat flow rate The control checks for a signal from the flame sensor within seven seconds after the gas valve is energized opens Gas will only continue to flow if a signal is present The control checks the thermostat to see whether the call for heat is for low stage heat or high stage heat If the call is for high stage heat the induced blower is switched to high speed and the gas valve is energized on high flow rate The control waits 30 seconds and turns on the air circu lator blower to the appropriate speed high heat speed for high heat or low heat speed for low heat The circula tor blower will take 30 seconds to ramp up to full speed Electronic air cleaner terminals are energized with the circulator blower Thefurnace is now operating on the specified stage called for by the two stage thermostat If the two stage thermostat changes the call from low heat to high heat the control will immediately switch the induced draft blower motor gas valve and air circulating blower speed to their high stage setting 11 12 13 14 15 16 17 18 If the two stage thermostat changes the call from high heat low heat the control will immediately switch the induced draft blower motor to low speed and switch the flow rate on the gas valve to low The air circulator blower will remain on high heating speed
288. ocess air shall be provided as required for cooling of equipment or material controlling dew point heating drying oxidation or dilution safety exhaust odor control and air for compressors d In addition to air needed for combustion air shall be supplied for ventilation including all air required for comfort and proper working conditions for personnel e A draft hood or a barometric draft regulator shall be installed in the same room as the equipment served so as to prevent any difference in pressure between the hood or regulator and the combustion air supply f While all forms of building construction cannot be covered in detail airforcombustion ventilation and dilution of flue gases for gas utilization equipment vented by natural draft normally may beobtained by application of one ofthe methods covered in 5 3 3 and 5 3 4 g Air requirements for the operation of exhaust fans kitchen ventilation systems clothes dryers and fireplaces shall be con sidered in determining the adequacy of a space to provide combustion air requirements 5 3 2 Equipment Located in Unconfined Spaces Inunconfined spaces see definition below in buildings infiltra tion may be adequate to provide air for combustion ventilation and dilution of flue gases However in buildings of tight construc tion for example weather stripping heavily insulated caulked vapor barrier etc additional air may need to be provided using the methods de
289. odels to the heat terminal Heatterminal on GUIA GCIA GUIC GCIC GUID GUCA GCCA and GUSA models or Heat High and Heat Lowterminals on GUIS GCIS and GUSA mod els on the ignition control No voltage replace igni tion control b On the 80 and 90 GCVA GUVA two stage variable speed furnaces 120 Volts will be present at the motor at all times WH 33 and BK 6wires on GUIV and WH 45 and BK 37wires on GUVA even without a call for cooling or heating These motors receive their operational signals 24 Volts through the 16 pin wiring harness connected between the motor and in terface board on GUIV CA DX models and GUVA AX models or connected between the motor and ignition control on GCVA GUVA BX GUIV FX models NOTE For complete troubleshooting information on units using the ECM ICM blower motors refer to the servicing section Checking Air Circulator Blowers S 9A ECM ICM in this service manual NOTE Accessory Electronic Air Cleaners and Humidifiers powered through the ignition control accessory terminals under some circumstances can create interference with the ignition control causing intermittent lockouts If the source of the lockouts cannot be otherwise determined it is recom mended that these accessories be disconnected from the ignition control and powered through alternate means S 13A CHECKING WR50A52 INTEGRATED IGNI TION CONTROL RADIANT SENSE NOTE Failure to earth ground the furnace reversing
290. ols Similar OPTIONAL ACCESSORIES ELECTRONIC AIR CLEANER TERMINALS INTEGRATED CONTROL MODULE 120 VAC NEUTRAL TERMINALS 12 PIN CONNECTOR Accessory Wiring WR50A55 WR50A65 WR50T55 Ignition Control Shown HSI 2 Ignition Control Similar 12 CIRCUIT CONNECTOR INTEGRATED CONTROL MODULE HUMIDIFIER ELECTRONIC AIR CLEANER OPTIONAL ACCESSORIES Accessory Wiring WR50M61 amp 50V61 Ignition Control If it is necessary for the installer to supply additional line voltage wiring to the inside of the furnace the wiring must conform to all local codes and have a minimum tempera ture rating of 105 C All line voltage wire splices must be made inside the furnace junction box The integrated control module humidifier terminals HUM are energized with 115 volts whenever the induced draft blower is energized The integrated control module electronic air cleaner terminals EAC are energized with 115 volts when ever the circulator blower is energized on all single stage ignition controls NOTE The EAC Electronic Air Cleaner terminals on the two stage variable speed integrated control module 50A51 225 used on GUIV CA DX models amp 50A51 235 used on GUVA AX models will not energize when G from the ther mostat is connected to G on the Air Circulator Motor Inter face Board To energize the EAC terminals the G wire from the thermostat must be connected di
291. on carbide ignitor electrodepositioned textured steel cabinet and 409 stainless steel tubular heat exchanger Change from embossed bottom knock out to perforated bottom knock out and addition of internal side filter retention GCIC CX P1230501F P1230508F Gas Furnace Counterflow Horizontal Induced Draft C Air Command 80 SSE Furnace F Sixth Design Series X NOx Certified 40 80 furnace redesign incorporating feature changes introduced by the new 40 90 furnaces Changes include standardized blower decks access door blower door scroll wrap burner bracket Silicon Nitride Igniter and plug connect wiring harness These furnaces also feature an integrated electronic ignition control prepainted textured steel cabinet and 409 stainless steel tubular heat exchanger GCIC FX P1234401F P1234408F Gas Furnace Counterflow Horizontal Induced Draft D Air Command 80 SSE Furnace A First Design Series X NOx Certified GCID AX 1249702 P1249706F The 40 80 furnace features an integrated electronic ignition control prepainted textured steel cabinet Changes include Silicon Carbide Mini Igniter and aluminized steel tubular heat exchanger PRODUCT IDENTIFICATION This section will identify the models covered and the changes per each model group from one release to the next Model Manufacturing Description Gas Furnace Upflow Horizontal Induced Draft D Air Command 80 SV Furnace C Third Design Series A Stand
292. on the appropriate cool speed following a fixed five second on delay The circu lator blower requires 30 seconds to ramp up to full speed Electronic air cleaner terminals are energized with cir culator blower 5 Furnace circulator blower and outdoor cooling unit run their appropriate speed integrated control module moni tors safety circuits continuously 6 Rand YLO or Y thermostat contacts open completing the call for cool 7 Outdoor fan and compressor are de energized 8 Circulator blower continues running for a fixed 45 sec ond cool off delay period The speed run during this pe riod depends on the last cooling call from the thermo stat If the call was for low cool the blower will operate at 88 of low cool speed If call was for high cool blower operate at 8896 of high cool speed 9 Electronic air cleaner terminals and circulator blower are de energized 10 Furnace awaits next call from thermostat Fan Only Mode The normal operational sequence in fan only mode is as follows 1 R and G thermostat contacts close initiating a call for fan 2 Integrated control module performs safety circuit checks 3 Circulator blower is energized on continuous fan speed 56 of high stage cooling following a five 5 second delay Electronic air cleaner terminals are energized 4 Circulator blower runs integrated control module moni tors safety circuits continuously 5 Rand thermostat contacts open completin
293. oned textured steel cabinet and aluminized steel tubular heat exchanger Gas Furnace Counterflow Horizontal Induced Draft C Air Command 80 SSE Furnace C Third Design Series X NOx Certified GCIC CX P1207501F P1207508F 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor electrodepositioned textured steel cabinet and 409 stainless Steel tubular heat exchanger Gas Furnace Counterflow Horizontal Induced Draft C Air Command 80 SSE Furnace D Fourth Design Series X NOx Certified 40 80 furnace featuring integrated electronic ignition control silicon GCIC DX P1226801F P1226807F carbide ignitor and 409 stainless steel tubular heat exchanger Use of smooth cold rolled steel substrate and a smooth top coat for furnace cabinet to replace prepainted furnaces until new coating is approved for prepainted material Gas Furnace Counterflow Horizontal Induced Draft C Air Command 80 SSE Furnace C Third Design Series X NOx Certified 40 80 furnace featuring integrated electronic ignition control silicon carbide ignitor and 409 stainless steel tubular heat exchanger Release of prepainted G30 galvanized steel cabinet parts to replace post painted parts on furnace GCIC CX P1230401F P1230408F Gas Furnace Counterflow Horizontal Induced Draft C Air Command 80 SSE Furnace C Third Design Series X NOx Certified 40 80 furnace featuring integrated electronic ignition control silic
294. oneuiuuej pue eBexoojq 10 Buidid Y90949 10 joedsu pezipixo pereoo Josues PUES Buum 1961400 pue jedoud Aya uonoy 8A11981109 U91IMS 100p 10 1 eui si ejnpouu y 4 JI 25299 ysel GAT Z NOY JOYE INO YOO 19591 0119 866 Duisojo MOIS Jeuunq BuueBur esues 0 POUS 01 Sjoejuoo 10 juiod 19 ses esp JO wajshs urejp pexoojq 10 pexoojq esou YAMS puno4B 1004 peg uonsnquioo Jo ainssaid seb enp eurej jeuung Aze7 eure j Jeuunq peuonisod 108495 swej SI JOSUBS 1 1004 si A Jo Ajuejog joyjuoo
295. ons of the kit High Altitude Propane Gas Conversion Kit For use with Amana furnace models GUIC EA GUIC FA GUIC EX GUIC FX GUID EA GUIE EX This kit is required when installing Amana Air Command 95 SSE furnaces HALP12 P1129114F above their maximum rated altitude These kits contain propane gas orifices The orifices in the kit have been selected as a result of testing with the American Gas Association They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installation instructions of the kit High Altitude Propane Gas Conversion Kit For use with Amana furnace models GUSA070 X35 GUSA090 X40 GUSA090 X50 GUSA115 X50 GCVA090 X50 GCVA115 X50 This kit is required when installing Amana P1129115F Air Command 90 furnaces above their maximum rated altitude These kits contain propane gas orifices The orifices in the kit have been selected as a result of testing with the American Gas Association They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installation instructions of the kit High Altitude Natural Gas Kit For use with Amana furnace models GUIA GUIB GUIC GUID GCIA GCIB and GCIC These kits are required when installing Amana Air Command 80 SSE and SV furnaces above their P1129007F 1129010 maximum rated altitude This kit contains natural gas orifices The orifices in the kit have been selected as a result of te
296. or mally Open should read closed If not as above re place control 143 SERVICING 6 Reconnect wires to the control and place in a heating cycle 7 Beginto restrictthe flue outlet until the pressure control trips cycling OFF the burner Also a blocked drain test will need to be performed until the coil cover pressure control trips cycling OFF the burner The trip points should be as shown in the Pressure Switch Trip Points and Usage Charts in furnace Technical Manual If not as listed replace control 9 After completing check and or repair of pressure switch reinstall burner compartment door 10 Turn on electrical power and verify proper unit operation The pressure readings listed in the Pressure Switch Trip Points and Usage Charts in furnace Technical Manual must be adhered to for proper operation S 9 CHECKING AIR CIRCULATOR BLOWER MO TOR OR INDUCED DRAFT BLOWER MOTOR warnina HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 Remove blower compartment door to gain access to the circulator blower motor and induced draft blower motor wire leads connected at integrated ignition control 2 Disconnectthe motor wire leads from its connection point at integrated ignition control module and capacitor if ap plicable 3 Using an ohmmeter test for continuity b
297. orelles ou la perte de vies humaines B BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will WHAT TO DO IF YOU SMELL GAS light any appliance any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions reach your gas supplier call the fire department Use only your hand to push in or turn the gas control lever the lever will not push in or turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire Do not use this appliance if any part has been underwater qualified service technician to inspect to replace any part of the control Cet appareil ne comporte pas de veilleuse Il est muni d un dispositif d allumage qui allume automatiquement le br leur Ne pas tenter d allumer le br leur manuellement AVANT DELE FAIRE FONCTIONNER renifler tout autour de l appariel pour d celer une odeur de gaz Renifler pr s du plancher car certains gaz sont plus lourds que l air et peuvent s accumuler au niveau du 50 QUE FAIRE S IL Y A UNE ODEUR DE GAZ Ne pas tenter d allumer l appariel Ne toucher aucun interrupteur lectrique n utiliser aucun t l phone dans le b timent Appeler imm diatement le fournisseur de gaz en employant le t l phone d n
298. osed Ignitor warm 20 seconds begins upon step to low speed and presence of closed low stage pressure switch contacts After 20 second ignitor warm up period low stage gas valve is energized 4 second ignition trial delivering gas to burners and establishing flame Ignitor remains on for 3 seconds after gas valve is opened ignition activation period Integrated control module monitors flame presence and control begins timing 30 second heat on delay Gas valve will remain open only if flame is sensed If the thermostat call is for low heat gas valve and in duced draft blower will continue on low stage If the call is for high heat the gas valve and induced draft blower will change to high stage 114 10 11 12 13 14 15 16 17 18 19 Circulator blower is energized on the appropriate heat speed following a fixed thirty second blower on delay Electronic air cleaner terminals are energized with cir culator blower Furnace is now operating on the specified stage called for by the two stage thermostat Furnace runs integrated control module monitors safety circuits continuously If the two stage thermostat changes the call from low heat to high heat the integrated control module will im mediately switch the induced draft blower gas valve and circulator blower to their high stage settings If the two stage thermostat changes the call from high heat low heat the control will i
299. pareil y compris pr s du then smell gas STOP Follow in the safety plancher pour decelar gueur de 515821 information above on this Label _____ GAZ ARR l tape B des instructions de s curiti If you don t smell gas go to MANUEL EN POS sur la portion sup rieure de cette tiquette next step S il pas odeur de gaz passer l tape suivant 7 Turn gas control lever 7 Tourner le levier a le sens inverse des counterclockwise to ON GAS aigilles d ne montre 7 en pos ON MARCHE INLET 8 Remettre en place le panneau d acc s 9 Mettre l appareil sous tension 10 R gler le thermostat la temp rature desir e ARRIVEE 11 Si l appareil ne se met pas en marche suiyre les lt I DU GAZ instructions intitul es Comment coupler l admission 4 gaz de et appeler un technicien qualifi ou le fourrnisseur de gaz 8 Replace access panel 9 Turn on all electric power to the appliance 10 Set thermostat to desired setting 11 1f the appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service technician or gas company EVER GC WM IN ON POSITION TURN OFF GAS APPLIANCE EBENE POUR COUPER L ADMISSION DE GAZ DE L APPAREIL 1 Setthe thermostat to lowest setting 1 R gler le thermostat la temp rature la plus basse
300. partment Never use tools If the lever will not push in or turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion Immediately call a qualified service technician to inspect the appliance and to replace any part of the control System and any gas control which has been underwater B BEFORE OPERATING smell all around the appliance C Use only your hand to push in or turn the gas control lever D Do not use this appliance if any part has been underwater entrainant des dammages mat riels des l sions corporelles ou la perte de vies humaines Cet appareil ne comporte pas de veilleuse Il est muni d un dispositif d allumage qui allume automatiquement le br leur Ne pas tenter d allumer le br leur manuellement B AVANT DELE FAIRE FONCTIONNER renifler tout autour de l appariel pour d celer une odeur de gaz Renifler pr s du plancher car certains gaz sont plus lourds que l air et peuvent s accumuler au niveau du 50 1 QUE FAIRE S IL Y A UNE ODEUR DE GAZ 5 9 Ne pas tenter d allumer l appariel Ne toucher aucun interrupteur lectrique n utiliser aucun t l phone dans le b timent Appeler imm diatement le fournisseur de gaz en employant le t l phone d n voisin Respecter la lettre les instructions du fournisseur de gaz Si personne ne r pond appeler le service des incendies Ne pousser ou tourner le levier d adm
301. pe while a 3 1 2 diameter hole is required for 3 diameter pipe To secure the pipe passing through the wall and prohibit damage to piping PRODUCT DESIGN connections a coupling should be installed on either side of the wall and solvent cemented to a pipe connecting the two couplings The pipe length should be the wall thickness plus the depth of the socket fittings to be installed on the inside and outside of the wall The wall penetration should straps be sealed with silicone caulking material 9 12 3 MINIMUM VENT FLUE TEE 12 MINIMUM ABOVE _ HIGHEST ANTICIPATED 12 MINIMUM ABOVE SNOW LEVEL HIGHEST ANTICIPATED SNOW LEVEL 3 MINIMUM 24 MAXIMUM VENT FLUE TEE 3 MINIMUM 24 MAXIMUM er MEDIUM RADIUS 22 90 Furnace Standard Horizontal Terminations ELBOW Above Anticipated Snow Level ts Dual Pipe SCREEN eO oe gt lt 90 Furnace Standard Horizontal Terminations Dual Pipe 12 MINIMUM ABOVE HIGHEST ANTICIPATED SNOW LEVEL 9096 Furnace Alternate Horizontal Terminations Above Anticipated Snow Level we Dual Pipe In a basement installation the pipes may be run between the joist spaces If the pipes must go below the joist and then up into the last joist space to penetrate the header two 45 elbows should be used to reach the header rather than two 90 elbows 9096 Furnace
302. pplicable length elbows and pipe diameter for construction of the vent flue and com bustion air intake pipe systems of a direct vent dual pipe installation The number of elbows tabulated represents the number of elbows and or tees in each Vent Flue amp Com bustion Air Intake pipe Elbows and or tees used in the terminations must be included when determining the num ber of elbows in the piping systems 59 PRODUCT DESIGN If the combustion air intake pipe is to be installed above a finished ceiling or other area where dripping of condensate will be objectionable insulation of the combustion air pipe may be required Use 1 2 thick closed cell foam insulation such as Armaflex or Insultube where required GCLA Model Furnaces Direct Vent Dual Pipe Venting Table Maximum Allowable Length of Vent Flue amp Combustion Air Intake Pipe ft GUCA GULA GCCA Model Furnaces Direct Vent Dual Pipe Venting Table Maximum Allowable Length of Vent Flue amp Combustion Air Intake Pipe ft Number of Elbows 2 9 Style pus inch 2 3 4 5 56 7 8 45 000 Standard 2 68 65 62 59 43 53 50 Alternate 2 55 52 49 46 56 40 37 70 000 Standard 2 68 65 62 59 43 53 50 Alternate 2 5 52 49 46 43 40 37 90 000 Standard 2 55 52 49 46 30 40 37 Alternate 2 42 39 36 33 30 27 24 1
303. pport terminations for both the vent flue and the combustion air intake pipe Vertical concentric vent kits can be installed through roof penetrations having a minimum of 3 4 inch to a maximum of 22 inches thickness NOTE Does not apply to FX models Does not apply to FX models 19 OPERATING INSTRUCTIONS 20 FOR YOUR SAFETY READ BEFORE OPERATING LIRE AVANT DE METTRE EN MARCHELIRE mam WARNING If you do not follow these instructions explosion may result causing property damage ersonal injury or loss of life This appliance does not have a pilot It is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Use only your hand to turn the gas control knob Never use tools If the knob will not turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion Do notuse this appliance if any part has
304. ption Gas Furnace Upflow Horizontal S 2 Stage Condensing A Air Command 90 Furnace Second Design Series X NOx Certified GUSA BX P1233902F P1233906F 40 90 two stage furnace featuring intell ignition integrated electronic ignition control silicon nitride ignitor two stage gas valve two speed induced draft blower prepainted steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal 5 2 Stage Condensing A Air Command 90 Furnace Second Design Series X NOx Certified 40 90 two stage furnace featuring intell ignition integrated electronic ignition control 21239502F 1239506 ln nitride ignitor two stage gas valve two speed induced draft blower prepainted P1242002F P1242006F stage 9 peed Induced blower prepainte steel cabinet and 409 stainless steel tubular heat exchanger electrical junction box relocation from blower compartment to the burner compartment and incorporation of coarser threaded thumb screw and U clips instead of clinched inserts for engagement Gas Furnace_Upflow Horizontal S 2 Stage Condensing A Air Command 90 Furnace Third Design Series X NOx Certified 40 90 two stage furnace featuring intell ignition integrated electronic ignition control silicon nitride ignitor two stage gas valve two speed induced draft blower prepainted steel cabinet and 409 stainless steel tubular heat exchanger 316L Header Plates Sil
305. r CFM being delivered through a given furnace the less the rise will be so the less air CFM being deliv ered the greater the rise The temperature rise should be adjusted in accordance to given furnace specifications and its external static pressure An incorrect temperature rise may result in condensing in or overheating of the heat ex changer An airflow and temperature rise table is provided in the Technical Information Manual Determine and adjust tem perature rise as follows 1 Operate furnace with burners firing for approximately ten minutes Check BTU input to furnace do not exceed input rating stamped on rating plate Ensure all registers are open and all duct dampers are in their final fully or partially open position 2 Place thermometers in the return and supply ducts as close to the furnace as possible Thermometers must not be influenced by radiant heat by being able to see the heat exchanger 160 HEAT EXCHANGER RADIATION LINE OF SIGHT SUPPLY AIR TSUPPLY RISE TSUPPLY TRETURN i TRETURN RETURN AIR Checking Temperature Rise 80 Furnace Shown 9096 Similar 3 Subtract the return air temperature from the supply air temperature to determine the air temperature rise Allow adequate time for thermometer readings to stabilize 4 Adjusttemperature rise by adjusting the circulator blower speed Increase blower speed to reduce temperature rise Decrease blower speed to increase t
306. r OFF air circulator blower delay is only available on GUIV CA DX amp GUVA AX models X Time 30 sec PRODUCT DESIGN Heating Fan Timing The heating fan timing has a fixed on sequence with an ad justable delay off timing The delay timing may be adjusted using the switches near the low voltage terminal strip see the previous switch position figure For heating operation W1 from the thermostat must be connected to W1 on the two stage integrated furnace control W2 from the ther mostat must be connected to W2 on the two stage inte grated furnace control The thermostat connections have no bearing on the operational sequence timings of the circula tor blower during heating The following on and off sequences ofthe air circulating blower fan will occur Air Circulator Blower Operation 100 Heating On Delay 30 seconds Heating On Ramp Up 30 seconds Heating 60 90 120 or 180 Heating seconds Adjustable speed i 0 30 60 X X Time Heating Off Ramp Down 30 seconds 60 90 8 Satisfied 90 120 Heat 180 210 CIRCULATING AIR AND FILTERS DUCTWORK AIR FLOW Duct systems and register sizes must be properly designed for the C F M and external static pressure rating of the fur nace Ductwork should be designed in accordance with the recommended methods of Air Conditioning Contractors of America manual D A duct system should be installed in accordance with Stan dards of
307. re the next ignition attempt S 14 CHECKING FLAME RECTIFICATION FLAME SENSOR A flame sensing device is used in conjunction with the igni tion control module to prove combustion If proof of flame is not present the control will de energize the gas valve and retry for ignition or lockout The following drawings illustrate from a bottom view the ap proximate distances for the ignitor and flame sensor to the gas inshot burner You will note they are in the main burner stream not in the carry over ports as shown in the following figure IGNITOR Ness ES fi cul D Models with Integrated Ignition Control amp Flame Sensor Probe 80 Upflow Model Shown Counterflow Similar FLAME SENSOR 1 4 1 16 IGNITOR FLAME SENSOR 23 64 1 64 DISTANCE SENSOR BURNER 3 16 1 16 DISTANCE OF N IGNITOR TO BURNER BURNERS Models with Integrated Ignition Control amp Flame Sensor Probe 90 Upflow Model Shown Counterflow Similar warnina HIGH VOLTAGE Disconnect ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 Disconnect the flame sensor BU 36 wire from the sen sor terminal 2 Connect a micro amp meter in series with this wire and the sensor terminal 3 Be sure the positive side of the meter is to BU
308. rectly to the G terminal on the two stage integrated control module 24 VOLT THERMOSTAT WIRING NOTE Low voltage connections can be made through ei ther the right or left side panel Wire routing must not inter fere with circulator blower operation filter removal or routine maintenance A 40 V A transformer and an integrated electronic control are built into the furnace to allow use with most cooling equip ment Consult the wiring diagram located in the Technical Manual or on the blower door for further details of 115 Volt and 24 Volt wiring Thermostat Wiring 80 amp 90 Single Stage Furnaces The single stage furnace will have a W terminal and will use a single stage thermostat The following drawing illus trates the typical field wiring for a heat only single stage system and a single stage heating single stage cooling sys tem Refer to the following figures for proper connections to the integrated control module 71 PRODUCT DESIGN Thermostat Single Stage Heatin Furnace Integrated Control Module Thermostat Single Stage Heating with Single Stage Cooling Furnace Integrated Control Module Remote Condensing Unit Single Stage Cooling Single Stage Heating with Single Stage Cooling Typical Field Wiring for Single Stage Gas Furnaces 24 VAC Control Circuit Thermostat Wiring 80 GUIS GCIS amp 90 GUSA BX CX Two Stage Furnaces As a two stage furnace the furnace s integrated con
309. ressor are energized Circulator blower is energized following a fixed five sec ond on delay Electronic air cleaner terminals are ener gized with circulator blower Furnace circulator blower and outdoor cooling unit run and integrated control module monitors safety circuits continuously R and Y thermostat contacts open completing the call for cool Outdoor fan and compressor are de energized Electronic air cleaner terminals are de energized Circulator blower is de energized following a fixed forty five second cool off delay period Furnace awaits next call from thermostat Fan Only Mode The normal operational sequence in fan only mode is as follows 1 R and G thermostat contacts close initiating a call for fan Integrated control module performs safety circuit checks Circulator blower is energized on low heat speed Elec tronic air cleaner terminals are energized Circulator blower runs integrated control module moni tors safety circuits continuously R and thermostat contacts open completing the call for fan Circulator blower is de energized Electronic air cleaner terminals are de energized Furnace awaits next call from thermostat 115 SYSTEM OPERATION HEATING TIMING CHARTS FOR WHITE RODGERS 50 61 288 TWO STAGE INTEGRATED IGNITION CONTROL OPERATION Example 1 Continuous Call For Low Stage Heat Only 3 High Air Low Circulator Off Blower High L Gas Valve OH Igniter o
310. riac switches and Solid State Relays may allow enough leakage current to turn on G Thermostats that steal power thru Y or other functions are not compatible The ECM control interface can be as simple as a direct connection to the thermostat For example R to G will cause the fan to come at Fan Only R to G to Y will cause the fan to come on at Cooling speed and to to W will cause the fan to come on at heating speed The control requires a common connection from the transformer transformer common to C1 C2 on control In typical applications C1 and C2 will be tied together Addi tional features can be utilized through the motor interface control board these features include 2 Cool CFMs 2 De humidification CFMs 2 Heat CFMs separate Fan Only CFM and feed back information CFM demand SERVICING Power Conditioning HVAC System Control x b Inverter gt LT INPUTS 24 Volts A C Compressor On Hi Low Motor Fan On Control Reversing Valve Aux Emergency Heat Capacity Select Outputs CFM Demand lt ECM ICM CONTROL FLOW CHART NOTE An inductor Power Correction Factor Choke is re quired when powering the 3 4 and 1 horsepower motors with 115 volts The operation of this inductor is to reduce the line current by storing the electrical energy in a magnetic field such that the voltage AC waveform leads the current AC waveform In other word
311. riel pour d celer WHAT TO DO IF YOU SMELL GAS une odeur de gaz Renifler pr s du plancher car certains gaz sont plus lourds que l air et Do not try to light any appliance peuvent s accumuler au niveau 50 Do not touch any electric switch do not use any phone in your building QUE FAIRE S IL Y A UNE ODEUR DE GAZ Immediately call your gas supplier from a neighbor s Ne pas tenter d allumer l appariel phone Follow the gas supplier s instructions Ne toucher aucun interrupteur lectrique f you cannot reach your gas supplier n utiliser aucun t l phone dans le b timent call the fire department Appeler imm diatement le fournisseur de gaz en employant le t l phone d n voisin Respecter la lettre les instructions du C Use only your hand to turn the gas control knob fournisseur de gaz Never use tools If the knob will not turn by Si personne ne r pond appeler le service des hand don t try to repair it call a qualified service incendies technician Force or attempted repair may result in a fire C Ne pousser ou tourner le robinet d admission du gaz or explosion qu la main ne jamais emploer d outil cet effet Si la manette reste coinc e ne pas tenter de la D Do not use this appliance if any part has been underwater r parer appeler un technicien qualifi Quiconque Immediately call a qualified service technician to inspect tente de forcer la manette ou de la reparer peut the appliance and to
312. ring the ON cycle to help prevent overheating of the conditioned space The anticipator is a part of the thermostat and if it should fail for any reason the thermostat must be replaced The heating anticipator setting for furnaces covered in this manual is 0 70 Amps If the anticipator current draw is unknown then an amp draw SERVICING should be taken to determine the anticipator setting Use an amprobe as shown the following drawing 10 TURNS OF THERMOSTAT WIRE From W on thermostat OF AMPROBE READS 4 AMPS CURRENT DRAW WOULD BE 4 AMPS Checking Heating Anticipator Current Amp Draw S 3C Cooling Anticipator The cooling anticipator is a small heater resistor in the thermostat During the OFF cycle it heats the bimetal ele ment helping the thermostat call for the next cooling cycle This prevents the room temperature from rising too high be fore the system is restarted A properly sized anticipator should maintain room temperature within 1 1 2 to 2 degrees range The anticipator is fixed in the subbase and is not to be re placed If the anticipator should fail for any reason the sub base must be changed S 4 CHECKING TRANSFORMER AND CONTROL CIRCUIT A step down transformer 120 volt primary to 24 volt second ary 40 VA Heating and Cooling Models supplies ample capacity of power for either operation DISCONNECT ELECTRICAL POWER SUPPLY 1 Remove blower compartment door to gain acce
313. rizontal Induced Draft C Air Command 80 SSE Furnace E Fifth Design Series X NOx certified 40 80 furnace redesign incorporating feature changes introduced by the new 40 90 GUIC EX 1234101 1234108 furnaces Changes include standardized blower decks access door blower door scroll wrap burner bracket Norton mini igniter and plug connect wiring harness These furnaces also feature an integrated electronic ignition control prepainted textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft C Air Command 80 SSE Furnace Sixth Design Series A Not NOx certified 40 8096 furnace redesign incorporating feature changes introduced by the new 40 9096 GUIC FA P1241801F P1241808F furnaces Changes include standardized blower decks access door blower door scroll wrap burner bracket Silicon Nitride Igniter and plug connect wiring harness These furnaces also feature an integrated electronic ignition control prepainted textured steel cabinet and 409 stainless steel tubular heat exchanger Gas Furnace Upflow Horizontal Induced Draft C Air Command 80 SSE Furnace Sixth Design Series X NOx certified 40 8096 furnace redesign incorporating feature changes introduced by the new 40 9096 GUIC FX 1241901 P121908F furnaces Changes include standardized blower decks access door blower door scroll wrap burner bracket Silicon Nitride I
314. rmostat High Call For Heat Low Off 0 10 64 94 0 15 30 60 90 90 120 Tim 120 150 4 second ime sec 180 210 maximum trial for ignition period Example 4 Initial Call For High Heat Subsequent Call To Low Heat Call Change to Low Heat di 30 Seconds After Call Change to Low Heat f High 7 Circulator Low c Blower Off Y High Gas Valve Low Igniter On PS2 Closed PS1 Closed VA Switches Open High Induced Draft Low Blower Off High Thermostat Low Call For Heat otf 0 10 d 64 94 0 15 60 90 90 120 120 150 4 second 180 210 maximum trial for ignition period 123 SYSTEM OPERATION COOLING TIMING CHARTS FOR WHITE RODGERS 50V61 288 124 Air Circulator Blower Outdoor Fan And Compressor Thermostat Call for Cool Air Circulator Blower Outdoor Fan And Compressor Thermostat Call for Cool TWO STAGE VARIABLE SPEED INTEGRATED IGNITION CONTROL OPERATION Example 1 Continuous Call for Low Stage Cooling Only High Low 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 High Low Off High 0 5 35 Time sec 0 45 CONTINUOUS FAN TIMING CHART FOR WHITE RODGERS 50V61 288 Air Circulator Blower Thermostat Call For Fan TWO STAGE VARIABLE SPEED INTEGRATE
315. rnace The application of a single stage thermostat does not offer true thermostat driven two stage operation but provides a timed transition from low to high fire The furnace will run on low stage for a fixed period of time before stepping up to high stage to satisfy the thermostat s call for heat The delay period prior to stepping up can be set at either 5 or 10 minutes through the DIP switch adjacent to the Heat Off delay DIP switches on the integrated control module To use a single stage thermo stat turn off power to the furnace move the thermostat se lection jumper on the integrated control module from the 74 two stage position to the single stage position turn power back on Refer to the following figures AS _ T Stat selection jumper in T XL Single stage thermostat bw 5 Position TSTAT 5 wm 5 N ES 1 N OFF 8 1 G G L 4 2 L 2 y E 1 _ SR gs 2 E PA I ee 7 El DIP switch position 3 ON DIP Switch position 3 OFF Delay Period 10 minutes Delay Period 5 minutes Single Stage Thermostat Application GUSA BX CX and GUVA BX CX Models 24 Volt Dehumidistat Wiring Typical Field Wiring for 80 GUIV CA DX amp 90 GUVA AX BX Two Stage Variable Speed Gas Furnaces The op
316. roof must terminate at least 12 inches above the roof line or the anticipated snow level and be at least 12 inches from any vertical wall including any antici pated snow build up Aventtermination shall notterminate over public walk Ways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators relief valves or other equipment Thecombustion air intake termination of a direct vent application should not terminate in an area which is frequently dusty or dirty NOTE In Canada the Canadian Fuel Gas Code takes pre cedence over the preceding termination restrictions OTHER THAN COMBUSTION AIR TERMINATION NON DIRECT VENT VENT FLUE TERMINATION NO TERMINATIONS ABOVE WALKWAY GRADE OR HIGHEST ANTICIPATED SNOW LEVEL FORCED AIR INLET DIRECT VENT 9096 Furnace Vent Termination Clearances CANADIAN VENTING REQUIREMENTS 90 FURNACES ONLY In Canada venting must conform to the requirements of the current CAN CGA B149 Installation Code Use only CSA listed two or three inch diameter PVC or ABS pipe solvent cement and fittings throughout Carefully follow the manu facturers instructions for cutting cleaning and solvent ce menting PVC and or ABS The vent can be run through an existing unused chimney provided the space between the vent pipe and the chimney is insulated and closed with a weather tight corrosion re sista
317. rs and establishing flame Ignitor remains on for 3 seconds after gas valve is opened ignition activation period 7 Integrated control module monitors flame presence control begins timing 30 second heat on delay Gas valve will remain open only if is sensed 8 If the thermostat call is for low heat gas valve and in duced draft blower will continue on low stage If the call is for high heat the gas valve and induced draft blower will change to high stage 120 9 Circulator blower is energized on the appropriate heat speed following a fixed thirty second blower on delay The circulator blower requires 30 seconds to ramp up to full speed Electronic air cleaner terminals are energized with circulator blower 10 Furnace is now operating on the specified stage called for by the two stage thermostat 11 Furnace runs integrated control module monitors safety circuits continuously 12 If the two stage thermostat changes the call from low heat to high heat the integrated control module will im mediately switch the induced draft blower gas valve and circulator blower to their high stage settings 13 If the two stage thermostat changes the call from high heat low heat the control will immediately switch the induced draft blower and gas valve to their low stage settings The circulator blower will remain on high heat ing speed for thirty seconds before switching to the low heat circulating speed 14 R
318. s 1 0 Amp maximum at 120 VAC Electronic Air Cleaner 1 0 Amp maximum at 120 VAC Turn OFF power to the furnace before installing any acces sories Follow the humidifier or air cleaner manufacturers instructions for locating mounting grounding and control ling these accessories Refer to the following two figures for installation of either an Electronic Air Cleaner or Humidifier on GUIB or GCIB model furnaces that have a WR50A52 ignition control FLOW ACTUATED SWITCH SR C m ELECTRONIC AIR CLEANER Electronic Air Cleaner Wiring GUIB GCIB with WR50A52 Ignition Control PRODUCT DESIGN INTEGRATED CONTROL MODULE HOT 120 VAC NEUTRAL 120 VAC H L E 1 1 N N HUMIDIFIER TO INDOOR BLOWER HEATING SPEED Humidifier Wiring GUIB GCIB with WR50A52 Ignition Control On all other 8096 amp 9096 furnaces accessory wiring con nections are to be made through the 1 4 quick connect terminals provided on the furnace integrated control module The Humidifier and Electronic Air Cleaner hot and neutral terminals are identified as HUM and field wiring must conform to applicable codes Connections should be made as shown below Control Module Neutral 120 VAC Hot 120 VAC NUES Optional Accessories Accessory Wiring WR50A51 Ignition Control Shown WR50A50 amp HSI 1 1A Ignition Contr
319. s tration 2 AUXILIARY LIMIT CONTROL __ M 4 a 74 7 BLOWER HOUSING Auxiliary Limit Control Location 9096 GCCA GCLA GCVA amp GUVA Furnaces The auxiliary limit control is connected in series with the primary limit control wiring to the integrated ignition control If its temperature should be exceeded it will open interrupt ing the voltage to the gas valve causing it to close If this limit control opens the air circulation blower and in duced draft blower will run continuously on models with White Rodgers 50A50 50A51 or Heatcraft HSI 1 1A ignition con trol On models with the White Rodgers 50A55 50 61 50V61 or Heatcraft HSI 2 ignition control only the air cir culation blower will run continuously The diagnostic light will flash four times These symptoms are identical to a trip of the primary limit control The auxiliary limit control is designed to prevent furnace op eration in case of main blower failure on horizontal or counterflow installations It may also open if the power sup ply is interrupted while the furnace is firing The auxiliary limit control is suitable for both horizontal right and horizontal left installations Regardless of airflow direc tion it does not need to be relocated Disconnect ELECTRICAL Power SUPPLY 1 Remove blower compartment door to gain access to the auxiliary limit control which is located on the lower
320. s the inductor reduces line current which extends the life of the 3 4 and 1 horsepower motors The furnaces requiring an inductor are shown in the follow ing chart 80 Models 90 Models GUIV090 50 GCVA070 40 GUIV115 50 GCVA090 50 GUVA070 40 GUVAO7O 40 ____________ GUVA090 50 80 115550 GUVA115 50 IMPORTANT If the inductor fails there will be no motor operation since this is the LINE power supply black wire BK 6 from the integrated ignition control to the motor To determine if the inductor is at fault you can bypass by the inductor by disconnecting the black wire BK 6 wire from the inductor and connecting it directly to the motor If the motor operates then the inductor will need to be replaced Checking ECM ICM Motors ECM ICM motors connect directly to the AC Line Voltage DO NOT insert contactors in series with the ECM ICM Mo tor AC Line The control is powered continuously to insure reliable start up The connector plug is polarized verify and reverify correct connector orientation before applying power DO NOT force plug into motor and make sure power is off before inserting power connector DO NOT apply voltage to terminals 1 or 2 LINE VOLTAGE NOW PRESENT Check for line voltage on terminals 4 and 5 Verify terminal 3 is ground terminals Terminals 1 and 2 are jumpered in the harness for 120VAC operation AC Line Hot Connection AC Line Neutral Connection Gnd or 120VA
321. s located on either side of the grommet drain holes 3 Confirm that tubes reach bottom of drain trap and that all hoses maintain a downward slope and are not kinked or binding 4 Attach PVC drain line to drain trap outlet with either a 90 elbow or coupling Gas Supply and Piping The furnace rating plate includes the approved furnace gas input rating and gas types The furnace must be equipped to operate on the type of gas applied This includes any con version kits required for alternate fuels and or high altitude PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE THE INLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING PRODUCT DESIGN Inlet gas supply pressures must be maintained within the ranges specified below The supply pressure must be con stant and available with all other household gas fired appli ances operating The minimum gas supply pressure must be maintained to prevent unreliable ignition The maximum must not be exceeded to prevent unit overfiring Inlet Gas Supply Pressure Minimum 5 0 W C Maximum 10 0 W C Minimum 11 0 W C Maximum 13 0 W C Natural Gas HIGH ALTITUDE DERATE When this furnace is installed at high altitude the appropri ate High Altitude orifice kit must be applied This is required due to the natural reduction in the density of both the gas fuel and combustion air as altitude increases The
322. s pressure switch kits Propane Gas Conversion POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH MAY OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED THE APPROPRIATE KITS MUST BE APPLIED TO INSURE SAFE AND PROPER FURNACE OPERATION ALL CONVERSIONS MUST BE PERFORMED BY A QUALIFIED INSTALLER OR SERVICE AGENCY This unit is configured for natural gas The appropriate manufacturer s propane gas conversion kit must be applied for propane gas installations Refer to the propane gas and or High Altitude Installations section for details Gas Valve This unit is equipped with a 24 volt gas valve controlled dur ing furnace operation by the integrated control module As shipped the valve is configured for natural gas The valve is field convertible for use with propane gas by using the ap propriate propane gas conversion kit Taps for measuring the gas supply pressure and manifold pressure are provided on the valve The gas valve has a manual ON OFF control located on the valve itself This control may be set only to the or OFF position Refer to the Lighting Instructions Labelor the Put ting the Furnace Into Operation section of this manual or the installation instructions for use of this control during start up and shut down periods GASPIPING CONNECTIONS To AVOID POSSIBLE UNSATISFACTORY OPERATION OR EQUIPMENT DAMAGE DUE TO UNDERFIRING OF EQUIPMENT USE THE PROPER SIZE OF NATURAL PROPANE GAS PIPI
323. s valves terminal 5 YL 8 wire If you should experience a flame sense problem with the GUIB or GCIB series furnace it is important to verify correct positioning and alignment of the components before replac ing the flame sensor The following drawing illustrates the proper positioning and alignment of the ignitor radiant shield and flame sensor 154 FLAME SWITCH J RADIANT SENSE MODELS Models with WR50A52 Integrated Ignition Control amp Radiant Sense Flame Sensor 80 GUIB amp GCIB Models Only NOTE Any bending twisting or distortion of the electrical tabs on the sensor will adversely affect the calibration of the switch and result in unacceptable performance of the sen SOr Refer to the Radiant Sense System Wiring Diagram in GUIB GCIB Technical Manual for details DISCONNECT ELECTRICAL POWER SUPPLY Remove burner compartment door to gain access to the radiant flame sensor Disconnect the wires from the Radiant Sensor 3 Using a VOM check from common terminal to NC Nor mally Closed should read closed Check from Com mon to NO Normally Open should read open LINE VOLTAGE NOW PRESENT Place unit into a heating cycle 5 gue a VOM check from chassis ground to pin 8 FSO GR 9 wire on ignition control No power check pres sure switch and ignition control 6 Within the ignitor preheat period check from chassis ground to pin 12 FSI BR 10 wire on ignition
324. scribed in 5 3 3 b or 5 3 4 45 PRODUCT DESIGN Space Unconfined For purposes of this Code a space whose volume is not less than 50 cubic feet per 1 000 BTU per hour of the aggregate input rating of all appliances installed in that space Rooms communicating directly with the space in which the appliances are installed through openings not furnished with doors are considered a part of the unconfined space 5 3 3 Equipment Located in Confined Spaces a All Air from Inside the Building The confined space shall be provided with two permanent openings communicating directly with other spaces of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space The total input of all gas utilization equipment installed in the combined space shall be used to determine the required minimum volume Each opening shall have a minimum free area of 1 square inch per 1 000 BTU per hour of the total input rating of all gas utilization equipment in the confined space but not less than 100 square inches One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure The minimum dimension of air openings shall not be less than 3 inches lt Chimney or Gas Vent NOTE Each opening must have a free area of not less than one square inch per 1000 BTU of the total input rating of all equip ment in the enclosure but not less than 100 square inches
325. se 251 28 336 384 E NCC 384 480 p C U C U 045 30 070 30 C U CA070 40 1 SS gt 1 2 1 1 1 1 1 0 A B C D A B C D A B C D A B C D A B C D A B C D 115 40 A B C D 115 50 GUI A B C D 140 50 GUIS070 35 GUIS090 30 GUIS090 50 GUIS115 40 GUIS115 50 GUIS140 50 GUIV070 40 GUIV090 50 GUIV115 50 045 30 168 070 30 2517 070 40 090 30 305 090 50 0 336 305 305 336 384 336 GUI GUI GUI GUI 1 1 c Po 3815 381 384 480 419 419 419 480 251 288 336 3059 905 805 305 336 384 480 391 381 381 384 Po 381 381 594 480 pe Jp get 9 jJ 419 480 gt 279 279 29 28 336 384 __ 335 335 336 384 480 Les 419 419 19 419 480 GUIV140 50 419 419 49 419 480 GCI A B C 045 30 168 192 20 288 GCI A B C D 070 30 210 210 240 288 GCI A B C 070 40 240 288 336 384 GCI A B C 090 30 279 279 28 GCI A B C D 090 50 GCI A B C D 115 40 349 349 349 384 GCI A B C 115 50 __ 349 349 384 480 GCI A B C 140 50 419 419 419 480 GCIS070 88 1 1 251 21 288 395 GCIS090 5
326. side of the blower deck on all 8096 furnaces and on 9096 GUCA GULA and GUSA furnaces or on the blower housing on 9096 GCCA GCLA GCVA and GUVA fur naces Remove the wires from the auxiliary limit control termi nals Use ohmmeter test for continuity across the two ter minals refer to the following auxiliary limit control fig ure No reading indicates the control is open Push red reset button test again if still open replace the con trol VOLT OHM METER RED RESET BUTTON COLOR IDENTIFYING TAB Testing Auxiliary Limit Control 80 amp 90 Furnaces 141 SERVICING To AVOID POSSIBLE FIRE ONLY RESET THE AUXILIRY LIMIT CONTROL ONCE IF IT SHOULD OPEN A SECOND TIME A QUALIFIED SERVICER MUST DETERMINE WHY THE AUXILIARY LIMIT OPENED BEFORE RESETTING AGAIN NOTE If it becomes necessary to slide the blower assem bly out of any of the 8096 furnaces or the 9096 GUCA GULA or GUSA furnace the auxiliary limit control must be removed from the blower deck before the blower assembly can be removed After the blower assembly is reinstalled the aux iliary limit must be reinstalled To aid in identifying these controls color coded labels are attached to the back of the controls Refer to the Auxiliary Limit Charts in furnace Technical Manual for color codes and temperature settings S 7 CHECKING FLAME ROLLOUT CONTROL Atemperature activated manual reset control is mounted to the mani
327. so x x x xx x x x x x x x x x x x x x x x x x x x Guicozocxao x x x x x x x x x x FSESESESE Guicozocaso x x x Dr C045CA30 C045CX30 C045DX30 C070DA30 C070DX30 C070DA40 090 0 090 30 C090DX30 C115DX40 115 50 115 50 C115DA50 C115DX50 140 50 140 50 140 50 C140DX50 Guicozonxao Guicozocx30 GUICO90DA50 GUICO90DX50 GUIC115CA40 GUIC115CX40 C115DA40 GUICO90CA50 GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU GU 3 0 to 6 000 ft 1 6 001 to 8 500 ft X Available for this model Not used in this application 4 8 501 to 11 000 ft 000 ft 000 ft require a pressure switch change 2 6 001 to 11 Note All installations above 6 Note For installations in Canada the Amana 80 furnace is certified only to 4 500 ft 28 LOVIN CLd IVH SLSdLOWH Model Number ACCESSORIES momen EEE EE EEE EEE emo EEE EEE EEE TT ET PEE EE rem EE GEE we fee mes felle Wy UOWWOD Wy UOWWOD EIE
328. ss to the thermostat low voltage wires located at the furnace inte grated control module 2 Remove the thermostat low voltage wires at the furnace integrated control module terminals With Power On and Door Interlock Switch closed LINE VOLTAGE NOW PRESENT 3 Use a voltmeter check voltage across terminals R and C Must read 24 VAC 4 No voltage indicates faulty transformer open fuse bad wiring bad splice or open door interlock switch 5 Checktransformer primary voltage at incoming line volt age connections fuse splices and blower door inter lock switch 6 Ifline voltage is available to the primary side of trans former and not at secondary side the transformer is in operative Replace 7 After completing check and or replacement of transformer and check and or repair of control circuit reinstall blower compartment door 8 Turn on electrical power and verify proper unit opera tion 5 5 CHECKING PRIMARY LIMIT CONTROL All 8096 furnaces use a nonadjustable automatic reset Klixon type limit control stat on a stick part number 107283 Refertothe following drawing for location of the primary limit on the 8096 furnaces Primary Limit Control 74 Primary Limit Control Location 8096 Upflow Furnace Shown Counterflow Similar Style 1 is an open face limit styles 2 and 3 are closed face limits Limit styles are not interchangeable use only the limit listed for that furnace The followin
329. sseoeu 09 00 19ejuoo pejoeuuoosiu 10 pezipixo 10 ue eoeuun uonejedo yms 19109 YOOYD 10 uedo uondnuequ 1981109 pue HONJS 110 s1euing 01 ou oj eunjreJ euo si 037 pue jou si 4 Ajsnonunuoo 1181 041 pue ejeJedo 0 eoeuunJ ejnpoui umouy Ney ue seu pereJDeju ie sei A YZ A 911 ui Suous 2115304 10 ou q31 onsouBeip Gay paeau pue eje1edo 01 eoeuunJ 99S uonejedo uonoy 2A1 981109 sesne9 2016504 s uonduoseg 4 2p09 euuouqy payelossy jo suiojdu AS 10
330. sting with the American Gas Association They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installation instructions of the kit High Altitude Natural Gas Kit For use with Amana furnace models GUCA and GCCA These kits are required when installing Amana Air Command 90 SSE furnaces above their maximum rated altitude This kit contains natural P1210305F P1210306F gas orifices The orifices in the kit have been selected as a result of testing with the American Gas Association They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installation instructions of the kit 17 PRODUCT IDENTIFICATION Model Manufacturing Description High Altitude Natural Gas Kit For use with Amana furnace models GUVA These kits are required when installing Amana Air Command 95 SSE furnaces above their maximum rated P1210307F P1210308F altitude This kit contains natural gas orifices The orifices in the kit have been selected as a result of testing with the American Gas Association They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installation instructions of the kit High Altitude Natural Gas Kit For use with Amana furnace models GUIC EA GUIC FA GUIC EX GUIC FX GUID EA GUIE EX These kits are required when installing Amana Air 1210009 Command 95 SSE furnaces above their maximum
331. switch to close The diagnostic light code for this problem is three short flashes followed by a longer pause The probable cause is either a restricted air in take restricted flue piping disconnected hose to pres sure switches miswiring or faulty pressure switch 5 Open Thermal Protection Device If the primary high limit auxiliary limit or rollout limit control opens the gas valve is de energized Both the induced draft blower motor and air circulator blower are energized on low heat speed The diagnostic light code for this problem is four short flashes followed by a longer pause Ifthe primary or auxiliary limit is open the probable cause is either low conditioned air flow due to dirty filter or high resistance in duct work faulty limit faulty blower or blower speed set too low The primary limit will automatically reset while the auxiliary limit control must be manually reset If the rollout limit control is open the probable cause is insufficient combustion air restricted flue passage or restricted heat exchanger The rollout limit control must be manually reset 6 Flame Sensed with No Call for Heat If the control senses a flame when the gas valve is de energized it will run the induced draft blower and air circulator blower con tinuously on the low heat speed for each The diagnostic light code for this problem is continuous flashing The probable causes are either a short to ground in flame sense circuit misw
332. t door and verify proper unit operation S 13 CHECKING WHITE RODGERS 50450 50A51 50A65 50M61 or 50V61 AND HEATCRAFT HSI 1 1A OR HSI 2 INTE GRATED IGNITION CONTROLS NOTE Failure to earth ground the furnace reversing the neutral and hot wire connection to the line polarity or a high resistance connection in the neutral line may cause the control to lockout due to failure to sense flame To AVOID THE RISK OF ELECTRICAL SHOCK WIRING TO THE UNIT MUST BE PROPERLY POLARIZED AND GROUNDED DISCONNECT POWER BEFORE PERFORMING SERVICE LISTED BELOW The ground wire must run from the furnace all the way back to the electrical panel Proper grounding can be confirmed by disconnecting the electrical power and measuring resis tance between the neutral white connection and the burner closest to the flame sensor Resistance should be less than 10 ohms The ignition control is a combination electronic and electro mechanical device and is not field repairable Complete unit must be replaced The White Rodgers 50A50 or 50A51 and the Heatcraft HSI 1 1A or HSI 2 ignition controls control all furnace opera tions including blower operation in air conditioning Blower time delays are controlled by the ignition control see Circu lator Blower Timings section in this manual for blower delay information LINE VOLTAGE NOW PRESENT These tests must be completed within a given time frame due to the operation of the ignition control Refer to
333. tal Furnace Shown 8096 Horizontal Furnace Similar DRAIN TRAP AND LINES 90 FURNACES ONL Y In horizontal applications the condensate drain trap is se cured to the furnace side panel suspending it below the furnace A minimum clearance of 4 3 4 below the furnace must be provided for the drain trap Additionally the appro priate downward piping slope must be maintained from the drain trap to the drain location Refer to Condensate Drain Trap and Lines section in this manual or the installation instructions for further details If the drain trap and drain line will be exposed to temperatures near or below freezing ad equate measures must be taken to prevent condensate from freezing NOTE The use of insulation and or heat tape is recommended Failure to provide proper condensate drain age can result in property damage LEVELING 90 6 FURNACES ONLY Leveling ensures proper condensate drainage from the heat exchanger and induced draft blower For proper flue pipe drainage the furnace must be level lengthwise from end to end The furnace should also be level from back to front or have a slight tilt with the access doors downhill approxi mately 3 4 from the back panel The slight tilt allows the heat exchanger condensate generated in the recuperator coil to flow forward to the recuperator coil front cover ALTERNATE VENT FLUE AND COMBUSTION AIR CONNECTIONS 90 FURNACES ONL Y In horizontal installations provisions for alternate
334. tallation GCVA This kit is not certified for and must not be applied to any furnace not listed in the above table 39 ACCESSORIES COMMON VENT KIT Vent Damper 2051 1410 From furnace Flow To Chimney Install vent damper with actuator to sides of vent only Do not mount vent damper with actuator above or below the vent Horizontal Vent Installation CVK4 7 COMMON VENT KITS Kit Model Vent Diameter Numbers Inches 4 5 7 40 gt From furnace Install vent damper with actuator in any position Vertical Vent Installation CVK4 7 COMMON VENT KITS Used on Models PRODUCT DESIGN Safely Please adhere to the following warnings and cautions when installing adjusting altering servicing or operating the fur nace PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE REFER TO THIS MANUAL FOR ADDITIONAL ASSISTANCE OR INFORMATION CONSULT QUALIFIED INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER THIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL S WHICH MAY CAUSE DEATH OR SERIOUS ILLNESS AND WHICH ARE KNOWN BY THE STATE OF CALIFORNIA TO CAUSE CANCER BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM PREVENT POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK THE FURNACE MUST BE LOCATED TO PROTECT THE ELECTRICAL COMPONENTS FROM WATER This furna
335. tch or loose or misconnected wir ing NOTE There is a twenty minute lockout if the pressure switch has tripped five times during a single call for heat 10 Primary or Auxiliary Limit Opened Five Times Dur ing a Single Call for Heat Heatcraft HSI 2 Control Only If the furnace fails to operate due to primary or auxiliary limit opening five times during a single call for heat the control will run the air circulation blower con tinuously with no further furnace operation The diagnos tic light code for this problem is nine flashes followed by a pause The probable cause is either low conditioned air flow due to dirty filter s or resistance in duct work faulty limit faulty blower or blower speed set to low NOTE There is a one hour lockout if either the primary or auxiliary limit has tripped five times during a single call for heat SYSTEM OPERATION 11 Flame Sensed with No Call for Heat If the control senses a flame when the gas valve is de energized it will run the air circulation blower and the induced draft blower continuously with no further furnace operation The diagnostic flash code for this is a continuous flash The probable causes are either a shortto ground in flame sense circuit miswiring lingering burner flame or a slow closing gas valve NORMAL SEQUENCE OF OPERATION 80 90 Models with White Rodgers 50A65 Integrated Ignition Control Power Up The normal power up sequence is as follows 115 V
336. ter Testing Primary Limit Control 8096 Furnaces VOLT OHM METER COLOR IDENTIFYING TAB Testing Primary Limit Control 9096 Furnaces 4 After completing check and or replacement of primary limit control reinstall burner compartment door 5 Turnon electrical power and verify proper unit operation To aid in identifying these controls refer to the T O D Pri mary Limit Charts in furnace Technical Manual for style num ber temperature setting and sleeve color s code SERVICING S 6 CHECKING AUXILIARY LIMIT CONTROL All the 80 and 90 furnaces use an additional limit switch required for safety control of high temperature within the fur nace or duct work This control is preset nonadjustable and must be manually reset The control is located in the blower compartment of the furnace either on the blower deck or blower housing The auxiliary manual reset limit is located on the lower side of the blower deck near the center on all 80 furnaces and on the 90 GUCA GULA and GUSA furnaces as shown in the following illustration AUXILIARY LIMIT r CONTROL X gt X 2 BLOWER DECK Auxiliary Limit Control Location All 80 Furnaces amp 90 GUCA Furnace The auxiliary manual reset limits Qty 2 are located on the blower housing one on each side on 90 GCCA GCLA GCVA and GUVA furnaces as shown in the following illu
337. terface board on GUIV CA DX amp GUVA AX models or adjacent to the DEHUM screw terminal on the furnace s integrated control module on the GUVA BX CX models Refer to the following figures PRODUCT DESIGN GUIV FX amp GUVA BX CX Two Stage Variable Speed Furnace Thermostat Wiring Reference Chart GENERAL HEATING COOLING CONTINUOUS FAN Thermostat Connection 24 Volts HOT 24 Volts COMMON Low Stage Connection For Two Stage Heating High Stage Connection For Two Stage Heating Connection For Single Stage Cooling Low Stage Connection For Two Stage Cooling High Stage Connection For Two Stage Cooling Continuous Fan Connection From Room Thermostat From Room Thermostat From Room Thermostat From Room Thermostat From Room Thermostat From Room 8 Thermostat From Room Thermostat From Room Thermostat Connection Options On Two Stage Integrated Control Module On Two Stage Integrated Control Module On Two Stage Integrated Control Module On Two Stage Integrated Control Module On Two Stage Integrated Control Module On Two Stage Integrated Control Module On Two Stage Integrated Control Module On Two Stage Integrated Control Module Furnace Circulator Blower Operation During Call From Thermostat N A Circulator blower will operate on
338. terminals are de energized Circulator blower is de energized following a fixed forty five second cool off delay period The air circulator blower will ramp down for another 30 seconds and shut down Furnace awaits next call from thermostat Fan Only Mode The normal operational sequence in fan only mode is as follows 1 R and G thermostat contacts close initiating a call for fan Integrated control module performs safety circuit checks 3 Circulator blower is energized on low heat speed Elec tronic air cleaner terminals are energized Circulator blower runs integrated control module moni tors safety circuits continuously R and Gi thermostat contacts open completing the call for fan Circulator blower is de energized Electronic air cleaner terminals are de energized The air circulator blower will ramp down for another 30 seconds and shut down Furnace awaits next call from thermostat 106 NORMAL SEQUENCE OF OPERATION Dehumidification Mode The normal operational sequence for dehumidification is as follows 1 R and Y thermostat contacts close initiating a call for cool Integrated control module performs safety circuit checks 3 Outdoor fan and compressor energized 4 Circulator blower is energized following a fixed five sec 10 11 ond on delay The circulator blower will take 30 seconds to ramp up to full speed Electronic air cleaner terminals are energized with circulator
339. the neutral and hot wire connection to the line polarity or a high resistance connection in the neutral line may cause the control to lockout due to failure to sense flame To AVOID THE RISK OF ELECTRICAL SHOCK WIRING TO THE UNIT MUST BE PROPERLY POLARIZED AND GROUNDED DISCONNECT POWER BEFORE PERFORMING SERVICE LISTED BELOW The ground wire must run from the furnace all the way back to the electrical panel Proper grounding can be confirmed by disconnecting the electrical power and measuring resis tance between the neutral white connection and the burner closest to the flame sensor Resistance should be less than 10 ohms The ignition control module is a combination electronic and electromechanical device and is not field repairable Com plete unit must be replaced SERVICING The WR50A52 ignition control controls all furnace opera tions including blower operation in air conditioning Blower time delays are controlled by the ignition control and are nonadjustable see the specification section for blower de lay information LINE VOLTAGE NOW PRESENT These tests must be completed within a given time frame due to the operation of the ignition control See Sequence of Operation section for timing chart 1 Checkfor 120 volts from Line 1 BK6 wire to line 2 neu tral WH 33 wire atthe ignition control No voltage check the door switch connections and wire harness for conti nuity 2 Check 24 volts from
340. the National Board of Fire Underwriters for the In stallation of Air Conditioning Warm Air Heating and Venti lating Systems Pamphlets No 90A and 90B A return air filter is not supplied with the furnace The in staller must supply a means of filtering all of the return air Filter s shall comply with UL900 or CAN ULC S1 11 Stan dards If the furnace is installed without filters the warranty will be voided The following two charts show the bottom and side return filter sizes available for each size furnace Larger sizes are also acceptable BOTTOM RETURN AIR FILTER SIZES Cabinet Width Filter Size Inches Filter Area in2 16 1 2 14 25 1 350 20 1 2 16 X 25 X 1 24 1 2 20 X 25 X 1 SIDE RETURN AIR FILTER SIZE Cabinet Width Filter Size Inches Filter Area in All Widths 16x 25x 1 The following sketch below shows how the filter is retained over the bottom return air opening Z 5 CAPTIVE LANCES T IN BACK PANEL 2 FILTER 00 2 LL RETAINER gt c FILTER FURNACE BOTTOM Bottom Return Filter Retention One inch throwaway filters should be sized for a face veloc ity of 300 feet per minute or less 14x25x1 throwaway 730 maximum 16x25x1 throwaway 830 maximum 18x25x1 throwaway 940 maximum 20x25x1 throw away 1040 maximum All other filters should be sized according to their manufacturer s instructions To find the minimum
341. ther ap pliance outside the liner is not acceptable PRODUCT DESIGN Next use a flashlight and small mirror to sight up the liner B vent must be supported so as to not come into direct contact with the chimney walls or tile liner If itis not it can probably be rehung so as to be acceptable A thimble or fire stop may be helpful here Flexible liners should be hung straight or nearly straight If it is spiraled in the chimney and in good condition it should be rehung To do this break the top seal pull up and cut off the excess liner length and refit the top seal Use caution when doing this as the cut edges of flexible liners may be sharp The surfaces of the liner must be physically sound If gaps or holes are present the metal liner must be removed and replaced Fix 4 Finally confirm that the metal liner is the correct size for the appliances to be installed Use the GAMA tables and rules If a metal liner is not present a clay tile liner must be present or the chimney must be lined Fix 4 Use a flashlight and small mirror at the cleanout or vent connector to inspect the clay tile liner If any of the following problems are present Tile sections misaligned Tile sections missing Gaps between tile sections Signs of condensate drainage at the cleanout or vent connectors Mortar protruding from between tile sections Useofsewer pipe or drainage pipe rather than an ap proved fire clay tile reline
342. tion devices that can be installed in any position except with the access door facing down The best location for the air cleaner is in the return air duct next to the blower compartment Before installing the air cleaner consider the application The electronic air cleaner must be readily accessible for periodic inspection and clean ing of the pre filters and electronic cells while the media air cleaner must be readily accessible for periodic inspection and replacement of the media cartridge MAF to maintain maximum efficiency and trouble free operation Accomodator Filter Housing ACG1625 3 6 ACG2025 3 6 and ACG2424 3 6 The Accomodator is a filter cabinet that provides a location external to the furnace casing for installation of a filter on upflow model furnaces using bottom return The Accomodater gives the homeowner the option of using many choices of filter types and sizes The filter sizes that may be used are 1 2 and 4 86 Horizontal Filter Housing HR20 amp HR25 The Horizontal Filter Housing provides a location external to the furnace casing for installation of a filter s on upflow model furnaces using side air return s The Horizontal Filter Hous ing gives the homeowner the option of using many choices of filter types and sizes The filter sizes that may be used are 1 2 or 4 NOTE For complete details on each of the additional filter ing accessories refer to the instructions provided with each accessory
343. tional usage of a dehumidistat allows the furnace s circulator blower to operate at a slightly lower speed during a combined thermostat call for cooling and dehumidistat call for dehumidification This lower blower speed enhances de humidification of the conditioned air as it passes through the AC coil For proper function a dehumidistat applied to this furnace must operate on 24 VAC and utilize a switch which opens on humidity rise To install connect a dehumidistat 1 Turn OFF power to furnace 2 Securethe dehumidistat neutral wire typically the white lead to the screw terminal marked on the furnace s circulator blower interface board on GUIV CA DX amp GUVA AX models or the furnace s integrated con trol module on GUIV FX GUVA BX C X models 3 Secure the dehumidistat hot wire typically the black lead to the screw terminal marked R1 on the furnace circulator blower interface board on GUIV CA DX amp GUVA AX models or to the screw terminal marked R on the furnace s integrated control module on GUVA BX CX models 4 Secure the dehumidistat ground wire typically the green lead to the ground screw on the furnace junction box NOTE Ground wire may not be present on all dehumidistats 5 Turn ON power to furnace To enable the dehumidify function on the circulator blower interface board 1 Cutthe jumper wire labeled CUT TO ENABLE located within the box labeled DEHUMIDIFY on the circulator blower in
344. tment to the burner compartment and incorporation of coarser threaded thumb screw and U clips instead of clinched inserts for engagement GUVA CX P1252901F P1252906F PRODUCT IDENTIFICATION This section will identify the models covered and the changes per each model group from one release to the next Model Manufacturing Description Adjustable Subbase Kit For use with Amana furnace models GCIA GCIB GCIC and GCIS Must be used to prevent excessive temperature from reaching combustible ASBO1 materials if the furnace is installed on a combustible floor This subbase effectively P1200201F P1200202F separated the furnace base and plenum from combustible materials To ensure safe installation do not install the counterflow floor base directly on carpeting tile or other combustible material other than wood flooring Counterflow Floor Base Kit For use with Amana furnace models GCCA Must be used to prevent excessive temperature from reaching combustible materials if the furnace is CFB16 24 installed on a combustible floor This subbase effectively separated the furnace base and P1228001F P1228003F plenum from combustible materials To ensure safe installation do install the counterflow floor base directly on carpeting tile or other combustible material other than wood flooring Common Vent Kit For use with Amana 8096 furnace models GUIA GUIB GUIC GUID GCIA GCIB and GCIC Must be used on
345. to Type B BW or L vent or vent connector and must not be vented into any portion of a factory built or masonry chimney except when used as a pathway for PVC as described later in this sec tion Never common vent this appliance with another appli ance or use a vent which is used by a solid fuel appliance Do not use commercially available no hub connectors other than those shipped with this product 54 It is the responsibility of the installer to follow the manufac turers recommendations and to verify that all vent flue pip ing and connectors are compatible with furnace flue prod ucts Additionally it is the responsibility of the installer to ensure that all piping and connections possess adequate structural integrity and support to prevent flue pipe separa tion shifting or sagging during furnace operation DUAL CERTIFICATION NON DIRECT DIRECT VENT 90 FURNACES ONL Y The 90 furnace is dual certified and may be installed as a non direct vent single pipe or direct vent dual pipe appli ance A non direct vent installation requires only a vent flue pipe while a direct vent installation requires both a vent flue pipe and a combustion air intake pipe Refer to the appropri ate section for details concerning piping size length num ber of elbows furnace connections and terminations MATERIALS AND JOINING METHODS 90 FURNACES ONLY To AVOID BODILY INJURY FIRE OR EXPLOSION SOLVENT CEMENTS MUST KEPT AWA
346. trol module provides terminals for both W1 and W2 and Y thermostat connections This allows the furnace to support the following system applications Two Stage Heating Only or Two Stage Heating with Single Stage Cooling Refer to the following figures for proper connections to the integrated control module Thermostat Two Stage Heating Ww 8 OO OO 09 09 Two Stage Heating Only 12 Thermostat Two Stage Heating with Single Stage Cooling Furnace Integrated Control Module Remote Condensing Unit Two Stage Heating with Single Stage Cooling Typical Field Wiring for GUIS and GCIS Two Stage Gas Furnaces 24 VAC Control Circuit Thermostat Single Stage Heatin with Single Stage Cooling Furnace Integrated Control Module Twinning Communication Optional Remote Condensing Unit Single Stage Cooling Single Stage Heating with Single Stage Cooling NOTE To apply a single stage heating thermostat the thermostat selector jumper on the integrated control module must be set on single stage Thermostat Two Stage Heating with Single Stage Cooling Furnace Integrated Control Module Twinning Communication Optional Remote Condensing Unit Two Stage Heating with Single Stage Cooling Typical Field Wiring for GUSA BX Two Stage Gas Furnaces 24VAC Control Clrcuit PRODUCT DESIGN Thermostat Wiring 80 GUIV
347. tul es Comment coupler l admission follow the instructions To Turn LEVER SHOWN de gaz de l appereil et appeler un technicien Off Gas To Appliance and call your IN ON POSITION qualifi ou le fourrnisseur de gaz vise o ARRETER Lisez les instructions de s curit sur la portion sup rieure de cette tiquette R gler le thermostat la temp rature la plus basse Couper l alimentation lectrique de l appareil Cet appareil m nager tant dot d un syst me d allumage automatique ne pas essayer allumer le br leur manuellement 5 Pousse le levier du contr le du gaz OFF ARRET position 6 Attendre cinq 5 minutes pour laisser echapper tout le gaz Renifler tout autour de l appareil y compris pr s du plancher pour d celer une odeur de gaz Si c est le cas ARRETER Passer l tape B des instructions de s curiti sur la portion sup rieure de cette tiquette S il n y a pas d odeur de gaz passer l tape suivant 7 Pousse le levier du contr le du gaz position 8 Remettre en place le panneau d acc s 9 Mettre l appareil sous tension R gler le thermostat la temp rature desir e 11 Si l appareil ne se met pas en marche suiyre les Ron LEVIER A GAZ ON MARCHE TURN OFF GAS TO APPLIANCE 1 Set the thermostat to lowest setting 2 Turn off all electric power to the appliance if service is to be per
348. u 14 09 1294109 BSN ILON 2189 21u0J129J8 Buiuedo Jamod Bunoeuuoosip G We M ureda 1019 440 un si ee ansio PUB peunooo QINISIO JO woad pue I sey ML p 10 0 Bumes peeds 1ewo q 1981109 01 1snfpy JONP 1994109 429u2 redau 440 10 520 peeds 1ewo q 1981109U Ajddns 1984109U peeds W42 40 128409UJ 10 peeds samojq JO YO9YD Sjeued 10 sjeuiqeo sjonp ui BUINSIQM 10 yOOUD sjeued 9600 10 YOOUD sjaued Jo sjeuiqeo Syed peeds 1ewo q 1 sjaued 18m0jq 95001 esiou redau 440 jo SION Bumes peeds 12909
349. u de la reparer peut the appliance and to replace any part of the control d clencher une explosion ou un incendie System and any gas control which has been underwater D Ne pas se servir de cet appareil s il a t plong dans l eau compl tement ou en partie Appeler un technicien qualifi pour inspecter l appareil et remplacer tout partie du syst me de contr le et toute commande qui ont t plong s dans l eau B OPERATING INSTRUCTIONS wise EN 1 STOP Read the safety information above on ARRET RI Lisez les instructions de s curit sur i this label la portion sup rieure de cette tiquette 2 Set the thermostat to lowest setting 2 R gler le thermostat la temp ratu re la plus basse 8 Turn off all power to the appliance 3 Couper l alimentation lectrique de appareil 4 This appliance is equipped with an ignition 4 Cet appareil m nager tant dot d un syst me device which automatically lights the burner d allumage automatique ne pas essayer Do not try to light the burner by hand allumer le br leur manuellement 5 the gas control lever clockwise 4 to 5 Torner le levier a gaz dans le sens des aigilles OFF Position Do not force d une montre 4 en position OFF ARRET 6 Wait five 5 minutes to clear out any gas Then 6 Attendre cinq 5 minutes pour laisser echapper tout le smell for gas including near the floor If you gaz Renifler tout autour de l ap
350. union to reach the exterior of the furnace NOTE The rigid pipe must be long enough to reach the outside of the cabinet so as to seal the grommet cabinet penetration on the 9096 amp 9596 furnaces A semi rigid connector to the gas piping can be used outside the cabinet per local codes PRODUCT DESIGN SR SE ALTERNATE SHUT OFF VALVE MANIFOLD BURNERS SHUT DRE VALVE UPSTREAM FROM GAS LINE UPSTREAM FROM F GROUND JOINT ES j GROUND JOINT y PIPE UNION ES PIPE UNION H I E 100 pe 520 1 HEIGHT REQUIRED AUN E HEIGHT REQUIRED BY LOCAL CODE GAS LINE BY LOCAL CODE R 7 27 42 IN STANDARD GAS LINE HOLE GROUND JOINT 7 GAS VALVE PIPE UNION GROMMET IN STANDARD GAS LINE HOLE e MANIFOLD DRIP LEG lt DRIP LEG BURNERS GROUND JOINT PIPE UNION gt MANUAL SHUT OFF VALVE 7 UPSTREAM FROM GROUND 24 MANUAL SHUT OFF VALVE JOINT PIPE UNION 7 UPSTREAM FROM GROUND A GROUND JOINT A JOINT PIPE UNION GROUND JOINT PIPE UNION PIPE UNION 1 AL DRIP LEG 11 DRIP LEG CoU b d GAS VALVE GROMMET IN STANDARD GAS VALVE __ GROMMET IN STANDARD ps GAS LINE HOLE um Pd GAS LINE HOLE BURNERS BURNERS AO
351. ur nace 6 Turn OFF any unnecessary gas appliances started in step 3 7 Turn on gas to furnace and check for leaks If leaks are found repair and then reinstall burner compartment door 8 on electrical power and verify proper unit operation Gas Manifold Pressure Measurement and Adjustment 80 amp 90 Single Stage Furnaces To PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULATOR Only small variations in gas pressure should be made by adjusting the gas valve pressure regulator The manifold pres sure must be measured with the burners operating To mea sure and adjust the manifold pressure use the following pro cedure Disconnect ALL ELECTRICAL POWER AND SHUT OFF GAS SUPPLY BEFORE SERVICING OR INSTALLING 1 Afterturning off gas to furnace at the manual gas shutoff valve external to the furnace remove burner compart ment door to gain access to the gas valve 2 Connect a calibrated water manometer or appropriate gas pressure gauge at the gas valve outlet pressure tap as shown in the following figure GAS VALVE CONTROL g ON Off SWITCH MANOMETER HOSE OPEN TO ATMOSPHERE INLET PRESSURE SIDE OF VALVE OUTLET MANIFOLD PRESSURE TAP SIDE OF VALVE PRESSURE REGULATOR ADJUSTMENT UNDER CAP SCREW
352. ure with Integrated Ignition Control If the control determines it has an internal fault it enters a locked out state and the diagnostic light will light continuously with no flashes The control should be replaced 2 External Lockout An external lockout occurs when the integrated ignition control determines that a measurable combustion cannot be established or maintained after three consecutive tries four if flame is established then lost to turn on the furnace If a flame is not sensed during the first seven seconds after a gas valve has been energized the ignition control will internally turn off the gas After 120 seconds for 50A51 225 and after 60 seconds for 50A51 235 during which time the induced draft blower purges the heat exchanger the ignitor will reenergize and preheat for 27 seconds The gas valve is then reenergized If a flame is not sensed again in seven seconds the gas valve will de energize and another purge is performed The ignition control will cycle the gas valve three times before it determines it cannot establish measurable combustion and enter a lockout state If a flame is sensed but lost after 10 sec onds the control will cycle four more times before lock ing out A lockout stops ignition attempts and causes the air circulating blower to run continuously The diag nostic light code for either problem is one short flash followed by a longer pause The control can be reset and brought out of lockout mode
353. ures in excess of 1 2 psig 3 48 kPa Isolate this unit from the gas supply piping system by closing its external manual gas shutoff valve before pressure testing supply piping sys tem with test pressures equal to or less than 1 2 psig 3 48 kPa Propane Gas Tanks and Piping PROPANE GAS IS HEAVIER THAN AIR AND ANY LEAKING GAS CAN SETTLE IN ANY LOW AREAS OR CONFINED SPACES TO PREVENT PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK INSTALL A GAS DETECTION WARNING DEVICE A gas detecting warning system is the only reliable way to detect a propane gas leak oxide rust can reduce the level of odorant in propane gas Do not rely on your sense of smell Contact a local propane gas supplier about installing a gas detecting warning system If the presence of gas is suspected follow the instructions on Pages 20 25 of this manual All propane gas equipment must conform to the safety stan dards of the National Board of Fire Underwriters NBFU Manual 58 For satisfactory operation propane gas pressure must be 11 inch WC at the furnace manifold with all gas appliances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate depending on temperature of the lig uid and wetted surface area of the container or tainers 2 Proper pressure regulation Two stage regulation is rec ommended for both cost and efficiency 3 Pr
354. use tools If the knob will not turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been underwater Immediately call a qualified service technician to inspect the appliance and to replace any part of the control System and any gas control which has been underwater AVERTISSEMENT Quiconque ne respecte pas la lettre les instructions dans le pr sent manuel risque de d clecher un incendie ou une explosion entrainant des dammages mat riels des l sions corporelles ou la perte de vies humaines Cet appareil ne comporte pas de veilleuse Il est muni d un dispositif d allumage qui allume automatiquement le br leur Ne pas tenter d allumer le br leur manuellement B AVANT DELE FAIRE FONCTIONNER renifler tout autour de l appariel pour d celer une odeur de gaz Renifler pr s du plancher car certains gaz sont plus lourds que l air et peuvent s accumuler au niveau du 50 1 QUE FAIRE S IL Y A UNE ODEUR DE GAZ Ne pas tenter d allumer l appariel Ne toucher aucun interrupteur lectrique n utiliser aucun t l phone dans le b timent Appeler imm diatement le fournisseur de gaz en employant le t l phone d n voisin Respecter la lettre les instructions du fournisseur de gaz Si personne ne r pond appeler le service des incendies C Ne pousser ou tourner le robinet d admissio
355. ve Tap 9 Turn on gas to furnace and check for leaks If leaks are found repair and then reinstall burner compartment door 10 Turn on electrical power and verify proper unit operation Gas Manifold Pressure Measurement and Adjustment 80 amp 90 Two Stage Furnaces Natural Gas Adjustments 1 Afterturning off gas to furnace at the manual gas shutoff valve external to the furnace remove burner compart ment door to gain access to the gas valve 2 Connecta calibrated water manometer or appropriate gas pressure gauge at the gas valve outlet pressure tap Refer to previous Measuring Manifold Gas Pressure figure for proper connection LINE VOLTAGE NOW PRESENT 3 Turn ON the gas and electrical power supply and oper ate the furnace 4 Remove the cap screw from the high stage manifold pres sure regulator 5 Using a 3 32 Allen wrench adjust the high stage mani fold pressue regulator to the required pressure setting 6 Reinstall high stage cap screw and recheck manifold pressure setting with cap on 7 Remove the cap screw from the low stage manifold pres sure regulator 8 Using a 3 32 Allen wrench adjust the ow stage regula tor to the required pressure setting 9 Reinstall lowstage cap screw and recheck manifold pres sure setting with cap on 158 Disconnect ALL ELECTRICAL POWER AND SHUT OFF GAS SUPPLY BEFORE SERVICING OR INSTALLING 10 Disconnect manometer after turning off gas at manu
356. vide filter retention as well as a location for attaching return air ductwork EN P9458403F Electronic Air Cleaner P1171303F P1171305F 4 blowers set to deliver the same air flow at the same time The furnaces may deliver different CFM s in the cooling mode if applicable This kit cannot be used to control more than two furnaces High Altitude Pressure Switch Kit For use with Amana furnace models GUIA GUIB GUIC GUID GCIA GCIB and GCIC These kits contain a high altitude Category pressure switch that must be used at altitudes above the rated altitudes because of reduced air density High Altitude Pressure Switch Kit For use with Amana furnace models GUIC EA HAC1PS15 1204227 GUIC FA GUIC EX GUIC FX GUID EA GUIE EX These kits contain a high Furnace Twinning Kit This kit allows two Amana Air Command gas furnaces containing an Integrated Ignition control to operate at the same time from a single thermostat The two furnaces to be twinned must be the exact same model with their circulating air HAC1PS1 14 P1204211F P1204226F altitude Category pressure switch that must be used at altitudes above the rated altitudes because of reduced air density PRODUCT IDENTIFICATION This section will identify the models covered and the changes per each model group from one release to the next Model Manufacturing 8 Description High Altitude Propane Gas Conversion Kit For use with Amana furnace
357. visions for venting combustion products outdoors through a proper venting system Special consideration should be given to vent flue pipe routing and combustion air intake pipe when applicable 8096 Furnaces All installations must be vented in accordance with National Fuel Gas Code NFPA 54 ANSI Z223 1 lateset edition In Canada the furnaces must be vented in accordance with the National Stan dard of Canada CAN CGA B149 NOTE Also for the installers use Amana brand ships a Category Two Stage Venting Manual with each two stage 80 fur nace PRODUCT DESIGN 90 Furnaces Refer to the Vent Flue Pipe Com bustion Air Pipe Termination Locations section in this manual or the installation instructions for appropriate termination locations Also for 9096 furnaces refer to the Vent Flue Pipe and Combustion Air Pipe Termi nation Locations section in this manual or the instal lation instructions to determine if the piping system from furnace to termination can be accomplished within the guidelines given NOTE The length of flue and or combustion air piping can be a limiting factor in the location of the furnace Locate the 9096 furnace so that the condensate can be piped at a downward slope away from the furnace to the drain Do not locate the furnace or its conden sate drainage system in any area subject to below freezing temperatures without proper freeze protec tion Refer to the Condensate Drain Lines and Trap section
358. w models relocation of the front cover pres sure switch hose is required from the right side as shipped pressure tap to the left down side tap The pressure switch hose must be connected to the down side to guard against blocked drain conditions The hose must be cut to appropri ate length to minimize sagging NOTE Use RF000142 Drain Coupling Kit for horizontal left applications 64 INDUCED DRAFT BLOWER DRAIN PORT _ HOSEB 2 COVER WV HOSE A PRESSURE 57 4 GREEN HOSE CLAMPS 8 PLACES T a LEFT SIDE lt ML TuBE S 2 PANEL FRONTCOVER DRAIN PORT RED HOSE CLAMP p DRAIN TRAP SIDE PANEL GROMMET HOLES 9096 Furnace Horizontal Drain Hose Connections Left Side Down NOTE Ensure hoses and tubes maintain a downward slope for proper drainage and that they are not kinked or binding For details concerning mounting of the drain trap refer to Condensate Drain Lines and Drain Trap Horizontal Drain Trap Mounting in this manual or the installation instructions Horizontal Drain Trap Mounting Left or Right Side Panel 1 Position the drain trap against side panel with drain tubes inserted into trap Note that the trap may be orientated with the outlet facing either the furnace s top cover or base pan 2 Secure drain trap to side panel at the dimples or crosshair
359. wiring 4 Pressure Switch Stuck Open If after the induced draft blower is energized the pressure switch does not close the control will keep the induced draft blower on and wait for the switch to close The diagnostic light code for this problem is three short flashes followed by a pause The probable causes are either a blocked pinched or disconnected hose to the pressure switch faulty pres sure switch or loosse or misconnected wiring restricted air intake or flue piping blocked drain system or weak induced draft blower 5 Open Primary Auxiliary or Rollout Limit If the limit control opens the air circulator blower will be turned on until the limit closes The diagnostic light code for this problem is four short flashes followed by a pause The probable cause for either an open primary or auxiliary limit is low conditioned air flow due to dirty filter or resis tance in duct work faulty limit faulty blower blower speed set to low or loose or misconnected wiring The rollout limit s is are open due to flame rollout The probable cause for an open rollout limit is misaligned burners blocked flue and or air inlet pipe failed induced draft blower or loose or misconnected wiring 6 Reversed Polarity If the 115V or 24V AC power leads are reversed the furnace will fail to operate The diag nostic light code for this problem is six flashes followed by a pause The probable cause is either the 115V AC power to furnace or integr
360. with an exit through the side of the building or run vertically with an exit through the roof of the building The vent can also be run through an existing unused chimney however it must extend a mini mum of 12 inches above the top of the chimney The space between the vent pipe and the chimney must be closed with a weather tight corrosion resistant flashing For details con cerning connection of the vent flue pipe to the furnace refer to Vent Flue Pipe and Combustion Air Pipe Standard Fur nace Connections or Alternate Furnace Connections sec tion in this manual or the installation instructions for specific details Refer to the following Non Direct Vent Single Pipe Piping Vent Flue Pipe Terminations section in this manual or the installation instructions for specific details on termi nation construction Although non direct ventinstallations do not require a com bustion air intake pipe a minimum of one 90 elbow must be attached to the furnace s combustion air intake if an upright installation uses the standard intake location or a horizontal installation uses the alternate air intake location This elbow will guard against inadvertent blockage of the air intake 57 PRODUCT DESIGN Vent Flue Pipe Lengths and Diameters 90 Furnaces Only Refer to the following tables for applicable length elbows and pipe diameter for construction of the vent flue pipe sys tem of a non direct vent installation In addition to the vent
361. wn 11 Furnace awaits next call from thermostat 121 SYSTEM OPERATION HEATING TIMING CHARTS FOR WHITE RODGERS 50V61 288 TWO STAGE INTEGRATED IGNITION CONTROL OPERATION Example 1 Continuous Call For Low Stage Heat Only Air High Circulator Low Blower Off On Gas Valve Off On Igniter Off Pressure PS2 Closed Switches PS1 Closed Open High Induced Draft Low Blower Off High Thermostat Low Call for Heat Off 2 10 m o 64 94 0 15 30 60 90 90 120 120 150 14554 180 210 maximum trial for ignition period Example 2 Continuous Call For High Stage Heat Only Air i Circulator Blower High Gas Valve pe Igniter Off 52 Closed ressure PS1 Closed Switches Open Induced Draft ja Blower Off High Thermostat ps Call for Heat Off 10 64 94 0 15 30 120 150 4 second Tine sec 180 ad maximum trial for ignition period 122 SYSTEM OPERATION HEATING TIMING CHARTS FOR WHITE RODGERS 50V61 288 TWO STAGE INTEGRATED IGNITION CONTROL OPERATION Example 3 Initial Call For Low Heat Change In Call To High Heat Call Change to High Heat High V Circulator Low Blower High Gas Valve Low Off Igniter On Off V PS2 Closed U Pressure PS1 Closed Switches Open Induced Draft High VA Blower Low Off The
362. xIxIxI Tat EE EE EE 22 GCIS090CX50 ACCESSORIES 3 0 to 7 000 ft 3 001 to 7 000 ft 2 7 001 to 8 500 ft Note installations above 6 000 ft require a pressure switch change 1 Note For installations in Canada the Amana 80 furnace is certified only to 4 500 ft Note High Altitude Natural Gas Orifices are included in all HATS kits X Available for this model Not used in this application 32 ACCESSORIES AADA LOVIN 601191 109191 6 einsseid 6 einsseid ubiH eunssejd Ld IVH OLd IVH AAOH 14 50 02835 9 939 2 5 2 5 z 529 epniniv 529 epniniv 529 epniniv 529 epniniv 529 epniniv 525 euedojd seo ubiH 29 euedojg 192919 9110439915 eseg 10014 eseg 10014
363. y reset one hour after lockout occurs If the furnace frequently has to be re set it means that a problem exists that should be corrected Refer to Troubleshooting Chart on the following pages for aid in determining the cause 3 Pressure Switch Stuck Closed If the control senses the pressure switch is closed when the induced draft blower is off it waits until the fault is corrected The di agnostic light code for this problem is two short flashes followed by a longer pause The probable cause is either a faulty pressure switch or wiring 4 Pressure Switch Stuck Open If after the induced draft blower is energized the pressure switch does not close the control will keep the induced draft blower on and wait for the switch to close The diagnostic light code for this problem is three short flashes followed by a pause The probable causes are either disconnected hose to the pressure switch faulty pressure switch or wiring or restricted air intake or flue piping 92 5 Open Primary or Auxiliary Limit If the limit control opens the air circulator blower and induced draft blower will be turned on until the limit closes The diagnostic light code for this problem is four short flashes followed by a pause The probable cause is either low conditioned air flow due to dirty filter or resistance in duct work faulty limit faulty blower or blower speed set to low 6 Open Rollout Limit If the rollout control opens the air circulator
Download Pdf Manuals
Related Search
Related Contents
Phonix TABRS holder SPIDER TM MANUEL D`INSTRUCTIONS GLOBAL STAR 360° - Termomeccanica GL LD ・ 洋室 - 東急不動産の住まい カタログデータ Haier HL42XR1 42" Full HD Black LCD TV KGH Clinical Lab User Manual v7.5 取扱説明書(装着方法) Copyright © All rights reserved.
Failed to retrieve file