PULTRUDED RAIL SYSTEM - Pentair Water Literature
Contents
1. c clamp s and rubber gasket Test gap by pulling out on bottom of the sealing flange If the flange is adjusted properly it should not pull back out of set position more than 1 16 Test disconnect by pulling up on eyebolt sealing flange should release easily Step 2 Attach supplied chain leg to achieve a three point lift Test the balance of the pump by adjusting the location of the shackle in reference to individual chain links The pump must be level to function properly WARNING If the sealing flange end of pump is raised above the horizontal the guide rail may be damaged upon lowering the pump Ensure pump is horizontal before lowering the pump into basin 1 8 Gap LE a Information Thank you for purchasing your Hydromatic pump To help ensure years of trouble free operation please read the following manual carefully Before Operation Read the following instructions carefully Reasonable care and safe methods should be practiced Check local codes and requirements before installation Attention This manual contains important information for the safe use of this product Read this manual completely before using this product and refer to
2. are automatically alternated if using a standard Hydromatic panel Also additional float controls may be used to indicate height and or low water sump conditions The general equipment for a simplex and duplex system includes the following Simplex Duplex One pump Two pumps One discharge Two discharges Elbow assembly Elbow assemblies One hydraulic Two hydraulics Sealing flange Sealing flanges One guide rail Two guide rails One lifting chain Two lifting chains One door amp Two doors amp frame assembly frame assemblies Electrical Electrical controls controls Two level Three level controls controls Pump Not Operating or in Storage Pumps with carbon ceramic seals must have impellers manually rotated 6 revolutions after setting nonoperational for 3 months or longer and prior to electrical start up Pumps with tungsten carbide seals must have impellers manually rotated 6 revolutions after setting nonoperational for 3 weeks or longer and prior to electrical start up Codes All codes must be observed Consult with the local inspector before installation to avoid costly delays Hydromatic is not responsible for any expense incurred to meet local codes Installation Instructions 1 Concrete Basin s Pour one or two concrete systems one for pumps and control etc and one for valves if required or obtain precast concrete rings A 45 degree slope may be poured around the inside perimeter of the b
3. disconnect the power first Do not smoke or use sparkable electrical devices or flames in a septic gaseous or possible septic basin To remove a pump from a standard installation control panel mounted on basin cover the power to the control panel is first turned off Close the plug valve Disconnect the power cords and sensor cords in the control panel from their terminals Lift out the pump from the basin by means of the chain or cable Disconnect the flexible conduit power and sensor cords from the control panel Pull the pump cord down through the pipe coupling while holding the cord on the underside of the basin cover so the cords do not fall into the basin For reinstalling the pump reverse the above procedure Removing Float Controls for Replacement To remove a float for replacement from a standard installation control panel mounted on basin cover the power is first turned off to the control panel Disconnect the float leads from the terminals in the control panel Disconnect the flexible conduit from the control panel Remove the flexible conduit and the float control leads from the control panel Pull the pump cord through the pipe coupling while holding the cords on the underside of the basin cover so the cords do not fall into the basin Remove flexible conduit from potting head Break out potting from the potting head and remove the float wire Remove float cord from float cord mounting bracket and r
4. gt PENTAIR HYDROMATIC PULTRUDED RAIL SYSTEM INSTALLATION AND SERVICE MANUAL NOTE To the installer Please make sure you provide this manual to the owner of the equipment or to the responsible party who maintains the system Item E 03 359 Part 5625 359 1 2012 Pentair Pump Group Inc 10 30 12 IMPORTANT Read and follow these instructions for adjusting the pultruded rail system disconnect Failure to follow these instructions may result in diaphragm leakage during pumping or guide rail damage Step 1 If disconnect elbow and sealing flange were ordered separately the proper diaphragm gap must be set Complete factory assembled systems are factory preset and require no adjusting Gap setting Procedure 1 Loosen guide arms on each side of discharge elbow 2 Insert loose sealing flange into guide arms 3 To set the top 1 8 gap insert the loose red rubber ring gasket in between the sealing flange and discharge elbow to act as a spacer 4 C clamp sealing flange to discharge elbow to hold required gap 2 required snug parts together without tightening 5 Rotate each guide arm to ensure the protruding block on each guide arm is up against the sealing flange rib and the guide arm opposite block side is against the sealing flange hanger rods Torque bolts as follows 3 systems 40 ft Ibs 4 amp 6 systems 140 ft Ibs 6 Remove
5. it often for continued safe product use DO NOT THROW AWAY OR LOSE THIS MANUAL Keep it in a safe place so that you may refer to it often Unpacking Pump Remove pump from carton When unpacking unit check forconcealed damage Claims for damage must be made at the receiving end through the delivery carrier Damage cannot be processed from the factory WARNING Before handling these pumps and controls always disconnect the power first Do not smoke or use sparkable electrical devices or flames in a septic gaseous or possible septic sump CALIFORNIA PROPOSITION 65 WARNING A WARNING This product and related accessories contain chemicals known to the State of California to cause cancer birth defects or other reproductive harm System Description In a Hydromatic Pultruded Rail System the pump is raised and lowered in the basin using a noncorrosive fiberglass I beam A unique patented hydraulic sealing flange at the pump discharge allows the pump to be connected and removed from the discharge elbow with ease at any time without entering the wet well There is no need to disconnect any piping or electrical connections to remove a pump for inspection or routine maintenance checks A typical system will operate on float control switches A bottom float control will turn off the pump s An additional float control per pump is then used to turn on the pump s In a multiple pump station the pumps
6. ECIFICALLY DISCLAIMS THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR ANY PARTICULAR PURPOSE Liability Limitation IN NO EVENT SHALL PENTAIR HYDROMATIC BE LIABLE OR RESPONSIBLE FOR CONSEQUENTIAL INCIDENTAL OR SPECIAL DAMAGES RESULTING FROM OR RELATED IN ANY MANNER TO ANY PENTAIR HYDROMATIC PRODUCT OR PARTS THEREOF PERSONAL INJURY AND OR PROPERTY DAMAGE MAY RESULT FROM IMPROPER INSTALLATION PENTAIR HYDROMATIC DISCLAIMS ALL LIABILITY INCLUDING LIABILITY UNDER THIS WARRANTY FOR IMPROPER INSTALLATION PENTAIR HYDROMATIC RECOMMENDS INSTALLATION BY PROFESSIONALS Some states do not permit some or all of the above warranty limitations or the exclusion or limitation of incidental or consequential damages and therefore such limitations may not apply to you No warranties or representations at any time made by any representatives of Pentair Hydromatic shall vary or expand the provision hereof gt PENTAIR HYDROMATIC 740 EAST 9TH STREET 490 PINEBUSH ROAD UNIT 4 ASHLAND OHIO USA 44805 CAMBRIDGE ONTARIO CANADA NIT 0A5 419 289 1144 800 363 PUMP WWW HYDROMATIC COM Warranty Rev 12 13
7. asin at the bottom to prevent solids buildup providing the slope does not interfere with the discharge elbow and pump locations Before beginning the installation refer to the Installation Data as found in the Hydromatic Engineered Products Catalog Follow the Installation Data taking into account the location of the discharge pipe inlet pipe controls vent pipe and anchoring requirements of the discharge elbow s Allofthe above concrete work to be done by others 2 Discharge Elbow Installation See Installation Data for the proper location of the discharge elbow on the basin bottom Either cast 5 8 anchor bolts into basin bottom protruding 2 from basin floor with 5 8 lock washers and nuts securing or drill holes for expansion lag screws to secure elbow to basin bottom Each elbow requires four anchors all furnished by others Each elbow must be level Length of anchors embedded in concrete varies with materials used but must be sufficient to withstand the weight torque and thrust loads imposed by the pump 3 Discharge Piping All supplied by others Install vertical discharge piping modules to elbow using bolts nuts lock washers and gasket NOTE When increasing the pipe size at the discharge elbow an eccentric flanged reducer coupling may be required to avoid interference with the guide rail See Installation Data Install remainder of the sump discharge piping This typically includes a
8. e i HYDROMATIC SOLIDS HANDLING SUBMERSIBLE PUMP E HOPPER BOTTOM RECOMMENDED DISCH ELBOW ALL DIMENSIONS IN INCHES 4 ac Bein THIS PAGE INTENTIONALLY LEFT BLANK THIS PAGE INTENTIONALLY LEFT BLANK THIS PAGE INTENTIONALLY LEFT BLANK STANDARD LIMITED WARRANTY Pentair Hydromatic warrants its products against defects in material and workmanship for a period of 12 months from the date of shipment from Pentair Hydromatic or 18 months from the manufacturing date whichever occurs first provided that such products are used in compliance with the requirements of the Pentair Hydromatic catalog and technical manuals for use in pumping raw sewage municipal wastewater or similar abrasive free noncorrosive liquids During the warranty period and subject to the conditions set forth Pentair Hydromatic at its discretion will repair or replace to the original user the parts that prove defective in materials and workmanship Pentair Hydromatic reserves the right to change or improve its products or any portions thereof without being obligated to provide such a change or improvement for prior sold and or shipped units Start up reports and electrical schematics may be required to support warranty claims Submit at the time of start up through the Pentair Hydromatic website http forms pentairliterature com startupform startupform asp type h Warranty is effective only if Pentair Hydromatic authori
9. emove float from basin Replace 3900 float by reversing removal procedure Repot the leads in the potting head according to N E C and or local codes For the removal of the pumps and float controls from system with the control panel mounted remote from the basin cover see the Pump Installation and Service Manual WARNING Before handling these pumps and controls always disconnect the power first Do not smoke or use sparkable electrical devices or flames in a septic gaseous or possible septic basin Troubleshooting The following is a list of common problems and possible solutions Refer to Pump Installation and Service Manual for any necessary adjusting dismantling or repair work required on the pump For Control Panel troubleshooting chart refer to the Control Panel Installation and Service Manual Q 701 Pump runs but does not pump down the basin with the selector switch on either Hand or Automatic position 1 Impeller may be clogged Amperage higher than name plate will indicate this 2 Pump rotation may be wrong Reversing any two line leads on three phase pumps will reverse the rotation 3 Discharge plug valve may be closed 4 Plugging anywhere from impeller to sealing flange This is evident if no water runs out of sealing flange after raising the pump Pull the pump from the basin to find the clog 5 Plugging beyond the sealing flange This is evident if water does run ou
10. lling into covers Either cast four 38 anchor bolts into the top of the precast cover or drill holes for expansion lag screws Use either nuts or stainless steel bolts to secure door and frame assembly to cover If valves are to be inside the wet well provide access ways as required for the piping and valves to access piping shut off valves see Installation Data for general dimensions of access Ways Access ways must be covered and secured with tamper proof hardware by others 5 Guide Rail Installation Install the pultruded guide rail I beam by attaching the lower end of the guide rail to the slotted lugs on the top side of the discharge elbow Two 9 x 2 bolts one rectangular washer lock washers and nuts are provided with the discharge elbow parts package At the top of the guide rail plumb and then fasten the guide rail to the door amp frame assembly or other suitable bracket using the four 1 4 x 1 stainless steel cap screws If Hydromatic door and frame assemblies are not used obtain suitable upper guide rail brackets by others to locate and support the rail s A flat surface 4 wide is required for each rail 6 Intermediate Guide Rail Bracing Sump depths of 9 6 and greater require intermediate guide rail bracing The braces mount on the vertical discharge pipes with U bolts which are sized according to the discharge pipe size The number of guide rail braces required are as follows S
11. per float in the right hand and with the bulbs hanging free turn selector switch to Automatic Lower the left hand until the float hits the ground and lies on its side Nothing should happen After lowering the right hand in the same manner the pump should start When raising the right hand to suspend the float the pump should continue to run The pump should stop when raising the left hand to suspend the float If this procedure does not cause the pump to operate as described either order new float switches or replace alternator relay PULTRUDED RAIL SYSTEM ACCESS FRAME LIFTING CHAIN bL OPTIONAL 5 OL PULTRUDED RAIL GUIDE RAIL REM CONNECTOR gt gt FLANGE GUIDE I RODS US X y IST DISCHARGE FLANGE j _ OF PUMP DISCHARGE ELBOW HYDRAULIC SEALING FLANGE ASSEMBLY WITH BUNA DIAPHRAGM ZINC FACED FLANGE STAINLESS STEEL GUIDE ARMS SIMPLEX 3 THROUGH 6 PUMPS HINGED SIDE 5 8 DIA BOLTS DUPLEX 3 THROUGH 6 PUMPS HINGED SIDE 5 8 DIA BOLTS LIFTING CHAIN HYDROMATIC DUPLEX ALUM HATCH RIM ELEV VENT PIPING MOUNTING BRACKET y HL __ INTERMEDIATE GUIDE RAIL SUPPORT REQ FOR DEPTHS EXCEEDING 9 6 HYDROMATIC 3900 SUBMERSIBLE LEVEL SWITCHES FRP GUIDE RAIL DEPTH OF WELL FT IN B
12. s for proper installation and tightness Attach the lifting chain assembly or cable to the lifting eye s on the top of the pump with the shackle s provided Lower the pump into the basin with the guide rail connector engaged over the pultruded guide rail I beam Ensure that the chain or cable does not interfere with the cord cap assembly Attach the upper end of lifting assembly to the hook provided on the inside of the Hydromatic door and frame The heavy rubber sealing diaphragm on the pump discharge should not touch the discharge elbow flange when the pump is being installed or removed or is installed but not running Its sole purpose is to flex due to water pressure when the pump turns on and form a leak proof seal between the pump and the discharge elbow 10 Float Switches Mount the float switch mounting bracket to the door and frame assembly using s 16 stainless steel screws Include a dielectric gasket by others between dissimilar metals to avoid galvanic corrosion Allow excess float cable to loop over mounting bracket The sump level is controlled Hydromatic float switch controls The float is held in position in the sump by a weight attached to the power cord above the float The cord supports the float and is adjusted for height from the surface Duplex systems use three controls one at all pumps off one set at one pump on and one set for both pumps on Pumps alternate operation on each s
13. stall coupling through basin wall Screw protective bushing from inside basin into coupling all furnished by others Make connections outside station using wiring conduit seals potted and conduit to remotely located Control Panel conduit and seals not furnished Insert the power and sensor cords through the coupling provided with bushing Grout in coupling going through sump wall by others When installing pump power cords make certain that cords do not rub against pump or on bottom of basin Shorten cords to suit the installation See Bulletin Q 701 for the Installation and Service Manual on the electrical Control Panel system Electrical Connection Make all connections in compliance with N E C and or local codes Connect the control panel ground wire to a good ground Ground wire must be grounded properly per N E C and or local codes AII electrical connections are to be made by a qualified electrician Pump Operations WARNING Before handling these pumps and controls always disconnect the power first Do not smoke or use sparkable electrical devices or flames in a septic gaseous or possible septic basin See Pump Installation and Service Manual for submersible pump operation on starting system Clean all trash and sticks from basin and connect pump to piping Maintenance Removing Pump from Basin for Servicing WARNING Before handling these pumps and controls always
14. t when pump is operating when disconnecting the sealing flange from the discharge elbow Remove the check valve clean out cover and plug valve and other piping if necessary inside valve box to find clog Reassemble all valves and piping If the basin is still not pumped down after the pump is lowered again and the sealing flange is reconnected proceed in a logical manner to locate and clear the plugging 6 Discharge head may be too high Check elevation against design point of pump 7 Improper discharge flow Check for correct impeller size and proper voltage 8 Check for possible broken or clogged forced main Basin level is pumped down with selector switch on Hand position but is not pumped down with selector switch on Automatic position 1 Floats are not hanging free in the basin or are covered with debris Pump the level down with the selector switch on Hand so that the floats can be observed Relocate and clean all floats as necessary 2 If this is a new installation and original start up the floats may be miswired into the control panel Recheck the wiring diagrams and schematics in the panel If the start and stop floats are hooked in reverse the pump will short cycle on and off and will not pump the level down 3 Floats or alternator are malfunctioning Pull the floats out of the basin clean them and lay them on the ground Lift up the stop lower float in the left hand the start up
15. uccessive cycle with a Hydromatic Control Panel The alarm level is usually set above the override both pumps on level so the alarm will signal only if the override level is exceeded However some engineers prefer to have the alarm set below the override level as it is possible for one pump to fail and the other to operate on the override level with the sump level never reaching the alarm level Do not let floats rest against basin wall or bottom or entangle with each other or pump s 11A Control Panel on Mounting Stand When the Control Panel mounting stand is used either cast four l anchor bolts into the concrete cover or drill holes for expansion lag screws and attach stand bolts or lag screws furnished by others Insert power and sensor cords from the pumps and all float cords through the bushing in the sump cover Bolt the panel to the panel stand Nuts bolts and washers are not supplied Make connections between the bottom of the control panel and the basin cover using flexible conduit and conduit seals by others When installing pump power cords make certain that the cords do not rub against the pump or bottom of the basin Shorten cords to suit the installation See Bulletin Q 701 for the Installation and Service Manual on the electrical Control Panel system 11B Control Panel Mounted Remote from Basin If the Control Panel is remotely located instead of on the mounting stand at the basin in
16. ump Depths 9 6 to 180 1 guide rail brace required 18 6 to 270 2 guide rail braces required 2776 to 30 0 3 guide rail braces required On depths requiring more than one brace space the braces equally on the pipe and tighten U bolts Match drill two holes through the guide rail flange and attach with two 1 4 x 1 stainless steel bolts nuts and lock washers provided with braces Install with bolt heads against the bracket 7 Exterior Piping Install the inlet hub s in side of basin and install inlet piping in hub and grout or install inlet pipe s directly into basin and grout Install drain pipe from valve box if required to basin Slope pipe to give proper drainage to basin Install vent piping in side of basin if required Extend piping to a proper elevation above grade as required by plans and specifications and or local codes All piping furnished by others See Installation Data for typical piping arrangement 8 Pump and Sealing Flanges Assemble the sealing flange with arms to the pump discharge flange using a gasket between the two Screw nuts with lock washers on the bottom six studs Slide the guide rail connector through the sealing flange ears and below the top two studs protruding through the back side of the pump flange Place the retainer clips on the studs followed by lock washers and nuts and follow illustration 9 Pump Installation Check all piping braces and support
17. vertical run of piping appropriately sized and configured to mate with the vertical discharge piping a ninety degree elbow and a horizontal run of piping appropriately sized and configured to mate with the valve box or main piping Install horizontal run extending through the wall of basin Secure vertical run to the vertical discharge piping using the appropriate method 1 flange weld gasketed collar coupling and grout all piping extending through basin walls Installation Instructions NOTE If using flanged connections be certain that adequate clearances are provided throughout for the installation of bolts nuts lock washers and gaskets If total run of vertical piping exceeds twelve 12 feet install a piping brace at the approximate midpoint of the piping Secure brace i e U bolt with angle iron strap and angle iron extensions to both piping and wall of basin 4 Basin Cover s The basin cover for the sump and valve box can either be poured concrete precast If Hydromatic door and frame assemblies are used locate the concrete openings with respect to the discharge elbow mounting studs as shown in the Installation Data If the covers are poured place the door and frame assembly inside the concrete form and position per installation data Anchor straps are provided on the door frames to secure them to the concrete If precast covers are used remove anchor straps from frame before insta
18. zed control panels are used All seal fail and heat sensing devices must be hooked up functional and monitored or this warranty will be void Pentair Hydromatic will cover only the lower seal and labor thereof for all dual seal pumps Under no circumstance will Pentair Hydromatic be responsible for the cost of field labor travel expenses rented equipment removal reinstallation costs or freight expenses to and from the factory or an authorized Pentair Hydromatic service facility This limited warranty will not apply to defects or malfunctions resulting from failure to properly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such service d to units that are not installed in accordance with applicable local codes ordinances and good trade practices e if the unit is moved from its original installation location f if unit is used for purposes other than for what it is designed and manufactured 9 to any unit that has been repaired or altered by anyone other than Pentair Hydromatic or an authorized Pentair Hydromatic service provider h to any unit that has been repaired using non factory specified OEM parts Warranty Exclusions PENTAIR HYDROMATIC MAKES NO EXPRESS OR IMPLIED WARRANTIES THAT EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF PENTAIR HYDROMATIC SP