Home
        product manual
         Contents
1.                                                          Is the R 22 charge    Find leak  then repair and properly  correct  no charge system     yes  Are the liquid line filter 3 Replace   driers clogged  yes    no  Is the drive plate turning at correct Are the speed pots adjusted  speed  no correctly   yes    yes  ANSA Remove drive  y   gt  assembly and replace  countercranks broken   yes countercranks   j no  O in thesvaporat  r Shut unit down  Remove drive assembly and thaw out ice   g up P   gt  Caution  Unit will most likely freeze up again   tubes  i   yes Cause for freeze up must be determined     no  Is the liquid level valve controlling Adjust  repair  or replace   properly  no    yes  Is the evaporator Check feed supply pressure   solution flow rate  gt  in line strainer filter  pump  correct  no operation   yes  Is the glycol solution concentration With no ice in the tank  measure  0 9   percentage level and adjust to  level above 7   LET  yes 7  minimum   MaximICE TES ORE 25 100 Owner s Manual 37  Part No  9840502    Effective September 1  1998  Revised December 1  2000    10 6          System will not make ice                   Is the solution temperature above  30  F   1 0  C      Troubleshooting Chart 6  System Will Not Make Ice        __   yes       pra    Allow unit to operate and decrease  solution temperature  Ice making  should begin below 30  F   1  C                  Is the R 22 charge correct        no            yes    Find leak  repair   and charge u
2.                                      LINE LINE  WET SUCTION OUT    SUCTION  HEAT  EXCHANGER  I  ull  Fw I  i AS FILTER DRIER    EXPANSION  DEVICE             LIQUID FEED    RECIRCULATED    DRY SUCTION RETURN        OIL RETURN LINE    FCV  AN  GLYCOL  pd  lt   SOLUTION  IN  E ORE EVAPORATOR ASSEMBLY si  MaximICE TES ORE 25 100 Owner   s Manual 15 Effective September 1  1998  Part No  9840502 Revised December 1  2000    SECTION 4 0   PRE START UP INSTALLATION REQUIREMENTS    4 1 Evaporator Unit Drive    The unit must be level within 1 5   3 mm  over the entire length and width of the evaporator  compartment  shim and grout as necessary      The unit must be uniformly supported along the base beams     The unit must not have restricted access  At least 4   1 2 m  of clearance is required on all sides of the  unit  Service access must be provided for removal of whip rods  approximately 4  or 1 2 m above  evaporator compartment   Do not suspend or support any piping or conduit from this unit     This unit contains rotating equipment  thus vibration and sound control may be required for this unit  Where  vibration may be transmitted to a structure  all external piping to the unit should be vibration isolated     4 2 Water Loop Piping    All piping must be complete and correctly installed     Water piping shall be flushed and drained prior to final connection to the MaximICE  The flushing  procedure shall use an environmentally approved cleaning solution and consist of flushing the 
3.               Clean  repair  or replace        yes  y Readjust to maintain a slow   yes steady liquid oil mixture flow             ro       Contact factory           MaximICE TES ORE 25 100 Owner   s Manual    Part No  9840502             42    Effective September 1  1998  Revised December 1  2000                         10 11  Does solution have correct  phosphate levels  4 000 ppm   no    yes  Is solution cloudy in appearance   yes    no  Are the left countercranks worn  more than the right  or vice versa   yes            155    Is the eccentric pin worn on one  side only       ro    Is plastic housing bearing   wallowed out                                    ro    Does drive plate have a number of  oval shaped or enlarged holes                 no             E    Has the drive motor failed              no       HS    yes    yes    no  Is thrust face of sleeve bearing  broken or worn out  yes 2       yes plate clears it everywhere in orbit  yes  Unit ran while tubes full of ice and  Are any countercranks cracked                3 countercrank frozen in position   yes See Chart 1  yes        __   yes       yes       Are whip rods worn at neck and  bottom        yes            yes          High solution level  Check vent  switch for proper operation  See  Chart 2              MaximICE TES ORE 25 100 Owner   s Manual  Part No  9840502    Troubleshooting Chart 11  Excessive Wear          Add k HPO  inhibitor  Systems with stainless steel  H   tubes are especially sensitive to th
4.             gt  Add glycol and water     no            yes    Does tank reach 50  ice fraction    Reset high ice level  temperature   before shutting down  yes switch                    no          Are process building loads higher 3    than expected  design basis   yes Contact Factory                MaximICE TES ORE 25 100 Owner   s Manual 40 Effective September 1  1998  Part No  9840502 Revised December 1  2000    10 9 Troubleshooting Chart 9  Excessive Evaporator Shell Vibration       Excessive Evaporator Shell Vibration    F Remove drive assembly and install  Are all countercranks installed left and right countercranks    2  GUS  no correctly   See Figures 3 5        yes  Remove drive assembly and replace  Are any countercranks damaged                    gt  gt   damaged countercranks  Note  Remove ice  yes slurry pump and clean impeller vanes   i no    Is the drive plate damaged              gt     yes    no  Remove drive assembly and replace damaged    Are any whip rods damaged                gt   whip rods  Note  Remove any whip rod material  yes within ice slurry pump or ORE outlet shell     no    Is ice freezing up in the evaporator     See Chart  1   Low Pressure  tubes  yes Evaporator Freeze Up       no  Adjust drive speed slightly higher  Is system 50 hz    gt  or lower    10   to get away from  yes resonance    ro    See Section 3 2 for foundation  Is system supported properly        _  details  no i    yes    EEE Secure motor bolts with Loctite and    yes split 
5.            STEEL RIVETS  POSITIONED  TOWARDS  ALIGNMENT  MARK    P ALIGNMENT MARK       8200062 1 P1    MaximICE TES ORE 25 100 Owner   s Manual 11 Effective September 1  1998  Part No  9840502    Revised December 1  2000    Figure 4   MaximICE ORE 50 Drive Assembly    PLAT  0338     ING    PE   O  nol          O      N    O  On    fi    EVAPORATOR       ALIGNMENT MARK       40347     N             7    HOUSING T                                     Ks pe CRANK    1 16 NZ    16 MM 0 8                              No    E                                        BEARING SLEEVE    DETAIL A    Li PLATE         GAP                         7       MaximICE TES ORE 25 100 Owner   s Manual    Part No  9840502         HL       ay  A    Sey    12    MOTOR   98 40319     ECHANCAL S  9840339                              984268       AL    EG CRANK             BE ARIN       VE       G   9840320               9842349     DRIVE PLAT  9842626    RUBBER GASK   9840343    LET SHELL  9840301                                 9842676    9842677     WHIP ROD  8850044                       POSITIO  RIVETS  ALIGNM             STEEL  TOWARDS                Becca BE ARING       ET    a E    ENT MARK 8200096 1 P1    Effective September 1  1998  Revised December 1  2000    Figure 5   MaximICE ORE 100 Drive Assembly    DRIVE MOTOR  EE  9840850   LEVEL ai  ADJUSTMENT O  MOUNTING PLAT ECCENTRIC CRANK  984088     9842681  O RING HOUSING_BEARING   9840347   9842349   DRIVE PLATE  5 COUNTERCRANK  Meana RH  98426
6.   8 0  8 1  8 2    8 3  8 4    Maintenance ut Atri A Lua ANN ail 23  Daly Chek S errero S  s ra Sat He hac ekkel ba at h   kes ea AIR ir 23  Recommended Inspection Procedures ooo 23  Figure 8   Drive Plate Inspection Criteria 0    24  Figure 9   Drive Plate Inspection Criteria Le 25  Figure 10   Countercrank Inspection Criteria i    26  Figure 11   Whip Rod Inspection Criteria caor to EAA eee 27  Figure 12   Bearing Sleeve Inspection Criteria    1  ee eee 28  Figure 13   Tube Insert Inspection Criteria    0    eee 29  Figure 14   Eccentric Crank Inspection Criteria LL 29  Recommended Drive Component s  Replacement Schedule    30  Recommended Monitoring Points   Le 30    Section 9 0   Recommended Spare Parts    9 0  9 1  9 2  9 3  9 4    Recommended Spare Parts  a da dd A AAA BER Ba del aed 31  ORE  COMMON PA  S  AE AAA A a Ra Pe EE Oe A A A AD NIE EE ei ENA 31  ORE25 Past sect Airco ars ala A ag Ree Hee eau Me act Bel oa 31  ORESO Parts    ricos   eee RG  Gy ee he Gude e OR RE hee A OE OE oh a Bey er AG E 31  ORES100 Bart A Ed a OE Patents ale Oa A de eee 32    SECTION 1 0   INTRODUCTION    1 0 Introduction    The MaximICE   evaporator assembly is a thermal energy storage system intended for producing a large  amount of ice slurry  The ice slurry is used to take advantage of off peak electrical power usage  usually  at night   The ice slurry is then used during the on peak electrical usage periods for air conditioning or  process cooling  This in turn reduces the electrical d
7.   Typical quaternary amines are C   to  Cig mixtures of n alkyl dimethyl benzyl ammonium chloride or n alkyl dimethyl ethyl benzyl  ammonium chloride  Manufacturers include Albemarle Chemical  BQ 451 5   Lonza  Barquat 50 65    and Stepan Company  BTC 818      Dry ingredients  such as dipotassium phosphate  must be dissolved in water prior to addition to the  ice slurry tank  A small tank and mixer is convenient for this purpose     Water Quality   Water used to make up the glycol solution must meet certain standards of purity   Distilled or de ionized water is recommended  Levels of chlorides and sulfates should be less than 25  ppm each  Total hardness should be less than 100 ppm expressed as ppm calcium carbonate  If good  quality water is unavailable  pre diluted solutions are available from manufacturers     Local conditions must always be taken into consideration  particularly when it comes to biofouling and  scaling fouling deposits  A local water treatment authority should be consulted for guidance in this  matter  PMC recommends calling your county or city water department to find out the specification of  your local water supply  If the water contains less than 100 ppm of hardness  it can be used to dilute  your glycol based heat transfer fluid  Another option would be to test the water yourself with a HACH  test kit     One word of caution about the common practice of using softeners when filling HVAC systems  resins  typically used in these softeners will replace 
8.  15 0   WARRANTY    WARRANTY    Mueller  MaximICE   for Thermal Storage       One Year Parts Warranty    Paul Mueller Company  hereinafter referred to as Company  will repair or  or at the Company   s option  replace any part or portion of a  Mueller MaximICE Evaporator Assembly found to be defective in workmanship or material under normal use  service  and installation  procedures  for a period of one  1  year from date of installation by the original purchaser user or eighteen  18  months from the date  of shipment from the Company factory  whichever occurs first  This Warranty covers replacement of parts or repair of the equipment  only  This warranty does not cover consumable products or parts such as refrigerant  driers  glass  or rubber components  See General  Provisions      Claim Procedure for One Year Parts Warranty    All defective parts covered by the one year parts warranty must be returned to Paul Mueller Company with an attached Returned  Goods Tag  O 209  and with transportation cost prepaid  Current instructions for return procedures  provided by the Thermal Storage  Products Service Department  must be followed to receive warranty     General Provisions    This warranty does not cover items such as  refrigerant  transportation  mileage  freight  product loss  cost of substitutions  or labor and  parts charged by others  Replacement and or repair of certain components not manufactured by the Company will be handled by  authorized service stations designated b
9.  5mm  OR MORE       Az REPLACE IF ANY CRACKS  ARE VISIBLE    ORIGINAL  DIMENSION  0 125   3 2mm        REPLACE IF SHOULDER  SURFACE IS WORN   040   1 0mm  OR MORE    ORIGINAL  DIMENSION  0 313   8 0mm        1 438        ORIGINAL       36 5mm   DIMENSION             REPLACE IF DIAMETER  IS WORN  040   1 0mm   OR MORE    MaximICE TES ORE 25 100 Owner   s Manual 26 Effective September 1  1998  Part No  9840502 Revised December 1  2000    Figure 11   Whip Rod Inspection Criteria    REPLACE IF ANY VISIBLE FLAT SPOTS ON WHIP ROD  MEASURE BOW WITH FEELER GAUGE IF WHIP ROD WON T  ROLL FREELY ON A FLAT SURFACE       1 16   1 5mm   MAXIMUM BOW       REPLACE IF  A    IS EQUAL  OR LESS THAN 5 16   8mm   AT ANY POINT ON THE ROD    MaximICE TES ORE 25 100 Owner   s Manual 27 Effective September 1  1998  Part No  9840502 Revised December 1  2000    Figure 12   Bearing Sleeve Inspection Criteria    A Drive Plate Bearing Housing       Make sure that there is not any apparent scoring inside the bearing sleeve  Measure the ID of the  bearing sleeve and refer to the tolerance chart to see if this part can be reinstalled or needs  replacing  The lip on the bearing sleeve should be fully seated into the bearing housing     REPLACE IF  A  IS EQUAL OR GREATER  THAN 1 015   25 78mm     REPLACE IF LOOSE  IN HOUSING BEARING       REPLACE IF  B  IS EQUAL OR  LESS THAN  040   1mm     A Freeze Up Protection Switch       Remove the 2 wires that are connected to the freeze up protection switch  Shut the an
10.  Horsepower  200 volts 380 volts  3 5 amps     2  1 75 amps    2   762 rpm 857 rpm  60 Hertz  Drive Motor 3   Horsepower 60 Hertz  Drive Motor 3   Horsepower  208 volts 230 volts  3 7 amps     2  3 05 amps     2   794 rpm 794 rpm  60 Hertz  Drive Motor 3   Horsepower 60 Hertz  Drive Motor 3   Horsepower  460 volts 380 volts  1 53 amps     2  1 75 amps     2   833 rpm 794 rpm  3 13 Electrical Specifications  ORE 50  but not limited to   PLC  24 Volts  Inputs DC  Outputs AC  Power Supply 120 volts AC  50 Hertz  Drive Motor 1 5 Horsepower 50 Hertz  Drive Motor 1 5 Horsepower  200 volts 380 volts  6 0 amps     2  3 0 amps     2   850 rpm 850 rpm  60 Hertz  Drive Motor 1 5 Horsepower 60 Hertz  Drive Motor 1 5 Horsepower  208 volts 230 volts  5 2 amps     2  4 75 amps     2   850 rpm 850 rpm  60 Hertz  Drive Motor 1 5 Horsepower  460 volts  2 35 amps     2   850 rpm  MaximICE TES ORE 25 100 Owner   s Manual 6 Effective September 1  1998    Revised December 1  2000    3 14    3 15    3 16    3 17    3 18    MaximICE TES ORE 25 100 Owner   s Manual  Part No  9840502    Electrical Specifications  ORE 100  but not limited to     PLC  24 Volts  Inputs DC  Outputs AC  Power Supply 120 volts AC    50 Hertz  Drive Motor 3 Horsepower 50 Hertz  Drive Motor 3 Horsepower  200 volts 380 volts  13 8 amps     2  6 9 amps     2   850 rpm 850 rpm   60 Hertz  Drive Motor 3 Horsepower 60 Hertz  Drive Motor 3 Horsepower  230 volts 460 volts  12 6 amps     2  6 3 amps     2   850 rpm 850 rpm    Ice Sto
11.  ORE 25   50  and  100     MaximICE TES ORE 25 100 Owner   s Manual 28 Effective September 1  1998  Part No  9840502 Revised December 1  2000    Figure 13   Tube Insert Inspection Criteria    A REPLACE IF EITHER SURFACE    SCORED OR HAS ROUGHNESS  IS 250 u INCH Ra  6 25 u m  OR  MORE     REPLACE IF ANY CRACKS  VISIBLE     Figure 14   Eccentric Crank Inspection Criteria    REPLACE IF SURFACE  ROUGHNESS IS 125 u INCH Ra   3 1 um  OR MORE       MaximICE TES ORE 25 100 Owner   s Manual 29 Effective September 1  1998  Part No  9840502 Revised December 1  2000    8 3    8 4    Recommended Drive Component s  Replacement Schedule    A 1 000 hours     a  Disassemble drive assembly   b  Inspect wear surfaces   c  Apply a thin coating of Petroleum Gel to all surface wearing drive parts   A 8 000 hours     a  Possible replacement of countercranks  drive plate  and flange bearing   b  Clean ORE inlet strainer     NOTE  The above schedule is based on good glycol solution quality and normal wear  Systems with  poor water quality and operational difficulties may require more frequent replacement     Recommended Monitoring Points    Temperatures    F    Ambient   Solution Supply To Process  Solution Supply To Evaporator  Compressor Discharge  Compressor Suction  Condenser Liquid Outlet  Pressures  psig    Compressor Discharge  Condenser Liquid Outlet   Drier Core AP   Evaporator Suction   Main Voltage   AMPS   Compressor Motor   Evaporator Drive Motor  Evaporator Solution Pump Motor    di di 
12.  R 22  i i 9840556  Power Head  amp  Heater   MVE  VVE   amp  WVE  R 22  i   9840564  Power Head  amp  Heater    R 717 only  i i 9842704  9 3  ORE 50 Parts   T T  Description   Recommended Qty    PMC Part    Drive Plate i 1 i 9842626  Drive Plate Assembly  plate  housing bearing  bearing sleeve    1 9842640  Drive Motor Shaft Seal l 1 i 9840339  Housing Bearing i 1 i 9842349  Liquid Level Valve Kit  LMC MVE 42    1 i 9840560  Liquid Level Valve Kit  LMC MVE 52  i 1 i 9840561  Liquid Level Valve Kit  LMC MVE 70    1   9840562  Liquid Level Valve Kit  LMC AAE 50  1 i 9842707  Power Head  amp  Heater  LMC MVE  VVE   R 22 only  i 1 9840564  Power Head  amp  Heater  R 717 only  1 i 9842704  Crank Electric Assembly i 1 i 9842862                                     MaximICE TES ORE 25 100 Owner   s Manual    Part No  9840502    31    Effective September 1  1998  Revised December 1  2000    9 4 ORE 100 Parts                                               Description   Recommended Qty    PMC Part    Drive Plate i 1 i 9842620  Drive Plate Assembly  plate  housing bearing  bearing sleeve    1 9842872  Drive Motor Shaft Seal i 1 i 9840666  Housing Bearing l 1   9842349  Bearing Sleeve i 1 i 9840320  Liquid Level Valve Kit  LMC VVE 100  i 1 i 9840562  Liquid Level Valve Kit  LMC AAE 100  1   9842705  Liquid Level Valve Kit  LMC WVE 135  1 9840563  Power Head  amp  Heater  R 22 only  1 9840564  Power Head  amp  Heater  R 717 only  1 i 9842704  Crank Electric Assembly i 1 i 9842681       Max
13.  TYPICAL WRING Unit Pumpdown Low Pressure Switch   Provide normally closed dry contacis   SCHEMATIC Contacts open when suction pressure drops to 5 psig  condensing unit shuts down     Condensing Unit Alarm 1  Provide normally closed dry contacts  Contacts open  upon condensing unit alarm condilion  condensing unit shuts down       Single compressor  condensing unit wiring shown   See unit wiring diagram   for multiple condensing urits  and optional items               Condensing Unit Alarm 2    Jumper in control box   OPTIONAL     Remote temperature switch   Wired to remote ice level inventory sensor  Comacts close on full ice condition  predetermined temperature setting    OPTIONAL       Condensing Unit Start   24VAC contacts close to siart condensing unit      Compressor Unicading  Step 1   24VAC contacts close to untoad compressor      Compressor Untoading  Step 2    24VAC contacts close to unload compressor       Remote Alarm   Dry contacts close upon alarm condition for remole alarm indication       Remote Solution Pump Start   Dry contacts close lo siart solution pump         INPUT TO MaximiCE PLC   O   OUTPUT FROM MaximiCe PLC     CUSTOMER SUPPLIED  3 PHASE WITH GROUND    MUELLER       eee   2 89   x   m  pra a    gt   2586  er  es  Cane    es     Pete    MODEL ORE 25    Flooded Refrigerant Feed  Pumped Slush Discharge    820046 3 7 97          MaximICE TES ORE 25 100 Owner   s Manual 49 Effective September 1  1998  Part No  9840502 Revised December 1  2000    13 3 Mod
14.  adequate air circulation  The most important  consideration when determining the location of the air cooled equipment is ambient air supply and  removal of heated air to prevent air recirculation  A minimum distance of 3   0 9 m  clearance should  be provided for proper hot air removal and servicing     The general rule of thumb for evaporative cooled units is to allow a minimum distance around the unit  of 6   1 8 m  for smaller units and 8   2 4 m  or more with larger units  Consult PMC for further details     MaximICE TES ORE 25 100 Owner   s Manual 5 Effective September 1  1998  Part No  9840502 Revised December 1  2000    Part No  9840502    3 11 Electrical  The MaximICE wiring schematic identifies the minimum remote interconnecting field customer wiring  required  All power wiring and grounding must be installed in accordance with all local  state  and  national codes  Separate field supplied breaker disconnect is required and shall be supplied by others   Article 440 of the NEC requires that the system have    disconnecting means capable of disconnection of  air conditioning and refrigeration equipment including motor compressor and controllers from the  circuits feeder     The circuit breaker and or fused disconnect switch should be selected and located  within the NEC guidelines   3 12 Electrical Specifications  ORE 25  but not limited to   PLC  24 Volts  Inputs DC  Outputs AC  Power Supply 120 volts AC  50 Hertz  Drive Motor 3   Horsepower 50 Hertz  Drive Motor 3  
15.  capacity       Start up sequence complete     6 2 Shutdown Sequence    A Shutdown initiated by either selecting    OFF    on the toggle switch  removing the remote enable  signal  if in AUTO   or    high ice    condition  temperature set point reached  in tank     A Unload solenoids on 5 minute delay     A End of 5 minute delay   Condensing unit  oil return solenoid  unload solenoid  and LLM heater  turn off     A After 15 minute delay   drive shuts down     MaximICE TES ORE 25 100 Owner   s Manual 19 Effective September 1  1998  Part No  9840502 Revised December 1  2000    A End of 30 second delay   Slush and feed pump shut down    A Shutdown sequence complete    NOTE  When a unit shutdown is initiated for any reason  the unit will complete the shutdown  sequence before a restart is enabled  If the unit is in the process of starting  the start up sequence will    be completed before the shutdown sequence begins  If an immediate shutdown is required  the     E STOP    switch must be pushed     6 3 Restart Sequence  60 minute  typical  delay for restart after full ice condition   Unit will automatically start the solution    pump s  and check for absence of full ice condition  If full ice exists  the pumps shall shutdown and  another 60 minute delay will take place and the restart process will repeat     Pressing the    E Stop    push button or an alarm condition will initiate shutdown     All operating components are de energized immediately     Toggle switch must be moved t
16.  continue until all requirements for correct and safe operation of the MaximICE are satisfied   The installing trades should be available to resolve installation problems as required during the start   up period     Contractors    personnel and the owner   s representative who will be operating and maintaining the unit  should be available for training during the entire start up period     4 6 Start Up Policy    MaximICE units require two  three  or four days of start up assistance depending on the size of  equipment  Delays in the start up caused by failure to comply with any of the following procedures  are not the responsibility of PMC  Additionally  start up time caused by delays  not the responsibility of  PMC  must be authorized by customer in advance  Failure to follow these procedures will result in  delays and may result in the voiding of the equipment warranty  Contact the Paul Mueller Company  Thermal Energy Storage Department if you have any questions pertaining to the installation  requirements of this equipment     MaximICE TES ORE 25 100 Owner   s Manual 17 Effective September 1  1998  Part No  9840502 Revised December 1  2000    SECTION 5 0   START UP REFRIGERANT CHARGING    5 0  Start Up Refrigerant Charging    Apply main power at least 12 hours prior to starting unit  This will allow the compressor crankcase  ample time to boil off any possible liquid refrigerant within the compressor     NOTE  Refrigerant charges provided are conservative and will vary due 
17.  equivalent 100   30 m   increase tubing size accordingly  The liquid line should be sized to prevent  excessive pressure drop to ensure a solid liquid column to the expansion valve  Use only Trade K or L  refrigerant grade tubing or Schedule 40 pipe  When brazing refrigerant tubing  an inert gas should be  passed through the line at low pressure to prevent scaling and oxidation inside the tubing   dry  nitrogen is preferred  Use suitable silver solder alloy on all refrigerant tubing  Refrigerant lines should  be supported and fastened properly     3 7 Refrigerant Piping Pressure Test    After all lines are connected  the entire system must be leak tested  including the ORE and condensing  unit  The complete system should be pressurized to not more than 150 psig  1 000 kPa  using dry  nitrogen vapor  The use of an electronic type leak detector is highly recommended due to its greater  sensitivity of small leaks  It is recommended that this pressure be held for a minimum of four hours  and then rechecked     3 8 System Evacuation    Prior to connecting hoses  remove the core from the Schrader fitting  A minimum evacuation to 500  microns and a five minute hold period is recommended  Proper evacuation processes include vacuum  pump oil changes and large diameter  short hose connections to both high and low sides of the  system     3 9 Refrigerant Charge    See Section 5 0 for further details     3 10 Condensing Unit    Provide a suitable solid base under protective shelter with
18.  leak  repair  and properly  charge system     Is oil accumulating in evaporator              Adjust  repair  or replace          yes       Increase oil return flow back to  compressor              Check inline strainer filter and  pump operation     and          Check oil separator for missing  filter elements              Check pressure drop across flow  control valve   must be at least 12  psi  83 kPa         Adjust  replace        Reduce compressor capacity           Increase pre wash and post wash  times     33    and             Make sure compressor is unloaded    gt 50  capacity  during pump   down and start up           Effective September 1  1998  Revised December 1  2000    10 2 Troubleshooting Chart 2  Unit Fails on Vent Switch          Unit fails on vent switch   PLC Output O Y14  Continuous light          l          Is the ice slurry pump  operating properly     no    Check power to pump  fuses     contactor  and motor             yes             Is a valve closed on the ice slurry  pump  Discharge     yes    Open valve              ie          Is the vent line above the  maximum glycol solution level     i   i  yes       Locate vent line above  maximum glycol level              pre          Is the vent line float switch  operating properly     no    Replace switch             yes             Is there excessive foaming in the  inlet shell or vent line          yes          Add antifoam to solution              MaximICE TES ORE 25 100 Owner s Manual    Part No  98
19.  on page 15      2 2  Ice Build Circuit    The circuit consists of an insulated tank  ice storage tank  with necessary fittings for field plumbing  It  must include an internal water spray system for    burning    ice uniformly during the melt mode  The ice  slurry is pumped to the storage tank  filling the tank as shown from the top down  Once the ice  inventory reaches the full ice  a temperature sensing device will cycle the unit off     MaximICE TES ORE 25 100 Owner   s Manual 2 Effective September 1  1998  Part No  9840502 Revised December 1  2000    2 3 Building Cooling Circuit    The circuit consists of a plate and frame heat exchanger  coolant pumps  and temperature regulating  valve  Low temperature glycol solution is pumped from the bottom of the ice storage tank into the  plate and frame heat exchanger and returned over the ice pile via a spraying system  The spraying  system may consist of a specially designed spray ball s  drilled with holes or a spraying nozzle s    Warm building load water is then pumped into the heat exchanger and cooled  Depending on the  building  temperatures may vary from 37 42  F  3 6  C      NOTE  The ORE glycol solution loop must incorporate a heat exchanger to separate the building  process from the ORE solution loop  This reduces the amount of piping which carries the glycol  solution  minimizing the cost and danger associated with piping leaks  All system fluid piping should  be properly insulated     MaximICE TES ORE 25 100 Owner   
20.  over the length and width     All remote piping must be cleaned      gt   gt   gt     All pumps must be secured  vertical shaft pumps should be properly protected and aligned    A Control wiring connected between the ORE and the condensing unit   A All shipping material removed from the inlet shell and the bottom of the evaporator     11 3 Refrigerant Piping For Remote Condenser Systems    A All remote refrigerant piping must be installed in accordance with the approved piping practice   ANSI AMSE      All piping must be properly supported   Pressure test complete system for leak  including PMC equipment      Complete system evacuated      gt   gt   gt   gt     Full refrigerant charge  provided by others  to be on site at start up     MaximICE TES ORE 25 100 Owner   s Manual 44 Effective September 1  1998  Part No  9840502 Revised December 1  2000    11 4 Water Piping     If required  strainer installed   Check for water leaks     All flow controls checked and calibrated     A  A  A  A  Water cooled condenser  install water regulating valve on the condenser outlet   A  Oil cooler  water piping installed    A Check water loop design control    A    Freeze protection installed on all applicable piping     11 5 Electrical       Adequate power supply to unit    A Three phase and control wiring completed to the unit and any remote equipment    A All wiring and grounding conforms to national  state  and local electrical codes    A  High voltage systems  megohmmeter test main wirin
21.  power off to the unit   c  Remove the insulation from the inlet shell and set aside   d  Remove the inlet solution header  this will consist of removing 8 flange bolts and 2 union fittings      e  On the top plate there will be 12        nuts  Remove all 12 nuts and the lock washers    NOTE  Do not remove the motor   If this preventive maintenance is performed on an ORE   100  200  300  or 400  and a hoist is not available  the motor may have to be removed due to  the weight and the awkwardness of the drive motor and top plate  If you have to remove the  motor  the following steps must be followed  There are three 3 4  bolts with a lock nut on the  bolt  Remove the 3    bolts from the motor mounting plate  not the adjusting inserts  This will  allow the motor to be removed by lifting it along with the motor lifting lugs that are provided  with the motor straight up     f  With the motor and the top plate removed  the drive plate will be visible  Carefully lift the  drive plate up and out of the evaporator and set aside     g  With the drive plate removed  the counter cranks and the tops of the whip rods will be  exposed  You will notice they are configured in a left and right format  Refer to Figures 3  4   or 5 for counter crank arrangement  Randomly pull 8 to 10 counter cranks  along with the  whip rods  out of the evaporator for inspection  Look at the counter cranks to see if there is  any sign of scoring or frictional wear  If so  refer to the tolerance chart to see if 
22.  pump must be properly protected against freeze damage  The Paul  Mueller Company warranty specifically excludes any liability for damage resulting from low ambient  temperature  Failure to maintain proper operation of the condenser by allowing fouling will  result in decreased MaximICE system performance and operation     Water cooled units may be provided with a condenser water regulating valve  which is shipped loose  for field installation at the outlet side of the condenser     Remote  evaporatively cooled  air cooled condenser or cooling towers  when supplied by other than  PMC  require head pressure capacity control  Consult factory for details and minimum requirements      If applicable  Water cooled oil cooler  if installed  shall be connected by the installing contractor to a  water source with a maximum water temperature of 85  F  30  C   with the required flow rate shown on  the submittal  Supply water piping must be properly protected against freeze damage by the installer     MaximICE TES ORE 25 100 Owner   s Manual 16 Effective September 1  1998  Part No  9840502 Revised December 1  2000    4 3 Electrical    All power wiring and grounding must be installed in accordance with all local  state  and national  codes  All wiring to the MaximICE shall be copper   do not use aluminum wire     The following control interlocks must be installed prior to operating the unit     Water flow   Proof of condenser water flow is required  Either a flow switch or a pressure diff
23. 14 0 Start Up Request Form    I request that a factory authorized service representative be scheduled to perform start up on  or about the week of   Please note that this is a requested date and must       be confirmed by the service department  Start up is usually performed within five days  travel  included   Upon arrival on site  the start up technician will verify that the system is capable of  being started and that the items identified in the prestart up check list have been satisfied     If site construction installation cannot be completed within 24 hours  the service technician  will depart from the job site  In this situation  all costs associated with this trip will be  charged to the purchaser on a time and material basis  The technician will return to the  installation site to perform start up upon the following conditions     A Verification of the purchaser that all construction items issues are in compliance with and  satisfy the concerns of the start up technician     A Full payment has been received for the initial start up trip     Please fax to  417  862 9008  attention Thermal Energy Storage Department  You will be  contacted within two weeks to confirm the start up of your unit s   Contact our service  department if you have any questions regarding this form or the installation of your  equipment  We will be happy to assist you     MaximICE TES ORE 25 100 Owner   s Manual 60 Effective September 1  1998  Part No  9840502 Revised December 1  2000    SECTION
24. 40502    34    Effective September 1  1998  Revised December 1  2000    10 3 Troubleshooting Chart 3  Unit Will Not Start       Unit will not start                           Check 115V power  Is power supplied to supply  control  control box  4  no transformer  and fuse             yes    Is the on off switch in Turn switch to    on                      the    on    position  no   position   yes  Is the PLC Check for main power   contact  run light    on     48   factory                      yes    Is the PLC CPU fault light    on        _ Contact factory                                                                          yes  i no  Is the PLC toggle switch in the Toggle to    run    position   run    position  no  j yes  he full ice light    on    k full ice   Is the full ice lig t on and tank fu Allow process load to melt ice Replace   of ice  yes a Allow unit to restart     no pro  Is the full ice light    on    but no ice is Is the PLC input I XO light    on     Are the ice level AS operating  in storage tank  yes yes properly   no  Ae   Contact factory                          pro    Is an alarm light    on     I Identify failure and restart unit   yes             Is there voltage   24 VDC  at PLC  output O Y11     ie    Contact factory     Is the temperature sensor showing  full ice condition  but full ice light is  gt   Is the PLC input I XO light    on     Contact factory   not    on     yes                                              MaximICE TES ORE 25 100 Own
25. 76     ee  LH  9842677        o co   pl  N7 A E i   INLET SHELL  RUBBER EG     9840854   o   r a   1 32 ECCENTRIC CRANK  GAP    e     HOUSING BEARINC  DRIVE PLATE    BEARING SLEEVE    PRONTI  Tt  VIVO E   NG  OG     2      amp    D            STEEL RIVETS                                                                                                                   SOS POSITIONED   90   OF THE   ALIGNMENT   da MARK  NOTE   AI NOT OPPOSITE  JE x  ARRANGEMENT  i Sale CRANK 8200137 P1  HOUSING BEARING Da ae GaP    a  BEARING SLEEVE ENN 2       x       E        MaximICE TES ORE 25 100 Owner   s Manual    Part No  9840502    Effective September 1  1998    13 Revised December 1  2000    Figure 6   ORE Countercrank Assembly    WHIP ROD              COUNTERCRANK  LEFT     COUNTERCRANK  RIGHT      DRIVE PLATE RIVET    9842676 9842677      REVISED COUNTERCRANK  AS OF OCT 99    8200135 P1    MaximICE TES ORE 25 100 Owner   s Manual 14 Effective September 1  1998  Part No  9840502 Revised December 1  2000    3 23 Packing Material s     The whip rods are secured in place with cellophane wrap  which must be removed from the bottom of  each evaporator  On units with an ice discharge pump option  the outlet manifold ships loose and  should be installed after the cellophane wrap     Figure 7   MaximICE Refrigeration Schematic Diagram       CONDENSING UNIT I    CONDENSER     DA    HIGH PRESSURE RECEIVER COMPRESSOR                   I       LOW PRESSURE    RECEIVER SUCTION   LIQUDY           
26. 9823978    47    Section 13 0   Equipment Specifications    13 1  13 2  13 3  13 4  13 5  13 6  13 7  13 8  13 9             Model ORE 25  Flooded Refrigerant Feed  Pumped Slush Discharge  Drawing No  8200139           48  Model ORE 25  Flooded Refrigerant Feed  Pumped Slush Discharge Schematic  Drawing No  8200146  49  Model ORE 25  Flooded Refrigerant Feed  Gravity Slush Discharge  Drawing No  8200153            50  Model ORE 25  Flooded Refrigerant Feed  Gravity Slush Discharge Schematic  Drawing No  8200160    51  Model ORE 50  Flooded Refrigerant Feed  Pumped Slush Discharge  Drawing No  8200140           52  Model ORE 50  Flooded Refrigerant Feed  Pumped Slush Discharge Schematic  Drawing No  8200147  53  Model ORE 50  Flooded Refrigerant Feed  Gravity Slush Discharge  Drawing No  8200154            54  Model ORE 50  Flooded Refrigerant Feed  Gravity Slush Discharge Schematic  Drawing No  8200161    55  Model ORE 100  Flooded Refrigerant Feed  Pumped Slush Discharge  Drawing No  8200141          56  13 10 Model ORE 100  Flooded Refrigerant Feed  Pumped Slush Discharge Schematic  Drawing No  8200148 57  13 11 Model ORE 100  Flooded Refrigerant Feed  Gravity Slush Discharge  Drawing No  8200155           58  13 12 Model ORE 100  Flooded Refrigerant Feed  Gravity Slush Discharge Schematic  Drawing No  8200162  59    Section 14 0   Start Up Request Form    60  Section 15 0 Warranty      urta EA 61  A kreditten 28 5 ANER DER OPS Bed rd Tag a a      aiaa 62    TABLE OF CONTEN
27. FLANGE  SOLUTION N 2   FNPT  46    LEFT SDE VEW               REFRIGERANT  sala ca rca  ee NR   er    rene sne   amp    3  2  sm fam   NOTES     All dimensions are in inches unless specified otherwise               3 PMC reserves the right to make product design changes which may  alter the weights and or dimensions without prior notification   3  Three foot  3  minimum service clearance is required on all  sides of assembly   4  Three feet  3  minimum clearance above ORE is required for removal gr  A of whip rods     Single point electrical connection through side of control panel   6  Insulated paneling adds 5   to length  5   to width  2 1 2  to height  MODEL ORE  25  Flooded Refrigerant Feed  Pumped Slush Discharge  820009 3 7 97  MaximICE TES ORE 25 100 Owner   s Manual Effective September 1  1998    Part No  9840502 48 Revised December 1  2000    13 2 Model ORE 25 Flooded Refrigerant Feed  Pumped Slush Discharge Schematic   Drawing No  8200146    Remote Start   Provide normally open dry contacts lo start unit from remote location   With unit toggle switch turned to    Auto     unit wil start upon contaci closure     Load Pump Operation   Provide mormaliy open dry contacts for monitoring of pump  operalion  either ouxiiary contacts or from EMS   Contacts close upon pump siari     Solution Pump Operation   Provide normally open dry contacts for moniloring of  pump operation  either auxiliary contacts or from EMS   Contacts close upon pump stort     SINGLE PHASE    ORE 25 
28. MaximlICcE      LIQUID ICE TES SYSTEM  ORE 25  50   amp  100  OWNER S MANUAL       PART NO  9840502    EFFECTIVE SEPTEMBER 1  1998  REVISED DECEMBER 1  2000    UT N      THERMAL STORAGE PRODUCTS    MIUELLER    Part No  9840502    MaximiICE  LIQUID ICE TES SYSTEM  ORE 25  50   amp  100 OWNER   S MANUAL    TABLE OF CONTENTS    Section 1 0   Introduction    1 0  1 1  1 2    Introduction nt ida ay Da GENT EL GE h   fi ed Grad GY I iaia DE DET IA atdet he 1  Delivery Inspection Mi E A E Lee RN ee OA 1  Safety Considerations x puede A Aa A AS AA AAA Lila 1    Section 2 0   Thermal Storage System   System Overview    2 0  2 1  2 2  2 3    Thermal Storage System   System Overview     sasaaa aa 2  Refrigeration  Circuit    sas  a EA 4 hark ees Pees A dei 2  Tee Build Circuit  s  ren A ene SS Bae AA eee ee SL  FRPS EE 2  Building Cooline  Circuit li tate tae ee pie Gee Raid ween Ewe Ue ee ee dd 3    Section 3 0   Installation    3 0  3 1  3 2  3 3    3 4  3 5  3 6  3 7  3 8  3 9  3 10  3 11  3 12  3 13  3 14  3 15  3 16  3 17  3 18  3 19  3 20  3 21    3 22    Installation cd e ON GAME El ENT E Ad 4  Equipment Rigging a ow acts La lai E AAA A dle n 4  Foundation dire eske a Oe A A eee th A Rana AAA 4  ANCHOrns  gt  spie ra ada Ata ee S   ty Oe Bie Ber Aa Weg ae dca AAA aah ee 4  Figure d Anchorage Details evo O S  r Oa ae san es WEN oe i 4  S  rviceability    sarete A Ea eee ee RS GE ih STIENE 5  Shipping AA mee ee FAG Ge ee EEA ON BER EEO REY Poa oem ee LG 5  Remote Refrigeration Pipi
29. N 7 0   SAFETY    7 1 Label  Danger     Unit Starts Up Automatically       The unit is intended to operate automatically and will start at any time  Power must be disconnected  and locked out when servicing the unit        DANGER       STARTS  AUTOMATICALLY    BRADY  SIGRMARE   DM CAT  MO  65172 MEN           7 2 Label  Electrical Symbol  Part No  8820623    Indicates the high voltage electrical components of the system        7 3 Label  Danger     High Voltage       This unit should be serviced by qualified electrical and refrigeration technicians     DANGER  HIGH VOLTAGE    BESO  SGM MAAK    D   CATALOG NO  54875                   MaximICE TES ORE 25 100 Owner   s Manual 91 Effective September 1  1998  Part No  9840502 Revised December 1  2000    7 4 Label  Caution     Do Not Run Unit Dry     Part No  8850229    Major damage will occur if the drive parts are ran without the solution     A CAUTION    DO NOT RUN UNIT DRY     EQUIPMENT DAMAGE  WILL OCCUR        7 5 Label  Caution     If this Gap Measurement        Part No  9842772    If the bearing gap is not set correctly  it will cause the failure of the drive bearing and the drive plate     A CAUTION    IF THIS GAP MEASUREMENT IS  NOT CORRECT  IT WILL CAUSE  SERIOUS DAMAGE TO THE UMIT        7 6 Equipment dB Readings    The equipment   s dB readings   A weighting  taken during ice making at 3 feet  1 M  from evaporator  are listed below      ORE 25 ORE 50 ORE 100  75 75 78                            A WARNING  When operatin
30. ONAL       Condensing Unit Start 1   Z4VAC contacts close to start condensing unit      Compressor Unloading  Step 1   24VAC contacts close to unioad compressor    7 Condensing Unit Start 2   24VAC contacts close to start condensing unit   OPTIONAL   I Remote Alarm   Dry conlacis close upon alarm condition for remote alarm indication     7 Remote Solution Pump Start   Dry contacts close to start solution pump     I   INPUT TO MaximiCE PLC   O   OUTPUT FROM MaxmiCE PLC     CUSTOMER SUPPLIED  3 PHASE WITH GROUND    MAJE LL LE    MODEL ORE 50    Flooded Refrigerant Feed  Gravity Slush Discharge    820061 3 1V97          MaximICE TES ORE 25 100 Owner s Manual 55 Effective September 1  1998  Part No  9840502 Revised December 1  2000    13 9 Model ORE 100 Flooded Refrigerant Feed  Pumped Slush Discharge   Drawing No  8200141        LOW PRESSURE  RECEIVER          ORBITAL ROD  EVAPORATOR                         94    SLUSH OUT 3    ANSI 1505 FLANGE SOLUTION IN 4    ANSI 15028 FLANGE  78    BACK VIEW LEFT SIDE VEW    SHP   DESIGN REFRIGERANT  WEIGHT   WEIGHT  REFRIGERANT  CHARGE FLOW T  tbe  Fla oae oeron   uoo T ae Seon HP   OSTE ESA   p 3  3   aet   30FT    am   e COME       NOTES   1     All dimensions are in inches unless specified otherwise                2  PMC reserves the right to make product design changes which may  alter the weights and or dimensions without prior notification   3  Three foot  3  minimum service clearance is required on all A  sides of assembly  a   4  Th
31. TS   CONTINUED    Section 4 0   Pre Start Up  Installation Requirements    4 1  4 2  4 3  4 4  4 5  4 6    Evaporator Unit D  VE riker Seah BE AS AA UNOS Le a e 16  Water LOOp Piping  gt  ora pra i ele ae a die de ohare Pane ele a 16  El Mid E Se Raf oa ele res ee We es 17  Refrigerant  Piping  a pe ee age ee Pa ING Fra Bek DEAD Re nad 17  Start Up Coordination Inspection o    17  Start UpsPOlCy  A RR Gare  17    Section 5 0   Start Up Refrigerant Charging    5 0    Start Up Refrigerant Charging   ui ira ed ea he eee en ele i Bete a aio sand dt 18    Section 6 0   Sequence Of Control    6 0  Sequence of Control   ci ane  ct te pe we Ee PERS wees db wale ODE oe ee aa Fe oe rane 19  GI    Start Up  Sequence vista side FA Arre aL A Beet 19  6 2  gt     Shutdown Sequence  sa da at ska A Bey SEG OS ao yay ee ek ee Sen ae ath 19  635 Restarksequencee Su  E A AA na 20  64     Alarm Condition  Sequence anta aI ENS SEE SO Ay Be WEEDS A SE Bia Ble 20  6 5 Additional Control Elements  vrsqrrntar rra terra a ta aa p   20  Section 7 0   Safety  7 1 Label  Danger     Unit Starts Up Automatically    2 0    eee 21  7 2 Label  Electria  Symbol  Part No 8820623  201000 rocne A piace 21  7 3 Label Danger   High Voltage    a a A A erat Ga Rai 21  7 4 Label  Caution     Do Not Run Dry     Part No  8850229        o o o oo ooo 22  7 5 Label  Caution     If The Bearing Gap     Part No  9842772 rosas ee 22  6    Equipment dB Ratings  ton  yea seai adie ee ng A A a pa 22    Section 8 0   Maintenance  
32. ation     The following information should be provided to the owner     A Manufacturer   s name  address  and telephone numbers    A Material safety data sheet    A Instruction for system cleaning  flushing  and testing of system water prior to charging   A Off season lay up of equipment     Solution Additives   Prior to filling and charging the storage tank  the interior of the tank and all  piping runs should be thoroughly cleaned to remove pipe scale  dirt  and other impurities  The system  should also be checked for leaks at this time     7 Effective September 1  1998  Revised December 1  2000    It is imperative that these guidelines be followed  Since the concentration in the tank will be  between 7 0  and 7 5   by weight   the additives present in the HVAC grade inhibited glycol will not  be sufficient to protect the system from corrosion and bacterial growth  Dipotassium phosphate   K HPO   must be used as a corrosion inhibitor to protect steel and stainless steel components at a  concentration no less than 4 000 ppm as PO   7 350 ppm as dry K HPO    An azole type corrosion  inhibitor must be added to protect copper and brass components  The best choice is halogen resistant  azole like BetzDearborn AZ8104  10 ppm   Alternatively  one may use tolyl triazole  30 ppm of typical  formulation with approximately 20  active ingredient   Anti foaming agents  such as Dow Corning  1410  may also be added as needed     To inhibit bacterial growth  add 200 ppm of quaternary amine
33. aximICE TES ORE 25 100 Owner s Manual 51 Effective September 1  1998  Part No  9840502 Revised December 1  2000    13 5 Model ORE 50 Flooded Refrigerant Feed  Pumped Slush Discharge   Drawing No  8200140    A LIQUID LINE  SUCTION LINE             36   NOTE 4        fio    ANSI 150  FLANGE  58      BACK VEW LEFT SIDE VIEW  vela ea REF RANT REFRIGERANT CONNECTIONS SOLUTION FEED  N  SLUSH PUMP  OUT   FLOW NET DISCHARGE HEAD  BST EER perreo SERE   aeron   on   RE  adem    DES SO      F FT  sono  asco LBZ   600 eos 13805  pg 2  ert  ar      NOTES   1 All dimensions are in inches unless specified otherwise            2  PMC reserves the right to make product design changes which may  alter the weighis and or dimensions without prior notification   3  Three foot  3  minimum service clearance is required on all  gt   sides of assembly   gt   4  Three feet  3  minimum clearance above ORE is required for removal  5 Si i a trical tion through side of control MODEL ORE 50    ingle point electrical connection rougn side of control panel  3  6  Insulated paneling adds 5  to length  5   to width  2 1 2  to height  pied Suse Deschares  820040 3 0 97  MaximICE TES ORE 25 100 Owner s Manual 52 Effective September 1  1998  Part No  9840502 Revised December 1  2000    13 6 Model ORE 50 Flooded Refrigerant Feed  Pumped Slush Discharge Schematic   Drawing No  8200147    Remote Start   Provide normally open dry contacts lo start unit from remote location   With unit toggle switch turned to  Auto   
34. di dididididi di di di di di di di di di a    Evaporator Slurry Pump Motor    MaximICE TES ORE 25 100 Owner   s Manual 30 Effective September 1  1998    Part No  9840502    Revised December 1  2000    SECTION 9 0   RECOMMENDED SPARE PARTS    9 0 Recommended Spare Parts    The following list consists of specialty type or hard to find parts  while most all other parts can be  purchased locally  See Figure 4     9 1 ORE Common Parts                                                                                      Description Recommended Qty  PMC Part    Oil Return Solenoid Valve  R 22  1 i 9840018  Oil Return Solenoid Valve  R 717  E 1 i 9841307  Whip Rod i  ORE 25   20   ORE 50   40   ORE 100   80  i 8850044  Counter Crank   Right Hand i  ORE 25   20   ORE 50   40   ORE 100   80    9842676  Counter Crank   Left Hand    ORE 25   20   ORE 50   40   ORE 100   80    9842677  Thrust Washer  manufactured before 10 1 99   ORE 25   20   ORE 50   40   ORE 100   80  i 9840477  Full Ice Sensor  temperature controller  l 1 l 9840492  Full Ice Sensor  RTD  i 1 i 9840550  Liquid Level Valve   Heater  amp  Cord i 1 i 9840551  9 2 ORE 25 Parts   Description Recommended Qty  i PMC Part    Drive Plate i   9840975  Drive Motor Shaft Seal   9823991  Housing Bearing i 9840455  Liquid Level Valve Kit  LMC MVE 20  l i 9840557  Liquid Level Valve Kit  LMC MVE 26  i i 9840558  Liquid Level Valve Kit  LMC MVE 34  i i 9840559  Liquid Level Valve  LMC AAB 30  i i 9842708  Power Head  amp  Heater   MVE 
35. e Evaporator   Freeze Up Protection Alarm LL  33  10 2    Unit Fails  on  VentSwitchs ss e234 24586444 ee hi be ee deal e e pta 34  10 Unit Will Not Start  fot pr aaa Ce dat PORT Meee A AAN e Ge tae or 35  10 4 Compressor Operates with High Discharge Pressure   0    36  10 5 Compressor Operates with Low Suction Pressure 1    0    eee 37  10 6   Syst  m Will NOt Mak  166s n  41 pu eon ii ke ente an Ye eS ke Gs 38  10 7 Compressor Fails on Motor Overload   nuaa auaa 39  10 8 System Will Not Cool Building Process Load      coco 40  10 9  Excessive Evaporator Shell Vibration    ius sax 40      44 44 paran e aa e ee ee Rs ean aa 41  10 10 Compressor Fails on Low Oil Pressure   0    42  10 11  EXCESSIVE  Wear ad a alte tee EE apt ae VEE A hl Path note i ales Baa eS 43    Section 11 0   Start Up Requirements    11 1  11 2  11 3  11 4  11 5  11 6  11 7    MaximICE Start Up Request Form   11    aa eee eee 44  Maxim CE Evaporator Unit    es ae ek eke Se glance eh eh eee ae Pa ele    44  Refrigerant Piping for Remote Condenser Systems    44  Water Pipino intere a ca Ra Mom Pag ay E ai bo ue wm re A 45  Electrical  wie b we eas waa eae cada ad he Wee dd aie ea eder goe oO ales Wa Pe he oa ee he ae 45  Installing Contractor Shall Furnish the Following LL    45  Compressor Packager  aye Pe eae AA th el WE EA RE JE ee Rata BRAC Na dae Lai 45    Section 12 0   Wiring Diagram    12 1  12 2    Schematic Wiring Diagram  50 hz   Part No  9841026    46  Schematic Wiring Diagram  60 hz   Part No  
36. e taken if  individual component s  are selected and supplied by others  System performance and operation can  be compromised if any part of the system is incorrectly sized     The typical MaximICE system consists of three individual circuits  refrigeration circuit  ice building  circuit  and cooling circuit  The working system includes an ice storage tank  plate and frame heat  exchanger  coolant pump s   temperature control valve  and piping  The following information  describes each component of the system  along with its operational function     2 1 Refrigeration Circuit    The expansion device consists of a standard  Sporlan  expansion valve equipped with a Level Master   LMC   The bulb of a conventional thermostatic element has been modified to an insert type bulb  which incorporates a low wattage electrical heater  The bulb is installed within a canister which is  attached to the Low Pressure Receiver  LPR   As the refrigerant level drops  electrically added heat  increases pressure within the thermostatic element and opens the valve     As the liquid refrigerant level raises  the electrical input is balanced by heat transfer from the bulb to  the liquid refrigerant  and the LMC either modulates or eventually shuts off  Liquid flows from the  condenser to a suction line heat exchanger  tube in tube  where the refrigerant temperature is cooled  approximately 10  F  5 5  C   The high pressure liquid then enters the expansion valve flashing to  intermediate pressure  ente
37. ed December 1  2000    The supplier of the glycol should be consulted to determine correct RI for the inhibited solution used  at the temperature tested  Adjustments to the solution may be necessary to achieve the correct  concentration  This should always be done prior to starting the MaximICE system  as glycol  concentration will change as the production of liquid ice begins  An accurate measurement of the  concentration of glycol can be accomplished using a hand held refractometer  This instrument is  portable  requires only a few drops of fluid  and needs no adjustment for fluid temperature  PMC  recommends that the glycol solution be tested every month  see Maintenance and Service Manual     It is also recommended that the owner test the alkalinity four times per year for the first year and  annually after that     Glycol Solution Concentration Adjustments   lt is sometimes necessary to increase or decrease the  concentration of the glycol solution in your system to replace fluid lost through leakage or moisture  absorbed from the atmosphere  Either adjustment can be carried out in batch or continuous operation     Procedure for Adjusting Freezing Point of Glycol Fluids   If the concentration of glycol must be  increased  use the formula below to determine the amount of solution to drain and the number of  gallons of glycol to add to increase glycol concentration     A   V D P   100 P     To decrease the glycol concentration  the following formula should be used to deter
38. el ORE 25 Flooded Refrigerant Feed  Gravity Slush Discharge   Drawing No  8200153    LIQUID LINE    36   NOTE 4  LOW    RECEIVER    SOLUTION IN 2   FNPT             SOLUTION IN 2   FNPT     LEFT SIDE VIEW  SIDE VIEW                    NOTES     All dimensions are in inches unless specified otherwise     gt  PMC reserves the right to make product design changes  which may alter the weights and or dimensions without prior  notification      Three foot  3  minimum service clearance is required on all  sides of assembly      Three feet  3  minimum clearance above ORE is required for  removal of whip rods      Single point electrical connection through side of control panel      Insulated paneling adds 5  to length  5  to width  2 1 2   to height     On  u       18 DIA  ICE OPENING               MODEL ORE 25    Flooded Refrigerant Feed  Gravity Slush Discharge    8200183 3 7 97        OCA A E 230  oem    reefurom       MaximICE TES ORE 25 100 Owner   s Manual 50 Effective September 1  1998  Part No  9840502 Revised December 1  2000    13 4 Model ORE 25 Flooded Refrigerant Feed  Gravity Slush Discharge Schematic   Drawing No  8200160    Remote Start   Provide normally open dry contacts to start unit from remote location   With unt toggle switch turned lo    Auto     unit wil start upon contact closure     Load Pump Operation   Provide normally open dry contacts for monitoring of pump  operation  either auxiliory contacts or from EMS   Contacts close upon pump start     Solution Pum
39. emand usage and energy costs  Compared to  traditional cooling systems  the MaximICE system utilizes smaller equipment  thus reducing capital cost     The MaximICE should only be operated by trained personnel and serviced by qualified electrical and  refrigeration technicians  Any use of the equipment not covered by the instructions is prohibited     This manual has been prepared to present to the owner and service technician the installation  operation   and maintenance procedures recommended by Paul Mueller Company for the MaximICE thermal storage  system  The installation plans  piping layouts  etc   must be detailed in accordance with local codes  If  you are uncertain about any installation or operating procedure outlined in this manual  please contact  the Mueller Thermal Storage Department for guidance at 1 800 683 5537 or  417  831 3000     1 1 Delivery Inspection    Each MaximICE evaporator is tested  operational or electrical test  at the factory prior to shipment   however  damage can occur during shipment  The unit should be thoroughly inspected upon arrival at  the installation site  Any damage noted should be reported immediately to the transportation company  so that an authorized transportation representative can examine the unit  determine the extent of the  damage  and take the necessary steps to rectify the claim  At the same time  a Paul Mueller Company  representative should be notified of any claim made     1 2 Safety Considerations    Installation  star
40. er s Manual    35 Effective September 1  1998  Part No  9840502    Revised December 1  2000                                                                                                             Effective September 1  1998    10 4 Troubleshooting Chart 4  Compressor Operates with High Discharge Pressure  Compressor operates with high  discharge pressure   Air Cooled Verify that the fan contactor  Condenser Is the condenser fan    on     is pulled in  Check for  failed fan motor     Clean coil with condenser coil soap  Is the condenser coil clean    gt  i  no solution   j yes  Any Type of al  Condenser AA Adjust  repair  or replace   controlling properly  do  yes  Is the liquid line Mer y Replace   drier clogged  yes  Water  Check the temperature rise  Cooled Is the cooling water flow sufficient  L             through the condenser and adjust  Condenser no cooling water flow as necessary     yes  Is the cooling water inlet  temperature too high  above Check cooling tower for problems   design   yes    no  Is the condenser fouled or scaled  Cleanithe tube to rem  v   fo  ling or  yes scale   MaximICE TES ORE 25 100 Owners Manual 36    Part No  9840502    Revised December 1  2000    10 5       Compressor operates with low  suction pressure                                                                         Troubleshooting Chart 5  Compressor Operates with Low Suction Pressure          Is the motor operating properly   Check voltage and amp draw                          
41. erential  switch can be employed     For a remote  evaporatively cooled condenser   Proof of condenser water pump and fan operation  is required     For a remote  air cooled condenser   Proof of operation or signal upon a unit failure is required     4 4 Refrigerant Piping    The installing contractor shall provide and install all interconnection piping and service valves  All  refrigerant  R 22  piping shall be Type L or K hard copper or Schedule 40 steel piping  All piping shall  be purged with an inert gas during welding or brazing  Ammonia  R 717  must be piped per ASHRAE  15 latest revision     A pressure leak test of the complete refrigeration system is required once field piping is complete  The  system shall be proven tight at 25 psig  175 kPa  below the lowest setting pressure relief valve     The entire system must be evacuated to at least 500 microns with a five minute hold period     The contractor shall provide a charging line from the charging connection on the MaximICE unit to the  charging drum s      4 5 Start Up Coordination Inspection    Upon arrival of PMC authorized start up personnel at the job site  a start up coordination meeting will  be held and a walk through inspection of the job site conditions will be conducted  All trades involved  in the installation should be represented  This includes  but is not limited to  the general contractor   mechanical contractor  plumbing contractor  tank contractor  and owner s representative  The start up  will not
42. ffective September 1  1998  Part No  9840502 Revised December 1  2000    13 8 Model ORE 50 Flooded Refrigerant Feed  Gravity Slush Discharge Schematic   Drawing No  8200161    Remote Start   Provide normally open dry contacts to start unit from remote location   With unit toggle switch turned lo    Auto     unit will start upon contact closure     Load Pump Operation   Provide normally open dry contacts for monitoring of pump  operation  either auxiiary contacts or from EMS   Contacts close upon pump stort     Solution Pump Operation   Provide normaliy open dry contacts for monitoring of  pump operation  either auxiliary contacts or from EMS   Contacts close upon pump start     SINGLE PHASE             ORE 50  TYPICAL WRING  gt  Condensing Unit Pumpdown Low Pressure Switch   Provide normally closed dry contacts   SCHEMATIC Contacts open when suction pressure drops to 5 psig  condensing unit shuts down       Dual compressor condensing  unt wring shown  See unit  wiring diagram for single  condensing unit   and optional ilems     Condensing Unit Alarm 1  Provide normally closed dry contacts  Contacts open  upon condensing unit alarm condition  condensing unit shuts down     Candensing Unit Alarm 2  Provide normally closed dry contacts  Contacts open  upon condensing unit alarm condition  condensing unit shuts down   OPTIONAL     Remote temperature switch    Wired to remote ice level inventory sensor  Conacts close on full ice condition  predetermined temperature setting    OPTI
43. for approximately 1       1 6 mm  clearance between the eccentric crank and drive plate  bearing  no pressure on drive plate      Figure 2   ORE Drive Assembly Detail    HOUSING BEARING             ECCENTRIC CRANK    1 16 IN  1 32    16 MM 08 CAP            iS    TOIT ML   4    N        EZ LLL 22 dt    SS        SS       BEARING SLEEVE    DETAIL A    3 22 Gravity Feed System    A gravity feed ice discharge system  with a telescopic type housing mounted to the evaporator  bottom  that  extends into the ice opening  is incorporated for systems where the evaporator is installed on top of the ice  storage tank  A watertight seal must be applied once the unit is set in place and the housing is lowered into    the opening  The gap  about      12 mm  can be filled with insulation rope and sealed with a layer of  silicone     MaximICE TES ORE 25 100 Owner   s Manual 10 Effective September 1  1998    Part No  9840502    Revised December 1  2000    Figure 3   MaximICE ORE 25 Drive Assembly                                            MOTOR  Oy  DRIVE SHAFT  TOP PLATE   9823989  OAS   DRIVE PLATE  MOUNTING  9840975   i  oa  __  at fal STEEL PIN  5 KA WT 7 Al  RUBBER GASKET_   L   9823996    SA A La  9825000   TOA satin COUNTERCRANK  INSERT l RH  9842676    9840476  i LH  9842677   WHIP  ROD   8850044    n   ERE di a Ai  cd 1 16 IN  HOUSING n 16 na                         f    i   prat i i  da i DRIVE PLATE  se BEARING SLEEVE  Gr K  DETAIL A J    WHIP ROD                                   
44. g circuit complete to compressor motor     A All wire is copper  no aluminum wiring      11 6 Installing Contractor Shall Furnish The Following  A All materials and labor necessary to assist in the installation start up      Arefrigeration service mechanic to assist PMC start up personnel during start up for necessary  training in the operation of the unit  This training is essential in performing in warranty labor    incumbent upon contractor and or end user     11 7 Compressor Package    A Check compressor motor alignment and align as necessary to within   004   0 1 mm   angular parallel     A Check oil pump motor alignment and align as necessary to within   004   0 1 mm     angular parallel   MaximICE TES ORE 25 100 Owner   s Manual 45 Effective September 1  1998    Part No  9840502 Revised December 1  2000    SECTION 12 0   WIRING DIAGRAMS    12 1 Schematic Wiring Diagram  50 hz   Part No  9841026    MaximICE TES ORE 25 100 Owner   s Manual 46 Effective September 1  1998  Part No  9840502 Revised December 1  2000    12 2 Schematic Wiring Diagram  60 hz   Part No  9823978    MaximICE TES ORE 25 100 Owner   s Manual 47 Effective September 1  1998  Part No  9840502 Revised December 1  2000    SECTION 13 0   MUELLER MaximiCE LIQUID ICE EVAPORATOR  EQUIPMENT SPECIFICATIONS    13 1 Model ORE 25 Flooded Refrigerant Feed  Pumped Slush Discharge   Drawing No  8200139    LIQUID LINE  SUCTION LINE    36   NOTE 4   PRESSURE       ORBITAL ROD  EVAPORATOR       87       5 z   ANS 1502 
45. g or servicing the equipment  adequate hearing protection must be  used           MaximICE TES ORE 25 100 Owner   s Manual 22 Effective September 1  1998  Revised December 1  2000    Part No  9840502       SECTION 8 0   MAINTENANCE    8 0 Maintenance    The MaximICE system is designed to be a low maintenance piece of equipment  Preventive  maintenance is the key to a properly operating unit  It is recommended to maintain an inspection log  book for tracking the history of operation     8 1 Daily Checks    A Inspect the ORE unit for solution leaks and excessive vibrations  Check for proper compressor  suction pressure and temperature     Inspect around ice storage tank for solution leaks  piping  fittings  and tank surface    Check for oil spots around condensing unit     Listen to compressor for any noises different than normal  Sound level s  should be constant      gt   gt   gt   gt     Listen to the ORE  The whip rods should make a sibilant noise  sh      Rattling noises may indicate  one or more frozen tubes     8 2 Recommended Inspection Procedures    The following points should be inspected when performing preventive maintenance on the MaximICE  thermal energy storage system     A Drive Component Inspection       a  Turn the on auto off control switch inside the ORE control panel to the off position  At this time   the liquid line solenoid and the oil return solenoid will close and the unit will pump down     b  After the pumps and the drive assembly stop  turn the main
46. gle valve off  at the evaporator and remove the hose that is connected to the freeze up protection switch    NOTE  Loosen the hose fitting very slowly because of the possibility of the presence of liquid in  the line   Using a VOM meter  set the meter to the OHM position  Attach the leads to the NC set of  contacts on the freeze up protection switch  Attach the suction hose from your gauge set  blue  hose  to the freeze up protection switch  Attach your charging hose  yellow hose  to a bottle of  pressurized gas  preferably nitrogen  When pressure is applied to the switch it will show you the  exact pressure of your suction gauge  The freeze up protection switch should be set to open at 35  psig  240 kPa   If the switch opens before the 35 psig  240 kPa   adjust the switch accordingly     A Water Regulating Valve       You will see 2 valve stems on the inlet and on the outlet side of the solution regulating valve   Using a 0 50  0 350 kPa  psig gauge with the proper valve stem connection  take a pressure  reading on the inlet side of the solution regulating valve  This pressure must be at least 5 psig  35  kPa  and no more than 32 psig  220 kPa   If the pressure on the inlet of the regulator is not within  these parameters  the machine is either not getting enough solution and has the possibility of  freeze up or  if it exceeds the pressure  the unit will not be running at the designed capacity  The  design flow rates are 65  130  and 245 gpm  245  490  and 930 1 min  for the
47. he program is causing a failure   The on auto off switch located in the control enclosure facilitates unit operation within the panel  A  manual switch reset is required after a system failure shutdown  The MaximICE unit is programmed  with a unique system start up and shutdown sequence unlike common refrigeration equipment  The  following information describes a typical system operation sequence   NOTE  The PLC is equipped with dual  low voltage 24V  input side is 24VDC and output side is 24VAC   6 1 Start Up Sequence   A Select either    MANUAL    or    AUTO    on local 3 position toggle switch    MANUAL   System starts immediately    AUTO   System starts when remote    Enable    signal is received   A Slush pump and feed pump on    Enable temperature sensor while system fluid circulates for 5 minutes     A End of 5 minute circulation  Check to see if high ice condition exists         No full ice condition   Drive motor  pump down solenoid  and LLM heater are energized   Continue start up         Full ice condition exists   System shutdown on full ice         Periodically  the system shall restart the glycol solution to verify a full ice condition  If full ice  exists after a 5 minute check  the system should remain off     A 10 seconds delay after drive is on   Condensing unit  oil return solenoid  and unload  solenoid s  are energized  system operates unload for 2 minutes  At the end of 2 minutes  the  unload solenoid s  are de energized  allowing for full load compressor
48. igh        Verify expansion device operation              MaximICE TES ORE 25 100 Owner s Manual    Part No  9840502    39    Effective September 1  1998  Revised December 1  2000    10 8 Troubleshooting Chart 8  System Will Not Cool Building Process Load       System will not cool  building process load              Allow system to operate and begin       Is there ice in Kop     the storage tank    gt  making ice  If possible  turn  ge tank  no pi    building process cooling pump off   yes          Check pump motor voltage  amp draw  pump    discharge pressure  and impeller  Most likely  the motor is faulty  Repair replace     Is the building process cooling  pump operating properly  no      yes  Is the pressure drop across the  Is the process flow rate correct  plate heat exchanger above  no normal  yes    yes                      Disassemble and clean heat  exchanger plates                                                                                                     Is the heat exchanger Disassemble valve  Clean spray ball or spray nozzle in  temperature water regulating valve                Clean  repair  or install no ice storage tank   controlling properly  no repair kit   yes  Is refrigerant level too low  Add charge  Fix leaks   yes    no  Are some of the tubes frozen      See Chart  Section 9 1   yes    no  Is solution bypassing ice in tank  Check spa Ad performanc     LWT will be higher than design     yes  gt  pray P      no  Is solution level in tank correct
49. imICE TES ORE 25 100 Owner   s Manual 32    Part No  9840502    Effective September 1  1998  Revised December 1  2000       SECTION 10 0   TROUBLESHOOTING FAILURES    10 1          Low pressure evaporator     freeze up  protection  PLC Output O Y12  Continuous light          y                                                             Is the glycol solution  concentration level            above 7   no    yes  Is the drive plate rotating at  the correct speed  no  yes  Are any of  gt  EEE  roken  yes   ro  Is the R 22 charge correct    See Section 5 0 for discussion of  gt  gt    correct charge   no  yes  Is the liquid level valve operating 3  properly  no  0 yes  Is evaporator solution  flow rate correct  no  yes  no  Is the full ice sensor faulty and the tank  over filling with ice  allowing ice slurry  gt  gt    to be pumped into the evaporator  yes    no  Is compressor capacity too large  for ORE   gt   yes   mo  Does ice build up on tubes during  either start up or   gt   pump down  yes  no    MaximICE TES ORE 25 100 Owner   s Manual  Part No  9840502       With no ice in the tank   measure percentage level  and adjust to 7  minimum           Are the  drive motor  speed pots  adjusted correctly    50 hz units only      Troubleshooting Chart 1  Low Pressure Evaporator   Freeze Up Protection Alarm       3  gt    yes             Is the motor operating  properly   Check voltage and amp draw              Remove drive assembly and  replace countercranks        no          Find
50. is issue and may  experience rapid wear of eccentric  tube inserts   countercrank pins  whip rod heads  and necks              Add 1 micron sidestream filter to remove suspended solids  Run  until solution is clear  Systems with agitated ice slurry tanks are  especially sensitive to this issue  and may experience rapid wear  of eccentric  tube inserts  whip rod neck  and countercranks                 This is normal for Acetal countercranks   especially in chilling service  Replace  with PEEK countercranks     yes          Drive running too fast  Adjust  speed to  lt  850 rpm                 This is normal  Only one side is loaded  load  force rotates with eccentric   To extend life   switch drive motor leads so opposite side of   pin becomes loaded                 Replace with stainless steel    H   housing bearing and new sleeve    bearing              Check for proper clearance between  drive plate and eccentric   Replace sleeve bearing                 Sleeve bearing is worn out or loose  in housing  See above     yes       Unit ran while tube full of ice and  countercranks frozen in position   See Chart 1  Low Pressure  Evaporator Freeze Up           Drive plate not centered inside inlet  shell  Adjust inner shell so drive       Pin on countercrank has rough  surface  Replace drive plate and  countercrank                       Driveplate lifted off countercranks   Contact PMC to discuss problem                    Motor overloaded because tubes  frozen solid  See Troublesho
51. lycol solution              NOTE  Refer to Figures 3 through 6 with the following drive installation steps   A Using a flashlight  inspect each tube for any foreign debris     A Apply a thin coat of petroleum jelly on each countercrank prior to installing  lower end  top edges      MaximICE TES ORE 25 100 Owner   s Manual 9 Effective September 1  1998  Part No  9840502 Revised December 1  2000    A    Working clockwise at the alignment mark  place each countercrank in a left hand right hand  arrangement  Countercrank type is determined by positioning the drive pin at six o   clock and  checking the slot point direction     NOTE  The ORE 50 and 100 have several countercranks that may appear out of sequence  See the  appropriate layout drawing for specific alignment     A    A    A    A    Install each whip rod   Position all drive pins towards the evaporator top tube sheet alignment mark   Install lower rubber gasket     Install drive plate by matching the top tube sheet alignment mark with the drive plate     NOTE  The evaporator top sheet and drive plate are labeled with an alignment mark s  to ensure  proper assembly      gt      gt      gt      gt     Install clear PVC top water chamber   Install upper rubber gasket   Install top head     Install drive motor  Adjustments can be made to the eccentric crank during assembly by rotating  the motor fan blades with small screwdriver     Tighten top plate mounting bolt using a star pattern while tightening bolts     Adjust motor 
52. mine the volume  to drain and replace with high quality water     A   V P D  P  Where     A   The quantity  in gallons or m3  of glycol to be added to the system to lower the freeze point or  the quantity  in gallons or m3  of glycol solution that must be drained from the system to decrease  glycol concentration    V   The total solution capacity of the system in gallons or m3    D   The volume percent of glycol desired in the system    P   The volume percent of glycol presently in the system     3 19 Freeze Protection    Units located outside shall require freeze up protection  heat tape on all solution lines   A glycol  solution is required for the MaximICE system  however  during low ambient conditions  outside  temperatures below 27  F or  3  C   the solution may freeze and cause piping damage     3 20 Insulation    All glycol solution piping should be insulated with 2   50 mm  polyfoam Armaflex to prevent external  heat gain  The ice storage tank s  supplied by PMC  polyethylene type  must be placed on top of at  least 3   75 mm  of styrofoam with a loading strength of 25 psi  175 kPa   Heat gain and proper  insulation practices should be considered for concrete tanks constructed on site     3 21 ORE Drive Assembly    The drive system is designed with very close tolerances to ensure proper clearance  water sealing  and  operation of all drive components extreme caution should be taken during installation        A CAUTION  Do not operate drive system without circulating g
53. n  with appropriately sized hold down anchor bolts  not furnished with equipment  and are to be  securely anchored to the concrete pad by the customer  Refer to Figure 1 below for anchorage details   Polyethylene tank s  will require tie down straps  All applicable seismic zone regulations and proper  construction practices should be considered in areas designed by the state     Figure 1   Anchorage Details    TANK    OPTIONAL WELD              1  RED HEAD WELD   25 mm   TANK BASE RING  PLATE  BASE RING  SHIM PLATE   BEAM    CONCRETE  PAD    CONCRETE PAD    ALTERNATE ANCHORAGE  1 ALTERNATE ANCHORAGE  2    MaximICE TES ORE 25 100 Owner   s Manual 4 Effective September 1  1998  Part No  9840502 Revised December 1  2000    3 4  Serviceability    Accessibility is required for servicing the equipment  A 3   0 9 m  clearance around the evaporator  compartment and a 4   1 2 m  clearance above the top are required  Review the appropriate submittal  drawing for exact required top clearance     3 5 Shipping Charge    All units are shipped with a dry nitrogen charge  approximately 5 psig 35 kPa  that is required to be  bled off prior to installation  Extreme care must be taken while removing flanges or caps when the  system is under pressure     3 6 Remote Refrigeration Piping    The refrigerant connections  suction  liquid  on the evaporator skid are sized based on the condensing  unit located within 10   3 m  of equivalent length tubing of the ORE skid  For systems with more than  the
54. ng LL  5  Refrigerant Piping Pressure Testi ii a Re AI 5  System EVAGUAHONi tiran delas a Ee aaa bbb eee we vague tele 00 5  Refrigerant Charge    os fice aa Oe bee bean et dep ode aa e edad 5  Condensing Unite  tl RIS etna REG iS oa 5  Electrical  E AR A ee EEE ROR ani Rae aes II 6  Electrical Specifications  ORE 25  musas pa e ee ee a EEE GE HOE EM ee 6  Electrical Specifications  ORE 50 ais ei a Gee Re gah Mas ea    6  Electrical Specifications  ORE 100   lt a terser ad sogar Rb a ee ee   n 7  Ice Storage Tank   Full Ice Sensor Option LL    7  Ice Storage Tank   Vent Line Leo he BAe io See TEST EN eee ed hee AP SoeEe ni 7  Ice Storage  Tank  Spraying System ess ianen cadre A A Ge dea e ben a 7  Glycol Solution Specification ri aA ooo    7  Freeze PTOLECLON 1 4  tack ioe ue e RE ie Fr   uk S   eee E Gare ale STEG RE Re ie 9  Insulation  se A AA ate be a La ee ehh E A A 9  ORE  Drive  Assembly iy ets Sag A ee eh La RESALES and ee AA 9  Figure 2   ORE Drive Assembly Detail 2 44522 64    4444eGee09R Eso e bee put end 10  Gravity Feed System A ia 10  Figure 3   MaximICE ORE 25 Drive Assembly    11  Figure 4   MaximICE ORE 50 Drive Assembly      ooo o o oocooooo eee 12  Figure 5   MaximICE ORE 100 Drive Assembly    13  Figure 6   ORE Countercrank Assembly    14  Packins Material s  xy os  i RAEE ILL RA rap AAA REIS id SEG 15    Figure 7   MaximICE Refrigeration Schematic Diagram LL 15    TABLE OF CONTENTS   CONTINUED    Section 10 0   Troubleshooting Failures    10 1 Low Pressur
55. nit           Is the liquid level valve  controlling properly                gt   no       j yes    Adjust  repair  or replace           Is the compressor  operating properly          no            yes    Check suction versus discharge pressure     Normally discharge pressure exceeds  suction by approximately 150 psig           Is the unit shutting off on  temperature sensor prior to making  ice  Operating as a chiller only        yes          V yes          Check set point on high ice sensor   It should be 24 26   F    4 4 to  3 3  C            MaximICE TES ORE 25 100 Owner   s Manual    Part No  9840502    Glycol concentration solution may be too  high  With no ice in the tank  measure  glycol concentration and adjust to 7 8      38       Effective September 1  1998  Revised December 1  2000    10 7       Compressor continues to fail  on internal motor overload             Troubleshooting Chart 7  Compressor Fails on Motor Overload          Is the voltage correct at  the motor     yes    no    Check motor nameplate data and  apply correct voltage                    Do all three legs draw some  amps           0 yes       Is the compressor discharge  pressure above 300 psig     Check motor wiring to find cause  of single phasing               ie    Verify condenser operation           Is the compressor discharge  temperature above 180  F  82  C             gt    yes            ro    Verify oil cooling   condenser operation                 Is the suction superheat extremely  h
56. nit Condensing Unit Alarm 2  Provide normally closed dry contacts  Contacts open    upon condensing unit alarm condition  condensing unit shuts down   OPTIONAL     Remote temperature swilch   Wired to remole ice level nventory sensor  Conacts close on ful ice condition  predetermined temperature setting    OPTIONAL                Condensing Unit Start 1   24VAC contacts close to start condensing unil      Compressor Unloading  Step 1   24VAC contacts close to unload compressor      Condensing Unit Start Z   24VAC contacts close to start condensing unit   OPTIONAL     Remote Alarm   Dry contacis close upon alarm condition for remole alarm indication       Remote Solution Pump Start   Dry contacts close to start solution pump         INPUT TO MaximiCE PLC   O   OUTPUT FROM MaxmiCE PLC     CUSTOMER SUPPLIED  3 PHASE WITH GROUND    MUELLER    MODEL ORE 100    Flooded Refrigerant Feed  Pumped Slush Discharge    3200148 3 97          LOT TE 1 387                 MaximICE TES ORE 25 100 Owner   s Manual 57 Effective September 1  1998  Part No  9840502 Revised December 1  2000    13 11 Model ORE 100 Flooded Refrigerant Feed  Gravity Slush Discharge     Drawing No  8200155  EE ae 11 2  I I 36 LIQUID LINE     NOTE 4  ai    LOW PRESSURE  RECEIVER       ORBITAL ROD  I    EVAPORATOR          Sr MEET Er PN     SOLUTION N 4   ANSI 1501 FLANGE  TETT  en    78  ACK VIEW LEFT SIDE VIEW    NOTES     1  All dimensions are in inches unless specified otherwise   2  PMC reserves the right to moke p
57. o    OFF    position to reset alarm condition after shutdown is complete      gt   gt   gt     Alarm status     6 4 Alarm Condition Sequence    A Condensing unit alarm   Compressor motor overload  high discharge switch  and low oil pressure  switches are wired in series     Motor overload   Drive motor  slush pump  and solution pump in series     Freeze Up Protection   Evaporator low pressure switch set for  3 psi 20 kPa to 5 psi 35 kPA   below normal operating pressure  lowest      A High level solution vent line switch   Ice slurry discharge from ORE interruption   A Glycol solution flow switch   Glycol solution feed to ORE interruption   A Emergency stop     6 5 Additional Control Elements    A Vent switch intermediate trip alarm   a  Vent switch must be tripped for 10 seconds before intermediate trip condition     b  Condensing unit will shut down for 10 minutes while the rest of the system continues to  function as usual     c  After 10 minutes   1  Vent switch clear  Condensing unit restarts     2  Vent switch not clear  System shutdown on vent alarm  If intermediate trip condition  occurs three times in 30 minutes  system shuts down on vent alarm     A High vent switch    The entire unit shuts down after a 5 second delay     Drive motor will not operate when the high temperature solution feed indicates glycol  temperatures above 55  F  13  C      MaximICE TES ORE 25 100 Owner   s Manual 20 Effective September 1  1998  Part No  9840502 Revised December 1  2000    SECTIO
58. or remote alarm indication       Remote Solution Pump Start   Dry contacts close to start solution pump         INPUT TO MaximiCE PLC   O   OUTPUT FROM MaxmiCE PLC        THREE PHASE POWER    CUSTOMER SUPPLIED  3 PHASE WITH GROUND    MUELLER    MODEL ORE 50    Flooded Refrigerant Feed  Pumped Slush Discharge    820047 31497          MaximICE TES ORE 25 100 Owner   s Manual 53 Effective September 1  1998  Part No  9840502 Revised December 1  2000    13 7 Model ORE 50 Flooded Refrigerant Feed  Gravity Slush Discharge   Drawing No  8200154    LIQUID LINE       LIQUID LINE CONTROL LIFTI  PANEL    36   NOTE 4         gt  70 FRAME              58 FRAME    SOLUTION N 3  ANSI 1502 FLANGE    dl     contro  Box   NOTES   lait  1  All dimensions are in inches uniess specified otherwise     2  PMC reserves the right to make product design changes  which may alter the weights and or dimensions    3  Three foot  3  minimum service clearance is required  on all sides of assembly    4  Three foot  3  minimum clearance above ORE is required  for removal of whip rods    5  Single point electrical connection through side of  control panel    6  Insulated paneling adds 5  to length  5  to width    24 DIA 2 1 2  to height     ICE OPENING       OP VEW    bs    tbs  tbs  acmon   Loun   RATE eeit eoo  spa  amo   00 19009  ye T sao  ar   o aro  reo                 MODEL ORE 50  Flooded Refrigerant Feed  Gravity Slush Discharge    8200154 3 1V97            MaximICE TES ORE 25 100 Owner   s Manual 54 E
59. oting  Chart 1                    Whip rod cannot roll  Replace bent  whip rod  Check head thickness    Make sure only one thrust washer  is used  Acetal countercranks               Mechanical seal failure  Replace  seal and bearings   yes  Condensation build up inside  motor  Add drainage holes at motor  bottom flange  Do not run cold yes  solution in unit when drive off   Unit ran while tubes full of ice  See  a  Chart 1  Replace whip rods  yes             Notify PMC if problem continues   May lead to tube failure if  underlying problem is not fixed           43    Effective September 1  1998  Revised December 1  2000       SECTION 11 0   START UP REQUIREMENTS    11 1 MaximiCE   Start Up Request Form  Prior to requesting start up  verify that all the following items are complete  Only PMC qualified start   up personnel shall be authorized for start up  Unauthorized start up of equipment will result in    immediate void of warranty     Purchaser        Address        Contact Person        Telephone No         Facsimile No         Unit Model        Unit Serial No         Installation Location        Address        11 2 MaximiCE Evaporator Unit    A Equipment must be inspected for any damage that may have occurred during shipping  If damage  is found  a claim should be made against the trucking company           Check the packing slip or bill of lading to ensure that all accessory parts called for in the sales  order are included     The unit must be level to within   g  G mm 
60. p Operation   Provide normally open dry contacts for monitoring of  pump operation  either auxiliary conlacts or from EMS   Contacts close upon pump start     SINGLE PHASE    ORE 25  TYPICAL WIRING Condensing Unit Pumpdown Low Pressure Switch   Provide normally closed dry contacts   SCHEMATIC Contacts open when suction pressure drops to 5 psig  condensing unit shuts down     Condensing Unit Alarm 1  Provide normally closed dry contacts  Contacts open      Single compressor  upon condensing unit alarm condition  condensing unit shuts down     condensing unit wring shown   See unit wring dagram   for multiple condensing units      gt  Condensing Unit Alarm 2    Jumper in conirol box   OPTIONAL   and optiond items   Remote temperature switch    Wired to remote ice level inventory sensor   Conacts close on full ice condition  predetermined temperature setting    OPTIONAL          I Condensing Unit Start   ZAVAC contacts close to start condensing unit      Compressor Unloading  Step 1   24VAC contacts close to unload compressor      Compressor Unloading  Step 2    24VAC contacts close to unload compressor    7 Remote Alarm   Dry contacis close upon alarm condition for remole alarm indication      gt   Remote solulion Pump Start   Dry contacis close to start solution pump     I   INPUT TO MaximiCE PLC   O   OUTPUT FROM MaximiCE PLC     CUSTOMER SUPPLIED  3 PHASE WITH GROUND    MUELLER       MODEL ORE 25    Flooded Refrigerant Feed  Gravity Slush Discharge  220060 3 10 97          M
61. piping  at not less than 10 ft sec  3 m sec  velocity for six hours  The water piping shall then be flushed with  clean water to remove any residue     All exposed exterior water piping shall be heat traced and insulated  The Paul Mueller Company  warranty specifically excludes any liability for freezing damage resulting from low ambient temperatures     The ice storage tank must be cleaned with an approved cleaning solution and rinsed with clean water  prior to adding water glycol solution  The water piping system  including the tank  shall then be filled  with clean water and 7  glycol to 60  of the height of the tank  The water glycol solution should be   analyzed by a water treatment authority and properly treated for oxygen corrosion  scales  algae  and   fungus growth  The water should be periodically checked by a water treatment authority     Water cooled condenser water piping shall be cleaned and flushed to remove all debris  The  condenser cooling tower water shall be properly treated  A properly sized strainer should be used on  the condenser water supply to the MaximICE  The condenser  condenser water piping  condenser  pump  and cooling tower must be properly protected against freeze damage resulting from low  ambient temperatures     Evaporative condensers shall be flushed and properly treated  A proper water treatment system usually  consists of a continuous blow down and chemical feeder  The condenser  condenser water piping   condenser water make up line  and
62. rage Tank   Full Ice Sensor Option    To determine a full ice storage tank condition  a temperature bulb is mounted in the evaporator  solution inlet which sends a signal to a digital temperature controller located in the PMC control box   As the amount of ice increases within the storage tank  the glycol percentage increases and lowers the  solution freeze point  At approximately 24 to 26  F   4 4 to  3 3  C  the PLC receives an input from the  controller initiating a full ice shutdown     Ice Storage Tank   Vent Line    To ensure proper solution flow  a vent system is incorporated  Attach the vent line to the top of the ice  storage tank top  The line must be mounted to ensure full draining  with no loops or kinks     Ice Storage Tank   Spraying System    To ensure that the stored liquid ice is burned efficiently and a low temperature supply solution can be  maintained to the cooling loads  spray devices s  must be used to distribute the warm solution over the  liquid ice  For field fabricated storage tanks  spray distribution system should be supplied in sufficient  numbers and location  based upon spray pattern  to provide maximum coverage over the liquid ice   Please consult PMC for field fabricated storage tank spray distribution systems     Glycol Solution Specification    The MaximICE TES system uses a very low concentration of propylene or ethylene glycol solution as  the storage medium to promote the growth of the ice crystals     Glycol Manufacturer Supplied Inform
63. ree feet  3  minimum clearance above ORE is required for removal  of whip rods     5  Single point electrical connection through side of control panel  MODEL ORE 100  6  Insulated paneling adds 5  to length  5  to width  2 1 2  to height  Flooded Refrigerant Feed  Pumped Slush Discharge  820041 31 97  MaximICE TES ORE 25 100 Owner   s Manual 56 Effective September 1  1998  Part No  9840502 Revised December 1  2000    13 10 Model ORE 100 Flooded Refrigerant Feed  Pumped Slush Discharge Schematic   Drawing No  8200148    Remote Start   Provide normally open dry contacts to start unit from remote location   With unt toggle switch turned lo  Auto   unit will start upon contact closure     Load Pump Operation   Provide normally open dry contacts for monitoring of pump  operation  either auxiliary contacts or from EMS   Conlacts close upon pump start     Solution Pump Operation   Provide normally open dry contacts for moniloring of  pump operation  either auxiliary contacts or from EMS   Contacts close upon pump start     SINGLE PHASE    ORE 100  TYPICAL WIRING Condensing Unit Pumpdown Low Pressure Switch   Provide normally closed dry contacts   SCHEMATIC Contacts open when suction pressure drops lo 5 psig  condensing unit shuts down     Candensing Unit Alarm 1  Provide normally closed dry contacis  Contacts open  upon condensing unii alarm condition  condensing unit shuts down       Dual compressor condensing  unit wring shown  See unil   wing dagram for single i   i  condensing u
64. roduct design changes  which may alter ihe weights and or dimensions   3  Three foot  3  minimum service clearance is required  on all sides of assembly   4  Three foot  3  minimum clearance above ORE is required  for removal of whip rods   5  Single point electrical connection through side of  control panel   6  Insulated paneling adds 5  to length  5   to width   2 1 2  to height        32 DIA  ICE OPENING       TOP VIEW    Feen REFRIGERANT CONNECTIONS SOLUTION FEED IN  MER CHARGE FLOW NET  lbs    b   be   SucTON   uouo   Raf rett neon  n     so    vevos  1518005  25   550  am   es EEE  M   bo                   Flooded Refrigerant Feed  Gravity Slush Discharge    8200855 3 1497       MaximICE TES ORE 25 100 Owner   s Manual 58 Effective September 1  1998  Part No  9840502 Revised December 1  2000    13 12 Model ORE 100 Flooded Refrigerant Feed  Pumped Slush Discharge Schematic   Drawing No  8200162    Remote Start   Provide normally open dry contacis lo start uni from remote location   With unit toggle switch turned to    Auto     unit will start upon contact closure     Load Pump Operation   Provide normally open dry contacts for monitoring of pump  operation  either auxiiary contacts or from EMS   Contacts close upon pump start     Solution Pump Operation   Provide normally open dry contacts for monitoring of  pump operation  either auxiliary contacts or from EMS   Contacts close upon pump start     SINGLE PHASE    ORE 100  TYPICAL WIRING Condensing Unit Pumpdown Low Pres
65. rs the evaporator  bottom   and surrounds the evaporator tubes     The evaporator is also coupled to the LPR employing a gravity feed  constant liquid refrigerant  recirculation effect  Gravity feed liquid flows from the LPR  enters the evaporator  bottom   and mixes  with refrigerant supplied from the expansion valve  A two phase refrigerant flows from the evaporator  into the accumulator  where dry suction gas is then returned to the compressor  Inside each evaporator  tube is a free hanging 3 3   9 5 mm  stainless steel rod running the entire tube length  A plastic  countercrank holds the whip rod in place  while a small pin is attached to the drive plate  The drive  motor coupled to the drive plate rotates the attached whip rods continuously  approximately 800 rpm   during system operation  The drive is equipped with a soft start system to reduce starting internal  torque  A seal gasket provides an air tight seal at the drive shaft penetration point  located on the top  plate  Solution pouring into the evaporator tubes and gravity drains gives up heat to the refrigerant   producing a boiling effect  pushing liquid gas out the top  As two phase refrigerant enters the LPR  gas  velocity is reduced and the separated dry vapor is drawn into the compressor  The whip rod spinning  action creates a high agitation rate  increasing solution to tube surface contact  The end result is a  highly efficient slurry ice maker  see Figure 7     MaximICE Refrigeration Schematic Diagram    
66. s Manual 3 Effective September 1  1998  Part No  9840502 Revised December 1  2000    SECTION 3 0   INSTALLATION    3 0 Installation    NOTE  It is very important in installations where the customer supplies certain components  ice  storage tank  heat exchanger  valves  and or fittings  that the following information and details are  addressed  PMC shall not be held responsible for performance on systems constructed  piped  or  designed differently than outlined in this manual     3 1 Equipment Rigging    The MaximICE unit and ice storage tank must be lifted in accordance with industry practice  Lifting  lugs and sleeves are not intended to be used for extended periods of time  The evaporator section is  designed for four point top lifting only  Please refer to equipment specifications section for weights        CAUTION  A spreader bar must be employed during the lifting process   failure to do so will  result in equipment damage              3 2 Foundation    MaximICE units should be anchored to a concrete or structural steel base  Due to the varying  conditions across the globe  it is recommended than an architectural engineer be consulted to  determine the thickness of the concrete pad or structural steel in accordance with local codes  The  concrete pad or structural steel must be level within       3 mm  to adequately support the refrigeration  equipment     3 3 Anchoring    According to local codes and practices  the refrigeration equipment should be welded or bolted dow
67. sure Switch   Provide normally closed dry contacts   SCHEMATIC Contacts open when suction pressure drops to 5 psig  condensing unit shuts down     Condensing Unit Alarm 1  Provide normally closed dry contacts  Contacts open  upon condensing unii alarm condition  condensing unit shuts down       Dual compressor condensing  unit wring shown  See unil  wiring diagram for single  condensing unit   and optional items     Condensing Unit Alarm 2  Provide normally closed dry contacts  Contacts open  upon condensing uni alarm condition  condensing unit shuts down   OPTIONAL     Remote temperature switch    Wired to remote ice level inventory sensor  Conacts close on full ice condition  predetermined temperature setting    OPTIONAL               Condensing Unit Start 1   24VAC contacts close to start condensing unit    4  Compressor Unicading  Step 1  24VAC contacts close to unload compressor      Condensing Unit Start 2   24VAC contacts close to start condensing unit   OPTIONAL     Remote Alarm   Dry contacts close upon alarm condition for remote alarm indication     7 Remote Solution Pump Start   Dry contacts close to siart solution pump         INPUT TO MaximiCE PLC   O   OUTPUT FROM MaximiCE PLC     CUSTOMER SUPPLIED  3 PHASE WITH GROUND    MODEL ORE 100    Flooded Refrigerant Feed  Gravity Slush Discharge  820062 3 1V97       MaximICE TES ORE 25 100 Owner s Manual 59 Effective September 1  1998  Part No  9840502 Revised December 1  2000    SECTION 14 0   START UP REQUEST FORM    
68. t up  and service of this equipment pose hazards due to automatic equipment  operation  high system pressure  and electrical power service  It is extremely important to consider all  aspects of safety when working on or around machinery and high voltage  This equipment will be  connected to a high voltage and or current power supply which can seriously injure or kill a worker   There is moving equipment which can start automatically and cause serious injury  It is imperative that  only qualified service personnel install and service this equipment     This equipment is designed for use with and contains R 22 hydrochlorofluorocarbon  HCFC    R 717 ammonia or other types of refrigerant  This equipment shall be serviced and disposed  of in accordance with the current Ozone Depleting Substance Regulation   Clean Environment  Act     When working on this equipment  observe precautions identified in the literature provided  any tags   stickers  and labels attached to the equipment  and any other safety precautions that apply     A Follow all applicable safety codes   A Wear safety glasses and work gloves     A Use care in handling  rigging  and setting bulky equipment     MaximICE TES ORE 25 100 Owner   s Manual 1 Effective September 1  1998  Part No  9840502 Revised December 1  2000    SECTION 2 0   THERMAL STORAGE SYSTEM   SYSTEM OVERVIEW    2 0 Thermal Storage System   System Overview    It is very important that each component be properly sized and selected  Extreme care must b
69. the calcium and magnesium ions with sodium ions  This  in  itself  is fine  However  these resins do not sufficiently reduce high concentrations of chloride or sulfate  ions  To accomplish the latter  another type of ion exchange resin must be used  Resins that remove  calcium and magnesium ions are typically regenerated with a strong brine solution  and the excess  sodium chloride is flushed out as waste water  This must be followed by thoroughly flushing the  regenerated resin bed with water  Otherwise  an excess of chloride ions will be flushed into the so called  good quality water  Glycol manufacturers recommend using de mineralized water that has been distilled   de ionized  or passed through a reverse osmosis  RO  process to remove certain minerals and salts     Good water quality is typically defined by the following parameters     Less than 50 ppm of calcium   Less than 50 ppm of magnesium   Less than 100 ppm  or 6 grains  of total hardness  Less than 25 ppm of chloride   Less than 25 ppm of sulfate       gt    gt  gt    gt    gt       After combining the proper amounts of water and inhibited glycol  the system should be mixed for a  minimum of four hours to achieve uniformity  This can be accomplished with the MaximICE feed and  solution pumps or with the cooling load pump  Solution concentration should be verified using a  refractometer to measure Refractive Index  RD     MaximICE TES ORE 25 100 Owner   s Manual 8 Effective September 1  1998  Part No  9840502 Revis
70. these parts  need to be replaced or if they are in specification  Then they can be reinstalled in the  evaporator and returned to service     MaximICE TES ORE 25 100 Owner   s Manual 23 Effective September 1  1998  Part No  9840502 Revised December 1  2000    A Drive Plate       With the drive plate removed and placed on a flat surface  check all the holes and make sure the  holes in the drive plate are round and not elongated  If there are any holes that are out of round     please refer to the tolerance chart to see if the drive plate can be reinstalled or if it needs to be  replaced     Figure 8   Drive Plate Inspection Criteria    3 4    HOLE DRIVE PLATE    REPLACE IF GROOVE DEPTH  IS EQUAL OR GREATER  THAN  080   2mm        CHECK SCREW  TIGHTNESS       REPLACE IF HOLE DIAMETER  OR MAJOR    DIAMETER IF HOLE IS ELLIPTICALLY SHAPED  IS EQUAL  OR GREATER THAN 7 8   22mm     MaximICE TES ORE 25 100 Owner   s Manual 24 Effective September 1  1998  Part No  9840502 Revised December 1  2000    Figure 9   Drive Plate Inspection Criteria    5 8    HOLE DRIVE PLATE    REPLACE IF GROOVE DEPTH  IS EQUAL OR GREATER  THAN  080   2mm        CHECK SCREW  TIGHTNESS    REPLACE IF HOLE DIAMETER  OR MAJOR  DIAMETER IF HOLE IS ELLIPTICALLY SHAPED  IS EQUAL  OR GREATER THAN 3 4   19mm     MaximICE TES ORE 25 100 Owner   s Manual 25 Effective September 1  1998  Part No  9840502 Revised December 1  2000    Figure 10   Countercrank Inspection Criteria    REPLACE IF THRUST  SURFACE IS WORN  060  1
71. to condenser type and  equipment layout  Final charging will be necessary once the system is under a stable operating  condition     Approximate refrigerant charge s      ORE 25   400 lbs  180 kg   ORE 50   700 Ibs  320 kg   ORE 100   1 000 lbs  450 kg     Locate the 5 3  flare fitting on the ORE evaporator  Only this fitting can be used to charge the system  with liquid refrigerant  Add refrigerant to bring the pressure up  and equalize prior to starting   Continue to add refrigerant until a 10  liquid level is reached in the high pressure receiver during  normal operation     The air evaporative condenser package is equipped with a fan cycling head pressure control system   which maintains a minimum compressor discharge pressure during low ambient conditions  175  psig 1 200 kPa      MaximICE TES ORE 25 100 Owner   s Manual 18 Effective September 1  1998  Part No  9840502 Revised December 1  2000    SECTION 6 0   SEQUENCE OF CONTROL    6 0 Sequence of Control    The operation of the MaximICE unit is controlled by a Programmable Logic Controller  PLC   a very  reliable  continuous duty  automatic control device  By observing LED input output lights  the  operational status can be determined  serving as a useful tool during troubleshooting  It is  recommended to study the system wiring diagram while matching the proper input output LED lights  with each function  Exhaust all other possible failure causes before assuming a PLC control  malfunction  It is highly unlikely that t
72. unit wil start upon contact closure     Load Pump Operation   Provide normally open dry contacts for monitoring of pump  operation  either auxiliary contacts or from EMS  Contacts close upon pump start     Solution Pump Operation   Provide normaliy open dry contacts for monitoring of  pump operation  either auxiliary contacts or from EMS   Contacts close upon pump start     SINGLE PHASE    ORE 50  TYPICAL WIRING Condensing Unit Pumpdown Low Pressure Switch   Provide normally closed dry contacts   SCHEMATIC Contacts open when suction pressure drops to 3 psig  condensing unit shuts down     Condensing Unit Alarm 1  Provide normally closed dry contacis  Contacts open  upon condensing unit alarm condition  condensing unit shuts down       Dual compressor condensing  unit wiring shown  See unit  wiring dagram for single  compressor condensing unit  and optional items     Condensing Unit Alarm 2  Provide normally closed dry contacts  Contacts open  upon condensing uni alarm condition  condensing unit shuts down   OPTIONAL     Remote temperature switch   Wired to remote ice level inventory sensor  Conacts close on full ice condition  predetermined temperature setting    OPTIONAL            _  Condensing Unit Start 1   24VAC contacts close to start condensing uni    7 Compressor Unloading  Step 1  Z4VAC contacts close to unload compressor    7 Condensing Unit Start 2   24VAC contacts close to start condensing unit  OPTIONAL     Remote Alarm   Dry contacts close upon alarm condition f
73. washers   i no  Replace bearings and mechanical seal as necessary  Make  Are motor bearings worn out               3 gt   sure motor drainage holes at motor bottom flange aren t    plugged  Do not run cold solution in unit when drive off     no    Is bearing sleeve worn out or  loose  yes                                                    Remove drive assembly and  replace damaged drive plate                                                                                   For ORE 50 and  100 models  manufactured before 11 1 99  an  improved mounting plate is available                                Replace bearing sleeve  Also  replace  I housing bearing  if plastic on 100  amp  50     with stainless steel version                 MaximICE TES ORE 25 100 Owner   s Manual Effective September 1  1998    Part No  9840502 41 Revised December 1  2000    10 10          Low Compressor Oil Pressure                     Is an oil level visible in the  compressor crankcase sight glass          yes       Is compressor oil pressure low              y ro       Is the compressor rotation correct     Troubleshooting Chart 10  Compressor Fails on Low Oil Pressure                         Add oil to compressor at suction   gt   service valve until level reaches  no middle of sight glass   a Replace oil pump   yes  Change compressor motor  no rotation          yes       Is the oil return solenoid valve  faulty or damaged             yes       Is the oil hand expansion valve  adjusted incorrectly
74. y the manufacturer of the component  Transportation and inspection cost incurred by the  Company will be charged to the purchaser user if returned material is not found to be defective  The above will constitute the  Companys total responsibility  The above warranties will not apply in the event of abuse  negligence  improper installation procedures   alterations by unauthorized service  damage by flood  fire  windstorm  lightning  or acts of God  Oral statements made by employees or  representatives of the Company  will not constitute warranties  The above warranties apply only to the original purchaser user and  original installation location and are not transferable     NOZIONI SIN  J    THERMAL STORAGE PRODUCTS    Paul Mueller Company  P O  Box 828   Springfield  Missouri 65801 0828  U S A   Telephone   417  831 3000 e Facsimile   417  862 9008    MaximICE TES ORE 25 100 Owner   s Manual 61 Effective September 1  1998  Part No  9840502 Revised December 1  2000    NOTES                                                                                           MaximICE TES ORE 25 100 Owner s Manual 62 Effective September 1  1998  Part No  9840502 Revised December 1  2000    MUELLER    P O  Box 828 e Springfield  Missouri 65801 0828  U S A   Phone   417  831 3000    1 800 MUELLER e Fax   417  862 9008    www muel com e E mail  thermal muel com    International Inquiries  Fax   417  831 6906   E mail  international muel com  12 00  Part No  9840502    
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Manuel centrale d`alarme SC9000 Marmitek - Maison  JVC Everio GZ-MG70U User's Manual  Kompernass KH 4300 User's Manual  Lexmark XS862de 4 12/16/2011  HDL KNX / EIB – BUS Panel controller  table of contents  Temperature and Relative Humidity E-9  LaserPAD™ PC    PTM-BEM8 簡単ガイド    Copyright © All rights reserved. 
   Failed to retrieve file