Home
        for your safety for your safety important caution warning
         Contents
1.                                                                                                                                                           36 67 29 36 48 08 J Over Roof      12 67     N  Vent Dia     2 200 200      4     Outlet Air     I B        E L  E    Duct   1    RRN  Connection i 19 28    E   F  Height                  H           Inside       G  INSIDE  24 00 P   X i     Inside    K     Width              Inside      I usi aaaamananan      L                     o  7 65 10 26               921  i      5223 529   Eun                  5 29  B r  8  n 24 00  34 27 Min  approx   Qty  4  Drill Locator Dimples for  Inside      435 1 3 00  Field Drilled Electrical Conduit Return Air Duct Connection 150 L  Entry Holes  spaced 2 0  apart   116 98                   Table 42 1   IBG ICG Indoor Gravity Vented Unit Dimensions  All dimensions in inches     Blower Type  Qty  of Dimensions   Digit 16   Furnaces G H    75 All 1 2  100 125 All 1 2  150 175 All 1 2  200 225 All 1 2 1 3 4  250 300   E  F      or H 3 4  350 400   E  F  G  orH 3 4  500 600 Gor H 3 4  700 800 GorH 3 4                                                                                  For Right Hand Access Units   Drill Locator Dimples for Field Drilled Electrical Conduit Entry Holes  spaced 2 0  apart      For Left Hand Access Units   Drill Locator Dimples for Field Drilled Electrical Conduit Entry Holes  spaced 2 0  apart     42 AIR 5 565 2    DIMENSIONS   UNIT    Figure 43 1   IBG Indoor Gravity
2.                                                       Lf                                                                9  MIN     9 EU STEEL ANGLE    VENT TERMINATION  SUPPORT BRACKET   WHERE REQUIRED                                      TEE WITH DRIP LEG  AND CLEANOUT CAP 2    UNIT INSTALLATION    Gas Connections    A WARNING       1  All field gas piping must be pressure leak tested prior to  operation  Never use an open flame  Use a soap solution or  equivalent for testing    2  Gas pressure to appliance controls must never exceed 14   W C   1 2 psi     3  To reduce the opportunity for condensation  the minimum  Sea level input to the appliance  as indicated on the serial  plate  must not be less than 5  below the rated input  or 5   below the minimum rated input of dual rated units        CAUTION    Purging of air from gas supply line should be performed as  described in ANSI Z223 1   latest edition  National Fuel Gas  Code   or in Canada in CAN CGA B149 codes                   IMPORTANT       To prevent premature heat exchanger failure  the input to the  appliance  as indicated on the serial plate  must not exceed  the rated input by more than 5            1  Installation of piping must conform with local building codes   or in the absence of local codes  with the National Fuel Gas  Code  ANSI Z223 1  NFPA 54    Latest Edition  In Canada   installation must be in accordance with CAN CGA B149 1 for  natural gas units and CAN CGA B149 2 for propane units     2  Piping to 
3.                    Total static pressure should include external static pressure and accessory   option static pressure from Tab             been included in the unit performance tables     Brake Horsepower and RPM values are approximate values only  Please consult the AccuSpec selection software for values at other than listed  CFM   static pressures                          AIR 5 565 2                            e 32 1  Unit internal resistance has    33    BLOWER PERFORMANCE DATA    Table 34 1   Unit Performance Tables         Total Static Pressure     030   975 10   1285   150   20   250   300             RPM            RPM   BHP   RPM   BHP   RPM            RPM   BHP   RPM   BHP   RPM   BHP   RPM          Start 300         83  F   100  F  74  F   89  F  62  F   74  F  53  F   63  F  46  F 7 56  F  41  F   49  F  37  F   44  F  34  F  40  F   Sao     9    83  F   100  F   2222   0 28   424   0 43 1123   2 67  74  F   89  F  62  F   74  F  53  F   63  F  46  F   56  F  41  F   49  F  37  F   44  F  34  F   40  F  31  F   37  F  28  F   34  F   I  J  K  46  F   56  F  37  F   44  F  31  F   37  F  26  F   32  F  23  F   28  F  20  F   24  F                                                                      100          96  F                 74  F   85  F  65  F   74  F  58  F   66  F  52  F   59  F             350 400   G H 100 F       Start 400          87       100 F  74  F   85  F  65  F   74  F  58  F 7 66  F  52  F   59  F  47  F   54  F  43  F   49  F  40  F   46  F
4.             2  Low Gas Pressure Switch      OPT    The low gas pressure switch is factory installed in the duct  furnace above the gas train  The switch monitors the gas  pressure upstream of all the gas controls and shuts off the  electric supply to the ignition controller and combination gas  valve if low gas pressure is experienced  This will shut off all  gas flow to the burner  The switch has an automatic reset so  that if the gas pressure is interrupted and then is returned  the  Switch will automatically allow the unit to operate when gas  conditions are returned to the allowable range of the pressure  Switch  The pressure switch range is 2  to 14  W C  and should  be set to insure that the minimum inlet gas pressure is available   6  W C  for natural gas  11  W C  for propane gas       3  High Gas Pressure Switch      OPT    The high gas pressure switch is factory installed in the duct  furnace above the gas train  The switch monitors the gas  pressure downstream of all the gas controls and shuts off   the electric supply to the ignition controller and combination  gas valve if high gas pressure is experienced right before the  manifold  This will shut off all gas flow to the burner  The switch  has a manual reset so that if the gas pressure is too high  a  Service person must check the unit to make sure that none of    Figure 20 3   Low or High Gas Pressure Switch                the gas controls have been damaged by the high gas pressure  and then reset the switch to
5.        E                                 A  A          mk   oa       Qty  2  BX82  Qty  2  BX82  Qty  2  B86  Qty  2  B86  B71  BX74  Qty  2  BX79  Qty  2  BX79  Qty  2  B83  Qty  2  B83   B77    E                 N                         3H36622                                  oj  o    o  mi        3H35128          Qty                                                                NIN             SIUS ov olo t          AIR 5 565 2 39    ELECTRICAL DATA   MOTOR DATA    Total Unit Amp Draw    The total unit amp draw is a combination of the motor  the control step down transformer  and the power exhauster amp draw  The  control step down transformer includes damper actuators  ignition controllers  gas valves  control relays  amplifiers  and motor starters     Unit Amp Draw  Table 40 1   Motor Amp Draw  Tables 40 2 to 41 2     H    ll    Total Amp Draw  Table 40 1   Unit Amps    ah mor mpi Draw Power Exhauster Amp Draw  Supply Voltage Digit 15   Transformer Model Size  did I 00 1 2 4 75 175   200 400   500 800   840 960    3            A 115 60 1 1 3 1 4 2 4 4 8 7 2          208 60 1 0 72 i    1 4          Unit controls amp draw is included in master unit amp draw   230 60 1 0 65   1 8   Requires a 250 VA transformer   208 60 3 0 72      1 4      G Requires a 500 VA transformer   230 60 3 0 65   1 3 i i   Requires a 750 VA transformer     Requires a 1000 VA transformer   460 60 3    0 33 0 30      0 65      For Digits F  460V  and G  575V   amp draw shown is on  575 60 3   0 2
6.      NOTE  For units equipped with two stage or modulating gas  controls  only the high fire manifold pressure needs to be  adjusted  No adjustments to the low fire manifold pressure are  necessary on these units     Selection of the Proper High Altitude Kit    All units installed at elevations greater than 2000 feet above sea  level require a kit  in addition to potential manifold pressure  adjustment outlined in the previous step  To determine the proper  kit to use  refer to Table 10 2     Table 10 3 shows the contents of the kit  For more information   refer to the latest revision of Modine Bulletin 75 530     Table 10 2   High Altitude Kit Selection Table           Model Elevation Above Sea Level  ft   Size 2 001 5 500   5 501 6 500   6 501 7 500   IBG  Item       67248 67248  75 350 Item  500 700 Code 67248 67248 67248  IBP    840  ICP   400  goo   Hem 67248 68409 68411  Code  960    Applies to both installations in the U S  and Canada     Applies to both natural and propane gas     Sizes 75 400 require a kit qty  of 1  sizes 500 800 require a kit qty of 2   sizes 840 960 require a kit qty of 3   Table 10 3   High Altitude Kit Contents  Kit Contents    Pressure  Switch          High Altitude  Conversion Label    Installation  Instructions          If a unit is to be installed at higher elevations AND converted from  natural gas to propane gas operation  a propane conversion kit  must be used in conjunction with the manifold pressure  adjustment and high altitude kit lis
7.      ODP  1         5     TE  5   ODP  1    ODP  1   TE  5           5   ODP  1  d ODP  1   TE  5           5   ODP HE  2  d ODP HE  2   TE HE  6    TE HE  6   ODP HE  2  f ODP HE  2   TE HE  6    TE HE  6   ODP HE  2  ODP HE  2   TE HE  6  TE HE  6   ODP HE  2  ODP HE  2   TE HE  6  TE HE  6   ODP HE  2  ODP HE  2   TE HE  6  TE HE  6   ODP HE  2  ODP HE  2   TE HE  6  TE HE  6   ODP HE  2  ODP HE  2   TE HE  6  TE HE  6   ODP HE  2  ODP HE  2   TE HE  6  TE HE  6   ODP HE  2  ODP HE  2   TE HE  6  TE HE  6   ODP  1  k ODP  1   TE  5  j TE  5   ODP  1     ODP  1         5  f TE  5   ODP  1    ODP  1   TE  5          5   ODP HE  2    ODP HE  2   TE HE  6  d TE HE  6   ODP HE  2     ODP HE  2   TE HE  6  f   TE HE  6   ODP HE  2  ODP HE  2   TE HE  6  TE HE  6   ODP HE  2  ODP HE  2   TE HE  6  TE HE  6   ODP HE  2  ODP HE  2   TE HE  6  TE HE  6   ODP HE  2  ODP HE  2   TE HE  6  TE HE  6   ODP HE  2  ODP HE  2   TE HE  6  TE HE  6   ODP HE  2  ODP HE  2   TE HE  6  TE HE  6   ODP HE  2  ODP HE  2   TE HE  6  TE HE  6                                                                                      208V 60Hz 3ph  D   460V 60Hz 3ph  F                                                                                                                                   230V 60Hz 3ph  E   575V 60Hz 3ph  G                                                                                    Motors rated 1hp and larger are inverter duty rated as standard     Three phase motors do not ha
8.     LJ K   100  F    1 66  Start 400   1 81  65  F   74  F  52  F   59  F  43  F   49  F  37  F   42  F  32  F   37  F  29  F   33  F  26  F   30  F  24  F   27  F   23  F   26  F 12 09  14 34                                                                                                         Total static pressure should include external static pressure and accessory   option static pressure from Table 32 1  Unit internal resistance has been    included in the unit performance tables     Brake Horsepower and RPM values are approximate values only  Please consult the AccuSpec selection software for values at other than listed    CFM   static pressures     34 AIR 5 565 2    BLOWER PERFORMANCE DATA    Table 35 1   Unit Performance Tables         Total Static Pressure Inches  W C       025   oso   075   100   125   150   200   250   300    Cru  EE RPA SPP                             BHEISEM BHPIREM EHEIEEM EHE eat PIP eM    500 600 120  F     06  F     Start 600 100  F   120  F  93  F   111  F  82  F 7 99  F  74  F   89  F  67  F   81  F  62  F   74  F  57  F 1 68  F    500 600 120  F        Start 600 100  F   120 F H  93  F   111 F E  74  F   89  F    62  F   74  F 2  53  F   63  F    46  F   56  F    End 500 41  F   49  F 3    1 44  F 10000   9 62   975      43  F 10 77   1011     40  F 12 66   1065      40  F 13 04  1075                                                       500 600 62  F   74  F   53  F   63  F   46  F   56  F   41  F   49  F     44  F  10000   7 04   793  
9.     Morrison etc   etc  um  SERIES IDENTITY    NUMBER WEEK OF  Identifies which series MANUFACTURE  of controls were 01     1st week of year  furnished on the unit    26     26th week of year                   AIR 5 565 2    55    START UP CHECKLIST    INDIRECT GAS FIRED HEATING EQUIPMENT  Job Name  Date   Address  Model No    City  amp  State  Order No    Start Up Check List  ALL ITEMS MUST BE CHECKED  Serial No        All shipping straps  braces  tie downs removed     Unit installed level and secure     Gas burner properly located and aligned     Blower and motor alignment okay     Bearings aligned and tight on shaft bearing supports     Electrical connections checked and secure     Gas piping checked and tightened if necessary     Any visible damage to unit   Describe   If damaged  was the damage repaired     Air inlet and discharge checked for obstructions     Bearings checked for proper lubrication     Filters in place and correct to direction of air flow     Belt tension checked     Electric supply to unit  Volts  Hz  Phase    Gas supply to unit  _ Natural  _ Propane    Gas supply pressure to unit       W C   PSIG    Inlet and or discharge dampers operating correctly     Blower rotation correct     Blower speed  Hi Speed  RPM  Lo Speed RPM    Motor speed  Hi Speed    RPM  Lo Speed RPM    Is unit noisy  Excessive vibration     Motor voltage  L1          V  L2 V  L3 V    Motor amps  L1 _Amp L2_    Ampl3   Amp    High temperature limit control continuity checked     Burner
10.    Max  Temp  Rise    F     100    100 100 100    100 100       Min  Temp  Rise    F     27    20 33 20    39 23       Max  CFM    3450    4630 3350 5556    3350 5556       Min  CFM       Model Size  Digits 4 6           Btu Hr Input       200 000             926    225 000          926 1111 1111    250 000          1296 1296       Btu Hr Output       160 000    180 000    200 000       Blower Style  Digit 16 Letter     EorF    EorF    GorH       Max  Temp  Rise    F   Min  Temp  Rise    F     85    95    100       Max  CFM       Min  CFM       Model Size  Digits 4 6           Btu Hr Input       300 000          350 000          400 000          Btu Hr Output       240 000    280 000    320 000       Blower Style  Digit 16 Letter     GorH    GorH    GorH       Max  Temp  Rise    F     100    100    100       Min  Temp  Rise    F   Max  CFM    31    37    42  12000 5700       Min               Model Size  Digits 4 6           Btu Hr Input       500 000          600 000          2593 2963    700 000          Btu Hr Output       400 000    480 000    560 000       Blower Style  Digit 16 Letter     I  J  or K    l  J  or K    I  J  or K       Max  Temp  Rise    F     120    120    120       Min  Temp  Rise    F     40    40    40       Max  CFM       Min  CFM 2    Model Size  Digits 4 6   Btu Hr Input          800 000          1 050 000          1 200 000       Btu Hr Output       640 000    840 000    960 000       Blower Style  Digit 16 Letter     I  J  orK    I  J  or K    I  
11.   36 68                                                      G  30 5  HEIGHT      24 00 43 23  E  WIDTH   921  765 5 20 529    P             3 00    BOTTOM DRILL LOCATOR  QTY  4  DRILL LOCATOR DIMPLES FOR DIMPLES FOR FIELD DRILLED    FIELD DRILLED ELECTRICAL CONDUIT  ENTRY HOLES  SPACED 2 0  APART  HOLES  SPACED 2 0 APART        ONLY ON ACCESS SIDE              Table 45 1   IBP ICP Indoor Power Vented Unit Dimensions with Blower Type l  J  K  or L   All dimensions in inches     Blower Type Qty  of Dimensions   Digit 16    Furnaces L N    250 300 I  J  or K 123 35  350 400 l  J  or K 123 35             500 600   I  J  K  or L 156 76  700 800   1  J  K  or L 156 76  840 960      J  K  or L 185 99                                              Applies to units with Digit 16   L only     AIR 5 565 2 45    DIMENSIONS   BASE    Figure 46 1   Unit Base Dimensions          C To end of unit           nH            gt         gt  0 63       5       0 75  Suspension  Hanging Locations   Typical 4 Corners             E Inside    Suspension    Doint 24 00 Inside    a Lifting  Liftin i         Doint             Return Air  gt  bt  Opening 145 la             N                Table 46 1   Indoor Power Vented Blower Package Units  All dimensions in inches     Dimensions    Blower Type    Digit 16  E N  75 All  100 125 All  150 175 All  200 225 All   250 300 E F G  or H                      250 300 I  J  or K  350 400 E F G  or H  350 400 I  J  or K  500 600 G  or H  500 600 1  J  K  or L  700 8
12.   43  F   10400   7 88 ES  288 11000   9 27    700 800 GorH 120  F      115  F     Start 800 105  F   120  F  104  F   119  F  94  F   108  F  86  F   99  F  80  F   91  F    700 800 120  F         657   2 04  Start 800 104  F   119 F    86       99       731  65  F   74  F      845 6  30   888  58  F   66  F       i                  Start 500                                           52  F   59  F  47  F 1 54  F  43  F   49  F  40  F   46  F                                  120  F       111  F     105  F   120  F  97  F   111  F  86  F   99  F  78  F   89  F  70  F   80  F  65  F   74  F  62  F   71  F  60  F   68  F    840 960          End 840                         840 960                   End 840          700 800 65  F   74  F       i  58  F   66                         52  F   59  F      j 7       B    47  F   54  F      I                47  F   54  F j j i    i   i       43  F   49  F       End 700 40   I           1 10          E    41   E 14500 n 02   968 D A 994 x 21   1019  T 82   1045      Total static pressure should include external static pressure and accessory   option static pressure from Table 32 1  Unit internal resistance has been included in the unit  performance tables       Brake Horsepower and RPM values are approximate values only  Please consult the AccuSpec selection software for values at other than listed CFM   static pressures     AIR 5 565 2 35    BLOWER SHEAVE ASSEMBLY DATA    Adjusting the Blower Drive Setting       Based on the Sheave Arrang
13.   Inside  7 65 21  kus   L    34 27 Min  approx      Return Air  Inside  4 35          Qty  4  Drill Locator Dimples for Duct Connection  Field Drilled Electrical Conduit  Entry Holes  spaced 2 0  apart     152 84                      Table 43 1   IBG ICG Indoor Gravity Vented Unit Dimensions with Blower Type I  J  K  or L   All dimensions in inches     Blower Type   Qty  of Dimensions   Digit 16    Furnaces L N       250 300 I J  or K 27 13   30 00 123 35  350 400 I J  or K 38 63   42 00 123 35  500 600   I  J  K  or L 156 76  700 800   1  J  K  or L 156 76  840 960   I  J  K  or L 185 99                                                      For Right Hand Access Units   Drill Locator Dimples for Field Drilled Electrical Conduit Entry Holes  spaced 2 0  apart     For Left Hand Access Units   Drill Locator Dimples for Field Drilled Electrical Conduit Entry Holes  spaced 2 0  apart     Applies to units with Digit 16   L only     AIR 5 565 2    DIMENSIONS   UNIT    Figure 44 1   IBP Indoor Power Vented Blower Package Unit Dimensions           J  OVER ROOF             30 07                 6  VENT I  CONNECTOR  23 07  HEIGHT   x 43 23    C WIDTH  17 40            H   pese  QTY  4  DRILL LOCATOR DIMPLES FOR   BOTTOM DRILL LOCATOR  FIELD DRILLED ELECTRICAL CONDUIT DIMPLES FOR FIELD DRILLED  ENTRY HOLES  SPACED 2 0  APART  ELECTRICAL CONDUIT ENTRY  HOLES  SPACED 2 0  APART   120 90  ONLY ON ACCESS SIDE     500   800 Model Shown       9 21          3 00                         Figure
14.   It is important that  all grease  oil  flux and sealing compounds present from the  installation be removed     Figure 13 1   General Chilled Fluid Piping           Air Vent     ees                         Vent Plug  Gate Valve      Te   e   gt                a             Drain Plug  Dirt Leg     Union  Cap              Table 13 1   Cooling Coil Performance Limits    Single Circuit   Dual Circuit Max    Cooling       Max   Area Max Area               ft                 ft2   Tons                                                  Chilled  Water                                       Based on 550 feet per minute  FPM  coil face velocity      Based on 95  F 75  F Entering Dry Bulb Wet Bulb      Model Size 75 minimum CFM for DX Dual Circuit is 621     Model Size 100 minimum CFM for DX Dual Circuit is 745     AIR 5 565 2 13    START UP PROCEDURE  Start Up Procedure    IMPORTANT    1  To prevent premature heat exchanger failure  observe heat  exchanger tubes by looking at the heat exchanger through  the field installed access openings in connecting ductwork  in blower package units or the unit access doors in  cooling package units  If the bottom of the tubes become  red while blower and duct furnace are in operation  check  to be sure the blower has been set to the proper rpm for  the application  Refer to page 16 for Blower Adjustments     2  Start up and adjustment procedures should be performed  by a qualified service agency           1  Turn off power to the unit at the disco
15.   Main gas is off   Power supply is off   Air in gas line    Dirt in pilot orifice     Gas pressure out of proper range     Pilot valve does not open    a  Defective ignition controller   b  Defective gas valve    No spark at ignitor    a  Loose wire connections    b  Pilot sensor is grounded    c  Defective ignition controller   Safety device has cut power     Excessive drafts     Pilot orifice fitting leak     Defective valve    Loose wiring    Defective pilot sensor   Defective ignition controller   Improper thermostat wiring     Blocked vent safety switch tripped     Too much primary air   Main pressure set too high   Orifice too large     Insufficient primary air   Dirty orifice     Misaligned orifice       Too much primary air     Main pressure set too high   Orifice too large     Insufficient primary air   Main pressure set too high   Orifice too large     Blocked vent     Main pressure set too high   Orifice too large     Blocked vent     AIR 5 565 2       Bowl    10                     N                Open manual gas valve    Turn on main power    Purge gas line    Check for plugged pilot orifice and clean  with compressed air if necessary   Adjust to a maximum of 14  W C   Minimum for Natural Gas   6  W C   Minimum for Propane Gas   11  W C   Check wiring for 24 volts to valve    a  Replace ignition controller    b  Replace gas valve    a  Check all ignition controller wiring   b  Replace sensor if cracked or worn   c  Replace ignition controller     Check all safe
16.   RA Mod motor w  0 10 Vdc External Input   GB   FA  amp  RA Mod motor w  4 20 mA External Input   GC   FA  amp  RA Mod motor w  Minimum Position   GD   FA  amp  RA Mod motor w  Remote Position  On Remote Panel   GE   FA amp  RA Mod motor w  3 pos  damper  10096 RA  Variable  10096 OA   GG   FA  amp  RA Mod motor w  Minimum Position  amp  Prop  Temp Controller  GH         amp  RA Mod motor w  Remote Position  amp  Prop  Temp Controller  GJ         amp  RA Mod motor w  FA Enthalpy Controller         ASHRAE Cycle II     GG  with Warm up Stat    GM  ASHRAE Cycle II               with Warm up Stat    HP         amp       Floating motor w  Space Pressure Controller   JA  Manual FA  amp  RA Dampers    22  Evaporative Cooling  EC   0  None    23  Cooling Coil  CC   0   None  1   Factory Installed Coil    AIR 5 565 2 57    58    THIS PAGE INTENTIONALLY LEFT BLANK    AIR 5 565 2    THIS PAGE INTENTIONALLY LEFT BLANK    AIR 5 565 2    59    COMMERCIAL WARRANTY    Seller warrants its products to be free from defects in material and  workmanship  EXCLUSIVE  HOWEVER  of failures attributable to the use   of materials substituted under emergency conditions for materials normally  employed  This warranty covers replacement of any parts furnished from the  factory of Seller  but does not cover labor of any kind and materials not  furnished by Seller  or any charges for any such labor or materials  whether  such labor  materials or charges thereon are due to replacement of parts   adjustments
17.   SECTION    DUCT  FURNACE    DISCONNECT  SWITCH WIRING   AND CONNECTOR    a    ELECTRIC SUPPLY BLOWER  COMPONENTS MUST BE SECTION  CLEAR OF SERVICE DOORS DOOR             6  The power supply must be within 5  of the voltage rating  and each phase must be balanced within 2 percent of each  other  If not  advise the utility company    7  External electrical service connections that must be installed  include    a  Supply power connection  120  208  240  480  or 600  volts     b  Connection of thermostats  remote monitoring panels   building pressure sensors  CO detectors  time clocks  or  any other accessory control devices that may be supplied   24 volts     8  Refer to the unit dimensional drawings on pages 42 45 for  the electrical entry locations    9  All supply power electrical connections are made in the  electrical section of the unit  The low voltage  thermostat  and accessory control devices  can be wired to either the  electrical section or the duct furnace electrical junction box   Refer to the wiring diagram for the terminal location of all low  voltage wiring     AIR 5 565 2 11    UNIT INSTALLATION    Cooling Coil Units    Models with a cooling section can be provided with either a  factory installed direct expansion  DX  evaporator  a chilled  fluid  for use with water  ethylene glycol  or propylene glycol  fluids  coil  or the coil can be field supplied and installed by  others  For units equipped with a factory installed cooling coil   Digit 23   1   refer to 
18.   approved service replacement parts  A complete replacement  parts list may be obtained by contacting Modine Manufacturing  Company  Refer to the rating plate on the appliance for  complete appliance model number  serial number  and  company address  Any substitution of parts or controls not  approved by the factory will be at the owners risk                       CAUTION    1  Purging of air from gas supply line should be performed  as described in ANSI Z223 1   latest edition    National Fuel  Gas Code     or in Canada in CAN CGA B149 codes     2  Do not attempt to reuse any mechanical or electronic ignition  controllers which has been wet  Replace defective controller     3  Ensure that the supply voltage to the appliance  as indicated  on the serial plate  is not 5  less than the rated voltage     IMPORTANT    1  To prevent premature heat exchanger failure  do not  locate ANY gas fired appliances in areas where corrosive  vapors  i e  chlorinated  halogenated or acid  are present  in the atmosphere     2  To prevent premature heat exchanger failure  the input to  the appliance  as indicated on the serial plate  must not  exceed the rated input by more than 5     3  To prevent premature heat exchanger failure  observe  heat exchanger tubes by looking at the heat exchanger  through the field installed access openings in connecting  ductwork in cooling package units or the unit access doors  in blower package units  If the bottom of the tubes become  red while blower and du
19.   condition should be observed periodically to assure trouble free  operation     To Adjust the Pilot Flame  1  Create a call for heat from the thermostat     2  Remove the cap from the pilot adjustment screw  For location   see the combination gas control literature supplied with unit   3  Adjust the pilot length by turning the screw in or out  to achieve a soft steady flame 3 4  to 1  long and  encompassing 3 8  1 2  of the tip of the thermocouple or  flame sensing rod  See Figure 14 1      4  Replace the cap from the pilot adjustment screw   Figure 14 1   Correct Pilot Flame       P 3 4  to 1     ae JU  i                                                                                     14 AIR 5 565 2    START UP PROCEDURE    Main Burner Adjustment    The gas pressure regulator  integral to the combination gas  control  is adjusted at the factory for average gas conditions    It is important that gas be supplied to the duct furnace in  accordance with the input rating on the serial plate  Actual  input should be checked and necessary adjustments made  after the duct furnace is installed  Over firing  a result of too  high an input  reduces the life of the appliance and increases  maintenance  Under no circumstances should the input exceed  that shown on the serial plate     Measuring the manifold pressure is done at the tee in the  manifold or at the pressure tap of the gas valve for standard gas  string   See Figure 15 1      To Adjust the Manifold Pressure    1  Move th
20.   repairs  or any other work done  This warranty does not apply to  any equipment which shall have been repaired or altered outside the factory of  Seller in any way so as  in the judgment of Seller  to affect its stability  nor  which has been subjected to misuse  negligence  or operating conditions in  excess of those for which such equipment was designed  This warranty does  not cover the effects of physical or chemical properties of water or steam or  other liquids or gases used in the equipment     BUYER AGREES THAT SELLER S WARRANTY OF ITS PRODUCTS TO BE  FREE FROM DEFECT IN MATERIAL AND WORKMANSHIP  AS LIMITED  HEREIN  SHALL BE IN LIEU OF AND EXCLUSIVE OF ALL OTHER  WARRANTIES  EITHER EXPRESS OR IMPLIED  WHETHER ARISING  FROM LAW  COURSE OF DEALING  USAGE OF TRADE  OR OTHERWISE   THERE ARE NO OTHER WARRANTIES  INCLUDING WARRANTY OF  MERCHANTABILITY OR FITNESS FOR PURPOSE  WHICH EXTEND  BEYOND THE PRODUCT DESCRIPTION CONFIRMED BY BUYER AND  SELLER AS OF THE DATE OF FINAL AGREEMENT     This warranty is void if the input to the product exceeds the rated input as  indicated on the product serial plate by more than 5  on gas fired and oil fired  units  or if the product in the judgment of SELLER has been installed in a  corrosive atmosphere  or subjected to corrosive fluids or gases  been subjected   to misuse  negligence  accident  excessive thermal shock  excessive humidity   physical damage  impact  abrasion  unauthorized alterations  or operation  contrary to SELLER S p
21.  1     Determine the Sheave Arrangement     To establish the Sheave Arrangement  the motor frame size  must be determined  The Motor Data tables on pages 40 41  contain the motor frame size     A  Using the Supply Voltage  460V 60Hz SPh   enter the  correct Motor Data table  Table 41 2   Using Model  Nomenclature Digits 17 and 18  G1  determined in steps  13 and 14  find the motor frame size  182T      Using the Motor Frame Size enter the Sheave Selection  table for the selected blower determined by step 13   Table 37 2   Using the rpm calculated in step 12    870 rpm   select the sheave range that contains the  required rpm  Find the intersection with the Motor  Frame Size to determine the Sheave Selection  For this  example with a 182T frame with 870 rpm  from Table  37 2  the Sheave Arrangement   1          Determine the Air Control     The Air Control option is selected based on the required  damper configuration  The available damper selections are  detailed on pages 22 23  For this selection  a 100  fresh air  unit without return air was required so the Air Control   DA     Determine the Evaporative Cooler    An evaporative cooler is not available  so for purposes of  this selection the Evaporative Cooler   0    Determine the Cooling Coil     A cooling coil cabinet was not specified so for purposes of  this selection the Cooling Coil   0     Based on the previous steps  the model number for the base  unit is the following     IBP400SMRLNAOF2GG1IDAOO    Once the basic mo
22.  1 E   230 60 8  C   230 60 1 F   460 60 8   G  575 60 3    15   Transformer  TR     1   40 VA 4   250 VA   2   75 VA 0   None   3   150 VA   16  Blower Size  amp  Bearing Type  BB    A   9 7 Spider Bearings G   15 15 Spider Bearings   B   9 7 Pillow Block Bearings H   15 15 Pillow Block Bearings   C   9 9 Spider Bearings     18 18 Spider Bearings under 15       D   9 9 Pillow Block Bearings J   18 18 Pillow Block Bearings under 15 Hp  E   12 12 Spider Bearings K   18 18 Pillow Block Bearings for 15 Hp  amp  up  F   12 12 Pillow Block Bearings L   20 18 Pillow Block Bearings   17  Motor Horsepower  HP    A   1 3 Hp L   1 3 Hp with Motor Starter   B   1 2Hp M   1 2 Hp with Motor Starter   C   3   4 Hp N   3 4 Hp with Motor Starter  D 1Hp P   1 Hp with Motor Starter   E   1 1 2 Hp Q   1 1 2 Hp with Motor Starter  F 2Hp R   2 Hp Hp with Motor Starter   G   3Hp S   3 Hp with Motor Starter   H   5Hp T   5 Hp with Motor Starter       7 1 2 Hp W  7 1 2 Hp with Motor Starter   J   10 Hp X   10 Hp with Motor Starter   K   15 Hp Y   15 Hp with Motor Starter   V   20Hp Z   20 Hp with Motor Starter    18  Motor Type  MT   1   ODP  2   ODP   High Eff     5         6          High Eff     19  Sheave Arrangement  SA   A    See Sheave Tables 34 1 to 35 5     20  21   Air Control  AC    AA  RA Opening   BA  FAOpening   CA         amp  RA Openings   DA   FA Dampers w  2 pos motor  No RA    EA  FA  amp  RA Dampers w  2 pos motor   EQ  ASHRAE Cycle         EA    with Warm up Stat    GA   FA  amp
23.  1001 978 1265 1150 1561    1526 1858 1763 2147       Size  48    Digit 19  Sheave Assembly    3H35125B1    Digit 19  Sheave Assembly    3H35125B3    Digit 19    Sheave Assembly    Digit 19 Sheave Assembly Digit 19  Sheave Assembly       56 3H35125B2 3H35125B4    3H35125B6    3H35125B8 3H35125B10                         143 or 145 3H35125B5    RPM Range    3H35125B7             3H35125B9 3H35125B11       Motor Frame 656 1001 978 1265    1150 1561    1526 1858 1763 2147       Size  48    Digit 19 Sheave Assembly    3H35126B1    Digit 19  Sheave Assembly    3H35126B3    Digit 19    Sheave Assembly    Digit 19 Sheave Assembly Digit 19  Sheave Assembly       56 3H35126B2 3H35126B4    3H35126B6    3H35126B9 3H35126B12       143 or 145  182 or 184    3H35126B5                      36    3H35126B7  3H35126B8       3H35126B10  3H35126B11    3H35126B13    K 3H35126B14             AIR 5 565 2       BLOWER SHEAVE ASSEMBLY DATA    Blower Sheave Assembly Numbers  Con t   Table 37 1   Digit 16   E or F  12 12 Blower Units     Motor Frame  Size  48    RPM Range       468 715    644 874    863 1078    1029 1332    1150 1438    1327 1659       Digit 19 Sheave Assembly    3H35127B1    Digit 19    Sheave Assembly    Digit 19  Sheave Assembly    Digit 19 Sheave Assembly    Digit 19  Sheave Assembly    Digit 19 Sheave Assembly       56    3H35127B2    3H35127B3    3H35127B6    3H35127B17       143 to 145    3H35127B4    3H35127B7    3H35127B9    3H35127B12       182 or 184    3H35127B5    3H35127
24.  2    DUCT INSTALLATION VENTING    Discharge Duct Connection  refer to Figure 5 1     1  The furnace discharge is designed to accept straight  ductwork  Provide an airtight seal between the ductwork  and the furnace to prevent leakage  Seams with cracks in  the ductwork should be caulked and or taped and be of  permanent type    2  Provide removable access panels on the downstream side  of the ductwork  This opening should be large enough to  view smoke or reflect light inside the casing to indicate leaks  in the heat exchanger and to check for hot spots on heat  exchangers due to poor air distribution or lack of sufficient  air  CFM     3  Provide uniform air distribution over the heat exchanger   Use turning vanes where required to obtain uniform air  distribution  see Figure 5 1      Figure 5 1   Recommended Field Installed Discharge  Duct Configurations       PROVIDE LEAK TIGHT ACCESS PANELS  IN SIDE OF DISCHARGE DUCT FOR  HEAT EXCHANGER INSPECTION        TURNING VANES    3  MINIMUM 3  MAXIMUM                               12  MINIMUM                    SIDE VIEW      B  4  DIMENSION      SHOULD NEVER       LESS THAN 1 2 OF DIMENSION  A      PROVIDE LEAK TIGHT ACCESS PANELS  IN SIDE OF DISCHARGE DUCT FOR  HEAT EXCHANGER INSPECTION    TURNING VANES  3  MAXIMUM          PA  3  MINIMUM                    4   12  MINIMUM                TOP VIEW             DIMENSION  B  SHOULD NEVER BE  LESS THAN 1 2 OF DIMENSION  A                  Blower Section and Cooling Cabinet Duct Con
25.  3 27   1511 3 86   1632  42    48    3500   1 66   972   1 88   1047   2 12   1119   2 36   1188   2 61 1255 2 88  1320 3 43   1455   4 03   1563      37  F 42  F 4000   2 40   1091   2 65   1157   2 91   1221   318   1284   3 46 1345 3 75  1404 4 35   1518   4 98   1628      33  F 37  F 4500   3 34   1211   3 62   1270   3 91   1329   4 21 1385   4 51 1441 4 82  1495              30  F 33  F 5000   4 52   1332   4 82   1387                              200 225   G H 85  F 95  F 1750   0 20   425   0 33   546 0 48   653                          74  F 83  F 2000   0 26   449   0 40   562 0 56   662   0 74 754                      59  F 67  F 2500   0 42   507   0 58   603 0 75   692   0 94 774 1 16 851 1 38   925              49  F 56  F 3000  0 65   571   0 83   654 1 02   732   1 23 807 1 45 877 1 69   944 2 21   1071          42  F 48  F  3500   0 97   639   1 17   713 1 38   782 1 60 850 1 84 914 2 10   975 2 64   1093   3 23   1202 3 86   1307  37     42     4000   1 38   710   1 60   776 1 83   839   2 08 899 2 34 958 2 60  1014 3 18   1123   3 80   1226 4 46   1324  33  F 37  F 4500   1 90   783   2 14   842 2 40   899   2 66 955 2 94 1008 3 23  1061 3 84   1161   4 48   1258      30     33      5000   2 54   858   2 81   911 3 08   963   3 37   1014   3 67 1064 3 98   1112 4 62   1206          27     30      5500   3 32   933   3 61   982 3 91   1030   4 22   1077   4 54 1123 4 87  1168              25  F 28  F 6000   4 25   1009   4 57   1054   4 89   1099           
26.  44 2   ICP Indoor Power Vented Cooling Package Unit Dimensions                  J              OVER ROOF                            BOTTOM DRILL LOCATOR    QTY  4  DRILL LOCATOR DIMPLES FOR  DIMPLES FOR FIELD DRILLED    FIELD DRILLED ELECTRICAL CONDUIT       ENTRY HOLES  SPACED 2 0  APART  ELECTRICAL CONDUIT ENTRY  HOLES  SPACED 2 0  APART   116 98  ONLY ON ACCESS SIDE                 Table 44 1   IBP ICP Indoor Power Vented Unit Dimensions  All dimensions in inches     Blower Type  Qty  of Dimensions   Digit 16   Furnaces G H    75 All  100 125 All  150 175 All  200 225 All  250 300   E  F  G  orH  350 400   E  F  G  orH  500 600 G or H  700 800 G or H                                                                            NIN                               44 AIR 5 565 2    DIMENSIONS   UNIT    Figure 45 1   IBP Indoor Power Vented Blower Package Unit Dimensions with Blower Type I  J  K  or L          J  OVER ROOF                                                 6  23 07  HEIGHT  24 00 4323  C  WIDTH   921  897 10 26  APPROX    9 21 5 29 5 29          5 65  APPROX     BOTTOM DRILL LOCATOR  DIMPLES FOR FIELD DRILLEI  ELECTRICAL CONDUIT ENTRY  HOLES  SPACED 2 0  APART    ONLY ON ACCESS SIDE        FIELD DRILLED ELECTRICAL CONDUIT    QTY  4  DRILL LOCATOR DIMPLES FOR  ENTRY HOLES  SPACED 2 0  APART           156 76     500   800 Model Shown          Figure 45 2   ICP Indoor Power Vented Cooling Package Unit Dimensions with Blower Type l  J  K  or L    J  OVER ROOF           
27.  622 0 56   735   0 72 837                      34  F 42  F  2200   0 43   553   0 58   662 0 75   762   0 93 855 1 12 942 1 33   1025              28  F 36  F  2600   0 63   614   0 81   710 1 00   800 1 20 885 1 41 965 1 63   1042              25  F 31  F 3000   0 91   680   1 11   766 1 32   847   1 54  1731   1 77 997 2 01   1068 2 51   1202   3 04   1328 3 60   1446  22  F 27  F 3400   1 26   748   1 48   825 1 72   899 1 96 970 2 21 1038 2 47   1104 3 01   1229   3 58   1347 4 17   1459  End 100       20     25    3704   1 58   802   1 83   873 2 08   942   2 34   1008   2 60 1072 2 88   1135 3 45   1254   4 04   1367 4 67   1474    23 F  4100   2 09   873   2 35   938 2 63   1001   2 91 1062   3 20 1122 3 49   1180 4 10   1291 4 74   1398        20  F  4630   293   969   3 23   1028   3 53   1085   3 84   1140   4 16 1194 4 48  1247              150 175   C D 1009   1179    1111   0 19   727   0 28   884 0 38   1023   0 48   1148   0 59 1262 0 70   1369 0 94   1563   1 21 1738 1 48   1899  Start 175 86     100      1296   0 27   793   0 37   937   0 47   1066   0 59   1184   0 71   1293   0 83   1395   1 09   1582   1 37   1752   1 66   1909  79  F 93  F  1400   0 32   832   0 42   970 0 54   1093   0 66   1208   0 78 1313 0 91   1412 1 18   1596   1 47   1763 1 78   1917  62  F 72  F  1800   0 59   994   0 72   1109   0 86   1216   1 00   1316   1 15 1410 1 30   1500 1 62   1667   1 95   1823 2 29   1967  51  F 59  F 2200   1 00   1166   1 16   1264   1 32   1356   1 
28.  P   is determined using  the ASHRAE Guide for duct losses  or may be provided by  the design engineer     Unit configuration with options and accessories   Filters or dampers     The unit configuration is determined by the location  where the unit is to be installed  The critical options and  accessories are those that add internal static pressure   I S P   to the unit  Once these items are determined  the  pressure drop curves would be used to calculate the total  pressure drop  T S P      Total Static Pressure   Internal   External Static Pressure  Heat exchanger material     The heat exchanger type is determined by the application   The standard heat exchanger material is aluminized   Steel  A 409 stainless steel heat exchanger and burner is  recommended when the unit is installed downstream of a  cooling coil or evaporative cooler  and when the combined  entering return air to the unit is below 40  F     Type of fuel    Either natural or propane gas determined by the design  engineer    Gas control staging method     Either single stage  two stage  or electronic modulation  determined by the design engineer     Main power supply voltage to unit   Altitude at which unit is to be installed     With this information a basic unit can be selected as shown in  the following example     30    Selection Example Conditions  Select an indirect fired  100  make up air unit to meet the  following conditions    1  CFM at sea level   5 000 cfm    2  Outdoor design temp    10  F   Indo
29.  Sheave Assembly  3H35130B3    Digit 19 Sheave Assembly    3H35130B5    Digit 19 5           Assembly       3H35130B2    3H35130B4    3H35130B6       3H35130B13    3H35130B15    3H35130B17    3H35130B19       Motor Frame  Size  143 or 145          3H35130B14             3H35130B16       3H35130B18    RPM Range          3H35130B20             3H35129B21       626 765    765 901    901 1059    995 1161    1101 1285       3H36622B1    Digit 19    Sheave Assembly  3H36622B3    Digit 19 Sheave Assembly    Digit 19 5           Assembly    Digit 19  Sheave Assembly    Digit 19   Sheave Assembly       182 to 184    3H36622B2    3H36622B4    3H36622B6    3H36622B12       213 or 215    3H36622B5    3H36622B7    3H36622B13    3H36622B18       254    3H36622B8    3H36622B14    3H36622B19    3H36622B23       256    3H36622B9    3H36622B15    3H36622B20    3H36622B24       284    3H36622B10    3H36622B16    3H36622B21    3H36622B25       286                3H36622B11       AIR 5 565 2    3H36622B17    3H36622B22                3H36622B26          37    BLOWER SHEAVE ASSEMBLY DATA    Table 38 1   Blower Sheave Assembly Settings    Turns Open  Sheave  Assembly I   2 2       Blower R  3H35125B1 2  3H35125B3 5  3H35125B6 7  3H35125B8 9   3H35125B10 11  3H35126B1 2  3H35126B3 5  3H35126B6 8  3H35126B9 11   3H35126B12 14  3H35127B1 2  3H35127B3 5  3H35127B6 8  3H35127B9 11  3H35127B12 14  3H35127B15 16  3H35127B17  3H35128B1 3  3H35128B4 6  3H35128B7 9  3H35128B10 12  3H35128B13 14  3H35128B15  
30.  The power exhauster pre purge time delay relay then  closes after 20 to 40 seconds and energizes the gas control  circuit    3  The pilot valve opens and the spark igniter sparks in an  attempt to light the pilot   If the unit was not provided with a  time delay relay  the blower starts     4  Once the pilot is lit  the flame sensor proves the pilot and  stops the spark igniter from sparking    5  The main gas valve is opened and the main burner is  controlled as follows    a  Single Stage Units  The main burner is lit to 100  full fire    b  Two Stage Units  The main burner is lit to 5096 fire  If  the temperature at the thermostat continues to fall  the  thermostat will call for high stage heat and the main burner  is lit to 100  full fire    c  Modulating Thermostat  Room or Duct   The main  gas valve is opened 10096 and the burner firing rate is  modulated between 40  and 100  full fire  A resistance  signal  8000 to 12000 ohms  in the thermostat is converted    6     by the modulating amplifier to an inverted DC voltage   OVDC for high fire to 12 VDC for low fire   The output  voltage is applied to the modulating gas valve to control  the gas flow to the main burner  The modulating valve is  modulated open or closed based on the voltage from the  amplifier  less gas flow required   higher voltage  more  gas flow required   lower voltage     Note  When modulating duct sensing is utilized  a room  override thermostat can be added  When the room  override calls for heat  t
31.  Vented Blower Package Unit Dimensions with Blower Type I  J  K  or L                                                                                                                                                                         3322 47 36 36 68  J Over Roof      Y  _   nNr    2 00 u  3 86      X Blower Hat          nn go  N  Vent Dia           ee sss  I et   y   er E         3 3 00 w 2 32  i   l  34 00     gt    T3400         N 2                    23 07  Height Outside                Ik  24 00 G  INSIDE  24 00  C  Width Outside               Inside   SS    42 37      i Z M MORE        Fresh Air       2 a Duct Connection    Or Qr t 7 Nath   SG   fh u  1026 905                921  oe YY     9 21 529                     EXE        l         1 vierte epp pt sc Ig               2 08         3 00  Lol     5 65 Min   approx   Qty  4  Drill Locator Dimples for inside  4 35  Field Drilled Electrical Conduit Return Air 1 50    k    Entry Holes  spaced 2 0  apart  Duct Connection          5    500   800 Model Shown             Figure 43 2   ICG Indoor Gravity Vented Cooling Package Unit Dimensions with Blower Type    J  K  or L                                                                                                         36 67 29 36 47 86 36 68  J Over Roof     12 67        L  N  Vent Dia  p    2 00 2 32  Outlet Air             Duct 1 Fresh Air  Connection       M  Duct Connection  28 00  Height         00 24 00 43  42 37  inser ide  G  NSDE           naq  E  Width  
32.  allow the unit to operate when gas  conditions are returned to the allowable range of the pressure  switch  The pressure switch range is 2  to 16  W C  and should  be set to insure that the maximum manifold gas pressure is not  exceeded  3 5  W C  for natural gas  10  W C  for propane gas       5  Timed Freeze Protection      OPT    The timed freeze protection system is factory installed in the  duct furnace electrical junction box with the sensor  30  75 F  adjustable  factory installed in the discharge air stream  On  initial start up  the timed delay in the system allows the unit to  go through the normal ignition sequence  The timed delay is   a manual reset switch and adjustable for 1 10 minutes  In the  event that the unit fails to fire after this period  the discharge air  sensor will sense the cold air and will shut down the entire unit     Figure 20 4   Timed Freeze Protection Module             60                   o       T  35 30975 2                 0   WI    55  1  G                      O   4    UD       6  50  5117 B  Owe L65 44  8 TIME Qi      sg 40        9 MIN  o  Ty cm H  1     mmo                                              Q 0 Om  Ow  OW  Ows O         ERIE o        c  nei N L   L                                                                            6  Ignition Controller      STD    The ignition controller is factory installed in the duct furnace  electrical junction box with the spark ignitor and sensor located  on the burner     For both natura
33.  amp  960    75   75 000 Btu Hr Input 350   350 000 Btu Hr Input  100   100 000 Btu Hr Input 400   400 000 Btu Hr Input  125   125 000 Btu Hr Input 500   500 000 Btu Hr Input  150   150 000 Btu Hr Input 600   600 000 Btu Hr Input  175   175 000 Btu Hr Input 700   700 000 Btu Hr Input  200   200 000 Btu Hr Input 800   800 000 Btu Hr Input  225   225 000 Btu Hr Input 840   1 050 000 Btu Hr Input  250   250 000 Btu Hr Input 960   1 200 000 Btu Hr Input  300   300 000 Btu Hr Input    7   Heat Exchanger Burner Drip Pan Material  HE    A   Aluminized Steel   S   409 Stainless Steel Heat Exchanger Burner   T   409 Stainless Steel Heat Exchanger Burner Drip Pan    8   Development Sequence Designation  DS   F   Single Stage M   2 stage or Modulating    9   Access Side  AS   R   Right Hand L   Left hand  10   Air Temperature Rise  ATR    H   High 60   100  F    11   Gas Type  GT   N   Natural with ignition controller  P   Propane with ignition controller    12   Gas Valve  GV   1   Single Stage 6   Electronic Modulation Slave  2   Two Stage 7   Electronic Modulation 0 10 Vdc  4   Electronic Modulation External Input   5   Electronic Modulation Master 8   Electronic Modulation 4 20 mA    External Input    13   Additional Safety Switches  SS   4   No Switches  Standard  1   Low Gas Pressure Switch  Premium   0   No Switches  Premium  2   High Gas Pressure Switch  Premium   3   High and Low Gas Pressure  Switch  Premium     14   Supply Voltage  SV     A   115 60 1 D   208 60 3  B   208 60
34.  cfm line up the   right until it intersects with the T S P  line of 0 75  W C   which is shown at the top of the table  At the point of  intersection of these two columns  read the required  horsepower and blower rpm  Repeat this process for  1 00 T S P  and literate to determine the BHP and rpm for  0 89  W C  For this example the horsepower is 5 and the  blower rpm is 1280     Following this procedure for G H blowers  Using 5000  cfm and 0 89  W C  T S P   the horsepower is 5 hp and  920 rpm  Following this procedure for I J H blowers   Using 5000 cfm and 0 87  W C  T S P   the horsepower  is 3hp and 700 rpm  Although I J H blowers results in     3 hp motor  this blower requires the use of the extended  cabinet length  As a result  for purposes of this selection  example G H will be used     Since the Bearing Type was not specified  the standard  spider bearings will be used  Thus  using Table 34 1 with  spider bearings  the Blower Size and Bearing Type   G     13     14     15     16     17     18     Determine the Motor Horsepower    The motor horsepower determined in step 12 was a 3 Hp   Since the supply voltage is 460V 60Hz 3Ph  a motor starter  will need to be provided either with the unit or by others  For  purposes of this selection  a motor starter by others will be  used so the Motor Horsepower   G     Determine the Motor Type    The motor type was not specified so for purposes of this  selection the standard open drip proof motor will be used so  the Motor Type  
35.  feet  The following instructions are for units that will be installed  over 2 000 feet elevation  If this does not apply  you may skip  ahead to the Electrical Connections section on page 11     Manifold Pressure Adjustment    The unit manifold pressure is factory set for operation at  elevations up to 2000 feet as follows       For Natural Gas units  3 5  W C  based on a gas heating value  of 1 050 BTU ft3       For Propane Gas units  10 0  W C  based on a gas heating  value of 2 500 BTU ft3     For higher elevations  some utility companies may derate the  BTU content  heating value  of the gas provided at altitude to a  lower value to allow certain heating appliances to be used with  no manifold pressure adjustments  For this reason it is necessary  that the supplying utility be contacted for detailed information  about the gas type and BTU content  heating value  before  operating any heater  Table 10 1 shows the standard derated  heating values of natural and propane gases at various  elevations     Table 10 1  Gas Heating Values at Altitude  Btu ft      2         0 2 000  2 001 3 000  3 001 4 000  4 001 4 500                4 501 5 000  5 001 6 000  6 001 7 000  7 001 8 000  8 001 9 000  9 001 10 000                        Values shown are for 3 5  W C  manifold pressure for Natural Gas and 10 0   W C  for Propane Gas  If the local utility supplies gas with a different Btu ft   value  use Equation 10 1 to calculate the required manifold pressure       Gas heating values
36.  life      The vent pipe must not pass through an unheated space  or interior part of an open chimney unless the vent pipe is  insulated      Where the vent pipe may be exposed to extreme cold  or  come into contact with snow or ice  the entire vent must  be insulated or double wall  includes outdoors   It is  preferred that the double wall vent is one continuous  piece but a joint is allowed outside the building      The heater system shall be checked at least once a year  by a qualified service technician     Additional Requirements for Horizontally Vented   Category III Units  Model IBP ICP units only    1  Seal the joints with a metallic tape or silastic suitable for  temperatures up to 350  F   3M tapes 433 or 363 are  acceptable   Wrap tape two full turns around the vent pipe    2  Refer to Table 7 1 for total minimum and maximum vent  lengths making the vent system as straight as possible    The equivalent length of a 90  elbow is 5 feet for 4  diameter  and 7 feet for 6  diameter     Table 7 1   Horizontal Category III Vent Sizing  Requirements 2    Model Vent Connector Minimum Vent   Maximum Vent  Size Diameter Pipe Diameter Length  75 4  4  48        100 175  200          225  250 300  500 600    350 400  800 960      Unit can be vented with 5  diameter pipe if a 6  to 5  reducer is used   Otherwise  use 6  pipe     Per furnace           3  The vent terminal must be Modine part number     5H072285 0001  Item Code 27866  for 4  vent pipe    5H072285 0004  Item Code 2
37.  light off  Low Fire  Does entire burner light off   Hi Fire  Burner pressure reading                   Is flame clean and stable   Does flame modulate in response to temperature control s      Gas input checked   Input at maximum firing rate      __ Btu Hr  Input at minimum firing rate        Btu Hr    Gas piping checked for and free of leaks     Has wiring been verified to match the unit wiring diagram     Have all the modes of the sequence of operation been verified and tested     What optional and or accessory control devices have been set   Device  Setting  __      VF psi Inches W C  etc    Device  Setting  __ ___  F psi Inches W C  etc    Device  Setting  __        F psi Inches W C  etc                  ONOaARWN                                      Customer Owner instructed in operation and maintenance of unit  Yes No  Name of Person s  Instructed        Comments           Start Up Company Name  Phone           Signature  Date           56 AIR 5 565 2    MODEL NOMENCLATURE FOR SYSTEM UNITS    Indoor Duct Furnace Make Up Air Unit Model Nomenclature    8 9 10 11    2 13 14 15      16   17     18   19 120 21   22   23            DS AS ATR GT    GV   SS   SV TR BB   HP    MT   SA  AC   EC   CC          1    Product Type  PT   Indoor HVAC Unit    Unit Configuration  UC    Furnace   Blower Package   Furnace  amp  Blower     Cooling Package   Furnace  Blower  amp  Cooling    O DU TN    3   Venting  V   G   Gravity  P   Power    4 5 6  Furnace Input Rating  MBH   Output on 840 
38.  locating units  it is important to consider that the  exhaust vent piping must be connected to the outside  atmosphere    8  In garages or other sections of aircraft hangars such as  offices and shops that communicate with areas used for  servicing or storage  keep the bottom of the unit at least  7  above the floor unless the unit is properly guarded to  provide user protection from moving parts  In parking  garages  the unit must be installed in accordance with the  standard for parking structures ANSI NFPA 88    and in  repair garages the standard for repair garages NFPA  88B   In Canada  installation of heaters in airplane hangars must  be in accordance with the requirements of the enforcing  authority  and in public garages in accordance with the  current CAN CGA B149 codes    9  Do notinstall units in locations where gas ignition system is  exposed to water spray  rain  or dripping water     AIR 5 565 2    Figure 3 1   Combustible Material and Service  Clearances       Access  Slide    o                                                                                                                           Model IBP ICP          Model IBGACG                        minimum clearance to combustible material is required from the vent collar     Table 3 2   Combustible Material Clearances          Access Side   Non Access   A  Side  B   Model Size All    75 thru 175   6    12  4  2  3   200 thru 960  6   12  2  2  3     Table 3 3   Recommended Service Clearances      Acce
39.  or electrical controllers  which have been wet  Replace defective controller     IMPORTANT    To check most of the Possible Remedies in the troubleshooting  guide listed in Table 51 1  refer to the applicable sections of the  manual                       All heating equipment should be serviced before each heating  Season to assure proper operations  The following items may be  required to have more frequent service schedule based on the  environment in which the unit is installed  and the frequency of  the equipment operation     Blower Assembly   The blower assembly includes the bearings  drive sheaves and belts   Blower bearings should be checked and lubricated based on the  blower manufacturer s recommendations  Bearings should also  be checked for any unusual wear and replaced if needed    Drive sheaves should be checked at the same time the bearings  are inspected  Check to make sure the sheaves are in alignment  and are securely fastened to the blower and motor shafts Belt  tension should be rechecked shortly after the unit has been  installed to check for belt stretching  After the initial start up   monthly checks are recommended     Filters   If the unit is supplied with a dirty filter switch and light  clean or  replace the filters any time the dirty filter light comes on    Units which do not have a dirty filter warning light should have  the filters checked monthly  Clean or replace if necessary  In dirty  atmospheres  filter maintenance may be required more oft
40.  section    The blower housing contains a double width  double inlet  DWDI   blower wheel so both sides of the blower must be free from  obstructions for proper operation  For Right Hand units    Digit 9   R   during operation the blower wheel should rotate   in the clockwise direction when viewed from the service side of  the unit  For Left Hand units  Digit 9 2 L   during operation the  blower wheel should rotate in the counterclockwise direction  when viewed from the service side of the unit  If necessary   interchange supply power wiring to reverse blower rotation      24  Pillow Block Bearings      OPT    The blower bearings are factory installed in the blower section   The blower can be provided with either spider or pillow block  bearings  Spider bearings are permanently lubricated and do not  require lubrication  Pillow block bearings are shipped non   greased from the factory and require lubrication before start up   For lubrication recommendations  see Lubrication  Recommendations      25  Blower Motor      STD    The blower motor is factory installed in the blower section  The  blower motor can be provided in a variety of supply voltages   frame types  and motor horsepowers  Refer to the model  nomenclature to determine the type of motor provided  The  blower motor is supplied with an adjustable sheave that can be  used to increase decrease the blower RPM  For instructions on  changing the blower RPM  refer to Blower Adjustments      26  Filters      OPT    When fi
41.  should the discharge air  temperature become excessive  See Figure 19 1  indicator   for  the location of either the standard automatic or optional manual  reset high limit switch  The switch should operate only when  something is seriously wrong with the unit operation  Anytime  the switch operates  correct the difficulty immediately or serious  damage may result  If the switch cuts off the gas supply during  normal operation  refer to the    Not Enough Heat    section of  Service  amp  Troubleshooting     Lifting Flame Condition                 00000000                         Figure 52 2 Figure 52 3  Floating Flame Condition Flame Rollout Appearance          wx  BOSS                               gt        Wu     TOE    A                                     52 AIR 5 565 2       SERVICE  amp  TROUBLESHOOTING    Blocked Vent Safety Switch Figure 53 1   Blocked Vent Safety Switch Location       A manual reset blocked vent safety switch is supplied on all  Model IBG ICG units and is designed to prevent operation of   the main burner in the event there is spillage of flue products   into the space  This spillage may occur due to a restricted vent   inadequate vent draw  uninsulated vent pipe in cold ambient   long vent runs  excessive vent diameter  restrictive vent terminal   negative pressure within space  etc  After the cause of the  spillage has been corrected  depressing the button of the blocked  vent safety switch found on top of the unit may reset the switch   See Figu
42.  shown are derated 4  per 1 000  of elevation  10   between 2 000  and 4 500  elevation in Canada  in accordance with ANSI  Z223 1 and CSA B149  respectively        945 Btu ft  for Canada   amp  2 250 Btu ft  for Canada      When installed at altitudes above 2 000   a pressure switch may need to be  changed  Refer to Tables 10 2 and 10 3 to determine if a switch change is  required     If the utility is supplying gas with heating values SAME as shown  in Table 10 1  the manifold pressure should remain set to 3 5   W C  for natural gas and 10 0  W C  for propane gas and you  may proceed to the section on this page titled  Selection of the  Proper High Altitude Kit      If the utility is supplying gas with heating values DIFFERENT  than shown in Table 10 1  use Equation 10 1 to determine the  appropriate manifold pressure for the elevation and gas heating  value being supplied  Note what that value is  as it will be  needed later for Start Up  Proceed to the section on this page  titled  Selection of the Proper High Altitude Kit            Equation 10 1   Manifold Pressure for Gas Heating  Values Different Than Shown in Table 10 1                   TBL   MP     Erg  x MP   ACT   Where           EV   Manifold Pressure    W C   at installed  elevation   BTUTg    BTU ff content of gas from Table 10 1   BTUACT   BTU ft  content of gas obtained from the  utility company   MPs    Manifold Pressure    W C    at Sea Level     use 3 5  W C  for natural gas and  10 0  W C  for propane   
43.  the Proportional Temperature Controller Sensor  The controller  sends a 2 10 Vdc signal to the modulating damper actuator in  order to maintain the set point  The controller includes a set point  dial that must be field set to the desired mixed air temperature   typically 55  F      Figure 25 3   Proportional Temperature Controller                    43  Warm Up Stat      OPT    A warm up stat is provided with Air Control options GK or GM   Digits 20  amp  21  and factory installed in the electrical section with  the sensor in the return air stream  The warm up thermostat  monitors the return air temperature to the unit and prevents   the fresh air dampers from opening until the temperature of the  return air has reached the desired set point  typically 65  F or 5  F  below the room temperature       44  Blower Supply Power Terminal Strip      STD    The blower supply power terminal strip is located in the electrical  section  The terminal strip is labeled to match the electrical wiring  diagram provided with the unit  Supply power labeling ranges  from terminal numbers 80 to 99  All field wiring connections  should be made to the bottom side of the terminals to prevent  miswiring by modifying the factory wiring which is made to the  top of the terminal strip      45  Service Switches      OPT    The service switches are factory installed in the electrical  section  The service switches allow for service personnel to  independently test operation of the damper  blower  and f
44.  the pump will be greater than the rest of the system    Evacuate the coil to 500 microns or less then close the  valve between the pump and the system  If the vacuum  holds to 500 microns or less for one minute  the system  is ready to be charged or refrigerant pumped down in  another portion of the system can be opened to the coil   A steady rise in microns would indicate that moisture is still  present and that the coil should be further vacuumed until  the moisture has been removed     12 AIR 5 565 2    UNIT INSTALLATION    9  Failure to obtain a high vacuum is indicative of a great  deal of moisture or a small leak  Break the vacuum with  a charge of dry nitrogen or other suitable gas and recheck  for leaks  soapy water works well   If no leaks are found   continue vacuuming the coil until the desired vacuum is  reached     10  All field piping must be self supporting     Chilled Fluid Piping    To prevent noise and coil damage from water hammer  an  air vent is necessary to bleed off the accumulated air in the  System  The vent should be located on the top of the inlet  manifold where the air collects  This vent should be opened  twice a year     The outlet manifold should have a drain installed on the bottom  to allow for periodic flushing of the system to remove sediments  and corrosion products from the cooling coil  This drain   should be opened to allow some fluid to drain twice a year   Check coloration and viscosity of the effluent for indications of  corrosion i
45.  unit  the damper  is factory installed in the blower section  The return air damper is  used as an air balancing damper so low leak  Class III leakage  resistance  less than 40 CFM ft  at 1  W C   dampers with self   compensating stainless steel side seals and santoprene blade  seals are used      34  Proportional Temperature Controller Sensor      OPT    A proportional temperature controller sensor is provided with Air  Control options GG  GH  GK or GM  Digits 20  amp  21  and factory  installed in the blower section  The sensor provides the mixed  air temperature signal to the A350P Proportional Temperature  Controller which is mounted in the electrical section      35  Motor and Blower Vibration Isolation      STD    The motor vibration isolation is factory installed in the blower  section below the blower support bracket  The four  4  13 32    neoprene vibration mount grommet provides isolation of the  blower housing and motor from the blower support channels   The blower vibration isolation is factory installed in the   blower section between blower discharge and the blower   duct connection  The blower duct connection is not rigidly  mechanically fastened and the 1 4  thick gasketing around the  duct transition provides vibration isolation     Figure 24 1   Blower Motor Vibration Isolation       BLOWER  SUPPORT    BLOWER  SUPPORT  RAIL    NEOPRENE  VIBRATION  ISOLATOR                                                                36  Blower Support      STD    The blow
46. 0          556   0 09   679   0 15   871 0 22   1031   0 29   1170   0 37 1296 0 45  1411 0 63   1617   0 81 1800 1 01   1968  79          700   0 14   747   0 21   924 0 29   1074   0 37   1206   0 46 1327 0 55   1438 0 75   1638   0 95   1818 1 17   1982  699     1800  0 18   801   0 26   966 0 35   1109   0 44   1237   0 54 1354 0 64   1462 0 84   1658   1 06   1832 1 30   1996  56  F     1000   0 29   917   0 39   1062   0 50   1192   0 60   1310   0 72 1419 0 83   1522 1 07   1709   1 32   1879      46  F     1200   0 45   1042   0 57   1171 0 69   1289   0 82   1397   0 94 1499 1 08   1595 1 35   1773          40  F     1400   0 66   1173   0 80   1288   0 94   1395   1 08   1495   1 23 1589 1 38   1680                5         1600   0 93   1308   1 09   1412   1 25   1509   1 42   1601                      31  F     1800   1 28   1445   1 46   1539                              75      69  F      800     0 15   795 0 21   960                          56  F     1000     0 20   822 0 28   975   0 36 1112                      46  F     1200   0 19   705   0 27   862 0 35   1003   0 44   1131 0 54 1250 0 65   1361              40  F     1400   0 27   770  36 00  912 0 45   1041   0 55   1161 0 66 1273 0 77  1377 1 00   1572          35  F    1600   0 37   839   0 47   968 0 57  1087   0 68   1199   0 80 1304 0 92   1403 1 17   1589   1 44   1760 1 72   1920  31  F     1800   0 49   912   0 60   1030   0 72   1139   0 84   1244   0 96 1343 1 09   1437 1 36   1613   1 65   1
47. 0 00 0 03 0 01  1000 0 02 0 02 0 03 0 04 0 04 0 12 0 01 0 05 0 01  1500 0 03 0 04 0 05 0 07 0 08 0 23 0 02 0 07 0 02  2000 0 05 0 06 0 07 0 10 0 15 0 36 0 04 0 10 0 03  2500 0 07 0 08 0 10 0 14 0 23 0 53 0 07 0 13 0 04  3000 0 09 0 11 0 13 0 19 0 34 0 73 0 11 0 16 0 05  3500 0 11 0 13 0 16 0 24 0 46 0 97 0 15 0 18 0 07  4000 0 14 0 16 0 20 0 30 0 60 1 28 0 19 0 22 0 09  4500 0 17 0 20 0 25 0 37 0 25 0 25 0 1  4630 0 17 021 0 26 0 38 4000 Max CFM for Evap 0 26 0 26 0 11  1111 0 01 0 02 0 03 0 04 0 03 0 09 0 02 0 02 0 01  1500 0 02 0 03 0 04 0 05 0 05 0 15 0 02 0 03 0 01  2000 0 03 0 04 0 06 0 08 0 09 0 24 0 04 0 05 0 02  2500 0 05 0 06 0 09 0 11 0 14 0 34 0 05 0 08 0 02  3000 0 06 0 08 0 1 0 15 0 20 0 46 0 07 0 10 0 04  3500 0 08 0 1 0 14 0 18 0 27 0 61 0 10 0 14 0 05  4000 0 1 0 13 0 18 0 23 0 35 0 77 0 13 0 18 0 06  4500 0 13 0 16 0 21 0 27 0 45 0 95 0 17 0 22 0 08  5000 0 16 0 19 0 25 0 32 0 55 1 15 0 21 0 27 0 10  5200 0 17 0 21 0 27 0 34 0 60 1 23 0 23 0 29 0 1  5556 0 19 0 23 0 30 0 38 4000 Max CFM for Eva 0 26 0 33 0 13  1481 0 01 0 02 0 03 0 03 0 04 0 12 0 02 0 03 0 01  2000 0 01 0 02 0 04 0 04 0 07 0 19 0 03 0 05 0 01  2500 0 02 0 04 0 05 0 06 0 10 0 27 0 04 0 08 0 02  3000 0 03 0 05 0 07 0 08 0 15 0 36 0 06 0 10 0 04  3500 0 03 0 06 0 09 0 10 0 20 0 47 0 09 0 14 0 05  4000 0 05 0 08 0 1 0 12 0 27 0 60 0 11 0 18 0 06  4500 0 06 0 10 0 18 0 15 0 34 0 73 0 14 0 22 0 08  5000 0 07 0 1 0 16 0 18 0 42 0 89 0 18 0 27 0 10  5500 0 09 0 14 0 19 0 21 0 50 1 05 0 21 0 32 0 12  
48. 00 G or H  700 800 I J  K  or L  840 960 I J  K  or L                                                          Table 46 2   Indoor Power Vented Cooling Package Units  All dimensions in inches   Dimensions  Blower Type   Digit 16   75 All  100 125 All          150 175 All  200 225 All  250 300 E  F      or H  250 300 I  J  or K  350 400 E  F  G  or H  350 400 l  J  or K                                           46 AIR 5 565 2    DIMENSIONS   COOLING COILS    Figure 47 1   DX Coil Drawing  All dimensions in inches           Airflow Direction                               E    ns  Coil for Right Hand Units   Digit 9   R   Headers on opposite  side for Left Hand Units       FRONT VIEW           RR                   1 5                          4                Rows  2 314 6  W   7 5  6  7 5   10              TOP VIEW    L   lt  1 5 15  gt  765  gt  W   lt   A    Distributor Inlet  Liquid             7 Line  Connection s      Second Inlet on Dual  Circuit Coils     a SIDE VIEW    Airflow  Direction    Suction Line Connections in direction  of airflow   Second Inlet on Dual Circuit Coils        Table 47 1   DX Coil Dimensions    Model Size Cooling MBH FH H  75 All    S  1 5    All 24 31 24  27 34 30    Below 185 MBH    100 125 1 5    150 175    27 5 30 5    27 5 30 5 1 5    30       200 225    185 MBH  amp  Up 27 34 5    Below 185 MBH       250 300  185 MBH  amp  Up    Below 185 MBH  185 MBH  amp  Up      Single Circuit DX coils have 1 each Suction Line and Liquid Lines  Refer to A
49. 1481   0 36   871   0 48   1016   0 60   1144   0 73   1259   0 85   1366   0 99  1465   1 26   1646   1 54   1808   1 84   1958  Start 225 89     100       1667   0 48   943   0 61   1078   0 75   1198   0 88   1309   1 03 1411 1 17   1507 1 47   1682   1 77   1842 2 09   1988  85     95      1750   0 54   975   0 68   1106   0 82   1224   0 96   1332   1 11 1433 1 26  1527 1 57   1700   1 88   1857 2 21   2003  74  F 83  F 2000   0 76   1077   0 92   1197   1 08   1306   1 24   1407   1 40 1502 1 57  1592 1 91   1758   2 26   1910 2 62   2051  66  F 74  F 2250   1 04   1181   1 21   1291 1 39   1393   1 57   1488   1 75 1577 1 94  1663 2 31   1822   2 69   1969      59  F 67  F 2500   1 38   1288   1 57   1389   1 77   1484   1 97   1573   217 1658 2 37   1739 2 78   1892          54  F 61  F 2750   1 79   1396   2 00   1490   2 22   1579   2 44   1663   2 66 1743 2 88   1820              49  F 56  F 3000   2 28   1506   2 51   1593   2 75   1677   2 98   1756                      200 225        85  F 95  F 1750   0 29   594   0 43   723 0 58   838   0 75 944 0 94 1042 1 14  1134 1 58   1303   2 07   1458 2 60   1600     174  F 83  F  2000   0 40   642   0 54   759 0 71   866   0 88 966 1 08 1058 1 28   1146 1 74   1309   2 23   1458 2 78   1595  59  F 67  F 2500   0 68   746   0 85   845 1 04   938 1 23   1025   1 45 1108 1 67  1188 2 15   1337   2 67   1475 3 24   1604  49  F 56  F 3000   1 09   857   1 29   942 1 50   1024   1 72   1101 1 95 1176 2 19  1248 2 71   1384  
50. 3H35129B1 3  3H35129B4 7  3H35129B8 10  3H35129B11 14  3H35129B15 18  3H35129B19 21  3H35130B1 2  3H35130B3 4  3H35130B5 6  3H35130B13 14  3H35130B15 16  3H35130B17 18  3H35130B19 20  3H36622B1 2  3H36622B3 5  3H36622B6 11  3H36622B12 17  3H36622B18 22  3H36622B23 26                                                                                                                                              38 AIR 5 565 2    BLOWER SHEAVE ASSEMBLY DATA    Table 39 1   Blower Sheave Assembly Components    Sheave Assembly Motor Sheave Blower Sheave Sheave Assembly Motor Sheave Blower Sheave  Browning Browning    i i Belt     in   Prefix Suffix  in              Pitch Dia Pitch Dia                        Pitch Dia Pitch Dia    Prefix Suffix Belt   Bore  in       in                                 3H35125                     cjoj    jojo 2ljo m         cioj  J ojo in  o m             ak  o              o    3H35129    alfa                             Er            _                                  3H35126                                N                         E  o    Qty  2  B74  Qty  2  B74  Qty  2  B78  Qty  2  B78  Qty  2  B77  Qty  2  B77  Qty  2  B82  Qty  2  B82  Qty  2  B79  Qty  2  B79  Qty  2  B77  Qty  2  B77  Qty  2  B75  Qty  2  B75                                                                        3H35130                                                         RE RE RE RE REI REL                       o  N             3H35127                 k  o                 
51. 49   1444   1 66 1529 1 84  1610 2 20   1762   2 57   1906 2 96   2041  43     50      2600   1 58   1344   1 76   1429   1 95   1510   2 14   1589   2 34 1664 2 54   1737 2 95   1877          372   43     3000   2 35   1526   2 57   1600   2 78   1673   3 00   1743                      150 175        86  F 100  F   1296     0 25   609 0 37   734                          79  F 93  F  1400   0 17   474   0 28   615 0 40   737                          62  F 72  F 1800   0 28   526   0 41   650 0 55   760   0 70 859 0 85 952                  51  F 59  F 2200   0 44   588   0 59   697 0 75   796   0 91 887 1 09 972 1 27  1052 1 67   1201          43  F 50  F 2600   0 67   657   0 83   753 1 01   842   1 19 925 1 39 1004 1 59  1078 2 02   1218   2 47   1348 2 96   1469  37  F 43  F 3000   0 96   729   1 15   815 1 35   895 1 55 972 1 76 1044 1 98   1114 2 45   1245   2 94   1368 3 45   1483  33  F 38  F 3400   1 35   804   1 55   881 1 77   955   2 00   1025   223 1092 2 47  1157 2 96   1280   3 49   1396 4 03   1505  29  F 34  F 3800   1 82   880   2 05   951 2 29   1018   2 53   1083   2 79 1146 3 04  1206 3 58   1322   4 14   1431 4 72   1535  26     31     4200   2 40   959   2 66   1023   2 92   1085   3 18   1145   3 45 1204 3 73  1260 4 30   1369   4 90   1472      24    28    4700   3 80   1058   3 58   1116   3 87   1172   4 16   1227   4 46 1281 4 76  1333              21  F 25  F 5200   4 40   1158   4 71   1212                              200 225   c p  100  FM13  F  
52. 6 primary  line  side of required step down transformer                          Table 40 2   Motor Data       Table 40 3   Motor Data          Supply Motor Size   Motor Type Full Load            Frame   Efficiency Supply Motor Size   Motor Type Full Load NEMA Efficiency    Voltage    pigit 17        Digit 18  6   Amp Draw Size    Voltage    Digit 17       Digit 18       Amp Draw   Frame Size     Digit 14   Digit 14                                                                 115V 60Hz 1ph  A   208V 60Hz 1ph  B                                                                          230V 60Hz 1ph  C                                  Single phase motors are not rated for use with a variable frequency drive      Motors rated below 1hp have integral thermal overload protection  Motors rated 1hp and larger require the use of a motor starter for overload protection     Motor Sizes  Digit 17  A through H do not include a motor starter  D through H require a motor starter by others   All others include a motor starter      ODP   Open Drip Proof  TE   Totally Enclosed      Motor manufacturers typically do not list efficiency for single phase motors     40 AIR 5 565 2    MOTOR DATA    Table 41 1   Motor Data    2 Table 41 2   Motor Data          Ve Motor Size Motor Type Full Load NEMA Efficiency ie Motor Size Motor Type Full Load NEMA Frame  Efficiency   Digit 14   Digit 17  OG    Digit 18  6   Amp Draw   Frame Size     Digit 14   Digit 17        Digit 18       Amp Draw Size  ODP  1
53. 6000 0 11 0 16 0 22 0 25 0 60 128 0 26 0 38 0 14  6500 0 13 0 18 0 25 0 28 5200 Max CFM for Evap 0 30 0 45 0 16  1852 0 03 0 02 0 05 0 05 0 05 0 15 0 02 0 07 0 02  2000 0 03 0 03 0 05 0 06 0 06 0 17 0 02 0 08 0 02  2500 0 04 0 04 0 07 0 09 0 09 0 24 0 03 0 09 0 03  3000 0 05 0 06 0 10 0 11 0 18 0 32 0 04 0 12 0 04  3500 0 07 0 08 0 12 0 15 0 17 0 41 0 06 0 14 0 06  4000 0 08 0 10 0 15 0 18 0 23 0 52 0 08 0 16 0 07  4500 0 10 0 13 0 18 0 22 0 29 0 64 0 10 0 19 0 09  5500 0 14 0 19 0 25 0 81 0 43 0 91 0 15 0 25 0 13  6500 0 19 0 26 0 34 0 42 0 60 1 28 0 21 0 81 0 18  7250 0 23 0 32 0 41 0 51 6000 Max CFM for Eva 0 27 0 37 0 23  1925 0 02 0 01 0 03 0 03 0 02 0 08 0 02 0 07 0 02  3000 0 03 0 03 0 05 0 05 0 05 0 15 0 04 0 12 0 04  4000 0 05 0 05 0 08 0 09 0 09 0 23 0 08 0 16 0 07  5000 0 08 0 08 0 1 0 12 0 14 0 34 0 12 0 22 0 1  6000 0 1 0 1 0 15 0 16 0 20 0 46 0 18 0 28 0 16  7000 0 15 0 15 0 19 0 21 0 27 0 61 0 25 0 35 0 21  8000 0 19 0 20 0 24 0 27 0 35 0 77 0 33 0 42 0 28  9000 0 24 0 25 0 30 0 33 0 45 0 95 0 42 0 51 0 35  10400 0 32 0 33 0 38 0 42 0 60 1 23 0 57 0 64 0 47  1111 0 36 0 38 0 43 0 47  10400 Max CFM for        0 66 0 71 0 53  2593 0 02 0 02 0 04 0 04 0 05 0 16 0 02 0 03 0 01  3000 0 02 0 02 0 05 0 05 0 07 0 20 0 03 0 04 0 01  3500 0 03 0 03 0 06 0 06 0 10 0 25 0 04 0 05 0 01  4000 0 03 0 04 0 07 0 08 0 13 0 32 0 05 0 07 0 01  4500 0 04 0 05 0 09 0 10 0 16 0 39 0 06 0 09 0 02  5000 0 05 0 06 0 10 0 12 0 20 0 47 0 07 0 1 0 02  5500 0 06 0 07 0 12 0 14 0 24 0 55 0 0
54. 777 1 94   1931  28 F    2000   0 65   987   0 77   1095   0 90   1197   1 03   1295   1 16 1388 1 30   1477 1 59   1645   1 89   1802 2 20   1950  24  F     2300   0 94   1104   1 08   1200   1 22   1292   1 37   1380   1 52 1465 1 67   1547 1 98   1703   2 31 1850 2 65   1990  20  F     2778   1 59   1296   1 75   1377   1 92   1456   2 09   1532   2 26 1606 2 44   1679 2 80   1818          100 125           100          741      0 15           0 23   962   0 30   1093   0 38   1212   0 47  1320   0 60   1514   0 86   1686   1 07   1840  Start 125           80 F 100 F  926   0 13   670   0 21   846 0 29   993   0 38   1121   0 47 1236 0 56   1342 0 77   1532   0 99   1702 1 22   1856  62  F 77  F  1200   0 22   758   0 31   916 0 41   1052   0 52   1173   0 62 1282 0 74   1384 0 97   1568   1 22   1733 1 48   1884  53  F 66  F  1400   0 30   828   0 41   975 0 53   1103   0 64   1218   0 76 1323 0 89   1422 1 15   1600   1 42   1762 1 70   1910  41  F 51  F 1800   0 55   982   0 69   1108   0 83   1220   0 98   1325   1 12 1422 1 27  1513 1 58   1681 1 90   1834 2 23   1976  34  F 42  F  2200   0 93   1145   1 10   1254   1 27   1354   1 44   1449   1 61 1537 1 79  1621 2 15   1778   2 52   1923 2 90   2057  28  F 36  F  2600   1 45   1315   1 65   1410   1 85   1500   2 05   1585   2 25 1666 2 46   1744 1 35   1638          25  F 31  F  3000   2 16   1489   2 39   1573   2 61   1654   2 84   1731                      100 125   E F  41     51      1800   0 28   497   0 41  
55. 7867  for 5  vent pipe    5H072285 0002  Item Code 27868  for 6  vent pipe  A Gary Steel 1092 cap is an acceptable alternate     4  The vent must extend a minimum of 12  beyond the exterior  wall surface and must be supported as shown in Figure 7 1   Precautions must be taken to prevent degradation of building  materials by flue products    5  The vent system shall terminate at least 3 feet above any  forced air inlet  except direct vent units  located within 10  feet  and at least 4 feet below  4 feet horizontally from  or 1  foot above any door  window  or gravity air inlet into any  building  The bottom of the vent terminal shall be located  above the snow line or at least 1 foot above grade  whichever  is greater  When located adjacent to public walkways the  vent system shall terminate not less than 7 feet above grade     6  The venting system must be exclusive to a single unit  and  no other unit is allowed to be vented into it     AIR 5 565 2          7  Horizontally vented units must use single wall vent pipe    although one continuous section of double wall vent pipe  may be used with the vent system  Under no circumstances  should two sections of double wall vent pipe be joined  together within one vent system due to the inability to verify  complete seal of inner pipes     Figure 7 1   IBP ICP Horizontal Venting    USE LISTED THIMBLE  THROUGH WALL    SPECIFIED     SLOPE PIPE DOWN  1 4  PER FOOT TERMINAL    TOWARD DRIP LEG                                            
56. 9 0 14 0 03  6000 0 06 0 08 0 14 0 17 0 29 0 64 0 10 0 17 0 04  6500 0 07 0 10 0 16 0 19 0 34 0 74 0 12 0 20 0 04  7000 0 08 0 11 0 18 0 22 0 39 0 85 0 14 0 23 0 05  2503 0 02 0 01 0 02 0 02 0 08 0 11 0 02 0 03 0 01  3000 0 02 0 02 0 02 0 03 0 04 0 14 0 08 0 04 0 01  4000 0 03 0 03 0 04 0 04 0 08 0 22 0 05 0 07 0 01  5000 0 04 0 04 0 05 0 06 0 12 0 31 0 07 0 1 0 02  6000 0 06 0 05 0 07 0 08 0 18 0 42 0 10 0 17 0 04  7000 0 07 0 07 0 10 0 11 0 24 0 55 0 14 0 23 0 05  8000 0 09 0 09 0 12 0 13 0 32 0 70 0 19 0 30 0 08  9000 0 1 0 12 0 15 0 16 0 40 0 86 0 24 0 38 0 10  10000 0 13 0 14 0 18 0 19 0 50 1 04 0 30 0 48 0 14  11050 0 15 0 17 0 22 0 23 0 61 1 24 0 36 0 58 0 17  12000 0 18 0 20 0 26 0 27 0 43 0 69 0 21  13000 0 20 0 24 0 30 0 31 VIOSD MaX GEM Tor Evap 0 51 0 81 0 26      Accesssory   Option static pressure losses are approximate values only  Please consult the Accuspec selection software for static pressure  losses at other than listed CFM     32    AIR 5 565 2    BLOWER PERFORMANCE DATA    Table 33 1   Unit Performance Tables         Total Static Pressure   W C                                                                                                                                                                                                                             Digit dns  0 25 0 50 0 75 1 00 1 25 1 50 2 00 2 50 3 00  Unit Size  16   Rise          Bup npM  BHP  RPM  BHP   RPM  BHP   RPM   BHP   RPM   BHP   RPM   BHP  RPM   BHP   RPM   BHP   RPM  75 A B 10
57. A two position damper actuator  is provided with Air Control options DA  EA and EQ  Digits   20  amp  21   The two position damper actuator provides open   closed operation of the fresh air damper  When the damper is  energized  the fresh air damper is opened to 100  outside air in  75 seconds  for outside air percentages lower than 100   refer  to the following section   Setting the Damper Limiter    All two   position damper actuators are spring return  so when the damper  is de energized  the fresh air damper will spring closed  All two   position dampers include auxiliary switches  one normally open  and one normally closed  that reverse when the damper actuator  is at 85   rotation  adjustable         Setting the Damper Limiter  The two position damper limiter is  factory set to prevent the outside air damper from opening  100   Field adjustment of the two position damper limiter is  accomplished by the following    1  Determine the amount of damper rotation required   Percentage of outside air     2  Locate the angle of rotation limiter on the actuator so that its  edge lines up with the degree graduation on the actuator  face which corresponds with the required rotation   See  Figure 22 1 which is shown at 50  rotation limit     3  Position the limiter back to the desired position  making sure  the locating    teeth    on the limiter are engaged into the  locating holes on the actuator    4  Fasten the limiter to the actuator using the screw provided    5  Test the dam
58. B8    3H35127B10    3H35127B13    3H35127B15       213 or 215    Motor Frame  Size  48                      RPM Range    3H35127B11          3H35127B14             568 771    767 958    934 1136    1136 1380       3H35128B1    Digit 19    Sheave Assembly    Digit 19 Sheave Assembly    Digit 19  Sheave Assembly    Digit 19  Sheave Assembly       56    3H35128B2    3H35128B4    3H35128B7    3H35128B15       143 to 145    3H35128B3    3H35128B5    3H35128B8    3H35128B10       182 or 184    3H35128B6    3H35128B9    3H35128B11    3H35128B13       213 or 215    Motor Frame  Size  56                   RPM Range    3H35128B12          3H35128B14          3H35127B16             491 649    586 744    682 821    821 1009    995 1161    1101 1285       Sheave Assembly  3H35129B1    Digit 19    Sheave Assembly  3H35129B4    Sheave Assembly    Digit 19               Assembly    Digit 19  Sheave Assembly    Digit 19   Sheave Assembly       143 or 145    3H35129B2    3H35129B5    3H35129B8       182 to 184    3H35129B3    3H35129B6    3H35129B9    3H35129B11    3H35129B15       213 or 215    3H35129B7    3H35129B10    3H35129B12    3H35129B16    3H35129B19       254    3H35129B13    3H35129B17    3H35129B20       256                            3H35129B14    Table 37 4   Digit 16 2 K  18 18 Blower Units with 15 Hp motor  amp  up   RPM Range    Motor Frame  Size          3H35129B18       826 1009    995 1161    1101 1285    1232 1438       Digit 19 Sheave Assembly    3H35130B1    Digit 19   
59. Both the main and pilot valves close  100     b  Two Stage Units  Once the high stage of the thermostat  is satisfied  the main valve closes to 50  fire  The unit  continues to operate until the low stage thermostat is  satisfied  at which time both the main and pilot valves close  100     c  Electronic Modulation Units  The unit continues to  operate in this manner until the thermostat is satisfied or  the BMS heat enable contact opens  Power is then cut to  both the main and pilot valves  closing them 100  and  stopping gas flow to the main and pilot burners       If the unit was not provided with a time delay relay  the blower    stops immediately  If the unit was provided with a time delay  relay  the blower stops after 30 to 45 seconds     AIR 5 565 2 17    START UP PROCEDURE    Multiple Furnace Controls    Staged Control  Digit 12 1     For control of multiple staged units  each furnace would be  individually controlled  Refer to the section for Single Furnace  Controls  Staged Control  Digit 12 1 or 2      Electronic Modulating Control  Digit 12 4     These units are the same as Electronic Modulating Gas   Controls     Single Furnace  Digit 12 4  except the Master unit   features a modulating amplifier capable of driving multiple   modulating gas valves for systems with a Master and up to two   Slave units  Slave units do not have a modulating amplifier    The units would be controlled by one of the following      Modulating room thermostat     Modulating duct thermost
60. DATE OF SHIPMENT FROM SELLER  WHICHEVER OCCURS FIRST    As Modine Manufacturing Company has a continuous product improvement program  it reserves the right to change design and specifications without notice      lt      MODINE       Modine Manufacturing Company 2015    Modine Manufacturing Company  1500 DeKoven Avenue   Racine  WI 53403   Phone  1 866 823 1631  toll free   www modinehvac com schoolsystems    
61. E  D  TO        H  FEET MINMUM  ABOVE WALL OR  ADJOINING  BUILDING PER  TABLE 6 2    3 FEET  MINIMUM       SIZE ACCORNING  TO EXPECTED  SNOW DEPTH                USE LISTED  THIMBLE  THROUGH  CEILING    Js WITH DRIP LEG    AND CLEANOUT CAP    LISTED      WALL OR ADJOINING  PUDING m e    ROOF  FLASHING       OOS    AS       MAINTAIN MINIMUM  CLEARANCE TO  COMBUSTIBLES                             5                   SLOPE PIPE UP  1 4  PER FOOT  TOWARD DRIP LEG           USE LISTED  THIMBLE  THROUGH  CEILING    TEE WITH DRIP LEG  AND CLEANOUT CAP       Table 6 1   Minimum Height from Roof to Lowest    Discharge Opening    Roof Rise     X     in     Equivalent  Roof Pitch    Flat to 10 12    Minimum Height     H     ft           10 12 to 12 12       12 12 to 14 12       14 12 to 16 12  16 12 to 18 12  18 12 to 21 12                Increase      as required to accommodate snow depth     Table 6 2   Minimum Height Above Adjacent Wall    Less than 10 Feet Away    10 Feet or Less    2 Feet Minimum       Greater than 10 Feet    AIR 5 565 2       No Additional Height Required       INSTALLATION    18  When condensation may be a problem  the venting system  shall not terminate over public walkways or over an area  where condensation or vapor could create a nuisance or  hazard or could be detrimental to the operation of regulator  relief openings or other equipment    19  In cold ambient conditions  such as Canada  the following  items are recommended for proper operation and  equipment
62. ER USER  WITHIN TEN YEARS  FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION  OR WITHIN ONE  HUNDRED TWENTY SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER  WHICHEVER  OCCURS FIRST       Heat Exchangers  Low Intensity Infrared Units   Gas Heat option on  MPR models    Compressors  Condensing Units for Cassettes    FIVE YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER  WITHIN  FIVE YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER  WITHIN FIVE YEARS  FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION  OR WITHIN SIXTY SIX  MONTHS FROM DATE OF SHIPMENT FROM SELLER  WHICHEVER OCCURS FIRST       Burners   Low Intensity Infrared Units  Compressors   MPR Models   Other    Components excluding Heat Exchangers   Coils  Condensers  Burners  Sheet Metal    TWO YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER  WITHIN  TWO YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION  OR WITHIN  THIRTY MONTHS FROM DATE OF SHIPMENT FROM SELLER  WHICHEVER OCCURS FIRST       Heat Exchangers Coils   Indoor and Outdoor Duct Furnaces and  System Units  Steam Hot Water Units   Oil Fired Units  Electric Units  Cassettes   Vertical Unit Ventilators       Compressors  Vertical Unit Ventilators    Burners  High Intensity Infrared Units    Sheet Metal Parts  All Products          ONE YEAR FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER  WITHIN  ONE YEAR FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION  OR WITHIN  EIGHTEEN MONTHS FROM 
63. FH for Propane gas     8 AIR 5 565 2    INSTALLATION    Table 9 1   Burner Orifice Sizing and Gas Consumption          au Type Orifice  Natural      Propane    Qty   Cfh   Orifice Drill Size   Cfh   Orifice Drill Size   Cfh   Orifice Drill Size   Cfh   Orifice Drill Size   Cfh   Orifice Drill Size   Cfh   ifice Drill Size   Cfh   ifice Drill Size   Cfh   ifice Drill Size   Cfh   ifice Drill Size   Cfh   ifice Drill Size   Cfh   ifice Drill Size   Cfh   ice Drill Size   Cfh   ice Drill Size   Cfh   ice Drill Size   Cfh   ifice Drill Size   Cfh   ifice Drill Size   Cfh   ice Drill Size             m    175       9       9    9          Q    Q       500                                      es             eS  Q                 Q                      Based on natural gas properties of 1040 Btu Cu  Ft  and specific gravity of 0 60      Based on propane gas properties of 2500 Btu Cu  Ft  and specific gravity of 1 53      Model sizes 500 800 contain 2 furnaces  Values shown are per furnace      Model sizes 840 960 contain 3 furnaces  Values shown are per furnace     AIR 5 565 2    INSTALLATION    Considerations for Elevation    The standard ratings for Models IBG ICG and IBP ICP are  certified for elevations up to 2000 feet above sea level   Operation at elevations above 2 000 feet requires ratings be  reduced 496 for each 1000 feet above sea level per ANSI  Z223 1  The exception is for units in Canada  CSA requires that  ratings be reduced 1096 for elevations between 2 001 and 4500 
64. Figure 8 1      5  When Pressure Leak testing  pressures above 14  W C    1 2 psi   close the field installed shut off valve  disconnect  the appliance and its combination gas control from the gas  supply line  and plug the supply line before testing  When  testing pressures 14  W C   1 2 psi  or below  close the  manual shut off valve on the appliance before testing        Figure 8 1   Recommended Sediment Trap Manual  Shut off Valve Installation   Side or Bottom Gas  Connection                                                                                              GAS  SUPPLY LINE GROUND  a JOINT  pA UNION  EE W  BRASS        MANUAL GAS_q SEAT        SHUT OFF VALVE  GAS b  N  SUPPLY LINE ae as  ee 14                  iL k 7   TO  Lf CONTROLS  PLUGGED  3  1 8  NPT TEST  MIN  GAGE CONNECTION  SEDIMENT  TRAP                Manual shut off valve is in the    OFF    position when handle is perpendicular  to pipe     Table 8 1   Gas Pipe Capacities   Natural Gas            Pipe Natural Gas  Length  ft  1 2  1  1 1 4                                                    Capacities in Cubic Feet per Hour through Schedule 40 pipe with maximum  0 3  W C  pressure drop with up to 14  W C  gas pressure  Specific gravity is 0 60  for Natural gas and 1 50 for Propane gas       For Pipe Capacity with Propane Gas  divide Natural gas capacity by 1 6  Example   What is the Propane gas pipe capacity for 60 feet of 1 1 4  pipe  The Natural gas  capacity is 400 CFH  Divide by 1 6 to get 250 C
65. IONS ARE SUBJECT  TO ANY MORE RESTRICTIVE LOCAL OR NATIONAL CODES     HAZARD INTENSITY LEVELS    1  DANGER  Indicates an imminently hazardous situation which   if not avoided  WILL result in death or serious injury    2  WARNING  Indicates a potentially hazardous situation which   if not avoided  COULD result in death or serious injury    3  CAUTION  Indicates a potentially hazardous situation which  if  not avoided  MAY result in minor or moderate injury    4  IMPORTANT  Indicates a situation which  if not avoided   MAY result in a potential safety concern        DANGER    Appliances must not be installed where they may be exposed  to a potentially explosive or flammable atmosphere        WARNING    1  Gas fired heating equipment must be vented   do not operate  unvented    2  a  Model IBG ICG has a built in draft diverter   additional   external diverters are not required or permitted   b  Model IBP ICP has a built in power exhauster   additional  external power exhausters are not required or permitted    3  If you are replacing an existing heater  it may be necessary to  resize the venting systems  Improperly sized venting systems  can result in vent gas leakage or the formation of condensate   Refer to the National Fuel Gas Code ANSI 2223 1 or CSA B149 1  latest edition  Failure to follow these instructions can result in  injury or death    4  For Model IBG ICG  gas fired heating equipment which has  been improperly vented  or which experiences a blocked vent  condition m
66. If the pilot does not light   purge the pilot line  If air purging is required  disconnect the  pilot line at outlet of pilot valve  In no case should line be  purged into heat exchanger  Check the pilot flame length   See Pilot Flame Adjustment     22  Once the pilot has been established  check to make sure  that the main gas valve opens  Check the manifold gas  pressure  See Main Gas Adjustment  and flame length  See  Air Shutter Adjustment  while the supply fan blower is  operating    23  Check to insure that gas controls sequence properly  See  Control Operating Sequence   Verify if the unit has any  additional control devices and set according to the  instructions in the Control Options    24  Once proper operation of the unit has been verified  remove  any jumper wires that were required for testing    25  Close the electrical compartment door    26  Replace all exterior panels     Refer to page 56 for the Start up Checklist     Pilot Burner Adjustment   The pilot burner is orificed to burn properly with an inlet pressure  of 6 7  W C  on natural gas and 11 14  W C  on propane gas   but final adjustment must be made after installation  If the pilot  flame is too long or large  it is possible that it may cause soot  and or impinge on the heat exchanger causing failure  If the  pilot flame is shorter than shown  it may cause poor ignition and  result in the controls not opening the combination gas control   A short flame can be caused by a dirty pilot orifice  Pilot flame
67. J  or K L       Max  Temp  Rise    F     120    120    120 120       Min  Temp  Rise    F     46    60 60    68 63       Max  CFM    13000 13000       Min  CFM                6481 6481               Ratings are shown for elevations up to 2000 ft  For higher elevations the input rating should be reduced at the rate of 4  for each 1000 feet above sea level   For Canada  in elevations between 2000 and 4500 feet  the unit must be derated to 90  of the rating listed above       For Variable Air Movement Applications  see page 18     28    AIR 5 565 2    GENERAL PERFORMANCE DATA    Table 29 1   Air Temperature Rise    Air Temperature Rise through Unit    F   40 45 50 55 60 65 70  CFM          75 000   60 000  100 000   80 000  125 000   100 000  150 000   120 000  175 000   140 000  200 000   160 000  225 000   180 000  250 000   200 000  300 000   240 000  350 000   280 000  400 000   320 000                                                                                  ir Temperature Rise thro nit    F           65 70 75 85       500 000   400 000 5291   600 000   480 000 6349  700 000   560 000 7407  800 000   640 000 8466  840 000 11111  960 000 12698                                                                           Ratings are shown for elevations up to 2000 ft  For higher elevations the input rating should be reduced at the rate of 4  for each 1000 feet above sea level   For Canada  in elevations between 2000 and 4500 feet  the unit must be derated to 9096 of the ra
68. L GAS    1  Open windows    2  Don   t touch electrical switches    3  Extinguish any open flame    4  Immediately call your gas supplier     FOR YOUR SAFETY    The use and storage of gasoline or other  flammable vapors and liquids in open containers  in the vicinity of this appliance is hazardous     IMPORTANT    The use of this manual is specifically intended  for a qualified installation and service agency   A qualified installation and service agency  must perform all installation and service of  these appliances     Inspection on Arrival   1  Inspect unit upon arrival  In case of damage  report it  immediately to transportation company and your local factory  sales representative     2  Check rating plate on unit to verify that power supply meets    available electric power at the point of installation     3  Inspect unit upon arrival for conformance with description of    product ordered  including specifications where applicable      THIS MANUAL IS THE PROPERTY OF THE OWNER   PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB     SPECIAL PRECAUTIONS   TABLE OF CONTENTS    SPECIAL PRECAUTIONS    THE INSTALLATION AND MAINTENANCE INSTRUCTIONS   IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE SAFE   EFFICIENT AND TROUBLE FREE OPERATION  IN ADDITION   PARTICULAR CARE MUST BE EXERCISED REGARDING THE  SPECIAL PRECAUTIONS LISTED BELOW  FAILURE TO  PROPERLY ADDRESS THESE CRITICAL AREAS COULD  RESULT IN PROPERTY DAMAGE OR LOSS  PERSONAL  INJURY  OR DEATH  THESE INSTRUCT
69. NIMUM CLEARANCE TO COMBUSTIBLE MATERIAL MASSACHUSETTS   MUN  INPUT 2 00000 sx  TE OF 585          or ni m rl D  GAGEMENT MINIMUM POUR MATI  RES COMSUSIELEI APPROVED FOR USE IN        CALORIFIQUE   Natural 400000  360000 iid en C   BY THE CHC   an  ACCEPTED BY CITY   MIN  INLET PRESS  FOR PURPOSE OF INPUT ADJ  RECOMMENDED SERVICE   CALORIEIQUE  117120  105408 24 a OF NEU YORK   PRESSION D ALTMENTATIDN EN GAZ         ADMISE  CLEARANCES   BTU HR NOV ACCESS       DEGAGEMENT DE    SERVICE RECOMMENDE  ACCESS COTE    SIDE    6 IN U C  49 kha  MANIFOLD PRESSURE    PRESSION A L   TUBULURE D ALIMENTATION    3 5muc  0 87       TEMPERATURE RISE RANGE  ELEVATION DE TEMPERATURE    20 100 _    INSTALL ON THE POSITIVE PRESSURE SIDE OF AIR CIRCULATING BLOWER   INSTALLER DU COTE DE LA PRESSION POSITIVE DU VENTILATEUR          ORIFICE 5179  DIM  DE     THIER    ACC  DEZ    Alu 10416    VENT CATEGORY          EXTERNAL STATIC PRESSURJVENT CONNECTOR   IZR    VENT CAT  GORIE  PRESSION STATIQUE EXTERIEUR         CONNECTEUR DE VENTILATION  III I  3 woe    ror 6 m m           G  N  RAL  SEULEMENT POUR   NSTALLATION INT  RIEURE  LA TEMPERATURE MINIMUM DE L AIR DEHORS    GENERAL    FOR INDOOR INSTALLATIONS ONLY   MINIMUM AMBIENT TEMPERATURE  40 F     FOR INSTALLATION DOWNSTREAM OF REFRIGERATION dinde  SYSTEMS  INSTALLER DU COT 08 L   PRESSION POSITIVE DU  VENTILATEUR     FOR UNITS WITH MANUAL RESET HIGH LIMIT  SWITCH  RESET BUTTON IS LOCATED IN  ELECTRICAL JUNCTION BOX          USA  FOR INSTALLATIONS AB
70. OVE 2000 FEET   DERATE 4 PERCENT FOR EACH 1000 FEET OF  ELEVATION ABOVE SBA LEVEL     THIS APPLIANCE REQUIRES A SPECIAL VENTING  SYSTEM  REFER TO INSTALLATION INSTRUCTIONS  HO  5 564 FOR PARTS LIST AND METHOD OF  INSTALLATION     POUR APPAREILS AVEC INTERRUPTEUR REMIS  MANUEL HAUT LIMITE  REMISE BST SITU  E DANS  LA BO  TE JUNCTION  SLECTRIQUE  POUR REMBTTRE  PRESSER LE BOUTON     CET APPAREIL N  CESSITE UN SYST  ME  D   VACUATION SP  CIAL  LA M  THODE  D INSTALLATION ET LA LISTE DES PIRCES  N  CESSAIRES FIGURENT DANS LES INSTRUCTIONS    1     DUTPUT BTU HR  320009  268000  23    1  OPEN ALL GAS VALVES  TURN ON POWER   2  SET  THERMOSTAT TO DESIRED SETTING                           CINIBCIOR 5  CONNECTEUR       D AERATIDN    DESIGN COMPLIES WITH DUCT FURNACE STANDARD     om  CSA 2 6 2013  ca ANSI 283 8 2013              372 01                  NON COT    D ACCES   AIR THROUGHPUT  DEBIT D AIR                             MIN VARIABLE SPEED       5H80581B    INSTRUCTIONS D ALLUMAGE  1  DUVRIR TOUTES LES ROBINETS A GAZ   DONNER LE COURANT     2  REGLER LE THERMOSTAT SUR LA POSITION  DESIREE     REFERREZ AU MANUAL D INSTALLATION ET  DE SERVICE POUR PLUS D  INSTRUCTIONS      POUR APPAREILS AVEC DEUX PHASES  MODULATION MECHANIQUE  QU APPAREILS DE  CONTR  LE DE GAZ   LECTRIQUES MODULES  UN  AIR CONTR  LEUR D  CHARGE INSTALL      LA  MANUFACTURE  BY THERMOSTAT DE CHAMBRE  N EST PAS INCLUS     INSTRUCTIONS DE FER METURE     LIGHTING INSTRUCTIONS    18S08HS    REFER TO INSTALLATION AND 
71. SERVICE  MANUAL FOR MORE INSTRUCTIONS      FOR UNITS WITH TWO STAGE  MECHANICAL  MODULATION  OR ELECTRONIC MODULATING  GAS CONTROLS  A FACTORY DISCHARGE AIR  CONTROLLER AND NO ROOM THERMOSTAT  INCLUDED     SHUT DOWN INSTRUCTIONS   TURN OFF POWER  amp  CLOSE ALL GAS VALVES     1 COUPER LE COURANT ET FERMER TOUTES LES  ROBINETS    GAZ        COMMON REPLACEMENT PARTS 5H080687  FOR PARTS ORDERING  contdct the parts wholesaler or the manufacture 5  080689  representative serving your area  WHEN INQUIRING ABOUT PARTS    1       5  71675   provide model number  serial number  description and part number  ibH79441   ordering parts  provide part number listed  FOR SERVICE  contact yd5H73598   local qualified installation and service contractor or appropriate 118  80563     Comb  Gas Valve 5H71956 1 Ctrl Transformer  Ignition Control 3H37454 1 Pilot Replace Kit  TD1 Relay 3H37398 11 Heat Exch  Kit   3 Pressure Switch 3  35628 6 Burner Kit   1 Power Exhauster 5  71790  Optional TDR   4 Wiring Diagram       54 AIR 5 5    65 2       MODEL DESIGNATIONS    Figure 55 1   Model Identification Plate       MODEL IDENTIFICATION PLATE     Model Number     Serial Number   IBP75AFRHN10A1AA1AAA1A    MOTOR DATA   Voltage  Hertz     Phase  Amps    SYSTEM DATA   Supply Voltage   Hertz  Phase  Max System Amps  Fuse Size  Time Delay        Time Delay Relay    COMMON REPLACEMENT PARTS    For parts ordering  contact the parts wholesaler or the manufacturer s representative serving your area     A complete 
72. ances should two sections  of double wall vent pipe be joined together within one horizontal  vent system due to the inability to verify complete seal of inner  pipes     General Venting Instructions   1  Installation of venting must conform with local building codes   or in the absence of local codes  with the National Fuel Gas  Code  ANSI 2223 1  NFPA 54    Latest Edition  In Canada   installation must be in accordance with CAN CGA B149 1 for  natural gas units and CAN CGA B149 2 for propane units    2  To determine the Venting Category of the unit being installed   refer to Table 5 1     Table 5 1   Venting Category Determination    Venting Vent Configuration  Category  IBG ICG Vertically vented units only     lo Vertically vented units only   IBP ICP            Horizontally vented units only          Vent is negative pressure  non condensing  Follow standard venting requirements     Vent is positive pressure  non condensing  Vent must be gastight     3  For units vented as Category I  refer to Table 5 2 for vent  sizing  Vent sizing for units vented as Category Ill are covered  in a later section on page 7  Do not use a vent pipe smaller  than the size of the outlet or vent transition of the appliance   The pipe should be suitable corrosion resistant material   Follow the National Fuel Gas Code for minimum thickness  and composition of vent material  The minimum thickness for  connectors varies depending on the pipe diameter     Table 5 2   Category    Minimum Vent Pipe S
73. arly inspect and clean the    cooling coil cabinet  condensate drain pan  and trap drain  System to ensure proper function       Depending on climate  freeze protection of the trap may be    required during non cooling days     Cooling Coil Maintenance    1     2     C    Periodically  inspect the coil for signs of corrosion and leaks   Repair and replacement of the coil and the connecting piping   valves  etc   must be performed as needed by a qualified  technician     Should the coil surface need cleaning  caution should be  exercised in selecting the cleaning solution as well as the  cleaning equipment  Improper selection can result in damage  to the coil and or health hazards  Cleaning solutions must not  be corrosive or cause damage to copper tube aluminum fin  coils  Clean the coil from the leaving air side so that foreign  material will be washed out of the coil rather than pushed  further in  Be sure to carefully read and follow the cleaning  fluid manufacturer s recommendations before using any  cleaning fluid       For DX coils  replace the filter dryer s  as needed     For chilled fluid coils     a  Maintain the circulated fluid free of sediment  corrosive  products and biological contaminants    b  Freeze Protection   During the winter  chilled water coils  need to be protected against freezing  Two common  methods are 1  blowing out the coils with air  or 2   flushing coils with inhibited glycol designed for corrosion  protection in HVAC applications  Select an i
74. at with remote temperature set point  adjuster    The sequence of operation for Electronic Modulating Gas  Controls   Master Slave is the same as Electronic Modulating  Gas Controls   Single Furnace  The modulating amplifier sends  an equal voltage signal to all of the modulating gas valves so  that they modulate at the same percentage  between 40  and  100  full fire     Electronic Modulating Control  Digit 12 7  or 8     For control of multiple electronic modulation units for BMS  control  each furnace would be individually controlled  Refer to  the section for Single Furnace Controls  Electronic Modulation  Control  Digit 12 7 or 8      Variable Air Movement Applications    Units may be supplied with variable frequency drives for  applications where variable air volume is required  The minimum  air flow may be varied between 30 and 100  of the full speed  air flow depending on the controls selection of the unit  Due to the  extra restrictions of the controller all selections must be performed  with the AccuSpec configuration software  Within AccuSpec  three  variable frequency drive speed control changeover options are  available    1  Two speed which may be controlled by a manual high low  Switch which may be factory mounted on the control panel or  shipped loose for field installation or by exhaust fan  interlocks    2  Floating building pressure sensing which utilizes a photohelic  pressure controller to adjust the building pressure by  varying the amount of makeup air 
75. ay have flue gases accidentally spilled into the heated  space  See page 53 for specific information about the blocked  vent safety switch supplied on the unit    5  For Model IBP ICP  under no circumstances should two sections of  double wall vent pipe be joined together within one horizontal vent  system due to the inability to verify complete seal of inner pipes    6  All field gas piping must be pressure leak tested prior to operation   Never use an open flame  Use a soap solution or equivalent for  testing    7  Gas pressure to appliance controls must never exceed 14  W C    1 2 psi     8  Disconnect power supply before making wiring connections to  prevent electrical shock and equipment damage    9  All appliances must be wired strictly in accordance with wiring  diagram furnished with the appliance  Any wiring different from  the wiring diagram could result in a hazard to persons and  property    10  To reduce the opportunity for condensation  the minimum sea  level input to the appliance  as indicated on the serial plate   must not be less than 5  below the rated input  or 5  below  the minimum rated input of dual rated units    11  Ensure that the supply voltage to the appliance  as indicated on  the serial plate  is not 5  greater than the rated voltage    12  Any original factory wiring that requires replacement must be  replaced with wiring material having a temperature rating of at  least 105  C    13  When servicing or repairing this equipment  use only factory 
76. ay require the removal of the manifold  see Manifold Assembly  Removal      Adjusting the primary combustion air is achieved by resetting  the primary air shutters  See Figure 50 2   Prior to flame  adjustment  operate duct furnace for about fifteen minutes  The  main burner flame can be viewed after loosening and pushing  aside the gas designation disc on the side of the burner box    1  To increase primary air  loosen the air shutter set screws and  move the air shutters closer to the manifold until the yellow  tipped flames disappear and a clean blue flame with a well  defined inner cone appears     2  To decrease primary air  move the air shutters away from the  manifolds until flames no longer lift from burner ports  but  being careful not to cause yellow tipping     3  Re tighten set screws after adjustment     AIR 5 565 2 15       START UP PROCEDURE    Blower Adjustments    If blower fan speed changes are required  adjust motor sheave  as follows     1  Refer to page 33 to determine correct blower speed  according to job requirements  then proceed with steps 2  through 8    2  Loosen motor base and take belt off of motor sheave    3  Loosen set screw on outer side of adjustable motor sheave     Figure 16 1   Motor Sheave Adjustment            Set Screw    Toward Motor       Adjustable Half  of Sheave                 4  Turn outer side of motor sheave clockwise until motor  sheave is fully closed    5  From fully closed position  turn outer side of motor sheave  counter
77. bination gas control closed and no spark  After six minutes   the cycle will begin again  After three cycles  some ignition  controllers lockout for approximately one hour before the cycle  begins again  This will continue indefinitely until the pilot flame is  sensed or power is interrupted to the system     Note  Gas Control Options  see page 19  could change the  listed sequence of operation based on their function   The descriptions given are for the basic duct furnace     Single Furnace Controls    Staged Control  Digit 1221 or 2    These units utilize a single  or two stage combination gas valve   an ignition control  and a low voltage thermostat     Electronic Modulating Control  Digit 12 4  7  or 8     These units utilize a single stage combination gas valve  an   electronic modulating gas valve  a modulating amplifier  an   ignition control  and one of the following      Modulating room thermostat       Modulating duct thermostat with remote temperature set point  adjuster     Building Management System  BMS  signal by others  an  inverted signal where 0 VDC or 4 mA is high fire and 10 VDC  or 20 mA is low fire      The control operating sequence for all units is as follows     1  The thermostat calls for heat  For BMS controlled units  the  BMS closes a heat enable contact at the unit    2  Model IBP ICP only   The power exhauster relay is  energized starting the power exhauster motor  Once the  motor has reached full speed  the differential pressure switch  closes 
78. ccuSpec for line size diameters   Q Dual Circuit DX coils have 2 each Suction Line and Liquid Lines  Refer to AccuSpec for line size diameters     Figure 47 2   Chilled Water Coil Drawing  All dimensions in inches        350 400                         DX   Dual Circuit       23                                                                                   Airflow Direction  V Rows 4   6     W  75  TOP VIEW   gt  W  lt   L   lt   Eb  lt  1 5 15    Y 18    gt    eo Return Water Line     o  s 29 Connection turned 90   in  direction of airflow  2d EE  Coil for Right Hand Units 225   Digit 9       FE    Airflow     sipe VIEW  Headers on opposite side for Direction  Left Hand Units    FRONT VIEW   2 25 Supply Water Line    Connection turned 90   in     4    direction of airflow  v 1  k            I  gt   1 8       Table 47 2   Chilled Water Coil Dimensions    Model Size    75    Supply Line    1 50 MPT    Return Line    1 50 MPT       100 125    1 50 MPT    1 50 MPT       150 175    1 50 MPT    1 50 MPT       200 225    1 50 MPT    1 50 MPT       250 300    1 50 MPT    1 50 MPT       350 400                            AIR 5 565 2    1 50 MPT          1 50 MPT    47    DIMENSIONS WEIGHTS    Figure 48 1   Remote Panel Dimensions Table 48 3   Remote Panel Dimensions   All dimensions in inches        Remote Panel Type  Light and Switch Panels Only  Light and Switch Panels with Single Stage    Thermostat or Electronic Set Point Adjustor    Light and Switch Panels with  Two Stage The
79. ce or field labor participation  Seller will not honor any expenses  incurred in its behalf with regard to repairs to any of Seller s products  No  credit shall be issued for any defective part returned without proper written  authorization  including  but not limited to  model number  serial number   date of failure  etc   and freight prepaid     OPTIONAL SUPPLEMENTAL WARRANTY   Provided a supplemental warranty has been purchased  Seller extends the  warranty herein for an additional four  4  years on certain compressors   Provided a supplemental warranty has been purchased  Seller extends the  warranty herein for an additional four  4  years or nine  9  years on certain  heat exchangers     EXCLUSION OF CONSUMABLES  amp  CONDITIONS BEYOND SELLER S  CONTROL   This warranty shall not be applicable to any of the following items  refrigerant  gas  belts  filters  fuses and other items consumed or worn out by normal wear  and tear or conditions beyond Seller s control  including  without limitation as  to generality  polluted or contaminated or foreign matter contained in the air or  water utilized for heat exchanger  condenser  cooling or if the failure of the part  is caused by improper air or water supply  or improper or incorrect sizing of  power supply            APPLICABLE WARRANTY PERIOD     Heat Exchangers  Gas Fired Units except MPR Models    TEN YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER  WITHIN  TEN YEARS FROM DATE OF RESALE BY BUYER OR ANY OTH
80. ch    For instructions on common venting refer to the National   Fuel Gas Code    The vent must terminate no less than 5  above the vent   connector for Category   vent systems    A unit located within an unoccupied attic or concealed space   shall not be vented with single wall vent pipe    Single wall vent pipe must not pass through any attic  inside   wall  concealed space  or floor    Do NOT vent Model IBP ICP units into a masonry chimney    Model IBG ICG units can be vented into a masonry chimney   if the following requirements are met    a  Do not vent a Category   unit into a common vent with  mechanical draft systems operating under positive  pressure  Category Ill or IV units     b  When connecting a vent to an existing chimney  do not  push the vent pipe beyond internal surface of chimney    c  When venting into a common vent  the area of the  common vent should be equal to or greater than the  area of the largest vent plus 50 percent of the area of all  additional vents    d  When venting into a common vent  the individual vents  should enter at different levels     Figure 6 1   Vertical Category   Vent System            10 FEET OR LESS  TO ROOF PEAK NAE          2 FEET MINIMUM       ROOF PITCH IS  L      x112 USE LISTED  THIMBLE  THROUGH   ROOF           H  FEET MINIMUM  PER TABLE 6 1        ROOF  FLASHING       MAINTAIN MINIMUM  CLEARANCE TO  COMBUSTIBLES                               12  MINIMUM  H     SLOPE PIPE UP  1 4  PER FOOT  TOWARD DRIP LEG        DISTANC
81. changer Burner Drip Pan Material   S     4  Determine the Development Sequence   From item  8 in Selection Example Conditions  the  modulating gas controls result in the Development  Sequence   M    5  Determine the Access Side   From item  5 in Selection Example Conditions  the Right  Hand Gas controls result in the Access Side   R    6  Determine the Air Temperature Rise   From item Z2 in Selection Example Conditions  the Air  Temperature Rise is 60  F  70  F   10  F   However  using  the output capacity of the IBP400   5000 cfm  the resulting  temperature rise is 59 3  F  320 000  5000 x 1 08    Since  the rise is less than 60  F  the air baffle must remain in place    7  Determine the Gas Type   From item  7 in Selection Example Conditions  the Natural  Gas results in the Gas Type  N    8  Determine the Gas Valve     From item  8 in Selection Example Conditions  the  Electronic Modulating with Duct Sensing results in the Gas  Valve   4     9  Determine the Additional Safety Switches     Since no additional safety switches were specified  the  Additional Safety Switches   0     AIR 5 565 2    UNIT SELECTION    10     11     12     Determine the Supply Voltage     From item  9 listed above  the 460V 60Hz SPh results in the  Supply Voltage   F     Determine the Transformer     For IBP ICP models  a 75VA Transformer is required  Thus   the Transformer   2     Determine the Blower Size and Bearing Type    Using Table 29 1  the Model Size 400 has three available   blowers for w
82. clockwise until the proper number of turns open are  achieved    6  Retighten motor sheave set screw  replace belt and retighten  motor base  Motor base should be shifted for proper belt  tension which is 3 4  deflection with about 5 Ibs  of force     Figure 16 2   Belt Tension Adjustment          3 4  deflection  with 5 Ibs  of force             7  Recheck blower rpm after adjustment   NOTE  Do not fire unit until blower adjustment has been  made or unit may cycle on high limit control    8  Check motor amps  Do not exceed nameplate amps shown  on motor nameplate     Lubrication Recommendations    The blower can be provided with either spider or pillow block  bearings  Spider bearings are permanently lubricated and do not  require lubrication  Pillow block bearings are shipped greased  from the factory but will require lubrication  The bearings should  be checked and lubricated before each heating season but a  more frequent lubrication schedule may be required based on  the environment in which the unit is installed  and the frequency  of the equipment operation  Shell Alvania Z2 lubricant is  recommended     Damper Linkage Adjustment    If the unit is provided with a return air damper  to prevent   shipping damage  the return air damper linkage is disconnected   and the damper closed  Before operating the unit  the fresh and   return air dampers must be connected  This is accomplished by   the following    1  The damper actuator should be de energized and the fresh  air da
83. crated with  Skid supports below the unit  The unit may be lifted from the  bottom by means of a fork lift or other lifting device only if the  shipping support skids are left in place  DO NOT attempt to lift  the unit from the bottom unless the shipping skid supports are  still in place  When lifting units  make sure the load is balanced   All extended cabinet systems are shipped without a crate and  cannot be lifted with a fork truck  Use a crane or other overhead  lifting device in conjunction with the lifting holes  refer to page  46 for base rail lifting hole locations  for safe unit relocation  If  the unit must be lifted from the bottom for final installation of the  unit be sure to properly support the unit over its entire length to  prevent damage     UNIT MOUNTING   Be sure the method of unit support  suspension or floor  mounting  is adequate to support the weight of the unit  see  Weights for base unit and factory installed option weights   For  proper operation  the unit must be installed in a level horizontal  position  Combustible material and service clearances as  specified in Figure 3 1 and Tables 3 2 and 3 3 must be strictly  maintained  To assure that flames are directed into the center of  the heat exchanger tubes  the unit must be level in a horizontal  position  Use a spirit level to ensure that the unit is suspended  or floor mounted correctly     Unit Suspension   3 4  diameter suspension hanging locations are provided in   the base rail assembly of t
84. ct furnace are in operation  check  to be sure the blower has been set to the proper rpm for  the application  Refer to page 16 for Blower Adjustments    4  Start up and adjustment procedures should be performed  by a qualified service agency    5  To check most of the Possible Remedies in the trouble   shooting guide listed in Table 51 1 on pages 51 52  refer  to the applicable sections of the manual                    Table of Contents    Inspection on                                                   1  Special Precautions  no ates eese mero ck wh E 2  SI  Metric  Conversion Factors                              3  Unit Location    2      my m mde RR 3  Combustible Material and Service Clearances              3  Unit Lifting and Unit Mounting                               4  Unit Installation    onm ro edet e RUE      5  Duct lnstallatiori                garda dra mend Rr DRE SK achkan 5                 mE                mm 5  Gas Connections                                     8  Connections for                                            10  Electtical Connections  555529 weg RE        IRR RS 11  Cooling Coil Specifications and Installation                12  Start Up Procedure          cites ek y TR Eck RUP hte oen 14  Pilot Burner Adjustment                               14  Main Burner                                                  15  Blower                                                    16  Lubrication                                                      16  Con
85. d servicing      55  Differential Pressure Switch   A differential pressure switch is supplied on all power vented  duct furnaces and is designed to prevent operation of the main  burner in the event there is improper venting through the vent  System  This may occur due to a restricted vent  inadequate  vent draw  uninsulated vent pipe in cold ambient or long vent  runs  excessive vent diameter  restricitve vent terminal  negative  pressure within space  etc  See Troubleshooting section for  more information      Not Shown  Circuit Analyzer      OPT    The circuit analyzer is factory installed on the door of the  electrical section  The circuit analyzer is used to quickly assist  service personnel in troubleshooting by monitoring the unit firing  sequence and vital operating steps  Lights will come on as a  point of electrical operation is passed and proven  If any light is  not lit  that is the point where failure occurred     Figure 26 1   Circuit Analyzer  Circuit analyzer tagging will vary based on the unit ordered   Circuit analyzer shown is for reference only                 V2          26 AIR 5 565 2       THIS PAGE INTENTIONALLY LEFT BLANK    AIR 5 565 2    27    GENERAL PERFORMANCE DATA    Table 28 1   General Performance Data   Models With Blower    Model Size  Digits 4 6        Btu Hr Input       125 000    150 000    175 000       Btu Hr Output  D    100 000    120 000    140 000       Blower Style  Digit 16 Letter     Cor D    Eor F Cor D Eor F    Cor D Eor F    
86. del has been determined  the additional  options and accessories outlined on pages 19 26 can be added  to the unit     AIR 5 565 2 31    OPTION  amp  ACCESSORY PRESSURE DROP DATA    Table 32 1   Option  amp  Accessory Pressure Drop Tables  in  W C         Unit  Size    75    100 125    150 175    200 225    250 300  500 600    350 400  700 800  840 960    Digit 16    A B C D    C D E F    C D E F    C D E F G H    E F G H    LJ K L    E F G H    IJ  K L                                                                                                                                                                                                                                                                All Units Weatherproof Unit Only         gt    8 8 8    s       5 c 5 5 o           m 2   Es 89   832           Pg   5 iS 86  88 pz s gt                E  crm       NE GE AE as HER           a5  556 0 01 0 01 0 02 0 03 0 02 0 07 0 00 0 01 0 00  600 0 01 0 01 0 02 0 03 0 02 0 07 0 00 0 01 0 01  800 0 02 0 01 0 03 0 04 0 04 0 12 0 01 0 02 0 01  1000 0 02 0 02 0 04 0 05 0 06 0 17 0 01 0 03 0 01  1200 0 03 0 02 0 05 0 06 0 08 0 22 0 02 0 03 0 01  1400 0 03 0 03 0 06 0 07 0 11 0 29 0 03 0 04 0 02  1600 0 04 0 04 0 07 0 09 0 15 0 36 0 04 0 06 0 02  1800 0 04 0 04 0 08 0 10 0 19 0 44 0 05 0 07 0 03  2000 0 05 0 05 0 10 0 11 0 23 0 53 0 06 0 08 0 03  2300 0 06 0 07 0 11 0 13 0 31 0 68 0 08 0 11 0 04  2778 0 08 0 09 0 15 0 16 0 45 0 96 0 12 0 15 0 06  741 0 01 0 02 0 02 0 02 0 02 0 08 
87. dun  MODINE    AIR 5 565 2    5H0806450000       August  2015    AIREDALE       INSTALLATION AND SERVICE MANUAL  gas fired indoor gravity and power vented duct furnace make up air units                   Model ICP          A WARNING      Improper installation  adjustment  alteration   service or maintenance can cause property  damage  injury or death  and could cause  exposure to substances which have been  determined by various state agencies to  cause cancer  birth defects or other  reproductive harm  Read the installation   Operating and maintenance instructions  thoroughly before installing or servicing this  equipment      Installing  starting up and servicing heating   ventilation and air conditioning equipment  poses significant hazards and requires  specialized knowledge of Modine products  and training in performing those services   Failure to have any service properly  performed by  or making any modification  to Modine equipment without the use of   qualified service personnel could result in  serious injury to person and property   including death  Therefore  only qualified  service personnel should work on any  Modine products           models IBG ICG  IBP ICP             LISTED    Intertek  IBP ICP models approved for use in California by the CEC        CAUTION    To prevent premature heat exchanger failure  do not locate ANY gas fired units in areas  where chlorinated  halogenated  or acid  vapors are present in the atmosphere     FOR YOUR SAFETY    IF YOU SMEL
88. e  such as material distortion or discoloration   could result       Avoid venting through unheated space  When venting does    pass through an unheated space  insulate runs greater than  5 feet to minimize condensation  Inspect for leakage prior to  insulating and use insulation that is noncombustible with a  rating of not less than 350  F  Install a tee fitting at the low  point of the vent system and provide a drip leg with a clean  out cap as shown in Figure 6 1       When the vent passes through a combustible wall or floor  a    metal thimble 4 inches greater than the vent diameter is   necessary  If there is 6 feet or more of vent pipe in the open   space between the appliance and where the vent pipe   passes through the wall or floor  the thimble need only be 2   inches greater than the diameter of the vent pipe  If a thimble   is not used  all combustible material must be cut away to  provide 6 inches of clearance  Any material used   to close the opening must be noncombustible      Do NOT use dampers or other devices in the vent pipes      Precautions must be taken to prevent degradation of   building materials by flue products    For category   vent systems the outlet of the vent should   extend as shown in Figure 6 1 and Tables 6 1 and 6 2    Use a listed vent terminal to reduce downdrafts and moisture   in vent  For model IBG ICG  a vent terminal that is very open   will avoid spillage at unit s diverter relief opening and tripping  of the blocked vent safety swit
89. e field installed manual shut off valve to the  OFF   position    2  Remove the 1 8  pipe plug in the pipe tee or gas valve and  attach a water manometer of  U  tube type which is at least  12  high    3  Move the field installed manual gas shut off valve to the   ON  position    4  Create a high fire call for heat from the thermostat     5  Determine the correct high fire manifold pressure  For  natural gas 3 5  W C   for propane gas 10  W C  Adjust the  main gas pressure regulator spring to achieve the proper  manifold pressure  for location  see the combination gas  control literature supplied with unit     6  Iftheunit has Electronic Modulation gas controls  determine  from the Model Identification Digit 12   the low fire gas  pressure needs to be adjusted  Using Figure 15 2 for item  number locations  this is accomplished as follows    a  Disconnect power     b  Remove all wires from Maxitrol Amplifier terminal  3  or  duct furnace terminal  43   if available     c  Turn on power at the disconnect switch    d  Remove the maximum adjustment screw  4   spring   b   and plunger  8   A small magnet is useful for this  purpose  CAUTION   The plunger is a precision part   Handle carefully to avoid marring or picking up grease  and dirt  Do not lubricate    e  Using minimum adjusting screw  9   adjust low fire  manifold pressure to 0 56  W C  for natural gas and  1 6  W C  for propane gas    f  Replace plunger and spring retainer  spring  and  maximum adjusting screw in proper 
90. e trip  condition is indicated by a red color in the trip indicator window   The motor starter can be placed in the automatic or manual  reset positions  Automatic reset is accomplished by depressing  the  RESET  button and turning the button 1 4 turn  When in the  automatic reset position  if the overload module trips  the module  will reset itself once the overload relay has cooled  In the manual  reset position  if the overload module trips  the  RESET  button  must be depressed before the blower can operate     The contractor module includes one  1  normally open auxiliary  contact  The contact rating is 10 amps     If the factory installed motor starter option was not ordered with a  unit that has a three phase motor or single phase motor 1 1 2 Hp  or greater  a motor starter must be field supplied and installed     Figure 25 2   Motor Starter                                                                                                                               bord  CONTACTOR  MODULE             TRIP  INDICATOR  CURRENT          J WINDOW  SETPOINT  pa  amp g   mo      RESET  ees LI LULA 1     OVERLOAD Fe  MODULE         GG 6 9  8 8 8                       42  Proportional Temperature Controller      OPT    A proportional temperature controller is provided with Air Control  options GG  GH  GK or GM  Digits 20  amp  21  and factory installed  in the electrical section  The controller compares the mixed   air temperature set point and the mixed air temperature from  
91. ement  Tables 36 1 through 37 5 2  Locate the unit Model Identification Plate and note Digit 16  give the Sheave Assembly numbers used on units that include a and Digit 19 of the model number  Digit 16 is the Blower  blower  The Sheave Arrangement is Digit 19 and is found on the Size and Type and Digit 19 is the Sheave Arrangement   unit Model Identification Plate  The Sheave Assembly describes 3  Once the Blower Size and Type  Digit 16  is known  enter  the motor and blower sheave size and bore as well as the belt the proper Sheave Arrangement table   provided  4  Use the Sheave Arrangement  Digit 19  to determine the    Sheave Assembly provided   To determine how many turns open the motor sheave should be  set for  y P 5  Use Table 38 1 and the Sheave Assembly number to  determine the required turns open to achieve the  1  Follow the Selection Procedure found on pages 30 31 desired blower rpm   to determine what blower rpm is required to meet the job 6  Set the motor sheave as described in Blower Adjustments   specifications   Figure 36 1   Blower Section  EXTENDED ADJUSTABLE FILTER  GREASE MOTOR RACK  LINES SHEAVE            EXTENDED    T   GREASE LINE  ZERK FITTINGS    1 4  PERIMETER  GASKETED  BLOWER  CONNECTION       CONVENIENCE  OUTLET                BLOWER DOOR BOTTOM  SAFETY SWITCH SUPPORTED  BLOWER AND   MOTOR       DIRECT  DRIVE  DAMPER  ACTUATOR       Blower Sheave Assembly Numbers  Table 36 1   Digit 16 2 A or B  9 7 Blower Units   RPM Range       Motor Frame 656
92. emove the residual  heat from the heat exchanger  For single phase units below 1 1 2  Hp  the time delay relay controls the motor directly  For single  phase units 1 1 2 Hp and greater and all three phase units  the  time delay relay controls the motor starter      10  Furnace Low Voltage Terminal Strip      STD    The furnace low voltage terminal strip is located in the duct  furnace electrical junction box  The terminal strip is labeled   to match the electrical wiring diagram provided with the unit   Low voltage labeling ranges from terminal numbers 1 to 79  All  field wiring connections should be made to the top side of the  terminals to prevent miswiring by modifying the factory wiring  which is made to the bottom of the terminal strip      12  Furnace Supply Power Terminal Strip      STD    The furnace supply power terminal strip is located in the duct  furnace electrical junction box  The terminal strip is labeled   to match the electrical wiring diagram provided with the unit   Supply power labeling ranges from terminal numbers 80 to 99   All field wiring connections should be made to the bottom side  of the terminals to prevent miswiring by modifying the factory  wiring which is made to the top of the terminal strip      13  Control Step Down Transformer    STD    The control step down transformer is located in the duct furnace  electrical junction box  The transformer is used to step down  the supply power  115V  208V  230V  460V  575V  to 24V  This  transformer is 
93. en     Figure 49 1   Filter Replacement Arrangement for  Blower Size  Digit 16  A  B  C  D  E  F  G and H    FILTER SPACER          Sy  75 100 125 150 175    FILTER SPACER    200 225 250 300 er     500 600       20  X 25  FILTER 700 800  B   16  X 25  FILTER  C   15  X 25  FILTER  Filter Spacer to be inserted on non access side of unit                Figure 49 2   Filter Replacement Arrangement  for Blower Size  Digit 16      J  K  and L                     NON ACCESS NON ACCESS    SIDE  FILTER    SPACER FILTER    SPACER       20   25        16    25      C   20  x 16  700800  500 600 D   15  X 25  840 960       Cooling Coil Drain Pan and Drain System    The drain pan  trap  and drain pipe must be cleaned regularly to  avoid blockage that can reduce or stop water flow as follows     1      At the beginning of the cooling season  inspect and clean    the entire cooling coil cabinet and condensate drain pan to  remove contaminants       Inspect and clean the condensate drain trap and piping  The    use of a cleanout opening at the top of the trap can help  facilitate this maintenance       Fill the trap with water to ensure proper operation and replace    the cap on the cleanout opening to close the system       During the end of cooling season shutdown of the system     disconnect and remove all water from the trap and drain to  prevent freeze damage  If local building codes permit  the trap  may be filled with an antifreeze solution       If the unit is used year round  regul
94. entage of outside air  The minimum  positioner dial is manually set between 0 to 100  resulting in a  2 to 10 VDC signal being sent to the damper actuator  When  used in conjunction with the Proportional Temp Controller  the  positioner sets the minimum outside air percentage and the  Proportional Temp Controller then modulates between the  minimum position and 10096 outside air     Figure 21 2   Minimum Positioner                   AIR 5 565 2 21    OPTIONS     20  21  Extended Grease Lines      OPT     The extended grease lines  21  are factory installed in the blower  section and include Zerk   grease fittings  20  factory installed on  the exterior corner post between the electrical and blower  sections  This option allows the pillow block bearings to be  lubricated with a grease gun without requiring the service  personnel to remove both blower doors to access the bearings   Refer to Lubrication Recommendations for lubricant  recommendations      22  Return Air Fire Stat      OPT     The return air fire stat is factory installed in the electrical section  with the sensor in the return air stream  In case of elevated  temperatures in the return air stream  the manual reset switch  shuts down the entire unit  If the limit temperature is exceeded    a service person must inspect the unit for the cause of the high  discharge temperature  take corrective action  and then reset the  switch      23  Blower Housing    STD     The blower housing is factory installed in the blower
95. er and pilot assembly for cleanliness and     or obstructions as necessary  see Duct Furnace for cleaning  instructions        Replace the burner assembly in reverse order  In replacing    the burner  be certain that the rear burner slots are located  properly on the burner retaining pins  Do not force the burner  side access panel  it will not fit if the burner is not properly  aligned       Reconnect the ignition cable and pilot gas supply line     Turn on the electric and gas supply     Figure 50 2   Burner and Pilot Assembly Removal          AIR SHUTTERS    NOT SHOWN    ARE LOCATED  ON THE    MANIFOLD        PILOT  ASSEMBLY    IGNITION  CABLE          50 AIR 5 565 2    SERVICE  amp  TROUBLESHOOTING    Table 51 1   Troubleshooting    Trouble    Power Exhauster Motor will not start   Models IBP ICP only     Possible Cause    1  Power supply is off    2  No 24V power to thermostat    3  Thermostat malfunction    4  Defective power exhauster relay   5  Defective power exhauster motor     Possible Remedy    1  Turn on main power    2  Check control transformer    3  Check replace thermostat    4  Replace power exhauster relay   5  Replace power exhauster motor        Pilot does not light stay lit    Main burners do not light  Pilot is lit     Lifting Flames  See Figure 52 1     Yellow Tipping   With propane gas  some yellow tipping  is always present      Flashback    Floating Flames  See Figure 52 2     Flame Rollout  See Figure 52 3        Bom    10     omn ON            _  
96. er is disconnected to all unit wiring electrically  following the switch  See Warning   For servicing the unit  the  disconnect switch can be manually overridden by using a wrench  and turning the disconnect switch shaft 90   clockwise  See  Figure 21 1   Fusible and circuit breaker switches available    For fusible switches  Class    J    time delay fuses must be field  provided matching the fuse size listed on the Model Identification  plate     Figure 21 1   Dead Front Disconnect Switch Assembly       BLOWER SECTIO   ELECTRICAL   COMPARTMENT   ACCESS DOOR            DISCONNECT    SWITCH HANDLE  OPERATION  INSTRUCTION  LABEL    BLOWER SECTION  ELECTRICAL  COMPARTMENT  STAND OFF PANEL    DISCONNECT      SWITCH HANDLE   SHOWN IN THE    ON  POSITION    SUPPLY POWER  NG TERMINALS   SEE WARNING        z       DISCONNECT      SWITCH HANDLE  SHOWN IN THE   OFF  POSITION              17  Step Down Transformer Fuses      OPT   The transformer fuses are factory installed in the electrical section   The fuses are included to protect the transformer  Fuses included      18  Step Down Transformer      OPT    The step down transformer is factory installed in the eletrical  section  The transformer is required for power exhausted units  with a supply voltage of 460V 3Ph and 575V 3Ph      19  Factory Installed Minimum Positioner      OPT    The factory installed minimum positioner is installed in the  electrical section and is used with a modulating damper actuator  to set the minimum perc
97. er supports are factory installed in the blower section   The blower supports are used to rigidly support the weight of the  blower and motor during operation and shipping      37  Convenience Outlet      OPT     A WARNING    Do not perform service on the convenience outlet without    disconnecting its power supply  The convenience outlet  power supply is separate from main power supply to the  unit  When the main disconnect switch is de energized   the convenience outlet power supply remains energized        The convenience outlet is factory installed in the blower section  for providing power for 115V service equipment  trouble light   power tools  etc    The 115V ground fault circuit interrupter   GFCI  is rated for 15 amps and includes test and reset  Switches  A separate field supplied 115V 1Ph power supply must  be routed through the electrical section wall into the back of the  convenience outlet junction box      38  Blower Door Switch      OPT    The blower door switch is factory installed inside the blower  section door on the access side of the unit  When the blower  section door is removed  the momentary switch is released and  interrupts power to the low voltage circuit  For single phase  units 1 1 2 Hp and less  the door switch de energizes a relay  that controls blower motor operation  For three phase units   and single phase units 1 1 2 Hp and greater  the door switch  de energizes the motor starter that controls blower motor  operation  For servicing  the swi
98. he burner modulates to full fire  operation until the room override is satisfied  The unit then  reverts back to duct sensing control  When equipped  with both  either the duct sensor or the room override  thermostat can call for heat     d  BMS Signal  The main gas valve is opened 10096 and  the burner firing rate is modulated between 40  and 10096  full fire  ABMS 0 10VDC or 4 20mA signal  inverted  such  that 0 VDC or 4      is high fire and 10 VDC or 20 mA is  low fire  is converted by the signal conditioner modulating  amplifier into an inverted DC voltage  OVDC for high fire to  12 VDC for low fire   The output voltage is applied to the  modulating gas valve to control the gas flow to the main  burner  The signal conditioner can accept a 0 10 VDC  signal when all the dip switches are in the    OFF    position  and 4 20 mA signal when all the dip switches are in the   ON  position  The modulating valve is modulated open or  closed based on the voltage from the amplifier  less gas  flow required   higher voltage  more gas flow required    lower voltage   which correlates to the control signal from  the BMS    Note  For further information regarding the operation of  any of the electronic modulating system options above   consult the literature provided with the unit   If the unit was provided with a time delay relay  the blower  starts after 30 to 45 seconds       The unit continues to operate until the thermostat is satisfied     Once satisfied    a  Single Stage Units  
99. he unit  Refer to Figure 46 1 for  Suspension Hanging Locations and Figure 4 1 demonstrates  how the unit should be suspended and the suspension rods  fastened to the unit base rail  If required  vibration isolators may  be added     Figure 4 1   Unit Suspension Method             3 4  SUSPENSION  RODS  BY OTHERS           P     1  3 4             LOCKWASHER   N        1      es    j        x  2     4  NUTS      M  LOCKWASHER                                 Model IBP standard blower cabinet shown  Mounting is the same for Model IBG        Floor Mounted Units   For floor installations  the floor structure must be adequately  designed to support the live weight load of the unit and any  other required support structure  Additional reinforcement should  be provided  if necessary  The floor should include threaded 5 8   inch anchor bolts spaced according to Figure 4 2  for securing  the unit in place  Anchor bolts should extend at least 1 1 2   above the surface of the floor to allow clearance for mounting  washers  nuts and bolts  mounting washers  nuts  and bolts by  others      Figure 4 2   Floor Mounted Unit Anchor Bolt Locations          5 8 Dia   4                 pod          Digit 16   75      100 25 All  150 175 All  200 225 All  250 300  E F G  or H  250 300 I J  or K  350 400   E F G or H  350 400   I J  or K  500 600 G or H  500 600 I J  or K  700 800 G or H  700 800   l J K  or L  840 960   l J K  or L                                                       4 AIR 5 565
100. hich the performance tables are shown on   pages 33 35  Since all of the blower performance curves  can provide the required 5000 cfm  the total static pressure  must be determined    A  The Pressure Drop of an option or accessory is  determined by entering the right of the table at the  desired cfm and reading up the table until the cfm  intersects the desired item  For this example  in Table  32 1 the 2  Permanent Filter line is used  At the point of  intersection  read across the table to the left and read the  pressure drop  in inches of water column for the filters   For this example  the pressure drop is 0 06  W C    As a result     For the Model Size 400 with Digit 16   E F G  or H   2  Permanent Filters  0 06  W C   Internal Static Pressure Drop 0 06  W C     The Total Static Pressure for the system is determined by  Internal Static   External Static   Total Static Pressure  For this example 0 06    0 65    0 71  W C  T S P     From page 32    for the Model Size 400 with Digit 16      J  or K   2  Permanent Filters  0 04  W C   Internal Static Pressure Drop 0 04  W C     The Total Static Pressure for the system is determined by  Internal Static   External Static   Total Static Pressure  For this example 0 04    0 65    0 69  W C  T S P     B  Using the total static pressure  T S P   calculated in step  12a  use blower performance tables for the Model Size  400  Table 34 1      Using Table 34 1  enter the table at the required 5000  cfm for E  F blowers  and follow the
101. il the continuity  tester senses a closed circuit  This determines the base  pressure of the system    6  Turn the screw clockwise until the continuity tester senses an  open circuit and then one additional full turn  This is approx   imately 0 25  W C   This will allow for the increase in static  pressure due to dirty filters     24 AIR 5 565 2    OPTIONS    Figure 25 1   Dirty Filter Pressure Switch and Air Flow  Proving Switch       Negative pressure    Positive pressure connector  connector                                                                                  z  Pressure adjustment set screw              40  Motor Starter      OPT    The motor starter is factory installed in the electrical section    A motor starter is required for all three phase motors and single  phase motors 1 1 2 Hp and greater  The motor starter current set  point dial is factory set to the motor full load amp draw listed on  the motor nameplate      40  Variable Frequency Drive      OPT    The VFD controller adjusts the motor rpm to vary the unit air  flow  The minimum air flow may be varied between 30 and 100   of the full speed air flow depending on the controls selection of  the unit  The control changeover options are two speed  floating  building pressure sensing  and building management control     The overload module of the motor starter is designed to trip to  protect the motor from exceeding the nameplate amps  If the  motor exceeds the amp draw on the current set point dial  th
102. ir damper will remain open  The damper  can be manually closed through the use of the manual override  switch on the floating damper actuator      31  Enthalpy Controller      OPT    An enthalpy controller is provided with Air Control option GJ   Digits 20  amp  21  and factory installed in the blower section    The purpose of the enthalpy controller is to use outside air for  cooling  whenever possible  to reduce compressor operation of  the mechanical cooling system  The economizer functions as a  true first stage of cooling and provides maximum fuel economy  during the cooling cycle     The components used for the Enthalpy Economizer are      Enthalpy Economizer Controller  The Enthalpy Controller is  used in conjunction with the Enthalpy Sensor and a Mixed Air  Temperature sensor  The controller is factory mounted in the  blower control cabinet      Outside Air Enthalpy Sensor  The sensor provides a signal  in relation to enthalpy  temperature and humidity  of the  outside air  The sensor is installed in the outside air stream      Mixed Air Temperature Sensor  The sensor is factory  installed in the blower section to sense the mixed air  temperature of the fresh and return air streams     Typical Sequence of Operation   Heating or Ventilation Mode   When the space thermostat calls for heat or the fan is on  without a call for cooling  ventilation mode   the economizer is  automatically locked out and holds the outdoor air damper at the  minimum position setting  The mini
103. isting of both can be found in your Installation and Service Manual     When inquiring about parts  always provide model number  serial number  description and part number     _   When ordering parts  provide part number listed    For service  contact your local qualified installation and service contractor or appropriate utility company     Blower Motor   2             Sheave     Motor Sheave    Design conforms to  UL Std 1995    Certified to  CAN CSA C22 2 No  236          tiste     9900100    Blower Belt    c   15    9 6     9900100    5H764718 Rev B                   Figure 55 2   Serial Number Designation   Furnace       09 17    SERIAL NUMBER PREFIX   lt blank gt  if standard   S  if Special Product Order    SERIES IDENTITY NUMBER    CONTROL SUPPLIER   01 Robertshaw 09 White Rodgers  05 Honeywell     17 United Technologies  08 Fenwal    GAS VALVE SUPPLIER  01 Robertshaw 09 White Rodgers  05 Honeywell       09       10    0123 10000    SPO NUMBER   lt blank gt  if standard  THHHHE if Special Product Order              SEQUENTIAL NUMBER  Varies   0000 TO 9999  Each unit in a week has a  unique number    YEAR  PRODUCED    WEEK  PRODUCED          Figure 55 3   Serial Number Designations   System       Serial Number Designations    01 10 201 01 02   1000                                                    MOTOR SEQUENCE  VENDOR CODE   NUMBER  01     Century  15   Marathon  etc          mE YEAR OF  FAN OR BLOWER MANUFACTURE  VENDOR CODE 01     2001  10     Lau 02     2002  20 
104. izing    75  100 125    Minimum Vent Pipe Diameter 2  IBG ICG IBP ICP             150 175       200 225  250  500    300 400  600 960      Requires a 4  to 5  adapter for the larger 5  vent pipe diameter     Per furnace           AIR 5 565 2 5    4     9  10    11     12     13     14     15     16     17     For Category   vent systems limit length of horizontal runs to  75  of vertical height  Install with a minimum upward slope  from unit of 1 4 inch per foot and suspend securely from  overhead structure at points no greater than 3 feet apart    For best venting  put vertical vent as close to the unit as  possible  For Model IBP ICP units  a minimum of 12  straight  pipe is recommended from the power exhauster outlet before  turns in the vent system  Fasten individual lengths of vent  together with at least three corrosion resistant sheet metal  Screws       Itis recommended that vent pipes be fitted with a tee with a    drip leg and a clean out cap to prevent any moisture in the  vent pipe from entering the unit  The drip leg should be inspected  and cleaned out periodically during the heating season       The National Fuel Gas Code requires a minimum clearance    of 6 inches from combustible materials for single wall vent  pipe  The minimum distance from combustible materials is  based on the combustible material surface not exceeding  160  F  Clearance from the vent pipe  or the top of the unit   may be required to be greater than 6 inches if heat damage  other than fir
105. l Strip  12  Furnace Supply Power Terminal Strip    20   21   22   23   24   25   26   2f   30     45   44   42  41   89    Extended Grease Line Zerk Fittings  Extended Grease Lines   Return Air Fire Stat   Blower Housing   Pillow Block Bearings   Blower Motor   Filters   Fresh Air Damper   Direct Drive Damper Actuator    36  35 33 31    38   39   40   41   42   43   44   45   46   47   48   49   50   51   52     Blower Door Switch   Dirty Filter Switch   Motor Starter VFD Control   Mild Temperature Thermostat  Proportional Temp Controller  Warm Up Stat   Blower Supply Power Terminal Strip  Service Switches   Electronic Modulating Amplifier  Electronic Modulating Gas Valve  Air Flow Proving Switch   High Limit Switch   Supply Air Fire Stat   Main Gas Valve   Burner Box       All units include the standard  STD  features  The unit  must be reviewed to determine the optional  OPT   features that may have been supplied with the unit      1  Discharge Thermostat      OPT   Not Shown    The discharge thermostat is field installed in the discharge  air stream of the unit  For additional information  refer to  the thermostat vendor literature provided in the literature  packet with the unit  Model Sizes 500 960 contain multiple  furnaces so multiple thermostats sensors may be included   The thermostat s  provided can be one of the following     a  Two stage Capillary Type Thermostat     The thermostat  includes a thermostat body and capilary to be field  installed in duct work  The 
106. l and propane gas units  the ignition controller  is 100  shut off with continuous retry  On a call for heat  the  system will attempt to light the pilot for 70 seconds  If the pilot  is not sensed for any reason  the ignition control will wait for  approximately six minutes with the combination gas control  closed and no spark  After six minutes  the cycle will begin  again  After three cycles  some ignition controllers lockout for  approximately one hour before the cycle begins again  This will  continue indefinitely until the pilot flame is sensed or power is  interrupted to the system      8  Control Relay      OPT    The control relay is factory installed in the duct furnace electrical  junction box  The relay has a 24V coil with double pole  double  throw  DPDT  contacts  Refer to the unit wiring diagram for the  function of the switching operation of the relay  The two normally  open and two normally closed contacts are rated for a maximum  of 30 amps   115V 1Ph     20 AIR 5 565 2    OPTIONS     9  Time Delay Relay    STD    The time delay relay is factory installed in the duct furnace  electrical junction box  The time delay relay allows the gas controls  to operate for approximately 30 seconds before the blower starts   This allows the heat exchanger a warm up period so that the initial  delivered air coming out of the ductwork is not cool  The time delay  relay also keeps the motor running for approximately 30 seconds  after the call for heat has been satisfied to r
107. led  Water coil     Fin spacings  of 6 8 10 12  or 14 fins per inch       Adjustable  mounting bracket  for 2 3 4 and 6 row  coils    Full coverage  3 way sloping  409 stainless    0  s Steel drain pan  Right or left hand coil 1  stubbed drain    header access to match connection  gas controls             Condensate Drain Pan Trap    The condensate drain line needs to include a P trap immediately  downstream of the connection to the unit  This trap should  extend at least two inches below the connection to prevent air  pressure from forcing air into the unit  The trap should be primed  with a water glycol solution to prevent freezing     Direct Expansion  DX  Piping   The refrigerant lines should be insulated to prevent warming  or cooling of the refrigerant  If the suction line is allowed to be  cooled  liquid will condense in the line and can severely damage  the compressor  If the liquid line is warmed  the refrigerant  can  flash  into a gas  This will cause erratic operation of   the expansion device and impair the heat transfer ability of  the cooling coil  Long runs of piping need to be periodically  supported to prevent excess vibration that can damage the  piping and joints  It is recommended to provide dampening  supports at intervals of length equivalent to 15 tube diameters     Figure 12 2   General DX Piping             Expansion Valve   By Others     Suction Line    Remote Sensing Bulb Sauco             1  Inspect the refrigerant distributor and verify that the 
108. lters are supplied with the unit  a rack and the filters are  factory installed in the blower section  The unit can be supplied  with 1  or 2  permanent filters  2  FARR  Aeropleat MERV 7 or  2  FARR  30 30 MERV 8 filters  For filter replacement  refer to  Maintenance      27  Fresh Air Damper    OPT    When a fresh air damper is supplied with the unit  the damper is  factory installed in the blower section  The fresh air damper is  used as an outside air shut off damper  so ultra low leak  Class II  leakage resistance  less than 10 CFM ft  at 1  W C   dampers  with self compensating stainless steel side seals and santoprene  and galvanized steel blade seals are used      30  Direct Drive Damper Actuator      OPT    The direct drive damper actuator is factory installed in the blower  section on the side of the fresh air damper  The actuator controls  the position of the fresh air damper  The return air damper  if  provided  is controlled by the damper linkage between the two  dampers  All damper actuators are low voltage  24V   For Right  Hand units  Digit 9   R   during operation the actuator should  rotate in the counterclockwise direction when viewed from the    service side of the unit  For Left Hand units  Digit 9   L   during  operation the actuator should rotate in the clockwise direction  when viewed from the service side of the unit  Three different  types of dampers actuators can be provided  Two position   Modulating  and Floating     Two position Damper Actuator  
109. mation  refer  to Control Operating Sequence      48  Air Flow Proving Switch      OPT    The air flow proving switch is factory installed in the duct furnace  electrical junction box  The air flow proving switch monitors   the pressure differential between the duct furnace and the  atmosphere  The purpose of the air flow proving switch is to cut  power to the gas controls if a positive pressure is not measured  by the switch  This could be caused by a lack of air movement  through the heat exchanger     NOTE  The air flow proving switch will prevent any heat  exchanger warm up because the gas controls can not  be energized until air flow is proven     Setting the Air Flow Proving Switch    The range of the air flow proving switch is adjustable between O 17   to 5 0  W C     1  Set the thermostat so that there is a call for heat  This should start  the blower and then the burner ignition sequence     2  Turn the set screw of the pressure switch clockwise until it stops   This will set the pressure at 5 0  W C     3  Tum the screw counter clockwise until the gas controls light and  then one additional full turn  This is approximately 0 25  W C     This will allow for dirty filters or any other slight static pressure  increases in the system      49  High Limit Switch   Automatic      STD    The automatic reset high limit switch is factory installed in the  duct furnace electrical junction box  If the limit temperature is  exceeded  the gas controls are de energized until the s
110. mper in a fully closed position    2  Open the return air damper in a fully open position    3  Slide the connecting rod into the ball joint on the blade arm  with the return air damper fully open  See Figure 16 3    4  Tighten the 5 16  hex head screw on the ball joint     Figure 16 3   Damper Linkage Adjustment    BALL           CONNECTING ROD        BLADE ARM    DAMPER  L                Cooling Coil Operation   1  Proper air distribution is vital to coil performance  Air flow  anywhere on the coil face should not vary by more than 20     2  Air velocities should be maintained between 200 and 550 feet  per minute    3  For chilled fluid coils  fluid velocities should be maintained  within the recommended values of 1 to 8 feet per second  fps   for Water and 1 to 6 fps for Glycol solutions     16 AIR 5 565 2    START  UP PROCEDURE    Control Operating Sequence    IMPORTANT    To prevent premature heat exchanger failure  with all control  Systems  a blower starting mechanism must be provided so  that the blower is running or energized within 45 seconds of  the gas control operation           Indoor duct furnaces are supplied with intermittent pilot systems  with continuous retry  which both the main burner and pilot  burner are turned off 10096 when the thermostat is satisfied    On a call for heat  the system will attempt to light the pilot   for 70 seconds  If the pilot is not sensed for any reason  the  ignition control will wait for approximately six minutes with the  com
111. mum position adjustment  keeps the outdoor air damper from closing completely during  System operation to provide ventilation in both the heating and  cooling modes        Cooling Mode  When the space thermostat calls for cooling  the system  operates as follows   Outdoor Air Enthalpy is Below Changeover Set Point  1  The outdoor air damper is proportioned open  and the  return air damper is proportioned closed  to maintain a  temperature of 53  F  default  adjustable  at the mixed  temperature air sensor   2  During economizer operation  mechanical cooling is  operated by the second stage of the cooling on the space  thermostat     Outdoor Air Enthalpy is Above Changeover Set Point   1  The outdoor air damper is closed to its minimum position    2  A call for cooling from the space thermostat brings on  mechanical cooling     For complete details on the Enthalpy Economizer controller  setup and operation  please refer to the latest revision of Modine  publication 5 598   Setup Instructions  Enthalpy Economizer  Controller      Figure 23 2   Enthalpy Controller                AIR 5 565 2 23    OPTIONS     32  Damper to Damper Linkage      OPT    Units with fresh and return air dampers include a damper  actuator that controls the fresh air damper  The return air  damper position is controlled by the fresh air damper through  the connecting rod  For adjustment  refer to Damper Linkage  Adjustment      33  Return Air Damper    OPT    When a return air damper is supplied with the
112. n the system  The lines between the unit and the  structure should be insulated to prevent freezing of the water     1  Once installed  the coil should be pressurized to 100 psig  with dry nitrogen or other suitable gas  The coil should be  left pressurized for a minimum of 10 minutes  If the coil  holds the pressure  the hook up can be considered leak  free  If the pressure drops by 5 psig or less re pressurize  the coil and wait another 10 minutes  If the pressure drops  again  there is more than likely one or more small leaks  which should be located and repaired  Pressure losses  greater than 5 psig would indicate a larger leak that should  be isolated and repaired    2  All field brazing and welding should be performed using  high quality materials and an inert gas purge  such as  nitrogen  to reduce oxidation of the internal surface of  the coil    3  All field piping must be self supporting  System piping  should be flexible enough to allow for thermal expansion  and contraction of the coil    4  Fill the coil with water with all air vents open so that air is  eliminated from within the coil circuitry and headers  Verify  that all vents and drains are not obstructed and do discharge  a stream of water    5  Close all vents and perform a hydrostatic leak test  of all brazed  threaded or flanged joints  valves and  interconnecting piping  Recheck the coil level and correct  if necessary  When the setup is found to be leak free   discharge and discard initial water charge
113. nections  The blower section back and bottom and cooling cabinet section  discharge are designed to accept 90   flanged ductwork  see  Figure 5 2   Provide an airtight seal between the ductwork and  the unit to prevent leakage  Seams with cracks in the ductwork  should be caulked and or taped and be of permanent type     Figure 5 2   Blower Section and Cooling Cabinet Duct  Connections              BLOWER OR  COOLING COIL  SECTION    DUCTWORK  WITH 90    1 2  FLANGE                    VENTING    AWARNING    1  Gas fired heating equipment must be vented   do not  operate unvented   2  a  Model IBG ICG has a built in draft diverter   additional  external diverters are not required or permitted   b  Model IBP ICP has a built in power exhauster   additional  external power exhausters are not required or permitted      If you are replacing an existing heater  it may be necessary to  resize the venting systems  Improperly sized venting systems  can result in vent gas leakage or the formation of condensate   Refer to the National Fuel Gas Code ANSI 2223 1 or CSA  B149 1 latest edition  Failure to follow these instructions can  result in injury or death      For Model IBG ICG  gas fired heating equipment which has  been improperly vented  or which experiences a blocked vent  condition may have flue gases accidentally spilled into the  heated space  See page 53 for specific information about the  blocked vent safety switch supplied on the unit      For Model IBP ICP  under no circumst
114. nhibited glycol  solution that will protect the coil from the lowest possible  temperatures that can occur at that locality     AIR 5 565 2 49       MAINTENANCE    Manifold Assembly Removal    To remove the manifold  Refer to Figure 50 1    1  Shut off gas and electric supply    2  Disconnect gas manifold at ground union joint    3  Remove the two screws holding the manifold to the heat  exchanger support    4  Slide the manifold through the manifold bracket    5  Clean the orifices and adjust the air shutters as necessary    6  Follow steps 3 6 in reverse order to install the manifold  assembly    7  Turn on the electric and gas supply    8  Check the ground union joint for leaks with a soap solution   Tighten if necessary     Figure 50 1   Manifold Assembly Removal          ELECTRICAL  JUNCTION  BOX    MANIFOLD    SERIAL PLATE    BURNER SIDE  ACCESS PANEL             Burner and Pilot Assembly Removal  To remove the burner  Refer to Figure 50 2     1      Shut off gas and electric supply   2   3     Disconnect the pilot supply line from the gas valve   Disconnect the ignition cable from the ignition controller  located  in the electrical junction box   Feed the cable through the  bushing in the bottom of the electrical junction box       Remove the screws holding the burner side access panel     Attached to the panel are the burner retaining pins that align  the burner       Slide the burner assembly out  The pilot is attached to the    burner assembly       Examine the burn
115. nit that  is ETL ETL Canada certified  For this reason  two identification  plates are used on these models  The Serial Plate is used   to identify the duct furnace and its components  The Model  Identification Plate is used to identify the complete model   including blower and cooling sections     Figure 54 1   Serial Plate    Ordering   When servicing  repairing or replacing parts on these units   locate the model identification plate of the unit and always give  the complete Model Number and Serial Number from the model  identification plate  The model identification plate is located on  the door of the electrical control box or on the side of unit  The  part number for some common replacement parts are listed on  the serial plate  See Figure 54 1  and the model identification  plate  See Figure 55 1   For a complete description of the model  number  see Model Identification        Modine Manufacturing Company                                                   Made in U S A                             1500 Dekoven Avenue  Racine  WI 53403 2552 9   Phone  1 866 823 1631 GAS FIRED DUCT FURNACE FOR INDUSTRIAL   COMMERCIAL USE usce us  GENERATEUR D AIR CHAUD A GAINE POUR USAGE INDUSTRIEL COMMERCIAL   MODEL NUMBER  IN USA  EOR INSTALLATIONS ABOVE 2000 FEET  DERATE   VOLTS masi               mel F    40 OAMRNN2 4A154321 4  FOR EACH 1000 FEET OF ELEVATION ABOVE SEA ms    Ai  APPROVALS      sm        60917094908 0034        APPROVED FOR USE IN   NUMERO DE SERIE            e Lu   MI
116. nnect switch  Check  that fuses or circuit breakers are in place and sized  correctly  Turn all hand gas valves to the  OFF  position    2  Remove the blower exterior panels and open the electrical  compartment door    3  Check that the supply voltage matches the unit supply  voltage listed on the Model Identification plate  Verify that  all wiring is secure and properly protected  Trace circuits to  insure that the unit has been wired according to the wiring  diagram    4  Checkto insure that the venting system is installed and  free from obstructions    5  Check to see that there are no obstructions to the intake  and discharge of the unit    6  Check the belt tension and sheave alignment  Refer to  Blower Adjustments for proper belt tension    7  Check bearings for proper lubrication  For units provided  with pillow block bearings  See Model Nomenclature   refer  to Lubrication Recommendations for lubrication requirements    8  Check to make sure that all filters are in place and that they  are installed properly according to direction of air flow    9  Perform a visual inspection of the unit to make sure no  damage has occurred during installation    10  Turn on power to the unit at the disconnect switch  Check to  insure that the voltage between duct furnace electrical box  terminals 1 and 2 is 24V    11  Check the thermostat  ignition control  gas valve  and  supply fan blower motor for electrical operation  If these do  not function  recheck the wiring diagram  Check t
117. nozzle  is in place    2  All field brazing and welding should be performed using  high quality materials and an inert gas purge  such as  nitrogen  to reduce oxidation of the internal surface of the coil     3  For DX coils  the use of filter dryers in the system piping is  recommended along with a sight glass that has a moisture  indicator     4  Connect the suction line and suction connection     5  Install the expansion valve  By Others   Follow the  expansion valve manufacturer s recommendations for  installation to avoid damaging the valve     6  Connect the liquid line to the expansion valve  Pressurize  the coil  expansion valve assembly and suction connection  to 100 psig with dry nitrogen or other suitable gas  The coil  should be left pressurized for a minimum of 10 minutes     7  If the coil holds pressure  the installation can be considered  leak free  If the pressure drops by 5 psi or less   repressurize the coil and wait another 10 minutes  If the  pressure drops again  there are more than likely one or  more small leaks  which should be located and repaired   Pressure losses greater than 5 psi would indicate a larger  leak  which should be isolated and repaired  Be sure to  check valves and fittings as potential sites for leakage or  bleed     8  Use a vacuum pump to evacuate the coil and any  interconnecting piping that has been open to atmosphere   Measure the vacuum in the piping using a micron gauge  located as far from the pump as possible  the vacuum at 
118. o insure  that none of the Control Options have tripped    12  For units with a return air damper  the return air damper  linkage needs to be adjusted  Refer to Damper Linkage  Adjustment    13  Check to make sure that the damper opens properly  without binding    14  Check the blower wheel for proper direction of rotation  when compared to the air flow direction arrow on the  blower housing  Blower wheel rotation  not air movement   must be checked as some air will be delivered through the  duct furnace with the blower wheel running backwards    15  Check the blower speed  rpm   Refer to Blower  Adjustments for modification    16  Check the motor speed  rpm     17  Check the motor voltage  On three phase systems  check  to make sure all legs are in balance    18  Check the motor amp draw to make sure it does not  exceed the motor nameplate rating  On three phase  Systems  check all legs to insure system is balanced     19  Recheck the gas supply pressure at the field installed  manual shut off valve  The minumum inlet pressure should  be 6  W C  on natural gas and 11  W C  on propane gas   The maximum inlet pressure for either gas is 14  W C  If  inlet pressure exceeds 14  W C   a gas pressure regulator  must be added upstream of the combination gas valve    20  Open the field installed manual gas shut off valve    21  Open the manual main gas valve on the combination gas  valve  Call for heat with the thermostat and allow the pilot  to light for intermitent pilot ignition  
119. or design temp    70  F  3  Heating output capacity     5000 cfm x  70  F  10  F  x 1 08   324 000 Btu Hr  4  External Static Pressure   0 65    The unit with the controls on the Right Hand Side is to be  provided with the following     2  Permanent Filters  and Fresh Air Damper    Heat exchanger and burner   409 Stainless Steel    Gas Type   Natural   Gas Controls   Electronic Modulating with Duct Sensing   9  Supply Voltage  460V 60Hz 3Ph   10  Altitude  1000 feet          ouo    With the information listed above  the basic model  using the  Model Nomenclature shown on page 57  can be selected as  shown in the following example     1  Determine the Model Configuration and Venting   The Model Configuration is determined by the required  sections of the unit  Blower only  and the venting style   power vented  that are obtained from item  5  Using the  Model Nomenclature on page 57  the Model Configuration  and Venting   IBP     2  Determine the Furnace Input Rating  MBH    Using the Heating output capacity  the Furnace Input  Rating is determined from Table 29 1  The closest model  to 324 000 Btu Hr output has an Btu Hr Input rating of  400 000 Btu Hr so the Furnace Input Rating   400     3  Determine the Heat Exchanger Burner Drip Pan  Material   From item Z2 in Selection Example Conditions  the Heat  Exchanger and Burner required are 409 Stainless Steel   Because the Drip Pan material is not specified  the standard  Aluminized Steel drip pan will be used  Thus  the Heat  Ex
120. order    g  Using maximum adjustment screw  4   adjust high fire  manifold pressure to 3 5  W C  for natural gas and 10   W C  for propane gas    h  Disconnect power    i  Replace cover plate  2  and re install all wires from  Maxitrol amplifier terminal  3  or duct furnace terminal  43     7  After adjustment  move the field installed manual shut off  valve to the  OFF  position and replace the 1 8  pipe plug    8  After the plug is in place  move the field installed manual  shut off valve to the  ON  position and recheck pipe plugs  for gas leaks with soap solution     Figure 15 1   Manifold Pressure Test Points                                       Manifold Pressure Test Point    Standard Controls          Figure 15 2   Maxitrol Modulating Valve Adjustments       1  TOP HOUSING   2  COVER PLATE   3  SEAL GASKET   4  MAXIMUM ADJUSTMENT SCREW   5  MAXIMUM ADJUSTMENT SPRING   6  SOLENOID   7  MINIMUM ADJUSTMENT SPRING   8  PLUNGER   9  MINIMUM ADJUSTMENT SCREW   10  MINIMUM ADJUSTMENT SCREW STOP             Air Shutter Adjustment    Proper operation provides a soft blue flame with a well defined  inner core  A lack of primary air will reveal soft yellow tipped  flames  Excess primary air produces short  well defined flames  with a tendency to lift off the burner ports  For both natural   and propane gas  the air shutters can be adjusted to control   the burner flame height  The air shutters can be accessed by  reaching behind the gas valve in Figure 15 1  The larger models  m
121. per rotation either manually with the manual  crank or apply power  Re adjust if necessary    6  If the damper end switch is being used in the control circuit  and needs to be adjusted for the new minimum position   refer to the next section   Adjusting the Damper End Switch         Figure 22 1   Two position Damper Actuator and Limiter                   Philips screwdriver             22 AIR 5 565 2    OPTIONS    Adjusting the Damper End Switch   If the damper limiter was adjusted in the previous section  it may   be required to adjust the Damper End Switch as follows    1 The actuator must be in its fail safe position    2  Insert the crank handle into the torx shaped hole located in  the center of the adjustable switch pointer as shown in  Figure 23 1    3  Gently rotate the crank until the switch pointer is at the  desired switch point in degrees as shown        Figure 23 1   Adjusting the Damper End Switch       Rotate with  crank handle    Factory setting 90   60   set                                  Modulating Damper Actuator  A modulating damper actuator is  provided with Air Control options GA  GB  GC  GD  GE  GG  GH   GJ  GK and GM  Digits 20  amp  21   The modulating damper  actuator provides incremental operation of the fresh air damper   The return air damper is controlled by the fresh air damper  position   Full 90  rotation of the modulating actuator requires  150 seconds  All modulating damper actuators operate using a  0 10 Vdc input signal  Air Control GB u
122. re 53 2 for additional troubleshooting information     a  lt              BLOCKED VENT  SAFETY SWITCH             Figure 53 2   Blocked Vent Safety Switch Troubleshooting Flow Chart  Model IBG ICG only        S NO  NO    YES  Is there a negative pressure in space   see note 2  Replace blocked vent switch   Does switch still trip   YES YES NO  Can negative pressure Is vent in compliance  be corrected  with NFGC     YES NO         Correct Install    negative power vent    pressure accessory  Is unit overfired   Reduce input Can one or more of the following be done     Lengthen vertical vent run      Insulate vent      Use larger diameter vent    Use less restrictive weather cap          Note 1  To determine spillage  place lit match  Stick  6    8  match stick if possible  2    3   into diverter relief opening and determine  direction of the flame  or direction of  smoke if flame goes out   If flame or Install power vent  smoke comes back at you  there is accessory    spillage  The flame or smoke should be  pulled in     Note 2  One indication of negative pressure is Install power  that outside doors tend to be pulled toward  inside of space  exhauster accessory       AIR 5 565 2    53       MODEL DESIGNATIONS    Model Identification   Duct furnace make up air units contain an ETL ETL Canada  certified indoor duct furnace  This duct furnace is combined with  either a blower section or a blower and cooling section to make  a complete make up air or heating ventilating  cooling u
123. rinted instructions  or if the serial number has been  altered  defaced or removed     BUYER AGREES THAT IN NO EVENT WILL SELLER BE LIABLE FOR  COSTS OF PROCESSING  LOST PROFITS  INJURY TO GOODWILL  OR  ANY OTHER CONSEQUENTIAL OR INCIDENTAL DAMAGES OF ANY KIND  RESULTING FROM THE ORDER OR USE OF ITS PRODUCT  WHETHER  ARISING FROM BREACH OF WARRANTY  NONCONFORMITY TO  ORDERED SPECIFICATIONS  DELAY IN DELIVERY  OR ANY LOSS  SUSTAINED BY THE BUYER     Component  Applicable Models    BUYER S REMEDY FOR BREACH OF WARRANTY  EXCLUSIVE OF ALL  OTHER REMEDIES PROVIDED BY LAW  IS LIMITED TO REPAIR OR  REPLACEMENT AT THE FACTORY OF SELLER  ANY COMPONENT WHICH  SHALL  WITHIN THE APPLICABLE WARRANTY PERIOD DEFINED HEREIN  AND UPON PRIOR WRITTEN APPROVAL  BE RETURNED TO SELLER  WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE  EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE   EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYERAS A  COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER   BUYER S REMEDY FOR BREACH  AS LIMITED HEREIN  SHALL BE  LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER  FOR  GAS FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS  AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS  BUYER S  REMEDY FOR BREACH  AS LIMITED HEREIN  SHALL BE LIMITED TO   TEN YEARS FROM DATE OF SHIPMENT FROM SELLER     These warranties are issued only to the original owner user and cannot be  transferred or assigned  No provision is made in these warranties for any  labor allowan
124. rmostat                               NOTES   1  Holes visable on right side are             also on left side in the same location   2  Holes on top are also on the back   in the same location horizontally    1  down vertically              Table 48 1   Blower Package Unit Operating Weights   All weights in pounds     Model Blower Type i Dampers   Dampers i Double Wall  Digit 16 Filters oh Alr  F amp  RA  nsulation an Sections             NIN Joyo    E F G  or H  I  J  orK  E F G  or H  I  J  orK  GorH  I J  K  or L          I  J  K orL  I J  K  or L       _  A          zx  A       See Motor Data                                               Table 48 2   Cooling Package Unit Operating Weights   All weights in pounds     Blower Dampers  Model Type Dampers Fresh  amp  Double Wall  Size  Digit 16  Filters Fresh Air   Return Air Insulation  All Sections   5    All    100 125 All    All  All  EFG  or H See Motor  I  J  or K Data  E F G  or H  l  J  or K                            48 AIR 5 565 2    MAINTENANCE    A WARNING    When servicing or repairing this equipment  use only factory   approved service replacement parts  A complete replacement  parts list may be obtained by contacting Modine Manufacturing  Company  Refer to the rating plate on the appliance for  complete appliance model number  serial number  and  company address  Any substitution of parts or controls not  approved by the factory will be at the owner s risk     A CAUTION    Do not attempt to reuse any mechanical
125. ss Side  Model Size  75    100 125  150 175             Non Access  Side  B              200 225       250 300  500 600    350 400  700 800  840 96                Combustion Air Requirements   Units installed in tightly sealed buildings or confined spaces  must be provided with two permanent openings  one near  the top of the confined space and one near the bottom  Each  opening should have a free area of not less than one square  inch per 1 000 BTU per hour of the total input rating off all  units in the enclosure  freely communicating with interior areas  having  in turn adequate infiltration from the outside    For further details on supplying combustion air to a confined   tightly sealed  space or unconfined space  see the National  Fuel Gas Code ANSI Z223 1 of CAN CGA B149 1 or  2  Installation Code  latest edition     Sound and Vibration Levels   All standard blower mechanical equipment generates some  sound and vibration that may require attenuation  Libraries   private offices and hospital facilities will require more  attenuation  and in such cases  an acoustical consultant may  be retained to assist in the application  Locating the equipment  away from the critical area is desirable within ducting limitations   Generally  a unit should be located within 15 feet of a primary  support beam  Smaller deflections mean lesser vibration and  noise transmission     UNIT LOCATION UNIT LIFTING UNIT MOUNTING    UNIT LIFTING   All standard blower system units are shipped fully 
126. supplied to the the space    3  Building management control which allows for an external  signal of 0 10VDC of 4 20mA to adjust the unit airflow    The allowable minimum CFM of the system can be 66  of  the minimum listed CFM in Table 29 1 if the unit is applied as  follows    1  The unit is provided with 2 stage or electronic modulating   gas controls    2  The unit is provided with a discharge air thermostat    3  The system does not include a room thermostat   The discharge air thermostat will prevent the unit from firing  above the allowable 100  F rise when the unit is at or above the  minimum CFM by monitoring the discharge air and going to low  fire  A room thermostat  because it is located remote from the  unit  could cause the unit to over fire     18 AIR 5 565 2    OPTIONS    Options   Factory Installed  Figure 19 1   Factory Mounted Option Locations         46    19  21   23  DEAS 22 24   25   26   27                   8 2  13  10         4     DA        D ae s  Q mam                                 Og  NE   27                                          50                                        90       ca  OO                       49                                                  5   069       UNITS WITH PREMIUM CONTROL BOX    40   38    34    30    2  Low Gas Pressure Switch   3  High Gas Pressure Switch   4  Power Exhauster   5  Timed Freeze Protection   6  Ignition Controller   8  Control Relay   9  Differential Pressure Switch   10  Furnace Low Voltage Termina
127. tch is equipped with an override  position that can be manually pulled out to override the switch    See Figure 24 2      Figure 24 2   Blower Door Switch with Manual Override                  DOOROPEN OVERRIDE  DOOR CLOSED POSITION  POSITION POSITION                   COM  NC NO              39  Dirty Filter Switch      OPT    The dirty filter pressure switch is factory installed in the electrical  section  The dirty filter pressure switch monitors the pressure  differential between the two sides of the filters  When the   filters become dirty  the differential pressure increases and   trips the pressure switch which energizes a light on the remote  monitoring panel  The pressure differential switch must be field  Set because setting the switch requires the blower to be in  operation and the ductwork to be installed     Setting the Dirty Filter Switch   The range of the dirty filter pressure switch is adjustable   between 0 17  to 5 0  W C    1  Ensure that the unit filters are clean  Clean or replace if  necessary    2  Connect the leads of a continuity tester to the NO and C  terminals of the dirty filter pressure switch  See Figure 25 1   3  Set the thermostat so that there is a call for heat  This should  fire the burner and the blower should start    4  Turn the set screw of the pressure switch clockwise until  it stops  This will set the pressure at 5 0  W C  and the  continuity tester should be sensing an open circuit    5  Begin turning the screw counterclockwise unt
128. ted above  For the Selection  and Installation Instructions for propane conversion kits  please  see the latest revision of Modine Bulletin 75 511     10 AIR 5 565 2       UNIT INSTALLATION    Electrical Connections       WARNING    1  Disconnect power supply before making wiring connections  to prevent electrical shock and equipment damage    2  All appliances must be wired strictly in accordance with  wiring diagram furnished with the appliance  Any wiring  different from the wiring diagram could result in a hazard  to persons and property    3  Any original factory wiring that requires replacement must  be replaced with wiring material having a temperature  rating of at least 105  C    4  Ensure that the supply voltage to the appliance  as  indicated on the serial plate  is not 5  greater than rated  voltage                 A CAUTION    Ensure that the supply voltage to the appliance  as indicated  on the serial plate  is not 5  greater than rated voltage        1  Installation of wiring must conform with local building codes   or in the absence of local codes  with the National Electric  Code ANSI NFPA 70   Latest Edition  Unit must be electri   cally grounded in conformance to this code  In Canada   wiring must comply with CSA C22 1  Part 1  Electrical Code    2  Two copies of the job specific wiring diagram are provided  with each unit  one located in the duct furnace electrical  junction box and one in the electrical section of the unit   Refer to this diagram for all 
129. the packing slip to determine the coil type  provided     The cooling section includes a full coverage  3 way sloping   409 stainless steel drain pan to remove condensate from coil  headers  thermal expansion valves  and refrigerant piping   Insulation is standard on outdoor units and optional on indoor  units  The cabinet includes two doors  a removable upper door  for service access to the coil once the plumbing has been  installed and a lower door which includes a factory supplied 1   stubbed drain connection to the exterior of the cabinet  Field  connections for coil inlet and outlet piping can be made through  the cabinet corner post or back of the unit  The cooling section  duct transition includes 1 1 2  flanges for fastening the sides   of the coil  The bottom duct transition is angled to remove any  condensation that may be entrained in the supply air stream   For field supplied coils  do not exceed the maximum coil  dimensions listed in Literature 82 135  The dimensions listed  are for the maximum coil dimensions  If the coil supplied is  smaller than the listed dimensions  field supplied blank off plates  are required to prevent air bypass around the coil  The coil is  supported by two 14 gauge support rails which contain mounting  provisions for fastening 4   5   6   7 5   8 5   and 10  deep coils     Figure 12 1   Cooling Section       Optional double  wall construction    DX single circuit  shown  and dual  circuit coils available           Installed  DX or Chil
130. thermostat body contains the  discharge air set point adjuster that must be field set     AIR 5 565 2    13  Control Step Down Transformer 31  Enthalpy Controller   14  Control Relay 32  Damper to Damper Linkage   15  Blower Low Voltage Terminal Strip 33  Return Air Damper   16  Dead Front Disconnect Switch 34  Proportional Temp Controller Sensor  17  Step Down Transformer Fuses 35  Motor and Blower Vibration Isolation  18  Step Down Transformer 36  Blower Support   19  Factory Installed Minimum Positioner 37  Convenience Outlet    55  Time Delay Relay       Figure 19 2   Two Stage Capillary Type Thermostat          Downstream  Ductwork   by others            Setpoint  Adjuster    Capillary    Thermostat body   Shown with cover removed           19    OPTIONS    b  Two stage Electronic Type Thermostat   Includes a field  installed discharge air sensor  The thermostat body is  field installed remotely and includes the discharge air set  point adjuster that must be field set  Refer to Literature  5 577 latest revision     Figure 20 1   Two Stage Electronic Type Thermostat Sensor              Note  Second stage  5350 module not shown           C  Electronic Modulating Discharge Air Thermostat      Includes a field installed mixing tube and discharge air  sensor field installed in duct work  The set point adjuster  is field installed remotely and must be field set  Refer to  Literature 5 578 latest revision     Figure 20 2   Electronic Modulating Discharge Air  Thermostat        
131. they may be exposed  to a potentially explosive or flammable atmosphere           IMPORTANT    To prevent premature heat exchanger failure  do not locate  ANY gas fired appliances in areas where corrosive vapors  i e   chlorinated  halogenated or acid  are present in the atmosphere           Location Recommendations    1  When locating the furnace  consider general space and  heating requirements  availability of gas and electrical  supply  and proximity to vent locations    2  Unit must be installed on the positive pressure side of the  circulating blower    3  Besure the structural support at the unit location site is  adequate to support the weight of the unit  For proper  operation the unit must be installed in a level horizontal  position    4  Do notinstall units in locations where the flue products  can be drawn into the adjacent building openings such as  windows  fresh air intakes  etc    5  Besure that the minimum clearances to combustible  materials and recommended service clearances are  maintained  Units are designed for installation on non   combustible surfaces with the minimum clearances shown  in Figure 3 1 and Tables 3 2 and 3 3    6  Units installed downstream of refrigeration systems  or  exposed to inlet air temperatures of 40  F or less  may  experience condensation  therefore  provisions should  be made for disposal of condensate  Means have been  provided in the bottom pan of the unit to accommodate a  condensate drain line connection flange    7  When
132. tilizes a resistor to convert  from a 4 20 mA to 0 10 Vdc  from a damper controller    All modulating damper actuators are spring return  so when the  damper is de energized  the fresh air damper will spring closed        Floating Damper Actuator  A floating damper actuator is provided  with Air Control option HP  Digits 20  amp  21   The floating damper  actuator provides forward and reversing damper operation in  response to contact closures from the space pressure controller   When the space pressure is above the desired set point  a high  pressure contact on the space pressure controller energizes the  damper to drive the fresh air damper closed  When the space  pressure is below the desired set point  a low pressure contact  on the space pressure controller energizes the damper to drive  the fresh air damper open  When the space pressure is between  the high and low set points  the damper  floats  at the fresh air  percentage that satisfied the space pressure controller  Full 90   rotation of the floating actuator requires 150 seconds  For  additional information on the space pressure controller  refer to  Literature 5 585        The damper actuator is designed to  float  and therefore it is not  spring return  When the unit is de energized under normal  operation  the fresh air damper is closed by a relay contact  closure which electrically drives the damper closed  If the supply  power to the unit is interrupted before the damper actuator can  drive closed  the fresh a
133. ting listed above     For Variable Air Movement Applications  see page 18     Air Temperature Limits   The maximum allowable discharge air temperature is 150  F   The maximum allowable air temperature rise per furnace for  Low Air Temperature Rise Units is 60  F  All system units are  designed for a maximum allowable total static pressure of  3 0  W C     AIR 5 565 2 29    UNIT SELECTION    Selection Procedure    In order to properly select an indirect fired heating  ventilating   cooling or make up air unit  it is necessary to have the following  basic information     1     9     10     Required air handling capacity  CFM     The air capacity of the unit is usually determined by the  ventilation air requirements  exhaust load of the building   infiltration losses  or the air turns changes of the space     Outdoor and indoor design temperature    The outdoor design temperature is determined by using  the ASHRAE Guide design temperatures for the city where  the equipment is to be installed  For heating and ventilating  units  the desired room temperature would be used as the  indoor design temperature  In the case of 10096 make up  air units  the discharge air temperature should be at least  equal to the temperature of the air being exhausted     Required heating output capacity  Btu Hr    The heating output capacity of the unit is determined by  using the formula    BTU HR   CFM x Temp  Rise    F  x 1 08    External static pressure to unit    The external static pressure  E S
134. trol Operating Sequence                           17  ODLUOFIS                nha av RUE m        e ERBEN       dade  19  General Performance Data                                28  Unit Selection    oec De Il      Pa ee 30  Option  amp  Accessory Pressure Drop Data                     32  Blower Performance Data                                 33  Blower Sheave Assembly Data                             36  Electrical Data                                          38  Motor Data i ua               Caca WERE REM Sanu E LAE E Rue 40  DIMENSIONS es ins              eek ea eee dead EP RU ena ede a 42  WEIGHS         Rx X eee eb ken bete eR d 48  Maintenance      c ucecienxken kr kh enden Re RE xe enden a 49  Service  amp  Troubleshooting                                 51  Model Designations                                      54  Start Up  Checklist     uy usss su pu sua ae      mex          Ens 56  Model Nomenclature                                     57  Commercial Warranty                             Back Page    2 AIR 5 565 2    SI  METRIC  CONVERSION FACTORS   UNIT LOCATION    SI  METRIC  CONVERSION FACTORS  Table 3 1    To Convert   Multiply By To Convert   Multiply By     W C  0 24 CFH 1 699 ms min  psig 6 893 Btu ft  0 0374 mJ m      F    F 32  x 0 555 pound 0 453 kg  inches 25 4 Btu hr 0 000293 kW hr  feet 0 305 meters gallons 3 785 liters  CFM 0 028 m min psig 27 7  W C     UNIT LOCATION    A DANGER                               Appliances must not be installed where 
135. ty devices  High limit  air flow  proving switch  differential pressure switch   gas pressure switches  etc   Determine and  correct problem  Reset if necessary    Find source and re direct airflow away from  unit    Tighten pilot orifice  Flame impingment   on pilot sensor may cause pilot sensor to  become inoperative     Replace valve    Check wiring to gas valve    Replace pilot sensor    Replace ignition controller    Verify wiring compared to wiring diagram   Refer to page 53     Reduce primary air    Adjust to a maximum of 14  W C    Check orifice size with those listed on the  serial plate     Increase primary air    Check orifices and clean with compressed  air if necessary    Check manifold  replace if necessary     Reduce primary air    Adjust to a maximim of 14    W C   Check orifice size with those listed on  the serial plate     Increase primary air    Adjust to a maximum of 14  W C   Check orifice size with those listed on  the serial plate    Clean correct venting system     Adjust to a maximum of 14  W C     2  Check orifice size with those listed on    the serial plate   Clean correct venting system     51    SERVICE  amp  TROUBLESHOOTING    Trouble    Not Enough Heat    Too Much Heat       1     Possible Cause    Unit cycling on high limit      a  Obstructions leaks in duct system   b  Main pressure set too high    c  Blower motor not energized     d  Loose belt  e  Blower speed too low     f  Blocked damaged venting system    g  Air distribution baffle remo
136. units should conform with local and national  requirements for type and volume of gas handled  and  pressure drop allowed in the line  Refer to Table 9 1 to  determine the cubic feet per hour  cfh  for the type of gas  and size of unit to be installed  Using this cfh value and  the length of pipe necessary  determine the pipe diameter  from Table 8 1  Where several units are served by the same  main  the total capacity  cfh and length of main must be  considered  Avoid pipe sizes smaller than 1 2   Table 8 1  allows for a 0 3  W C  pressure drop in the supply pressure  from the building main to the unit  The inlet pressure to the  unit must be 6 7  W C  for natural gas and 11 14  W C  for  propane gas  When sizing the inlet gas pipe diameter  make  sure that the unit supply pressure can be met after the 0 3   W C  has been subtracted  If the 0 3  W C  pressure drop  is too high  refer to the Gas Engineer s Handbook for other  gas pipe capacities    3  The gas piping to the unit can enter the unit from the side of  the unit or from below  Install a ground joint union with brass  seat and a manual shut off valve external of the unit casing   and adjacent to the unit for emergency shut off and easy  servicing of controls  including a 1 8  NPT plugged tapping  accessible for test gauge connection  See Figure 8 1    Verify the manual shut off valve is gas tight on an annual  basis     4  Provide a sediment trap before each unit in the line where  low spots cannot be avoided   See 
137. urnace  without using jumper wires  The switches override the remote  monitoring panel and or thermostats to energize each compo   nent directly  All switches need to be reset to the    OFF    position  after testing otherwise the components will remain energized     Figure 25 4   Service Switches          SYSTEM OVERRIDE SWITCH POSITIONS    DAMPERS ONLY  ON OFF OFF       qq    DAMPERS  amp  BLOWER ONLY  ON OFF    ON  DAMPERS  BLOWER  amp  FURNACE ONLY  ON ON ON               RESET SWITCHES TO  OFF  POSITION AFTER TESTING    ON ON on          O          OFF OFF OFF          SHTS637A                AIR 5 565 2 25    OPTIONS     46  Electronic Modulation Amplifier      OPT    An electronic modulation amplifier is provided factory installed  in the duct furnace electrical junction box when the unit is  equipped with Electronic Modulating Gas Controls  Digit 12    4   The amplifier processes the thermostat temperature and set  point signals to modulate the firing rate between 40  to 100   full fire  For additional information  refer to Control Operating  Sequence      47  Electronic Modulating Gas Valve      OPT    An electronic modulating gas valve is provided factory installed  in the duct furnace gas train when the unit is equipped with  Electronic Modulating Gas Controls  Digit 12   4  7  or 8   The  gas valve modulates the firing rate between 40  to 100  full  fire based on the input signal from the Electronic Modulation  Amplifier or Signal Conditioner  For additional infor
138. used to control the gas controls  damper actuator   motor starter  etc  Refer to the unit model number to determine  the volt  amp  VA  capacity of the duct furnace  The 15th digit  indicates the VA  See Model Nomenclature       14  Control Relay      OPT   The control relay is factory installed in the electrical section   See description of Option 8 for additional details      15  Blower Low Voltage Terminal Strip      STD    The blower low voltage terminal strip is located in the   electrical section  The terminal strip is labeled to match the  electrical wiring diagram provided with the unit  Low voltage  labeling ranges from terminal numbers 1 to 79  All field wiring  connections should be made to the right side of the terminals to  prevent miswiring by modifying the factory wiring which is made  to the left side of the terminal strip      16  Dead Front Disconnect Switch      OPT        WARNING    When the dead front disconnect switch is in the    OFF       position  supply power remains energized at the blower supply  power terminal strip and the top of the dead front disconnect  switch  When providing service on or near these terminals   building supply power to the unit should be de energized        The dead front disconnect switch is factory installed in the  electrical section  The disconnect switch is designed so that   it must be turned    OFF    before entry to the electrical control  cabinet can be obtained  See Figure 21 1   When in the    OFF     position  pow
139. ve thermal overload protection  Overload protection is required through the use of a motor starter or variable frequency drive       Motor Sizes  Digit 17  A through K and V do not include a motor starter  used with either a motor starter by others or variable frequency drive    All others include a motor starter       ODP   Open Drip Proof  TE   Totally Enclosed  the added suffix HE indicates NEMA Premium Efficiency     Motor manufacturers typically do not list efficiency for three phase motors smaller than 1hp     AIR 5 565 2 41    DIMENSIONS   UNIT    Figure 42 1   IBG Indoor Gravity Vented Blower Package Unit Dimensions          33 22 48 08                                                                                                 J Over Roof  3 86     L  N  Vent Dia         gt  x 2 20        I   gt      3425        _    Wie  Cw  NN               2400                11     inside  G  INSIDE   sun  P  C  Width Outside                  U Cal    m Se S 23  921  dios FAS 921 529            529                                                                CD CD bi 5    l        i l              Pps s 119      s 65 Min      i BOD     3 00  pprox  Qty  4  Drill Locator Dimples for  inside  4 85    Field Drilled Electrical Conduit    Entry Holes  spaced 2 0  apart  Return Air Duct Connection 1 50     he          500   800 Model Shown             Figure 42 2   ICG Indoor Gravity Vented Cooling Package Unit Dimensions                                                            
140. ved  high  temperature rise units only     h  Defective high limit switch    Main pressure set too low       Too much outside air       Thermostat malfunction     Gas controls wired incorrectly     Unit undersized       Thermostat malfunction     Gas controls do not shut off    a  Gas controls wired incorrectly   b  Short circuit    Main gas pressure set too high   Defective gas valve     Figure 52 1       Possible Remedy      Clean correct duct system      Adjust to a maximum of 14  W C      Check correct to insure blower motor  operates within 45 seconds of when gas  controls are energized      Adjust belt tension      Check correct blower drive settings for  proper rpm      Check correct venting system    g  Replace air distribution baffle     h  Replace high limit switch       Adjust main gas pressure     Minimum for Natural Gas     6  W C   Minimum for Propane Gas     11  W C       Adjust outside air damper to decrease    outside air percentage  if possible        Check replace thermostat     Check unit wiring against the wiring    diagram       Check design conditions  If unit is    undersized  an additional unit s  or other  heat source must be added       Check replace thermostat      amp   Check unit wiring against the wiring    diagram   b  Check for loose or worn wires       Adjust to a maximum of 14  W C     Replace gas valve          Automatic Reset High Limit    The duct furnace comes standard with an automatic reset high  limit switch that will shut off the gas
141. wiring connections    3  The wire gauge must be sized according to the National  Electric Code or CSA code based on the power supply  voltage  amp draw  and length of run  Refer to Table 11 1 for  maximum wire lengths and the number of wires for which the  low voltage terminal blocks in the unit are rated     Table 11 1   Low Voltage  24V  Maximum Wire Length  ft     NEC 1996  Table 310 17  Copper wire with 90  C insulation   conductors in free space  not in conduit   86  F ambient  For  other wire types  refer to the NEC of CSA code     Size  VA       18Ga   16Ga   14Ga   12Ga   10 Ga  162 315   360   495  86  43  26  5       1 40 216  2 75 168 192 264  3    150  4 250    Maximum   of Wires  per Terminal                      4  Make sure all multi voltage components  motors  transform   ers  etc   are wired in accordance with the power supply  voltage    5  The power supply to the unit must be protected with a fused  or circuit breaker disconnect switch  Refer to the Factory  Mounted Option Locations  Figure 19 1  for the factory  mounted disconnect switch location and then review the  unit to determine if a factory installed dead front disconnect  Switch was provided  Accessory field installed disconnect  Switches should be mounted where shown in Figure 11 1  For  fusible disconnect switches  refer to the Model Identification  plate for the fuse size and type     Figure 11 1   Recommended Accessory Field Installed  Disconnect Switch Mounting Locations             ELECTRICAL
142. witch   is cooled    Manual      OPT    The manual reset high limit switch is factory installed in place  of the standard automatic reset high limit switch located in the  duct furnace electrical junction box  In case of a failure of the  blower motor  blockage of the inlet air  etc   the manual reset  Switch prevents the unit from cycling on the high limit  If the limit  temperature is exceeded  a service person must inspect the unit  for the cause of the high discharge temperature  take corrective  action  and then reset the switch      50  Supply Air Fire Stat      OPT    The supply air fire stat is factory installed in the duct furnace  electrical junction box with the sensor in the discharge air  stream  In case of elevated temperatures in the supply air  stream  the manual reset switch shuts down the entire unit  If  the limit temperature is exceeded  a service person must inspect  the unit for the cause of the high discharge temperature  take  corrective action  and then reset the switch      51  Main Gas Valve    STD    The main gas valve is factory installed in the duct furnace gas  train  The main gas valve provides the pilot  regulator  main gas   and manual shutoff functions  For additional information  see the  supplier literature included with the unit      52  Burner Box    STD    The burner box is located in the duct furnace section and contains  the burner and pilot assembly  The burner box includes an access  panel for removal of the burner for inspection an
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Use and Care Manual    VD04-DBA ユーザーズマニュアル ユーザーズマニュアル  液晶コントロールターミナル - PRODUCT SEARCH サービス終了の  デジタルシグナル プロセッサー    Copyright © All rights reserved. 
   Failed to retrieve file