Home
50 AMP Smart Energy Management System Model 800
Contents
1. 131 Eisenhower Lane North Intellitec Lombard IL 60148 630 268 0010 1 800 251 2408 www intellitec com 6 P N 53 00684 100 Rev B 011905 50 AMP Smart Energy Management System Model 800 At the bottom of the column is the Relay Shed Order This determines which relays will be used for each load The one at the top of the column is first to be shed The one below it will turn off next and so forth The loads MUST be wired in this order for the system to operate as desired Finally the number and size of the circuit breakers should be selected to meet the needs of the installation The breakers can be either single or dual types The center two breakers on the Main Distribution Panel MUST be 50 Amp units to act as the Main breakers The breakers must be obtained and then installed in the box See information on breaker types later in this manual Distribution Panel The EMS Distribution Panel should be installed in a convenient location where it can get air circulation to keep it from over heating There should be a minimum of 7 of depth behind the mounting surface to provide enough room for the box and wiring A hole should be cut in the mounting panel as shown 19 9 16 1 8 DISTRIBUTION PANEL CUTOUT This opening must be cut carefully to be sure the mounting screws will have enough wood to hold and there is enough clearance around the box for the front cover screws The wiring to the b
2. Industry Association in conjunction with the N E C National Electrical Council have established rules regarding the rating of electrical systems and the use of energy management systems One of these rules requires that if an energy management system is used the average total load current for the system over a 3 hour period be limited to 80 of the service rating For that reason the 50 amp EMS calculates the average running current for the system and if itexceeds 8096 ofthe service rating the EMS sheds loads to reduce the average current below that limit For example if a system operating under 120 VAC 30 Amp service has been running at the 30 Amp limit for three hours the EMS will change its shedding threshold to 24 Amps and turn off loads until the 24 Amp limit is attained If the user selects the 20 Amp service mode this limit will translate to 16 Amps Because the EMS calculates a running 3 hour average if the average load current drops below the limit the system will restore power to loads based on their impact on the limit If the System is in the Averaging mode the decimal point at the lower right corner of the Load Meter display on the Display Panel will illuminate DISPLAY PANEL 50 AMP SERVICE TYPE SMART EMS POWER STATUS GEN SET AC LINE FIRST SHED 50 MEM AMP NEXT SHED 30 EV 30 NEXT SHED 20 EU NEXT SHED 30 20 AMP ta SELECT LOAD METER NEXT SHED LAST SHED by Mfintellitec POWERED WHEN LIT The Display
3. JP1 is reserved for future development 50 AMP EMS CONTROL MODULE LOW VOLTAGE CONNECTION SIDE 131 Eisenhower Lane North Intellitec Lombard IL 60148 630 268 0010 1 800 251 2408 www intellitec com 5 P N 53 00684 100 Rev B 011905 50 AMP Smart Energy Management System Model 800 These jumpers are all installed at the factory Removing JP2 JP3 or JP4 will alter the order of shedding to suit the particular need of the installation The following tables will assist in determining the proper settings for the three jumpers The first step is to fill in the blanks with the names of the loads you want the system to shed in the order they are to be shed with the first to be shed at the top Then fill in the second Load Type column with an A D an fora 120 VAC controlled load such as a washer dryer or a D for DC controlled load such as a thermostat wire You can select a maximum of 4 AC and 2 DC relays LOAD NAME First to Shed at Top Next looking across the other eight columns find the one that matches the Load Type column you just filled in Using the number atthe top ofthe column look in the table below to determine the settings ofthe three jumpers JP2 JP3 and Jp4 A Y foryes means the jumper should be installed and an N for no means there should not be a jumper installed COLUMN NUMBER RELAY SHED ORDER Top is First Shed
4. into the circuit breaker bus to feed power to the branch breakers The remaining six positions on the Main Distribution Panel may be occupied by single or dual units All the loads in the RV including the inverter converter are fed from the branch breakers The 120 VAC output of the inverter is fed to a sub panel containing three positions that may be occupied by single or dual units Energy Management Note When connected to 50 Amp 240 VAC service or generator service the Energy Management features ofthe unit are disabled and the unit switches all controlled loads ON The main neutral line is routed through the magnetically coupled current sensor which measures the current flowing through the neutralline This is the total amount being drawn by all the 120 volt appliances in the RV when the available power service is 120 VAC When this current exceeds 30 Amps 20 Amps if the threshold has been set lower and 240 VAC or generator service is not available the 50 AMP SMART EMS will turn off the controlled loads in an effort to bring the total currentto the limit ofthe incoming service 131 Eisenhower Lane North Intellitec Lombard IL 60148 630 268 0010 1 800 251 2408 www intellitec com 2 P N 53 00684 100 Rev B 011905 50 AMP Smart Energy Management System Model 800 Controlled Loads The system offers control of up to six powered loads each one connected to one of the relay circuits of the 50 AMP Smart EMS system F
5. 50 AMP Smart Energy Management System Model 800 SERVICE MANUAL FIRST SHED NEXT SHED NEXT SHED NEXT SHED NEXT SHED LAST SHED 50 Amp EMS Display Panel P N 00 00684 000 OM Oni 120 20 ME 20 2o ME zo 20 126 2 20 i 20 20 20 CLECE n m m mt mm omo omo omo oto ono omo ofo omo 50 AMP EMS MODEL 800 DISTRIBUTION PANEL P N 00 00683 300 CAUTION The 50 AMP SMART EMS Model 800 is a centralized power switching fusing and distribution center Power from the 120 240 volt power source is fed into the box The potential of lethal electrical shock is present in this box Inadvertent shorts at this box could result in damage and or injury All servicing of this box should be done ONLY by a qualified Service Technician Diagnostic tools required Low current Test Light Accurate Voltmeter digital read out preferred Clam on AC ammeter 131 Eisenhower Lane North Intellitec Lombard IL 60148 630 268 0010 1 800 251 2408 www intellitec com 1 P N 53 00684 100 Rev 011905 50 AMP Smart Energy Management System Model 800 The 50 Amp Smart EMS Model 800 consists of two elements the Display Panel and the Model 800 D
6. LY 131 Eisenhower Lane North Intellitec Lombard IL 60148 630 268 0010 1 800 251 2408 www intellitec com 12 P N 53 00684 100 Rev B 011905 50 AMP Smart Energy Management System Model 800 Trouble Shooting If the following problems occur proceed with analysis in the order in which these steps are listed I No 120 volt appliances working A Checkincoming power source 1 Make sure the shore power cord is plugged into the outlet 2 Check the circuit breaker at the shore power outlet to be sure it is set Turn it off and then back on to be sure 3 Check the 50 Amp Main circuit breakers in the EMS Distribution Panel to be sure they are set Turn them off and then back on to be sure 4 Using a circuit checker be sure the 30 Amp shore power outlet has 120 volts available Check Change Over relay if so equipped 1 Measure the voltage at the incoming side of the Main 50 Amp breaker If voltage is NOT the same as the incoming line repair the change over Refer to the change over service literature for trouble shooting Il 120volts available at non controlled appliances and receptacles Controlled appliances do not operate A Check the 12 volt power to the EMS module 1 Check 12 volt 3 Amp fuse on EMS Control Module Replace if necessary B Check 120 volt circuit breakers in EMS 1 Reset circuit breakers if necessary Check for presence of voltage at branch circuit breakers with voltmeter 2 3 Check for pres
7. Panel can be mounted remotely and connects to the main unit with a light gauge four wire cable Six Power Status LED s indicate power is applied to those loads These LED s are on when the power is applied The Load Meter has a two digit display to indicate the amount of current actually being drawn by all the appliances in the coach Four Service Type LED s indicate the source for 120 240 VAC power Three of these sources are automatically detected and indicated by the EMS namely Gen Set service 50 Amp 240VAC service and 30 Amp 120 VAC service The 20 Amp service mode is not automatically detected and the operator must manually select the 20 Amp mode when 20 Amp service is available The Service Select button allows the current threshold to be set to either 30 Amps pressing this button again will switch the system back to the 30 Amp mode 131 Eisenhower Lane North Intellitec Lombard IL 60148 630 268 0010 1 800 251 2408 www intellitec com 4 P N 53 00684 100 Rev B 011905 50 AMP Smart Energy Management System Model 800 If the pictured adaptor is used on the incoming service press the service select button to select the 20 Amp mode When power is first applied the system will always be in the 30 Amp mode The 30 20 Amp indicator LED will be on when the system is in the 30 Amp mode Momentarily pressing this button will switch the system to the 20 Amp mode Momentarily pressing this button again will switch the system back to th
8. are 8 positions for circuit breakers on the Main Distribution Panel and 3 positions for circuit breakers on the Sub Panel in the box The circuit breakers can be single or dual types The breakers in the two center positions of the Main Distribution Panel Must be rated at 50 Amps to be used as the Main Breakers The following breakers are suitable for MAIN and BRANCH breakers Eaton Cutler Hammer BR BD GFCB Filler Plate BRFP Siemens DPD QP QT Filler Plate QF3 The replacement circuit breakers must be of the same type and rating Branch circuit wires should be routed through the remaining knock out holes in the back of the box The wires should be stripped and the ground wire of each cable connected to the GROUND bar terminal strip The white or neutral wires should all be connected to the NEUTRAL bar terminal strip The black or hot leads of all the uncontrolled loads should be connected to their associated breakers Each terminal screw should be tightened to 76 in Ib of torque See the box drawing If removed during installation the white jumper wire should be re installed between the NEUTRAL block and J6 terminal 5 of the EMS module labeled NEUTRAL See box drawing page 15 To connect the 120 volt controlled loads jumper wires should be connected from the respective circuit breakers to the associated screw terminals of J6 and J7 on the EMS control module d NOTE To insure proper operation of the source sensing circuitr
9. ate a possible fire hazard EMS CONTROL MODULE PLUGS PINS AND FUNCTIONS J1 2 pin Molex KK 100 connector HI POT TEST Power Up Function Hi Pot Override Hi Pot Override J2 3 pin Amp Mate n Lok connector Power connector Pin Function 1 12 Volts Supply 2 3 12 Volts Gen Set Run input Chassis Ground J3 2 pin Molex KK 156 Current Sensor Connector Pin Function 1 Current Sensor Input 2 Current Sensor Input J4 6 pin Amp Mate n Lok connector Control Relays 5 amp 6 contacts 2 5 Function Relay 5 N O Relay 5 COM Relay 5 N C Relay 6 COM Relay 6 N C Relay 6 N O 131 Eisenhower Lane North Intellitec Lombard IL 60148 630 268 0010 1 800 251 2408 www intellitec com 11 P N 53 00684 100 Rev B 011905 50 AMP Smart Energy Management System Model 800 J5 4 pin Molex KK 156 Display Panel Connector Mating Housing Molex 09 50 3041 Function Data Ground 4 30 20 Amp Select Line J6 5 Position Terminal Block Pin 1 Power 2 3 Term Function 1 From Circuit Breaker for Relay 2 Must be connected to a LINE 2 Breaker Output of Relay 2 From Circuit Breaker for Relay 1 Must be connected to a LINE 1 Breaker Output of Relay 1 Neutral J7 4 Position Terminal Block Term Function Output of Relay 3 From Circuit Breaker for Relay 3 Output of Relay 4 From Circuit Breaker for Relay 4 NOTE J6 and J7 terminal blocks Will accept up to 12 GA or 14 GA copper wire ON
10. d fuse is acceptable since the EMS is internally protected with a 3 Amp fuse The connections are as follows J2 Pin Function 12 Volts Gen Set Run Input Ground The low voltage controlled load connections are made through J4 a 6 pin Mate N Lok connector on the low voltage side of the control module The connections are as follows J4 Pin Function Relay 5 Normally Open Relay 5 Common Relay 5 Normally Closed Relay 6 Common Relay 6 Normally Closed Relay 6 Normally Open The low voltage controlled load relay connections are typically made to the thermostat wires of the air conditioners The normally open contacts are wired in series with the thermostat This means that the thermostat wire is cut and the two ends are wired to the Common and the Normally Open contacts of the relay s In this way the EMS can interrupt the operation of the compressor just as the thermostat does The low voltage wires are brought into the box through the large hole in the lower right hand corner ofthe back of the box There are several methods to utilize Relay 5 and 6 connections for controlling air conditioner systems with the EMS 1 If only the compressors ofthe front and rear A C s are to be controlled connections are typically made to the low voltage compressor control wires of the air conditioners The normally closed contacts are wired in series with the compressor control lead This means that the compressor control wire is cut and the two ends are
11. e 30 Amp E mode The Display Panel can also be used to display the value of current stored in memory for each of the six loads To display the values of current stored in memory for each of the six loads push and hold the Service Select button The uppermost LED will illuminate and the stored value will appear on the Load Meter Pushing Service Select again will cycle to the next load After the last stored value has been displayed the unit will display average current if the unit is in the AVERAGING mode indicated by the decimal point in the lower right corner of the Load Meter Otherwise the Load Meter will return to normal operation and display total current draw INSTALLATION The Control Module The first step when installing an EMS is to determine which loads will be controlled and in what order they will be shed A typical scheme would be to control the two air conditioners the water heater and the washer dryer With these loads the first load to be shed should be the water heater as its loss of operation would be the least noticed it would switch to operate on gas if needed The next would be the bedroom air the third would be the washer dryer and finally the main air Choosing this sequence would provide the least inconvenience to the occupants The EMS Control Module has three jumpers on the board that determine the order of shedding of the loads These jumpers are labeled JP2 JP3 and JP4 See figure below
12. ence of voltage at EMS terminals with voltmeter 4 Check wire from EMS Control Module to neutral bar is installed Some controlled appliances turn on others do not A Reduce total current appliance may be shed B Check wiring to and from EMS Control Module 1 Check wiring from circuit breakers to EMS Control Module 2 Check wiring from EMS Control Module to controlled appliance 3 Check for power at associated EMS relay terminal IV Branch circuit breaker trips when power is applied A Check wiring for shorts V Air conditioner doesn t work A Check thermostat wiring and settings B Check air conditioner 131 Eisenhower Lane North Intellitec Lombard IL 60148 630 268 0010 1 800 251 2408 www intellitec com 13 P N 53 00684 100 Rev B 011905 50 AMP Smart Energy Management System Model 800 Trouble Shooting Shedding order incorrect A Check jumper setting per Figure on page 5 and Tables on page 6 B Check relay wiring per Table on page 6 Remote Display out or strange characters are displayed Check wiring between J5 on EMS Control Module and Display Panel Pin Function Voltage Power 12V Data Ground Ground Ground Select Line Ground 12V when pressed Wirng 11 22 33 44 Both the EMS Control Module and Display Panel have internal protection Shorts or mis wiring should not cause the units to fail Vill Remote Display does not indicate GEN SET service source when generator is runnin
13. f current that was removed which is the value for that load This value is placed in memory If the current remains above the service limit the system will turn off the next load in the shedding table Again it calculates the amount of current that was removed and places this value which is the value for that load in memory The system continues to turn off loads until the total current falls below the service limit or all of the six controlled loads have been shed Thru this process the system has learned the amount of current that each particular load draws This feature compensates for the differences in current draw over a range of line voltage and ambient temperature by re learning the load each time it is turned off or shed The 50 Amp Smart EMS now waits until the total current is lower than the service limit and enough current is available as compared with the amount in memory for the last load shed before it will turn that load back on This assures that there is sufficient currentto operate the load Note There is a two minute minimum delay period after a load is shed before the load will be turned back on again to prevent air conditioners from turning on with a head of pressure 131 Eisenhower Lane North Intellitec Lombard IL 60148 630 268 0010 1 800 251 2408 www intellitec com 3 P N 53 00684 100 Rev B 011905 50 AMP Smart Energy Management System Model 800 3 HOUR AVERAGING The R V I A Recreational Vehicle
14. ff and the jumper removed from J1 If not the problem must be corrected before proceeding further SYSTEM TEST All the 120 volt loads should be turned off or disconnected Both 120 volt AC and 12 volt DC power should now be applied to the system When this is done the relays should be heard pulling in On the Display Panel the numeric display should read O the six Power Status LED s should come on and the 30 Amp Service Type LED should light A clamp on type ammeter should be used to measure the current being supplied by the 30 Amp shore power cord Connect or turn on one of the controlled AC loads It should operate and the numeric display or the clamp on ammeter should show the amount of current that load is drawn Turn that appliance off and repeat this with each ofthe others 131 Eisenhower Lane North Intellitec Lombard IL 60148 630 268 0010 1 800 251 2408 www intellitec com 10 P N 53 00684 100 Rev B 011905 50 AMP Smart Energy Management System Model 800 To test the load shedding turn on all the controlled appliances The total current drawn should exceed 30 Amps If not add additional loads to the non controlled receptacles When the total amount of current exceeds 30 Amps the loads should begin to turn off to bring the total below 30 Amps FUSES F1 3 Amp ATO type for EMS Control Module circuitry only DO NOT replace with a fuse of higher rating This could result in severe damage to the circuitry or cre
15. g Check wiring between generator run light circuit and J2 pin 2 on EMS Control Module J2 pin 2 should measure 12Vdc or greater when generator is running and 0 Vdc otherwise VIX Remote Display does not indicate 50 AMP service source when 50 Amp 240 VAC shore power is Connected Check to make sure that jumpers are present between any LINE 1 breaker and J6 terminal 3 and any LINE 2 breaker and J6 terminal 1 Also check that the NEUTRAL jumper is in place between J6 terminal 5 and a position on the NEUTRAL block With 50 Amp service available the voltage between J6 3 and J6 1 should measure 240 VAC With any other source the voltage between J6 3 and J6 1 should measure 0 VAC In addition the voltage measured between J6 3 and J6 5 should be 120 VAC and the voltage measured between J6 1 and J6 5 should be 120 VAC t 1 t 131 Eisenhower Lane North n I Lombard IL 60148 e ec 630 268 0010 1 800 251 2408 www intellitec com 14 P N 53 00684 100 Rev B 011905 Model 800 TM INV3HO9VIG 9NIHIM IWOIdAL AIS LIOA ZI 3GIS LIOA 07 021 3din9 SSH3NMO 33S Lg sSMadWnfr NOILdO HOLO3NNOO AV1dSI0 ILONAN vaj O N 9 Z SSV19 LVLSOWYSHL YANOILIGNOS YIV SOINOYLIATS LN3AIWASDVNVW AOSH3N3 ZH09 2VAOZL VSL Speo pejouo SINA E o0 gt o c E Oo c gt Oo E E o e Ww Lomba
16. istribution Panel The Display Panel is mounted on a wall or suitable surface remotely from the Distribution Panel and convenient to the user The Model 800 Distribution Panel is a completely self contained 120 240 volt power distribution and energy management system intended tp be used in recreational vehicles Itis housed in a sheet metal enclosure with removable front panel It provides circuit protection for all the 120 VAC loads in the RV and a system of energy management to minimize the over loading and tripping of circuit breakers In addition the Model 800 Distribution Panel incorporates a sub panel to accommodate inverter converter connected loads Circuit Breakers The 50 Amp Smart EMS Model 800 Main Distribution Panel offers slots for eight single or dual standard 120 volt circuit breakers Two of these breakers located in the two center stab positions must be a 50 Amp Unit that act as a main input protection for each of the lines supplying the reminder of the branch breakers up to 12 An additional sub panel provides slots for three single or dual standard 120 volt circuit breakers for loads connected to the 120 VAC output of an inverter converter Energy Management The 50 Amp Smart EMS Model 800 automatically senses the available power to the vehicle It determines whether it is connected to a 120 VAC 30 Amp shore power source 240 VAC 50 Amp shore power source or Generator source Depending upon available power it control
17. of the power source If 240 VAC 50 Amp service is available the energy management feature is disabled and all control relay contacts are closed energizing all of the controlled loads The Control Module sends a signal to the Display Module which causes the load meter to go blank the 50 AMP service indicator to light and all power status indicators to light If the generator is running 120 VAC will be present at the L1 and L2 inputs and a 12 VDC signal will be present at J2 pin 2 on the Control Module In this mode the energy management feature is disabled and all control relay contacts are closed energizing all of the controlled loads The Control Module sends a signal to the Display Module causing the load meter to display actual load current the GEN SET service indicator to light and all power status indicators to light If 120 VAC is present at the L1 and L2 inputs and no 12 VDC signal is present at J2 pin 2 on the Control Module the EMS will assume that 120 VAC 30 Amp shore power is available and the energy management feature will be enabled If only 20 Amp service is available the user must select the 20 AMP service mode by momentarily pressing the 20 30 Amp select switch on the Control Panel Initially all relay contacts are closed and the total current is monitored If the total current should exceed the service limit the system will turn off the first load in the shedding table As it turns the loads off it calculates the amount o
18. ol Module assuring it is properly seated on all four pins Note This cable is polarized the latches of each end of the connector mate to each other and will go on easily in the right direction but can be forced on in the reverse direction The Display Panel should be plugged onto the harness observing the polarity as before The panel should then be installed in the hole and screwed in place using two 6 flat head screws through the holes in the panel A white function label should be lettered to correspond to the order of load shedding and installed behind the cover label The cover label should be placed against the front panel and the trim bezel snapped on to hold the label in place PERFORMANCE TEST The system is now ready for testing Hi POT TEST At the installers preference to assure there are no potential shorts a Hi Pot test can be performed on the installation To do this 12 volts must be applied to the system Ajumper wire must be installed to tie the two pins of the Hi Pot Test plug J1 to turn the system on without the presence of 120 volt power This plug is located on the right side of the EMS Control module The relays on the module should be heard clicking as they pull in On the Display Panel the LED s should light and the numeric display should read 0 The Hi Pot test should now be conducted in accordance with standard procedures for the tester being used Assuming the system passes the covers should be taken o
19. our of these relays relays 1 2 3 and 4 are 30 Amp relays with normally open contacts used to interrupt the 120 volt power to the loads These circuits are intended to control 120 volt appliances such as refrigerator water heater washer dryer coffee maker etc For the 120 VAC switched loads power is routed from the individual branch circuit breakers to one of these 120 VAC relays on the Control Module The controlled load is then fed from that relay The remainder of the relays relays 5 and 6 are intended to switch low voltage loads Relays 5 and 6 are single pole double throw relays with all contacts available These relays are intended to control air conditioners or other appliances equipped with low voltage controls or thermostats The contacts of the relays are typically wired in series with the low voltage controls or thermostats of air conditioners so the EMS turns off only the compressor or the compressor and fan These circuits could also control other 120 volt appliances if an additional control relay is added externally OPERATION IN VEHICLES USING AVAILABLE SERVICE If 120 VAC or 240 VAC is not available at the L1 or L2 inputs J6 pin 3 and 1 respectively on the Control Module the EMS shuts itself off This feature is intended to prevent the EMS from drawing current from the 12 VDC battery supply when not in operation When 120 VAC or 240 VAC power is applied the system automatically powers up and determines the nature
20. ox should be routed through the holes in the back and secured using approved cable connectors The wires should be Copper conductors ONLY with the appropriate size and insulation to meet N E C The main supply cable should be brought through the large hole in the lower center of the box and secured with an appropriate connector The LINE 1 and LINE 2 supply mains should be connected to the corresponding main breaker The main ground lead should be connected to the nearest GROUND bar terminal strip The current sensor should be mounted in a knock out hole near the insulated NEUTRAL block so that the signal leads from the current sensor exit the rear of the box These signal wires should be routed through the lower right hole into the low voltage section of the EMS and connected to J3 a 2 pin connector on the low voltage side of the Control Module The inverter converter should be wired so that the AC input to the inverter converter is supplied via a branch breaker on the Main Distribution Panel and the 120 VAC output of the inverter converter wired to the individual lug on the far right side of the sub panel 131 Eisenhower Lane North Intellitec Lombard IL 60148 630 268 0010 1 800 251 2408 www intellitec com 7 P N 53 00684 100 Rev B 011905 50 AMP Smart Energy Management System Model 800 The main NEUTRAL wire should be routed through the CURRENT SENSOR and connected to an appropriate position on the insulated NEUTRAL block There
21. rd IL 60148 131 Eisenhower Lane North 630 268 0010 1 800 251 2408 Josueg zuan SWI uBnouu ssed snw juauino dwy 0g 40 02 OWA 021 404 TWHLNAN GALVINSNI S 9099990090099 vL 0L Jea EANN MOSN3S S punous dinb3 SMV nb o 2 E jj tec Intelli 100 Rev B 011905 00684 P N 53 5 1 www intellitec com 50 AMP Smart Energy Management System Model 800 131 Eisenhower Lane North Intellitec Lombard IL 60148 630 268 0010 1 800 251 2408 www intellitec com 16 P N 53 00684 100 Rev B 011905
22. s the operation of 6 possible loads that may include the front and rear air conditioner fan and compressor using low voltage switching and other 120 Volt loads such as the refrigerator water heater washer dryer microwave oven or other large appliances These appliances may be any type load but are typically heavier loads those whose use can be postponed until a time when current is available for their use If the available power source is 120 VAC 30 Amp shore power it attempts to keep the total 120 volt current draw to less than 30 Amps HOW IT WORKS The 50 AMP SMART EMS Model 800 provides main circuit protection for 120 240 VAC single phase incoming lines and branch circuit protection for up to 12 circuits including Energy Management of up to six selected branch circuits A sub panelis available on the Model 800 for up to 6 sub breakers for inverter connected loads If 120 VAC 30 20 Amp source is available the control helps to limit the total current draw of all the appliances in the RV at or below 30 20 Amps provided by the main power feed Circuit Protection Circuit protection for ALL the 120 VAC loads is offered by standard reset able circuit breakers provided by the installer There are eight positions available for circuit breakers on the Main Distribution Panel The breakers located in the two center stab positions must be 50 Amp breakers to act as the main breakers for the entire system These breakers back feed power
23. stat control lead This means that the low voltage thermostat control wire is cut and the two ends are wired to the Common and the Normally Closed contacts on Relay 5 In this way the EMS can interrupt the operation of the fan just as the thermostat does Finally on the Control Module there is a small 2 pin plug labeled J1 which is only used for the High Pot Test on the system When the two pins are shorted together the EMS will operate without the presence of 120 VAC 131 Eisenhower Lane North Intellitec Lombard IL 60148 630 268 0010 1 800 251 2408 www intellitec com 9 P N 53 00684 100 Rev B 011905 50 AMP Smart Energy Management System Model 800 Now the 50A EMS Model 800 Distribution Panel should be moved into the mounting hole being careful not pinch any of the wires It should be screwed in place using four 8 round head screws into the 4 holes in the side flanges The front cover should be secured into place with the 6 screws provided in the holes in the top and bottom flanges DISPLAY PANEL Select a convenient location for the panel where it can be easily viewed by the owner Cuta hole forthe panel as shown Remote Panel Cutout Atwo foot long double ended pigtail is available as Intellitec P N 11 00589 002 This pigtail may be cut in half and up to 40 feet of additional cable may be spliced into the harness Route the harness from the hole for the display panel to the EMS Plug the cable into J5 on the EMS Contr
24. wired to the Common and the Normally Closed contacts of Relay 5 or 6 In this way the EMS can interrupt the operation of the compressor just as the thermostat does 2 If both the compressors and fans of the front and rear A C s are to be controlled connections are typically made to the low voltage thermostat control wires of the air conditioners The normally closed contacts are wired in series with each thermostat control lead This means that the thermostat control wire is cut and the two ends are wired to the Common and the Normally Closed contacts of Relay 5 or 6 In this way the EMS can interrupt the operation of the compressor and fans just as the thermostat does 3 If the compressor and fan for one of the A C systems are to be controlled individually connections are typically made to the individual low voltage thermostat control wires for the fan and compressor of the air conditioner The Relay 6 connections are typically made to the low voltage compressor control wires of the air conditioner to control the compressor The normally closed contacts are wired in series with the compressor control lead This means that the low voltage compressor control wire is cut and the two ends are wired to the Common and the Normally Closed contacts on Relay 6 The Relay 5 connections are typically made to the low voltage thermostat control wires of the air conditioner to control the fan The normally closed contacts are wired in series with the thermo
25. y on the 50 AMP EMS jumper wires must always be connected from a line 1 breaker to J6 terminal 3 and from a line 2 breaker to J6 terminal 1 These connections must be made even though Relay 1 or Relay 2 may not be used Q for controlled loads J The black wires to the controlled loads should be connected to the proper relay output screw terminals of J6 and J7 on the EMS control module Be sure these wires are under the screw terminals and that they are tight The connections are as follows J6 Terminal Function From Circuit Breaker for Relay 2 Must be connected to a LINE 2 Breaker Output of Relay 2 From Circuit Breaker for Relay 1 Must be connected to a LINE 1 Breaker Output of Relay 1 Neutral J7 Terminal Function Output of Relay 3 From Circuit Breaker for Relay 3 Output of Relay 4 From Circuit Breaker for Relay 4 NOTE J6 and J7 terminal blocks Will accept up to 12 GA or 14 GA copper wire ONLY A WN NN oO FP c 131 Eisenhower Lane North Intellitec Lombard IL 60148 630 268 0010 1 800 251 2408 www intellitec com 8 P N 53 00684 100 Rev B 011905 50 AMP Smart Energy Management System Model 800 The 12 VDC voltage connections are made through J2 a 3 pin Mate N Lok connector on the low voltage side of the control module The 12 volts should be supplied from a source fused at 3 Amps minimum and capable of delivering up to 1 Amp of AVERAGE current Protecting this connection with a higher rate
Download Pdf Manuals
Related Search
Related Contents
Corporate PowerPoint Guidelines - ZF CI-Portal Spirit XBR25 User's Manual datasheet PDF L`éco-citoyen n°14 (mars 2012) - Sirtom de la région Flers Curtiss-Wright / DY4 SVME / DMV-179 Manual Séance n°6 Mode d`Emploi note de service N° 4 Copyright © All rights reserved.
Failed to retrieve file