Home
        Keeprite-R4A3-service-manual
         Contents
1.                                                                                                                                                                                                                                                                                                                                                                                                                                       Note  Long radius elbows recommended    A07123  Fig  10     Suction Line Loop             __     EXAMPLE        BY ELIMINATION      TO DETERMINE INTERNAL CONNECTIONS OF SINGLE   e        PHASE MOTORS  C S R  EXCEPT SHADED POLE  e       POWER OFF  DEDUCTION   2      GREATEST RESISTANCE  RUN WINDING  R   0   9  5 80          START WINDING  S   OHMMETER  6 100 SCALE  2         SMALLEST RESISTANCE   2  is COMMON  C      REMAINING RESISTANCE   2  is COMMON   Pos 529 THEREFORE   1  IS    0 60            START WINDING  S          IS RUN WINDING               A88344  Fig  11     Identifying Compressor Terminals    Francis Plumbing  amp  Heating   www FrancisPlumbing com   613 224 0041   office francisplumbing com    421 08 5400 00 16    Specifications subject to change without notice     SERVICE MANUAL    Electrical Failures    The compressor mechanical pump is driven by an electric  motor within its hermetic shell  In electrical failures   compressor does not run although external electrical and  mechanical systems appear normal  Compressor must be  checked electricall
2.                                                                       1                                        Or  OD DID DIDI DIO                                               EN EN EA RA EN EN        NIN ool                                              RT RE                OCLOLOLOINT ODIO  OTR          421 08 5400 00 36    Specifications subject to change without notice     SERVICE MANUAL    R 410A  amp  R 22 Split System AC  amp  HP    TWO STAGE  CAT   CAS9   CH6        9   SA6   SH5    Application Guidelines    ICP designed and tested the two stage air conditioner and  heat pump products with R 410A refrigerant to operate at a  minimum outdoor operating ambient in cooling mode at  55  F and the maximum outdoor operating ambient in  cooling is 125  F 51 6  C  The maximum outdoor operating  ambient in heating mode is 66  F 18 8  C  Continuous  operation in heating mode is approved to  30 F  34 4 C   Thermostat options for the two stage units are as follows     e     Dx   Dx       four wire connections for  Communicating wall control     e W Y1 Y2  and    wire connections for standard   non communicating thermostat     CA7   CA9   CH6  and  CH9 units can run  and are  matched with  both Observer amp  communicating wall control  and non communicating 2 stage indoor fan coils and  furnaces  Only unit combinations listed in the two stage  specifications  technical support manuals  or  AHRldirectory org are recommended   Line sets for two stage units are similar to the single s
3.                     BP COT                                                                         gt                41  1                   Ri ofp           Of         og              KSA  KOLI KOLI KOL                                Keu                    RP             RE RE RPE RE RE RE RE RE RT 02            021 021                                   COP OOFOOTN INI      or               OPPO    gt                         I                                                            oi ot                       52     53     5554 1    55    56      58      59     60    61   62    63      64      65      66      68     69            2   78     79   80      82     83      84      85      86      87      88      89      90     91     92         OLOLOIN                       5                     gt                                                  opr   1                                                 e gt   DI     DIO OOO                                                                                EN ES ES      EN EN                                                                             DAI LA LA K ES ES e DS DS E e e KA eA eA I e eA A ES A e DS E e                      o  e gt   OI DIDI                                                                                   EN EN RP REPRE RP ARTRT RE RE RE RE RT OO     ie                                                                                    of           e                                                    N Co  
4.              See Humidifier Instructions for proper wiring     A150027  Fig  37     2 Stage Thermostat with Single Stage  Furnace  and 2 Stage Air Conditioner       Humidify T   Humidifier Solenoid  Outdoor Air Temp Valve    Remote Room Sensor    OAT RRS Com    A150002  Fig  34     Wall Control with Variable Speed Furnace and  2 Stage Heat Pump   non communicating     WALL CONTROL SINGLE STAGE    FURNACE    TWO SPEED  AIR CONDITIONER       N A                   COOL STAGE 1                   HEAT STAGE 1   wj                      COOL STAGE 2                            FAN                   24 VAC HOT                         DEHUMIDIFY                      24 VAC COMM                               HUMIDIFY          N A                OUTDOOR poi    SENSOR        CONNECTION                                          See Humidifier Instructions for proper wiring     A150004  Fig  36     Wiring for Single Stage Furnace with 2 Stage  Air Conditioner       LEGEND          24v Factory Wiring          24  Field Wiring    n Field Splice Connection             A09306    42108 5400 00 Francis Plumbing  amp  Heating   www FrancisPlumbing com   613 224 0041   office francisplumbing com 46    Specifications subject to change without notice     SERVICE MANUAL  CARE AND MAINTENANCE    To assure high performance and minimize possible  equipment malfunction  it is essential that maintenance be  performed periodically on this equipment  The frequency  with which maintenance is performed is depen
5.             BAR STOCK FRONT SEATING VALVE    A91447  Fig  12     Suction Service Valve  Front Seating   Used in Base and Comfort ACs and HPs    NOTE  All outdoor unit coils will hold only factory supplied  amount of refrigerant  Excess refrigerant  such as in  long line applications  may cause unit to relieve pressure  through internal pressure relief valve  indicated by sudden  rise of suction pressure  before suction pressure reaches 5  psig  35kPa   If this occurs  shut unit off immediately  front  seat suction valve  and recover remaining pressure   Heating Piston  AccuRater      Heat Pumps Only   In this product line  AccuRater pistons are used to meter  refrigerant for heat pump heating mode only  All indoor coils  are supplied with a bi flow TXV for metering in the cooling  mode  AccuRater   piston has a refrigerant metering hole  through it  The piston seats against the meters refrigerant in  to the outdoor coil in heating and allows refrigerant to flow  around it in cooling mode    There are 2 types of liquid line connections used  Flare  connections are used in R 22 systems    1  Shut off power to unit    2  Pump unit down using pumpdown procedure  described in this service manual    3  Loosen nut and remove liquid line flare connection  from AccuRater      4  Pull retainer out of body  being careful not to scratch  flare sealing surface  If retainer does not pull out  easily  carefully use locking pliers to remove it    5  Slide piston and piston ring out by insert
6.           gt   MES  Nm s  OZ              Bi                         n  PADS                                                                                        7 3 COMMSTATUS 2  Dec          of Cwivi v2                      f  FE  a             bd  m  m                                        UTE        v2 0                         us    Liquid Line Solenoid  A150064  Fig  30     2 Stage Control Board    TROUBLESHOOTING    Troubleshooting circuit board FAST    1185237  1186140    The Communicating Series outdoor units all use the same  control board  A model plug is used to identify the system  type  and set the operating parameters for airflow  start  circuit timing etc   See Model Plug section     Replacement boards may have a different part number from  the original board  A newer board will always be backward  compatible to previous units if it is superseded at Fast Parts   Old boards are not always forward compatible due to new  functions  or software changes made to resolve field issues     Systems Communication Failure  If communication with the Communicating control is lost with  the wall control  the control will flash the appropriate fault    code   See Table 15   Check the wiring to the wall control  and the indoor and outdoor units    Pressure Switch Protection   The outdoor unit is equipped with high  and low pressure  switches  If the control senses the opening of a high  or  low pressure switch  it will respond as follows    1  De energize the appropriate co
7.        Se    F  ER    T  TAB ON BOTTOM OF  START RELAY TO BE  PLACED IN THIS CORNER                         C    A10157  Fig  29     Start Relay and Capacitor Mounting Locations    Communicating in Cube Cabinet                                v5 2    tf DDF CCH     0 0 00                                                                                                                         RED      VEL                              H                e E  4 ff il  F 1  Btu  D 1        x    CF Put   Uu SEC2 es               he                      ame     mz  w  x 7             29    Walz  wr  as m                                                                                                                               Exe  du za    at                aR     TA T Som Da              CLI         3coMMsraru            Dera        H1 VT VZ SE                    mm en      1  2          0   0                          2 g CE                 f    UTILITY RELAY             UTILITY SIGNAL   lt               RELAY  gt       SUPPLIED BY UTILITY PROVIDER                         A150063    421 08 5400 00    R 410A  amp  R 22 Split System AC  amp  HP           45 12         DDF CCH     0 0 00                                                                                                                                                                  RED      VEL                   e       um             NT F  D 4 E i 77  i 1       E           PL   U SEC2 4         Lj                   um  LE
8.     SERVICE MANUAL    Table 8   R 410A Subcooling Chart  Liquid Line Temperature    F      7       57            o  o  2  E  o    g   o    Ln  s       03  or     I                   NT  s                       sss  Le  s Er Esp 71                         A         sa      2  sof   ro  7                    eo   76   sof                NETT RTT T NEN      of         ef       f f  of                     f f  o                  osf orf        eof                                                          e                                               or pe s                               er es        Dr                          eer ps fro f                s pur ps pers  9 E           73  120  121   123  125  126  128  129  131   144       NE      CEST EST        N  NIS       Ek g  amp  5   amp  a       SERES         Q                               co EN                                                         5    CF                   cof sp sol sp  ps    P T    Liq Press   psig        421 08 5400 00    Specifications subject to change without notice     33    R 410A  amp  R 22 Split System AC  amp  HP    SERVICE MANUAL    Table 9   R 410A Superheat Chart    Vapor Line Temperature    F     2 d  lt  3     M  n n  R M     d  R M    Eg             lt                       lt                       lt    lt                    oel l   a     lt                                               lt                                                                            SE     SE   SE   SE   
9.    INDOOR COIL  FROSTED    SLIGHTLY  LOW ON  REFRIGERANT    LIQUID LINE  SLIGHTLY  RESTRICTED    PISTON  RESTRICTED    INCORRECT  SIZE  PISTON    INDOOR COIL  STRAINER  RESTRICTED    INDOOR  BLOWER MOTOR  DEFECTIVE OR  CYCLING ON OL    Fig  38     Air Conditioner Troubleshooting Chart    Specifications subject to change without notice        HIGH SUCTION  LOW  SUPERHEAT    UNIT  OVERCHARGED    INCORRECT  SIZE  PISTON    FAILED  TXV    A90208    421 08 5400 00    SERVICE MANUAL    HEAT PUMP    R 410A  amp  R 22 Split System AC  amp  HP    TROUBLESHOOTING HEATING CYCLE    NO HEATING OR  INSUFFICIENT  HEATING       COMPRESSOR  WILL NOT RUN    CONTACT  OPEN    DEFECTIVE LOW   VOLTAGE  TRANSFORMER    REMOTE  CONTROL  CENTER  DEFECTIVE    CONTACTOR  COIL OPEN OR  SHORTED    OPEN INDOOR  THERMOSTAT    LIQUID LINE  PRESSURE  SWITCH OPEN    LOSS OF  CHARGE       OPEN CONTROL  CIRCUIT    Francis Plumbing  amp  Heating   www FrancisPlumbing com   613 224 0041   office francisplumbing com    421 08 5400 00             CONTACTOR  CLOSED    COMPRESSOR  POWER SUPPLY    LOOSE LEADS AT  COMPRESSOR    FAULTY START  GEAR  1 PH     COMPRESSOR  STUCK    COMPRESSOR  INTERNAL  OVERLOAD  OPEN    OPEN SHORTED  OR GROUNDED  COMPRESSOR    WINDINGS    DEFECTIVE RUN  CAPACITOR    DEFECTIVE  START  CAPACITOR          COMPRESSOR  RUNS BUT  CYCLES ON  INTERNAL  OVERLOAD    DIRTY FILTERS  OR INDOOR  COIL    INDOOR FAN   STOPPED OR  CYCLING ON  OVERLOAD    DEFECTIVE FAN  MOTOR  CAPACITOR    DAMAGED LOOSE LEAD
10.    R 410A  amp  R 22 Split System AC  amp  HP    The thermistor comparison is not performed during low  ambient cooling or defrost operation     Failed Thermistor Default Operation    Factory defaults have been provided in the event of failure  of outdoor air thermistor  OAT  and or outdoor coil thermistor   OCT     If the OAT sensor should fail  low ambient cooling will not be  allowed and the one minute outdoor fan off delay will not  occur  Defrost will be initiated based on coil temperature and  time    If the OCT sensor should fail  low ambient cooling will not be  allowed  Defrost will occur at each time interval during  heating operation  but will terminate after 5 minutes    If there is a thermistor out of range error  defrost will occur at  each time interval during heating operation  but will  terminate after 5 minutes    Count the number of short and long flashes to determine the  appropriate flash code  Table 15 gives possible causes and  actions related to each error          OCT Thermistor  must be secured  tight on stub tube              A05408  Fig  32   Outdoor Coil Thermistor  OCT  Attachment    Table 14   Two Stage Compressor Resistances   Winding Resistance at 70  F 20       Winding 024 036  Start  S C  1 64 1 52  Run  R C  1 30 0 88    048 060  1 86 1 63  0 52 0 39    Francis Plumbing  amp  Heating   www FrancisPlumbing com   613 224 0041   office francisplumbing com    421 08 5400 00    44    Specifications subject to change without notice     SERVICE MA
11.    Reciprocating compressors may have a  noticeable discharge pulsation that could be  remedied with a field installed discharge muffler   Recommend loop by continuous tubing with no more  than 12 inches vertical and 6 inch horizontal loop    thunking    thumping    grinding  or   rattling  noise could indicate compressor internal  failures and may be verified by comparing the  compressor amperage to what the compressor  should be drawing according to a manufacturer s  performance data     10     11     R 410A  amp  R 22 Split System AC  amp  HP      A whistling or squealing noise during operation may    indicate a partial blockage of the refrigerant charge       A whistle on shut down could indicate a partial leak    path as refrigerant is equalizing from high to low side   On occasion  an in line discharge check valve has  prevented this sound       If a compressor hums but won t start it could indicate    either a voltage or amperage issue  Verify adequate  voltage and operational start components if installed   If it is drawing excessive amperage and voltage  doesn t appear to be the problem it may be assumed  a locked condition  Ensure refrigerant has had ample  time to equalize and boil out of the compressor before  condemning     When a heat pump switches into and out of defrost  a   swooshing  noise is expected due to the rapid  pressure change within the system  However  customers sometimes complain that the noise is  excessive  or it is sometimes accompanied by a   
12.    With non communicating thermostats  these are selected  by dip switches on the unit control board  With  Communicating thermostats  the Communicating control  wall control  The Communicating control selection overrides  the control board dip switch settings   AUTO defrost adjusts the defrost interval time based on the  last defrost time as follows    e When defrost time   3 minutes  the next defrost   interval 120 minutes     e When defrost time 3 5 minutes  the next defrost  interval 90 minutes     e When defrost time 5 7 minutes  the next defrost  interval 60 minutes     e When defrost time  gt 7 minutes  the next defrost  interval 30 minutes    The control board accumulates compressor run time  As the  accumulated run time approaches the selected defrost  interval time  the control board monitors the coil temperature  sensor for a defrost demand  If a defrost demand exists  a  defrost cycle will be initiated at the end of the selected time  interval  A defrost demand exists when the coil temperature  is at or below 32  F for 4 minutes during the interval     The defrost cycle is terminated when the coil temperature  reaches 65  F or 10 minutes has passed           Specifications subject to change without notice     37    421 08 5400 00    SERVICE MANUAL    On  CH6 models  defrost will occur in low  or high stage as  demanded by the thermostat or wall control regardless of  OAT    On  CH9 models  when OAT is  gt 25       3 9 C   defrost will  occur in low  or high stage 
13.    defective capacitor s   relays  wiring  etc  Compressor has  internal line break overload  so be certain it is closed     Open Circuit    4   WARNING    UNIT PERSONAL INJURY HAZARD  Failure to follow this warning could result in  personal injury     Use caution when working near compressor  terminals  Damaged terminals have the potential  to cause personal injury        Never put face or body directly in line with  terminals     To determine if any winding has a break in the internal wires  and current is unable to pass through  follow these steps       Be sure all power is off      Discharge all capacitors      Remove wires from terminals C  S  and R      Check resistance from C R  C S  and R S using an  ohmmeter on 0 1000 ohm scale    Because winding resistances are usually less than 10   ohms  each reading appears to be approximately 0 ohm  If   resistance remains at 1000 ohms  an open or break exists   and compressor should be replaced     ON         R 410A  amp  R 22 Split System AC  amp  HP    CAUTION    UNIT DAMAGE HAZARD    Failure to follow this caution may result in equipment  damage or improper operation     Be sure internal line break overload is not temporarily       Ground Circuit    To determine if a wire has broken or come in direct contact  with shell  causing a direct short to ground  follow these  steps   1  Allow crankcase heaters to remain on for several  hours before checking motor to ensure windings are  not saturated with refrigerant     2  Using an
14.   80  F  21 11  C and 26 67  C   Follow the procedure below   Unit is factory charged for 15ft  4 57 m  of lineset  Adjust  charge by adding or removing 0 6 oz ft of 3 8 liquid line  above or below 15ft  4 57 m  respectively              38    Specifications subject to change without notice     SERVICE MANUAL    For standard refrigerant line lengths  80 ft 24 38 m or less    allow system to operate in cooling mode at least 15 minutes   If conditions are favorable  check system charge by  subcooling method  If any adjustment is necessary  adjust  charge slowly and allow system to operate for 15 minutes to  stabilize before declaring a properly charged system     If the indoor temperature is above 80  F  26 67  C   and the  outdoor temperature is in the favorable range  adjust system  charge by weight based on line length and allow the indoor  temperature to drop to 80  F  26 67  C  before attempting to  check system charge by subcooling method as described  above     If the indoor temperature is below 70 F  21 11 C   or the  outdoor temperature is not in the favorable range  adjust  charge for line set length above or below 15ft  4 57 m  only   Charge level should then be appropriate for the system to  achieve rated capacity  The charge level could then be  checked at another time when the both indoor and outdoor  temperatures are in a more favorable range    NOTE  If line length is beyond 80 ft  24 38 m  or greater  than 20 ft  6 10 m  vertical separation  see Split System  L
15.   S  and R   4  Place instrument probes together and determine  probe and lead wire resistance   5  Check resistance readings from C R  C S  and R S   6  Subtract instrument probe and lead resistance from  each reading   If any reading is within  20 percent of known resistance   motor is probably normal  Usually a considerable difference  in reading is noted if a turn to turn short is present             Ww       Specifications subject to change without notice     17    421 08 5400 00    SERVICE MANUAL  REFRIGERATION SYSTEM    Refrigerant    4  WARNING    UNIT OPERATION AND SAFETY HAZARD    Failure to follow this warning could result in personal  injury or equipment damage    R 410A refrigerant which has higher pressures than  R 22 and other refrigerants  No other refrigerant may be  used in this system  Gauge set  hoses  and recovery  system must be designed to handle R 4104A  If you are  unsure consult the equipment manufacturer     4  CAUTION    UNIT DAMAGE HAZARD    Failure to follow this caution may result in equipment  damage or improper operation     The compressor in a R 410A system uses a polyol  ester  POE  oil  This oil is extremely hygroscopic   meaning it absorbs water readily  POE oils can absorb  15 times as much water as other oils designed for  HCFC and CFC refrigerants  Take all necessary  precautions to avoid exposure of the oil to the  atmosphere        In an air conditioning and heat pump system  refrigerant  transfers heat from one replace to another  Th
16.   energizes the T1 terminal on the circuit board  The T1             R 410A  amp  R 22 Split System AC  amp  HP    terminal energizes the defrost logic  This will energize the  OF2 fan relay start the outdoor motor  The T1 terminal must  be energized for defrost to function     When the cycle is complete  R Y is turned off and the  compressor and outdoor fan should stop  There is no  compressor delay built into this control     Defrost Sequence  FAST    1173636   1177927     The defrost control is a time temperature control that has  field selectable settings of 30  60  and 90 minutes  These  represent the amount of time that must pass after closure of  the defrost thermostat before the defrost sequence begins     The defrost thermostat senses coil temperature throughout  the heating cycle  When the coil temperature reaches the  defrost thermostat setting of approximately 32  F  it will  close  which energizes the DFT terminal and begins the  defrost timing sequence  When the DTF has been  energized for the selected time  the defrost cycle begins   and the control shifts the reversing valve into cooling  position  and turns the outdoor fan off  This shifts hot gas  flow into the outdoor coil which melts the frost from the coil   The defrost cycle is terminated when defrost thermostat  opens at approximately 65  F  or automatically after 10  minutes              Q                            OUTDOOR FAN  RELAY                         DEFROST THERMOSTAT  MUST BE CLOSED BEFORE  D
17.  22 Split System AC  amp  HP    be zero  indicating closed defrost thermostat   or  Communicating     for open thermostat  depending on  outdoor temperature    4  Jumper between DFT and R terminals on control  board as shown in Fig  7    5  Disconnect outdoor fan motor lead from OF2  Tape  lead to prevent grounding    6  Turn on power to outdoor unit     7  Restart unit in heating mode  allowing frost to  accumulate on outdoor coil    8  After a few minutes in heating mode  liquid line  temperature at defrost thermostat should drop below  closing set point of defrost thermostat of  approximately 32  F  Check resistance across defrost  thermostat leads using ohmmeter  Resistance of zero  indicates defrost thermostat is closed and operating  properly    9  Short between the speed up terminals using a  thermostat screwdriver  This reduces the timing  sequence to 1 256 of original time   See Table 2      Table 2   Defrost Control Speed Up Timing Sequence    MINIMUM MAXIMUM SPEED UP   PARAMETER  MINUTES   MINUTES   NOMINAL   30   minute cycle 27 33 7 sec  60   minute cycle 56 66 14 sec  90   minute cycle 81 99 21 sec  10   minute cycle 9 11 2 sec  5   minutes 5 5 1 sec    CAUTION    UNIT DAMAGE HAZARD    Failure to follow this caution may result in equipment  damage or improper operation     Exercise extreme caution when shorting speed up  pins  If pins are accidentally shorted to other terminals   damage to the control board will occur     10  Unit is now operating in defrost mod
18.  DRY NITROGEN    v    WAIT    v  v  CHECK FOR TIGHT  DRY SYSTEM   IF IT HOLDS DEEP VACUUM                                Y    CHARGE SYSTEM           95425  Fig  25   Triple Evacuation Method    26    Specifications subject to change without notice     SERVICE MANUAL    TROUBLESHOOTING WITH SUPER   HEAT    This troubleshooting routine was developed to diagnose  cooling problems using superheat in TXV systems  It is  effective on heat pumps in cooling mode as well as air  conditioners  The system must utilize a        as the  expansion device in cooling mode    Basic Diagnostics    NOTE  When checking refrigerant charge and  troubleshooting operating systems  the indoor airflow has  significant effect on the determination  If you are at this  stage  it is assumed you have already checked the  subcooling once and believe the charge is correct  From this  point  the airflow must be verified prior to proceeding  hence  step 1 below     1  Check or verify proper indoor airflow       e Indoor air filter  e Duct dampers and supply registers are open  e   ndoor coil for debris   2  Check subcooling at OD unit liquid service valve  e Outdoor airflow  debris on coil  etc      e Set the subcooling at value listed on rating plate if  standard lineset    e Set the subcooling at the maximum of 10  F or  value listed on rating plate if a long line application  3  Check superheat at OD unit vapor service valve     e         lt  2  F   proceed to Low SuperHeat section     e  f between 2 and 2
19.  Locate unit on side of structure opposite prevailing  winds    2  Elevate unit to height where drifting sand cannot pile  up against coil  Mounting feet  4 in  high  are available  as accessories and can be used to elevate unit    Maintenance in desert and seacoast locations     1  Frequent inspection of coil and basepan especially  after storms and or high winds    2  Clean coil by flushing out sand from between coil fins  and out of basepan as frequently as inspection  determines necessary    3  In off season  cover with covering that allows air to  circulate through but prevents sand from sifting in   such as canvas material   Do not use plastic as  plastic will hold moisture possibly causing corrosion        R 410A  amp  R 22 Split System AC  amp  HP  Cleaning Coil    A CAUTION    UNIT DAMAGE HAZARD  Failure to follow this caution may result in equipment    damage or improper operation     Coil fin damage can result in higher operating costs or  compressor damage  Do not use flame  high pressure  water  steam  volatile or corrosive cleaners on fins or  tubing        1  Clean coil using vacuum cleaner and its crevice tool   Move crevice tool vertically  close to area being  cleaned  making sure tool touches only dirt on fins  and not fins  to prevent fin damage  do not scrub fins  with tool or move tool horizontally against fins    2      oil deposits are present  spray coil with ordinary  household detergent  Wait 10 minutes  and proceed  to next step    3  Using garden 
20.  R 22 Refrigerant Pressure Temperature                                                         7  R 410A Subcooling Chart                                3  ehh hh        8  R 410A Supetheat Chart         aree ER RU RES                                 9  R 22 Subcooling Chart          en ERR ER                     eat 10  R 22 Superheat Chart    secos                               LIP ERI Dae a Ee ee      11  TWO STAGE  CA7   CAQ   CH6   CH9   SA6   SH5   Model Plug Intormatlori                       MI ROLE DO SEN pid    e E      12  Outdoor Fan Motor PWM Above 55  F 12 7  C Outdoor Temp  DC volts  Tolerance     296                               18  Two Stage Compressor Resistances  Winding resistance at 70  F   20                                                14  Troubleshooting  i  4            Macaw ea ee ete ed      aw doe pean Te nae deed acai ae FR REG Ede 15   Francis Plumbing  amp  Heating   www FrancisPlumbing com   613 224 0041   office francisplumbing com   42108540000 Copyright2015 International Comfort Products 52    Lewisburg  Tennessee 37091 USA    Specifications subject to change without notice     
21.  R 410A  amp  R 22 Split System AC  amp  HP    specific value  as different part numbers will have  different resistance values     3  Reconnect leads and apply low voltage power to  contactor coil  This may be done by leaving  high voltage power to outdoor unit off and turning  thermostat to cooling  Check voltage at coil with  voltmeter  Reading should be between 20v and 30v   Contactor should pull in if voltage is correct and coil is  good  If contactor does not pull in  replace contactor    4  With high voltage power off and contacts pulled in   check for continuity across contacts with ohmmeter  A  very low or    resistance should be read  Higher  readings could indicate burned or pitted contacts  which may cause future failures     Capacitor    4  WARNING    ELECTRICAL SHOCK HAZARD    Failure to follow this warning could result in personal  injury or equipment damage     Capacitors can store electrical energy when power is  off  Electrical shock can result if you touch the capacitor  terminals and discharge the stored energy  Exercise  extreme caution when working near capacitors  With  power off  discharge stored energy by shorting across  the capacitor terminals with a 15 000 ohm  2 watt  resistor        NOTE  If bleed resistor is wired across start capacitor  it  must be disconnected to avoid erroneous readings when  ohmmeter is applied across capacitor   S     4  WARNING    ELECTRICAL SHOCK HAZARD    Failure to follow this warning could result in personal  injury or
22.  Valves and Pumpdown                     18  Liquid Line Filter                                     21  Suction Line Filter Drier                           21  Accumulator         0 0  c cece eee teens 22  Thermostatic Expansion Valve  TXV                 22  MAKE PIPING CONNECTIONS                       24    Francis Plumbing  amp  Heating   www FrancisPlumbing com   613 224 0041   office francisplumbing com    PAGE  REFRIGERATION SYSTEM REPAIR                24 26  Leak Detection oce      Denk 24  Coil Removal                                    25  Compressor Removal and Replacement             25  System Clean Up After Burnout                    25  Evacuation    ocius urn RETIA eR 26  TROUBLESHOOTING WITH SUPERHEAT             27  TWO STAGE  CA7   CAS   CH6   CH9   SA6   SH5   37 42  Application guidelines                             37  Model plug      2s eee 37  Airflow Selections For  CA7   CA9   CH6   CH9  Using Non Communicating Thermostats           37    Airflow Selection For FVM4 Fan Coils For  CA7   CAQ    CH6   CH9 Using Non Communicating Thermostats 37    GENERAL INFORMATION                           37  CHECK CHARGE               eke ore n 38  SYSTEM FUNCTIONS AND   SEQUENCE OF OPERATION   CH6   CH9   CS5        39  TROUBLESHOOTING                               42  CARE AND MAINTENANCE                          47  R 410A REFRIGERANT QUICK REFERENCE GUIDE   48  AC TROUBLESHOOTING CHART                     49    HP TROUBLESHOOTING CHART   HEATING CYCLE   50  HP 
23.  both air  conditioner and heat pump on the ECM equipped  units    Outdoor Coil Thermistor  OCT     The coil or defrost thermistor is the same thermistor used to  monitor outdoor air temperature  The control board must  know the coil temperature so it can activate various  functions  These functions include        e Frost sensing on heat pumps   e  Coil vs Ambient temperature relationship   e Low ambient cooling operation  Thermistor Curve    The resistance vs  temperature chart enables the service  technicians to check thermistor resistance  regardless of the  temperature    For example  at a 60  F temperature  thermistor resistance  should be around 16 000 Ohms   See Fig  28     We will talk about the thermistor in more detail when we  review the control board fault codes     THERMISTOR CURVE          90  80     gt        70  60  50                40  30  20       RESISTANCE  KOHMS        10  0                      0 20 40 60 80 100 120   17 77   6 67   4 44   15 56   26 67   37 78   48 89     TEMPERATURE  F                 A08054  Fig  28     Resistance Values Versus Temperature    Control Box  Contactor And Capacitor    Removal of the information plate exposes the control  components  Both air conditioner and heat pump control  boxes will appear to be nearly identical  There are two  contactors  two capacitors  a control board and a  compressor start assist  The contactors are identical to  those used in the standard single speed units  One controls  low capacity operatio
24.  brass   copper to steel  or copper to copper  Flux is  required when using silver brazing alloy  Do not use  low temperature solder    3  Fluxes should be used carefully  Avoid excessive  application and do not allow fluxes to enter into the  system    4  Brazing temperature of copper is proper when it is  heated to a minimum temperature of 800 F and it is a  dull red color in appearance     Service Valves and Pumpdown    4  WARNING    PERSONAL INJURY AND UNIT DAMAGE HAZARD    Failure to follow this warning could result in personal  injury or equipment damage     Never attempt to make repairs to existing service  valves  Unit operates under high pressure  Damaged  seats and o rings should not be replaced  Replacement  of entire service valve is required  Service valve must be  replaced by properly trained service technician        Service valves provide a means for holding original factory  charge in outdoor unit prior to hookup to indoor coil  They  also contain gauge ports for measuring system pressures  and provide shutoff convenience for certain types of repairs    See Fig  12     Front seating service valves are used in outdoor residential  equipment  This valve has a service port that contains a  Schrader fitting  The service port is always pressurized after  the valve is moved off the front seat position    The service valves used in the outdoor units come from the  factory front seated  This means that the refrigerant charge  is isolated from the line set connection 
25.  coils to be damaged  It is recommended to  protect the top cover from damage of tools  belt buckles   etc  while servicing from the top    1  Should the unit height allow components to be   accessed from the top of the unit  follow procedures       R 410A  amp  R 22 Split System AC  amp  HP    2 Large components may not be removed easily  without having access from the top and side  Side  access may allow procedures such as brazing   cutting  and removal easier  Follow procedures below   a  Follow procedures to remove the fan motor assembly   b  Air conditioning units only  remove the screws from the  top of the electrical control panel   Heat pumps will not  have screws holding the electrical control panel in  place at the top once the control box cover has been    removed      c  Remove the base pan screws holding the control panel  and lift off the unit    Certain maintenance routines and repairs require removal of  cabinet panels                                                                                                                                                           for removing fan motor assembly  Access  components through the top cap   po            START CAPACITOR          U    U     U          Y     x Lae BOX  do            1      U L0   U   N  V                      Sees Ar                   START RELAY  BRN YEL  CAPACITOR    YEL BLU  AGAR  Siig jo       2 3    CONTACTOR  CAPACITOR        2          e  o   e       9  11                     HARNESS AS
26.  com    421 08 5400 00 48    Specifications subject to change without notice     SERVICE MANUAL    R 410A  amp  R 22 Split System AC  amp  HP    AIR CONDITIONER  TROUBLESHOOTING CHART    NO COOLING OR  INSUFFICIENT  COOLING       COMPRESSOR  WILL NOT RUN    CONTACTOR  OPEN    POWER SUPPLY    DEFECTIVE  LOW VOLTAGE  TRANSFORMER    OPEN  THERMOSTAT    OPEN CONTROL  CIRCUIT    LOSS OF  CHARGE    CONTACTOR OR  COIL DEFECTIVE       49    LOOSE  ELECTRICAL  CONNECTION    CONTACTOR  CLOSED    COMPRESSOR  POWER SUPPLY  OPEN    LOOSE LEADS AT  COMPRESSOR    FAULTY START  GEAR  1 PH     OPEN SHORTED  OR GROUNDED  COMPRESSOR  MOTOR  WINDINGS    COMPRESSOR  STUCK    COMPRESSOR  INTERNAL  PROTECTION  OPEN    DEFECTIVE RUN  CAPACITOR    DEFECTIVE  START  CAPACITOR    COMPRESSOR  RUNS BUT  CYCLES ON  INTERNAL  OVERLOAD    COMPRESSOR  RUNS BUT  INSUFFICIENT  COOLING          OUTDOOR FAN  STOPPED OR  CYCLING ON   OVERLOAD    OUTDOOR AIR  RESTRICTED OR  RECIRCULATING    RESTRICTED  DISCHARGE  TUBE    OVERCHARGE  OR NON   CONDENSABLES  IN SYSTEM    LOW  REFRIGERANT  CHARGE    LINE VOLTAGE  TOO HIGH OR  LOW    DEFECTIVE RUN  CAPACITOR    COMPRESSOR  BEARINGS    HIGH  SUPERHEAT    DEFECTIVE  START  CAPACITOR       LOOSE LEAD  AT FAN MOTOR    MOTOR  DEFECTIVE    INCORRECT  OFM  CAPACITOR             HIGH SUCTION  LOW HEAD  PRESSURE    LOW SUCTION  PRESSURE          DEFECTIVE  COMPRESSOR  VALVES    DIRTY AIR  FILTERS       DUCT INTERNAL    PRESSURE  RESTRICTED RELIEF OPEN    DAMPERS  PARTLY CLOSED 
27.  compressor  If  bleed hole plugs  oil is trapped in accumulator  and  compressor will eventually fail from lack of lubrication  If  bleed hole is plugged  accumulator must be changed  The  accumulator has a fusible element located in the bottom end  bell   See Fig  19   This fusible element will melt at  430  F  221  C and vent the refrigerant if this temperature is  reached either internal or external to the system  If fuse  melts  the accumulator must be replaced   To change accumulator    1  Shut off all power to unit    2  Recover all refrigerant from system    3  Break vacuum with dry nitrogen  Do not exceed 5   psig    NOTE  Coil may be removed for access to accumulator   Refer to appropriate sections of Service Manual for  instructions     A CAUTION    PERSONAL INJURY HAZARD    Failure to follow this caution may result in personal  injury     Wear safety glasses  protective clothing  and gloves  when handling refrigerant    4  Remove accumulator from system with tubing cutter    5  Tape ends of open tubing    6  Scratch matching marks on tubing studs and old  accumulator  Scratch matching marks on new  accumulator  Unbraze stubs from old accumulator  and braze into new accumulator    7  Thoroughly rinse any flux residue from joints and  paint with corrosion resistant coating such as  zinc rich paint    8  Install factory authorized accumulator into system  with copper slip couplings    9  Evacuate and charge system    Pour and measure oil quantity  if any  from old ac
28.  delay is  encountered or device never times out  change control     Crankcase Heater    Crankcase heater is a device for keeping compressor oil  warm  By keeping oil warm  refrigerant does not migrate to  and condense in compressor shell when the compressor is  off  This prevents flooded starts which        damage  compressor     On units that have a single pole contactor  the crankcase  heater is wired in parallel with contactor contacts and in  series with compressor   See Fig  5   When contacts open  a  circuit is completed from line side of contactor  through  crankcase heater  through run windings of compressor  and  to other side of line  When contacts are closed  there is no  circuit through crankcase heater because both leads are  connected to same side of line  This allows heater to  operate when system is not calling for cooling  The heater  does not operate when system is calling for cooling     TEMP SWITCH  CRANKCASE HTR d    WN hd  BLK BLK BLK BLK    e       A97586  Fig  5     Wiring for Single Pole Contactor    The crankcase heater is powered by high voltage power of  unit  Use extreme caution troubleshooting this device with  power on  The easiest method of troubleshooting is to apply  voltmeter across crankcase heater leads to see if heater  has power  Do not touch heater  Carefully feel area around  crankcase heater  If warm  crankcase heater is probably  functioning  Do not rely on this method as absolute  evidence heater is functioning  If compressor has b
29.  equipment damage     Always check capacitors with power off  Attempting to  troubleshoot a capacitor with power on can be  dangerous  Defective capacitors may explode when  power is applied  Insulating fluid inside is combustible  and may ignite  causing burns        Capacitors are used as a phase shifting device to aid in  starting certain single phase motors  Check capacitors as  follows     1  With power off  discharge capacitors as outlined  above  Disconnect capacitor from circuit  Put  ohmmeter on R X 10k scale  Using an analog  ohmmeter  check each terminal to ground  use  capacitor case   Discard any capacitor which  measures 1 2 scale deflection or less  Place  ohmmeter leads across capacitor and place on R X  10k scale  Meter should jump to a low resistance  value and slowly climb to higher value  Failure of  meter to do this indicates an open capacitor  If  resistance stays at O or a low value  capacitor is  internally shorted    2  Capacitance testers are available which will read  value of capacitor  If value is not within  10 percent  value stated on capacitor  it should be replaced  If  capacitor is not open or shorted  the capacitance    Specifications subject to change without notice     421 08 5400 00    SERVICE MANUAL    value is calculated by measuring voltage across  capacitor and current it draws     4  WARNING    ELECTRICAL SHOCK HAZARD    Failure to follow this warning could result in personal  injury or death     Exercise extreme caution when taking 
30.  flash the appropriate fault code  see Table 15      230v Brown Out Protection Defeated    The brownout feature can be defeated if needed for severe  noisy power conditions  This defeat should always be a last  resort to solving the problem  Defeat is available for  Communicating systems on the wall control or outside  board  or it can be initiated through the forced defrost pins  for non communicating systems as follows     The brownout toggle is accomplished by shorting the defrost  pins from power up with the OAT and OCT sensor  connector removed  After 3 seconds  the status of the force  defrost short and the OAT OCT as open will be checked  If  correct  then the brownout will be toggled     e Status code 6 shows the brownout is disabled   e Status code 5 shows the brownout is active     After the brownout defeat is set  power down and reinstall  the OAT OCT sensor and remove the short from the forced  defrost pins  As long as the short on the forced defrost  remains  the OAT and OCT faults will not be cleared  The  code will continue to be flashed     The control is shipped with the brownout active  The change  in status is remembered until toggled to a new status  A  power down power up sequence will not reset the status  It  may be necessary to do the toggle twice to cycle to the  desired state of the defeat     230V Line  Power Disconnect  Detection    If there is no 230v at the compressor contactor s  when the  indoor unit is powered and cooling or heating demand  ex
31.  impermeable polyethylene  plastic  drop cloth or tarp   Cover an approximate 10 x 10 ft area    2  Cover area in front of the unit service panel with a  terry cloth shop towel to absorb lubricant spills and  prevent run offs  and protect drop cloth from tears  caused by tools or components        421 08 5400 00    R 410A  amp  R 22 Split System AC  amp  HP    3  Place terry cloth shop towel inside unit immediately  under component s  to be serviced and prevent  lubricant run offs through the louvered openings in  the base pan    4  Perform required service    5  Remove and dispose of any oil contaminated material  per local codes    Brazing   This section on brazing is not intended to teach a technician  how to braze  There are books and classes which teach and  refine brazing techniques  The basic points below are listed  only as a reminder    Definition  The joining and sealing of metals using a  nonferrous metal having    melting point over  800  F 426 6  C    Flux  A cleaning solution applied to tubing or wire before it  is brazed  Flux improves the strength of the brazed  connection    When brazing is required in the refrigeration system  certain  basics should be remembered  The following are a few of  the basic rules    1  Clean joints make the best joints  To clean         Remove all oxidation from surfaces to a shiny  finish before brazing        Remove all flux residue with brush and water  while material is still hot    2  Silver brazing alloy is used on copper to
32.  not replaced     3  Change out indoor coil or verify existing coil is listed in  the specifications or AHRIdirectory org     4  Unless indoor unit is equipped with a R 410A  approved metering device  change out metering  device to factory supplied or field accessory device  specifically designed for R 410A     5  Replace outdoor unit with R 410A outdoor unit   6  Install factory supplied liquid line filter drier     4  CAUTION    UNIT DAMAGE HAZARD    Failure to follow this caution may result in equipment  damage or improper operation     Never install suction line filter drier in the liquid line  of an R 410A system        7      suction line filter drier was installed for system  clean up  operate system for 10 hr  Monitor pressure  drop across drier  If pressure drop exceeds 3 psig   replace suction line and liquid line filter driers  Be  sure to purge system with dry nitrogen and evacuate  when replacing filter driers  Continue to monitor  pressure drop across suction line filter drier  After 10  hr of runtime  remove suction line filter drier and  replace liquid line filter drier  Never leave suction line  filter drier in system longer than 72 hr  actual time      8  Charge system   See unit information plate    Seacoast    Coastal units are available in selected models and sizes of  Air Conditioners and Heat Pumps  These units have  protection to help resist the corrosive coastal environment   Features include     e Epoxy coated coils    e Complete baked on paint cover
33.  ohmmeter on R X 10 000 ohm scale or  megohmmeter  follow manufacturer   s instructions        Be sure all power is off      Discharge all capacitors      Remove wires from terminals C  S  and R      Place one meter probe on ground or on compressor  shell  Make a good metal to metal contact  Place  other probe on terminals C  S  and R in sequence    7  Note meter scale    8  If reading of    or low resistance is obtained  motor is   grounded  Replace compressor     Compressor resistance to ground should not be less than  1000 ohms per volt of operating voltage    Example    230 volts X 1000 ohms volt   230 000 ohms minimum   Short Circuit   To determine if any wires within windings have broken  through their insulation and made contact with other wires   thereby shorting all or part of the winding s   be sure the  following conditions are met     1  Correct motor winding resistances must be known  before testing  either from previous readings or from  manufacturer s specifications     2  Temperature of windings must be as specified   usually about 70  F     3  Resistance measuring instrument must have an  accuracy within   5 10 percent  This requires an  accurate ohmmeter such as a Wheatstone bridge or  null balance type instrument     4  Motor must be dry or free from direct contact with  liquid refrigerant     Make This Critical Test   Not advisable unless above conditions are met   1  Be sure all power is off   2  Discharge all capacitors   3  Remove wires from terminals C
34. 0  F 11  C valve is probably  operating properly    e  f greater than 20  F 11  C  perform Pseudo  Evaporator SuperHeat Instructions check as  follows         Check refrigerant pressure at vapor service  valve and  refrigerant temperature at outlet of evaporator        Use suction line geometry  diameter and equiv   alent length   unit capacity and Tables 4 and 5 to  determine suction pressure drop      For standard lineset diameters  vapor service  valve diameters and larger  and lengths  less  than 80 ft   generally no pressure adjustment   per Table 4 or 5  is required      For longer  greater than 80 ft  and small  diameter linesets  less than service valve  size   correct pressure  add to gauge  pressure reading  per Tables 4 and 5     e  f Pseudo Superheat is greater than 15  proceed to  High SuperHeat section   e  f Pseudo Evaporator Superheat is between 2 and  15  TXV appears to be functioning properly   e  f operation erratic  hunting   proceed to Hunting  Superheat   F Superheat in repetition section   NOTE  Hunting is when the valve superheat swings more  than 10     Low Superheat with Normal or Low Suction Pressure  NOTE  Normal or low suction pressure is considered for  R 22   lt  80 psig  R 410A     135 psig  1  Re check airflow and then check sensing bulb  tightness  orientation on vapor tube and is properly  wrapped        R 410A  amp  R 22 Split System AC  amp  HP  e Low Superheat with Normal or Low Suction  Pressure  e If OK proceed to Step 2  2  Check super
35. 3    N  coils only      9  Attach equalizer tube to suction line  If coil has  mechanical connection  then use wrench and back up  wrench to attach  If coil has brazed connection  use  file or tubing cutters to remove mechanical flare nut  from equalizer line  Then use coupling to braze the  equalizer line to stub  previous equalizer line  in  suction line     10  Attach TXV bulb to vapor tube inside cabinet  in same  location as original was when removed  using  supplied bulb clamps  nylon or copper   See Fig  20  for correct positioning of sensing bulb    11  Route equalizer tube through suction connection  opening  large hole  in fitting panel and install fitting  panel in place    12  Sweat inlet of TXV  marked  IN  to liquid line  Avoid  excessive heat which could damage valve     13  Proceed with remainder of unit installation     MAKE PIPING CONNECTIONS  a WARNING    PERSONAL INJURY AND ENVIRONMENTAL  HAZARD    Failure to follow this warning could result in personal  injury or death        Relieve pressure and recover all refrigerant before  system repair or final unit disposal     Use all service ports and open all flow control  devices  including solenoid valves        CAUTION    ELECTRICAL OPERATION HAZARD    Failure to follow this caution may result in equipment  damage or improper operation     Do not leave system open to atmosphere any longer  than minimum required for installation  POE oil in  compressor is extremely susceptible to moisture  absorption  Always k
36. 4  WARNING    ELECTRICAL SHOCK HAZARD    Failure to follow this warning could result in personal  injury or death     Do not supply power to unit with compressor terminal  box cover removed     4  WARNING    ELECTRICAL SHOCK HAZARD    Failure to follow this warning could result in personal  injury or death     Exercise extreme caution when reading compressor  currents when high voltage power is on  Correct any of  the problems described below before installing and  running a replacement compressor     Locked Rotor    In this type of failure  compressor motor and all starting  components are normal  When compressor attempts to  start  it draws locked rotor current and cycles off on internal  protection  Locked rotor current is measured by applying a                ammeter around common        lead of  compressor  Current drawn when it attempts to start is then  measured  Locked rotor amp  LRA  value is stamped on  compressor nameplate     If compressor draws locked rotor amps and all other  external sources of problems have been eliminated   compressor must be replaced  Because compressor is a  sealed unit  it is impossible to determine exact mechanical  failure  However  complete system should be checked for  abnormalities such as incorrect refrigerant charge   restrictions  insufficient airflow across indoor or outdoor coil   etc   which could be contributing to the failure     Runs  Does Not Pump    In this type of failure  compressor motor runs and turns  compressor  but c
37. 6  58  60  62                68  70   56  58         62         66  68  70   57  59  et  63  65  ev  eo  71    58  6o  62        66        70  72   58  60  62        66              72   59  61  63  65  ev  eo  71 73   60  e2               68  70  721 74    60  62  64  66   68         72  74    61  63  65  67 69 71  7    75    64  66  68   70  72  74  76    64  66        70  72  74  76    65  67 69  71  7    75  77    66  68          72  74  76  78    66  68          72  74  76  78  65  67  69    73  75  77 7    68  vo  72  74  76  78           66  68  vo  72  74  76  78  80   67  69 71  73  75  77  79  81   67  69 71  v3  75  77  79  81    68  vo  72  74  76  78        82   69  71  73  75  77  79       83   69  71  v3  75  77  79  41 83   70  72  74  76  78        22  84   70  72  74  76  78        22  84                                   F    psig   26  27    ol                                           A         gt   N      A    oa                   oa                               OOF              a    a    N        BA           I      A  N  o    A                     BA                 Co  nof no                               ooo   ee  Tee  The     oa  A                                                                w  alojo e       ES ES A       uri Fa      lt    63   23  RA             BR  5             Koul        KOLI KOL      KOL                                                            RP REPRE RE RTO       62                                                       
38. APPLICATION GUIDELINE  amp   SERVICE MANUAL    R 410A  amp  R 22 Split System AC  amp  HP    TABLE OF CONTENTS    PAGE   UNIT IDENTIFICATION             seem Re 2  SAFETY CONSIDERATIONS                          4  INTRODUCTION          sseeeseee ee 4  INSTALLATION GUIDELINE                           4  LOW AMBIENT COOLING GUIDELINE                 4  LONG LINE GUIDELINE                              5  ACCESSORY DESCRIPTIONS                        5  CABINET ASSEMBLY                                5  ELECTRICAL                            ee xd Faroe 7 8  Aluminum Wire                  000 eee eee eee 7  Contactor       0  cee ees 7  Capacitor sos nce hee aw wks eee eR Sade REUS 7  Cycle Protector                                   8  Crankcase Heater                                 8  Time Delay Relay                                 8  PRESSURE SWITCHES                              9  DEFROST THERMOSTAT                             9  DEFROST CONTROL                                   10  COPELAND SCROLL COMPRESSOR                12  LG SCROLL COMPRESSOR                         13  COMPRESSOR TROUBLESHOOTING             14 17  Compressor                5                             14  Mechanical Failures                              14  Electrical Failures                                17  REFRIGERATION SYSTEM                       18 24  Refrigerarit  2  2                Rig 18  Servicing Systems on Roofs With Synthetic Materials 18  Brazing PP                      18  Service
39. Check for restriction in liquid line  kinked line  filter  drier restricted  etc    e If OK proceed to Step 10  10  Check for restriction in suction line  kink  restricted  suction filter drier etc     e If OK proceed to Step 11  11  Check power element cap tube is not broken  e If OK proceed to Step 12  12  Check that equalizer tube is not kinked or plugged  e If OK proceed to Step 13  13  Check that inlet screen  R 22 systems  is not  restricted  e If OK proceed to Step 14  14  Replace Valve  High Superheat with Normal or High Suction Pressure  NOTE  Normal to High suction pressure is considered  for R 22   gt   65 psig  R 410A   gt   110 psig  An application  issue or other system component failure typically causes  this condition     15  Check airflow  sensing bulb tightness  orientation on  vapor tube and ensure bulb is properly wrapped           Specifications subject to change without notice     27    421 08 5400 00    SERVICE MANUAL    e  f OK proceed to Step 16  16  R 410A Systems  Make sure proper valve is used   Not R 22   e If OK proceed to Step 17  17  Check for even temperature distribution at outlet of  each circuit of evaporator  e If OK proceed to Step 18  18  Check for high evaporator load  Return Air Leaks   high indoor wet bulb and or dry bulb temp  undersized  system  etc   e  f OK proceed to Step 19  19  Check that compressor is pumping properly  e Loose Rule of Thumb  Is discharge saturated     20 F higher than ambient temperature   5  discharge superhe
40. EFROST TIMER BEGINS      1   ENABLES DEFROST  TIMER MUST BE  ENERGIZED FOR    DEFROST TIMER  bei          COMMON       REVERSING VALVE ae  ooon     E                              P OR i SPEEDUP       THERMOSTAT INPUTS       Y OUTPUT TO PRESSURE  SWITCHES AND CONTACTOR                               y  DFT                                  A150020  Fig  7     FAST   1173636   1177927 Defrost Control    Troubleshooting  FAST    1173636   1177927   If outdoor unit will not run     1  Does the Y input has 24 volts from thermostat  If not   check thermostat or wire  If yes proceed to  2    2  The Y spade terminal on the circuit board should  have 24 volts if Y input is energized  This output goes  through the pressure switches and to the contactor  If  24 volts is present on the Y spade terminal  and the  contactor is not closed  check voltage on contactor  coil  If no voltage is present  check for opened  pressure switch     3  If voltage is present and contactor is open  contactor  may be defective  Replace contactor if necessary    4      contactor is closed and unit will still not run  check  wiring  capacitor and compressor       421 08 5400 00 Francis Plumbing  amp  Heating   www FrancisPlumbing com   613 224 0041   office francisplumbing com 10    Specifications subject to change without notice     SERVICE MANUAL    Defrost Speedup  FAST   1173636     To test the defrost function on these units  speed up pins  are provided on the circuit board  To force a defrost cycle   the 
41. NUAL    Status Codes    Table 15 shows the status codes flashed by the amber  status light  Most system problems can be diagnosed by  reading the status code as flashed by the amber status light  on the control board     The codes are flashed by a series of short and long flashes  of the status light  The short flashes indicate the first digit in  the status code  followed by long flashes indicating the  second digit of the error code     R 410A  amp  R 22 Split System AC  amp  HP    The short flash is 0 25 seconds ON and the long flash is 1 0  second ON  Time between flashes is 0 25 seconds  Time  between short flash and first long flash is 1 0 second  Time  between code repeating is 2 5 seconds with LED OFF   EXAMPLE     3 short flashes followed by 2 long flashes indicates a 32  code  Table 15 shows this to be low pressure switch open     Table 15   TROUBLESHOOTING    AMBER LED  OPERATION FAULT FLASH  CODE      On solid  no  Standby   no call for unit operation None flash  Low Stage Cool Heat Operation None 1  pause  High Stage Cool Heat Operation None 2  pause  Brown out protection is Disabled None 5  pause  Brown out protection is Active None 6  Pause  System Commu  16  nications Failure  Invalid Model Plug 25  High Pressure  Switch or Dis  31   charge Temp  Switch Open  Low Pressure 32   Switch Open  Control Fault 45  Brown Out  230 v  46  No 230v at Unit 47  Outdoor Air Temp 53  Sensor Fault  Outdoor Coil 55  Sensor Fault  Thermistors out of 56  range  Low Stage 71   Th
42. O1  IO                        02                           N                              N O       2  CO   N   gt     olol      NJ                    jo o  2   oo  s                        NI  o oa    gt    A  NINN  a  alo                 N    170    N  N           CO         CO  NINININI N                                          180  185  190  195 100  200 102  205 103  210 105  215 107  220 108  225 110  230  235  240 114  245 116  250 117  255 119  260 120  265 121  270 123  275  280  285  290  295  300  305  310  315  320  325  330                     N o                                                   0                                             Y              Alo  NI O01             gt          _       lt                        CO         NI NI NTN    Al N     O1       O    O1  IO O AB     gt            gt               70    72               76    79    81      8      5      87      8     9     93        95        9        98        100        102        103        210   105      215   107      220   108   106  104    1o    M3                16     H7      H9      120     121     _123__    29     131     132 _       133        195     136        137     1398                          eo  O    113                     gt          i    h      a lolo                                                  N                        E                  09  OD                            N                   AJN                                6                                      N
43. S  REVERSING    AT  VALVE FAN MOTOR       FAN MOTOR  RESTRICTION IN BURNED    DISCHARGE LINE OUT    OVERCHARGE  OR NON   CONDENSABLES  IN SYSTEM    LOW  REFRIGERANT  CHARGE    LINE VOLTAGE  TOO HIGH OR  LOW    DEFECTIVE RUN  CAPACITOR   1 PH     COMPRESSOR  BEARINGS    HIGH LOAD  CONDITION    REVERSING  VALVE JAMMED  IN MIDPOSITION    HIGH  SUPERHEAT    DEFECTIVE  START  CAPACITOR       COMPRESSOR  RUNS  INSUFFICIENT  HEATING              LOW SUCTION  LOW HEAD    OUTDOOR FAN  STOPPED    LOOSE LEADS  AT OUTDOOR  FAN MOTOR    INTERNAL FAN  MOTOR KLIXON  OPEN    FAN MOTOR  BURNED OUT    DEFROST RELAY  N C  CONTACTS    OPEN ON  CIRCUIT BOARD       FAN MOTOR  CONTACTS  WELDED CLOSED  IN DEFROST  RELAY    REVERSING  VALVE DID NOT  SHIFT    UNIT NOT  PROPERLY  CHARGED    Specifications subject to change without notice        OUTDOOR FAN  RUNNING    REVERSING  VALVE STUCK    RESTRICTED  LIQUID LINE    PISTON  RESTRICTED OR  IS CLOGGED    UNDER   CHARGED    OUTDOOR COIL  DIRTY       STRIP HEATERS  NOT OPERATING    OUTDOOR  THERMOSTAT  DEFECTIVE    ODT SETTING  TOO LOW    CAP TUBE  PINCHED OR  BULB NOT  SENSING TRUE  ODT    STRIP HEATER  RELAY OR  CONTACTOR  DEFECTIVE    OPENING IN  POWER CIRCUIT    TO HEATER  ELEMENTS       BROKEN FUSE  LINK       STRAINER  RESTRICTED    OUTDOOR COIL  HEAVILY  FROSTED             DEFECTIVE  DEFROST  THERMOSTAT    DEFROST  THERMOSTAT IN  POOR PHYSICAL   CONTACT WITH  TUBE       DEFECTIVE  CIRCUIT BOARD    BAD ELECTRICAL  CONNECTION  ANYWHERE IN  DEFROS
44. SE   SF   SF              1O   tO                    LO PLO         bris          Vap Press   psig        34    421 08 5400 00    Specifications subject to change without notice     SERVICE MANUAL R 410A  amp  R 22 Split System AC  amp  HP    Table 10   R 22 Subcooling Chart  R   22 Liquid Line Temperature    F   PT    F  Subcooling    F    10  12  14  16  18  20  22  24  2  64  62 58  56  54  52  50  48  46  4    66         62         58  56   54  52  50  48  46    66         62  60 4    69    73    75    77  7   71  69  67    89  87  85  83  81   79  77 75  73  71  69    90  88  86  84  82                 76 74  72          92  90  88  sej 84  82                 76  74  72    94  92  90  88  86  84  82         781 76  74    96  94  92  90  88         84  82                 76    97  95 93  91         87  85  83  81 79  77    99  97  95 93  91         87 85  83  81  79    101  99  97  95  93  91         87 85  83  81    102  100  98  96  94  921 90  88 86  84  82    104  102  100  98  96  94  92         88         84    105  103  101         97  95  93  91         87  85  95  93  91  89 87     7                97                  114  112         108  106  104  102  100             M    120  125  130        AR  c             olol oa olaja       02    NI 01  Go       CO      NIN Od  OD  oa OD  1  1  wj     lj O1      2      O              140  145  150    Oo                           N  Ol    2    N  O01  C                       160    N                      C1   O1  0    N  
45. SIZE OD     IN   90   STD  A    1 2 12   5 8 1 6   3 4 1 8   7 8 2 0  1   1 8 2 6    421 08 5400 00    A01058  90  LONG RAD  B  45   STD  C   0 8 0 6  1 0 0 8  1 2 0 9  1 4 1 0  1 7 1 3    28    Specifications subject to change without notice     SERVICE MANUAL    R 410A  amp  R 22 Split System AC  amp  HP    Table 4   R 410A System Suction Pressure Drop    Nominal Suction Line Pressure Suction  Size OD Drop Velocity    Btuh   in    psi 100 ft  fpm 20  1 2 9 9 1649 2   18000 5 8 3 1 1018 1  3 4 1 2 678 0   1 2 16 7 2199 3   24000 5 8 5 2 1357 1  3 4 2 0 904 0   7 8 1 0 678 0   5 8 7 8 1696 2   30000 3 4 2 9 1130 1  7 8 1 5 848 0   5 8 10 9 2036 2   36000 3 4 4 1 1356 1  7 8 2 0 1017 0   5 8 14 1 2375 3   42000 3 4 5 4 1582 1  7 8 2 7 1187 1   1 1 8 0 8 696 0   3 4 6 9 1808 1   48000 7 8 3 5 1357 1  1 1 8 1 0 796 0   3 4 10 4 2260 2   60000 7 8 5 2 1696 1  1 1 8 1 4 995 0   Line set application not recommended  Example 1    While on a service call  after checking for proper indoor and  outdoor airflow  Tom finds the following pressures and  temperatures at the service valves of a R 410A air  conditioner       Liquid line pressure   340 psig    Liquid line temperature   97  F  e Suction line pressure   125 psig    e Suction line temperature   70  F    Using a R 410A PT chart  the subcooling is determined to  be 8  F  which is within  3 of the 10  F listed on the rating  plate  Tom believes the charge is correct  He calculates the  superheat to be approximately 27  F superheat  
46. SY                                                                      il                         i    Fig  1   Typical AC Control Box       UJ    GROUND LUG    Francis Plumbing  amp  Heating   www FrancisPlumbing com   613 224 0041   office francisplumbing com    Specifications subject to change without notice     421 08 5400 00    SERVICE MANUAL R 410A  amp  R 22 Split System AC  amp  HP                                                                                                 _  sz cms  d  e ae n d      CIRCUIT BOARD                                                           START CAPACITOR       zn    U   MS BOX            e   gt   Moo    i                           ASSY  lA A    P4 208 9             YA J wW A MEME a      RELAY                                                                                                                                                                                                       SOFT START          e    PEREN    BLK  CAPACITOR                     l     Hd    CONTACTOR  CAPACITOR STRAP        MEPIS       GROUND LUG  HARNESS ASSY               L  Fig  2   Typical HP Control Box  Labeling  Wiring Label  Tech Label                            Rating Plate g         Caution Label   3 phase only                                                                                                    Dio Ou  2 o 9  9  oo                                                                                          Warning Label    Fig  3   Typi
47. T  CIRCUIT       Fig  39     Heat Pump Troubleshooting   Heating Cycle          BROKEN  HEATER  ELEMENT    OPEN  KLIXON   OVER  TEMPERATURE  THERMOSTAT    DEFECTIVE  ROOM  THERMOSTAT   2ND STAGE     A90206    50    SERVICE MANUAL R 410A  amp  R 22 Split System AC  amp  HP    HEAT PUMP  TROUBLESHOOTING COOLING CYCLE    NO COOLING OR  INSUFFICIENT  COOLING       COMPRESSOR COMPRESSOR  RUNS BUT RUNS BUT  CYCLES ON INSUFFICIENT  INTERNAL COOLING   OVERLOAD    COMPRESSOR  WILL NOT RUN             CONTACTOR  OPEN          POWER SUPPLY    DEFECTIVE  LOW VOLTAGE  TRANSFORMER    OPEN  THERMOSTAT    OPEN CONTROL  CIRCUIT    LOSS OF  CHARGE    CONTACTOR OR  COIL DEFECTIVE    LOOSE  ELECTRICAL  CONNECTION          CONTACTOR  CLOSED    COMPRESSOR  POWER SUPPLY  OPEN    LOOSE LEADS AT  COMPRESSOR    FAULTY START  GEAR  1 PH     OPEN SHORTED  OR GROUNDED  COMPRESSOR  MOTOR  WINDINGS    COMPRESSOR  STUCK    COMPRESSOR  INTERNAL  PROTECTION  OPEN    DEFECTIVE RUN  CAPACITOR    DEFECTIVE  START  CAPACITOR       OUTDOOR FAN  STOPPED OR  CYCLING ON   OVERLOAD    OUTDOOR AIR  RESTRICTED OR  RECIRCULATING    DAMAGED OR  STUCK  REVERSING  VALVE    RESTRICTED  DISCHARGE  TUBE    OVERCHARGE  OR NON   CONDENSABLES  IN SYSTEM    LOW  REFRIGERANT  CHARGE    LINE VOLTAGE  TOO HIGH OR  LOW    DEFECTIVE RUN  CAPACITOR    COMPRESSOR  BEARINGS    HIGH  SUPERHEAT    DEFECTIVE  START  CAPACITOR          LOOSE LEAD  AT FAN MOTOR    DEFROST RELAY  N C  CONTACTS  OPEN    MOTOR  DEFECTIVE    INCORRECT  OFM  CAPACI
48. TOR    DEFECTIVE  DEFROST  THERMOSTAT             DIRTY AIR  FILTERS    DUCT  RESTRICTED    DAMPERS  PARTLY CLOSED    INDOOR COIL  FROSTED        SLIGHTLY  LOW ON  REFRIGERANT    LIQUID LINE  SLIGHTLY  RESTRICTED    PISTON  RESTRICTED    INCORRECT  SIZE  PISTON    INDOOR COIL  STRAINER    RESTRICTED    INDOOR  BLOWER MOTOR  DEFECTIVE OR  CYCLING ON OL       Fig  40     Heat Pump Troubleshooting   Cooling Cycle    HIGH SUCTION  LOW HEAD  PRESSURE             REVERSING  VALVE HUNG UP  OR INTERNAL  LEAK    DEFECTIVE  COMPRESSOR  VALVES    INTERNAL  PRESSURE  RELIEF OPEN       Francis Plumbing  amp  Heating   www FrancisPlumbing com   613 224 0041   office francisplumbing com    51    Specifications subject to change without notice     HIGH SUCTION  LOW  SUPERHEAT          UNIT  OVERCHARGED    INCORRECT  SIZE  PISTON    FAILED  TXV       A90207    421 08 5400 00    SERVICE MANUAL R 410A  amp  R 22 Split System AC  amp  HP    INDEX OF TABLES   DESCRIPTION TABLE    Air Conditioner and Heat Pump Model Number Nomenclature               sssssssess nnn 1  Defrost Control Speed Up Timing Sequence                                      2  Fitting Losses in Equivalent Feet         RR Re e phe        err RR ERI MAREA DRE ERI eee ERR ed 3  R 410A System Suction Pressure Drop                                          hh 4  R 22 System Suction Pressure                      teree dirii          eee hm n nnn 5  R 410A Refrigerant Pressure Temperature Chart                                     hh 6 
49. TROUBLESHOOTING CHART   COOLING CYCLE 51  INDEX OF                                               52    421 08 5400 00 3 11 2015    SERVICE MANUAL  UNIT IDENTIFICATION    Troubleshooting Charts for Air Conditioners and Heat  Pumps are provided in the appendix at back of this manual   They enable the service technician to use a systematic  approach to locate the cause of a problem and correct    R 410A  amp  R 22 Split System AC  amp  HP    system malfunctions  This section explains how to obtain  the model and serial number from the unit rating plate   These numbers are needed to service and repair the  R 410A and R 22 air conditioner or heat pump  Model and  serial numbers can be found on unit rating plate     Table 1   Air Conditioner and Heat Pump Model Number Nomenclature    mewn            feel ze                     Example Part Number       Mainline  N   Entry BRANDING    REFRIGERANT  A   Air Conditioner  H   Heat Pump  3   13 SEER    4   14 SEER  5   15 SEER    6   16 SEER NOMINAL EFFICIENCY    18   18 000 BTUH   1 1 2 tons  24   24 000 BTUH   2 tons  30   30 000 BTUH   2 1 2 tons  36   36 000 BTUH   3 tons  42   42 000 BTUH   3 1 2 tons  48   48 000 BTUH   4 tons    60   60 000 BTUH   5 tons NOMINAL CAPACITY    A   Standard Grille  C   Coastal       Coil Guard Grille    H   208 230 3 60  K   208 230 1 60  L   460 3 60    Sales Code  Engineering Revision  Extra Digit   Extra Digit    421 08 5400 00       FEATURES    VOLTAGE    Continued on next page    Specifications s
50. The  apparently high superheat has Tom concerned     Tom uses the Pseudo Evaporator Superheat method to  check the TXV performance  The system is a 3 ton R 410A  air conditioner with 75 feet equivalent length of 3 4    suction  line  Based on Table 4  the system has approximately  3 psig pressure drop in the vapor line  Per the instructions   he takes the suction line temperature at the outlet of the  evaporator and finds it to be 53  F  Tom adds 3 psig to the  125 psig suction pressure at the outdoor unit to get 128  psig evaporator pressure  The saturated pressure of 128  equates to 44  F  Tom calculates the evaporator superheat  to be  53  F   44  F    9  F  The TXV appears to be  operating properly     a                                                 m                             410   Suction Line Pressure Drop  psig   Total Equivalent Line Length  ft     80 100 125 150 175 200 225 250  8 10 12 15 17 20 22 25  2 3 4 5 5 6 7 8  1 1 1 2 2 2 3 3  13 17 21 25 29 33 38 42  4 5 7 8 9 10 12 13  2 2 2 3 3 4 4 5  1 1 1 1 2 2 2 2  6 8 10 12 14 16 18 20  2 3 4 4 5 6 7 7  1 1 2 2 3 3 3 4  9 11 14 16 19 22 24 27  3 4 5 6 7 8 9 10  2 2 3 3 4 4 5 5  11 14 18 21 25 28 32 35  4 5 7 8 9 11 12 14  2 3 3 4 5 5 6 7  1 1 1 1 1 2 2 2  6 7 9 10 12 14 16 17  3 3 4 5 6 7 8 9  1 1 1 1 2 2 2 2  8 10 13 16 18 21 23 26  4 5 6 8 9 10 12 13  1 1 2 2 3 3 3 4    NOTE  The additional superheat at the compressor is due  principally to heat gain in the 75 feet of suction line with a  minor contribution by 
51. V allows additional  protection to the TXV as the liquid line drier also acts as a  strainer   Install Liquid line Filter Drier Indoor   AC    A CAUTION    UNIT DAMAGE HAZARD    Failure to follow this caution may result in equipment  damage or improper operation     To avoid performance loss and compressor failure   installation of filter drier in liquid line is required        4  CAUTION    UNIT DAMAGE HAZARD   Failure to follow this caution may result in equipment  damage or improper operation    To avoid filter drier damage while brazing  filter drier  must be wrapped in a heat sinking material such as a  wet cloth        Refer to Fig  17 and install filter drier as follows   1  Braze 5 in  liquid tube to the indoor coil   2  Wrap filter drier with damp cloth     3  Braze filter drier to above 5  liquid tube  Flow arrow  must point towards indoor coil    4  Connect and braze liquid refrigerant tube to the filter  drier     Specifications subject to change without notice     21    R 410A  amp  R 22 Split System AC  amp  HP  Install Liquid line Filter Drier Indoor   HP       Refer to Fig  18 and install filter drier as follows   1  Braze 5 in  liquid tube to the indoor coil   2  Wrap filter drier with damp cloth   3  Braze filter drier to 5 in  long liquid tube from step 1   4  Connect and braze liquid refrigerant tube to the filter  drier     Suction Line Filter Drier    The suction line drier is specifically designed to operate with  R 410A  use only factory authorized com
52. When the reversing  valve is energized  O is powered on     Communication and Status Function Lights  For Communicating Control only  Green  communications  COMM  Light    A green LED  COMM light  on the outdoor board indicates  successful communication with the other system products   The green LED will remain OFF until communication is  established  Once a valid command is received  the green  LED will turn ON continuously  If no communication is  received within 2 minutes  the LED will be turned OFF until  the next valid communication     Amber Status Light    An amber colored STATUS light is used to display the  operation mode and fault codes as specified in the  troubleshooting section  See Table 15 for codes and  definitions     NOTE  Only one code will be displayed on the outdoor unit  control board  the most recent  with the highest priority      Utility Interface With Communicating Control    The utility curtailment relay should be wired between R and  Y2 connections on the control board for Communicating  Systems only  see Fig  30   This input allows a power utility  device to interrupt compressor operation during peak load  periods  When the utility sends a signal to shut the system  down  the wall control will display     Curtailment Active      Compressor Operation    The basic scroll design has been modified with the addition  of an internal unloading mechanism that opens a bypass  port in the first compression pocket  effectively reducing the  displacement of t
53. X                                                             N                   _           E                   o           o        _  o  e       o                                  O            A                                                       O                                                    0              gt   PO                    N J                                         gt                                               N   gt     E       m  E  mm      E      ud  E  e      E             A   l     l  aj c     ij  l                   A   d     8     l  ojo  OJN              ol                                                           N  o    12    AR    12                   _                   NINI           OINI O  oO                     h                  N  0J A       gt    69        gt                 k                            gt   C      E               69                         Specifications subject to change without notice     35 421 08 5400 00    SERVICE MANUAL R 410A 8  R 22 Split System AC  amp  HP  Table 11   R 22 Superheat Chart    R   22 Vapor Line Temperature    F   Superheat    F     a e  af  5  2   14        18  20 22  24  26  28        1  6  48  50  52  54  56  58  60  7  49  5 53  55  57  569  6t   50  52  54  56  58         62   50  52  54  56  58         62   52  54  56  58         62  64   52  54  56  58        62  64  66   54  56  58         62         66  68   54  56  58         62         66  68   55  57  59  61  6    65  67  69   5
54. able 5  Jason determines there should be  10 psig pressure drop in the suction line     Jason now takes the suction line temperature at the outlet of  the evaporator and obtains 51 F  Per the instructions  Jason  adds the 10 psig pressure drop to the 60 psig pressure at  the outdoor unit to get 70 psig at the evaporator  Saturated  pressure of 70 psig equates to approximately 41  F  Jason  determines the Evaporator superheat to be  51  F   41  F     10      Jason concludes the TXV is functioning properly     NOTE  In this situation  both the pressure drop and the heat  gain in the suction line are significant contributions to the  superheat at the service valve  The pressure drop  contributes approximately 7  F superheat and the heat gain  in the suction line contributes 13  F                    Fig  27     Pseudo Evaporator Superheat Pressure and Temperature Measurement Locations    421 08 5400 00    30    Specifications subject to change without notice     SERVICE MANUAL R 410A  amp  R 22 Split System AC  amp  HP  Table 6   R 410A Refrigerant Pressure Temperature Chart    705 163 0          Source  Allied Signal   Genetron for Windows version R1 0     1999    Specifications subject to change without notice     31 421 08 5400 00    SERVICE MANUAL R 410A  amp  R 22 Split System AC  amp  HP  Table 7   R 22 Refrigerant Pressure Temperature Relationship             421 08 5400 00 32    Specifications subject to change without notice     R 410A  amp  R 22 Split System AC  amp  HP
55. ach to liquid line near defrost  thermostat  Insulate for more accurate reading    3  Turn on power to outdoor unit      Restart unit in heating    5  Within a few minutes  liquid line temperature drops  within a range causing defrost thermostat contacts to  close  Temperature range is from 33  F to 27  F   Notice temperature at which ohmmeter reading goes  from ee to zero ohms  Thermostat contacts close at  this point    6  Short between the speed up terminals using a small  slotted screwdriver    7  Unit changes over to defrost within 21 sec  depending  on timing cycle setting   Liquid line temperature rises  to range where defrost thermostat contacts open   Temperature range is from 60  F to 70  F  Resistance  goes from zero to      when contacts are open    8  If either opening or closing temperature does not fall  within above ranges or thermostat sticks in 1 position   replace thermostat to ensure proper defrost  operation    NOTE  With timing cycle set at 90 minutes  unit initiates   defrost within approximately 21 sec  When you hear the   reversing valve changing position  remove screwdriver  immediately  Otherwise  control will terminate normal  10 minute defrost cycle in approximately 2 sec     Fan Motor    The fan motor rotates the fan blade that draws air through  the outdoor coil to exchange heat between the refrigerant  and the air  Motors are totally enclosed to increase reliability   This eliminates the need for a rain shield  For the correct  position of fan 
56. age   both sides of external sheet metal and grilles     e Paint coated screws    Coastal environments are considered to be within 2 miles of  the ocean  Salt water can be carried as far away as 2 miles  from the coast by means of sea spray  mist or fog     Line of sight distance from the ocean  prevailing wind  direction  relative humidity  wet dry time  and coil  temperatures will determine the severity of corrosion  potential in the coastal environment     LOW AMBIENT COOLING  GUIDELINE    The minimum operating temperature for these units in  cooling mode is 55  F 12 7  C outdoor ambient without  additional accessories  Low ambient cannot be used with  Communicating control  If Low ambient requirements are  needed  use as non communicating  and refer to  specification sheets for proper accessories required  Wind  baffles are required when operating in cooling mode at  ambients below 55  F 12 7  C  Plans are shown in Low  Ambient Pressure Kit instructions     Specifications subject to change without notice     SERVICE MANUAL  LONG LINE GUIDELINE    Refer to Split System Long Line Applications Guidelines for  air conditioner and heat pump systems     ACCESSORY DESCRIPTIONS    See the appropriate specification sheets and installation  manuals for accessory information     CABINET ASSEMBLY    Access Compressor Or Other Internal Cabinet  Components  NOTE  It is not necessary to remove the top cover to gain  access  Removing the top cover may cause grill panels   corner posts or
57. anged to terminate  defrost  It is a thermally actuated switch clamped to outdoor  coil to sense its temperature  Normal temperature range is  closed at 30     3  F and open at 65     5  F  Defrost  thermostats are used in non communicating models  a coil  temperature thermistor is used in Communicating units        Specifications subject to change without notice     421 08 5400 00    SERVICE MANUAL  FEEDER TUBE      STUB TUBE       LM    THERMOSTAT                                                                   A97517  Fig  6     Defrost Thermostat Location    Check Defrost Thermostat    There is a liquid header with a distributor and feeder tube  going into outdoor coil  At the end of 1 of the feeder tubes   there is a 3 8 in  OD stub tube approximately 2 in   50 8  mm  long   See Fig  6   The defrost thermostat should be  located on stub tube  Note that there is only 1 stub tube  used with a liquid header  and on most units it is the bottom  circuit    NOTE  The defrost thermostat must be located on the liquid  side of the outdoor coil on the bottom circuit and as close to  the coil as possible  For a copper stub tube  the DFT will  have a copper cup  For an aluminum stub tube  the DFT will  have an aluminum cup  Don t interchange material types     Defrost Control Board    Troubleshooting defrost control involves a series of simple  steps that indicate whether or not board is defective    NOTE  This procedure allows the service technician to  check control board and def
58. as a discharge temperature  switch  DTS   This is to protect against excessively high  scroll temperatures due to loss of charge or operating  outside the compressor envelope  This temperature sensor  opens to stop the compressor if temperatures exceed  239 257 F  115 125  C  and resets at 151 187  F   66 86       The DTS will break the Y signal in the 24 volt  circuit if it trips open    NOTE  The LG generation 2 compressor models will not  have this temperature switch     Test sensor wires for continuity  open above 239 257  F   115 125  C  and resets at 151 187  F  66 86          If replacement is deemed necessary  perform the following  to replace sensor     1  Locate top cap and discharge temperature sensor       A12342    Specifications subject to change without notice     13    421 08 5400 00    SERVICE MANUAL  2  Carefully remove sensor cover       A12343    3  Expose the sensor holder       A12344    4  Slide out the sensor  slide in replacement and reinstall  the cover       A12345  COMPRESSOR TROUBLESHOOTING  Compressor Failures    Compressor failures are classified in 2 broad failure  categories  mechanical and electrical  Both types are  discussed below     421 08 5400 00       R 410A  amp  R 22 Split System AC  amp  HP    Mechanical Failures    A compressor is a mechanical pump driven by an electric  motor contained in a welded or hermetic shell  In a  mechanical failure  motor or electrical circuit appears  normal  but compressor does not function normally     
59. as demanded by the thermostat  or wall control     On  CH9 models  if OAT is  lt 25  F   3 9  C   defrost will  occur in high stage only  regardless of thermostat or wall  control demand  and will terminate at 50  F  10      coil  temperature with a minimum of 2 5 minutes in defrost    If the coil temperature does not reach 32  F  0  C  within the  interval  the interval timer will be reset and start over     e Upon initial power up the first defrost interval is  defaulted to 30 minutes  Remaining intervals are at  selected times     e  Defrost is only allowed to occur below 50  F  10  C   outdoor ambient temperature    The outdoor fan output  ODF  will remain off for 20 seconds  after termination  This delay will allow time for the system to  capture the heat from the outdoor coil and reduce the   steam cloud  effect that may occur on transition from  defrost to the heating cycle  The outdoor fan output OFF  delay of 20 seconds may be defeated to enable the fan to  energize immediately at the time of termination and 12  seconds prior to the reversing valve de energizing  through  forced defrost pins as follows     e        ODF fan delay defeat can be toggled by  shorting the forced defrost pins for  gt 15 seconds  while in the standby mode  status LED on solid    The LED will start to flash when the toggle has  taken place     e Status code 4 shows the fan delay defeat is active   no delay     e Status code 3 shows that it is not active  20  second delay    The code will con
60. at between 15  F and 50  F     Hunting Superheat  NOTE  Hunting is when the valve superheat swings more  than 10 F Superheat in repetition  This is typically an  application issue   20  Check for obvious kinked or pinched distributor   capillary  tubes causing imbalance to the circuiting   e If OK proceed to Step 21    21  Check that proper size valve is used per Product  Literature     e  f OK proceed to Step 22  22  Check airflow  sensing bulb tightness  orientation on  vapor tube and ensure bulb is properly wrapped   e  f OK proceed to Step 23  23  Check for even temperature distribution   5    difference  at outlet of each circuit of evaporator and  for even air distribution over all evaporator slabs  e If OK proceed to Step 24   24  Move sensing bulb further down suction line        e  f problem not corrected  replace valve  Pseudo Evaporator Superheat Instructions    The Pseudo Evaporator Superheat calculates the superheat  at the outlet of the evaporator with known and available  information  Because there generally is not a pressure port       90  STD    90  LONG RAD    R 410A  amp  R 22 Split System AC  amp  HP    on the vapor line at the indoor coil  this procedure allows the  service personnel to evaluate the evaporator superheat with  the vapor pressure port at the outdoor unit    The method requires the following information     e Suction line temperature at the outlet of the  evaporator   F      e Suction line pressure at the outdoor unit  psig    e Outdoor nomi
61. ationary and an orbiting  scroll   See Fig  8   The scroll compressor has no dynamic  suction or discharge valves  and it is more tolerant of  stresses caused by debris  liquid slugging  and flooded  starts  The compressor is equipped with an internal  pressure relief port  The pressure relief port is a safety  device  designed to protect against extreme high pressure   The relief port has an operating range between 550 to 625  psi differential pressure for R 410A and 350 to 450 psi  differential pressure for R 22  Scrolls have a variety of shut  down solutions  depending on model  to prevent backward  rotation and eliminate the need for cycle protection     LG SCROLL COMPRESSOR    The compressors used in these products are specifically  designed to operate with designated refrigerants and cannot  be interchanged     LG produced scroll compressors are designed to operate  and function as the typical orbiting scroll on a fixed scroll  design  Refrigerant flow and compression is basically the  same     Characteristics of the LG Scroll Compressor     Internal Motor Overload Protection  OLP   This is       inherent protection system sensing both motor winding  temperature and motor current  This is designed to open the  common wire on single phase units and stop the motor  operation if motor high temperature or over current  conditions exist  Trip of the OLP opens the common line     Vacuum protection device  If the suction side of the  compressor is blocked or limited  an extrem
62. blade assembly  the fan hub should be flush  with the motor shaft  Replacement motors and blades may  vary slightly     4  WARNING    ELECTRICAL SHOCK HAZARD    A    Failure to follow this warning could result in personal  injury or death     Turn off all power before servicing or replacing fan  motor  Be sure unit main power switch is turned off        The bearings are permanently lubricated  therefore  no oil  ports are provided     For suspected electrical failures  check for loose or faulty  electrical connections  or defective fan motor capacitor  Fan  motor is equipped with thermal overload device in motor  windings which may open under adverse operating  conditions  Allow time for motor to cool so device can reset   Further checking of motor can be done with an ohmmeter   Set scale on    X 1 position  and check for continuity  between 3 leads  Replace motors that show an open circuit  in any of the windings  Place 1 lead of ohmmeter on each  motor lead  At same time  place other ohmmeter lead on  motor case  ground   Replace any motor that shows  resistance to ground  arcing  burning  or overheating     Compressor Plug    The compressor electrical plug provides a quick tight  connection to compressor terminals  The plug completely  covers the compressor terminals and the mating female    421 08 5400 00    R 410A  amp  R 22 Split System AC  amp  HP    terminals are completely encapsulated in plug  Therefore   terminals are isolated from any moisture so corrosion and  re
63. cal Labeling             Piston Label       A150066    Francis Plumbing  amp  Heating   www FrancisPlumbing com   613 224 0041   office francisplumbing com    421 08 5400 00 6    Specifications subject to change without notice     SERVICE MANUAL  ELECTRICAL    4  WARNING    ELECTRICAL SHOCK HAZARD    Failure to follow this warning could result in personal  injury or death     Exercise extreme caution when working on any  electrical components  Shut off all power to system prior  to troubleshooting  Some troubleshooting techniques  require power to remain on  In these instances  exercise  extreme caution to avoid danger of electrical shock   ONLY TRAINED SERVICE PERSONNEL SHOULD  PERFORM ELECTRICAL TROUBLESHOOTING        Aluminum Wire    4  CAUTION    UNIT OPERATION AND SAFETY HAZARD  Failure to follow this caution may result in equipment    damage or improper operation     Aluminum wire may be used in the branch circuit  such  as the circuit between the main and unit disconnect    but only copper wire may be used between the unit  disconnect and the unit   Whenever aluminum wire is used in branch circuit wiring  with this unit  adhere to the following recommendations     Connections must be made in accordance with the National  Electrical Code  NEC   using connectors approved for  aluminum wire  The connectors must be UL approved   marked Al Cu with the UL symbol  for the application and  wire size  The wire size selected must have a current  capacity not less than that of th
64. cal support  manuals for rating information  electrical data  required  clearances  additional component part numbers and related  pre sale data  Installation Instructions are also available per  specific models     INSTALLATION GUIDELINE    Residential New Construction    Specifications for these units in the residential new  construction market require the outdoor unit  indoor unit   refrigerant tubing sets  metering device  and filter drier listed  in specification sheets and technical support manuals  DO  NOT DEVIATE  Consult unit Installation Instructions for  detailed information     Add On Replacement  Retrofit    R 22 to  R 410A    Specifications for these units in the add on  replacement retrofit market require change out of outdoor  unit  metering device  and all capillary tube coils   Change out of indoor coil is recommended  There can be  no deviation    1  If system is being replaced due to compressor  electrical failure  assume acid is in system  If system  is being replaced for any other reason  use approved  acid test kit to determine acid level  If even low levels  of acid are detected install factory approved  100  percent activated alumina suction line filter drier in  addition to the factory supplied liquid line filter drier     421 08 5400 00    R 410A  amp  R 22 Split System AC  amp  HP  Remove the suction line filter drier as soon as  possible  with a maximum of 72 hr     2  Drain oil from low points or traps in suction line and  evaporator if they were
65. cifically designed to  operate with R 410A systems  R 22 pressure switches  must not be used as replacements for the R 410A air  conditioner or heat pump  R 410A pressure switches are  identified by a pink stripe down each wire     Low Pressure Switch  AC Only   The low pressure switch is located on suction line and  protects against low suction pressures caused by such  events as loss of charge  low airflow across indoor coil  dirty  filters  etc  It opens on a pressure drop at about 50 psig for  R 410A and about 27 for R 22  If system pressure is above  this  switch should be closed  To check switch    1  Turn off all power to unit    2  Disconnect leads on switch    3  Apply ohmmeter leads across switch  You should   have continuity on a good switch    NOTE  Because these switches are attached to refrigeration  system under pressure  it is not advisable to remove this  device for troubleshooting unless you are reasonably  certain that a problem exists  If switch must be removed   remove and recover all system charge so that pressure  gauges read 0 psi  Never open system without breaking  vacuum with dry nitrogen     A CAUTION       PERSONAL INJURY HAZARD    Failure to follow this caution may result in personal  injury   Wear safety glasses  protective clothing  and gloves  when handling refrigerant    To replace switch     1  Apply heat with torch to solder joint and remove  switch     A CAUTION    PERSONAL INJURY HAZARD       Failure to follow this caution may result in p
66. connected to the compressor HAS an internal rectifier that  converts the 24v AC signal to 24v DC  DO NOT INSTALL A  PLUG WITHOUT AN INTERNAL RECTIFIER     Unloader Test Procedure    CAT   CA9   CH6    CH9    The unloader is the compressor internal mechanism   controlled by the DC solenoid  that modulates between high  and low stage  If it is suspected that the unloader is not  working  the following methods may be used to verify  operation     1  Operate the system and measure compressor  amperage  Cycle the unloader on and off at 30  second plus intervals at the UI  from low to high stage  and back to low stage   Wait 5 seconds after staging  to high before taking a reading  The compressor  amperage should go up or down at least 20 percent     2  If the expected result is not achieved  remove the  solenoid plug from the compressor and with the unit  running and the UI calling for high stage  test the  voltage output at the plug with a DC voltmeter  The  reading should be 24 volts DC     3  If the correct DC voltage is at the control circuit mold   ed plug  measure the compressor unloader coil resis   tance  The resistance should be approximately 330 or  1640 ohms depending on unloader coil supplier  If the  coil resistance is infinite or is grounded  the compres   sor must be replaced     Specifications subject to change without notice     43    421 08 5400 00    SERVICE MANUAL    Temperature Thermistors   Thermistors are electronic devices which sense  temperature  As the t
67. cumulator   If more than 20 percent of oil charge is trapped in  accumulator  add new POE oil to compressor to make up for  this loss        421 08 5400 00    R 410A  amp  R 22 Split System AC  amp  HP    ie 430   FUSE    ELEMENT    A88410  Fig  19     Accumulator    Thermostatic Expansion Valve  TXV     All fan coils and furnace coils will have a factory installed  thermostatic expansion valve  TXV   The TXV will be a  bi flow  hard shutoff with an external equalizer and a  balance port pin  A hard shut off TXV does not have a  bleed port  Therefore  minimal equalization takes place after  shutdown  TXVs are specifically designed to operate with  R 410A or R 22 refrigerant  use only factory authorized  TXV s  Do not interchange R 410A and R 22 TXVs     TXV Operation   The TXV is a metering device that is used in air conditioning  and heat pump systems to adjust to changing load  conditions by maintaining a preset superheat temperature at  the outlet of the evaporator coil  The volume of refrigerant  metered through the valve seat is dependent upon the  following     1  Superheat temperature is sensed by cap tube  sensing bulb on suction tube at outlet of evaporator  coil  This temperature is converted into pressure by  refrigerant in the bulb pushing downward on the  diaphragm which opens the valve via the pushrods     2  The suction pressure at the outlet of the evaporator  coil is transferred via the external equalizer tube to  the underside of the diaphragm  This is neede
68. d to  account for the indoor coil pressure drop  Residential  coils typically have a high pressure drop  which  requires this valve feature     3  The pin is spring loaded  which exerts pressure on   the underside of the diaphragm  Therefore  the bulb  pressure works against the spring pressure and  evaporator suction pressure to open the valve   If the load increases  the temperature increases at the  bulb  which increases the pressure on the top side of  the diaphragm  This opens the valve and increases  the flow of refrigerant  The increased refrigerant flow  causes the leaving evaporator temperature to  decrease  This lowers the pressure on the diaphragm  and closes the pin  The refrigerant flow is effectively  stabilized to the load demand with negligible change  in superheat     22    Specifications subject to change without notice     SERVICE MANUAL    Install TXV   The thermostatic expansion valve is specifically designed to  operate with a refrigerant type  Do not use an R 22 TXV on  a R 410A system  and do not use a R 410A valve on an  R 22 system  Refer to specification sheets for the  appropriate TXV kit number     A CAUTION    UNIT OPERATION HAZARD    Failure to follow this caution may result in  equipment damage or improper operation     Al indoor coil units must be installed with a hard  shut off R 410A TXV metering device        IMPORTANT  The TXV should be mounted as close to  the indoor coil as possible and in a vertical  upright  position  Avoid mounting th
69. de that either draws or blows  air through outdoor coil to exchange heat between  refrigerant and air  Motors are totally enclosed to increase  reliability  This also eliminates need for rain shield     4  WARNING    ELECTRICAL SHOCK HAZARD    Failure to follow this warning could result in personal  injury or death     Turn off all power to unit before servicing or replacing  fan motor  Be sure unit main power switch is turned off        The bearings are permanently lubricated  therefore  no oil  ports are provided     For suspected electrical failures  check for loose or faulty  electrical connections  or defective fan   motor capacitor  Fan  motor is equipped with thermal overload device in motor  windings which may open under adverse operating  conditions  Allow time for motor to cool so device can reset   Further checking of motor can be done with an ohmmeter   Set scale on R X 1 position  check for continuity between  three leads  Replace motors that show an open circuit in  any of the windings  Place 1 lead of ohmmeter on each  motor lead  At same time  place other ohmmeter lead on  motor case  ground   Replace any motor that shows  resistance to ground  signs of arcing  burning        overheating    Located above the compressor is a single speed fan motor  and fan  The  CA9 and  CHO air conditioner and heat pump  models use the ECM variable speed fan motor     The outdoor Integral Control Motor  ECM   is a  variable speed motor which operates from 450 to 850 rpm   The 
70. defrost thermostat must be closed  or the defrost  thermostat pins must be jumpered  Follow the steps below  to force a defrost cycle   1  Jumper the DFT input  2  Short the speed up pins  This speeds up the defrost  timer by a factor of 256  The longer the defrost  interval setting  the longer the pins must be shorted to  speed through the timing  For example  if interval is  90 min  the speed up will take  90 256 min x   60seconds  minute   21 seconds max  This could be  shorter depending on how much time has elapsed  since the defrost thermostat closed   3  Remove the short immediately when the unit shifts  into defrost  Failure to remove the short immediately  will result in a very short forced defrost cycle  the 10  minute timer will be sped through in 2 seconds   4  When defrost begins  it will continue until the defrost  thermostat opens or 10 minutes has elapsed   NOTE  The T1 terminal on the defrost board powers the  defrost timing function  This terminal must be energized  before any defrost function will occur     If defrost thermostat is stuck closed     Whether the unit is in heating or cooling mode  it will run a  defrost cycle for 10 minutes each time the compressor has  been energized for the selected time interval  The board will  terminate automatically after 10 minutes of defrost time  regardless of defrost thermostat position    If defrost thermostat is stuck open    The unit will not defrost   NOTE  Unit will remain in defrost until defrost thermostat  re
71. dent on such  factors as hours of operation  geographic location  and local  environmental conditions     4  WARNING    ELECTRICAL SHOCK HAZARD  Failure to follow this warning could result in personal    injury or death     Disconnect all electrical power to unit before performing  any maintenance or service on outdoor unit  Remember  to disconnect power supply to air handler as this unit  supplies low voltage power to the outdoor unit        The minimum maintenance that should be performed on this  equipment is as follows     1  Check outdoor coil for cleanliness each heating and  cooling season and clean as necessary     2  Check fan motor and blade for cleanliness each  month during cooling season and clean as necessary     3  Check electrical connections for tightness and  controls for proper operation each cooling season  and service as necessary        CAUTION    UNIT DAMAGE HAZARD  Failure to follow this caution may result in equipment    damage or improper operation     Because of possible damage to the equipment or  personal injury  maintenance should be performed by  qualified personnel only        Desert and Seacoast Locations    Special consideration must be given to installation and  maintenance of condensing units installed in coastal or  desert locations  This is because salt and alkali content of  sand adheres to aluminum fins of coil and can cause  premature coil failure due to corrosion    Preventive measures can be taken during installations  such  as    1 
72. detects this sound and uses it as a valuable  troubleshooting tool     Using a remote measuring device  check inlet and outlet line  temperatures  DO NOT touch lines  If reversing valve is  operating normally  inlet and outlet temperatures on  appropriate lines should be close to each other  Any  difference would be due to heat loss or gain across valve  body  Temperatures are best checked with a remote reading  electronic type thermometer with multiple probes  Route  thermocouple leads to inside of coil area through service  valve mounting plate area underneath coil  Fig  15 and Fig   16 show test points  TP  on reversing valve for recording  temperatures  Insulate points for more accurate reading     If valve is defective        R 410A  amp  R 22 Split System AC  amp  HP    1  Shut off all power to unit and remove charge from  system    2  Remove solenoid coil from valve body  Remove valve  by cutting it from system with tubing cutter  Repair  person should cut in such a way that stubs can be  easily re brazed back into system  Do not use  hacksaw  This introduces chips into system that  cause failure  After defective valve is removed  wrap it  in wet rag and carefully unbraze stubs  Save stubs for  future use  Because defective valve is not  overheated  it can be analyzed for cause of failure  when it is returned    3  Braze new valve onto used stubs  Keep stubs  oriented correctly  Scratch corresponding matching  marks on old valve and stubs and on new valve body  to aid 
73. e  Check  between C and W2 using voltmeter  Reading on  voltmeter should indicate 24v  This step ensures  defrost relay contacts have closed  energizing  supplemental heat  W2  and reversing valve solenoid   O     11  Unit should remain in defrost no longer than 10  minutes  Actual time in defrost depends on how  quickly speed up jumper is removed  If it takes 2 sec  to remove speed up jumper after unit has switched to  defrost  the unit will switch back to heat mode    12  After a few minutes  in defrost  cooling  operation   liquid line should be warm enough to have caused  defrost thermostat contacts to open  Check  resistance across defrost thermostat  Ohmmeter  should read infinite resistance  indicating defrost  thermostat has opened at approximately 65  F    13  Shut off unit power and reconnect fan lead    14  Remove jumper between DFT and R terminals   Reconnect defrost thermostat leads  Failure to  remove jumper causes unit to switch to defrost every  30  60  or 90 minutes and remain in defrost for full 10  minutes    15  Replace control box cover  Restore power to unit    If defrost thermostat does not check out following  above items or incorrect calibration is suspected  check  for defective thermostat as follows     Specifications subject to change without notice     11    421 08 5400 00    SERVICE MANUAL    1  Follow items 1 5 above     2  Route sensor or probe underneath coil  or other  convenient location  using thermocouple temperature  measuring device  Att
74. e High Stage         amp  high  Model  OAT lt 104  F   40              lt 104       40  C  Stage    OAT gt 104  F   40  C     CH924 8 72 9 35 11 90   CH936 9 06 10 23 11 90   CH948 9 91 11 04 11 90   CH960 10 83 11 70 11 90   CA924 9 57 10 88 11 90   CA936 9 06 10 23 11 90   CA948 9 91 11 04 11 90   CA960 10 83 11 70 11 90    NOTE  For  CH9 models in low ambient cooling  the PWM  output for both high  and low stage equals the value for  low stage operation below 55 F  12 8 C      ECM Fan Motor Troubleshooting  If the outdoor fan motor fails to start and run        e Check the high voltage supply  The unit need not  be running to check high voltage  but the power  must be on     e Ifthe 230vac is present  use Table 13 to check for  proper control voltage output to the fan motor from  the control board  The control board sends DC  voltage signals to the motor through the terminals  labeled PWM1        PWM  Set a voltmeter on a DC  voltage scale and check across these terminals     e First check voltage with the motor disconnected  If  no control voltage is present  check control board  connections  If connections are good  replace the  control board    e  f voltage is present  reconnect the motor and  check again  Shut down the unit to reconnect the  motor and restart the unit to complete this  troubleshooting procedure  If control voltage is no  longer present or motor fails to respond  check  motor connections     e  f connections are good  replace the motor   Time Delays  Th
75. e condenser  is the outdoor coil in the cooling mode and the evaporator is  the indoor coil     In a heat pump  the condenser is the indoor coil in the  heating mode and the evaporator is the outdoor coil     In the typical air conditioning mode  compressed hot gas  leaves the compressor and enters the condensing coil  As  gas passes through the condenser coil  it rejects heat and  condenses into liquid  The liquid leaves condensing unit  through liquid line and enters metering device at evaporator  coil  As it passes through metering device  it becomes a  gas liquid mixture  As it passes through indoor coil  it  absorbs heat and the refrigerant moves to the compressor  and is again compressed to hot gas  and cycle repeats     Servicing Systems on Roofs With Synthetic  Materials    POE  polyol ester  compressor lubricants are known to  cause long term damage to some synthetic roofing  materials  Exposure  even if immediately cleaned up  may  cause embrittlement  leading to cracking  to occur in one  year or more  When performing any service which may risk  exposure of compressor oil to the roof  take appropriate  precautions to protect roofing  Procedures which risk oil  leakage include but are not limited to compressor  replacement  repairing refrigerants leaks  replacing  refrigerant components such as filter drier  pressure switch   metering device  coil  accumulator  or reversing valve   Synthetic Roof Precautionary Procedure   1  Cover extended roof working area with an 
76. e copper wire specified  and  must not create a voltage drop between service panel and  unit in excess of 2 of unit rated voltage  To prepare wire  before installing connector  all aluminum wire must be   brush scratched  and coated with a corrosion inhibitor  such as Pentrox A  When it is suspected that connection will  be exposed to moisture  it is very important to cover entire  connection completely to prevent an electrochemical action  that will cause connection to fail very quickly  Do not reduce  effective size of wire  such as cutting off strands so that wire  will fit a connector  Proper size connectors should be used   Check all factory and field electrical connections for  tightness  This should also be done after unit has reached  operating temperatures  especially if aluminum conductors  are used     Contactor    The contactor provides a means of applying power to unit  using low voltage  24v  from transformer in order to power  contactor coil  Depending on unit model  you may encounter  single  or double pole contactors  Exercise extreme  caution when troubleshooting as 1 side of line may be  electrically energized  The contactor coil is powered by  24vac  If contactor does not operate    1  With power off  check whether contacts are free to  move  Check for severe burning or arcing on contact  points    2  With power off  use ohmmeter to check for continuity  of coil  Disconnect leads before checking  A low  resistance reading is normal  Do not look for a      
77. e inlet tube vertically down   The valve is more susceptible to malfunction due to  debris if inlet tube is facing down  A factory approved  filter drier must be installed in the liquid line at the  indoor unit   Installing TXV in Place of Piston in a Rated Indoor Coil   pre 2006   1  Pump system down to 2 psig and recover refrigerant   2  Remove hex nut from piston body  Use backup  wrench on fan coils   3  Remove and discard factory installed piston  Be sure  Teflon seal is in place   4  Reinstall hex nut  Finger tighten nut plus 1 2 turn   NOTE  If the piston is not removed from the body  TXV will  not function properly     A CAUTION    EQUIPMENT DAMAGE HAZARD       Failure to follow this caution may result in  equipment damage or improper operation     Use a brazing shield and wrap TXV with wet  cloth or use heat sink material       5  Install TXV on indoor coil liquid line  Sweat swivel  adapter to inlet of indoor coil and attach to TXV outlet   Use backup wrench to avoid damage to tubing or  valve  Sweat inlet of TXV  marked  IN  to liquid line   Avoid excessive heat which could damage valve    6  Install vapor elbow with equalizer adapter to suction  tube of line set and suction connection to indoor coil   Adapter has a 1 4 in  male connector for attaching  equalizer tube    7  Connect equalizer tube of TXV to 1 4 in  equalizer  fitting on vapor line adapter    8  Attach TXV bulb to horizontal section of suction line  using clamps provided  Insulate bulb with  field su
78. e unit time delays include     e Five minute time delay to start cooling or heating  operation when there is a call from the thermostat  or wall control  To bypass this feature  momentarily    40    Specifications subject to change without notice     SERVICE MANUAL    short and release Forced Defrost pins  Speed up is  also possible by pressing the Cool To or Heat To  button on the Communicating wall control     e Five minute compressor re cycle delay on return  from a brown out condition     e Two minute time delay to return to standby  operation from last valid communication  with  Communicating only      e  Oneminute time delay of outdoor fan at termination  of cooling mode when outdoor ambient is greater  than or equal to 100  F     e Fifteen second delay at termination of defrost  before the auxiliary heat  W1  is de energized     e Twenty second delay at termination of defrost  before the outdoor fan is energized     e Thirty second compressor delay when quiet shift  enabled     e Seventy and sixty second compressor delays  when Quiet Shift 2 is enabled     e       CH6 models there is a 1 minute time delay  between staging from low to high and from high to  low capacity  On  CH6 models there is no delay   the compressor will change from low to high and  from high to low capacity  on the fly  to meet the  demand     Pressure Switches    The R 410A two stage air conditioner contains two  pressure switches to prevent system operation if the  pressures get excessively high 
79. een  running  the area will still be warm     With power off and heater leads disconnected  check across  leads with ohmmeter  Do not look for a specific resistance  reading  Check for resistance or an open circuit  Change  heater if an open circuit is detected     Time Delay Relay    The TDR is a solid state control  recycle delay timer which  keeps indoor blower operating for 90 sec after thermostat is  satisfied  This delay enables blower to remove residual  cooling in coil after compression shutdown  thereby  improving efficiency of system  The sequence of operation  is that on closure of wall thermostat and at end of a fixed on  delay of 1 sec  fan relay is energized  When thermostat is  satisfied  an off delay is initiated  When fixed delay of 90    20 sec is completed  fan relay is de energized and fan  motor stops  If wall thermostat closes during this delay  TDR  is reset and fan relay remains energized  TDR is a 24v  device that operates within a range of 15v to 30v and draws  about 0 5 amps  If the blower runs continuously instead of    8                   Specifications subject to change without notice     SERVICE MANUAL    cycling off when the fan switch is set to AUTO  the TDR is  probably defective and must be replaced     Pressure Switches    Pressure switches are protective devices wired into control  circuit  low voltage   They shut off compressor if abnormally  high or low pressures are present in the refrigeration circuit   R 410A pressure switches are spe
80. eep ends of tubing sealed  during installation     A CAUTION    UNIT DAMAGE HAZARD    Failure to follow this caution may result in equipment  damage or improper operation     If ANY refrigerant tubing is buried  provide a 6 in   vertical rise at service valve  Refrigerant tubing lengths  up to 36 in  may be buried without further special  consideration  Do not bury lines longer than 36 in        421 08 5400 00    R 410A  amp  R 22 Split System AC  amp  HP    SENSING  BULB        EQUALIZER    TUBE             THERMOSTATIC  EXPANSION  VALVE          A91277  Fig  21     Typical TXV Installation    REFRIGERATION SYSTEM REPAIR    Leak Detection    New installations should be checked for leaks prior to  complete charging  If a system has lost all or most of its  charge  system must be pressurized again to approximately  150 psi minimum and 375 psi maximum  This can be done  by adding refrigerant using normal charging procedures or  by pressurizing system with nitrogen  less expensive than  refrigerant   Nitrogen also leaks faster than refrigerants   Nitrogen cannot  however  be detected by an electronic leak  detector   See Fig  22         A95422  Fig  22     Electronic Leak Detection    4  WARNING    PERSONAL INJURY AND UNIT DAMAGE HAZARD  Failure to follow this warning could result in personal    injury or death     Due to the high pressure of nitrogen  it should never  be used without a pressure regulator on the tank        Assuming that a system is pressurized with either all  
81. ely low vacuum  situation is formed by the optimum efficiency of the scrolls   The high vacuum pressure causes the arc at the internal  power terminal and cause tripping of the internal overload or  breaker or damage to the compressor  This compressor is  equipped with internal protection that opens if this high  vacuum condition exists and bypasses high pressure gas to  the low pressure and the internal overload may trip  In the  case of refrigerant pump down  the unit can operate with  pump down but this protection may not allow the refrigerant  to be pumped down completely     Internal Pressure Relief  IPR   The internal pressure relief  is located between the high and low pressure of the  compressor and is designed to open when the difference of  the suction and discharge pressure is 500 550 psid  When  the IPR valve opens  the high temperature gas bypasses  into the motor area and will trip the motor OLP    Quiet Shut Down Device  The LG scroll has a shut down  device to efficiently minimize the shut down sound  The  reversing sound is minimized by a check valve located in  the discharge port of the scroll sets  This slows the       R 410A  amp  R 22 Split System AC  amp  HP    equalization of the high side to low side upon shut down to  prevent the scrolls from operating backwards    Discharge Temperature Protection  The compressor  discharge temperature may be monitored by a temperature  sensor mounted on the top cap of the compressor  Wire  diagrams may refer to this 
82. emperature increases  the resistance  decreases  Thermistors are used to sense outdoor air  OAT   and coil temperature  OCT   Refer to Fig  28 for resistance  values versus temperature    If the outdoor air or coil thermistor should fail  the control will  flash the appropriate fault code   See Table 15   IMPORTANT  The outdoor air thermistor and coil  thermistor should be factory mounted in the final  locations  Check to ensure thermistors are mounted  properly per Fig  31 and Fig  32     Thermistor Sensor Comparison    The control continuously monitors and compares the  outdoor air temperature sensor        outdoor coil  temperature sensor to ensure proper operating conditions   The comparison is         ncooling if the outdoor air sensor indicates  gt  10  F  warmer than the coil sensor  or  the outdoor air  sensor indicates  gt  20  F cooler than the coil  sensor  the sensors are out of range          n heating if the outdoor air sensor indicates  gt  35  F  warmer than the coil sensor  or  the outdoor air  sensor indicates   10  F cooler than the coil  sensor  the sensors are out of range    If the sensors are out of range  the control will flash the  appropriate fault code as shown in Table 15     OAT Thermistor must be  locked in place with spheri   cal nib end facing towards  the front of the control box          Bs    f t 1 NO  Dx  D   C use                                                                   A150065  Fig  31     Outdoor Air Thermistor  OAT  Attachment 
83. ermal Cutout  High Stage 72   Thermal Cutout  Contactor Shorted 73  No 230V at 74  Compressor  Low Stage 81  Thermal Lockout  High Stage 82  Thermal Lockout         Pressure  Lockout 83  High   Pressure  Lockout iy         POSSIBLE CAUSE AND ACTION    Normal operation    Normal operation  Normal operation  User made selection  see instructions for more detail  User made selection  see instructions for more detail    Communication with wall control lost  Check wiring to wall control  indoor  and outdoor units    Control does not detect a model plug or detects an invalid model plug  Unit  will not operate without correct model plug     High    pressure switch trip  Check refrigerant charge  outdoor fan operation  and coils for airflow restrictions     Low   pressure switch trip  Check refrigerant charge and indoor air flow     Outdoor unit control board has failed  Control board needs to be replaced     Line voltage    187v for at least 4 seconds  Compressor and fan operation  not allowed until voltage 190v  Verify line voltage     There is no 230v at the contactor when indoor unit is powered and cooling   heating demand exists  Verify the disconnect is closed and 230v wiring is  connected to the unit     Outdoor air sensor not reading or out of range  Ohm out sensor and check  wiring     Coil sensor not reading or out of range  Ohm out sensor and check wiring     Improper relationship between coil sensor and outdoor air sensor  Ohm out  sensors and check wiring    Compressor o
84. ersonal  injury     Wear safety glasses when using torch  Have quenching  cloth available  Oil vapor in line may ignite when switch  is removed   2  Braze in 1 4 in  flare fitting and screw on replacement  pressure switch     High Pressure Switch  AC  amp  HP     The high pressure switch is located in liquid line and  protects against excessive condenser coil pressure  It  opens around 610 to 670 psig for R 410A and 400 psig for  R 22      10 for both   Switches close at 298      20  psig  for R 22 and 420 or 470      25  psig for R 410A  High  pressure may be caused by a dirty condenser coil  failed fan  motor  or condenser air re circulation     To check switch           R 410A  amp  R 22 Split System AC  amp  HP    1  Turn off all power to unit    2  Disconnect leads on switch    3  Apply ohmmeter leads across switch  You should   have continuity on a good switch    NOTE  Because these switches are attached to refrigeration  system under pressure  it is not advisable to remove this  device for troubleshooting unless you are reasonably  certain that a problem exists  If switch must be removed   remove and recover all system charge so that pressure  gauges read 0 psi  Never open system without breaking  vacuum with dry nitrogen     4 CAUTION    PERSONAL INJURY HAZARD    Failure to follow this caution may result in personal  injury   Wear safety glasses  protective clothing  and gloves  when handling refrigerant    To replace switch     1  Apply heat with torch to solder join
85. ethod and the triple evacuation method     Deep Vacuum Method    The deep vacuum method requires a vacuum pump  capable of pulling a vacuum of 500 microns and a vacuum  gauge capable of accurately measuring this vacuum depth   The deep vacuum method is the most positive way of  assuring a system is free of air and moisture   See Fig  24         421 08 5400 00    R 410A  amp  R 22 Split System AC  amp  HP    5000  4500  4000      3500   5 3000      2500     2000  1500  1000   500          LEAK IN  SYSTEM          VACUUM TIGHT  TOO WET    TIGHT  DRY SYSTEM         0 1 2 3 4 5 6 7  MINUTES      95424  Fig  24   Deep Vacuum Graph  Triple Evacuation Method    The triple evacuation method should be used when vacuum  pump is only capable of pumping down to 28 in  of mercury  vacuum and system does not contain any liquid water  Refer  to Fig  25 and proceed as follows     1  Pump system down to 28 in  of mercury and allow  pump to continue operating for an additional 15  minutes    2  Close service valves and shut off vacuum pump    3  Connect a nitrogen cylinder and regulator to system  and open until system pressure is 2 psig    4  Close service valve and allow system to stand for 1  hr  During this time  dry nitrogen will be able to diffuse  throughout the system absorbing moisture    5  Repeat this procedure as indicated in Fig  25  System  will then be free of any contaminants and water vapor     v    BREAK VACUUM WITH DRY NITROGEN    v    v    EVACUATE    v    BREAK VACUUM WITH
86. gher efficiency ratings of the system  The outdoor unit  control energizes outdoor fan anytime compressor is  operating  except for defrost or low ambient cooling  The  outdoor fan remains energized if a pressure switch or  compressor overload should open  The outdoor fan motor  will continue to operate for one minute after the compressor    421 08 5400 00       R 410A  amp  R 22 Split System AC  amp  HP    shuts off when the outdoor ambient is greater than or equal  to 100  F 37 7  C  This reduces pressure differential for easier  starting on next cycle  On  CA7 and  CH6 models  the  outdoor fan remains energized during the 1           compressor staging time delay    On  CA7 and  CH6 models  the outdoor fan motor is a PSC  type  A fan relay on the control board turns the fan off and  on by opening and closing a high voltage circuit to the  motor  It does not change speeds between low and high  stage operation    On  CA9 and  CH9 models  the outdoor fan is an ECM type   The motor control is continuously powered with high  voltage  The motor speed is determined by electrical pulses  provided by the PWM outputs on the control board  The  ECM motor RPM adjusts to outdoor conditions as described  in Table 13  The PWM output can be measured with a volt  meter set to DC volts    In low ambient cooling  below 55  F 12 7  C   the control  board cycles the fan off and on     Table 13   Outdoor Fan Motor PWM  Outdoor Temp  DC volts  Tolerance     2            Low  amp  High   Low Stag
87. groaning  or howling    noise  When receiving these  complaints  Quiet Shift 2  if available  may improve  the noise  but will probably not eliminate it totally   Check that the defrost thermostat or thermistor is  Operating properly  Insulating the defrost sensing  device may also help  If the howling or groaning noise  is intermittent  replacing the reversing valve may or  may not help     Rattling that occurs during a shift into or out of defrost  on a heat pump could indicate a pressure differential  issue  This is usually a brief occurrence  under 60  seconds  and can be remedied by incorporating Quiet  Shift 2  if available  This is a feature available in  communicating heat pumps that shuts down the  compressor during the defrost shift for approximately  1 minute allowing the pressures to equalize  It is  enabled by either a dip switch setting on the defrost  board  or in the wall control on Communicating  systems  Verify proper system charge as well     Specifications subject to change without notice     421 08 5400 00    SERVICE MANUAL R 410A  amp  R 22 Split System AC  amp  HP                                                                         A07124  Fig  9     Split Post Grommet part number  1172271                                                                                                                                                                                                                                                                          
88. he oil  and then  condenses into the oil  Upon start up  the compressor  draws suction from within itself first and lowers the  boiling point of the refrigerant that is entrained in the  oil  This can cause the liquid refrigerant and oil to boil  into the compression area or liquid refrigerant to wipe  off oil films that are critical for proper lubrication   Migration is worsened by greater temperature  differentials and or extra refrigerant in the system   Prevention of migration can be reduced by various  options but some of the more common remedies is to  verify proper charge and add a crankcase heater  where this situation is suspected       Operational vibration could indicate a charge issue     Verify charge and ensure proper piping and structural  penetration insulation  Tubing that is too rigid to  building rafters without proper insulation could  transfer noise throughout the structure  On some  occasions a sound dampener or mass weight  FAST  part no  1185726  placed on the vibrating tubing has  been known to reduce this noise  Utilizing  compressor split post grommets  see Fig  9  may also  reduce this vibration if piping cannot be remedied       An operational high pitch frequency or    waa waa       sound that appears to resonate through the suction  line could indicate a need to add more flex or muffling  in the lines  This has been occasional in scroll  compressor applications and is usually remedied by  adding a field fabricated suction line loop  see Fig   10
89. he scroll  The opening and closing of the  bypass port is controlled by an internal electrically operated  solenoid    The modulated scroll uses a single step of unloading to go  from full capacity to approximately 6796 capacity  A single  speed  high efficiency motor continues to run while the scroll  modulates between the two capacity steps  Modulation is  achieved by venting a portion of the gas in the first suction  pocket back to the low side of the compressor  thereby  reducing the effective displacement of the compressor  Full  capacity is achieved by blocking these vents  thus  increasing the displacement to 10096  A DC solenoid in the  compressor controlled by a rectified 24 volt AC signal in the  external solenoid plug moves the slider ring that covers and  uncovers these vents  The vent covers are arranged in such  a manner that the compressor operates at approximately  67  capacity when the solenoid is not energized and 10096  capacity when the solenoid is energized    The loading and unloading of the two step scroll is done  on  the fly  without shutting off the motor between steps    NOTE  67  compressor capacity translates to  approximately 80  cooling or heating capacity at the indoor  coil  The compressor will always start unloaded and stay  unloaded for five seconds even when the thermostat is  calling for high stage        Specifications subject to change without notice     39    421 08 5400 00    SERVICE MANUAL    Fan Motor    Fan motor rotates the fan bla
90. heat at Vapor Service Valve  and Pseudo Evaporator Superheat   e  f both are less than 2  F         likely not controlling  properly  i e  stuck open     REPLACE VALVE  e   fsuperheat is higher than 15  F  proceed to Step     3  Perform TXV function check   e With system running  place sensing bulb in ice  bath for  1 minute   gt  superheat should increase        f no response  Replace Valve       f OK proceed to Step 4  4  Check for even temperature distribution at outlet of  each circuit of evaporator  e  f greater than 15  F between circuits  distributor or  coil has a restriction   e If OK proceed to Step 5  Low Superheat with High Suction Pressure  NOTE  High suction pressure is considered for R 22      80  psig  R 410A      135 psig  An application issue or other  system component failure typically causes this condition   5  R 22 Systems  Check that proper valve used  not an  R 410A valve   e  f OK proceed to Step 6  6  Check airflow  sensing bulb tightness  orientation on  vapor tube and ensure bulb is properly wrapped   e If OK proceed to Step 7  7  Check that compressor is pumping properly    NOTE  Loose Rules of Thumb  Is discharge saturated   20 F higher than ambient temperature  15 discharge  superheat between 15 and 50     e If OK proceed to Step 8  8  Recheck Airflow and Subcooling        e  f OK proceed to Replace Valve  High Superheat with Normal or Low Pressure  NOTE  Normal or low suction pressure is considered   R 22  lt  80 psig  R 410A  lt  135 psig   9  
91. hose  spray coil vertically downward  with constant stream of water at moderate pressure   Keep nozzle at a 15  to 20  angle  about 3 in  from  coil face and 18 in  from tube  Spray so debris is  washed out of coil and basepan    4  Reinstall top cover and position blade    5  Reconnect electrical power and check for proper  operation    Cleaning Outdoor Fan Motor and Blade   1  Remove fan motor and blade  Be careful not to bend  or dent fan blade    2  Clean motor and blade with soft brush or cloth  Be  careful not to disturb balance weights on fan blade    3  Check fan blade setscrew for tightness    4  Reinstall fan motor and blade to top cover and check  for alignment    5  Reinstall top cover and position blade    6  Reconnect electrical power and check for proper  operation    Electrical Controls and Wiring   1  Disconnect power to both outdoor and indoor units    2  Check all electrical connections for tightness  Tighten  all screws      electrical connections  If any  connections appear to be burned or smoky   disassemble the connection  clean all parts and  stripped wires  and reassemble  Use a new connector  if old one is burned or corroded  and crimp tightly    3  Reconnect electrical power to indoor and outdoor  units and observe unit through 1 complete operating  cycle    4      there are any discrepancies in operating cycle   troubleshoot to find cause and correct    Refrigerant Circuit   1  Check refrigerant charge using the superheat  method  and if low on cha
92. iar with  standard service instruction and training material        equipment should be installed in accordance with  accepted practices and unit Installation Instructions  and in  compliance with all national and local codes  Power should  be turned off when servicing or repairing electrical  components  Extreme caution should be observed when  troubleshooting electrical components with power on   Observe all warning notices posted on equipment and in  instructions or manuals     4   WARNING    UNIT OPERATION AND SAFETY HAZARD  Failure to follow this warning could result in personal    injury or equipment damage     R 410A systems operate at higher pressures than  standard R 22 systems  Do not use R 22 service  equipment or components on R 410A equipment   Ensure service equipment is rated for R 410A        Refrigeration systems contain refrigerant under pressure   Extreme caution should be observed when handling  refrigerants  Wear safety glasses and gloves to prevent  personal injury  During normal system operations  some  components are hot and can cause burns  Rotating fan  blades can cause personal injury  Appropriate safety  considerations are posted throughout this manual where  potentially dangerous techniques are addressed     INTRODUCTION    This document provides required system information  necessary to install  service  repair or maintain the family air  conditioners and heat pumps using R 22 or R 410A  refrigerant     Refer to the unit specifications and techni
93. in lining up new valve properly  When brazing  stubs into valve  protect valve body with wet rag to  prevent overheating    4  Use slip couplings to install new valve with stubs back  into system  Even if stubs are long  wrap valve with a  wet rag to prevent overheating    5  After valve is brazed in  check for leaks  Evacuate  and charge system  Operate system in both modes           several times to be sure valve functions  properly   FROM INDOOR COIL VIA  TO OUTDOOR SERVICE VALVE ON  COIL OUTDOOR COIL  TO  ACCUMULATOR           FROM COMPRESSOR  DISCHARGE LINE    A88342  Fig  15     Reversing Valve   Cooling Mode or Defrost Mode  Solenoid Energized     421 08 5400 00 Francis Plumbing  amp  Heating   www FrancisPlumbing com   613 224 0041   office francisplumbing com 20    Specifications subject to change without notice     SERVICE MANUAL    TO INDOOR COIL  VIA SERVICE VALVE  ON OUTDOOR COIL    INSULATE  FOR X  TP 3  e   ACCURATE    READING      TO  FROM  OUTDOOR ACCUMULATOR    COIL  P TP 4    INSULATE FOR  ACCURATE ON  READING                          FROM COMPRESSOR  DISCHARGE LINE        ELECTRONIC  THERMOMETER      88341  Fig  16     Reversing Valve   Heating Mode  Solenoid De Energized    Liquid Line Filter Drier  Filter driers are specifically designed for R 22 or R 410A  refrigerant  Only operate with the appropriate drier using  factory authorized components   It is recommended that the liquid line drier be installed at the  indoor unit  Placing the drier near the TX
94. ine solenoid is  required to control refrigerant migration in the heating mode   The solenoid should be installed near the outdoor unit with  the arrow facing the outdoor unit  This is the direction of flow  control  See Split System Long Line Applications Guidelines  for long line application details    Accessory Liquid Solenoid with Communicating  Control    When using the Communicating control  the liquid line  solenoid output is provided at the Y1 connection  Connect  the solenoid as shown in the wiring label diagram  This is a  24vac output that is energized whenever the compressor is  energized  It closes  in the compressor off mode  to prevent  refrigerant migration into the unit through the liquid line    On Models with Accessory Liquid Solenoid Using a  Non Communicating Thermostat    The liquid solenoid is connect to the Y1 and C terminal  connections  The liquid solenoid closes  in the compressor  off mode  to prevent refrigerant migration into the unit  through the liquid line     CHECK CHARGE    All  CH6 units must be charged in high stage only    See Charging Tables 8  amp  10     Factory charge amount and desired subcooling are shown  on unit rating plate  Charging method is shown on  information plate inside unit  To properly check or adjust  charge  conditions must be favorable for subcooling  charging  Favorable conditions exist when the outdoor  temperature is between 70  F and 100  F  21 11  C and  37 78  C   and the indoor temperature is between 70  F and
95. ing a small  soft wire with small kinks through metering hole  Do  not damage metering hole  sealing surface around  piston cones  or fluted portion of piston    6  Clean piston refrigerant metering hole    7  Install a new retainer O ring  retainer assembly  or  Teflon washer before reassembling AccuRater          Specifications subject to change without notice     19    421 08 5400 00    SERVICE MANUAL  TEFLON  SEAL    XD  L PISTON    PISTON BODY    L SWEAT FLARE  ADAPTER    LIQUID SERVICE VALVE    A05226  Fig  13     Front Seating Service Valve with Chatleff  Connection Used in R 410A Heat Pumps            PISTON    PISTON  RETAINER    SWEAT FLARE ADAPTER      01019  Fig  14     AccuRater  Components   used in R 22 Heat Pumps     Reversing Valve    In heat pumps  changeover between heating and cooling  modes is accomplished with a valve that reverses flow of  refrigerant in system  This reversing valve device is easy to  troubleshoot and replace  The reversing valve solenoid can  be checked with power off with an ohmmeter  Check for  continuity and shorting to ground  With control circuit  24v   power on  check for correct voltage at solenoid coil  Check  for overheated solenoid     With unit operating  other items can be checked  such as  frost or condensate water on refrigerant lines     The sound made by a reversing valve as it begins or ends  defrost is a    whooshing    sound  as the valve reverses and  pressures in system equalize  An experienced service  technician 
96. ion until first stage is  satisfied or until second stage is required again  When both  first stage and second stage cooling are satisfied  the  compressor will shut off  The reversing valve will remain  energized until the control board power is removed or a call  for heating in initiated  With a call for heating  the outdoor  fan and compressor are energized  The compressor will  operate in high or low stage operation  as needed to meet  the heating demand  When the heating demand is satisfied   the compressor and fan will shut off  The reversing valve is  de energized in the heating mode    NOTE  When two stage unit is operating at low stage   system vapor  suction  pressure will be higher than a  standard single stage system or high stage operation   NOTE  Outdoor fan motor will continue to operate for one  minute after compressor shuts off  when outdoor ambient is    R 410A  amp  R 22 Split System AC  amp  HP    greater than or equal to 100  F  This reduces pressure  differential for easier starting on next cycle    NOTE  If unit has not operated within the past 12 hours  or  following a unit power up  upon the next thermostat high   or low stage demand  unit operates for a minimum of 5  minutes in high stage    On models with non communicating systems  with first  stage of cooling  Y1 and O are powered on  and with  second stage of cooling  Y1  Y2  and O are on  For these  systems  with first stage of heating Y1 is on and for second  stage of heating  Y1 and Y2 are on  
97. ists  the appropriate fault code is displayed  Verify the  disconnect is closed and 230v wiring is connected to the  unit     Compressor Voltage Sensing    The control board input terminals labeled VS  and L2 on   CA7        9   CH6  and  CH9 models  see Fig  30  are used  to detect compressor voltage status and alert the user of  potential problems  The control continuously monitors the  high voltage on the run capacitor of the compressor motor   Voltage should be present any time the compressor  contactor is energized and voltage should not be present  when the contactor is de energized     Contactor Shorted Detection  If there is compressor voltage sensed when there is no  demand for compressor operation  the contactor may be    stuck closed or there may be a wiring error  The control will  flash the appropriate fault code     Compressor Thermal Cutout    CA7   CA9    CH6   CH9   If the control senses the compressor voltage after start up  and is then absent for 10 consecutive seconds while cooling    or heating demand exists  the thermal protector is open  The  control de energizes the compressor contactor for 15    R 410A  amp  R 22 Split System AC  amp  HP    minutes  but continues to operate the outdoor fan  The  control Status LED will flash the appropriate code shown in  Table 15  After 15 minutes  with a call for low or high stage  cooling or heating  the compressor contactor is energized  If  the thermal protector has not re set  the outdoor fan is  turned off  If 
98. motor is a dc permanent magnet type motor with the  electronic controls integrated into its rear cover  The control  package includes a small diode bridge  capacitors  and  power switching devices  It converts ac to dc power and  switches the dc power to the motor windings on and off at  various rates to control the motor speed  The speed at  which the motor windings are thus commutated is  determined by a pulse width modulated  PWM  signal which  is received from the control board on the motor control lines     The PWM signal is created by turning a DC signal on and  off once within a given period of time  The signal on time  relative to the signal total period defines the percent of the  PWM  For example  if the period is 5 sec and the control  power is turned on for 1 sec then off  the signal will remain  off for 4 sec before turning on again to start the next cycle   The PWM is called a 20 percent duty cycle signal  If the on  time is increased to 4 sec of the 5 sec period  the PWM is  called an 80 percent duty cycle  The ECM reads the PWM  signal and increases the motor speed linearly from minimum  speed to maximum speed with the percent duty cycle value  of the supplied PWM signal     Outdoor Fan Motor Operation    There are two different types of motors used in the  Communicating 2 stage outdoor units  The  CH6 models  use a PSC type fan motor  and the speed does not change  between high and low speed operation    On  CH9 models  an ECM fan motor is used to achieve  hi
99. mpressor contactor    2  Keep the outdoor fan operating for 15 minutes    3  Display the appropriate fault code  see Table 15     4  After a 15 minute delay  if there is a call for cooling or  heating and LPS or HPS is reset  the appropriate  compressor contactor is energized    5  If LPS or HPS has not closed after a 15 minute delay   the outdoor fan is turned off  If the open switch closes  anytime after the 15 minute delay  then resume  operation with a call for cooling or heating    6  If LPS or HPS trips 3 consecutive cycles  the unit  operation is locked out for 4 hours    7  In the event of a high pressure switch trip or high   pressure lockout  check the refrigerant charge   outdoor fan operation  and outdoor coil  in cooling  for  airflow restrictions  or indoor airflow in heating     42    Specifications subject to change without notice     SERVICE MANUAL    8  In the event of a low pressure switch trip or low   pressure lockout  check the refrigerant charge and  indoor airflow  cooling  and outdoor fan operation and  outdoor coil in heating     Control Fault    If the outdoor unit control board has failed  the control will  flash the appropriate fault code  see Table 15   The control  board should be replaced     Brown Out Protection    If the line voltage is less than 187v for at least 4 seconds   the appropriate compressor contactor and fan relay are  de energized  Compressor and fan operation are not  allowed until voltage is a minimum of 190v  The control will 
100. mpressor oil will be positive  Follow these additional  steps    1  TXV must be cleaned or replaced    2  Drain any trapped oil from accumulator if used     3  Remove and discard liquid line strainer and filter  drier   4  After system is reassembled  install liquid and  suction line R 410A filter driers   NOTE  On heat pumps  install suction line drier between  compressor and accumulator     5  Operate system for 10 hr  Monitor pressure drop  across drier  If pressure drop exceeds 3 psig replace  suction line and liquid line filter driers  Be sure to  purge system with dry nitrogen when replacing filter  driers  If suction line driers must be replaced  retest  pressure drop after additional 10 hours  run time    Continue to monitor pressure drop across suction line  filter drier  After 10 hr of run time  remove suction line  filter drier and replace liquid line filter drier  Never  leave suction line filter drier in system longer than 72  hr  run time     6  Charge system   See unit information plate      A CAUTION    UNIT DAMAGE HAZARD  Failure to follow this caution may result in equipment    damage or improper operation     Only suction line filter driers should be used for  refrigerant and oil clean up  Use of non approved  products could limit system life and void unit warranty        Evacuation    Proper evacuation of the system wil remove  non condensibles and assure a tight  dry system before  charging  The two methods used to evacuate a system are  the deep vacuum m
101. n and the second controls high speed   The capacitors also are similar to those used in standard  single speed units  You have a fan capacitor for the outdoor  fan motor  and a run capacitor for the compressor motor   The control board  start capacitor  and start relay control the  starting of the compressor  Always replace these devices  with the Factory Approved Components     Incoming Power   Incoming power is attached to the two power wire stripped  leads  A ground lug is also provided  Outdoor unit should  always be grounded through the ground lug to the unit  disconnect and from the disconnect to the electrical fuse  box  Failure to do so can cause serious injury or death        Francis Plumbing  amp  Heating   www FrancisPlumbing com   613 224 0041   office francisplumbing com    Specifications subject to change without notice     41    421 08 5400 00    SERVICE MANUAL    e First check that the model plug is correct for the  unit model and size  and that it is installed properly                                                                                                                                   o ES e  U  o  gt  i     8       1 E  a 5                E          v  Te  L     uU    ws             5         5  U o 9 START CAPACITOR  8 6 MOUNTING HOLES     a f            gegen                                              START RELAY  MOUNTING HOLE                                                                                                              je     
102. nal unit size  btuh    e  Suction line equivalent line length  ft      e  Suction line pressure drop from tables  Table 4 and  Table 5      e  Pressure Temperature relationship for refrigerant  used  P T Chart    If system uses a vapor line the same size as vapor service  valve fitting or larger AND the line set equivalent length is 80  feet or less  the pressure drop in vapor line of line set can  be ignored   1  Take suction line temperature at outlet of evaporator  at indoor unit   2  Take suction service valve pressure at OD unit   3  Determine lineset vapor line equivalent length and  tube diameter   4  Determine suction line pressure drop from Table 4   R 410A  or Table 5     22    5  Calculate Pseudo Evaporator Superheat     e Add the suction line pressure drop to the pressure  reading obtained at suction service valve    NOTE  For nominal and larger diameter vapor lines with  standard length linesets  vapor line same size as service  valve fitting size and larger with equivalent length less than  80 ft  the pressure drop can be ignored     use vapor service  valve pressure and evaporator outlet temperature to  calculate superheat    e Determine saturated evaporator temperature from  a refrigerant pressure temperature relationship  chart  PT chart      e Subtract saturated evaporator from evaporator  suction line temperature to obtain evaporator  superheat     o  NE    45   STD    Fig  26     Tube Fitting Geometry    Table 3   Fitting Losses in Equivalent Feet    TUBE 
103. nd a  stationary spiral  Gas enters  an outer opening as one of the  spirals orbits     Nw    3 um    As the spiral continues to orbit   the gas is compressed into an  increasingly smaller pocket     The open passage is sealed off  as gas is drawn into the spiral         AN A    NN             s A  N  NS          NN  5 Ne    Ww Q  4              By the time the gas arrives at  the center port  discharge  pressure has been reached     Actually  during operation  all  six gas passages are in various  stages of compression at all  times  resulting in nearly con   tinuous suction and discharge        A90198  Fig  8     Scroll Compressor Refrigerant Flow    The compressors used in these products are specifically  designed to operate with designated refrigerant and cannot  be interchanged  The compressor is an electrical  as well as  mechanical  device  Exercise extreme caution when  working near compressors  Power should be shut off  if    Francis Plumbing  amp  Heating   www FrancisPlumbing com   613 224 0041   office francisplumbing com 12    Specifications subject to change without notice     SERVICE MANUAL    possible  for most troubleshooting techniques  Refrigerants  present additional safety hazards     A CAUTION    PERSONAL INJURY HAZARD    Failure to follow this caution may result in personal  injury     Wear safety glasses  protective clothing  and gloves  when handling refrigerant     The scroll compressor pumps refrigerant through the  system by the interaction of a st
104. oes  not meet the above requirements  an abbreviated  30 second defrost will occur         Both Quiet Shift and Quiet Shift 2 compressor ON   OFF delays will be included in a forced defrost if  either are enabled     Quiet Shift 2  Communicating models    FAST    1185237  1186140     Quiet Shift 2 is a field selectable defrost mode which may  eliminate occasional noise that could be heard at the start  and finish of the defrost cycle     On a non communicating system  this feature must be  enabled by selecting the 3rd position of the 3 position dip  switch on the outdoor control board  For Communicating  systems  it must be enabled at the wall control  When  activated  the following sequence of operation occurs   Defrost Initiation     The compressor is de energized for 70  seconds  During this 70 second compressor off time  the  reversing valve will be energized  Once the 70 second  compressor off time has been reached  the compressor will  be energized then the outdoor fan will be de energized at  which time the normal defrost cycle begins     Defrost Termination     the outdoor fan will be energized  shortly before the compressor is de energized for 60  seconds  During the compressor 60 second off time  the  reversing valve will be de energized  Once the 60 second  compressor off time has been completed  the compressor  will be energized at which time the system will be in normal  heat mode    Liquid Line Solenoid Accessory   In heat pump long line applications  a liquid l
105. oil        R 410A  amp  R 22 Split System AC  amp  HP    11  Replace filter drier  evacuate system  recharge  and  check for normal systems operation     Compressor Removal and Replacement    Once it is determined that compressor has failed and the  reason established  compressor must be replaced     4  CAUTION    PERSONAL INJURY HAZARD    Failure to follow this caution may result in personal  injury     Turn off all power to unit before proceeding  Wear  safety glasses  protective clothing  and gloves when  handling refrigerant  Acids formed as a result of motor  burnout can cause burns     4  CAUTION    PERSONAL INJURY HAZARD    Failure to follow this caution may result in personal  injury   Wear safety glasses  protective clothing  and gloves  when handling refrigerant and when using brazing  torch    1  Shut off all power to unit    2  Remove and recover all refrigerant from system until  pressure gauges read O psi  Use all service ports   Never open a system under a vacuum to atmosphere   Break vacuum with dry nitrogen holding charge first   Do not exceed 5 psig    3  Disconnect electrical leads from   compressor   Disconnect or remove crankcase heater and remove  compressor hold down bolts    4  Cut compressor from system with tubing cutter  Do  not use brazing torch for compressor removal  Oil  vapor may ignite when compressor is disconnected    5  Scratch matching marks on stubs in old compressor   Make corresponding marks      replacement  compressor    6  Use torch 
106. ompressor does not pump refrigerant  A  clamp on amp meter on common leg shows a very low  current draw  much lower than rated load amp  RLA  value  stamped on compressor nameplate  Because no refrigerant  is being pumped  there is no return gas to cool compressor  motor  It eventually overheats and shuts off on its internal  protection     Noisy Compressor    Noise may be caused by a variety of internal and external  factors  Careful attention to the    type    of noise may help  identify the source  The following are some examples of  abnormal conditions that may create objectionable noise     1  A gurgling sound may indicate a liquid refrigerant  floodback during operation  This could be confirmed if  there is no compressor superheat  A compressor  superheat of    0    degrees would indicate liquid  refrigerant returning to the compressor  Most common  reasons for floodback are  loss of evaporator blower   dirty coils  and improper airflow    2  A rattling noise may indicate loose hardware  Inspect  all unit hardware including the compressor grommets           14    Specifications subject to change without notice     SERVICE MANUAL  3  A straining  hard start  or vibration occurring at start    15     An internal    up but clears quickly after could indicate an off cycle  refrigerant migration issue  Refrigerant migration can  occur when a compressor is off and refrigerant vapor  transfers from other areas of the system  settles into  the compressor as it is attracted to t
107. ong Line Applications Guidelines for special charging  requirements    Heating Check Chart Procedure   To check system operation during heating cycle  refer to the  Tech Label on outdoor unit  This chart indicates whether a  correct relationship exists between system operating  pressure and air temperature entering indoor and outdoor  units  If pressure and temperature do not match on chart   system refrigerant charge may not be correct  Do not use  chart to adjust refrigerant charge    NOTE  When charging is necessary during heating season   charge must be weighed in accordance with unit rating  plate   0 6 oz  ft  of 3 8 in  liquid line above or below 15 ft    respectively    EXAMPLE     To calculate additional charge required for a 25 ft  line set   25 ft    15 ft    10 ft  X 0 6 oz  ft    6 oz  of additional charge     SYSTEM FUNCTIONS AND SEQUENCE  OF OPERATION   CH6   CH9   CS5     The outdoor unit control system has special functions  The  following is an overview of the two stage control functions     Cooling and Heating Operation    The  CA7   CA9   CH6  and  CH9 model utilizes either a  standard 2 stage indoor thermostat or Communication wall  control  With a call for first stage cooling  the outdoor fan   reversing valve  and low stage compressor are energized  If  low stage cannot satisfy cooling demand  high stage  cooling is energized by the second stage of indoor  thermostat or wall control  After second stage is satisfied   the unit returns to low stage operat
108. opens at approximately 65  F coil temperature at liquid line  or remainder of defrost cycle time     5  Turn off power to outdoor unit and reconnect  fan motor lead to OF2 on control board after above  forced defrost cycle    If unit will not defrost     1  Perform the speedup function as described above to  test the defrost function of the circuit board    2  If the unit does not go into defrost after performing the  speed up  check for 24 volts on the T1 terminal  This  terminal powers the defrost circuit  and must be  energized before any defrost function can occur  The  T1 should be energized once the Y terminal is  energized and the pressure switches are closed   Ensure the T1 wire is connected at the contactor  and  that 24 volts is present on the T1 spade terminal    3  If all voltages are present and unit will still not run  defrost  remove thermostat pigtail harness from board  and perform checks directly on input pins with jumper  wires  The pigtail may have a bad connection or be  mis wired    To fully troubleshoot defrost thermostat and control function   FAST   1173636   11779277      1  Turn thermostat to OFF  Shut off all power to outdoor  unit    2  Remove control box cover for access to electrical  components and defrost control board    3  Disconnect defrost thermostat leads from control  board  and connect to ohmmeter  Thermostat leads  are black  insulated wires connected to DFT and R  terminals on control board  Resistance reading may       R 410A  amp  R
109. or low  The air conditioner  low pressure switch in the suction line opens at 50 PSI and  closes at 95 PSI  The high pressure switch opens at 670  PSI and closes at 470 PSI  Both pressure switch settings  are considerably higher than on comparably sized R 22  units  The high and low pressure switches can be identified  by their pink stripe on the switch   s electrical wires    The R 410A two stage heat pump contains a loss of  charge switch in the suction line on the  CH6 and  CH9  and  in the liquid line on  CH6 models which opens at 23 PSI and  closes at 55 PSI  See troubleshooting section for sequence  when    pressure switch trip occurs     Muffler  Accumulator  Reversing Valve  RVS     The R 410A two stage air conditioners and heat pumps  have a compressor discharge line muffler  to dampen sound  pressure pulsations    The R 410A two stage heat pumps have a specifically  designed reversing valve  for R 410A application and an  accumulator for storing excess liquid refrigerant during the  heating mode to prevent damaging flood back     Thermistors  Outdoor Ambient Thermistor    The R 410A two speed air conditioner and heat pump units  have an outdoor ambient air thermistor  The control board  must know the outdoor air temperature so it can activate  various functions  These functions include        e Activating the compressor crankcase heater when  ever the outdoor unit is in the off cycle     R 410A  amp  R 22 Split System AC  amp  HP    e The fan motor speed changes for
110. panel and install fitting  panel in place    12  Sweat inlet of TXV  marked  IN  to liquid line  Avoid  excessive heat which could damage valve    13  Install vapor elbow with equalizer adapter to vapor  line of line set and vapor connection to indoor coil   Adapter has a 1 4 in  male connector for attaching  equalizer tube    14  Connect equalizer tube of TXV to 1 4 in  equalizer  fitting on vapor line adapter  Use backup wrench to  prevent damage to equalizer fitting    15  Proceed with remainder of unit installation     Replacing TXV on Indoor Coil  post 2006        A08083       1  Pump system down to 2 psig and recover refrigerant     2  Remove coil access panel and fitting panel from front  of cabinet     3  Remove TXV support clamp using a 5 16 in  nut  driver  Save the clamp  N coils only      4  Remove TXV using a backup wrench on connections  to prevent damage to tubing     5  Remove equalizer tube from suction line of coil   Note  Some coils may have a mechanical connection   If coil has a braze connection  use file or tubing cutter  to cut brazed equalizer line approximately 2 inches  above suction tube     Specifications subject to change without notice     23    421 08 5400 00    SERVICE MANUAL    6  Remove bulb from vapor tube inside cabinet     7  Install the new TXV using a wrench and backup  wrench to avoid damage to tubing or valve to attach  TXV to distributor     Replacing TXV on an Indoor Coil  pre 2006     8  Reinstall TXV support clamp  removed in item 
111. peration detected then disappears while low stage demand  exists  Possible causes are internal compressor overload trip or start relay  and capacitor held in circuit too long  if installed     Compressor operation detected then disappears while high stage demand  exists  Possible causes are internal compressor overload trip or start relay  and capacitor held in circuit too long  if installed     Compressor voltage sensed when no demand for compressor operation  exists  Contactor may be stuck closed or there is a wiring error   Compressor voltage not sensed when compressor should be starting  Con   tactor may be stuck open or there is a wiring error    Thermal cutout occurs in three consecutive low high stage cycles  Low  stage locked out for 4 hours or until 24v power recycled    Thermal cutout occurs in three consecutive high low stage cycles  High  stage locked out for 4 hours or until 24v power recycled    Low pressure switch trip has occurred during 3 consecutive cycles  Unit  operation locked out for 4 hours or until 24v power recycled    High pressure switch trip has occurred during 3 consecutive cycles  Unit  operation locked out for 4 hours or until 24v power recycled     Sequence  Compressor contactor is de energized and outdoor fan is energized for up to 15 minutes  If demand still exists  control will energize compressor contactor after 15 minute    delay  If fault is cleared  unit will resume operation  If fault still exists  fan shuts off  and error code continue
112. ponents  Suction  line filter drier is used in cases where acid might occur  such  as burnout  Heat pump units must have the drier installed  between the compressor and accumulator only  Remove  after 10 hours of operation  Never leave suction line filter  drier in a system longer than 72 hours  actual  time                                             A05178    Fig  17     Liquid Line Filter Drier   AC                                                             A05227  Fig  18     Liquid Line Filter Drier   HP    421 08 5400 00    SERVICE MANUAL    Accumulator    The accumulator is specifically designed to operate with  R 410A or R 22 respectfully  use only factory authorized  components  Under some light load conditions on indoor  coils  liquid refrigerant is present in suction gas returning to  compressor  The accumulator stores liquid and allows it to  boil off into a vapor so it can be safely returned to  compressor  Since a compressor is designed to pump  refrigerant in its gaseous state  introduction of liquid into it  could cause severe damage or total failure of compressor   The accumulator is a passive device which seldom needs  replacing  Occasionally its internal oil return orifice or bleed  hole may become plugged  Some oil is contained in  refrigerant returning to compressor  It cannot boil off in  accumulator with liquid refrigerant  The bleed hole allows a  small amount of oil and refrigerant to enter the return line  where velocity of refrigerant returns it to
113. ports  All heat  pumps are shipped with an adapter stub tube  This tube  must be installed on the liquid service valve  After  connecting the stub tube to the liquid service valve of a heat    18    Specifications subject to change without notice     SERVICE MANUAL    pump  the valves are ready for brazing  The interconnecting  tubing  line set  can be brazed to the service valves using  industry accepted methods and materials  Consult local  codes     Before brazing the line set to the valves  the belled ends of  the sweat connections on the service valves must be  cleaned so that no brass plating remains on either the inside  or outside of the bell joint  To prevent damage to the valve  and or cap  O  ring  use a wet cloth or other acceptable  heat sinking material on the valve before brazing  To  prevent damage to the unit  use a metal barrier between  brazing area and unit     After the brazing operation and the refrigerant tubing and  evaporator coil have been evacuated  the valve stem can  be turned counterclockwise until back seats  which  releases refrigerant into tubing and evaporator coil  The  system can now be operated     Back seating service valves must be back seated  turned  counterclockwise until seated  before the service port caps  can be removed and hoses of gauge manifold connected  In  this position  refrigerant has access from and through  outdoor and indoor unit    The service valve stem cap is tightened to 20   2 ft Ib  torque and the service port cap
114. pplied insulation tape  See Fig  20 for correct  positioning of sensing bulb    9  Proceed with remainder of unit installation     R 410A  amp  R 22 Split System AC  amp  HP    10 O CLOCK  2 O CLOCK  Pun SENSING BULB         STRAP    P a TUBE    Fig  20     Position of Sensing Bulb   1  Pump system down to 2 psig and recover refrigerant    2  Remove coil access panel and fitting panel from front  of cabinet    3  Remove TXV support clamp using a 5 16 in  nut  driver  Save the clamp    4  Remove R 22 TXV using a backup wrench on flare  connections to prevent damage to tubing    5  Using wire cutters  cut equalizer tube off flush with  vapor tube inside cabinet    6  Remove bulb from vapor tube inside cabinet    7  Braze equalizer stub tube closed  Use protective  barrier as necessary to prevent damage to drain pan    IMPORTANT  Route the equalizer tube of TXV through  suction line connection opening in fitting panel prior to  replacing fitting panel around tubing    8  Install TXV with 3 8 in  copper tubing through small  hole in service panel  Use wrench and backup  wrench  to avoid damage to tubing or valve  to attach  TXV to distributor    9  Reinstall TXV support clamp  removed in item 3     10  Attach TXV bulb to vapor tube inside cabinet  in same  location as original was when removed  using  supplied bulb clamps  nylon or copper   See Fig  20  for correct positioning of sensing bulb    11  Route equalizer tube through suction connection  opening  large hole  in fitting 
115. pproximately 100 180 percent of device ohm rating   12 5 ohm          12 5 22 5 ohm resistance  beige color    If PTC resistance is appreciably less than rating or more  than 200 percent higher than rating  device is defective                 A94006    Fig  4     Capacitors    Cycle Protector    ICP thermostats have anti cycle protection built in to protect  the compressor  Should a non ICP stat be utilized  it is  recommended to add a cycle protector to the system   Solid state cycle protector protects unit compressor by  preventing short cycling  After a system shutdown  cycle  protector provides for a 5   2 minute delay before  compressor restarts  On normal start up  a 5 minute delay    421 08 5400 00    R 410A  amp  R 22 Split System AC  amp  HP    occurs before thermostat closes  After thermostat closes   cycle protector device provides a 3 sec delay     Cycle protector is simple to troubleshoot  Only a voltmeter  capable of reading 24v is needed  Device is in control  circuit  therefore  troubleshooting is safe with control power   24v  on and high voltage power off     With high voltage power off  attach voltmeter leads across  T1 and T3  and set thermostat so that Y terminal is  energized  Make sure all protective devices in series with Y  terminal are closed  Voltmeter should read 24v across T1  and T3  With 24v still applied  move voltmeter leads to T2  and       After 5   2 minutes  voltmeter should read 24v   indicating control is functioning normally  If no time
116. readings while  power is on        Use following formula to calculate capacitance   Capacitance  mfd    2650 X amps  volts    3  Remove any capacitor that shows signs of bulging   dents  or leaking  Do not apply power to a defective  capacitor as it may explode     Sometimes under adverse conditions  a standard run  capacitor in a system is inadequate to start compressor  In  these instances  a start assist device is used to provide an  extra starting boost to compressor motor  This device is  called a positive temperature coefficient  PTC  or start  thermistor  It is a resistor wired in parallel with the run  capacitor  As current flows through the PTC at start up  it  heats up  As PTC heats up  its resistance increases greatly  until it effectively lowers the current through itself to an  extremely low value  This  in effect  removes the PTC from  the circuit    After system shutdown  resistor cools and resistance value  returns to normal until next time system starts  Thermistor  device is adequate for most conditions  however  in systems  where off cycle is short  device cannot fully cool and  becomes less effective as a start device  It is an easy  device to troubleshoot  Shut off all power to system    Check thermistor with ohmmeter as described below  Shut  off all power to unit  Remove        from unit  Wait at least 10  minutes for PTC to cool to ambient temperature     Measure resistance of PTC with ohmmeter    The cold resistance  RT  of any PTC device should be  a
117. refrigerant or a mixture of nitrogen and refrigerant  leaks in  the system can be found with an electronic leak detector  that is capable of detecting specific refrigerants     If system has been operating for some time  first check for a  leak visually  Since refrigerant carries a small quantity of oil   traces of oil at any joint or connection is an indication that  refrigerant is leaking at that point    A simple and inexpensive method of testing for leaks is to  use soap bubbles   See Fig  23   Any solution of water and  soap may be used  Soap solution is applied to all joints and  connections in system  A small pinhole leak is located by  tracing bubbles in soap solution around leak  If the leak is  very small  several minutes may pass before a bubble will    24    Specifications subject to change without notice     SERVICE MANUAL    form  Popular commercial leak detection solutions give  better  longer lasting bubbles and more accurate results  than plain soapy water  The bubble solution must be  removed from the tubing and fittings after checking for leaks  as some solutions may corrode the metal             LEAK  DETECTOR  SOLUTION      95423  Fig  23     Bubble Leak Detection    You may use an electronic leak detector designed for  specific refrigerant to check for leaks   See Fig  22   This  unquestionably is the most efficient and easiest method for  checking leaks  There are various types of electronic leak  detectors  Check with manufacturer of equipment for  sui
118. rge  check unit for leaks  using an electronic leak detector    2  If any leaks are found  remove and reclaim or isolate  charge  pumpdown  if applicable  Make necessary  repairs    3  Evacuate  recharge  and observe unit through 1  complete operating cycle     Specifications subject to change without notice     47    421 08 5400 00    SERVICE MANUAL R 410A  amp  R 22 Split System AC  amp  HP    Final Check Out  After the unit has been operating  the following items should be checked   1  Check that unit operational noise is not excessive due to vibration of component  tubing  panels  etc  If present  isolate    problem and correct     2  Check to be sure caps are installed on service valves and are tight     R 410A REFRIGERANT QUICK REFERENCE GUIDE    R 410A refrigerant operates at 50 70 percent higher pressures than R 22  Be sure that servicing equipment  and replacement components are designed to operate with R 410A refrigerant     R 410A refrigerant cylinders are rose colored   Recovery cylinder service pressure rating must be 400 psig  DOT 4BA400 or DOT      400     R 410A refrigerant systems should be charged with liquid refrigerant  Use a commercial type metering device  in the manifold hose when charging into suction line with compressor operating    Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard   Use hoses with 700 psig service pressure rating    Leak detectors should be designed to detect HFC refrigerant    R 410A ref
119. riate  fault code temporarily     Table 12   Model Plug Information  PIN RESISTANCE    MODEL MODEL PLUG  K   ohms   NUMBER NUMBER  Pins 1   4 Pins 2   3   CH624 HK70EZ041 18 91   CH636 HK70EZ043 18 150   CH648 HK70EZ045 18 220     CH660 HK70EZ047 18 360   CH924 HK70EZ010 5 1 120   CH936 HK70EZ012 5 1 180   CH948 HK70EZ014 5 1 270   CH960 HK70EZ016 11 5 1   CA924 HK70EZ009 5 1 91   CA936 HK70EZO1 1 5 1 150   CA948 HK70EZ013 5 1 220   CA960 HK70EZ015 5 1 360   CA624 HK70EZ040 18 75   CA636 HK70EZ042 18 120   CA648 HK70EZ044 18 180   CA660 HK70EZ046 18 270    Airflow Selections for  CA7   CA9   CH6    CH9 Using Non  Communicating  Thermostats    Airflow Selection for FVM4 Fan Coils for  CA7        9    CH6   CH9 Using Non Communicating Thermostats  The FVM4 provides high  and low stage blower operation  to match the capacities of compressor at high  and  low stage  To select recommended airflow  refer to FVM4  Installation Instructions  The FVMA utilizes an Easy Select  control board that allows the installing technician to select  proper airflows  For adjustments to control board  select  appropriate HP SIZE and CFM ADJUST setting  This fan  coil has an adjustable blower off delay factory set at 90 sec  for high  and low stage blower operation    For other combinations of equipment consult specifications   technical support manuals  or AHRIdirectory org     GENERAL INFORMATION    Defrost    This control offers 5 possible defrost interval times  30  60   90  120 minutes  or AUTO
120. rigerant  as with other HFCs  is only compatible with POE oils    Vacuum pumps will not remove moisture from oil    Do not use liquid line filter driers with rated working pressures less than 600 psig   Do not leave R 410A refrigerant suction line filter driers in line longer than 72 hours   Do not install a suction line filter drier in liquid line    POE oils absorb moisture rapidly  Do not expose oil to atmosphere    POE oils may cause damage to certain plastics and roofing materials    Wrap all filter driers and service valves with wet cloth when brazing    A factory approved liquid line filter drier is required on every unit    Do NOT use an R 22 TXV     If indoor unit is equipped with an R 22 TXV or piston metering device  it must be changed to a hard shutoff  R 410A TXV     Never open system to atmosphere while it is under a vacuum     When system must be opened for service  recover refrigerant  evacuate then break vacuum with dry nitrogen  and replace filter driers  Evacuate to 500 microns prior to recharging     Do not vent R 410A refrigerant into the atmosphere    Do not use capillary tube coils    Observe all warnings  cautions  and bold text    All indoor coils must be installed with a hard shutoff R 410A TXV metering device     3  Check to be sure tools  loose parts  and debris are removed from unit   4  Check to be sure all panels and screws are in place and tight     Francis Plumbing  amp  Heating   www FrancisPlumbing com   613 224 0041   office francisplumbing
121. rly sized and in good shape  and the evaporator coil is clean  He then checks the  superheat and subcooling at the outdoor unit service valves   Taking pressures and temperatures he finds the following       Liquid line pressure   260 psig  e Liquid line temperature   110  F  e  Suction line pressure   60 psig    e Suction line temperature   65  F    Using an R 22 PT relationship  Jason calculates the  subcooling to be approximately 10  F with 30  F superheat   Because the subcooling is correct but the superheat  appears to be high  he is concerned and decides to perform  the Pseudo Evaporator Superheat check     2        a        O U      gt                                                              22 Suction Line Pressure Drop  psig   Total Equivalent Line Length  ft     80 100 125 150 175 200 225 250  11 14 17 20 24 27 31 34  3 4 5 6 7 8 9 10  1 1 2 2 3 3 3 4  1 1 1 1 1 2 2 2  5 7 8 10 12 13 15 17  2 3 3 4 4 5 6 6  1 1 2 2 2 3 3 3  8 10 13 15 18 20 23 25  3 4 5 6 7 8 9 9  2 2 2 3 3 4 5  4 5 7 8 9 11 12 13  2 3 3 4 5 6 7  1 1 1 1 1 1 2 2  6 7 9 10 12 14 16 17  3 3 4 5 6 7 8 9  1 1 1 1 2 2 2 2  7 9 11 13 16 18 20 22  4 4 6 7 8 9 10 11  1 1 2 2 2 2 3 3  5 7 8 10 12 13 15 17  1 2 2 3 3 4 4 5  1 1 1 1 1 1 2 2    Examining the lineset  Jason finds approximately 145 ft of  suction line with 4 long radius elbows  Per Fig  27 and Table  5  each fitting has an equivalent length of 1 4 ft  The total  equivalent length of the suction line is  145     4   1 4      150 ft  Based on T
122. rost thermostat for defects  First   troubleshoot to make sure unit operates properly in heating  and cooling modes  This ensures operational problems are  not attributed to the defrost control board     FAST   1173636   1177927 DEFROST  CONTROL    The FAST   1173636   1177927 defrost control is used in all  Performance heat pump models  Its features include  selectable defrost intervals of 30  60  90 minutes  and  standard defrost speed up capability  This section describes  the sequence of operation and trouble shooting methods for  this control    Cooling Sequence of Operation  FAST   1173636    1177927    On a call for cooling  thermostat makes R O  R Y  and  R G  Circuit R O energizes reversing valve switching it to  cooling position  Circuit R Y sends low voltage through the  safeties and energizes the contactor  which starts the  compressor and energizes the T1 terminal on the circuit  board  This will energize the OF2 fan relay which starts the  outdoor fan motor     When the cycle is complete  R Y is turned off and  compressor and outdoor fan should stop  With ICP  thermostats  the O terminal remains energized in the cooling  mode  If the mode is switched to heat or Off  the valve is  de energized  There is no compressor delay built into this  control    Heating Sequence of Operation  FAST   1173636    On a call for heating  thermostat makes R Y  and R G   Circuit R Y sends low voltage through the safeties and  energizes the contactor  which starts the compressor and
123. s to 9   2 ft Ib torque  The  seating surface of the valve stem has a knife set edge  against which the caps are tightened to attain a  metal to metal seal  If accessory pressure switches are  used  the service valve must be cracked  Then  the  knife set stem cap becomes the primary seal    The service valve cannot be field repaired  therefore  only a  complete valve or valve stem and service port caps are  available for replacement    If the service valve is to be replaced  a metal barrier must be  inserted between the valve and the unit to prevent  damaging the unit exterior from the heat of the brazing  operations     A CAUTION    PERSONAL INJURY HAZARD    Failure to follow this caution may result in personal  injury     Wear safety glasses  protective clothing  and gloves  when handling refrigerant     Pumpdown Procedure    Service valves provide a convenient shutoff valve useful for  certain refrigeration system repairs  System may be  pumped down to make repairs on low side without losing  complete refrigerant charge   1  Attach pressure gauge to suction service valve  gauge port   2  Front seat liquid line valve     3  Start unit in cooling mode  Run until suction pressure  reaches 5 psig  35kPa   Do not allow compressor to  pump to a vacuum     4  Shut unit off  Front seat suction valve           R 410A  amp  R 22 Split System AC  amp  HP    FIELD  SIDE       STEM      SERVICE PORT  MEUSE NERIS  W SCHRADER CORE    SEAT   HT                                             
124. s to flash  Control will attempt re start every 15 minutes  Cycling low voltage    defeats the 15 minute delay     Specifications subject to change without notice     45    421 08 5400 00    SERVICE MANUAL    Wall Contro    RVS Cooling  Heat Stage 3  Heat Cool Stage 1  Heat Cool Stage 2    Fan    24VAC Hot Heating  24VAC Hot Cooling    Dry Contact 1  Dry Contact 2  24VAC Common    Fan Coil    z    511     C    Heat Pump    Wall Control    RVS Cooling  Heat Stage 3  furnace   Heat Cool Stage 1  Heat Cool Stage 2  Fan  24VAC Hot Heating  24VAC Hot Cooling  Dry Contact 1  Dry Contact 2  24VAC Common    R 410A  amp  R 22 Split System AC  amp  HP                        2                  Furnace Heat Pump     lt       il    Humidify T   Humidifier Solenoid  Outdoor Air Temp Valve    Remote Room Sensor    OAT RRS Com    A150001  Fig  33     Wall Control Wiring with 2 Stage Heat Pump   non communicating     Communicating                                                                                                                             Wall Control Furnace or Fan Coil HP         C                Dx        PECETE  Dx   c   gt   Humidifier 9     o 4o   9  a X  A150003    Fig  35     Variable Speed Furnace or Fan Coil Wiring  with Communicating 2 Stage HP   AC    TWO SPEED  AIR CONDITIONER    SINGLE STAGE  FURNACE    TWO STAGE  THERMOSTAT                                                                                                                                               
125. sultant pitted or discolored terminals are reduced  The  plug is oriented to relief slot in terminal box so cover cannot  be secured if wires are not positioned in slot  assuring  correct electrical connection at the compressor  The plug  can be removed by simultaneously pulling while  rocking   plug  However  these plugs can be used only on specific  compressors  The configuration around the fusite terminals  is outlined on the terminal covers  The slot through which  wires of plug are routed is oriented on the bottom and  slightly to the left  The correct plug can be connected easily  to compressor terminals and plug wires can easily be routed  through slot terminal cover    It is strongly recommended to replace the compressor plug  should a compressor fail due to a suspected electrical  failure  At a minimum  inspect plug for proper connection  and good condition on any compressor replacement     Low Voltage Terminals   The low voltage terminal designations  and their description  and function  are used on all split system condensers   W   Energizes first stage supplemental heat through  defrost relay  wht     R   Energizes 24 v power from transformer  red    Y   Energizes contactor for first stage cooling or first stage  heating for heat pumps  yel     O   Energizes reversing valve on heat pumps  orn    C   Common side of transformer  blk      COPELAND SCROLL COMPRESSOR    Scroll Gas Flow    Compression in the scroll is  created by the interaction of  an orbiting spiral a
126. t and remove  switch     4 CAUTION    PERSONAL INJURY HAZARD          Failure to follow this caution may result in personal  injury     Wear safety glasses when using torch  Have  quenching cloth available  Oil vapor in line may ignite  when switch is removed        2  Braze in 1 4 in  flare fitting and replace pressure  switch     Loss of Charge Switch  HP Only     Located on liquid line of heat pump only  the liquid line  pressure switch functions similar to conventional  low pressure switch     Because heat pumps experience very low suction  pressures during normal system operation  a conventional  low pressure switch cannot be installed on suction line   This switch is installed in liquid line instead and acts as  loss of charge protector  The liquid line is the low side of  the system in heating mode  It operates identically to  low pressure switch except it opens at 23        5  psig for  R 410A and 7      5  psig for R 22 and closes at 55      5   psig for R 410A and 22      5  psig for R 22  Two stage  heat pumps have the low pressure switch located on the  suction line  The two stage control board has the capability  to ignore low pressure switch trips during transitional   defrost  operation to avoid nuisance trips  Troubleshooting  and removing this switch is identical to procedures used on  other switches  Observe same safety precautions     Defrost Thermostat    Defrost thermostat signals heat pump that conditions are  right for defrost or that conditions have ch
127. tability  Generally speaking  they are portable  lightweight   and consist of a box with several switches and a probe or  sniffer  Detector is turned on and probe is passed around all  fittings and connections in system  Leak is detected by  either the movement of a pointer on detector dial  a buzzing  sound  or a light    In all instances when a leak is found  system charge must  be recovered and leak repaired before final charging and  operation  After leak testing or leak is repaired  replace  liquid line filter drier  evacuate system  and recharge with  correct refrigerant quantity     Coil Removal  Coils are easy to remove if required for compressor  removal  or to replace coil    1  Shut off all power to unit     2  Recover refrigerant from system through service  valves     3  Break vacuum with nitrogen     4  Remove top cover   See Remove Top Cover in  Cabinet section of the manual      5  Remove screws in base pan to coil grille   6  Remove coil grille from unit     7  Remove screws on corner post holding coil tube  sheet     4  WARNING    FIRE HAZARD    Failure to follow this warning could result in personal  injury or equipment damage     Cut tubing to reduce possibility of personal injury and  fire        8  Use midget tubing cutter to cut liquid and vapor lines  at both sides of coil  Cut in convenient location for  easy reassembly with copper slip couplings    9  Lift coil vertically from basepan and carefully place  aside    10  Reverse procedure to reinstall c
128. tage  units  However  some restrictions may apply to specific  combinations in long line applications  Refer to the Split  System Long Line Applications Guidelines for further  information   The Tennessee Valley Authority  TVA  requires that electric  strip heat have a lockout feature  This is achieved through  Observer   communicating wall control must be used on all  TVA approved units     Model Plug    Each control board contains a model plug  The correct  model plug must be installed in order for the system to  operate properly   See Table 12     The model plug is used to identify the type and size of unit  to the control  On  CH6 models  the model plug is also used  to determine the start sequence timing for each individual  model    On new units  the model and serial numbers are inputted  into the board   s memory at the factory  If a model plug is lost  or missing at initial installation  the unit will operate  according to the information input at the factory and the  appropriate error code will flash temporarily  A FAST Parts  replacement board contains no model and_ serial  information  If the factory control board fails  the model plug  must be transferred from the original board to the  replacement board for the unit to operate    NOTE  The model plug takes priority over factory model  information input at the factory  If the model plug is removed  after initial power up  the unit will operate according to the  last valid model plug installed  and flash the approp
129. the call for cooling or heating continues  the  control will energize the compressor contactor every 15  minutes  If the thermal protector closes   at the next 15  minute interval check  the unit will resume operation    If the thermal cutout trips for three consecutive cycles  then  unit operation is locked out for 4 hours and the appropriate  fault code is displayed     Low or High Contactor Open   No 230V at  Compressor Contactor    CA7        9   CH6    CH9    If the compressor voltage is not sensed when the  compressor should be starting  the appropriate contactor  may be stuck open or there is a wiring error  The control will  flash the appropriate fault code  Check the contactor and  control box wiring     Troubleshooting units for proper switching  between low  amp  high stages    CA7   CA9    CH6   CH9    Check the suction pressures at the service valves  Suction  pressure should be reduced by 3 1096 when switching from  low to high capacity    NOTE  The liquid pressures are very similar between low  and high stage operation  so liquid pressure should not be  used for troubleshooting     Compressor current should increase 20 45  when  switching from low to high stage  The compressor solenoid  when energized in high stage  should measure 24vac     When the compressor is operating in low stage the 24v DC  compressor solenoid coil is de energized  When the  compressor is operating in high stage  the 24v DC solenoid  coil is energized  The solenoid plug harness that is  
130. the pressure drop  Because the  suction line of the lineset was the same size as the vapor  service valve fitting and less than 80 feet  Tom could have  ignored the pressure drop in the suction line and obtained  the evaporator superheat by using the vapor service valve  pressure of 125 psig  saturated temperature   43 F  and the  evaporator outlet temperature of 53  F  The evaporator  superheat is calculated to be  53  F     43  F    10   F     Francis Plumbing  amp  Heating   www FrancisPlumbing com   613 224 0041   office francisplumbing com    Specifications subject to change without notice     29    421 08 5400 00    SERVICE MANUAL    R 410A  amp  R 22 Split System AC  amp  HP    Table 5   R 22 System Suction Pressure Drop    Nominal Line Pressure Suction  Size OD Drop Velocity    Btuh   in    psi 100 ft  Fpm 20  5 8 13 6 2563 3   18000 5 8 4 0 1539 1  3 4 1 5 1025 0   7 8 0 8 769 0   5 8 6 7 2052 1   24000 3 4 2 5 1367 1  7 8 1 3 1026 0   5 8 10 1 2565 2   30000 3 4 3 8 1708 1  7 8 1 9 1282 0   3 4 5 8 2050 1   36000 7 8 2 6 1538 1  1 1 8 0 7 902 0   3 4 7 0 2392 1   42000 7 8 3 5 1795 1  1 1 8 1 0 1053 0   3 4 8 9 2733 2   48000 7 8 4 4 2051 1  11 8 1 2 1203 0   7 8 6 7 2564 1   60000 11 8 1 8 1504 0  13 8 0 7 987 0   Line set application not recommended  Example 2    Jason is servicing a 5 ton R 22 air conditioner with 7 8   suction line  As part of his basic inspection he believes he  has normal airflow because the air filters are clean   ductwork appears to be prope
131. tinue to be displayed until after the short is  removed  Once the short is removed  there is a 5 second  wait before the code is cancelled  The code that is flashing  will finish before going back to sold LED  the control is  shipped with the ODF fan delay defeat NOT active  the  change in status is remembered until toggled to a new  status  A power down   power up sequence will not reset the  status  It may be necessary to do the toggle twice to cycle to  the desired state of defeat   Defrost Hold  in a non communicating system  if the thermostat becomes  satisfied  Y1 or Y1 and Y2  before the defrost cycle is  terminated  the control will    hold    in defrost mode and finish  the defrost cycle on the next call for heat   With Communicating control  defrost hold is not needed in a  Communicating system because the wall control will  complete the defrost cycle before shutting down the system   Forced Defrost  With non communicating control  forced defrost can be  initiated by manually shorting the 2 pin header labeled  FORCED DEFROST  see Fig 30  on the control board for 5  seconds then releasing   With Communicating control  forced defrost is initiated with  the wall control     On all models  during a Forced Defrost     e  f coil temperature is at defrost temperature of  32  F  and outdoor air temperature is below 50  F  a  full defrost sequence will occur     421 08 5400 00    R 410A  amp  R 22 Split System AC  amp  HP    e If coil temperature or outdoor air temperature d
132. to remove stubs from old compressor and  to reinstall them in replacement compressor    7  Use copper couplings to tie compressor back into  system    8  Replace filter drier  evacuate system  recharge  and  check for normal system operation     A CAUTION    UNIT DAMAGE HAZARD    Failure to follow this caution may result in equipment  damage or improper operation     Do not leave system open to atmosphere  Compressor  oil is highly susceptible to moisture absorption        System Clean Up After Burnout    Some compressor electrical failures can cause motor to  burn  When this occurs  by products of burn  which include  sludge  carbon  and acids  contaminate system  Test the oil  for acidity using POE oil acid test to determine burnout  severity  If burnout is severe enough  system must be  cleaned before replacement compressor is installed  The 2  types of motor burnout are classified as mild or severe     Specifications subject to change without notice     25    421 08 5400 00    SERVICE MANUAL    In mild burnout  there is little or no detectable odor   Compressor oil is clear or slightly discolored  An acid test of  compressor oil will be negative  This type of failure is treated  the same as mechanical failure  Liquid line strainer should  be removed and liquid line filter drier replaced   In a severe burnout  there is a strong  pungent  rotten egg  odor  Compressor oil is very dark  Evidence of burning may  be present in tubing connected to compressor  An acid test  of co
133. ubject to change without notice     SERVICE MANUAL R 410A  amp  R 22 Split System AC  amp  HP    OUTDOOR UNIT MODEL NUMBER IDENTIFICATION GUIDE  single phase                                   8  9        n              Example Part Number         Mainline    BRANDING    C   Two stage  communicating   S   Single stage  communicating   A   Air Conditioner         Heat Pump                                 1        24   24 000 BTUH   2 tons  36   36 000 BTUH   3 tons  48   48 000 BTUH   4 tons  60   60 000 BTUH   5 tons         Coil Guard Grille         208 230 1 60  Sales Code  Engineering Revision  Extra Digit    Extra Digit    OUTDOOR UNIT MODEL NUMBER IDENTIFICATION GUIDE  single phase        DigtPoson   t2        4   56   7        9    24 4    KEY    CHARACTERISTIC    NOMINAL EFFICIENCY    NOMINAL CAPACITY    FEATURES    VOLTAGE    Example Part Number  WC    WC   Condensing Unit  A   Air Conditioner       Heat Pump    18   18 000 BTUH   11 tons  24   24 000 BTUH   2 tons  30   30 000 BTUH   2  tons  36   36 000 BTUH   3 tons  42   42 000 BTUH   3  tons  48   48 000 BTUH   4 tons  60   60 000 BTUH   5 tons    A   Standard Grille  G   Coil Guard Grille    K   208 230 1 60  Sales Code  Extra Digit    NOMINAL CAPACITY    REFRIGERANT    FEATURE    VOLTAGE       Specifications subject to change without notice     421 08 5400 00    SERVICE MANUAL  SAFETY CONSIDERATIONS    Installation  service  and repair of these units should be  attempted only by trained service technicians famil
134. y for abnormalities     Before troubleshooting compressor motor  review this  description of compressor motor terminal identification     Single Phase Motors  To identify terminals C  S  and R    1  Turn off all unit power    2  Discharge run and start capacitors to prevent shock   3  Remove all wires from motor terminals   4      Read resistance between all pairs of terminals using  an ohmmeter on 0 10 ohm scale     5  Determine 2 terminals that provide greatest  resistance reading    Through elimination  remaining terminal must be common   C   Greatest resistance between common  C  and another  terminal indicates the start winding because it has more  turns  This terminal is the start  S   The remaining terminal  will be run winding  R    NOTE  If compressor is hot  allow time to cool and internal  line break to reset  There is an internal line break protector  which must be closed     All compressors are equipped with internal motor protection   If motor becomes hot for any reason  protector opens   Compressor should always be allowed to cool and protector  to close before troubleshooting  Always turn off all power to  unit and disconnect leads at compressor terminals before  taking readings    Most common motor failures are due to either an open   grounded  or short circuit  When a compressor fails to start  or run  3 tests can help determine the problem  First  all  possible external causes should be eliminated  such as  overloads  improper voltage  pressure equalization
    
Download Pdf Manuals
 
 
    
Related Search
 Keeprite R4A3 service manual  keeprite appliance repair manual  keeprite heater technical manual  keeprite furnace installation manual  keeprite furnace fix manual  keeprite heat pump manual  keeprite heater technical support  keeprite furnace parts diagram  keeprite warranty lookup canada  keeprite g96vtn installation manual  keeprite appliance repair parts  keeprite furnace fix troubleshooting  keeprite air conditioner parts  keeprite appliance repair tips  keeprite warranty registration canada  keeprite furnace parts list  keeprite appliance repairman tips  keeprite appliance repair online booking  keeprite appliance repair warranty  keeprite tech support canada  keeprite furnace fix warranty  keeprite furnace fix parts  keeprite appliance repairman warranty  keeprite heater repairman phone number  keeprite heater repairman tips  keeprite air conditioner reviews 
    
Related Contents
  TP series  Distance and Time Calculator USER MANUAL - Opti XL  KR7 TYPE - LUMEL SA  Use and Care Manual    Direção Defensiva  GUÍA BÁSICA DEL USUARIO  Black & Decker 494511-00 Instruction Manual  LISTSERV Maestro 2.0 Data Administrator - L    Copyright © All rights reserved. 
   Failed to retrieve file