Home
        important
         Contents
1.    9  Use dry nitrogen to break the vacuum on the refriger   ant lines and indoor coil before removing the recovery  machine  gauges and HCFC 22 refrigerant drum  Re   install pressure tap valve cores into HSXB15 service  valves     10  Install the field provided expansion valve  approved  for use with R 410A refrigerant  in the liquid line at the  indoor coil     Refrigerant Metering Device    HSXB15 units are used in check expansion valve systems  only  See the Lennox Engineering Handbook for approved  TXV match ups and application information     Check expansion valves equipped with Chatleff fittings are  available from Lennox  Refer to the Engineering Hand   book for applicable expansion valves for use with specific  match ups     If you install a check expansion valve with an indoor  coil that includes a fixed orifice  remove the orifice be   fore installing the check expansion valve     See figure 11 for installation of the check expansion valve     Metering Device Installation    EXPANSION VALVE  amp   Wa O RING  See NOTE            1    STRAINER  DISTRIBUTOR  amp     O RING    LIQUID LINE  STUB    NOTE   If necessary  remove R 22 flow control device  fixed  orifice thermal expansion valve  from existing line set before  installing R 410A approved expansion valve and o ring     Figure 11       Manifold Gauge Set    Manifold gauge sets used with systems charged with  R 410A refrigerant must be capable of handling the higher  system operating pressures  The gauges should
2.   upside down  The cylinder will be marked if it is  equipped with a dip tube           This system is charged with R410A refrigerant which oper   ates at much higher pressures than HCFC 22  The expan   sion valve and liquid line filter drier provided with the unit  are approved for use with R 410A  Do not replace them  with components designed for use with HCFC 22  This unit  is NOT approved for use with coils which include metering  orifices or capillary tubes    Factory Charge   Units are factory charged with the amount of R 410A re   frigerant indicated on the unit rating plate  This charge is  based on a matching indoor coil and outdoor coil with 15  feet  4 6 m  line set  For varying lengths of line set  refer to  table 3 for refrigerant charge adjustment     Table 3    Refrigerant Charge per Line Set Lengths  Liquid Line Ounces per 5 feet  grams per 1 52 meter   Set Diameter adjust from 15 ft   4 57m  line set     3 8 in   9 5mm  3 ounces per 5 feet  85 grams per 1 52 me     ter      Add the amount shown if line length is greater than 15     4 57m   sub   tract the amount shown if less than 15           Units Delivered Void of Charge    A IMPORTANT    Mineral oils are not compatible with R 410A  If oil    must be added  it must be a polyol ester oil     The compressor is charged with sufficient polyol  ester oil for approved line set lengths        If the system is void of refrigerant  clean the system us   ing the following procedure    1  Use dry nitrogen to pressuri
3.  1  Record outdoor ambient temperature using a digital  thermometer           2  Attach high pressure gauge set and operate unit for  several minutes to allow system pressures to stabilize    3  Compare stabilized pressures with those provided in  table 5     Normal Operating Pressures     Minor varia   tions in these pressures may be expected due to differ   ences in installations  Significant differences could  mean that the system is not properly charged or that  a problem exists with some component in the system   Pressures higher than those listed indicate that the  system is overcharged  Pressures lower than those  listed indicate that the system is undercharged  A tem   perature pressure chart for R 410A refrigerant is pro   vided in table 6 for your convenience  Verify adjusted  charge using the approach method    4  Use the same digital thermometer you used to check  the outdoor ambient temperature to check the liquid  line temperature    5  The difference between the ambient and liquid tem   peratures should match values given in table 4  If the  values don   t agree with the those in table 4  add refrig   erant to lower the approach temperature  or recover  refrigerant from the system to increase the approach  temperature  Be aware of the R 410A refrigerant cylin   der  It will be light maroon colored  Refrigerant should  be added through the vapor valve in the liquid state     Table 4    Approach Values    Approach Temperature  Model No    Liquid Line   Outdoor Am
4.  2  Parts Arrangement  amp  Unit Dimensions             2  Setting The Unit        0000 0000 00 eee 3  El    tical cemas egw a aaea ty 4  Refrigerant Piping                naana rrara 4  Flushing Existing Line Set  amp  Indoor Coil            7  Refrigerant Metering Device                      9  Manifold Gauge Set            0 0 0 cece eee eee 9  Service Valves         0  cc cece eee n nee 9  Leak  Testing  itv chee nee ued oles BR ed nes 10  EVACUATION  renei eneen i cin dot Saute ENE a Sales 10  StartUp 4 itso ie ae a Redes A AS 11  Refrigerant Charging                 0c cece eee uae 11  System Operation        0  0 0 00  c eee eee 13  Maintenance               006s cece ec ee eee eens 15  Optional Accessories           00 66 cece eee eee 15  Homeowner Information             00000    c eae 15  Thermostat Operation               00 0000 cece 16  Start Up  amp  Performance Check List                16    HSXB15 Outdoor Unit    HSXB15 outdoor units use R 410A HFC refrigerant  This  unit must be installed with a matching indoor coil and line set  as outlined in the Lennox Engineering Handbook  HSXB15  outdoor units are designed for use in expansion valve sys   tems only  They are not designed to be used with other refrig   erant flow control devices  The filter drier is factory installed   The Lennox Engineering Handbook lists indoor TXV kits that  must be ordered separately     Shipping  amp  Packing List    1   Assembled HSXB15 outdoor unit  2   Grommets  for liquid and su
5.  above has  been met  disconnect the manifold hose from the vac   uum pump and connect it to an upright cylinder of  R 410A refrigerant  Open the manifold gauge valves  to break the vacuum from 1 to 2 psig positive pressure  in the line set and indoor unit  Close manifold gauge  valves and shut off the R 410A cylinder and remove  the manifold gauge set     1  Rotate fan to check for frozen bearings or binding     2  Inspect all factory  and field installed wiring for loose  connections     3  After evacuation is complete  open the liquid line and  vapor line service valves to release the refrigerant  charge  contained in outdoor unit  into the system     4  Replace the stem caps and secure finger tight  then  tighten an additional one sixth  1 6  of a turn     5  Check voltage supply at the disconnect switch  The  voltage must be within the range listed on the unit   s  nameplate  If not  do not start the equipment until you  have consulted the power company and the voltage  condition has been corrected     6  Set the thermostat for a high stage cooling demand   Y1 and Y2 demand   Turn on power to the indoor  blower and close the outdoor unit disconnect switch to  start the unit    7  Recheck voltage while the unit is running  Power must  be within range shown on the nameplate     Refrigerant Charging    A IMPORTANT    Some R 410A cylinders are equipped with a dip tube    which allows you to draw liquid refrigerant from the  bottom of the cylinder without turning the cylinder
6.  be installed on exterior of outside wall     OUTSIDE WALL IMPORTANT   Refrigerant  lines must not contact wall  VAPOR LINE LIQUID LINE    WOOD BLOCK  BETWEEN  STUDS    WIRE TIE  INSIDE WALL    STRAP    Reva    SLEEVE    VAPOR LINE WRAPPED    WITH ARMAFLEX   quip WIRE TIE    OUTSIDE WALL    IMPORTANT  WOOD BLOCK    Refrigerant  lines must  not contact  structure     WIRE TIE    A OY SEY EG A SE OT oT N AT SLY ST AIT AS OT SY EY AY PA i    STRAP    ii  m  x  ie  B     a  F  C  C  Sl    CAULK    PVC PIPE FIBERGLASS  INSULATION    SLEEVE       Figure 8    Refrigerant Line Sets  Transition From Vertical To Horizontal    ANCHORED AUTOMOTIVE  HEAVY NYLON MUFFLER TYPE    WIRE TIE HANGER       Strap Liquid    eras  Line To Va  Strap Liquid Line  por Line To Vapor Line    LIQUID LINE LIQUID LINE       METAL VAPOR LINE   WRAPPED METAL VAPOR LINE   WRAPPED  SLEEVE IN ARMAFLEX SLEEVE IN ARMAFLEX    Figure 9       Page 6    504710M 03 06    4 WARNING    Polyol ester  POE  oils used with R 410A refriger   ant absorb moisture very quickly  It is very impor     tant that the refrigerant system be kept closed as  much as possible  DO NOT remove line set caps or  service valve stub caps until you are ready to make  connections     Brazing Connection Procedure  1  Cut ends of the refrigerant lines square  free from  nicks or dents   Debur the ends  The pipe must remain  round  do not pinch end of the line     2  Before making line set connections  use dry nitrogen  to purge the refrigerant pipi
7.  be rated  for use with pressures of 0   800 on the high side and a low  side of 30    vacuum to 250 psi with dampened speed to 500  psi  Gauge hoses must be rated for use at up to 800 psi of  pressure with a 4000 psi burst rating           rvice Valves       The liquid line and vapor line service valves and gauge  ports are used for leak testing  evacuating  charging and  checking charge  Each valve is equipped with a service  port which has a factory installed Schrader valve  A ser   vice port cap protects the Schrader valve from contamina   tion and serves as the primary leak seal     Front Seated Service Valve  Liquid Line    The front seated service valve is shown in figure 12  When  this valve is closed  the service port is open to the line set   Access the service port and open and close valves as de   scribed in the following paragraphs     Front Seated Liquid Line Service Valve     Valve Shown Closed  SERVICE  P    Insert hex wrench here  ea    indoor coil    To outdoor coil  SERVICE     Valve Shown Open     insert hex wrench here    l indoor coil  Service port Is open to    line set when valve is    closed  front seated  To outdoor coil    Figure 12    To Access Schrader Port    1  Remove access panel    2  Remove service port cap with an adjustable wrench    3  Connect gauge to the service port    4  When testing is completed  replace service port cap   Tighten finger tight  then torque per table 1  Page 2     To Open Front Seated Service Valves    1  Remove stem c
8.  screws   16 in   Ib    G   22 1 8  562    28 1 8 718    28 1 8  718    28 1 8  718  MARERE AO   cre  H 2 7 8  73  3 7 8  98  3 7 8  98  3 7 8  98  Compressor bolts   90 in  Ib   J   5 1 2 140    7 1 2 191    7 1 2 191    7 1 2  191  Gauge port seal cap                               Page 2    504710M 03 06          Setting the Unit    Refer to unit dimensions  figure 1  on page 2  for sizing  mounting slab  platforms or supports  Refer to figure 2 for  installation clearances     Installation Clearances    A service access clearance of 30     762 mm  must be maintained in  front of the service access panel  Clearance to one side must be 36      914 mm   Clearance to one of the remaining two sides may be 12      305 mm  and the final side may be 6     152 mm      A clearance of 24     610 mm  must be maintained between two units     48     1219 mm  clearance required on top of unit  Maximum soffit  overhang is 36     914 mm         Figure 2    4 CAUTION    In order to avoid injury  take proper precaution when  lifting heavy objects           4  CAUTION    Physical contact with metal edges and corners    while applying excessive force or rapid motion can  result in personal injury  Be aware of  and use  caution when working near these areas during  installation or while servicing this equipment        Slab Mounting    When installing a unit at grade level  the top of the slab  should be high enough above the grade so that water from  higher ground would not collect around the u
9. 6 9 to  13 8 kPa      Using an Electronic Leak Detector  1  Connect the high pressure hose of the manifold gauge  set to the vapor valve service port   Normally  the high  pressure hose is connected to the liquid line port  how   ever  connecting it to the vapor port helps to protect the  manifold gauge set from damage caused by high pres   sure      2  With both manifold valves closed  connect the cylinder  of R 410A refrigerant  Open the valve on the R 410A  cylinder  vapor only     3  Open the high pressure side of the manifold to allow  R 410A into the line set and indoor unit  Weigh in a  trace amount of    A trace amount is a maximum of 2  ounces  57 g  refrigerant or 3 pounds  31 kPa  pres   sure   Close the valve on the R 410A cylinder and the  valve on the high pressure side of the manifold gauge  set  Disconnect R 410A cylinder     4  Connect a cylinder of dry nitrogen with a pressure reg   ulating valve to the center port of the manifold gauge  set     5  Adjust dry nitrogen pressure to 150 psig  1034 kPa    Open the valve on the high side of the manifold gauge  set in order to pressurize the line set and the indoor  coil           6  After afew minutes  open a refrigerant port to check  that an adequate amountof refrigerant has been add   ed fordetection  refrigerant requirements will vary with  line lengths   Check all joints for leaks  Purge dry nitro   gen and R 410A mixture  Correct any leaks and re   check     A IMPORTANT    Leak detector must be capable of s
10. LENNOX      2006 Lennox Industries Inc   Dallas  Texas  USA       RETAIN THESE INSTRUCTIONS  FOR FUTURE REFERENCE    4  WARNING    Improper installation  adjustment  alteration  ser   vice or maintenance can cause property damage   personal injury or loss of life  Installation and ser   vice must be performed by a qualified installer or  service agency     A IMPORTANT    This unit must be matched with an indoor coil as  specified in Lennox    Engineering Handbook   Coils previously charged with R 22 must be flu   shed     4 WARNING    This product and or the indoor unit it is matched  with may contain fiberglass wool     Disturbing the insulation during installation  main   tenance  or repair will expose you to fiberglass wool  dust  Breathing this may cause lung cancer   Fiber   glass wool is known to the State of California to  cause cancer    Fiberglass wool may also cause respiratory  skin   and eye irritation   To reduce exposure to this substance or for further  information  consult material safety data sheets  available from address shown below  or contact  your supervisor    Lennox Industries Inc     P O  Box 799900  Dallas  TX 75379 9900    03 06    CAAA       Page 1    INSTALLATION  MANUAL    HSXB15 Series Units       CONDENSING UNITS leone    ublications  poe mn Litho U S A     Supersedes 11 05    Table of Contents    HSXB15 Outdoor Unites pinen aera d gaha 1  Shipping  amp  Packing List                  0 0 04  1  General Information               0 0 0 e eee eens
11. ant Line Sets    Valve Field Size  Connections       Recommended Line Set       Model   Liquid   Vapor Liquid Vapor L15  No  Line Line Line Line Line Sets        024 3 8 in  3 4 in  3 8 in  3 4 in  L15 41   030    10 mm     19mm     10mm     19 mm     15 ft    50 ft    036  4 6 m  15m      042 3 8 in  7 8 in  3 8 in  7 8 in  L15 65   048    10mm     22mm     10mm     22 mm  15 ft    50 ft    4 6 m  15 m      060 3 8 in    1 1 8 in    3 8 in  1 1 8 in  Field   10 mm     29mm     10mm     29 mm  Fabricated                            NOTE   Units are designed for line sets of up to 50     15m      Refrigerant Connections   HSXB15 Matched  with New Indoor Coil and Line Set   If an existing indoor coil that was equipped with an  RFCI metering device is being replaced  the liquid line  must also be replaced prior to the installation of the  HSXB15 unit     If refrigerant lines are routed through a wall  seal and iso   late the opening so vibration does not transmit to building     Installing Refrigerant Line   During the installation of any heat pump or a c system  it is  important to properly isolate the refrigerant lines to prevent  unnecessary vibration  Line set contact with the structure   wall  ceiling or floor  causes some objectionable noise  when vibration is translated into sound  As a result  more  energy or vibration can be expected  Closer attention to  line set isolation must be observed  Following are some    To hang line set from joist or rafter   use either metal s
12. ap with an adjustable wrench    2  Use a service wrench with a hex head extension   3 16    for liquid line valve sizes  5 16    for vapor line  valve sizes  to back the stem out counterclockwise as  far as it will go    3  Replace the stem cap  Tighten finger tight  then torque  per table 1  Page 2     To Close Front Seated Service Valves   1  Remove the stem cap with an adjustable wrench     Page 9    HSXB15 SERIES    2  Use a service wrench with a hex head extension   3 16    for liquid line valve sizes  5 16    for vapor line  valve sizes  to turn the stem clockwise to seat the  valve  Tighten it firmly     3  Replace the stem cap  Tighten finger tight  then torque  per table 1  Page 2      ene testn    After the line set has been connected to the indoor and out   door units  the line set connections and indoor unit must be  checked for leaks     4 WARNING    Refrigerant can be harmful if it is inhaled  Refriger     ant must be used and recovered responsibly     Failure to follow this warning may result in personal  injury or death        amp AWARNING        AAWARNING e of explosion  Can cause inju   ry or death  or equipment damage     Never use oxygen to pressurize a re   frigeration or air conditioning system   Oxygen will explode on contact with    oil and could cause personal injury     When using a high pressure gas such  as dry nitrogen to pressurize a refrig   eration or air conditioning system   use a regulator that can control the  pressure down to 1 or 2 psig  
13. bient   F    C     HSXB 15 030 8 1 4 5  5   HSXB 15 036 6  1  3 3   5   HSXB15 042 9 1 5  5    HSXB15 048 8 1 4 5  5   HSXB15 060 12 1 6 7  5     NOTE   For best results  the same electronic  thermometer should be used to check both outdoor  ambient and liquid line temperatures           Table 5  Normal Operating Pressures  Liquid  10 and Vapor   5 psig     Outdoor Coil HSXB15 024 HSXB15 030 HSXB15 036 HSXB15 042 HSXB15 048  Entering Air    HSXB15 060    TES       Page 12    504710M 03 06    R 410A Temperature    F    Pressure  Psig     F Psig   F Psig   F Psig Psig  100 8    63  102 9    64  105 0    65  107 1    66  109 2    67  1114    68  113 6    69  115 8    70  118 0    71  120 3    72  122 6    73  125 0    74  127 3    75  129 7    76  132 2    77  134 6    78  137 1    79  139 6    80  142 2    81  144 8    82  147 4    83  150 1    84  54   152 8 47   8    85  57 161 0 88 266 0 119 412 2 150 608 1  61 i 92   i  2 93                                        a       a             a          1  2  3  4  45  6  7  8  9       OEN       oa  ae        oa  a       oO  N       a  oO          172 6 282 3 123   434 5    154   637 5    6                                  175 4 286 5 124   440 2    155   645 0       System Operation    The outdoor unit and indoor blower cycle on demand from  the room thermostat  When the thermostat blower switch  is in the ON position  the indoor blower operates continu   ously     High Pressure Switch    HSXB15 units are equipped with a high pres
14. cedure below  see figure 10     If the existing outdoor unit is not equipped with  shut off valves  or if the unit is not operational  AND you plan to use the existing R 22 refrigerant   to flush the system    e Disconnect all power to the existing outdoor unit   e Connect to the existing unit  a clean recovery cyl   inder and the recovery machine according to the  instructions provided with the recovery machine   e Remove all R 22 refrigerant from the existing sys   tem  Check gauges after shutdown to confirm that  the entire system is completely void of refrigerant   e Disconnect the liquid and vapor lines from the ex    isting outdoor unit     Page 7    HSXB15 SERIES    Flushing Connections    Inverted R 22 Cylinder   Contains clean R 22 to  be used for flushing     z    Low High  Pressure Pressure       bo ee HSXB15    Vapor Line UNIT    EXISTING VAPOR LINE Service Valve    a m  d H  GAUGE MANIFOLD       m  D m        EXISTING  INDOOR COIL       EXISTING LIQUID LINE Liquid Line  Service Valve                Tank Return    NOTE   The inverted R 22 cylinder  must contain at least the same  Inlet amount of refrigerant as was recov     Discharge ered from the existing system        RECOVERY CYLINDER RECOVERY MACHINE    Figure 10    A IMPORTANT    The line set and indoor coil must be flushed with    If the existing outdoor unit is equipped with  manual shut off valves AND you plan to use NEW  R 22 refrigerant to flush the system      e Start the existing R 22 system in the coo
15. ction lines   1   Bushing  for low voltage wiring     Check equipment for shipping damage  If you find any  damage  immediately contact the last carrier     504 710M    TL    COMPRESSOR SYSTEM OPERATION  RUN MONITORS CONTACTOR  CAPACITOR VAPOR LINE       GROUND  LUG                                                       VAPOR VALVE  AND GAUGE PORT             COMPRESSOR   LIQUID LINE  POWER SERVICE VALVE   TERMINALS AND GAUGE     PORT                                     J FILTER DRIER          x n    a    DISCHARGE     LOW PRESSURE HIGH PRESSURE O  INLET AIR                            LINE SWITCH SWITCH    PARTS ARRANGEMENT TOP VIEW  ELECTRICAL INLETS    C  a B p a      VAPOR LINE INLET Bd scharce AIR    LIQUID LINE INLET                                                                   ACCESS VIEW SIDE VIEW  Figure 1  a HSXB15 Model General Information   seis Weenies 2 Boe These instructions are intended as a general guide and do  A   27 718  708    30 7 8  784    34 7 8  886    40 7 8  1038  not supersede local codes in any way  Consult authorities  B   25 7 8 657    32 1 8 816    32 1 8  816    32 1 8  816  who have jurisdiction before installation   c   29 7 8 759    34 1 16  865    34 1 16  865    34 1 16  865  Table 1  D   12 1 4  311    12 3 4  324    13 3 4  349    19 3 4  602  Torque Requirements  E   22 7 16  570   26 5 8  676    26 5 8  676    26 5 8  676  Recommended Torque  F   14 7116  367   18 5 8  473    18 5 8  473    18 5 8  473  peice valve cap   Sheet metal
16. e Valves      Fully Opened  J Caps Tight        Voltage With Compressor Operating    Vapor Pressure Refrigerant Charge Checked  d  Outdoor Fan Checked  J  g Thermostat  Calibrated     Properly Set     Level  J                   Page 16    504710M 03 06    
17. ensing HFC re   frigerant     Evacuation    Evacuating the system of noncondensables is critical for  proper operation of the unit  Noncondensables are defined  as any gas that will not condense under temperatures and  pressures present during operation of an air conditioning  system  Noncondensables and water vapor combine with  refrigerant to produce substances that corrode copper pip   ing and compressor parts     A IMPORTANT    Use a thermocouple or thermistor electronic vacuum  gauge that is calibrated in microns  Use an instrument  that reads from 50 microns to at least 23 000 microns           1  Connect manifold gauge set to the service valve ports   e low pressure gauge to vapor line service valve  e high pressure gauge to liquid line service valve  2  Close manifold gauge set valves  Connect the center  manifold hose to an upright cylinder of R 410A    3  Connect micron gauge     4  Connect the vacuum pump  with vacuum gauge  to  the center port of the manifold gauge set    5  Open both manifold valves and start the vacuum  pump    6  Evacuate the line set and indoor unit to an absolute  pressure of 23 000 microns  29 01 inches of mercu   ry   During the early stages of evacuation  it is desir   able to close the manifold gauge valve at least once to  determine if there is a rapid rise in absolute pressure   A rapid rise in pressure indicates a relatively large  leak  If this occurs  repeat the leak testing procedure     NOTE   The term absolute pressure means the t
18. er  manifold hose to an upright cylinder of R 410A    2  Set the room thermostat to call for heat  This will  create the necessary load for properly charging the  system in the cooling cycle    3  Use a digital thermometer to record the outdoor ambi   ent temperature    4  When the heating demand has been satisfied  switch  the thermostat to cooling mode with a set point of 68  F   20  C   When pressures have stabilized  use a digital  thermometer to record the liquid line temperature    5  The outdoor temperature will determine which charg   ing method to use  Proceed with the appropriate  charging procedure     Charge Using the Weigh in Method      Outdoor Temperature  lt  65  F  18  C   If the system is void of refrigerant  or if the outdoor ambient  temperature is cool  the refrigerant charge should be  weighed into the unit  Do this after any leaks have been re   paired    1  Recover the refrigerant from the unit    2  Conduct a leak check  then evacuate as previously   outlined    3  Weigh in the unit nameplate charge   If weighing facilities are not available or if you are charging  the unit during warm weather  follow one of the other pro   cedures outlined below   Charge Using the Approach Method      Outdoor Temperature  gt  65  F  18  C   The following procedure is intended as a general guide and  is for use on expansion valve systems only  For best re   sults  indoor temperature should be 70  F  21  C  to 80  F   26  C   Monitor system pressures while charging    
19. h is open and requires manual reset   5 Open circuit in compressor supply wiring or connections   6 Unusually long compressor protector reset time due to extreme ambient temperature   7 Compressor windings are damaged     Open Start Circuit   Current   1 Run capacitor has failed   only in run circuit 2 Open circuit in compressor start wiring or connections   3 Compressor start winding is damaged     Open Run Circuit   Current   1 Open circuit in compressor start wiring or connections   only in start circuit 2 Compressor start winding is damaged    Welded Contactor   Com    1 Compressor contactor failed to open    pressor always runs 2 Thermostat demand signal not connected to module     Low Voltage   Control circuit   1 Control circuit transformer is overloaded   lt  17VAC 2 Low line voltage  contact utility if voltage at disconnect is low        Flash code number corresponds to a number of LED flashes  followed by a pause  and then repeated   TRIP and ALERT LEDs flashing at the same time indicates that the control circuit voltage is too low for operation     Reset ALERT flash code by removing 24VAC power from monitor  Last ALERT flash code will display for 1 minute after monitor is powered on     504710M 03 06       Page 14    Maintenance l    AWARNING    Electric shock hazard  Can cause inju   ry or death  Before attempting to per   form any service or maintenance  turn       ly the electrical power to unit OFF at dis   W connect switch es   Unit may have  multiple power su
20. his instruction     NOTE   Outdoor fan motor is prelubricated and  sealed  No further lubrication is needed     Optional Accessories    Refer to the Engineering Handbook for optional accesso   ries that may apply to this unit  The following may or may  not apply       Compressor crankcase heater      Mounting bases        Start kit      Timed off control      Freezestat      Low ambient kit      Low ambient cut off kit        SignatureStat    room thermostat    Homeowner Information   Maintenance    In order to ensure peak performance  your system must be  properly maintained  Clogged filters and blocked airflow  prevent your unit from operating at its most efficient level   1  Ask your Lennox dealer to show you where your indoor  unit s filter is located  It will be either at the indoor unit   installed internal or external to the cabinet  or behind  a return air grille in the wall or ceiling  Check the filter  monthly and clean or replace it as needed     2  Disposable filters should be replaced with a filter of the  same type and size     NOTE   If you are unsure about the filter required for  your system  call your Lennox dealer for assistance     A IMPORTANT    Turn off electrical power to the unit at the    disconnect switch before performing any  maintenance  The unit may have multiple power  supplies        3  Many indoor units are equipped with reusable foam fil   ters  Clean foam filters with a mild soap and water  solution  rinse thoroughly  allow filter to dry com
21. ling mode  and close the liquid line valve     at least the same amount of clean refrigerant that  previously charged the system  Check the charge    e Pump all of the existing R 22 refrigerant back into  the outdoor unit   It may be necessary to bypass  the low pressure switches to ensure complete re   frigerant evacuation     e When the low side system pressures reach 0 psig   close the vapor line valve    e Disconnect all power to the existing outdoor unit   Check gauges after shutdown to confirm that the  valves are not allowing refrigerant to flow back into  the low side of the system    e Disconnect the liquid and vapor lines from the ex   isting outdoor unit    2  Remove the existing outdoor unit  Set the new R 410A  unit and follow the brazing connection procedure  which begins on the previous page to make line set  connections  DO NOT install the expansion valve at  this time  Make low voltage and line voltage connec   tions to the new outdoor unit  DO NOT turn on power  to the unit or open the outdoor unit service valves  at this time       Remove the existing refrigerant flow control orifice or  thermal expansion valve before continuing with flush   ing procedures  The existing devices are not approved  for use with R 410A refrigerant and may prevent prop   er flushing  Useafield provided fitting to reconnect the  lines     Page 8    504710M 03 06       in the flushing cylinder before proceeding       Remove the pressure tap valve cores from the    HSXB15 unit   s 
22. mode to maintain   predetermined comfort settings    Temperature Indicator   The temperature indicator displays the actual room   temperature    Programmable Thermostats   Your Lennox system may be controlled by a   programmable thermostat  These thermostats provide the   added feature of programmable time of day setpoints for   both heating and cooling  Refer to the user   s information   manual provided with your thermostat for detailed pro    gramming and operation details    Preservice Check   If your system fails to operate  check the following before   calling for service    e Make sure all electrical disconnect switches are ON    e Make sure the room thermostat Temperature Selector  and System Switch  Heat  Cool  Auto  are properly  set    e Check for and replace any blown fuses  or reset any  tripped circuit breakers    e Make sure unit access panels are in place    e Make sure air filter is clean     e Write down the unit model number and have it handy  before calling           Electrical Connections Tight   J  Indoor Blower RPM  Discharge Pressure    S P  Drop Over Indoor  Dry     Job Name Job no  Date  Job Location City State  Installer City State  Unit Model No  Serial No  Service Technician  Nameplate Voltage   Rated Load Ampacity  Amps    Maximum Fuse or Circuit Breaker Compressor Outdoor Fan    Indoor Filter clean           Supply Voltage  Unit Off   Outdoor Coil Entering Air Temp           Refrigerant Lines    Leak Checked  Properly Insulated   _        Servic
23. n to the Manifold Gauge Set section           A IMPORTANT    If this unit is being matched with an approved line  set or indoor coil which was previously charged  with mineral oil  or if it is being matched with a coil  which was manufactured before January of 1999   the coil and line set must be flushed prior to instal   lation  Take care to empty all existing traps  Polyol  ester  POE  oils are used in Lennox units charged  with R 410A refrigerant  Residual mineral oil can  act as an insulator  preventing proper heat trans   fer  It can also clog the expansion device  and re   duce the system performance and capacity   Failure to properly flush the system per the in   structions below will void the warranty     A IMPORTANT    The Environmental Protection Agency  EPA  pro   hibits the intentional venting of HFC refrigerants  during maintenance  service  repair and disposal of  appliance  Approved methods of recovery  recycl   ing or reclaiming must be followed     4  CAUTION    This procedure should not be performed on sys   tems which contain contaminants  Example  com   pressor burn out         Required Equipment   You will need the following equipment in order to flush the  existing line set and indoor coil  two clean HCFC 22 recov   ery bottles  an oilless recovery machine with a pump down  feature  and two sets of gauges  one for use with HCFC 22  and one for use with the R 410A      Flushing Procedure  1  Remove existing HCFC 22 refrigerant using the ap   propriate pro
24. ng  This will help to prevent  oxidation and the introduction of moisture into the sys   tem     3  Wrap a wet cloth around the valve body and copper  tube stub to protect it from heat damage during braz   ing  Wrap another wet cloth underneath the valve body  to protect the base paint     NOTE   The tube end must stay bottomed in the fitting  during final assembly to ensure proper seating  seal   ing and rigidity    4  Install the field provided thermal expansion valve  ap   proved for use with R 410A refrigerant  in the liquid  line at the indoor coil     5  Use silver alloy brazing rods  5 or 6 percent minimum  silver alloy for copper to copper brazing or 45 percent  silver alloy for copper to brass or copper to steel  brazing  which are rated for use with R 410A refriger   ant  Wrap a wet cloth around the valve body and the  copper tube stub  Remove light maroon washers from  service valves and shield light maroon stickers in order  to protect them during brazing  Braze the line set to the  service valve           Flushing Existing Line Set  amp  Indoor Coil    AWARNING    Danger of fire  Bleeding the refriger   ant charge from only the high side  may result in the low side shell and    ba suction tubing being pressurized  Ap   Pig plication of a brazing torch while  pressurized may result in ignition of  the refrigerant and oil mixture   check  the high and low pressures before un    brazing     NOTE   If the indoor unit line and set is new  skip this sec   tion and go o
25. nit  See figure  3  Slab may be level or have a slope tolerance away from  the building of not more than 2 degrees or 2 inches per 5  feet  51 mm per 1524 mm      Slab Mounting  INSTALL UNIT LEVEL OR   IF ON A SLOPE  MAINTAIN  SLOPE TOLERANCE OF 2 DISCHARGE AIR  DEGREES  OR 2 INCHES  PER 5 FEET  51 MMPER  1 5 MI  AWAY FROM  BUILDING STRUCTURE     BUILDING  STRUCTURE    NS    MOUNTING  SLAB          HHHHHHH I    GROUND LEVEL      Figure 3    Roof Mounting   Install unit at a minimum of 4 inches above surface of the  roof  Care must be taken to ensure weight of unit is proper   ly distributed over roof joists and rafters  Either redwood or  steel supports are recommended     Page 3    HSXB15 SERIES    Electrical l    In the U S A   wiring must conform with current local codes  and the current National Electric Code  NEC   In Canada   wiring must conform with current local codes and the cur   rent Canadian Electrical Code  CEC     Refer to the furnace or blower coil installation instructions  for additional wiring application diagrams and refer to unit  nameplate for minimum circuit ampacity and maximum  overcurrent protection size     A WARNING    Electric Shock Hazard  Can cause in   jury or death    Unit must be grounded in accordance  with national and local codes     Line voltage is present at all compo     nents on units with single pole con     tactors  even when unit is not in op   eration     Unit may have multiple power sup   plies  Disconnect all remote electric  powe
26. onnection of the mod   ule     Alert LED  yellow    communicates an abnormal system  condition through a unique flash code  The alert LED will  flash a number of times consecutively  pause and then re   peat the process  The number of consecutive flashes  de   fined as the Flash Code  correlates to a particular abnor   mal condition    Trip LED  red    indicates there is a demand signal from  the thermostat but no current to the compressor is de   tected by the module     Flash code number corresponds to a number of LED  flashes  followed by a pause  and then repeated    TRIP and ALERT LEDs flashing at the same time indicates  that the control circuit voltage is too low for operation   Reset ALERT flash code by removing 24VAC power from  monitor  Last ALERT flash code will display for 1 minute af   ter monitor is powered on     Page 13    HSXB15 SERIES    Table 7  Status LED Troubleshooting    Green    Power     Red    Trip       Yellow    Alert     Flash Code 1    Yellow    Alert     Flash Code 2    Yellow    Alert     Flash Code 3    Yellow    Alert     Flash Code 4    Yellow    Alert     Flash Code 5    Yellow    Alert     Flash Code 6    Yellow    Alert     Flash Code 7    Yellow    Alert     Flash Code 8    Yellow    Alert     Flash Code 9    Module has power  Supply voltage is present at module terminals     Thermostat demand signal   1 Compressor protector is open    Y1 is present  but the com    2 Outdoor unit power disconnect is open    pressor is not running  3 Comp
27. ons  If indoor unit is not equipped with blower relay  It must  be field provided and installed  P 8 3251 or equivalent      Figure 4    Outdoor Unit Field Wiring Diagram       B4  OUTDOOR FAN GROUND  LEADLESS LUG  De CAPET SYSTEM   COMPRESSOR    CAPACITOR OPERATION 7  5 HIGH  MONITOR CONTACTOR L2    L1  B4  OUTDOOR FAN                            BLACK  COMMON cl2    ORANGE  RUN DUAL  PURPLE  CAPACITOR    208 230 60  I          CAPACITOR CHECHA                      ANNOTE   FOR USE WITH COPPER CONDUCTORS  A WARNING   ONLY REFER TO UNIT RATING ELECTRIC SHOCK HAZARD CAN CAUSE INJURY  PLATE FOR MINIMUM CIRCUIT OR DEATH  UNIT MUST BE GROUNDED IN  AMPACITY AND MAXIMUM OVER  ACCORDANCE WITH NATIONAL AND LOCAL CODES   CURRENT PROTECTION SIZE LINE VOLTAGE FIELD INSTALLED    Figure 5    Refrigerant Piping    If the HSXB15 unit is being installed with a new indoor coil  and line set  the connections should be made as outlined in  this section  If an existing line set and or indoor coil  used  with mineral oil  is going to be used to complete the  HSXB15 system  refer to the following section which in   cludes flushing procedures     Page 4    504710M 03 06    Field refrigerant piping consists of liquid and vapor lines  from the outdoor unit  sweat connections  to the indoor coil   flare or sweat connections   Use Lennox L15  sweat  non   flare  series line sets as shown in table 2 or use field fabri   cated refrigerant lines  Valve sizes are also listed in table 2     Table 2  Refriger
28. otal  actual pressure within a given volume or system   above the absolute zero of pressure  Absolute pres   sure in a vacuum is equal to atmospheric pressure mi   nus vacuum pressure    7  When the absolute pressure reaches 23 000 microns   29 01 inches of mercury   close the manifold gauge  valves  turn off the vacuum pump and disconnect the  manifold gauge center port hose from vacuum pump   Attach the manifold center port hose to a dry nitrogen  cylinder with pressure regulator set to 150 psig  1034  kPa  and purge the hose  Open the manifold gauge  valves to break the vacuum in the line set and indoor  unit  Close the manifold gauge valves     Page 10    504710M 03 06    4 WARNING    Danger of Equipment Damage  Avoid deep vacu   um operation  Do not use compressors to evacu     ate a system  Extremely low vacuums can cause  internal arcing and compressor failure  Damage  caused by deep vacuum operation will void war   ranty     8  Shut off the dry nitrogen cylinder and remove the man   ifold gauge hose from the cylinder  Open the manifold  gauge valves to release the dry nitrogen from the line  set and indoor unit     9  Reconnect the manifold gauge to the vacuum pump   turn the pump on  and continue to evacuate the line set  and indoor unit until the absolute pressure does not  rise above 500 microns  29 9 inches of mercury  within  a 20 minute period after shutting off the vacuum pump  and closing the manifold gauge valves     10  When the absolute pressure requirement
29. pletely  before it is returned to the unit or grille     NOTE   The filter and all access panels must be in  place any time the unit is in operation    4  Some systems are equipped with an electronic air  cleaner  designed to remove the majority of airborne  particles from the air passing through the cleaner  If  your system is so equipped  ask your dealer for main   tenance instructions     5  Inspect and clean indoor coil  The indoor evaporator  coil is equipped with a drain pan to collect condensate  formed as your system removes humidity from the in   side air  Have your dealer show you the location of the  drain line and how to check for obstructions   This  would also apply to an auxiliary drain  if installed      A IMPORTANT    Sprinklers and soaker hoses should not be installed  where they could cause prolonged exposure to the    outdoor unit by treated water  Prolonged exposure  of the unit to treated water  i e   sprinkler systems   soakers  waste water  etc  will corrode the surface of  steel and aluminum parts and diminish performance  and longevity of the unit        6  Inspect and clean outdoor coil     e Make sure no obstructions restrict airflow to the  outdoor unit  Leaves  trash or shrubs crowding the  unit cause the outdoor unit to work harder and use  more energy  Keep shrubbery trimmed away from  the unit and periodically check for debris which  collects around the unit    e The outdoor coil may require frequent cleaning   depending on environmental condi
30. pplies        Before the start of each heating and cooling season  the  following service checks should be performed by a quali   fied service technician  First  turn off electrical power to  the unit prior to performing unit maintenance    e Inspect and clean the outdoor and indoor coils  The  outdoor coil may be flushed with a water hose   NOTE   It may be necessary to flush the outdoor coil  more frequently if it is exposed to substances which  are corrosive or which block airflow across the coil   e g   pet urine  cottonwood seeds  etc     e Visually inspect the refrigerant lines and coils for leaks    e Check wiring for loose connections    e Check voltage at the indoor and outdoor units  with  units operating       Check the amperage draw at the outdoor fan motor   compressor  and indoor blower motor  Values should  be compared with those given on unit nameplate    e Check  clean  or replace  indoor unit filters      Check the refrigerant charge and gauge the system  pressures    e Check the condensate drain line for free and unob   structed flow  clean  if necessary    e Adjust blower speed for cooling  Measure the pressure  drop over the coil to determine the correct blower CFM   Refer to the unit information service manual for pressure  drop tables and procedure    e Check drive belt for wear and proper tension    NOTE   If owner reports insufficient cooling  the unit    should be gauged and refrigerant charge checked  Re   fer to section on refrigerant charging in t
31. r supplies before opening ac   cess panel     1  Install line voltage power supply to unit from a properly  sized disconnect switch     2  Ground unit at unit disconnect switch or to an earth  ground     NOTES   e Connect conduit to the contro  box using a proper  conduit fitting    e Units are approved for use only with copper con   ductors    e 24V  Class II circuit connections are made in the  low voltage junction box  Refer to figure 5 for field  wiring diagram    e A complete unit wiring diagram is located inside  the unit   s front access panel     NOTE   For proper voltages  select thermostat wire  gauge per the following chart     Wire run length  less than 100     30m   more than 100     30m   3  Install room thermostat  ordered separately  on an in   side wall approximately in the center of the conditioned  area and 5 feet  1 5 m  from the floor  It should not be    installed on an outside wall or where it can be effected  by sunlight  drafts or vibrations     Insulation type       color coded  temperature  rating 35  C minimum                      4  Install low voltage wiring from outdoor to indoor unit  and from thermostat to indoor unit  See figure 4        Typical Field Low Voltage Wiring Diagram  Outdoor Unit    Thermostat      v   heat Cw   Y1 Outdoor      cooling     Unit    G   indoor blower   G j    common    Indoor Unit   R  System  Operation  Monitor             C Outdoor  Unit             Ne    NOTE   see unit wiring diagram for power supply connec   ti
32. ressor circuit breaker or fuse s  is open   4 Broken wire or connector is not making contact   5 Low pressure switch open if present in the system   6 Compressor contactor has failed to close     Long Run Time   Compres    1 Low refrigerant charge   sor is running extremely long   2 Evaporator blower is not running   run cycles 3 Evaporator coil is frozen   4 Faulty metering device   5 Condenser coil is dirty     Liquid line restriction  filter drier blocked if present   7 Thermostat is malfunctioning     System Pressure Trip   Dis    1 High head pressure   charge or suction pressure   2 Condenser coil poor air circulation  dirty  blocked  damaged    out of limits or 3 Condenser fan is not running   compressor overloaded 4 Return air duct has substantial leakage   5 If low pressure switch is present  check Flash Code 1 information     Short Cycling   Compressor   1 Thermostat demand signal is intermittent    is running only briefly 2 Time delay relay or control board is defective   3 If high pressure switch is present  check Flash Code 2 information   4 If low pressure switch is present  check Flash Code 1 information     Locked Rotor 1 Run capacitor has failed   2 Low line voltage  contact utility if voltage at disconnect is low    3 Excessive liquid refrigerant in the compressor   4 Compressor bearings are seized     Open Circuit 1 Outdoor unit power disconnect is open   2 Unit circuit breaker or fuse s  is open   3 Unit contactor has failed to close   4 High pressure switc
33. service valves  Connect an HCFC 22  cylinder with clean refrigerant to the vapor service  valve  Connect the HCFC 22 gauge set to the liquid  line valve and connect a recovery machine with an  empty recovery tank to the gauge set       Set the recovery machine for liquid recovery and start    the recovery machine  Open the gauge set valves to  allow the recovery machine to pull a vacuum on the ex   isting system line set and indoor coil       Invert the cylinder of clean HCFC 22 and open its    valve to allow liquid refrigerant to flow into the system  through the vapor line valve  Allow the refrigerant to  pass from the cylinder and through the line set and the  indoor coil before it enters the recovery machine       After all of the liquid refrigerant has been recovered     switch the recovery machine to vapor recovery so that  all of the HCFC 22 vapor is recovered  Allow the re   covery machine to pull a vacuum on the system     NOTE  A single system flush should remove ail of the  mineral oil from the existing refrigerant lines and in   door coil  A second flushing may be done  using clean  refrigerant  if insufficient amounts of mineral oil were    removed during the first flush  Each time the system  is flushed  you must allow the recovery machine  to pull a vacuum on the system at the end of the  procedure     8  Close the valve on the inverted HCFC 22 drum and  the gauge set valves  Pump the remaining refrigerant  out of the recovery machine and turn the machine off  
34. sure switch  that is located in the liquid line of the compressor  The  switch  SPST  manual reset  normally closed  removes  power from the compressor when discharge pressure  rises above factory setting at 640   10 psi     Low Pressure Switch    HSXB15 units are also equipped with a low pressure  switch that is located in the vapor line of the compressor   The switch  SPST  auto reset  normally closed  removes  power from the compressor when vapor line pressure  drops below factory setting at 40   5 psi        Filter Drier   A filter drier is factory installed with each HSXB15 unit   This filter drier is installed to ensure a clean  mois   ture free system  A replacement filter drier is available as  Lennox part no  37L5201     System Operation Monitor   The diagnostic indicator detects the most common fault  conditions in the air conditioning system  When an abnor   mal condition is detected  the module communicates the  specific condition through its ALERT and TRIP lights  The  module is capable of detecting both mechanical and elec   trical system problems  See figure 13 for the system op   eration monitor     A IMPORTANT    This monitor does not provide safety protection   The monitor is a monitoring device only and cannot  control or shut down other devices    System Operation Monitor          Figure 13    LED Functions  See table 7 for LED troubleshooting diagnostic codes     Power LED  green    indicates voltage within the range of  19 28VAC is present at the power c
35. tions   Clean  the outdoor coils with an unpressurized water  hose to remove surface contaminants and debris     Page 15    HSXB815 SERIES    e If necessary  clean the outdoor coil more frequent   ly  especially if it is exposed to substances which  are corrosive or which block airflow across the coil   ie  pet urine  cottonwood seeds  etc      Thermostat Operation       Thermostat operations vary from one thermostat to anoth   er  The following provides general operation procedures   Refer to the user   s information manual provided with your  thermostat for specific operation details     Temperature Setting Levers   Set the lever or dial to the desired temperature setpoints  for both heating and cooling  Avoid frequent temperature  adjustment  turning the unit off   then back on   before  pressures can equalize will put unusual stress on the unit   s  compressor     Fan Switch   In AUTO or INT  intermittent  mode  the blower operates  only when the thermostat calls for heating or cooling  This  mode is generally preferred when humidity control is a  priority  The ON or CONT mode provides continuous in   door blower operation  regardless of whether the com   pressor or furnace is operating  This mode is required  when constant air circulation or filtering is desired     System Switch  Set the system switch for heating  cooling or auto opera      Up  amp  Performance Check List       tion  The auto mode allows the system to automatically   switch from heating mode to cooling 
36. trapping material  or anchored heavy nylon wire ties  8 feet    STRAPPING MATERIAL   Around vapor line only   ROOF RAFTER    TAPE OR WIRE TIE        FLOOR JOIST OR 44  oe TN         points to consider when placing and installing a high effi   ciency outdoor unit     1  Placement   Be aware that some localities are adopt   ing sound ordinances based on how noisy the unit is  from the adjacent property not at the original installa   tion  Install the unit as far as possible from the property  line  When possible  do not install the unit directly out   side a window  Glass has a very high level of sound  transmission     2  Line Set Isolation   The following illustrations demon   strate procedures which ensure proper refrigerant line  set isolation  Figure 6 shows how to place the outdoor  unit and line set  Figure 7 shows how to install line sets  on horizontal runs  Figure 8 shows how to install line  sets on vertical runs  Finally  figure 9 shows how to  make a transition from horizontal to vertical     Outside Unit Placement and Installation    Install unit away  from windows and  neighbors    windows          WIRE TIE   Around vapor line only     Strap the vapor line to the joist or  rafter at 8 ft  intervals then strap  the liquid line to the vapor line     FLOOR JOIST OR  ROOF RAFTER       Figure 7    Page 5    HSXB15 SERIES    Refrigerant Line Sets  Installing Vertical Runs  new construction shown     NOTE   Similar installation practices should be used if line set is to
37. ze the system and check  for leaks  Repair leaks  if possible    2  Evacuate the system to remove as much of the mois   ture as possible  triple evacuation     3  Use nitrogen to break the vacuum and install the pro   vided filter drier in the system    4  Evacuate the system again  Then  weigh the appropri   ate amount of R 410A refrigerant  listed on unit name   plate  into the system    5  Start the unit and monitor the system to determine the  amount of moisture remaining in the oil  Use test kit  10N46 to verify that the moisture content is within the  kit   s dry color range    6  If the moisture content is not within the dry color range   add a new filter drier between the liquid valve and the  TXV  You may have to add a new filter drier several  times to achieve the required level of dryness    If system dryness is not verified  the compressor  will fail in the future   Checking Charge  The outdoor unit should be charged during warm weather   However  applications arise in which charging must occur  in the colder months  The method of charging is deter   mined by the unit s refrigerant metering device and the  outdoor ambient temperature   Measure the liquid line temperature and the outdoor ambi   ent temperature as outlined below     Page 11    HSXB15 SERIES    1  Connect the manifold gauge set to the service valves   e low pressure gauge to vapor valve service port  e high pressure gauge to liquid valve service port  Close manifold gauge set valves  Connect the cent
    
Download Pdf Manuals
 
 
    
Related Search
 important  important synonym  important  important numbers  important links  important documents  important information  important dates  important definition  important thesaurus  important phone numbers  important notes  important dates in august  important women in history  important message from medicare  important links uofl  important person  important html  important synonyms in english  importante png  important medical event list  important tailwind  important records  important cities  important and urgent  importante significado 
    
Related Contents
CatTrack Live 2 - Mr. Lee CatCam  User`s Manual - Boland Communications  Philips Tornado Spiral energy saving bulb 872790087630700  LumiSource LPN-TWRXX User's Manual  Bedienungsanleitung/Garantie TKS 3504 TEE  User Manual  Manual de usuario www.philips.com/welcome  Manual (english)  3. panel de control desmontable (dcp)  Manuel - CaryMart    Copyright © All rights reserved. 
   Failed to retrieve file