Home
        Manuals - Lochinvar
         Contents
1.                                                      13  Revision Notes                                                     Back Cover       Hazard definitions    The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels  or to important information concerning the life of the product     A DANGER a indicates an imminently hazardous situation which  if not avoided  will result in death or serious       A WARNING     a a potentially hazardous situation which  if not avoided  could result in death or    A CAUTION CAUTION indicates a potentially hazardous situation which  if not avoided  may result in minor or  moderate injury     CAUTION used without the safety alert symbol indicates a potentially hazardous situation which  if not  CAUTION      avoided  may result in property damage     NOTICE NOTICE indicates special instructions on installation  operation  or maintenance that are important but  not related to personal injury or property damage        SENNA  s Ys TEM    Multi Temperature Loop Control    Loop Control Board Instructions    1 Introduction    The information contained in this manual provides installation and operation instructions for the addition of the Multi   Temperature Loop Control Board in conjunction with the Lochinvar Knight  KB N L  81 286   Knight XL  KB N L  400  801    Wall Mount  WB N L  51 211  WH N L  55 399  and FTXL  FTX 400   850  boilers     When connected on the Cascade commu
2.       The MTLCB communicates with the boiler   s SMART  SYSTEM control for operation of the mixing valves and  loop pumps to regulate each loop temperature  The  power supply required for the MTLCB is 120 V 60 Hz  at less than 12 amps     2  Loop Temperature Sensors     The loop temperature sensors measure the temperature  of each loop  Each sensor should be placed on the  discharge side of the loop pump as shown in FIG    s  2 1 and 2 2 on pages 5 and 6 of this manual  Use  only the three  3  NTC thermistor sensors supplied  Ifa  replacement sensor is needed  order Lochinvar part  number TST2032  For the best reading  the sensor  should be securely fastened to the pipe and insulated     3  Mixing Valves     Field supplied  The MTLCB is designed to control  24 VAC floating 3 way mixing valves with open and  close signals  These valves have an actuator  motor   time from full open to full close  The time in seconds  must be consistent across all 3 way valves installed  For  information on programming the mixing valve time  into the boiler  reference Section 4   Boiler Parameter  Setup  For 3 way valve requirements  reference Table  2A        Action Type    Table 2A 3 Way Valve Requirements    3 Way Valve Requirements    tem Description    Control Signal 3 Point  Open  Close  Com    Floating   Modulating    Loop Pumps     Field supplied  The MTLCB provides 120 VAC power to  operate three  3  loop pumps  The maximum current rating  for each pump cannot exceed 1 8 amps        EWN
3.    SENSOR                AIR SEPARATOR       EXPANSION    TANK  MAY SUBSTITUTE oo   LOW LOSS HEADER    CIRCULATOR           L FLOW CHECK  BALL VALVE   m VALVE   TYPICAL  L NOT TO EXCEED 4 PIPE DIA  OR MAX  OF 12  APART  DRAIN POINT Y STRAINER MIXING VALVE   TYPICAL   RECOMMENDED   BOILER      COLD  CIRCULATOR ae  UNION     TYPICAL  DRAIN     lt   TEMPERATURE    PRESSURE   B      GAUGE  BOILER INDIRECT  DHW TANK  IMG00654    NOTICE Please note that these illustrations are meant to show system piping concept only  the installer is responsible  for all equipment and detailing required by local codes     NOTICE A system supply sensor MUST BE installed for proper boiler operation to occur     3 Wiring Requirements    A WARNING ELECTRICAL SHOCK HAZARD     For  your safety  turn off electrical power supply  before making any electrical connections  to avoid possible electric shock hazard     Failure to do so can cause severe personal  injury or death     NOTICE Wiring must be N E C  Class 1     If original wiring as supplied with boiler  must be replaced  use only type 105  C  wire or equivalent     Boiler must be electrically grounded as  required by National Electrical Code  ANSI NFPA 70   latest edition     Label all wires prior to disconnection when  A CAUTION   P e   servicing controls  Wiring errors can   cause improper and dangerous operation     Installation must comply with     1  National Electrical Code and any other national  state   provincial  or local codes  or regula
4.   TPT_ 3 125  E  SH3 OFFSET   26   E    SH3 DIFF   3A VALUE TIME    26   EXIT  S5ELECT HOME  24 hour pump in activity operation    In the event there is not a call for heat in 24 hours  the loop pump will operate for the time of the system pump delay setting     To set time for SYS PUMP DELAY     1  While still on the Menu Selection Screen  scroll down and select  CIRCULATION PUMPS  by pressing the NAVIGATION  dial     2  In the CIRCULATION PUMPS Menu  FIG  4 7 and FIG  4 8   select  SYS PUMP DELAY   scroll to the intended time value  and press the RIGHT SELECT  SAVE  key        Figure 4 7 System Pump Delay Screen  Models KB  Figure 4 8_System Pump Delay Screen  FTXL  KBX  WB and WH  Models   STANDBY  SHUTDOWN 7 SYSTEME  DHU TANK  reve EHE DERRY son OLER Dhu CIRCO  GH PUMP DELAY z0 BY PUNE DELAY OB  ELR ANTI SELEE 0 20 CAL PUMP DELAY   61 60  EXIT A ADJUST SAVE BLRANTT SETZE   00 20    E  gas  SYS PUMP TYPE   CFH  EAIT  5ELECT HOME    17    5 Basic Operation    The MTLCB serves as the controlling device for up to three   3  individual loops  branching off the system loop of a space  heating system  It will control each loop pump and mixing  valve position in order to satisfy the set point for that loop     By installing the sensors  provided in kit  on the pipe  after the  pump  a mixed temperature is relayed to the boiler display   Each thermostat input to the boiler should receive a loop  temperature feedback for proper operation  Using this input   the MTLCB operates the 3
5.  ER ss TEM    Multi Temperature Loop Control    Loop Control Board Instructions    2 Components and Hydronic Piping continue       Figure 2 1 Single Boiler Multi  Temperature                                  LOOP  PRESSURE SENSOR  REDUCING VALVE  TYPICAL  TEMPERATURE TEMPERATURE TEMPERATURE  LOOP  1      gt   BACKFLOW    PREVENTER 1 RE L  K GAUGE N  weg als     UP I NN i i IIB   MIXING VALVES  WATER an l  TYPICAL   SENSOR  m  AIR SEPARATOR    EXPANSION   TANK   MAY SUBSTITUTE   LOW LOSS HEADER   NOT TO EXCEED 4 PIPE DIA  BALL VALVE OR MAX  OF 12  APART   TYPICAL   Y STRAINER  RECOMMENDED   i BOILER  DRAIN POINT T CIRCULATOR   TYPICAL  DOMESTIC  HOT WATER HOT  CIRCULATOR WATER  FLOW CHECK OUT     ANTI SCALD    MIXING VALVE    Da        COLD  T WATER  se      IN         UNION   TYPICAL        TEMPERATURE    PRESSURE DRAIN  GAUGE    Ir    IMG00640  NOTICE Please note that these illustrations are meant to show system piping concept only  the installer is responsible  for all equipment and detailing required by local codes     NOTICE A system supply sensor MUST BE installed for proper boiler operation to occur        SYSTEM    Loop Control Board Instructions    Multi Temperature Loop Control    2 Components and Hydronic Piping    Figure 2 2 Single Boiler Multi Temperature DHW Zoned    PRESSURE LOOP TEMPERATURE TEMPERATURE        REDUCING VALVE SENSOR LOOP  2        TYPICAL         BACKFLOW e     PREVENTER N PRESSURE  A GAUGE  me 6 dls  UP ALAN LI LI MIXING VALVES  WATER a  TYPICAL
6.  way valve to the correct position  for mixed water supply  The pump will run continuously with  the valve positioning until the thermostat set point is met or a  Protection Mode is active     When demands of more than one loop are active  the system  set point is maintained at the highest space heat set point  enabled  All enabled loops are actively satisfied together  with  up to three  3  different set points mixing down for each set  point temperature below the system     NOTICE At the beginning of successful  communication  all 3 way valves will see  a signal to close 125  of the time value    entered in the General Setup Section   FIG  4 3 and FIG  4 4 on page 10     Once a thermostat demand is enabled  the pump will run  for one  1  minute to stabilize loop temperature before  opening to system water  Note  For smaller systems  the  use of Ramp Delay is recommended to prevent short cycling  and extend runtime  At this time the 3 way valve will adjust   open to a calculated initial position based on the differential  of the sensed temperature and set point  The MTLCB will  continue to raise the mixed temperature of the loop toward its  individual set point  while continuously relating to the loop   s  sensor input by a specific algorithm     At the end of a loop demand cycle  the pump powers off  and  the valve will move to the fully closed position     12       EN SYSTEM    Multi Temperature Loop Control       Loop Control Board Instructions    Protections  Initial    
7. B  terminals A and B  FIG  3 1      Connect the shield wires to one of the shield terminals  on the Low Voltage Connection Board  FIG  3 2  and the  MTLCB  FIG  3 1           LLO0SINI YO S  O 3SN3 ANWA                                  ONIAIM 3dVOSVO                   Loop Control Board Instructions  PUMP     FUSE    ya1108    ROO ale    O L AlddNS   7 IWYLNAN A 02L     q13lIHs O ANI                                    L YOSNIS dOO1 a 2 2  ZUOSNIS dOO    D      YOSN3S dOOT m                      EAS Ys TEM    Multi Temperature Loop Control                      O 0000 O 0     0000600                                                                                     NdO  sn  WOO  NdO  sn  WOO  NdO  S10  WOO                        JAVA JA IVA JA IVA    ONIXIN ONIXIN ONIXIN    AVM     AYME AYME    L C              Qd  1ddf1S 01313    Figure 3 1_Multi Temperature Loop Control Board  MTLCB     3 Wiring Requirements    Gd  IddN S 071313           Loop Control Board Instructions    Multi Temperature Loop Control    3 Wiring Requirements  continuec     Figure 3 2_Terminal Strip Connections to the Boiler s Low Voltage Connection Board  Knight Knight XL shown  below for illustration purposes        IMG00103       LOW VOLTAGE CONNECTION BOARD    ENABLE  CONTACTS y       4 Boiler Parameters Setup    Once the wiring requirements of all the MTLCB components  are complete  the next step is to adjust the following parameters  through the boiler   s display     Cascade Address   Loop Temperatur
8. In the event the sensed temperature continues to exceed the  set point  set point   offset   2  F  but within the set point    20  F  for a given loop  a Protection Mode is entered to stop  excessive temperatures from being reached  To prevent the  loop temperature from exceeding this range  the following  stages are enacted     l  The pump active on the loop exceeding the set point  temperatures is powered off     2  The mixing valve is adjusted from the current position   plus 25  to the closed position     3  The pump is powered ON for two  2  minutes     4  Ifthe temperature has not dropped below the  set point    offset   2  F   the pump is turned OFF     The control will automatically reset the demand as active once  the sensor input is below the  set point   offset   2  F      Error Mode    If the sensed temperature rises above set point   20    the  display of the boiler will present the sensor input with an  exclamation mark  ex  128  F    The following protection  algorithm will begin to prevent a lockout of the loop     1  Ifrunning  the pump will immediately power off and the  3 way valve is adjusted 125  in the closed direction    2  Once the close signal ends  the pump is powered back on  for two  2  minutes  Within this time  the sensed  temperature must drop below  set point   offset  or the  pump will be powered off    3  Asa result  the temperature will drop below  set point    offset  and the error code  ex  128  F   is removed     With the Initial and Erro
9. LCB I O Rev D       Multi Temperature Loop Control    MULTI TEMPERATURE  LOOP CONTROL BOARD  INSTRUCTIONS    Models  KB 81   286   KBXL 400   801  WB 51   211   FTX 400   850 and  WH 55   399       This manual must only be used  by a qualified heating installer    service technician  Read all  instructions  including this manual   the Installation and Operation  Manual  and the Service Manual   before installing  Perform steps in  the order given  Failure to comply  could result in severe personal  injury  death  or substantial property          y damage   Lochinvar    Save this manual for future reference   ef       High Efficiency Water Heaters  Boilers and Pool Heaters    1  INTRODUCTION Zee 3 4  BOILER PARAMETERS SETUP  2  COMPONENTS AND HYDRONIC PIPING                  4 6 Cascade Communication Setup                                    10  3  WIRING REQUIREMENTS To Access Cascade Address                                         10  Line Voltage Connections                                             7 3 Way Valve Selup                                                        10  LOD  SEMIS ONS ee a 7 24 Hour Pump In Activity Operation                              11  Mixing ValVes nme ee er 7 To Set Time for SYS Pump Delay                                 11  Wiring of the Cascade                                                  7 5  BASIC OPERATION                                                      12  A o 12  Milla ee ee editadas 12  Error ModE enge ea 12  Forced Change  
10. e Settings  3 Way Valves   Pumps    Power ON the boiler and place into Shutdown Mode  leaving  the MTLCB powered OFF  With the boiler in Shutdown  Mode  all calls for heat are disabled and the above parameters  can be adjusted     Cascade communication setup    When the MTLCB is used with a single boiler  the boiler must  be programmed as a Cascade Leader by setting its Cascade  address to 0     To access cascade address     1  While on the Menu Selection Screen  select  CONTROL  MODES     2  In the Control Modes Menu  FIG  4 1 and FIG  4 2    select  CASCADE ADDRESS  and set to  0     3  Press the RIGHT SELECT  SAVE  key    4  Press the  HOME  key to exit and download all   parameters     To adjust the set points for each space heat loop  reference the  Service Manual for a detailed explanation     The 3 Way Mixing Valve Time can be accessed as shown  below     NOTICE Please note that the brackets      denote    screen status     3 way valve setup       Press and hold the LEFT SELECT  MENU  key     Enter the pass code    3  Scroll down and select  TEMPERATURE  SETTINGS     4  Scroll down and select 3 Way Valve Time by pressing  the NAVIGATION dlal  FIG  4 5   FIG  4 6     5  Scroll to the intended value    6  Press the RIGHT SELECT  SAVE  key    de Exit one level     10       EITNERWSYSTEM  Multi Temperature Loop Control       Loop Control Board Instructions    Once all the parameters have been adjusted for the application   power ON the MTLCB  TX and RX LED   s will light u
11. nication bus to the boiler control  the Multi Temperature Loop Control Board   MTLCB  will actively control the water temperature supplied  up to three  3  loops  The MTLCB will control the 3 way mixing  valves and pumps for each of these loops  and provide the actual loop temperatures to the boiler for display     The MTLCB has been tested  and is in compliance with the following standards        CSA Standard C22 2 No 0   General Requirements   Canadian Electrical Code  Part II     CSA Standard C22 2 No 24   Temperature Indicating  amp  Regulating Equipment     ANSVUL 873   Temperature Indicating and Regulating Equipment       ENYA  s Ys TEM    Multi Temperature Loop Control    Loop Control Board Instructions    2 Components and Hydronic Piping    Components    The multi temperature loop control consists of four  4   major components in conjunction with the boiler system   These components are as follows     Multi Temperature Loop Control Board  Loop Temperature Sensors   Mixing Valves   Loop Pumps    In order for the system to work properly the components  listed above must be installed correctly  Reference the  piping illustrations included in this section  FIG  s 2 1 and  2 2  for suggested guidelines in piping     Please note that the piping illustrations   NOTICE   FIG    s 2 1 and 2 2  are meant to show  system piping concept only  the installer    is responsible for all equipment and  detailing required by local codes     1  Multi Temperature Loop Control Board  MTLCB
12. p to  signify data is being sent and received from the boiler   s control   With successful communication  the SH1  SH2  and SH3  temperatures can be read with a clockwise rotation of the  NAVIGATION dial  see FIG  4 3  amp  FIG  4 4   If successful  communication does not occur  reference FIG  4 1  amp  FIG 4  2  for set up of the Cascade address     Figure 4 1 Cascade Screen  Models KB  KBX  WB and WH     Moo BUS INACTIVE  MOD BUS TO 0 10   gt CASCADE ADDRESS 0  CASCADE TYPE LL  EIT    ADIUST SAVE    Figure 4 2 Cascade Screen  FTXL Models   s TANDET    SYSTEM  DHU TANK    BOILER 2 DHU CIRCO   CASCADE   STANDBY  Pol   x    MEWU eJSCREEH SHOH    Figure 4 3_SH1  SH2  and SH3 Screen  Models KB   KBX  WB and WH     SHUTDOUN    HI LOOP TEMP  10  F  SHz LOOP TEMP  140  F  SHS LOOP TEMP  1S0 F    MEHO  5ETFOINTS   H    Figure 4 4_SH1  SH2  and SH3 Screen  FTXL Models     STANDBY    SYSTEM  DHU TANEC 3  BOILER    DHU CIRCE 3      5H1 SETFOINT   125    SH2 SETFOIHT    1253 F  SHA SETFOIHT   125  F  DALI SETFOIHT    128  F    LIMITS s amp SCROLL HOME       SENNA Ys Ys TEM  Multi Temperature Loop Control       Loop Control Board Instructions    4 Boiler Parameters Setup  continued        Figure 4 5_3 Way Valve Time Screen  Models KB  Figure 4 6_3 Way Valve Time Screen  FTXL Models   KBX  WB and WH   s TANDET  SHUTDOWN SVSTEMC   DHL TAME   Src SEIFI 45  F  SH3 OFFSET  Tee BOILER  DHW CIRCE   SHS DIFF  IF SH  SETFT   125  E   gt S WAY VALVE TIME 105 aie ee   a q  EXIT MADIUST SAVE SHS   
13. r Mode Protections  the valve is fully  closed to reduce the loop temperature by preventing continued  hot water supply from the system  If the temperature sensed  is not reduced within the steps listed above  the MTLCB will  lockout this loop until temperatures below  set point   offset   are reached  During these scenarios  ensure the physical  movement of the 3 way valve in the event the system needs  to be repaired     5 Basic Operation  continued   Forced Change    It is necessary for the MTLCB to sense a temperature change  of 2  F within the time of a call for heat and the initial  position of the 3 way valve  This is a two fold protection  where the MTLCB protects the loop from continued normal  operation when it cannot calculate the sensitivity of the valve  movement needed     As a secondary operation  the sequence below protects  the loop when the loop temperature sensor is connected  to the MTLCB but not installed properly  not installed  or  malfunctioning     1  With a call for heat the pump turns on     2  The3 way valve movesto the initial open position after the  pump is on for one  1  minute     3  If after three  3  minutes the initial position does not  create a 2 F change in sensed temperature  the 3 way  valve is moved to the closed position     4  After two  2  minutes of closure  the 3 way valve is  opened to the initial position     5  Repeat Steps  3 and  4     6  Once the 3 way valve is moved to the closed position  the  loop is locked out for the d
14. tions     2  In Canada  CSA C22 1 Canadian Electrical Code Part 1   and any local codes     Line voltage connections    1  Connect 120 VAC power wiring to the line voltage  terminal strip in the junction box  as shown in FIG  3 1  on page 8     2  Wire the loop pumps  provided by the installer  as shown  in FIG  3 1     NOTICE The loop pump connections provide 120  VAC power to the pumps at a maximum    current rating of 1 8 amps for each pump        EITERWSYSTEM    Multi Temperature Loop Control    Loop Control Board Instructions    Loop sensors    ll    Install the kit provided loop temperature sensors  see  FIG    s 2 1 and 2 2      Route the sensor wires through a knockout on the side of  the MTLCB  FIG  3 1      Connect the loop temperature sensors to the SEN1  SEN2   and SEN3 terminals on the MTLCB     Mixing valves    l   2     Install the mixing valves as shown in FIG    s 2 1 and 2 2     Route the mixing valve wires through a knockout on the  right side of the MTLCB  FIG  3 1      Connect the mixing valve wires to terminals MV1  MV2   and MV3 on the MTLCB     Wiring of the cascade    Communication between the boiler and the MTLCB    IS    accomplished using shielded  2 wire twisted pair    communication cable  Try to keep the cable as short as  possible     l     Connect one end of the twisted pair wires to Cascade  terminals A and B on the Low Voltage Connection Board  of the boiler  see FIG  3 2 on page 9      Connect the other end of the twisted pair wires to MTLC
15. uration of the call for heat     7  The lockout continues for 30 minutes after the call for  heat has ended     8  After 30 minutes  the next call for heat will begin at Step   1     Please note  the first two  2  steps are normal operation and  at Step  3  if a 2  F change in temperature is not sensed  the  protection process will begin  If at any point a 2  F change is  sensed  normal operation will resume        SMART  Multi Temperature Loop Control          SYSTEM    Loop Control Board Instructions    13       s       m    Revision Notes  Revision A  ECO  C08954   initial release     Revision B  ECO C 10236  reflects the update of  the control image in Figure 3 1 on page 8     Revision C  ECO  011814  reflects edits made  to place the check valves on the outlet side of   a    the pump on both piping diagrams       Lochinvar    Revision D  ECO C15810  reflects the addition    V       High Efficiency Water Heaters  Boilers and Pool Heaters of FTXL models and screens    300 Maddox Simpson Parkway   Lebanon  TN 37090 LCB I O Rev D  615 889 8900   Fax  615 547 1000 07 14    www Lochinvar com    
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
XR ADVANCED Thank you for purchasing this Thinkgizmos.com  Mapgen User`s manual  Zoroufy 24052 Installation Guide  Contents - Alabin.pl  USO E MANUTENZIONE    Copyright © All rights reserved. 
   Failed to retrieve file