        Data Sheet 85001-0527
         Contents
1.     Security Open w Tamper  Short sends security alarm  open  sends tamper  41      Security Closed w Tamper  open sends security alarm  short  sends tamper  42      Basic Security  open or short sends security alarm  43    Security Tamper  open or short sends tamper  44         Security Open  short sends active  open sends fault  45     Maintenance  open or short sends maintenance  48     Active Non Latching  short sends active  open sends trouble  3    Security Closed  open sends active  short sends fault  46    The Dual Input Security Module shall be a Edwards model SIGA   SEC2     85001 0527    Issue 3 1    Typical Wiring    From Signature  Loop Controller  or previous device              Data In        Data In      Data Out      Data Out        To next Signature  device    Signature loop    Signature Series Overview    The Signature Series intelligent analog addressable system from  Edwards is an entire family of multi sensor detectors and mount   ing bases  multiple function input and output modules  network  and non network control panels  and user friendly maintenance  and service tools  Analog information from equipment connected    to Signature devices is gathered and converted into digital signals     An onboard microprocessor in each Signature device measures  and analyzes the signal and decides whether or not to input an  alarm  The microprocessor in each Signature device provides four  additional benefits     Self diagnos tics  Automatic Device Mapping  and Fast
2.   Stable Communication     Self diagnostics and History Log   Each Signature Series   device constantly runs self checks to provide important mainte    nance information  The results of the self check are automatically   updated and permanently stored in its non volatile memory  This   information is accessible for review any time at the control panel    PC  or using the SIGA PRO Signature Program Service Tool  The   information stored in device memory includes    e Device serial number  address  and type   e Date of manufacture and hours of operation      e Most recent trouble code logged by the device     32 possible  trouble codes may be used to diagnose faults     Automatic Device Mapping  The Signature Data Control    ler  SDC  learns where each device   s serial number address is  installed relative to other devices on the circuit  The SDC keeps a     map    of all Signature Series devices connected to it  The Signa   ture Series Data Entry Program also uses the mapping feature   With interactive menus and graphic support  the wired circuits be   tween each device can be examined  Layout or    as built    drawing  information showing branch wiring  T taps   device types and their  address are stored on disk for printing hard copy  This takes the  mystery out of the installation  The preparation of    as built    drawings  is fast and efficient     Page 3 of 4    Tamper  Circuit 1 Aarm  input EOL EOL EOL    Basic Security    Alarm    Tamper    N C with tamper N O with ta
3. EST    Life Safety  amp  Communications       Dual Input    security Module  SIGA SEC2    Overview    The SIGA SEC2 is an intelligent analog addressable device used  to connect one or two normally open or normally closed dry con   tact security circuits     The actual function of this module is determined by the    person   ality code    selected by the installer  This code is downloaded   to the module from the Signature loop controller during system  configuration  The input module gathers information from the  devices connected to them and converts it into digital signals   The module   s on board microprocessor analyzes the signal and  decides whether or not to input an alarm  tamper  or maintenance  condition     The intelligence built into every SIGA SEC2 means that the mod   ule can decide when to report information and when to suppress  sending information to the host system  As an example  when  the SIGA SEC2 module is disarmed  changes of state that would  normally create an alarm are recognized by the module and sent  to the host as a background task  This enhances reponse time  by removing the burden of normal room activity on the network   Should a trouble or tamper condition be detected these events  are immediately transmitted to the host helping to ensure system  integrity is maintained  Once the module is armed  alarms are sent  immediately to the host     The module is housed in a small attractive thermo plastic enclo   sure designed for surface mounting  Wi
4. XX  UUKL and SYZV  UL 294 category ALVY  UL 609 category AOTX   UL 636 category ANET  UL 1076 category APOU  UL 365 category APAW  UL 1610 category AMCX   UL 1635 category AMCX ULC S527  ULC S301  ULC S302  ULC S303  ULC S306  ULC ORD   C1076  ULC ORD C693  Please refer to ESTS Installation and Service Manual for complete system  requirements     Ordering Information       Catalog Number Description Shipping Wt  Ib  kg   SIGA SEC2 Dual Input Security Module 0 4  0 15        Page 4 of 4    ET 85001 0527    Issue 3 1       L  Z 90    
5. e devices  may be turned off temporarily  from the control panel     Quality and Reliability   Edwards Signature devices are manu   factured in North America to strict international ISO 9001 stand   ards  All electronics utilize surface mount technology  SMT  for  smaller size and greater immunity to RF noise  A conformal coat   ing is used for humidity and corrosion resistance     1 Retrievable with SIGA PRO programming tool     85001 0527    Issue 3 1       EDWARDS    Contact us      Email  edwards fire fs utc com   Web  www est fire com   EST is an EX WARDS brand   1016 Corporate Park Drive  Mebane  NC 27302    In Canada  contact Chubb Edwards     Email  inquiries chubbedwards com  Web  www chubbedwards com          2013 UTC Fire  amp  Security Americas  Corporation  Inc  All rights reserved   Specifications subject to change  without notice  Edwards is part of UTC  Climate  Controls  amp  Security  a unit of  United Technologies Corporation        Specifications       Agency Listings UL  ULC  See Note                       Dimensions 1 7 8    x 3    x 1      HWD   4 52cm x 7 62cm x 2 54cm   Wire Size 16 AWG  1 0mm   to 22 AWG  0 25mmz    Mounting Surface mount directly on wall or in a 4    square electrical box  Finish White Cycoloy  Operating 30  F to 120  F  0  C to 49  C    Environment O to 93  Humidity non condensing   Current Draw Standby  720 uA  Tamper Active  850 pA  Note     The EST3 is modularly listed under the following standards    UL 864 categories  UOJZ  UO
6. he circuit  is shorted  Outputs are non latching     BASIC SECURITY  Personality code 43    Assign to one or  both circuits  Configures circuit 1 or 2 or both to transmit an alarm  condition when the input circuit is opened or shorted  Outputs are  non latching     TAMPER  Security Personality code 44    Assign to one or  both circuits  Configures circuit 1 or 2 or both to transmit a tamper  condition when the input circuit is opened or shorted  For use   in conjunction with another circuit used to detect security alarm  condition  Outputs are non latching     MAINTENANCE  Security Personality code 48    Assign to  one or both circuits  Configures circuit 1 or 2 or both to trans   mit a maintenance condition when the input circuit is opened or  shorted  For use with device such as a motion detector providing  a separate maintenance contact indicating the device is opera   tional but requires service  Outputs are non latching     NORMALLY OPEN w TROUBLE  Personality code 3  Active    Non Latching    Assign to both circuits  Configure both circuits  to transmit an active condition when the input circuit is shorted  and transmit a trouble condition when the circuit is opened     SECURITY OPEN w FAULT  Personality code 45    Assign to  one or both circuits  Configures circuit 1 or 2 or both to transmit  a security alarm condition when the input circuit is shorted and  transmit a fault condition when the circuit is opened  Outputs are  non latching     SECURITY CLOSED w FAULT  Per
7. mper    Circuit 2 EOL EOL EOL  input    Tamper Security open    with fault    Secuity closed  with fault    Device mapping allows the Signature Data Controller to discover   e Unexpected additional device addresses   e Missing device addresses   e Changes to the wiring in the circuit     Most Signature modules use a    personality code    selected by the  installer to determine their actual function  Personality codes are  downloaded from the System Definition Utility  SDU  during system  configuration and are indicated during device mapping     Fast Stable Communication     Built in intelligence means less  information needs to be sent between the device and the Signa   ture Data Controller  SDC   Other than regular supervisory polling  response  Signature devices only need to communicate with the  SDC when they have something new to report  This provides very  fast control panel response and allows a lower baud rate  speed   to be used for communication on the circuit  The lower baud rate  offers several advantages including    e Less sensitivity to circuit wire characteristics    e Less sensitivity to noise glitches on the cable    e Less emitted noise from the data wiring    e Twisted or shielded wiring is not required     Testing  amp  Maintenance     Automatic self diagnosis identifies  when a Signature device is defective and causes a trouble mes   sage  The user friendly maintenance program shows the current  state of each device and other pertinent information  Singl
8. ring terminals are provided  for up to 16 AWG  1 00 mm   to 22 AWG  0 25 mm     wires     Page 1 of 4       Intelligent Initiating                PJ  7300 1657   0209    Standard Features    e Two input circuits  Suitable for doors  windows and other locally powered security  devices such as motion detectors  etc     e Small aesthetic enclosure   e Multiple applications   e Automatic device mapping   e Electronic addressing   e Intelligent device with microprocessor  e Non volatile memory   e Diagnostic LEDs for service    e Designed in accordance with ISO 9001 Quality System    85001 0527    Issue 3 1    Application    The duty performed by the SIGA SEC2 is determined by its  personality code  SIGA SEC2 provides two security circuits  each  circuit can be assigned a personality code  The SIGA SEC2 is  ideal for connection to door contacts  motion detectors  glass  break detectors or any sensor offering dry contact alarm  trouble   or tamper contacts     NORMALLY OPEN w TAMPER  Personality code 41  Secu   rity      Assign to one or both circuits  Configures circuit 1 or 2 or  both to transmit a security alarm condition when the input circuit  is shorted and transmit a tamper condition when the circuit is  opened  Outputs are non latching     NORMALLY CLOSED w TAMPER  Personality code 42   Security    Assign to one or both circuits  Configures circuit 1 or  2 or both to transmit a security alarm condition when the input  circuit is opened and transmit a tamper condition when t
9. sonality code 46  Security  Closed    Assign to one or both circuits  Configures circuit 1 or   2 or both to transmit an alarm condition when the input circuit is  opened and transmit a fault condition when the circuit is shorted   Outputs are non latching     Page 2 of 4    Installation    The SIGA SEC2 should be mounted in the protected space  and  in close proximity to the device it is monitoring     Electronic Addressing     The loop controller electronically ad   dresses each module  saving valuable time during system com   missioning  Setting complicated switches or dials is not required   Each module has its own unique serial number stored in its on  board memory  The loop controller identifies each device on the  loop and assigns a    soft    address to each serial number used by  the systems     Compatibility  The SIGA SEC2 is compatible with the EST3 Signature loop con   trollers  and requires two Signature addresses     Engineering Specifications   Provide intelligent dual input security modules at the locations  shown on the drawings  The Dual Input Security Module shall  provide two  2  input circuits each capable of a minimum of 6 per   sonalities  each with a distinct operation  The module shall have an  aesthetically pleasing enclosure for unobtrusive mounting in visible  areas  and shall be capable of being directly surface mounted  without the need for an electrical box     The dual input security module shall support the following circuit  configurations   
    