Home
Point-on-Wave Controller Series RPH2
Contents
1. 5 1 3 Control Voltage Type in the rated voltage of your CB coil available only for modules RPH2 xxA0 RPH2 xxA1 RPH2 xxA3 This value acts as base for the calculation of the additional compensation value of the mechanical operating time of the CB System Data Password System Frequency Control Voltage Rated Pressure BE 0 V 5 1 4 Rated Pressure Type in the value of the rated pressure of the hydraulic system of your CB drive available only for module RPH2 xxA1 RPH2 xxA3 This value acts as base for the calculation of the compensation value of the operating time of the CB eo c0 System Frequency Control Voltage Rated Pressure Switching Program NEAR A N T I hielsjslejzie IEE IE TEST T 5 1 5 Switching Program Select the suitable switching program by pressing the or button transformer shunt reactor capacitor bank user program Page 40 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 al Sey es ete rae at ee Control Voltage Rated Pressure Switching Program Language MES toi ment PLT TTT I Ielsf4lslelzle Y ARA REESE TAE e A 5 1 5 1 User Program You can define your own switching moments for each phase by selecting the User Program Note If you select user program you have to select the rated frequency first see chapter 5 2 Adjustable switching moments T C1 Neutral isolated Type in the switching moments
2. Pp RG Pp Pp y C oo Pp y Pp AS gt A A ArcingTime CH Ei i Oo i pO Pd Pp y AN E E EJ Oooo y PA 1 Deltat xe kU2 Voltage CH2 REA KP2PresreCH2 Temp Comp CH J Table Temp CH2 gt Oooo e Analogue Data EE A Roe pod Thresholds 3 Ourrentmax peak 1 1 Control Voltage max 1 Control Voltage min Temperature max A Temperature min Pressure max A TIERE MAA Rated Curr prim IO Rated Curr sec Pp Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 Chapter Module Levelt Level2 Level3 Analogue Data contin 534 Ax Actual Contr Voltage 535 Ax 9 Temperature 5 3 5 1 Ax Value at mA 5352 Ax AGHD JjVaueat20mA Pressure gt Valueat20 mA NE A bee taco Reset obligatory Lock out Alarmbist o ooo IO TT Frequenymax Current max peak Ref Voltage Failure PRTC Impulse Failure Neutralintermediate Neutral grounded Neutralisolated SelftstERROR__ SelftstCHiERROR SelftestCH2 ERROR Command Time CH1 min po Command Time CH2 min OperatingTime min JOperatingTime max Drive Mech Failure Po Archive Full Archive Failure
3. SESS AE AA es This submenu is available only with modules RPH2 xxA0 RPH2 xxA1 RPH2 xxA3 5 3 1 3 Control Voltage min Type in the lower limit for the control voltage If the measured value of the control voltage becomes lower than the limit an alarm is generated The permissible range is from 35 V to 300 V CNE gt Current max peak Op Voltage max Op Voltage min Temperature max 200 0 V El A LL I hielslslelzie Y A EE ET ES This submenu is available only with modules RPH2 xxA0 RPH2 xxA1 RPH2 xxA3 5 3 1 4 Temperature max Type in the upper limit for the ambient temperature of the CB If the measured value of the temperature becomes higher than the limit an alarm is generated The permissible range is from 100 C to 100 C Schneider Electric Energy Austria AG Leonding Page 49 Issue 4 58 020 034 E 2011 02 TASA IS E Op Voltage max Op Voltage min Temperature max Temperature min 45 0 07 El IIIT T I Mielle AAA A ee This submenu is available only with modules RPH2 xxA0 RPH2 xxA1 RPH2 xxA3 5 3 1 5 Temperature min Type in the lower limit of the ambient temperature of the CB If the measured value of the temperature becomes lower than the limit an alarm is generated The permissible range is from 100 C to 4100 C ia a SU Op Voltage min Temperature max Temperature min Pressure max 50 0 C PET TTT I lelsisslelrist AE EA A ESSI This subm
4. 3 3 2 Opening Breaking of small inductive currents as is with reactors can lead to high switching surges if current chopping or restriking in the circuit breaker occurs Contact separation should take place a sufficient time before current zero crossing so that after current breaking the contact gap is great enough to withstand the recovery voltage The switching times given in table 1 indicate the moment of current breaking The necessary arcing window is taken into account by the RPH2 through the arcing time 3 3 3 Data on circuit breaker required The following data on the circuit breaker are absolutely necessary to operate the RPH2 Page 22 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 The mechanical closing and or opening operating time of the three circuit breaker poles see 3 1 2 for definition Accuracy about 0 1 ms 3 3 3 1 Closing The pre arcing times of the circuit breaker must be known e Pre arcing time of the breaker in the voltage peak equal value for all three phases with grounded neutral or for phase L1 with isolated neutral e Pre arcing time with partial voltage for phases L2 and L3 with isolated neutral see table 2 3 3 3 2 Opening The optimum arcing time input determines the arcing window for a secure current breaking free from restrikes in the next zero crossing The value is given by the breaker manufacturer In order not to come into conflict with unavoidable operating
5. Value at 20 mA Obar NAAA E OC EUER PT LETT TTT Ielsifjejzla EA FREEZE PEERS ES Page 53 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 5 3 6 2 Value at 20 mA Type in the rated value of the pressure transducer at an output current of 20 mA This information is part of the documentation of the pressure transducer Value at 4 mA Value at 20 mA 500bar MERA PTET TT TT be lefsia sie 7 e PHS EA ESTEE EE 5 4 Alarms 5 4 1 Reset Obligatory In this submenu you can select which alarm outputs and the according LED on the front panel of the RPH2 are to be acknowledged Alarm outputs which are marked as reset obligatory are displayed on the front panel and activated closed until you press the Quitt button regardless whether the alarm is still active or already gone Example NAAA Reset obligatory Lock out Alarm List 10100000 NAAA PT TET TY I hielstslelzie PESAS EA In the example mentioned above the alarms 1 and 3 are marked with the function Reset obligatory must be acknowledged Reset Obligatory Setting 1 Alarm is active gt LED is blinking alarm output active Alarm is acknowledged gt LED has steady light alarm output active Alarm off gt LED off alarm output not active respectively Alarm is active gt LED is blinking alarm output active Alarm off gt LED is blinking alarm output active Alarm is acknowledged gt L
6. 3 1 2 Circuit breaker The mechanical closing time of the circuit breaker is defined as the time between the electrical command to the operating coil and touching of the main contacts On the other hand the opening time is the time between the electrical command and the separation of the main contacts The operating times of circuit breakers independent of the breaking system and the type of operating mechanism changes in dependence on certain service parameters e With reduced control voltage at the operating coil there is less energy available to change the electrical control commands into a mechanical action The operating time extends itself Valid for all types of operating drives e By altering the hydraulic pressure on hydraulic drives the energy available to carry out the switching movement changes e The ambient temperature is the most complex parameter of influence The electrical resistance of the operating coils the oil viscosity and the pressure of the SF6 gas are all dependent on the temperature Moreover there is expansion of operating rods and porcelains All these parameters influence the operating time in different Ways In the extreme each of these 3 parameters can alter the operating time by some milliseconds The RPH2 is in the position to compensate these operating time variations 3 1 3 RPH2 structure The outstanding features of the RPH2 are e Microprocessor control with a switching command time resolutio
7. 5 3 6 1 Value at 4 mA 53 5 3 6 2 Value at 20 mA 54 Page 3 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 5 4 Alarms 54 5 4 1 Reset Obligatory 54 5 4 2 Lock Out 55 5 4 3 Alarm List 55 5 4 3 1 Lock out 56 5 4 3 2 Frequency min 56 5 4 3 3 Frequency max 56 5 4 3 4 Current max peak 57 5 4 8 5 Reference Voltage Failure 57 5 4 3 6 RTC Impulse Failure 57 5 4 3 7 Neutral intermediate 57 5 4 8 8 Neutral grounded 57 5 4 3 9 Neutral isolated 57 5 4 3 10 Selftest ERROR 57 5 4 3 11 Selftest CH1 ERROR 57 5 4 3 12 Selftest CH2 ERROR 58 5 4 3 13 Command Time CH1 min 58 5 4 3 14 Command Time CH2 min 58 5 4 3 15 Operating Time min 58 5 4 3 16 Operating Time max 58 5 4 3 17 Drive mech Failure 59 5 4 3 18 Archive Full 59 5 4 3 19 Archive Failure 59 5 4 3 20 Control Voltage min 59 5 4 3 21 Control Voltage max 59 5 4 3 22 Temperature min 59 5 4 3 23 Temperature max 60 5 4 3 24 Temp Transducer Fault 60 5 4 3 25 Pressure min 60 5 4 3 26 Pressure max 60 5 4 3 27 Press Transducer Fault 60 5 5 Measurement 60 5 5 1 Current Graphs 60 5 5 2 Measured Times 61 5 5 2 1 Command OUT 61 5 5 2 2 CB Signal received 61 5 5 2 8 Calculated Operating Time 62 5 5 2 4 Measured Operating Time 62 5 5 8 Frequency 63 5 5 4 Current RMS 63 5 5 5 Control Voltage 63 5 5 6 Actual Temperature 64 5 5 7 Temperature for Compensation 64 5 5 8 Additional Operating Times 64 5 5 8 1 Voltage CH1 64 5 5 8 2 Voltage CH2 65 5 5 8 3 Tempera
8. Control Voltage min Control Voltage max Temperatue min Temperature max Temp Transd Faut Pressuemin EM Pressure max Pressure Transd Fault Current Graphs puo Pp Command OUT CBSignalreceived Calculated Op Time Frequency Current RMS Control Voltage Measurement Page 15 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 Chapter Module Levelt___________ Level2_______ Level3 sss eme 0 Temperature pr er 5 58 Ax sd Additional Op Times 5 5 8 1 Ax A J Voltage CHT 5586 ALAS 559 AS Pressure L1 L2 L3 ooo VoageCH2 Temperature CHI SC Temperature CH2 PresueCHi PPresueCH DESCRI 5510 At Pressure Lt 56 aux Functions IEEE EEN 561 S of Alarm Output 562 s Alarminput 563 ff ErrorType 57 _ Switching Archive S SSCS 3 1 APPLICATION NOTES General Description of the Functions The RPH2 Point on Wave Controller is a three phase control device for circuit breakers with single pole drives It can be used for both the energizing and de energizing of high voltage devices 3 1 1 Synchronized switching 3 1 1 1 Closing Energizing of transformers reactors and capacitors is normally effected three pole for all 3 phases simultaneously In doing this the point on wave i
9. Frequency Current RMS AAA A TY ti etsiaiste 7tst Y ARA a EST 5 5 2 1 Command OUT This submenu shows the measured time from the zero crossing of the reference voltage phase L1 until the command is executed Measured Times gt Command OUT CB Signal received Calculated Op Time Measured Op Time MEE 9 5 9 5ms EEEEBEEBENHUESBHESHONEN HARE ce ERES Note The resolution of the time measurement is 0 1 ms 5 5 2 2 CB Signal received This submenu shows the measured time from the zero crossing of the reference voltage phase L1 until the auxiliary contacts of the CB are switched Measured Times gt Command OUT CB Signal received Calculated Op Time Measured Op Time NAAA PTET TTT h iellalslelie HIST SEHE TIT T8 17 Page 61 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 This submenu is available only with module RPH2 xxxS Note The resolution of the time measurement is 0 1 ms 5 5 2 3 Calculated Operating Time This submenu shows the calculated operating time according to the measured service conditions temperature pressure control voltage If the compensation facility is not active the set values of Operating Time CH1 see 5 2 1 and Operating Time CH2 see 5 2 2 are displayed Measured Times gt Command OUT CB Signal received Calculated Op Time Measured Op Time 128 7 129 0 129 0ms PTET TT TT hielsjalslel7ie T
10. O Free language esses Selftest Interval Hours CB Data Dwmmmmeon 1 fe Owemmmeog me Poore f fe Aux Timeshift CH1 EN 1 ES Aux Timeshift CH2 Adaptive Control Weighting Factor Compensation O Yes O No kU1 Voltage CH1 eeeectteeeeeetees kP1 Pressure CH1 kU2 Voltage CH2 kP2 Pressure CH Page 72 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 Configuration Checklist RPH2 Temperature Compensation Switching Channel 1 Analogue Data Switching Channel 2 Thresholds Current max peak A Control Voltage max V Control Voltage min V Temperature max C Temperature min C Pressure MIN bar Pressure max bar Actual Control Voltage CT rated current prim CT rated current sec O1A O5A Temperature Value at 4 mA Value at 20 mA Pressure Value at 4 mA Value at 20 mA Schneider Electric Energy Austria AG Leonding Page 73 Issue 4 58 020 034 E 2011 02 Configuration Checklist RPH2 Alarms _Alarm Functions Reset Obligator E al tke i EA PA EAS Ei iu unii iei el SAA HE ES PEE EUNT bes En ES ipa CEN Page 74 Issue 4 58 020
11. Position DPERATION After switching to this position the device carries out an internal test After the averaging of the analogue measured values pressure temperature control voltage is completed it takes approx 20 sec and no failure is present the device switches to OPERATION and the green LED READY lights up The alarm contact Device not ready X6 12 13 opens 2 4 3 LED indicators 2 4 3 1 LED READY green Status Steady light Dark Blinking 2 4 3 2 LED 1 to 7 red Function The device is ready for operation Key operated switch in OFF position Averaging of analogue measured values is still not completed see 1 2 Voltage reference is missing or frequency is not in the permitted range 10 96 The device has identified an internal failure The password is activated the device can be parameterized All functions are active To show the parameterized alarms The LED s are assigned to the alarm relays 1 to 7 Next to the LED s is a window in which the user s message texts can be placed For a withdrawn cassette the input tag with the texts is inserted from the top behind the front As insert use a sheet of paper 41 mm x 90 mm Status Function Steady light An alarm has occurred The LED remains alight until the alarm is active regardless of whether the Quitt button has been pressed As long as the LED is alight the affiliated output relay is also activated Page 11 Schneider Electric Energy A
12. actual date and time The format for date and time is YYYY MM DD HH MM ASA EAN Switching Program Language Time Date New Password EE SIG TS ESO Se PLT TT ET lelsiWfsislrlst Y AR A A O Note Type in only correct values for date and time Note There are no problems with a date after 2000 01 01 5 1 9 New Password If you want to change the actual password simply type in the new password Possible values are all numbers between 0000 and 9999 Page 42 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 MS tema Language Time Date New Password Selftest PARA NA PT LETT LL I hielstslelzie Y AAA ee Note If you have forgotten the selected password you can ask for a temporary password call your local Schneider Electric representative 5 1 10 Selftest Start You can activate the selftest facility by pressing the Enter button The selftest facility checks the internal function of the module and the switching outputs System Data Time Date New Passwo Selftest Selftest RES PTET I ielsieslofrtsl A A TS E Note You can activate the selftest with the key operated switch too see chapter 2 4 2 5 1 11 Selftest Interval Type in the desired interval between the automatic selftests The possible range is from 0 0 hours shortest interval is 0 1 hour 6 minutes to 500 hours Choosing a value of 0 0 hours deactivates the automatic selft
13. in delta connection the program for isolated neutral must be used short circuit the terminals X6 8 with X8 11 of the RPH2 Page 20 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 3 2 1 Closing 3 2 1 1 Networks with grounded Neutral Circuit breaker closing takes place in the voltage peak in order to prevent transient processes With earthed neutral networks the obvious thing to do would be to switch offset the three phases L1 L2 and L3 in their respective voltage peak i e timewise each one about a third of the period Due to the mutual coupling of the individual phases via the iron core in three core transformers or via the low voltage winding in transformer banks this switching sequence did not have the desired effect The first phase L1 is closed in the voltage peak a quarter period after the voltage zero crossing of the reference voltage L1 N Because the first phase is laid to nominal voltage the flux in the relevant core rises also to its nominal value This flux closes via both the remaining non generated cores to each a half If closing of the two remaining phases occurs a quarter period after the first current flow can start immediately and without transient process switching sequence L1 L2 L3 3 2 1 2 Networks with isolated Neutral With an isolated neutral closing of one phase makes no sense Two phases must be closed first L2 and L3 and the obvious thing to do would be to select for th
14. indicates that the upper limit of the control voltage is reached see chapter 5 3 1 2 Control Voltage max This alarm message is available only with modules RPH2 xxA0 RPH2 xxA1 RPH2 xxA3 5 4 3 22 Temperature min This alarm message indicates that the lower limit of the ambient temperature is reached see chapter 5 3 1 5 Temperature min This alarm message is available only with modules RPH2 xxA0 RPH2 xxA1 or RPH2 xxA3 Page 59 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 5 4 3 28 Temperature max This alarm message indicates that the upper limit of the ambient temperature is reached see chapter 5 3 1 4 Temperature max This alarm message is available only with modules RPH2 xxA0 RPH2 xxA1 or RPH2 xxA3 5 4 3 24 Temp Transducer Fault This alarm message indicates an error of the temperature transducer cable or sensor i e the temperature measurement is not working This alarm message is available only with modules RPH2 xxA0 RPH2 xxA1 or RPH2 xxA3 5 4 3 25 Pressure min This alarm message indicates that the lower limit of the hydraulic pressure is reached see chapter 5 3 1 7 Pressure min This alarm message is available only for module RPH2 xxA1 or RPH2 xxA3 5 4 3 26 Pressure max This alarm message indicates that the upper limit of the hydraulic pressure is reached see chapter 5 3 1 6 Pressure max This alarm message is available only with modules RPH2 xxA1 o
15. of the three phases L1 L2 L3 for channel 1 with isolated neutral isolated Neutr grounded Neutr isolated grounded ORO OA OS dl IT ITI LE lelsisslelrist Y PEA A A ERES T_C1 Neutral grounded Type in the switching moments of the three phases L1 L2 L3 for channel 1 with grounded neutral The following two submenus are available only for module RPH2 2xx module with two switching channels T_C2 Neutral isolated Type in the switching moments of the three phases L1 L2 L3 for channel 2 with isolated neutral T C2 Neutral grounded Type in the switching moments of the three phases L1 L2 L3 for channel 2 with grounded neutral Page 41 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 5 1 6 Function Channel 1 For the module RPH2 1xxx you have to select whether if you use the RPH2 for closing or opening of the CB 5 1 7 Language Select your preferred language Available languages e German e English e French User language SNA ITE Rated Pressure Switching Program Language Time Date lt PLT TTT IL Ielsf4lslelvle Y ANA EA A RES Note You can load the menutext in any language with the RPH Tool PC based software If there any problems with the loaded language file you can return to the English menus Turn the key operated switch to OFF press the Quitt button and meanwhile return the key operated switch back to OPERATION 5 1 8 Time Date Type in the
16. p t a JU kU drive mechanism parameter The input from above results in a compensation parameter kU 36 6 With RPH2 s with two switching functions the calculation for KU1 and kU2 is to be carried out separately for both switching channels and the values stored in the RPH2 Temperature Compensation An external sensor with integrated transducer 2 conductors auxiliary voltage 24 VDC and standard output signal 4 20 mA is necessary for measuring the temperature The transducer supply is effected through the RPH2 Up to eight RPH2 s can be parallel switched to one temperature transducer See the connection plan 58 010 111 xx also The RPH2 calculates the additional times for operating time compensation according to a piecewise linear function with one control point every 10 C in the range of 50 C and 50 C So all kinds of temperature functions of the circuit breaker from linear to exponential can be set to the RPH2 The measured values can be entered in the table in figure 10 The line Delta t O ms defines the nominal operating time of the circuit breaker under normal conditions The values of Delta t at different ambient temperatures are the differences of the measured operating times to the nominal operating time The 11 values of Delta t T T 50 C to 50 C must be set to the RPH2 In the example in figure 11 the procedure is shown The measured values are marked by squares Connect the points by lines end eventuall
17. the circuit breaker This is essential for using the function of the adaptive control For devices with two switching functions RPH2 2 repeat the procedure for the second switching channel too Page 30 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 4 1 2 2 Remote reset An input for remote reset is available A potential free contact closer is necessary as control device Drive takes place with the RPH2 intern 48 VDC voltage 4 1 2 3 Real time clock synchronization 4 2 A further input is for synchronizing with a radio clock It can be parallel switched with other synchronized control devices A potential free contact is necessary Analogue Module Option A With this module the influence of environmental parameters on the pole operating time can be compensated External sensors are necessary for pressure and temperature measurement Control voltage pressure and temperature are continually measured The voltage and pressure values are immediately available for the calculation of compensation times The shown vales in the menus Measured value Control voltage and Measured value Pressure are the basic calculating factors An average value formation is carried out for temperature compensation Update takes place every two hours The stored temperature value is compared with the measured value and the stored temperature is compensated by half the difference figure 8 In the menu Measured value Tempe
18. this function see also 4 2 5 REA A N T I hielslslelzie Y UETA Page 45 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 This submenu and the following menus are available only with module RPH2 xSAx 5 2 7 1 Weighting Factor This factor defines the friction of time difference added to the operating time es IER age LLL TT TT TT Fn gapie s EESTI ERE T EE The permissible range is from 0 00 to 0 50 step 0 05 A value of 0 00 disables this function 5 2 7 2Adaptive Times CH1 Here the adaptive times for each pole related to switching channel 1 are displayed 5 2 7 3 Adaptive Times CH2 Here the adaptive times for each pole related to switching channel 2 are displayed 5 2 7 4 Reset Adaptive Times This function allows to reset the additional times due to adaptive control to zero After this the RPH2 operates with the pre set pole operating times 5 2 8 Compensation If you select NO all compensation functions are blocked If you select YES compensation is active for description see chapter 4 2 Aux Timeshi Compensatio Voltage MESES ADA PT TATE T I Eelsifbjejzla PA A 5 2 9 kU1 Voltage CH1 Type in the calculated value for compensation of changes of the control voltage see chapter 4 2 1 The permissible range is from 0 0 to 150 0 Page 46 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 Aux Timeshift CH2 Compensat
19. time tolerances contact separation should begin 1 5 ms after zero crossing at the earliest i e do not select an arcing time of longer than 8 5 ms 6 8 ms at 60 Hz About a quarter period as arcing time is regarded as standard time 3 3 4 Necessary Switching Time Accuracy For circuit breaker closing point 3 2 4 applies standard value 2 ms For circuit breaker opening the breaker should achieve an operating time accuracy of 1 5 ms 3 4 Switching of unloaded Capacitors For this switching task select the program Capacitor in the menu System Data Switching Program The switching times are specified as seen in table 1 3 4 1 Closing High inrush currents and high voltage surges can occur with the random switching of capacitors especially if switching takes place in the voltage peak The effects of parallel switching of capacitors is particularly serious Particularly high voltage surges can occur due to reflections at the end of radial networks 3 4 1 1 Networks with grounded Neutral Closing takes place in the voltage zero crossing of the related phase to earth voltage i e all phases offset one third of the period switching sequence L1 L3 L2 3 4 1 2 Networks with isolated Neutral As a unipolar switching makes no sense two phases are simultaneously closed in the voltage zero crossing of their phase to phase voltage The third phase follows a quarter period later switching sequence L2 L3 L1 Page 23 Schneide
20. voltage is also used as a reference for circuit opening The amount of phase shift between current and voltage is almost always 90 el or 90 el A deviation of 1 el creates a variation of 0 06 ms of the switching point The controller s mode of operation shown below The diagrams are only single phased and shown without transient effects which may possibly occur 1 Energizing of an inductive load in the voltage maximum Fig 1 At any point on wave whatever the control impulse is given to the RPH2 1 The next voltage zero crossing is the internal synchronizing impulse 2 Depending on the given operating time for the respective pole a time delay t d is calculated so that current starts at the required time 3 Through the unavoidable pre arcing in the circuit breaker pole the current begins before actually touching the contacts Contact touching happens at the pre arcing time after the voltage maximum optimum switching time The required pre arcing time t arc is separately adjustable for all three phases The two other phases are controlled in the same independent manner Page 18 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 Figure 1 System voltada N 7 J N E SC E m E E x l P Current AS A A ZL Ne Ew t arc CB ON command to RPH2 td CB operating time Command by RPH2 CB main contact L T T1 T T1 gt t arc pre ar
21. 034 E Schneider Electric Energy Austria AG Leonding 2011 02
22. 2 conductor constructions auxiliary voltage 24 VDC and standard output signal 4 20 mA are necessary The supply for the transducer bank is effected by the RPH2 Up to 8 RPH2 s can be switched in parallel on one temperature sensor When measuring pressure an individual transducer is necessary for each circuit breaker option A1 or each circuit breaker pole option A3 The measuring range of the measuring instruments depends on the requirements and can be simply parameterized in the RPH2 Three types of this additional module are available 2 3 3 1 Option AO Measuring and compensation of control voltage and temperature for springloaded drives Page 9 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 2 3 3 2 Option A1 Same design as 2 3 3 1 however with additional measurement and compensation for hydraulic pressure for hydraulic drives which have a mutual pressure generation for all three poles 2 3 3 3 Option A3 Like 2 3 3 2 however for circuit breakers which have pressure generation per pole 2 3 3 4 List of available models RPH2 1 RPH2 1S RPH2 11 RPH2 1A0 RPH2 1A1 RPH2 2 RPH2 2S RPH2 21 RPH2 2A0 RPH2 2A1 RPH2 1A3 RPH2 1SI RPH2 1SA0 RPH2 1SA1 RPH2 1SA3 RPH2 2A3 RPH2 28Sl RPH2 2SA0 RPH2 28A1 RPH2 2SA3 RPH2 1SIAO RPH2 1SIA1 RPH2 1SIA3 RPH2 2SIA0 RPH2 2SIA1 RPH2 2SIA3 2 4 Elements on the front of the device The device identification is located on the right side of the grip ra
23. ED off alarm output not active Alarm is not reset obligatory Setting 0 Alarm is active gt LED has steady light alarm output active Alarm off gt LED off alarm output not active Page 54 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 Note With the function reset obligatory you can change an alarm message from the type pulse type to a steady alarm type see 5 4 3 5 4 2 Lock Out Here you can mark each of the 7 alarm outputs to produce a blocking of the device in case of the corresponding alarm occurs That means No switching operation is possible the green LED is dark and the contact Device not ready X6 12 13 is closed Some actions or alarms cause a lock out in any case also without activating the responding alarm green LED dark contact X6 12 13 is closed e Keyswitch is OFF Relay starting up Reference voltage is missing Frequency not in permitted range Neutral earthing switch in intermediate position Example MESAS Reset obligatory Lock out Alarm List MARA LLELLTLTLLLLIeIst4flelia Y SESS Sie AE ee In the example mentioned above the activating of alarm 3 blocks the RPH2 No operation is possible as long as the alarm is active The output contact Device not ready X6 12 13 is closed 5 4 3 Alarm List The following submenus are depending on the configuration of the RPH2 Each internal alarm message can be assigned to up to 7 al
24. ETE ESI 5 5 2 4 Measured Operating Time This submenu shows the measured operating times assuming that the values for Aux Timeshift CH1 CH2 see 5 2 5 5 2 6 and 4 1 2 1 have been determined correctly IAS STER ERES Command OUT CB Signal received Calculated Op Time Measured Op Time BEES 9 129 an TERT 9ms Eo espro peajes This submenu is available only with module RPH2 xxxS Note The resolution of the time measurement is 0 1 ms For RPH2 with software version J006 x a new function for easy setting of the values for Aux Timeshift is available After a switching operation of the circuit breaker position the cursor in the menu Measured Op Time and press the ENTER button repeatedly to initialize the automatic setting procedure The cursor will first move to the value L1 of the bottom display line then to L2 and L3 At last the message OK YES_NO is displayed Press ENTER once again and the settings in the appropriate Aux Time shift CHx are automatically set to values necessary for correct operation For devices with two switching functions RPH2 2 repeat the procedure for the second switching channel too Page 62 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 5 5 3 Frequency This submenu shows the actual frequency of the reference voltage The resolution of the frequency measurement is 0 05 Hz Measurement Current Graphs Measured Times
25. Frequency Current RMS INSERERE DENIED SE III IT llelsi Wslelrist ana ES Ea Ae ES The switching moments switching programs are permanently corrected according to the measured frequency Note The measurement of the frequency works only when the reference voltage is connected If the reference voltage is missing the rated frequency is displayed instead 5 5 4 Current RMS This submenu shows the actual measured line current per phase Measurement f Measured Times Frequency Current RMS Control Voltage AAA A III TTT Eelsifbjejzia ELA ETE IET ESI E This submenu is available only with module RPH2 xxl 5 5 5 Control Voltage This submenu shows the actual measured control voltage Measurement Frequency Current RMS Control Voltag Actual This submenu is available only with modules RPH2 xxA0 RPH2 xxA1 RPH2 xxA3 Page 63 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 5 5 6 Actual Temperature This submenu shows the actual measured ambient temperature Measurement a a Current RMS Control Voltage Actual Temperature Temperature f Comp Hzc ee ES al JIII hiellslel7 e MA E IET This submenu is available only with modules RPH2 xxA0 RPH2 xxA1 RPH2 xxA3 5 5 7 Temperature for Compensation This submenu shows the averaged environmental temperature see chapter 4 2 Measurement Control Vol Actual Temp Te
26. Point on Wave Controller Series RPH2 Service Manual 58 020 034 E Schneider RPH2 Service Manual CONTENTS 1 IN GENERAL 6 1 1 Handling of electronic equipment 6 1 2 Unpacking 6 1 3 Storage 6 1 4 Installation 6 1 5 Technical data 7 2 INTRODUCTION 8 2 1 Using the handbook 8 2 2 Models available Assembly 8 2 3 Additional modules 8 2 3 1 Signal module Option S 8 2 3 2 Current measurement module Option 9 2 3 3 Analogue module Option A 9 2 3 3 1 Option AO 9 2 3 8 2 Option A1 10 2 3 3 3 Option A3 10 2 3 3 4 List of available models 10 2 4 Elements on the front of the device 10 2 4 1 Graphic display 10 2 4 1 4 Setting Contrast of LC Display 10 2 4 2 Key operated switch 11 2 4 2 1 Position OFF 11 2 4 2 2 Position OPERATION 11 2 4 3 LED indicators 11 2 4 3 1 LED READY green 11 2 4 8 8 LED 1 to 7 red 11 2 4 4 Keys 12 2 4 5 Serial interface 12 2 5 Menu system 12 2 5 1 Menu structure 14 3 APPLICATION NOTES 16 3 1 General Description of the Functions 16 3 1 1 Synchronized switching 16 3 1 1 1 Closing 16 3 1 1 2 Opening 17 3 1 2 Circuit breaker 17 Page 1 74 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 23 Compiled Approved File code 2011 02 23 2011 02 23 EPS U Samitz VMSO K Bauer RPHDOC E DOC 3 1 3 RPH2 structure 17 3 1 4 Function of the RPH2 18 3 1 4 1 Energizing of an inductive load in the voltage maximum Fig 1 18 3 1 4 2 Bre
27. T Rated UNIS Cie Rial end ECUS tene ActualContr Voltage EAN A N T I hielslslelzie Y TETA This submenu is available only for module RPH2 xxl Note The current transformer has to be connected to the correct terminal of the RPH2 1 A or 5 A see wiring diagram Page 51 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 5 3 4 Actual Control Voltage Type in the measured value of the actual control voltage This input calibrates the internal voltage measurement This value acts as base for the calculation of compensation of the switching moment The permissible range is from 35 V to 300 V ie ai Sa CT Rated Curr prim CT Rated Curr sec ActualContr Voltage Temperature 112 2 Y A TT I hielslslelzie Y AR eme A This submenu is available only with modules RPH2 xxA0 RPH2 xxA1 RPH2 xxA3 Determine the correct value Measure the actual value of the control voltage on terminal X6 10 and X6 11 with an calibrated voltmeter and type in this value Type in the determined value Note This input calibrates the voltage measurement function The correct input of this value is absolutely necessary You cannot calibrate the RPH2 with the PC software RPH Tool In the Normal Mode Ready LED is steady light the measured voltage is displayed After calibrating the voltage measurement check the correct function by monitoring the display 5 3 5 Temperature The following submenu
28. The circuit breaker auxiliary contacts signalling contact 52a works with an internal RPH2 voltage 48 VDO i e potential free contacts are necessary The necessary wiring is to be carried out according to the accompanying wiring diagram Figure 5 CB main contact closing CB aux At contact CB main opening contact CB aux At contact time To compensate the time shift between the main contacts and the auxiliary contacts of the breaker poles the possibility exists to feed in a compensation time in order to maintain the operating time as real value on the display and in the archives Figure 5 shows the correlation as an example If the auxiliary contact closes after the main contact then the compensation time value At is negative if the auxiliary contact opens before the main contact then a positive value results If no possibility exists to measure the time shift of the auxiliary contacts this value can also be determined via the RPH2 within the time release limits Conditions e The pole operating times given by the manufacturer are correctly fed in see 5 1 and 5 2 Page 29 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 e The environmental conditions correspond approx to the conditions when measuring the pole operating times in the factory With strong deviations in the environmental conditions the pole operating times must be measured again on site e The RPH2 compens
29. Un 2 5 ms at Y2 V2 Un and 4 5 ms at 1 5 V 2 3 Un 3 2 3 2 Opening Data of the optimum arcing time in order to guarantee a sure current breaking in the next zero crossing See 3 3 3 for further information 3 2 4 Necessary Switching Time Accuracy With regard to the accuracy of the switching time closing in the voltage peak is not so critical By closing at 1 ms before or after the peak the voltage still amounts to 95 96 of the peak value at 2 ms at least 81 valid for 50 Hz Therefore an accuracy of 2 ms at 50 Hz or 60 Hz is sufficient See 3 3 4 for opening values 3 3 Switching of Reactor Groups For this switching task select the program Reactor in the menu System Data Switching Program The switching times are specified as seen in table 1 If the RPH2 is only to be used for opening then this program can also be used to switch three core reactors switching moments are identical to the transformer program 3 3 1 Closing 3 3 1 1 Networks with grounded Neutral Closing takes place in the voltage peak in order to prevent transient processes With grounded neutral networks the three phases L1 L2 and L3 are closed in their respective voltage peak i e timewise each one offset about a third of the period as there is no coupling between the phases switching sequence L2 L1 L3 3 3 1 2 Networks with isolated Neutral Closing runs according to the same principles as in the program for transformers see 3 2 1 2
30. ady The RPH2 Point on Wave Controller is assembled in a modular system The function can be extended through the combination of various modules Extending the function at a later date is only possible by the manufacturer The casing is a standard 19 inch sub rack with half width for one device or alternatively with full width for 2 devices After removing the 4 external screws of the front panel the plug in unit on the grip rail can be removed from the housing Safety notes see 1 1 Additional modules 2 3 1 Signal module Option S This module offers 6 alarm outputs alarm 2 to alarm 7 and 6 optoelectronic coupler inputs Inputs 1 3 serve as circuit breaker monitors via its auxiliary contacts With this the pole operating times can be measured Resolution 0 1 ms Input 4 serves as an input for a remote reset Inputs 5 and 6 are not in use at present A further input is used for synchronizing with a radio clock It can be switched in parallel with other Point on Wave Controllers Page 8 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 2 3 2 Current measurement module Option With this the phase currents during the switching process can be recorded and graphically displayed Data from the last 4 switching operations curves amplitudes are stored in a non volatile memory and can be analysed on the display Primary values are shown after feeding in the current transformer ratios 2 3 3 Analogue modul
31. aking of an inductive current 19 3 1 4 8 Switching program 20 3 2 Switching of Transformers and Reactors 20 3 2 1 Closing 21 3 2 1 1 Networks with grounded Neutral 21 3 2 1 2 Networks with isolated Neutral 21 3 2 2 Opening 21 3 2 3 Data on circuit breaker required 21 3 2 8 1 Closing 21 3 2 3 2 Opening 22 3 2 4 Necessary Switching Time Accuracy 22 3 3 Switching of Reactor Groups 22 3 3 1 Closing 22 3 3 1 1 Networks with grounded Neutral 22 3 3 1 2 Networks with isolated Neutral 22 3 3 2 Opening 22 3 3 3 Data on circuit breaker required 22 3 3 3 1 Closing 23 3 3 3 2 Opening 23 3 3 4 Necessary Switching Time Accuracy 23 3 4 Switching of unloaded Capacitors 23 3 4 1 Closing 23 3 4 1 1 Networks with grounded Neutral 23 3 4 1 2 Networks with isolated Neutral 23 3 4 2 Opening 24 3 4 3 Data on circuit breaker required 24 3 4 4 Necessary Switching Time Accuracy 27 3 5 Switching closing of uncharged Lines 28 4 FUNCTIONS OF THE ADDITIONAL MODULES 29 4 1 Signal Module Option S 29 4 1 1 Alarm outputs 29 4 1 2 Opto coupler inputs 29 4 1 2 1 Measuring the operating time 29 4 1 2 2 Remote reset 31 4 1 2 3 Real time clock synchronization 31 4 2 Analogue Module Option A 31 4 2 1 Control Voltage Compensation 32 4 2 2 Temperature Compensation 33 4 2 3 Hydraulic Pressure Compensation 35 4 2 4 Specifications for the external sensors 37 4 2 5 Adaptive Control 37 4 3 Current Module Option 38 5 RPH2 MENUE SYSTEM 39 Page 2 Issu
32. alled in the casing no safety measures are necessary at all Unpacking Despite the general robust construction of the Point on Wave Controller it must be handled with care before installation Before accepting the Point on Wave Controller it should be checked for damage which could have originated during transportation If you have cause for complaint please refer to the transport company and notify a person responsible at Schneider Electric Storage If the Point on Wave Controller is not to be installed immediately upon receipt it should be stored in a place which is free of dust and moisture in its original packaging If a moisture absorption bag is in the packaging leave it as it is The effectiveness of the drying agent is impaired if the non protected bag is subjected to the surrounding conditions Before the Point on Wave Controller is placed in the box again warm the drying bag slightly in order to regenerate the drying agent Storage temperature 40 C to 70 C Installation The RPH2 Point on Wave Controller can either be installed in a switchboard or a suitable frame with the provided material panel cut out see diagram 58 001 115 Page 6 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 1 5 We suggest the control room or the relays room as the most favourable installation site Installation in a heated outdoor control cubicle is also possible Installation directly in the operating
33. amentally treated like capacitors Due to the inter phase coupling the switching moments are not the same as for capacitor banks The RPH2 can also be used for auto reclosing of uncompensated lines equipped with inductive potential transformers During the auto reclose dead time the trapped charges on the line must be fully discharged by the inductive potential transformers Whether the system neutral is earthed or isolated does not effect the switching moments The RPH2 must be set to the User Program with the following settings see also 5 1 5 1 For T_C1 Neutral isolated and for T_C1 Neutral grounded the same values must be set 50 Hz L1 0 ms L2 7 3ms L3 13 3ms 60 Hz L1 0 ms L2 6 1ms L3 11 1ms Page 28 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 FUNCTIONS OF THE ADDITIONAL MODULES Signal Module Option S Alarm outputs The module offers additional outlets alarm 2 to 7 Each alarm contact corresponds with the associated indicator LED LED 2 to 7 at the front The allocation of the alarm functions to the output contacts is user defined Many alarm functions can be laid to one output The procedure is described in chapter 5 Opto coupler inputs Opto coupler inputs with pre defined functions are available 4 1 2 1 Measuring the operating time Three inputs serve to measure the operating time of the three poles via their auxiliary contacts Resolution 0 5 ms
34. arm outputs The assignment is made through the setting of a 1 at the corresponding display unit Example Eee as Frequency min Frequency max Current max peak mm Voltage Failure 00100100 na MAA AA O ES Page 55 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 In the example mentioned above the alarm message Current max peak is assigned to alarm output 3 and alarm output 6 The asterisk at the position Ref Voltage Failure in the picture above indicates that the fault Ref Voltage Failure is pending that means the reference voltage is missing Pulse alarm If an alarm message is a pulse this alarm message is active only for a period of 0 5 seconds If this alarm message is assigned to an alarm output which is marked as reset obligatory the alarm output remains active until this alarm is acknowledged Note The assignment of an alarm message to the alarm output number 8 has no effect 5 4 3 1 Lock out This is only a summary alarm It is generated by other alarms which cause a blocking of the relay It is active when the device is blocked see 5 4 2 The alarm itself causes no blocking of the device 5 4 3 2 Frequency min The reference voltage phase L1 is monitored permanently If the lower limit of the frequency is reached an alarm message Frequency min is generated Limits Rated Frequenc 50 Hz 45 Hz 60 Hz 54 Hz 16 2 3 Hz 15Hz Not
35. ating function is deactivated see 5 6 e The circuit breaker can be operated repeatedly without load with opened busbar disconnector Operate the circuit breaker via the RPH2 with channel 1 Check that password is active flashing READY LED Change to the menu Measurement Measured Times In the menu Measured Op Times Figure 6 the measured pole operating times appear in the status line including the main contact auxiliary contact time shift Figure 6 Measurd Times ts UA Pole operating times CB Signal Received Calculated Op Times L1 139 3 ms gt Measured Op Time L2 138 7 ms 146 5 145 6 146 1ms L3 139 6 ms AIII mielslstsfts E AAA TIE The value for Aux Timeshift CH1 for every pole is calculated with Aux Timeshift CH1 Pole operating time Measured Op Time The input values in figure 7 are calculated with the values form figure 6 and the values of the pole operating times shown on the right side in figure 6 Feed in the determined values under CB Data Aux Timeshift CH1 figure 7 Figure 7 CB Data Arcing Time CH1 Arcing Time CH2 gt Aux Timeshift CH1 Aux Timeshift CH2 a 2 6 9 6 5ms FETT TT TT be lelsi4 ste 7 s Y SS ae SN ES For RPH2 with software version J006 x a new function for easy setting of the values for Aux Timeshift is available see 5 5 2 4 Check in all cases that the measured operating time corresponds with actual operating times of
36. ching tests Page 25 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 Note The system voltage in the following formulas is related to one interrupting chamber of the circuit breaker take care in case of breakers with multiple interrupting chambers The voltage across one interrupting chamber is calculated as follows where m is the number of interrupting chambers of one pole 1 05 m Un U nia Un Voltage for one interrupting chamber system voltage rms for one interrupting chamber peak value neutral grounded for all poles peak value neutral isolated for the two first poles L2 and L3 peak value neutral isolated for the last pole L1 rate of fall of system voltage rate of fall of CB withstand voltage see figure 3 variation of CB closing time prearcing time set to RPH2 AT U sin u earcing voltage gt sin TL kV pn g voltag The following example demonstrates the calculation for the pre arcing time for each pole with various system neutral treatments Page 26 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 3 4 4 Example Un 145 kV uw 118 4 kV u 102 5 kV u 177 6 kV du 37 2 kV ms dt ae 32 22 kV ms dt 20 55 8 kV ms dt 100 kV ms k 2 7 p u k 3 1 p u k 1 8 p u AT 1 ms ta 0 4 ms ta 0 3 ms ta 0 5 ms system voltage rms peak value neu
37. chneider Electric Energy Austria AG Leonding 2011 02 6 1 3 First operation When all inspections are done operate the dead circuit breaker via the RPH2 On Point on Wave Controllers with option S check if the measured operating times are correct otherwise adjust the values for Aux Timeshift according to 4 1 2 1 Prove that the command impulse to the RPH2 is of sufficient length For the first load switchings we recommend using an oscillograph to measure the currents of the three phases together with the reference voltage in order to verify that the unit is working correctly It is helpful if the three relayed drive commands can also be recorded on additional oscillograph traces By using a RPH2 with the option the currents during switching can be displayed and analysed see 5 5 1 If the results are not satisfactory you must adapt the pole operating times and or the arcing times to achieve the optimal function Page 71 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 Configuration Checklist RPH2 System Data System Frequency O 16 2 3 Hz O 50 Hz O 60 Hz Control Voltage 48V 250V 2255 V Rated Pressure eee bar Switching program O Transformer O Shunt Reactor O Capacitor Bank O User Program ICC TT TGrwwawmm Toi Newrt rounded fm Tomum fm ICE fT Function Channel 1 O CB Close O CBOpen RPH2 1xx only Language O German O English O French
38. cing time of CB time t d delay time of RPH2 3 1 4 2 Breaking of an inductive current At any point on wave whatever the control impulse is given to the RPH2 1 The next voltage zero crossing is the internal synchronizing impulse 2 Depending on the given operating time for the respective pole a time delay t d is calculated so that contact separation occurs at the required time 3 In the time between contact separation and the following current zero crossing the contacts have separated so far that after the current breaking in the zero crossing 4 an adequate contact gap exists to withstand the transient recovery voltage The required arcing time t arc is separately adjustable for all three phases The two other phases are controlled in the same independent manner Figure 2 System 2 A ne z ye ES SES voltage Nea p N F I f yi K E XC l Y 3 N PES uo alee Current X 2 A 3 NL pw N tarc 1 CB OFF command to RPH2 f td CB operating time gt Command by RPH2 CB main contact LT TT T1 Lr time t arc arcing time of CB t d delay time of RPH2 Page 19 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 Whether the system neutral is grounded or isolated the RPH2 registers the signal contacts of the neutral earthingswitch and automatically selects the correct switching time 3 1 4 3 Switching program 3 2 The RPH2 already
39. e 6 1 1 2 Necessary Settings Before the RPH2 is ready to operate all relevant settings must be completed These data must be set before the first operation depending on the model System frequency 5 1 2 Control voltage 5 1 3 Rated pressure 5 1 4 Switching program 5 1 5 Function channel 1 5 1 6 Operating times of each pole 5 2 1 5 2 2 Arcing Times 5 2 3 5 2 4 All data for compensation and adaptive control 5 2 7 5 2 16 Actual control voltage 5 3 4 Ratings of external transducers 5 3 5 5 3 6 Page 69 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 All other parameters are not essential for operation To evaluate the necessary data use the configuration checklist shown on the last pages of this service manual Inspection Check whether the external wiring corresponds to the relevant RPH2 wiring diagram Particularly whether the reference voltage and the neutral earthing switch position signals are wired If a switching of the neutral is not intended then it is necessary to short circuit the relevant input terminals of the RPH2 X6 8 with X8 11 for neutral isolated or X6 8 with X8 12 for neutral grounded Make sure that the case is properly earthed If external sensors are necessary they are to be installed according to the manufacturer s information Check whether the plug in unit is sitting firmly and the fixing screws are tightened Measure the actual RPH2 co
40. e One Option A1 or three Option A3 external sensors with integrated transducer 2 conductors auxiliary voltage 24 VDC and standard output signal 4 20 mA are necessary for measuring hydraulic pressure The transducer supply is effected through the RPH2 Page 35 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 The RPH2 calculates the additional times for operating time compensation according to a function with one open parameter By fixing this parameter the compensation function can be suited to the character of the circuit breaker Calculation for opening and closing takes place separately The parameter kP1 works for switching channel 1 kP2 for switching channel 2 only for devices with 2 switching functions For the model with option A3 with pressure measuring per pole only a compensation parameter for each of the three poles is fed in If a zero value is fed in for a parameter then no additional times are calculated and the compensation function concerned is blocked Fixing the compensation parameters takes place through calculation or with the assistance of the accompanying PC Software Two measuring points of the switching characteristic analogue for 4 2 1 are required to calculate the equalising curve e One point with rated conditions value 1 measured pole operating time of one pole with rated voltage rated pressure and rated temperature In general that is the manufacturer value for pole
41. e Option A Independent of the breaking system and the kind of operating mechanism the operating times of a circuit breaker change in dependence on certain service parameters With reduced control voltage at the circuit breaker coil there is less energy available to change the electrical control commands into a mechanical action The operating time extends itself Valid for all types of operations By altering the hydraulic pressure on hydraulic drives the energy available to carry out the switching movement changes The ambient temperature is the most complex parameter of influence The electrical resistance of the trip coils the oil viscosity and the pressure of the SF6 gas are dependent on the temperature In addition changes of length in the driving linkage and the porcelains occur All these parameters influence the operating time in different ways In the extreme each of these 3 parameters can alter the operating time by some milliseconds The RPH2 with option A is in the position to compensate these operating time alterations There are inputs available for the measurements acquired when measuring the control voltage pressure and temperature for the compensation of pole operating times The control voltage is measured directly in the RPH2 at the input terminals for the auxiliary voltage There are no external measuring devices necessary For measuring pressure and temperature external sensors with integrated transducer banks
42. e The monitoring of the frequency is active only if the reference voltage is connected to the device If the reference voltage is missing no alarm Frequency min is generated 5 4 3 8 Frequency max The reference voltage is monitored permanently on phase L1 If the upper limit of the frequency is reached an alarm message Frequency max is generated Limits Rated Frequenc 50 Hz 55 Hz 60 Hz 66 Hz 16 2 3 Hz 18 26 Hz Note The monitoring of the frequency is active only if the reference voltage is connected to the device If the reference voltage is missing no alarm Frequency min is generated Page 56 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 5 4 3 4 Current max peak This alarm message is generated if the setting of the current maximum peak value is reached or exceeded during a switching operation in one or more phases thresholds see 5 3 1 1 The peak value of the current is monitored not the RMS value This alarm message is a pulse see chapter 5 4 3 Pulse alarm This alarm message is available only for module RPH2 xxl 5 4 3 5 Heference Voltage Failure This alarm message is generated if the reference voltage is missing for more than 2 seconds Note This alarm message blocks the RPH2 in any case regardless whether the alarm is set for blocking or not see chapter 5 4 2 5 4 3 6 RTC Impulse Failure This alarm message is generated if the minute pulse is missi
43. e dU at dUg dt gt dU at k gt 1 Figure 3 t 1 interrupter dielectric strength lower than dU dt of system voltage 2 interrupter dielectric strength equal dU dt of system voltage 3 interrupter dielectric strength greater than dU dt of system Page 24 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 However some pre arcing may be inevitable due to variations in the closing time and the spread in dielectric withstand To minimise energizing transients the closing should aim at an instant ty after the voltage zero the RPH2 takes this into account through a given arcing time If data is not available from the breaker manufacturer the pre arcing time can be approximated Modern breakers have closing contact speeds of typical 5 m s and a dielectric strength of more than 20 kV mm That results in a fall rate dUg dt of more than 100 kV ms Figure 4 shows the voltage across the open contact gap and the withstand voltage fall with varying closing times The arcing time t4 is calculated so that the withstand voltage is approx the same value as the upper and lower operating time tolerance Figure 4 Ua T voltage across the open contact gap and withstand voltage fall with varying closing time T EAT The RPH2 arcing time setting can be calculated according to the following formulas Take note of the differing arcing times with isolated neutrals The calculations must be verified by swit
44. e 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 5 1 System data 39 5 1 1 Password 39 5 1 2 System Frequency 39 5 1 3 Control Voltage 40 5 1 4 Rated Pressure 40 5 1 5 Switching Program 40 5 1 5 1 User Program 41 5 1 6 Function Channel 1 42 5 1 7 Language 42 5 1 8 Time Date 42 5 1 9 New Password 42 5 1 10 Selftest Start 43 5 1 11 Selftest Interval 43 5 2 CB Data 44 5 2 1 Operating Time CH1 44 5 2 2 Operating Time CH2 44 5 2 8 Arcing Time CH1 44 5 2 4 Arcing Time CH2 45 5 2 5 Auxiliary Timeshift CH1 45 5 2 6 Auxiliary Timeshift CH2 45 5 2 7 Adaptive Control 45 5 2 7 1 Weighting Factor 46 5 2 7 2 Adaptive Times CH1 46 5 2 7 8 Adaptive Times CH2 46 5 2 7 4 Reset Adaptive Times 46 5 2 8 Compensation 46 5 2 9 kU1 Voltage CH1 46 5 2 10 kP1 Pressure CH1 47 5 2 11 Temperature Compensation CH1 47 5 2 12 Table Temp CH1 47 5 2 12 1 Delta t xx C 47 5 2 13 kU2 Voltage CH2 48 5 2 14 kP2 Pressure CH2 48 5 2 15 Temperature Compensation CH2 48 5 2 16 Table Temp CH1 48 5 2 16 1 Delta t xx C 48 5 3 Analogue Data 48 5 3 1 Thresholds 48 5 3 1 1 Current max 48 5 3 1 2 Control Voltage max 49 5 3 1 3 Control Voltage min 49 5 3 1 4 Temperature max 49 5 3 1 5 Temperature min 50 5 3 1 6 Pressure max 50 5 3 1 7 Pressure min 50 5 3 2 CT Rated Current prim 51 5 3 8 CT Rated Current sec 51 5 3 4 Actual Control Voltage 52 5 3 5 Temperature 52 5 3 5 1 Value at 4 mA 52 5 3 5 2 Value at 20 mA 53 5 3 6 Pressure 53
45. e switching time the voltage peak of the phase to phase voltage i e zero crossing of the reference voltage L1 N Switching on the third phase occurs about a quarter period later at the peak of voltage L1 switching sequence L2 L3 L1 3 2 2 Opening For switching off transformers and three leg reactors with the RPH2 please read point 3 3 2 Switching off Reactor Groups 3 2 3 Data on circuit breaker required The following data on the circuit breaker are absolutely necessary to operate the RPH2 The mechanical closing and or opening operating time of the three circuit breaker poles see 3 1 2 for definition Accuracy about 0 1 ms 3 2 8 1 Closing For closing at the correct time the pre arcing time of the breaker at the closing voltage see table 2 according to the phases and the treatment of the system neutral Table 2 Closing Voltage Un system voltage rms Neutral Grounded Neutral Isolated v 2 3 Un 1 5 2 3 Un 5 Y2 Un Y2 Un Y2 Un i2 Un If the exact value cannot be obtained from the breaker manufacturer the optimum closing time can be determined through switching tests with oscillographical measurements of the inrush currents For RPH2 with option the inrush currents are directly shown by the device curve course and peak value For the tests it is advisable Page 21 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 to begin with an assumed pre arcing time of 3 ms at V 2 3
46. enu is available only for module RPH2 xxA0 RPH2 xxA1 RPH2 xxA3 5 3 1 6 Pressure max Type in the upper limit of the hydraulic pressure of the CB If the measured value of the temperature becomes higher than the limit an alarm is generated The permissible range is from O bar to 1000 bar E O A Temperature max Temperature min Pressure max Pressure min 350bar B A T I hielslslelzie Y NAAA This submenu is available only with modules RPH2 xxA1 RPH2 xxA3 5 3 1 7 Pressure min Type in the lower limit of the hydraulic pressure of the CB If the measured value of the temperature becomes lower than the limit an alarm is generated The permissible range is from O bar to 1000 bar Page 50 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 MA gt Temperature max Temperature min Pressure max Pressure min 180bar E IIIT T I hieljaislel7ie UETAN This submenu is available only with modules RPH2 xxA1 RPH2 xxA3 5 3 2 CT Rated Current prim Type in the rated primary current of your current transducer The permissible range is from 0 A to 5000 A we eg Tresholds CT Rated CURED ered CT REALECO CUr S06 ActualContr Voltage ev A HESSE SERE EE This submenu is available only with module RPH2 xxl 5 3 3 CT Rated Current sec Type in the rated secondary current of your current transducer Permissible values are 1 A and 5 A A nioo Tresholds C
47. ers The measuring range of the sensors adjust itself to the respective requirements However unnecessarily large measuring ranges reduce the measuring accuracy of the RPH2 The RPH2 measuring input is adapted to the measuring range of the sensor through parameterisation Transducer installation is carried out according to the manufacturer s guidelines Likewise the connection cables to the RPH2 must be selected according to the manufacturer s information If no information is available we recommend a shielded two wire cable per transducer or at least a twisted pair of wires 4 2 5 Adaptive Control RPH2 with analogue module A and signal module S provide the additional feature of an adaptive control to compensate the long time drift in operating time of the CB drive The actual operating times of the poles are measured by the signal module A weighting factor in the range of 0 to 0 5 step 0 05 0 function is disabled is used for controlling this function A fraction depending on the weighting factor of the time difference between the operating time of the last operation and the operation before is added to the actual operating time Additional operating times due to compensation functions are not taken into consideration so the pure long time drift of the drive mechanism is compensated The additional adaptive times are displayed and a function is available to reset these times The compensation of the time shift between the main contact
48. es place through calculation or with the assistance of the accompanying PC Software Two breaker characteristic measured points are required to calculate the compensation function e One point with nominal conditions value 1 measured pole operating time of one pole with rated voltage rated pressure and rated temperature In general that is the manufacturer value for pole operating time e A second point with deviation conditions value 2 measured pole operating time of the same pole with rated pressure rated temperature and reduced control voltage Figure 9 shows an example of a circuit breaker opening Value 1 with nominal conditions Uy 220 VDC Rated control voltage ty 27 0 ms Pole operating time with nominal conditions Value 2 Us 180 VDC Reduced control voltage b 29 2 ms Pole operating time with control voltage U2 Figure 9 32 1 J Function calculated pr RPH2 31 30 vr Value 2 U2 t2 o g 29 E D Ss 28 I o le 27 Value 1 Ut t1 26 140 160 180 200 220 240 Operating Voltage V a Page 32 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 4 2 2 The compensation parameter kU can be calculated using the following formula Value 1 Ui V rated control voltage ti ms CB operating time at nominal conditions Value 2 U V reduced control voltage t ms CB operating time with U2 _ t2 100 Ui
49. est facility ISO ONE Sia Time Date New Passwo rd Sree tessa Sra nt SOlftest NEAR PTT TT TY LIII Hue MECA AA IPSE E In the menu Aux Functions Error Type the type errors are displayed see 5 6 3 Page 43 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 5 2 CB Data 5 2 1 Operating Time CH1 Type in the operating time for each phase at the rated voltage rated pressure and a temperature of 20 C for switching channel 1 The permissible range is from 0 0 ms minimum value is 0 1 ms to 200 ms The switching function closing or opening for module RPH2 1xx depends on the selection made in the submenu Function Channel 1 see chapter 5 1 6 Module RPH2 2xx uses channel 1 for closing of the CB Operating T Operating T ime ime Arcing T CH1 AN eM fn C 1 NAAA EEENEEEENEENHUESBRSSHONENN NOA Hes ERE ERIS ERSTER Lad Note 1 The value of the operating time for each phase of the CB depends on the type and manufacturer of the CB This value is part of the CB documentation delivered with your CB Note 2 The difference between 2 phases should be less than one period 20 ms for 50 Hz Note 3 For single phase CBs the values for all three phases must be the same 5 2 2 Operating Time CH2 Type in the operating time for each phase at the rated voltage rated pressure and a temperature of 20 C for switching channel 2 Channel 2 always is used for opening The per
50. has several preconfigured switching programs for various uses The treatment of the system neutral of the network is automatically taken into consideration The trigger point for the switching times is the beginning of the period that is determinated by the zero crossing of the voltage L1 N reference voltage The given delay times in table 1 are given in milliseconds after the trigger point They show the moment where current flow begins or ends point 4 in figures 1 and 2 The RPH2 automatically takes pre arcing and breaking times into account The following programs are available e Transformer transformer transformer bank three core reactor e Reactor reactor group e Capacitor bank e Free program The following table is based on a phase sequence of the network of L1 reference L2 reference 120 L3 reference 240 Table 1 Delay times of the various switching pro grams Switching programs Delay time a Transformer GROUNDED ISOLATED CLOSING 542 o 4 0 7 Reactor 17 Capacitor o ois ws HER eee 5 4 2 The free Pe enables the user to select whatever switching time for both switching functions if available and for both types of neutral treatment Values in for 60 Hz Switching of Transformers and Reactors For this switching task select the program Transformer in the menu System Data Switching Program The switching times are specified as seen in table 1 For transformers with primary windings
51. he input procedure to be repeated After completing the input turn the key operated switch to OFF and then to OPERATION or start the selftest via the menu After the selftest the data in the system is accepted The following pages show a list of all the available menu points The cross references to the chapter with the detailed function description are in the column Chapt The column Module shows with which model variation this menu is available The following coding system applies 1 RPH2 with one switching function 2 RPH2 with two switching functions Ax Analogue module in all models with module A A1 Analogue module e g Option 1 Current measuring module Option S Signal module Option S Menu points without a particular task are available on all models Page 13 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 2 5 1 Menu structure Chapter Module Level Level2 Level3 5 1 1 51 SystemData poo Password 512 sd System Frequency 353535 513 Ax ControlVoltage Pp 5 14 Ax Rated Pressure Page 14 Pp Switching Program PEN Function CHi J ___ AAA B Data A Operating Time CH1 Operating Time CH2 AE PP ooo Adaptive Times CH1_ ooo Adaptive Times CH2 o eset Adaptive Times Compensation 1 kU1 Voltage CH1 kP1 Pressure CH1 Temp Comp CH1
52. il The top line shows the model variation code and the serial number is located on the line beneath With any queries or questions please state both numbers 2 4 1 Graphic display To show the adjusted and measured values The top line shows each active menu point Underneath four menu lines appear The last line under the drawn line is the status line The feed in or measured values appear here The digits which are pressed into the front panel underneath the display indicate the positions for setting the alarms Password System Frequency Control Voltage Rated Pressure 0000 HESS I T i T heshlslelzis Y EETA 2 4 1 1 Setting Contrast of LC Display Turn key operated switch to OFF Press the Enter button and hold it Turn the key operated switch to OPERATION The contrast changes within its limits from dark to light When the optimal contrast for your requirements is reached release the Enter button Page 10 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 Note The whole contrast range of the display is adjustable Therefore the display becomes nearly transparent or dark respectively for a moment The selected contrast is stored in a non volatile memory 2 4 2 Key operated switch 2 4 2 1 Position OFF The RPH2 is blocked No switching operation is possible The green LED READY is extinguished and the alarm contact Device not Ready X6 12 13 closes 2 4 2 2
53. ion kU1 Voltage CH1 kP1 Pressure CH1 SIONES ASA AAA PT LETT LL I hielstslelzie AAA A ae This submenu is available only with modules RPH2 xxA0 RPH2 xxxA1 RPH2 xxxA3 5 2 10kP1 Pressure CH1 same as 5 2 9 but for pressure compensation for channel 1 This submenu is available only with modules RPH2 xxxA1 RPH2 xxxA3 5 2 11 Temperature Compensation CH1 This submenu enables or disables the temperature compensation kU1 Voltage CH1 kP1Presure CH1 Temp Comp cCH1 Table Temp CH 1 This submenu is available only with modules RPH2 xxA0 RPH2 xxxA1 RPH2 xxxA3 5 2 12 Table Temp CH1 This menu opens a submenu for setting the values for temperature compensation 5 2 12 1 Delta t xx TC Here the 11 values of Delta t T for defining the temperature compensation function can be entered to the RPH2 see also 4 2 2 The permissible range for Delta t is from 10 0 ms to 25 0 ms Page 47 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 5 2 13kU2 Voltage CH2 same as 5 2 9 but for control voltage compensation for channel 2 This submenu is available only with modules RPH2 xxA0 RPH2 xxxA1 RPH2 xxxA3 5 2 14 kP2 Pressure CH2 same as 5 2 10 but for temperature compensation for channel 2 This submenu is available only with modules RPH2 xxxA1 RPH2 xxxA3 5 2 15 Temperature Compensation CH2 same as 5 2 11 but for temperature compensation for channel 2 This submenu is available only w
54. ith modules RPH2 xxA0 RPH2 xxxA1 RPH2 xxxA3 5 2 16 Table Temp CH1 same as 5 2 12 but for temperature compensation for channel 2 5 2 16 1 Delta t xx T same as 5 2 12 1 but for temperature compensation for channel 2 5 3 Analogue Data 5 3 4 Thresholds The following submenus are depending on the configuration of the RPH 2 obtained Exceeding of limit settings cause an alarm if set see chapter 5 4 eA taise Tresholds CT Rated OU dp CT Rated Curr sec ActualContr Voltage PERA AA PT TTT TT TT hielsjatslel7 e AAA A E 5 3 1 1 Current max Type in the allowed maximum value peak value of the current during the switching operation If the current during a switching operation exceeds this limit an alarm is generated The permissible range is from 0 A to 9999 A Page 48 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 ITresholds Current max peak Op Voltage max Op Voltage min Temperature max 500 A E A N T I hielslslelzie TAE E This submenu is only available for module RPH2 xxl 5 3 1 2 Control Voltage max Type in the upper limit for the control voltage If the measured value of the control voltage becomes higher than the limit an alarm is generated The permissible range is from 35 V to 300 V ITresholds gt Current max peak Control Voltage max Control Voltage min Temperature max 242 0 a V III IT llelsi slelrist
55. lated to channel 2 This alarm message is a pulse see chapter 5 4 3 Pulse alarm This alarm message is available only for module RPH2 2xx 5 4 3 13 Command Time CH1 min This alarm message is generated when the command time for channel 1 the function of channel 1 is depending on configuration of the RPH2 and the Function Channel 1 chapter 5 1 6 is to short i e perhaps not all three phase are switched within this time The alarm is generated if the duration of the command impulse is less than 100 ms This alarm message is a pulse see chapter 5 4 3 Pulse alarm 5 4 3 14 Command Time CH2 min This alarm message is generated when the command time for channel 2 opening is to short The alarm is generated if the duration of the command impulse is less than 100 ms This alarm message is a pulse see chapter 5 4 3 Pulse alarm This alarm message is available only for module RPH2 2xx 5 4 3 15 Operating Time min This alarm message is generated when the measured operating time differs more than 2 ms of the calculated operation time measured time is shorter This alarm message is a pulse see chapter 5 4 3 Pulse alarm This alarm message is available only for module RPH2 xxS 5 4 3 16 Operating Time max This alarm message is generated when the measured operating time differs more than 2 ms of the calculated operation time measured time is longer This alarm message is a pulse see chapter 5 4 3 Pulse alarm This alar
56. m message is available only for module RPH2 xxS Page 58 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 5 4 3 17 Drive mech Failure This alarm message is generated when e The monitoring of the CB position is undefined e The operating time corrected by adaptive control has drifted away for more than 5 ms for opening and 10 ms for closing from the pre set operating times only with adaptive control see 4 2 5 This alarm message is a pulse see chapter 5 4 3 Pulse alarm This alarm message is available only for module RPH2 xxS 5 4 3 18 Archive Full This alarm message indicates that the archive is nearly full This alarm message is a pulse see chapter 5 4 3 Pulse alarm Note The archive is capable to store 1000 switching operations When the 900th switching operation is stored in the archive the alarm message is generated Each switching operation following generates an alarm message until the archive is read by the PC Software RPH Tool 5 4 3 19 Archive Failure This alarm message is generated when storing data into the archive fails This alarm message is a pulse see chapter 5 4 3 Pulse alarm 5 4 3 20 Control Voltage min This alarm message indicates that the lower limit of the control voltage is reached see chapter 5 3 1 3 Control Voltage min This alarm message is available only with modules RPH2 xxA0 RPH2 xxA1 RPH2 xxA3 5 4 3 21 Control Voltage max This alarm message
57. measured hydraulic pressure Page 66 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 Measurement Temperature Addition Pressure Pressure E LLELLTETLLLLIaISI E A This submenu is available only with module RPH2 xxxA1 5 6 Auxiliary functions 5 6 1 Alarm Input This submenu is for testing only It shows the inputs auxiliary contacts and position of the neutral earthing switch of the alarm board only available for module RPH2 xxS 5 6 2 Alarm Output This submenu is for testing only You can set the alarm outputs individually by typing a 1 at the according position of the pattern shown on the display only available for module RPH2 xxS 5 6 3 Error Type If an internal fault is detected selftest interval gt O h error flags are displayed in this menu Error type 1 Error type 2 4 Error type 5 7 Error type 8 10 Error type 11 13 Error type 14 16 Error type 17 19 the switching command on input x8 1 or x8 6 is still bending CH1 phase L1 is defective CH1 phase L2 is defective CH1 phase L3 is defective CH2 phase L1 is defective CH2 phase L2 is defective CH2 phase L3 is defective If an error code appears please contact the manufacturer 5 7 Switching archive This submenu shows the result of the last 8 switching operations List of messages e Switching OK e NOT Switched e Command Time min no operation of the breaker command impulse to
58. measured values are shown here The menu structure depends on the RPH2 configuration e g with a device without a current measuring module option I menu points are not available which are connected with his function There are menu cells which can only be read and others where an alteration to the setting can be carried out Changes are only possible after the password has been activated After feeding the auxiliary voltage the first four lines of the master menu 1st plane appear on the display Move the menu cursor black triangle on the left side of the Page 12 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 display up and down using the an keys The first four lines of the 2nd plane are shown after pressing Enter Analogues are also valid for the 3rd plane The menu cursor is moved again using or The contents of the cells are shown in the status line If a value is to be altered move the menu cursor to the desired plane and line After pressing Enter a blinking cursor appears under the first status line position Change this position using or Enter moves the cursor right to the next position With Esc the input mode can be left at any time without storing the changes made After feeding in the last position the message Accept YES NO appears in the status line The input is confirmed with Enter The new value is stored and the menu cursor appears Esc enables t
59. mechanism of a circuit breaker is not provided for please contact Schneider Electric regarding this The position should be well lit in order to make inspections easier Wiring is carried out according to the wiring diagram which is enclosed with every Point on Wave Controller Take care to earth the housing appropriately Technical data Nominal Operative range supply voltage CB trip coil voltage 48 V 250 VDC 35 V 300 VDC special power supply for 48 V 44 ANSI Standard available power consumption Nominal Operative range reference voltage L1 N rated frequency power consumption of measuring inputs maximum permissible current of CB trip coil minimum command time polarity of command impulse resolution of time setting accuracy of switching times over temperature range 55 C to 55 C current inputs rated short time current accuracy of current measurement measurement control voltage input temperature measurement input pressure measurement accuracy of measurement by RPH2 control voltage ambient temperature hydraulic pressure signalling inputs e g CB or neutral ground disconnector position CB aux contacts external reset indication outputs contact rating communication port Schneider Electric Energy Austria AG Leonding 20W 100 43 V 220 43 V AC 15 V 105 VAC 30 V 250 VAC 16 2 3 50 60 Hz 10 96 2 V 14 5 A phase for 1 sec 100 ms posi
60. missible range is from 0 0 ms minimum value is 0 1 ms to 200 ms This submenu is available only for module RPH2 2xxx 5 2 3 Arcing Time CH1 Type in the arcing time for each phase of the CB see chapter 3 2 to 3 4 The permissible range is from 0 0 ms minimum value is 0 1 ms to 50 ms Closing Pre arcing time of the CB The closing of the main contact happens after the chosen switching moment Page 44 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 Opening Arcing time of the CB The opening of the main contact happens before the zero crossing of the current CORA Operatin Operatin 5 2 4 Arcing Time CH2 This submenu is available only for module RPH2 2xxx It works as for channel 1 except that channel 2 always is used for opening 5 2 5 Auxiliary Timeshift CH1 This value is used for compensating the time lag between the main contact and the auxiliary contact of the CB see chapter 4 1 2 1 The permissible range is from 25 5 ms to 25 5 ms Arcing Time CH1 Arcing Time CH2 Aux Timeshift CH1 Aux Timeshift CH2 PS This submenu is available only with module RPH2 xxS For RPH2 with software version JOO6_x a new function for setting is available see 5 5 2 4 5 2 6 Auxiliary Timeshift CH2 This submenu is available only for module RPH2 2xxx It works as for channel 1 except that channel 2 always is used for opening 5 2 7 Adaptive Control This menu opens a submenu for controlling the
61. mperature Addition Op Di OA PETTITT TTY Htlalsi4jslejzla ESESETTIET TEE SIE ESSET EI This submenu is available only with modules RPH2 xxA0 RPH2 xxA1 RPH2 xxA3 5 5 8 Additional Operating Times The following submenus show the calculated additional times according to the service conditions and the configuration of the RPH2 5 5 8 1 Voltage CH1 This submenu shows the compensation value for channel 1 for the actual control voltage per phase Addition Op Times gt Voltage CH1 Voltage CH2 Temperature CH1 Temperature CH2 20 1 0 1 0 2ms H PTET TT TT be lelsia se 7 qe Y APTA PA A 509 This submenu is available only with modules RPH2 xxxA0 RPH2 xxxA1 RPH2 xxxA3 Page 64 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 5 5 8 2 Voltage CH2 This submenu shows the compensation value for channel 2 for the actual control voltage per phase Addition Op Times gt Voltage CH1 Voltage CH2 Temperature CH1 Temperature cne AF ESSERE aE Gd E This submenu is available only with modules RPH2 xxxAO RPH2 xxxA1 RPH2 xxxA3 5 5 8 3 Temperature CH1 This submenu shows the compensation value for the environmental temperature measured for channel 1 per phase ESSERE ST REINES ES Voltage CH1 Voltage CH2 Temperature CH1 Temperature CH2 MEANS EEENEEEENEENHUEBSBRESHSENN ALEA DEI EE E EA This submenu is available only with modules RPH2 xxxA0 RPH2
62. n of 0 1 ms e Large graphic display to show the adjusted and measured values in German English and French or user defined language e Easy setting via keypad or PC interface e Analogue module for measuring control voltage pressure and temperature for the compensation of changes in operating time Page 17 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 3 1 4 e Current measuring function for the graphic display of the line currents during switching e Extensive alarm functions e Two switching functions CLOSING and OPENING with one device are possible e Switching programs with fixed switching times for the most frequent applications e Afree program is available for special user defined applications e g switching unloaded lines e Extensive archive function The most important data for the last 1000 operations are stored in a non volatile memory and are available for diagnostic purposes e Comfortable PC software for setting and read out archive data All data can be stored and printed out If the user cannot find sufficiency with the three languages mentioned previously then the display can be translated into the user s national language using PC software e Compact housing for flush mounting Function of the RPH2 The phase synchronous trigger signal is taken from the network voltage phase L1 The trigger signal is based on the voltage zeros of the reference voltage The network
63. ng 5 4 3 7 Neutral intermediate This alarm message is generated if the position of the Neutral switch is not defined Note This alarm message blocks the RPH2 in any case regardless whether the alarm is set for blocking or not see chapter 5 4 2 5 4 3 8 Neutral grounded This message indicates that the Neutral switch is in position grounded If the position grounded is indicated the RPH2 uses the parameter set Neutral grounded Note This message is not an alarm message but may be helpful for supervising 5 4 3 9 Neutral isolated This message indicates that the Neutral switch is in position isolated If the position isolated is indicated the RPH2 uses the parameter set Neutral isolated see 5 4 3 8 5 4 3 10 Selftest ERROR This alarm message is generated when the automatic selftest discovers an internal error output circuit is not working correct This alarm message is a pulse see chapter 5 4 3 Pulse alarm Note This alarm message blocks the RPH2 in any case regardless whether the alarm is set for blocking or not see chapter 5 4 2 5 4 3 11 Selftest CH1 ERROR This alarm message is the detailed message from 5 4 3 10 related to channel 1 Page 57 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 This alarm message is a pulse see chapter 5 4 3 Pulse alarm 5 4 3 12 Selftest CH2 ERROR This alarm message is the detailed message from 5 4 3 10 re
64. ng core as well as a protection core of the current transformer Page 38 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 5 RPH2 MENUE SYSTEM 5 1 System data RPH2 2SI A3 System Data CB Data Analog Data Alarms ESA PENITUS PTET TT TT hielsjalslel7 e Y ARA A ES Le JL f 5 1 1 Password The factory setting of the password is 0000 To activate the password you must change to the submenu System Data Password The actual status active or off is shown in the bottom left corner of the display Type in the correct password and confirm the assumption by pressing the Enter button see chapter 2 5 The display shows active and the green LED ready starts blinking if the password is correct see chapter 2 4 3 1 The password will be deactivated automatically if no button is pressed for more than 90 seconds ENANA Password System Frequency Control Voltage Rated Pressure 0000 El IIIT T I Mielle ARA PSs ss 5 1 2 System Frequency After activating this function by pressing the Enter button you can choose any item of the list by pressing the or the button see chapter 2 5 Available items 50 Hz 60 Hz 16 2 3 Hz Page 39 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 ENE Password System Frequency Control Voltage Rated Pressure 1150 Hz Oi PTT TT LL I hielslslelzie TUETAN
65. ntrol voltage with a multimeter This value depending on the model is required for parameterization 5 3 4 Check the 48 V field voltage between the terminals X6 8 and X6 11 ground Measure the voltage at the inputs of the external transducers approx 24 VDC Compare the displayed values on the RPH2 for control voltage hydraulic pressure and ambient temperature only models RPH2 xxA with the externally measured ones Verify the connections of the voltage and current transformer circuits current only for model RPH2 xl to the correct terminals 100 V3V or 220 V3V 1A or 5A of the RPH2 The two functions of the menu Aux Functions maybe helpful by testing the external connections The proper connection of the CB s auxiliary contacts to the RPH2 only model RPH2 Sxx can easily be checked by the function Aux Functions Alarm Input When the circuit breaker is in the closed position you must see three 1 at the first positions in the status line AA T I hielslslelzie Y AAA AA SS A When the breaker is in the open position three 0 will be displayed If the remote reset input is activated at the fourth position a 1 must be displayed By using the function Aux Functions Alarm Output you can activate individually each alarm relay by typing a 1 at the according position of the pattern So the external wiring of the alarm circuits can be checked on correct function Page 70 Issue 4 58 020 034 E S
66. operating time e A second point with deviation conditions value 2 measured pole operating time of the same pole with rated control voltage rated temperature and reduced hydraulic pressure Example Value 1 with nominal conditions P Z 265 bar Rated pressure t 110 5 ms Pole operating time with nominal conditions Value 2 P 200 bar Reduced pressure to 127 7 ms Pole operating time with pressure P The compensation parameters kP can be calculated using the following formula Pi V rated hydraulic pressure ti ms CB operating time at nominal conditions Value 2 P V reduced hydraulic pressure t ms CB operating time with P2 _ t2 t 100 Pi 1 ti e kP drive mechanism parameter The input from above results in a compensation parameter kP 47 9 With RPH2 s with two switching functions the calculation for kP1 and kP2 is to be carried out separately for both switching channels and the values stored in the RPH2 Page 36 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 4 2 4 Specifications for the external sensors For measuring pressure and temperature external sensors with integrated transducer are necessary which are not part of the delivery The integrated transducers must meet the following requirements Auxiliary voltage 24 VDC supplied by the RPH2 2 conductor system Output signal 4 mA to 20 mA Such transducers can be obtained from many manufactur
67. r Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 3 4 2 Opening In general breaking of capacitive currents represents no problem for modern circuit breakers If the RPH2 is used for the synchronized switching of capacitor banks then the same applies as in 3 3 2 i e contact separation in sufficient time before voltage zero crossing 3 4 3 Data on circuit breaker required The following data on the circuit breaker are absolutely necessary to operate the RPH2 The mechanical closing and or opening operating time of the three poles see 3 1 2 for definition Accuracy about 0 1 ms In order to achieve the necessary accuracy when closing in the voltage zero crossing the rate of fall of the withstand voltage dUg dt of the breaker should be greater than the rate of change of the gap voltage at voltage zero dU dt Figure 3 shows three possible cases 1 The rate of fall of the breakers withstand voltage dUg dt is less than the rate of fall of the system voltage dU dt dUg dt dU dt k 1 The breaker can be used for this application if dUg dt gt 0 8 dU dt In this case please contact the manufacturer of the breaker for calculation of the pre arcing times 2 The rate of fall of the breakers withstand voltage dUg dt is equal to the rate of fall of the system voltage dU dt dUg dt dU at k 1 3 The rate of fall of the breakers withstand voltage dUg dt is greater than the rate of fall of the system voltag
68. r RPH2 xxA3 5 4 3 27 Press Transducer Fault This alarm message indicates an error of the pressure transducer cable or sensor i e the pressure measurement is not working This alarm message is available only with modules RPH2 xxA1 or RPH2 xxA3 5 5 Measurement 5 5 1 Current Graphs In this submenu you can display the current curves of the last 4 switching operations for each phase L1 L2 L3 as well as the maximum currents peak value Measurement Current Graphs Measured Times Frequency Current RMS NEAR PET TT ELT lelsiWfsielrlst Y MEA AAA AS E Page 60 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 Pressing the Enter button activates the Graph mode Repeatedly pressing the Enter button allows to go through the last 4 switching operations Pressing the or button changes from phase L1 to phase L2 to phase L3 to the peak values of the current of each phase When a graph is displayed the amplification factor of the graph can be changed Pressing the Quitt and button at the same time increases the amplification Quitt and button decreases the amplification This submenu is available only for module RPH2 xxl 5 5 2 Measured Times The measured times of the last switching operation are displayed in this submenu The values available are depending on the configuration of the RPH2 Measurement 0 Current Graphs Measured Times
69. rature the actual measured temperature is shown in the menu Measured value Temperature f Comp the average is shown which is effective for compensation Figure 8 15 ambient temperature C 0 3 3 V BE BS 5 Ss E P4 temperature for compensation 10 15 2 4 6 8 10 12 14 16 18 20 22 24 Time In the menu Measured value Compensation each of the actual additional times are shown After the key operated switch is turned form OFF to OPERATION the RPH 2 carries out an automatic check and all analogue measured values for compensation are set at the actual measured value Page 31 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 4 2 1 Control Voltage Compensation Measuring the control voltage is done internally in the RPH2 and no additional equipment is necessary The RPH2 calculates the additional times for operating time compensation according to a function with an open parameter By fixing these parameters the compensation function can be suited to the character of the power switch Calculation for opening and closing takes place separately The parameter kU1 works for switching channel 1 kU2 for switching channel 2 only for devices with 2 switching functions If a zero value is fed in for a parameter then no additional times are calculated and the compensation function concerned is blocked Fixing the compensation parameters tak
70. s and the auxiliary contacts of the breaker poles must be done very exactly to avoid errors in measuring of the actual operating times e Time deviations of the measured values greater than 10 ms are not considered no operation of the CB or incorrect measurement of operating times e Additional adaptive time is limited to 1 ms from one operation to the next e f the operating time corrected by adaptive control has drifted away from the pre set operating times for more than 5 ms for opening 10 ms for closing the alarm Drive mech Failure is generated The value of the weighting factor depends on the type of drive mechanism We propose a value of 0 25 to 0 30 for all types of mechanism Page 37 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 4 3 Current Module Option A current measuring module is available to make the switching of large transformers and reactors easy when putting the RPH2 Point on Wave Controller into operation With this the inrush current can be recorded and graphically displayed during the switching process Data for the last 4 switching operations are stored in a non volatile memory and can be analysed on the display Primary values are shown after feeding in the current transformer current ratio For every phase there is an input for each 1 A and 5 A available Because the current inputs have a short time withstand of 100 xIn current measurement can be carried out over a measuri
71. s are available only with modules RPH2 xxA0 RPH2 xxA1 RPH2 xxA3 In this submenu the temperature transducer is calibrated LA Eke ey CT Rated Curr sec ActualContr Voltage Temperature gt Pressure URRACA AA PTET TT TT i lelsia sie 7 e Y AE StS PA E 5 3 5 1 Value at 4 mA Type in the rated value of the temperature transducer at an output current of 4 mA This information is part of the documentation of the temperature transducer Page 52 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 Temperature Value at 4 mA Value at 20 mA 40 0 C EA OO A TY I hielslslelzie Y AAA A 5 3 5 2 Value at 20 mA Type in the rated value of the temperature transducer at an output current of 20 mA This information is part of the documentation of the temperature transducer Temperature Value at 4 mA Value at 20 mA UMSO SCHEDE SONS PT LETT LL I hielslslelzie Y MPA AA AREA E 5 3 6 Pressure These submenus are available only with modules RPH2 xxA1 RPH2 xxA3 In the following submenus the pressure transducer can be calibrated NAAA CT Rated Curr sec ActualContr Voltage Temperature Pressure Sa O EBERENEEEENEENHUBSRHSSHUONENEN MAA RETE O ES 5 3 6 1 Value at 4 mA Type in the rated value of the pressure transducer at an output current of 4 mA This information is part of the documentation of the pressure transducer MEE E Value at 4 mA
72. s left up to chance If closing is carried out in this manner high inrush currents with high DC components are unavoidable When energizing capacitors additional high switching surges can occur The results are unwanted operation of protection devices and repercussions on machines and network The inrush currents and switching surges can be reduced to an acceptable rate by installing closing resistors at the circuit breaker The costs for such closing resistors are very high due to the mechanical expenditure Besides the necessarily high energetic absorbtivity of the resistor material sets relatively restricted limits of practicability By selecting a suitable switching time the physical causes of these high inrush currents can be counteracted This possibility is effected through synchronized switching with the RPH2 This enables the three poles of a circuit breaker to be controlled independently Page 16 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 3 1 1 2 Opening The de energizing of shunt reactors is a critical process liable to generate re ignitions between circuit breaker contacts This means very high stress for the insulation of both the shunt reactor and the circuit breaker If the contact separation takes place a sufficient amount of time before the current zero crossing through suitable circuit breaker control to ensure a gap capable of withstanding the transient recovery voltage at interruption
73. short lt 100 ms Page 67 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 In the statusline the date and the time of the operation is displayed Ahead of the messages a reference to the archive entries is shown n last operation n 1 operation before etc Page 68 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 6 1 COMMISSIONING Commissioning preliminaries Before initial operation of a RPH2 Point on Wave Controller time should be taken in order to become familiar with operation of the device and if a portable PC is available with the parameterization software also NOTE After the RPH2 is connected to the supply voltage the first time or after a self test it will last about 20 seconds until the green LED is illuminated and the relay is ready for operation see also 2 4 2 2 If the green LED stays dark please check at first the proper connection of the reference voltage and the neutral earthing switch 6 1 1 Settings 6 1 1 1 Factory Settings Depending on the model all values for CB Data compensation and all thresholds for the alarms are set to 0 except System Frequency 50 Hz Control Voltage 125 V Switching Program Transformer Function Cannel 1 CB closing Selftest Interval 24h CT Rated Current primary 1A secondary 1A Alarms Ref Voltage Failure gt Alarm1 Neutral intermediate gt Alarm2 All other alarm functions are inactiv
74. tive negative on request 0 1 ms 0 3 ms 1Aand5A 100 xIn 1s 10 0 5 In 4 In internal 4 20 mA of Pt 100 4 20 mA of pressure sensor 13 13 13 potential free contacts required potential free contacts 24 250 V AC DC 25 max 70 VA max 3A RS 232 DC decoupled Page 7 Issue 4 58 020 034 E 2011 02 2 1 2 2 2 3 INTRODUCTION Using the handbook This handbook will guide the user through the setting up procedure for the Point on Wave Controller It explains the additional functions of this appliance and how they are selected and used In addition some examples of its usage are given the theory behind it examined and explained and which circuit breaker and main data are absolutely necessary for operation The handbook shows the complete list of all menu points with cross references to the chapter with the accompanying descriptions The menu point order for the individual modules is shown on this list as well Notes on checking and commissioning are given in the last chapter Models available Assembly The RPH2 is available in 2 basic models e RPH2 1xx for one switching function closing or opening alternatively e RPH2 2xx for 2 switching functions channel 1 for closing channel 2 for opening only when using the given switching programs The 7 alarm LED s are active however there is only one alarm contact Alarm 1 available In addition there is an alarm contact Device not re
75. tral grounded for all poles peak value neutral isolated for the two first poles L2 and L3 peak value neutral isolated for the last pole L1 rate of fall of system voltage neutral grounded rate of fall of system voltage neutral isolated for the two first poles L2 and L3 rate of fall of system voltage neutral isolated for the last pole L1 rate of fall of CB withstand voltage neutral grounded for L1 L2 L3 neutral isolated for L2 L3 neutral isolated for L1 variation of CB closing time neutral grounded prearcing time set to RPH2 for all poles neutral isolated prearcing time set to RPH2 for poles L2 and L3 neutral isolated prearcing time set to RPH2 for pole L1 Necessary Switching Time Accuracy Capacitor energizing places the greatest demands on the breaker in reference to operating time constancy Every variation from the required switching time leads to a higher withstand voltage value which causes greater surges and inrush currents Closing time variation should amount to 1 ms at the most When this accuracy cannot be maintained under all conditions we recommend the use of the analogue module option A to correct the operating time influences For opening the switch should reach a operating time accuracy of 1 5 ms Page 27 Issue 4 58 020 034 E 2011 02 Schneider Electric Energy Austria AG Leonding 3 5 Switching closing of uncharged Lines Uncharged high voltage lines are to be fund
76. ture CH1 65 5 5 8 4 Temperature CH2 65 5 5 85 Pressure CH1 65 5 5 8 6 Pressure CH2 66 5 5 9 Pressure L1 L2 L3 66 5 5 10 Pressure L1 66 5 6 Auxiliary functions 67 5 6 1 Alarm Input 67 5 6 2 Alarm Output 67 5 6 3 Error Type 67 Page 4 Issue 4 58 020 034 E Schneider Electric Energy Austria AG Leonding 2011 02 5 7 Switching archive 67 6 COMMISSIONING 69 6 1 Commissioning preliminaries 69 6 1 1 Settings 69 6 1 1 1 Factory Settings 69 6 1 1 2 Necessary Settings 69 6 1 2 Inspection 70 6 1 3 First operation 71 Page 5 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 1 1 1 2 1 3 1 4 IN GENERAL Handling of electronic equipment A person can cause an electronic potential of many thousands of volts When this potential is discharged into appliances with semiconductor components serious damage can occur which is not immediately evident but can still impair operational reliability The electronic switching circuit of the RPH2 Point on Wave Controller from Schneider Electric Energy Austria AG Leonding meets all the requirements concerning electromagnetic compatibility in accordance with the EN 50 081 1 1992 and EN 50 082 2 1995 Care is necessary only if the plug in unit is pulled out of the casing Take care not to touch the plug contact on the back For storing and transporting loose plug in units we recommend a conductive fail packaging As soon as the plug in unit is properly inst
77. ustria AG Leonding Issue 4 58 020 034 E 2011 02 Status Function Blinking An alarm has occurred which is marked as Reset obligatory After pressing the Quitt button two possibilities arise 1 The LED extinguishes i e the alarm was no longer active when reseted the output relay is released 2 The indicator switches over to permanent light i e the alarm is still active the output relay remains energized As long as the LED is alight or blinks the affiliated output relay is energized 2 4 4 Keys Enter Menu point open confirm Cursor up increase value Cursor down decrease value Esc Leave menu point break off action Quitt Acknowledge alarm alter current scale together with or 2 4 5 Serial interface 2 5 To connect the RPH2 to a computer via a standard interface cable Pinning of connection cable Nullmodem Cable PC Serial Por RPH2 Serial Port PC Serial Port RPH Serial Port 1 e 1 3 a 3 3 a ap 3 4 am 4 4 e am 4 5 am 5 5 a ame 5 6 6 6 a ye 6 7 em 7 7 em 7 8 e e 8 zou 8 9 am 9 25 a e 9 9 pin plug 9 pin plug 25 pin plug 9 pin plug Menu system The user surface is organized in several master menu points each with linked sub menu points For their part the sub menus can contain further sub menus The last line under the drawn line is the status line Adjusted or
78. xxxA1 RPH2 xxxA3 5 5 8 4 Temperature CH2 This submenu shows the compensation value for the environmental temperature measured for channel 2 per phase Addition Op Times gt Voltage CH2 Temperature CH1 Temperature CH2 Pressure CH1 1 0 2ms MEANS PTET TT Ll ielslesloftsl Y A SS ESTEE T ESI A This submenu is available only with modules RPH2 xxxAO RPH2 xxxA1 RPH2 xxxA3 5 5 8 5 Pressure CH1 This submenu shows the compensation value for the actual hydraulic pressure measured for channel 1 per phase Page 65 Issue 4 58 020 034 E 2011 02 Schneider Electric Energy Austria AG Leonding SES mies AS Temperature CH1 Temperature CH2 Pressure CH1 Pressure CH2 MEET A ES T1111 hHlell4slel7 s Y AREA Sle ESTERI EST This submenu is available only with modules RPH2 xxxA1 RPH2 xxxA3 5 5 8 6 Pressure CH2 This submenu shows the compensation value for the actual hydraulic pressure measured for channel 2 per phase MAA Temperature CH1 Temperature CH2 Pressure CH1 Pressure CH2 O 0I 0 See ee EEENENEEENEENHUEBSBRESHSENN AAA PA This submenu is available only with modules RPH2 xxxA1 RPH2 xxxA3 5 5 9 Pressure L1 L2 L3 This submenu shows the actual measured hydraulic pressure per phase L1 L2 L3 Measurement Temperature Addition Pressure Pressure 310 This submenu is available only with module RPH2 xxxA3 5 5 10 Pressure L1 This submenu shows the actual
79. y extend the lines to the extremes dotted line in the example Evaluate the values of Delta t T at the control points 50 C to 50 C so to get the 11 values for Delta t T shown in the table in figure 11 By using the PC software RPH2 Tool also an exponential function with one open parameter can be calculated Especially for circuit breakers with spring drive mechanism this option will be useful Page 33 Schneider Electric Energy Austria AG Leonding Issue 4 58 020 034 E 2011 02 Figure 10 Delta t ms Page 34 Issue 4 58 020 034 E 2011 02 10 0 10 20 30 40 50 Ambint Temperature C Schneider Electric Energy Austria AG Leonding Figure 11 Delta t ms mo La Temperature 50 C 13 0 ms 40 C 9 0 ms 30 C 5 0 ms 20 C 2 5 ms 10 C 1 6 ms n ro xr ec 0 0 8 ms 10 C 0 4 ms 20 C 0 0 ms 30 C 0 2 ms 40 C 0 4 ms 50 C 1 0 ms ES posqp uq up E em pepa sa Fr cae Emp ae pee a ah b0 AC M 0 90 10 th TE 21 a ath nt Ambient Temperature PC With RPH2 s with two switching functions the evaluation of Delta_t T has to be carried out separately for both switching channels and the values stored in the RPH2 4 2 3 Hydraulic Pressure Compensation There are two module models available for measuring pressure e Option A1 for breakers with a mutual hydraulic system for all three poles e Option A3 for breakers with separate hydraulic systems for each pol
Download Pdf Manuals
Related Search
Related Contents
GeoVision GV-Data Capture Troubleshooting Interactive document summarization 取扱説明書 (1.72 MB/PDF) Ford 2008 Explorer Sport Trac Automobile User Manual Centaur Horse Walkers, Inc. Adaptec RAID Controller Command Line Utility User's Guide Copyright © All rights reserved.
Failed to retrieve file